14 Electrak has led the power distribution market for cavity floor solutions since 1984 when it launched the first small power track system. With minimal parts and push-fit assembly, this flexible system is easy to install and minimises disruption as office layouts evolve. DESIGN AND INSTALLATION The system consists of continuous lengths of track (generally arranged in parallel format) which are fed from the distribution board via track feed boxes and can be installed in floor voids as low as 48 mm. Track lengths fit together using integral track connectors for quick assembly with access to power via tap-offs from the shuttered outlets. Electrak ® power track underfloor distribution system

electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

  • Upload
    doananh

  • View
    225

  • Download
    0

Embed Size (px)

Citation preview

Page 1: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

14

electrak has led the power distribution market for cavity fl oor solutions since 1984 when

it launched the fi rst small power track system. With minimal parts and push-fi t assembly,

this fl exible system is easy to install and minimises disruption as offi ce layouts evolve.

deSIgn and InStaLLatIOn

The system consists of continuous lengths of track

(generally arranged in parallel format) which are fed from

the distribution board via track feed boxes and can be

installed in fl oor voids as low as 48 mm.

Track lengths fi t together using integral track connectors

for quick assembly with access to power via tap-offs from

the shuttered outlets.

electrak®

power trackunderfl oor distribution system

Page 2: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

15

extended range

Available in four versions to meet all power requirements

in today's modern offices... standard, low noise / clean

earth, dual circuit and three phase.

Integral track connector plugs into track feed unit.

Tap-off units plug into shuttered socket outlets and lock on to track body. Remove by compressing side clips and pulling out.

Integral fixing brackets fixed to track

2 on 1.2 m track2 on 2.4 m track3 on 3.6 m track

Lengths of track fit together by simply plugging the integral track connector into the end of the previous fitted track length.

Page 3: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

16

Electrak® power track systems

Track lengths with 300 mm socket centres

Description Length (m)

4 sockets

8 sockets

12 sockets

1·2

2·4

3·6

Standard tap-off

Low noise / clean earth tap-off

Dual circuit tap-off

3 phase tap-off

Tap-off, track feed and track connector key code

32 A unfused 16 mm Ø L, N, PE

13 A fused 16 mm Ø L, N, PE

13 A 543·7 unfused 16 mm Ø L, N, PE

32 A unfused 16 mm Ø CE, L, N, PE

13 A fused 16 mm Ø CE, L, N, PE

13 A 543·7 unfused 16 mm Ø CE, L, N, PE

32 A unfused 20 mm Ø CE, L1, N1 L2, N2, PE

32 A 415 V 3 phase 20 mm Ø L1, L2, L3, N, PE

32 A L1 unfused reconfigurable live pin 16 mm Ø L1, N, PE

32 A L2 unfused reconfigurable live pin 16 mm Ø L1, N, PE

32 A L3 unfused reconfigurable live pin 16 mm Ø L1, N, PE

3

5

3

5

3

5

3

5

3

5

3

5

3

5

3

5

3

5

3

5

3

5

Track feed

Flexible interlink / corner

Excluding cables and conduit

Flexible metal conduit

Flexible metal conduit

1·2

2·4

016_017P_D2010 v5.qxd 4/6/10 08:59 Page 16

Page 4: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

17

ELECTRAK 24Standard system

(white)

ELECTRAK 25Low noise / clean earth

system (light green)

ELECTRAK 26Dual circuit system

(dark green)

ELECTRAK 273 phase system

(grey)

DA1123 JA2123 KA3123 NA4123

DA1243 JA2243 KA3243 NA4243

DA1363 JA2363 KA3363 NA4363

(1) All NP tap-offs are reconfigurable between L1, L2 or L3 for 3 phase track

DP1332 – DP1332 –

DP1532 – DP1532 –

DP1313 – DP1313 –

DP1513 – DP1513 –

DP1327 – DP1327 –

DP1527 – DP1527 –

– JP2332 JP2332 –

– JP2532 JP2532 –

– JP2313 JP2313 –

– JP2513 JP2513 –

– JP2327 JP2327 –

– JP2527 JP2527 –

– – KP3328 –

– – KP3528 –

– – – NZ4331

– – – NZ4531

– – – NP4332(1)

