12
Echoflex Installation Guide Elaho Occupancy Sensor Main Office n Squamish, BC, Canada n Toll Free +888 324 6359 n Phone +778 733 0111 n Fax +604 815 0078 Email [email protected] n Web echoflexsolutions.com n Product information and specifications subject to change. © 2018 Echoflex Solutions, Inc. n Echoflex intends this document to be provided in its entirety. 8181M2181 n Revision A n Released 2018-09 Overview The Elaho Occupancy Sensor is a ceiling mounted sensor that utilizes passive infrared (PIR) technology, providing reliable vacancy and occupancy detection for lighting control. The sensor allows for both auto on and auto off functionality along with any commands supplied from local stations. The Occupancy Sensor provides 360 degree coverage of the installed location and is available in three models: E-OCC-SR- Occupancy Sensor with small room lens covers 450 sq. ft. at 8 ft. or 800 sq. ft. at 10 ft. E-OCC - Occupancy Sensor with standard room lens covers 1,800 sq. ft. at 8 ft. or 3,000 sq. ft. at 10 ft. E-OCC-HC - Occupancy Sensor with high ceiling lens covers 300 sq. ft. at 10 ft or 7,000 sq. ft. at 40 ft. Each sensor is available in white or black finish. Lens masks are provided to allow customized occupancy detection fields as required by each installation. Custom Configuration This document guides you through the installation and local configuration of the Elaho Occupancy Sensor. For more detailed information about custom configuration options available for the Occupancy Sensor using ElahoAccess, reference the ElahoAccess Mobile App integrated help system. To use the configuration settings applied using ElahoAccess, DIP switch 2 must be enabled. Reference DIP Switch Settings on page 7.

Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

  • Upload
    others

  • View
    24

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideElaho Occupancy Sensor

Main Off ice n Squamish, BC, Canada n Toll Free +888 324 6359 n Phone +778 733 0111 n Fax +604 815 0078Email [email protected] nWeb echoflexsolutions.com n Product information and specifications subject to change.© 2018 Echoflex Solutions, Inc. n Echoflex intends this document to be provided in its entirety.8181M2181 n Revision A n Released 2018-09

OverviewThe Elaho Occupancy Sensor is a ceiling mounted sensor that utilizes passiveinfrared (PIR) technology, providing reliable vacancy and occupancy detectionfor lighting control. The sensor allows for both auto on and auto offfunctionality along with any commands supplied from local stations.

The Occupancy Sensor provides 360 degree coverage of the installed locationand is available in three models:

• E-OCC-SR- Occupancy Sensor with small roomlens covers 450 sq. ft. at 8 ft. or 800 sq. ft. at 10 ft.

• E-OCC - Occupancy Sensor with standard roomlens covers 1,800 sq. ft. at 8 ft. or3,000 sq. ft. at 10 ft.

• E-OCC-HC - Occupancy Sensor with high ceilinglens covers 300 sq. ft. at 10 ft or7,000 sq. ft. at 40 ft.

Each sensor is available in white or black finish. Lens masks are provided toallow customized occupancy detection fields as required by each installation.

Custom ConfigurationThis document guides you through the installation and local configuration ofthe Elaho Occupancy Sensor. For more detailed information about customconfiguration options available for the Occupancy Sensor using ElahoAccess,reference the ElahoAccess Mobile App integrated help system.

To use the configuration settings applied using ElahoAccess, DIP switch 2must be enabled. Reference DIP Switch Settings on page 7.

Page 2: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

Wire SpecificationSensors connect to the EchoConnect® communication bus. EchoConnect is abidirectional protocol that uses one pair of wires (data + and data -) for bothdata and power. Echoflex recommends using Belden 8471 (or approved equal)Class 2 wire. The total combined length of an EchoConnect wire run (usingBelden 8471, or equal) may not exceed 1,640 feet (500 m).

Note: All control wiring should be installed and terminated by aqualified installer and should follow standard wiring installation practices.

Leave approximately 8" (20 cm) of wiring in the back box for connectionand to allow slack for future service needs.

Note: Echoflex requires that all Elaho stations and devices be groundedfor ESD protection. Pull an additional 14 AWG (2.5 mm2) wire forgrounding when control wires are not installed in grounded metal conduit.

Note: When using Category 5 (or equivalent) cable on the EchoConnectcommunication bus, please note the following:

• Cat5 wiring must be terminated using EchoConnect Cat5Termination Kit and must be installed using a bus topology.Refer to the installation guide that is provided with the Cat5Termination Kit (8186A1207) for information to terminateCat5 wiring.

• Not all topologies are supported using Cat5; careful planningis required to ensure the proper termination kits are availableand the wire is pulled appropriately.

Installation EnvironmentOccupancy Sensors are intended for installation to a finished ceiling surface,ceiling tile mounted, attached to a round fixture junction box or single-gangRACO switch box.

