| P a g e 1. 2008 ENVIRONMENTAL SCORECARD

ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

| P a g e

1.

2008

ENVIRONMENTAL SCORECARD

Page 2: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 2 | P a g e

Foreword In December 2005, the University Council endorsed Charles Sturt University’s (CSU) University Strategy as a document of strategic intent. This strategy identified the responsible stewardship of resources among the University’s key objectives for 2007-2011 and beyond. CSU’s Environmental Scorecard is an annual report that has been developed to provide an open and frank assessment of the University’s progress against its sustainability targets set out in the Institutional Development Plan. This is the second edition of the report and I look forward to further supporting its development in future years. Encouraging progress has been made since 2006 towards the University’s 25% reduction targets in water and energy use by 2011 and 2015 respectively. Despite this progress, there is no doubt that future challenges lie ahead in order for the targets to be realised and the University community must continue to work together to maximise resource efficiency in our day-to-day roles and responsibilities. I would like to thank the staff and students that have already made a contribution to CSU’s sustainability targets through projects that they have been involved in – some of which are outlined in Section 2 of this report. I would also like to congratulate those who have made small changes in their daily routines in the interests of the environment – collectively these actions make a big difference to the University’s footprint.

Professor Ian Goulter Vice Chancellor and President

Page 3: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 3 | P a g e

Executive Summary This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major campuses (Wagga Wagga, Bathurst, Orange, Thurgoona, Albury, Dubbo, Canberra and Broken Hill) for 2008 against values for 2007 and the baseline year, 2006. The purpose of this report is to provide a comparison and commentary of CSU’s performance against the sustainability targets referred to within the University’s Strategic Plan. The University’s Institutional Development Plan (IDP) sets out the following sustainability targets in relation to the baseline year, 2006:

­ reduction in water consumption of 25% by 2011 ­ reduction in energy use of 10% by 2011 & 25% by 2015 ­ to utilise at least 10% of CSU land for the purposes of increasing biodiversity by 2011 and

20% by 2015 ­ to become a no waste University by 2011 ­ to be carbon neutral by 2015

In 2008, an additional 3,596 m2 of gross floor area was commissioned across the University’s building portfolio. This represents an increase of 1.5% of total floor area. Overall, CSU consumed more energy in 2008 than it did in 2007 resulting in a 1.5% increase in stationary energy related greenhouse gas emissions (Figure 0-1). Despite this small increase in energy related greenhouse gas emissions, 2008 figures remained 8.5% below the 2006 baseline year.

Figure 0-1 - Energy related greenhouse gas emissions for all CSU campuses for the period 2006 to 2008

Total water consumption for all CSU campuses reduced significantly from 2007 to 2008 (Figure 0-2). In 2008 water consumption was reduced by 40% compared to the 2006 baseline year. This surpasses the 25% reduction target set for 2011.

Page 4: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 4 | P a g e

Figure 0-2 - Water consumption associated with all CSU campuses for the period 2006 to 2008

Greenhouse gas emissions produced by CSU staff travel activities (vehicle and air travel) have increased significantly since 2006 (Figure 0-3) with increases of 23% and 39% in 2007 and 2008 respectively. It should be noted that some increases in air travel emissions may be attributed to improvements in the centralised collection of data since 2006.

Figure 0-3 - Travel related greenhouse gas emissions associated with CSU operations for the period 2006 to 2008

Page 5: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 5 | P a g e

It should be noted that data contained in this Scorecard has not been normalised for temperature and rainfall variations to provide more accurate comparisons with the baseline data. Current observations in energy and water use (ie apparent increases or decreases) may be influenced in part by climatic variations from one year to the next. These adjustments will be made in future years.

Footprint ready reckoner The following provides some everyday comparisons to the volume of resources consumed and travel undertaken by CSU in 2008.

Resource 2008 Figure Comparisons

Energy 25,954 tonnes CO2 equivalent

2,003 4-person households

Water 448,900,000 litres 2,232 urban 4-person households

448 Olympic-sized swimming pools Vehicle travel 4,940,000 kilometres Annual distance travelled by 345 family

cars Air travel 20,065,623 kilometres 28,142 trips from Sydney to Melbourne

Page 6: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 6 | P a g e

Table of Contents Introduction ............................................................................................................................................ 8 1. University wide analysis ............................................................................................................. 9

1.1. Electricity consumption analysis ..................................................................................... 9 1.2. Gas usage analysis ......................................................................................................... 11 1.3. Water consumption analysis ......................................................................................... 12 1.4. Waste production analysis ............................................................................................ 14 1.5. Motor vehicle travel analysis ........................................................................................ 16 1.6. Air travel analysis .......................................................................................................... 17 1.7. Greenhouse gas emissions analysis .............................................................................. 18 1.8. Planned building additions ............................................................................................ 20

2. Sustainability initiatives implemented in 2008 ........................................................................ 21 3. Wagga Wagga campus analysis ............................................................................................... 23

3.1. Campus information ..................................................................................................... 23 3.2. Electricity audit ............................................................................................................. 23 3.3. Gas audit ....................................................................................................................... 24 3.4. Water audit ................................................................................................................... 24 3.5. Waste audit ................................................................................................................... 25

4. Bathurst campus analysis......................................................................................................... 27 4.1. Campus information ..................................................................................................... 27 4.2. Electricity audit ............................................................................................................. 27 4.3. Gas audit ....................................................................................................................... 27 4.4. Water audit ................................................................................................................... 28 4.5. Waste audit ................................................................................................................... 29

5. Orange campus analysis........................................................................................................... 30 5.1. Campus information ..................................................................................................... 30 5.2. 5.2 Electricity audit ....................................................................................................... 30 5.3. Gas audit ....................................................................................................................... 30 5.4. Water audit ................................................................................................................... 31 5.5. Waste audit ................................................................................................................... 32

6. Thurgoona campus analysis ..................................................................................................... 33 6.1. Campus information ..................................................................................................... 33 6.2. Electricity audit ............................................................................................................. 33 6.3. Gas audit ....................................................................................................................... 34 6.4. Water audit ................................................................................................................... 34 6.5. Waste audit – Thurgoona & Albury .............................................................................. 35

7. Albury campus analysis ............................................................................................................ 37 7.1. Campus information ..................................................................................................... 37 7.2. Electricity audit ............................................................................................................. 37 7.3. Gas audit ....................................................................................................................... 37 7.4. Water audit ................................................................................................................... 38

8. Dubbo campus analysis ............................................................................................................ 39 8.1. Campus information ..................................................................................................... 39 8.2. Electricity audit ............................................................................................................. 39 8.3. Gas audit ....................................................................................................................... 39 8.4. Water audit ................................................................................................................... 40 8.5. Waste audit ................................................................................................................... 40

9. Canberra campus analysis........................................................................................................ 42 9.1. Campus information ..................................................................................................... 42 9.2. Electricity audit ............................................................................................................. 42

Page 7: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 7 | P a g e

9.3. Gas audit ....................................................................................................................... 42 9.4. Water audit ................................................................................................................... 43

10. Broken Hill campus analysis ..................................................................................................... 44 10.1. Campus information ..................................................................................................... 44 10.2. Electricity audit ............................................................................................................. 44 10.3. Water audit ................................................................................................................... 44

11. TEFMA Benchmarking .............................................................................................................. 46 12. Referenced published documents ........................................................................................... 48 13. Appendix A - Conversion factors .............................................................................................. 49 14. Appendix B – Abbreviations & units used ................................................................................ 50 15. Appendix C – Worksheets ........................................................................................................ 51

Page 8: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 8 | P a g e

Introduction

Charles Sturt University as an institution is committed to efficient resource use in facilities across all campuses. This Scorecard reviews the energy and water use and associated costs for CSU’s major campuses (Wagga Wagga, Bathurst, Orange, Thurgoona, Albury, Dubbo, Canberra and Broken Hill) for 2008 against values for 2007 and the baseline year, 2006. The first edition of CSU’s Scorecard was published in 2007 and was titled Energy & Water Scorecard. The scope of the document has grown in 2008 to capture other metrics possessing sustainability targets under CSU’s IDP (eg waste, travel-related GHG emissions). It is envisaged that future editions of the Scorecard will also include a measurement against CSU’s land use target for improving biodiversity as the organisation’s progress in this area matures. Data for CSU’s Goulburn, Manly, Ontario and Parramatta operations is not presented given the University’s role as a tenant/sub-tenant within these facilities. In reviewing resource use associated with the major campuses, the following indicators have been selected:

Electricity consumption in kilowatt hours (kWh) and equivalent tonnes of CO2 emissions

Gas consumption in megajoules (MJ) and equivalent tonnes of CO2 emissions

Mains supplied water consumption in kilolitres (kL)

Waste management costs in dollars ($)a

Travel by university vehicles for business use in kilometres (km), associated fuel use in litres (L) and equivalent tonnes of CO2 emissions

Air travel for university business in kilometres (km) and equivalent tonnes of CO2 emissions

a Dollars used as a proxy for volume of waste produced due to the availability of data. It is envisaged that waste will be

reported in terms of volume in future versions of the Scorecard.

