EVOMAX. 30kW CONDENSING - WALL HUNG IDEAL COMMERCIAL BOILERS PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN T: 0844 5436060 F: 0844 5436181 E: [email protected] IDEALCOMMERCIALBOILERS.COM DIMENSIONS AND CLEARANCES The following minimum clearances must be maintained for operation and servicing: For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM A DIM B DIM C 30kW 360 130 118 Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations. • Largest range of outputs in market (30 – 150 kW) • Robust & light aluminium silicon alloy heat exchanger • Up to 110% part load efficiency • High 5:1 turndown • Compact – one width & height for easy siting • Simple controls interface with large backlit display • Comprehensive range of options • Designed for easy installation, commissioning and servicing • Quality product through design, component selection and proving • NOx <40mg/kWh (Class 5) for all natural gas models • 5 year parts and labour warranty FEATURES AND BENEFITS All dimensions in mm TOP DEPENDENT ON FLUE SIZE SIDES 25mm BELOW 300mm FRONT 450mm CLEARANCE BETWEEN MULTIPLE BOILER INSTALLATIONS 25mm

EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.30kWCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

30kW 360 130 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 2: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 49

Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

Full Load % 89.6

Part Load % 98.4

Seasonal Efficiency % 96.7

Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 3.2

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 6-30

Boiler Output (Mean 40°C) kW 6.5-31.54

Boiler Input (Gross cv) kW 33.7

Gas Inlet Size G¾”

Weighted Power Level dB(A) 53

NOx Rating/emissions at 0% O2 mg/kWh Class 5 (31)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 425

Hydraulic Resistance (20°C ∆T) mbar 127

Nominal Flow Rate (11°C ∆T) l/s 0.651

Nominal Flow Rate (20°C ∆T) l/s 0.358

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.07

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 3

FLUE/AIR INLET

Flue Size mm 80/125 Concentric or Open Flue

Flue Gas Volume m³/h 47.6

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 140

B/F Max Counter Pressure Diff Pa 140

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 0.6

Power Consumption watt 126

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 30kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS

211156

Page 3: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.30kW - LPGCONDENSING - WALL HUNG

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

All dimensions in mm

The following minimum clearances must be maintained for operation and servicing:

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

30kW LPG 360 130 118

FEATURES AND BENEFITS

Page 4: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 49

Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

Full Load % 91.6

Part Load % 99.6

Seasonal Efficiency % 97.2

Min/Max Gas pressure (Nat Gas) mbar 37

BURNER PRE MIX

Fuel (Type G31) LPG Model

Fuel Consumption (Nat Gas) m³/h 1.26

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 6-30

Boiler Output (Mean 40°C) kW 6.4-30.9

Boiler Input (Gross cv) kW 33

Gas Inlet Size G¾”

Weighted Power Level dB(A) 53

NOx Rating/emissions at 0% O2 mg/kWh Class 4 (79)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 425

Hydraulic Resistance (20°C ∆T) mbar 127

Nominal Flow Rate (11°C ∆T) l/s 0.651

Nominal Flow Rate (20°C ∆T) l/s 0.358

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.08

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 3

FLUE/AIR INLET

Flue Size mm 80/125 Concentric or Open Flue

Flue Gas Volume m³/h 46.5

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 140

B/F Max Counter Pressure Diff Pa 140

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 0.6

Power Consumption watt 126

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 30kW LPG

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

WALL HUNG NOx CLASS 4 BIM FLUE VARIANTS

211163

Page 5: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.40kWCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

40kW 360 130 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 6: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 49

Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

Full Load % 89.6

Part Load % 97.8

Seasonal Efficiency % 96.2

Min/Max Gas pressure (Nat Gas) mbar 17.5 - 20.0

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 4.3

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 8-40

Boiler Output (Mean 40°C) kW 8.5-42

Boiler Input (Gross cv) kW 44.9

Gas Inlet Size G¾”

Weighted Power Level dB(A) 53

NOx Rating/emissions at 0% O2 mg/kWh Class 5 (39.1)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 875

