Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Steel Structures 7 (2007) 201-208 www.kssc.or.kr
Experimental Behaviour of Steel Connections to Concrete
Filled Steel Tubular Columns in Fire
Y. C. Wang* and J. Ding
School of MACE, University of Manchester, UK
Abstract
This paper presents observations and some structural behaviour results of five fire tests on a structural assembly consistingof a steel beam connected to a pair of concrete filled tubular (CFT) columns in a rugby style arrangement. The objectives ofthis study are to obtain thermal behaviour data of joints and to examine large deflection structural behaviour of axiallyrestrained steel beams and robustness of different types of steel joint to CFT column. The five tests include one test using asimple fin plate welded to the steel tube and bolted to the beam web, two tests using a T-stub bolted to the steel tube and thesteel beam, and two tests using a channel welded to the steel tube on the toes and bolted to a flexible end plate welded to theweb of the steel beam. In each test, only the steel beam was loaded by two point loads at approximately 1/3 spans. All firetests continued beyond the limiting temperatures of the steel beams based on pure bending in order to examine the developmentof catenary action and the behaviour of the joint components under combined tension, shear and bending moment in fire. Thetest results indicate that all the joints would survive the fire if the beam temperature does not exceed the beam’s limitingtemperature for pure bending. The joints were sufficiently strong to enable the beams to develop some catenary action so thatthe steel beam failure temperature was 100oC higher than the beams’ limiting temperatures. However, to enable the steel beamto survive much higher temperatures in catenary action, the joint strength in tension would have to be substantially increased.
Keywords: joints, concrete filled tube, catenary action, fire resistance, fire test
1. Introduction
Joints are critical members in structures. Despite extensive
research studies of CFT column behaviour in fire in the
past, very little information is available on joints between
steel beams and CFT columns under fire conditions. In
particular, observations from fire tests and real fire
accidents in other types of steel structure indicate that
there is strong interaction between joints and the
connected beams and columns, and that the behaviour of
the joints in complete structures is different from that in
isolation. In general, steel beams restrained by the
adjacent structure would go through a number of phases
in behaviour when exposed to fire (Wang, 2002),
including combined flexural bending and compression
during the early stage of fire exposure (as a result of
restrained thermal expansion of the beam), through pure
flexural bending at temperatures around the beam’s
limiting temperature for pure bending, and finally to
catenary action at the late stage of fire exposure when the
beam deflection is very large. As a result, the forces in the
joints will change during the course of a fire exposure. In
particular, catneary action in the steel beam can allow the
beam to survive very high temperatures and it is possible
to utlilise catanary action in the steel beam to remove fire
protection (Yin and Wang, 2004, 2005a, b; Wang and
Yin, 2006). However, it is important that the joints have
sufficient resistance to the catenary forces. Isolated joint
tests under fixed loads, either in bending, tension,
compression or their combinations, cannot capture the
changing nature of joint performance and its impact on
the adjacent structural behaviour. Therefore, the fire tests
of this research were carried out in a structural assembly,
consisting of a steel beam and two CFT columns in a
rugby frame. The aim of this research is to provide detailed
experimental information to help quantify temperature
fields in the joint region, and structural performance of the
joints and structural assemblies in fire. In this research,
the beam was loaded and heated to very high
temperatures and very large deflections, so that these new
fire tests can provide information on joint behaviour over
the entire range of steel beam behaviour.
A few previous research studies of a similar nature
examined steel beam to H-column joints (Dong and Li,
2005, Liu et al., 2002). However, these investigations
have mainly been concerned with joint rotational restraint
to the steel beams, with limited information on beam
behaviour during the catenary stage. The joints of Dong
and Li (2005) were outside the test furnace. Furthermore,
these previous studies did not report in detail whether and
*Corresponding authorTel: +44 161 3068968E-mail: [email protected]
202 Y. C. Wang and J. Ding
how the joints had failed during the tests.
