608 State St. South Kirkland, WA 98033 www.faira.com [email protected] +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 1035 Chestnut St, Bremerton, WA 98310 August 7 th , 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property. You may view more detailed information for this home and can make an offer at http://www.faira.com/listings/11383 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

FAIRA TRANSPARENCY REPORTS 1035 Chestnut St, … · FAIRA TRANSPARENCY REPORTS . 1035 Chestnut St, Bremerton, ... Your siding is more than likely a Louisiana Pacific (LP) siding,

  • Upload
    lytuong

  • View
    221

  • Download
    1

Embed Size (px)

Citation preview

608 State St. South Kirkland, WA 98033

www.faira.com

[email protected] +1.800.571.FAIR

FAIRA TRANSPARENCY REPORTS

1035 Chestnut St, Bremerton, WA 98310

August 7th, 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.

You may view more detailed information for this home and can make an offer at

http://www.faira.com/listings/11383 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Inspection Report for Mr. Tim BakerProperty Address: 1035 Chestnut St., Bremerton, Washington 98310

NW WASHINGTON HOME INSPECTIONS LLC

Carl Liberman WA License # 1758 Bainbridge Island, WA

Table of Contents

Cover Page.................................................................1

Table of Contents ........................................................2

Intro Page ...................................................................3

Significant Issues ........................................................5

Repair & Maintenance Summary ................................6

Complete Wood Destroying Organism InspectionReport .........................................................................9

1 Roof .......................................................................10

2 Attic ........................................................................13

3 Exterior...................................................................15

4 Wall Exteriors.........................................................18

5 Structure ................................................................21

6 Electrical ................................................................25

7 Garage...................................................................31

8 Interior....................................................................32

9 Plumbing ................................................................33

10 Heating.................................................................35

11 Cooling .................................................................37

12 Bathrooms............................................................38

13 Kitchen and Built-in Appliances ...........................40

14 Laundry Room .....................................................44

Invoice.......................................................................46

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 2 of 46

Date: 8/4/2017 Time: 09:00 AM Report ID: 170804 A / ICN10236AR002

Property:1035 Chestnut St.Bremerton Washington 98310

Customer:Mr. Tim Baker

Real Estate Professional:Chris EllisFaira.com

Dear Mr. & Mrs. Baker,

Thank you for choosing NW WASHINGTON HOME INSPECTIONS LLC for your home inspection needs. I greatlyappreciate the importance of this inspection and can assure you I have done my utmost to provide you with anorganized, sufficiently-detailed, and easy-to-read report.

Two summary reports are provided at the beginning of the report highlighting the most significant findings. TheSignificant Issues Summary includes the most serious issues identified during the inspection. The Repair &Maintenance Summary includes the remainder of those potentially near-term actionable items for you to considerbased on the inspection. The results of your Structural Pest Inspection are also summarized in the Complete WoodDestroying Organism Inspection Report, also included at the beginning of the Home Inspection Report.

The body of the report is organized by system: Roofing, Structure, Electrical, etc. I have included pictures whenpossible. Please review the entire report as there is additional information presented in the body of the report thatmay not be found in the summaries.

If you have any questions regarding your inspection, please feel free to contact me directly at 206.841.9532 or emailme at [email protected]. I look forward to providing future home inspection needs to you, yourfriends, and family.

Warm Regards,

Carl Liberman

Significant Issues ( ) = Items or discoveries indicate that these systems or components may cost significant moneyto correct now or in the near future, or items that require immediate attention to prevent additional damage or eliminatesafety hazards. Further investigation by a specialist and/or subsequent observation may be required.

Repair & Maintenance ( ) = Items or discoveries indicate that these systems or components do not function asintended and/or maintenance is required in the near term. Further investigation by a specialist and/or subsequentobservation may be required.

Wood Destroying Organisms ( ) = Items or discoveries that indicate the presence of wood destroying organisms orconditions conducive to wood destroying organisms. Conducive conditions include but are not limited to, inadequateclearances, earth/wood contact, cellulose debris, inadequate ventilation, and excessive moisture.

Standard Limitations: Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes ofthe need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance ornon-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability;The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence ofpests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Homeinspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system orcomponent; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspectoror other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 3 of 46

respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debristhat obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardoussubstance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine theeffectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limitedto failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information shouldhire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.

Type of building::Single Family (1 story)

Approximate Square Footage::1500

Approximate Year of OriginalConstruction::1991

Inspection started at::9am

Inspection ended at::11am

Occupancy::The home was occupied

Attending the Inspection::Seller

Weather during the Inspection::Clear

Significant precipitation in last 3 days::No

Temperature during inspection::Over 65 (F) = 18 (C)

Ground/Soil surface condition:Dry

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 4 of 46

Significant IssuesSignificant Issues = Items or discoveries indicate that these systems or components may cost significant money tocorrect now or in the near future, or items that require immediate attention to prevent additional damage or eliminatesafety hazards.

3. Exterior

3.6 Deck, Balcony, Bridge and Porch,(1) The back deck does not meet today's basic safety standards, specifically; the ledger board is not bolted to thehouse rim joist, hangers are not used to support load bearing joists at the ledger-board or at the mid-span supportbeam, the ledger board is partially attached to a cantilever bay window detail (not allowed), railing balusters exceedthe 4 inch maximum recommended spacing. I would recommend consulting a licensed decking contractor foroptions to improve the safety of the structure.