It is important to note that the indicators chosen are those with readily available data, as recorded by Division of Facilities Management and Finance Division. The Environmental Scorecard will be published annually in March for the purposes of assessing CSU’s performance against its sustainability targets and increasing awareness among staff, students and the general community of the measures being taken to address these targets. It is noted that the 2007 version of the Scorecard utilised a European conversion factor for calculating electricity-related GHG emissions. The 2008 version utilises the appropriate factor for NSW-based electricity generation. In addition, a quality review process for collated data was introduced to the preparation of the 2008 Scorecard that involved a revision of 2006 and 2007 data. As a result, there are several minor variations in values presented in the 2007 version compared to the current.

Page 9: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 9 | P a g e

1. University wide analysis

1.1. Electricity consumption analysis

In 2008, a small increase in electricity consumption across all campuses was observed compared to 2007. The increase represented 1.4% of 2006 electricity use. Overall the University used 4.5% less electricity in 2008 than the baseline year, 2006.

Figure 1-1 - Electricity use across all CSU campuses

Wagga Wagga and Bathurst campuses were the largest users of electricity accounting for 52% and 30% respectively in 2008 (Figure 1-2). Orange, Albury, Thurgoona, Dubbo, Canberra and Broken Hill collectively represented 18% of CSU’s electricity use.

Figure 1-2 - Proportion of total electricity used by each CSU campus in 2008

Analysing electricity consumption for each campus against gross floor area provides a means of comparing the intensity of electricity use by the varied-sized campuses (Figure 1-3). In 2008, Wagga Wagga and Bathurst campuses were the most intensive users of electricity at 111 and 94 kWh/m2 of gross floor area (GFA) respectively. Canberra was the least intensive electricity user at 29 kWh/m2.

Page 10: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 10 | P a g e

These results highlight the challenges associated with the efficient operation of large campuses such as Wagga Wagga and Bathurst that comprise a multitude of decentralised plant, buildings and equipment. It is likely that the figure for Albury campus is suppressed as a result of staff and students being relocated to the Thurgoona campus and population densities being reduced. Conversely, efficiencies gained at the Thurgoona campus figurers have been offset as a result of staff and student relocations to the site. It is noted that the 2007 Scorecard analysed energy and water use by useable floor area rather than gross floor area. Gross floor area will be used in future versions of the scorecard to ensure consistency with the industry standard for normalisation.

Figure 1-3 - Electricity use intensity comparison, based on gross floor area, for CSU campuses in 2008 compared to 2006

A summary of electricity related charges (summation of network and usage charges) is provided in Table 1-1. Average electricity market prices have increased by more than 16% between the 2005/2006 and 2008/2009 financial years (NEMMCO, 2009). CSU entered new supply agreements at several of its campuses during this period. CSU’s total electricity related charges have increased by 14.8% from 2006 to 2008 as a result of increased prices, despite a 5.1% reduction in electricity use over the same period. It is noted that a billing anomaly for Thurgoona occurred throughout 2006 and 2007 period which resulted in a one off back-charge of approximately $45,000 being applied by the retailer in the 2008 reporting period.

Table 1-1 - Electricity related charges for CSU campuses in 2008

Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra Broken Hill

CSU Total

2006 $1,131,187 $869,331 $176,030 $118,115 $134,121 $52,594 $2,521 $9,493 $2,483,899

2007 $1,181,730 $872,142 $160,039 $138,153 $163,858 $43,900 $4,566 $9,493 $2,564,389

2008 $1,331,488 $881,137 $214,900 $159,492 $210,979 $44,458 $7,933 $29,044 $2,850,387

Page 11: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 11 | P a g e

1.2. Gas usage analysis

In 2008, a small increase in natural gas consumption across all campuses was observed compared to 2007 (Figure 1-4). The increase represented 2.1% of 2006 natural gas use. Overall the University consumed 11.3% less natural gas in 2008 than the baseline year, 2006. A rudimentary review of climate data associated with campus locations indicates that 2007 had a more mild winter than 2006 with mean minimum monthly temperatures being consistent or slightly above the long term average. The winter of 2008 was also observed to be more mild than 2006. The affect of a more mild winter is reduced heating loads to buildings and hot water.

Figure 1-4 – Natural gas consumption across all CSU campuses

Wagga Wagga and Bathurst campuses were the largest users of natural gas accounting for 47% and 43% respectively in 2008 (Figure 1-5). Orange, Albury, Thurgoona, Dubbo and Canberra collectively represented 10% of CSU’s natural gas use.

Figure 1-5 - Proportion of total natural gas used by each CSU campus in 2008

Page 12: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 12 | P a g e

In 2008, Bathurst campus was the most intensive user of natural gas by a significant margin at 579 MJ/m2 of GFA followed by Wagga Wagga campus at 437 MJ/m2. Orange was the least intensive natural gas user at 90 MJ/m2. These trends, in part, can be attributed to the relatively cool winter climates experienced in Bathurst compared to the other campuses and the fact that most existing buildings on the Orange campus are fitted with electric rather than gas heating.

Figure 1-6 – Natural gas use intensity comparison, based on gross floor area, for CSU campuses in 2008 compared to 2006

A summary of natural gas related charges (summation of network and usage charges) is provided in Table 1-2. CSU’s total natural gas related charges have increased by 7.1% from 2006 to 2008 as a result of the increased prices, despite an 11.3% reduction in natural gas consumption over the same period. Natural gas supply agreements for the campuses are with several different suppliers. For each of these, usage charges have generally been revised on an annual basis. Using Wagga Wagga Campus as an example, natural gas usage charges per MJ increased by 3.7% from 2006 to 2007 and by 4.3% from 2007 to 2008.

Table 1-2 – Natural gas related charges for CSU campuses in 2008

Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra CSU Total

2006 $442,589 $315,458 $26,880 $49,318 $42,761 $21,093 $1,650 $899,749 2007 $403,199 $310,794 $21,806 $43,385 $30,067 $17,723 $2,211 $829,184 2008 $407,021 $425,419 $26,396 $40,912 $33,720 $26,320 $4,263 $964,052

1.3. Water consumption analysis

In 2008, CSU experienced a significant reduction in mains supplied water use compared to 2007 (Figure 1-7). The reduction represents 16.1% of 2006 water use. Overall the University consumed 40.0% less mains supplied water in 2008 than the baseline year, 2006. This result surpasses the University’s target of a 25% reduction on 2006 water use. It is noted that the term mains supplied water is used over potable water due to Bathurst campus receiving a raw water supply for irrigation purposes. Water supplied from both potable and raw water supplies has been included in the data for Bathurst campus.

Page 13: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 13 | P a g e

Figure 1-7 – Mains supplied water consumption across all CSU campuses for the period 2006 to 2008

Wagga Wagga and Bathurst campuses were the largest users of mains supplied water accounting for 67% and 23% respectively in 2008 (Figure 1-8). Orange, Albury, Thurgoona, Dubbo, Canberra and Broken Hill collectively represented 10% of CSU’s mains supplied water consumption.

Figure 1-8 - Proportion of total mains supplied water used by each CSU campus in 2008

In 2008, Wagga Wagga was the most intensive user of mains supplied water at 2.7 kL/m2 of GFA. Thurgoona and Broken Hill campuses were the least intensive water users at 0.3 kL/m2. These trends, in part, can be attributed to water use for irrigation of vineyards, glasshouses, playing fields and selected lawn areas at Wagga Wagga campus. Canberra campus’ water use intensity has been observed to decrease significantly with the commissioning of water efficient new facilities. Thurgoona is deemed a low intensity water user due to the absence of irrigated playing fields or lawn areas and a very high composition of indigenous plants making up landscaped areas. The limited number of evaporative coolers and cooling towers present at the Thurgoona campus is another contributing factor.

Page 14: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 14 | P a g e

Figure 1-9 – Mains supplied water use intensity comparison, based on gross floor area, for CSU campuses in 2008 compared to 2006

A summary of water related charges (summation of network and usage charges) is provided in Table 1-3. CSU’s total water related charges have decreased by 24.2% from 2006 to 2008 representing an annual saving of more than $140,000. Each of CSU’s campuses is supplied water from a different water utility. Price increases did occur from 2006 to 2008, however these varied across the campuses. Bathurst campus experienced the greatest price increase with the cost of filtered water increasing by 35% from January 2006 to August 2008. It is noted that the apparent cost reductions at the Canberra campus are a result of a faulty revenue meter.

