thyssenkrupp Industrial Solutions (India) Private Limited 1 | 25.03.2019| AMAI SEMINAR Sanjay Vyas 25.03.2019 | Sanjay Vyas thyssenkrupp Industrial Solutions India Private Limited, Mumbai ELECTROLYSER MONITORING, SAFETY AND CONTROLS AMAI SEMINAR-2019, Bharuch

Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

  • Upload
    others

  • View
    19

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

thyssenkrupp Industrial Solutions (India) Private Limited1 | 25.03.2019| AMAI SEMINAR Sanjay Vyas

25.03.2019 | Sanjay Vyasthyssenkrupp Industrial Solutions India Private Limited, Mumbai

ELECTROLYSER MONITORING, SAFETY AND CONTROLS

AMAI SEMINAR-2019, Bharuch

Page 2: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

thyssenkrupp Industrial Solutions (India) Private Limited2 | 25.03.2019| AMAI SEMINAR Sanjay Vyas

Topics Covered

o Electrolyser Monitoring

-Key process parameters to be monitored

-Instrumentation Around Electrolyser

o Electrolyser Safety

-Old Concept

- New Concept

o Process Controls

Page 3: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

3thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser Monitoring

Continuous Monitoring of process parameters is necessary for efficient

plant operation

Selection of proper Instrumentation and control plays vital role in safe plant

operation

Electrolysis process involve many process variables

Page 4: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

4thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser MonitoringKey Process Parameters to be Monitored

Chlorine and Hydrogen Header

Pressure

Differential pressure

Brine flow and Caustic

flow to Electrolyser

Catholyte and Anolyte

Temperature

Single Element Voltage

Cell Rack Voltage

Voltage deviation

across Cell rack

Corrected Voltage

Page 5: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

5thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser MonitoringKey Process Parameters to be Monitored

Electrolyser/ Rectifier current

Anolyte Concentration

and pH

Catholyte Concentration

HCl flow to Electrolyser

Anolyte Header

Pressure

Catholyte Header

Pressure

Diff. press. between Anolyte & Catholyte header

Hydrogen in Chlorine

Page 6: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

6thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser MonitoringInstrumentation Around Electrolyser

Pressure transmitters for

Chlorine & Hydrogen

Chlorine and Hydrogen Header

Pressure

Brine flow and Caustic

flow to Electrolyser

Catholyte and Anolyte

Temperature

Differential Pressure

transmitters

Flow transmitter for Feed brine

and feed caustic

Temperature transmitter in Anolyte and

Catholyte Header

Page 7: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

7thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Pressure transmitter for Chlorine and Hydrogen

Differential Pressure transmitter

Flow transmitter for Feed brine and feed caustic.

Temperature transmitter in Anolyte and Catholyte Header

Electrolyser MonitoringInstrumentation Around Electrolyser

Page 8: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

8thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser MonitoringInstrumentation Around Electrolyser

Uhde Evaluator/ Voltage

monitoring system

Single Element Voltage

Cell Rack Voltage

Corrected VoltageVoltage deviation

transmitter for each rack

Voltage transmitter on individual cell

rack

Voltage of Ely compared with

corrected voltage based on

temperature

Voltage deviation

across Cell rack

Page 9: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

9thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser MonitoringInstrumentation Around Electrolyser

Uhde Evaluator/ Voltage monitoring system

Voltage transmitter

Voltage deviation transmitter

Page 10: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

10thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser MonitoringInstrumentation Around Electrolyser

DC shunt/ Current transducer

Electrolyser/ Rectifier current

Anolyte Concentration

and pH

HCl flow to Electrolyser

Coriolis flow meter in

individual Electrolyser

Catholyte outlet

pH transmitter and Coriolis flow

meter in individual

Electrolyser anolyte outlet

Flow meter in HCl to feed Brine for

individual electrolyser

.

Catholyte Concentration

Page 11: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

11thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser Monitoring

Current Measurement

pH meters and Mass flowmeter assemblyInstrumentation Around Electrolyser

Page 12: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

12thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser MonitoringInstrumentation Around Electrolyser

Pressure transmitter for

Individual Electrolyser

Anolyte header

Anolyte Header

Pressure

Catholyte Header

pressure

Hydrogen in Chlorine

Calculation block with indication for

Diff.pressure between Anolyte

and Catholyte header

Pressure transmitter for

Individual Electrolyser

Catholyte header

Hydrogen in Chlorine analyzer

Diff. pressure between

Anolyte and Catholyte header

Page 13: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

13thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Pressure transmitter for Individual Electrolyser Anolyte header

Pressure transmitter for Individual Electrolyser Catholyte header

Electrolyser MonitoringInstrumentation Around Electrolyser

Page 14: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

14thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Principle: Conversion of H2 to HCl and then infrared photometric determination

H2 + Cl2 2HCl

H2 and Cl2 is Oxidized by UV to HCl

HCl is measured by INFRARED analyzer.

