UNDERFLOOR TO WORKSTATION / SYSTEM gUIDE
Electrak®...powering the workstation
P O W E R E D B Y S P E C I A L I S T S
Global strength built on local knowledge
Legrand is the global specialist in electrical and digital building infrastructures. Innovation is the driving force behind its development. With an increasing investment in research and development (circa 5% of sales) and more than 4,000 active patents, the Legrand Group is focused on maintaining a high rate of new product launches that present innovative solutions to the market.
LeGrand In the UK - poWered by specIaLIstsIn the UK Legrand has developed a customer focused structure which harnesses the power of its market leading specialist brands including bticino, electrak and Zucchini to deliver innovative, integrated solutions for every phase of construction.
LEgRAND’S POWER DISTRIBUTION DIVISION From Zucchini transformers, through rising main busbars and distribution boards to electrak’s power track, desk modules and lighting control, Legrand’s power distribution division provides market leading solutions to the increasing demands of today’s buildings.
contents
sUstaInabLe deveLopment From design through to manufacturing, the Legrand Group selects materials and processes that respect people and the environment.
• efficient and environmentally aware product design
• product functions that help to avoid energy waste
• management of manufacturing and logistics sites
• Integration of environmental concerns and Iso 14001 procedures at the Group’s global sites*
poWer tracK overview 8 ordering information 10 technical information 17
FLoor boXesoverview 22 ordering information 24technical information 29 Grommetsoverview 30 ordering information 32technical information 33
Intersoc-roverview 34 ordering information 38technical information 44
* 84% of sites are Iso 14001:2004 accredited including all UK sites.
Electrak®... the specialist in power distribution throughout the workplaceElectrak, part of the Legrand group in the UK, is a leading manufacturer of power distribution and lighting control solutions. Its power track, floor boxes, grommets, desk modules and lighting control ranges are installed in high specification offices around the world.
04
POWERINg ThE WORKSTATION
poWer tracK see page 8
Grommets see page 30
bUscom power and data backbone
cavIty FLoor boXes see page 22
Intersoc-r see page 34
LIGhtraK lighting control system
UNDERFLOOR POWER Electrak’s power track system is perfect for supplying underfloor power in cavity floor installations. With minimal parts, push-fit assembly and a complementary range of floor boxes, this flexible, easy to install system can be reconfigured as office layouts evolve.
WORKSTATION POWER Electrak’s access grommets provide the gateway for power to feed from the underfloor power track network to the workstation, where all desk power requirements are met with our new range of desk modules, Intersoc-R.
FULLy ADDRESSAbLE LIghTINg cONTROL Designed to work in harmony with Electrak’s buscom trunking, Lightrak’s lighting control system offers high end sophistication with unbeatable flexibility and speed of installation. Find out more at www.electrak.co.uk
05
Electrak®... UK manufacturing. global recognition
30 years oF eXperIenceelectrak has been designing and manufacturing cost effective systems that distribute power reliably and safely throughout the workplace since the 1980s.
as the inventor of underfloor busbar systems, electrak sets the benchmark for flexible power distribution.
IndUstry eXperts as part of its ongoing commitment to research and development, electrak continually evolves its product ranges to ensure it produces the best and most innovative solutions available on the market.
electrak takes pride in its enviable reputation for market leading customer service, industry knowledge and product expertise.
QUaLIty assUred UK manUFactUrInGWith its UK manufacturing base situated in the north east of england, electrak adapts to the changing demands of projects by providing a rapid production process whilst ensuring quality meets the highest standards.
electrak’s products are manufactured within an Iso 9001 : 2008 facility and many carry the Intertek diamondmark (where indicated).
06
trUsted throUGhoUt the UK and across the WorLd
UnIted KInGdom• morgan stanley, canary Wharf• media city, manchester• Jp morgan, canary Wharf• rbs, edinburgh• bridgewater place, Leeds• network rail, nationwide• swiss re, city of London• amazon, swansea• heathrow airport, London• morgan stanley, canary Wharf• Fort dunlop, birmingham• royal bank of canada,
city of London• snow hill, birmingham• barclays capital, canary Wharf• temple back, bristol• standard chartered bank, city of London• London Underground• bbc, White city• mann Island, Liverpool
mIddLe east & IndIa • adma-opco hQ, dubai• Internet city, dubai• burjuman centre, dubai• adIc/al bahr towers, abu dhabi• al dar hQ, abu dhabi• central bank of Kuwait• ministry of education, Kuwait• pIFFs aridya, Kuwait• paaet, Kuwait• Qatar news agency• barclays, chennai, India• barclays, pune, India• barclays, andheri, India• barclays, mumbai, India• rbs, delhi, India• Fidelity, delhi, India
asIa pacIFIc • credit suisse, Icc I, hong Kong• deutsche bank, Icc I, hong Kong• barclays capital, cheung
Kong centre• customs headquarters,
north point, hong Kong• standard chartered bank,
IFc II, hong Kong• citi bank tower, hong Kong• macquarie bank, IFc I, hong Kong• Ubs bank, IFc II, hong Kong• Jp morgan, hong Kong• standard chartered bank, marina
bay, singapore• barclays capital, marina bay, singapore• nomura bank, marina bay, singapore• credit suisse, serangoon road,
singapore• abn amro, one raffles Quay, singapore• rbs, one George street, singapore• barclays capital, shanghai• standard chartered bank, shanghai• Ubs bank, shanghai
07
Power track...adaptable, reliable underfloor power
08
the IndUstry standard In UnderFLoor poWerelectrak’s power track system is perfect for cavity floor installations. With minimal parts, push-fit assembly and a complementary range of floor boxes and grommets, this flexible, easy to install system can be reconfigured as office layouts evolve.
the system consists of continuous lengths of track which are fed via a feed unit and can be installed in floor voids as low as 48mm.
• 63 a rated, Ip 40 protection
• available in five versions: single phase, clean earth, dual circuit, three phase and auxiliary earth
• available in 1.2m, 1.8m, 2.4m and 3.6m lengths
• tap-off outlets are located at every 300 or 600mm pitch
• Floor mountable (stand-off brackets also available)
Integral track connector plugs into feed unit Lengths simply push-fit together Integral fixing brackets for rapid installation Tap-offs plug in to shuttered socket outlets and lock on to track body
09
Track feed
Excluding cables and conduit
Flexible metal conduit
Flexible metal conduit
–
–
1·2
2·4
10
Electrak® power track systems
Track lengths with 300 mm socket centres
Description Length (m)
4 sockets
6 sockets
8 sockets
12 sockets
1·2
1·8
2·4
3·6
Standard tap-off / auxiliary earth tap-off
Low noise / clean earth tap-off
Dual circuit tap-off
3 phase tap-off
Key code / Busbar arrangement
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
32 A unfused 16 mm Ø L, N, PE
13 A fused 16 mm Ø L, N, PE
13 A 543·7 fused 16 mm Ø L, N, PE
32 A unfused 16 mm Ø CE, L, N, PE
13 A fused 16 mm Ø CE, L, N, PE
13 A 543·7 fused 16 mm Ø CE, L, N, PE
32 A unfused 20 mm Ø CE, L1, N1 L2, N2, PE
32 A 415 V 3 phase 20 mm Ø L1, L2, L3, N, PE
32 A L1 unfused reconfigurable live pin 16 mm Ø L1, N, PE
32 A L2 unfused reconfigurable live pin 16 mm Ø L2, N, PE
32 A L3 unfused reconfigurable live pin 16 mm Ø L3, N, PE
010_011_Electrak v2.indd 10 20/12/2012 12:39
DF1010 JF2010 KF3010 NF4010 YF5010
DW1000 JW2000 KW3000 NW4000 YW5000
DW1010 JW2010 KW3010 NW4010 YW5010
DW1020 JW2020 KW3020 NW4020 YW5020
11
ELECTRAK 26Dual circuit system
(dark green)
ELECTRAK 273 phase system
(grey)
DA1123 JA2123 KA3123 NA4123 YA5123
DA1183 JA2183 KA3183 NA4183 YA5183
DA1243 JA2243 KA3243 NA4243 YA5243
DA1363 JA2363 KA3363 NA4363 YA5363
(1)AllNPtap-offsarereconfigurablebetweenL1,L2orL3for3phasetrack
ELECTRAK 28Auxiliary earth system
(red)
DP1332 – DP1332 – YP5332
DP1532 – DP1532 – YP5532
DP1313 – DP1313 – YP5313
DP1513 – DP1513 – YP5513
DP1327 – DP1327 – YP5327
DP1527 – DP1527 – YP5527
– JP2332 JP2332 – –
– JP2532 JP2532 – –
– JP2313 JP2313 – –
– JP2513 JP2513 – –
– JP2327 JP2327 – –
– JP2527 JP2527 – –
– – KP3328 – –
– – KP3528 – –
– – – NZ4331 –
– – – NZ4531 –
– – – NP4332(1) –
– – – NP4532(1) –
– – – NP4302(1) –
– – – NP4502(1) –
– – – NP4303(1) –
– – – NP4503(1) –
ELECTRAK 25Low noise / clean earth
system (green)
PE N2L2 PE CEN1L1 PE CEN1L1N2L2 PENL1L2L3 PEN1L1
ELECTRAK 24Standard system
(white)
010_011_Electrak v2.indd 11 20/12/2012 12:39
Electrak® 24 power track systemstandard system (white)
12
Pack Cat.Nos. Tap-offunits
Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)
Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A
32Aunfused
16mm؂L,N,PE
1 DP1332 3m 1 DP1532 5m
13Afused
16mm؂L,N,PE
1 DP1313 3m 1 DP1513 5m
13A543·7fused-highintegrity
16mm؂L,N,PE
1 DP1327 3m 1 DP1527 5m
Pack Cat.Nos. Tracksystemcomponents
Electrak24standardtracklengths
TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres
