UNDERFLOOR TO WORKSTATION / SYSTEM gUIDE

Electrak®...powering the workstation

P O W E R E D B Y S P E C I A L I S T S

Page 2: Legrand uk electrak brochure

Global strength built on local knowledge

Legrand is the global specialist in electrical and digital building infrastructures. Innovation is the driving force behind its development. With an increasing investment in research and development (circa 5% of sales) and more than 4,000 active patents, the Legrand Group is focused on maintaining a high rate of new product launches that present innovative solutions to the market.

LeGrand In the UK - poWered by specIaLIstsIn the UK Legrand has developed a customer focused structure which harnesses the power of its market leading specialist brands including bticino, electrak and Zucchini to deliver innovative, integrated solutions for every phase of construction.

LEgRAND’S POWER DISTRIBUTION DIVISION From Zucchini transformers, through rising main busbars and distribution boards to electrak’s power track, desk modules and lighting control, Legrand’s power distribution division provides market leading solutions to the increasing demands of today’s buildings.

Page 3: Legrand uk electrak brochure

contents

sUstaInabLe deveLopment From design through to manufacturing, the Legrand Group selects materials and processes that respect people and the environment.

• efficient and environmentally aware product design

• product functions that help to avoid energy waste

• management of manufacturing and logistics sites

• Integration of environmental concerns and Iso 14001 procedures at the Group’s global sites*

poWer tracK overview 8 ordering information 10 technical information 17

FLoor boXesoverview 22 ordering information 24technical information 29 Grommetsoverview 30 ordering information 32technical information 33

Intersoc-roverview 34 ordering information 38technical information 44

* 84% of sites are Iso 14001:2004 accredited including all UK sites.

Page 4: Legrand uk electrak brochure

Electrak®... the specialist in power distribution throughout the workplaceElectrak, part of the Legrand group in the UK, is a leading manufacturer of power distribution and lighting control solutions. Its power track, floor boxes, grommets, desk modules and lighting control ranges are installed in high specification offices around the world.

04

Page 5: Legrand uk electrak brochure

POWERINg ThE WORKSTATION

poWer tracK see page 8

Grommets see page 30

bUscom power and data backbone

cavIty FLoor boXes see page 22

Intersoc-r see page 34

LIGhtraK lighting control system

UNDERFLOOR POWER Electrak’s power track system is perfect for supplying underfloor power in cavity floor installations. With minimal parts, push-fit assembly and a complementary range of floor boxes, this flexible, easy to install system can be reconfigured as office layouts evolve.

WORKSTATION POWER Electrak’s access grommets provide the gateway for power to feed from the underfloor power track network to the workstation, where all desk power requirements are met with our new range of desk modules, Intersoc-R.

FULLy ADDRESSAbLE LIghTINg cONTROL Designed to work in harmony with Electrak’s buscom trunking, Lightrak’s lighting control system offers high end sophistication with unbeatable flexibility and speed of installation. Find out more at www.electrak.co.uk

05

Page 6: Legrand uk electrak brochure

Electrak®... UK manufacturing. global recognition

30 years oF eXperIenceelectrak has been designing and manufacturing cost effective systems that distribute power reliably and safely throughout the workplace since the 1980s.

as the inventor of underfloor busbar systems, electrak sets the benchmark for flexible power distribution.

IndUstry eXperts as part of its ongoing commitment to research and development, electrak continually evolves its product ranges to ensure it produces the best and most innovative solutions available on the market.

electrak takes pride in its enviable reputation for market leading customer service, industry knowledge and product expertise.

QUaLIty assUred UK manUFactUrInGWith its UK manufacturing base situated in the north east of england, electrak adapts to the changing demands of projects by providing a rapid production process whilst ensuring quality meets the highest standards.

electrak’s products are manufactured within an Iso 9001 : 2008 facility and many carry the Intertek diamondmark (where indicated).

06

Page 7: Legrand uk electrak brochure

trUsted throUGhoUt the UK and across the WorLd

UnIted KInGdom• morgan stanley, canary Wharf• media city, manchester• Jp morgan, canary Wharf• rbs, edinburgh• bridgewater place, Leeds• network rail, nationwide• swiss re, city of London• amazon, swansea• heathrow airport, London• morgan stanley, canary Wharf• Fort dunlop, birmingham• royal bank of canada,

city of London• snow hill, birmingham• barclays capital, canary Wharf• temple back, bristol• standard chartered bank, city of London• London Underground• bbc, White city• mann Island, Liverpool

mIddLe east & IndIa • adma-opco hQ, dubai• Internet city, dubai• burjuman centre, dubai• adIc/al bahr towers, abu dhabi• al dar hQ, abu dhabi• central bank of Kuwait• ministry of education, Kuwait• pIFFs aridya, Kuwait• paaet, Kuwait• Qatar news agency• barclays, chennai, India• barclays, pune, India• barclays, andheri, India• barclays, mumbai, India• rbs, delhi, India• Fidelity, delhi, India

asIa pacIFIc • credit suisse, Icc I, hong Kong• deutsche bank, Icc I, hong Kong• barclays capital, cheung

Kong centre• customs headquarters,

north point, hong Kong• standard chartered bank,

IFc II, hong Kong• citi bank tower, hong Kong• macquarie bank, IFc I, hong Kong• Ubs bank, IFc II, hong Kong• Jp morgan, hong Kong• standard chartered bank, marina

bay, singapore• barclays capital, marina bay, singapore• nomura bank, marina bay, singapore• credit suisse, serangoon road,

singapore• abn amro, one raffles Quay, singapore• rbs, one George street, singapore• barclays capital, shanghai• standard chartered bank, shanghai• Ubs bank, shanghai

07

Page 8: Legrand uk electrak brochure

Power track...adaptable, reliable underfloor power

08

Page 9: Legrand uk electrak brochure

the IndUstry standard In UnderFLoor poWerelectrak’s power track system is perfect for cavity floor installations. With minimal parts, push-fit assembly and a complementary range of floor boxes and grommets, this flexible, easy to install system can be reconfigured as office layouts evolve.

the system consists of continuous lengths of track which are fed via a feed unit and can be installed in floor voids as low as 48mm.

• 63 a rated, Ip 40 protection

• available in five versions: single phase, clean earth, dual circuit, three phase and auxiliary earth

• available in 1.2m, 1.8m, 2.4m and 3.6m lengths

• tap-off outlets are located at every 300 or 600mm pitch

• Floor mountable (stand-off brackets also available)

Integral track connector plugs into feed unit Lengths simply push-fit together Integral fixing brackets for rapid installation Tap-offs plug in to shuttered socket outlets and lock on to track body

09

Page 10: Legrand uk electrak brochure

Track feed

Excluding cables and conduit

Flexible metal conduit

Flexible metal conduit

1·2

2·4

10

Electrak® power track systems

Track lengths with 300 mm socket centres

Description Length (m)

4 sockets

6 sockets

8 sockets

12 sockets

1·2

1·8

2·4

3·6

Standard tap-off / auxiliary earth tap-off

Low noise / clean earth tap-off

Dual circuit tap-off

3 phase tap-off

Key code / Busbar arrangement

3

5

3

5

3

5

3

5

3

5

3

5

3

5

3

5

3

5

3

5

3

5

32 A unfused 16 mm Ø L, N, PE

13 A fused 16 mm Ø L, N, PE

13 A 543·7 fused 16 mm Ø L, N, PE

32 A unfused 16 mm Ø CE, L, N, PE

13 A fused 16 mm Ø CE, L, N, PE

13 A 543·7 fused 16 mm Ø CE, L, N, PE

32 A unfused 20 mm Ø CE, L1, N1 L2, N2, PE

32 A 415 V 3 phase 20 mm Ø L1, L2, L3, N, PE

32 A L1 unfused reconfigurable live pin 16 mm Ø L1, N, PE

32 A L2 unfused reconfigurable live pin 16 mm Ø L2, N, PE

32 A L3 unfused reconfigurable live pin 16 mm Ø L3, N, PE

010_011_Electrak v2.indd 10 20/12/2012 12:39

Page 11: Legrand uk electrak brochure

DF1010 JF2010 KF3010 NF4010 YF5010

DW1000 JW2000 KW3000 NW4000 YW5000

DW1010 JW2010 KW3010 NW4010 YW5010

DW1020 JW2020 KW3020 NW4020 YW5020

11

ELECTRAK 26Dual circuit system

(dark green)

ELECTRAK 273 phase system

(grey)

DA1123 JA2123 KA3123 NA4123 YA5123

DA1183 JA2183 KA3183 NA4183 YA5183

DA1243 JA2243 KA3243 NA4243 YA5243

DA1363 JA2363 KA3363 NA4363 YA5363

(1)AllNPtap-offsarereconfigurablebetweenL1,L2orL3for3phasetrack

ELECTRAK 28Auxiliary earth system

(red)

DP1332 – DP1332 – YP5332

DP1532 – DP1532 – YP5532

DP1313 – DP1313 – YP5313

DP1513 – DP1513 – YP5513

DP1327 – DP1327 – YP5327

DP1527 – DP1527 – YP5527

– JP2332 JP2332 – –

– JP2532 JP2532 – –

– JP2313 JP2313 – –

– JP2513 JP2513 – –

– JP2327 JP2327 – –

– JP2527 JP2527 – –

– – KP3328 – –

– – KP3528 – –

– – – NZ4331 –

– – – NZ4531 –

– – – NP4332(1) –

– – – NP4532(1) –

– – – NP4302(1) –

– – – NP4502(1) –

– – – NP4303(1) –

– – – NP4503(1) –

ELECTRAK 25Low noise / clean earth

system (green)

PE N2L2 PE CEN1L1 PE CEN1L1N2L2 PENL1L2L3 PEN1L1

ELECTRAK 24Standard system

(white)

010_011_Electrak v2.indd 11 20/12/2012 12:39

Page 12: Legrand uk electrak brochure

Electrak® 24 power track systemstandard system (white)

12

Pack Cat.Nos. Tap-offunits

Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)

Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A

32Aunfused

16mm؂L,N,PE

1 DP1332 3m 1 DP1532 5m

13Afused

16mm؂L,N,PE

1 DP1313 3m 1 DP1513 5m

13A543·7fused-highintegrity

16mm؂L,N,PE

1 DP1327 3m 1 DP1527 5m

Pack Cat.Nos. Tracksystemcomponents

Electrak24standardtracklengths

TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres

1 DA1123 1·2m,4sockets,2floorfixingbrackets 1 DA1183 1·8m,6sockets,2floorfixingbrackets 1 DA1243 2·4m,8sockets,2floorfixingbrackets 1 DA1363 3·6m,12sockets,3floorfixingbrackets