The sensor operates in ambient temperatures of 0° C to 40° C, with amaximum of 90% non-condensing humidity.

Echoflex recommends paying special attention to the installationenvironment:

• The sensor must have an unobstructed view of the room. Do notmount behind or near tall cabinets, shelves, hanging light fixtures, etc.

• Do not install the sensor within eight feet from an HVAC airflowduct/vent.

Elaho Occupancy Sensor Page 2 of 12 Echoflex Solutions, Inc.

Page 3: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

• Install the sensor where it cannot easily sense movement in areasoutside of the intended space, such as hallways, glass partitions, oradjacent rooms. If the installation location cannot avoid theseconditions, portions of the lens can be masked to block the sensorview of these undesired areas. Reference Lens Masking on page 10.

Parts and SuppliesThe following parts and supplies are included with the Occupancy Sensorordered:

• Soft ceiling tile adaptor• 2 each screws, 6-32 x 3/4” and 1 3/4”• EchoConnect and ESD ground wire pigtails• 3 lens masks

Note: Follow all local code requirements for terminating wire.

Use appropriately sized wire nuts (not provided) to secure eachtermination.

The EchoConnect pigtail is only required when the sensor is installed inseries with other stations or sensors. If you are not continuing the datarun, direct termination on the control board is recommended.

InstallationThe Occupancy Sensor is provided with a twist-lock mounting plate that canbe mounted to a junction box, finished ceiling, or soft ceiling tile. Determinethe installation method and follow the detailed instructions provided:

• Junction Box Installation on the next page• Soft Ceiling Tile Installation on page 5• Lens Masking on page 10

Elaho Occupancy Sensor Page 3 of 12 Echoflex Solutions, Inc.

Page 4: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

Junction Box Installation

Terminate

wires here

1. Pull the Belden 8471 (orequivalent wire) and the14 AWG (2.5 mm2 ground wireto the junction box.

2. I f you are instal l ing thesensor in series with othersensors or stations(continuing the data run), usethe provided EchoConnectpigtail, ESD ground wirepigtail. Termination connectorsare not provided. If you arenot continuing the data run,proceed to Step 3.

a. Strip each wire to the appropriate length, depending on the wirenut or other termination used (wire nuts are not provided).

b. Twist the data - (typically black) EchoConnect wire, the blacklead from the EchoConnect pigtail, and any continuingEchoConnect (typically black) wire together and secure with awire nut.

c. Repeat the above steps for the data + (typically white)EchoConnect wire and the ESD ground wire.

3. Orient the smooth side of the mounting plate to the junction box andpull the EchoConnect wires (or terminated pigtail) from the junctionbox through the provided holes near the center of the mounting plate.

4. Secure the mounting plate to the junction box using the screwsprovided (both short and long screws are provided for convenience).

5. Strip each wire 5/16” (8 mm) and terminate the EchoConnect (whiteand black wires) and the ground wire (green/yellow) to theEchoConnect terminal block located on the sensor controller. Torqueeach termination to 3.1-3.5 in-lb.

a. Terminate the white incoming wire to the data + terminal.b. Terminate the black incoming wire to the data - terminal.c. Terminate the green/yellow (ground) wire to the ground terminal.

6. Attach the sensor to the mounting plate by aligning the tabs on thesensor with the slots on the mounting plate, then twist clockwise untilthe two are secured into place.

Elaho Occupancy Sensor Page 4 of 12 Echoflex Solutions, Inc.

Page 5: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

Soft Ceiling Tile Installation

Poke the adapter through the ceiling tile, then bend

it over for a secure fit.

EchoConnect pigtail

and connectors

(optional use)

Terminate

wires here

1. Pull the Belden 8471 (or equivalent) and 14 AWG (2.5 mm2) groundwire to the installation location.

2. I f you are instal l ing the sensor in series with other sensors orstations (continuing the data run), use the provided EchoConnectpigtail, ESD ground pigtail and connectors (not provided) to make theterminations. If you are not continuing the data run, proceed toStep 3.

a. Strip each wire to the appropriate length, depending on thewire nut or other termination used.

b. Twist the data - (typically black) EchoConnect wire, the blacklead from the EchoConnect pigtail, and any continuingEchoConnect (typically black) wire together and secure with thewire nut.

c. Repeat the above steps for the data + (typically white)EchoConnect wire, and for the ESD ground wires.

3. Create a hole for wire pass-through in the ceiling tile by pokingthrough the center hole or oblong hole of the mounting plate, then pullthe wires through.

4. Orient the smooth side of the mounting plate to the finished side ofthe ceiling tile and align and insert the soft ceiling tile adapter throughthe holes provided near the center of the mounting plate. Referencethe graphic above.

5. Poke the tines of the adapter through the ceiling tile, then bend eachtine over in opposite directions for a secure fit on the unfinished sideof the ceiling tile.

