> NRC Meeting – June 20, 2006 AREVA NP Inc. 1 U.S. EPR Pre-Application Review Meeting: Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

  • Upload
    others

  • View
    9

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 1

U.S. EPR Pre-Application Review Meeting:Electrical Systems, Fire Protection and

Train Separation Requirements Overview

AREVA NP Inc. and the NRCJune 20, 2006

Page 2: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 22

Introduction

Sandra M. SloanManager, Regulatory Affairs

New Plants Deployment

Page 3: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 3

Meeting ObjectivesElectrical Systems Overview

> Describe the approach for the design of electrical systems for the U.S. EPR

> Provide an overview of U.S. EPR electrical design

> Obtain early NRC feedback concerning the electrical system design strategy

> Discuss upcoming activities associated with the U.S. EPR electrical design

Page 4: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 4

Meeting ObjectivesFire Protection & Train Separation

> Provide an overview of the U.S. EPR design features to meet NRC requirements for Fire Protection

> Describe the defense-in-depth design for Fire Protection

> Provide an overview of the inherent safe shutdown design features

> Obtain early NRC feedback associated with the U.S. EPR Fire Protection strategy

Page 5: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 5

Outline

> U.S. EPR status update (Mathews)

> U.S. EPR electrical systems overview (Grundman)

> U.S. EPR fire protection and train separation (Redmond)

> Next steps (Sloan)

Page 6: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 66

Status Update

Toney MathewsProject Manager, EPR

New Plants Deployment

Page 7: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 7

Current Activities> OL3 reference plant

Under construction in Finland2009 commercial operationDesign freeze on electrical load listCable penetration and cable tray specification issuedMain generator rotor has been fabricated

> U.S. EPR deploymentDCD development for December 2007 submittalCOLA development for June 2008 submittalDesign continuum developmentElectrical licensing and design basis reconciliationElectrical global competence team oversight

Page 8: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 8

Planned Activities

> Electrical Design ProcessPhase 1 – Conceptual Design Phase 2 – Basic DesignPhase 3 – Detailed DesignPhase 4 – Manufacturing/Testing/Installation

Page 9: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 9

Planned Activities - TimelineQ1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4

EPR Design Certification

DC Application Preparation & Review DCA Prep, NRC Interactions NRC Review DC Rule

Electrical Conceptual Design

COL Licensing

COL Application Preparation & Review COLA Prep, NRC Interactions NRC COLA Reviews COLA

Electrical Basic Design

Project Execution

"Construction-Ready" Design Detailed engineering for construction

Electrical Basic Design

Electrical Detailed Design

Plant Construction Early Site Work Plant Construction, Start-up Testing

Electrical Manufacturing/Installation/Testing

2013 2014 2015Activity

2005 2006 2007 20122008 2009 2010 2011

AnticipatedFDA IssuenceDC Application

Submitted

ITAAC Complete

AnticipatedFSER Issuance

COL Application Submitted

Anticipated Issuance of

COL

Anticipated Issuance of

DC

Phase 1

Phase 2

Phase 3

Phase 4

Page 10: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 10

Dan GrundmanElectrical and I&C Deputy Manager

New Plants Engineering

U.S. EPR Electrical Systems Overview

Page 11: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 11

U.S. EPR Electrical SystemsTopics

> Electrical – goals and objectives> Electrical design approach> Major differences between OL3 and U.S. EPR> Conceptual single line diagram> Offsite power system> Onsite AC power system (Non-Class 1E)> Onsite AC power system (Class 1E)> Onsite UPS power system (Non-Class 1E)> Onsite UPS power system (Class 1E)> ETAP® analysis

Page 12: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 12

U.S. EPR Electrical SystemsGoals and Objectives

> Support advanced plant PRA goals

> Support advanced plant staffing goals

> World-wide standardization to maximum extent possible

> Acceptance by international regulatory authorities

Improved Electrical Safety, Performance and Reliability

> Improved safety/reliabilityEnsure preferred power source is available to support safety system operationEnsure emergency power sources are available when neededMinimize single point vulnerabilities which could cause unit trip or loss of preferred power source