See American Wood Council's Prescriptive Residential Wood Deck Construction Guide for best practices here:http://www.awc.org/pdf/codes-standards/publications/dca/AWC-DCA62012-DeckGuide-1405.pdf

4. Wall Exteriors

4.4 Composite SidingOriginal hard-board horizontal lap siding is the siding on the front of the house. Fiber-cement siding has replacedthe siding for the remainder of the exterior. Hard-board siding produced from 1990 to 1996 of various manufacturers(including LP) have seen problems with susceptibility to water absorption and subsequent related problems anddamage. Several class action lawsuits have been settled. Your siding is more than likely a Louisiana Pacific (LP)siding, identified by a unique knot in the pattern. It is extremely important to keep this type of siding sealed withcaulk and paint to avoid problems (it appears to be so at the time of the inspection). Once damaged, replacement isgenerally the best option. Please further consult a licensed siding contractor to discuss options for your situation.

5. Structure

5.6 Crawl Space Rodent ActivityRodent activity was evident throughout the crawlspace. Insulation has been disturbed and has fallen. I wouldrecommend you retain a pest specialist to exterminate the rodents. The affected insulation needs to be replacedand the crawlspace cleaned up. Please consult a crawl space remediation specialist for options and costs. A ventscreen requires repair, this is a possible entry point for rodents.

Please note this section is not all-inclusive, please read the complete report.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 5 of 46

Repair & Maintenance SummaryRepair & Maintenance Issues = Items or discoveries indicate that these systems or components do not function asintended and/or maintenance is required in the near term. Further investigation by a specialist and/or subsequentobservation may be required.

1. Roof

1.5 Chimney at RoofThe metal chimney cap and some of the roof vents are rusting and may fail soon (holes and leaks). I wouldrecommend repair or replacement by a licensed roofing contractor.

1.6 Asphalt Composition Shingle(2) A repair has been attempted in this area using many screws to penetrate the shingles from above. This is notideal and may eventually leak. I would recommend repairs by a licensed roofing contractor.

3. Exterior

3.3 General GroundsRecommend trimming this tree back away from the structure and chimney.

3.6 Deck, Balcony, Bridge and Porch,(2) Some rot was evident in a bench behind the deck. I would recommend replacing affected wood. This conditionis further conducive to wood destroying organisms.

4. Wall Exteriors

4.3 Exterior Wall MembraneA section of sheathing needs to be re-fastened in the soffit.

4.5 Fiber-cementRecommend caulking the few seams that have opened in the fiber-cement siding.

5. Structure

5.3 FoundationQuarter-span support beams are supported on 6 inch CMU's (solid cinder-blocks), no poured concrete footings wereevident. Consider adding poured concrete footings to best support the structure in accordance with modernbuilding practices.

5.4 Crawlspace(1) Crawlspace vents on the front of the house need to be cleared of mulch so that the vents can properly ventilate.

(2) Strapping to support ventilation ducting needs to be re-hung.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 6 of 46

6. Electrical

6.14 Exterior Electrical ReceptaclesExterior outlets require repair or replacement. GFCI type exterior outlets are required. Please consult a licensedelectrician.

6.16 GFCI/AFCI Electrical ReceptaclesThe outlet in laundry room was not GFCI protected. Electrical receptacles located in basements, crawlspaces,garages, the home exterior, and interior receptacles located within 6 feet of a plumbing fixture should be providedwith ground fault circuit interrupter (GFCI) protection. Please consult a licensed electrician for replacement.

6.20 Smoke DetectorsSmoke detectors are recommended on each floor of the home, in each bedroom of the home, outside commonbedroom areas. Install in accordance with manufactures recommend guidance or hire a licensed contractor forproper installation.

Reference WAC 212-10-040: http://apps.leg.wa.gov/wac/default.aspx?cite=212-10-040

6.21 Carbon Monoxide DetectorsCarbon monoxide alarms must be located outside of each separate sleeping area, in the immediate vicinity of thebedroom and on each level of the residence. Install in accordance with manufactures recommend guidance or hire alicensed contractor for proper installation.

Reference WAC 51-51-315: http://apps.leg.wa.gov/WAC/default.aspx?cite=51-51-0315

9. Plumbing

9.1 Source of WaterThis is most likely the main water cut-off. Recommend verifying and labeling for future reference.

9.4 Gas Water HeaterConsider adding a surge tank to your hot water heater for improved protection from pressure transients, pleaseconsult a licensed plumber.

10. Heating

10.1 FurnaceThe furnace was dirty. I would recommend you have the furnace (and air conditioning system) serviced andannually thereafter.

11. Cooling

11.0 Central Air ConditionerPlease note, this air condition unit was manufactured in 1997 and may require replacement in the future.

12. Bathrooms

12.11 Bathtub

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 7 of 46

The bathtub water diverter to activate the shower does not work properly, recommend replacement or repair.

