608 State St. South Kirkland, WA 98033 www.faira.com [email protected] +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, WA 98223 March 9, 2016 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property. You may view more detailed information for this home and can make an offer at http://www.faira.com/listings/10464 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

608 State St. South Kirkland, WA 98033

www.faira.com

[email protected] +1.800.571.FAIR

FAIRA TRANSPARENCY REPORTS

231 McRae Rd NE, Arlington, WA 98223

March 9, 2016

Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.

You may v iew more detai led information for th is home and can make an offer at

http://www.faira.com/l ist ings/10464 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Page 2: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

Precise Home Inspection Services, LLC

Residential Home

INSPECTION REPORT

For

Prepared By

Precise Home Inspection Services, LLC

FAIRA.COM & Rick Cheesman 231

McRae Rd NE, Arlington, WA 98223

Page 3: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

2

Date: 2/29/16 Precise Home Inspection Service

Name: FAIRA.COM & Rick Cheesman

Address: 231 McRae Rd NE, Arlington, WA 98223

Dear: Home Buyer,

At your request, an inspection was performed at: 231 McRae Rd NE, Arlington, WA 98223. Precise Home

Inspection Services is pleased to submit the enclosed report. This report is a professional opinion based on a visual

inspection of the accessible components of the home, including: foundation, structure, roof, electric, plumbing,

HVAC systems. As with all Precise Home Inspections, yours was performed by a certified inspector under the strict

guidelines of ISHI and ASHI. Refer to attached ASHI Standards of Practice, or visit the ASHI web site www.ashi.org

for more info.

Before you review the report, please understand that there are limitations to such an inspection. The report does not

reflect the results of an exhaustive technical evaluation, but rather a visual inspection. The distinction between the

two is important. A technical evaluation requires exhaustive testing and analysis of a house’s parts, taking more time

and costing significantly more money. Our inspection does not consider components in the home that are not visible.

Also understand that, even with and exhaustive inspection, there still may be defects in the home that are not revealed

during the inspection. A visual inspection provides you with a solid, overall picture of the home, its problems,

positive attributes, and areas where we recommended immediate attention. But with anything as complex as a home

(a home has roughly 500 separate components), unexpected repairs are the norm, not the exception.

Please carefully review your copy of the Pre-Inspection Agreement. It explains in detail the scope of the inspection

and the limit of our liability in performing this inspection. The Inspector Standards of the International Society of

Home Inspectors prohibits us from making any repairs of referring contractors. Precise Home Inspection serves as an

independent third-party in home-purchasing transactions and is not directly associated with any of the parties in this

transaction.

The information provided in this report is solely for your uses. Precise Home Inspections will not release a copy of

this report without your written consent.

Thank you for selecting Precise Home Inspection. The growth of our business depends on customers like you telling

your friends and family about your positive experience with us. Take your time reviewing all comments in the report

and keep it with your permanent records. It will be a valuable source of information in the future. Of course, if you

have any question about the report or the property in question, don’t hesitate to call at (206) 683-3775.

Sincerely,

Tim M Peterson

Precise Home Inspection Service 24024 150th ST.SE Monroe, WA, 980272 Phone: (206) 683-3775 Email: [email protected]

Page 4: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

3

PRECISE HOME INSPECTION SERVICE, LLC

This Inspection Report is for the exclusive use of: FAIRA.COM & Rick Cheesman

On February 29, 2016, Precise Home Inspection Service, LLC made a visual inspection of the accessible

portions of the property located at: 231 McRae Rd NE, Arlington, WA 98223.

Table of Contents

Inspection Agreement

Summary of Inspection Report

Inspection Report:

Inspection Report:

Structural Section 1

Exterior Section 2

Grounds Section 3

Basement (or Lower Level) Section 4

Roofing Section 5

Attic Section 6

Heating and Cooling Section 7

Plumbing Section 9

Electrical Section 8

Page 5: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

4

PRECISE HOME INSPECTION SERVICE, LLC

24024 150TH STREET SE, MONROE, WA. 98272, PHONE (206) 683-3775

www.precisehomeinspection.com

Name: FAIRA.COM & Rick Cheesman

Address:

City: State: Zip:

Phone # MLS#

Property Location

231 McRae Rd NE, Arlington, WA 98223

This is our report of a visual inspection of the readily accessible areas of this building, in accordance with the terms and conditions contained in the

PRE-INSPECTION AGREEMENT, which is a part of this Report and incorporated herein. Please read the REMARKS printed on each page and call

us for an explanation of any aspect of this Report, written or printed, which you do not understand.

