SP-SO500TL-V2.0-EN

SolarOcean PV Grid-tied Inverter SolarOcean 500TL

Product Manual

TM

Samil PowerExpert for PV Grid-tied Inverters

Page 2: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters
Page 3: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Copyright StatementThe copyright of this User Manual belongs to Samil Power Co., Ltd. (hereinafter referred to as Samil Power). Any unit or individual shall neither extract or copy part or all of the content in this User Manual, nor transmit this part or all of the content in this User Manual in any form (including data and prints) without permission of our company in written form. All rights are reserved by Samil Power.

The Samil Power reserves the Final Interpretation Right of this User Manual. Any change of the product parameters shall be based on the latest data of our company without notice.

01

Page 4: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Thank you for choosing the PV Grid-connected inverter of Samil Power.

Since the PV Grid-connected inverter of Samil Power is released on the market both at home and abroad, it has been widely recognized and used by the majority. The newly released PV Grid-connected inverter of SolarOcean series is characterized by leading edge efficiency, wide range MPPT, advanced DSP digital control techniques, and high-degree protection making the PV system operate more reliable, user-friendly and easy to maintain. We believe that the new series of products will be used more widely in various industrial, commercial and civil fields. We hereby express our heartfelt thanks to the mass users of Samil Power, as well as those who concern about the products of Samil Power.

To help the users know and use the SolarOcean series PV Grid-connected inverter of Samil Power better, this User Manual gives a detailed description of the function, installation, operation, maintenance etc. of SolarOcean 500TL Grid-connected inverter, which is essential in installing, debugging and maintaining the PV Grid-connected power generation system.

Inadequacies are inevitable in this User Manual, and thanks for your understanding. If you find any inadequacy in using this User Manual, please contact our customer service personnels for technology department. We will treasure any suggestion of you. Thanks for your help. Suggestions in any time at anywhere are welcome.

02

Page 5: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Contents1 ABOUT THIS USER MANUAL..................................................................................05 1.1 CONTENT INTRODUCTION.............................................................................................................05

1.2 TARGET READER............................................................................................................................05

1.3 IMPORTANT INFORMATION............................................................................................................05

1.4 SYMBOL DESCRIPTION..................................................................................................................05

2 SAFETY NOTICE.....................................................................................................07 2.1 CORRECT METHOD OF INSTALLATION..........................................................................................07

2.2 OPERATOR.....................................................................................................................................08

2.3 INSPECTION AND STORAGE...........................................................................................................08

2.4 TRANSPORTATION..... . ...................................................................................................................08

2.5 INSTALLATION................................................................................................................................09

2.6 MAINTENANCE AND REPAIR...........................................................................................................09

2.7 PROTECTION DEGREE / EMC / NOISE LEVEL OF INVERTER.........................................................09

3 PRODUCT DESCRIPTION........................................................................................10 3.1 PV POWER GENERATION SYSTEM.................................................................................................10

3.2 ELECTRIACL PRINCIPLES OF INVERTER..... . .................................................................................10

3.3 LAYOUT OF KEY COMPONENTS...... ...............................................................................................11

3.3.1 LAYOUT OF INTERNAL COMPONENTS.. . . ..............................................................................11

3.3.2 LAYOUT OF EXTERNAL COMPONENTS.................................................................................12

3.3.3 LED INDICATOR.....................................................................................................................13

3.3.4 GRID SWITCH/ PV SWITCH....................................................................................................13

3.3.5 EMERGENCY STOP BUTTON.................................................................................................13

3.4 OPERATIONAL MODE.....................................................................................................................14

3.4.1 STANDBY MODE.....................................................................................................................14

3.4.2 GRID-CONNECTED POWER GENERATION MODE..................................................................14

3.4.3 FAULT MODE..........................................................................................................................14

3.5 FUNCTION PROTECTION................................................................................................................15

3.6 STORAGE........................................................................................................................................15

3.7 DIMENSIONS...................................................................................................................................16

3.8 PRODUCT NAMEPLATE...................................................................................................................16

3.9 PACKAGE INFORMATION................................................................................................................17

4 PRODUCTS INSTALLATION....................................................................................18 4.1 INSTALLATION CONDITION REQUIREMENTS.................................................................................18

4.2 TOOLS AND SPARE PARTS REQUIRED FOR WHOLE MACHINE INSTALLATION............................19

4.3 MECHANICAL INSTALLATION....... . .................................................................................................19

4.3.1 TRANSPORTATION OF PACKAGED WHOLE MACHINE..........................................................19

4.3.2 MOVEMENT AND INSTALLATION OF BARE MACHINE............................................................21

4.4 ELECTRICAL INSTALLATION...........................................................................................................25

4.4.1 INPUT AND OUTPUT REQUIREMENTS...................................................................................25

03

Page 6: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

4.4.2 PREPARATION FOR ELECTRICAL WIRING.............................................................................26

4.4.3 DC SIDE WIRING....................................................................................................................27

4.4.4 AC SIDE WIRING....................................................................................................................28

4.5 COMMUNICATION...........................................................................................................................29

4.5.1 SINGLE-MACHINE CONTROL.................................................................................................29

4.5.2 MULTI-MACHINE CONTROL....................................................................................................30

4.6 INSTALLATION INSPECTION.....................................................................................................32

5 PILOT OPERATION.................................................................................................33 5.1 RELEVANT REQUIREMENTS...........................................................................................................33

5.2 INSPECTION....................................................................................................................................33

5.2.1 INVERTER INSPECTION...... . . .................................................................................................33

5.2.2 GRID VOLTAGE INSPECTION.................................................................................................33

5.2.3 DC SIDE VOLTAGE INSPECTION............................................................................................33

5.3 POWER-ON STEPS..........................................................................................................................33

5.4 PILOT OPERATION COMPLETION.. . ...............................................................................................34

5.5 POWER-OFF STEPS........................................................................................................................34

6 OPERATION GUIDE FOR MAN-MACHINE INTERFACE............................................35 6.1 ABOUT LCD.....................................................................................................................................35

6.2 TOUCH-SCREEN DISPLAY INFORMATION......................................................................................36

6.3 TOUCH-SCREEN OPERATION.........................................................................................................39

6.3.1 INITIAL OPERATION...............................................................................................................39

6.3.2 POWER ON/OFF OPERATION.................................................................................................40

6.3.3 OPERATING INFORMATION EXAMINATION............................................................................41

6.3.4 HISTORICAL INFORMATION EXAMINATION...........................................................................43

6.3.5 SAFETY SETTINGS.................................................................................................................45

6.3.6 TIME SETTINGS..... ................................................................................................................46

6.3.7 POWER LIMITATION...............................................................................................................47

7 ROUTINE MAINTENANCE..... ..................................................................................49 7.1 DUST SCREEN CHANGE.................................................................................................................49

7.2 REGULAR MAINTENANCE...............................................................................................................50

7.3 WASTE DISPOSAL...........................................................................................................................50

8 ANNEX..... . ..............................................................................................................51 8.1 PRODUCT LABEL............................................................................................................................51

8.2 PRODUCT SPECIFICATIONS...........................................................................................................51

8.2.1 APPLICABLE STANDARDS.. . . .................................................................................................51

8.2.2 ELECTRICAL CHARACTERISTICS (INPUT).............................................................................52

8.2.3 ELECTRICAL CHARACTERISTICS (OUTPUT).........................................................................52

8.2.4 OTHER PARAMETERS............................................................................................................53

8.3 QUALITY ASSURANCE..... ...............................................................................................................53

9 CONTACT SAMIL POWER.......................................................................................55

04

Page 7: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

1 About this User ManualThis chapter includes Content introduction, Target reader, Symbol description and other contents, which will help the reader know this Manual better.

1.1 Content introduction

This Manual is applicable for SolarOcean 500TL PV Grid-connected inverter (hereinafter referred to as inverter), and contains the following contents:

Safety noticesThe safety notices in operating and maintaining inverter.

Product descriptionThe function and role the inverter plays in PV Grid-connected power generation; the structure and principle of the inverter; and the function protection, operational mode, storage, packaging and other information of the inverter.

Product installationThe installation conditions and tools required for inverter installation; the mechanical and electrical installation of the inverter; communication connection installation and installation inspection etc..

Pilot operationThe inspection before trial operation of the inverter, the power-on and power-off procedures etc..

Touch-screen operationLCD information for displaying and operating setting method in touch screen interface of inverter, etc..

Routine maintenanceThe daily maintenance, change of waste proposal and other information of the inverter.

AnnexThe inverter label, technical data, quality assurance clauses and contact information of the inverter.

1.2 Target reader

This Manual is applicable for the personnel who install or perform other functions of this product, such as inverter installer, PV system designer and maintainer etc.. Acknowledge in the field of electricity, electrical wiring and mechanics is required upon the reader.

