User’sManual

Yokogawa Electric Corporation

EJX110B, EJX310B and EJX430BDifferential Pressure andPressure Transmitters

IM 01C27B01-01EN

IM 01C27B01-01EN15th Edition

Page 2: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

Toc-1

IM 01C27B01-01EN

Contents1. Introduction ............................................................................................... 1-1

1.1 Safe Use of This Product .................................................................................1-21.2 Radio Wave ........................................................................................................1-31.3 Warranty .............................................................................................................1-41.4 Trademarks ........................................................................................................1-41.5 Control of Pollution Caused by the Product ..................................................1-5

2. Handling Cautions .................................................................................... 2-12.1 Model and Specifications Check .....................................................................2-12.2 Unpacking ..........................................................................................................2-12.3 Storage ...............................................................................................................2-22.4 Selecting the Installation Location ................................................................2-22.5 Pressure Connection ........................................................................................2-32.6 Restrictions on Use of Radio Transceivers ...................................................2-32.7 Insulation Resistance and Dielectric Strength Test ......................................2-32.8 Installation of an Explosion-Protected Instrument .......................................2-4

2.8.1 FM Approval .......................................................................................2-52.8.2 CSACertification ................................................................................2-62.8.3 ATEXCertification ..............................................................................2-62.8.4 IECExCertification .............................................................................2-8

2.9 EMC Conformity Standards .............................................................................2-82.10 Pressure Equipment Directive (PED) .............................................................2-92.11 Low Voltage Directive .......................................................................................2-92.12 Regulatory Compliance for Radio and Telecommunication ......................2-10

2.12.1 RadioEquipmentDirective(RE) ......................................................2-102.12.2 FCCcompliance ..............................................................................2-102.12.3 IndustryCanada(IC)compliance ....................................................2-10

2.13 RoHS ................................................................................................................. 2-11

3. Component Names .................................................................................. 3-14. Installation ................................................................................................. 4-1

4.1 Precautions .......................................................................................................4-14.2 Mounting ...........................................................................................................4-14.3 Changing the Process Connection .................................................................4-3

EJX110B, EJX310B and EJX430BDifferential Pressure and Pressure Transmitters

IM 01C27B01-01EN 15th Edition

15thEdition:July2019(YK)AllRightsReserved,Copyright©2009,YokogawaElectricCorporation

Page 3: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

Toc-2

IM 01C27B01-01EN

4.4 Swapping the High/Low-pressure Side Connection .....................................4-34.4.1 RotatingPressure-detectorSection180° ......................................... 4-34.4.2 UsingtheConfigurationTool ..............................................................4-4

4.5 Rotating Transmitter Section ...........................................................................4-44.6 Changing the Direction of Integral Indicator .................................................4-54.7 Changing the direction of the antenna ...........................................................4-5

5. Installing Impulse Piping ......................................................................... 5-15.1 Impulse Piping Installation Precautions ........................................................5-1

5.1.1 ConnectingImpulsePipingtoaTransmitter ...................................... 5-15.1.2 Routing the Impulse Piping ................................................................5-3

5.2 Impulse Piping Connection Examples ...........................................................5-4

6. Wiring ......................................................................................................... 6-16.1 Mounting Antenna and Wiring .........................................................................6-1

6.1.1 Mounting the antenna ........................................................................6-16.1.2 Mounting External Antenna and Wiring Antenna Extension Cable ... 6-26.1.2.1 Mounting of External Antenna ............................................................6-26.1.2.2 Wiring of Antenna Extension Cable ................................................... 6-26.1.2.3 MountingofSurgeProtectiveDeviceandWiring .............................. 6-4

6.2 Grounding ..........................................................................................................6-46.3 Power Supply Wiring Precautions ..................................................................6-56.4 Selecting the Wiring Materials .........................................................................6-56.5 Connection of the External Power Source Terminal .....................................6-5

7. Operation ................................................................................................... 7-17.1 Preparation for Starting Operation .................................................................7-17.2 Zero Point Adjustment .....................................................................................7-27.3 Starting Operation ............................................................................................7-37.4 Connecting to the Field Wireless Network .....................................................7-37.5 Shutting Down the Transmitter .......................................................................7-57.6 Venting or Draining Transmitter Pressure-detector Section .......................7-6

7.6.1 Draining Condensate .........................................................................7-67.6.2 Venting Gas........................................................................................7-6

8. Setting Parameters ................................................................................... 8-18.1 Environment for parameter setting .................................................................8-18.2 Preparing Software ...........................................................................................8-1

8.2.1 SoftwaresfortheFieldWirelessConfigurationToolandtheDeviceConfigurationTool ..............................................................................8-1

8.2.2 SoftwareDownload ............................................................................8-18.3 Setting Parameters ...........................................................................................8-1

8.3.1 ParameterUsageandSelection ........................................................8-18.3.2 FunctionBlockandMenuTree ..........................................................8-28.3.3 ParametersforWirelessCommunication ........................................8-108.3.4 TagandDeviceInformation .............................................................8-10

Page 4: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

Toc-3

IM 01C27B01-01EN

8.3.5 Unit ................................................................................................... 8-118.3.6 Range Change ................................................................................. 8-118.3.7 Output Mode .................................................................................... 8-118.3.8 OutputSignalLowCutModeSetup ................................................ 8-118.3.9 ImpulseLineConnectionOrientationSetup ....................................8-128.3.10 IntegralIndicatorDisplayMode .......................................................8-128.3.11 IntegralIndicatorScaleSetup ..........................................................8-128.3.12 Unit for Displayed Temperature .......................................................8-128.3.13 UnitforDisplayedStaticPressure ...................................................8-138.3.14 Zero Point Adjustment and Span Adjustment ..................................8-138.3.15 SoftwareWriteProtect .....................................................................8-158.3.16 SwitchingtoDeepSleepMode ........................................................8-168.3.17 SwitchingtoSilenceMode ...............................................................8-16

8.4 Self-Diagnostics ..............................................................................................8-178.4.1 IdentifyProblemsbyUsingtheDeviceConfigurationTool ..............8-178.4.2 Alert Report ......................................................................................8-188.4.3 CheckingwithIntegralIndicator .......................................................8-20

9. Maintenance .............................................................................................. 9-19.1 Overview ............................................................................................................9-19.2 Calibration Instruments Selection ..................................................................9-19.3 Calibration .........................................................................................................9-19.4 Disassembly and Reassembly ........................................................................9-3

9.4.1 ReplacingtheIntegralIndicator .........................................................9-39.4.2 ReplacingtheRFAssembly ...............................................................9-49.4.3 ReplacingtheCPUAssembly ............................................................9-49.4.4 CleaningandReplacingtheCapsuleAssembly ............................... 9-59.4.5 ReplacingtheProcessConnectorGaskets ....................................... 9-69.4.6 ReplacingtheBatteryPack ...............................................................9-69.4.7 ReplacingtheBatteries ......................................................................9-79.4.8 Handling Batteries ..............................................................................9-79.4.9 ReplacingthePowerSupplyModule ................................................. 9-8

9.5 Troubleshooting ................................................................................................9-89.5.1 BasicTroubleshooting .......................................................................9-99.5.2 TroubleshootingFlowcharts ...............................................................9-99.5.3 Errors and Countermeasures .......................................................... 9-11

10. Parameter Summary .............................................................................. 10-111. General Specifications .......................................................................... 11-1

11.1 Standard Specifications ................................................................................. 11-111.2 Model and Suffix Codes ................................................................................. 11-411.3 Optional Specifications ................................................................................. 11-911.4 Dimensions .................................................................................................... 11-12

Revision Information

Page 5: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<1. Introduction> 1-1

IM 01C27B01-01EN

1. IntroductionThankyouforpurchasingtheDPharpEJXDifferentialPressureandpressuretransmitter.

YourEJXPressureTransmitterwaspreciselycalibratedatthefactorybeforeshipment.Toensurebothsafetyandefficiency,pleasereadthismanualcarefullybeforeyouoperatetheinstrument.

NOTEThismanualcoverstheEJX110Bdifferentialpressure transmitter, EJX430B gauge pressure transmitter and EJX310B absolute pressure transmitteranddescribeshowtouseforthedetachableantennatypetransmitters(Amplifierhousingcode8or9).Unlessotherwisestated,theillustrationsinthismanualareoftheEJX110Bdifferentialpressuretransmitter withadetachableantennatype. Usersoftheothermodelsandspecificationsshouldbearinmindthatcertainfeaturesoftheirinstrumentwilldifferfromthoseshownintheillustrations of the EJX110B.

MODEL SUFFIXEJX110B

--8*--9*EJX310B

EJX430B

Regarding This Manual

• This manual should be provided to the end user.

• Thismanualandtheidentificationtagattachedonpackingboxareessentialpartsoftheproduct;keeptheminasafeplaceforfuturereference.

• Thecontentsofthismanualaresubjecttochangewithoutpriornotice.

• All rights reserved. No part of this manual may bereproducedinanyformwithoutYokogawa’swrittenpermission.

• Yokogawamakesnowarrantyofanykindwithregardtothismanual,including,butnotlimitedto,impliedwarrantyofmerchantabilityandfitnessforaparticularpurpose.

• If any question arises or errors are found, or if any information is missing from this manual, pleaseinformthenearestYokogawasalesoffice.

• Thespecificationscoveredbythismanualarelimited to those for the standard type under the specifiedmodelnumberbreak-downanddonotcovercustom-madeinstruments.Whenproductswhosesuffixcodeoroptionalcodescontaincode“Z”andanexclusivedocumentisattached,pleasereaditalongwiththismanual.

• Pleasenotethatchangesinthespecifications,construction,orcomponentpartsoftheinstrumentmaynotimmediatelybereflectedinthismanualatthetimeofchange,providedthatpostponementofrevisionswillnotcausedifficultytotheuserfromafunctionalorperformancestandpoint.

• Yokogawaassumesnoresponsibilitiesforthisproductexceptasstatedinthewarranty.

• Ifthecustomeroranythirdpartyisharmedbytheuseofthisproduct,Yokogawaassumesnoresponsibilityforanysuchharmowingtoanydefectsintheproductwhichwerenotpredictable,orforanyindirectdamages.

• Thefollowingsafetysymbolsareusedinthismanualandontheproduct:

WARNING

Indicatesapotentiallyhazardoussituationwhich,ifnotavoided,couldresultindeathorseriousinjury.

CAUTIONIndicatesapotentiallyhazardoussituationwhich,if not avoided, may result in minor or moderate injuryorphysicaldamage.Itmayalsobeusedtoalertagainstunsafepractices.

Page 6: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<1. Introduction> 1-2

IM 01C27B01-01EN

IMPORTANTIndicatesthatoperatingthehardwareorsoftwarein this manner may damage it or lead to system failure.

NOTEDrawsattentiontoinformationessentialforunderstanding the operation and features.

Functionalgroundingterminal

CautionThissymbolindicatesthattheoperatormustrefertoanexplanationintheuser’smanualinordertoavoidtheriskofinjuryor death of personnel or damage to the instrument.

Notice

NO RIGHTS OR LICENSES, EXPRESS OR IMPLIED,AREGRANTEDTOUSETHIRD-PARTYDEVICES IN COMBINATION WITH THESE PRODUCTSINAWIRELESSMESHNETWORK,ORTOUSETHIRD-PARTYSERVICESTOACCESS, MONITOR OR CONTROL THESE PRODUCTSINAWIRELESSMESHNEWORKVIA THE INTERNET OR ANOTHER EXTERNAL WIDEAREANETWORK.

Patent Marking

Coveredbyoneormoreclaimsofpatents:http://sipcollc.com/patent-list/and http://intusiq.com/patent-list/.

1.1 Safe Use of This Product Thisproductisdesignedtobeusedbyapersonwithspecializedknowledge.Forthesafetyoftheoperatorandtoprotecttheinstrumentandthesystem,pleasebesuretofollowthismanual’ssafetyinstructionswhenhandlingthisinstrument.Iftheseinstructionsarenotheeded,theprotectionprovided by this instrument may be impaired. In thiscase,Yokogawacannotguaranteethattheinstrumentcanbesafelyoperated.Pleasepayspecialattentiontothefollowingpoints:

(a) Installation

• This instrument may only be installed by an engineerortechnicianwhohasanexpertknowledgeofthisdevice.Operatorsarenotallowedtocarryoutinstallationunlesstheymeetthiscondition.

• Withhighprocesstemperatures,caremustbetakennottoburnyourselfbytouchingtheinstrumentoritscasing.

• Neverloosentheprocessconnectornutswhentheinstrumentisinstalledinaprocess.Thiscanleadtoasudden,explosivereleaseofprocessfluids.

• Whendrainingcondensatefromthepressuredetectorsection,takeappropriateprecautionsto prevent the inhalation of harmful vapors and thecontactoftoxicprocessfluidswiththeskinor eyes.

• When removing the instrument from a hazardousprocess,avoidcontactwiththefluidand the interior of the meter.

• Allinstallationshallcomplywithlocalinstallationrequirementsandthelocalelectricalcode.

(b) Wiring

• The instrument must be installed by an engineerortechnicianwhohasanexpertknowledgeofthisinstrument.Operatorsarenotpermittedtocarryoutwiringunlesstheymeetthiscondition.

Page 7: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<1. Introduction> 1-3

IM 01C27B01-01EN

(c) Maintenance

• Pleasecarryoutonlythemaintenanceproceduresdescribedinthismanual.Ifyourequirefurtherassistance,pleasecontactthenearestYokogawaoffice.

• Careshouldbetakentopreventthebuildupofdust or other materials on the display glass and thenameplate.Tocleanthesesurfaces,useasoft,drycloth.

(d) Explosion Protected Type Instrument

• Users of explosion proof instruments should referfirsttosection2.8(InstallationofanExplosionProtectedInstrument)ofthismanual.

• Theuseofthisinstrumentisrestrictedtothosewhohavereceivedappropriatetraininginthedevice.

• Takecarenottocreatesparkswhenaccessingtheinstrumentorperipheraldevicesinahazardouslocation.

• Repairormodificationtothisinstrumentbycustomerwillcausemalfunctionofexplosionprotectfunctionandhazardoussituation.Ifyouneedtorepairormodification,pleasecontactthenearestYokogawaoffice.

(e) Modification

• Yokogawawillnotbeliableformalfunctionsordamageresultingfromanymodificationmadetothisinstrumentbythecustomer.

(f) Product Disposal

• The instrument should be disposed of in accordancewithlocalandnationallegislation/regulations.

(g) Authorized Representative in EEA

• InrelationtotheCEMarking,TheauthorizedrepresentativeforthisproductintheEEA(EuropeanEconomicArea)is:

YokogawaEuropeB.V. Euroweg2,3825HDAmersfoort,

The Netherlands

1.2 Radio Wave

IMPORTANT- Thisinstrumentisequippedwithawireless

modulewhichisdesignatedasacertificationofconstructiontypeasawirelessfacilityfor2.4GHzbandlow-powerdatacommunicationsystemoftheRadioAct.Referto2.12“RegulatoryComplianceforRadioandTelecommunication”fordetail.

- Duetothedesignatedcertificationofconstructiontype,usersmaybesubjecttolegalpunishmentincaseof:- Disassemblingormodifyingthewireless

module or antenna in this instrument- Peelingoffthecertificationlabelattachedtothewirelessmoduleinthisinstrument

- Preventinginterferencewithotherwirelessstations

Theoperatingfrequencybandwidthofthisinstrument may overlap the same range asindustrialdevices,scientificdevices,medicaldevices,microwaveovens,licensedpremisesradiostationsandnon-licensedspecifiedlow-powerradiostationsformobileobjectidentificationsystemsusedinfactoryproductionlines.

Before using this instrument, ensure that neitherapremisesradiostationnorspecifiedlowpowerradiostationformobileobjectidentificationsystemsisinusenearby.

Ifthisinstrumentcausesradiowaveinterferencetoawirelessstationformobileobjectidentificationsystems,promptlychangethefrequencybeingusedorturnoffthesourceofradiowaveemissions.Then,contactaYokogawaofficeregardingcountermeasurestopreventinterference,suchassettinguppartitions.

Page 8: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<1. Introduction> 1-4

IM 01C27B01-01EN

1.3 Warranty• Thewarrantyshallcovertheperiodnotedonthequotationpresentedtothepurchaseratthetimeofpurchase.Problemsoccurringduringthewarrantyperiodshallbasicallyberepairedfreeofcharge.

• Ifanyproblemsareexperiencedwiththisinstrument,thecustomershouldcontacttheYokogawarepresentativefromwhichthisinstrumentwaspurchasedorthenearestYokogawaoffice.

• Ifaproblemariseswiththisinstrument,please inform us of the nature of the problem andthecircumstancesunderwhichitdeveloped,includingthemodelspecificationand serial number. Any diagrams, data and otherinformationyoucanincludeinyourcommunicationwillalsobehelpful.

• ThepartyresponsibleforthecostoffixingtheproblemshallbedeterminedbyYokogawafollowinganinvestigationconductedbyYokogawa.

• Thepurchasershallbeartheresponsibilityforrepaircosts,evenduringthewarrantyperiod,ifthemalfunctionisdueto:

- Improperand/orinadequatemaintenancebythepurchaser.