Trackfeedunit

1 DF1010 Withone25mmdiameterholesuitableforMICC,armouredcablesorsinglecorecablesinconduit

Flexibleinterlinks

Canbeusedtoovercomeobstructionsorascornerswhererequired

1 DW1000 Excludingcablesandconduit 1 DW1010 1·2mflexiblemetalconduit 1 DW1020 2·4mflexiblemetalconduit

Specialfixingbrackets

Requiredwhentrackisraisedoffsurfacelevel Bracketsraisetrackby21mmandshouldbe spaced600mmapart

1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors

picto loupe-65765j.eps

Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)

ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm

DF1010

DW1010

DP1332DA1123

(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266

- - -/

- - -

012_013_Electrak v3.indd 12 20/12/2012 12:38

Page 13: Legrand uk electrak brochure

Electrak® 25 power track systemlow noise / clean earth system (green)

13

Pack Cat.Nos. Tap-offunits

Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)

Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A

32Aunfused

16mm؂CE,L,N,PE

1 JP2332 3m 1 JP2532 5m

13Afused

16mm؂CE,L,N,PE

1 JP2313 3m 1 JP2513 5m

13A543·7fused-highintegrity

16mm؂CE,L,N,PE

1 JP2327 3m 1 JP2527 5m

Pack Cat.Nos. Tracksystemcomponents

Electrak25lownoise/cleanearthtracklengths

TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres

1 JA2123 1·2m,4sockets,2floorfixingbrackets 1 JA2183 1·8m,6sockets,2floorfixingbrackets 1 JA2243 2·4m,8sockets,2floorfixingbrackets 1 JA2363 3·6m,12sockets,3floorfixingbrackets

Trackfeedunit

1 JF2010 Withone25mmdiameterholesuitableforMICC,armouredcablesorsinglecorecablesinconduit

Flexibleinterlinks

Canbeusedtoovercomeobstructionsorascornerswhererequired

1 JW2000 Excludingcablesandconduit 1 JW2010 1·2mflexiblemetalconduit 1 JW2020 2·4mflexiblemetalconduit

Specialfixingbrackets

Requiredwhentrackisraisedoffsurfacelevel Bracketsraisetrackby21mmandshouldbe spaced600mmapart

1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors

picto loupe-65765j.eps

Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)

ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm

JF2010

JW2010

JP2332JA2123

- - -/

- - -

(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266

012_013_Electrak v3.indd 13 20/12/2012 12:38

Page 14: Legrand uk electrak brochure

Electrak® 26 power track systemdual circuit system (dark green)

14

Pack Cat.Nos. Tap-offunits

Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)

Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A

Standard32Aunfused

16mm؂L,N,PE

1 DP1332 3m 1 DP1532 5m

Standard13Afused

16mm؂L,N,PE

1 DP1313 3m 1 DP1513 5m

Standard13A543·7fused

16mm؂L,N,PE

1 DP1327 3m 1 DP1527 5m

Lownoise/cleanearth32Aunfused

16mm؂CE,L,N,PE

1 JP2332 3m 1 JP2532 5m

Lownoise/cleanearth13Afused

16mm؂CE,L,N,PE

1 JP2313 3m 1 JP2513 5m

Lownoise/cleanearth13A543·7fused

16mm؂CE,L,N,PE

1 JP2327 3m 1 JP2527 5m

Dualcircuit32Aunfused

20mm؂CE,L1,N1,L2,N2,PE

1 KP3328 3m 1 KP3528 5m

Pack Cat.Nos. Tracksystemcomponents

Thedualpowertracksystemhasbothstandardandlownoise/cleanearthsystemsincorporated

Electrak26dualcircuittracklengths

TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres

1 KA3123 1·2m,4sockets,2floorfixingbrackets 1 KA3183 1·8m,6sockets,2floorfixingbrackets 1 KA3243 2·4m,8sockets,2floorfixingbrackets 1 KA3363 3·6m,12sockets,3floorfixingbrackets

Trackfeedunit

1 KF3010 Withtwo25mmdiameterholessuitableforMICC,armouredcablesorsinglecorecablesinconduit

Flexibleinterlinks

Canbeusedtoovercomeobstructionsorascornerswhererequired

1 KW3000 Excludingcablesandconduit 1 KW3010 1·2mflexiblemetalconduit 1 KW3020 2·4mflexiblemetalconduit

Specialfixingbrackets

Requiredwhentrackisraisedoffsurfacelevel Bracketsraisetrackby21mmandshouldbe spaced600mmapart

1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors

picto loupe-65765j.eps

Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)

ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm

KF3010

KW3010

KP3328KA3123

- - -/

- - -

(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266

014_015_Electrak v3.indd 14 20/12/2012 12:43

Page 15: Legrand uk electrak brochure

Electrak® 27 power track system3 phase system (grey)

15

Pack Cat.Nos. Tap-off units

Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)

Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A

32 A 415 V 3 phase

20mm؂L1,L2,L3,N,PE

1 NZ4331 3m 1 NZ4531 5m

32 A L1(2) unfused

Unfused Reconfigurablelivepin

16mm؂L,N,PE

1 NP4332 3m 1 NP4532 5m

32 A L2(2) unfused

Unfused Reconfigurablelivepin

16mm؂L,N,PE

1 NP4302 3m 1 NP4502 5m

32 A L3(2) unfused

Unfused Reconfigurablelivepin

16mm؂L,N,PE

1 NP4303 3m 1 NP4503 5m

Pack Cat.Nos. Track system components

Electrak 27 3 phase track lengths

TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres

1 NA4123 1·2m,4sockets,2floorfixingbrackets 1 NA4183 1·8m,6sockets,2floorfixingbrackets 1 NA4243 2·4m,8sockets,2floorfixingbrackets 1 NA4363 3·6m,12sockets,3floorfixingbrackets

Track feed unit

1 NF4010 Withone25mmdiameterholesuitableforMICC,armouredcablesorsinglecorecablesinconduit

Flexible interlinks

Canbeusedtoovercomeobstructionsorascornerswhererequired

1 NW4000 Excludingcablesandconduit 1 NW4010 1·2mflexiblemetalconduit 1 NW4020 2·4mflexiblemetalconduit

Special fixing brackets

RequiredwhentrackisraisedoffsurfacelevelBracketsraisetrackby21mmandshouldbespaced600mmapart

1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors

picto loupe-65765j.eps

Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)

ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm

NF4010

NW4010

NZ4331NA4123

- - -/

- - -

(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266(2)AllNPtap-offsarereconfigurablebetweenL1,L2,orL3for3phasetrack

014_015_Electrak v3.indd 15 20/12/2012 12:43

Page 16: Legrand uk electrak brochure

Electrak® 28 power track systemauxiliary earth system (red)

16

Pack Cat.Nos. Tap-offunits

Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)

Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A

32Aunfused

16mm؂L,N,PE

1 YP5332 3m 1 YP5532 5m

13Afused

16mm؂L,N,PE

1 YP5313 3m 1 YP5513 5m

13A543·7fused-highintegrity

16mm؂L,N,PE

1 YP5327 3m 1 YP5527 5m

Pack Cat.Nos. Tracksystemcomponents

Electrak28auxiliaryearthtracklengths

TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres

1 YA5123 1·2m,4sockets,2floorfixingbrackets 1 YA5183 1·8m,6sockets,2floorfixingbrackets 1 YA5243 2·4m,8sockets,2floorfixingbrackets 1 YA5363 3·6m,12sockets,3floorfixingbrackets

Trackfeedunit

1 YF5010 Withone25mmdiameterholesuitableforMICC,armouredcablesorsinglecorecablesinconduit

Flexibleinterlinks

Canbeusedtoovercomeobstructionsorascornerswhererequired

1 YW5000 Excludingcablesandconduit 1 YW5010 1·2mflexiblemetalconduit 1 YW5020 2·4mflexiblemetalconduit

Specialfixingbrackets

Requiredwhentrackisraisedoffsurfacelevel Bracketsraisetrackby21mmandshouldbe spaced600mmapart

1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors

picto loupe-65765j.eps

Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)

ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm

YF5010

YW5010

YP5332YA5123

(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266

- - -/

- - -

016_Electrak v3.indd 16 20/12/2012 12:58

Page 17: Legrand uk electrak brochure

17

Electrak® power track systemsdesign and installation

7593

2 x 25 Ø

46

25 Ø

46

250

47

109 118

3215

68

65

End view A

92

End view B

Integral fixing bracket fixing centres

All dimensions (mm) are nominal

n General installation notesElectrak power track is a compact system that can be installed in floor voids as low as 48 mm

Track feed boxes are provided with one or two 25 mm diameter holes suitable for MICC, armoured cables or single core cables in conduitTrack lengths connect together and to track feeds using the integral connectors on each length

Track lengths should always be secured using the integral floor fixing brackets ; three on the 3·6 m length and two on 2·4 m, 1·8 m or 1·2 m lengths

Access to power is provided along the track length by simply plugging tap-off units into shuttered socket outlets. These tap-off units feed all types of conventional floor service outlet boxes or feed workstations directly through the floor via 4 mm2 or 1·5 mm2 insulated conductors contained in flexible metal or VO rated nylon conduit. When connecting tap-offs directly through the floor via grommet outlets to workstations care must be taken to ensure that the tap-off length is adequate

The dual power track system has both standard and low noise / clean earth systems incorporated. As well as dual tap-offs, both standard and low noise / clean earth tap-offs can be plugged into any socket outlet along the track length. The dual tap-off incorporates both standard and low noise cables

Optimum layout flexibility is achieved by positioning track lengths a maximum of 5·2 m apart and 2·5 m from the wall, and by connecting the 3 m tap-off units to floor outlet boxes. This means every part of the floor area can be served. Flexible interlinks can be used to overcome obstructions or used as corners if required

n Special fixing bracketsWhen installing track off-floor, Electrak special fixing brackets raise track by 21 mm. Ensure brackets are spaced 600 mm apart and always have support under the integral track connector and track feed. Failure to do so may undermine the integrity of the system

Cat. No. DZ1210 raised off-floor fixing brackets are spaced at 600 mm centres along track. Also use bottom half of bracket under track feed and flexible interlinkCat. No. DZ1230 raised off-floor fixing brackets are always used under integral track connectors. Track is secured to raised brackets using the track’s integral fixing bracket

50 mm

99 mm

7 mm Ø

Cat. No. DZ121021 mm to underside of track36 mm to top of track

Integral track connector

Cat. No. DZ1230

185 mm

7 mm Ø

Integral track fixing bracket screws to special bracket

n Dimensions

Example floor layout

2·5

m5·

2 m

5·2

m

track feed

5·2

m 3 m flexibletap-off unit

floor serviceoutlet box

integral trackconnectors

socket outlet points every300 or 600 mm alongtrack length

017_021_Electrak v3.indd 17 20/12/2012 13:00

Page 18: Legrand uk electrak brochure

18

Electrak® power track systemsdesign and installation (continued)

n Product configuration

Flexible interlink Tap-off connection

Track and flexible interlink boxes must be securely fixed inline to surface so no movement can take place after fixing