Date of Inspection 02/22/16 Time 10:30AM Weather Conditions SUNNY Outside Temperature 52o

PRE-INSPECTION AGREEMENT (PLEASE READ CAREFULLY)

Precise Home Inspection Service, LLC agrees to conduct an inspection for the purpose of informing the CUSTOMER of major deficiencies in the

condition of the property. The inspection and report are performed and prepared for the sole, confidential and exclusive use and possession of the

CUSTOMER. The written report will include the following only:

structural condition and basement

electrical, plumbing, hot water heater, heating and air

conditioning

general interior, including ceilings, walls, floors, windows,

insulation and ventilation

quality, condition and life expectancy of major systems

general exterior, including roof, gutter, chimney, drainage,

grading

kitchen and appliances

It is understood and agreed that this inspection will be of readily accessible areas of the building and is limited to visual observations of apparent

conditions existing at the time of the inspection only. Latent and concealed defects and deficiencies are excluded from the inspection; equipment,

items and systems will not be dismantled.

Maintenance and other items may be discussed, but they are not a part of our inspection. The report is not a compliance inspection or certification

for past or present governmental codes or regulations of any kind.

The inspection and report do not address and are not intended to address the possible presence of or danger from any potentially harmful substances

and environmental hazards including but not limited to radon gas, lead paint, asbestos, urea formaldehyde, toxic or flammable chemicals and

water and airborne hazards. Also excluded are inspections of and report on swimming pools, wells, septic systems, security systems, central

vacuum systems, water softeners, sprinkler systems, fire and safety equipment and the presence or absence of rodents, molds and mildews.

The parties agree that Precise Home Inspection Service, LLC and its agents and employees, assume no liability or responsibility for the cost of

repairing or replacing any unreported defect of deficiency, either current or arising in the future, or for any property damage, consequential damage

or bodily injury of any nature. THE INSPECTION AND REPORT ARE NOT INTENDED TO BE USED AS A GUARANTEE OR

WARRANTY, EXPRESSED OR IMPLIED, REGARDLING THE ADEQUACY, PERFORMANCE OR CONDITION OF ANY INSPECTED

STRUCTURE, ITEM OR SYSTEM. PRECISE HOME INSPECTION SERVICE IS NOT AN INSURER OF ANY INSPECTED CONDITIONS.

It is understood and agreed that should Precise Home Inspection Service, LLC and/or its agents or employees be found liable for any loss or

damages resulting from a failure to perform any of its obligations, including but not limited to negligence, breach of contract, or otherwise, then

the liability of Precise Home Inspection Service, LLC and/or its agents and employees shall be limited to a sum equal to the amount of the fee

paid by the CUSTOMER for the Inspection and Report.

Company Representative Date Customer Date

Inspection Fee: $450.00 Paid by: ESCROW Re-inspection fee if needed: $ 225.00

R.E. Agent:

Page 6: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

5

PRECISE HOME INSPECTION SERVICE, LLC 24024 150TH

STREET SE, MONROE, WA. 98272, WA STATE LIC# 0734,

HOME INSPECTION SUMMARY REPORT

This Inspection Summary is for the exclusive use of: FAIRA.COM & Rick Cheesman

On January 29, 2016, Precise Home Inspection Service, LLC made a visual inspection of the accessible

portions of the home located at: 231 McRae Rd NE, Arlington, WA 98223.

The home was found in overall good to very good condition showing good maintenance and pride of

ownership throughout. All Mechanical systems, appliances have recently been updated. The furnace and

water heater is newer (<10yrs). Multiple maintenance issues are noted yet the home housekeeping and

Defects and deficiencies found on the date this inspection was made:

STRUCTURAL:

1. No structural deficiencies observed at the time of this inspection.

2. Earth to wood contact south & west exterior shed wall and car port (SW) support post. Repair as

needed.

3. Fungal rotted wood siding observed at shed exterior wall (round contact). Damage limited to trim

and siding. No structural damage observed at the time of this inspection. Recommend clearing all

earth to wood contact. Install gutter runs to eliminate water run off at roof drip edge.