13. Kitchen and Built-in Appliances

13.9 RangePlease note, the range/oven is an older model and may require replacement in the future.

13.12 Dishwasher(1) The dishwasher did not appear to have an anti-siphon device installed in the drain line. Anti-siphon devices areinstalled to prevent wastewater from the dishwasher from being siphoned back into the dishwasher andcontaminating its contents. The Inspector recommends an anti-siphon device be installed by a qualified technician.(2) Please note, the dishwasher is an older model and may require replacement in the future.

14. Laundry Room

14.10 DryerPlease note, the dryer is an older model and may require replacement in the future.

Please note this section is not all-inclusive, please read the complete report.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 8 of 46

Complete Wood Destroying Organism Inspection ReportComplete Wood Destroying Organism Inspection Report: This report identifies the presence of wood destroyingorganisms or conditions conducive to wood destroying organisms. Conducive conditions include but are not limited to,inadequate clearances, earth/wood contact, cellulose debris, inadequate ventilation, and excessive moisture. PestInspection Standards in Washington State, WAC 16-228-2045 - requires that a diagram / drawing be prepared forwood destroying organism (WDO) Reports. If the photos and descriptions in this report are inadequate, a drawingis available upon request.

WSDA ICN # 10236AR002

_________________________________________________________________________________________________________

Summary of Findings:

Visible Evidence of Active Wood Destroying Insects: None Noted / Present

Visible Evidence of Inactive Wood Destroying Insects: None Noted / Present

Visible Evidence of Active Wood Decaying Fungi: None Noted / Present

Visible Evidence of Damage by Wood Destroying Organisms: None Noted / Present

Visible Evidence of Conditions Conducive to Wood Destroying Organisms: None Noted / Present

_________________________________________________________________________________________________________

Moisture Meter Testing: Where moisture meter testing is indicated in this report a GE Protimeter BLD5365 SurveymasterDual-Function Moisture Meter was used.

Standard Limitations: Complete WDO inspections will identify conditions present at a subject property at the time of an inspection. Inspectorsare not required to report on any WDO infestation or other condition that might be subject to seasonal constraints or environmental condition ifevidence of those constraints or conditions is not visible at the time of inspection. Please note that most WDO observations are related to highmoisture conditions that could be conducive to mold-like substances. NORTHWEST WASHINGTON HOME INSPECTIONS LLC is not a moldspecialist and recommends consulting with an industrial hygienist or other mold remediation expert if concerned about mold or indoor airquality.

3. Exterior

3.6 Deck, Balcony, Bridge and Porch,(2) Some rot was evident in a bench behind the deck. I would recommend replacing affected wood. This conditionis further conducive to wood destroying organisms.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 9 of 46

1. RoofThe roof inspection portion of the General Home Inspection will not be as comprehensive as an inspection performed by a qualified roofing contractor.Because of variations in installation requirements of the huge number of different roof-covering materials installed over the years, the General HomeInspection does not include confirmation of proper installation. Home Inspectors are trained to identify common deficiencies and to recognizeconditions that require evaluation by a specialist. Inspection of the roof typically includes visual evaluation of the roof structure, roof-coveringmaterials, flashing, and roof penetrations like chimneys, mounting hardware for roof-mounted equipment, attic ventilation devices, ducts forevaporative coolers, and combustion and plumbing vents. The roof inspection does not include leak-testing and will not certify or warranty the roofagainst future leakage. Other limitations may apply and will be included in the comments as necessary.

Styles & Materials

Method of inspection:Walked the roof

The roof style was:Gable

Primary roof-covering type:3-tab Fiberglass Asphalt Shingle

Drainage system description:Gutters and downspouts installed

Chimney flue material:Metal

Underlayment/Interlayment::Mostly hidden from view

Sky Light(s):One

Items

1.0 Roof Structure ExteriorComments: Inspected

1.1 UnderlaymentComments: Inspected

1.2 Roof FlashingComments: Inspected

1.3 Roof Drainage SystemComments: Inspected

1.4 Plumbing and Combustion VentsComments: Inspected

1.5 Chimney at RoofComments: Inspected

Most underlayment was hidden beneath the roof-covering material. The inspector was able to view edges onlya representative areas around the perimeter of the roof.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 10 of 46

1.6 Asphalt Composition ShingleComments: Inspected

The metal chimney cap and some of the roof vents are rusting and may fail soon (holes and leaks). Iwould recommend repair or replacement by a licensed roofing contractor.

1.5 (1) Chimney Cap 1.5 (2) Vents

(1) View of asphalt shingle roof.

1.6 (1) 1.6 (2)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 11 of 46

The roof of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

(2) A repair has been attemptedin this area using many screws topenetrate the shingles from above.This is not ideal and may eventuallyleak. I would recommend repairs by alicensed roofing contractor.

1.6 (3)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 12 of 46

2. AtticInspection of the attic typically includes visual examination the following:roof structure (framing and sheathing); roof structure ventilation; thermalenvelope; electrical components (wiring, junction boxes, outlets, switches and lighting); plumbing components (supply and vent pipes, bathroom ventterminations) and HVAC components (drip pans, ducts, condensate and TPR discharge pipes).