1.3 Important information

Please read this Manual carefully, or contact the local distributors before using the equipments. More product information can be found in our official website: www.samilpower.com.

1.4 Symbol description

To facilitate more efficient and safer installation and use of this inverter, this User Manual lists symbols possible to use. Please read carefully for better installation and use of this inverter.

05

About this User Manual

Page 8: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

This means important warning information.

This means important notices.

Please pay attention to the labels on the body of the inverter, which contains respects as follows:

Attention!Electric shock danger●There is high voltage in inverter. Do not touch any accessible conductive metal part before all powers are disconnected.

PE terminal Here is a protective earthing (PE) terminal. It shall be firmly grounded in installing earthing to ensure the safety of personnel.

Warning!Electric shock danger●This equipment contains AC and DC power terminals, maintenance shall be made at least 5 minutes after the power for each line is disconnected separately.●When the PV array is receiving sunlight, there is DC voltage in DC power terminal of this equipment. ●Electrical shock danger exists in the capacitor, the cover shall be moved at least 5 minutes later after all powers are disconnected.

06

About this User Manual

Page 9: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

2 Safety noticeAll installers and servers of inverter shall be trained, and be familiar with the general safety regulations to comply with in working on electrical equipments. The installers and servers shall also be familiar with local laws and regulations and safety requirements.

□ Please read this User Manual carefully before use. Any equipment damage attributed to failing to operate in accordance with this User Manual, our company is not be responsible for fulfilling quality assurance.

□ All operations of inverter shall be conducted by qualified electrical engineer.

□ In operation, please do not touch electrical parts other than when examining the equipment's operational information through the touch screen.

□ All electrical operations shall comply with the local electrical operation standards.

□ The quality assurance service of inverter excludes components maintenance. If required, please contact the designated local personnel for system installation and maintenance.

□ It shall be permitted by local power supply department to generate power with inverter connected grid, and the relevant operations shall be done by the professionals.

Warning: DC input voltage limit of inverter Please confirm before use that the DC input voltage is not higher than 880Vdc(for machine with electrolytic capacitor as its energy storage capacitor)/1000Vdc (for machine with film capacitor as its energy storage capacitor)●When DC input voltage of inverter inverter exceeds 880Vdc(for machine with electrolytic capacitor as its energy storage capacitor) /1000V (for machine with film capacitor as its energy storage capacitor), this equipment may be damaged.●The damage arising herefrom are beyond the quality assurance range.

2.1 Correct method of installation

Correct installation of inverter means compliance with all instructions of this User Manual, which involves the transportation, installation, circuit connection, and pilot operation. Any deviation from this User Manual shall be deemed as incorrect use of this equipment, for which Samil Power bears no responsibility to any damage attributed to it. The following items are also necessary for correct use:

● Pay attention to the safety instructions listed here and after;● Pay attention to SolarOcean 500TL User Manual instructions; ● Take into account technical data relating to this equipment.

2.2 Operator

Only the trained electrician who is approved by the power supply company can install and make pilot operation of this inverter. Before the installation and pilot operation of this inverter, all installers and servers shall be trained to be familiar with the general safety regulations to comply with in operating electrical equipments. The installers and servers shall also be familiar with local laws and regulations and safety requirements.

2.3 Inspection and storage

07

Safety notice

Page 10: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Before signing for acceptance of the inverter delivered by the transportation company, the user shall check the goods carefully. User shall compare the received article with the items listed in the Delivery Notice and notify the transportation company if any defect or damage is found. If potential defects or damages are found, the user shall contact the transportation company immediately, and require equipment identification. If you fail to notify the transportation company, in some cases, you may lose the right to claim for the damages and defects. If required, you can turn to local customer service of Samil Power.

Attention!This equipment can only be stored in encapsulation, hence it shall be dampproof and dustproof inside; if long-term storage is required, this inverter shall be placed in a dry environment to avoid water.

2.4 Transportation

The transportation method described in this Use Manual (see Section 4.3) is the only method permitted to transport this inverter. Please take into account the weight and the non-centered gravity center of this inverter. The gravity center has been marked on the package.

Warning!The inverter is very heavy, and its gravity center is not centered;Qualified hoisting equipments and personnel are essential in transportation of the inverter, it must be transported perpendicular to the horizontal plane, which is based on the mark of gravity center, the inverter's inclination shall be less than 10 degrees in comparison with the vertical;Transportation with upside down or in horizontal position is prohibited; failure of lifting and transporting inverter may result in serious personal injury or death, property loss and damage to the inverter.

In case the equipment is damaged, you shall take the following actions:

① This equipment is damaged in transportation:• The receiver shall make endeavors to reduce / limit the damage;• Preserve the site of damage till the transportation company or the transportation insurer has made decisions. In this case, the principal of Samil Power in the region where the damage occurs must be ensured to participate in work as an independent judge.• Record the actual condition into transportation documents, signed by the ship / rail or air transportation company.• Prepare a damaged equipment record and send this record to the transportation company and the supplying company. • Make the transportation company bear its responsibility in written form.

② The following damages must be reported to the police departments• Damages attributed to theft.• Damages attributed to fire.

③ Notification period for damages which can not be identified immediately (any damage which can only be found by opening the package) • Ship transportation company: 6 days.• Rail or air transportation company: 7 days.For damages found as above, the damage conditions report shall be delivered to the ship and rail or air transportation company.

08

Safety notice

Page 11: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

④ Transportation insuranceTransportation insurance of inverter is the insurance from delivery. No insurance shall be provided in the following conditions:

• Transportation of the inverter from one place to another after the initial transportation is finished.• Transportation within the company facilities.

2.5 Installation

SolarOcean 500TL, with the protection degree of IP20, is designed for indoor installation. In installing the inverter, the information in this User Manual, particularly "Products installation" in Chapter 4 shall be observed.

2.6 Maintenance and repair

Only when the inverter is safely disconnected with the PV components array and electricity grid, and at least 5 minutes after these powers are made sure not to be reconnected, the maintenance or repair of the inverter can be carried out.

Only qualified technical personnel who are familiar with the operation system can perform these operations.

Disconnect the circuit breakerOperate PV OFF button, to disconnect the inverter with the PV components, and then operate GRID OFF button, to disconnect the inverter with the AC electricity grid. Ensure the inverter will not be reconnected by accident. Use multimeter to test so as to ensure all equipments are disconnected with no voltage existing, as though the inverter is disconnected with the electricity / main power supply and PV components, it may carry high and dangerous voltage. Therefore, after it is disconnected with the electricity grid or PV components, please wait for at least 5 minutes to continue operation.

Maintenance and repairOnly personnel who is authorized by the Samil Power can repair or change the inverter. To ensure your safety, please use the genuine parts from the manufacturer. The non-genuine parts can not ensure the consistency of the electrical safety, EMC and machine safety with relevant certified standards.

Function and safety parametersPlease do not change the inverter's parameters without the authorization of local power supply company or the instruction of the Samil Power. Unauthorized change of functional safety parameters may cause damage or accident to the people or the inverter. In this case, the Samil Power will provide no quality assurance service. In addition, these unauthorized actions may result in revocation of inverter operation approval certificate.

2.7 Protection degree / EMC / noise level of inverter

Electromagnetic compatibility (EMC) refers to that one electrical equipment functions in a given electromagnetic environment without any trouble or error, and impose no unacceptable effect upon the environment.

Therefore, EMC represents the quality characters of electrical equipments:

● The inherent noise-immune character: immunity to internal electrical noise ● External noise immunity: immunity to electromagnetic noise in external system ● Noise emission level: influence of electromagnetic emission upon environment

The inverter may produce some noise and electromagnetic radiation. According to EMC radiation and noise level, the inverter is regarded as applicable to installation and operation in industrial environment. We therefore suggest that all personnel shall not linger around the equipment for long when it is operating.

2.8 Improtant notices

09

Safety notice

Page 12: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

PV Panel Inverter Grid

Attention 1: Static electricity may cause damage to the inverter● Irreversible damage may be caused to the inverter due to the electrostatic discharge of internal components!● Electrostatic protections norms must be observed in operating the inverter!Attention 2: Use restrictionsThis inverter shall not be used to directly connect with life aid equipments or medical equipments!Attention 3: Tools notices Before this inverter is powered on, check if installation tools or other unnecessary articles are left inside the inverter or where the normal operation of this inverter is endangered.Attention 4: Maintenance noticesMaintenance must be done after this inverter's power is certainly disconnected, and all electrical components of this machine are totally discharged.

3 Product description3.1 PV power generation system

The main function of SolarOcean 500TL is to generate DC power through PV components array which receives solar energy, then invert the DC power into the sine wave AC power consistent with the grid requirement and input it into the grid. It is a key component of PV Grid-connected power generation system.