- Malfunctionordamageduetoafailureto handle, use, or store the instrument in accordancewiththedesignspecifications.

- UseoftheproductinquestioninalocationnotconformingtothestandardsspecifiedbyYokogawa,orduetoimpropermaintenanceoftheinstallationlocation.

- FailureordamageduetomodificationorrepairbyanypartyexceptYokogawaoranapprovedrepresentativeofYokogawa.

- Malfunctionordamagefromimproperrelocationoftheproductinquestionafterdelivery.

- Reasonofforcemajeuresuchasfires,earthquakes,storms/floods,thunder/lightening, or other natural disasters, or disturbances,riots,warfare,orradioactivecontamination.

1.4 TrademarksInthisdocument,trademarksorregisteredtrademarksarenotmarkedwith“™”or“®”.Productnamesandcompanynamesinthisdocumentaretrademarksorregisteredtrademarksoftherespectivecompanies

Page 9: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<1. Introduction> 1-5

IM 01C27B01-01EN

1.5 Control of Pollution Caused by the ProductThisisanexplanationfortheproductbasedon“ControlofPollutioncausedbyElectronicInformationProducts”inthePeople’sRepublicofChina.

電子情報製品汚染制御管理弁法(中国版RoHS) 产品中有害物质或元素的名称及含量

产品中有害物质或元素的名称及含量

型号 部件名称有害物质

铅(Pb)

汞(Hg)

镉(Cd)

六价铬(Cr(VI))

多溴联苯(PBB)

多溴二苯醚(PBDE)

EJX-B series无线差压 / 压力变送器

YTA510无线温度变送器

壳体 × ○ ○ ○ ○ ○

膜盒组件 × ○ ○ ○ ○ ○

基板组件 × ○ ○ × ○ ○

电源连接线 × ○ ○ ○ ○ ○

天线组件 × ○ ○ ○ ○ ○

电池组件 × ○ ○ ○ ○ ○

○ :表示该部件的所有均质材料中的有害物质的含量均在 GB/T26572 标准中所规定的限量以下。× :表示至少该部件的某些均质材料中的有害物质的含量均在 GB/T26572 标准中所规定的限量以上。

环保使用期限 :

该标识适用于 SJ /T11364 中所述,在中华人民共和国销售的电子电气产品的环保使用期限。

注)该年数为“环保使用期限”,并非产品的质量保证期。

Page 10: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-1

IM 01C27B01-01EN

2. Handling CautionsThischapterprovidesimportantinformationonhowtohandlethetransmitter.Readthiscarefullybeforeusing the transmitter.

EJX Series transmitters are thoroughly tested at the factorybeforeshipment.Whentakingdeliveryofaninstrument,visuallycheckthemtomakesurethatnodamageoccurredduringshipment.

Alsocheckthatalltransmittermountinghardwareshowninfigure2.1isincluded.Ifthetransmitterisorderedwithoutthemountingbracketandtheprocessconnector,thetransmittermountinghardwarewillnotbeincluded.Aftercheckingthetransmitter,carefullyrepackitinitsboxandkeepitthere until you are ready to install it.

No antenna is provided for Amplifier housing code 9.

BoltProcess connectorProcess connector gasket

U-bolt nut

Mounting bracket(L type)

Transmitter mounting bolt

Spacer

Mounting bracket (Flat type)

F0201.ai

U-bolt nut

Transmitter mounting bolt

U-bolt

U-bolt

Antenna

Figure 2.1 Transmitter Mounting Hardware

2.1 Model and Specifications Check

Themodelnameandspecificationsarewrittenonthenameplateattachedtothecase.

: Refer to USER'S MANUAL.Made in JapanTOKYO 180-8750 JAPAN

MODELSUFFIX

SUPPLYOUTPUTMWP

mA DCV DC

STYLE

CALRNG

NO.

F0202.ai

Figure 2.2 Name Plate

• QR CodeTheproducthasaQRCodepastedforefficientplantmaintenanceworkandassetinformationmanagement. Itenablesconfirmingthespecificationsofpurchasedproductsanduser’smanuals.Formoredetails,pleaserefertothefollowingURL.https://www.yokogawa.com/qr-codeQRCodeisaregisteredtrademarkofDENSOWAVE INCORPORATED.

2.2 UnpackingKeepthetransmitterinitsoriginalpackagingtoprevent it from being damaged during shipment. Donotunpackthetransmitteruntilitreachestheinstallation site.

Page 11: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-2

IM 01C27B01-01EN

2.3 StorageThefollowingprecautionsmustbeobservedwhenstoringtheinstrument,especiallyforalongperiod.

(a) Selectastorageareawhichmeetsthefollowingconditions:• Itisnotexposedtorainorsubjecttowaterseepage/leaks.

• Vibrationandshockarekepttoaminimum.• It has an ambient temperature and relative humiditywithinthefollowingranges.

Ambient temperature: –40to85°C –30to80°CLCDvisiblerangeRelative humidity: 0% to 100% R.H. Preferred temperature and humidity: approx.25°Cand65%R.H.

(b) Whenstoringthetransmitter,repackitcarefullyinthepackagingthatitwasoriginallyshippedwith.

(c) Ifthetransmitterhasbeenused,thoroughlycleanthechambersinsidethecoverflanges,sothatthereisnoprocessfluidremaininginside.Beforeplacingitinstorage,alsomakesurethatthepressure-detectorissecurelyconnectedtothetransmittersection.

(d) Preferablyremovethebatteriesforstorage.Formaximum battery life, the storage temperature shouldnotexceed30°C.

NOTEWhenstoringtheinstrumentwithabatterypack,itisrecommendedtoputtheinstrumentinDeepSleepmodetoconservethebatteries.FordetailsonhowtoswitchtoDeepSleepmode,refertosubsection8.3.16“SwitchingtoDeepSleepMode”.

2.4 Selecting the Installation Location

Thetransmitterisdesignedtowithstandsevereenvironmentalconditions.However,toensurethatitwillprovideyearsofstableandaccurateperformance,takethefollowingprecautionswhenselectingtheinstallationlocation.

(a) WirelessCommunication

NOTETheinstallationlocationofthistransmittermustmeetthefollowingconditions:- Adjustthedirectionoftheantennatobe

in the upright position regardless of the orientationofthistransmitter.Seesection4for adjusting the antenna.

- Install the transmitter at least 1.5m above thegroundorfloor.

F0203.ai

1.5m

or m

ore

- Ensurethattherearenoobstaclessuchaswallsorpipeswithina30-cmradiusofeachantenna.

- ConfirmthateachfieldwirelessequipmentcompliantwithISA100.11acanseetheantennaofotherdeviceswhichlocatewithinitsowncommunicationrange.Inthestartopologynetwork,thevisibilitytotheantennaofgatewayisamandatoryclause.

Page 12: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-3

IM 01C27B01-01EN

(b) AmbientTemperatureAvoidlocationssubjecttowidetemperaturevariationsorasignificanttemperaturegradient.Ifthelocationisexposedtoradiantheatfromplant equipment, provide adequate thermal insulation and/or ventilation.

(c) AmbientAtmosphereDonotinstallthetransmitterinacorrosiveatmosphere.Ifthiscannotbeavoided,theremust be adequate ventilation.

(d) ShockandVibrationAlthough the transmitter is designed to be relativelyresistanttoshockandvibration,aninstallationsiteshouldbeselectedwherethisiskepttoaminimum.

(e) InstallationofExplosion-protectedTransmittersAnexplosion-protectedtransmittersiscertifiedforinstallationinahazardousareacontainingspecificgastypes.Seesubsection2.8“InstallationofanExplosion-ProtectedTransmitters.”

2.5 Pressure Connection

WARNING

• Neverloosentheprocessconnectorboltswhenaninstrumentisinstalledinaprocess.Thedeviceisunderpressure,andalossofsealcanresultinasuddenanduncontrolledreleaseofprocessfluid.

• Whendrainingtoxicprocessfluidsthathavecondensedinsidethepressuredetector,takeappropriatestepstopreventthecontactofsuchfluidswiththeskinoreyesandtheinhalationofvaporsfromthesefluids.

Thefollowingprecautionsmustbeobservedin order to safely operate the transmitter under pressure.

(a) Makesurethatalltheprocessconnectorboltsaretightenedfirmly.

(b) Makesurethattherearenoleaksintheimpulsepiping.

(c) Neverapplyapressurehigherthanthespecifiedmaximumworkingpressure.

2.6 Restrictions on Use of Radio Transceivers

IMPORTANTAlthough the transmitter has been designed to resisthighfrequencyelectricalnoise,ifaradiotransceiverisusednearthetransmitteroritsexternalwiring,thetransmittermaybeaffectedbyhighfrequencynoisepickup.Totestthis,startoutfromadistanceofseveralmetersandslowlyapproachthetransmitterwiththetransceiverwhileobservingthemeasurementloopfornoiseeffects.Thereafterusethetransceiveroutsidetherangewherethenoiseeffectswerefirstobserved.

2.7 Insulation Resistance and Dielectric Strength Test

Sincethetransmitterhasundergoneinsulationresistanceanddielectricstrengthtestsatthefactorybefore shipment, normally these tests are not required.Iftheneedarisestoconductthesetests,heedthefollowing:

(a) Donotperformsuchtestsmorefrequentlythanisabsolutelynecessary.Eventestvoltagesthatdonotcausevisibledamagetotheinsulationmaydegradetheinsulationandreducesafetymargins.

(b) Neverapplyavoltageexceeding500VDC(100VDCwithaninternallightningprotector)fortheinsulationresistancetest,noravoltageexceeding500VAC(100VACwithaninternallightningprotector)forthedielectricstrengthtest.

(c) Theprocedureforconductingthesetestsisasfollows:

Page 13: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-4

IM 01C27B01-01EN

• Insulation Resistance Test

1)Removethebatterypackorpowersupplymodule.Seesubsection9.4.6ReplacingtheBatteryPackor9.4.9ReplacingthePowerSupply Module.

2)Short-circuitthebatteryconnectionterminalsinthe terminal box.

3)TurnOFFtheinsulationtester.Thenconnecttheinsulationtesterplus(+)leadwiretotheshortedbatteryconnectionterminalsandtheminus(–)leadwiretothegroundingterminal.

4)TurnONtheinsulationtesterpowerandmeasuretheinsulationresistance.Thevoltageshouldbeappliedasbrieflyaspossibletoverifythattheinsulationresistanceisatleast20MΩ.

5)Aftercompletingthetestandbeingverycarefulnottotouchexposedconductorsdisconnecttheinsulationtesterandconnecta100kΩresistorbetweenthegroundingterminalandtheshort-circuitingbatteryconnectionterminals.Leavethisresistorconnectedatleastonesecondtodischargeanystaticpotential.Donottouchtheterminalswhileitisdischarging.

NOTEWhenstoringtheinstrumentwithabatterypack,itisrecommendedtoputtheinstrumentinDeepSleepmodetoconservethebatteries.FordetailsonhowtoswitchtoDeepSleepmode,refertosubsection8.3.16“SwitchingtoDeepSleepMode”.

• Dielectric Strength Test

1)Removethebatterypackorpowersupplymodule.Seesubsection9.4.6ReplacingtheBatteryPackor9.4.9ReplacingthePowerSupply Module.

2)Short-circuitthebatteryconnectionterminalsinthe terminal box.

3)TurnOFFthedielectricstrengthtester.Thenconnectthetesterbetweentheshortedbatteryconnectionterminalsandthegroundingterminal.Besuretoconnectthegroundingleadofthedielectricstrengthtestertothegroundterminal.

4)Setthecurrentlimitonthedielectricstrengthtesterto0.1mA,thenturnONthepowerandgraduallyincreasethetestvoltagefrom‘0’tothespecifiedvoltage.

5)Whenthespecifiedvoltageisreached,holditfor one minute.

6)Aftercompletingthistest,slowlydecreasethevoltage to avoid any voltage surges.

NOTEWhenstoringtheinstrumentwithabatterypack,itisrecommendedtoputtheinstrumentinDeepSleepmodetoconservethebatteries.FordetailsonhowtoswitchtoDeepSleepmode,refertosubsection8.3.16“SwitchingtoDeepSleepMode”.

2.8 Installation of an Explosion-Protected Instrument

Ifacustomermakesarepairormodificationtoanintrinsicallysafeinstrumentandtheinstrumentisnotrestoredtoitsoriginalcondition,itsintrinsicallysafeconstructionmaybecompromisedandtheinstrumentmaybehazardoustooperate.PleasecontactYokogawabeforemakinganyrepairormodificationtoaninstrument.

CAUTIONThisinstrumenthasbeentestedandcertifiedasbeingintrinsicallysafe.Pleasenotethatsevererestrictionsapplytothisinstrument’sconstruction,installation,externalwiring,maintenanceandrepair.Afailuretoabidebytheserestrictionscouldmaketheinstrumentahazardtooperate.

WARNING

Thebatterypackmaybereplacedinahazardousarea.Thebatterypackhassurfaceresistivitygreaterthan1Gohmandmustbeproperlyinstalledintheenclosureofthetransmitter.Caremustbetakenduringtransportation to and from the point of installation topreventelectrostaticchargebuild-up.

Page 14: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-5

IM 01C27B01-01EN

2.8.1 FM ApprovalCautionforFMintrinsicallysafetype.(Followingcontentsrefer“DOC.No.IFM037-A20”)

Note1. ModelEJXSeriesDifferential,gaugeandabsolutepressuretransmitterswithoptionalcode/FS17areapplicableforuseinhazardouslocations.

• ApplicableStandard:Class3600:2011, Class 3610:2015, Class 3611:2016, Class 3810:2005, ANSI/UL-60079-0-2013, ANSI/UL-60079-11-2014, NEMA-250:2003

• IntrinsicallySafeforClassI,Division1,Groups A, B, C & D, Class II, Division 1, Groups E, F & G and Class III, Division 1, ClassI,Zone0,inHazardousLocations,AExia IIC

• NonincendiveforClassI,Division2,GroupsA, B, C & D, Class II, Division 2, Groups F & G and Class III, Division 1, Class I, Zone 2, GroupsIIC,inHazardousLocations.

• Enclosure:Type4X• Temperature Class: T4• Ambienttemperature:-50to70°C

Note 2. Installation• Installationshouldbeinaccordancewith

ANSI/ISA-RP12.06.01 and the National ElectricCode(NFPA70).

• Dust-tightconduitsealmustbeusedwheninstalled in a Class II, III, Group E, F and G environments.

• Noteawarninglabelworded“SUBSTITUTIONOFCOMPONENTSMAYIMPAIRINTRINSICSAFETY,”and“INSTALLIN ACCORDANCE WITH DOC. NO. IFM037-A20”.

Model: EJX-L Series Date: March 8, 2010

Rev.1: May 21, 2010 Doc. No.: IFM037-A20 P.1 Rev.2: October 16, 2012 Rev.3: April 24, 2014 Rev.4: July 11, 2016

Yokogawa Electric Corporation

9.0 Control Drawing Specific conditions of use: - In case of the enclosure of the Pressure Transmitter is made of aluminum, if it is

mounted in Zone 0, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.

- Electrostatic charges on the non-metallic parts (excluding glass parts) or coated parts of the Pressure Transmitter shall be avoided.

Model: EJX-L Series Date: March 8, 2010

Rev.1: May 21, 2010 Doc. No.: IFM037-A20 P.1 Rev.2: October 16, 2012 Rev.3: April 24, 2014 Rev.4: July 11, 2016

Yokogawa Electric Corporation

Notes: 1. No revision to this drawing without prior approval of FM.

2. Installation must be in accordance with the National Electric Code (NFPA 70),

ANSI/ISA-RP12.06.01 and relevant local codes.

3. Antenna and Arrester are simple apparatus.

3.1 The following conditions must be met. (total Li of simple apparatus) + (total Lcable) ≤ 1 mH (total Ci of simple apparatus) + (total Ccable) ≤ 1 μF

3.2 The temperature class of Antenna and Arrester must be determined from Po = 20 mW at Antenna Connector, in accordance with Article 504 of NFPA 70.

3.3 Arrester may not be connected. 3.4 The connection diagram is for the transmitter with an external an antenna

connection. The transmitter with an integral antenna has no external connection as shown in the diagram.

4. WARNING – POTENTIAL ELECTROSTATIC CHARGING HAZARD – SECURE DISTANCE OF 100MM FROM ANTENNA

5. WARNING – IN THE CASE WHERE THE ENCLOSURE OF THE PRESSURE TRANSMITTER IS MADE OF ALUMINUM, IF IT IS MOUNTED IN ZONE 0, IT MUST BE INSTALLED SUCH, THAT EVEN IN THE EVENT OF RARE NCIDENTS, IGNITION SOURCES DUE TO IMPACT AND FRICTION SPARKS ARE EXCLUDED

6. WARNING – DO NOT OPEN WHEN CL II, III, DIV 1, 2 ATMOSPHERE IS

PRESENT

7. WARNING – USE ONLY BATTERY PACK YOKOGAWA F9915MA OR F9915NS

8. WARNING – THE BATTERY PACK CAN BE REPLACED IN A HAZARDOUS LOCATION. THE BATTERY PACK HAS SURFACE RESISTIVITY GREATER THAN 1G OHM AND MUST BE PROPERLY INSTALLED IN THE ENCLOSURE OF THE TRANSMITTER. CARE MUST BE TAKEN DURING TRANSPORTATION TO AND FROM THE POINT OF INSTALLATION TO PREVENT ELECTROSTATIC CHARGE BUILD-UP

9. WARNING – SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY

OnlyElectricalconnectioncode:Jisapplicable.