Hydraulic Resistance (20°C ∆T) mbar 225

Nominal Flow Rate (11°C ∆T) l/s 0.868

Nominal Flow Rate (20°C ∆T) l/s 0.478

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.09

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 3

FLUE/AIR INLET

Flue Size mm 80/125 Concentric or Open Flue

Flue Gas Volume m³/h 63.4

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 225

B/F Max Counter Pressure Diff Pa 200

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 0.98

Power Consumption watt 207

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 40kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS

211157

Page 7: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.40kW - LPGCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

40kW LPG 360 130 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 8: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 49

Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

Full Load % 91.5

Part Load % 99.5

Seasonal Efficiency % 96.7

Min/Max Gas pressure (Nat Gas) mbar 37

BURNER PRE MIX

Fuel (Type G31) LPG Model

Fuel Consumption (Nat Gas) m³/h 1.69

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 8-40

Boiler Output (Mean 40°C) kW 8.3-41.2

Boiler Input (Gross cv) kW 44

Gas Inlet Size G¾”

Weighted Power Level dB(A) 53

NOx Rating/emissions at 0% O2 mg/kWh Class 4 (80)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 875

Hydraulic Resistance (20°C ∆T) mbar 225

Nominal Flow Rate (11°C ∆T) l/s 0.868

Nominal Flow Rate (20°C ∆T) l/s 0.478

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.08

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 3

FLUE/AIR INLET

Flue Size mm 80/125 Concentric or Open Flue

Flue Gas Volume m³/h 62.1

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 225

B/F Max Counter Pressure Diff Pa 200

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 0.98

Power Consumption watt 207

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 40kW LPG

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

WALL HUNG NOx CLASS 4 BIM FLUE VARIANTS

211164

Page 9: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.60kWCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

60kW 360 130 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 10: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 60.3

Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

Full Load % 89.7

Part Load % 97.9

Seasonal Efficiency % 96.4

Min/Max Gas pressure (Nat Gas) mbar 17.5 - 20.0

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 6.4

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 12-60

Boiler Output (Mean 40°C) kW 12.7 - 63.5

Boiler Input (Gross cv) kW 67.4

Gas Inlet Size G¾”

Weighted Power Level dB(A) 52

NOx Rating/emissions at 0% O2 mg/kWh Class 5 (32.3)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 435

Hydraulic Resistance (20°C ∆T) mbar 83

Nominal Flow Rate (11°C ∆T) l/s 1.3

Nominal Flow Rate (20°C ∆T) l/s 0.716

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.14

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 5

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 60kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

FLUE/AIR INLET

Flue Size mm 80/125 Concentric or 100/150 or Open Flue

Flue Gas Volume m³/h 95.1

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 150

B/F Max Counter Pressure Diff Pa 117

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 0.7

Power Consumption watt 131

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS

211158

Page 11: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.60kW - LPGCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

60kW LPG 360 130 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 12: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 60.3

Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

Full Load % 91.7

Part Load % 99.7

Seasonal Efficiency % 96.9

Min/Max Gas pressure (Nat Gas) mbar 37

BURNER PRE MIX

Fuel (Type G31) LPG Model

Fuel Consumption (Nat Gas) m³/h 2.53

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 15-60

Boiler Output (Mean 40°C) kW 15.5 - 62.1

Boiler Input (Gross cv) kW 66

Gas Inlet Size G¾”

Weighted Power Level dB(A) 52

NOx Rating/emissions at 0% O2 mg/kWh Class 4 (83.8)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 435

Hydraulic Resistance (20°C ∆T) mbar 83

Nominal Flow Rate (11°C ∆T) l/s 1.3

Nominal Flow Rate (20°C ∆T) l/s 0.716

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.17

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 5

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 60kW LPG

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

FLUE/AIR INLET

Flue Size mm 80/125 Concentric or 100/150 or Open Flue

Flue Gas Volume m³/h 93.1

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 150

B/F Max Counter Pressure Diff Pa 117

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 0.7

Power Consumption watt 131

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

WALL HUNG NOx CLASS 4 BIM FLUE VARIANTS

211165

Page 13: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.80kWCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