PV Grid-connected power generation system is mainly composed of solar energy components array, PV Grid-connected inverter, SolarArray Combiner, AC&DC power distribution cabinet, SolarPower Manager and SolarEnvi Monitor etc.. The PV Grid-connected power generation system is shown in Figure 3-1.

Figure 3-1 Schematic Diagram PV Grid-connected Power Generation System

3.2 Electriacl principles of inverter

The DC produced from solar PV array is also inverted into AC through inverter, and filtered into 270v voltage to output through a filter, then input into the power grid via an external step-up transformer. The main circuit of inverter is shown in Figure 3-2.

Figure 3-2 Main Circuit of inverter

10

Product description & Product description

Page 13: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

3.3 Layout of key components

3.3.1 Layout of internal components

The layout of key internal components for the inverter is shown in Figure 3-3-1.

3

2

1

4

5

6

Figure 3-3-1 The layout of key internal components

Table 3-3 The name of key internal components

No.

1

2

3

Components Name

PV- input terminal

PV+ Input Terminal

DC ari breaker

No.

4

5

6

Components Name

Filter

AC air breaker

AC output terminal

3.3.2 Layout of external components

As shown in Figure 3-3-2, the main external components of inverter cover LCD touch screen, PV ON/ PV OFF control button, PV POWER indicator light, GRID ON/ GRID OFF control button, GRID POWER indicator light, EMERGENCY STOP button and LED indicator light etc.

11

Product description

Page 14: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

1234

5

Figure 3-3-2 Appearance Description for inverter

Table 3-3-2 Description for component

No. Components Name Specification

1 Indicator Light(OPERATION /FAULT) Indicating the current operation state of the inverter.

2 LCD Touch Screen Showing operating information of inverter, and performing control commands and parameters settings etc.

3PV Control Button for Main

DC Breaker(PVON/ PV OFF); PV POWER indicator (PV POWER)

Used to electrically connect and disconnect the inverter with the PV components; Indicating the DC power operation state of the inverter.

4 Emergency Stop Button

5

AC Control Button for Main AC Breaker(GRID ON/ GRID OFF);

Grid Power Indicator light(GRID POWER)

Used for emergency stop button of the inverter.

Used to electrically connect and disconnect the inverter with the grid; Indicating the grid power operation state of the inverter.

3.3.3 LED indicator

With intelligent design adopted, SolarOcean 500TL PV Grid-connected inverter can start and stop work automatically everyday without human control. On the top of the inverted power, there are 2 LED lamps indicating main operating status of machines, and the current working status of the inverter is accessible through LED indicator.

12

Product description

Page 15: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

OPERATION FAULT

LED

OPERATION

FAULT

Meaning

Grid-connected operation indicator (it lights when the inverter work with grid connected)

Fault indicator (it lights when fault happens)

3.3.4 Control button

The DC air breaker and AC air breaker of inverter adopt intelligent button control method, you can easily control the state of inverter by the buttons. Meanwhile, state indicator light can indicate the valid state of breakers, it’s convenient for maintainance and safty of PV system. GRID ON/OFF button can connect/disconnect the AC side of inverter with the grid, while PV ON/OFF can connect/ disconnect the DC side of inverter with the PV components. When using the control button in case of load, components of inverter will bear a great pressure. Frequent use of control button may cause stress damage to some individual parts, and incorrect use of control button may cause damage to inverter.

PV POWERPV ON PV OFF

Figure 3-3-3 Indicator light (LED)

Table 3-3-3 LED working condition

Figure 3-3-4-1

Table 3-3-4-1

GRID POWERGRID ON GRID OFF

Figure 3-3-4-2

Button

PV ON

PV OFF

PV POWER

Meaning

Control button for PV power on

Control button for PV power off

Indicator light for the status of PV power

13

Product description

Page 16: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Table 3-3-4-2

Button

GRID ON

GRID OFF

GRID POWER

Meaning

Control button for grid power on

Control button for grid power off

Indicator light for the status of grid power

3.3.5 Emergency Stop Button

Attention!The emergency button can only be used under emergency.

E M

E R G E N C Y POTS

Figure 3-3-5 Emergency Stop Button

Emergency Stop Button can disconnect the inverter with grid and PV power generator, thus place the inverter in safety. Through pressing the Emergency Stop Button, the equipment will be locked at "off" status, and it will not recover to operate until the emergency button is released.

3.4 Operational mode

SolarOcean 500TL PV Grid-connected inverter has a lot of operational mode.

3.4.1 Standby modeThe standby mode refers to the first power-on of the inverter for work after installation, but not yet generating power in connected grid. Under this mode, it continuously detects whether the PV array has enough power to generate in connected grid. When power generation conditions are satisfied, the inverter will change from standby mode into Grid-connected power generation mode.

3.4.2 Grid-connected power generation mode

Brief introduction to grid connected process of the inverter

① The DC input terminal of the inverter is connected with the DC output of the PV array, and AC output terminal of inverter is connected with the grid;② Close the AC and DC circuit breaker, the inverter enters "waiting" status;③ When the DC input voltage exceeds 450V, the inverter prepares to send AC energy to grid;④ The inverter will self-inspect before tie grid to confirm that the current status satisfy all conditions required for grid connected work, then connect with the grid and generate power.

14

Product description

Page 17: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

The inverter is automatic, and the system will inspect whether the DC input and DC grid satisfy the Grid-connected power generation conditions. When all met, it will enter the power generation mode. It will disconnect with the grid immediately and launch protection program.

Under this mode, inverter will input the DC from PV array into grid. Meanwhile, the inverted power is maximizing the output energy of PV array in the manner of maximum power point tracking (MPPT). Therefore, Grid-connected power generation mode is also called MPPT mode.

Attention!When the ambient temperature is too high, it is also a normal operational mode for the inverter to reduce output power. However, if this phenomenon occurs too often, you need to check the cooling surface of the inverter, or consider installing the inverter at a place of better ventilation. If the fan of the inverter is too dirty, please clean it, and while if the power reduction is caused by the internal electrical default, please turn to professional service.

3.4.3 Fault mode

When faults occur at the PV power generation system, the inverted power will disconnect the AC side contactor immediately, and enter protection program and fault state to protect the system safety. At that moment, the inverter will keep monitor whether the fault is eliminated. If not, the fault status will be kept, and while if so, it will enter Grid-connected power generation mode again.

3.5 Function protection

[Anti-islanding protection]When local grid is cut off due to default or equipment maintenance, SolarOcean 100 / SolarOcean 100TL inverter will cut the connection with the grid physically to protect the operators who work on the grid. The inverter is in full compliance with relevant state standards.

[Lightening protection]Lightening protection module is set inside the inverter, it has the function of lightning over-voltage protection at the DC/AC terminal to avoid lightning strike of the inverter.

[More protections]Inverter provides more protections to ensure safe work under any environment.

The protections includes but not limited to:

● Protection of over-voltage and under voltage ● Protection of over-frequency and under frequency● Protection of over-current and Over-load● Short circuit protection● Prevent reverse discharge protection● Protection of preventing polarity reverse connect● Over-temperature protection● DSP fault protection

15

Product description

Page 18: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

3.6 Storage

After product acceptance is finished, if storage other than on-site installation and operation is required for the equipment, the following items shall be noticed;

● Recover the package to the original state;● Reserve the desiccant in the package;● Pay attention to ventilation and dampproof in storage, water logging is prohibited in the storage environment;● Storage temperature: -20℃~70℃, storage humidity: 5~95%;● Note to deal with the ambient harsh environment, such as sudden cold, sudden fever, collision etc., to avoid damages to the inverter;● Inspect regularly, generally once a week, to inspect whether the package is intact to avoid pest and rodent. Any damaged one shall be replaced immediately;● Open the package to re-inspect if it has been stored for half a year or more, and package it again.

Attention!Storage without package is strictly prohibited; the inverter shall be stored in the environment without direct sunlight; please do not tilt or overlap the inverter cabinets. After a long-term storage, the inverter shall be inspected before use to confirm whether the equipment is intact. Ask some professionals to test, and then install when necessary.

3.7 Dimensions

Long/ Wide/ High of inverter are signified by B /C /A respectively. B=2600mm, C=850mm, A= 2180mm.

CB

A

16

Product description

Page 19: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

3.8 Product nameplate

Product nameplate is pasted on side of inverter, as shown in Figure 3-8, it provides the type and some other important specification information of inverter. Please do not alter the information on the nameplate without permission. Samil Power will not provide standard quality assurance for inverter with illegible nameplate, altered parameters and dismantled nameplate.

PV GRID-CONNECTED INVERTERMODEL:SolarOcean 500TL

Address:No.66 Taihangshan Road,Suyu Economic Development Zone, Suqian, Jiangsu Province, China

Http://www.samilpower.com Made in ChinaSAMIL POWER CO., LTD.

