4/1.1/B/2 Shutter Fire Damper Type FSD • FSP • FSE

Shutter Fire Damper Type FSD FSP FSE

Embed Size (px)

DESCRIPTION

shutter fire damper

Citation preview

Page 1: Shutter Fire Damper Type FSD FSP FSE

4/1.1/B/2

Shutter Fire DamperType FSD • FSP • FSE

Page 2: Shutter Fire Damper Type FSD FSP FSE

Contents • Description

Description .................................................................... 2 Product Range Accessories .......................................... 7Construction Dimensions Materials .............................. 3 Technical Data .............................................................. 9Installation Details ......................................................... 5 Order Details ................................................................ 10

Fire dampers provide an automatic means of localising areas offire in ventilation systems.

The FSD range of curtain bladed fire dampers are suitable forinstallation in walls and ceilings made from concrete orbrickwork, and will stop the spread of fire through duct, walls orfloors.

There is a wide choice of sizes available suitable for low,medium and high velocity applications and include rectangular,square, circular and flat oval connections.

The dampers are fitted with standard release 72°C fusible linksunless otherwise specified.

Note: The installer should note that all fire damper installationsplus required access panels have to be to thesatisfaction of the District Surveyor or the appropriateFire Protection Authority.

2

Page 3: Shutter Fire Damper Type FSD FSP FSE

Construction • Dimensions • Materials

Type FSDType FSD shutter fire dampers are constructed with a 1.2mmcase and 0.8mm blades in galvanised mild steel to BS EN 101421991 FE PO 2GZ275 NA or equivalent.

Various construction options are available, these are given in thetable on page 7, standard supply unless otherwise stated is theFSD-A with a fusible link which has a fusing temperature of 72°C.

When fitted the twin catchplates are of galvanised mild steel(specification as case and blades).

When fitted the side seals are convex in shape to close the gapsbetween blades and case. The material is spring stainless steelgrade 302.

The closing springs (constant force) are also stainless steel.

The bottom blade of FSD...P...E - A...B...D...E are fitted with aring pull device to allow blades to be reset.

Type FSPThe construction is similar to type FSD, except that the blades aremanufactured from stainless steel grade 430.

Type FSEOf similar construction to type FSP, except that the case andcatchplates are manufactured from stainless steel grade 304L.

Type FSD...P...EConstruction Variants: A, B and C have blade packs partially inthe airstream

Rectangular / Square ConnectionType FSD...P...E – A...C Type FSD...P...E – A

Type FSD...P...E – B Type FSD...P...E – C

2

6

5

6

5

2

6

5

1

Note:All types shown canhave prefix FSD,FSP,FSE

'Y'is dimension of bladeprotrusion into airstream

Duct size Dim

B or H Y

150 10

200 10

250 10

300 20

350 20

400 30

450 30

500 30

550 30

600 40

650 40

700 50

750 50

800 60

850 60

900 60

950 70

1000 70

x

B – 3mm= (o/a spigot)

Overall WidthB + 45mm

H –

3m

m=

(o/

a sp

igot

)

Ove

rall

Hei

ght

H +

45m

m

5 6 4

Y

38 80 38

13

Y

Galvanised or stainless Galvanised or Fusible linksteel catchplates stainless steel frame

Closing springs Galvanised orstainless steel blade

Side seals assembly

1

2

3

4 6

5

3

Page 4: Shutter Fire Damper Type FSD FSP FSE

Construction • Dimensions • Materials

Type FSD...P...EConstruction variants: DR, DC, DO and ER, EC, EOhave blade packs out of airstream

Rectangular / Square ConnectionType FSD...P...E – DR and ER

B – 3mm= (o/a spigot)

Overall widthB + 45mm

H –

3m

m=

(o/

a sp

igot

)Type FSD...P...E – DR Type FSD...P...E – ER

5 6

38 80 38

5

2 6

3

2

1

5

1

X

Circular Duct ConnectionType FSD...P...E – DC and EC Type FSD...P...E – DC Type FSD...P...E – ECNote: When ordering circular duct dampers see note on page 10