> Improved maintainabilityOn-line testing and diagnosticsOn-line maintenance

Page 13: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 13

EPR Electrical SystemsDesign Approach

> OL3 comprises the base plant design

> Systematic process is being applied to prepare the design for U.S. deployment

Conversion to U.S. design codes & standardsCompliance with NRC regulations and QA requirements

> Industry operating experience addressed in the design certification process

> Use of global competence team to develop and implement worldwide EPR electrical design concepts

> Recent EPR electrical design experience is factored into the U.S. EPR with the implementation of a rotational electrical engineering position

Standardization is a design goal

Page 14: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 14

EPR Design Conversion

U.S. Licensing BasisDCD

OL3OL3

U.S.QA

Codes & Standards

Design Control

Approved Methods

U.S. EPR Design

Page 15: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 15

Major Differences between OL3 and U.S. EPR Electrical Design

Regulatory Guidance/Standards

Frequency

Voltage

IEEE, NRCIEC, STUK

60 Hz50 Hz

13.8kV, 4.16kV, 480V10kV, 690VU.S. EPROL3

Page 16: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 16

Standard Review Plan (NUREG 0800) Correlation with U.S. EPR Electrical Systems

1) SBO Diesel Generators (SBDG)Section 8.4 “Station Blackout (Future)”

1) Class 1E UPS (EUPS)Section 8.3.2 “DC Power Systems (Onsite)”

1) Emergency Power Supply System (EPSS)2) Emergency Diesel Generators (EDG)3) SBO Diesel Generators (SBDG)

Section 8.3.1 “AC Power Systems (Onsite)”

1) Preferred Power Supply (PPS)2) Switchyard (SWYD)

Section 8.2 “Offsite Power System”

U.S. EPR Electrical SystemStandard Review Plan

Page 17: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 17

EPR General Plant Layout

Office Building

Safeguard Building 4

Fuel Building

Nuclear Auxiliary Building

Access Building Turbine Building

Safeguard Building 2+3

Safeguard Building 1

Reactor Building

Switchgear BuildingTurbine Island

Waste Building

Emergency Diesel Division 1Emergency Diesel Division 2SBO Diesel Division 1

Emergency Diesel Division 3Emergency Diesel Division 4SBO Diesel Division 4

Page 18: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 18

Conceptual Single Line Diagram

N0BBT01 N0BBT02 N0BBT03 N0BBT04

Division 4Division 2 Division 3Division 1

N1BBA13.8kV

N1BBB13.8kV

N1BDA13.8kV

N2BBA13.8kV

N2BDA13.8kV

N3BBA13.8kV

N3BDA13.8kV

N4BBA13.8kV

N4BBB13.8kV

N4BDA

13.8kV

N1BDG4160V

N1BDH4160V

N2BDG4160V

N2BDH4160V

N3BDG4160V

N3BDH4160V

N4BDG4160V

N4BDH4160V

N1BBC13.8kV

To Reactor Coolant Pump

N2BBC

To Reactor Coolant Pump

N3BBC13.8kV

To Reactor Coolant Pump

N4BBC13.8kV

To Reactor Coolant Pump

2 55 441 1

13.8kV

EDG EDG EDG EDG

SBO DG

SBO DG

N2BBH

4160V

N4BBH4160V

N3BBH4160V

N1BBH

4160V

To Switchyard

To Switchyard

To Switchyard

To Switchyard

2

G

SWYD

Main

Generator

Page 19: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 19

Offsite Power System

> The offsite system is comprised of two physically independent circuits (in accordance with GDC-17) connecting the transmission network (grid) to the onsite distribution system

> Each redundant safety division is supplied directly from both offsite power sources with no intervening non-safety buses

> The U.S. EPR electrical design group is actively involved in the industry issues involved with grid reliability including NRC GL 2006-02 “Grid Reliability and the Impact on Plant Risk and the Operability of Offsite Power ”