Track feed protective earth terminal and earth bond

Lift terminal tab to access terminal screws and close after use

Lift lid

Protective earth must always be connected via the earth terminal block

Close lid and secure with lid fixing screw before power up

25 mm Ø cable conduit fixing hole

Depress tap-off side clips and push down

Make sure both tap-off side clips are fully pushed home on both

sides of track

Tap-off

Side clip

Push down

Power trackInterlink feed entry socket. Remove dust cover label

Remove dust cover from power track end entry socket before use

Screw fix to surface

Track feed (Cat. No. DF1010) Sub-cabling Tap-off connection

Tap-off metal flexible conduit

20 mm Ø conduit fitting. Tighten back nut securely

Track feed protective earth terminal and earth bond

Clean earth

Connector terminals

Connector terminals

Lift terminal tab to access terminal screws and close after use

Lift lid

Protective earth must always be connected via the earth terminal block

Close lid and secure with lid fixing screw before power up

25 mm Ø cable conduit fixing hole

Track feed (Cat. No. JF2010) Sub-cabling Tap-off connection

Tap-off metal flexible conduit

20 mm Ø conduit fitting Tighten back nut securely

017_021_Electrak v3.indd 18 20/12/2012 13:00

Page 19: Legrand uk electrak brochure

19

Track feed protective earth terminal and earth bond

Connector terminals

Lift terminal tab to access terminal screws and close after use

Lift lid

Protective earth must always be connected via the earth terminal block

Close lid and secure with lid fixing screw before power up

25 mm Ø cable conduit fixing hole

Track feed (Cat. No. NF4010) Sub-cabling 3 phase tap-off connection

Tap-off metal flexible conduit

20 mm Ø conduit fitting Tighten back nut securely

Track feed protective earth terminal and earth bond

Connector terminals

Lift terminal tab to access terminal screws and close after use

Lift lid

Protective earth must always be connected via the earth terminal block

Close lid and secure with lid fixing screw before power up

25 mm Ø cable conduit fixing hole

Track feed (Cat. No. YF5010) Sub-cabling Tap-off connection

Tap-off metal flexible conduit

20 mm Ø conduit fitting Tighten back nut securely

Clean earth

ConnectionsL1, N1, CE = low noise L2, N2, PE = standard

ConnectionsL1, N1, CE = low noise L2, N2, PE = standard

Connector terminals

Lift terminal tab to access terminal screws and close after use

Lift lidProtective earth must always be connected via the earth terminal block

Close lid and secure with lid fixing screw before power up

2 x 25 mm Ø cable conduit fixing hole

Track feed (Cat. No. KF3010) Sub-cabling Dual tap-off connection (dark green)

Tap-off metal flexible conduit

20 mm Ø conduit fitting Tighten back nut securely

Track feed protective earth terminal and earth bond

017_021_Electrak v3.indd 19 20/12/2012 13:01

Page 20: Legrand uk electrak brochure

20

Electrak® power track systemsinstallation

1 Fix track feed to surface

Pull out track fixing bracket lugs and screw fix on both sides

Track outlets reusable plastic dust covers

First track fixing bracket

Power track and integral track connector

Track length

Track feed Make chalk line to align track lengthsDirection of

track run

Integral track connector

Push down

Push down

Remove dust cover

Track feed

Remove dust cover before connecting track connector

Make sure track connector clips are fully pushed home on both sides of track

All integral track fixing brackets must be fixed to surface at 1·2 m fixing centres from first bracket on each track length

2 Connect track length to track feed

3 Connect additional track lengths

4 Secure track lengths to surface

017_021_Electrak v3.indd 20 20/12/2012 13:01

Page 21: Legrand uk electrak brochure

Electrak® power track systemstechnical data

21

Ratedcurrent 63A Ratedvoltage 230/400V~ Frequency 50/60Hz Conductorresistance-liveandneutral 3·0mΩ/m Conductorimpedance 1·5mΩ/m

Electricaltestdata

Busbars 3·0mV/A/m Cableconnector 0·4mV/A Trackconnector 0·4mV/A 32Atap-off 0·4mV/A +4mm2cable 11mV/A/m Flexiblecornerassembly 1·5mV/A +10mm2cable 4·0mV/A/m

Voltdrops(liveandneutral)

Phasebusbar 1·5mΩ/m Earthbusbar 1·5mΩ/m Earthhousing 1·1mΩ/m Earthbusbarandhousing 0·8mΩ/m Cableconnector 0·4mΩ Trackconnector 0·6mΩ 32Atap-off 0·6mΩ +4mm2cable 11mΩ/m Flexiblecornerassembly 1·5mΩ +10mm2cable 4·0mΩ/m Ratedconditionalshort-circuitcurrent 16KA Ambienttemperature 25˚C

Earthfaultloopimpedance

Numberofconductors 3to6 Busbarconductorcrosssectionalarea 13mm2

Housingcrosssectionalarea(copperequivalent) 13mm2

Cableterminalcapacity 16mm2

Tap-offcable32A 4mm2

Tap-offcable13Afused 1·5mm2

Tap-offconduit,upto4conductors 16mmØ Tap-offconduit,5and6conductors 20mmØ Flexiblecornercable(tri-rated,hightemperature) 10mm2

Flexiblecornerconduit 25mmØ IPrating 40

Mechanicaldata

Powertrackhousing Galvanisedsteel,naturalfinish Busbars Highconductivitycopper Busbarinsulator PTFE Trackconnector/socketoutlet/trackfeedconnector Flameretardantpolycarbonate Socketoutletentryshutter Acetal Tap-offhousing Flameretardantpolycarbonate Trackconnectorblades Copper Tap-offblades Copper Tap-off/flexiblecornerconduit,metal Electro-galvanisedsteel Tap-offconduit,plastic VOrated Tap-offcable LSOHtoBS7211 Flexibleinterlinkcable Tri-ratedtoBS6231 Trackfeedbox/flexibleinterlinkboxes Galvanisedsteel Trackfeedconnectorterminals/earthblock Brass Trackfixingbrackets Galvanisedsteel 13Atap-off,fuse ToBS1362,ASTAapproved

Materialspecifications

nEarthfaultloopimpedanceBS7671:2008+A1:2011IETWiringRegulationsrequireaccuratedeterminationofthetotalearthloopimpedance,whichmustbesufficientlylowtoallowtheprotectivedevicetooperatewithinthespecifiedtime,whichforsocketoutletsis0·4seconds.ThevaluesrelevanttoElectrakforcalculatingtheearthfaultloopimpedanceareshownintheelectricaltestdatatable,seeopposite

nDurabilityElectraksystemsaresuperblydesignedandextremelyrobust.Theycanbeexpectedtostanduptoallnormalsiteconditions.ElectrakhasbeenshortcircuitstrengthtestedbyASTA

nInstallationswithhighprotectiveconductorcurrentsAllunfusedtap-offscomplywithRegulation543·7withouttheneedforadditionalearthconductors.Regulation543·7·1·103(ii)states“asinglecopperprotectiveconductorhavingacross-sectionalareaofnotlessthan4mm2,complyingwiththerequirementsofRegulations543·2and543·3,theprotectiveconductorbeingenclosedtoprovideadditionalprotectionagainstmechanicaldamage,forexample,withinaflexibleconduit”Forinstallationswithhighprotectiveconductorcurrentsrequiringfusedtap-offs,a543·7complianttap-offmustbeused.Normallyfusedtap-offsincorporate1·5mm2conductors,howeverinthefused543·7tap-offs,the1·5mm2earthconductorisreplacedwitha4mm2conductorandthereforecomplieswithSection543·7·1·103(ii)

n32Atap-offunitThe3m32Atap-offunitcomprisesanunfusedtap-offwitheither2·6mof16mm/20mmdiameterflexiblemetalconduitorVOratednylonconduitbothwithintegral4mm2LSOHconductors

Theseunitsaredesignedtocomplywithregulation434·2·1oftheIETWiringRegulationsbyvirtueofthefollowing:•maximumlengthofcableis3m•itisfactoryassembledandfullytesteditemwithcableinstalledinhighqualityflexibleconduit

Faultconditionprotectionforthetap-offassemblyandthefloorboxsocketoutletsisdeliveredbythecircuitprotectiondeviceDisconnectiontimeforsocketoutletsis0·4seconds(Regulation411·3·2·2).TheElectraksystemmeetsthisrequirement

Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorthepowertrackisprotectedbyaprotectivedevicenotexceeding32A

nStandards

ApprovedtoASTAStandard138BSEN60439-2:2000,BSEN61534-22:2009andIEC61534-22:2009ManufacturedwithinanapprovedISO9001:2008facilityAssessedQualityAssuranceCertificateNo.2029ElectrakfullycomplieswiththerequirementsofBS7671:2008+A1:2011(IETWiringRegulations)

017_021_Electrak v3.indd 21 20/12/2012 13:01

Page 22: Legrand uk electrak brochure

Floor boxes...choice, flexibility and easy installationElectrak’s 2, 3 and 4 compartment raised access floor boxes and slab boxes offer complete versatility. Floor boxes are available pre-wired with power track tap-off, or supplied empty (unassembled), with a choice of single or separate compartment bases and three depth options. With a vast selection of power and data plates available, boxes can be tailored to the specific requirements of each office installation.