Overall widthD + 76mm

D –

3m

m=

(o/

a sp

igot

)

5 6

24

X40

4

65

21

65

13

235

80

50

2

Circular Duct ConnectionType FSD...P...E – DC and EC Type FSD...P...E – DO Type FSD...P...E – EONote: When ordering circular duct dampers see note on page 10

5 64

65

21

65

13

235

80

50

2

D –

3m

m=

(o/

a sp

igot

)X

40

Overall widthD+76mm

B – 3mm= (o/a spigot)

100150200 49250300

350400450500550 74600650700

750800850900

99

9501000

Duct size DimB X H XB X D

D

Galvanised or stainless Galvanised or Fusible linksteel catchplates stainless steel frame

Closing springs Galvanised orstainless steel blade

Side seals assembly

1

2

3

4 6

5

Note:All types shown canhave prefixFSD, FSP, FSE

‘X’ is dimension ofvariable top casesection

4

Page 5: Shutter Fire Damper Type FSD FSP FSE

InstalIation Details

B + 105mm

H-3

(o/a

spi

got)

Rectangular / Square Connection Rectangular / Square ConnectionType FSD...E...P – A...– C TYPE FSD...E...P – DR and ER

HEVAC Installation Frame Type H

H +

105

mm

B-3(o/a spigot)

B + 105mm

H +

130

mm

whe

n X

= 4

9mm

H +

155

mm

whe

n X

= 7

4mm

H +

180

mm

whe

n X

= 9

9mm

Oval / Circular ConnectionType FSD...E...P- DC, DO and EC, EO

D +

146

mm

whe

n X

= 4

9mm

D +

171

mm

whe

n X

= 7

4mm

D +

196

mm

whe

n X

= 9

9mm

B + 136mm

Note: Two dampers can be supplied assembled in a single HEVAC frame up tosize B x H 1524 x 1000mm. Receipt of an order for this configuration will be takenby Trox as the client having obtained this approval from the appropriate authority.

1

2

3

4

6

57

HEVAC Installation Frame Type H

The HEVAC Installation Frame Type H is built to specificationHVC 615183. Various fire damper designs can be used with thisinstallation frame, see below.

The installation frame is factory assembled with its respectivefire shutter damper and delivered to site as one unit. This unitshould be installed centrally within the thickness of thesurrounding wall or floor such that the centre line of the frame isa minimum distance of 50mm from the nearest face of the wallor floor.

On installation all fixing tabs except those which are completelyinaccessible shall be bent into the mortar joints between thebrickwork or blockwork surrounding wall or floor. Then withcement mortar fill all joints solidly.

In reinforced concrete the tabs should be bent out and tiedwith wire to the reinforced bars. The gap between the frameshould then be backfilled with concrete or mortar both sides ofthe frame.

Where more than one duct penetrates a fire wall or floor,adjacent fire dampers and frame assemblies must be separatedby builder's work of a minimum thickness of 225mm.All FSD, FSP and FSE types can be fitted in the HEVACinstallation frame.Note in all cases HEVAC frame is manufactured fromgalvanised mild steel.

10mm clearance between frame and fire damper to allow for

expansion.

Galvanised steel spacer to permit expansion.

Galvanised steel building ties.

Aluminium rivets fix the corner angles to the frame

Galvanised steel frame the corners left open.

Steel corner angles retain frame open corner.

15mm clearance between mitre corner.

1

2

3

4

5

6

7

5

Page 6: Shutter Fire Damper Type FSD FSP FSE

InstalIation Details

Type FSD...P...E – A...– E

Installation

Multiple SectionsType FSD...P...E – A...– E Type FSD...P...E – A...– E(not Type FSD...P...E – C)

Multiple Assembly Multiple AssemblyHorizontal Damper Vertical Damper

Sleeve

Fixing Angles(optional)

Cover Angles

1

2

3

2

31

1

Installation RequirementsThe installer should note that the installationand location of access panels is to be to thesatisfaction of the District Surveyor or BuildingInspector or the appropriate Fire ProtectionAuthority.