1 DA1123 1·2m,4sockets,2floorfixingbrackets 1 DA1183 1·8m,6sockets,2floorfixingbrackets 1 DA1243 2·4m,8sockets,2floorfixingbrackets 1 DA1363 3·6m,12sockets,3floorfixingbrackets
Trackfeedunit
1 DF1010 Withone25mmdiameterholesuitableforMICC,armouredcablesorsinglecorecablesinconduit
Flexibleinterlinks
Canbeusedtoovercomeobstructionsorascornerswhererequired
1 DW1000 Excludingcablesandconduit 1 DW1010 1·2mflexiblemetalconduit 1 DW1020 2·4mflexiblemetalconduit
Specialfixingbrackets
Requiredwhentrackisraisedoffsurfacelevel Bracketsraisetrackby21mmandshouldbe spaced600mmapart
1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors
picto loupe-65765j.eps
Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)
ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm
DF1010
DW1010
DP1332DA1123
(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266
- - -/
- - -
012_013_Electrak v3.indd 12 20/12/2012 12:38
Electrak® 25 power track systemlow noise / clean earth system (green)
13
Pack Cat.Nos. Tap-offunits
Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)
Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A
32Aunfused
16mm؂CE,L,N,PE
1 JP2332 3m 1 JP2532 5m
13Afused
16mm؂CE,L,N,PE
1 JP2313 3m 1 JP2513 5m
13A543·7fused-highintegrity
16mm؂CE,L,N,PE
1 JP2327 3m 1 JP2527 5m
Pack Cat.Nos. Tracksystemcomponents
Electrak25lownoise/cleanearthtracklengths
TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres
1 JA2123 1·2m,4sockets,2floorfixingbrackets 1 JA2183 1·8m,6sockets,2floorfixingbrackets 1 JA2243 2·4m,8sockets,2floorfixingbrackets 1 JA2363 3·6m,12sockets,3floorfixingbrackets
Trackfeedunit
1 JF2010 Withone25mmdiameterholesuitableforMICC,armouredcablesorsinglecorecablesinconduit
Flexibleinterlinks
Canbeusedtoovercomeobstructionsorascornerswhererequired
1 JW2000 Excludingcablesandconduit 1 JW2010 1·2mflexiblemetalconduit 1 JW2020 2·4mflexiblemetalconduit
Specialfixingbrackets
Requiredwhentrackisraisedoffsurfacelevel Bracketsraisetrackby21mmandshouldbe spaced600mmapart
1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors
picto loupe-65765j.eps
Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)
ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm
JF2010
JW2010
JP2332JA2123
- - -/
- - -
(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266
012_013_Electrak v3.indd 13 20/12/2012 12:38
Electrak® 26 power track systemdual circuit system (dark green)
14
Pack Cat.Nos. Tap-offunits
Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)
Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A
Standard32Aunfused
16mm؂L,N,PE
1 DP1332 3m 1 DP1532 5m
Standard13Afused
16mm؂L,N,PE
1 DP1313 3m 1 DP1513 5m
Standard13A543·7fused
16mm؂L,N,PE
1 DP1327 3m 1 DP1527 5m
Lownoise/cleanearth32Aunfused
16mm؂CE,L,N,PE
1 JP2332 3m 1 JP2532 5m
Lownoise/cleanearth13Afused
16mm؂CE,L,N,PE
1 JP2313 3m 1 JP2513 5m
Lownoise/cleanearth13A543·7fused
16mm؂CE,L,N,PE
1 JP2327 3m 1 JP2527 5m
Dualcircuit32Aunfused
20mm؂CE,L1,N1,L2,N2,PE
1 KP3328 3m 1 KP3528 5m
Pack Cat.Nos. Tracksystemcomponents
Thedualpowertracksystemhasbothstandardandlownoise/cleanearthsystemsincorporated
Electrak26dualcircuittracklengths
TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres
1 KA3123 1·2m,4sockets,2floorfixingbrackets 1 KA3183 1·8m,6sockets,2floorfixingbrackets 1 KA3243 2·4m,8sockets,2floorfixingbrackets 1 KA3363 3·6m,12sockets,3floorfixingbrackets
Trackfeedunit
1 KF3010 Withtwo25mmdiameterholessuitableforMICC,armouredcablesorsinglecorecablesinconduit
Flexibleinterlinks
Canbeusedtoovercomeobstructionsorascornerswhererequired
1 KW3000 Excludingcablesandconduit 1 KW3010 1·2mflexiblemetalconduit 1 KW3020 2·4mflexiblemetalconduit
Specialfixingbrackets
Requiredwhentrackisraisedoffsurfacelevel Bracketsraisetrackby21mmandshouldbe spaced600mmapart
1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors
picto loupe-65765j.eps
Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)
ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm
KF3010
KW3010
KP3328KA3123
- - -/
- - -
(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266
014_015_Electrak v3.indd 14 20/12/2012 12:43
Electrak® 27 power track system3 phase system (grey)
15
Pack Cat.Nos. Tap-off units
Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)
Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A
32 A 415 V 3 phase
20mm؂L1,L2,L3,N,PE
1 NZ4331 3m 1 NZ4531 5m
32 A L1(2) unfused
Unfused Reconfigurablelivepin
16mm؂L,N,PE
1 NP4332 3m 1 NP4532 5m
32 A L2(2) unfused
Unfused Reconfigurablelivepin
16mm؂L,N,PE
1 NP4302 3m 1 NP4502 5m
32 A L3(2) unfused
Unfused Reconfigurablelivepin
16mm؂L,N,PE
1 NP4303 3m 1 NP4503 5m
Pack Cat.Nos. Track system components
Electrak 27 3 phase track lengths
TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres
1 NA4123 1·2m,4sockets,2floorfixingbrackets 1 NA4183 1·8m,6sockets,2floorfixingbrackets 1 NA4243 2·4m,8sockets,2floorfixingbrackets 1 NA4363 3·6m,12sockets,3floorfixingbrackets
Track feed unit
1 NF4010 Withone25mmdiameterholesuitableforMICC,armouredcablesorsinglecorecablesinconduit
Flexible interlinks
Canbeusedtoovercomeobstructionsorascornerswhererequired
1 NW4000 Excludingcablesandconduit 1 NW4010 1·2mflexiblemetalconduit 1 NW4020 2·4mflexiblemetalconduit
Special fixing brackets
RequiredwhentrackisraisedoffsurfacelevelBracketsraisetrackby21mmandshouldbespaced600mmapart
1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors
picto loupe-65765j.eps
Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)
ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm
NF4010
NW4010
NZ4331NA4123
- - -/
- - -
(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266(2)AllNPtap-offsarereconfigurablebetweenL1,L2,orL3for3phasetrack
014_015_Electrak v3.indd 15 20/12/2012 12:43
Electrak® 28 power track systemauxiliary earth system (red)
16
Pack Cat.Nos. Tap-offunits
Tap-offlengthisdeterminedbythecableandnottheconduitlength,e.g.a3mtap-offhas3mofcableand2·6mofflexiblemetalconduit(1)
Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorifthepowertrackisprotectedbyaprotectivedevicenotexceeding32A
32Aunfused
16mm؂L,N,PE
1 YP5332 3m 1 YP5532 5m
13Afused
16mm؂L,N,PE
1 YP5313 3m 1 YP5513 5m
13A543·7fused-highintegrity
16mm؂L,N,PE
1 YP5327 3m 1 YP5527 5m
Pack Cat.Nos. Tracksystemcomponents
Electrak28auxiliaryearthtracklengths
TracklengthsfittogetherusingtheintegralconnectorsoneachlengthTracklengthsshouldalwaysbesecuredusingtheintegralfloorfixingbrackets300mmsocketcentres
1 YA5123 1·2m,4sockets,2floorfixingbrackets 1 YA5183 1·8m,6sockets,2floorfixingbrackets 1 YA5243 2·4m,8sockets,2floorfixingbrackets 1 YA5363 3·6m,12sockets,3floorfixingbrackets
Trackfeedunit
1 YF5010 Withone25mmdiameterholesuitableforMICC,armouredcablesorsinglecorecablesinconduit
Flexibleinterlinks
Canbeusedtoovercomeobstructionsorascornerswhererequired
1 YW5000 Excludingcablesandconduit 1 YW5010 1·2mflexiblemetalconduit 1 YW5020 2·4mflexiblemetalconduit
Specialfixingbrackets
Requiredwhentrackisraisedoffsurfacelevel Bracketsraisetrackby21mmandshouldbe spaced600mmapart
1 DZ1210 Forfittingundertrackbodyandtrackfeed 1 DZ1230 Forfittingunderintegraltrackconnectors
picto loupe-65765j.eps
Selection chart (p. 10-11)Dimensions and technical information (p. 17-21)
ApprovedtoASTAStandard138andISO9001:2008ConformstoBSEN60439-2:2008.FullycomplieswiththerequirementsofBS7671:2008IEEWiringRegulationsAcompactsystemthatcanbeinstalledinfloorvoidsaslowas48mm
YF5010
YW5010
YP5332YA5123
(1)Tap-offsaresuppliedasstandardwithflexiblemetalconduitForalternativewiringsolutions,contactuson+44(0)8456006266
- - -/
- - -
016_Electrak v3.indd 16 20/12/2012 12:58
17
Electrak® power track systemsdesign and installation
7593
2 x 25 Ø
46
25 Ø
46
250
47
109 118
3215
68
65
End view A
92
End view B
Integral fixing bracket fixing centres
All dimensions (mm) are nominal
n General installation notesElectrak power track is a compact system that can be installed in floor voids as low as 48 mm
Track feed boxes are provided with one or two 25 mm diameter holes suitable for MICC, armoured cables or single core cables in conduitTrack lengths connect together and to track feeds using the integral connectors on each length
Track lengths should always be secured using the integral floor fixing brackets ; three on the 3·6 m length and two on 2·4 m, 1·8 m or 1·2 m lengths
Access to power is provided along the track length by simply plugging tap-off units into shuttered socket outlets. These tap-off units feed all types of conventional floor service outlet boxes or feed workstations directly through the floor via 4 mm2 or 1·5 mm2 insulated conductors contained in flexible metal or VO rated nylon conduit. When connecting tap-offs directly through the floor via grommet outlets to workstations care must be taken to ensure that the tap-off length is adequate
The dual power track system has both standard and low noise / clean earth systems incorporated. As well as dual tap-offs, both standard and low noise / clean earth tap-offs can be plugged into any socket outlet along the track length. The dual tap-off incorporates both standard and low noise cables
Optimum layout flexibility is achieved by positioning track lengths a maximum of 5·2 m apart and 2·5 m from the wall, and by connecting the 3 m tap-off units to floor outlet boxes. This means every part of the floor area can be served. Flexible interlinks can be used to overcome obstructions or used as corners if required