Page 15: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-6

IM 01C27B01-01EN

Note3. MaintenanceandRepair• TheinstrumentmodificationorpartsreplacementbyotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidFMApprovals approval.

Note4. BatteryPack USEONLYBATTERYPACKYOKOGAWA

F9915MA OR F9915NS.Note5. SpecialConditionsforsafeuse POTENTIAL ELECTROSTATIC CHARGING

HAZARD-SECURE DISTANCE OF 100MM FROM ANTENNA.

DO NOT OPEN WHEN CL II, III, DIV 1,2 ATMOSPHERE IS PRESENT.

2.8.2 CSA CertificationCautionforCSAIntrinsicallysafetype.(Followingcontentsreferto“DOCNo.ICS030”)Note1. ModelEJXSeriesdifferential,gauge,

andabsolutepressuretransmitterswithoptionalcode/CS17areapplicableforuseinhazardouslocations

• No. CSA10CA2325443X• Applicablestandard:

CAN/CSA-C22.2 No.94, C22.2 No.213, CAN/CSA-C22.2 No.61010-1, CAN/CSA-C22.2 No.60079-0, CAN/CSA-C22.2 No.60079-11, CAN/CSA-C22.2 No.60529

• Ex ia IIC T4 Ga• IntrinsicallySafeforClassI,Division1,

Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III, Division 1

• NonincendiveforClassI,Division2, Groups A, B, C & D, Class II, Division2, Groups F & G, Class III, Division1

• Enclosure:IP66/IP67andType4X• Temperature Code: T4• AmbientTemperature:-50to70°C• Max.ProcessTemp.:120°C

Note 2. Installation• InstallationshouldbeinaccordancewithCanadianElectricalCodePartIandLocalElectricalCode.

• Donotalterdrawingwithoutauthorizationfrom CSA.

• TheinstrumentmodificationorpartsreplacementbyotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidCanadianStandardsIntrinsicallysafeandnonincendiveCertification.

[Installation Diagram]

F0205.ai

Transmitter

[Intrinsically Safe]Group IIC, Zone 0Class I, II, III, Division 1,Groups A,B,C,D,E,F,G

[Nonincendive]Class I, II, Division 2,Groups A,B,C,D,F,GClass III, Division 1

Antenna(*1)

Arrester(*1, *2)

*1: These apparatus are simple apparatus.*2: Arrester may not be connected.

Antenna Connector

Battery Pack

Hazardous Area

Note3. BatteryPack• UseonlyYOKOGAWAbatterypack

F9915MA or F9915NS.Note4. SpecialConditionsforsafeuse

• Potentialelectrostaticcharginghazard-securedistanceof100mmfromantenna.

OnlyElectricalconnectioncode:Jisapplicable.

2.8.3 ATEX Certification

(1) Technical Data

CautionforATEXIntrinsicallysafetype.Note 1. Model EJX Series pressure transmitters

withoptionalcode/KS27forpotentiallyexplosive atmospheres:

• No.KEMA10ATEX0164X• ApplicableStandard: EN60079-0:2012+A11:2013 EN 60079-11: 2012, EN 60079-28: 2015

• TypeofProtectionandMarkingcode: Ex ia op is IIC T4 Ga

• Group: II• Category: 1 G• AmbientTemperature:–50°Cto70°C• ProcessTemperature(Tp.):120°Cmax.• Enclosure:IP66/IP67

Page 16: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-7

IM 01C27B01-01EN

Note 2. Installation• Installationshouldbeinaccordancewithlocalinstallationrequirements.(RefertotheControlDrawing)

[Control Drawing]

F0206.ai

*1: These apparatus are simple apparatus.*2: Arrester may not be connected.

Hazardous Area

Transmitter

Battery Pack

Arrester(*1, *2)

Antenna(*1)

Antenna connector

Note3. BatteryPack• UseonlyYOKOGAWAbatterypack

F9915MA or F9915NS.

Note4. SpecialconditionsforSafeUse• IncasetheenclosureofthePressure

Transmitter is made of aluminum, if it ismountedinanareawheretheuseofcategory1Gapparatusisrequired,itmustbeinstalledsuch,that,evenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.

• Electrostaticchargesonthenon-metallicparts(excludingglassparts)orcoatedpartsof the Pressure Transmitter shall be avoided.

WARNING

Potentialelectrostaticcharginghazard-securedistanceof100mmfromantenna.

(2) Operation

WARNING

Takecarenottogeneratemechanicalsparkingwhenaccesstotheinstrumentandperipheraldevicesinahazardouslocation.

(3) Maintenance and repair

WARNING

TheinstrumentmodificationorpartsreplacementbyotherthananauthorizedRepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidthecertification.

(4) Name Plate

• Name Plate

: Refer to USER'S MANUAL.Made in JapanTOKYO 180-8750 JAPAN

MODELSUFFIX

SUPPLYOUTPUTMWP

mA DCV DC

STYLE

CALRNG

NO.

F0207.ai

• Tagplateforintrinsicallysafetype

F0208.ai

KS27

No. KEMA 10ATEX0164 X Ex ia op is IIC T4 GaENCLOSURE: IP66/IP67Tamb.: -50 TO 70°C MAX PROCESS TEMP.: 120°C*3

POTENTIAL ELECTROSTATIC CHARGING HAZARD - SECURE DISTANCE OF 100MM FROM ANTENNA.USE ONLY BATTERY PACK YOKOGAWA F9915MA OR F9915NS.POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.

WARNING

MODEL:Specifiedmodelcode. STYLE:Stylecode. SUFFIX:Specifiedsuffixcode. SUPPLY:Supplyvoltage. OUTPUT: Output signal. MWP:Maximumworkingpressure. CALRNG:Specifiedcalibrationrange. NO.:Serialnumberandyearofproduction *1. TOKYO180-8750JAPAN: Themanufacturernameandtheaddress *2.

*1: Thefirstdigitinthefinalthreenumbersoftheserialnumberappearingafter“NO.”onthenameplateindicatestheyearofproduction.Thefollowingisanexampleofaserialnumberforaproductthatwasproducedin2010: 91K819857 032 ↑ The year 2010

*2: “180-8750”isazipcodewhichrepresentsthefollowingaddress.2-9-32Nakacho,Musashino-shi,TokyoJapan

*3: TheidentificationnumberofNotifiedBody.

OnlyElectricalconnectioncode:Jisapplicable.

Page 17: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-8

IM 01C27B01-01EN

2.8.4 IECEx CertificationCautionforIECExIntrinsicallysafetype.

Note 1. Model EJX Series pressure transmitters withoptionalcode/SS27forpotentiallyexplosive atmospheres:

• No.IECExKEM10.0074X• ApplicableStandard:

IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-28:2015

• TypeofProtectionandMarkingcode: Ex ia op is IIC T4 Ga*

*ForOutputsignal-L,theTypeofProtectionandMarkingcodeisExiaIICT4Ga.

• AmbientTemperature:–50°Cto70°C• ProcessTemperature(Tp.):120°Cmax.• Enclosure:IP66/IP67

Note 2. Installation• Installationshouldbeinaccordancewithlocalinstallationrequirements. (RefertotheControlDrawing)

[Control Drawing]

F0209.ai

Hazardous Area

*1: These apparatus are simple apparatus.*2: Arrester may not be connected.

Transmitter

Battery Pack

Arrester(*1, *2)

Antenna(*1)

Antenna connector

Note3. MaintenanceandRepair• TheinstrumentmodificationorpartsreplacementbyotherthanauthorizedrepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidIECExIntrinsicallysafeCertification.

WARNING

TheinstrumentmodificationorpartsreplacementbyotherthananauthorizedRepresentativeofYokogawaElectricCorporationisprohibitedandwillvoidthecertification.

Note4. BatteryPack• UseonlyYOKOGAWAbatterypack

F9915MA or F9915NS.

Note5. SpecialconditionsforSafeUse• IncasetheenclosureofthePressure

Transmitter is made of aluminum, if it ismountedinanareawheretheuseofapparatusofequipmentprotectionlevelGaisrequired,itmustbeinstalledsuch,that,evenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.

• Electrostaticchargesonthenon-metallicparts(excludingglassparts)orcoatedpartsof the Pressure Transmitter shall be avoided.

WARNING

• Potentialelectrostaticcharginghazard-securedistanceof100mmfromantenna.

• Takecarenottogeneratemechanicalsparkingwhenaccesstotheinstrumentandperipheraldevicesinahazardouslocation.

OnlyElectricalconnectioncode:Jisapplicable.

2.9 EMC Conformity StandardsEN61326-1ClassA,Table2(Foruseinindustriallocations),EN61326-2-3

CAUTIONThisinstrumentisaClassAproduct,anditisdesigned for use in the industrial environment. Please use this instrument in the industrial environment only.

Page 18: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-9

IM 01C27B01-01EN

2.10 Pressure Equipment Directive (PED)

(1) General

• EJX Series pressure transmitters are categorizedaspressureaccessoriesunderthevesselsectionofdirective2014/68/EU,whichcorrespondstoArticle4,Paragraph3ofPED,denotedasSoundEngineeringPractice(SEP).

• EJX110B-MS, EJX110B-HS, EJX110B-VS, EJX510B-D, and EJX530B-Dcanbeusedabove200barandthereforeconsideredasapartofapressureretainingvesselwherecategoryIII,ModuleHapplies.Thesemodelswithoptioncode/PE3conformtothatcategory.

(2) Technical Data

• Modelswithout/PE3 Article4,Paragraph3ofPED,denotedasSoundEngineeringPractice(SEP).

• Modelswith/PE3 Module: H TypeofEquipment:PressureAccessory-Vessel Typeoffluid:LiquidandGas Groupoffluid:1and2

Model Capsulecode

PS(bar)*1 V(L) PS·V

(bar·L) Category*2

EJX110BF, L 160 0.01 1.6 Article4,

Paragraph 3(SEP)M, H, V 250 0.01 2.5

EJX110Bwithcode

/PE3M, H, V 250 0.01 2.5 III

EJX310B L, M, A, B 160 0.01 1.6Article4,

Paragraph 3(SEP)

EJX430B H, A, B 160 0.01 1.6Article4,

Paragraph 3(SEP)

EJX510BA, B, C 100 0.1 10 Article4,

Paragraph 3(SEP)D 700 0.1 70

EJX510Bwithcode

/PE3D 700 0.1 70 III

EJX530BA, B, C 100 0.1 10 Article4,

Paragraph 3(SEP)D 700 0.1 70

EJX530Bwithcode

/PE3D 700 0.1 70 III

*1: PSismaximumallowablepressureforvesselitself.*2: ReferredtoTable1coveredbyANNEXIIofECDirective

onPressureEquipmentDirective2014/68/EU

(3) Operation

CAUTION• Thetemperatureandpressureoffluidshouldbemaintainedatlevelsthatareconsistentwithnormaloperatingconditions.

• The ambient temperature should be maintainedatalevelthatisconsistentwithnormaloperatingconditions.

• Pleasetakecaretopreventwaterhammerandthelikefrominducingexcessivepressures in pipes and valves. If phenomena arelikely,installasafetyvalveortakesome other appropriate measure to prevent pressurefromexceedingPS.

• Takeappropriatemeasuresatthedeviceorsystemleveltoprotecttransmittersiftheyare to be operated near an external heat source.

2.11 Low Voltage DirectiveApplicablestandard:EN61010-1, EN61010-2-030

(1) Pollution Degree 2

"Pollutiondegree"describesthedegreetowhichasolid,liquid,orgaswhichdeterioratesdielectricstrengthorsurfaceresistivityisadhering. " 2 " applies to normal indoor atmosphere.Normally,onlynon-conductivepollutionoccurs.Occasionally,however,temporaryconductivitycausedbycondensationmustbeexpected.

(2) Installation Category I (Anticipated transient overvoltage 330 V)

"Overvoltagecategory(Installationcategory)"describesanumberwhichdefinesatransientovervoltagecondition.Itimpliestheregulationforimpulsewithstandvoltage."I"appliestoelectricalequipmentwhichissuppliedfromthecircuitwhenappropriatetransientovervoltagecontrolmeans(interfaces)areprovided.

Page 19: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-10

IM 01C27B01-01EN

2.12 Regulatory Compliance for Radio and Telecommunication

Pleaseconfirmthatainstallationregionfulfilsastandards, require additional regulatory information andapprovals,contacttoYokogawaElectricCorporation.

2.12.1 Radio Equipment Directive (RE)Hereby,YokogawaElectricCorporationdeclaresthat the radio equipment type EJXB is in compliancewithDirective2014/53/EU.

ThefulltextoftheEUdeclarationofconformityisavailableatthefollowingInternetaddress:http://www.yokogawa.com/fld/

2.12.2 FCC complianceThisequipmentcontainstransmittermoduleFCCID:SGJ-WFC001*1

SGJ-WFC014*2*1:Onlyapplicableforselectingoutputsignalcode-L.*2:Onlyapplicableforselectingoutputsignalcode-1.

ThisdevicecomplieswithPart15ofFCCRules.Operationissubjecttothefollowingtwoconditions:(1)thisdevicemaynotcauseinterference,and(2)thisdevicemustacceptanyinterferencereceived,includinginterferencethatmaycauseundesiredoperationofthisdevice.

Co-located:

Thistransmittermustnotbeco-locatedoroperatedinconjunctionwithanyotherantennaortransmitter.

FCC WARNING:

Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoidtheuser’sauthoritytooperatetheequipment.

RF Exposure Compliance:

ThisequipmentcomplieswithFCCradiationexposurelimitssetforthforanuncontrolledenvironmentandmeetstheFCCradiofrequency(RF)ExposureGuidelines.Thisequipmentshouldbeinstalledandoperatedkeepingtheradiatoratleast20cmormoreawayfromperson’sbody.

2.12.3 Industry Canada (IC) complianceThisequipmentcontainstransmittermoduleIC:8999A-WIC001*1 / 8999A-WIC013*2.

ThisdevicecomplieswithISED’sapplicablelicense-exemptRSSs.Operationissubjecttothefollowingtwoconditions:(1)thisdevicemaynotcauseinterference,and(2)thisdevicemustacceptanyinterference,includinginterferencethatmaycauseundesired,operationofthedevice.

ThisequipmentcomplieswithICradiationexposurelimitssetforthforanuncontrolledenvironmentandmeetsRSS-102oftheICradiofrequency(RF)Exposure rules. This equipment should be installed andoperatedkeepingtheradiatoratleast20cmormoreawayfromperson’sbody.

This radio transmitter IC Number 8999A-WIC001*1 / 8999A-WIC013*2 has been approved by Industry Canadatooperatewiththeantennatypeslistedbelowwiththemaximumpermissiblegainindicated.Antennatypesnotincludedinthislist,having a gain greater than the maximum gain indicatedforthattype,arestrictlyprohibitedforusewiththisdevice.

Antenna type: Gain: COLLINEAR 9 dBi*1 / 6 dBi*2Sleeve 2.14 dBi

French: LeprésentappareilestconformeauxCNRd’ISDEapplicablesauxappareilsradioexemptsdelicence.L’exploitationestautoriséeauxdeuxconditionssuivantes:(1)l’appareilnedoitpasproduiredebrouillage,et(2)l’utilisateurdel’appareildoitacceptertoutbrouillageradioélectriquesubi,mêmesilebrouillageestsusceptibled’encompromettrelefonctionnement.

Cetéquipementestconformeauxlimitesd’expositionauxrayonnementsénoncéespourunenvironnementnoncontrôléetrespectelesrèglesd’expositionauxfréquencesradioélectriques(RF)CNR-102del’IC.Cetéquipementdoitêtreinstalléetutiliséengardantunedistancede20cmouplusentreleradiateuretlecorpshumain.

Page 20: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<2. Handling Cautions> 2-11

IM 01C27B01-01EN

Le présent émetteur radio IC Number 8999A-WIC001*1 / 8999A-WIC013*2 a été approuvéparIndustrieCanadapourfonctionneraveclestypesd’antenneénumérésci-dessouset ayant un gain admissible maximal. Les types d’antennenoninclusdanscetteliste,etdontlegain est supérieur au gain maximal indiqué, sont strictementinterditspourl’exploitationdel’émetteur.

Antenne type: Gain: COLLINEAR 9 dBi*1 / 6 dBi*2Sleeve 2.14 dBi

*1:Onlyapplicableforselectingoutputsignalcode-L.*2:Onlyapplicableforselectingoutputsignalcode-1.