22

Page 23: Legrand uk electrak brochure

Various RCD protection options available

Rapid fit push lock secures base in floor aperture

Single or separate compartment bases

Three depth options: 75mm, 85mm, 110mm

Durable ABS trim and lid surround

Rapid fit /remove mechanism adjusts for flooring thickness

available in 2, 3 and 4 compartments and with a choice of three depths, electrak’s floor boxes have been developed with a host of special features:

• available pre-wired with tap-off or supplied unassembled

• a vast selection of power and data plates, including rcd options

• single or separate compartment bases for ease of data cabling

• rapid installation and fast ratchet mechanism which adjusts to floor finish thickness

Quick-fit, reversible lid for rapid installation

Available pre-wired with tap-off

23

Page 24: Legrand uk electrak brochure

24

access floor service outlet and slab mounted floor boxesempty boxes and accessory plates

100 mm width plates

100 mm width plates

75 mm width plates

To configure boxes as required, select :

1. Box depth2. Number of compartments required3. Desired accessory plates

4 compartment

230 mm

366 mm

3 compartment

230 mm

366 mm

2 compartment

230 mm

290 mm

CR2001 CR011 CR4001

CR2002 CR012 CR4002

CR2003 CR013 CR4003

CR2004 CR014 CR4004

CR2005 CR015 CR4005

CR2006 CR016 CR4006

CR5102 CR5202 CR5302 CR5402

CR020 CR4100

CR022 CR4101

CR023 CR4102

CR027 CR4103

CR029 CR4104

CR030 CR4105

CR044 CR4118

CR036 CR4111

CR043 CR4117

CR026 –

CR028 –

CR042 CR4115

CR031 CR4106

CR033 CR4108

CR024 CR4112

CR025 CR4113

Single base – 75 mm depth

Single base – 85 mm depth (standard box)

Single base – 110 mm depth

Separate compartment base – 75 mm depth

Separate compartment base – 85 mm depth

Separate compartment base – 110 mm depth

Fix directly onto floor slab (supplied empty)

Blank plate

2 gang switched socket outlet

2 gang switched socket outlet, low noise / clean earth

2 gang non-standard switched socket outlet

2 gang unswitched socket outlet

3 gang unswitched socket outlet

3 gang unswitched socket outlet,low noise / clean earth

2 gang RCD socket outlet

2 gang RCD socket outlet, low noise / clean earth

Punched plate for 2 x 1 gang accessories (60·3 mm fixing centres)

Punched plate for 2 gang accessories (120·6 mm fixing centres)

Angled punched plate for 4 x RJ45 sockets(37 mm x 22 mm cut-outs)

2 x LJ2 accessory plate (50 mm fixing centres)

4 x BNC connector plate

4 x Data / telecoms plate (37 mm x 22 mm cut-outs)

6 x Data / telecoms plate (37 mm x 22 mm cut-outs)

Empty boxes Example

Accessory plates For 1, 2 and 3 compartment boxes For 4 compartment boxes

Slab boxes 2 compartment 3 compartment 4 compartment1 compartment

024_Electrak v3.indd 24 20/12/2012 16:47

Page 25: Legrand uk electrak brochure

CF-EP0

25

access floor pre-wired service outlet boxesand accessory plates

Includes 1 x twin switched socket outlet

Pre-wired service outlet boxes with Electrak tap-offs

1. Select power track tap-off and desired configuration2. Select additional accessory plates (if required)

3 compartment

Additional plates for 3 compartment boxes

CR020

CR026

CR028

CR042

Blank plate

Punched plate for 2 x 1 gang accessories (60·3 mm fixing centres)

Punched plate for 2 gang accessories (120·6 mm fixing centres)

Angled punched plate for 4 xRJ45 sockets (37 mm x 22 mm cut-outs)

Includes 2 x twin switched socket outlet

Includes 1 x 2 gang RCD socket outlet

Includes 2 x 2 gang RCD socket outlet

Electrak 24 - standard tap-off

Electrak 25 - low noise / clean earth tap-off

Electrak 28 - auxiliary earth tap-off

DP1332 - 3 m CR100 CR102 CR100R CR102R

DP1532 - 5 m CR101 CR103 CR101R CR103R

JP2332 - 3 m CR110 CR112 CR110R CR112R

JP2532 - 5 m CR111 CR113 CR111R CR113R

YP5332 - 3 m CR104 CR106 CR104R CR106R

YP5532 - 5 m CR105 CR107 CR105R CR107R

Blank plate

Angled punched plate for 4 x RJ45 sockets (37 mm x 22 mm cut-outs)

2 x LJ2 accessory plate (50 mm fixing centres)

CR4100

CR4115

CR4106

DP1332 - 3 m CR120 CR122 CR120R CR122R CR4402

DP1532 - 5 m CR121 CR123 CR121R CR123R CR4403

JP2332 - 3 m CR130 CR132 CR130R CR132R CR4412

JP2532 - 5 m CR131 CR133 CR131R CR133R CR4413

YP5332 - 3 m CR124 CR126 CR124R CR126R CR4406

YP5532 - 5 m CR125 CR127 CR125R CR127R CR4407

230 mm

366 mm

230 mm

366 mm

CR031

CR033

CR024

CR025

2 x LJ2 accessory plate (50 mm fixing centres)

4 x BNC connector plate

4 x Data / telecoms plate (37 mm x 22 mm cut-outs)

6 x Data / telecoms plate (37 mm x 22 mm cut-outs)

4 x BNC connector plate

4 x Data / telecoms plate (37 mm x 22 mm cut-outs)

6 x Data / telecoms plate (37 mm x 22 mm cut-outs)

CR4108

CR4112

CR4113

4 compartment

Electrak 24 - standard tap-off

Electrak 25 - low noise / clean earth tap-off

Electrak 28 - auxiliary earth tap-off

Includes 1 x twin switched socket

outlet

Includes 2 x twin switched socket

outlet

Includes 1 x 2 gang RCD socket outlet

Includes 2 x 2 gang RCD socket outlet

Modular RCD protecting 2 x twin switched socket

outlets and 1 spare compartment

Additional plates for 4 compartment boxes

025_Electrak v4.indd 25 20/12/2012 16:49

Page 26: Legrand uk electrak brochure

access floor service outlet boxesempty boxes

26

Pack Cat.Nos. 2compartmentfloorboxes Emptyboxes

100mmcompartmentwidths

1 CR2001 Singlebase-75mmdepth 1 CR2002 Singlebase-85mmdepth(standardbox) 1 CR2003 Singlebase-110mmdepth 1 CR2004 Separatecompartmentbase-75mmdepth 1 CR2005 Separatecompartmentbase-85mmdepth 1 CR2006 Separatecompartmentbase-110mmdepth

3compartmentfloorboxes Emptyboxes

100mmcompartmentwidths

1 CR011 Singlebase-75mmdepth 1 CR012 Singlebase-85mmdepth(standardbox) 1 CR013 Singlebase-110mmdepth 1 CR014 Separatecompartmentbase-75mmdepth 1 CR015 Separatecompartmentbase-85mmdepth 1 CR016 Separatecompartmentbase-110mmdepth

4compartmentfloorboxes Emptyboxes

75mmcompartmentwidths

1 CR4001 Singlebase-75mmdepth 1 CR4002 Singlebase-85mmdepth(standardbox) 1 CR4003 Singlebase-110mmdepth 1 CR4004 Separatecompartmentbase-75mmdepth 1 CR4005 Separatecompartmentbase-85mmdepth 1 CR4006 Separatecompartmentbase-110mmdepth

picto loupe-65765j.eps

Selection chart (p. 24)Dimensions and technical information (p. 29)

LidandtrimmouldingsareprecisionengineeredfromhardwearingdurableABS.ThelidisreinforcedwithagalvanisedmildsteelplateMountingframeandboxbase-0·9mmthickgalvanisedsteelEachcompartmenthas2entriesfor20mmand2entriesfor25mmflexibleconduitsGreymouldings.Alternativecoloursavailabletospecialorder.Goosewinggreyplates2,3and4compartmentboxesarealsoavailablewithseparateindividualcompartmentbaseunitsforconvenientoffsitepre-wiringSuppliedinpartsorfullyassembledandconfiguredtocustomerspecificationConformtoIEC-61534-22

CR4002

CR012

slab mounted floor boxesempty boxes

Pack Cat.Nos. Slabfloorboxes

FixesdirectlyontofloorslabFastandefficientinstallationwithintegratedfixingplates

Widerangeofpoweranddataaccessoryplates Manufacturedfrom0·9mmthickgalvanisedsteel Eachcompartmenthas2entriesfor20mmand

2entriesfor25mmflexibleconduits

100mmcompartmentwidths

Useplatesfromthe1,2and3compartmentfloorboxsection(p.24)

1 CR5102 1compartmentslabfloorbox

1 CR5202 2compartmentslabfloorbox

1 CR5302 3compartmentslabfloorbox

75mmcompartmentwidths

Useplatesfromthe4compartmentfloorboxsection(p.24)

1 CR5402 4compartmentslabfloorbox

ElectrakslabfloorboxesareanidealsolutionforunderfloorpoweranddatarequirementsUsedinconjunctionwithElectrakfloorgrommets,slabboxespreventunwantedaccesstopoweranddataconnections

CR5102

3compartmentslabfloorboxshownwithtwotwinswitchedsocketoutlets,puncheddataplateandapowertracktap-off

CR5302

Screed/edgetrimboxes,andmetalorlockablelidsareavailabletoordercontactuson+44(0)8456006266

026_027_Electrak v4.indd 26 20/12/2012 13:04

Page 27: Legrand uk electrak brochure

access floor service outlet boxesaccessory plates and ancillary items

27

Pack Cat.Nos. 4compartmentaccessoryplates

75mmcompartmentwidths

1 CR4100 Blankplate 1 CR4101 2gangswitchedsocketoutlet 1 CR4102 2gangswitchedsocketoutlet,lownoise/cleanearth 1 CR4103 2gangnon-standardswitchedsocketoutlet 1 CR4104 2gangunswitchedsocketoutlet 1 CR4105 3gangunswitchedsocketoutlet CR4118 3gangunswitchedsocketoutlet, lownoise/cleanearth 1 CR4111 2gangRCDsocketoutlet 1 CR4117 2gangRCDsocketoutlet,lownoise/cleanearth 1 CR4115 Angledpunchedplatefor4xRJ45

(37mmx22mmcut-outs) 1 CR4106 2xLJ2accessoryplate(50mmfixingcentres) 1 CR4108 4xBNCconnectorplate 1 CR4112 4xData/telecomsplate(37mmx22mmcut-outs) 1 CR4113 6xData/telecomsplate(37mmx22mmcut-outs)

Pack Cat.Nos. 1,2and3compartmentaccessoryplates

100mmwidth

1 CR020 Blankplate 1 CR022 2gangswitchedsocketoutlet 1 CR023 2gangswitchedsocketoutlet,lownoise/cleanearth 1 CR027 2gangnon-standardswitchedsocketoutlet 1 CR029 2gangunswitchedsocketoutlet 1 CR030 3gangunswitchedsocketoutlet CR044 3gangunswitchedsocketoutlet, lownoise/cleanearth 1 CR036 2gangRCDsocketoutlet 1 CR043 2gangRCDsocketoutlet,lownoise/cleanearth 1 CR026 Punchedplatefor2x1gangaccessories

(60·3mmfixingcentres) 1 CR028 Punchedplatefor2gangaccessories

(120·6mmfixingcentres) 1 CR042 Angledpunchedplatefor4xRJ45

(37mmx22mmcut-outs) 1 CR031 2xLJ2accessoryplate(50mmfixingcentres) 1 CR033 4xBNCconnectorplate 1 CR024 4xData/telecomsplate(37mmx22mmcut-outs) 1 CR025 6xData/telecomsplate(37mmx22mmcut-outs)

picto loupe-65765j.eps

Selection chart (p. 24-25)Dimensions and technical information (p. 29)

LidandtrimmouldingsareprecisionengineeredfromhardwearingdurableABS.LidisreinforcedwithagalvanisedmildsteelplateMountingframeandboxbase-0·9mmthickgalvanisedsteelEachcompartmenthas2entriesfor20mmand2entriesfor25mmflexibleconduitsGreymouldings.Alternativecoloursavailabletospecialorder.Goosewinggreyplates2,3and4compartmentboxesarealsoavailablewithseparateindividualcompartmentbaseunitsforconvenientoffsitepre-wiringSuppliedinpartsorfullyassembledandconfiguredtocustomerspecificationConformtoIEC-61534-22