This paper will present the results of 5 tests on joints to
CFT columns, which have recently been completed. This
paper will provide observations of different joint failure
modes as well as the beam behaviour. Preliminary
conclusions will be drawn on design implications.
2. Test Descriptions
The fire tests were carried out in one of the three
furnaces in the Fire Testing Laboratory of the University
of Manchester. This furnace was a rectangular box having
internal dimensions 3000 mm × 1600 mm × 900 mm. The
interior faces of the furnace were lined with ceramic fibre
materials of thickness 200 mm that efficiently transferred
heat to the specimen. An interior full-height honeycomb
ceramic wall, as shown in Fig. 1, was constructed to
ensure uniform heating. A gas burner and an exhaust
were connected to the furnace. The firing and control
equipment was installed with the gas burner. Before
actual fire testing of loaded specimens, a number of trial
fire tests without a test specimen were carried out. In
these tests, the hole positions in the interior wall were
adjusted until the most uniform temperature distribution
inside the furnace was reached. The burner system was
fully computer-controlled to follow any required time-
temperature curve, with automatic recording of the results
and a runtime display.
The furnace consisted of 6 panels bolted at their
junctions for easy assembly. It could accommodate
frames with 2 m beam length and 3m total column height
and take account of the large displacements associated
with high-temperature testing.
The arrangement of the members to be tested was in the
form of a complete ‘Rugby goalpost’ frame as shown in
Fig. 2. The steel beam was mainly unprotected. In order
to simulate the heat-sink effect due to the concrete slab in
realistic structures, the top flange of the beam was
wrapped with 15 mm thick ceramic fibre blanket. The
columns were unprotected. The columns were restrained
from lateral movement (so as to provide axial restraint to
the beam) at the ends and were free to move in the
longitudinal direction at the top. The lateral restraint at
each column end was provided by a bracket bolted to the
strong reaction frame around the furnace. Two transverse
point loads were applied to the beam using two
independent hydraulic jacks connected to the top member
of the strong reaction frame surrounding the furnace to
form a self-equilibrating system. The jacks and the
brackets were protected by ceramic fibre blanket during
the fire test.
Each assembly consisted of two concrete filled tubular
(CFT) columns and a steel beam. The cross-section size
of the beams in all tests was the same, being grade S275
universal beam section 178 × 102 × 19UB. SHS tubes
were used, and the overall dimensions were 200 × 200
mm. The five tests investigated three types of joint: fin
Figure 1. Schematic arrangement of the furnace.
Figure 2. Schematic arrangement of test.
Figure 3. Fin plate joint (Test 1).
Figure 4. T-stub joint (Tests 2 & 3).
Experimental Behaviour of Steel Connections to Concrete Filled Steel Tubular Columns in Fire 203
plate welded to the tubular wall (Fig. 3), T-section bolted
to the tubular wall using Molabolts (Fig. 4), reverse
channel welded to the tubular wall (Fig. 5). The Molabolt
was a new type of blind bolting system for application to
tubular structures (www.molabolt.com). It worked by
expanding inside the tube. In order for the Molabolt to
tightly join the tube, the hole diameter should not exceed
the Molabolt diameter by 0.5 mm. For comparison, the
clearance for conventional bolts is 2 mm. The Molabolts
should be inserted into the tube before concreting. There
was no applied load in the columns. The same load
(30 kN in each jack) was applied in all tests, being about
50% of the lateral torsional buckling load carrying capacity
of the simply supported beam at ambient temperature.
The average temperature inside the furnace was
programmed to rise according to the ISO834 standard
time-temperature curve. However, due to high thermal
mass of the test assembly, especially that of the wet
concrete, in relation to the furnace size, the furnace
temperatures could not follow the standard fire curve.
The furnace temperatures were measured with the aid of
6 control thermocouples, which were placed in two lines
opposite each other at 430 mm apart (Fig. 1). These
thermocouples were embedded in ceramic tubes and their
measuring tips project out-side the ceramic tubes and
were located in the mid height of the furnace.