2.13 RoHSApplicablestandard:EN50581(FortheproductsdeliveredafterJuly1st,2017)

Page 21: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<3. Component Names> 3-1

IM 01C27B01-01EN

3. Component Names

F0301.aiYES (Note 3)

(Write disabled)NO

(Write enabled)

Preccure-detector sectionVertical impulse pipimg type

Cover flange

Terminal box cover

Horizontal impulse piping type

Zero-adjustmentscrew

Ground terminal

Process connction

Process connector (Note1)

Drain plug

Vent plug

RF assembly

CPU assembly

Transmitter section

Amplifier Cover

Mountingscrew

Slideswitch

Hardware write protection switch (WR)

Write protection

Write protection Switch Position

(Note 2)

Integral indicator

E WRD

Not in use

Write protection switch

HL

ED

HL

ED

Antenna

● Terminal configuration(External powered type)

Ground terminalPower supply terminal +

Power supply terminal –

Note1: AprocessconnectorwillnotbeappliedforlowersideofEJX430BandEJX310B.Note2: Settheswitchasshowninthefigureabovetosetthewriteprotection.ThehardwarewriteprotectionswitchissettoEside.Set

toHsidefortheswitchofnot-in-use.Note3: WhentheswitchisDside(writeprotectionsetting),provisioningisacceptable.Fordetailsofprovisioning,refertosection7.4

“ConnectingtotheFieldWirelessNetwork”.

Figure 3.1 Component Names

Table 3.1 Display Symbol

Display Symbol Meaning of Display SymbolDisplaymodeis‘squareroot’.(Displayisnotlitwhen‘linear’mode.)

▲ Theoutputsignalbeingzero-adjustedisincreasing.▼ Theoutputsignalbeingzero-adjustedisdecreasing.

Writeprotectfunctionisenabled.

Page 22: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<4. Installation> 4-1

IM 01C27B01-01EN

4. Installation4.1 Precautions Beforeinstallingthetransmitter,readthecautionarynotesinsection2.4,“SelectingtheInstallationLocation.”Foradditionalinformationontheambientconditionsallowedattheinstallationlocation,refertosubsection11.1“StandardSpecifications.”

NOTEToconnectthistransmittertotheFieldWirelessNetwork,informationforconnectingtothefieldwirelessdevicesneedstobesetbeforehand.Referto7.4“ConnectingtotheFieldWirelessNetwork.”

IMPORTANT• Whenweldingpipingduringconstruction,takecarenottoallowweldingcurrentstoflowthroughthetransmitter.

• Do not step on this instrument after installation.

• FortheEJX430B,theatmosphericopeningislocatedonthelowpressuresidecoverflange.Takecaredonotenterrainintotheopening.Theopeningmustnotfaceupward.Seesection11.4,“Dimensions,”forthelocationoftheopening.

4.2 Mounting ■ Thetransmitterisshippedwiththeprocess

connection,accordingtotheorderingspecifications.Tochangetheorientationoftheprocessconnections,refertosection4.3.

■ Withdifferentialpressuretransmitters,thedistancebetweentheimpulsepipingconnectionportsisusually54mm(figure4.1).Bychangingtheorientationoftheprocessconnector,thedimensioncanbechangedto 51 mm or 57 mm.

■ Thetransmittercanbemountedonanominal50mm(2-inch)pipeusingthemountingbracketsupplied,asshowninfigure4.2and4.3. Thetransmittercanbemountedoneitherahorizontaloraverticalpipe.

■ Whenmountingthebracketonthetransmitter,tightenthe(four)boltsthatholdthetransmitterwithatorqueofapproximately39N·m{4kgf·m}.

57 mm 54 mm 51 mmF0401.ai

Figure 4.1 Process Connector Impulse Piping Connection Distances for Differential Pressure Transmitters

CAUTIONWhenthesuffixcodeofthemountingbracketis“B,”makesuretoputthespacerbetweenthebracketandtransmitterasshowninFigure4.2.

Transmitter mounting bolt

Spacer

U-bolt nut

Mounting bracket

50 mm (2-inch) pipe

U-bolt

F0402.ai

Spacer

U-bolt nut

Mounting bracket

50 mm (2-inch) pipe

U-bolt

Transmitter mounting bolt

Horizontal pipe mounting

Vertical pipe mounting

Figure 4.2 Transmitter Mounting (Horizontal Impulse Piping Type)

Page 23: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<4. Installation> 4-2

IM 01C27B01-01EN

F0403.ai

Transmitter mounting bolt

Transmitter mounting bolt

Mounting bracket

Mounting bracket

U-bolt nut

U-bolt nut

U-bolt

U-bolt

50 mm (2-inch) pipe

50 mm (2-inch) pipe

Vertical pipe mounting (Process connector downside)

Vertical pipe mounting (Process connector upside)

Figure 4.3 Transmitter Mounting (Vertical Impulse Piping Type)

F0404.ai

Transmitter mounting bolt

Transmitter mounting bolt

Mounting bracket

Mounting bracket

U-bolt nut

U-bolt nut

U-bolt

U-bolt

50 mm (2-inch) pipe

50 mm (2-inch) pipe

Horizontal pipe mounting (Process connector downside)

Horizontal pipe mounting (Process connector upside)

Page 24: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<4. Installation> 4-3

IM 01C27B01-01EN

4.3 Changing the Process Connection

Thetransmitterisshippedwiththeprocessconnectionspecifiedatthetimeofordering.Tochangetheprocessconnection,thedrain(vent)plug must be repositioned.

Torepositionadrain(vent)plug,refertoFigure4.4anduseawrenchslowlyandgentlytounscrewit. Then, remove and remount it on the opposite side.Wrapsealingtapearoundthedrain(vent)plugthreads(*1inthefigurebelow),andapplyalubricanttothethreadsofthedrain(vent)screw(s)(*2below).Totightenthedrain(vent)plugs,applyatorqueof34to39N·m(3.5to4kgf·m).Processconnectorboltsaretobetighteneduniformlytoatorqueshownintable4.1.

Table 4.1 Torque

ModelEJX110BEJX310BEJX430B

Torque(N·m){kgf·m} 39to49{4to5}

F0405.ai

Vent/drain plug

Vertical impulse piping type

Horizontal impulse piping type

Note: For a horizontal impulse piping type, moving the process connectors from the front side to the back cannot be made.

Bolt

Process connector gasket

1 2

Figure 4.4 Changing Process Connection

4.4 Swapping the High/Low-pressure Side Connection

IMPORTANTThissectionisapplicableonlyforEJX110Bdifferentialtransmitters,andnotapplicableforgauge or absolute pressure transmitters.

4.4.1 Rotating Pressure-detector Section 180°

Thisprocedurecanbeappliedonlytoatransmitterwithaverticalimpulsepipingtype.

Theprocedurebelowcanbeusedtoturnthepressuredetectorassembly180°.Performthisoperationinamaintenanceshopwiththenecessarytoolslaidoutandreadyforuse,andtheninstallthetransmitterinthefieldaftermakingthechange.

1)UseanAllenwrench(JISB4648,nominal2.5mm)toremovethefivesetscrewsatthejointbetweenthepressure-detectorsectionandtransmittersection.

2)Leavingthetransmittersectioninposition,rotatethepressure-detectorsection180°.

3)Tightenthefivesetscrewstofixthepressure-detectorsectionandtransmittersectiontogether(atatorqueof1.5N·m).

Repositiontheprocessconnectoranddrain(vent)plugstotheoppositesideasdescribedinsubsection4.3.

IMPORTANTDonotrotatethetransmittersectionmorethanabove limit.

F0406.ai

Process connector

Setscrew

Before After rotating 180°

Figure 4.5 Before and After Modification

Page 25: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<4. Installation> 4-4

IM 01C27B01-01EN

4.4.2 Using the Configuration ToolThismethodisapplicableonlytothemodelEJX110B.

Withaconfigurationtool,youcanchangewhichprocessconnectionisusedasthehigh-pressuresidewithoutmechanicallyrotatingthepressure-detectorsection180asdescribedinsubsection4.4.1.Tochange,callupthe‘H/L_SWAP’parameterandselectREVERSE(rightside:lowpressure;leftside:highpressure)orselectNORMALtochangebacktonormal(rightside:highpressure;leftside:lowpressure).

Output

Input

NORMAL

REVERSEF0407.ai

Figure 4.6 Input/Output Relationship

IMPORTANTSincetheH/Llabelplateonthecapsuleassemblywillremainunchanged,usethisfunctiononlywhenyoucannotswitchtheimpulsepiping.Ifthe‘H/L_SWAP’parametersettingischanged,theinput/outputrelationshipisreversedasshowninFigure4.6;besurethisis understood by all. After reversing the setting, modifytheH/Llabelplatetoclearlyindicatethischange.

4.5 Rotating Transmitter Section

WARNING

Intrinsicsafetypetransmittersmustbe,asarule,donotrotatetransmittersectionifitispowered.Incaseyouneedtorotatewhenthetransmitterispowered,usinggasdetectorandconfirmnoexistenceofexplosivegasbeforerotating.

Thetransmittersectioncanberotatedapproximately360°(180°toeitherdirectionor360°toonedirectionfromtheoriginalpositionatshipment,dependingontheconfigurationoftheinstrument.)Itcanbefixedatanyanglewithinabove range.

1)Removethefivesetscrewsthatfastenthetransmittersectionandcapsuleassembly,usingtheAllenwrench.

2)Rotatethetransmittersectionslowlyandstopitat designated position.

3)Tightenthefivesetscrewstoatorqueof1.5N·m.

IMPORTANTDonotrotatethetransmittersectionmorethanthe above limit.

Page 26: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<4. Installation> 4-5

IM 01C27B01-01EN

F0408.ai

Vertical impulse piping type

Horizontal impulse piping type

Pressure-detector section

Transmitter section

Transmitter section

Pressure-detector section

Zero-adjustment screw

Figure 4.7 Rotating Transmitter Section (Left Side High Pressure Type)

4.6 Changing the Direction of Integral Indicator

WARNING

Intrinsicsafetypetransmittersmustbe,asarule,removeabatterypackinnon-hazardousareabeforeopen/closetheAmplifierCoverordisassembling and reassembling the Integral Indicator.

Anintegralindicatorcanberotatedinfourpositionsat90°.Followtheinstructionsinsection9.4.1forremovingandattachingtheintegralindicator.

4.7 Changing the direction of the antenna

Adjustthedirectionoftheantennatobeintheuprightposition.Figure4.8showsfactorysetupantenna position. If the transmitter is installed to verticalimpulsepiping,followtheprocedurebelowandchangetheantennaposition.

1)Loosenthetwomountingscrewsatthebottomoftheantennabyusinga2.5mmAllenwrench(seeFigure4.8).

Thescrewsmightcomeoffandbelostifloosenedtoomuch;loosenthescrewsbyaboutthree rotations.

2)Pressforwardanddown90degreesbyrotatingthe axis at the bottom of the antenna.

3)Tightenthetwoscrewstoatorqueof1.5N·mbyusingatorquewrench.Whendoingthis,becarefulnotleaveagapbetweentheantennaand housing.

F0409.ai

Figure 4.8 Mounting Screw Position

F0410.ai

Figure 4.9 Adjusting Antenna Position

Page 27: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<5. Installing Impulse Piping> 5-1

IM 01C27B01-01EN

5. Installing Impulse Piping5.1 Impulse Piping Installation

PrecautionsTheimpulsepipingthatconnectstheprocessoutputstothetransmittermustconveytheprocesspressureaccurately.If,forexample,gascollectsinaliquid-filledimpulseline,orthedrainforagas-filledimpulselinebecomesplugged,itwillnotconveythepressureaccurately.Sincethiswillcauseerrorsinthemeasurementoutput,selecttheproperpipingmethodfortheprocessfluid(gas,liquid,orsteam).Paycarefulattentiontothefollowingpointswhenroutingtheimpulsepipingandconnectingtheimpulsepipingtoatransmitter.

5.1.1 Connecting Impulse Piping to a Transmitter

(1) Check the High and Low Pressure Connections on the Transmitter (Figure 5.1)

Symbols“H”and“L”havebeenplacedonthecapsuleassemblytoindicatehighandlowpressureside.Withdifferentialpressuretransmitters,connectthehighpressuresideimpulselinetothe“H”side,andthelowpressuresideimpulselinetothe“L”side.

F0501.ai

Processconnection

“H” and “L” are shown

Process connection

Process connector

Bolt

Differential Pressure Transmitter

“H” and “L” are shown

Process connection

Process connector

Bolt

Gauge/Absolute Pressure Transmitters

Figure 5.1 “H” and “L” Symbols on a Capsule Assembly

(2) Changing the Process Connector Piping Connections (Figure 4.1) (for differential pressure transmitters)

Theimpulsepipingconnectiondistancescanbechangedbetween51mm,54mmand57mmbychangingtheorientationoftheprocessconnectors.Thisisconvenientforaligninganimpulselinewithaprocessconnectors.

(3) Tightening the Process Connector Mounting Bolts

Afterconnectinganimpulseline,tightentheprocessconnectormountingboltsuniformly. (Applyatorqueof39~49N·m{4~5kgf·m})

(4) Removing the Impulse Piping Connecting Port Dustproof Cap

The impulse piping and a 3-valve manifold connectingportonthetransmitteriscoveredwithaplasticcaptokeepoutdust.Thiscapmustberemovedbeforeconnectingtheline.(Becarefulnottodamagethethreadswhenremovingthiscap.Neverinsertascrewdriverorothertoolbetweenthecapandportthreadstoremovethecap.)

(5) Connecting the Transmitter and 3-Valve Manifold (for differential pressure transmitters)

A3-valvemanifoldconsistsoftwostopvalvestoblockprocesspressureandanequalizingvalvetoequalizethepressuresonthehighandlowpressuresidesofthetransmitter.Suchamanifoldmakesiteasiertodisconnectthetransmitterfromtheimpulsepiping,andisconvenientwhenadjustingthetransmitterzeropoint.

Therearetwo3-valvemanifoldtypes:thepipe-mountingtypeandthedirect-mountingtype;careshouldbetakenwithrespecttothefollowingpointswhenconnectingthemanifoldtothetransmitter.

Page 28: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<5. Installing Impulse Piping> 5-2

IM 01C27B01-01EN

Pipe-Mounting Type 3-Valve Manifold (Figure 5.2)

1) Screwnipplesintotheconnectionportsonthetransmitter side of the 3-valve manifold, and intotheimpulsepipingconnectingportsontheprocessconnectors.(Tomaintainpropersealing,windsealingtapearoundthenipplethreads.)

2) Mountthe3-valvemanifoldonthe50mm(2-inch)pipebyfasteningaU-bolttoitsmountingbracket.TightentheU-boltnutsonlylightlyatthis time.

3) Installthepipeassembliesbetweenthe3-valvemanifoldandtheprocessconnectorsandlightlytightentheballheadlocknuts.(Theball-shapedendsofthepipesmustbehandledcarefully,sincetheywillnotsealproperlyiftheballsurfaceisscratchedorotherwisedamaged.)

4) Nowtightenthenutsandboltssecurelyinthefollowingsequence:

Processconnectorbolts→transmitter-endballheadlocknuts→3-valvemanifoldballheadlocknuts→3-valvemanifoldmountingbracketU-bolt nuts

F0502.ai

Nipple

Nipple

Processconnector

Ball headlock nut

Pipe assembly

Ball headlock nut

Processconnector

bolts

50 mm (2-inch) pipe

Pipe assembly

3-valvemanifold

Impulse pipingVent plug

(optional)

Stop valve(low pressure side)

Equalizing valve(balancing)

Stop valve(high pressure side)

Figure 5.2 3-Valve Manifold (Pipe-Mounting Type)

Direct-Mounting Type 3-Valve Manifold (Figure 5.3)

1) Mountthe3-valvemanifoldonthetransmitter. (Whenmounting,usethetwogasketsandthe

fourboltsprovidedwiththe3-valvemanifold.Tightentheboltsevenly.)

2) Mounttheprocessconnectorsandgasketsonthetopofthe3-valvemanifold(thesideonwhichtheimpulsepipingwillbeconnected).

Bolts

Processconnector

Gasket

GasketProcess

connector

Bolts

Stop valve(low pressure side)

Stop valve(low pressure side)

3-valvemanifold

3-valvemanifold

Equalizing valve

Equalizingvalve

Stop valve(high pressure side)

Impulsepiping

Impulsepiping

Stop valve(high pressure side)

F0503.ai

(high pressure side)

Figure 5.3 3-Valve Manifold (Direct-Mounting Type)

NOTEAftercompletingtheconnectionofthetransmitterand3-valvemanifold,besuretoCLOSEthelowpressure and high pressure stop valves, OPEN theequalizingvalve,andleavethemanifoldwiththeequalizingvalveOPEN. Youmustdothisinordertoavoidoverloadingthetransmitterfromeitherthehighorthelowpressuresidewhenbeginningoperation. Thisinstructionmustalsobefollowedaspartofthestartupprocedure(chapter7.)

Page 29: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<5. Installing Impulse Piping> 5-3

IM 01C27B01-01EN

5.1.2 Routing the Impulse Piping

(1) Process Pressure Tap Angles

Ifcondensate,gas,sedimentorotherextraneousmaterialintheprocesspipinggetsintotheimpulsepiping, pressure measurement errors may result. To preventsuchproblems,theprocesspressuretapsmustbeangledasshowninfigure5.4accordingtothekindoffluidbeingmeasured.