Elaho Occupancy Sensor Page 5 of 12 Echoflex Solutions, Inc.

Page 6: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

6. Strip each wire 5/16” (8 mm) and terminate the EchoConnect (whiteand black wires) and ground wire (green/yellow) to the EchoConnectterminal block located on the sensor control board. Torque eachtermination to 3.1-3.5 in-lb.

a. Terminate the white incoming wire to the data + terminal.b. Terminate the black incoming wire to the data - terminal.c. Terminate the green/yellow (ground) wire to the labeled ground

terminal.

Sensor ConfigurationThe Occupancy Sensor participates in an Elaho system using the configuredSpace and Address, which are selectable using the rotary switches on the rearpanel of the sensor.

Additional DIP switches and the [MODE] button, also located on the rearpanel, set the sensor functionality and the occupancy detected action.

Set Space and AddressTwo rotary switches on the rear panel of the controller provide for assignmentof the sensor Space and Address. By default, these switches are set to Space1, Address 1. Commands are shared by all devices within a given space.1. Set the Space rotary switch to the desired number (1 through 16) for

the space you want the sensor to control.2. Set the Address rotary switch to desired address (1 through 16) for the

sensor identification in the selected space.

Note: Do not duplicate a device Address within the same Space.

Elaho Occupancy Sensor Page 6 of 12 Echoflex Solutions, Inc.

Page 7: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

DIP Switch SettingsDIP switches on the rear panel of the OccupancySensor provide for additional configuration optionsincluding Use Custom Config, Vacancy Timeout,Enable/Disable PIR detection LED, and the ability torestore the sensor to its factory defaults.

DIP Switch 2DIP switch 2 enables “Custom Config” whichinstructs the sensor to use settings that are configured using the ElahoAccessMobile App. This setting is Off by default.

• When “Custom Config” is set to Off, the default position, local DIPswitch settings for Vacancy Timeout and Enable PIR LED are used.Sensor actions can be adjusted using the program [MODE] button.

• When “Custom Config” is set to On, all other local DIP switch settingsare ignored. Instead, the settings made by the ElahoAccess MobileApp for Vacancy Timeout, Enable PIR LED, and Occupancy actions areused.

DIP Switch 3&4DIP switch 3 & 4 set the “Vacancy Timeout” to 5, 15, 30 minutes, or Auto.See Vacancy Timeout on page 9.

• 5 min = Switches 3 and 4 are Off.• 15 min = Switch 3 is Off and Switch 4 is On (default).• 30 = Switch 3 is On and Switch 4 is Off.• Auto = Both switches are On. See Auto Vacancy Timeout on page 9.

DIP Switch 5DIP switch 5 enables/disables the red PIR detection LED. When the switch isOff, the PIR LED disables unless it is in Walk Test mode. When set to On, thered PIR LED will illuminate the sensor lens when movement is detected. Thedefault position is On.

DIP Switch 8DIP switch 8 provides a “Restore Defaults at Boot” function. The factorydefaults are restored by setting this DIP switch On, and cycling power to thestation. The default position is Off.

Note: DIP switches 1, 6, and 7 are not currently used and are reservedfor future development. Leave them at their default Off setting.

Elaho Occupancy Sensor Page 7 of 12 Echoflex Solutions, Inc.

Page 8: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

Power Up and TestPower Up

All EchoConnect terminations in the system must be made before applyingpower to the system and sensor. When the sensor is powered up, the PIR LEDilluminates for one minute for calibration and warm-up, and then returns tonormal operation.

ConfigurationSensor configuration for Basic config mode (DIP switch 2 set to Off) can beaccomplished locally on the sensor using the other available DIP switches,[MODE] button and LED, and the Auxiliary button. See Preset below, andVacancy Timeout on the facing page for local configuration instructions.

PresetThe [MODE] button located on the rear panel of the sensor places the sensorinto “Program Mode.” Both the [MODE] button and related Mode LED, aswell as the Auxiliary “A” button are used for configuration of the occupancyaction.

• The “A” button andMode LED are used to program the preset that isactivated with an occupancy state change. When programming, theMode LED blinks to indicate the current preset number used.

• When vacancy is detected, the sensor will activate a Space Offcommand. When functionality other than Space Off is required, placethe sensor in Custom config mode (DIP switch 2 On). Customization ofthe Occupancy Sensor and all related actions are configured using theElahoAccess Mobile App.

Note: For more detailed information about custom configurationoptions available for the Occupancy Sensor using ElahoAccess, referencethe ElahoAccess Mobile App integrated help system.

Auxiliary

button

Walk Test

button

MODEbutton

MODELED

Elaho Occupancy Sensor Page 8 of 12 Echoflex Solutions, Inc.