Page 20: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 20

Typical U.S. Switchyard ConfigurationBreaker and ½ Scheme

PCB

PCB

PCB

TL2TL1

PCB PCBPCB

PCB

PCB

PCBPCB

PCB

PCB

PCB

MSUN0BBT01 N0BBT02 N0BBT03 N0BBT04

Page 21: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 21

Offsite Power Interface SLD

N0BBT01 N0BBT02 N0BBT03 N0BBT04

Division 4Division 2 Division 3Division 1

N1BBA

13.8 kV

N1BDA

13.8 kV

N2BBA

13.8 kV

N2BDA

13.8 kV

N3BBA

13.8 kV

N3BDA

13.8 kV

N4BBA

13.8 kV

N4BDA

13.8 kV

255 4

41

1

EDG EDG

To Switchyard

To Switchyard

To Switchyard

To Switchyard

2

EDG EDG

Non-Class 1E Power

Class 1E Power

Page 22: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 22

Offsite Connection Reliability

N0BBT01 N0BBT02 N0BBT03 N0BBT04

Division 4Division 2 Division 3Division 1

N1BDA1E 13.8kV

N2BDA1E 13.8kV

N3BDA1E 13.8kV

N4BDA1E 13.8kV

N1BDG

1E 4160V

N1BDH1E 4160V

N2BDG1E 4160V

N2BDH1E 4160V

N3BDG1E 4160V

N3BDH1E 4160V

N4BDG1E 4160V

N4BDH1E 4160V

22 55

44

11

EDG EDG EDG EDG

To Switchyard

To Switchyard

To Switchyard

To Switchyard

Loss of Auxiliary Transformer (N0BBT04)

SBO DG

SBO DG

Page 23: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 23

Onsite AC Power (Non-Class 1E)Normal Power Supply System (NPSS)

> Four train bus concept with two maintenance buses capable of being supplied from two sources

> Turbine generator capable of a load rejection (grid) and still maintain house load operation (island mode)

> Largest electrical loads consists of reactor coolant pumps, feedwater pumps, condensate pumps

> Investment protection power supply for a backup power source to supply critical loads (turbine lube oil, UPS, etc) during a loss of offsite power

> No bus transfers required at plant startup or shutdown

Significantly improved reliability

Page 24: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 24

Onsite AC Power (Non-Class 1E) SLDNPSS

N0BBT01 N0BBT02 N0BBT03 N0BBT04

Division 4Division 2 Division 3Division 1

N1BBA13.8kV

N1BBB13.8kV

N2BBA13.8kV

N3BBA13.8kV

N4BBA13.8kV

N4BBB

To Reactor Coolant Pump

2

2 5

35 44 63

11

6

M

N1BFE480V

N1BFT05

N1BBC13.8kV

N1BDT08

N1BBH4.16kV

N2BBC13.8kV

MTo Reactor

Coolant Pump

N2BBH4.16kV

N2BDT08

N2BBC13.8kV

MTo Reactor

Coolant Pump

N2BBH4.16kV

N4BBC13.8kV

MTo Reactor

Coolant Pump

N4BBH4.16kV

N4BFE480V

N4BFT05

Page 25: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 25

Onsite AC Power (Class 1E)Emergency Power Supply System (EPSS)

> Four division concept with four redundant emergency diesel generators

> Four 480V fast regulating transformers for voltage sensitive loads, i.e. containment isolation valves

> Divisional electrical cross connects are used to enhance the flexibility and reliability of performing on-line maintenance and outage maintenance

Increased flexibility, reliability and design margin

Page 26: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 26

13.8 kV

480 V

21

480 V

G

∼-

∼-

N1BMA

N1BNA01 480 V 480 VN1BND

23

N1BRA

N1BMC

N1BTP01

N1BRU01

N1BTD01

N1BDA

XKA10

XKA50N1BDT08N1BMT01

N1BNT04N1BNC 480 V

20

Fuel Pool Cooling

from N0BT03

20

21

23

MaintenanceCross Connects

EDG

SBO

UPS

Division 1 or 4

N1BMT03

N1BDG 4160 V

EPSSElectrical Distribution

Systems

N1BDH

G N1BDT07

480 V

4160 V

Page 27: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 27

13.8 kV

480 V

21

480 V

G

∼-

∼-

N2BMA

N2BNA01 480 V 480 VN2BND

23

N2BRA

N2BMC

N2BTP01

N2BRU01

N2BTD01

N2BDA

XKA20

N2BDT08N2BMT01

N2BNT0420

from N0BBT04

20

21

23

MaintenanceCross Connects

EDG

UPS

N2BMT03

N2BDG 4160 V

EPSS Electrical Distribution

Systems

N2BDH

N2BDT07

Division 2 or 3

480 V

4160 V

Page 28: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 28

Loss of Offsite Power (LOOP)