DC Operating Voltage Range 450-880 Vdc NominalAC Voltage 270 Vac

MPPT Voltage Range 450-820 Vdc NominalAC Current 1070 A

DC Max.Input Current 1200 A AC Opeating Frequency 50Hz

Operating Temp.Range -20to+50℃ AC Nominal power 500 KW

Max.Efficiency 98.6% Max.AC Power 550 KW

Power Factor 0.99 Communication Port RS485/RS232

Protective Class Class Ⅰ Ingress Protection IP20

ENEL2010 RD1663

PV GRID-CONNECTED INVERTERMODEL:SolarOcean 500TL

Address:No.66 Taihangshan Road,Suyu Economic Development Zone, Suqian, Jiangsu Province, China

Http://www.samilpower.com Made in ChinaSAMIL POWER CO., LTD.

DC Operating Voltage Range 450-1000 Vdc NominalAC Voltage 270 Vac

MPPT Voltage Range 450-820 Vdc NominalAC Current 1070 A

DC Max.Input Current 1200 A AC Opeating Frequency 50Hz

Operating Temp.Range -20to+50℃ AC Nominal power 500 KW

Max.Efficiency 98.6% Max.AC Power 550 KW

Power Factor 0.99 Communication Port RS485/RS232

Protective Class Class Ⅰ Ingress Protection IP20

ENEL2010 RD1663

Figure 3-8-1 Equipment Nameplate (for machine with electrolytic capacitor as its energy storage capacitor)

Figure 3-8-2 Equipment Nameplate (for machine with film capacitor as its energy storage capacitor)

Note:Equipment nameplates respectively direct at machine with electrolytic capacitor and film capacitor as its energy storage capacitor)

Table 3-8 Nameplate Information

No.

A

B

C

D

Information

LOGO and product name of Samil Power Co., Ltd.

Product's parameter data

Identification of product certification agency

Company name, address, and place of origin

17

Product description

Page 20: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

3.9 Package information

Table 3-9 Product Package Information

No.

1

2

3

4

5

Qty. Specification UnitName

DC cabinet

AC cabinet

User Manual

Quality certificate

CD disk of monitoring software

Including a key of DC cabinet

Including a key of AC cabinet

unit

unit

pc

pc

pc

1

1

1

1

1

4 Products installation 4.1 Installation condition requirements

To ensure normal operation of the machine, the installation environment is required as follows:

● The ingress protection of inverter is IP20. Moreover, as this product is an electronic equipment, it shall not be placed in humid environment;● Install indoors and avoid sunlight and rain;● Ventilation around the machine shall be good;● The installation environment shall be clean;● As some noise will be produced in operation, this equipment shall be installed far from residential quarters; ● The installation ground shall not shake, and the support face shall satisfy load requirements of the inverter;● The installation position shall be convenient for operating inverter;● Ambient temperature range: –20°C~50°C;● Appropriate space shall be reserved for the machine to ensure ventilation and cooling.

We suggest inverter is installed in the distribution room. The floor, wall clearance, ventilation equipment and precaution should be designed by professional personnel and satisfy the following requirements.

[Foundation requirement]Inverter is required to install on even ground with fire-retardant material as the surface or channel steel support structure, and sag or tilt ground is prohibited. The foundation shall be solid, safe and reliable. The foundation shall be capable of bearing the load of the inverter. Its load bearing ability shall be concerned throughout the installation place selection.

[Clearance space]During installation of the inverter, appropriate space shall be left to the wall or other equipments, in order to satisfy the requirements on narrowest maintenance channel, emergency access and ventilation.

In front of the installation place of inverter, a space of 1.5m or more shall be ensured, the back 0.6m or more, the top 0.6m or more to ensure easy installation, cooling and maintenance.

[Cable trench]The cable connection of inverter adopts bottom inlet and bottom outlet. Cable trenches are recommended.

The cable trenches are often designed and constructed by the construction side based on relevant standards, with the equipment weight and dimensions required to be considered. Good electrical connection is needed

18

Product description & Products installation

Page 21: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

between different cable trenches and GND terminals.

[Wiring specification]Cables in the inverter can be classified into either power cables or data cables.In cabling, the power cable shall be kept far away from, and the cable shall be kept in right angle at cross. The cable shall be as short as possible, and an appropriate distance shall be kept to the power cable. We suggest the DC PV+ and PV- insulation resistance is more than 1MΩ.The power cable and data access shall be placed in different cable trenches respectively to avoid lengthy routing between the power cable and other cables, so as to reduce the electromagnetic interruption caused by sudden change of the output voltage. The distance among the power cable and data access shall be more than 0.2m. When the cables are crossed, the cross angle shall be 90 degrees, while the distance can be reduced appropriately.

[Ventilation requirement]In operation, inverter will produce a lot of heat. When ambient temperature is too high, the electrical property of the equipment may be affected, the equipment may even be damaged. Therefore, the heat release shall be fully considered in designing the control room to ensure operation of the equipment in high efficiency.

[Ventilation environment]To satisfy the ventilation requirement of inverter, its installation environment shall meet the following conditions:

※ Inverter shall be prevented from being installed in the place of poor ventilation condition and insufficient air flow;※ The air inlet shall have enough air supplementation.

[Ventilation equipment] To ensure safe and reliable operation of the equipment, the ambient temperature must be within the permission range –20°C~50°C, therefore, appropriate ventilation devices must be equipped with to release the heat generated by the equipment. We suggest the ventilation rate is more than 11000m³/h per inverter.

● There must be ventilation equipment inside the distribution room to ensure release of the waste heat generated by the inverter from the equipment, and allow for maximum amment temperature. This can be realized from installation of exhaust devices;● Another fan can be added at the air duct outlet to exhaust the air out and ensure balanced pressure;● The direction of the air outlet shall be selected according to the local actual wind direction;● Pay attention to the dustproof measures and waterproof design at the air inlet and outlet;● If more air ducts are required, its dimensions shall be designed by the professionals according to the air output amount.

[Other protections]With IP20 of protection level, inverter is appropriate to be installed in dry and clean environment. Meanwhile, water leakage of the house shall be prevented, as it may damage the inverter. According to EMC requirement and noise level, the inverter shall be installed in industrial environment.

4.2 Tools and spare parts required for whole machine installation

Tools and spare parts required for installation is as follows:

● Hoisting crane, forklift or fork lift truck (with the capacity for bearing the weight of the inverter)● Torque wrench● Screwdriver● Wire stripper● Terminal crimping machine● Heat dryer● Megger and multimeter

4.3 Mechanical installation

19

Products installation

Page 22: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Inspect whether all materials are complete based on the packing list in the cabinet:

4.3.1 Transportation of packaged whole machine

[Relevant notices]This inverter adopts whole operation, and the user can hoist it from the bottom with a forklift, or move it with a hoisting crane or crane.

Notice 1: The inverter is integrated and can not be dissembled either in transportation or installation. Any fault attributed to modification unauthorized by the Samil Power is beyond the quality assurance.Notice 2: In movement, tilt, violent shake or sudden force upon the inverter shall be prevented, such as sudden down of lifting.Notice 3: Please read carefully the labeled parameters to select an appropriate transportation means and storage place.

We suggest the user to choose forklift to move the inverter if possible.

Attention!Before the inverter is moved to the designated place, we suggest to lay the DC input cable and AC main power supply cable. As these cables are relatively thick, they are hard to be cabled after the inverter is installed.

To keep the equipment in a better protective status, please adopt transportation with package as much as possible, and comply with the labels printed on the package in transportation.

Inverters whose packages are not demolished can be moved with forklift, hoisting crane or crane. In moving, attention shall be paid to the weight painted on the package to ensure enough load capacity of the devices. As the gravity center of the equipment locates at the lower place symmetrical in front and back and left and right, the support point or hoisting point shall be arranged reasonably in transportation.

The forklift transportation is the standard one. The gravity center of the cabinet in transportation locates between two forks of the forklift. The big-size inverter may block driver's sight, and it shall be treated with cooperation of the aid personnel. The moving method can be found in Figure 4-3-1-1.

20

Products installation

Page 23: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Figure 4-3-1-1 Forklift Transportation (With Package)

In hoisting transportation, we recommend flexible strap with a buckle at either end, and make the strap load evenly. It is shown in Figure 4-3-1-2

Figure 4-3-1-2 Hoisting Transportation (With Package)

4.3.2 Movement and installation of bare machine

[Demolish the package of inverter]Please demolish the packaged cabinet of the equipment according to the following procedures:

Procedure 1: Demolish the wood side and roof of the packaged cabinet

Figure 4-3-2-1

21

Products installation

Page 24: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

[Movement and installation of bear machine]The bear machine without package is mainly used around the final installation position in general. The inverter with demolished package can be moved with forklift, hoisting crane, slide rail or crane.