n Special fixing bracketsWhen installing track off-floor, Electrak special fixing brackets raise track by 21 mm. Ensure brackets are spaced 600 mm apart and always have support under the integral track connector and track feed. Failure to do so may undermine the integrity of the system
Cat. No. DZ1210 raised off-floor fixing brackets are spaced at 600 mm centres along track. Also use bottom half of bracket under track feed and flexible interlinkCat. No. DZ1230 raised off-floor fixing brackets are always used under integral track connectors. Track is secured to raised brackets using the track’s integral fixing bracket
50 mm
99 mm
7 mm Ø
Cat. No. DZ121021 mm to underside of track36 mm to top of track
Integral track connector
Cat. No. DZ1230
185 mm
7 mm Ø
Integral track fixing bracket screws to special bracket
n Dimensions
Example floor layout
2·5
m5·
2 m
5·2
m
track feed
5·2
m 3 m flexibletap-off unit
floor serviceoutlet box
integral trackconnectors
socket outlet points every300 or 600 mm alongtrack length
017_021_Electrak v3.indd 17 20/12/2012 13:00
18
Electrak® power track systemsdesign and installation (continued)
n Product configuration
Flexible interlink Tap-off connection
Track and flexible interlink boxes must be securely fixed inline to surface so no movement can take place after fixing
Track feed protective earth terminal and earth bond
Lift terminal tab to access terminal screws and close after use
Lift lid
Protective earth must always be connected via the earth terminal block
Close lid and secure with lid fixing screw before power up
25 mm Ø cable conduit fixing hole
Depress tap-off side clips and push down
Make sure both tap-off side clips are fully pushed home on both
sides of track
Tap-off
Side clip
Push down
Power trackInterlink feed entry socket. Remove dust cover label
Remove dust cover from power track end entry socket before use
Screw fix to surface
Track feed (Cat. No. DF1010) Sub-cabling Tap-off connection
Tap-off metal flexible conduit
20 mm Ø conduit fitting. Tighten back nut securely
Track feed protective earth terminal and earth bond
Clean earth
Connector terminals
Connector terminals
Lift terminal tab to access terminal screws and close after use
Lift lid
Protective earth must always be connected via the earth terminal block
Close lid and secure with lid fixing screw before power up
25 mm Ø cable conduit fixing hole
Track feed (Cat. No. JF2010) Sub-cabling Tap-off connection
Tap-off metal flexible conduit
20 mm Ø conduit fitting Tighten back nut securely
017_021_Electrak v3.indd 18 20/12/2012 13:00
19
Track feed protective earth terminal and earth bond
Connector terminals
Lift terminal tab to access terminal screws and close after use
Lift lid
Protective earth must always be connected via the earth terminal block
Close lid and secure with lid fixing screw before power up
25 mm Ø cable conduit fixing hole
Track feed (Cat. No. NF4010) Sub-cabling 3 phase tap-off connection
Tap-off metal flexible conduit
20 mm Ø conduit fitting Tighten back nut securely
Track feed protective earth terminal and earth bond
Connector terminals
Lift terminal tab to access terminal screws and close after use
Lift lid
Protective earth must always be connected via the earth terminal block
Close lid and secure with lid fixing screw before power up
25 mm Ø cable conduit fixing hole
Track feed (Cat. No. YF5010) Sub-cabling Tap-off connection
Tap-off metal flexible conduit
20 mm Ø conduit fitting Tighten back nut securely
Clean earth
ConnectionsL1, N1, CE = low noise L2, N2, PE = standard
ConnectionsL1, N1, CE = low noise L2, N2, PE = standard
Connector terminals
Lift terminal tab to access terminal screws and close after use
Lift lidProtective earth must always be connected via the earth terminal block
Close lid and secure with lid fixing screw before power up
2 x 25 mm Ø cable conduit fixing hole
Track feed (Cat. No. KF3010) Sub-cabling Dual tap-off connection (dark green)
Tap-off metal flexible conduit
20 mm Ø conduit fitting Tighten back nut securely
Track feed protective earth terminal and earth bond
017_021_Electrak v3.indd 19 20/12/2012 13:01
20
Electrak® power track systemsinstallation
1 Fix track feed to surface
Pull out track fixing bracket lugs and screw fix on both sides
Track outlets reusable plastic dust covers
First track fixing bracket
Power track and integral track connector
Track length
Track feed Make chalk line to align track lengthsDirection of
track run
Integral track connector
Push down
Push down
Remove dust cover
Track feed
Remove dust cover before connecting track connector
Make sure track connector clips are fully pushed home on both sides of track
All integral track fixing brackets must be fixed to surface at 1·2 m fixing centres from first bracket on each track length
2 Connect track length to track feed
3 Connect additional track lengths
4 Secure track lengths to surface
017_021_Electrak v3.indd 20 20/12/2012 13:01
Electrak® power track systemstechnical data
21
Ratedcurrent 63A Ratedvoltage 230/400V~ Frequency 50/60Hz Conductorresistance-liveandneutral 3·0mΩ/m Conductorimpedance 1·5mΩ/m
Electricaltestdata
Busbars 3·0mV/A/m Cableconnector 0·4mV/A Trackconnector 0·4mV/A 32Atap-off 0·4mV/A +4mm2cable 11mV/A/m Flexiblecornerassembly 1·5mV/A +10mm2cable 4·0mV/A/m
Voltdrops(liveandneutral)
Phasebusbar 1·5mΩ/m Earthbusbar 1·5mΩ/m Earthhousing 1·1mΩ/m Earthbusbarandhousing 0·8mΩ/m Cableconnector 0·4mΩ Trackconnector 0·6mΩ 32Atap-off 0·6mΩ +4mm2cable 11mΩ/m Flexiblecornerassembly 1·5mΩ +10mm2cable 4·0mΩ/m Ratedconditionalshort-circuitcurrent 16KA Ambienttemperature 25˚C
Earthfaultloopimpedance
Numberofconductors 3to6 Busbarconductorcrosssectionalarea 13mm2
Housingcrosssectionalarea(copperequivalent) 13mm2
Cableterminalcapacity 16mm2
Tap-offcable32A 4mm2
Tap-offcable13Afused 1·5mm2
Tap-offconduit,upto4conductors 16mmØ Tap-offconduit,5and6conductors 20mmØ Flexiblecornercable(tri-rated,hightemperature) 10mm2
Flexiblecornerconduit 25mmØ IPrating 40
Mechanicaldata
Powertrackhousing Galvanisedsteel,naturalfinish Busbars Highconductivitycopper Busbarinsulator PTFE Trackconnector/socketoutlet/trackfeedconnector Flameretardantpolycarbonate Socketoutletentryshutter Acetal Tap-offhousing Flameretardantpolycarbonate Trackconnectorblades Copper Tap-offblades Copper Tap-off/flexiblecornerconduit,metal Electro-galvanisedsteel Tap-offconduit,plastic VOrated Tap-offcable LSOHtoBS7211 Flexibleinterlinkcable Tri-ratedtoBS6231 Trackfeedbox/flexibleinterlinkboxes Galvanisedsteel Trackfeedconnectorterminals/earthblock Brass Trackfixingbrackets Galvanisedsteel 13Atap-off,fuse ToBS1362,ASTAapproved
Materialspecifications
nEarthfaultloopimpedanceBS7671:2008+A1:2011IETWiringRegulationsrequireaccuratedeterminationofthetotalearthloopimpedance,whichmustbesufficientlylowtoallowtheprotectivedevicetooperatewithinthespecifiedtime,whichforsocketoutletsis0·4seconds.ThevaluesrelevanttoElectrakforcalculatingtheearthfaultloopimpedanceareshownintheelectricaltestdatatable,seeopposite
nDurabilityElectraksystemsaresuperblydesignedandextremelyrobust.Theycanbeexpectedtostanduptoallnormalsiteconditions.ElectrakhasbeenshortcircuitstrengthtestedbyASTA
nInstallationswithhighprotectiveconductorcurrentsAllunfusedtap-offscomplywithRegulation543·7withouttheneedforadditionalearthconductors.Regulation543·7·1·103(ii)states“asinglecopperprotectiveconductorhavingacross-sectionalareaofnotlessthan4mm2,complyingwiththerequirementsofRegulations543·2and543·3,theprotectiveconductorbeingenclosedtoprovideadditionalprotectionagainstmechanicaldamage,forexample,withinaflexibleconduit”Forinstallationswithhighprotectiveconductorcurrentsrequiringfusedtap-offs,a543·7complianttap-offmustbeused.Normallyfusedtap-offsincorporate1·5mm2conductors,howeverinthefused543·7tap-offs,the1·5mm2earthconductorisreplacedwitha4mm2conductorandthereforecomplieswithSection543·7·1·103(ii)
n32Atap-offunitThe3m32Atap-offunitcomprisesanunfusedtap-offwitheither2·6mof16mm/20mmdiameterflexiblemetalconduitorVOratednylonconduitbothwithintegral4mm2LSOHconductors
Theseunitsaredesignedtocomplywithregulation434·2·1oftheIETWiringRegulationsbyvirtueofthefollowing:•maximumlengthofcableis3m•itisfactoryassembledandfullytesteditemwithcableinstalledinhighqualityflexibleconduit
Faultconditionprotectionforthetap-offassemblyandthefloorboxsocketoutletsisdeliveredbythecircuitprotectiondeviceDisconnectiontimeforsocketoutletsis0·4seconds(Regulation411·3·2·2).TheElectraksystemmeetsthisrequirement
Tap-offunitsinexcessof3mshouldonlybeusediftheycontainafuseorthepowertrackisprotectedbyaprotectivedevicenotexceeding32A
nStandards
ApprovedtoASTAStandard138BSEN60439-2:2000,BSEN61534-22:2009andIEC61534-22:2009ManufacturedwithinanapprovedISO9001:2008facilityAssessedQualityAssuranceCertificateNo.2029ElectrakfullycomplieswiththerequirementsofBS7671:2008+A1:2011(IETWiringRegulations)
017_021_Electrak v3.indd 21 20/12/2012 13:01
Floor boxes...choice, flexibility and easy installationElectrak’s 2, 3 and 4 compartment raised access floor boxes and slab boxes offer complete versatility. Floor boxes are available pre-wired with power track tap-off, or supplied empty (unassembled), with a choice of single or separate compartment bases and three depth options. With a vast selection of power and data plates available, boxes can be tailored to the specific requirements of each office installation.
