Experimental Study on Interception Failure of Lightning Protection System of Wind Turbine Blade Waqas Arif 1 , Qingmin Li 1 , Zixin Guo 1 , Muhammad Ali Aizaz 2 , Yufei Ma 1 , Wah Hoon Siew 3 1 School of Electrical and Electronics Engineering, North China Electric Power University, Beijing 102206, China 2 Department of Electrical Engineering, University of South Asia, Lahore 55150, Pakistan 3 Department of Electronic and Electrical Engineering, The University of Strathclyde, Glasgow G1 1XQ, United Kingdom [email protected], [email protected], [email protected], [email protected], [email protected], [email protected] AbstractWind turbine (WT) blades are equipped with lightning protection system (LPS) consisting of receptors and down conductor in order to intercept lightning strikes. However, severe damages caused by lightning strikes still happen frequently, which costs huge losses. In this paper, experiments were conducted to study the lightning interception failure of WT blade LPS, and the results can be useful to improve the optimal design of LPS. Experiments using 5m blade specimen with tip receptor from 1.5MW wind turbine under 3m air gap are conducted to investigate the lightning interception failure of LPS in different orientations and lateral distances (LDs). Factors such as the polarity of lightning strikes, the blade orientation of wind turbine and lateral distance between wind turbine and lightning downward leader were investigated. The lateral distance between downward leader (DL) and wind turbine blade is a key factor which influences the interception efficiency. Three patterns of receptor interception failure are discovered. The protection area shows asymmetry under different lateral distance. Multi-upward leaders (UL) from WT blade have been observed in the experiment. Index Terms—Lightning protection, Wind turbine blade, receptor, Lightning attachment, Multi-upward leaders I. INTRODUCTION ind turbine is a nonstandard construction with rotating elements which is extremely exposed to the electrical environment. The most frequent damages happens to the blades, which are the most expensive single components of the turbine [1], [2] More than 88% of lightning attachments occur within the outermost 1 m of the blade tip, where the thickness of the surface skin is around 2-10 mm, but increased risk of inboard puncture for lightning strike of smaller current than 20 kA is also noticed [3]. Current LPS for WT blades are designed to withstand about 98% of lightning strikes, but there is still a risk of local damage, particularly at the attachment point [4], [5]. Lightning damage occurs to blades, generator, controller, control cables, etc. Among those, the blades are the most vulnerable components, which show the highest frequency (approximately 75%), highest repair cost, and longest downtime (approximately ten days per lightning incident) [6]. In addition, the increasing size of wind turbines in the recent years also poses significant challenges for the development of lightning protection system since the number of lightning strikes grows with the increase of structure height [7]. Field observation shows that the numbers of lightning strikes to wind turbine blade in orientation of 90°, 60° and 30° share similar proportion [8]. However, the behavior of receptor is different under different blade orientations. Some researchers use long air gap experiment to simulate the behavior of lightning strikes hit on blades with different kinds of receptors [9]-[12]. Simulation work has been done to discover the mechanism of upward inception of wind turbine [13], and to analyze the protection area of receptors [14]. Most manufacturers have decided the strategy of designing blade’s LPS according to the research and operation experience. However, the wind turbine blades are still hit by lightning strikes. The reason, why LPS of wind turbine blade fails to intercept lightning downward leader remains a question. The process of interception failure needs to be reproduced by experiments first, and then the model can be modified to simulate the fact more accurately. In this paper, experiments are conducted to investigate how the receptor behaves to lightning strikes and how the LPS fails to intercept it. Different situations, including positive and negative polarity impulse, different blade orientations and different lateral distances, are taken into consideration. The asymmetrical influence of lateral distance is analyzed. The patterns of receptor interception failure under positive discharge are summarized. II. EXPERIMENTAL WORK A. Description of wind turbine blade specimen In consideration of both operating feasibility and experimental comparability, 5m Glass fiber reinforced polymer (GFRP) wind turbine blade tip is used to conduct the experiments, WT blade specimen cut from SINOMA45.2B which was designed for 1.5MW Wind turbine and the length was 45.2m. The blade specimen is equipped with lightning protection system including an aluminum-made tip receptor and 70mm 2 copper stranded conductor inside blade chamber connected to the ground as shown in Figure 1. W

Experimental Study on Interception Failure of Lightning ......Experimental Study on Interception Failure of Lightning Protection System of Wind Turbine Blade Waqas Arif1, Qingmin Li1,

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

  • Experimental Study on Interception Failure of Lightning Protection System of Wind Turbine Blade

    Waqas Arif1, Qingmin Li1, Zixin Guo1, Muhammad Ali Aizaz2, Yufei Ma1, Wah Hoon Siew3 1School of Electrical and Electronics Engineering, North China Electric Power University, Beijing 102206, China

    2Department of Electrical Engineering, University of South Asia, Lahore 55150, Pakistan 3Department of Electronic and Electrical Engineering, The University of Strathclyde, Glasgow G1 1XQ, United Kingdom