Styles & Materials

Attic info:Scuttle hole

Attic inspected from:Inside the attic

Attic thermal insulation material:Fiberglass Batt

Approximate attic thermal insulationdepth:

R-19 or better

Roof structure ventilation device type:Roof ventsSoffit vents

Roof Framing Type:Manufactured Roof Trusses

Roof Sheathing Material:Oriented Strand Board (OSB)

Items

2.0 Attic AccessComments: Inspected

2.1 Roof Framing (from attic)Comments: Inspected

2.2 Roof SheathingComments: Inspected

2.3 Roof Structure VentilationComments: Inspected

2.4 Attic ElectricalComments: Inspected

2.5 Venting Systems (Kitchens, Baths and Laundry)Comments: Inspected

2.6 Attic Rodent ActivityComments: Inspected

View of attic.

2.1 (1) 2.1 (2)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 13 of 46

The attic of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 14 of 46

3. ExteriorInspection of the home exterior typically includes: exterior wall covering materials; exterior trim; window and door exteriors; adequate surfacedrainage; driveway and walkways; window wells; exterior electrical and plumbing components; and retaining wall conditions that may affect the homestructure. The potential for dangers/damage associated with trees- such as falling branches or root damage to foundations- varies with tree speciesand age, and requires an arborist evaluation.

The General Home Inspection does not include inspection of landscape irrigation systems, fencing or swimming pools/spas.

Styles & Materials

Driveway Material:Concrete

Walkway Materials:Concrete

Appurtenance:Deck with steps

Downspout Discharge:Below Grade

Lot Description:Flat

Clearance to Grade:Standard

Items

3.0 Exterior ViewsComments: Inspected

3.1 DrivewayComments: Inspected

3.2 WalkwaysComments: Inspected

3.3 General GroundsComments: Inspected

3.4 Exterior TrimComments: Inspected

3.5 PorchComments: Inspected

3.6 Deck, Balcony, Bridge and Porch,Comments: Inspected

Recommend trimming this treeback away from the structure andchimney.

3.3 (1)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 15 of 46

(1) The back deck does not meet today's basic safety standards, specifically; the ledger board is notbolted to the house rim joist, hangers are not used to support load bearing joists at the ledger-board or at themid-span support beam, the ledger board is partially attached to a cantilever bay window detail (not allowed),railing balusters exceed the 4 inch maximum recommended spacing. I would recommend consulting alicensed decking contractor for options to improve the safety of the structure.

See American Wood Council's Prescriptive Residential Wood Deck Construction Guide for best practiceshere: http://www.awc.org/pdf/codes-standards/publications/dca/AWC-DCA62012-DeckGuide-1405.pdf

3.6 (1) Back Deck 3.6 (2) Attached to bay window (cantilever)

3.6 (3) Baluster spacing exceeds 4 inches 3.6 (4) No hangers for joists

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 16 of 46

The exterior of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

(2) Some rot was evident ina bench behind the deck. I wouldrecommend replacing affected wood.This condition is further conducive towood destroying organisms.

3.6 (5)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 17 of 46

4. Wall ExteriorsInspection of the home exterior typically includes: exterior wall covering materials; exterior trim; window and door exteriors; adequate surfacedrainage; driveway and walkways; window wells; exterior electrical and plumbing components; and retaining wall conditions that may affect the homestructure. The potential for dangers/damage associated with trees- such as falling branches or root damage to foundations- varies with tree speciesand age, and requires an arborist evaluation.

The General Home Inspection does not include inspection of landscape irrigation systems, fencing or swimming pools/spas.

Styles & Materials

Exterior wall-covering Material:Fiber-cement SidingHardboard Lap Siding

Exterior Doors:Hollow coreFiberglass

Items

4.0 Door ExteriorsComments: Inspected

4.1 Window ExteriorsComments: Inspected

4.2 Exterior Wall PenetrationsComments: Inspected

4.3 Exterior Wall MembraneComments: Inspected

4.4 Composite SidingComments: Inspected

A section of sheathing needs tobe re-fastened in the soffit.

4.3 (1)

Original hard-board horizontal lap siding is the siding on the front of the house. Fiber-cement siding hasreplaced the siding for the remainder of the exterior. Hard-board siding produced from 1990 to 1996 of variousmanufacturers (including LP) have seen problems with susceptibility to water absorption and subsequentrelated problems and damage. Several class action lawsuits have been settled. Your siding is more than likelya Louisiana Pacific (LP) siding, identified by a unique knot in the pattern. It is extremely important to keep thistype of siding sealed with caulk and paint to avoid problems (it appears to be so at the time of the inspection).

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 18 of 46

4.5 Fiber-cementComments: Inspected

Once damaged, replacement is generally the best option. Please further consult a licensed siding contractorto discuss options for your situation.

4.4 (1) LP Hard-board siding - identifying feature

4.4 (2)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 19 of 46

The exterior of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

Recommend caulking the fewseams that have opened in the fiber-cement siding.

4.5 (1)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 20 of 46

5. StructureThe General Home Inspection includes inspection of the home structural elements that were readily visible at the time of the inspection. This mayinclude the: foundation; walls; floor structure; and/or roof structure. Soils vary in their stability and ability to support the weight of a structure. Minorcracking is normal with some common foundation materials, is typically limited to the material surface, is not a structural concern, and may not becommented on. Cracking related to soil/foundation movement indicates the potential for present or future structural concerns and will be commentedon to the best of the inspector's ability.