Table 1-3 - Water related charges for CSU campuses in 2008

Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra Broken Hill

CSU Total

2006 $315,483 $153,799 $73,225 $12,676 $8,940 $20,379 $3,174 $3,025 $590,701 2007 $246,893 $134,813 $57,908 $30,521 $13,321 $30,259 $5,097 $2,340 $521,151 2008 $227,979 $88,622 $47,358 $25,989 $13,075 $36,482 $2,702 $2,230 $444,437

1.4. Waste production analysis

Waste management costs have been collated for this analysis due to data on actual volumes of waste produced not being available for each of the campuses. Reporting processes have been established to allow this data to be compiled for 2009 and into the future. It is noted that waste management costs do not provide an ideal proxy for volumes of waste produced by waste type. This is due to single suppliers providing individual invoices for services that in some cases cover multiple waste streams (eg general waste and recycling). In 2008, waste management related charges reduced by 9.1% compared to the baseline year, 2006 (Figure 1-10). This reduction in charges is primarily attributable to changes in the way that waste is managed at the Wagga Wagga Campus. A compactor is now housed at the site that has the ability to reduce general waste down by 75 – 80% of its original volume. This process reduces that number of

Page 15: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 15 | P a g e

trips to site that are required from the waste contractor and the embedded energy associated with transportation of the waste to landfill. It is noted that the introduction of a closed-loop organics recycling scheme and co-mingled recycling to the Wagga Wagga campus is also expected to have reduced the total volume of general waste going to landfill.

Figure 1-10 – Waste management related charges for Wagga Wagga, Bathurst, Orange, Thurgoona, Albury and Dubbo campuses for the period 2006 to 2008

General waste to landfill represents approximately 50% of CSU’s waste management costs (Figure 1-11). There has been a 17.4% reduction in the cost of managing general waste in 2008 compared to 2006. Recycling and sanitary waste represent a similar proportion of CSU’s waste management costs, both fluctuating between 22% and 28%. Compost, liquid waste and bulk dumping management costs typically represent less than 3% of total waste management costs.

Figure 1-11 - Break down of waste management costs for all campuses, by waste stream, for the period 2006 to 2008

Page 16: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 16 | P a g e

In 2008, Wagga Wagga campus comprised 44% of CSU’s waste management costs (Figure 1-12). Combined costs for Thurgoona and Albury campuses were the next largest contributors at 27%.

Figure 1-12 – Proportion of waste management related charges, by campus, for 2008

Electronic waste or E-waste (computers and peripheral devices) is not captured by the categories provided above. For several years, CSU’s Division of IT (DIT) has practised a policy of no E-waste to landfill. For the period 2005-2008, E-waste was disposed of via an appropriate recycling agent. In 2008, these disposal practices became cost prohibitive and a new process of renovating computers and selling via auction has been utilised. In 2008, 140 desktop computers were sold at a profit of $13,900. This money is redirected by the Executive Director, DIT back into sustainability related projects throughout CSU. It is noted that computers that are considered obsolete are still disposed of via a recycling agent to minimise the risk of such equipment quickly becoming disposed of via landfill.

1.5. Motor vehicle travel analysis

Data relating to fuel consumption by CSU vehicles on business related travel has been collated as a rolled-up figure. A breakdown of fuel use, by fuel type (eg ULP, diesel, LPG) is planned for future versions of the Scorecard. In 2008, there was a 5% increase in the volume of fuel consumed by CSU vehicle on business related travel (Figure 1-13). This increase is attributed to a 10.7% increase in the number of kilometres that were travelled by University vehicles compared to 2006 (Figure 1-14) and is likely to have been offset to some extent by improvements in fuel efficiency of the vehicle fleet.

Page 17: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 17 | P a g e

Figure 1-13 - Litres of fuel consumed by CSU vehicles for business related travel

Figure 1-14 - Kilometres travelled by CSU vehicles for business related travel

1.6. Air travel analysis

In 2008, there was an 89% increase in the number of kilometres travelled by CSU staff on domestic flights and a 37% increase in kilometres travelled on international flights compared to 2006. These two figures combined represent a 45% increase in total flight kilometres. It is noted that improvements in the centralised collation of travel data since 2006 may provide an apparent increase air travel (ie not all flights taken by CSU staff were captured in 2006).

Page 18: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 18 | P a g e

Figure 1-15 - Kilometres travelled by CSU staff on domestic and international flights for the period 2006 to 2008

1.7. Greenhouse gas emissions analysis

A summary of greenhouse gas (GHG) emissions associated with the consumption of stationary energy at all CSU campuses is provided in Table 1-4. These figures follow the trends associated with electricity and natural gas consumption. In 2008, there was a 8.5% reduction in the volume of energy related GHG emissions compared to 2006. A significant contributor to the reduced energy related greenhouse gas emissions that is not highlighted through reductions in electricity and natural gas consumption, is the decommissioning of a coal fired boiler at Bathurst campus in mid-2006. Table 1-4 - Greenhouse gas emissions associated with stationary energy consumption (electricity, natural gas and coal) for each CSU campus (shown in Tonnes CO2 equivalent). Percentage change represents difference from the 2006 baseline year

Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra Broken Hill

CSU Total

% Change

2006 14253 9868 1417 1072 1235 432 33 56 28367 2007 13534 8447 1327 983 725 406 44 56 25522 -10.0% 2008 13282 8467 1601 919 1026 431 50 178 25954 -8.5%

In 2008, Wagga Wagga campus represented 51% of CSU’s combined energy use while Bathurst was then next highest user at 33%. Combined energy use at the other five campuses comprised 16% of energy use.

Page 19: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 19 | P a g e

Figure 1-16 - Proportion of energy related greenhouse gas emissions for each CSU campus in 2008

In 2008, there was a 0.2% decrease in total GHG emissions associated with energy use and travel compared to 2006 (Figure 1-17). This shows that the GHG savings achieved through an 8.5% reduction in energy use have been nearly offset by increases in vehicle use and air travel. Overall it is estimated that travel related activities accounted for 25% of CSU’s total GHG emissions in 2008 (Figure 1-18). GHG emissions associated with stationary energy consumption were responsible for 75% of the total.

Figure 1-17 - Combined energy and travel related greenhouse gas emissions for CSU during the period 2006 to 2008

Page 20: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 20 | P a g e

Figure 1-18 - Breakdown of CSU's GHG emissions by source type for 2008

1.8. Planned building additions

CSU has experienced a period of significant building development since 2006 with the introduction of Veterinary Science, Dentistry and Health Sciences to the University’s course range. In addition is the final stage of development associated with the Albury-Wodonga Campus Relocation Project. As a result of these factors, significant construction is planned to continue on CSU campuses out until 2011. The net affect of planned construction activities and CSU vacating the Albury City Campus will be a 13% increase in building GFA by 2012. Inherently energy intensive operations such as laboratories, specialist teaching spaces and clinics form a large component of the proposed new buildings. CSU faces a real challenge in achieving a 25% reduction in energy consumption by 2015 in light of the proposed expansion activities that are to occur. This target will only be reached through significant investment in energy efficiency measures within existing building stock and setting stringent performance targets for all new facilities.

Page 21: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 21 | P a g e

2. Sustainability initiatives implemented in 2008

This section of the Scorecard is intended to provide a high-level overview of the various sustainability initiatives that have been implemented across CSU in 2008. These initiatives are summarised in Table 2-1.