When duct size B or H is greater than1000mm, multiple dampers sections will berequired. With all multi section installationsthe proposed arrangements must be to thesatisfaction of the appropriate local authorityand/or fire officer responsible for theinstallation. Receipt of an order requestingmultiple sections will be taken by Trox as theclient having obtained this approval from theappropriate authority.

Expansion GapAllowance for expansion between sleeveand builder's work in both horizontal andvertical planes.

B x H Total ClearanceClearance per side

0-500 6mm 3mm

500-1000 13mm 6mm

1

Type U Channel FrameSupplied in lengthsfor site assembly.

1

Installation with Sleeve and Peripheral Angles:

As an alternative for use where the HEVAC frame is notdesired, cannot be fitted, or for multi section arrangements,peripheral sleeves and angle frames can be constructed inaccordance with the following:The damper should be installed centrally within the surroundingwall or floor thickness such that the centre line of the frame is aminimum distance of 50mm from the nearest face of the wallor floor.The damper should be installed in a rectangular galvanisedsteel sleeve with a minimum thickness of 1.2mm.The fixing of the damper can be by tack welding the case onboth sides directly to the sleeve, or by the use of 20 x 20 x1.2mm steel angles which should be tack welded to the sleeve.In both cases welds to be at a maximum of 225mm pitch.The sleeve should be of a suitable length to extend through thewall or floor opening to enable the fitting of the cover angles andductwork. The cover angles should be attached to the sleeve by

6mm diameter bolts at a maximum of 225mm centres, andshould form a complete frame around the sleeve and cover overthe expansion gap (see table) required between sleeve and wallor floor opening. The expansion gap should be filled withcompressible, non combustible material (mineral wool). Thecover angles should be of such a size as always to form a coverover the wall or floor opening by 25mm minimum, and shouldbe manufactured from a minimum size of 38 x 38 x 3mm steelangle.All fixings must be positioned clear of the damper blade path soas not to impede proper closure.Warning Dampers supplied without installation frames asshown on page 5 or not being fitted into installation sleeves,must not be installed within a solid masonary structure as theouter case has no facility to cater for expansion during fireconditions.Note: Supply and fixing of sleeve and peripheral angles byothers.

6

Page 7: Shutter Fire Damper Type FSD FSP FSE

Product Range • Accessories

Construction Descri tion Mounting Mode Velocity RangeVariant

Blades partially in airstream, square or rectangular spigot, Vertical/horizontal mounting LowA fitted with closing springs and catchplates. Medium

B As code A but includes side seals. Vertical/horizontal mounting LowMedium

C As code A but excludes closing springs Vertical mounting only Lowand catchplates. Medium

Variable height top case section to contain blades out ofDR airstream. Fitted with closing springs and catchplates. Vertical/horizontal mounting HighDC Can be supplied with square or rectangular, circular orDO oval duct connections.

EREC As code D series but includes side seals. Vertical/horizontal mounting HighEO

– Fusible link release (basic unit) – ETL Release:

Automatic closure of the fire damper at an air A dual response fusible link release providingtemperature of t > 72°C, in the area of the fusible link; automatic closure of the fire damper;for smouldering fires where t < 72°C, the system does a) at an air temperature t > 74°C in the area of thenot release. Iink.

– Magnetic release: b) When subject to a short duration low power(AC or DC solenoid or DC electro magnet) electrical impluse which triggers a chemical heatingThermal closure of fire damper at t > 72°C, or of the centre element causing the link to release inelectrically when the current is interrupted (power off to approximately 7 seconds. This signal could beclose) DC electro magnet, or pulsed (power on to provided for example by a smoke detector, e.g.close) AC or DC solenoid. Signal from central control Trox Type RM-O or RM-1/2.or via a smoke detector built into ventilation systeme.g. Trox Smoke Detector Type RM-O or RM-1/2.