Much of the home structure is hidden behind exterior and interior roof, floor, wall, and ceiling coverings, or is buried underground. Because theGeneral Home Inspection is limited to visual and non-invasive methods, this report may not identify all structural deficiencies. Identification of portionsof the wall structure not directly visible requires logical assumptions on the part of the Inspector that are based on the Inspectors past experience andknowledge of common building practices.

Upon observing indications that structural problems may exist that are not readily visible, or the evaluation of which lies beyond the Inspector'sexpertise, the inspector may recommend evaluation or testing by a specialist that may include invasive measures, which would require homeownerpermission.

Styles & Materials

Typical Ceiling Structure:Drywall attached to roof trusses

Exterior Wall Structures:Wood Frame

Wall Insulation:Not Visible

Foundation Configuration:Crawlspace

Foundation Method/Materials:Poured concrete foundation walls

Main Floor Structure:2x10 wood joistsShiplap

Main Floor Structure- Perimeter Bearing:Rests on top of foundation wall

Main Floor Structure- IntermediateSupport:

Wood beam girderWood postsConcrete Piers

Floor System Insulation:UnfacedFiberglass

Evidence of Seismic Protection:None Noted

Crawl Space Vapor Barrier:6 Mil Poly

Items

5.0 Exterior Wall ConstructionComments: Inspected

5.1 Floor StructureComments: Inspected

5.2 Insulation Under Floor SystemComments: Inspected

5.3 FoundationComments: Inspected

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 21 of 46

5.4 CrawlspaceComments: Inspected

Quarter-span support beams aresupported on 6 inch CMU's (solidcinder-blocks), no poured concretefootings were evident. Consideradding poured concrete footings tobest support the structure inaccordance with modern buildingpractices.

5.3 (1) CMU footing (left), Concrete footing (right)

(1) Crawlspace vents on the front of the house need to be cleared of mulch so that the vents can properlyventilate.

5.4 (1) mulch in vents 5.4 (2) partially blocked vent

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 22 of 46

5.5 Crawl Space Moisture ConditionsComments: Inspected

5.6 Crawl Space Rodent ActivityComments: Inspected

(2) Strapping to supportventilation ducting needs to be re-hung.

5.4 (3)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 23 of 46

5.7 OtherComments: Inspected

The structure of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

Rodent activity was evident throughout the crawlspace. Insulation has been disturbed and has fallen. Iwould recommend you retain a pest specialist to exterminate the rodents. The affected insulation needs to bereplaced and the crawlspace cleaned up. Please consult a crawl space remediation specialist for options andcosts. A vent screen requires repair, this is a possible entry point for rodents.

5.6 (1)

5.6 (2)

5.6 (3) Possible entry point

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 24 of 46

6. ElectricalOver the years, many different types and brands of electrical components have been installed in homes. Electrical components and standards havechanged and continue to change. Homes electrical systems are not required to be updated to meet newly enacted electrical codes or standards. Fulland accurate inspection of electrical systems requires contractor-level experience. For this reason, full inspection of home electrical systems liesbeyond the scope of the General Home Inspection.

The General Home Inspection is limited to identifying common electrical requirements and deficiencies. Conditions indicating the need for a morecomprehensive inspection will be referred to a qualified electrical contractor.Inspection of the home electrical system typically includes visualinspection of the following:service drop: conductors, weatherhead, and service mast; electric meter exterior; service panel and sub-panels; serviceand equipment grounding; system and component bonding; and visible branch wiring: receptacles (representative number), switches, lighting

Styles & Materials

Electrical Service Conductors:Overhead serviceAluminum120/240 volt service

Service Panel Ampacity:200 amps

Service Panel Type:Edison Fuse Panel

Service Panel Manufacturer:General Electric

Service Disconnect Location:At Service Panel

Service Disconnect Type:Breaker

Service Grounding Electrode:Not Visible

Wiring Methods:Romex

Type of Branch Wiring:Solid CopperStranded Copper

Ground Fault Circuit Interruptor (GFCI)Protection:

YES

Arc Fault Circuit Interruptor (AFCI)Protection:

NO

Items

6.0 General Electrical System DescriptionComments: Inspected

6.1 General Electrical System ConditionComments: Inspected

6.2 Service Drop, Drip Loop, Splice and AttachmentComments: Inspected

6.3 Mast & WeatherheadComments: Inspected

6.4 Electric MeterComments: Inspected

6.5 Service Entrance ConductorsComments: Inspected

6.6 Service Panel ManufacturerComments: Inspected

6.7 Service Panel Exposure RatingComments: Inspected

6.8 Service Panel Cabinet, Ampacity, and CoverComments: Inspected

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 25 of 46

6.9 Service Panel WiringComments: Inspected

6.10 Service DisconnectComments: Inspected

6.11 Overcurrent Protection DevicesComments: Inspected

6.12 Service Grounding Electrode System & Service BondComments: Inspected

6.13 Equipment Grounding & BondingComments: Inspected

6.14 Exterior Electrical ReceptaclesComments: Inspected

Please note, the generator panel was not inspected as it is beyond the scope of the standard homeinspection.

6.8 (1) generator panel above main panel

6.8 (2) main panel

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 26 of 46

Exterior outlets require repair or replacement. GFCI type exterior outlets are required. Please consult alicensed electrician.