Table 2-1 - Summary of sustainability projects implemented across CSU in 2008

Target area Campus Project overview Expected outcomes

Energy Wagga Wagga Education and awareness program for student residences

Involved in house displays for energy consumption and social marketing initiatives

Received $72,631 contribution from NSW Government’s Public Facilities Program

Partnership project with Country Energy and Landis+Gyr

15 – 18% reduction in energy use within targeted residences

Provide findings that can be applied to a University-wide project

Energy & sustainability

Thurgoona Opening of Academic Accommodation Stage 3 Pending assessment of 6-Star As Designed Green Star submission representing “World Leader” in sustainable building design

Energy & water Wagga Wagga Energy efficiency improvements to light fittings Installation of power factor correction equipment Water efficiency improvements in amenity areas Received $77,000 contribution from NSW Government’s

Public Facilities Program Required $300,000 investment by CSU

463,000 kWh of electricity savings per year 4,430,000 L of potable water savings per year

Sustainability All campuses Signing onto the NSW Department of Environment & Climate Change’s Sustainability Advantage Program

Formalised assessment of CSU’s current systems & processes to support sustainability

Implementation plan and access to resources to improve current processes

Waste All DIT computer renovation and resale 140 computers re-sold rather than disposed of via recycling or landfill

$13,900 profit from sales reinvested into sustainability projects

Waste Bathurst Bokashi bin (composting of organics) trial commenced Redirecting organic waste from landfill

Page 22: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 22 | P a g e

Target area Campus Project overview Expected outcomes

Waste Dubbo Introduction of co-mingled recycling bins Redirecting recyclable plastics and aluminium cans from landfill

Waste Wagga Wagga Commencement of closed-loop organic recycling scheme

Approximately 200 tonnes of waste per year redirected from landfill

Waste Wagga Wagga Introduction of co-mingled recycling bins Redirecting recyclable plastics and aluminium cans from landfill

Water Bathurst Installation of Muller 3C cooling tower to replace conventional open loop cooling tower

New cooling tower has the ability to operate in a dry mode when ambient temperatures are suitable

80% reduction in potable water compared to conventional cooling tower

Water Thurgoona Grey water recycling ponds upgrade Received $45,499 of support from Australian

Government’s Community Water Grants

More effective treatment of wastewater generated on the campus

Water Wagga Wagga Upgrade of dam and pump facilities to supply stormwater for irrigation and compost production

Received $16,500 of support from Australian Government’s Community Water Grants

500,000 L of potable water savings per year

Water Wagga Wagga Inclusion of rainwater harvesting project in new Veterinary Clinic Building

Provides water for hosing down of hard surfaces in animal holding pens

Received $49,905 of support from Australian Government’s Community Water Grants

720,000 L of potable water savings per year

Water Wagga Wagga Conversion of ornamental lake to stormwater top-up More than 10,000,000 L of potable water saved per year

Water All campuses Trial of waterless urinal technologies Will determine whether University-wide implementation of technology is feasible

Page 23: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 23 | P a g e

3. Wagga Wagga campus analysis

3.1. Campus information

Total building gross floor area (m2) 109,967 Student headcount - 2007 12,230 (3,164 internal; 9,066

distance) Site area (hectares) 82

(42 actively managed; 40 woodland) Student residences 1,262

(50 St Francis College; 92 St Martins College)

Significant plant and/or facilities wine & cheese production facilities

printery

2 irrigated playing fields

swimming pool

gymnasium

glasshouses

irrigated vineyards

The Wagga Wagga campus of Charles Sturt University is divided into the north and south campuses. The data provided combines energy and water consumption for both campuses. In 2008, there was a 5.1% reduction in electricity use at Wagga Wagga campus compared with 2006 (Figure 3-1). This figure is a further improvement on the 3.3% reduction achieved in 2007. An additional 1,700 m2 of GFA was added to the Wagga Wagga Campus in 2008 as a result of the commissioning of the Vet Science Clinical Building and extensions to the CD Blake Experimental Winery.

3.2. Electricity audit

Figure 3-1 - Electricity consumption at Wagga Wagga campus for the period 2006 to 2008

Page 24: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 24 | P a g e

3.3. Gas audit

In 2008, there was 13.6% reduction in the consumption of natural gas at Wagga Wagga campus compared to 2006 (Figure 3-2). This change represents a 1.7% reduction from 2007.

Figure 3-2 – Natural gas consumption at Wagga Wagga campus for the period 2006 to 2008

3.4. Water audit

In 2008, there was 28.8% reduction in the consumption of potable water at Wagga Wagga campus compared to 2006 (Figure 3-3). This change represents a further 15.4% reduction from that achieved in 2007. Wagga Wagga campus has surpassed its 25% reduction target for potable water. The significant water savings at the campus are attributed to the voluntary implementation of level 4 water restrictions on all irrigated areas except playing fields, progressive installation of sub-surface irrigation where feasible, conversion of an ornamental lake to stormwater make-up, extensive use of mulch to reduce evaporation from landscaped areas and the implementation of a stormwater harvesting project to provide water for irrigation and compost-processing requirements.

Page 25: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 25 | P a g e

Figure 3-3 – Mains supplied water consumption at Wagga Wagga campus for the period 2006 to 2008

3.5. Waste audit

In 2008, there was a 36.1% reduction in the cost of waste management at Wagga Wagga campus compared to 2006 (Figure 3-4). This reduction in charges is primarily attributable to changes in the way that waste is managed at the site. A compactor is now housed at the site that has the ability to reduce general waste down by 75 – 80% of its original volume. This process reduces that number of trips to site that are required from the waste contractor and the embedded energy associated with transportation of the waste to landfill. Although the actual volumes of various waste streams produced by the campus were not measured throughout 2008, observations suggest that the commencement of a closed-loop organics recycling scheme and co-mingled recycling have also reduced the total volume of general waste going to landfill. It is noted that the costs presented in this figure do not include labour and blending materials required for the management of the organics recycling scheme. A detailed analysis of the cost and benefits associated with the management of the scheme was completed with funding made available through Riverina Eastern Regional Organisation of Councils . This analysis demonstrated that the scheme had a net financial benefit in that the treated product from the recycling scheme could be produced at a lower cost than soil improvers that were previously purchased and imported on to the campus.

Page 26: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 26 | P a g e

Figure 3-4 - Costs associated with waste management at Wagga Wagga campus for the period 2006 to 2008

Page 27: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 27 | P a g e

4. Bathurst campus analysis

4.1. Campus information

Total building gross floor area (m2) 74,729 Student headcount - 2007 9,367 (2,981 internal; 6,386

distance) Site area (hectares) 74 (56 actively managed) Student residences 1,180 Significant plant and/or facilities printery

2 irrigated playing fields

gymnasium

centralised low pressure hot water boilers

4.2. Electricity audit

In 2008, there was 7.7% reduction in the consumption of electricity at Bathurst campus compared to 2006 (Figure 4-1). This change represents a further 2% reduction from 2007.

Figure 4-1 - Electricity consumption at Bathurst campus for the period 2006 to 2008

4.3. Gas audit

In 2008, there was 6.7% increase in the consumption of natural gas at Bathurst campus compared to the previous year (Figure 4-2). Despite this increase, overall natural gas use at Bathurst in 2008 remained 4.8% below that used in the 2006 baseline year. Factors that may have contributed to the observed increase in natural gas use in 2008 include the operation of the 4 additional Windradyne Colleges for the full year (commissioned mid-2007) and a cooler winter in 2008 compared to 2007.

Page 28: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 28 | P a g e

Figure 4-2 - Natural gas consumption at Bathurst campus for the period 2006 to 2008

4.4. Water audit

In 2008, there was 50.3% reduction in the consumption of mains supplied water at Bathurst campus compared to 2006 (Figure 4-3). This change represents a further 26.7% reduction from that achieved in 2007. Bathurst campus has surpassed its 25% reduction target for mains supplied water. The primary factor for the observed reductions in water use at the Bathurst campus is attributed to changes in irrigation. The decommissioning of the site’s golf course in 2008 and the elimination of its associated irrigation requirements is one such change.

Figure 4-3 – Water consumption at Bathurst campus for the period 2006 to 2008

Page 29: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 29 | P a g e

4.5. Waste audit

In 2008, there was a 17.3% increase in the cost of waste management at Bathurst campus (Figure 4-4). The only driver for this increase in costs was associated with sanitary waste. Small savings were achieved in the areas of general waste and recycling management costs.

Figure 4-4 - Costs associated with waste management at Bathurst campus for the period 2006 to 2008

Page 30: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 30 | P a g e

5. Orange campus analysis

5.1. Campus information

Total building gross floor area (m2) 20,498 Student headcount - 2007 605 (325 internal; 493 distance) Site area (hectares) 49 actively managed Student residences 172 Significant plant and/or facilities 1 irrigated playing field

irrigated vineyards

predominantly electric room heating

5.2. 5.2 Electricity audit

In 2008, there was 13.2% increase in the consumption of electricity at Orange campus compared to 2006 (Figure 5-1). This upwards trend follows from a 6.5% saving achieved in 2007. There are no obvious reasons for the increase in electricity consumption at this campus. It is likely that climatic factors and extensive construction activities on site did contribute.

Figure 5-1 – Electricity consumption at Orange campus for the period 2006 to 2008

5.3. Gas audit

In 2008, there was 10.9% increase in the consumption of natural gas at Orange campus compared to 2006 (Figure 5-2). This upwards trend follows from a 3.1% saving achieved in 2007. There are no obvious reasons for the increase in gas consumption at this campus. As with electricity, it is likely that climatic factors did contribute.

Page 31: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 31 | P a g e

Figure 5-2 - Natural gas consumption at Orange campus for the period 2006 to 2008

5.4. Water audit

In 2008, there was 53.6% reduction in the consumption of potable water at Orange campus compared to 2006 (Figure 5-3). This change represents a further 30.6% reduction from that achieved in 2007. Orange campus has surpassed its 25% reduction target for potable water. It is noted that 2008 experienced substantially higher summer rainfall than 2007 or 2006 which may have reduced demand on potable water supply for irrigation requirements.