N0BBT01 N0BBT02 N0BBT03 N0BBT04

Division 4Division 2 Division 3Division 1

N1BDA1E 13.8kV

N2BDA1E 13.8kV

N3BDA

1E 13.8kV

N4BDA1E 13.8kV

N1BDG1E 4160V

N1BDH1E 4160V

N2BDG1E 4160V

N2BDH1E 4160V

N3BDG1E 4160V

N3BDH1E 4160V

N4BDG1E 4160V

N4BDH1E 4160V

22 55

44

11

NO NO NO NO

EDG EDG EDG EDG

SBO DG

SBO DG

To Switchyard

To Switchyard

To Switchyard

To Switchyard

Auto Start of All Four EDG’s on Loss of Offsite Power (~20 seconds)

Page 29: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 29

Station Blackout (SBO)

> Two SBO Non-Class 1E diesel generators (division 1 & 4) which are credited as Alternate AC sources (AAS) for station blackout event

> SBO diesel generators can be started and controlled either from the control room or locally

Page 30: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 30

Station Blackout

N0BBT01 N0BBT02 N0BBT03 N0BBT04

Division 4Division 2 Division 3Division 1

N1BDA

1E 13.8kV

N2BDA1E 13.8kV

N3BDA1E 13.8kV

N4BDA1E 13.8kV

N1BDG

1E 4160V

N1BDH1E 4160V

N2BDG1E 4160V

N2BDH1E 4160V

N3BDG1E 4160V

N3BDH1E 4160V

N4BDG1E 4160V

N4BDH1E 4160V

22 55

44

11

NO NO NO NO

EDG EDG EDG EDG

SBO DG

SBO DG

To Switchyard

To Switchyard

To Switchyard

To Switchyard

Manual Start of Both SBO Diesel Generators (Remote or Local)

Page 31: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 31

Onsite DC Power (Class 1E UPS)

> DC/UPS system is an evolutionary design feature:Motor operated valve loads are AC loads fed from the bus on the output of the 480VAC inverter, which is supplied from the batteryDC loads (I&C, switchgear control power, etc) are supplied downstream of UPS inverters by multiple 480VAC/250VDC and 480VAC/24VDC converters

> Advantages vs conventional DC system:Better reliability• A backup source of power is available to safety significant loads

from the 480VAC fast regulating transformers in the event of a failure of the normal inverter, battery or charger

• Safety significant loads are fed from a regulated power source vs. one in which voltage decays as the battery is discharged

Four fewer battery systems (24VDC)24VDC converters located close to the loads minimizes large diameter DC cabling runs

Page 32: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 32

Onsite Class 1E DC/UPS SLDDivision 1

N1BMC 480VAC

Battery BatteryCharger Charger

NO NC NON1BRA 480VAC

24VDC 250VDCI&C loads Circuit Breaker

Feeders

N1BND 480VAC

Inverter CROSS CONNECT

ES

- ~

~ - ~ -

~ -~ -

Division 2

Page 33: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 33

Non-Class 1E – UPS

> Two 250 VDC batteries, each supported by two 100% battery chargers

> 24 VDC I&C power is supplied from dual converters

> Power supply for the CRDM’s> Power supply for critical non-safety loads for

asset protection (turbine generator lube oil pumps, etc)

Page 34: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 34

Non-Class 1E Uninterruptible Power Supply Electrical Distribution Systems

N1BFA 480 V

N1BFX 480 V

G

Asset ProtectionPower Supply

N1BUM 250 VDC N2BUN 250 VDC

∼-

∼-

24 V DC for I&C

--

--

N1BRJ 480 VAC

∼- ∼-

N2BRK 480 VAC

Nuclear Island

Con

trol

rod

driv

es

Con

trol

rod

driv

es

Page 35: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 35

Electrical Systems Analysis

> ETAP® studies will be developed to verify the adequacy of the conceptual design

> Load flow, short circuit and dynamic analyses of the electrical system will be developed to:

Verify the adequacy of the diesel generator size and diesel generator loadingDevelop equipment specifications for transformers, switchgear, circuit breakers and MCCsDynamic transfer analyses to validate transfers to back up sources of power on a loss of a normal sourceDetermine requirements needed to assure off-site power system voltage adequacy

Page 36: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 36

Summary

> The U.S. EPR electrical systems design uses insights gained from the design of OL3 and incorporates world-wide operating experience

> The U.S. EPR electrical systems are being designed to meet applicable NRC requirements

> AREVA NP Inc. will provide sufficient information in the DCD and supporting documentation to allow the NRC to make the necessary finding with regard to safety

Robust, reliable electrical design

Page 37: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 37

Joe RedmondManager, Electrical & Fire Protection

Design and Analysis

Fire Protection and Separation Requirements

Page 38: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 38

Meeting ObjectivesFire Protection and Separation

> Provide an overview of the U.S. EPR design features to meet NRC requirements for Fire Protection

> Describe the defense-in-depth design for Fire Protection

> Provide an overview of the inherent safe shutdown design features

> Obtain early NRC feedback associated with the U.S. EPR Fire Protection strategy

Page 39: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 39

Topics

> Fire Protection Defense-in-Depth > Applicable Regulatory Requirements for U.S. EPR> Planned Approach for U.S. EPR> Elements of the Fire Protection Program> Fire Protection Design Approach> Fire Protection Systems and Design Features> Safety Train Separation> Multiple Redundancy of Safety Systems> Control Room Considerations> Containment Considerations

Page 40: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 40

Fire Protection Defense-in-Depth

> Minimize the potential for fires and explosions> Rapidly detect, control, and extinguish fires> Ensure that fire will not prevent the performance of

necessary safe shutdown functions and will not significantly increase the risk of radioactive releases to the environment

> Failure or inadvertent operation of fire protection systems will not adversely impact the ability of SSC important to safety to perform their safety functions

Page 41: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 41

U.S. EPR Fire Protection Criteria

> NUREG-0800, Standard Review Plan 9.5.1Appendix B addresses supplemental review criteria for Advanced ReactorsAppendix D addresses review criteria for fire PRAs

> SECY-90-016 and SECY-93-087

> 10CFR52.47(a)(1)(v)

> Regulatory Guide 1.189

Page 42: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 42

Fire Protection Regulatory Environment

> NFPA 804Applicable to new reactorsDeterministicAppendix B of NUREG 0800 cites NFPA 804Not endorsed by rulemaking

> NFPA 805Applicable to existing reactorsNot applicable to new reactorsNRC approved new risk-informed performance-based option -10CFR50.48(c)

> NFPA 806 is under developmentApplicable to new reactorsRisk informed / performance basedScheduled for approval in fall of 2007NRC endorsement unknown

AREVA is monitoring latest fire protectionregulatory developments

Page 43: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 43

Planned Approach for U.S. EPR

> U.S. EPR will use existing deterministic guidance (NUREG-0800, SECY 90-016 and SECY 93-087) to demonstrate compliance with NRC requirements, including Regulatory Guide 1.189

> Any deviations from existing deterministic guidance for fire protection will be based on risk-informed, performance-based analysis methods following guidance provided in NFPA 806

Page 44: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 44

Elements of the U.S. EPR Fire Protection Program (FPP)

> Comprehensive identification and analysis of fire and explosion hazards

> Organization and staff positions responsible for FPP management and implementation

> Fire prevention program> Automatic detection and suppression systems> Manual fire suppression capability> Building design features minimize the threat of fires> Safe shutdown analysis demonstrates that the plant can

achieve and maintain safe shutdown in the event of a fire> Probabilistic risk/safety analysis (PRA) specific to the U.S.

EPR design that identifies relative fire risks and vulnerabilities

Page 45: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 45

U.S. EPR Fire Protection Design Approach

> OL3 comprises the base plant design> Systematic process is being applied to prepare design for

U.S. deploymentConversion to U.S. design codes and standardsCompliance with NRC regulations and QA requirements

> Insights gained through operating experience will be incorporated into the U.S. EPR fire protection design

> U.S. based employees assigned to support OL3 to develop and implement standardization in worldwide EPR fire protection design concepts

Standardization is a design goal

Page 46: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 46

U.S. EPR Fire Protection Systems and Design Features: Fire Detection and Alarm

> Fire detection systems will be installed in all areas of the plant that contain or present an exposure fire hazard to SSCs important to safety.