Page 9: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

1. Press and hold the [MODE] button for 3 seconds to enter “ProgramMode.” Program Mode allows adjustment of the preset that activatesfor occupancy detection. By default, this is Preset 1. The “A” button,located on the front of the sensor, blinks to indicate the preset numbercontrolled by the occupancy action.

2. Press and release the “A” button the number of times to set the newpreset. (For example: press and release ten times to set Preset 10.)The “A” button blinks the number of the preset used for theoccupancy event action.

3. Press and release the [MODE] button to save the current setting. TheMode/Sensor count LED turns off and the “A” button again blinks outthe saved preset index.

4. Attach the sensor to the mounting plate by aligning the tabs on thesensor with the slots on the mounting plate, then twist clockwise untilthe two are locked into place.

Vacancy TimeoutVacancy timeout is the amount of time the sensor waits to take action afterno movement is detected. By default, vacancy timeout is set to 15 minutes(indicated by DIP switch 3 set to Off and 4 set to On). When the vacancytimeout ends, the grace period begins.

When the sensor detects vacancy, the vacancy timeout period begins. If thesensor does not detect occupancy again during the vacancy timeout period,the lights turn off and a 30 second grace period begins.

Grace PeriodThe sensor features a 30 second grace period after a vacancy timeout occursto help prevent false vacancy detection. During this grace period, if the sensordetects occupancy, it will restore the previous lighting condition.

Auto Vacancy TimeoutThe “Auto” vacancy timeout setting varies vacancy the timeout between5 and 30 minutes depending on how often it identifies an occupancy triggerafter a vacancy timeout occurs (during the grace period).

Elaho Occupancy Sensor Page 9 of 12 Echoflex Solutions, Inc.

Page 10: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

Lens MaskingLens masks are provided in the packaging for your convenience, used to blocka section of the lens from detecting occupancy.

1. As needed, trim the lens mask tofit the desired area to be blocked.

2. Gently press down on the sensorlens, which will give only slightly,and insert the lens mask.

3. Rotate the lens mask around thedome to block the required areafrom sensing.

PIR DetectionThe PIR detection automatically adjusts its sensitivity to eliminate nuisancetripping. When the sensor powers on, the red PIR LED illuminates forapproximately 60 seconds to identify “Power Up” state. Sensor configurationis not allowed. During this time, no events are triggered.

TestOccupancy Sensors offer a Walk Test mode which shortens the vacancy timerto ten seconds, allowing for simple and quick verification of the sensorscoverage and range in the installed space.

Auxiliary

button

Walk Test

button

Walk Test mode automatically exists and thesensor returns to normal operation after fiveminutes and can be manually terminatedearly by pressing the [Walk Test] button.

Elaho Occupancy Sensor Page 10 of 12 Echoflex Solutions, Inc.

Page 11: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

Enable Walk Test Mode1. Prepare the site for configuration.

a. Make certain the sensor and lighting loads are powered andconnected for control by the Elaho controller.

b. You will need direct access to the Occupancy Sensor in order toplace it into Walk Test mode.

2. Press the [Walk Test] button on the front of the sensor to enable theWalk Test feature at the sensor. A green LED will begin to flash,indicatingWalk Test is enabled and the vacancy/no vacancy occupancytimer will be shortened to 10 seconds.

3. Move throughout the space including corners and areas that mayspecifically be obscured from line of sight to the sensor. Each time thesensor detects movement, the lens will illuminate red.

4. Adjust the lens masking, if installed, blocking certain areas of theinstalled space from sensor detection. See Lens Masking on theprevious page.

5. Walk Test mode will automatically exit after five minutes from thetime it was enabled. To manually exit the Walk Test mode, presseither of the buttons on the sensor.

Elaho Occupancy Sensor Page 11 of 12 Echoflex Solutions, Inc.

Page 12: Elaho Occupancy Sensor Installation Guide · Elaho Occupancy Sensor Installation Guide Subject: Elaho Occupancy Sensor Created Date: 9/20/2018 10:23:58 AM

Echoflex Installation GuideOccupancy Sensor

High Ceiling side view

03.0m10ft

3.0m10ft

6.1m20ft

6.1m20ft

9.1m30ft

9.1m30ft

12.2m40ft

12.2m40ft

0

12.2m40ft

9.1m30ft

6.1m20ft

Small Room side view0

01.5m5ft

1.5m5ft

3.0m10ft

3.0m10ft

4.6m15ft

4.6m15ft

6.1m20ft

6.1m20ft

8ft2.4m

10ft3.0m

12ft3.7m

Large Room side view

0

8ft2.4m

10ft3.0m12ft3.7m

03.0m

10ft

3.0m

10ft

6.1m

20ft

6.1m

20ft

9.1m

30ft

9.1m

30ft

12.2m

40ft

12.2m

40ft

Elaho Occupancy Sensor Page 12 of 12 Echoflex Solutions, Inc.