Figure 5-3 - Water consumption at Orange campus for the period 2006 to 2008

Page 32: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 32 | P a g e

5.5. Waste audit

In 2008, there was a 71.2% increase in the cost of waste management at Orange campus (Figure 5-4). The primary driver for this increase in costs was associated with general waste. Small increases were also observed in the cost of managing sanitary waste.

Figure 5-4 - Costs associated with waste management at Orange campus for the period 2006 to 2008

Page 33: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 33 | P a g e

6. Thurgoona campus analysis

6.1. Campus information

Total building gross floor area (m2) 15,062 Student headcount - 2007 3,327a (1,889 internal, 1,338

distance) Site area (hectares) 90.2 Student residences 246 Significant plant and/or facilities grey water treatment ponds

several passive buildings a – This figure also includes Albury student numbers

CSU’s Thurgoona campus is progressively expanding to accommodate staff and students from Albury campus. By 2010, it is planned that all CSU operations at the Albury campus will be relocated to Thurgoona. There is a high level of ecological sustainable design (ESD) incorporated into buildings on the Thurgoona campus compared to other campuses. These ESD initiatives operate with varying degrees of success however have provided CSU with many insights into passive building design. The most recent addition to the Campus, Academic Accommodation Stage 3, was pending a determination of a 6-Star Green Star As Designed rating at the time of this Scorecard being developed.

6.2. Electricity audit

In 2008, there was a 12.2% reduction in electricity use at Thurgoona campus compared with 2006 (Figure 6-1). This is an increase on 2007 figures during which 41.2% less electricity was used than in 2006. Air conditioning equipment in the Gums Café that was not operational throughout 2007 was used throughout 2008. This factor along with extensive construction activities on site and the commissioning of Academic Accommodation, Stage 3 in late 2008 would have contributed to the observed increase in electricity use in 2008.

Page 34: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 34 | P a g e

Figure 6-1 - Electricity consumption at Thurgoona campus for the period 2006 to 2008

6.3. Gas audit

In 2008, there was a 59.5% reduction in electricity use at Thurgoona campus compared with 2006 (Figure 6-2). This is an increase on 2007 figures during which 71.7% less electricity was used than in 2006. A significant boiler on the site was out of operation in 2007 which may have contributed to the slight increase in 2008.

Figure 6-2 - Natural gas consumption at Thurgoona campus for the period 2006 to 2008

6.4. Water audit

In 2008, there was 48.9% reduction in the consumption of potable water at Thurgoona campus compared to 2006 (Figure 6-3). This change represents a further 41.7% reduction from that achieved in 2007. Thurgoona campus has surpassed its 25% reduction target for potable water.

Page 35: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 35 | P a g e

Improved utilisation of the rainwater harvesting system at Thurgoona campus in 2008 is considered the major factor that has contributed to the observed reductions in water use.

Figure 6-3 - Water consumption at Thurgoona campus for the period 2006 to 2008

6.5. Waste audit – Thurgoona & Albury

Consolidated contracts and invoicing are in place for waste management at Thurgoona and Albury campuses. As a result, the available data for 2008 cannot be separated between the two campuses. In 2008, there was a 43.8% increase in the cost of waste management at Thurgoona & Albury campuses (Figure 6-4). The primary driver for this increase in costs was associated with general waste. Small increases were also observed in the cost of managing recycling. It is noted that a single service provider supplies bin hire for both general and recyclable waste. This provides some distortion in the apparent increase to the cost of managing general waste. Clean-up and relocation activities that have occurred at the Albury City Campus throughout 2008 are the main likely causes for the increase in waste management costs.

Page 36: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 36 | P a g e

Figure 6-4 - Costs associated with waste management at both Thurgoona and Albury campuses for the period 2006 to 2008

Page 37: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 37 | P a g e

7. Albury campus analysis

7.1. Campus information

Total building gross floor area (m2) 11,857 Student headcount - 2007 3,327a (1,889 internal, 1,338

distance) Student residences 0 Significant plant and/or facilities N/A

a – This figure also includes Thurgoona student numbers

The majority of Albury campus is being relocated to the Thurgoona site via staged development. It is proposed that most staff and students will be relocated by early 2010. It is likely that reduced student and staff numbers on the campus have contributed to the observed reductions in electricity, gas and water consumption at the site.

7.2. Electricity audit

In 2008, there was a 7.9% reduction in electricity use at Albury campus compared with 2006 (Figure 6-1). This represents an additional 3.6% decrease from 2007 figures during which 4.3% less electricity was used than in 2006.

Figure 7-1 - Electricity consumption at Albury campus for the period 2006 to 2008

7.3. Gas audit

In 2008, there was a 35.4% reduction in natural gas use at Albury campus compared with 2006 (Figure 7-2). This represents an additional 14% decrease from 2007 figures during which 21.3% less natural gas was used than in 2006.

Page 38: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 38 | P a g e

Figure 7-2 – Natural gas consumption at Albury campus for the period 2006 to 2008

7.4. Water audit

In 2008, there was a 34.9% reduction in water use at Albury campus compared with 2006 (Figure 7-3). This follows from an increase of 10.5% that was observed during 2007 compared to 2006.

Figure 7-3 - Water consumption at Albury campus for the period 2006 to 2008

Page 39: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 39 | P a g e

8. Dubbo campus analysis

8.1. Campus information

Total building gross floor area (m2) 5,758 Student headcount - 2007 433 (385 internal; 48 distance) Site area (hectares) 41.4 (11 actively managed) Student residences 62 Significant plant and/or facilities Shower towers providing cooling

to Stage 1 building (scheduled for decommissioning in 2009)

8.2. Electricity audit

In 2008, there was a 2.3% reduction in electricity use at Dubbo campus compared with 2006 (Figure 8-1). This represents a very small increase of 0.2% over 2007 electricity consumption.

Figure 8-1 – Electricity consumption at Dubbo campus for the period 2006 to 2008

8.3. Gas audit

In 2008, there was an 8.1% increase in natural gas use at Dubbo campus compared with 2006 (Figure 8-2). This follows from a decrease of 20% in 2007 compared to 2006. There are no obvious reasons for the increase in gas consumption at this campus. It is likely that climatic factors did contribute.

Page 40: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 40 | P a g e

Figure 8-2 – Natural gas consumption at Dubbo campus for the period 2006 to 2008

8.4. Water audit

In 2008, there was a 46.5% reduction in water use at Dubbo campus compared with 2006 (Figure 8-3). This is an additional decrease of 3.9% compared to that achieved in 2007. Dubbo campus has surpassed its 25% reduction target for potable water.

Figure 8-3 - Water consumption at Dubbo campus for the period 2006 to 2008

8.5. Waste audit

In 2008, there was an 8.5% increase in the cost of waste management at Dubbo campus compared to 2006 (Figure 8-4). The primary driver for this increase in costs was associated with liquid waste management. There was a peak in waste management costs in 2007 where increases to both general waste and sanitary waste resulted in a 38.4% increase compared with 2006.

Page 41: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 41 | P a g e

Figure 8-4 - Costs associated with waste management at Dubbo campus for the period 2006 to 2008

Page 42: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 42 | P a g e

9. Canberra campus analysis

9.1. Campus information

Total building gross floor area (m2) 871 Student headcount - 2007 356 (41 internal; 315 distance) Site area (hectares) 3.4 Student residences 0 Significant plant and/or facilities High-quality landscaped gardens

9.2. Electricity audit

In 2008, there was a 61.2% increase in electricity use at Canberra campus compared with 2006 (Figure 9-1). This also represents a significant increase of 28.1% on 2007 figures. The observed increase in electricity consumption at the Canberra campus is attributed to the commissioning of the Academic House building comprising approximately 770 m2 of GFA. The new building has been constructed with energy efficiency principles and it is anticipated that these efficiencies will be realised as staff continue to relocate into the new building from older facilities.

Figure 9-1 - Electricity consumption at Canberra campus for the period 2006 to 2008

9.3. Gas audit

In 2008, there was a 3.6% increase in natural gas consumption at Canberra campus compared with 2006 (Figure 9-2). This is a significant step down from 2007 when natural gas use was 33.9% greater than in 2007.

Page 43: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 43 | P a g e

Figure 9-2 – Natural gas consumption at Canberra campus for the period 2006 to 2008

9.4. Water audit

In 2008, there was a problem with the revenue meter associated with the Canberra campus resulting in no water use being measured. Consumption at the site has been assumed to remain at 2007 levels in 2008.

