C e r t a i n Te e d
Shaftliner for Area Separation Walls
Area Separation Walls
Area Separation Walls from CertainTeed (formerly BPB)
offer the advantages of fire resistance and noise
attenuation between adjoining housing units. These
walls offer a 2-hour fire rating line of defense between
units and provide STC sound ratings up to 60-64.
Area Separation Walls are solid type separation walls
assembled using 1" ProRoc® Shaftliner Type X gypsum
board, metal framing and 1/2" ProRoc® Regular gypsum
board for the interior finish. The wall is easily stacked,
floor to floor, allowing progressive construction.
Breakaway aluminum clips are used to attach the interior
wall to adjacent structural framing and provide lateral
support. When one side is exposed to fire, the clips yield
from the heat and break away allowing the gypsum board
interior finish on the fire side to collapse. Thus the area
separation wall remains intact to protect neighboring
spaces.
Area Separation Walls can be built higher, are easier and
faster to construct, lighter weight, and take up less space
than masonry wall systems.
UL Design U366RAL TL 100-176 for STC ratings
For further technical information regarding sound control and fire resistance refer tothe following: Gypsum Association Fire Resistance Design Manual – GA-600
Area Separation Walls
HANDLING AND STORAGEProRoc® gypsum boards should bestacked flat on a smooth, level surface,not stored directly on the ground. Whenspacers are used, position them closelyenough together to minimize warpage.Care should be taken to prevent damageto edges and corners. Always keepProRoc® gypsum board dry prior toinstallation.CertainTeed assumes no responsibility for consequential damages thatmay result from the presence of standing water or where moisture isin direct contact with area separation wall system components.
CUTTINGThe score and snap method is a fast andefficient way to cut gypsum board.Steps:1. On the face side, position a straight
edge along the line of cut.2. Score sheets with a knife or other
suitable tool.3. With a quick, firm motion, snap back
away from the face.4. The back paper can either be cut with
a knife or separated by snapping thepiece in the opposite direction.
WORKING WITH THE PRODUCT5. Smooth all cut ends and edges to
ensure tight joints.
Gypsum boards can also be cut with a saw.For information on avoiding dustinhalation, refer to a Material Safety DataSheet available where CertainTeedproducts are sold. Safety glasses shouldalways be worn when using power tools.To make cut outs, score around theperimeter on the face and back and tapout the waste piece from the face side. Cutouts can also be made with a drywall saw.
INSTALLATIONSteel Framing and Installation of 1"ProRoc® Shaftliner Type X board for SolidType Area Separation Walls are used asthe common wall of one unit. An areaseparation wall can be constructed byfollowing these steps before continuingto frame the adjacent unit.
1. Attach 2" wide C-Track to slab atbottom of wall using suitable fastenersat a minimum of 24" o.c. Allow a 3/4"space from wood stud framing on eachside of the area separation wall.
2. Install vertical C-Track at the beginningof the wall and support as needed.
3. Insert two sections of 1" ProRoc®
Shaftliner Type X gypsum board in bottomchannel and plumb to vertical C-Track.
4. Install 1" ProRoc® Shaftliner Type Xboards vertically. Continue wall asneeded by placing H-Studs between theproceeding panels every 24" for thelength of the wall and enclose the endboards with vertical C-Track.
5. Cap the wall assembly before continuinghigher using C-Track fastened to the H-Studs on alternate sides with 3/8"Type S screws. A second C-Track for thenext row of shaftliner panels is thenplaced back to back with end jointsstaggered at least 12" o.c. and fastenedwith double 3/8" Type S screws at endsand 24" o.c.
6. Attachment Clips: Aluminum angle,0.063" thick, min. 2" wide with min. 2"and 2-1/4" legs. Clips secured withType S screws 3/8" long to “H” studsand with Type W screws 1-1/4" long towood framing through holes providedin clip. Clips spaced a max of 10' o.c.