80kW 360 130 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 14: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 60.3

Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

SEDBUK 2009 % 89.8

Seasonal Efficiency % 97.2

Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 8.7

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 16-80

Boiler Output (Mean 40°C) kW 17.2-84.4

Boiler Input (Gross cv) kW 90.9

Gas Inlet Size G¾”

Weighted Power Level dB(A) 56

NOx Rating/emissions at 0% O2 mg/kWh Class 5 (39.8)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 750

Hydraulic Resistance (20°C ∆T) mbar 180

Nominal Flow Rate (11°C ∆T) l/s 1.736

Nominal Flow Rate (20°C ∆T) l/s 0.955

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.19

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 5

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 80kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

FLUE/AIR INLET

Flue Size mm 80/125 Concentric or 100/150 or Open Flue

Flue Gas Volume m³/h 128.3

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 312

B/F Max Counter Pressure Diff Pa 260

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.4

Power Consumption watt 265

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS

211159

Page 15: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.80kW - LPGCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

80kW LPG 360 130 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 16: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 60.3

Boiler Dimensions mm 850 (H) x 500 (W) x 360 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

SEDBUK 2009 % 90.8

Seasonal Efficiency % 97.7

Min/Max Gas pressure (Nat Gas) mbar 37

BURNER PRE MIX

Fuel (Type G31) LPG Model

Fuel Consumption (Nat Gas) m³/h 3.41

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 20-80

Boiler Output (Mean 40°C) kW 21.2-82.6

Boiler Input (Gross cv) kW 88.9

Gas Inlet Size G¾”

Weighted Power Level dB(A) 56

NOx Rating/emissions at 0% O2 mg/kWh Class 5 (68.0)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 750

Hydraulic Resistance (20°C ∆T) mbar 180

Nominal Flow Rate (11°C ∆T) l/s 1.736

Nominal Flow Rate (20°C ∆T) l/s 0.955

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.23

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 5

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 80kW LPG

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

FLUE/AIR INLET

Flue Size mm 80/125 Concentric or 100/150 or Open Flue

Flue Gas Volume m³/h 125.4

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 312

B/F Max Counter Pressure Diff Pa 260

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.4

Power Consumption watt 265

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS

211166

Page 17: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.100kWCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

100kW 520 226 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 18: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 75.7

Boiler Dimensions mm 850 (H) x 500 (W) x 520 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

SEDBUK 2009 % 89.5

Seasonal Efficiency % 96.7

Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 10.8

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 20-100

Boiler Output (Mean 40°C) kW 21.6-103.9

Boiler Input (Gross cv) kW 113.6

Gas Inlet Size G¾”

Weighted Power Level dB(A) 51

NOx Rating/emissions at 0% O2 mg/kWh Class 5 (39.6)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar N/A

Hydraulic Resistance (20°C ∆T) mbar 134

Nominal Flow Rate (11°C ∆T) l/s N/A

Nominal Flow Rate (20°C ∆T) l/s 1.195

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.23

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 7

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 100kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

FLUE/AIR INLET

Flue Size mm 100/150 Concentric or Open Flue

Flue Gas Volume m³/h 160.3

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 220

B/F Max Counter Pressure Diff Pa 220

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.8

Power Consumption watt 370

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS

211160

Page 19: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.120kWCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

120kW 520 226 118

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 20: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 75.7

Boiler Dimensions mm 850 (H) x 500 (W) x 520 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

SEDBUK 2009 % 89.4

Seasonal Efficiency % 96.6

Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 13.0

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 24-120

Boiler Output (Mean 40°C) kW 26-124.7

Boiler Input (Gross cv) kW 136.4

Gas Inlet Size G¾”

Weighted Power Level dB(A) 54

NOx Rating/emissions at 0% O2 mg/kWh Class 5 (38.8)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar N/A

Hydraulic Resistance (20°C ∆T) mbar 218

Nominal Flow Rate (11°C ∆T) l/s N/A

Nominal Flow Rate (20°C ∆T) l/s 1.43

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.28

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 7

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 120kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

FLUE/AIR INLET

Flue Size mm 100/150 Concentric or Open Flue

Flue Gas Volume m³/h 192.5

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 365

B/F Max Counter Pressure Diff Pa 288

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.9

Power Consumption watt 403

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS

211161

Page 21: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

EVOMAX.150kWCONDENSING - WALL HUNG

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Evomax sales brochure.