Due to high temperatures in the fire test, the means of
measuring strains and displacements was very limited.
No strain gauges were placed on the specimen, as they
would be quickly destroyed during the fire exposure.
High temperature strain gauges were considered, but they
would be too expensive and would not be able to provide
reliable information due to different thermal expansions
from those of the structural materials at high temperatures.
Therefore, only the temperature distributions, displacements
and the horizontal reaction forces at the ends of the
columns were measured during the tests. In particular, a
large number of thermocouples were installed on each
test specimen in the beam, joint components and columns
to record detailed temperature distributions, as shown in
Fig. 6.
3. Observations
3.1. Furnace temperatures
In all tests, because the test frames were of the same
size and configuration, temperature distributions inside
the furnace were almost identical. This is confirmed by
Fig. 7, which compares the average recorded furnace
temperature for the five tests. Also due to the large mass
of the test specimen in comparison to the size of the
furnace, the furnace temperatures were slightly lower
than the intended ISO-834 heating curve. As indicated in
Fig. 1, the furnace temperatures were measured by six
control thermocouples. Because only one burner was
used, the six thermocouples inside the furnace recorded
non-uniform temperature distribution in the furnace,
which is shown in Fig. 8. Close examination of the
individual thermocouple results in Fig. 8 indicates that
the highest gas temperature was measured in the middle
of the furnace from thermocouples 2 and 5. Higher
temperatures were recorded towards the left hand side of
the furnace (thermocouples 3&6). Thermocouples 1&4
recorded the lowest temperatures towards the right hand
side of the furnace. The higher temperatures on the left
hand side of the furnace may be used to explain that in all
the tests, failure (or maximum damage) occurred on the
left hand side of the test frames.
Figure 5. Reverse channel joint (Tests 4 & 5).
Figure 6. Locations of measuring devices.
204 Y. C. Wang and J. Ding
3.2. Test 1
Before the furnace was ignited, the loads were applied
to the beam gradually. No visible deformation was found
in the specimen at this stage. After 23 minutes of fire test,
the beam deflection increased rapidly. As a result, the
applied loads failed to catch up with the deflection. At
24.5 minutes of fire test, the displacement transducer at
the mid-span of the beam (Fig. 6) was detached from the
beam, and did not give meaningful readings thereafter.
The sub-frame failed at 31 minutes with fracture at the
weld in the left hand joint, as shown in Fig. 9(a). The
beam experienced large twist and vertical deflections as
shown in Fig. 9(b).
3.3. Test 2
The loads were applied to the beam gradually at room
temperature. No visible deformation was found in the
specimen at this stage. After 23 minutes of fire test, the beam
deflection started to increase very quickly and the applied
loads failed to catch up with the deflection. The sub-frame
failed at 30 minutes with pull-out of the beam web at the left
end, as shown in Figs. 10(a) and 10(b). The beam had large
twist and vertical deflections as shown in figure 10(c). Due
to the large twist in the beam, parts of the T-section bolted to
the beam were also twisted to one side, as shown in Fig.
10(d). Consequently, the bolts between the left T-section and
the beam experienced large rotations as shown in Fig. 10(e).
Parts of the T-sections bolted to the steel tubes were pulled
out slightly. The steel tube walls were also pulled out slightly
around the connection area but there was no indication of
failure in the tubes.
3.4. Test 3
Test 3 used SHS 200 × 12.5 mm tubes and bolted T
joints. The only difference between the test 3 and test 2
configurations is in the thickness of the tube. Also, to
prevent pull-out failure of the beam web which occurred
in test 2, a length of 100 mm of the beam web was
protected by 15 mm thick ceramic fibre blanket at both
end, as shown in Fig. 11(a).
After applying the target loads at room temperature, no
clear deformation was found in the specimen. After 24.5
minutes of fire test, the beam deflection increased rapidly
and the applied loads could not be maintained. After 30
minutes of fire exposure, the beam deflection started to
increase at a lower rate and the applied loads were
increased to the original level. The applied loads were
then maintained until the sub-frame failed at 38.2 minutes
after fire exposure. As shown in Fig. 11(b), failure of this
sub-frame was due to fracture of the stem of the T-section
Figure 7. Average furnace temperatures.Figure 8. Measured temperature distribution inside furnace.