NNoonn--llooaadd bbeeaarriinnggFFiirree RRaattiinngg -- 22 HHoouurrFFiinniisshh RRaattiinngg -- 112200 MMiinnuutteess
EXPOSED TO FIRE FROM AREA SEPARATION WALL SIDE ONLY
EXPOSED TO FIRE FROM EITHER SIDE
FIRE TESTUL DESIGN U366
THICKNESS7-1/4"
(184 mm)
APPROX. WT.11 psf
(56 kg/m2)STC 60-64
FIRE TESTUL DESIGN U366
THICKNESS12-1/2"
(317 mm)
APPROX. WT.14 psf
(70 kg/m2)STC 60-64
Sound ratings (STC 60-64) are based on installed adjoining wood framed construction finished with 1/2" thick drywall on interior wall, with 3-1/2" fiberglass insulation in the framing cavities.
1" ProRoc® Shaftliner Type X Gypsum Board(2 layers)
#25 MSG Galv Steel “H” Studs(typical) 24" o.c. Maximum
#25 MSG Galv 2" Steel Channel(typical) 24" o.c. Maximum
1/2" ProRoc® Regular Gypsum BoardApplied Horizontally or Vertically
Insulationto Achieve STC 60-64
.063" Aluminum AngleAttachment Clips
3/4" Air SpaceNOM 2x4" Wood Studs24" o.c. Maximum
1" ProRoc® Shaftliner Type XGypsum Board (2 layers)
#25 MSG Galv Steel “H” Studs(typical) 24" o.c. Maximum
#25 MSG Galv 2" Steel Channel(typical) 24" o.c. Maximum
1/2" ProRoc® Regular Gypsum BoardApplied Horizontally or Vertically
Insulationto Achieve STC 60-64
.063" Aluminum AngleAttachment Clips
3/4" Air SpaceNOM 2x4" Wood Studs24" o.c. Maximum
vertically between wood framing and“H” studs for separation walls up to 23'high. For separation walls up to 44'high, clips spaced as described abovefor the upper 24' and the remainingwall area below requires clips spaced amax. 5' o.c. vertically between woodframing and “H” studs.
7. This assembly can be repeated, perplan, up to 44 feet high. Cap the top ofthe assembly with 2" C-Track andprotect the entire installation frommoisture.
8. Where required, use an approvedacoustical sealant to caulk around theperimeter of wall sections.
Interior Finish Wall:9. Wood Studs - Nom 2" by 4" max.
spaced 24" o.c. Studs cross-braced atmid-height where necessary for clipattachment. Min. 3/4" separationbetween wood framing and areaseparation wall.
10.ProRoc® Regular gypsum board min.1/2" thick, 4' wide, applied eitherhorizontally or vertically. Wall board
attached to studs with 1-1/4" long steeldrywall nails or 1-1/4" Type W drywallscrews spaced 8" o.c. Vertical jointslocated over studs. Joints covered withpaper tape and joint compound. Nailheads covered with joint compound.
Surface Preparation of Finished Sides
Joints, corners and fastener heads on theface side shall be finished in accordancewith ASTM C 840, the GA-216, the FireResistance Design Manual GA-600 andjoint compound manufacturer’sinstructions. joint compound shall comply with ASTM C 475.
1. No surface treatment shall be done untilthe interior temperature has beenmaintained at a minimum of 50°F(21°C) for at least 48 hours prior toapplication of compounds and until allmaterials have completely dried.Adequate continuous ventilation mustalso be provided.
2. Fill and level joints with joint compound.3. Embed tape into the wet compound and
allow to dry. For inside corners, crease
the tape and work it into joint.4. Apply a second coat of compound across
the joint and feather to approximately 4"on each side.
5. Apply a third coat and feather toapproximately 6" on each side.
6. Allow each coat to dry before proceeding.7. Attach corner bead to outside corners
and apply three coats of joint compound.Feather out each coat as described insteps 4-6.
8. Spot cover all fastener heads with threecoats of joint compound applied indifferent directions.
9. Lightly sand the last coat of all treatedareas, taking care not to rough thesurrounding gypsum board paper.Smoothing can also be accomplishedwith a damp sponge.