NOTE• Iftheprocessfluidisagas,thetapsmustbeverticalorwithin45°eithersideofvertical.

• Iftheprocessfluidisaliquid,thetapsmustbehorizontalorbelowhorizontal,butnotmorethan45°belowhorizontal.

• Iftheprocessfluidissteamorothercondensingvapor,thetapsmustbehorizontalorabovehorizontal,butnotmorethan45°abovehorizontal.

[Gas]

Pressuretaps

Processpiping

[Steam][Liquid]

45°

45°

45° 45°

45°

45°

F0504.ai

Figure 5.4 Process Pressure Tap Angle (For Horizontal Piping)

(2) Position of Process Pressure Taps and Transmitter

Ifcondensate(orgas)accumulatesintheimpulsepiping,itshouldberemovedperiodicallybyopeningthedrain(orvent)plugs.However,thiswillgenerateatransientdisturbanceinthepressuremeasurement,andthereforeitisnecessarytoposition the taps and route the impulse piping so that any extraneous liquid or gas generated in the leadlinesreturnsnaturallytotheprocesspiping.

• Iftheprocessfluidisagas,thenasarulethetransmittermustbelocatedhigherthantheprocesspressuretaps.

• Iftheprocessfluidisaliquidorsteam,thenasarulethetransmittermustbelocatedlowerthantheprocesspressuretaps.

(3) Impulse Piping Slope

Theimpulsepipingmustberoutedwithonlyanupwardordownwardslope.Evenforhorizontalrouting, the impulse piping should have a slope of atleast1/10topreventcondensate(orgases)fromaccumulatinginthepipes.

(4) Temperature Difference Between Impulse Lines (for differential pressure transmitters)

Ifthereisatemperaturedifferencebetweenthehighandlowimpulselines,thedensitydifferenceofthefluidsinthetwolineswillcauseanerrorinthemeasurementpressure.Whenmeasuringflow,impulse lines must be routed together so that there isnotemperaturedifferencebetweenthem.

(5) Condensate Pots for Steam Flow Measurement (for differential pressure transmitters)

If the liquid in the impulse piping repeatedly condensesorvaporizesasaresultofchangesintheambientorprocesstemperature,thiswillcauseadifferenceinthefluidheadbetweenthehighpressureandlowpressuresides.Topreventmeasurementerrorsduetotheseheaddifferences,condensatepotsareusedwhenmeasuringsteamflow.

(6) Preventing Wind Speed Effects in Very Low Differential Pressure Measurement (for differential pressure transmitters)

IMPORTANTWhenusingadifferentialpressuretransmittertomeasureverylowpressures(draftpressure),thelowpressureconnectionportisleftopentoatmosphericpressure(thereferencepressure).Anywindaroundthedifferentialpressuretransmitterwillthereforecauseerrorsinthemeasurement.Topreventthis,itwillbenecessaryeithertoenclosethetransmitterinabox,ortoconnectanimpulselinetothelowpressuresideandinsertitsendintoawind-excludingpot(cylindricalwithabaseplate).

Page 30: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<5. Installing Impulse Piping> 5-4

IM 01C27B01-01EN

(7) Preventing Freezing

Ifthereisanyriskthattheprocessfluidintheimpulsepipingortransmittercouldfreeze,useasteamjacketorheatertomaintainthetemperatureofthefluid.

NOTEAftercompletingtheconnections,closethevalvesontheprocesspressuretaps(mainvalves),thevalvesatthetransmitter(stopvalves),andtheimpulsepipingdrainvalves,sothatcondensate,sediment,dustandotherextraneousmaterialcannotentertheimpulsepiping.

5.2 Impulse Piping Connection Examples

Figure5.5and5.6showexamplesoftypicalimpulsepipingconnections.Beforeconnectingthetransmittertotheprocess,studythetransmitterinstallationlocation,theprocesspipinglayout,andthecharacteristicsoftheprocessfluid(corrosiveness,toxicity,flammability,etc.),inordertomakeappropriatechangesandadditionstotheconnectionconfigurations.

Notethefollowingpointswhenreferringtothesepiping examples.

• Thehighpressureconnectingportonthetransmitterisshownontheright(asviewedfromthefront).

• Thetransmitterimpulsepipingconnectionisshownforaverticalimpulsepipingconnectionconfigurationinwhichthedirectionofconnectioniseitherupwardsordownwards.

• Iftheimpulselineislong,bracingorsupportsshould be provided to prevent vibration.

• The impulse piping material used must becompatiblewiththeprocesspressure,temperature,andotherconditions.

• Avarietyofprocesspressuretapvalves(mainvalves)areavailableaccordingtothetypeofconnection(flanged,screwed,welded),construction(globe,gate,orballvalve),temperatureandpressure.Selectthetypeofvalvemostappropriatefortheapplication.

Tee

3-valvemanifold

Drainvalve

Orifice

Drainplug

Tapvalve

Unionor flange

Liguid Gas

Condensate pot

Steam

F0505.ai

Figure 5.5 Impulse Piping Connection Examples for Differential Pressure Transmitters

F0506.ai

Liquid Gas Steam

Union or flange

TeeTee

Drain plug

Drain valve

Drain valveDrain plug

Union or flange

Union or

flange

Union or flange

Tap valve

Tapvalve

Tee

Drain valveDrain plug

Tap valve

Figure 5.6 Impulse Piping Connection Examples for Gauge/absolute Pressure Transmitters

Page 31: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<6. Wiring> 6-1

IM 01C27B01-01EN

6. Wiring6.1 Mounting Antenna and

WiringAnantennaisnotattachedtothetransmitter.Thefollowingprovidestheinstructionsformountingthe antenna and installing the remote antenna and wiringusingantennaextensioncable.

IMPORTANTTheantennaconnectoriscoveredwithacapatthetimeofdelivery.Keepthecapattacheduntil the installation of the antenna or antenna cablestoprotecttheinsideconnectionpart.Theunscrewedcapshouldbestoredinordertoreplaceitimmediatelyaftertheantennaorantennacablesareremoved.

CAUTIONTomaintaintheultimateconditionsofradio-frequencysignal,protecttheconnectorsofantenna,extensionantennacable,andsurgeprotectivedevicefromthecorrosiveatmospherebythefollowingtreatment.1. Cleantheconnectiontobeprotected.2. Wind the butyl rubber self-bonding tape

aroundtheconnection.Seethemanualofthetapeaboutthewinding.

3. Toprotectthebutylrubberself-bondingtapefromtheenvironmentsuchasultravioletraysandsoon,windvinyltape(oravinyltypeself-bondingtape)onit.

6.1.1 Mounting the antennaScrewtheprovidedantennaintotheantennaconnectorofthetransmitter.Theantennamaybesoldasavailableaccessoriesandsuppliedseparately.

1.Unscrewtheantennaconnectorcapontheantennaconnector.

2.Screwtheprovidedantennaintotheantennaconnector.Tightentheantennaconnectorwithatorqueof2to3N∙m.

Antenna connector

F0601.ai

Figure 6.1 Mounting the antenna

CAUTIONWheninstallingtheantenna,screwtheantennabytighteningthelowernutpart.Screwingtheantennabyholdingtheantennabodymaycausefailuresuchascabledisconnection.Thesamemannershouldbetakenwhenunscrewingtheantenna.

Antenna body

F0602.ai

Nut part

Figure 6.2 Antenna

Page 32: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<6. Wiring> 6-2

IM 01C27B01-01EN

6.1.2 Mounting External Antenna and Wiring Antenna Extension Cable

6.1.2.1 Mounting of External AntennaMounttheexternalantennaattheproperlocationaccordingtothewirelessenvironmentdescribedin2.4SelectingtheInstallationLocation.Themountingtothepipesuchas50mm(2-inch)pipeneedstosecuretheenoughstrengthtoendureastrongwind,vibrationandsoon.Theantennamustbemountedvertically.

Fixing of External AntennaFix an external antenna appropriately using the bracketprovidedastheexternalantennaoptionto50mm(2-inch)pipe.

Bracket

Antenna

Vertical pipe mounting

Horizontal pipe mounting

Nut

2-inch pipe

U Bolt

Nut

AntennaExtension Cable

F0603.ai

Figure 6.3 Fixing the remote antenna

Mounting Procedure of External Antenna

1.FixthebracketbyU-boltandnutto50mm(2-inch)pipe.

2.Fixtheantennaextensioncabletothebracket1usingtheprovidednutwithatorqueof6to7N∙masshownintheFigure6.3above.Usethenutwhichisattachedtotheantennaextensioncable.

3.Screwtheantennaintotheantennaconnectoroftheantennaextensioncableonthebracket1.

Tightentheantennaconnectorwithatorqueof2to3N∙m.

4.Protecttheconnectionasnecessary.Fordetailsoftheprotection,see“6.1MountingAntennaandWiring.”

6.1.2.2 Wiring of Antenna Extension Cable1.Usetheprovidedantennaextensioncabletoconnecttheantennaconnectorwiththeexternalantenna.Tightentheconnectoroftheantennaextensioncablewithatorqueof2to3N∙m.Theminimumbendingradiuswhilecheckingthewiringpositionshouldbemorethan 200 mm.

2.Whenusingtwoextensioncables,theprovidedsurgeprotectivedeviceshouldbeinsertedbetweenthesecables.

3.Beforethewiringwork,confirmthepolarities(male/female)oftheconnectorsofantenna,extensionantennacable,andsurgeprotectivedevice.Tightentheconnectoroftheantennaextensioncablewithatorqueof2to3N∙m.

4.Protecttheconnectorsofantenna,extensionantennacable,andsurgeprotectivedeviceasnecessary.See“6.1MountingAntennaandWiring.”

5.Fixtheextensionantennacabletotheappropriatestructuretoprotectthecablefromthevibration,wind,andsoon.Theminimumbendingradiusforfixinginthestatemaintainedfor a long period should be more than 80 mm.

Page 33: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<6. Wiring> 6-3

IM 01C27B01-01EN

Transmitter body

Grounding cable

Protect by self-bonding tape

F0604.ai

Antenna extension cable 2: 10 m

Antenna

Antenna

Antenna extension cable 1: 3 mAntenna extension cable 1: 3 m

Protect by self-bonding tape

Transmitter body

Surge protective device

Figure 6.4 Wiring the antenna extension cable

CAUTIONUsethededicatedantennaextensioncableprovidedbyYokogawaasaccessoriesforthetransmitters.

Page 34: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<6. Wiring> 6-4

IM 01C27B01-01EN

6.1.2.3 Mounting of Surge Protective Device and Wiring

Mountansurgeprotectivedevicebetweentheextensioncablesandconnectthegroundingcabletothegroundingterminalofthesurgeprotectivedeviceasrequired.

Connectthegroundingcabletothegroundingterminal on the transmitter body. Class C grounding withthegroundingresistanceof10Ωorlessisnecessary.Donotsharethegroundwithotherdevices.

F0605.aiTransmitter side

Grounding cable

Antenna side

Antenna extension cable 2

Antenna extension cable 1

Surge protective device

Figure 6.5 Connection of the surge protective device and antenna extension cable

F0606.aiTransmitter side

Grounding cable

Antenna side

Protect by self-bonding tape

Figure 6.6 Surge protective device protection by self-bonding tape

6.2 GroundingWhenusingtheantennaextensioncablewithanarrestor,ClassCgroundingwiththegroundingresistanceof10Ωisrequired.Alwaysgroundthetransmittercaseinaccordancewithnationalandlocalelectricalcodes.Themosteffectivetransmittercasegroundingmethodisadirectconnectiontoearthgroundwithminimalimpedance.

IMPORTANTPropergroundingisnecessarytomaintainthefunctionandperformanceofthisproduct.Whenthe grounding is inadequate, the equipment may be damaged.Refer to TI 01W01A58-01EN for details of groundingmethodandprecautions.• UseagroundingcableofAWG14(2mm2)ormorebetweenthegroundingelectrodeandthegroundingterminalofthisproduct,andconnectwiththeshortestroute.

• Selectthegroundingcablethathasastructureofadequatelyprotectsagainstmechanicaldamage,chemicalorelectricaldegradation,electrodynamicforceandthermodynamicforceforconnectionofthegroundingelectrodeandthegroundterminalofthisproduct.

CAUTIONGrounding is required for safe operation.

F0607.ai

Ground terminal

Figure 6.7 Ground Terminal

Page 35: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<6. Wiring> 6-5

IM 01C27B01-01EN

6.3 Power Supply Wiring Precautions

IMPORTANT• Allthreadedpartsmustbetreatedwithwaterproofingsealant.(Anon-hardeningsiliconegroupsealantisrecommended.)

• Laywiringasfaraspossiblefromelectricalnoisesourcessuchaslargecapacitymotorsorpowersupplies.

• Removetheelectricalconnectiondustcapbeforewiring.

6.4 Selecting the Wiring Materials

(a) Usestrandedleadwiresorcableswhicharethe same as or better than 600 V grade PVC insulatedwire(JISC3307)oritsequivalent.

(b) Useshieldcablesinareasthataresusceptibletoelectricalnoise.

(c) Inareaswithhigherorlowerambienttemperatures,useappropriatewiresorcables.

(d) Inenvironmentwhereoils,solvents,corrosivegasesorliquidsmaybepresent,usewiresorcablesthatareresistanttosuchsubstances.

(e) Itisrecommendedthatcrimp-onsolderlessterminallugs(for4mmscrews)withinsulatingsleevesbeusedforleadwireends.

IMPORTANTExternalpoweredtypedoesnothaveapowerswitch.InstallabreakeronthepowersupplylineandturnthepowerON/OFF.

6.5 Connection of the External Power Source Terminal

Fortheexternalpoweredtype,connectthepowersupplywiringto+and−terminals.Ifthepowersupplycablehasshieldwires,connectthecableshield to the ground terminal.

Ground terminal Power supply terminal +

Power supply terminal –F0608.ai

Figure 6.8 Connection of External Power Source Terminal

(Note)Toprotectagainstexcessivesurge,besuretotightenthegroundterminalabout0.7N∙mregardlessoftheshieldcableconnection.

IMPORTANT• ConnectingwiththecommercialACpowersourcewilldamagethedevice.BesuretousetheDCpowersourceinthepredetermined range.

• Whenconnectingtotheexternalpowersource,becarefulnottoconnectthepolarityreversely. SUPPLY+terminal:Connectto+sideof

theexternalpowersource SUPPLY−terminal:Connectto− side of

theexternalpowersource

Page 36: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<7. Operation> 7-1

IM 01C27B01-01EN

7. Operation7.1 Preparation for Starting

OperationThissectiondescribestheoperationprocedurefortheEJX110Basshowninfigure7.1(verticalimpulsepipingtype,high-pressureconnection:rightside)whenmeasuringtheliquidflowrate,andEJX430Basshowninfigure7.2whenmeasuringpressure.

NOTEItisrequiredtosetsecurityandnetworkinformation to enable the transmitter to be connectedtotheFieldWirelessNetwork.Formoredetails,refertosection7.4“ConnectingtotheFieldWirelessNetwork”.

NOTECheckthattheprocesspressuretapvalves,drain valves, and 3-valve manifold stop valves onboththelowpressureandhighpressuresidesareclosed,andthatthe3-valvemanifoldequalizingvalveisopened.

(a) Followtheproceduresbelowtointroduceprocesspressureintotheimpulsepipingandtransmitter.

■ Differential Pressure Transmitters

1)Openthelowpressureandhighpressuretapvalvestofilltheimpulsepipingwithprocessliquid.

2)Slowlyopenthehighpressurestopvalvetofillthetransmitterpressure-detectorsectionwithprocessliquid.

3)Closethehighpressurestopvalve.4)Graduallyopenthelowpressurestopvalveandcompletelyfillthetransmitterpressure-detectorsectionwithprocessliquid.

5)Closethelowpressurestopvalve.6)Graduallyopenthehighpressurestopvalve.Atthistime,equalpressureisappliedtothelowand high pressure sides of the transmitter.

7)Checkthattherearenoliquidleaksintheimpulse piping, 3-valve manifold, transmitter, or othercomponents.

■ Gauge/Absolute Pressure Transmitters

1)Openthetapvalve(mainvalve)tofilltheimpulsepipingwithprocessfluid.

2)Graduallyopenthestopvalvetointroduceprocessfluidintothetransmitterpressure-detectorsection.

3)Confirmthatthereisnopressureleakinthe impulse piping, transmitter, or other components.

(b) Venting Gas from the Transmitter Pressure-detectorSection

Sincethepipingintheexampleoffigure7.1isconstructedtobeself-venting,noventingoperation is required. If it is not possible to makethepipingself-venting,refertosubsection7.5forinstructions.Leavetheequalizingvalveopen even after venting gas.

(c) Insertbatteriesintothebatterycase,andinstallto the transmitter. To insert batteries into the batterycase,becarefultopolarityofbatteriesandbatterycase.FordetailsofInstallationofbattery,refertosection9.4.6and9.4.7.

Fortheexternalpoweredtype,turnonthepowerandconnectwirelessfieldinstrumentstofieldwirelessnetwork.