22
Various RCD protection options available
Rapid fit push lock secures base in floor aperture
Single or separate compartment bases
Three depth options: 75mm, 85mm, 110mm
Durable ABS trim and lid surround
Rapid fit /remove mechanism adjusts for flooring thickness
available in 2, 3 and 4 compartments and with a choice of three depths, electrak’s floor boxes have been developed with a host of special features:
• available pre-wired with tap-off or supplied unassembled
• a vast selection of power and data plates, including rcd options
• single or separate compartment bases for ease of data cabling
• rapid installation and fast ratchet mechanism which adjusts to floor finish thickness
Quick-fit, reversible lid for rapid installation
Available pre-wired with tap-off
23
24
access floor service outlet and slab mounted floor boxesempty boxes and accessory plates
100 mm width plates
100 mm width plates
75 mm width plates
To configure boxes as required, select :
1. Box depth2. Number of compartments required3. Desired accessory plates
4 compartment
230 mm
366 mm
3 compartment
230 mm
366 mm
2 compartment
230 mm
290 mm
CR2001 CR011 CR4001
CR2002 CR012 CR4002
CR2003 CR013 CR4003
CR2004 CR014 CR4004
CR2005 CR015 CR4005
CR2006 CR016 CR4006
CR5102 CR5202 CR5302 CR5402
CR020 CR4100
CR022 CR4101
CR023 CR4102
CR027 CR4103
CR029 CR4104
CR030 CR4105
CR044 CR4118
CR036 CR4111
CR043 CR4117
CR026 –
CR028 –
CR042 CR4115
CR031 CR4106
CR033 CR4108
CR024 CR4112
CR025 CR4113
Single base – 75 mm depth
Single base – 85 mm depth (standard box)
Single base – 110 mm depth
Separate compartment base – 75 mm depth
Separate compartment base – 85 mm depth
Separate compartment base – 110 mm depth
Fix directly onto floor slab (supplied empty)
Blank plate
2 gang switched socket outlet
2 gang switched socket outlet, low noise / clean earth
2 gang non-standard switched socket outlet
2 gang unswitched socket outlet
3 gang unswitched socket outlet
3 gang unswitched socket outlet,low noise / clean earth
2 gang RCD socket outlet
2 gang RCD socket outlet, low noise / clean earth
Punched plate for 2 x 1 gang accessories (60·3 mm fixing centres)
Punched plate for 2 gang accessories (120·6 mm fixing centres)
Angled punched plate for 4 x RJ45 sockets(37 mm x 22 mm cut-outs)
2 x LJ2 accessory plate (50 mm fixing centres)
4 x BNC connector plate
4 x Data / telecoms plate (37 mm x 22 mm cut-outs)
6 x Data / telecoms plate (37 mm x 22 mm cut-outs)
Empty boxes Example
Accessory plates For 1, 2 and 3 compartment boxes For 4 compartment boxes
Slab boxes 2 compartment 3 compartment 4 compartment1 compartment
024_Electrak v3.indd 24 20/12/2012 16:47
CF-EP0
25
access floor pre-wired service outlet boxesand accessory plates
Includes 1 x twin switched socket outlet
Pre-wired service outlet boxes with Electrak tap-offs
1. Select power track tap-off and desired configuration2. Select additional accessory plates (if required)
3 compartment
Additional plates for 3 compartment boxes
CR020
CR026
CR028
CR042
Blank plate
Punched plate for 2 x 1 gang accessories (60·3 mm fixing centres)
Punched plate for 2 gang accessories (120·6 mm fixing centres)
Angled punched plate for 4 xRJ45 sockets (37 mm x 22 mm cut-outs)
Includes 2 x twin switched socket outlet
Includes 1 x 2 gang RCD socket outlet
Includes 2 x 2 gang RCD socket outlet
Electrak 24 - standard tap-off
Electrak 25 - low noise / clean earth tap-off
Electrak 28 - auxiliary earth tap-off
DP1332 - 3 m CR100 CR102 CR100R CR102R
DP1532 - 5 m CR101 CR103 CR101R CR103R
JP2332 - 3 m CR110 CR112 CR110R CR112R
JP2532 - 5 m CR111 CR113 CR111R CR113R
YP5332 - 3 m CR104 CR106 CR104R CR106R
YP5532 - 5 m CR105 CR107 CR105R CR107R
Blank plate
Angled punched plate for 4 x RJ45 sockets (37 mm x 22 mm cut-outs)
2 x LJ2 accessory plate (50 mm fixing centres)
CR4100
CR4115
CR4106
DP1332 - 3 m CR120 CR122 CR120R CR122R CR4402
DP1532 - 5 m CR121 CR123 CR121R CR123R CR4403
JP2332 - 3 m CR130 CR132 CR130R CR132R CR4412
JP2532 - 5 m CR131 CR133 CR131R CR133R CR4413
YP5332 - 3 m CR124 CR126 CR124R CR126R CR4406
YP5532 - 5 m CR125 CR127 CR125R CR127R CR4407
230 mm
366 mm
230 mm
366 mm
CR031
CR033
CR024
CR025
2 x LJ2 accessory plate (50 mm fixing centres)
4 x BNC connector plate
4 x Data / telecoms plate (37 mm x 22 mm cut-outs)
6 x Data / telecoms plate (37 mm x 22 mm cut-outs)
4 x BNC connector plate
4 x Data / telecoms plate (37 mm x 22 mm cut-outs)
6 x Data / telecoms plate (37 mm x 22 mm cut-outs)
CR4108
CR4112
CR4113
4 compartment
Electrak 24 - standard tap-off
Electrak 25 - low noise / clean earth tap-off
Electrak 28 - auxiliary earth tap-off
Includes 1 x twin switched socket
outlet
Includes 2 x twin switched socket
outlet
Includes 1 x 2 gang RCD socket outlet
Includes 2 x 2 gang RCD socket outlet
Modular RCD protecting 2 x twin switched socket
outlets and 1 spare compartment
Additional plates for 4 compartment boxes
025_Electrak v4.indd 25 20/12/2012 16:49
access floor service outlet boxesempty boxes
26
Pack Cat.Nos. 2compartmentfloorboxes Emptyboxes
100mmcompartmentwidths
1 CR2001 Singlebase-75mmdepth 1 CR2002 Singlebase-85mmdepth(standardbox) 1 CR2003 Singlebase-110mmdepth 1 CR2004 Separatecompartmentbase-75mmdepth 1 CR2005 Separatecompartmentbase-85mmdepth 1 CR2006 Separatecompartmentbase-110mmdepth
3compartmentfloorboxes Emptyboxes
100mmcompartmentwidths
1 CR011 Singlebase-75mmdepth 1 CR012 Singlebase-85mmdepth(standardbox) 1 CR013 Singlebase-110mmdepth 1 CR014 Separatecompartmentbase-75mmdepth 1 CR015 Separatecompartmentbase-85mmdepth 1 CR016 Separatecompartmentbase-110mmdepth
4compartmentfloorboxes Emptyboxes
75mmcompartmentwidths
1 CR4001 Singlebase-75mmdepth 1 CR4002 Singlebase-85mmdepth(standardbox) 1 CR4003 Singlebase-110mmdepth 1 CR4004 Separatecompartmentbase-75mmdepth 1 CR4005 Separatecompartmentbase-85mmdepth 1 CR4006 Separatecompartmentbase-110mmdepth
picto loupe-65765j.eps
Selection chart (p. 24)Dimensions and technical information (p. 29)
LidandtrimmouldingsareprecisionengineeredfromhardwearingdurableABS.ThelidisreinforcedwithagalvanisedmildsteelplateMountingframeandboxbase-0·9mmthickgalvanisedsteelEachcompartmenthas2entriesfor20mmand2entriesfor25mmflexibleconduitsGreymouldings.Alternativecoloursavailabletospecialorder.Goosewinggreyplates2,3and4compartmentboxesarealsoavailablewithseparateindividualcompartmentbaseunitsforconvenientoffsitepre-wiringSuppliedinpartsorfullyassembledandconfiguredtocustomerspecificationConformtoIEC-61534-22
CR4002
CR012
slab mounted floor boxesempty boxes
Pack Cat.Nos. Slabfloorboxes
FixesdirectlyontofloorslabFastandefficientinstallationwithintegratedfixingplates
Widerangeofpoweranddataaccessoryplates Manufacturedfrom0·9mmthickgalvanisedsteel Eachcompartmenthas2entriesfor20mmand
2entriesfor25mmflexibleconduits
100mmcompartmentwidths
Useplatesfromthe1,2and3compartmentfloorboxsection(p.24)
1 CR5102 1compartmentslabfloorbox
1 CR5202 2compartmentslabfloorbox
1 CR5302 3compartmentslabfloorbox
75mmcompartmentwidths
Useplatesfromthe4compartmentfloorboxsection(p.24)
1 CR5402 4compartmentslabfloorbox
ElectrakslabfloorboxesareanidealsolutionforunderfloorpoweranddatarequirementsUsedinconjunctionwithElectrakfloorgrommets,slabboxespreventunwantedaccesstopoweranddataconnections
CR5102
3compartmentslabfloorboxshownwithtwotwinswitchedsocketoutlets,puncheddataplateandapowertracktap-off
CR5302
Screed/edgetrimboxes,andmetalorlockablelidsareavailabletoordercontactuson+44(0)8456006266
026_027_Electrak v4.indd 26 20/12/2012 13:04
access floor service outlet boxesaccessory plates and ancillary items
27
Pack Cat.Nos. 4compartmentaccessoryplates
75mmcompartmentwidths
1 CR4100 Blankplate 1 CR4101 2gangswitchedsocketoutlet 1 CR4102 2gangswitchedsocketoutlet,lownoise/cleanearth 1 CR4103 2gangnon-standardswitchedsocketoutlet 1 CR4104 2gangunswitchedsocketoutlet 1 CR4105 3gangunswitchedsocketoutlet CR4118 3gangunswitchedsocketoutlet, lownoise/cleanearth 1 CR4111 2gangRCDsocketoutlet 1 CR4117 2gangRCDsocketoutlet,lownoise/cleanearth 1 CR4115 Angledpunchedplatefor4xRJ45
(37mmx22mmcut-outs) 1 CR4106 2xLJ2accessoryplate(50mmfixingcentres) 1 CR4108 4xBNCconnectorplate 1 CR4112 4xData/telecomsplate(37mmx22mmcut-outs) 1 CR4113 6xData/telecomsplate(37mmx22mmcut-outs)
Pack Cat.Nos. 1,2and3compartmentaccessoryplates
100mmwidth
1 CR020 Blankplate 1 CR022 2gangswitchedsocketoutlet 1 CR023 2gangswitchedsocketoutlet,lownoise/cleanearth 1 CR027 2gangnon-standardswitchedsocketoutlet 1 CR029 2gangunswitchedsocketoutlet 1 CR030 3gangunswitchedsocketoutlet CR044 3gangunswitchedsocketoutlet, lownoise/cleanearth 1 CR036 2gangRCDsocketoutlet 1 CR043 2gangRCDsocketoutlet,lownoise/cleanearth 1 CR026 Punchedplatefor2x1gangaccessories
(60·3mmfixingcentres) 1 CR028 Punchedplatefor2gangaccessories
(120·6mmfixingcentres) 1 CR042 Angledpunchedplatefor4xRJ45
(37mmx22mmcut-outs) 1 CR031 2xLJ2accessoryplate(50mmfixingcentres) 1 CR033 4xBNCconnectorplate 1 CR024 4xData/telecomsplate(37mmx22mmcut-outs) 1 CR025 6xData/telecomsplate(37mmx22mmcut-outs)
picto loupe-65765j.eps
Selection chart (p. 24-25)Dimensions and technical information (p. 29)
LidandtrimmouldingsareprecisionengineeredfromhardwearingdurableABS.LidisreinforcedwithagalvanisedmildsteelplateMountingframeandboxbase-0·9mmthickgalvanisedsteelEachcompartmenthas2entriesfor20mmand2entriesfor25mmflexibleconduitsGreymouldings.Alternativecoloursavailabletospecialorder.Goosewinggreyplates2,3and4compartmentboxesarealsoavailablewithseparateindividualcompartmentbaseunitsforconvenientoffsitepre-wiringSuppliedinpartsorfullyassembledandconfiguredtocustomerspecificationConformtoIEC-61534-22
Ancillaryitemsforserviceoutletboxes
1 CR0001 Floortilecut-outtemplate–2compartment 1 CR0003 Floortilecut-outtemplate–3/4compartment 10 CR0000 Cableoutletflap 10 CR0010 Cablerouters 50 CR0011 Screwsforaccessoryplates 1 CR0012 Packof5keysforusewithlockablefloorboxes 1 CR0002 Lid–2compartmentbox 1 CR0004 Lid–3/4compartmentbox 1 CR0005 Mountingframeforvinylfloor.For2compartmentbox