Finishing Interior Walls
ProRoc® gypsum board can be finished withpaint, texture or wallpaper. High qualityprimer/sealer must be used prior to any typeof final decoration. For high gloss paint andsevere lighting conditions, a thin skim coat ofjoint compound should be applied across theentire surface (Level 5 Finish). This will helpminimize the irregularities and porositydifferences between the materials. Refer toGA-214, GA-216, and ASTM C 840 foradditional finishing instructions. Finishing isnot required on area separation wall.
LIMITATIONS• Area Separation Walls are for non load-
bearing partitions only.• ProRoc® gypsum board must not be used
in areas that are continuously orrepeatedly exposed to excessive moistureor dampness.
• Systems shall not be exposed to sustainedtemperatures exceeding 125°F (52°C).
• ProRoc® gypsum board should not comein direct contact with concrete, masonryor other surfaces that have a highmoisture content.
• Unsupported wall height between floorsshould not exceed 12 feet. The assemblymay be used in buildings up to 4 storieswith a total height not to exceed 44 feet.
• Penetrations in Area Separation Walls areusually not allowed by code authorities.
IntermediateStory
IntermediateFloor
First Floor
Foundation orBearing Wall
Vertical H-Studs not
shown
First Story
Roof Deck
C-Track
2x4 WoodFraming
OptionalInsulation
1" ProRoc®
ShaftlinerType X
GypsumBoard
(2 layers)
AluminumClips
3/4" Air Space
Joist
Roof Truss
1/2" ProRoc®
Regular GypsumBoard
Two C-Tracks
ProRoc® Gypsum Board,insulation or other FireStopping/Draft Stoppingas required.
C-Track
C-Track Fasterners24" o.c.
H-STUD
ASW ALUMINUM CLIP
C-TRACK
TYPICAL INSTALLATION
2"13⁄8"
2"
2"
21⁄4"
1"
2"
Not to scale
TECHNICAL REFERENCESFor additional information on application and finishing consult:• ICC International Codes• UL Fire Resistance Directory - UL Design U366• Gypsum Association Brochure GA-290• GA-600 GA File No. AWS 1003• ASTM E 84, E 90, E 119• Riverbank Acoustical Laboratories TL100-176
COMPONENT SPECIFICATIONS
When tested inaccordance with theAmerican Society forTesting and MaterialsASTM E 84.
SURFACE BURNING CHARACTERISTICS
Consult local building codes for regulations in your area. For furtherinformation consult a CertainTeed sales representative.
ProRoc® Shaftliner Steel Type X Gypsum Board Framing
ASTM C 1396, C 442 C-Track25 Ga, 2"
Thickness 1" (25.4 mm) H-Stud25 Ga, 2"
Width 2' (609.5 mm) Alum Clip.063", 2"
Lengths 8', 12'(2438 mm, 3658 mm)
Approx. 4.1 psf (20 kg/m2)Weight
Edges Beveled
Paper Green Face, Green Back
ProRoc® Shaftliner Type X Gypsum Board
Flame 0 - 25 (Class A)Spread
Smoke 0Developed
LIMITED WARRANTYCERTAINTEED EXPRESSLY WARRANTS TITLE ANDTHAT THE PRODUCTS SOLD BY IT HEREUNDER AREFREE FROM DEFECTS IN MATERIALS AT THE TIMEOF SHIPMENT. THIS WARRANTY IS LIMITED TO THEORIGINAL OWNER, AND MAY NOT BE ASSIGNED ORTRANSFERRED. THIS WARRANTY MAY NOT BEAMENDED, RESTATED OR ENLARGED BY ANYCERTAINTEED REPRESENTATIVE, WRITTEN SALESINFORMATION OR DRAWINGS. EXCEPT FOR SUCHEXPRESS WARRANTY, CERTAINTEED MAKES NOWARRANTY OF ANY KIND WHATSOEVER, EXPRESSOR IMPLIED AND ALL