EXTERIOR ENVELOPE:

1. The wood “Fur” exterior cladding was found in very good condition. The absence of Knots indicates

the Fur cladding materials rate a #1 Graded Rating.

2. Slight paint blistering at the south exterior gable (2nd level) exterior wall. Recommend touchup paint

as needed.

3. Water damaged wood siding observed at west exterior (shed wall). Not structural damage observed.

Replace damaged materials a proper maintenance dictates.

CRAWLSPACE:

1. The crawl space was dry with no signs of water intrusion.

GROUNDS:

1. No deficiencies observed at the time of this inspection.

Page 7: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

6

ROOFING:

1. No deficiencies observed at the time of this inspection.

ATTIC:

1. Mold spores observed on the underside of the roof sheathing (within the attic space). Recommend

contacting a qualified contractor to kill and clean all mold spores from contaminated surface with a

EPA approved “Biocide” product. Remediation of molds is fairly common with complete

remediation achieved with treatment of EAP approved Biocide products, installation of adequate

ventilation, and elimination of all moister.

HVAC:

1. No deficiencies observed at the time of this inspection.

ELECTRICAL:

1. 200amp. main panel is properly installed with no deficiencies observed at the time of this inspection.

PLUMBING:

1. No deficiencies observed at the time of this inspection

BATHROOMS:

1. No deficiencies observed at the time of this inspection

KITCHEN/APPLIANCES:

1. No deficiencies observed at the time of this inspection

INTERIOR:

1. Propane gas supply not operable at the time of this inspection. All gas plumbing was installed for

ready hook-up if needed.

2. Broken glass lens observed at the north garage wall. Replace broken glass lens as needed.

Page 8: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

7

STRUCTURAL (Pest) Section 1

Type of Building: Single Duplex 4-plex Multi-Unit Condo/Townhouse Satisfactory

“0” Lot Line PUD No Remarks

Framing: Wood Frame Masonry Metal Satisfactory

Gable Roof Shed Hip Gambrel Mansard Flat No Remarks

Foundation: Poured Concrete Block/Brick Wood Timbers Post and Pier Satisfactory

No Remarks

Structure: Posts/Columns: Steel Masonry Wood Concrete None Not Visible

Floor Structure: 2x10's on 16inch centers Satisfactory

Wall Structure: 2x4's on 16inch centers Satisfactory

Roof Structure: 2x4's on 24inch centers Satisfactory

No Remarks

Settlement: No Settlement or major structural defects noted / normal condition for age of structure

Slight – Not Significant Satisfactory

Moderate – Repairs Needed

Substantial Structural Movement – Require further investigation No Remarks

Pest (WDO): Conducive Condition(s) Earth to Wood Contact Satisfactory

Fungal Rot Some Signs Extensive None observed

Wood Boring Insects Some Signs Extensive None observed See Remarks

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

4. Earth to wood contact south & west exterior shed wall and car port (SW) support post. Repair as

needed.

5. Fungal rotted wood siding observed at shed exterior wall (round contact). Damage limited to trim

and siding. No structural damage observed at the time of this inspection. Recommend clearing all

earth to wood contact. Install gutter runs to eliminate water run off at roof drip edge.

RICHARD CHEESMAN

231 McRae Rd NE.

Arlington, WA. 98223

Page 9: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

8

EXTERIOR Section 2

Exterior Doors: Satisfactory

No Remarks

Roof Windows Moisture stains Extensive None observed Satisfactory

And Skylights: No Remarks N/A

Exterior Wall Location Materials

Covering: All Horizontal Wood Lap Satisfactory

N/A Satisfactory

N/A Satisfactory

LP Observed EFIS Observed See Remarks

Exterior Trim: Signs of Rot Extensive None observed No Remarks Satisfactory

N/A

Chimney: Brick Metal Block Direct Vent In Chase Satisfactory

Stone Clean before use N/A

Chimney Liner METAL See Remarks

Garage/Carport: Garage Carport Attached Detached Common Satisfactory

Door Operator Operating Safety Reverse No Remarks N/A

Porch: Wood Concrete No Remarks Satisfactory

Railing/Guardrail N/A

Deck: Signs of Rot Extensive None observed No Remarks Satisfactory

On grade Raised Wood Concrete Handrail N/A

Patio: Concrete Brick Flagstone Other:N/A No Remarks Satisfactory

N/A

Steps to Landing: Concrete/Masonry Wood N/A No Remarks Satisfactory

Deck/Patio: Steps: Concrete/Masonry Wood N/A

Handrails

Outbuildings: Not observed See Remarks Satisfactory

N/A

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

4. The wood “Fur” exterior cladding was found in very good condition. The absence of Knots indicates

the Fur cladding materials rate a #1 Graded Rating.