Replacesmountingframeattachedtobase 1 CR0006 Mountingframeforvinylfloor.For3/4compartment
box.Replacesmountingframeattachedtobase 10 CR0007 Floorboxlidhandle 1 CR0020 Metallidandtrim-replacementfor3and4
compartmentboxes-powdercoatedgrey
Electraktap-offs(seep.12-16)
026_027_Electrak v4.indd 27 20/12/2012 13:04
access floor pre-wired service outlet boxes3 and 4 compartment
28
Pack Cat.Nos. 3compartmentpre-wiredboxeswith1xTSSO
100mmcompartmentwidths
Singlebase–85mmdepth,pre-wiredwith: 1 CR100 3mElectrak24standardtap-offCat.No.DP1332 1 CR101 5mElectrak24standardtap-offCat.No.DP1532 1 CR110 3mElectrak25lownoise/cleanearthtap-off
Cat.No.JP2332 1 CR111 5mElectrak25lownoise/cleanearthtap-off
Cat.No.JP2532 1 CR104 3mElectrak28auxiliaryearthtap-off
Cat.No.YP5332 1 CR105 5mElectrak28auxiliaryearthtap-off
Cat.No.YP5532
3compartmentpre-wiredboxeswith2xTSSO
100mmcompartmentwidths
Singlebase–85mmdepth,pre-wiredwith: 1 CR102 3mElectrak24standardtap-offCat.No.DP1332 1 CR103 5mElectrak24standardtap-offCat.No.DP1532 1 CR112 3mElectrak25lownoise/cleanearthtap-off
Cat.No.JP2332 1 CR113 5mElectrak25lownoise/cleanearthtap-off
Cat.No.JP2532 1 CR106 3mElectrak28auxiliaryearthtap-off
Cat.No.YP5332 1 CR107 5mElectrak28auxiliaryearthtap-off
Cat.No.YP5532
Pack Cat.Nos. 4compartmentpre-wiredboxeswith1xTSSO
75mmcompartmentwidths
Singlebase–85mmdepth,pre-wiredwith: 1 CR120 3mElectrak24standardtap-offCat.No.DP1332 1 CR121 5mElectrak24standardtap-offCat.No.DP1532 1 CR130 3mElectrak25lownoise/cleanearthtap-off
Cat.No.JP2332 1 CR131 5mElectrak25lownoise/cleanearthtap-off
Cat.No.JP2532 1 CR124 3mElectrak28auxiliaryearthtap-offCat.No.YP5332 1 CR125 5mElectrak28auxiliaryearthtap-offCat.No.YP5532
4compartmentpre-wiredboxeswith2xTSSO
75mmcompartmentwidths
Singlebase–85mmdepth,pre-wiredwith: 1 CR122 3mElectrak24standardtap-offCat.No.DP1332 1 CR123 5mElectrak24standardtap-offCat.No.DP1532 1 CR132 3mElectrak25lownoise/cleanearthtap-off
Cat.No.JP2332 1 CR133 5mElectrak25lownoise/cleanearthtap-off
Cat.No.JP2532 1 CR126 3mElectrak28auxiliaryearthtap-offCat.No.YP5332 1 CR127 5mElectrak28auxiliaryearthtap-offCat.No.YP5532
Electrakfloorboxescanbesuppliedpre-wiredtopowertracktap-offswithanyvariationofsockets,tap-offs,depthorotherconfiguration
picto loupe-65765j.eps
Dimensions and technical information (p. 29)
CR122CR100
Alsoavailable:-pre-wiredboxeswithfusedtap-offs-shallowordeepversions-separatecompartmentbasescontactuson+44(0)8456006266
Pre-wired floor boxes can be supplied with RCD rather than standard sockets. Add an R to the end of the part numbers for an RCD version.For example CR100R is a 3 compartment floor box with a twin RCD socket and a DP1332 tap-off
028_Electrak v3.indd 28 20/12/2012 17:03
access floor service outlet boxestechnical information
29
n Floor boxes
To fit carpet : Detach lid and trim assembly by lifting the blue locking handles and lifting out. Cut and fit carpet. Push lid and trim assembly back into place
Cut hole in raised floor tile, lower complete box into aperture and push firmly down
DimensionsLid can accommodate carpets up to 6 mm depthAccessory plates are 172 mm long, with 162 mm fixing centres
MaterialsLid and trim mouldings are precision engineered from hard wearing durable ABS. Lid is reinforced with a galvanised mild steel plateMounting frame and box base – 0·9 mm thick galvanised steelFloor service unit conforms to IEC-61534-22
WiringEach compartment has 2 entries for 20 mm and 2 entries for 25 mm flexible conduits
ColourGrey mouldings. Alternative colours available to special orderGoosewing grey plates
Floor tile cut-out dimensions2 compartment : 263 mm x 203 mm(1)
3 and 4 compartment : 340 mm x 203 mm(1)
Floor cut-out aperture is the same for single base or separate compartment base
(1) The aperture dimension 203 mm has a fixing tolerance between 203 to 205 mm
A
C
B
Dimensions from top of floor tile into floor void
A B C Accessory Underside lid to top of box depth accessory (plug clearance) (mm) (mm) (mm)
75 35 35 85 45 35 110 45 60
n To install box
access floor service outlet boxeswith RCD protection
Pack Cat. Nos. Floor boxes with RCD protection and 2 x TSSO
Boxes contain 1 spare 75 mm width compartment
1 CR4400 Includes standard sockets 1 CR4401 Includes low noise sockets
Pre-wired RCD protected floor boxes
Boxes contain RCD and 2 x TSSO with 1 spare 75 mm compartment
1 CR4402 Pre-wired with Cat. No. DP1332 tap-off 1 CR4403 Pre-wired with Cat. No. DP1532 tap-off 1 CR4412 Pre-wired with Cat. No. JP2332 tap-off 1 CR4413 Pre-wired with Cat. No. JP2532 tap-off
picto loupe-65765j.eps
Selection chart (p. 24-25)Dimensions and technical information (opposite)
Electrak floor boxes are available with various RCD protection options and can be supplied pre-wired to power track tap-offs
CR4401
029_Electrak v2.indd 29 20/12/2012 18:31
Floor grommets... perfectly balancing capacity and size
30
Flat mounted RCD socket
NEW 169mm diameter provides the perfect balance between size and capacity
Removable inlay for optional carpet fitting
Cable flap allows permanent connection of services
Spring loaded screws for rapid installation
Available pre-wired to power track tap-offs
poWer and data Grommetselectrak’s new cleaner’s grommets are the latest addition to its power and data grommets range. Within their 169mm diameter, the grommet can now house a flat rcd socket and provide ample space for the user to plug in or unplug equipment.
• neW cleaner’s grommet with flat mounted rcd socket or standard socket options
• push-fit lid with cable flap feature
• spring loaded screws for rapid installation
• available pre-wired to power track tap-offs
acccess Grommetselectrak’s simple to install access grommets allow cables and conduit to link between underfloor power and desk power systems
• ranging from 144mm to 232mm in diameter
• neW 169mm diameter grommet can accommodate up to 3 x 32mm conduits - perfectly balancing capacity and size
• push-fit lid with optional screw fixing to prevent unauthorised access
31
32
floor grommetsaccess / power and data
Pack Cat.Nos. Plasticaccessgrommets
QuickfitinstallationPrecisionengineeredfromhardwearingdurableABSGreymouldings.OthercoloursavailabletospecialorderGrommetsconformtoIEC-61534-22
Simplysecuredbypushingdownthespring-loadedscrewsandrotatingaquarterturn
1 EG0010 144mmØ–cut-outsize127mmØ Canaccomodateallcabletypesorthreemetal
conduitsuptoa20mmØor25mmwithoutfoam
1 EG0030 169mmØ–cut-outsize152mmØ Allowspower,dataandflexibleconduitupto32mm
topassthroughraisedaccessfloor Lidcanbelockedwithscrew(included) Maximumnumberofconduits:
9x20mmØ5x25mmØ3x32mmØ
1 EG0055 232mmØ–cut-outsize215mmØ Highcapacitygrommet Recommendedforinstallationinlighttrafficareas
Aluminiumaccessgrommet
Body–castaluminiumLid–injectionmouldedplasticNylon66withneoprenecablegasketSecuredbyquarter-turnfastenersFloordepth25to55mmAccessgrommetdepth60mm(95mmwhenbackboxincluded)
1 EG0015 144mmØ–cut-outsize127mmØ Allowspower,dataandflexible
conduitupto25mmtopassthroughraisedaccessfloor
Aluminiumpowergrommet
1 EG0025 13Apowergrommet Suppliedcompletewith13A
unswitchedsocket
picto loupe-65765j.eps
Dimensions and technical information (p. 33)
Pack Cat.Nos. Plasticpoweranddatagrommets
169mmØ–cut-outsize152mmØ
QuickfitinstallationPrecisionengineeredfromhardwearingdurableABSGreymouldings.Othercoloursavailabletospecialorder.ConformtoIEC-61534-22RemovablecarpetrecessCableflapfeaturesogrommetlidcanbeclosedwhileinuseSimplysecuredbypushingdownthespringloadedscrewsandrotatingaquarterturn
1 EG0040 13Apowergrommet Suppliedcompletewith
13Aunswitchedsocket
1 EG0045 RCDpowergrommet Suppliedcompletewith13ARCDsocket
1 EG0051 13Apower/datagrommet Suppliedcompletewith13Asocketand
1x37x22mmcut-out
1 EG0052 Datagrommet Suppliedcompletewithdataplate
2x37x22mmcut-out
Pre-wiredpowergrommets
169mmØ–cut-outsize152mmØ
Cleanerssocketversion 1 EG0041 DP1332-3munfused 1 EG0042 DP1532-5munfused 1 EG0043 DP1313-3m13Afused 1 EG0044 DP1513-5m13Afused
RCDsocketversion 1 EG0046 DP1332-3munfused 1 EG0047 DP1532-5munfused 1 EG0048 DP1313-3m13Afused 1 EG0049 DP1513-5m13Afused
EG0040
NEW
NEW NEW
EG0030
EG0045
NEW
NEW
EG0010
032_Electrakv2.indd32 20/12/201218:33
B
Wing
Push grommet into raised floor tile aperturePush down spring loaded screws and rotate quarter turn to secureEnsure wings are located under floor panelFor honeycombed floor panels one wing should face downwards and one wing should face upwards
floor grommetstechnical information
33
n 144 mm Ø plastic floor grommetDimensions
125 mm min
55 mm
90 mm
144 mm Ø
Floor panel cut-out diameter
Recommended holecutter is a 5"/127 mmhole saw blade127 mm min
144 mm grommet EG0010
n 232 mm Ø plastic floor grommetDimensions
Large quick fit grommet Cat. No. EG0055
58 mm
232 mm Ø
213 mm min215 mm max
Floor panel cut-out diameter
Recommended hole cutter is aadjustable hole saw blade withØ range of 40 mm - 300 mm
n To install plastic floor grommet
Lift handle and pull to remove lid
A
Slide lid into lug holes
D E
(1) Push down lid to close (2) If grommet is not in use, replace cable access insert
12
Drop cable access insert into housing opening
Cable access insert
C
125 mm min
55 mm
90 mm
144 mm Ø
Floor panel cut-out diameter
Recommended holecutter is a 5"/127 mmhole saw blade127 mm min
Power grommet
n 169 mm Ø plastic floor grommets
Access grommet
55
148
169Ø
Ø
102
148Ø169
Ø
Cat. No. EG0030
Recommended hole cutter is a 6’’/152 mm hole saw blade
13 A power grommet144
60
9540
144
60
9540
n 144 mm Ø aluminium grommets
Access grommet
60
90
60
90
Recommended hole cutter is a 5’’/127 mm hole saw blade
Cat. No. EG0015
Cat. No. EG0025
033_Electrak v3.indd 33 20/12/2012 17:15
Intersoc-RTM... fast, reliable,adaptable modular desk power
34
compLete soLUtIons For demandInG envIronmentsIntersoc-r is a modular desk power system designed to meet the demands of modern workplaces for faster and more adaptable solutions.