– – – NP4532(1)

– – – NP4302(1)

– – – NP4502(1)

– – – NP4303(1)

– – – NP4503(1)

DF1010 JF2010 KF3010 NF4010

DW1000 JW2000 KW3000 NW4000

DW1010 JW2010 KW3010 NW4010

DW1020 JW2020 KW3020 NW4020

016_017P_D2010 v5.qxd 4/6/10 08:59 Page 17

Page 5: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

Electrak® 24 power track systemstandard system (white)

18

Pack Cat. Nos. Tap-off units

Tap-off length is determined by the cable and notthe conduit length, e.g. a 3 m tap-off has 3 m ofcable and 2·8 m of flexible metal conduit(1)

Tap-off units in excess of 3 m should only be used ifthey contain a fuse or if the power track is protectedby a 32 A rated protective device

32 A unfused

16 mm Ø‚ L, N, PE

1 DP1332 3 m1 DP1532 5 m

13 A fused

16 mm Ø‚ L, N, PE

1 DP1313 3 m1 DP1513 5 m

13 A 543·7 fused - high integrity

16 mm Ø‚ L, N, PE

1 DP1327 3 m1 DP1527 5 m

Pack Cat. Nos. Track system components

Electrak 24 standard track lengths

Track lengths fit together using the integralconnectors on each lengthTrack lengths should always be secured using theintegral floor fixing brackets300 mm socket centres

1 DA1123 1·2 m, 4 sockets, 2 floor fixing brackets1 DA1243 2·4 m, 8 sockets, 2 floor fixing brackets1 DA1363 3·6 m, 12 sockets, 3 floor fixing brackets

Track feed unit

1 DF1010 With one 25 mm diameter hole suitable for MICC,armoured cables or single core cables in conduit

Flexible interlinks

Can be used to overcome obstructions or as corners where required

1 DW1000 Excluding cables and conduit1 DW1010 1·2 m flexible metal conduit1 DW1020 2·4 m flexible metal conduit

Special fixing brackets

Required when track is raised off surface levelBrackets raise track by 21 mm and should be spaced 600 mm apart

1 DZ1210 For fitting under track body and track feed1 DZ1230 For fitting under integral track connectors

Selection chart (p. 16-17)Dimensions and technical information (p. 22-25)

Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring RegulationsA compact system that can be installed in floor voids as low as 48 mm

DW1010

DF1010

DP1332DA1123

(1) Tap-offs are supplied as standard with flexible metal conduit

For alternative wiring solutions, contact us on +44 (0) 845 600 6266

- --/

- --

018_019P_D2010 v1.qxd 4/6/10 09:02 Page 18

Page 6: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

Electrak® 25 power track systemlow noise / clean earth system (light green)

19

Pack Cat. Nos. Tap-off units

Tap-off length is determined by the cable and notthe conduit length, e.g. a 3 m tap-off has 3 m ofcable and 2·8 m of flexible metal conduit(1)

Tap-off units in excess of 3 m should only be used ifthey contain a fuse or if the power track is protectedby a 32 A rated protective device

32 A unfused

16 mm Ø‚ CE, L, N, PE

1 JP2332 3 m1 JP2532 5 m

13 A fused

16 mm Ø‚ CE, L, N, PE

1 JP2313 3 m1 JP2513 5 m

13 A 543·7 fused - high integrity

20 mm Ø‚ CE, L, N, PE

1 JP2327 3 m1 JP2527 5 m

Pack Cat. Nos. Track system components

Electrak 25 low noise / clean earth track lengths

Track lengths fit together using the integralconnectors on each lengthTrack lengths should always be secured using theintegral floor fixing brackets300 mm socket centres