WARRANTIES OFMERCHANTABILITY, FITNESS FOR A PARTICULARPURPOSE, AND OTHER WARRANTIES OF ANY KINDARE HEREBY DISCLAIMED BY CERTAINTEED ANDEXCLUDED. PURCHASER AGREES THIS HAS BEENNEGOTIATED AND CONSENTS HERETO. ASPURCHASER’S SOLE AND EXCLUSIVE REMEDY,CERTAINTEED SHALL, AT CERTAINTEED’S SOLEOPTION, REPLACE OR REPAIR ANY DEFECTIVEPRODUCTS, REFUND THE PURCHASE PRICE PAIDFOR DEFECTIVE PRODUCTS, OR GRANT AREASONABLE ALLOWANCE BASED ON THEPURCHASE PRICE OF SUCH DEFECTIVE PRODUCTS.ANY CLAIMS OR EXCEPTIONS BY PURCHASER FORDEFECTIVE PRODUCTS MUST BE MADE IN WRITINGWITHIN 30 DAYS AFTER PURCHASER’S RECEIPT OFSHIPMENT AND IN ALL EVENTS BEFOREINSTALLATION IS COMMENCED, AND PURCHASER
SHALL GIVE CERTAINTEED AN OPPORTUNITY TOINVESTIGATE. CERTAINTEED IS FURNISHING BASICPRODUCTS AT STANDARD PRICES AND IS NOT INSURING PURCHASER AGAINST POSSIBLECONSEQUENCES OF ERROR, OMISSION ORNEGLECT IN PRODUCTION OR DELIVERY, EXCEPTFOR REPLACEMENT OR REPAIR OF THE PRODUCT,REFUND OF THE PURCHASE PRICE, OR GRANT OF AREASONABLE ALLOWANCE, IN CERTAINTEED’S SOLEDISCRETION, CERTAINTEED SHALL NOT, UNDERANY CIRCUMSTANCES, BE LIABLE ON ACCOUNT OFANY IMPERFECTION, DEVIATION FROMSPECIFICATIONS OR OTHER DEFECT IMPAIRING THEQUALITY, VALUE OR SUITABILITY FOR ANY PURPOSEOF ANY PRODUCT SOLD HEREUNDER, WHETHERPURSUANT TO THE EXPRESS LIMITED WARRANTYOR OTHERWISE, IN NO EVENT SHALL CERTAINTEEDBE LIABLE FOR CONSEQUENTIAL, SPECIAL,INCIDENTAL, INDIRECT, PENAL OR CONTINGENTDAMAGES, WHETHER BASED UPON BREACH OFWARRANTY, NEGLIGENCE, STRICT LIABILITY, TORT,BREACH OF CONTRACT, OR ANY OTHER LEGALTHEORY. PURCHASER ASSUMES ALL RISK OF LOSS,DAMAGE OR DELAY INCIDENT TO THE FURNISHINGOF ANY PRODUCT BY CERTAINTEED HEREUNDER,OR THE UTILIZATION THEREOF, EXCEPT TO THEEXTENT EXPRESSLY ABOVE PROVIDED. PURCHASERAGREES THIS HAS BEEN NEGOTIATED ANDCONSENTS HERETO.
Characteristics, properties or performance of materials or systems manufactured by CertainTeed herein described are derived from data obtained under controlled test conditions. CertainTeed makes no warranties, expressor implied, as to their characteristics, properties or performance under any variations from such conditions in actual construction. CertainTeed assumes no responsibility for the effects of structural movement.
™® CertainTeed and the tag line “Quality made certain. Satisfaction guaranteed.” are trademarks of CertainTeed Corporation. All other trademarks are the property of BPB plc or its affiliates and related companies.
NOTICE: The information in this document is subject to change without notice. CertainTeed assumes no responsibility for any errors that may inadvertently appear in this document.
©01/07 CertainTeed Corporation, Printed in U.S.A. Form # CTG-2318 Rev A/W/06-2007
CertainTeed CorporationP.O. Box 860Valley Forge, PA 19482
Professional: 800-233-8990Consumer: 800-782-8777www.certainteed.com
ASK ABOUT OUR OTHER CERTAINTEED PRODUCTS AND SYSTEMS:E X T E R I O R : R O O F I N G • S I D I N G • W I N D O W S • F E N C E • R A I L I N G • T R I M • D E C K I N G • F O U N D A T I O N S • P I P E
I N T E R I O R : I N S U L A T I O N • W A L L S • C E I L I N G S