    [email protected], [email protected], [email protected], [email protected], [email protected], [email protected]

    Abstract— Wind turbine (WT) blades are equipped with

    lightning protection system (LPS) consisting of receptors and down conductor in order to intercept lightning strikes. However, severe damages caused by lightning strikes still happen frequently, which costs huge losses. In this paper, experiments were conducted to study the lightning interception failure of WT blade LPS, and the results can be useful to improve the optimal design of LPS. Experiments using 5m blade specimen with tip receptor from 1.5MW wind turbine under 3m air gap are conducted to investigate the lightning interception failure of LPS in different orientations and lateral distances (LDs). Factors such as the polarity of lightning strikes, the blade orientation of wind turbine and lateral distance between wind turbine and lightning downward leader were investigated. The lateral distance between downward leader (DL) and wind turbine blade is a key factor which influences the interception efficiency. Three patterns of receptor interception failure are discovered. The protection area shows asymmetry under different lateral distance. Multi-upward leaders (UL) from WT blade have been observed in the experiment.

    Index Terms—Lightning protection, Wind turbine blade,

    receptor, Lightning attachment, Multi-upward leaders

    I. INTRODUCTION ind turbine is a nonstandard construction with rotating elements which is extremely exposed to the

    electrical environment. The most frequent damages happens to the blades, which are the most expensive single components of the turbine [1], [2] More than 88% of lightning attachments occur within the outermost 1 m of the blade tip, where the thickness of the surface skin is around 2-10 mm, but increased risk of inboard puncture for lightning strike of smaller current than 20 kA is also noticed [3]. Current LPS for WT blades are designed to withstand about 98% of lightning strikes, but there is still a risk of local damage, particularly at the attachment point [4], [5]. Lightning damage occurs to blades, generator, controller, control cables, etc. Among those, the blades are the most vulnerable components, which show the highest frequency (approximately 75%), highest repair cost, and longest downtime (approximately ten days per lightning incident) [6]. In addition, the increasing size of wind turbines in the recent years also poses significant

    challenges for the development of lightning protection system since the number of lightning strikes grows with the increase of structure height [7]. Field observation shows that the numbers of lightning strikes to wind turbine blade in orientation of 90°, 60° and 30° share similar proportion [8]. However, the behavior of receptor is different under different blade orientations. Some researchers use long air gap experiment to simulate the behavior of lightning strikes hit on blades with different kinds of receptors [9]-[12]. Simulation work has been done to discover the mechanism of upward inception of wind turbine [13], and to analyze the protection area of receptors [14]. Most manufacturers have decided the strategy of designing blade’s LPS according to the research and operation experience. However, the wind turbine blades are still hit by lightning strikes. The reason, why LPS of wind turbine blade fails to intercept lightning downward leader remains a question. The process of interception failure needs to be reproduced by experiments first, and then the model can be modified to simulate the fact more accurately. In this paper, experiments are conducted to investigate how the receptor behaves to lightning strikes and how the LPS fails to intercept it. Different situations, including positive and negative polarity impulse, different blade orientations and different lateral distances, are taken into consideration. The asymmetrical influence of lateral distance is analyzed. The patterns of receptor interception failure under positive discharge are summarized.

    II. EXPERIMENTAL WORK

    A. Description of wind turbine blade specimen In consideration of both operating feasibility and experimental comparability, 5m Glass fiber reinforced polymer (GFRP) wind turbine blade tip is used to conduct the experiments, WT blade specimen cut from SINOMA45.2B which was designed for 1.5MW Wind turbine and the length was 45.2m. The blade specimen is equipped with lightning protection system including an aluminum-made tip receptor and 70mm2 copper stranded conductor inside blade chamber connected to the ground as shown in Figure 1.

    W

  • Fig. 1. The 5m GFRP wind turbine blade specimen with an aluminum tip receptor and 70mm2 copper down conductor inside blade chamber.

    B. Arrangement of the experimental setup Experiment tests were conducted outdoors at Shahe testing yard of North China Electric Power Research Institute (NCEPRI) in China, and more than 200 strikes were applied. In order to produce the background electric field similar to real lightning, the voltage waveform is 250/2500μs (positive & negative) standard switching impulse were obtained using a 5.4 MV, 405 kJ, 28 stages impulse generator. The discharge voltage was measured using a voltage divider. A rod electrode was employed as the downward leader and the vertical height between the tip of wind turbine blade specimen and the bottom of rod electrode is 3m. The blade specimen is elevated above the ground on a 1m non-conductive support. A digital camera is used to capture the discharge behavior by long-exposure, and a high-speed camera Phantom V1210 is

    used to capture the discharge process by long-exposure. The frame rate is 240601 fps (4.156μs/frame), and the resolution is 128×128 pixel. The breakdown voltages were measured using an oscilloscope. The breakdown probability is approximately 100% for the applied voltage. The practical test platform configuration is displayed in Figure 2. There are 3 kinds of typical orientations: 30°, 60° and 90° with horizontal. In this paper, 90° and 30° are used for the experiments. The lateral distance (LD) between rod electrode and the tip of blade specimen is adjustable in order to simulate lightning strikes coming from different directions. The ratio between the horizontal distance from downward leader tip to the bottom of blade and the length of blade is proposed to classify different lateral distances (LD) from different directions:

    tip-bottom

    blade

    =L

    RL

    (1)

    Where Ltip-bottom is the horizontal distance between downward leader and the foot point of vertical line from the blade tip to the blade bottom, Lblade is the horizontal distance from the blade tip to the blade bottom (foot point), as shown in Figure 3.