1 JA2123 1·2 m, 4 sockets, 2 floor fixing brackets1 JA2243 2·4 m, 8 sockets, 2 floor fixing brackets1 JA2363 3·6 m, 12 sockets, 3 floor fixing brackets

Track feed unit

1 JF2010 With one 25 mm diameter hole suitable for MICC,armoured cables or single core cables in conduit

Flexible interlinks

Can be used to overcome obstructions or as corners where required

1 JW2000 Excluding cables and conduit1 JW2010 1·2 m flexible metal conduit1 JW2020 2·4 m flexible metal conduit

Special fixing brackets

Required when track is raised off surface levelBrackets raise track by 21 mm and should be spaced 600 mm apart

1 DZ1210 For fitting under track body and track feed1 DZ1230 For fitting under integral track connectors

Selection chart (p. 16-17)Dimensions and technical information (p. 22-25)

Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring RegulationsA compact system that can be installed in floor voids as low as 48 mm

JW2010

JF2010

JP2332JA2123

- --/

- --

(1) Tap-offs are supplied as standard with flexible metal conduit

For alternative wiring solutions, contact us on +44 (0) 845 600 6266

018_019P_D2010 v1.qxd 4/6/10 09:04 Page 19

Page 7: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

Electrak® 26 power track systemdual circuit system (dark green)

20

Pack Cat. Nos. Tap-off units

Tap-off length is determined by the cable and notthe conduit length, e.g. a 3 m tap-off has 3 m ofcable and 2·8 m of flexible metal conduit(1)

Tap-off units in excess of 3 m should only be used ifthey contain a fuse or if the power track is protectedby a 32 A rated protective device

Standard 32 A unfused

16 mm Ø‚ L, N, PE

1 DP1332 3 m1 DP1532 5 m

Standard 13 A fused

16 mm Ø‚ L, N, PE

1 DP1313 3 m1 DP1513 5 m

Standard 13 A 543·7 fused

16 mm Ø‚ L, N, PE

1 DP1327 3 m1 DP1527 5 m

Low noise / clean earth 32 A unfused

16 mm Ø‚ CE, L, N, PE

1 JP2332 3 m1 JP2532 5 m

Low noise / clean earth 13 A fused

16 mm Ø‚ CE, L, N, PE

1 JP2313 3 m1 JP2513 5 m

Low noise / clean earth 13 A 543·7 fused

20 mm Ø‚ CE, L, N, PE

1 JP2327 3 m1 JP2527 5 m

Dual circuit 32 A unfused

20 mm Ø‚ CE, L1, N1, L2, N2,PE

1 KP3328 3 m1 KP3528 5 m

Pack Cat. Nos. Track system components

The dual power track system has both standard andlow noise / clean earth systems incorporated

Electrak 26 dual circuit track lengths

Track lengths fit together using the integralconnectors on each lengthTrack lengths should always be secured using theintegral floor fixing brackets300 mm socket centres

1 KA3123 1·2 m, 4 sockets, 2 floor fixing brackets1 KA3243 2·4 m, 8 sockets, 2 floor fixing brackets1 KA3363 3·6 m, 12 sockets, 3 floor fixing brackets

Track feed unit

1 KF3010 With one 25 mm diameter hole suitable for MICC,armoured cables or single core cables in conduit

Flexible interlinks

Can be used to overcome obstructions or as corners where required

1 KW3000 Excluding cables and conduit1 KW3010 1·2 m flexible metal conduit1 KW3020 2·4 m flexible metal conduit

Special fixing brackets

Required when track is raised off surface levelBrackets raise track by 21 mm and should be spaced 600 mm apart

1 DZ1210 For fitting under track body and track feed1 DZ1230 For fitting under integral track connectors

Selection chart (p. 16-17)Dimensions and technical information (p. 22-25)

Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring RegulationsA compact system that can be installed in floor voids as low as 48 mm

KW3010

KF3010

KP3328KA3123

- --/

- --

(1) Tap-offs are supplied as standard with flexible metal conduit

For alternative wiring solutions, contact us on +44 (0) 845 600 6266

020_021P_D2010 v1.qxd 4/6/10 09:12 Page 20

Page 8: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

Electrak® 27 power track system3 phase system (grey)

21

Pack Cat. Nos. Tap-off units

Tap-off length is determined by the cable and notthe conduit length, e.g. a 3 m tap-off has 3 m ofcable and 2·8 m of flexible metal conduit(1)

Tap-off units in excess of 3 m should only be used ifthey contain a fuse or if the power track is protectedby a 32 A rated protective device

32 A 415 V 3 phase

20 mm Ø‚ L1, L2, L3, N, PE

1 NZ4331 3 m1 NZ4531 5 m

32 A L1(2) unfused

Unfused Reconfigurable live pin16 mm Ø‚ L, N, PE

1 NP4332 3 m1 NP4532 5 m

32 A L2(2) unfused

Unfused Reconfigurable live pin16 mm Ø‚ L, N, PE

1 NP4302 3 m1 NP4502 5 m

32 A L3(2) unfused

Unfused Reconfigurable live pin16 mm Ø‚ L, N, PE

1 NP4303 3 m1 NP4503 5 m

Pack Cat. Nos. Track system components

Electrak 27 3 phase track lengths

Track lengths fit together using the integralconnectors on each lengthTrack lengths should always be secured using theintegral floor fixing brackets300 mm socket centres

1 NA4123 1·2 m, 4 sockets, 2 floor fixing brackets1 NA4243 2·4 m, 8 sockets, 2 floor fixing brackets1 NA4363 3·6 m, 12 sockets, 3 floor fixing brackets

Track feed unit

1 NF4010 With one 25 mm diameter hole suitable for MICC,armoured cables or single core cables in conduit

Flexible interlinks

Can be used to overcome obstructions or as corners where required

1 NW4000 Excluding cables and conduit1 NW4010 1·2 m flexible metal conduit1 NW4020 2·4 m flexible metal conduit

Special fixing brackets

Required when track is raised off surface levelBrackets raise track by 21 mm and should be spaced 600 mm apart

1 DZ1210 For fitting under track body and track feed1 DZ1230 For fitting under integral track connectors

Selection chart (p. 16-17)Dimensions and technical information (p. 22-25)

Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring RegulationsA compact system that can be installed in floor voids as low as 48 mm

NW4010

NF4010

NZ4331NA4123

- --/

- --

(1) Tap-offs are supplied as standard with flexible metal conduit

For alternative wiring solutions, contact us on +44 (0) 845 600 6266

(2) All NP tap-offs are reconfigurable between L1, L2, or L3 for

3 phase track

020_021P_D2010 v1.qxd 4/6/10 09:17 Page 21

Page 9: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

Electrak® power track systemsdesign and installation

22

7593

2 x 25 Ø

46

25 Ø

46

250

47

109118

3215

68

65

92

End view BEnd view A

Integralfixing bracketfixing centres

All dimensions (mm) are nominal

■ General installation notesElectrak power track is a compact system that can be installed in floorvoids as low as 48 mm

Track feed boxes are provided with one or two 25 mm diameter holessuitable for MICC, armoured cables or single core cables in conduitTrack lengths connect together and to track feeds using the integralconnectors on each length

Track lengths should always be secured using the integral floor fixingbrackets ; three on the 3·6 m length and two on 2·4 m or 1·2 m lengthsAccess to power is provided along the track length by simply pluggingtap-off units into shuttered socket outlets. These tap-off units feed alltypes of conventional floor service outlet boxes or feed workstationsdirectly through the floor via 4 mm2 or 1·5 mm2 insulated conductorscontained in flexible metal or VO rated nylon conduit. When connectingtap-offs directly through the floor via grommet outlets to workstationscare must be taken to ensure that the tap-off length is adequate