If the package demolished place is far from the final installation place, it can be transported with forklift containing wood pallet. It is shown in Figure 4-3-2-2

Figure 4-3-2-2 Forklift Transportation (Without Package)

When moving the inverter with forklift, the cover lids in the front and back of the pedestal shall be removed first, and make the gravity center locate between two forks, then hoist the inverter. Lay the lead rails and push the inverter to the final installation place as shown in Figure 4-3-2-3

Figure 4-3-2-3 Moving Inverter with Forklift

After the DC cabinet and AC cabinet of inverter are moved and combined to the designated position, use the accessory bolts to fasten the DC cabinet and AC cabinet of inverter on the channel steel or the ground through the middle holes on the pedestal.

Warning!We must act slowly and gently when transporting the inverter with forklift to avoid violent vibration of the inverter or collision with other objects.

22

Products installation

Page 25: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Procedure 4: When the whole inverter is installed completely, open the back board of inverter, then connect and fix busbar copper platoon and communication wires, finally close the back board. Specific procedures of combining installation, please refer to below parts.

Combining installation for DC cabinet and AC cabinet:

1)Installation of electricity copper row. Open back door of inverter, install the busbar copper 59 into the location as shown in Figure 4-3-2-4. Using 24 pieces of M10*30 bolt, match up M10 nuts, flat gasket, split washer. .

Figure 4-3-2-4

2)Open front door, install the copper row 60 into the location as shown in Figure 4-3-2-5. Using 8 pieces of M8*30 bolt.

Figure 4-3-2-5

23

Products installation

Page 26: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

3)Open the front and back doors, install 2 pieces of combiner component into the locations respectively as shown in Figure 4-3-2-6. Using 16 pieces of M8*20 bolt.

Figure 4-3-2-6

4) Signal lines connection as shown in Figure 4-3-2-7. By signal line combiner, connect the signal lines according to the wire marks correspondingly.

Signal lines combiner

Figure 4-3-2-7

24

Products installation

Install Combiner

Install Combiner

Page 27: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

4.4 Electrical installation

4.4.1 Input and output requirements

Warning!There is a danger of electrical shock of high voltage in inverter's operation, only electricians of professional skills can operate. All connections with this equipment shall be done under non-voltage state.The inverter may be damaged if input or output terminal is incorrectly plugged!Failure of acting upon this information may cause death, serious personnel injury or significant property loss.

a) PV arrayThe anode and cathode open-circuit voltage of the PV array shall not exceed 880V/1000V(for machine with film capacitor as its energy storage capacitor) otherwise, the equipment will be in over-voltage protection state, and can not work normally. The power of SolarOcean 500TL Grid-connected inverter PV array can be 570kW.

SolarOcean 500TLModel

PV Array Power Limit

PV Array Open-circuit Voltage Limit

570 kW

880 V / 1000V

b) Three-phase gridInverter will continuously inspect whether the grid satisfy the grid connected conditions. The following is the grid limit for satisfaction of CQC Grid connected Conditions (requirements in different countries may vary, and please refer to local grid connected regulations for details), and the grid is three-phase grid. Meanwhile, it shall be permitted by local power supply department before install Grid-connected inverted power.

SolarOcean 500TLModel

Grid Voltage Limit

Grid Frequency Limit

270±7%V

50±0.5Hz

c) Cable requirements

Cable (Cu)

Model

Cable Diameter Requirements (mm2)

PV Array PV+ At least 4*95 mm² or 8*50mm²

SolarOcean 500TL

PV Array PV-

Grid Phase A At least 4*95 mm²

At least 4*95 mm² or 8*50mm²

Grid Phase B

Grid Phase C At least 4*95 mm²

At least 4*95 mm²

Earth Wire At least 70 mm²

25

Products installation

Page 28: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

4.4.2 Preparation for electrical wiring

Before wiring, the user need to open the front door of inverter, and the specific procedures are as follows:

Procedure 1: Cut off the circuit breaker at AC&DC sides, push the PV OFF and GRID OFF button.Procedure 2: Open the front door. The unlock schema is shown in Figure 4-4-2-1.

① ② ③ ④ ⑤

Figure 4-4-2-1 Open Machine's Front Door

Remove the protective coverTo improve safety and reduce noise, two protective covers are equipped in inverter. The protective plate shall be removed in electrical installation during the process of wiring.Note: It is better to wire all cables through the wiring plate at the bottom of the inverter into connecting terminals.

When closing the door, please note Lift gently the door brakes in the lower part of the left and right door, and then close the door. Brute force shall not be used to close the door to prevent damage. It is shown in Figure 4-4-2-2.

Figure 4-4-2-2

4.4.3 DC side wiring

Warning!The open-circuit voltage of PV array shall not exceed 880V/1000V (for machine with film capacitor as its energy storage capacitor), otherwise the equipment may be damaged! When connecting, use a multimeter to measure the open-circuit voltage of the PV array.

Warning!The anode and cathode of the PV array shall not be connected in reverse. A multimeter shall be used to determine the polarity first, and then connect into the corresponding input ends of the inverter.

26

Products installation

Page 29: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Cut off the distribution circuit breaker at the DC side, and ensure that no voltage on the wire at DC side.

d) Measure the open-circuit voltage of the PV array with a multimeter to ensure that the open-circuit voltage is not higher than 880V/1000V(for machine with film capacitor as its energy storage capacitor).e) Determine the anode and cathode with a multimeter.f) Connect the anode of the PV array to the "PV+" of DC input.g) Connect the cathode of the PV array to the "PV-" of DC input.h) Please be sure that all wirings are fastened.

We reserve four wiring terminals for users at the DC side, as shown in Figure 4-4-3. In wiring, the user need to wire at least 4 input lines of 95mm2, or at least 8 input lines of 50 mm2.

Figure 4-4-3 DC Input Wiring

4.4.4 AC side wiring

Warning! When connecting the AC grid, cut off the circuit breaker at the AC side to ensure that the AC wire connecting to terminals has no power.

Connect AC grid:

i) Cut off the circuit breaker at AC side, to ensure that the AC wire connecting to terminals has no power. Confirm it with a multimeter.j) Connect "L1" of AC output with "L1" of the grid.k) Connect "L2" of AC output with "L2" of the grid.l) Connect "L3" of AC output with "L3" of the grid.

Ensure that the wiring phase sequence at AC side is in consistent with the phase sequence at grid side.

m) Please confirm that the wiring is fastened.

27

Products installation

Page 30: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Figure 4-4-4 AC Output Wiring

Earth wireThe earthing terminals in inverter must be connected reliably with the earth wire of AC distribution cabinet.

4.5 Communication

The inverter of SolarOcean series has various communication methods. When the user needs to monitor the operating status of PV power generation system, we provide single-machine and multi-machine control programs, and diversified communication interfaces for customer's selection.

4.5.1 Single-machine control

● RS485 communicationThe inverter is connected with the monitor for communication through the RS232/RS485 communication line, which monitors in real time the single inverter via monitor software SolarNavigator-S, as shown in Figure 4-5-1-1.

The preparation procedure of RS232/RS485 communication line: select RJ11 modular plug, RS232/RS485 adaptor, super-category 5 shielded twisted-pair and wire them as shown in Figure 4-5-1-2. If the PC does not contain nine-pin RS232 communication port, you can connect another RS232/USB adaptor, and connect it with the PC monitor for communication via USB interface. The RS485 line should be less than 1000m, the RS232 line should be less than 12m.

RS485/RS232 PC

USB/RS232 RS232/RS485

Figure 4-5-1-1

Figure 4-5-1-2 RS485/RS232 Adaptor / RS232/USB Adaptor

28

Products installation

Page 31: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

● CAN communicationThe inverter can also be connected with the monitor through CAN/USB, and the single-machine monitoring software monitor SolarNavigator-S can monitor in real time the single inverter as shown in Figure 4-5-1-3 and Figure 4-5-1-4. We suggest the CAN line adopt the normal twisted-pair shielded wire, 2core STP-120Ω, across section area is about 0.5~1.5mm2, the CAN line should be less than 1000m.

CAN/USB PCFigure 4-5-1-3

Figure 4-5-1-4

● Internet monitoring A single inverter can connect with the monitor of SolarPower Manager System (SPM) through RS485 line, SPM can connect with the Internet for communication via connecting router. Therefore, you can monitor in real time the inverter's operating status and the power generation system's environment status at any place of the world, as shown in Figure 4-5-1-5 and Figure 4-5-1-6. We suggest the RS485 line adopt the normal twisted-pair shielded wire, 4core 120Ω, across section area is about 0.5~1.5mm2, the shielded wire should connect to ground, the both ends use the RJ11 modular plug to parallel connect. TheRS485 line should be less than 1000m, the line between SPM and router should be less the 80m.