Description Code Description Code Description Code

– Z01 Z02

Fitted to all FSD...P...E variants. Electrical limit switch assembly Mechanical device to indicateExcept type FSD...P...E – C to indicate blade closure. blade closure visable externallyRing pull permits the release of from the damper.the blades from the catchplateswhen access is from the oppositeside to the catchplates.

Code Description

HEVAC model sub-frame sub-frame supplied assembled to theH Additional HEVAC sub-frame for wall mounting. fire damper.

U U channel joining sub-frame for multiple assemblies. Supplied loose for site assembly by others.

Construction Variants

Functional Description

Accessories

Sub-frames

7

Page 8: Shutter Fire Damper Type FSD FSP FSE

Accessories

Construction or construction variant Combined with Code

8

Double changeover contactCircuit breaking capacity max 380V ~, 50Hz, 10A, min 24V–, 100mAContact resistance 60mΩ. Protective system IP 66

Double changeover contactCircuit breaking capacity max 380V ~, 5OHz, 10A, min 24V–, 100mAContact resistance 60mΩ. Protective system IP 66

Double changeover contactCircuit breaking capacity max 380V ~, 50Hz, 10A, min 24V–, 100mAContact resistance 60mΩ. Protective system IP 66

Double changeover contactCircuit breaking capacity max 380V ~, 50Hz, 10A, min 24V–, 100mAContact resistance 60mΩ. Protective system IP 66

Double changeover contactCircuit breaking capacity max 380V ~, 50Hz, 10A, min 24V –, 100mAContact resistance 60mΩ. Protective system IP 66

Double changeover contactCircuit breaking capacity max 380V ~, 50Hz, 10A, min 24V–, 100mAContact resistance 60mΩ. Protective system IP 66

Limit switch indicates blades ‘CLOSED’ Z01Visual indicator indicates blades ‘CLOSED’ Z02Limit switch with visual indicators indicates blades ‘CLOSED’ Z03

Z04

Limit switch indicates blades ‘CLOSED’ Z05Visual indicator indicates blades ‘CLOSED’ Z06Limit switch with visual indicator indicates blades ‘CLOSED’ Z07

Z08

Limit switch indicates blades ‘CLOSED’ zogVisual indicator indicates blades ‘CLOSED’ Z10Limit switch with visual indicator indicates blades ‘CLOSED’ Z11

Z12

Limit switch indicates blades ‘CLOSED’ Z13Visual indicator indicates blades ‘CLOSED’ Z14Limit switch with visual indicator indicates blades ‘CLOSED’ Z15

Z16

Limit switch indicates blades ‘CLOSED’ Z17Visual indicator indicates blades ‘CLOSED’ Z18Limit switch with visual indicator indicates blades ‘CLOSED’ Z19

Z20

Limit switch indicates blades ‘CLOSED’ Z21Visual indicator indicates blades ‘CLOSED’ Z22Limit switch with visual indicator indicates blades ‘CLOSED’ Z23

Base holder with ETL fuse link whichis a dual response device with fusiblelink which reacts (melts) whensubjected to either local heat or anelectrical impluse of low power andshort duration. The standardtemperature rating is 74ºC. It can bereleased with an electrical impluse(between 6 volt and 30 volt AC or DCminimum current of 0.2 amperes).

Universal release holder with fuselink. Each side of release device hasa spring loaded lever allowing thedamper to be easily tested for closureand re-loaded with one hand fromeither side. Standard fusingtemperature 72°C.

Universal link fitted with an ACelectric solenoid 230/240V AC.Provides remote operation from anAC electrical signal. Power ON closesthe damper. It incorporates a fusiblelink within the universal release toalso provide normal closure in theevent of increasing temperatureAC Solenoid U = 230/240V 50HzPΩ 55VA inrush 20VA closed100% rated.