Ancillaryitemsforserviceoutletboxes

1 CR0001 Floortilecut-outtemplate–2compartment 1 CR0003 Floortilecut-outtemplate–3/4compartment 10 CR0000 Cableoutletflap 10 CR0010 Cablerouters 50 CR0011 Screwsforaccessoryplates 1 CR0012 Packof5keysforusewithlockablefloorboxes 1 CR0002 Lid–2compartmentbox 1 CR0004 Lid–3/4compartmentbox 1 CR0005 Mountingframeforvinylfloor.For2compartmentbox

Replacesmountingframeattachedtobase 1 CR0006 Mountingframeforvinylfloor.For3/4compartment

box.Replacesmountingframeattachedtobase 10 CR0007 Floorboxlidhandle 1 CR0020 Metallidandtrim-replacementfor3and4

compartmentboxes-powdercoatedgrey

Electraktap-offs(seep.12-16)

026_027_Electrak v4.indd 27 20/12/2012 13:04

Page 28: Legrand uk electrak brochure

access floor pre-wired service outlet boxes3 and 4 compartment

28

Pack Cat.Nos. 3compartmentpre-wiredboxeswith1xTSSO

100mmcompartmentwidths

Singlebase–85mmdepth,pre-wiredwith: 1 CR100 3mElectrak24standardtap-offCat.No.DP1332 1 CR101 5mElectrak24standardtap-offCat.No.DP1532 1 CR110 3mElectrak25lownoise/cleanearthtap-off

Cat.No.JP2332 1 CR111 5mElectrak25lownoise/cleanearthtap-off

Cat.No.JP2532 1 CR104 3mElectrak28auxiliaryearthtap-off

Cat.No.YP5332 1 CR105 5mElectrak28auxiliaryearthtap-off

Cat.No.YP5532

3compartmentpre-wiredboxeswith2xTSSO

100mmcompartmentwidths

Singlebase–85mmdepth,pre-wiredwith: 1 CR102 3mElectrak24standardtap-offCat.No.DP1332 1 CR103 5mElectrak24standardtap-offCat.No.DP1532 1 CR112 3mElectrak25lownoise/cleanearthtap-off

Cat.No.JP2332 1 CR113 5mElectrak25lownoise/cleanearthtap-off

Cat.No.JP2532 1 CR106 3mElectrak28auxiliaryearthtap-off

Cat.No.YP5332 1 CR107 5mElectrak28auxiliaryearthtap-off

Cat.No.YP5532

Pack Cat.Nos. 4compartmentpre-wiredboxeswith1xTSSO

75mmcompartmentwidths

Singlebase–85mmdepth,pre-wiredwith: 1 CR120 3mElectrak24standardtap-offCat.No.DP1332 1 CR121 5mElectrak24standardtap-offCat.No.DP1532 1 CR130 3mElectrak25lownoise/cleanearthtap-off

Cat.No.JP2332 1 CR131 5mElectrak25lownoise/cleanearthtap-off

Cat.No.JP2532 1 CR124 3mElectrak28auxiliaryearthtap-offCat.No.YP5332 1 CR125 5mElectrak28auxiliaryearthtap-offCat.No.YP5532

4compartmentpre-wiredboxeswith2xTSSO

75mmcompartmentwidths

Singlebase–85mmdepth,pre-wiredwith: 1 CR122 3mElectrak24standardtap-offCat.No.DP1332 1 CR123 5mElectrak24standardtap-offCat.No.DP1532 1 CR132 3mElectrak25lownoise/cleanearthtap-off

Cat.No.JP2332 1 CR133 5mElectrak25lownoise/cleanearthtap-off

Cat.No.JP2532 1 CR126 3mElectrak28auxiliaryearthtap-offCat.No.YP5332 1 CR127 5mElectrak28auxiliaryearthtap-offCat.No.YP5532

Electrakfloorboxescanbesuppliedpre-wiredtopowertracktap-offswithanyvariationofsockets,tap-offs,depthorotherconfiguration

picto loupe-65765j.eps

Dimensions and technical information (p. 29)

CR122CR100

Alsoavailable:-pre-wiredboxeswithfusedtap-offs-shallowordeepversions-separatecompartmentbasescontactuson+44(0)8456006266

Pre-wired floor boxes can be supplied with RCD rather than standard sockets. Add an R to the end of the part numbers for an RCD version.For example CR100R is a 3 compartment floor box with a twin RCD socket and a DP1332 tap-off

028_Electrak v3.indd 28 20/12/2012 17:03

Page 29: Legrand uk electrak brochure

access floor service outlet boxestechnical information

29

n Floor boxes

To fit carpet : Detach lid and trim assembly by lifting the blue locking handles and lifting out. Cut and fit carpet. Push lid and trim assembly back into place

Cut hole in raised floor tile, lower complete box into aperture and push firmly down

DimensionsLid can accommodate carpets up to 6 mm depthAccessory plates are 172 mm long, with 162 mm fixing centres

MaterialsLid and trim mouldings are precision engineered from hard wearing durable ABS. Lid is reinforced with a galvanised mild steel plateMounting frame and box base – 0·9 mm thick galvanised steelFloor service unit conforms to IEC-61534-22

WiringEach compartment has 2 entries for 20 mm and 2 entries for 25 mm flexible conduits

ColourGrey mouldings. Alternative colours available to special orderGoosewing grey plates

Floor tile cut-out dimensions2 compartment : 263 mm x 203 mm(1)

3 and 4 compartment : 340 mm x 203 mm(1)

Floor cut-out aperture is the same for single base or separate compartment base

(1) The aperture dimension 203 mm has a fixing tolerance between 203 to 205 mm

A

C

B

Dimensions from top of floor tile into floor void

A B C Accessory Underside lid to top of box depth accessory (plug clearance) (mm) (mm) (mm)

75 35 35 85 45 35 110 45 60

n To install box

access floor service outlet boxeswith RCD protection

Pack Cat. Nos. Floor boxes with RCD protection and 2 x TSSO

Boxes contain 1 spare 75 mm width compartment

1 CR4400 Includes standard sockets 1 CR4401 Includes low noise sockets

Pre-wired RCD protected floor boxes

Boxes contain RCD and 2 x TSSO with 1 spare 75 mm compartment

1 CR4402 Pre-wired with Cat. No. DP1332 tap-off 1 CR4403 Pre-wired with Cat. No. DP1532 tap-off 1 CR4412 Pre-wired with Cat. No. JP2332 tap-off 1 CR4413 Pre-wired with Cat. No. JP2532 tap-off

picto loupe-65765j.eps

Selection chart (p. 24-25)Dimensions and technical information (opposite)

Electrak floor boxes are available with various RCD protection options and can be supplied pre-wired to power track tap-offs

CR4401

029_Electrak v2.indd 29 20/12/2012 18:31

Page 30: Legrand uk electrak brochure

Floor grommets... perfectly balancing capacity and size

30

Page 31: Legrand uk electrak brochure

Flat mounted RCD socket

NEW 169mm diameter provides the perfect balance between size and capacity

Removable inlay for optional carpet fitting

Cable flap allows permanent connection of services

Spring loaded screws for rapid installation

Available pre-wired to power track tap-offs

poWer and data Grommetselectrak’s new cleaner’s grommets are the latest addition to its power and data grommets range. Within their 169mm diameter, the grommet can now house a flat rcd socket and provide ample space for the user to plug in or unplug equipment.

• neW cleaner’s grommet with flat mounted rcd socket or standard socket options

• push-fit lid with cable flap feature

• spring loaded screws for rapid installation

• available pre-wired to power track tap-offs

acccess Grommetselectrak’s simple to install access grommets allow cables and conduit to link between underfloor power and desk power systems

• ranging from 144mm to 232mm in diameter

• neW 169mm diameter grommet can accommodate up to 3 x 32mm conduits - perfectly balancing capacity and size

• push-fit lid with optional screw fixing to prevent unauthorised access

31

Page 32: Legrand uk electrak brochure

32

floor grommetsaccess / power and data

Pack Cat.Nos. Plasticaccessgrommets

QuickfitinstallationPrecisionengineeredfromhardwearingdurableABSGreymouldings.OthercoloursavailabletospecialorderGrommetsconformtoIEC-61534-22

Simplysecuredbypushingdownthespring-loadedscrewsandrotatingaquarterturn

1 EG0010 144mmØ–cut-outsize127mmØ Canaccomodateallcabletypesorthreemetal

conduitsuptoa20mmØor25mmwithoutfoam

1 EG0030 169mmØ–cut-outsize152mmØ Allowspower,dataandflexibleconduitupto32mm

topassthroughraisedaccessfloor Lidcanbelockedwithscrew(included) Maximumnumberofconduits:

9x20mmØ5x25mmØ3x32mmØ

1 EG0055 232mmØ–cut-outsize215mmØ Highcapacitygrommet Recommendedforinstallationinlighttrafficareas

Aluminiumaccessgrommet

Body–castaluminiumLid–injectionmouldedplasticNylon66withneoprenecablegasketSecuredbyquarter-turnfastenersFloordepth25to55mmAccessgrommetdepth60mm(95mmwhenbackboxincluded)

1 EG0015 144mmØ–cut-outsize127mmØ Allowspower,dataandflexible

conduitupto25mmtopassthroughraisedaccessfloor

Aluminiumpowergrommet

1 EG0025 13Apowergrommet Suppliedcompletewith13A

unswitchedsocket

picto loupe-65765j.eps

Dimensions and technical information (p. 33)

Pack Cat.Nos. Plasticpoweranddatagrommets

169mmØ–cut-outsize152mmØ

QuickfitinstallationPrecisionengineeredfromhardwearingdurableABSGreymouldings.Othercoloursavailabletospecialorder.ConformtoIEC-61534-22RemovablecarpetrecessCableflapfeaturesogrommetlidcanbeclosedwhileinuseSimplysecuredbypushingdownthespringloadedscrewsandrotatingaquarterturn

1 EG0040 13Apowergrommet Suppliedcompletewith

13Aunswitchedsocket

1 EG0045 RCDpowergrommet Suppliedcompletewith13ARCDsocket

1 EG0051 13Apower/datagrommet Suppliedcompletewith13Asocketand

1x37x22mmcut-out

1 EG0052 Datagrommet Suppliedcompletewithdataplate

2x37x22mmcut-out

Pre-wiredpowergrommets

169mmØ–cut-outsize152mmØ

Cleanerssocketversion 1 EG0041 DP1332-3munfused 1 EG0042 DP1532-5munfused 1 EG0043 DP1313-3m13Afused 1 EG0044 DP1513-5m13Afused