BOILER DIM A DIM B DIM C

150kW 610 233 120

Available in outputs of 30, 40, 60, 80, 100, 120 and 150 kW, the Evomax is designed to ensure all installation requirements can be achieved. There is also an LPG Evomax range from 30 – 80 kW for off mains installations.

• Largest range of outputs in market (30 – 150 kW)

• Robust & light aluminium silicon alloy heat exchanger

• Up to 110% part load efficiency

• High 5:1 turndown

• Compact – one width & height for easy siting

• Simple controls interface with large backlit display

• Comprehensive range of options

• Designed for easy installation, commissioning and servicing

• Quality product through design, component selection and proving

• NOx <40mg/kWh (Class 5) for all natural gas models

• 5 year parts and labour warranty

FEATURES AND BENEFITS

All dimensions in mm

TOPDEPENDENT ON

FLUE SIZE

SIDES25mm

BELOW300mm

FRONT450mm

CLEARANCE BETWEEN

MULTIPLE BOILER INSTALLATIONS

25mm

Page 22: EVOMAX. - storage.googleapis.com · MULTIPLE BOILER INSTALLATIONS 25mm For full details of all configurations & specifications, please refer to the Evomax sales brochure. BOILER DIM

TECHNICAL SPECIFICATIONS.

GENERAL

Dry Weight KG 89.75

Boiler Dimensions mm 850 (H) x 500 (W) x 610 (D)

Boiler Clearances mm Front: 450 Side: 25 Below: 300

SEDBUK 2009 % 89.5

Seasonal Efficiency % 96.7

Min/Max Gas pressure (Nat Gas) mbar 17.5-20.0

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 16.2

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 30-150

Boiler Output (Mean 40°C) kW 32.5-158

Boiler Input (Gross cv) kW 170.5

Gas Inlet Size G¾”

Weighted Power Level dB(A) 56

NOx Rating/emissions at 0% O2 mg/kWh Class 5 (38.1)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar N/A

Hydraulic Resistance (20°C ∆T) mbar 230

Nominal Flow Rate (11°C ∆T) l/s N/A

Nominal Flow Rate (20°C ∆T) l/s 1.79

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.35

Min Flow Temperature °C 30

Max Flow Temperature °C 82

Min Working Pressure bar 0.3

Max Working Pressure bar 4

Max Static Head Of Water metres 40.7

Condensate Connection mm 25

High Limit Set Point °C 105 flow, 95 return

Flow & Return Size G1¼”

Water Content litres 9.2

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

EVOMAX 150kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*5 year warranty subject to Terms and Conditions. 5 years parts and labour warranty available subject to being commissioned by Ideal Boilers.

FLUE/AIR INLET

Flue Size mm 100/150 Concentric or Open Flue

Flue Gas Volume m³/h 240.7

Flue Gas Temperature 80/60 °C 70

O/F Max Counter Pressure Diff Pa 430

B/F Max Counter Pressure Diff Pa N/A

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.9

Power Consumption watt 400

Modulating Input V/dc 0-10V or OpenTherm

Fuse Rating amp 4

Controls Voltage V 230 or Low

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm Yes

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Multi Boiler Frame & Header Kits Yes

Modulating Sequencer Kit Yes

Programmable Room Thermostat Kit Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Safety Interlock Kit Yes

Pump Kit Yes

Universal Sequencer Kit Yes

WALL HUNG NOx CLASS 5 BIM FLUE VARIANTS

211162