designed with speed of installation and flexibility in mind, Intersoc-r’s modular configuration enables thousands of different combinations to be made - providing solutions for every installation requirement.
• modular system - rapid configuration and easy workstation relocation
• push-fit connection - modules can simply be disconnected and additional modules inserted
• busbar interconnection - no need for wiring
• easily adapted to meet the changing demands of the workplace
35
36
desK modULesIntersoc desktop units provide easy access to power and data points. choose from:
• horizontal or vertical orientation
• a choice of electrical connections: bs 1362 plug, Gst connector or interlinked to the Intersoc-r underdesk system
• a range of socket options: angled to 45º or 90º, fused / unfused
• rJ45 and Usb outlets available
the neXt GeneratIon oF poWer dIstrIbUtIonavailable in standard and clean earth versions, with fixed or rotatable socket options and a safe shuttered electrical connection, Intersoc-r is the next generation of power distribution...
• simple push-fit, module connection with auto-lock mechanism creates robust joints and makes installation quicker and easier
• 32 a system with safe shuttered electrical connections for additional safety, meets the requirements of bs 7671 : 2008 (including section 543.7)
• mcb, rcd and rcbo modules, with reversible hinged covers, provide a full range of circuit protection options
• 2, 3 or 4 gang british standard socket modules with fixed or rotatable, fused or unfused (bs 6396) sockets options - all the options you need to meet the requirements of any installation
• 8 international socket options make Intersoc-r ideal for installations across the globe
• outgoing connections: flexible interlink or end cap with st or Gst options
37
Intersoc-RTM desk moduleselectrical supply
38
Pack Cat.Nos. 16Afeedmodulespre-wiredto13Afusedplug
1 IAB002A With2m1·5mm2cable 1 IAB003A With3m1·5mm2cable 1 IAB005A With5m1·5mm2cable
16Arewirablefeedmodules
1 IAB201A Rewirablefeedmodule(forcable)
16Afeedunitswithin-builtGSTconnector
1 IAB660B CompactfeedmodulewithmaleGSTconnector 1 IAB201B FeedmodulewithmaleGSTandearthbondlead
16Apre-wiredconnectionleads
13Afusedplugpre-wiredtoGSTconnector
1 IAB002B With2m1·5mm2cable 1 IAB003B With3m1·5mm2cable 1 IAB005B With5m1·5mm2cable
GSTtoGSTconnectionleads
1 IAB610BB1mlength 1 IAB620BB2mlength 1 IAB630BB3mlength
Internationalplugspre-wiredtoGSTconnector
Schuko
1 IAB002NBWith2m1·5mm2cable
French/Belgium
1 IAB002UBWith2m1·5mm2cable
5AIndian
1 IAB002PB With2m1·5mm2cable
15ASouthAfrican
1 IAB002QBWith2m1·5mm2cable
Australian/Chinese
1 IAB002RBWith2m1·5mm2cable
15AUSA
1 IAB002SB With2m1·5mm2cable
20AUSA
1 IAB002TB With2m1·5mm2cable
Pack Cat.Nos. 32Apre-wiredfeedmodules
Standardearthtap-offs(E24-Whitetap-off)
1 IAB311A 3munfusedmetaltap-offCat.No.DP1332 1 IAB312A 5munfusedmetaltap-offCat.No.DP1532 1 IAB315A 3m13Afused543·7metaltap-offCat.No.DP1327 1 IAB316A 5m13Afused543·7metaltap-offCat.No.DP1527
Lownoise/cleanearthtap-offs(E25-Greentap-off)
1 IAC311A 3munfusedmetaltap-offCat.No.JP2332 1 IAC312A 5munfusedmetaltap-offCat.No.JP2532 1 IAC315A 3m13Afused543·7metaltap-offCat.No.JP2327 1 IAC316A 5m13Afused543·7metaltap-offCat.No.JP2527
Auxiliaryearthtap-offs(E28-Redtap-off)
1 IAF311A 3munfusedmetaltap-offCat.No.YP5332 1 IAF312A 5munfusedmetaltap-offCat.No.YP5532 1 IAF315A 3m13Afused543·7metaltap-offCat.No.YP5327 1 IAF316A 5m13Afused543·7metaltap-offCat.No.YP5527
32Are-wirablefeedmodules
1 IAB301A Standardearth(forflexibleconduit) 1 IAC301A Lownoise(forflexibleconduit)
32Afeedunitswithin-builtNeutrikconnectors
1 IAB301E Standardearth 1 IAC301E Lownoise
32Atap-offspre-wiredtoNeutrikconnectors
Standardearthtap-offs(E24)
1 IAB311E 3munfusedmetaltap-offCat.No.DP1332 1 IAB312E 5munfusedmetaltap-offCat.No.DP1532 1 IAB315E 3m13Afused543·7metaltap-offCat.No.DP1327 1 IAB316E 5m13Afused543·7metaltap-offCat.No.DP1527
Lownoise/cleanearthtap-offs(E25)
1 IAC311E 3munfusedmetaltap-offCat.No.JP2332 1 IAC312E 5munfusedmetaltap-offCat.No.JP2532 1 IAC315E 3m13Afused543·7metaltap-offCat.No.JP2327 1 IAC316E 5m13Afused543·7metaltap-offCat.No.JP2527
picto loupe-65765j.eps
Dimensions and technical information (p. 44-47)
Intersoc-Rfeaturesfastmodularconnectionwithpush-fitautolockmechanism,safeshutteredelectricalconnectionsandarobustlydesignedrigidjointbetweenmodulesAvailableinstandardandcleanearthversions,conformstoBS5733andtherelevantpartsofBS1363part2.ManufacturedinanapprovedISO9001:2008facility.MeetstherequirementsofBS7671:2008forhighintegrityearthing(section543·7)
NEW
IAB301A
IAB660B
IAB002A
IAB610BB
IAB312A
038_039_Electrak v2.indd 38 20/12/2012 18:41
Intersoc-RTM desk modulesprotection, BS sockets, end caps and interlinks
39
Pack Cat.Nos. Socketmodules–lownoise/cleanearth(greensockets)(continued)
3gangunfused
1 IAC503F Fixedsockets 1 IAC503R Rotatablesockets
3gangindividuallyfused
1 IAC533F 3·15A–fixedsockets 1 IAC533R 3·15A–rotatablesockets
4gangunfused
1 IAC504F Fixedsockets 1 IAC504R Rotatablesockets
4gangindividuallyfused
1 IAC534F 3·15A–fixedsockets 1 IAC534R 3·15A–rotatable
Endcap
1 IAZ001A Blankendcap
Intersoctointersocpre-wiredinterconnection
16A
1 IAB603A 0·3mlength 1 IAB605A 0·5mlength 1 IAB610A 1mlength 1 IAB620A 2mlength 1 IAB630A 3mlength 1 IAB650A 5mlength
32A
1 IAB703A 0·3mlength 1 IAB705A 0·5mlength 1 IAB710A 1mlength 1 IAB720A 2mlength 1 IAB730A 3mlength 1 IAB750A 5mlength
Poweroutendcaps16A
Withoutflex
1 IAB600B EndcapwithfemaleGSTconnector 1 IAB600C EndcapwithfemaleSTconnector
WithflextofemaleGSTconnector
1 IAB610B 1mlength 1 IAB620B 2mlength 1 IAB630B 3mlength
Pack Cat.Nos. Protectionandswitchingmodules
1 IAB401A With13Afuse 1 IAB402A With13Afuseandsw/neon 1 IAB403A With13Afuseandneon 1 IAB404A 32Amax.singleisolationmodule 1 IAB405A With30mARCD 1 IAB408A Withneonindicator 1 IAB420A With16AMCB 1 IAB430A With20AMCB 1 IAB440A With32AMCB 1 IAB450A With16ARCBO 1 IAB460A With20ARCBO 1 IAB470A With32ARCBO
Socketmodules–standard(greysockets)
2gangunfused
1 IAB502F Fixedsockets 1 IAB502R Rotatablesockets
2gangindividuallyfused
1 IAB532F 3·15A–fixedsockets 1 IAB532R 3·15A–rotatablesockets
3gangunfused
1 IAB503F Fixedsockets 1 IAB503R Rotatablesockets
3gangindividuallyfused
1 IAB533F 3·15A–fixedsockets 1 IAB533R 3·15A–rotatablesockets
4gangunfused
1 IAB504F Fixedsockets 1 IAB504R Rotatablesockets
4gangindividuallyfused
1 IAB534F 3·15A–fixedsockets 1 IAB534R 3·15A–rotatablesockets
Socketmodules–lownoise/cleanearth(greensockets)
2gangunfused
1 IAC502F Fixedsockets 1 IAC502R Rotatablesockets
2gangindividuallyfused
1 IAC532F 3·15A–fixedsockets 1 IAC532R 3·15A–rotatablesockets
picto loupe-65765j.eps
Dimensions and technical information (p. 44-47)
TheBSversionisavailablewithfixedorrotatablesockets.IndividuallyfusedsocketsareavailabletomeettherequirementsofBS6396:2008(5x20mmanti-surgeceramicfuses)Awiderangeofinterconnectionsolutionsareavailable.When16Acablinginterconnectionisusedwith32Aunderdesksolutions,suitablede-ratingprotectiondevicesmustbeincorporatedtoprotectthecablesAllprotectionandswitchingmodules,endcapsandinterlinksareuniversallycompatiblewithstandardandcleanearth/lownoisesystems
NEW
IAB504R
IAB533F
IAB600B
IAB703A
IAB610B
IAC502R IAZ001AIAB402A
IAB450A
038_039_Electrak v2.indd 39 20/12/2012 17:31
Intersoc® international rangeinternational socket options
40
Pack Cat.Nos. 5 A Indian socket modules
2 gang – grey socket outlets
1 IAB5P2A 90°angledsockets 1 IAB5P2B 45°angledsockets
4 gang – grey socket outlets
1 IAB5P4A 90°angledsockets 1 IAB5P4B 45°angledsockets
2 gang – green socket outlets
1 IAC5P2A 90°angledsockets 1 IAC5P2B 45°angledsockets
4 gang – green socket outlets
1 IAC5P4A 90°angledsockets 1 IAC5P4B 45°angledsockets
15 A South African socket modules
2 gang – grey socket outlets
1 IAB5Q2A90°angledsockets 1 IAB5Q2B45°angledsockets
4 gang – grey socket outlets
1 IAB5Q4A90°angledsockets 1 IAB5Q4B45°angledsockets
2 gang – green socket outlets