6.14 (1) Reverse polarity

6.14 (2) GFCI not functional

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 27 of 46

6.15 Conventional Electrical Receptacles (interior)Comments: Inspected

6.16 GFCI/AFCI Electrical ReceptaclesComments: Inspected

6.17 SwitchesComments: Inspected

6.14 (3) Not approved for outdoor use

The outlet in laundry room wasnot GFCI protected. Electricalreceptacles located in basements,crawlspaces, garages, the homeexterior, and interior receptacleslocated within 6 feet of a plumbingfixture should be provided with groundfault circuit interrupter (GFCI)protection. Please consult a licensedelectrician for replacement.

6.16 (1)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 28 of 46

6.18 LightingComments: Inspected

6.19 Visible Branch WiringComments: Inspected

6.20 Smoke DetectorsComments: Inspected

6.21 Carbon Monoxide DetectorsComments: Inspected

Smoke detectors are recommended on each floor of the home, in each bedroom of the home, outsidecommon bedroom areas. Install in accordance with manufactures recommend guidance or hire a licensedcontractor for proper installation.

Reference WAC 212-10-040: http://apps.leg.wa.gov/wac/default.aspx?cite=212-10-040

6.20 (1)

6.20 (2)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 29 of 46

6.22 DoorbellComments: Inspected

The electrical system of the home was inspected and reported on with the above information. Outlets were not removed and the inspection was onlyvisual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates tothe comments in this inspection report.

Carbon monoxide alarms must be located outside of each separate sleeping area, in the immediatevicinity of the bedroom and on each level of the residence. Install in accordance with manufacturesrecommend guidance or hire a licensed contractor for proper installation.

Reference WAC 51-51-315: http://apps.leg.wa.gov/WAC/default.aspx?cite=51-51-0315

6.21 (1)

6.21 (2)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 30 of 46

7. GarageInspection of the garage typically includes examination of the following:general structure; floor, wall and ceiling surfaces; operation of all accessibleconventional doors and door hardware; vehicle door condition and operation proper electrical condition including Ground Fault Circuit Interrupter(GFCI) protection; interior and exterior lighting; stairs and stairways proper firewall separation from living space; and proper floor drainage

Styles & Materials

Garage Vehicle Door Type:Double

Number of Vehicle Doors:1

Number of Automatic Openers:1

Vehicle Door Automatic Reverse:Installed and operating correctly

Auto-opener Manufacturer:LIFT-MASTER

Items

7.0 Vehicle DoorsComments: Inspected

7.1 Conventional DoorsComments: Inspected

7.2 FloorsComments: Inspected

7.3 WallsComments: Inspected

7.4 CeilingComments: Inspected

7.5 Fire SeparationComments: Inspected

7.6 Stairs/Steps to Living SpaceComments: Inspected

7.7 Garage ElectricalComments: Inspected

7.8 General Condition and VentilationComments: Inspected

7.9 AtticComments: Inspected

7.10 Roof FramingComments: Inspected

The structure of the home was inspected and reported on with the above information. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 31 of 46

8. InteriorInspection of the home interior does not include testing for mold, radon, asbestos, lead paint, or other environmental hazards unless specificallyrequested as an ancillary inspection. Inspection of the home interior typically includes: interior wall, floor and ceiling coverings and surfaces; doorsand windows: condition, hardware, and operation; interior trim: baseboard, casing, molding, etc.; permanently-installed furniture, countertops,shelving, and cabinets; and ceiling and whole-house fans.

Styles & Materials

Walls and Ceilings:Drywall

Floor Covering Materials:CarpetVinyl

Interior Doors:Hollow

Window Material:Vinyl

Window Glazing:Double-pane

Window Operation:Sliding

Smoke/CO Detectors:Smoke detectors installed (hardwired)Additional carbon monoxide detector(s)

required

Items

8.0 FloorsComments: Inspected

8.1 WallsComments: Inspected

8.2 CeilingsComments: Inspected

8.3 LightingComments: Inspected

8.4 Misc. Components: Ceiling fans, doorbells, Env. Hazards, Detectors, etc.Comments: Inspected

8.5 DoorsComments: Inspected

8.6 Windows and SkylightsComments: Inspected

8.7 Interior TrimComments: Inspected

8.8 Cabinets and CountertopsComments: Inspected

8.9 Bathroom and Laundry VentilationComments: Inspected

The interior of the home was inspected and reported on with the above information. The inspection did not involve moving furniture and inspectingbehind furniture, area rugs or areas obstructed from view. Any repair items mentioned in this report should be considered before purchase. It isrecommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 32 of 46

9. PlumbingInspection of the plumbing system typically includes (limited) operation and visual inspection of: water supply source (identification as public orprivate); sewage disposal system (identification as public or private); water supply/distribution pipes; drain, waste and vent (DWV) system; waterheater (type, condition and operation); gas system; and sump pump (confirmation of installation/operation).