Figure 9. Failure mode of test 1.
Experimental Behaviour of Steel Connections to Concrete Filled Steel Tubular Columns in Fire 205
on the left hand side. Figure 11(c) shows a detailed image
of the failure surface. No noticeable deformation could be
seen in the steel tubes and there was no sign of tube
failure. As shown in Fig. 11(c), there was no noticeable
deformation in T-sections bolted to the steel tubes and the
Molabolts.
3.5. Test 4
The beam was loaded gradually at room temperature to
the target loads. No clear deformation was found in the
specimen before fire ignition. After 23 minutes of fire
test, the beam deflection increased rapidly and the applied
loads could not catch up with the deflection for a short
period. After 27 minutes of the fire test, the applied loads
were successfully increased to the original level and then
maintained until the end of the test. The sub-frame failed
at 33 minutes after fire exposure with fracture in the beam
web on the left hand side, as shown in Fig. 12(a). The
fracture length was the same as the weld length and the
fractured web formed a sharp edge, as shown in Fig.
12(b), indicating tension failure. Due to large deflections
in the beam and flexibility of the connection, the endplates
and the front faces (web) of the reverse channels deformed
significantly, as shown in Fig. 12(c). However, there was
no fracture in the reverse channels, indicating their extremely
high ductility. There was no noticeable deflection in the
steel tubes. Neither was any damage found in the connection
welds.
Figure 10. Behaviour and failure mode of test 2. (a) Jointfailure due to beam web fracture (b) Fractured beam web(c) Deformed beam (d) Deformed T-stub (e) Deformedbolts between T-stub and beam web.
Figure 11. Behaviour and failure mode of test 3. (a) Local fire protection to joint (b) Separation of T-stub from beam(c) Fracture of T-stub stem.
Figure 12. Behaviour and failure mode of test 4. (a) Joint failure due to beam web fracture (b) Fractured beam web (c)Deformed reverse channel web.
206 Y. C. Wang and J. Ding
3.6. Test 5
The only difference between the test 4 and test 5
configurations was the tube wall thickness. Also to
prevent fracture in the beam web which happened in test
4, a length of 100 mm of the beam web was protected by
15 mm ceramic fibre blanket at both ends as shown in
Fig. 13(a).
Before fire ignition, the beam was loaded gradually to
the target loads and no obvious deformation was found in
the specimen. After 25 minutes of the fire test, the beam
deflection increased rapidly and the applied loads
dropped and could not be maintained for a short period.
After 29.5 minutes of fire test, the applied loads were
successfully increased to the original level and were then
maintained until the end of the test. After 41.4 minutes of
fire exposure, the hydraulic jack on the left hand side ran
out of travel and was unable to maintain the load on the
beam. After 46.2 minutes of fire exposure, the hydraulic
jack on the right hand side also ran out of travel. When
the test was finally terminated at 51.5 minutes, no fracture
failure in the sub-frame could be observed from the view
aperture on the furnace door. However, after the specimen
was taken out of the furnace, fracture was found in the
steel tubes where the reverse channels were welded, as
shown in Fig. 13(b). There was also fracture in the weld
between the endplate and the beam web on the left hand
side, as shown in Fig. 13(c). A crack also appeared to
have started in the weld between the reverse channel and
the tube on the right hand side, as shown in Fig. 13(d).
The crack in the steel tube revealed the concrete core,
which did not show any damage at all. Due to the large
catenary force in the beam, the endplates and the reverse
channels distorted significantly, as shown in Fig. 13(e).