RCDsocketversion 1 EG0046 DP1332-3munfused 1 EG0047 DP1532-5munfused 1 EG0048 DP1313-3m13Afused 1 EG0049 DP1513-5m13Afused

EG0040

NEW

NEW NEW

EG0030

EG0045

NEW

NEW

EG0010

032_Electrakv2.indd32 20/12/201218:33

Page 33: Legrand uk electrak brochure

B

Wing

Push grommet into raised floor tile aperturePush down spring loaded screws and rotate quarter turn to secureEnsure wings are located under floor panelFor honeycombed floor panels one wing should face downwards and one wing should face upwards

floor grommetstechnical information

33

n 144 mm Ø plastic floor grommetDimensions

125 mm min

55 mm

90 mm

144 mm Ø

Floor panel cut-out diameter

Recommended holecutter is a 5"/127 mmhole saw blade127 mm min

144 mm grommet EG0010

n 232 mm Ø plastic floor grommetDimensions

Large quick fit grommet Cat. No. EG0055

58 mm

232 mm Ø

213 mm min215 mm max

Floor panel cut-out diameter

Recommended hole cutter is aadjustable hole saw blade withØ range of 40 mm - 300 mm

n To install plastic floor grommet

Lift handle and pull to remove lid

A

Slide lid into lug holes

D E

(1) Push down lid to close (2) If grommet is not in use, replace cable access insert

12

Drop cable access insert into housing opening

Cable access insert

C

125 mm min

55 mm

90 mm

144 mm Ø

Floor panel cut-out diameter

Recommended holecutter is a 5"/127 mmhole saw blade127 mm min

Power grommet

n 169 mm Ø plastic floor grommets

Access grommet

55

148

169Ø

Ø

102

148Ø169

Ø

Cat. No. EG0030

Recommended hole cutter is a 6’’/152 mm hole saw blade

13 A power grommet144

60

9540

144

60

9540

n 144 mm Ø aluminium grommets

Access grommet

60

90

60

90

Recommended hole cutter is a 5’’/127 mm hole saw blade

Cat. No. EG0015

Cat. No. EG0025

033_Electrak v3.indd 33 20/12/2012 17:15

Page 34: Legrand uk electrak brochure

Intersoc-RTM... fast, reliable,adaptable modular desk power

34

Page 35: Legrand uk electrak brochure

compLete soLUtIons For demandInG envIronmentsIntersoc-r is a modular desk power system designed to meet the demands of modern workplaces for faster and more adaptable solutions.

designed with speed of installation and flexibility in mind, Intersoc-r’s modular configuration enables thousands of different combinations to be made - providing solutions for every installation requirement.

• modular system - rapid configuration and easy workstation relocation

• push-fit connection - modules can simply be disconnected and additional modules inserted

• busbar interconnection - no need for wiring

• easily adapted to meet the changing demands of the workplace

35

Page 36: Legrand uk electrak brochure

36

Page 37: Legrand uk electrak brochure

desK modULesIntersoc desktop units provide easy access to power and data points. choose from:

• horizontal or vertical orientation

• a choice of electrical connections: bs 1362 plug, Gst connector or interlinked to the Intersoc-r underdesk system

• a range of socket options: angled to 45º or 90º, fused / unfused

• rJ45 and Usb outlets available

the neXt GeneratIon oF poWer dIstrIbUtIonavailable in standard and clean earth versions, with fixed or rotatable socket options and a safe shuttered electrical connection, Intersoc-r is the next generation of power distribution...

• simple push-fit, module connection with auto-lock mechanism creates robust joints and makes installation quicker and easier

• 32 a system with safe shuttered electrical connections for additional safety, meets the requirements of bs 7671 : 2008 (including section 543.7)

• mcb, rcd and rcbo modules, with reversible hinged covers, provide a full range of circuit protection options

• 2, 3 or 4 gang british standard socket modules with fixed or rotatable, fused or unfused (bs 6396) sockets options - all the options you need to meet the requirements of any installation

• 8 international socket options make Intersoc-r ideal for installations across the globe

• outgoing connections: flexible interlink or end cap with st or Gst options

37

Page 38: Legrand uk electrak brochure

Intersoc-RTM desk moduleselectrical supply

38

Pack Cat.Nos. 16Afeedmodulespre-wiredto13Afusedplug

1 IAB002A With2m1·5mm2cable 1 IAB003A With3m1·5mm2cable 1 IAB005A With5m1·5mm2cable

16Arewirablefeedmodules

1 IAB201A Rewirablefeedmodule(forcable)

16Afeedunitswithin-builtGSTconnector

1 IAB660B CompactfeedmodulewithmaleGSTconnector 1 IAB201B FeedmodulewithmaleGSTandearthbondlead

16Apre-wiredconnectionleads

13Afusedplugpre-wiredtoGSTconnector

1 IAB002B With2m1·5mm2cable 1 IAB003B With3m1·5mm2cable 1 IAB005B With5m1·5mm2cable

GSTtoGSTconnectionleads

1 IAB610BB1mlength 1 IAB620BB2mlength 1 IAB630BB3mlength

Internationalplugspre-wiredtoGSTconnector

Schuko

1 IAB002NBWith2m1·5mm2cable

French/Belgium

1 IAB002UBWith2m1·5mm2cable

5AIndian

1 IAB002PB With2m1·5mm2cable

15ASouthAfrican

1 IAB002QBWith2m1·5mm2cable

Australian/Chinese

1 IAB002RBWith2m1·5mm2cable

15AUSA

1 IAB002SB With2m1·5mm2cable

20AUSA

1 IAB002TB With2m1·5mm2cable

Pack Cat.Nos. 32Apre-wiredfeedmodules

Standardearthtap-offs(E24-Whitetap-off)

1 IAB311A 3munfusedmetaltap-offCat.No.DP1332 1 IAB312A 5munfusedmetaltap-offCat.No.DP1532 1 IAB315A 3m13Afused543·7metaltap-offCat.No.DP1327 1 IAB316A 5m13Afused543·7metaltap-offCat.No.DP1527

Lownoise/cleanearthtap-offs(E25-Greentap-off)

1 IAC311A 3munfusedmetaltap-offCat.No.JP2332 1 IAC312A 5munfusedmetaltap-offCat.No.JP2532 1 IAC315A 3m13Afused543·7metaltap-offCat.No.JP2327 1 IAC316A 5m13Afused543·7metaltap-offCat.No.JP2527

Auxiliaryearthtap-offs(E28-Redtap-off)

1 IAF311A 3munfusedmetaltap-offCat.No.YP5332 1 IAF312A 5munfusedmetaltap-offCat.No.YP5532 1 IAF315A 3m13Afused543·7metaltap-offCat.No.YP5327 1 IAF316A 5m13Afused543·7metaltap-offCat.No.YP5527

32Are-wirablefeedmodules

1 IAB301A Standardearth(forflexibleconduit) 1 IAC301A Lownoise(forflexibleconduit)

32Afeedunitswithin-builtNeutrikconnectors

1 IAB301E Standardearth 1 IAC301E Lownoise

32Atap-offspre-wiredtoNeutrikconnectors

Standardearthtap-offs(E24)

1 IAB311E 3munfusedmetaltap-offCat.No.DP1332 1 IAB312E 5munfusedmetaltap-offCat.No.DP1532 1 IAB315E 3m13Afused543·7metaltap-offCat.No.DP1327 1 IAB316E 5m13Afused543·7metaltap-offCat.No.DP1527

Lownoise/cleanearthtap-offs(E25)

1 IAC311E 3munfusedmetaltap-offCat.No.JP2332 1 IAC312E 5munfusedmetaltap-offCat.No.JP2532 1 IAC315E 3m13Afused543·7metaltap-offCat.No.JP2327 1 IAC316E 5m13Afused543·7metaltap-offCat.No.JP2527

picto loupe-65765j.eps

Dimensions and technical information (p. 44-47)

Intersoc-Rfeaturesfastmodularconnectionwithpush-fitautolockmechanism,safeshutteredelectricalconnectionsandarobustlydesignedrigidjointbetweenmodulesAvailableinstandardandcleanearthversions,conformstoBS5733andtherelevantpartsofBS1363part2.ManufacturedinanapprovedISO9001:2008facility.MeetstherequirementsofBS7671:2008forhighintegrityearthing(section543·7)

NEW

IAB301A

IAB660B

IAB002A

IAB610BB

IAB312A

038_039_Electrak v2.indd 38 20/12/2012 18:41

Page 39: Legrand uk electrak brochure

Intersoc-RTM desk modulesprotection, BS sockets, end caps and interlinks

39

Pack Cat.Nos. Socketmodules–lownoise/cleanearth(greensockets)(continued)

3gangunfused

1 IAC503F Fixedsockets 1 IAC503R Rotatablesockets

3gangindividuallyfused

1 IAC533F 3·15A–fixedsockets 1 IAC533R 3·15A–rotatablesockets

4gangunfused

1 IAC504F Fixedsockets 1 IAC504R Rotatablesockets

4gangindividuallyfused

1 IAC534F 3·15A–fixedsockets 1 IAC534R 3·15A–rotatable

Endcap

1 IAZ001A Blankendcap

Intersoctointersocpre-wiredinterconnection

16A

1 IAB603A 0·3mlength 1 IAB605A 0·5mlength 1 IAB610A 1mlength 1 IAB620A 2mlength 1 IAB630A 3mlength 1 IAB650A 5mlength

32A

1 IAB703A 0·3mlength 1 IAB705A 0·5mlength 1 IAB710A 1mlength 1 IAB720A 2mlength 1 IAB730A 3mlength 1 IAB750A 5mlength

Poweroutendcaps16A

Withoutflex

1 IAB600B EndcapwithfemaleGSTconnector 1 IAB600C EndcapwithfemaleSTconnector

WithflextofemaleGSTconnector

1 IAB610B 1mlength 1 IAB620B 2mlength 1 IAB630B 3mlength

Pack Cat.Nos. Protectionandswitchingmodules

1 IAB401A With13Afuse 1 IAB402A With13Afuseandsw/neon 1 IAB403A With13Afuseandneon 1 IAB404A 32Amax.singleisolationmodule 1 IAB405A With30mARCD 1 IAB408A Withneonindicator 1 IAB420A With16AMCB 1 IAB430A With20AMCB 1 IAB440A With32AMCB 1 IAB450A With16ARCBO 1 IAB460A With20ARCBO 1 IAB470A With32ARCBO

Socketmodules–standard(greysockets)

2gangunfused

1 IAB502F Fixedsockets 1 IAB502R Rotatablesockets

2gangindividuallyfused

1 IAB532F 3·15A–fixedsockets 1 IAB532R 3·15A–rotatablesockets

3gangunfused

1 IAB503F Fixedsockets 1 IAB503R Rotatablesockets

3gangindividuallyfused

1 IAB533F 3·15A–fixedsockets 1 IAB533R 3·15A–rotatablesockets

4gangunfused

1 IAB504F Fixedsockets 1 IAB504R Rotatablesockets

4gangindividuallyfused

1 IAB534F 3·15A–fixedsockets 1 IAB534R 3·15A–rotatablesockets

Socketmodules–lownoise/cleanearth(greensockets)