5. Slight paint blistering at the south exterior gable (2nd level) exterior wall. Recommend touchup paint

as needed.

Page 10: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

9

6. Water damaged wood siding observed at west exterior (shed wall). Not structural damage observed.

Replace damaged materials a proper maintenance dictates.

Page 11: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

10

GROUNDS Section3

Note: Inspection of grounds is limited to items listed below.

Grading: General grading, slope and drainage: Satisfactory

Grading and slope at house wall (within 5 feet of building): Satisfactory

No Remarks N/A

Sidewalk and Concrete Brick Flagstone OtherN/A Satisfactory

Walkway: No Remarks N/A

Driveway: Concrete Asphalt Gravel Other: Satisfactory

No Remarks N/A

Window Wells: Metal Brick Concrete Other:N/A Satisfactory

No Remarks N/A

Retaining Wall: Brick Block Stone Concrete Other:N/A Satisfactory

Mortared joints Dry Weep holes No Remarks N/A

Trees and Satisfactory

Shrubbery: No Remarks N/A

Fencing: Metal Wood Other:N/A Satisfactory

No Remarks N/A

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

1. No deficiencies observed at the time of this inspection.

2. The grounds are well drained with no signs of ponding water or eroded soils. The 1.75ac.

cleared lot drains to the east with a riparian pond and wetland located at the north perimeter.

LOOKING NORTH

East North – Front entry Garage -Parking

Page 12: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

11

BASEMENT Section 4

Basement: Full Partial Finished Under Construction No Basement

Walls: Open Closed Satisfactory

Ceiling: Open Closed N/A

Extensive basement storage limits visibility of floor and walls No Remarks

Floor: Concrete Dirt TILE Satisfactory

Vinyl Carpeting N/A

No Remarks

Floor Drain: Tested Not tested French Drain Satisfactory

N/A

Sump Pump: Tested Not tested French Drain Satisfactory

N/A

No Remarks

Basement Water Damage Some Signs Extensive None observed

Dampness: Past Present Not Known No Remarks

Crawl Space: Readily accessible Method:Crawled

Crawl Space Location BASEMENT WALL

Not readily accessible Satisfactory

Floor: Concrete Dirt N/A N/A

Vapor barrier Insulation Ventilation No Remarks

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

1. No deficiencies observed at the time of this inspection.

Crawl space

Page 13: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

ROOFING Section 5

Roof Covering: Location Materials Age

ALL Laminated Compostion 8YRS Satisfactory

PATIO Metal 8YRS Satisfactory

N/A Satisfactory

N/A Satisfactory

N/A

How observed: Walk on Roof

Roof Leaks: Some signs Extensive None observed

Overlay N/A No Remarks

Flashing: Aluminum Galvanized Steel Satisfactory

Rubberized membrane No Remarks

Gutters and Aluminum Galvanized Vinyl Wood Integral Satisfactory

Downspouts: Extensions / Splash Blocks: Yes No Enclosed No Remarks

Remarks :

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

1. No deficiencies observed at the time of this inspection.

Page 14: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

ATTIC Section 6

Access: How observed: ladder Not observed No access Satisfactory

Stairs Pull down Scuttle hole Location Hallway No Remarks N/A

Moisture Stains: Some signs Extensive None observed

Mold and mildew Condensation See Remarks

Storage: Heavy Light Floored Not floored

Insulation: Type:Blown Avg. inches: 18in, Satisfactory

Installed in: Rafters Floor Approx. R Rating: 31 N/A

Vapor barrier No Remarks

Ventilation: Window(s) Attic Fan Whole house fan Satisfactory

Ridge vent Soffit vent(s) Turbine Roof vent(s) N/A

Gable end louvers No Remarks

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

Dark stains, (possible mold spores) observed on the underside of the roof sheathing (within the attic space).

Recommend contacting a qualified contactor to further evaluate and correct the deficiencies noted.