Corresponding quantity 2HCl = H2

UV light

Capabilities:

o Measurement in presence of higher inert gas components possible, faster response, higher accuracy.

o This analyzer can detect high H2 in Cl2 levels and possible explosive mixture formation during following conditions:

At low loads / during start-up

During membrane leaks

o Detection limit approx.100 ppm H2 (equivalent 200 ppm HCl)

o Response time 60 … 100 sec.

o Stable operation, if proper maintenance of sample handling system is carried out.

o Relatively low maintenance

Limitations:

o High initial investment

Hydrogen in Chlorine analyzerElectrolyser MonitoringInstrumentation Around Electrolyser

Page 15: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

15thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser Safety in Cell Room

Safety means safeguarding of your personnel & equipment from hazards

Safety makes us stronger

Living a reasonable Safety philosophymeans Trust in Plant Safety

Safety first is not just a slogan it´s an attitude

Page 16: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

16thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas16thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Safety model

vent

Procedures

Personnel

Incident Level

vent

vent

Technology

Procedures

Technology State-of-the-art technology –

tkUCE generation 6 electrolyser Electrical safety in cell room Digitalization – Uhde Evaluator

Personnel

State-of-the-art operating procedures Electrolyser bypass concept HAZOP

Operator training Cause-Effect instructions

Incident Level Emergency Interlocks

(e.g. shut down of electrolyser)

vent

vent

Electrolyser Safety in Cell Room

Page 17: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

17thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser safeguardsFrom the beginning

Electrolyser Safeguard

Element Voltage

Manual Voltage measurement

Neutral point & Insulation

Manual insulation monitoring

DCS based Interlock

Normalized voltage of each electrolyser calculated

Safety Valves

Electrolyser high pressureprotection

Page 18: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

18thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

U0

0 2 4 6 CD[kA/m²]

U [V]

E

Interlock for voltage increase of total electrolyser Deviation of Alarm and Trip value

EAH = (U0 + k x CD + 100) x NCells

EAHH = (U0 + k x CD + 200) x NCells

Page 19: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

19thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser High Pressure ProtectionUse of Safety Valves at electrolysers

Cost intensive piping to route

Yearly maintenance and work bench recalibration of predefined opening pressure

Chlorine can permeate through PTFE bellows and corrode metallic parts

Page 20: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

20thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Limitations of old- systems….

Manual voltage measurement is not continues monitoring

Simple earth fault detection method with Mega Ohm Test

DCS based calculated voltage needs k-factor adaptation by timeNo adaptation causes unintended shutdowns

Safety valves need regular and frequent maintenance/testing, no automated Nitrogen purge

Page 21: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

21thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser safeguardsWhat is now?

Electrolyser Safeguard

Uhde EvaluatorTM system/ Voltage Monitoring system

Monitoring and Safeguarding of each single element and busbar symmetry

Symmetric-electrolyser earthingSymmetric earthing at defined locations around each electrolyser and cell room thus as second line of defense

Insulation monitoring systemInsulation Monitoring of platform and single racks (100 k)

On/Off bypass valves and automatic Nitrogen purge

bypass valves operated by DCS/ESD Immediate N2 flushing of single header

Page 22: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

22thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Monitoring membrane

operate. window

Displayof Single Element volt. &

temperature

SingleElement voltage

start-upcurves

Polarization testPinhole

detection / voltagetest

Alarms

Safeguarding by Uhde EvaluatorMonitoring and tests

Page 23: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

23thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Main components of the Uhde EvaluatorTM

DAU A DAU B

Uhde EvaluatorTM

Data ManagementSystem (PC)

Cel

l roo

m

DCS

Con

trol r

oom

Electrolyser B

Masterbox ESD

Electrolyser A

LaboratoryData base

Page 24: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

24thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Automatic insulation monitoring of platform & electrolyser rack

The lower the ohmic resistance, the higher the risk for operators!

Experience for typical resistance values 1) MOhm – No risk2) kOhm – salt bridge by leakages or dirt in wet atmosphere (maintenance case!)3) Ohm – short cut via direct metallic contact

Take Insulation monitoring serious

Page 25: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

25thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Earth fault in the service platform or electrolyser steel structure

Insulationmonitoring

Fatal risk by touching live parts and a second part with earth fault!

Only trained operators are allowed to enter service-walkway

Appropriate safety gear required (protective boots and gloves)

Insulationmonitoring

Alarm by Insulation monitoring device!

AH AH

Page 26: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

26thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

The pressure transmitter and the ON/OFF valve on each anolyte and catholyte header enables to monitor and protect each single electrolyser header with respect to pressure and differential pressure.