Universal link fitted with a DC electricsolenoid 24V DC. Provides remoteoperation from a DC electrical signal.Power ON closes the damper. Itincorporates a fusible link within theuniversal release to also providenormal closure in the event ofincreasing temperature.DC Solenoid 24V DC 1 2W100% rated

Universal link fitted with an electromagnet 24V DC. Provides remoteoperation from an DC electricalsignal. Power OFF closes thedamper.lt incorporates a fusible linkwithin the universal release to alsoprovide normal closure in the event ofincreasing temperature.DC Electro Magnet 24V DC 4W100% rated.

Base holder with fuse link (standardconstruction)

Page 9: Shutter Fire Damper Type FSD FSP FSE

Technical Data

Fire Test BS 476 Part 201987

The fire dampers shown have been tested by an independentauthority (Warrington Research Centre) according to BritishStandards 476 Part 20; 1987 for a period of 4 hours.

The time / temperature curve required by this test procedure isshown below, after 4 hours test the FSD retained its integritywith no significant openings being formed.

Pressure losses are shown below for units with blades eitherpartially in or out of the airstream.

Type FSD...P...E – A..– C Fire Test BS 476 Part 20: 1987Blades partially in airstreann

10080

605040

30

20

10

8654

3

2

1

Sta

tic p

ress

ure

drop

Pas

cals

(P

a)

Duct velocity m/s

1 1.5 2 3 4 5 6 8 10 12.5

Type FSD...P...E – D and EBlades out of airstream

Sta

tic p

ress

ure

drop

Pas

cals

(P

a)

150

100

80

60

50

40

30

25

20

15

106 8 10 15 20 30

Duct velocity m/s

Tem

pera

ture

ris

e (T

-To)

ºC

Time (T) min

0 30 60 90 120 150 180 210 240

1200

1100

1000

900

800

700

600

500

400

300

200

100

9

Page 10: Shutter Fire Damper Type FSD FSP FSE

Order Details

10

Specification Text

Square or rectangular shutter type fire dampers for the isolationof fire zones in air conditioning systems. Designed to maintainintegrity and stability for 4 hours when tested to BS 476 Part 20;1987. Tests carried out at Warrington Research Centre,England. The FSD fire dampers consist of perimeter frame caseand interlocking shutter type blades. As standard the case iscomplete with catchplates and constant tension closure springs.Suitable for either rectangular, circular or flat oval ducting andavailable in high or low pressure/velocity construction. Standardrelease 72°C fusible link.

Materials:

Case, blades and catchplates galvanised mild steel to BS EN101421991 FE PO 2GZ275 NA. Constant force stainless steelclosing springs. Brass soldered fusible link.

Options:

Universal release mechanism with fusible link or fusible link inconjunction with solenoid or electro magnet release.Fusible links available at other fusing temperatures.

Stainless steel blades, or all stainless steel construction(blades grade 430 case grade 304L).For reduced leakage addition of stainless steel side seals(grade 302).

For vertical installation only (horizontal duct work) damperwithout closure springs, catchplates or side seals.

This code must be used when These codes do not need to beH Dim exceeds 1000mm completed for standard products

Type

FSD Standard Supply

FSP

FSE(See page 3)

Duct SizeDimensions square orrectangular ‘B’ x ‘H’mm,circular ‘D’mm dia.Flat oval ‘B’ x ‘D’mm.All damper with spigotsare manufactured downon duct size to fitinside duct workconnections.

Accessories(See page 7 & 8)

Other Options0 = Standard supply.H = Hevac sub frame.U = U joiningframe.

MountingMounting V = Vertical damperMounting H = Horizontal damper

Construction Variants(See page 7)

A tb C blades partiaiiyin airstream

DR Rectangular SpigotDC Circular SpigotDO Oval SpigotER Rectangular SpigotEC Circular SpigotEO Oval Spigot

blades out of alrstream

1* Note: FSD - A is standard supply unless:otherwise specified.

1* ABC

Order Code

FSD – A – V 1000 x 500 0 Z01

Order Example

Make : TROXType : FSD – A / 1000 x 500 / 0 / Z01.Qty : 4