The dual power track system has both standard and low noise / cleanearth systems incorporated. As well as dual tap-offs, both standardand low noise / clean earth tap-offs can be plugged into any socketoutlet along the track length. The dual tap-off incorporates bothstandard and low noise cables

Optimum layout flexibility is achieved by positioning track lengths amaximum of 5·2 m apart and 2·5 m from the wall, and by connectingthe 3 m tap-off units to floor outlet boxes. This means every part of thefloor area can be served. Flexible interlinks can be used to overcomeobstructions or used as corners if required

■ Special fixing bracketsWhen installing track off-floor, Electrak special fixing brackets raisetrack by 21 mm. Ensure brackets are spaced 600 mm apart andalways have support under the integral track connector and track feed.Failure to do so may undermine the integrity of the system

DZ1210 raised off-floor fixing brackets are spaced at 600 mm centresalong track. Also use bottom half of bracket under track feed andflexible interlinkDZ1230 raised off-floor fixing brackets are always used under integraltrack connectors. Track is secured to raised brackets using the track’sintegral fixing bracket

50 mm

99 mm

7 mm Ø

DZ121021 mm to underside of track36 mm to top of track

Integral track connector

DZ1210

185 mm

7 mm Ø

Integral track fixing bracket screws to special bracket

■ Dimensions

■ Example floor layout

2·5

m5

·2 m

5·2

m

track feed

5·2

m 3 m flexible

tap-off unit

floor service

outlet box

integral track

connectors

socket outlet points every

300 or 600 mm along

track length

022_025P_D2010 v3.qxd 4/6/10 09:19 Page 22

Page 10: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

23

Electrak® power track systemsinstallation

Fix track feed to surface1

Connect track length to track feed2

Connect additional track lengths3

Secure track lengths to surface4Pull out track fixingbracket lugs andscrew fix on both sides

Track outletsreusable plasticdust covers

First trackfixing bracket

Power trackand integraltrack connector

Track length

Track feedMake chalk line toalign track lengths

Plug-in key code

Direction oftrack run

Integral trackconnector

Push down

Push down

Removedust cover

Track feed

Remove dust coverbefore connectingtrack connector

Make sure trackconnector clips arefully pushed home onboth sides of track

All integral track fixing bracketsmust be fixed to surface at 1·2 mfixing centres from first bracketon each track length

022_025P_D2010 v3.qxd 4/6/10 09:28 Page 23

Page 11: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

24

Electrak® power track systemstechnical information

■ Earth fault loop impedanceBS 7671 : 2008 IEE Wiring Regulations require accurate determinationof the total earth loop impedance, which must be sufficiently low toallow the protective device to operate within the specified time, whichfor socket outlets is 0·4 seconds. The values relevant to Electrak forcalculating the earth fault loop impedance are shown in the electricaltest data table, see opposite

■ DurabilityElectrak systems are superbly designed and extremely robust. Theycan be expected to stand up to all normal site conditions. Electrak hasbeen short circuit strength tested by ASTA

■ Installations with high protective conductor currentsAll unfused tap-offs comply with Regulation 543·7 without the need foradditional earth conductors. Regulation 543·7·1·3 (ii) states “a singlecopper protective conductor having a cross-sectional area of not lessthan 4 mm2, complying with the requirements of Regulations 543·2 and543·3, the protective conductor being enclosed to provide additionalprotection against mechanical damage, for example, within a flexibleconduit”For 543·7 installations with high protective conductor currents requiringfused tap-offs, a 543·7 compliant tap-off must be used. Normally fusedtap-offs incorporate 1·5 mm2 conductors, however in the fused 543·7tap-offs, the 1·5 mm2 earth conductor is replaced with a 4 mm2

conductor and therefore complies with Section 543·7·1·3 (ii)