Styles & Materials

Water Supply Source:Public Water Supply

Main Water Supply Pipe:1-inchCopper

Main Water Supply Location:Garage

Water Distribution Pipes:1/2-inch and 3/4-inch copper

Distribution Pipe Bonding:Pipes were bonded

Drain Waste and Vent Pipe Materials:Acrylonitrile butadiene styrene (ABS)

Water Heater Manufacturer:Whirlpool

Date of Manufacture:2006

Water Heater Fuel Type:Gas

Water Heater Type:Tank (conventional)

Water Heater Tank Capacity:50 gallons

Water Heater Location:Garage

Washer Drain Size:2" Diameter

Gas Pipe Material:Black Steel

Type of Gas:Natural Gas

Items

9.0 Exterior PlumbingComments: Inspected

9.1 Source of WaterComments: Inspected

This is most likely the main watercut-off. Recommend verifying andlabeling for future reference.

9.1 (1)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 33 of 46

9.2 Water Supply and DistributionComments: Inspected

9.3 Sewage and DWV SystemsComments: Inspected

9.4 Gas Water HeaterComments: Inspected

The plumbing in the home was inspected and reported on with the above information. Washing machine drain line for example cannot be checked forleaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed andbarely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waitingfor closing) rust or deposits within the pipes can further clog the piping system. Any repair items mentioned in this report should be considered beforepurchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

The plumbing in the home was inspected and reported on with the above information. Washing machine drain line for example cannot be checked forleaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed andbarely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waitingfor closing) rust or deposits within the pipes can further clog the piping system. Any repair items mentioned in this report should be considered beforepurchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

Consider adding a surge tank toyour hot water heater for improvedprotection from pressure transients,please consult a licensed plumber.

9.4 (1) No surge tank

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 34 of 46

10. HeatingHeating system inspection will not be as comprehensive as that performed by a qualified heating, ventilating, and air-conditioning (HVAC) systemcontractor. For example: identification of cracked heat exchangers requires a contractor evaluation. Report comments are limited to identification ofcommon requirements and deficiencies. Observed indications that further evaluation is needed will result in referral to a qualified HVAC contractor.The general home inspection does not include any type of heating system warranty or guaranty. Inspection of heating systems is limited to basicevaluation based on visual examination and operation using normal controls. Report comments are limited to identification of common requirementsand deficiencies. Observed indications that further evaluation is needed will be referred to a qualified heating, ventilating, and air-conditioning (HVAC)contractor. Inspection of heating systems typically includes (limited) operation and visual inspection of: the heating appliance (confirmation ofadequate response to the call for heat); proper heating appliance location; proper or adequate heating system configuration; exterior cabinetcondition; fuel supply configuration and condition; combustion exhaust venting; heat distribution components; proper condensation discharge; andtemperature/pressure relief valve and discharge pipe (presence, condition, and configuration).

Styles & Materials

Heating System Type:Gas-fired Furnace (medium efficiency)

Energy Source:Natural gas

Number of Heat Systems (excludingwood):

One

Heating/Cooling Ducts:Insulated

Air Filter:Electronic air filter

Air Filter Location:Behind removable panel at furnace

Heating System Brand:Carrier

Types of FIreplaces:Vented gas logs

Operational Fireplaces:One

Items

10.0 Presence of installed heat source in each roomComments: Inspected

10.1 FurnaceComments: Inspected

The furnace was dirty. I wouldrecommend you have the furnace(and air conditioning system) servicedand annually thereafter.

10.1 (1) furnace

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 35 of 46

10.2 Fuel, Piping and SupportComments: Inspected

10.3 ThermostatComments: Inspected

10.4 Filter conditionComments: Inspected

10.5 FireplaceComments: Inspected

The heating system of this home was inspected and reported on with the above information. The inspection is not meant to be technically exhaustive.The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensedheat contractor would discover. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualifiedcontractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 36 of 46

11. CoolingInspection of home cooling systems typically includes visual examination of readily observable components for adequate condition, and systemtesting for proper operation using normal controls. Cooling system inspection will not be as comprehensive as that performed by a qualified heating,ventilating, and air-conditioning (HVAC) system contractor. Report comments are limited to identification of common requirements and deficiencies.Observed indications that further evaluation is needed will result in referral to a qualified HVAC contractor. To avoid the potential for system damage,the air-conditioning system will not be operated if the outside air temperature is below 65 degrees F (17 C).

Styles & Materials

Number of cooling systems (excludingwindow AC):

One

Cooling System Type:Split System (indoor and outdoor

components

Cooling Equipment Energy Source:Electricity

Cooling System Manufacturer:Trane

Number of AC Only Units:One

Items

11.0 Central Air ConditionerComments: Inspected

11.1 Presence of installed cooling source in each roomComments: Inspected

The heating system of this home was inspected and reported on with the above information. The inspection is not meant to be technically exhaustive.The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensedheat contractor would discover. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualifiedcontractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

The cooling system of this home was inspected and reported on with the above information. The inspection is not meant to be technically exhaustive.The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensedheat contractor would discover. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualifiedcontractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

Please note, this air condition unit was manufactured in 1997 and may require replacement in the future.