Figure 9-3 - Water consumption at Canberra campus for the period 2006 to 2008

Page 44: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 44 | P a g e

10. Broken Hill campus analysis

10.1. Campus information

Total building gross floor area (m2) 5,041 Student residences 0 Site area (hectares) 1 Significant plant and/or facilities Large proportion of building area

leased to tenant

10.2. Electricity audit

No electricity consumption data was available for Broken Hill campus in 2006. An assumption has been made that 2006 consumption was consistent with 2007. A 216% increase in electricity use was observed in 2008 compared to 2007 (Figure 10-1). The significant increase in electricity use in 2008 is attributed to the leasing of a significant area of the facility to an external tenant. Refrigerative air conditioning equipment was installed to service the newly tenanted space. The previous tenants in the facility were separately metered for their electricity use.

Figure 10-1 - Electricity consumption at Broken Hill campus for the period 2006 to 2008

It is noted that the Broken Hill campus is not connected to a natural gas supply.

10.3. Water audit

In 2008, there was a 37.6% reduction in water use at the Broken Hill campus compared to 2006 (Figure 10-2). The observed reduction in water use is attributed to the fact that a tenanted area of the facility was previously occupied by a nursing home facility which has since been converted to office and teaching space. The new use for this area of the building has a significantly lower water demand.

Page 45: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 45 | P a g e

Figure 10-2 - Water consumption at Broken Hill campus for the period 2006 to 2008

Page 46: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 46 | P a g e

11. TEFMA Benchmarking

The Tertiary Education Facilities Management Association (TEFMA) each year undertakes a benchmarking exercise of University facilities. In 2007, energy was considered in detail and CSU performance can be tracked against all other institutions and the sector mean for a range of parameters. Data from TEFMA’s 2008 benchmarking survey was not available at the time that this Scorecard was developed. This comparison is based on the gross floor area of core university buildings and therefore excludes residences and enterprises. Figure 11-1 shows normalised energy use (GJ/m2), for all of CSU’s core facilities against the mean value calculated for all Australian universities. CSU consistently rates above the mean figure, however recent trends have shown the difference to be closing.

Figure 11-1 - Normalised energy use (GJ/m2) for all core CSU facilities against the mean for all Australian universities

1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007

AU MEAN 0.72 0.54 0.54 0.67 0.64 0.63 0.69 0.66 0.67 0.69 0.73 0.71 0.72 0.73 0.72

CSU ALL 0.87 1.01 0.89 0.85 0.94 0.95 0.93 0.92 0.82 1.16 1.22 0.85 0.83 0.81

0

0.2

0.4

0.6

0.8

1

1.2

1.4

Page 47: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 47 | P a g e

Figure 11-2 shows normalised water use (kL/m2), for all of CSU’s core facilities against the mean value calculated for all Australian universities. CSU consistently rates significantly above the mean figure. CSU’s normalised figure will drop significantly for 2008 data as a result of the reductions in water consumption that have been achieved at most campuses.

Figure 11-2 - Normalised water use (kL/m2) for all core CSU facilities against the mean for all Australian universities

1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007

AU MEAN 1.3 1.3 1.4 1.2 1.4 1.3 1.3 1.2 1.1 1.1 0.9 0.8

CSU ALL 1.5 2.1 3.2 3 3 3.2 3.1 1.8 3.3 2.7 2.9 2.6

0

0.5

1

1.5

2

2.5

3

3.5

Page 48: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 48 | P a g e

12. Referenced published documents

Australian Bureau of Statistics (1996), viewed Feb 2009, http://www.abs.gov.au/ausstats/[email protected]/2f762f95845417aeca25706c00834efa/b7f52642c92ff11cca2570ec0073f6a7!OpenDocument Australian Government, Department of Climate Change (2008), viewed Feb 2009, http://www.climatechange.gov.au/workbook/pubs/workbook-feb2008.pdf Australian Greenhouse Office (2007), viewed Feb 2009, http://www.climatechange.gov.au/inventory/2005/pubs/trends2005.pdf NEMMCO (2008), viewed Feb 2009, http://www.nemmco.com.au/data/avg_price/averageprice_main.shtm Riverina Eastern Regional Organisation of Councils (2008) Charles Sturt University Closed-loop Recycling System Ross, D. (2007), viewed Feb 2009, http://www.carbonplanet.com/downloads/ghg_emission_factors_for_flights.pdf Sydney Water (2008), viewed Feb 2009, http://www.sydneywater.com.au/SavingWater/InYourHome/WaterEfficientTargets/HouseholdTargets.cfm TEFMA (2008) 2007 Benchmark Report – Institutional Edition

Page 49: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 49 | P a g e

13. Appendix A - Conversion factors

Fuel / Energy Fuel Unit kg CO2-e Source

Air travel – long haul

1 prsn / km

0.32 GHG Emissions resulting from aircraft travel (Jun 07), Ross, D

Air travel – medium haul

1 prsn / km

0.3 GHG Emissions resulting from aircraft travel (Jun 07), Ross, D

Air travel – short haul

1 prsn / km

0.45 GHG Emissions resulting from aircraft travel (Jun 07), Ross, D

Coal 1 GJ 88.43 National Greenhouse Account Factors (Nov 08), DEC

Diesel 1 GJ 69.9 National Greenhouse Account Factors (Nov 08), DEC

Electricity 1 kWh 0.89 National Greenhouse Account Factors (Nov 08), DEC

LPG 1 GJ 0.0393 National Greenhouse Account Factors (Nov 08), DEC

Natural gas 1 GJ 51.33 National Greenhouse Account Factors (Nov 08), DEC

Unleaded fuel 1 GJ 69.6 National Greenhouse Account Factors (Nov 08), DEC

Fuel / Energy Fuel Unit GJ Source

Coal 1 tonne 27 National Greenhouse Account Factors (Nov 08), DEC

Diesel 1 kL 38.6 National Greenhouse Account Factors (Nov 08), DEC

LPG 1 m3 57 National Greenhouse Account Factors (Nov 08), DEC

Unleaded fuel 1 kL 34.2 National Greenhouse Account Factors (Nov 08), DEC

Page 50: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 50 | P a g e

14. Appendix B – Abbreviations & units used

CO2 carbon dioxide

DFM Division of Facilities Management

GFA gross floor area

GHG greenhouse gas

GJ gigajoules

IDP Institutional Development Plan

kg/CO2-e kilograms of carbon dioxide equivalent

kJ kilojoules

kL kilolitres

kWh kilowatt hours

LPG liquid petroleum gas

m2 square metres

MJ megajoules

UFA useable floor area

Page 51: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Division of Facilities Management, 2008 Environmental Scorecard 51 | P a g e

15. Appendix C – Worksheets

Page 52: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Electricity Data (All consumption units shown in kWh)

Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra Broken Hill CSU Total 2015 Target

% Change

2006 12808172 7605501 1495386 915437 1095008 388592 29837 63306 24401239 183009292007 12381786 7173519 1397463 877775 643906 378713 39704 63306 22956172 18253450 ‐5.92%2008 12153297 7019706 1692433 845842 961484 379544 48108 200129 23300543 18253450 ‐4.51%

2006 $1,131,187 $869,331 $176,030 $118,115 $134,121 $52,594 $2,521 $9,493 $2,483,8992007 $1,181,730 $872,142 $160,039 $138,153 $163,858 $43,900 $4,566 $9,493 $2,564,389 3.24%2008 $1,331,488 $881,137 $214,900 $159,492 $210,979 $44,458 $7,933 $29,044 $2,850,387 14.75%

Wagga Wagga Breakdown GJ ConversionNorth Campus

South Campus

Sth Camp Caravan Prk

Sth Camp Tennis Crts

Minor Accounts

Total 2015 Target

% Change

2006 11753829 889242 110370 4387 50344 12808172 9606129 42313.82007 11324936 905671 95390 2318 53471 12381786 9606129 ‐3.3% 40769.82008 11180229 842298 94860 2780 33130 12153297 9606129 ‐5.1% 40248.8

2006 $1,131,187 $90,586 $11,927 $468 $7,833 $1,242,0012007 $1,181,730 $100,409 $11,098 $559 $9,439 $1,303,2352008 $1,331,488 $107,884 $11,906 $705 $5,973 $1,457,956