Bypass valves automatically ramp close or open at electrolyser pressure upsets:

for example: High dp / high H2pressure

– Catholyte bypass valve opens

On/Off Automatic Bypass-valves & Electrolyser Pressure Monitoring via DCS

Cost intensive piping, maintenance of safety valves no more needed

Page 27: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

27thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Electrolyser protection by automatic N2 Purge

Automatic N2 purge ensure immediate flushing of outlet headers

Accumulation of H2 and Cl2 to ignitable mixtures due to membrane defects is prevented

Page 28: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

28thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

New cell room safety concept summary

On/Off Automatic Bypass-valves & Electrolyser PressureMonitoring

Automatic insulation monitoring of platform & electrolyser rack

Uhde Evaluator Safeguard on cell voltage absolute and deviation from threshold, bus bar symmetry, first out indication

Automatic N2 purge ensures immediate flushing of outlet headers and prevents accumulation of H2 and Cl2

Page 29: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

29thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Process Controls

Desire state means Maintain emission norms, safe operation and desire output

It’s not just about optimization; it’s about successful operation of the entire plant

Process controls maintain the process at the desired state or set of conditions –

“keep it out of the ditch”

Page 30: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

30thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

PIC

PICN2

N2

PICN2

Cl2 to compressor

Coolers

200 mbar

Cl2

PIC

Anolyte Catholyte

ElectrolyserH2 220 mbar

PDIC

H2 to consumer

Coolers

Waste gas

PIC

PDIC

TI

AI

FIC

Feed Caustic

Feed BrineFIC

HCl

Process Controls- Electrolyser

TI PI

PIDPI

Page 31: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

31thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Differential Pressure Across Membrane

• Most important parameter to be monitored and controlled

• Operating value : “Fixed” mmwc

• Depends on Hydrogen pressure and Chlorine pressure

• Transmitters are provided in cell house to measure directly differential pressure between Hydrogen and Chlorine.

• Special Rotary plug control valve are used

• Interlock is provided to trip plant on HH , HHH,and LL values of Differential pressure

Process Controls- Electrolyser

Page 32: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

32thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

PIC

PICN2

N2

PICN2

Cl2 to compressor

Coolers

200 mbar

Cl2

PIC

Anolyte Catholyte

ElectrolyserH2 220 mbar

PDIC

H2 to consumer

Coolers

Waste gas

PIC

PDIC

TI

AI

FIC

Feed Caustic

Feed BrineFIC

HCl

Process Controls- Electrolyser

TI

FICPI

PIDPI

Differential Pressure Across Membrane

Page 33: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

33thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Pressure Control-Chlorine

• Very crucial parameter as it directly affect DP, operation of downstream equipment/ units

• Operating Range : Up to 3500 mmwc

• Transmitters are provided at chlorine header in cell house

• Interlock is provided to trip plant on HH and HHH values of Chlorine pressure

Process Controls- Electrolyser

Page 34: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

34thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

PIC

PICN2

N2

PICN2

Cl2 to compressor

Coolers

200 mbar

Cl2

PIC

Anolyte Catholyte

ElectrolyserH2 220 mbar

PDIC

H2 to consumer

Coolers

Waste gas

PIC

PDIC

TI

AI

FIC

Feed Caustic

Feed BrineFIC

HCl

Process Controls- Electrolyser

TI

FICPI

PIDPI

Pressure Control-Chlorine

Page 35: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

35thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

Process Controls- ElectrolyserFlow Control- Feed Brine, Feed Caustic and Acid

• Flow of feed Brine, Feed Caustic and feed HCl to be adjusted based on Electrolyser load

• Flow Transmitters with control valve provided for each service

• Interlock is provided to trip of Electrolyser on LL flow of Feed brine and feed caustic. The interlock value is dynamic and keep on changing based on electrolyser load.

Page 36: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

36thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

PIC

PICN2

N2

PICN2

Cl2 to compressor

Coolers

200 mbar

Cl2

PIC

Anolyte Catholyte

ElectrolyserH2 220 mbar

PDIC

H2 to consumer

Coolers

Waste gas

PIC

PDIC

TI

AI

FIC

Feed Brine

Feed Caustic

FIC

Process Controls- Electrolyser

TI

HCl

FICPI

PIDPI

Flow Control- Feed Brine, Feed Caustic and Acid

Page 37: Electrolyser Monitoring,Safety and Controls .ppt...Electrolyser Safety in Cell Room Safety means safeguarding of your personnel & equipment from hazards Safety makes us stronger Living

37thyssenkrupp Industrial Solutions (India) Private Limited

| 25.03.2019| AMAI SEMINAR Sanjay Vyas

CONFIDENTIALthyssenkrupp Uhde Chlorine Engineers37 | 25.03.2019| AMAI SEMINAR Sanjay Vyas

Thank You