2gangunfused

1 IAC502F Fixedsockets 1 IAC502R Rotatablesockets

2gangindividuallyfused

1 IAC532F 3·15A–fixedsockets 1 IAC532R 3·15A–rotatablesockets

picto loupe-65765j.eps

Dimensions and technical information (p. 44-47)

TheBSversionisavailablewithfixedorrotatablesockets.IndividuallyfusedsocketsareavailabletomeettherequirementsofBS6396:2008(5x20mmanti-surgeceramicfuses)Awiderangeofinterconnectionsolutionsareavailable.When16Acablinginterconnectionisusedwith32Aunderdesksolutions,suitablede-ratingprotectiondevicesmustbeincorporatedtoprotectthecablesAllprotectionandswitchingmodules,endcapsandinterlinksareuniversallycompatiblewithstandardandcleanearth/lownoisesystems

NEW

IAB504R

IAB533F

IAB600B

IAB703A

IAB610B

IAC502R IAZ001AIAB402A

IAB450A

038_039_Electrak v2.indd 39 20/12/2012 17:31

Page 40: Legrand uk electrak brochure

Intersoc® international rangeinternational socket options

40

Pack Cat.Nos. 5 A Indian socket modules

2 gang – grey socket outlets

1 IAB5P2A 90°angledsockets 1 IAB5P2B 45°angledsockets

4 gang – grey socket outlets

1 IAB5P4A 90°angledsockets 1 IAB5P4B 45°angledsockets

2 gang – green socket outlets

1 IAC5P2A 90°angledsockets 1 IAC5P2B 45°angledsockets

4 gang – green socket outlets

1 IAC5P4A 90°angledsockets 1 IAC5P4B 45°angledsockets

15 A South African socket modules

2 gang – grey socket outlets

1 IAB5Q2A90°angledsockets 1 IAB5Q2B45°angledsockets

4 gang – grey socket outlets

1 IAB5Q4A90°angledsockets 1 IAB5Q4B45°angledsockets

2 gang – green socket outlets

1 IAC5Q2A90°angledsockets 1 IAC5Q2B45°angledsockets

4 gang – green socket outlets

1 IAC5Q4A90°angledsockets 1 IAC5Q4B45°angledsockets

Pack Cat.Nos. Schuko socket modules

2 gang – grey socket outlets

1 IAB5N2A 90°angledsockets 1 IAB5N2B 45°angledsockets

4 gang – grey socket outlets

1 IAB5N4A 90°angledsockets 1 IAB5N4B 45°angledsockets

2 gang – red socket outlets

1 IAF5N2A 90°angledsockets 1 IAF5N2B 45°angledsockets

4 gang – red socket outlets

1 IAF5N4A 90°angledsockets 1 IAF5N4B 45°angledsockets

French/Belgium socket modules

2 gang – grey socket outlets

1 IAB5U2A 90°angledsockets 1 IAB5U2B 45°angledsockets

4 gang – grey socket outlets

1 IAB5U4A 90°angledsockets 1 IAB5U4B 45°angledsockets

2 gang – red socket outlets

1 IAF5U2A 90°angledsockets 1 IAF5U2B 45°angledsockets

4 gang – red socket outlets

1 IAF5U4A 90°angledsockets 1 IAF5U4B 45°angledsockets

picto loupe-65765j.eps

Dimensions and technical information (p. 44-47)

TheIntersoc32Aunder-deskrangeisacompletemodularpowersystem.Intersocoffersawiderangeofinternationalsocketoptions.TheIntersocmodularsystemfeaturessafeshutteredelectricalconnectionsandarobustlydesignedrigidjointbetweenmodules.Allmodulesconnectwithsinglepush-fitactionandautolock

IAB5N4A

IAF5N2A IAC5P2A

IAB5P4A

040_Electrak v2.indd 40 20/12/2012 18:46

Page 41: Legrand uk electrak brochure

41

Intersoc® international range international socket options (continued)

Pack Cat.Nos. 15AUSAsocketmodules

2gang–greysocketoutlets

1 IAB5S2A 90°angledsockets 1 IAB5S2B 45°angledsockets

4gang–greysocketoutlets

1 IAB5S4A 90°angledsockets 1 IAB5S4B 45°angledsockets

2gang–greensocketoutlets

1 IAC5S2A 90°angledsockets 1 IAC5S2B 45°angledsockets

4gang–greensocketoutlets

1 IAC5S4A 90°angledsockets 1 IAC5S4B 45°angledsockets

20AUSAsocketmodules

2gang–greysocketoutlets

1 IAB5T2A 90°angledsockets 1 IAB5T2B 45°angledsockets

4gang–greysocketoutlets

1 IAB5T4A 90°angledsockets 1 IAB5T4B 45°angledsockets

2gang–greensocketoutlets

1 IAC5T2A 90°angledsockets 1 IAC5T2B 45°angledsockets

4gang–greensocketoutlets

1 IAC5T4A 90°angledsockets 1 IAC5T4B 45°angledsockets

Pack Cat.Nos. Australian/Chinesesocketmodules

2gang–greysocketoutlets

1 IAB5R2A 90°angledsockets 1 IAB5R2B 45°angledsockets

4gang–greysocketoutlets

1 IAB5R4A 90°angledsockets 1 IAB5R4B 45°angledsockets

2gang–greensocketoutlets

1 IAC5R2A 90°angledsockets 1 IAC5R2B 45°angledsockets

4gang–greensocketoutlets

1 IAC5R4A 90°angledsockets 1 IAC5R4B 45°angledsockets

picto loupe-65765j.eps

Dimensions and technical information (p. 44-47)

TheIntersoc32Aunder-deskrangeisacompletemodularpowersystem.Intersocoffersawiderangeofinternationalsocketoptions.TheIntersocmodularsystemfeaturessafeshutteredelectricalconnectionsandarobustlydesignedrigidjointbetweenmodules.Allmodulesconnectwithsinglepush-fitactionandautolock

IAB5S4AIAB5R4A

IAC5R2A IAC5S2A

041_Electrak v2.indd 41 20/12/2012 17:38

Page 42: Legrand uk electrak brochure

42

Intersoc® HDU and VDU moduleshorizontal and vertical desktop units can be configured to bespoke customer requirements

A Cat. No. for a bespoke unit can be created by following the flow table below :

Horizontal or vertical orientation

Cat. No. digit 1 H Horizontal desk unit

V Vertical desk unit

Electrical connection

A BS1363 plug

Cat. No. digit 2 B GST connector

D Flexible interlink to modular Intersoc system

Length of electrical connection cable

1 1 m connection lead

Cat. No. digit 3 2 2 m connection lead

3 3 m connection lead

5 5 m connection lead

Angle of socket outlets

Cat. No. digit 4 4 Sockets at 45º

9 Sockets at 90º

Individual fusing of socket outlets

0 Unfused

Cat. No. digit 5 3 Sockets individualy fused at 3·15 A

5 Sockets individualy fused at 5 A

Number of sockets

2 2 electrical sockets

Cat. No. digit 6 3 3 electrical sockets

4 4 electrical sockets

Switching requirements

A No switching

Cat. No. digit 7 B Single master switch

C Sockets individually switched

Data

A Unit without data

B With 1 x RJ45 outlet and 3 m cat 5 lead

C With 2 x RJ45 outlets and 3 m cat 5 leads

Cat. No. digit 8 D With 1 x RJ45 outlet and 3 m cat 6 lead

E With 2 x RJ45 outlets and 3 m cat 6 leads

F With 1 x USB outlet and 3 m lead

G With 2 x USB outlets and 3 m leads

H With 4 x USB outlets and 3 m leads

For example an HD1932BG would have the following specification :H = Horizontal desk unitD = Flexible interlink to modular Intersoc system1 = 1 m connection lead9 = Sockets at 90º3 = Sockets individualy fused at 3.15 A2 = 2 electrical socketsB = Single master switchG = With 2 x USB outlets and 3 m leads

NOTE : Fixings must be ordered separately

042_043_Electrak v3.indd 42 20/12/2012 17:52

Page 43: Legrand uk electrak brochure

43

Intersoc® HDU and VDU moduleshorizontal and vertical desktop units

picto loupe-65765j.eps

Dimensions and technical information (p. 44-45)

Pack Cat.Nos. 16Averticaldesktopunits(VDU)

Allunitsaresuppliedwithsocketsangledat45ºWheredataisoffered,unitscomecompletewith3mdataleads&RJ45plugs

1mpowerlead–BS136313Afusedplug

1 VA1452AA 2socketsindividuallyfusedat5A 1 VA1452AB 2socketsindividuallyfusedat5A+1xRJ45

CAT5edataoutlet 1 VA1452AC 2socketsindividuallyfusedat5A+2xRJ45

CAT5edataoutlets 1 VA1453AA 3socketsindividuallyfusedat5A 1 VA1454AA 4socketsindividuallyfusedat5A

3mpowerlead–BS136313Afusedplug

1 VA3452AA 2socketsindividuallyfusedat5A 1 VA3452AB 2socketsindividuallyfusedat5A+1xRJ45

CAT5edataoutlet 1 VA3452AC 2socketsindividuallyfusedat5A+2xRJ45

CAT5edataoutlets 1 VA3453AA 3socketsindividuallyfusedat5A 1 VA3454AA 4socketsindividuallyfusedat5A

1mpowerlead–maleGSTconnector

1 VB1432AA 2socketsindividuallyfusedat3·15A 1 VB1432AB 2socketsindividuallyfusedat3·15A+1x

RJ45CAT5edataoutlet 1 VB1432AC 2socketsindividuallyfusedat3·15A+2x

RJ45CAT5edataoutlets 1 VB1433AA 3socketsindividuallyfusedat3·15A 1 VB1434AA 4socketsindividuallyfusedat3·15A

Fixings

2 V001 Verticaldesktopunitfixingclamp

DesktopunitsofferpoweranddatasolutionswitharangeofmountingoptionstocomplimentyourfurniturearrangementsAllunitsarehousedinanaluminiumextrusionandareavailableineitherhorizontalorverticalorientationAnycombinationofsocketoutletsandotherservicescanbeintegratedintothealuminiumhousingtosuitindividualcustomerrequirementsincludingswitchingofindividualsockets

Pack Cat.Nos. 16Ahorizontaldesktopunits(HDU)

Allunitsaresuppliedwithsocketsangledat90ºWheredataisoffered,unitscomecompletewith3mdataleads&RJ45plugs