Bathurst BreakdownTotal 2015 Target

2006 7605501 57041262007 7173519 5704126 ‐5.7%2008 7019706 5704126 ‐7.7%

2006 $869,3312007 $872,1422008 $881,137

Albury BreakdownGuinea St  587 David St 

Mackie591 David St Ferhurst

595 David St Visual Arts

466 Wilson St Co‐op

470 Wilson St Drysdale

1/476 Wilson St 

476 Wilson St 

478 Wilson St Irvington

480 Wilson St 

492 Wilson St 

2/601 Olive St 

608 Olive St 

610 Olive St Cedar

616 Olive St Student A

616 Olive St Wilcara

618 Olive St Mudge

624 Olive St Avon 

626 Olive St

630 Olive St Flood 

Total 2015 Target

% Change

2006 915437 6865782007 461738 13887 12922 31107 22499 3609 71980 9330 6350 9553 5627 0 6810 67804 27084 12138 33395 22596 16026 43320 877775 686578 ‐4.3%2008 422608 838 7936 22664 11581 1467 72150 9170 5440 10952 3601 0 8806 73277 70651 10928 27356 23026 17731 45660 845842 686578 ‐7.9%

2006 $118,1152007 $66,817 $2,522 $1,933 $5,373 $3,549 $593 $12,106 $1,404 $1,261 $1,803 $1,141 $0 $1,342 $11,316 $4,813 $2,224 $5,797 $3,942 $2,867 $7,349 $138,1532008 $75,195 $514 $1,027 $4,399 $2,661 $494 $13,379 $1,921 $1,245 $2,262 $909 $0 $1,863 $13,490 $14,642 $2,247 $5,338 $4,437 $3,483 $9,984 $159,492

Thurgoona BreakdownEllis St Pump House

St Johns Rd Teaching Complex

1st Floor Ellis 

613 Ellis Gordon Beavan

Level 4 Ellis St 

Leahy Ave Ecology Lab

MSE Murray Sch of Ed

Elizabeth Mitchell Drv 

Thurgoona Streetlights

Total 2015 Target

% Change

2006 1095008 8212562007 0 222128 27699 158587 26804 20322 27802 160564 0 643906 821256 ‐41.2%2008 0 274489.63 75930 372076 18721 18362 42035 159870 0 961484 821256 ‐12.2%

2006 $134,1212007 $43 $37,341 $19,176 $69,387 $4,696 $3,595 $5,514 $21,152 $2,955 $163,858 ‐22.2%2008 $144 $50,861 $22,116 $88,751 $3,667 $3,873 $8,859 $26,727 $5,980 $210,979 ‐28.8%

Orange BreakdownMinor Accounts

Total 2015 Target % Change

2006 1495386 1495386 11215402007 1397463 1397463 1121540 ‐6.5%2008 1507216 185217 1692433 1121540 13.2%

2006 $176,030 $176,0302007 $160,039 $160,0392008 $182,141 $32,760 $214,900

Dubbo BreakdownTotal 2015 Target % Change

2006 388592 2914442007 378713 291444 ‐2.5%2008 379544 291444 ‐2.3%

2006 $52,5942007 $43,9002008 $44,458

Canberra BreakdownTotal 2015 Target % Change

2006 29837 223782007 39704 22378 33.1%2008 48108 22378 61.2%

2006 $2,5212007 $4,5662008 $7,933

Broken Hill BreakdownTotal 2015 Target % Change

2006 63306 474802007 63306 47480 0.0%2008 200129 47480 216.1%

2006 9493.152007 9493.152008 29043.59

Page 53: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Gas Data (All consumption units shown in MJ)

Wagga Wagga

Bathurst Orange Albury  Thurgoona Dubbo Canberra CSU Total 2015 Target

% Change

2006 55603045 45400976 1670742 5008355 5071824 1682387 126938 114564267 859232002007 48983842 40176486 1618551 3939147 2954046 1345427 170000 99187499 85923200 ‐13.4%2008 48036326 43240725 1853154 3233682 3314990 1817860 131569 101628306 85923200 ‐11.3%

2006 $442,589 $315,458 $26,880 $49,318 $42,761 $21,093 $1,650 $899,7492007 $403,199 $310,794 $21,806 $43,385 $30,067 $17,723 $2,211 $829,184 ‐7.8%2008 $407,021 $425,419 $26,396 $40,912 $33,720 $26,320 $4,263 $964,052 7.1%

Wagga Wagga Breakdown GJ ConversionNorth Campus

South Campus

2 College Ave

4 College Ave

22 Charleville Rd

Playhouse Total 2015 Target

% Change

2006 50130090 5242815 0 35449 86665 108027 55603045 41702284 50130.092007 43595692 5087930 0 57555 57430 185235.5 48983842 41702284 ‐11.9% 43595.692008 42109226 5628009 0 17393 12669 269028.1 48036326 41702284 ‐13.6% 42109.23

2006 $386,349 $53,391 $0 $546 $1,085 $1,218 $442,5892007 $346,552 $53,186 $0 $822 $829 $1,810 $403,199 8.9%2008 $344,042 $60,393 $0 $415 $349 $1,822 $407,021 8.0%

Bathurst BreakdownTotal 2015 

Target2006 45400976 340507322007 40176486 34050732 ‐11.5%2008 43240725 34050732 ‐4.8%

2006 $315,4582007 $310,7942008 $425,419

Albury Breakdown493 Guinea

587 David 591 David 470 Wilson 476 Wilson 478 Wilson

480 Wilson

492 Wilson 608 Olive 618 Olive 624 Olive 630 Olive 640 Olive 502 Dean Total 2015 Target

2006 5008355 37562662006 5008355 37562662007 375211 26441 39 24220 2545076 106548 31449 91245 130428 153148 188627 245745 20970 0 3939147 3756266 ‐21.3%2008 576763 0 0 0 1454645 116395 38601 78720 185303 196443 237030 302621 47161 0 3233682 3756266 ‐35.4%

2006 $49,3182007 $4,557 $408 $152 $456 $24,371 $1,496 $547 $1,196 $1,655 $2,087 $2,531 $3,245 $686 $0 $43,3852008 $6,940 $129 $155 $155 $16,623 $1,880 $715 $1,146 $2,377 $2,711 $3,236 $4,076 $769 $0 $40,912

Thurgoona Breakdown

615 Leahy Ellis St BromfieldTotal 2015 Target

2006 5071824 38038682007 91870 2527306 334870 2954046 2215535 ‐71.7%2008 107181 3062798 145011 3314990 2486243 ‐59.5%

2006 $42,7612007 $1,281 $24,684 $4,102 $30,0672008 $1,548 $30,151 $2,020 $33,720

Orange Breakdown

Total2015 Target

2006 1670742 12530572007 1618551 1253057 ‐3.1%2008 1853154 1253057 10.9%

2006 $26,8802007 $21,8062008 $26,396

Dubbo Breakdown

Total2015 Target

2006 1682387 12617902007 1345427 1261790 ‐20.0%2008 1817860 1261790 8.1%

2006 $21,0932007 $17,7232008 $26,320

Canberra Breakdown

Total2015 Target

2006 126938 952042007 170000 95204 33.9%2008 131569 95204 3.6%

2006 $1,6502007 $2,2112008 $4,263

Page 54: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Water Data (All consumption units shown in kL)

Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra Broken Hill

CSU Total 2011 Target

% Change

2006 444912 216185 49119 11472 9628 13183 1947 2065 748511 5613832007 337667 161473 37826 12682 8930 7563 1843 1485 569469 561383 ‐23.9%2008 298607 104907 22815 7467 4924 7048 1843 1289 448900 561383 ‐40.0%

2006 $315,483 $153,799 $73,225 $12,676 $8,940 $20,379 $3,174 $3,025 $590,7012007 $246,893 $134,813 $57,908 $30,521 $13,321 $30,259 $5,097 $2,340 $521,151 ‐11.8%2008 $227,979 $88,622 $47,358 $25,989 $13,075 $36,482 $2,702 $2,230 $444,437 ‐24.8%

Wagga Wagga BreakdownNorth Campus

South Campus

Ag Ave Playhouse Total 2011 Target

% Change

2006 402304 28495 12676 1437 444912 3336842007 311438 15545 9475 1209 337667 333684 ‐24.1%2008 275702 12490 9357 1058 298607 333684 ‐32.9%

2006 $284,963 $20,274 $9,109 $1,137 $315,4832007 $227,305 $11,507 $7,075 $1,006 $246,893 ‐21.7%2008 $210,230 $9,645 $7,196 $908 $227,979 ‐27.7%

Bathurst BreakdownMain Campus

Hargrave House M.T.G. Total

2011 Target

2006 208974 2300 4911 216185 1621392007 153294 2523 5656 161473 162139 ‐25.3%2008 97275 2137 5495 104907 162139 ‐51.5%

2006 $147,382 $1,762 $4,656 $153,7992007 $127,924 $2,044 $4,845 $134,8132008 $81,059 $2,068 $5,495 $88,622

Albury Breakdown492 Wilson

480 Wilson

478 Wilson 476 Wilson 472 Wilson

466 Wilson 644 Olive 640 Olive 630 Olive 626 Olive 624 Olive 614 Olive 610 Olive 608 Olive 604 Olive 595 David 591 David 587 David Guinea St 502 Dean