Batterycaseisinstalledinthetransmitterwhenshippedfromthefactory,however,batteriesaresoldseparatelyandnotincluded.

(d) Usingthedeviceconfigurationtool,confirmthatthetransmitterisoperatingproperly.Checkparametervaluesorchangethesetpointsasnecessary.

IntegralIndicator’sindicationcanbeusedtoconfirmthatthetransmitterisoperatingproperly.Fordetailsonhowtoconfirm,refertosubsection8.4“Self-Diagnostics.”

ISA100devicesdisplayself-diagnosticinformation in an easy-to-understand manner usingfourcategories(Checkfunction,Maintenancerequired,Failure,andOff-specification)accordingtoNAMURNE107*.

*NAMURNE107“Self-MonitoringandDiagnosisofFieldDevices”

Page 37: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<7. Operation> 7-2

IM 01C27B01-01EN

Orifice

Tap valve(high pressure)

Tap valve(low pressure)

3-valve manifold

Drain valve(high pressure)

Stop valve(low pressure)

Stop valve(high pressure)

Equalizing valve

F0701.ai

Figure 7.1 Liquid Flow Measurement

F0702.ai

Tap valve

Drain valve

Vent plug (Fill plug)

Stop valve

Figure 7.2 Liquid Pressure Measurement

■ Confirm that transmitter is operating properly by integral indicator.

Ifthetransmitterisfaulty,anerrorcodeisdisplayed.

F0703.ai

Self-diagnostic error on integral indicator(Faulity transmitter)

Figure 7.3 Integral Indicator with Error Code

NOTEIfanyoftheaboveerrorsareindicatedonthedisplayoftheintegralindicatororthedeviceconfigurationtool,refertosubsection9.5.3forthecorrectiveaction.

■ Verify and Change Transmitter Parameter Setting and Values

Theparametersrelatedtothefollowingitemsareminimum required to be set for operation, and set at factoryasspecifiedinorder.Confirmorchangetheparameters if needed.• Measurementrange(measurementlower/upperlimit,unit)

• Output(Nonlinearizationmode/Sqrootmode)

7.2 Zero Point AdjustmentAftercompletingpreparationsforoperatingthetransmitter,adjustthezeropoint.Therearetwozeropointadjustingways.

IMPORTANTDonotturnoffthepowertothetransmitterimmediatelyafterperformingazeropointadjustment.Poweringoffwithin30secondsofperformingthisprocedurewillreturnthezeropoint to its previous setting.

Page 38: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<7. Operation> 7-3

IM 01C27B01-01EN

(1) When you can obtain the Low Range Value from the actual measured value of 0% (0 kPa, atmospheric pressure);

■ Using the transmitter’s zero-adjustment screw

Beforeadjustingzeropoint,makesurefollowings.• TheExternalzerotrimparameter(ExternalZeroTrim)is“Trimon”.Fordetails,refertosection8“SettingParameters”.

• Useaslottedscrewdrivertoturnthezero-adjustmentscrew.Turnthescrewclockwisetoincreasetheoutputorcounterclockwisetodecreasetheoutput.

Thezeropointadjustmentcanbemadewitha resolution of 0.01% of the setting range. The degreeofzeroadjustmentsvarieswiththescrewturningspeed;turnthescrewslowlytomakeafineadjustment,quicklytomakearoughadjustment.

■ Using the Device Configuration Tool

Refertosubsection8.3.14“ZeroPointAdjustmentandSpanAdjustment”.

(2) When you cannot obtain the Low Range Value from the actual measured value of 0%;

Adjustthetransmitteroutputvaluematchestotheactualmeasuredvalueobtainedbyprecisepressure measurement equipment.

[Example] Themeasuringrangeof50to250kPa;theactualmeasuredvalueof130kPa.

130–50250–50

Actual measured value= x100=40.0%

■ Using the transmitter’s zero-adjustment screw

Turnthezeroadjustmentscrewtomatchtheoutputsignaltotheactualmeasuredvalue.

■ Using the Device Configuration Tool

Refertosubsection8.3.14”ZeroPointAdjustmentandSpanAdjustment”.

7.3 Starting OperationAftercompletingthezeropointadjustment,followtheproceduresbelowtostartoperation.Steps1)and2)arespecifictothedifferentialpressuretransmitters.

1) Closetheequalizingvalve.2) Graduallyopenthelowpressurestopvalve. Thisplacesthetransmitterinanoperational

condition.3) Afterconfirmingtheoperatingstatus,perform

thefollowing.

IMPORTANT• Closetheterminalboxcoverandtheamplifiercover.Screweachcoverintightlyuntilitwillnotturnfurther.

• Tightenthezero-adjustmentcovermountingscrewtosecurethecover.

7.4 Connecting to the Field Wireless Network

■ Preparation work prior to connecting to a Field Wireless Network

Thistransmitterdoesnotneedtobeconnectedwithaphysicalwire.Insteadofphysicalwiring,itisnecessarytosetthefieldwirelessdevicestocommunicatewithbeforeinstallingthetransmitter.Thisprocedureiscalledaprovisioning.This transmitter supports provisioning via infrared communicationusingaprovisioningdeviceandcanbesecurelyconnectedtoanetwork.Iftheprovisioning information is not set, the transmitter cannotbeconnectedtothefieldwirelessnetwork.

Provisioning:

Provisioningisworktosetthesecurityandnetworkinformationtoenablethetransmittertobeconnectedtothefieldwirelessnetwork.This transmitter supports a provisioning method usinginfraredcommunication.

For details on provisioning using a provisioning device,andprocedureforconnectingthetransmittertotheFieldWirelessNetwork,refertotheUser’sManual,FieldMateVersatileDeviceManagementWizard(IM01R01A01-01E)andYFGW410FieldWirelessManagementStation(IM01W02D01-01EN).

Page 39: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<7. Operation> 7-4

IM 01C27B01-01EN

F0704.ai

within 30cm

Figure 7.4 Provisioning Example

■ Provisioning work

ThissubsectiondescribesprovisioningworkusingFieldMateastheprovisioningdevice.ProvisioningworkperformsprovisioningforeachfieldwirelessdeviceusingFieldMateandaninfraredadapter.IfYokogawa-recommendedinfrareddeviceisusedforprovisioning,distancebetweenthetransmitterglasswindowandtheinfrareddeviceshouldbewithin30cm.FordetailsofYokogawa-recommendedinfrareddevice,refertosubsection9.2“CalibrationInstrumentsSelection”.Performthefollowingprovisioningtasks.

• Setting provisioning information• Creatingaprovisioninginformationfile

1) Settingprovisioninginformation SetthedevicetagandnetworkIDusinga

FieldMateprovisioningfunction.Thedevicetag,networkID,andjoinkeyaresetintheFieldWirelessDevice.ItisnotnecessarytoinputajoinkeybecauseFieldMateautomaticallygenerates it.

Settingdevicetag ThedevicetagisusedfortheusertorecognizetheFieldWirelessDevice.

SettingnetworkID ThisisthenetworkIDforthefieldwirelessnetworktowhichthefieldwirelessdeviceisconnected.Setavaluefrom2to65535.

ThefieldwirelessdeviceisconnectedtothefieldwirelessnetworkcorrespondingtothenetworkIDsetbyprovisioningwork.

2) Creatingaprovisioninginformationfile Thefollowingprovisionedinformationisstored

intheprovisioninginformationfile.

• NetworkID• Devicetag• EUI64• Joinkey• Provisioner(nameoftheuserwhoperformedprovisioningworkbyFieldMate)

• Date(TimeanddatewhenprovisioningwasperformedbyFieldMate)

ThisprovisioninginformationfileisrequiredtoloadfromtheFieldWirelessConfiguratortotheFieldWirelessIntegratedGateway.Storethefilecarefully.

■ Connecting to a field wireless network

Theactionafterinstallingthebatterypackorturningonthepowervariesdependingonthesilencesetting.Mountingthebatterypackorturningonthepowerautomaticallystartsasearchforthefieldwirelessnetwork.WhentheFieldWirelessIntegratedGatewayisfound,theinstrumententersthejoinstatus.Whenthefieldwirelessgatewayisnotfoundandaspecifiedtimebasedonthesilencemodehaselapsed,acycleofaone-hourpauseandsix-minutessearchisrepeateduntiltheinstrumentcanjointhefieldwirelessnetwork.Fordetailsontheproceduretoswitchtosilencemode,refertosubsection8.3.17“SwitchingtoSilenceMode.”

F0705.ai

Mounting battery pack or turning on the power

Boot

Infrared communication

Pause (b)Search failure for the specified time

Infrared communication 1 hour

passedSearch failure for 6 minutes

Ready 2: Searching (b)

(Connect)(Connect)

Confirm connecting status: Join (c)

(Publish)Operation (d)

Deep sleep setting

(Disconnect)(Disconnect)

Ready 1: Searching (b)

Deep sleep (a)Infrared communication

Figure 7.5 Wireless Connection Process

Page 40: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<7. Operation> 7-5

IM 01C27B01-01EN

(a) Deepsleep

F0706.ai

(b) Readyandpause

F0707.ai

(c) Confirmconnectingstatus

F0708.ai

(d) Join

F0709.ai

NOTEIfthetransmittersearchestheFieldWirelessNetworkforlongtimeatlowambienttemperaturecondition,sometimeserror“AL.70LOWBAT”isdisplayedontheIntegralIndicator.Eventhoughusingnewbatteries,itcanoccur.Itoccursbecauseofbatterycharacteristics.AfterjoiningtotheFieldWirelessNetwork,thiserrorwillbeclearedwithinonehourifbatteryhasnofailure.

7.5 Shutting Down the Transmitter

Shutdownthetransmitterasfollows.

1)Turnoffthepowerorremovethebatterypackor set the transmitter to deep sleep mode by the DeviceConfigurationTool.

2)Closethelowpressurestopvalve.3)Opentheequalizingvalve.4)Closethehighpressurestopvalve.5)Closethehighpressureandlowpressuretap

valves.

NOTE• Whenevershuttingdownthetransmitterforalongperiod,removeanyprocessfluidthatis in the impulse piping and in the transmitter pressure-detectorsection.

• TheequalizingvalvemustbeleftOPEN.• Refertosubsection9.4.6“ReplacingtheBatteryPack”forthebatterypackremoving.

• Whenstoringtheinstrumentwithabatterypackinserted,itisrecommendedtoputtheinstrumentintodeepsleepmodetoconservebatterypower.Fordetailsonhowtoswitchtodeepsleepmode,refertosubsection8.3.16“SwitchingtotheDeepSleepMode.”

Page 41: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<7. Operation> 7-6

IM 01C27B01-01EN

7.6 Venting or Draining Transmitter Pressure-detector Section

Sincethistransmitterisdesignedtobeself-drainingandself-ventingwithverticalimpulsepipingconnections,neitherdrainingnorventingwillberequirediftheimpulsepipingisconfiguredappropriately for self-draining or self-venting operation.

Ifcondensate(orgas)collectsinthetransmitterpressure-detectorsection,themeasuredpressuremaybeinerror.Ifitisnotpossibletoconfigurethepipingforself-draining(orself-venting)operation,youwillneedtoloosenthedrain(vent)screwonthetransmittertocompletelydrain(vent)anystagnatedliquid(gas.)Afterventingordraining,fastenthedrain(vent)screwonthetransmitter.

IMPORTANTDrainingcondensateorbleedingoffgasdisturbsthe pressure measurement, this should not be donewhentheloopisinoperation.

7.6.1 Draining Condensate1) Graduallyopenthedrainscrewordrainplug

anddrainthetransmitterpressure-detectorsection.(Seefigure7.7.)

2) Whenallaccumulatedliquidiscompletelyremoved,closethedrainscrewordrainplug.

3) Tightenthedrainscrewtoatorqueof10N·m,and the drain plug to a torque of 34 to 39 N·m.

WARNING

Sincetheaccumulatedliquid(orgas)maybetoxicorotherwiseharmful,takeappropriatecaretoavoidcontactwiththebody,orinhalationofvapors.

When you loosen the drain screw or drainplug, the accumulated liquid will be expelledin the direction of the arrow.

F0710.ai

Drain screw

Drain plug

Figure 7.6 Draining the Transmitter

7.6.2 Venting Gas1) Graduallyopentheventscrewtoventgasfrom

thetransmitterpressure-detectorsection.(Seefigure7.8.)

2) Whenthetransmitteriscompletelyvented,closetheventscrew.

3) Tightentheventscrewtoatorqueof10N·m.

WARNING

Sincetheaccumulatedliquid(orgas)maybetoxicorotherwiseharmful,takeappropriatecaretoavoidcontactwiththebody,orinhalationofvapors.

When you loosen the vent screw, the gasescpes in the direction of the arrow.

F0711.ai

Vent screw

Vent screw

Figure 7.7 Venting the Transmitter

Page 42: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-1

IM 01C27B01-01EN

8. Setting ParametersThistransmittercanremotelyhandlerangechanges,TagNo.setup,monitoringofself-diagnosticresults,andZeroPointAdjustment,etc.accordingtocommunicationwiththefieldwirelessconfigurationtoolorthedeviceconfigurationtool.

8.1 Environment for parameter setting

Afterinstallingthebatterypackorturnonthepowerperform provisioning and have the transmitter join thefieldwirelessnetwork.ThistransmittersupportstheOOB(out-of-band)methodusingtheinfraredcommunicationasaprovisioning method.RefertoSubsection7.4“ConnectingtotheFieldWirelessNetwork”fordetailsoftheprovisioning.

F0801.ai

Infrared port

Figure 8.1 Infrared port of the transmitter

8.2 Preparing Software8.2.1 Softwares for the Field Wireless

Configuration Tool and the Device Configuration Tool

Beforeusingthedeviceconfigurationtool,confirmthatCF/DDandDeviceDTMforyourtransmitter(wirelessEJX)areinstalledinthedeviceconfigurationtool.RefertothefollowingwebsiteforthelatestinformationonCF/DDandDeviceDTM.<http://www.yokogawa.com/>

CF (Capabilities File)/DD (Device Description)

ACFfilecontainsinformation,suchasthevendorofthefielddevice,itsmodelandrevision,availabletypesofprocessdata(flowrate,temperature,pressure,etc.),andnumberofdataitems.ADDfilecontainstheinformationonparameters,suchasdatastructuresandattributes.

DeviceDTM

DeviceDTM(DeviceTypeManager)isdriversoftwareforfielddevicesprovidedbasedontheFDT(FieldDeviceTool)technology.

Thefieldwirelessconfigurationtoolorthedeviceconfigurationtoolallowsconfirmingthedeviceinformation. RefertoSubsection9.2“CalibrationInstrumentsSelection”forthefieldwirelessconfigurationtoolorthedeviceconfigurationtoolofourrecommendation.

8.2.2 Software DownloadSoftwaredownloadfunctionpermitstoupdatewirelessfielddevicesoftwareviaISA100.11awirelesscommunication.Fordetails,refertoYFGW410FieldWirelessManagementStation(IM01W02D01-01EN).

8.3 Setting Parameters8.3.1 Parameter Usage and SelectionBeforesettingaparameter,pleaseseethefollowingtableforasummaryofhowandwheneachparameter is used.

IMPORTANTAftersettingandsendingdatawiththefieldwirelessconfigurationtoolorthedeviceconfigurationtool,wait30secondsbeforeturningoffthetransmitter.Ifitisturnedofftoosoon,thesettingswillnotbestoredinthetransmitter.

Page 43: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-2

IM 01C27B01-01EN

Table 8.1 Parameter Usage and Selection

Item DescriptionTag No SetsthetagNo.asDeviceTag(SoftwareTag).Sixteencharacters

(alphanumericcharacters,including-and•)canbeset.Output Theprocessvariableandthediagnosticresultcanbeoutput.

Eitherorallofdifferentialpressure/pressure(AI1:ProcessValue),staticpressure(AI2:ProcessValue),temperature(AI3:ProcessValue)ofcapsuleoramplifierandself-diagnosticinformation(UAPMO:DiagnosticStatus)canbesettotheoutput

Range Adjusttherangecorrespondingfor0%to100%.

Theunitoftherange,inputvalueat0%(LRV)andinputvalueat100%(URV)isset.Note: LRVandURVcanbesetwithintherangeof-32000to32000.

Dampingtimeconstant DampingtimeconstantisusedtoreducethelargefluctuationofpressuresignalandgivenbyeachProcessValueFilterTimeparameterfordifferentialPressure/pressure(AI1)andStaticpressure(AI2).

Outputsignalandintegralindicatormode Setsmodeforoutputsignalandintegralindicatorto“linearmode”(proportionaltoinputdifferentialpressure)orto“Squarerootmode”(proportionaltoflow).

Outputsignallowcutmode Usedmainlytostabilizeoutputnear0ifoutputsignalisthesquarerootmode.Twomodesareavailable:forcingoutputto0%forinputbelowaspecificvalue,orchangingtoproportionaloutputforinputbelowaspecificvalue.

Integralindicatorrangeofscaleandunit Setsoneofdifferentialpressure/pressurevalue,staticpressurevalue,ortemperaturevaluefortheintegralindicatorscale.Note: LRVandURVcanbesetwithintherangeof-32000to32000.