Page 15: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

14

HEATING AND COOLING Section 7

Heating and Fuel: Gas Forced Air Steam Boiler

Cooling: Oil Gravity Hot Water Boiler Radiant Heat

Electric Forced Hot Water Boiler Electric Baseboard

Gravity Air Furnace Heat Pump

No. 1 Capacity: 89,000 BTU’s Age: 2006 Satisfactory

No. 2 Capacity: BTU’s Age: N/A

When turned on by thermostat: Fired Did not fire No Remarks

Fuel Supply: Fuel Oil Tank Location N/A

Public gas supply Propane Satisfactory

Electricity Solar Wind Driven Generator No Remarks

Location of Main Fuel Shut Off

Heat Partially observed Not visible; enclosed combustion N/A

Exchanger: No Remarks

Distribution: Ductwork Fans Baseboard Convectors Satisfactory

Radiators Radiant N/A

Heat source for each room: Yes No No Remarks

Humidifier: Atomizer Evaporator Steam Not functioning Satisfactory

Not tested N/A

No Remarks

Filter: Washable Disposable Electronic Electrostatic N/A

No Remarks

Supplementary Location Type

Heat: Basement Baseboard Satisfactory

N/A Satisfactory

No Remarks

Cooling: Central Air Room Units Heat Pump

Electronic Compressor Gas Chiller Satisfactory

No. 1 - Condensing Unit Capacity: 3ton Age: 2011 N/A

No. 2 - Condensing Unit Capacity: Age:

Tested Not tested

Ductwork Roof mounted water conditioner No Remarks

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

No deficiencies observed at the time of this inspection.

Page 16: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

15

ELECTRICAL Section 8

Service Capacity: 200Amps 120/240 Volts Satisfactory

Entrance Cable: Service line entrance: Overhead Underground

Conductor material: Copper Aluminum No Remarks

Main Panel Box: Location: basement wall Grounded Bonded Satisfactory

1 200Amps Fuses Circuit Breakers N/A

Sub Panel Location:

Capacity of Main Current Disconnect: 200Amps No Remarks

Circuits and Quantity: Ample Branch Wiring: Copper Aluminum Satisfactory

Conductors: GFCI: Exterior Garage Kitchen Bathroom(s)

Knob & Tube 0% of total wiring No Remarks

Outlets, Fixtures Random testing Reversed polarity Open ground Satisfactory

And Switches: Smoke detectors Arc-suppressor(s) CO detectors No Remarks

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

No deficiencies observed at the time of this inspection.

Page 17: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

PLUMBING Section 9

Water Service Public Private Satisfactory

Entrance Pipe: Pipe: Copper Galvanized Brass Plastic N/A

Lead Unknown No Remarks

Main shutoff location: Utility closet

Serviced Pipes: Copper Galvanized Brass Plastic Unknown Satisfactory

Water Flow: Tested Not tested 65 PSI N/A

Leaks: None observed No Remarks

Cross Connections: None observed

Hose bibs: Operating Not operating Frost free Not tested

Drain/Waste/ Drain/Waste/Vent Pipes: Copper Galvanized Brass Plastic

Vent: Lead Cast iron Unknown

Slow drain Leaks None observed

Waste Disposal: Public Private/Septic System Not known

No Remarks

Water Heater: Gas Electric Oil Solar Integral with heating system Satisfactory

Capacity: 50Gal. Ample for 5 People N/A

Age: 2010 TPR Valve Extension Seismic Straps No Remarks

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

No deficiencies observed at the time of this inspection.