1 IAC5Q2A90°angledsockets 1 IAC5Q2B45°angledsockets
4 gang – green socket outlets
1 IAC5Q4A90°angledsockets 1 IAC5Q4B45°angledsockets
Pack Cat.Nos. Schuko socket modules
2 gang – grey socket outlets
1 IAB5N2A 90°angledsockets 1 IAB5N2B 45°angledsockets
4 gang – grey socket outlets
1 IAB5N4A 90°angledsockets 1 IAB5N4B 45°angledsockets
2 gang – red socket outlets
1 IAF5N2A 90°angledsockets 1 IAF5N2B 45°angledsockets
4 gang – red socket outlets
1 IAF5N4A 90°angledsockets 1 IAF5N4B 45°angledsockets
French/Belgium socket modules
2 gang – grey socket outlets
1 IAB5U2A 90°angledsockets 1 IAB5U2B 45°angledsockets
4 gang – grey socket outlets
1 IAB5U4A 90°angledsockets 1 IAB5U4B 45°angledsockets
2 gang – red socket outlets
1 IAF5U2A 90°angledsockets 1 IAF5U2B 45°angledsockets
4 gang – red socket outlets
1 IAF5U4A 90°angledsockets 1 IAF5U4B 45°angledsockets
picto loupe-65765j.eps
Dimensions and technical information (p. 44-47)
TheIntersoc32Aunder-deskrangeisacompletemodularpowersystem.Intersocoffersawiderangeofinternationalsocketoptions.TheIntersocmodularsystemfeaturessafeshutteredelectricalconnectionsandarobustlydesignedrigidjointbetweenmodules.Allmodulesconnectwithsinglepush-fitactionandautolock
IAB5N4A
IAF5N2A IAC5P2A
IAB5P4A
040_Electrak v2.indd 40 20/12/2012 18:46
41
Intersoc® international range international socket options (continued)
Pack Cat.Nos. 15AUSAsocketmodules
2gang–greysocketoutlets
1 IAB5S2A 90°angledsockets 1 IAB5S2B 45°angledsockets
4gang–greysocketoutlets
1 IAB5S4A 90°angledsockets 1 IAB5S4B 45°angledsockets
2gang–greensocketoutlets
1 IAC5S2A 90°angledsockets 1 IAC5S2B 45°angledsockets
4gang–greensocketoutlets
1 IAC5S4A 90°angledsockets 1 IAC5S4B 45°angledsockets
20AUSAsocketmodules
2gang–greysocketoutlets
1 IAB5T2A 90°angledsockets 1 IAB5T2B 45°angledsockets
4gang–greysocketoutlets
1 IAB5T4A 90°angledsockets 1 IAB5T4B 45°angledsockets
2gang–greensocketoutlets
1 IAC5T2A 90°angledsockets 1 IAC5T2B 45°angledsockets
4gang–greensocketoutlets
1 IAC5T4A 90°angledsockets 1 IAC5T4B 45°angledsockets
Pack Cat.Nos. Australian/Chinesesocketmodules
2gang–greysocketoutlets
1 IAB5R2A 90°angledsockets 1 IAB5R2B 45°angledsockets
4gang–greysocketoutlets
1 IAB5R4A 90°angledsockets 1 IAB5R4B 45°angledsockets
2gang–greensocketoutlets
1 IAC5R2A 90°angledsockets 1 IAC5R2B 45°angledsockets
4gang–greensocketoutlets
1 IAC5R4A 90°angledsockets 1 IAC5R4B 45°angledsockets
picto loupe-65765j.eps
Dimensions and technical information (p. 44-47)
TheIntersoc32Aunder-deskrangeisacompletemodularpowersystem.Intersocoffersawiderangeofinternationalsocketoptions.TheIntersocmodularsystemfeaturessafeshutteredelectricalconnectionsandarobustlydesignedrigidjointbetweenmodules.Allmodulesconnectwithsinglepush-fitactionandautolock
IAB5S4AIAB5R4A
IAC5R2A IAC5S2A
041_Electrak v2.indd 41 20/12/2012 17:38
42
Intersoc® HDU and VDU moduleshorizontal and vertical desktop units can be configured to bespoke customer requirements
A Cat. No. for a bespoke unit can be created by following the flow table below :
Horizontal or vertical orientation
Cat. No. digit 1 H Horizontal desk unit
V Vertical desk unit
Electrical connection
A BS1363 plug
Cat. No. digit 2 B GST connector
D Flexible interlink to modular Intersoc system
Length of electrical connection cable
1 1 m connection lead
Cat. No. digit 3 2 2 m connection lead
3 3 m connection lead
5 5 m connection lead
Angle of socket outlets
Cat. No. digit 4 4 Sockets at 45º
9 Sockets at 90º
Individual fusing of socket outlets
0 Unfused
Cat. No. digit 5 3 Sockets individualy fused at 3·15 A
5 Sockets individualy fused at 5 A
Number of sockets
2 2 electrical sockets
Cat. No. digit 6 3 3 electrical sockets
4 4 electrical sockets
Switching requirements
A No switching
Cat. No. digit 7 B Single master switch
C Sockets individually switched
Data
A Unit without data
B With 1 x RJ45 outlet and 3 m cat 5 lead
C With 2 x RJ45 outlets and 3 m cat 5 leads
Cat. No. digit 8 D With 1 x RJ45 outlet and 3 m cat 6 lead
E With 2 x RJ45 outlets and 3 m cat 6 leads
F With 1 x USB outlet and 3 m lead
G With 2 x USB outlets and 3 m leads
H With 4 x USB outlets and 3 m leads
For example an HD1932BG would have the following specification :H = Horizontal desk unitD = Flexible interlink to modular Intersoc system1 = 1 m connection lead9 = Sockets at 90º3 = Sockets individualy fused at 3.15 A2 = 2 electrical socketsB = Single master switchG = With 2 x USB outlets and 3 m leads
NOTE : Fixings must be ordered separately
042_043_Electrak v3.indd 42 20/12/2012 17:52
43
Intersoc® HDU and VDU moduleshorizontal and vertical desktop units
picto loupe-65765j.eps
Dimensions and technical information (p. 44-45)
Pack Cat.Nos. 16Averticaldesktopunits(VDU)
Allunitsaresuppliedwithsocketsangledat45ºWheredataisoffered,unitscomecompletewith3mdataleads&RJ45plugs
1mpowerlead–BS136313Afusedplug
1 VA1452AA 2socketsindividuallyfusedat5A 1 VA1452AB 2socketsindividuallyfusedat5A+1xRJ45
CAT5edataoutlet 1 VA1452AC 2socketsindividuallyfusedat5A+2xRJ45
CAT5edataoutlets 1 VA1453AA 3socketsindividuallyfusedat5A 1 VA1454AA 4socketsindividuallyfusedat5A
3mpowerlead–BS136313Afusedplug
1 VA3452AA 2socketsindividuallyfusedat5A 1 VA3452AB 2socketsindividuallyfusedat5A+1xRJ45
CAT5edataoutlet 1 VA3452AC 2socketsindividuallyfusedat5A+2xRJ45
CAT5edataoutlets 1 VA3453AA 3socketsindividuallyfusedat5A 1 VA3454AA 4socketsindividuallyfusedat5A
1mpowerlead–maleGSTconnector
1 VB1432AA 2socketsindividuallyfusedat3·15A 1 VB1432AB 2socketsindividuallyfusedat3·15A+1x
RJ45CAT5edataoutlet 1 VB1432AC 2socketsindividuallyfusedat3·15A+2x
RJ45CAT5edataoutlets 1 VB1433AA 3socketsindividuallyfusedat3·15A 1 VB1434AA 4socketsindividuallyfusedat3·15A
Fixings
2 V001 Verticaldesktopunitfixingclamp
DesktopunitsofferpoweranddatasolutionswitharangeofmountingoptionstocomplimentyourfurniturearrangementsAllunitsarehousedinanaluminiumextrusionandareavailableineitherhorizontalorverticalorientationAnycombinationofsocketoutletsandotherservicescanbeintegratedintothealuminiumhousingtosuitindividualcustomerrequirementsincludingswitchingofindividualsockets
Pack Cat.Nos. 16Ahorizontaldesktopunits(HDU)
Allunitsaresuppliedwithsocketsangledat90ºWheredataisoffered,unitscomecompletewith3mdataleads&RJ45plugs
1mpowerlead–BS136313Afusedplug
1 HA1952AA 2socketsindividuallyfusedat5A 1 HA1952AB 2socketsindividuallyfusedat5A+1xRJ45
CAT5edataoutlet 1 HA1952AC 2socketsindividuallyfusedat5A+2xRJ45
CAT5edataoutlets 1 HA1953AA 3socketsindividuallyfusedat5A 1 HA1954AA 4socketsindividuallyfusedat5A
3mpowerlead–BS136313Afusedplug
1 HA3952AA 2socketsindividuallyfusedat5A 1 HA3952AB 2socketsindividuallyfusedat5A+1xRJ45
CAT5edataoutlet 1 HA3952AC 2socketsindividuallyfusedat5A+2xRJ45
CAT5edataoutlets 1 HA3953AA 3socketsindividuallyfusedat5A 1 HA3954AA 4socketsindividuallyfusedat5A
1mpowerlead–maleGSTconnector
1 HB1932AA 2socketsindividuallyfusedat3·15A 1 HB1932AB 2socketsindividuallyfusedat3·15A+1x
RJ45CAT5edataoutlet 1 HB1932AC 2socketsindividuallyfusedat3·15A+2x
RJ45CAT5edataoutlets 1 HB1933AA 3socketsindividuallyfusedat3·15A 1 HB1934AA 4socketsindividuallyfusedat3·15A
Fixings
2 H001 Horizontaldesktopunitfixingclamp
10 H002 Desktopadhesivestrip
Verticalon-deskunit
Horizontalon-deskunit
Anycombinationofsocketandserviceoutletscanbeconfiguredonrequest(egUSB,IBM,Co-axial,SGVA,RJ45etc.)contactuson+44(0)8456006266
042_043_Electrak v3.indd 43 20/12/2012 18:48
Intersoc-RTM under-desk and Intersoc® desktop modulestechnical information
44
n Under-desk dimensions (mm)23 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
276·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
12 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
272·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
3 socket module
214·5
End view
37·9
60
23 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
276·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
12 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
272·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