Total 2011 Target % Change

2006 225 3792 48 15 2 156 700 11 366 53 139 67 2270 114 0 303 23 118 2814 256 11472 86042007 238 3615 55 14 1 255 648 14 239 62 129 36 3342 284 0 382 43 163 2903 259 12682 8604 10.5%2008 65 673 45 22 0 74 739 18 166 35 195 43 2383 313 0 270 42 42 2122 220 7467 8604 ‐34.9%

2006 $12,6762007 596.15 6450.91 311.87 233.08 140.59 713.44 2080.9 556.19 586.69 481.5 889.54 274.91 7622.8 773.66 207.23 1374.65 289.5 515.24 5664.6 757.19 $30,5212008 536.06 2314.41 326.43 279.8 236.3 382.9 2795.77 610.79 587.5 520.86 1080.15 321.76 7393.73 883.38 216.19 1194.76 320.73 319.15 4990.41 678.17 $25,9892008 536.06 2314.41 326.43 279.8 236.3 382.9 2795.77 610.79 587.5 520.86 1080.15 321.76 7393.73 883.38 216.19 1194.76 320.73 319.15 4990.41 678.17 $25,989

Thurgoona BreakdownLot 701 Bromfield

Lot 601 Table Top

Thurgoona Drv

Lot 613 Bromfield

386 Eliz Mitch

Lot 619 Leahy Lot 615 Leahy

Lot 614 Bromfield

Total 2011 Target

2006 2107 2462 0 1814 792 0 2299 154 9628 72212007 2545 2643 0 2734 582 0 217 209 8930 7221 ‐7.2%2008 1935 259 0 1717 736 0 21 256 4924 7221 ‐48.9%

2006 $8,9402007 $5,414 $1,032 $207 $5,559 $366 $207 ‐$475 $1,010 $13,3212008 $2,618 $1,465 $216 $5,212 $734 $216 $1,211 $1,403 $13,075

Orange Breakdown

Total2011 Target

2006 49119 368392007 37826 36839 ‐23.0%2008 22815 36839 ‐53.6%

2006 $73,2252007 $57,9082008 $47,358

Dubbo Breakdown

Total2011 Target

2006 13183 98872007 7563 9887 ‐42.6%2008 7048 9887 ‐46.5%

2006 $20,3792007 $30,2592008 $36,482

Canberra Breakdown

Total2011 Target % Change

2006 1947 14602007 1843 1460 ‐5.3%2008 1843 1460 ‐5.3%

2006 $3,1742007 $5,0972008 $2,702

Broken Hill Breakdown

Total2011 Target % Change

2006 2065 15492007 1485 1549 ‐28.1%2008 1289 1549 ‐37.6%

2006 3025.12007 2339.62008 2229 5

Page 55: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Waste Data (all figures shown as $)

Wagga Wagga

Bathurst Orange Alb / Thurg

Thurgoona Dubbo Canberra CSU Total

2006 111405 21713.8 8967.64 30748 5593.66 1784272007 99495 26406.79 12987.23 31131 7739.97 177760 ‐0.4%2008 61726 25476.26 15353.18 44228 6070.26 152853 ‐14.3%

Wagga BreakdownGeneral Waste

Recycling Liquid Waste

Sanitary Waste

Compost Bulk Dumping

Total

2006 48911.43 38157.29 430 23694.1 211.72 111404.52007 44427.84 33038.65 21816.19 212.3 99494.98 ‐10.7%2008 17634.6 28790.62 800 12394.76 1547.95 557.85 61725.78 ‐44.6%

Bathurst BreakdownGeneral Waste

Recycling Liquid Waste

Sanitary Waste

Compost Bulk Dumping

Total

2006 9652.6 3623.7 8437.5 21713.82007 11716.71 4077.62 10612.46 26406.79 21.6%2008 7719.16 2921.34 14835.76 25476.26 17.3%

Albury BreakdownGeneral Waste

Recycling Liquid Waste

Sanitary Waste

Compost Bulk Dumping

Total

2006 23802.22 327.75 6617.78 30747.752007 20498.84 3352.78 7279.56 31131.18 1.2%2008 35155.32 2434.5 6637.94 44227.76 43.8%

Orange BreakdownGeneral Waste

Recycling Liquid Waste

Sanitary Waste

Compost Bulk Dumping

Total

2006 7934.74 1032.9 8967.642007 11653.85 1333.38 12987.23 44.8%2008 13178.12 2175.06 15353.18 71.2%

Dubbo BreakdownGeneral Waste

Recycling Liquid Waste

Sanitary Waste

Compost Bulk Dumping

Total

2006 4624.25 969.41 5593.662007 6031.52 1708.45 7739.97 38.4%2008 4654.03 435.08 981.15 6070.26 8.5%

All Campuses BreakdownGeneral Waste

Recycling Liquid Waste

Sanitary Waste

Compost Bulk Dumping

2006 94925.24 42108.74 430 40751.69 0 211.72 178427.42007 94328.76 40469.05 0 42750.04 0 212.3 177760.22008 78341.23 34146.46 1235.08 37024.67 1547.95 557.85 152853.2

All Campuses Breakdown (%)General Waste

Recycling Liquid Waste

Sanitary Waste

Compost Bulk Dumping

2006 53.2% 23.6% 0.2% 22.8% 0.0% 0.1%2007 53.1% 22.8% 0.0% 24.0% 0.0% 0.1%2008 51.3% 22.3% 0.8% 24.2% 1.0% 0.4%

Page 56: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Normalised figures (all areas shown as gross floor area ‐ m2)

Electricity (kWh / m2)Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra Broken Hill CSU Total

2006 Area 106978 74226 20498 13702 14182 5758 871 5041 241254.52007 Area 108028 74729 20498 13702 14182 5758 871 5041 237766.32008 Area 109967 74729 20498 11857 15062 5758 1648 5041 239517.3

2006 119.7 102.5 73.0 66.8 77.2 67.5 34.3 12.6 101.92007 114.6 96.0 68.2 64.1 45.4 65.8 45.6 12.6 95.82008 110.5 93.9 82.6 71.3 63.8 65.9 29.2 39.7 97.3

Gas (MJ / m2)Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra CSU Av

2006 519.8 611.7 81.5 365.5 357.6 292.2 145.7 474.92007 453.4 537.6 79.0 287.5 208.3 233.7 195.2 417.22008 436.8 578.6 90.4 272.7 220.1 315.7 79.8 424.3

Water (kL / m2)Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra Broken Hill CSU Av

2006 4.2 2.9 2.4 0.8 0.7 2.3 2.2 0.4 3.12007 3.1 2.2 1.8 0.9 0.6 1.3 2.1 0.3 2.42008 2.7 1.4 1.1 0.6 0.3 1.2 1.1 0.3 1.9

CO2 (tonnes CO2‐e / m2)

Wagga Wagga

Bathurst Orange Albury Thurgoona Dubbo Canberra CSU Av

2006 0.13 0.13 0.07 0.08 0.09 0.08 0.04 0.092007 0.13 0.11 0.06 0.07 0.05 0.07 0.05 0.082008 0.12 0.11 0.08 0.08 0.07 0.07 0.03 0.08

Waste ($ / m2)Wagga Wagga

Bathurst Orange Alb/Thurg Thurgoona Dubbo Canberra CSU Av

2006 1.04 0.29 0.44 2.24 N/A 0.97 0.00 0.832007 0.92 0.35 0.63 2.27 N/A 1.34 0.00 0.922008 0.65 0.34 0.75 3.73 N/A 1.05 0.00 1.09

Page 57: ENERGY & WATER SCORECARD - Charles Sturt University · 2011. 3. 30. · This report reviews the energy and water use and associated costs for Charles Sturt University’s (CSU) major

Fuel use & vehicle travelAssumed ULP (L)

Assumed Diesel (L)

Assumed LPG (L)

Fuel used by CSU vehicles on business (L)

Total kms travelled by CSU vehicles

kms travelled by CSU vehicles on private use

kms travelled by CSU vehicles on business

Fuel % change

km % change

% break‐down

67% 30% 3%

2006 600000 6000000 1500000 4500000 402000 180000 180002007 580000 5500000 1500000 4000000 ‐3.3% ‐8.3% 388600 174000 174002008 664000 6300000 1360000 4940000 10.7% 5.0% 444880 199200 19920

600,000

580 000664,000600000

700000

CSU ‐ Fuel used by vehicles on business

5000000

6000000

CSU ‐ kms travelled by vehicles on business

580,000

0

100000

200000

300000

400000

500000

2006 2007 2008

Litres

4,500,000 4,000,0004,940,000

0

1000000

2000000

3000000

4000000

2006 2007 2008

Kilometres