4. Beam Structural Behaviour
4.1. Beam deflections
Figure 14(a) compares the beam vertical deflection -
temperature curves for the five tests. The temperature
measured in the beam bottom flange at the mid-span is
used in the figure. The beams were able to sustain the
load without excessive deflection up to a bottom flange
temperature of about 670ºC, which is about the limiting
temperature at a load ratio of 0.5 according to BS 5950
Part 8 (BSI 1990). Further rise in the steel beam temperature
led to a progressive run-away of the beam deflection as
the loss of stiffness and strength of steel accelerated.
Figure 14(b) shows the beam vertical deflection - time
curves for the five tests. It can be seen that the deflections
of test 1, 2 and 4 were very close during the first 24.5
minutes of heating. After that, the displacement transducer
at the mid-span of the beam in test 1 was detached from
the beam, and did not give the correct reading thereafter.
However, the deflections of test 2 and 4 were still very
close until about 27 minutes of fire test. Afterwards, the
rate of beam deflection increase in test 4 was lower than
in test 2. This is clearly linked to the greater catenary
force in test 4 than in test 2, as shown in Fig. 15(a). It can
also be seen in Fig. 14(a) that the run-away of the beam
deflection happened at about 23 minutes in test 1, 2 and
4. For test 3 and 5, the deflections were very close. Due
to fire protections on the joints, run-away deflection of
the beams in tests 3 and 5 occurred at about 25 minutes
of heating, which is a delay of about 2 minutes comparing
with tests 1, 2 and 4,. After about 30 minutes, the rate of
run-away deflection decreased in tests 3 and 5 compared
to other tests.
Figure 13. Behaviour and failure mode of test 5. (a) Beam protection near joint (b) Fractured weld on tube on left handside (c) Fracture of weld on beam (d) Fractured weld on tube on right hand side (e) Deformed end plate.
Experimental Behaviour of Steel Connections to Concrete Filled Steel Tubular Columns in Fire 207
4.2. Beam axial forces
During the early stage of fire exposure, axial compression
force developed when the thermal expansion in the
heated steel beam was restrained by the CFT columns.
The axial compression started to reduce when the steel
temperature approached the beam’s limiting temperature
for combined bending and axial compression. The
compression force continued to decrease until catenary
action started to develop in the beam at the late stage of
fire exposure when the beam deflection was very large.
Figures 15(a) and 15(b) compare the beam axial force -
time curves and beam axial force - temperature curves
recorded by the horizontal load cells on both sides of the
test assembly for the five tests. It can be seen that
catenary action in the steel beam has developed at the late
stage of fire exposure in all the tests. The compression
force in the steel beam of test 1 was relatively small due
to the low stiffness of the fin plate joint. By comparing
test 2 with test 3 and test 4 with test 5, it can be seen that
the beams connected with the thicker tubes developed
higher compression forces due to the higher axial restraint
stiffness (test 3 and 4) provided to the beam by the thicker
steel tubes. By comparing test 2 with test 5 and test 3
with test 4, it can be seen that the beam had higher
compression forces when the reverse channel joint was
used, indicating higher axial stiffness provided by the
reverse channel joint than the T-stub joint. In tests 3 and
5, when parts of the joints were protected, the beams
experienced a considerable period of catenary action so
that the beam failure times were much higher then the
time when the beams reached their limiting temperatures
Figure 14. Beam deflection behaviour. (a) Beam verticaldeflection-temperature relationships (b) Beam verticaldeflection-time relationships.
Figure 15. Beam axial force behaviour. (a) Beam axialforce-time relationships (b) Beam axial force-temperaturerelationships.
Table 1. Summary of fire test specimens
Test Tube size Thickness Joint Type
1 SHS 200 5 mm Fin plate
2 SHS 200 5 mm Bolted T
3 SHS 200 12.5 mm Bolted T with 100 mm long steel beam protection
4 SHS 200 12.5 mm Reverse channel
5 SHS 200 5 mm Reverse channel with 100 mm long steel beam protection
208 Y. C. Wang and J. Ding
under bending. Without the fire protection (tests 2 and 4),
beam failure occurred in the joint region much earlier
than in tests 3 and 5. Therefore, if the beam to column
joints possess sufficient strength, it is possible for the
steel beam to achieve high fire resistance even without
fire protection, through the development of catenary
action.