SPM

Router Internet

SPM Router

1

1

2

2

3

3

44

Figure 4-5-1-5

Figure 4-5-1-6

29

Products installation

Page 32: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

4.5.2 Multi-machine control

●RS485 communicationThe inverter, through RS485 tandem, is connected with the PC for communication through RS485/RS232 adaptor. Inside the PC, a multi-machine monitoring software SolarNavigator-M independently developed by the Samil Power is monitoring in real time the operating status of all inverters, as shown in Figure 4-5-2-1 and Figure 4-5-2-2. The both ends of RS485 line use the RJ11 modular plug to parallel connect. TheRS485 line should be less than 1000m.

PCRS485/RS232

Figure 4-5-2-1 RS485 Multi-machine Communication

USB/RS232 RS232/RS485

Figure 4-5-2-2 RS485/RS232 Adaptor / RS232/USB Adaptor

● CAN CommunicationThe inverter can also cascade the all inverters through CAN communication interface (We suggest theCAN line adopt the normal twisted-pair shielded wire, 2core STP-120Ω, across section area is about 0.5~1.5mm2, the both ends use the RJ11 modular plug to parallel connect. The CAN line should be less than 1000m), and finally connects with the PC for communication through CAN/USB adaptor. Inside the PC, a multi-machine monitoring software SolarNavigator-M independently developed by the Samil Power is monitoring in real time the operating status of all inverters, as shown in Figure 4-5-2-3 and Figure 4-5-2-4.

CAN/USB PCFigure 4-5-2-3

Figure 4-5-2-4

● Internet monitoring Multiple inverters can, through tandem of RS485 communication line, connect with the monitor of SolarPower Manager System(SPM), which can connect with the Internet for communication via connecting router. Therefore, you can monitor in real time the inverter's operating status and the power generation system's environment status at any place of the world, as shown in Figure 4-5-2-5. The both ends of RS485 line use the RJ11 modular plug to parallel connect. TheRS485 line should be less than 1000m.

30

Products installation

Page 33: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

SPM

InternetRouter

Figure 4-5-2-5 SolarPower Manager Monitoring

4.6 Installation inspection

Before the inverter is put into operation, it shall be inspected for installation. Two working personnels or more shall inspect to ensure correct installation of all installation according to the following table.

Table 4-6 Installation Inspection List

Mechanical Installation Items Inspection

Electrical Installation Inspection

□ Inverter's bottom is fixed, and the support is stable and reliable

No deformation and damage to inverter

□ The ambient temperature, humidity and ventilation of inverter satisfy requirements

Enough space is left around inverter

□ Complete and reliable sealing protection of cabinet

Smooth flow of cooling air

□ Grid voltage matching the rated input voltage of inverter

Complete and firm grounding of inverter

□ Correct connection of DC input anode and cathode, and tightening torque meeting requirements

Correct phase sequence of grid connection, and tightening torque meeting requirements

Other Inspections

□ No tools, spare parts, conductive dust generated from drilling or other matters left inside the cabinet

All useless conductive parts tied with insulating ribbon

□ No condensed humidity or icing inside the cabinet

□ Correct and legible mark of cable No.

□ Complete and reliable insulation shields, and legible and firm label of danger warnings

Correct connection of communication lines, and maintaining a certain distance to other cables

31

Products installation

Page 34: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

5 Pilot operation5.1 Relevant requirements

Before pilot operation, the installation conditions of the equipment shall be examined thoroughly, in particular whether voltages at DC and AC ends are consistent with inverter's requirements, and whether the polarity etc. are correct. Inspect if the system connection meets requirements in relevant standards or codes and if the system is grounding well.

Attentions!Before pilot operation, all switches at AC side and DC side shall ensure to be cut off.

5.2 Inspection

5.2.1 Inverter inspection

Before power on the inverter, please carry out inspections as the following procedures:

Procedure 1: Inspect inverter's installation and wiring conditions based on the Installation Inspection List in Table 4-6;Procedure 2: Ensure the AC&DC circuit breakers are cut off;Procedure 3: Ensure the emergency button is available and woks normally.

5.2.2 Grid voltage inspection

- Inspect whether the three phases of the inverter is correctively connected with the three phase sequence of the grid.- Inspect whether the line voltage and frequency are within the prescribed range, and record the value.- If possible, measure the phase THD (Total Harmonic Distortion), and inspect the curve. If distortion is serious, the inverter may fail to operate.

5.2.3 DC side voltage inspection

The DC side shall be connected to the inverter from the Combiner or DC distribution cabinet.- Ensure correct DC input polarity.- Measure and record the DC (open-circuit) voltage of each line. Voltages of each line shall be similar, and less than the permitted maximum DC voltage value.

5.3 Power-on steps

● First power-on

Operation procedures for the first power-on and operation of inverter are as follows:Procedure 1: Push “GRID ON” button, then the “GRID POWER” indicator light.lights up. Check the LCD display, if LCD displays any fault, please do troubleshooting; if there is no any fault, take up the second procedure.

32

Products installation & Pilot operation

Page 35: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Procedure 2: Push “PV ON” button, then the “PV POWER” indicator light lights up.Procedure 3: It takes about 10 seconds to automatically initialize the power inverted circuit and equipment. When the touch screen of the inverter shows "Starting" (initialization).Procedure 4: If the DC voltage is lower than the starting voltage (equal to 450Vdc), the touch screen keeps shown "Waiting" (in standby).Procedure 5: If the DC voltage is higher than the starting voltage (equal to 450Vdc), the inverter will inspect the grid connected conditions. When conditions are satisfied, it will automatically switch to "Normal state", at this moment, the "OPERATION" lamp will be on.

● Automatic power-onWhen the power-on conditions both at DC and AC sides are satisfied, the inverter will be powered on automatically. After the DC input or AC grid fault is demolished, the inverter will also be powered on automatically.

● Manual power-offIn the operation process of the inverter, we can power off the machine through the "OFF" button on the LCD panel. At this moment, the inverter stops work, and stops to transmit the electrical energy to grid.

Attention!1.After manual power-off on touch screen LCD, the machine should be powered on touch screen LCD, otherwise, the inverter is unable to power on. 2. It still maintains voltage after manual power-off.

5.4 Pilot operation completion

The following procedures shall be carried out after the inverter is grid connected.Procedure 1: Inspect whether abnormity exists in the inverter, such as excessive noise, excessive heat, abnormal smell or smoke.Procedure 2: Measure whether inverter connected grid voltage, current and THD are stable.Procedure 3: Operate LCD control panel and inspect whether it displays normally and accurately.By now, the pilot operation of inverter is fully completed, and we can enter the daily operational maintenance.

5.5 Power-off steps

Attention!After the inverter is completely powered off, the general PV switch at solar panel side and the Grid switch at grid side still maintain voltage. If operations are need, please be sure to cut off the outer power completely.

Exercise the OFF button on LCD operation panel;Press down PV OFF Button;Press down GRID OFF Button;Cut off the switch of DC distribution cabinet or header box;Cut off the switch of AC distribution cabinet.

Attention!It is normal that the inverter warns in power-off, and the power-off procedure can be continued.

33

Pilot operation

Page 36: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

6 Operation guide for man-machine interface6.1 About LCD

SAMILPOWER

Figure 6-1 Touch Screen

The user can examine the operation information of the inverter and set the operation parameters of the inverter on the touch screen. For easy operation, we set two main buttons on the host interface of the touch screen for

user's operation. These two buttons are "Host Interface" , and "Function List"

espectively, for which the logic structure distribution of display menu is shown in Table 6-1.

Home Function

Table 6-1 Logical Structure Distribution of Display Menu

Main Menu Sub-menu Level 1 Sub-menu Level 2 Sub-menu Level 3 Sub-menu Level 4

Host Interface

Function List

Real-time Data

Power Curve

Monthly Generation Histogram

Annual Generation Histogram

Generation HistogramOperating Status

Historical Data Historical errors

System Settings

Language Settings

Time Settings

Equipment Information

20-year Generation Histogram

ChineseEnglish

Parameter settings

34

Operation guide for man-machine interface

Page 37: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Continued:

Safety Settings

DK5940

RD1663

Golden sun

CEParameter settings

Power limits

Power-onPower-off

10%

30%

60%

100%

Power-on/power-off (password 1234)

Function List

6.2 Touch-screen display information Table 6-2-1 Touch-screen Main Display Information

Waiting…

Status Description

Checking… Checking grid, DC Input >450V and higher than the mains voltage peak value meanwhile

In power-on waiting, Waiting status DC Input < 450V

Normal

Fault Error status, it can recover automatically when error factor is demolished

Normal operating mode, the inverter ties grid to generate normally

Permanent Fault

Output power Output power

Permanent fault, it can only recover by power-on again

Total generation

Daily generation Generation of the very day

Total generation connected in grid

Operation status

Safety select Display the present grid connected safety standards

Inverted generation time period

Input power

Dc Voltage DC input voltage of PV array

Dc Current DC input current of PV array

Total input power display of PV array

Grid Voltage UV Grid voltage UV

Grid Voltage VW

Grid Voltage WU Grid voltage WU

Grid voltage VW

Grid Current U

Grid Current V Grid current V

Grid current U

Touch-screen Main Displayed Information (English)