Unit for displayed temperature Sets a temperature unit to be displayed.Unitfordisplayedstaticpressure SetsapressureunitforthestaticpressuretobedisplayedDirectionofimpulsepipingconnection(whichishighpressure,LsideorRside)

Usedwhereinstallationconditionsmakesitimperativetoconnecthighpressuresideimpulselinetolowpressuresideoftransmitter.

Normally,correspondbyreplacingimpulseline,andusethisfunctiononlywhenunavoidable.

Rangewithactualinputapplied Rangecorrespondingfor0%to100%signalissetwithactualinputapplied.

Theoutputsettingcanbedonejust100%touser’sreferencepressureoutput.

However,whenshippingit,thecalibrationisdoneinhighaccuracyasforDPharp. Please do the span setting by a usual range setting.

Zero Point Adjustment and Span Adjustment Handle Zero Point Adjustment and Span Adjustment.

TherearetwomethodsofZeroPointAdjustment,usingexternalzero-adjustmentscrewandusingthedeviceconfigurationtool.

Reset adjustment Theamountoftheadjustmentsetbyusercanbecleared.Softwarewriteprotect Prohibitwritingthesettingdata.Operational mode Settheoperationalmodeofthesensorandintegralindicator,etc.Note: Someoftheparametersettingsareinthedialogueformcalledmethod,theon-lineinstructionsyoucanconfiguretheparameters

easily.

8.3.2 Function Block and Menu Tree

(1) Function Block

Thefunctionofthistransmitterisshownbelow.Aspecificfunctionmightnotbeabletobeusedaccordingtothefieldwirelessconfigurationtoolused.Whenthefieldwirelessconfigurationtoolofourrecommendationisused,thesoftware

attachedtotheFieldWirelessIntegratedGatewayisnecessaryforsettingthedottedlinepart.RefertoSubsection9.2“CalibrationInstrumentsSelection”forthefieldwirelessconfigurationtoolofourrecommendation.

Page 44: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-3

IM 01C27B01-01EN

• Configuration• Diagnostics• Alerts• Power Status• Identification

(UAPMO)

• APP Download

(UDO)

• Configuration• Others

(CO)

• Block Info• Configuration/ Calibration

(TRANSDUCER)

• UAPMO• UDO• CO• TRANSDUCER• AI1 DP• AI2 SP• AI3 Temp

Online Menu

• UAP Option• Hardware Write Protect• Static Revision• Reset Energy Left• Radio Silence• Energy Harvest Type

(Configuration)

• Diagnostic Status• Diagnostic Status Detail.1• Diagnostic Status Detail.2• Diagnostic Switch• Diagnostic Configuration

(Diagnostics)

• Version Revision• CTS Version• ITS Version• Identification Number

(Identification)

• DESCRIPTION• STATE• MAX_BLOCK_SIZE• LAST_BLOCK_DOWNLOADED• ERROR_CODE

(APP Download)

• COMM_ENDPOINT• COMM_CONTRACT• PUB_ITEM_MAX• PUB_ITEM_NUM• PUB_ITEM

(Configuration)

• REVISION(Others)

• Network address of remote endpoint• Transport layer port at remote endpoint• Object ID at remote endpoint• Stale data limit• Data publication period• Ideal publication phase• PublishAutoRetransmit• Configuration status

(COMM_ENDPOINT)

• ContractID• Contract_Status• Actual_Phase

(COMM_CONTRACT)

• ObjectID• AttributeID• AttributeIndex• Size

(PUB_ITEM)

• Tag Description(Block Info)

• Auto Recovery• Model• Sensor Serial Number• Measurement Rate• Measurement Mode• Wireless Status• Display Selection

(Configuration/Calibration)

F0802-1.ai

• Energy Left• Power Supply Status• Power Supply Voltage

(Power Status)

• Others

• Display Unit1

• EJX Key

• Test Key 2• Test Key 1

• Test Key 3

• Unit Sel1

• XD Filter• LCD Intermittent Time

• Special Order ID• LCD Mode

• Special Cmd(Others)

• Other Faults Alert• Faults Non-compliance Alert• Faults Process Influence Alert• Simulation Active Alert• Soft Update Incomplete Alert• Power Low Alert• Power Critical Low Alert• Fault Prediction Alert• Environmental Conditions Alert• Outside Sensor Limits Alert• Out of Service Alert• Calibration Problem Alert• Faults Sensor or Actuator Alert• Faults Electronics Alert

(Alerts)

Page 45: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-4

IM 01C27B01-01EN

• Block Info• Block Mode• Dynamic Variables• Configuration• Calibration• Others

(AI1 DP)• Tag Description

(Block Info)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode )

• Process Value• Simulation

(Dynamic Variables)

• Simulate Switch• Transducer Value• Simulate Value

(Simulation)

• Process Value.Status• Process Value.Value **

(Process Value)

• Block Mode• Concentrator OID• Scale *• Process Value Filter Time

(Configuration) (Block Mode)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Scale)

• Scale.EU at 100% *• Scale.EU at 0% *• Scale.Units Index *• Scale.Decimal *

• Upper Limit• Lower Limit• PV Range *• Linerization Type *• Flow Constant *• Lower Cutoff• Low Cut Mode *• H/L Swap *• T Zero Cmp *• Temp Zero *• Temp Select *

(Others) (PV Range)

• PV Range.EU at 100% *• PV Range.EU at 0% *• PV Range.Units Index *• PV Range.Decimal *

F0802-2.ai

• Block Mode• Cal Cmd *• Cal Status• Calibration Highest Point *• Calibration Lowest Point *• Calibration Minimum Span• External Zero Trim *

(Calibration) (Block Mode)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

• Transducer Value. Status• Transducer Value. Value

(Transducer Value)

• Simulate Value. Status• Simulate Value. Value

(Simulate Value)

Online Menu (continued)

*: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoO/S(OutofService).**: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoManual.

Page 46: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-5

IM 01C27B01-01EN

• Block Info• Block Mode• Dynamic Variables• Configuration• Others

(AI2 SP)• Tag Description(Block Info)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode )

• Process Value• Simulation

(Dynamic Variables)

• Simulate Switch• Transducer Value• Simulate Value

(Simulation)

• Process Value.Status• Process Value.Value **

(Process Value)

• Block Mode• Concentrator OID• Scale *• Process Value Filter Time

(Configuration) (Block Mode)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Scale)

• Scale.EU at 100% *• Scale.EU at 0% *• Scale.Units Index *• Scale.Decimal *

• Upper Limit• Lower Limit• PV Range *• Linerization Type *• Flow Constant *• Lower Cutoff• Cal Cmd *• Cal Status• Calibration Highest Point *• Calibration Lowest Point *• Calibration Minimum Span• Static Pres Type *• SP Select *

(Others) (PV Range)

• PV Range.EU at 100% *• PV Range.EU at 0% *• PV Range.Units Index *• PV Range.Decimal *

F0802-3.ai

• Transducer Value. Status• Transducer Value. Value

(Transducer Value)

• Simulate Value. Status• Simulate Value. Value

(Simulate Value)

Online Menu (continued)

*: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoO/S(OutofService).**: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoManual.

Page 47: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-6

IM 01C27B01-01EN

• Block Info• Block Mode• Dynamic Variables• Configuration• Others

(AI3 Temp)• Tag Description(Block Info)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode )

• Process Value• Simulation

(Dynamic Variables)

• Simulate Switch• Transducer Value• Simulate Value

(Simulation)

• Process Value.Status• Process Value.Value **

(Process Value)

• Block Mode• Concentrator OID• Scale *• Process Value Filter Time

(Configuration) (Block Mode)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Scale)

• Scale.EU at 100% *• Scale.EU at 0% *• Scale.Units Index *• Scale.Decimal *

• Sensor Range• Tertiary Value Sel *

(Others) (Sensor Range)• Sensor Range.EU at 100%• Sensor Range.EU at 0%• Sensor Range.Units Index **• Sensor Range.Decimal **

F0802-4.ai

• Transducer Value. Status• Transducer Value. Value

(Transducer Value)

• Simulate Value. Status• Simulate Value. Value

(Simulate Value)

Online Menu (continued)

*: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoO/S(OutofService).**: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoManual.

Page 48: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-7

IM 01C27B01-01EN

(2) Menu TreeThemenutreeofthedeviceconfigurationtoolofourrecommendationisshownbelow.RefertoSubsection9.2“CalibrationInstrumentsSelection”forthedeviceconfigurationtoolofourrecommendation.

• UAPMO• TRANSDUCER• AI1 DP• AI2 SP• AI3 Temp

• Device Configuration• Diagnostic• Process Variable

(Device Configuration)Menu (Online)

F0803-1.ai

• Configure/Setup(UAPMO)

• UAP Option• Hardware Write Protect• Static Revision• Reset Energy Left• Radio Silence• Energy Harvest Type

(Configuration)

• Version Revision• CTS Version• ITS Version• Identification Number

(Identification)

• Configure/Setup(AI1 DP)

• Block Mode• Cal Cmd *• Cal Status• Calibration Highest Point• Set Calibration Highest Point *• Calibration Lowest Point• Set Calibration Lowest Point *• Calibration Minimum Span• External Zero Trim *

(Calibration)• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode)

• Upper Limit• Lower Limit• PV Range *• Linerization Type *• Flow Constant *• Lower Cutoff• Low Cut Mode *• H/L Swap *• T Zero Cmp *• Temp Zero *• Temp Select *

(Others)• PV Range.EU at 100% *• PV Range.EU at 0% *• PV Range.Units Index *• PV Range.Decimal*

(PV Range)

• Configure/Setup(TRANSDUCER)

• Auto Recovery• Model• Sensor Serial Number• Measurement Rate• Measurement Mode• Wireless Status• Display Selection• LCD Mode• Special Order ID• Unit Sel1• Display Unit1• LCD Intermittent Time• XD Filter• EJX Key• Test Key 1• Test Key 2• Test Key 3

(Configuration/Calibration)• Tag Description(Block Info)

• Special Cmd(Others)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode)

• Block Mode• Concentrator OID• Scale *• Process Value Filter Time

(Configuration)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode)

• Scale.EU at 100% *• Scale.EU at 0% *• Scale.Units Index *• Scale.Decimal *

(Scale)

• Tag Description(Block Info)

• Other Faults Alert• Faults Non-compliance

Alert• Faults Process Influence

Alert• Simulation Active Alert• Soft Update Incomplete

Alert• Power Low Alert• Power Critical Low Alert• Fault Prediction Alert• Environmental

Conditions Alert• Outside Sensor Limits

Alert• Out of Service Alert• Calibration Problem

Alert• Faults Sensor or

Actuator Alert• Faults Electronics Alert

(Alerts)

*: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoO/S(OutofService).

Page 49: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-8

IM 01C27B01-01EN

• Configure/Setup(AI2 SP)

F0803-2.ai

• Tag Description

(Block Info)

• Upper Limit• Lower Limit• PV Range *• Linerization Type *• Flow Constant *• Lower Cutoff• Cal Cmd *• Cal Status• Calibration Highest Point• Set Calibration Highest Point *• Calibration Lowest Point • Set Calibration Lowest Point *• Calibration Minimum Span• Static Pres Type *• SP Select *

(Others)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode)

• Sensor Range.EU at 100%• Sensor Range.EU at 0%• Sensor Range.Units Index *• Sensor Range. Decimal *

(Sensor Range)

(Block Mode)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(AI3 Temp) (Block Info)• Tag Description

• Sensor Range• Tertiary Value Sel *

(Others)

• Block Mode• Concentrator OID• Scale *• Process Value Filter Time

(Configuration)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode)

• Scale.EU at 100% *• Scale.EU at 0% *• Scale.Units Index *• Scale.Decimal *

(Scale)

• PV Range.EU at 100% *• PV Range.EU at 0% *• PV Range.Units Index *• PV Range. Decimal *

(PV Range)

• Configure/Setup

• Block Mode• Concentrator OID• Scale *• Process Value Filter Time

(Configuration)

• Mode.Target• Mode.Actual• Mode.Permitted• Mode.Normal

(Block Mode)

• Scale.EU at 100% *• Scale.EU at 0% *• Scale.Units Index *• Scale.Decimal *

(Scale)

Menu (Online) (continued)

Device Configuration(continued)

*: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoO/S(OutofService).

Page 50: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-9

IM 01C27B01-01EN

• Transducer Value. Status• Transducer Value. Value

• UAPMO

Menu (Online)(continued)

(Diagnostic)

F0803-3.ai

• Device Diagnostics

(UAPMO)

• Diagnostic Status• Diagnostic Status Detail.1• Diagnostic Status Detail.2• Diagnostic Switch• Diagnostic Configuration

(Diagnostics)

• Energy Left• Power Supply Status• Power Supply Voltage

(Power Status)

• AI1 DP• AI2 SP• AI3 Temp

(Process Variable)

• Process Variable

(AI1 DP)

• Process Value• Simulation

(Dynamic Variables)

• Process Value.Status• Process Value.Value **

(Process Value)

• Simulate Switch• Transducer Value• Simulate Value

(Simulation)(Transducer Value)

• Simulate Value. Status• Simulate Value. Value

(Simulate Value)

• Process Variable

(AI2 SP)

• Process Value• Simulation

(Dynamic Variables)

• Process Value.Status• Process Value.Value **

(Process Value)

• Simulate Switch• Transducer Value• Simulate Value

(Simulation)

• Process Variable

(AI3 Temp)

• Process Value• Simulation

(Dynamic Variables)

• Process Value.Status• Process Value.Value **

(Process Value)

• Simulate Switch• Transducer Value• Simulate Value

(Simulation)

• Transducer Value. Status• Transducer Value. Value

(Transducer Value)

• Simulate Value. Status• Simulate Value. Value

(Simulate Value)

• Transducer Value. Status• Transducer Value. Value

(Transducer Value)

• Simulate Value. Status• Simulate Value. Value

(Simulate Value)

• Diagnostic.Other Faults• Diagnostic.Faults Non-Compliance• Diagnostic.Faults Process Influence• Diagnostic.Simulation Active• Diagnostic.Soft Update Incomplete• Diagnostic.Power Low• Diagnostic.Power Critical Low• Diagnostic.Fault Prediction• Diagnostic.Environmental Conditions• Diagnostic.Outside Sensor Limits• Diagnostic.Out of Service• Diagnostic.Calibration Problem• Diagnostic.Faults Sensor or Actuator• Diagnostic.Faults Electronics

(Diagnostic Configuration)

*: Whenthedataoftheseparametersisrewritten,itisnecessarytosettheoperationalmodeoftheblocktoO/S(OutofService).

Page 51: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-10

IM 01C27B01-01EN

8.3.3 Parameters for Wireless Communication

(1) Network Information

Concentratorobjectblock:Configuration

Allowsconfirmingthenetworkinformation.

(2) Update Time

COblock:Datapublicationperiod

Setstheupdatetimevalueto0.5to3,600seconds.Thesettingaffectsthebatterylife.Whenupdatetimeisset0seconds,thetransmitterisstoppedtoupdateprocessvariablesbywayofthefieldwirelessnetwork.Andthetransmittercontinuestomeasureprocessvariableswithspecialintervaltimeinternally.

(3) Measurement Mode

TRANSDUCERblock:MeasurementMode

Thesettingaffectsthebatterylife;itbecomesshorterinthecontinuousmode.Whentheupdateperiodissetto1secondorlessinintermittentmode,themodeiscontinuousmode,regardless of the measurement mode and the display.

(4) Measurement Rate

TRANSDUCERblock:MeasurementRate

Reads the measurement rate value from 0.5 to 3600seconds.Theshorterthemeasurementperiod, the shorter the battery life.

(5) Remaining battery life

UAPMOblock:EnergyLeft

The number of days of remaining battery life is indicatedassumingthatatransmitterhasbeenworkingunderambienttemperatureconditionas23degreesCelsius.Ittakesseveraldaysfortheindicatedvaluetobestabiilzedafterthepoweronandinitializationoftheremainingbatterylife.

UAPMOblock:ResetEnergyLeft

Whenchangingbatteries,theremainingbatterylifeisinitializedbyResetEnergyLeftparameter.

(6) LCD display

ThefollowingstepsdescribehowtosetLCDdisplay.

1.On/Offofdisplay When“Enable”inLCDModeisselected,theLCDdisplaysasetofscreenstobeshownandturnsoffforthespecifiedtimebasedonLCDIntermittentTime,andthedisplaykeepsthecyclerepeatedly.NotselectingthisparameterturnstheLCDoff.

2.On/Offofcontinuousdisplaymode When“Enable”issettoLCDModeandzerois

set to LCD Intermittent Time, the LCD displays continuously.

3.On/Offofbargraph Select“LCDBargraphON”inLCDModewhen

the bar graph is required.

Whenthewirelessconnectionprocessisinthestatusof“ready,”“pause,”or“join,”theLCDdisplaystays on regardless of the status in LCD Mode.

NOTEWhenthedevicedetectsAL01andAL02,theLCD display stays on regardless of the status in LCD mode. See Table 9.3 and 9.4 Error Message Summary for details.