3 socket module
214·5
End view
37·9
60
n Desktop range dimensions (mm)
2 socket unit
40
100
40
100
Horizontal
40
100
40
100
Vertical
40
100
40
100
23 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
276·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
23 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
276·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
23 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
276·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
2 socket and 1 RJ45 unit
40
100
40
100
293
2 socket and 2 RJ45 unit
40
100
40
100
348
3 socket unit
40
100
40
100
293
4 socket unit
40
100
40
100
368
218
All dimensions (mm) are nominal
12 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
272·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
3 socket module
214·5
End view
37·9
60
12 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
272·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
3 socket module
214·5
End view
37·9
60
12 50
75 110·5
67
Blank end cap
GST interconnectmale
Rewirable interconnectmale
GST interconnectfemale
Rewirable interconnectfemale
411·5
4 socket in-feed module
4 socket module
272·5
2 socket in-feed module
291·5
60
2 socket module
156·5
60
End view
32
60
MCB, RCD protection module
174·5
60
Protection module
115·5
60
50 77·5
Interconnection
3 socket module
214·5
End view
37·9
60
Fixed –end view
Rotatable –end view
(1)
(1) 84·5 mm depth
Compact and GST feed unit Feed unit
(1) (1) (1)
(1) Dimensions only apply to BS sockets and not the international range
044_047_Electrak v2.indd 44 20/12/2012 18:50
45
n Under-desk testing and accreditation n Under-desk and desktop British StandardsBS 6396 : 2008 Electrical Systems in Office Furniture and Educational Furniture Specification
BS 7671 : 2008 incorporating amendment No. 1 : 2011. Requirements for Electrical Installation (IET Wiring Regulations 17th Edition)
Electricity at Work Regulations 1989
Health & Safety Legislation
Below is a brief outline of the main criteria within the standards :
BS 6396 : 2008 was published with regard to the use of electrical equipment within general office and educational furniture. This standard sets out in its scope the use and testing of electrical socket outlets and associated wiring when used together with a 13 A BS 1363 fused plug for mains supply and makes provision for the routing of cables through furniture
For compliance with this standard, socket outlet configurations of up to 4 outlets should be individually fused at 5 A and up to 6 outlets individually fused at 3·15 A
A note on individual socket fusing – BS 6396 Compliance :
The standard requires individual socket fusing (as per the table below)
Meets the requirements of BS 7671 : 2008 (2011) (17th Edition) The Health and Safety Executive states that installations which conform to the standards laid down in BS 7671 : 2008 (2011) are regarded by the HSE as likely to achieve conformity with the relevant parts of the Electricity at Work Regulations 1989
Special note should be taken of regulation 543·7 within BS 7671 : 2008 - Earthing requirements for the installation of equipment having high protective conductor currents
Regulation 543·7 has particular importance when there is a requirement for a quantity of information technology equipment being supplied from a final circuit in a location where the sum of their protective currents exceeds 10 mA in normal use. Due to current in the protective conductor arising from the use of IT equipment, there is a requirement to provide mechanically protected 4 mm2 conductor (543·7·1·103 (ii)). Intersoc achieves this when wired in accordance with the installation sheets by providing mechanically protected 5 mm2 protective conductors within the product
Electrical test data
Rated current up to 32 A Rated voltage 250 V ~ Frequency 50/60 Hz
Volt dropLive and neutral
2 socket module 1·5 m V/A 4 socket module 3·0 m V/A Protection module 4·0 m V/A (depending on device)
In-feeds :
16 A 4·0 m V/A
+1·5 mm2 29 m V/A/m
32 A 2·0 m V/A
+4 mm2 11 m V/A/m
Interconnections :
16 A/32 A 2·0 m V/A
+1·5 mm2 29 m V/A/m
+4 mm2 11 m V/A/m
Earth fault loop impedance
2 socket module 1·5 mΩ4 socket module 3·0 mΩProtection module 4·0 mΩ (depending on device)
In-feeds :
16 A 2·0 mΩ
+1·5 mm2 29 mΩ/m
32 A 2·0 mΩ
+4 mm2 11 mΩ/m
Interconnections :
16 A/32 A 4·0 m V/A
+1·5 mm2 29 mΩ/m
+4 mm2 11 mΩ/m
Mechanical data
Number of conductors 3
Busbar conductor cross-sectional area 5 mm2
16 A rewirable in-feed terminal capacity 10 mm2
32 A rewirable in-feed terminal capacity 10 mm2
Under desk :
Module housing Heat resistant ABS
Socket outlets polycarbonate
Busbars high conductivity copper CW004A (C101)
Other metalwork phosphor bronze CW451K (PB102), CW452K (PB103)
brass CW507L (CZ107), CW508L (CZ108)
high conductivity copper CW004A (C101)(1)
On desk :
Module housing aluminium
Module fascia flame retardant ABS
Socket outlets polycarbonate
End caps flame retardant ABS
Total number of sockets
2, 3 or 4 sockets 5 or 6 sockets
Individually fused at
5 A 3·15 A
Conforms to BS 5733 : 1995 incorporating amendment No. 1 and corrigendum No. 1Conforms to the relevant parts of BS 1363 part 2 Manufactured within an approved ISO 9001 : 2008 facility Quality assurance certificate No. 2029
Material specification
Conductor resistance at 20°C Fixed Rotatable
(1) European grades with nearest British Standard shown in brackets
2 socket module 0·8 mΩ 0·9 mΩ4 socket module 1·6 mΩ 1·7 mΩ
044_047_Electrak v2.indd 45 20/12/2012 18:11
Intersoc-RTM under-desk modulesinstallation and configuration
46
n Installation
Module self-locking latch
Underside ofmodules shown
Slide green latch Blank end cap
2 socket module
16 A 4 socket in-feed module
To connect and disconnect Intersoc modules
1.Connection/disconnectiontobemadebyacompetentperson 2.Beforeconnectingmodulesensuretheyarethecorrectwayupandinline 3.Pushmodulestogetheroneatatime 4.Modulesself-lockwhenfullypushedtogether 5.Todisconnectmodulesslidegreenlatchtounlockmoduleandpullapart 6.Alwaysendmodulerunwithblankendcaporinterconnect
To fix modules to surface 1.Insertthroughallfixingholesno.8pozi-panscrewor
M4bolttorequiredlength 2.Tightenscrew/boltdowntomountingsurface
044_047_Electrak v2.indd 46 20/12/2012 18:12
47
1.Selectthetypeofdistributionsystem-standard,orlownoise/cleanearth 2.Selectthemeansofpoweringthesystem-cableorpowertracktap-off 3.Selectthetypeofin-feedmoduletomatchthecablecapacity-16Aor32A 4.Selectthemeansofprotection 5.Selectthenumberofsocketmodulesfromthe2,3or4gangrange(individuallyfusedorunfused) 6.Selectfixedorrotatablesockets 7.Selecttheinterconnectionunitsifrequired 8.Finishsystemwiththeendcap (Allmodulespushfitandlocktogetheron-siteorcanbefactoryassembledtocustomerrequirement)
n Product configuration
1 2
llllllllllllllllllllllllllllllllllllllllllllllllllllll lllllllllllllllll
llllllllll
llllllllllllllllll llllllllllllliiiii
ilRaisedfloor Floorgrommet
In-feedandpowermodulepushtogetherandlockwithcamlocklever
Tap-offandin-feedpulledthroughfloorgrommetaftertestingandwhenrequired
32Ain-feedconnectedtotap-offandleftunderflooruntilrequired
Underfloorpowertrack
Tap-off
044_047_Electrak v2.indd 47 20/12/2012 18:12
Elec
trak
und
erflo
or to
wor
ksta
tion
syst
ems
guid
e 01
/201
3. 5
KHead office (UK and Ireland):Legrand Electric Limitedgreat King Street North, Birmingham, B19 2LFTel: 0870 608 9000 Fax: 0870 608 9004Website: www.legrand.co.uk
The Legrand logo is a registered trademark of the Legrand group of companies.
Distributor:
This document is printed on sustainably sourced paper. Please recycle.
Contact details
Quotations and Technical Support: The Power Distribution Division of Legrand Electric Ltd. Great King Street North, Birmingham, B19 2LF
Tel: +44 (0) 845 600 6266 Fax: +44 (0) 845 600 6760
E-mail: [email protected]
Customer Services: The Power Distribution Division of Legrand Electric Ltd. No. 1 Industrial Estate Medomsley Road, Consett, County Durham, DH8 6SR