35

Operation guide for man-machine interface

Page 38: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Continued:

Grid Current W

Inductor Current A Inductor 1A phase current

Grid current W

Inductor Current B

Inductor Current C Inductor 1C phase current

Inductor 1B phase current

Temp.Heatsink

Temp.Inductor A Temperature of inductor 1

Temperature of heatsink

Temp.Inductor B

RunTime Total run time of the inverter

Grid Frequency

Temperature of inductor 2

Grid frequency

Table 6-2-2 Error Information Display

EEPROM_Read_Failure

Fault Status DescriptionFault Information

EEPROM_Write_Failure EEPROM write failure

EEPROM read failure

AC_MainContactor_Failure

AC_SlaveContactor_Failure AC slave contactor failure (AC_SlaveContactor_ Fault occurs 3 times consecutively)

AC main contactoor failure (AC_MainContactor_Fault occurs 3 times consecutively)

DC_VoltHigh_Fault

DC_CurrHigh_Fault

DC voltage too high

DC_Insulation_Fault

GFDI_Fault

DC terminals insulation fault

DC current too high

AC_MainContactor_Fault

AC_SlaveContactor_Fault

DC main contactoor failure

DC side GFDI fault

AC_OverCurr_Fault

AC_Overload_Fault

AC over-current

AC_NoUtility_Fault

AC over-load

DC slave contactor failure

AC_GridPhaseSeque_Fault

AC terminal no utility fault

AC_WU_OverVolt_Fault

AC_WU_UnderVolt_Fault

AC WU line overvoltage

AC grid phase sequence fault

AC_VW_OverVolt_Fault AX VW line over-voltage

AC VW line under-voltage

AC WU line under-voltage

AC_VW_UnderVolt_Fault

36

Operation guide for man-machine interface

Page 39: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Continued:

AC_UV_UnderVolt_Fault

AC_OverFreq_Fault AC over-frequency

AC UV line under-voltage

AC_UnderFreq_Fault

AC_U_GridCurr_DcHigh_Fault AC U phase current too high

AC under-frequency

AC_V_GridCurr_DcHigh_Fault

AC_W_GridCurr_DcHigh_Fault

AC V phase current too high

Heatsink_LowTemp_Fault

Module1_OverTemp_Fault

Heat sink temperature too low

AC W phase current too high

Inductor_OverTemp_Fault

Transformer_OverTemp_Fault

Inductor temperature too high

Module 1 temperature too high

Inductor_LowTemp_Fault

Transformer_LowTemp_Fault

Inductor temperature too low

KeyEmergencyStop

Transformer temperature too low

Transformer temperature too high

LcdEmergencyStop

Emergency button fault

Fan_1_Fault_Warning

Fan_2_Fault_Warning

Fan 1 warning

LCD stop button fault

Fan_3_Fault_Warning

DC_VoltLow_Warning

Fan 3 warning

Fault_Feedback_Warning

DC voltage too low warning

Hardware fault no recovery

Fan 2 warning

DC_Inverse_Failure

IGBT_Module_A_Fault

Input DC inverse

IGBT_Module_B_Fault

IGBT_Module_C_Fault

IGBT B fault

Module1_OverTemp_Fault

IGBT C fault

IGBT A fault

Module2_OverTemp_Fault

IGBT 1 overtemperature

Module3_OverTemp_Fault

LVRT_Fault_Warning

IGBT 3 overtemperature

IGBT 2 overtemperature

LVRT fault

AC_UV_OverVolt_Fault AC UV line over-voltage

37

Operation guide for man-machine interface

Page 40: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

6.3 Touch-screen operation

6.3.1 Initial operation

I. Initialization interface: 30 seconds after LCD initialization, the screen will automatically switch to Language Selection page.

II. Language Selection page: select the required language, click , the screen will switch to Power-on Safety Selection page.

III. Power-on Safety Selection page: select the safety you need, click , it will switch to Host Interface. Click it will turn back to Language Selection page.

IV. Host Interface: it displays main operating parameters, including input parameter, output parameter, operating status and generation power etc., and shows the current date and time.

38

Operation guide for man-machine interface

Page 41: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Table 6-3-1 Specification of Remarks in Host Interface

1

SpecificationNo.

2 Three-phase line voltage and current

DC voltage and current

3

4 Communication status, time and date

Output power and working status

5 When the inverter is in normal operation status, the sun in the upper-left corner will flash.

6 Type for the current machine

6.3.2 Power on/off operation

I. Enter the Host Interface, click [Function], the following page will pop up.

II. Click [On/Off], the following page will pop up.

Note: When the inverter is operated for the first time, language setting and safety setting are required.When the inverter is powered on again, the page will not show Language Selection and Power-on Safety Selection pages.

39

Operation guide for man-machine interface

Page 42: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

III. Enter the password, and click [ENT], the following page will pop up.

IV. Click [ON] or [OFF] to selection power-on or power-off operation, and the following page will pop up.

V. Click [Yes] or [No] to selection power-on or power-off operation.

6.3.3 Operating information examination

40

Operation guide for man-machine interface

Page 43: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

I. Enter the Host Interface of the system, click [Function], and the following page will pop up.

II. Click [Running] and the following page will pop up. The default page is real-time data, which shows the current PV generation parameter and machine operating parameter etc.

III. The default page is real-time data, which shows the current PV generation parameter and machine operating parameter etc.

IV. Click [Power Curve], the picture in the left will pop up, showing the generation curve of the very day.

V. Click [Generation chart], the default page is monthly generation, and what the current page shows is the generation histogram of the very month. Click [Monthly Generation], [Yearly Generation] and [Generation for 20 years], the histograms of the very month, year and the past 20 years will be shown respectively.

[Monthly Generation]

41

Operation guide for man-machine interface

Page 44: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

[Yearly Generation]

[Generation for 20 years]

6.3.4 Historical information examination

Note:Different data types of the Operating Status can be switched via "Real-time Data", "Power Curve" and "Generation Histogram".

Real-time Data include grid voltage, grid frequency, grid current, DC input voltage, DC input current, temperature inside cabinet and total generation time etc.. The data are updated in real time, and the Generation Histogram per 12 minutes.

Note:Insert U disk into the USB interface on the back of inverter LCD screen, real-time data will be automatically deposited into U disk every two minutes, and inverter will automatically create a CSV format file in U disk monthly for real-time data storage.

42

Operation guide for man-machine interface

Page 45: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

II. Click [History information], and the following page will pop up. The default page is history data. The current page records the historical data in the past, including power, current, voltage etc...

III. Click [History fault], and the following page will pop up. The current page records the historical faults information in the past and the occurring time of the faults.

I. Enter the Host Interface of the system, click [Function], and the following page will pop up.

43

Operation guide for man-machine interface

Page 46: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Note: The system will keep the latest 100 faults information and their occurring times.

6.3.5 Safety settings

I. Enter the Host Interface of the system, click [Function], and the following page will pop up.

II. Click [Setup], the following page will pop up.

III. The current default page is Safety Setting, click the safety you need, and the following page will pop up.

IV. Eneter the password, click [OK] to choose the safety successfully; click [X] to cancel.

Note:1. This system is equipped with four safety regulations for customer's selection, including DK5940, RD1663, Golden sun, CE.; please choose the safety regulation adaptable to local conditions. If changes are required; and consult the customer service of the manufacture or local power grid company and other authorities.2. The safety selection will take effect only after powered on again after power-off operation.

44

Operation guide for man-machine interface

Page 47: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

6.3.6 Time settings

I. Enter the Host Interface of the system, click [Function], and the following page will pop up.

II. Click [Setup], and the following page will pop up.

III. Click [System Setting]. System setting includes Language Selection, Time Setting and Equipment Data. The current page is Language Selection. Click the language you need, the system language will be set as you like.

45

Operation guide for man-machine interface

Page 48: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

IV. Click [Time Setting] and the current page will pop up. Here we can set the system date and time. Click the date you want to set, and information input window will pop up.

V. Click [Equipment information)], and the following page will pop up. In this page, you can examine the corresponding equipment data.

Note:When the LCD displayed time and date are different from the local, you can modify them here.

6.3.7 Power limitation

I. Enter the Host Interface of the system, click [Function)], and the following page will pop up.

46

Operation guide for man-machine interface

Page 49: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

II. Click [Setup], the following page will pop up.

III. Click [Power Limitation], the following page will pop up.

IV. The current page provides 4 power limitation values for users. Click the [OK] after the value you need, then the following message box:

V. Enter the password. Click [OK] to complete the setting, [X] to cancel,.

47

Operation guide for man-machine interface

Page 50: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

7 Routine maintenance7.1 Dust screen change

When faults occur to the inverter, the inverter will automatically disconnect with the grid and send fault warning information. When the grid is cut due to faults or human work, the Grid-connected inverter system can disconnect with the grid in time to avoid islanding effect. After the grid is powered on again, the Grid-connected inverter can start automatically. Usually, the inverter requires no maintenance or calibration, but its dust screen shall be ensured to be free from dust and dirt. If there are a lot of dust and dirt on the dust screen, it shall be changed regularly as shown in Figure 7-1.