11.0 (1) 11.0 (2)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 37 of 46

12. BathroomsInspection of the bathrooms typically includes the following:walls, floors and ceiling; sink (basin, faucet, overflow); cabinets (exteriors, doors, drawers,undersink); toilet/bidet tub and shower (valves, showerhead, walls, enclosure); electrical (outlets, lighting); and room ventilation

Styles & Materials

Exhaust Fans:Fan only

Items

12.0 FloorsComments: Inspected

12.1 WallsComments: Inspected

12.2 CeilingsComments: Inspected

12.3 DoorsComments: Inspected

12.4 WindowsComments: Inspected

12.5 SkylightsComments: Inspected

12.6 Electrical Receptacles and SwitchesComments: Inspected

12.7 LightingComments: Inspected

12.8 VentilationComments: Inspected

12.9 CabinetsComments: Inspected

12.10 ToiletComments: Inspected

12.11 BathtubComments: Inspected

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 38 of 46

12.12 ShowerComments: Inspected

12.13 Medicine CabinetComments: Inspected

12.14 MirrorsComments: Inspected

12.15 SinkComments: Inspected

The bathrooms of the home was inspected and reported on with the above information. Any repair items mentioned in this report should beconsidered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to thecomments in this inspection report.

The bathtub water diverter toactivate the shower does not workproperly, recommend replacement orrepair.

12.11 (1)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 39 of 46

13. Kitchen and Built-in AppliancesInspection of kitchens typically includes (limited) operation and visual inspection of the following: wall, ceiling and floor; windows, skylights and doors;range/cooktop (basic functions, anti-tip); range hood (fan, lights, type); dishwasher; Cabinetry exterior and interior; door and drawer; Sink basincondition; supply valves; adequate trap configuration; functional water flow and drainage; disposal; Electrical switch operation; and outlet placement,grounding, and GFCI protection. Note: Appliances are operated at the discretion of the Inspector.

Styles & Materials

Cabinets:Solid WoodVeneer on MDF

Countertop Material:Tiled

Range:Electric

Range/Oven Brand:General Electric

Range Hood:Vents to exterior

Range Hood Brand:Samsung

Dishwasher:Present, not inspected

Dishwasher brand:General Electric

Dishwasher Anti-siphon method:No anti-siphon installed

Garbage Disposal brand:InSinkErator

Refrigerator:Inspected

Refridgerator Brand:Kenmore

Items

13.0 FloorsComments: Inspected

13.1 WallsComments: Inspected

13.2 CeilingsComments: Inspected

13.3 DoorsComments: Inspected

13.4 WindowsComments: Inspected

13.5 Interior TrimComments: Inspected

13.6 Receptacles and SwitchesComments: Inspected

13.7 LightingComments: Inspected

13.8 CabinetsComments: Inspected

13.9 RangeComments: Inspected

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 40 of 46

13.10 Range HoodComments: Inspected

13.11 Garbage DisposalComments: Inspected

13.12 DishwasherComments: Inspected

Please note, the range/oven is anolder model and may requirereplacement in the future.

13.9 (1)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 41 of 46

(1) The dishwasher did notappear to have an anti-siphon deviceinstalled in the drain line. Anti-siphondevices are installed to preventwastewater from the dishwasher frombeing siphoned back into thedishwasher and contaminating itscontents. The Inspector recommendsan anti-siphon device be installed by aqualified technician.

13.12 (1)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 42 of 46

The Kitchen and built-in appliances of the home were inspected and reported on with the above information. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates tothe comments in this inspection report.

(2) Please note, the dishwasheris an older model and may requirereplacement in the future.

13.12 (2)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 43 of 46

14. Laundry RoomIn addition to those items typically inspected as part of the interior, inspection of the laundry room includes examination of the following:dryerconnections and venting; room ventilation; and provision of proper clothes washer waste pipe.

Styles & Materials

Dryer Power:Both available

Dryer Vent:Smooth-bore metal

Dryer 240-volt electrical receptacle:Installed

Dryer Gas Supply:Natural gas

Items

14.0 FloorsComments: Inspected

14.1 WallsComments: Inspected

14.2 CeilingsComments: Inspected

14.3 DoorsComments: Inspected

14.4 WindowsComments: Inspected

14.5 Receptacles, Switches, ConnectionsComments: Inspected

14.6 LightingComments: Inspected

14.7 CabinetsComments: Inspected

14.8 Dryer VentingComments: Inspected

14.9 WasherComments: Inspected

14.10 DryerComments: Inspected

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 44 of 46

The laundry room of the home was inspected and reported on with the above information. Any repair items mentioned in this report should beconsidered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to thecomments in this inspection report.

Please note, the dryer is an oldermodel and may require replacement inthe future.

14.10 (1)

NW WASHINGTON HOME INSPECTIONS LLC Baker

1035 Chestnut St. Page 45 of 46

INVOICE

NW WASHINGTON HOME INSPECTIONS LLC Bainbridge Island, WA

Inspected By: Carl Liberman

Inspection Date: 8/4/2017Report ID: 170804 A / ICN 10236AR002

Customer Info: Inspection Property:

Mr. Tim Baker

Customer's Real Estate Professional:Chris EllisFaira.com

1035 Chestnut St.Bremerton Washington 98310

Inspection Fee:Service Price Amount Sub-TotalHeated Sq Ft 1,001 - 2,000 395.00 1 395.00

Tax $0.00Total Price $395.00

Payment Method: CheckPayment Status: Invoice sent to AgentNote:

NW WASHINGTON HOME INSPECTIONS LLC Baker