    (a) (b)

    (c)

    Fig. 2. (a) Test platform configuration for blade orientation 90° with horizontal. (b) Test platform configuration for blade orientation 30° with horizontal. (c) Experiment setup

  • Lateral distance can be divided into 3 groups: R >1, DL comes from direction far from wind turbine blade. LD is -1.5m. R =1, DL comes from above the tip of wind turbine blade. LD is 0m. R 1: LD=-1.5m; R =1: LD=0m; R

  • Fig. 6. (a) The paths of total 20 times positive discharges. (b) The paths

    of total 20 times negative discharges. (c) The position of positive discharge connection points is at about 40% of the gap. (d) The position

    of negative discharge connection points is at about 40% of the gap.

    B. The performance of LPS when the orientation of WT blade is 30° with horizontal 20 times standard positive switching impulse were applied for each lateral distance as shown Figure 7 and results are tabulated in Table III. The interception efficiency of tip receptor reaches maximum (approximately 95%) when lateral distance was 0m. With the increasing of lateral distance both R >1 and R 1. (b) The paths of total 20 times discharges for LD=0m, R =1. (c) The

    paths of total 20 times discharges for LD=0.75m, R

  • TABLE III DISCHARGE MANNER FOR ORIENTATION OF 30° WITH HORIZONTAL

    Lateral distance

    (m) Rtip-bottom

    Average breakdown

    voltage (kV)

    Attachment point

    total Tip receptor Blade surface

    Receptor tip Receptor side subtotal Close to tip

    receptor far from tip

    receptor subtotal

    1.5 1 1248.55 6 30% 9 45% 15 75% 5 25% 0 0% 5 25% 20

    1.5 >1 1268.06 1 6% 5 29% 6 35% 11 65% 0 0% 11 65% 17

    2.25 >1 1466.10 0 0% 2 10% 2 10% 10 50% 8 40% 18 90% 20

    (a) Creeping discharge from receptor along the leading/trailing edge

    (b) Discharge hitting on blade leading/trailing edge

    (c) Discharge hitting on blade surface directly

    Fig. 9. Three patterns of receptor interception failure. Pictures are taken by high speed camera.

    In third type of interception failure, the discharge can bypass the edge and hit on the blade surface directly. As shown in Figure 9(c), upward leaders incept both from edge and surface of blade, and discharge finally hits on the surface. Although the upward leader that incepts from leading edge connected the downward leader, the discharge continues to go downward to the upward leader which incepts from blade surface, and finally hit on blade surface.

    IV. DISCUSSION The experimental results show strong polarity effect, as positive lightning strikes are difficult to be intercepted by receptor. It can be regarded that the results won’t be influenced by the nearby objects and the surroundings won’t affect the electric field in the long air gap. The space charges caused by corona disturb the electric field near the receptor, which influence the inception of upward leader. With lateral distance increasing, the distribution of striking attachment points shows a tendency that striking attachment point moves away from tip receptor, as shown in Figure 10. When lateral distance is 0m, most discharges hit on receptor tip and side, then with the increasing of LD, more discharges hit on the blade surface near the boundary of receptor and blade body and cause creeping discharges instead of hit on the receptor. When lateral distance is large enough, the receptor fails to attract most downward leaders and discharges hit on the surface of blade body.

    Fig. 10. The striking attachment points of different lateral distances.

    In this paper, the experiments were conducted with standard switching impulses and it has be found that the tip receptor performs very well under negative impulses. However, the tip receptor fails to intercept discharge under positive impulses. If lightning impulse is more severe than switching impulses then polarity effect will be more pronounced with lightning impulses, and the influence of lateral distance will be more obvious, which will further prove the conclusion in this paper.

    (((((( ))))) ppppppppp ggggg ggggg pppppppppp ggggggggg gggggggg gggggggg gggg

    (((((((((( ) gggggg gg ggggggggggg gggg ggggg

  • V. CONCLUSIONS AND RECOMMENDATIONS Experiments of lightning attachment were conducted to study the inception performance of WT blade with LPS under different blade orientations and lateral distance. The conclusion can be summarized as follows. 1. The lateral distance between lightning downward leader

    and wind turbine blade is one of the key factors of receptor interception efficiency. The protection area of receptor shows obvious asymmetry when lateral distance is different, and discharges can be intercepted more efficiently when R >1 than R /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 200 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 400 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 600 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False