The change procedures of dust screen are as follows:Ⅰ. Open the front and back door of the inverter, we will see the dust screen on the back of th door.Ⅱ. Open the dustproof cover from the bottom the front and back dustproof cover.Ⅲ. Remove the old dust screen and install the clean one.Ⅳ. Install the dustproof cover to its original place and fasten it firmly.

Attention!To ensure normal operation of the system, wash the dust screen regularly.

Figure 7-1 Dust Screen on the Front Door of the Inverter

7.2 Regular maintenance

Inverter must be maintained regularly to ensure its normal operation and use life. The regular maintenance cycle and working contents we recommend are presented in Table 7-2.

Maintenance Item

Per month

Per month

Per month

Per month

Cycle

Read data in data collector

Clean heat sink of power module

Inspect whether there are dust, humidity or condensed vapour inside the cabinet

Inspect whether the connection is loose, and fasten the screws if necessary

Per month

Per month

Inspect warning labels, add or change in time if necessary

Manually inspect the AC&DC circuit breakers

48

Routine maintenance

Page 51: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Per month

Per week

Inspect the emergency button and the stop function of LCD

Inspect whether there is a abnormal noise during the inverter operation

Continued:

7.3 Waste disposal

Inverter imposes no pollution upon environment as the product's composed materials and components used by Samil Power satisfy the environmental protection requirements. The user shall, when the operating period of inverter ends, dispose of the inverter according to corresponding laws and regulations.

8 Annex8.1 Product label

Sequence number

Date(X): show the date of production. 1 to 9 stand for the first day to ninth day; A to V stand for the tenth day to 31th day.

Month(X): show the month of production. 1 to 9 stand for January to September; A to C stand for October to December.

Year(XX): show the year of production.10 to 99 stand for 2011 to 2099 year, A0 to J9 stand for year 2100 to 2199 year.

TB0 stand for SolarOcean 500TL (with transformerless, 0 stand for electrolytic capacitor, 1 stand for film capacitor);

TD0(standard) stand for SolarOcean 500TL (with trans-formerless, 0 stand for electrolytic capacitor, 1 stand for film capacitor);

TF0(backup) stand for SolarOcean 500TL (with trans-formerless, 0 stand for electrolytic capacitor, 1 stand for film capacitor);

XXX XX X X XXX

49

Operation guide for man-machine interface & Annex

Page 52: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

8.2 Product specifications

8.2.1 Applicable standards

The inverter is designed in accordance with the European and international standards shown in Table 8-1.

Table 8-1 European and International Standards

Item

IEC/EN62109,CE

Standard

General safety requirement in inverter operating area

EMC(electromagnetic radiation)

CNCA/CTS-0006 (CQC)Refer to VDE0126-1-1RD1663ENEL2010

IEC61727-2004/GB/T19939-2005

EMC ( anti-interference )

Inverter grid connected requirements

Inverter's performance determination approaches and test requirements

IEC 61000-4-2 (Electrostatic discharge immunity)IEC 61000-4-3 (Radiated,radio frequency electromagnetic field immunity)IEC 61000-4-4 (Electrical fast transient/burst immunity)IEC 61000-4-5 (Surge immunity)IEC 61000-4-6 (Immunity to conducted disturbances induced by FR fields)IEC 61000-4-8 (Power frequency magnetic field immunity)

EN61000-6-4:2007 (Mains terminal disturbance voltage\ Radiated disturbance))EN61000-3-3:2008(Voltage fluctuation &flicker)

Remarks: The listed product standards quote relevant clauses of general standards in IEC and EN about safety (60950), electromagnetic radiation and anti-interference (IEC/EN/AS61000 series) and structure (IEC/EN/AS60146 series and 60529).

8.2.2 Electrical characteristics (input)

Inverter Model SolarOcean 500TL

570

880 / 1000 (Optional)

1200

450 ~ 820

Max. DC Input Power [kW]

Max. DC Input Voltage [V]

Max. DC Input Current [A]

MPP Voltage Range (Under Nominal Power) [V]

1 / 4+8Number of MPP trackers/Strings per MPP Tracker

8.2.3 Electrical characteristics (output)

50

Annex

Page 53: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Inverter Model SolarOcean 500TL

500

550

1070

1200

Nominal AC Output Power [kW]

Max. AC Output Power [kW]

Nominal AC Output Current [A]

Max. AC Output Current [A]

270Nominal AC Voltage [V]

50

0.9lagging…0.9lagging

<3%

Nominal AC Frequency [Hz]

Power Factor (cosφ)

Total harmonic distortion (THDi) (Under Nominal Power)

98.6%

98.3%

99.9%

Max. Efficiency

Euro. Efficiency

MPPT Efficiency

8.2.4 Other parameters

Inverter Model SolarOcean 500TL

Dimensions (W/H/D) [mm]

Weight [kg]

Operating Temp. Range [°C]

Protection Degress

2600 / 2180 / 850

2300

-20 ~ +50

IP20

TransformerlessTopology

Internal Consumption (Night) [W]

Cooling Concept

Noise [dB]

<100

Fan

65

Touch Screen LCD

RS485/CAN

5

LCD Display

Communication Interface

Standard Warranty [Year]

8.3 Quality assurance

Quality warranty periodThe quality warranty period for this product is five years. If otherwise stipulated in contract, the contract shall prevail.

Evidence Within the quality warranty period of Samil Power, the customer shall, upon maintenance, show the service staffs of Samil Power the invoice and date of purchase. Meanwhile, the nameplate on the product shall be legible; otherwise, Samil Power is entitled to refuse maintenance.

51

Annex

Page 54: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Quality assurance conditionsFor products with faults in quality warranty period, Samil Power shall maintain, repair or change the products without charge.The changed fault machine shall be owned by Samil Power.The customer shall reserve a certain time period for Samil Power to maintain or repair.

Our company is entitled to refuse maintenance in case any one of the following conditions is met※ Products without the mark of Samil Power;※ Products or components have been beyond the quality warranty period of Samil Power;※ Faults or damages attributed to failure of operation according to requirement in Instruction, failure of operating in required environment, and incorrect installation, maintenance and use etc. (such as overhigh and overlow temperature, overhumid and overdry, too high altitude, instable voltage or current etc.);※ Faults or damages caused not by the installation, repair, change or demolition of after-service staffs from Samil Power (excluding those staffs entrusted by Samil Power);※ Faults or damages attributed to the use of Samil Power spare parts;※ Faults or damages and transportation damages caused by accidents or man-made reasons (operational errors, scratches, portages, hits, inappropriate voltage accession etc.);※ Faults or damages caused by natural disasters and other force majeures (such as earthquake, thunderstroke, fire and so on);※ Faults or damages caused no by the quality problems of Samil Power's machines (including spare parts).

Responsibility statement The copyright of this instruction is owned by Samil Power. Any unit or individual shall not extract or copy, part or all content of this instruction, and shall not transmit part or all content of this instruction by any means (including data and prints) without the permission of our company in written form. Samil Power reserves the Final Interpretation Right of this instruction, and all rights reserved.

Due to continuous upgrading of products, the contents in this instruction will be revised and adjusted continuously without notice. More products information see our official website; www.samilpower.com.

9 Contact Samil PowerSamil Power provides technical support for customers in an all-round way. The customer can contact with Samil Power offices or customer service center nearby, or contact directly with our headquarter.

Samil Power Co., Ltd.Address: No.66 Taihangshan Road, Suyu Economic Development Zone, Suqian City, Jiangsu Province, China.Postal Code: 223800Website: www.samilpower.comCustomer service hotline: +86(0)510 83593131 E-mail: [email protected]

52

Annex & Contact Samil Power

Page 55: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters
Page 56: Expert for PV Grid-tied Inverters - Samil Power · SP-SO500TL-V2.0-EN SolarOcean PV Grid-tied Inverter SolarOcean 500TL Product Manual TM Samil Power Expert for PV Grid-tied Inverters

Marketing & Sales OfficeAdd: No.52,Huigu Innovation Park, Huishan District, Wuxi,Jiangsu Province,P.R.China 214174Tel: +86 510 83593131Fax: +86 510 81819678E-mail:[email protected]://www.samilpower.com

FactoryAdd: No.66 Taihangshan Road, Suyu Economic Development Zone, Suqian City, Jiangsu Province, P.R.China 223800Tel: +86 527 88754666Fax: +86 527 84453877

Samil Power Co., Ltd.