■ 32 A tap-off unitThe 32 A tap-off unit comprises an unfused tap-off with either 2·8 m of16 mm / 20 mm diameter flexible metal conduit or VO rated nylonconduit both with integral 4 mm2 LSOH conductors

These units are designed to comply with regulation 434·2·1 of the IEE Wiring Regulations by virtue of the following :• maximum length of cable is 3 m• it is factory assembled and fully tested item with cable installed inhigh quality flexible conduit

Fault condition protection for the tap-off assembly and the floor boxsocket outlets is delivered by the circuit protection deviceDisconnection time for socket outlets is 0·4 seconds (Regulation411·3·2·2). The Electrak system meets this requirement

Tap-off units in excess of 3 m should only be used if they contain afuse or the power track is protected by a 32 A rated protective device

■ Standards

Approved to ASTA Standard 138BS EN 60439-2 : 2000Manufactured within an approved ISO 9001 : 2008 facilityAssessed Quality Assurance Certificate No. 10679Electrak fully complies with the requirements of BS 7671 : 2008(IEE Wiring Regulations)

022_025P_D2010 v3.qxd 4/6/10 09:30 Page 24

Page 12: electrak power track underfl oor distribution systemwview.denaploy.co.uk/public/Appendix 4/Electrical Services/Man Lit... · deSIgn and InStaLLatIOn The system consists of continuous

Electrak® power track systemstechnical data

25

Rated current 63 A

Rated voltage 230/400 V~

Frequency 50/60 Hz

Conductor resistance - live and neutral 3·0 mΩ/m

Conductor impedance 1·5 mΩ/m

Phase busbar 1·5 mΩ/m

Earth busbar 1·5 mΩ/m

Earth housing 1·1 mΩ/m

Earth busbar and housing 0·8 mΩ/m

Cable connector 0·4 mΩTrack connector 0·6 mΩ32 A tap-off 0·6 mΩ+ 4 mm2 cable 11 mΩ/m

Flexible corner assembly 1·5 mΩ+ 10 mm2 cable 4·0 mΩ/m

Rated conditional short-circuit current 16 KA

Ambient temperature 25˚C

Busbars 3·0 mV/A/m

Cable connector 0·4 mV/A

Track connector 0·4 mV/A

32 A tap-off 0·4 mV/A

+ 4 mm2 cable 11 mV/A/m

Flexible corner assembly 1·5 mV/A

+ 10 mm2 cable 4·0 mV/A/m

Number of conductors 3 to 6

Busbar conductor cross sectional area 13 mm2

Housing cross sectional area (copper equivalent) 13 mm2

Cable terminal capacity 16 mm2

Tap-off cable 32 A 4 mm2

Tap-off cable 13 A fused 1·5 mm2

Tap-off conduit, up to 4 conductors 16 mmØ

Tap-off conduit, 5 and 6 conductors 20 mmØ

Flexible corner cable (tri-rated, high temperature) 10 mm2

Flexible corner conduit 25 mmØ

IP rating 40

Power track housing Galvanised steel, natural finish

Busbars High conductivity copper

Busbar insulator PTFE

Track connector/socket outlet/track feed connector Flame retardant polycarbonate

Socket outlet entry shutter Acetal

Tap-off housing Flame retardant polycarbonate

Track connector blades Copper

Tap-off blades Copper

Tap-off/flexible corner conduit, metal Electro-galvanised steel

Tap-off conduit, plastic VO rated

Tap-off cable LSOH to BS 7211

Flexible interlink cable Tri-rated to BS 6231

Track feed box/flexible interlink boxes Galvanised steel

Track feed connector terminals/earth block Brass

Track fixing brackets Galvanised steel

13 A tap-off, fuse To BS 1362, ASTA approved

Electrical test data

Volt drops (live and neutral)

Earth fault loop impedance

Mechanical data

Material specifications