Page 18: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

17

BATHROOMS Section 10

Bathroom #1 Location Basement 3/4 Bath

Built-in tub Leg tub Stall shower Whirlpool

Toilet Lavatory Vanity Window Fan

Shower wall covering: Fiberglass N/A

Room floor covering: Vinyl CERAMIC TILE

Leaks: Some signs None observed

No Remarks Satisfactory

Bathroom #2 Location: Hallway Full Bath

Built-in tub Leg tub Stall shower Whirlpool

Toilet Lavatory Vanity Window Fan

Shower wall covering: Fiberglass CERAMIC TILE

Room floor covering: Vinyl CERAMIC TILE

Leaks: Some signs None

observed

No Remarks Satisfactory

Bathroom #4 Location: N/A

Built-in tub Leg tub Stall shower Whirlpool

Toilet Lavatory Vanity Window Fan

Shower wall covering: Fiberglass N/A

Room floor covering: Vinyl N/A

Leaks: Some signs None

observed

No Remarks Satisfactory

Bathroom #5 Location: N/A

Built-in tub Leg tub Stall shower Whirlpool

Toilet Lavatory Vanity Window Fan

Shower wall covering: Fiberglass N/A

Room floor covering: Vinyl N/A

Leaks: Some signs None

observed

No Remarks Satisfactory

Bathroom #3 Location: Master Bath

Built-in tub Leg tub Stall shower Whirlpool

Toilet Lavatory Vanity Window Fan

Shower wall covering: Fiberglass CERAMIC TILE

Room floor covering: Vinyl CERAMIC TILE

Leaks: Some signs None observed

No Remarks Satisfactory

Remarks: :

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

No deficiencies observed at the time of this inspection.

Page 19: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

18

KITCHEN AND APPLIANCES Section 11

Cabinets and Satisfactory

Countertops: No Remarks

Sink: Plumbing Leaks: Some signs None observed Satisfactory

Disposal: Operating Not operating Age:USED N/A

No Remarks

Dishwasher: Operating Not operating Air gap Age:USED Satisfactory

N/A

No Remarks

Range/Oven: Gas Electric Operating Not operating Age USED Satisfactory

Microwave Age USED N/A

No Remarks

Refrigerator: Operating Not operating Frost free Age USED Satisfactory

Ice maker Cold water dispenser N/A

No Remarks

Other Operating Not operating Age: None Satisfactory

Appliances: Operating Not operating Age: None N/A

No Remarks

Floor: Hardwood Vinyl Ceramic N/A Satisfactory

No Remarks

Ventilation: Exhaust fan Ductless Vented to outside Satisfactory

Filter Light N/A

No Remarks

Clothes Washer: Operating Not operating 120 Volt Circuit Satisfactory

Age: USED N/A

No Remarks

Clothes Dryer: Operating Not operating Gas 240 Electric Satisfactory

Vented to: Ext. Age: USED N/A

No Remarks

Remarks:

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

Page 20: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

19

INTERIOR Section 12

Floors: Hardwood Softwood Vinyl Wall-to-wall carpet Satisfactory

Other:CERAMIC TILE Not visible No Remarks

Walls: Plaster on: Gypsum Lath Wood Lath Not known Satisfactory

Drywall Wood Masonry N/A No Remarks

Ceilings: Plaster on: Gypsum Lath Wood Lath Not known Satisfactory

Drywall Wood N/A No Remarks

Stairs/Railings: Hand Railing Satisfactory

No Remarks N/A

Fireplace: Metal pre-fab Free-standing Wood stove 0 Clearance Gas Insert Satisfactory

2 Flue liner Damper wood stove N/A

Operating Not operating Clean before use No Remarks

Note: Testing fireplace draft is not part of this inspection.

Doors (inside): No Remarks Satisfactory

Windows: Sgl/Dbl hung Casement Awning Sliding Fixed Satisfactory

Wood Metal Vinyl Insulated glass Single pane N/A

Jalousie Vinyl covered wood Storm windows See Remarks

Remarks: :

REFER TO SUMMARY REPORT FOR ALL DEFICIENCY DETAILS.

1. Propane gas supply not operable at the time of this inspection. All gas plumbing was installed for

ready hook-up if needed.

2. Broken glass lens observed at the north garage wall. Replace broken glass lens as needed.

Page 21: FAIRA TRANSPARENCY REPORTS 231 McRae Rd NE, Arlington, … · 2 Date: 2/29/16 Precise Home Inspection Service Name: FAIRA.COM & Rick Cheesman Address: 231 McRae Rd NE, Arlington,

20

Please Read: The visual inspection of the accessible portions of the home and this report are not intended to be used as a

representation, guarantee or warranty, expressed or implied regarding the adequacy, performance or condition of any portion of

the home. Precise Home Inspection Service LLC , and its agents and employees, assume no liability or responsibility whatsoever

for the cost of repairing or replacing any defects or deficiencies in the home, either current or arising in the future, or for any

property damage, consequential damage, financial harm, or bodily injury of any nature resulting from any missed or unreported

defects in the home. Please call Precise Home Inspection Service, LLC at (206) 683-3775, should any questions arise.

By: Tim M. Peterson

Tim M. Peterson Manager.

PRECISE HOME INSPECTION SERVICE, LLC,

a Washington limited liability company

WSDA LIC. #0734