Fire Detection and Alarm Systems will comply with the applicable requirements established by NFPA 72 (National Fire Alarm Code)

Page 47: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 47

U.S. EPR Fire Protection Systems and Design Features: Water Supply Systems

> Fire pumps, water supply and fire mains will be sized and arranged to ensure that:

100% capacity will be available assuming a single active failure of a fire pump or a water supply or line break with the fire mainU.S. EPR water supply systems will comply with applicable NFPA codes of record: • NFPA 20 (fire pumps)• NFPA 22 (water tanks)• NFPA 24 (fire mains)

Page 48: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 48

U.S. EPR Fire Protection Systems and Design Features: Automatic Fire Suppression

> Automatic fire suppression systems will be installed as specified to:

Fire Hazards Analysis Provide protection of redundant systems or components necessary for safe shutdown

> U.S. EPR automatic fire suppression systems will comply with applicable NFPA codes of record:

NFPA 13 (sprinkler systems)NFPA 15 (water spray systems)NFPA 2001 (clean agent systems)

Due to spatial separation and four train shutdown design, the U.S. EPR is expected to require less

automatic suppression than existing plants

Page 49: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 49

U.S. EPR Fire Protection Systems and Design Features: Manual Fire Suppression

> Manual firefighting capability will be provided throughout the plant to limit the extent of fire damage

Standpipes and hose stations will be able to reach any location that contains, or could present, a fire exposure hazardto equipment important to safetyOutside hydrants will provide effective hose stream protection for any onsite location where fixed or transient combustibles could jeopardize equipment important to safety

> U.S. EPR will comply with the applicable codes of record for manual fire suppression systems:

NFPA 10 (fire extinguishers)NFPA 14 (Standpipes and hose systems)NFPA 24 (fire hydrants)

Page 50: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 50

U.S. EPR Fire Protection Systems and Design Features: Building Design

> Building layoutSSCs important to safety will be designed and located to minimize the probability and effect of fires and explosions by utilizing passive fire barriers to subdivide the plant into separate fire areas or zonesStructural fire barrier designs will be based on NFPA 251/ASTME 119 fire endurance test protocolFire door designs will be in accordance with NFPA 80

> Materials of constructionNoncombustible and heat resistant materials will be used wherever practical throughout the plantNFPA 221 will be used as guidance for specifying requirements for the design and construction of fire walls and fire barrier walls

Page 51: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 51

U.S. EPR Fire Protection Systems and Design Features: Other Building Systems

> Electrical cable and raceway constructionCables will meet the flame test criteria of IEEE 383 or 1202Cables will be routed in metal raceways and will be separated so that a fire cannot damage redundant systems

> HVAC systems will be designed to:Limit the consequences of a fire by preventing the spread of the products of combustion to opposite/adjacent division areas Provide a means to ventilate, exhaust, or isolate fire areas as required and consideration will be given to the consequences of failure of ventilation systems caused by fire, causing loss of control for ventilating, exhausting, or isolating a given fire area

Page 52: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 52

U.S. EPR Fire Protection Systems and Design Features: Other Building Systems

> Emergency lighting will be provided as necessary to support:

manual fire-fightingsafe shutdown operationsemergency egress during a fire event

> The communication system design will ensure effective communication capability between plant personnel to support fire-fighting efforts and safe shutdown of the plant

Page 53: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 53

EPR General Plant Layout

Diesel Building 3+4

Office Building

Safeguard Building 4

Fuel Building

Nuclear Auxiliary Building

Access Building Turbine Building

Safeguard Building 2+3

Diesel Building 1+2

Safeguard Building 1

Reactor Building

Electrical Building

Waste Building

Page 54: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 54

Redundancy of Safety Systems

Four train safety concept> 1 train is in maintenance> 1 train may be affected by a fire> Remaining train(s) required for safe shutdown

will be available

U.S. EPR redundant safety systemsexceed regulatory requirements

Page 55: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 55

Safety SystemsFour Separate Buildings

Each safety train is independent and located within a physically separate building