1mpowerlead–BS136313Afusedplug

1 HA1952AA 2socketsindividuallyfusedat5A 1 HA1952AB 2socketsindividuallyfusedat5A+1xRJ45

CAT5edataoutlet 1 HA1952AC 2socketsindividuallyfusedat5A+2xRJ45

CAT5edataoutlets 1 HA1953AA 3socketsindividuallyfusedat5A 1 HA1954AA 4socketsindividuallyfusedat5A

3mpowerlead–BS136313Afusedplug

1 HA3952AA 2socketsindividuallyfusedat5A 1 HA3952AB 2socketsindividuallyfusedat5A+1xRJ45

CAT5edataoutlet 1 HA3952AC 2socketsindividuallyfusedat5A+2xRJ45

CAT5edataoutlets 1 HA3953AA 3socketsindividuallyfusedat5A 1 HA3954AA 4socketsindividuallyfusedat5A

1mpowerlead–maleGSTconnector

1 HB1932AA 2socketsindividuallyfusedat3·15A 1 HB1932AB 2socketsindividuallyfusedat3·15A+1x

RJ45CAT5edataoutlet 1 HB1932AC 2socketsindividuallyfusedat3·15A+2x

RJ45CAT5edataoutlets 1 HB1933AA 3socketsindividuallyfusedat3·15A 1 HB1934AA 4socketsindividuallyfusedat3·15A

Fixings

2 H001 Horizontaldesktopunitfixingclamp

10 H002 Desktopadhesivestrip

Verticalon-deskunit

Horizontalon-deskunit

Anycombinationofsocketandserviceoutletscanbeconfiguredonrequest(egUSB,IBM,Co-axial,SGVA,RJ45etc.)contactuson+44(0)8456006266

042_043_Electrak v3.indd 43 20/12/2012 18:48

Page 44: Legrand uk electrak brochure

Intersoc-RTM under-desk and Intersoc® desktop modulestechnical information

44

n Under-desk dimensions (mm)23 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

276·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

12 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

272·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

3 socket module

214·5

End view

37·9

60

23 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

276·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

12 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

272·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

3 socket module

214·5

End view

37·9

60

n Desktop range dimensions (mm)

2 socket unit

40

100

40

100

Horizontal

40

100

40

100

Vertical

40

100

40

100

23 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

276·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

23 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

276·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

23 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

276·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

2 socket and 1 RJ45 unit

40

100

40

100

293

2 socket and 2 RJ45 unit

40

100

40

100

348

3 socket unit

40

100

40

100

293

4 socket unit

40

100

40

100

368

218

All dimensions (mm) are nominal

12 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

272·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

3 socket module

214·5

End view

37·9

60

12 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

272·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

3 socket module

214·5

End view

37·9

60

12 50

75 110·5

67

Blank end cap

GST interconnectmale

Rewirable interconnectmale

GST interconnectfemale

Rewirable interconnectfemale

411·5

4 socket in-feed module

4 socket module

272·5

2 socket in-feed module

291·5

60

2 socket module

156·5

60

End view

32

60

MCB, RCD protection module

174·5

60

Protection module

115·5

60

50 77·5

Interconnection

3 socket module

214·5

End view

37·9

60

Fixed –end view

Rotatable –end view

(1)

(1) 84·5 mm depth

Compact and GST feed unit Feed unit

(1) (1) (1)

(1) Dimensions only apply to BS sockets and not the international range

044_047_Electrak v2.indd 44 20/12/2012 18:50

Page 45: Legrand uk electrak brochure

45

n Under-desk testing and accreditation n Under-desk and desktop British StandardsBS 6396 : 2008 Electrical Systems in Office Furniture and Educational Furniture Specification

BS 7671 : 2008 incorporating amendment No. 1 : 2011. Requirements for Electrical Installation (IET Wiring Regulations 17th Edition)

Electricity at Work Regulations 1989

Health & Safety Legislation

Below is a brief outline of the main criteria within the standards :

BS 6396 : 2008 was published with regard to the use of electrical equipment within general office and educational furniture. This standard sets out in its scope the use and testing of electrical socket outlets and associated wiring when used together with a 13 A BS 1363 fused plug for mains supply and makes provision for the routing of cables through furniture

For compliance with this standard, socket outlet configurations of up to 4 outlets should be individually fused at 5 A and up to 6 outlets individually fused at 3·15 A

A note on individual socket fusing – BS 6396 Compliance :

The standard requires individual socket fusing (as per the table below)

Meets the requirements of BS 7671 : 2008 (2011) (17th Edition) The Health and Safety Executive states that installations which conform to the standards laid down in BS 7671 : 2008 (2011) are regarded by the HSE as likely to achieve conformity with the relevant parts of the Electricity at Work Regulations 1989

Special note should be taken of regulation 543·7 within BS 7671 : 2008 - Earthing requirements for the installation of equipment having high protective conductor currents

Regulation 543·7 has particular importance when there is a requirement for a quantity of information technology equipment being supplied from a final circuit in a location where the sum of their protective currents exceeds 10 mA in normal use. Due to current in the protective conductor arising from the use of IT equipment, there is a requirement to provide mechanically protected 4 mm2 conductor (543·7·1·103 (ii)). Intersoc achieves this when wired in accordance with the installation sheets by providing mechanically protected 5 mm2 protective conductors within the product

Electrical test data

Rated current up to 32 A Rated voltage 250 V ~ Frequency 50/60 Hz

Volt dropLive and neutral

2 socket module 1·5 m V/A 4 socket module 3·0 m V/A Protection module 4·0 m V/A (depending on device)

In-feeds :

16 A 4·0 m V/A

+1·5 mm2 29 m V/A/m

32 A 2·0 m V/A

+4 mm2 11 m V/A/m

Interconnections :

16 A/32 A 2·0 m V/A

+1·5 mm2 29 m V/A/m

+4 mm2 11 m V/A/m

Earth fault loop impedance

2 socket module 1·5 mΩ4 socket module 3·0 mΩProtection module 4·0 mΩ (depending on device)

In-feeds :

16 A 2·0 mΩ

+1·5 mm2 29 mΩ/m

32 A 2·0 mΩ

+4 mm2 11 mΩ/m

Interconnections :

16 A/32 A 4·0 m V/A

+1·5 mm2 29 mΩ/m

+4 mm2 11 mΩ/m

Mechanical data

Number of conductors 3

Busbar conductor cross-sectional area 5 mm2

16 A rewirable in-feed terminal capacity 10 mm2

32 A rewirable in-feed terminal capacity 10 mm2

Under desk :

Module housing Heat resistant ABS

Socket outlets polycarbonate

Busbars high conductivity copper CW004A (C101)

Other metalwork phosphor bronze CW451K (PB102), CW452K (PB103)

brass CW507L (CZ107), CW508L (CZ108)

high conductivity copper CW004A (C101)(1)

On desk :

Module housing aluminium

Module fascia flame retardant ABS

Socket outlets polycarbonate

End caps flame retardant ABS

Total number of sockets

2, 3 or 4 sockets 5 or 6 sockets

Individually fused at

5 A 3·15 A

Conforms to BS 5733 : 1995 incorporating amendment No. 1 and corrigendum No. 1Conforms to the relevant parts of BS 1363 part 2 Manufactured within an approved ISO 9001 : 2008 facility Quality assurance certificate No. 2029

Material specification

Conductor resistance at 20°C Fixed Rotatable

(1) European grades with nearest British Standard shown in brackets

2 socket module 0·8 mΩ 0·9 mΩ4 socket module 1·6 mΩ 1·7 mΩ

044_047_Electrak v2.indd 45 20/12/2012 18:11

Page 46: Legrand uk electrak brochure

Intersoc-RTM under-desk modulesinstallation and configuration

46

n Installation

Module self-locking latch

Underside ofmodules shown

Slide green latch Blank end cap

2 socket module

16 A 4 socket in-feed module

To connect and disconnect Intersoc modules

1.Connection/disconnectiontobemadebyacompetentperson 2.Beforeconnectingmodulesensuretheyarethecorrectwayupandinline 3.Pushmodulestogetheroneatatime 4.Modulesself-lockwhenfullypushedtogether 5.Todisconnectmodulesslidegreenlatchtounlockmoduleandpullapart 6.Alwaysendmodulerunwithblankendcaporinterconnect

To fix modules to surface 1.Insertthroughallfixingholesno.8pozi-panscrewor

M4bolttorequiredlength 2.Tightenscrew/boltdowntomountingsurface

044_047_Electrak v2.indd 46 20/12/2012 18:12

Page 47: Legrand uk electrak brochure

47

1.Selectthetypeofdistributionsystem-standard,orlownoise/cleanearth 2.Selectthemeansofpoweringthesystem-cableorpowertracktap-off 3.Selectthetypeofin-feedmoduletomatchthecablecapacity-16Aor32A 4.Selectthemeansofprotection 5.Selectthenumberofsocketmodulesfromthe2,3or4gangrange(individuallyfusedorunfused) 6.Selectfixedorrotatablesockets 7.Selecttheinterconnectionunitsifrequired 8.Finishsystemwiththeendcap (Allmodulespushfitandlocktogetheron-siteorcanbefactoryassembledtocustomerrequirement)

n Product configuration

1 2

llllllllllllllllllllllllllllllllllllllllllllllllllllll lllllllllllllllll

llllllllll

llllllllllllllllll llllllllllllliiiii

ilRaisedfloor Floorgrommet

In-feedandpowermodulepushtogetherandlockwithcamlocklever

Tap-offandin-feedpulledthroughfloorgrommetaftertestingandwhenrequired

32Ain-feedconnectedtotap-offandleftunderflooruntilrequired

Underfloorpowertrack

Tap-off

044_047_Electrak v2.indd 47 20/12/2012 18:12

Page 48: Legrand uk electrak brochure

Elec

trak

und

erflo

or to

wor

ksta

tion

syst

ems

guid

e 01

/201

3. 5

KHead office (UK and Ireland):Legrand Electric Limitedgreat King Street North, Birmingham, B19 2LFTel: 0870 608 9000 Fax: 0870 608 9004Website: www.legrand.co.uk

The Legrand logo is a registered trademark of the Legrand group of companies.

Distributor:

This document is printed on sustainably sourced paper. Please recycle.

Contact details

Quotations and Technical Support: The Power Distribution Division of Legrand Electric Ltd. Great King Street North, Birmingham, B19 2LF

Tel: +44 (0) 845 600 6266 Fax: +44 (0) 845 600 6760

E-mail: [email protected]

Customer Services: The Power Distribution Division of Legrand Electric Ltd. No. 1 Industrial Estate Medomsley Road, Consett, County Durham, DH8 6SR

Tel: +44 (0) 845 600 6266 Fax: +44 (0) 845 600 6366

E-mail: [email protected]

Accounts: Legrand Electric Ltd. Great King Street North, Birmingham, B19 2LF

Tel: +44 (0) 870 608 9000 Fax: +44 (0) 870 608 9004