Table 2 gives a summary of the test results.
5. Conclusions
This paper has described some results of five fire tests
on a rugby type structural arrangement using different
types of joints between steel beam and concrete filled
tubular columns. The following preliminary conclusions
may be drawn:
All the joints behaved well before the steel beam had
reached its limiting temperature for flexural bending,
which is about 670oC.
It is possible for moderately complex joints to concrete
filled tubular columns (T-stub, reverse channel) to develop
substantial catenary action, whereby the steel beams
could survive much higher temperatures than 670oC. The
fin plate joint had little stiffness to develop catenary
action in the beam and the resistance of the joint to
catenary action in the beam is low. The reverse channel
joint appeared to have higher stiffness and strength than
the T-stub joint to resist catenary action in the steel beam.
The failure modes of the test specimens were always in
the joint region and the steel beams were able to
accommodate very large deflections. By appropriate design
and protection of the joint components, it is possible for
the steel beams to develop catenary action and survive
very high temperatures. However, the catenary force and
its distributions in different joint components should be
carefully calculated so that the joints can be properly
designed. These are now being investigated by the authors.
In addition, the authors are also conducting further fire
tests to examine the behaviour of joints under cooling.
Acknowledgments
The work presented in this paper was funded by
CIDECT (Project 15S - 13/05). The authors would like to
thank Mr. Andrew Orton of Corus Tubes for his interests
and practical suggestions. Thanks are also due to Mr. Jim
Gorst and a number of post-graduate students who
assisted with the fire tests.
References
British Standards Institution (BSI 1990). British Standards
BS 5950, Structural use of Steelwork in Buildings, Part 8:
Code of practice for fire resistant design, British
Standards Institution, London.
Dong, Y.L. and Li, X.D. (2005). “The behaviours of H-section
steel beam in fire.” Proceedings of the 8th International
Symposium on Fire Safety Science, Beijing, China.
Liu, T.C.H., Fahad, M.K. and Davies, J.M. (2002).
“Experimental investigation of behaviour of axially
restrained steel beams in fire.” Journal of Constructional
Steel Research, 58, pp. 1211-1230.
Wang, Y.C. (2002). Steel and composite structures,
behaviour and design for fire safety, E & FN Spon.
Wang, Y.C. and Yin, Y.Z. (2006). “A simplified analysis of
catenary action in steel beams in fire and implications on
fire resistant design.” Steel and Composite Structures, An
International Journal, 6(5), pp. 367-386.
Yin, Y.Z. and Wang, Y.C. (2004). “A numerical study of
large deflection behaviour of restrained steel beams at
elevated temperatures.” Journal of Constructional Steel
Research, 60(7), pp. 1029-1047.
Yin, Y.Z. and Wang, Y.C. (2005a). “Analysis of Catenary
Action in Steel Beams Using a Simplified Hand
Calculation Method, Part 1: Theory and Validation for
Uniform Temperature Distribution.” Journal of
Constructional Steel Research, 61, pp. 183-211.
Yin, Y.Z. and Wang, Y.C. (2005b). “Analysis of Catenary
Action in Steel Beams Using a Simplified Hand
Calculation Method: Part 2. Validation for Non-uniform
Temperature Distribution.” Journal of Constructional
Steel Research, 61, pp. 213-234.
Table 2. Summary of test results
TestSteel beam
tensile strength(N/mm2)
Max. beambottom flange
temp. (oC)
Max. beam vertical def. at mid-span
(mm)Failure mode
Failure time(min)
1 358.4 753* Not reliable Fin plate weld fracture 31
2 439.1 744 265 Fracture of beam web 30
3 439.1 769 263 Fracture of T-stem 38.2
4 439.1 788 288 Fracture of beam web 33
5 439.1 817 264 No failure (fracture of weld to tube) 41.4