Page 56: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 56

Control Room Considerations

> Separation of redundant trains in the control room is not practical

For a fire in the control room, an independent alternative safe shutdown capability is provided that is physically separated and electrically independent of the control room

> Remote shutdown stationMeets RG 1.189 requirements for Alternate Shutdown

Page 57: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 57

Containment Considerations

> Containment fire area contains redundant train cables

Train separation will be demonstrated by a combination of spatial separation and physical barriersFire protection for redundant divisions will be provided to ensure that at least one shutdown division will be free of fire damageFire protection design features will be provided for fire hazards in containmentAutomatic fire detection throughout containment and automatic suppression for the reactor coolant pumps will be provided

> U.S. EPR will meet the requirements of RG 1.189

Page 58: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 58

Summary

> U.S. EPR fire protection approach will be based on standard NRC guidance and requirements

Any deviations will be based on risk-informed, performance-based analysis methods (per NFPA 806)

> U.S. EPR is a robust design with increased safety margin with respect to fire safe shutdown capability

> U.S. EPR fire protection design will use insights gained from the design of OL3

> The U.S. EPR fire protection design will incorporate insights gained from operating experience

> AREVA NP Inc. will provide sufficient information in the DCD and supporting documentation to allow the NRC to make the necessary finding with regard to safety

Page 59: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 59

Next Steps

Sandra M. SloanManager, Regulatory Affairs

New Plants Deployment

Page 60: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 60

Next Steps

> Next meetings

July 25, 2006: U.S. EPR Severe Accident Mitigation Testing, Design and Analysis

August, 2006: Pre-submittal meeting for U.S. EPR Transient and Accident Analysis Code Applicability Topical Report

I&C Safety System & Operational Architecture

Page 61: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

Handouts

Page 62: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 62

U.S. EPR Electrical Systems

> AC Power Systems (Onsite)Class 1E Emergency Power Supply System (EPSS)Emergency Diesel Generator Set (EDG)Class 1E UPS System (EUPS)Non-Class 1E Normal Power Supply System (NPSS)Non-Class 1E Diesel Generator Set (NDG)Non-Class 1E UPS System (NUPS)SBO Diesel Generator Set (SBDG)Power Transmission (GEN)Lighting and Small Power System (LGT))

> DC Power Systems (Onsite)Control Rod Drive Power supply System (CRD)Non-Class 1E DC Power System (NDC)

> Offsite Power SystemSwitchyard and Preferred Power System (SWYD)

> Generic Electrical SystemsCables and Cabling Concept Description (CABL)Lightning and Grounding System (GRD)Protection and Coordination Concept (PC)

Page 63: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 63

KKS Electrical Designators

480V Class 1E Load CentersBM

480V Non-Class 1E Motor Control CentersBH

Batteries and Battery ChargersBT

DC Class 1E EquipmentBV, BW

DC Non-Class 1E EquipmentBUUPS Related EquipmentBR

480V Class 1E Motor Control CentersBN

480V Non-Class 1E Load CentersBF

13.8kV and 4160V Class 1E EquipmentBD

13.8kV and 4160V Non-Class 1E EquipmentBB

Page 64: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 64

Electrical AcronymsAAS: Alternate AC Sources

CRDM: Control Rod Drive Mechanism

DCD: Design Control Document

EDG: Emergency Diesel Generator

EPSS: Emergency Power Supply System

ETAP: Electrical Transients Analysis Program

EUPS: Emergency Uninterruptible Power Supply

MCC: Motor Control Center

MSU: Main Start Up

NI: Nuclear Island

NPSS: Normal Power Supply System

PCB: Power Circuit Breaker

PPS: Preferred Power Supply

SBO: Station Blackout

SLD: Single Line Diagram

SWYD: Switchyard

TG: Turbine Generator

TI: Turbine Island

UPS: Uninterruptible Power Supply

Page 65: Electrical Systems, Fire Protection and Train Separation ... · Electrical Systems, Fire Protection and Train Separation Requirements Overview AREVA NP Inc. and the NRC June 20, 2006

> NRC Meeting – June 20, 2006AREVA NP Inc. 65

Fire Protection Acronyms

FHA: Fire Hazard AnalysisFPP: Fire Protection ProgramPRA: Probabilistic Risk/Safety AnalysisSSC: Structures, Systems and Components