8.3.4 Tag and Device InformationIfthesearespecifiedwhenordering,thedesignatedTagNo.anddeviceinformationaresetandshipped.TagNo.anddeviceinformationcanbecheckedasfollows.

• ProceduretocallupthetagNo.anddeviceinformation

- DeviceTag(SoftwareTag) Thisisspecifiedwhenwritingcharacters(upto16characters)ofamplifiersTAGthatdifferfromcharactersspecifiedinTagNo.

Refertosection7.4“ConnectiontotheFieldWirelessNetwork”forconfirmation.

- TagDescription This is a universal parameter to store the commentthatdescribesthecontentofthetaglocatedintheTRANSDUCERandAIblocks.

TheAI1,AI2,andAI3blocksoftheAIblockscorrespondtothedifferentialpressure/pressure,staticpressure,andtemperature,respectively.

Page 52: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-11

IM 01C27B01-01EN

• Whenchangingthedeviceinformation,inputtheinformationbasedonthefollowinglimitationonthenumberofcharacters.

- Messagefunction(upto32characters) TRANSDUCERblock:TagDescription AI1-AI3block:TagDescription

8.3.5 UnitTheunitparameterissetatthefactorybeforeshipmentifspecifiedatthetimeoforder.Followtheprocedurebelowtochangetheunitparameter.

• ProceduretocalluptheUnitdisplay(UnitsIndex)

Al1-Al3block:SCALE:UnitsIndex

TochangetheUnitdisplay,choosedesiredunitamongthelistofdisplayedunitselectingAI1blockasforthedifferentialpressure/pressure,AI2asforthestaticpressureandAI3blockasfortemperatureintheAIblocks.

8.3.6 Range ChangeTherangevaluesarefactory-setasspecifiedbythecustomer.Tochangetherange,followthestepsbelow.

The measurement span is determined by the upper andlowerrangevalues.Inthismethod,theupperandlowerrangevaluescanbesetindependently,andthespanchangesaccordingtotherangelimitvalues sent to the transmitter.

• ProceduretocallupthePVRangedisplay. AI1,Al2block:PVRange

SelecttheAI1blockforthedifferentialpressure/pressureandtheAI2blockforthestaticpressure,thenselect“EUat0%”and“EUat100%”displayedinthePVRangeparameters,andinputthelowerrangeandupperrangevaluesfortherange,respectively.

8.3.7 Output ModeTheoutputmodeoftheoutputsignalcanbesetasNoLinearizationorSqroot.

• ProceduretocalluptheLinearizationTypedisplay

AI1block:LinearizationType

SelecttheAI1blockforthedifferentialpressureandthenselectNoLinearizationorSqrootfortheLinearizationTypeparameter.

8.3.8 Output Signal Low Cut Mode SetupLowcutmodecanbeusedtostabilizetheoutputsignalnearthezeropoint.(Thereis10%ofhysteresisatonlypointoftransitionfromlowtohigh)

[Setup Low Cut Value]

• ProceduretocalluptheLowCutoff*display AI1block:LowCutoff*

Example:setupLOW_CUTofoutputto15%

*LowCutoff=(“Euat100%”-“Euat0%”)×0.15+“Euat0%”

[Setup Low Cut Mode]

• ProceduretocalluptheLowCutModedisplay AI1block:LowCutMode

Example:Lowcutat20%

(%)50

20

0 50 (%)

For low cut in Linear mode For low cut zero mode

[ sq root output ]

Example: Low cut 20%

Input

(%)50

20

0 50 (%)

Example: Low cut 20%

F0804.ai

(%)50

20

0 50 (%)

For low cut in Linear mode

[ Linear output ]

Example: Low cut 20%

Out

put

Out

put

Input

Input

Out

put

Figure 8.2 Low Cut Mode

Thelowcutpointhashysterisissothattheoutputaroundthepointisbehavedasbelowfigure.

<Example>Output mode: LinearLowcutmode:ZeroLowcut:20.00%

Output

Setting range:0 to 20%

Input0%

(20%)

2%

Low cutpoint

Hystrersis fixed at 10%of the cut point

F0805.ai

Page 53: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-12

IM 01C27B01-01EN

8.3.9 Impulse Line Connection Orientation Setup

Thisfunctionreversestheimpulselineorientation.

FollowtheprocedurebelowtoassignthehighpressureimpulselineconnectiontotheLsideofthetransmitter.

• ProceduretocalluptheH/LSwapdisplay TRANSDUCERblock:H/LSwap

SelectReverseamongtwochoices(Normal/Reverse)inaH/LSwapparameter.

Normalischosenatthetimeofshipment.

8.3.10 Integral Indicator Display ModeItiseasytocheckontheLCDwhetherNonLinearizationorSqrootissetintheLinearizationTypeparameterselectedintheoutputmodefortheoutput signal. WhenLinearissetintheLinearizationTypeparameter,“√”isdisplayedontheintegralindicator.

8.3.11 Integral Indicator Scale SetupThefollowingthreedisplaysareavailablefortheintegralindictor:differentialpressure/pressure,staticpressure,andtemperature.Thefollowingthreevariablescanbedisplayedontheintegralindicator:%ofdifferentialpressurerange,%ofstaticpressurerange,and%oftemperaturerange.

Available displays Descriptionand related parameters

% of range(PRES%)

Indicatesinputpressurein–10to110% range depending on the set range(LRV and URV).PRES % 45.6 %

%ofstaticpressurerange(SP%) *1

Indicatesinputstaticpressurein–10 to 110% range depending on thesetrange(SP LRV and SP URV).SP % 52.6 %

*1: Availablefordifferentialpressuretransmitter.

Followtheproceduredescribedin(1)to(2)belowtosettheintegralindicator.

(1) Display Selection

DisplaysettoDisplaySelectionisdisplayedontheintegralindicator.

• ProceduretocalluptheDisplaySelectiondisplay

TRANSDUCERblock:DisplaySelection

TheDisplaySelectionparameterenablesthedifferentialpressure/pressure(AI1block),staticpressure(AI2block),andtemperature(AI3block)tobedisplayedontheLCD.Selectwhetherornottoenableeachblocktobedisplayed

(2) Cyclic Display

InformationintheAI1toAI3blockscanbedisplayedcyclicallyaccordingtothedisplayOn/Offsettingforthedifferentialpressure(AI1block),staticpressure(AI2block),andtemperature(AI3block)selectedintheDisplaySelectionparameter.

8.3.12 Unit for Displayed TemperatureWhen the instrument is shipped, the temperature units are set to C(Centigrade).Followtheprocedurebelowtochangethissetting.

• ProceduretocalluptheSensorRange.UnitsIndex display

AI3block:SensorRange.UnitsIndex

Confirmthat°C(degC)isselectedintheSensor Range.Units Index parameter for the temperature(AI3block).

Note: WhentheunitischangedbySensorRange.UnitsIndexparameterintemperature(Al3block),unitsofcapsuletemperatureisalsochanged.

Page 54: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-13

IM 01C27B01-01EN

8.3.13 Unit for Displayed Static PressureFollowtheproceduretochangethestaticpressureunit.Changingthisparameteralsochangestheunitforthestaticpressuredisplay.

• ProceduretocalluptheSensorRange.UnitsIndex display

AI2block:SensorRange.UnitsIndex

ConfirmthatKPaisselectedintheSensorRange.UnitsIndexparameterforthestaticpressure(AI2block).

Monitoringthehighorlowstaticpressureofthecapsuledependsonthesettingofparameter ‘SPSelect.’

• ProceduretocalluptheSPSelectdisplay AI2block:SPSelect

SelectHighorLowintheSPSelectparameterforthestaticpressure(AI2block).

TypeofstaticpressureissetAbsolutepressure(Abs)atshipment.Whenchangingmonitoringtypeofstaticpressure,Followbelowprocedure.

• ProceduretocalluptheStaticPressTypedisplay

AI2block:StaticPressType

Selectgaugepressure(Gauge)orabsolutepressure(Abs)intheStaticPressTypeparameterforthestaticpressure(AI2block).

8.3.14 Zero Point Adjustment and Span Adjustment

EachEJX-BSeriesDifferentialPressure/PressureTransmitterischaracterizedbyfactory.Buttherearesomeerrorscausedbyenvironmentandinstalled posture.

ThereareZeroandSpanAdjustmentstofine-tunethose errors. Zero Adjustment is adjustment for one point to adjust the bottom value of the measurement range as 0 % of output..

TheSpanAdjustmentdefinesinputandoutputcharacteristicbetweentwopointsthat’sonesideassumed as standard. Thisisusedwhenthereisdoubtofspandriftorwhenitisimpossibletomakezeroatabsolutepressurewithadjustmentforuser’spressurestandard.

(1) Zero Point Adjustment

a. To set 0% at current input, perform following procedure.

Thismethodisusedonlywhenthepressureatbottomofmeasurementrangeiszero.

• Proceduretocallupthelowerlimitadjustmentparameter(CalibrationLowestPoint).

AI1block:CalibrationLowestPoint

Set0toCalibrationLowestPointparameterfordifferentialpressure(Al1block).

• Proceduretocallupthecalibrationadjustmentparameter(CalCmd).

AI1block:CalCmd:CAL_LOW

LowerlimitischangedbyusingCalCmdparameterfordifferentialpressure/pressure(Al1block).

• Proceduretocallupthecalibrationstatusparameter(CalStatus).

AI1block:CalStatus

ConfirmthecalibrationstatusofCAL_SUCCESS(1)usingtheCalStatusparameter.

b. To match current input and output value, follow procedure

Liketanklevelmeasurementthatisimpossibletosetactualleveltozero,outputvalueisadjustmenttoactuallevelbyothermeasurementusingglassgage.

Example: DifferentialPressureandPressureTransmitter’sspanis0to25.00kPa,currentlevelis13.50kPa,currentoutputis13.83kPa.

• Proceduretocallupthelowerlimitadjustmentparameter(CalibrationLowestPoint).

AI1block:CalibrationLowestPoint.

Settheactuallevelvalueof13.50kPatotheCalibrationLowestPointparameterforthedifferentialpressure(AI1block).ApplyanactualinputandconfirmthevaluespecifiedinCalibrationLowestPointastheoutputvalue.

• Proceduretocallupthecalibrationadjustmentparameter(CalCmd).

AI1block:CalCmd:CAL_LOW

Thepresentoutputischangedfrom13.83kPato13.50kPainCAL_LOWofthedifferentialpressure(AI1block)CalCmdparameter.

Page 55: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-14

IM 01C27B01-01EN

• Proceduretocallupthecalibrationstatusparameter(CalStatus).

AI1block:CalStatus

ConfirmthecalibrationstatusofCAL_SUCCESS(1)usingtheCalStatusparameter.

DPharp

F0806.ai

25.00 kPa

0.00 kPa

Actual level 13.50 kPa

DPharp span: 0~25.00 kPaActual level: 13.50 kPaTransmitter output: 13.83 kPa

Figure 8.3 Tank level measurement

c. Using External Zero-adjustment Screw

ExternalZero-adjustmentparameter(ExternalZeroTrim)cansetpermissionorprohibitiontoadjustmentbyExternalZero-adjustmentScrew.

Set“Trimon”tousetheExternalZero-adjustmentScrew.(“Trimon”atshipment)

Useaslottedscrewdrivertoturnthezero-adjustmentscrew.Equalizethetransmitter,thenturnthescrewclockwisetoincreasetheoutputorcounterclockwisetodecreasetheoutput.Thezeropointadjustmentcanbemadewitharesolutionof0.01%ofthesettingrange.Thedegreeofzeroadjustmentsvarieswiththescrewturningspeed;turnthescrewslowlytomakeafineadjustment,quicklytomakearoughadjustment.

Zero-adjustment Screw

F0807.ai

Figure 8.4 Zero-adjustment Screw

(2) Span Adjustment

SpanAdjustmentisfunctiontochangetheinputandoutputcharacteristicthatassumedthebottomvalue(zeropoint)ofmeasurementrangeastandard.Therefore,performspanadjustment(adjustmentoftheupperlimitvalue)afterzeroadjustment(adjustmentofbottomlimitvalue).

After adding the pressure at point of adjustment and setting pressure value as parameter, the transmitter calculatesquantityofadjustmentandperformsadjustmentautomatically.

• Proceduretocallupthelowerlimitvalueparameter(CalibrationLowestPoint).

AI1block:CalibrationLowestPoint

Setthelowerlimitadjustmentvalueonthedifferentialpressure/pressure(AI1block)CalibrationLowestPointparameterscreen.Applyareferencepressurecorrespondingtothelowerlimitofthemeasurementrangetothedifferentialpressure/pressuretransmitterandconfirmthereferencepressurewhenithasstabilized.

• Proceduretocallupthecalibrationadjustmentparameter(CalCmd).

AI1block:CalCmd:CAL_LOW

ConfirmthelowerlimitofthemeasurementrangeinCAL_LOWofthedifferentialpressure(AI1block)CalCmdparameter.

• Proceduretocallupthecalibrationstatusparameter(CalStatus).

AI1block:CalStatus

ConfirmthecalibrationstatusofCAL_SUCCESS(1)usingtheCalStatusparameter.

• Proceduretocalluptheupperlimitadjustmentparameter(CalibrationHighestPoint).

AI1block:CalibrationHighestPoint

Set the upper limit adjustment value for the differentialpressure(AI1block)CalibrationHighestPointparameter.Applyareferencepressurecorrespondingtotheupperlimitofthemeasurementrangetothedifferentialpressure/pressuretransmitterandconfirmthereferencepressurewhenithasstabilized.

• Proceduretocallupthecalibrationadjustmentparameter(CalCmd).

AI1block:CalCmd:CAL_HIGH

ConfirmtheupperlimitofthemeasurementrangeinCAL_HIGHofthedifferentialpressure/pressure(AI1block)CalCmdparameter.

Page 56: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-15

IM 01C27B01-01EN

• Proceduretocallupthecalibrationstatusparameter(CalStatus).

AI1block:CalStatus

ConfirmthecalibrationstatusofCAL_SUCCESS(1)usingtheCalStatusparameter.

(3) Adjustments for Static Pressure

FortheEJXdifferentialtransmitters,zeropointandspanadjustmentsofstaticpressureisperformedinthesamewayaswiththeprimaryprocessvariable(PV).Adjustmentshouldbeperformedusingthestaticpressure(AI2block)CalCmdparameter.Aftercalibration,confirmthestatusbyusingthestaticpressure(AI2block)CalStatus.

• Proceduretocallupthecalibrationadjustmentparameter(CalCmd).

AI2block:CalCmd

Performdifferentialpressurezero/spanadjustmentbeforestaticpressurezero/spanadjustment.

(4) Reset Adjustment

ResetAdjustmentcleartheamountofadjustment.ResetAjustmentcanbeperformedusingCAL_CLEARofthedifferentialpressure(AI1block)CalCmd parameter for the input pressure and using CAL_CLEARofthestaticpressure(AI2block)CalCmdparameterforthestaticpressure.AfterResetAdjustment,confirmthestatusbyusingCalStatusoftheclearedblock.Theamountofadjustmentmadebytheexternalzero-adjustmentscrewcanberesettotheinitialsettingaswell.

• Proceduretocallupthecalibrationadjustmentparameter(CalCmd).

AI1block:CalCmd:CAL_CLEAR AI2block:CalCmd:CAL_CLEAR

8.3.15 Software Write ProtectHardwarewriteprotectionandsoftwarewriteprotectionfunctionsareavailableforthistransmitter.

• Proceduretocalluptheprotectionsettingparameter(UAPOption)

UAPMOblock:UAPOption

ThefollowingsettingscanbeconfiguredintheUAP Option parameter.- Settingtoenableordisablesoftwarewriteprotection.

- Settingtoenableordisablethehardwarewriteprotectionswitch.

- SettingtoenableordisablechangingthesettingtotheDiagnosticSwitchandDiagnosticConfigurationparameters.

• Proceduretocalluptheprotectionsettingdisplayparameter(HardwareWriteProtect)

UAPMOblock:HardwareWriteProtect

TheHardwareWriteProtectparameterenablestheswitchstatusofhardwarewriteprotectiontobe displayed.

Fortherelationshipbetweenhardwarewriteprotectionandsoftwarewriteprotection,refertosection10.“ParameterSummary.”

Page 57: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-16

IM 01C27B01-01EN

8.3.16 Switching to Deep Sleep ModeWhentheinstrumentwillnotbeusedforalongtime,switchtheinstrumenttodeepsleepmodetoconservebatterypower.Toswitchtodeepsleepmode,followtheprocedurebelow.

• Proceduretocalluptheswitch-to-deep-sleepparameter

TRANSDUCERblock:SpecialCmd

SetDeepSleepmode(Standby)totheSpecialCmd parameter for the TRANSDUCER block.Tostartfromdeepsleepmode,eitherremoveandinsertthebatterypack,orusingtheprovisioningdevicetoolorthedeviceconfigurationtoolviainfraredcommunication.

Incaseoftheexternalpoweredtype,turnoffthepowerandonagain.

CAUTIONAfter setting the deep sleep mode by infrared deviceconfigurationtool,keeptheinfraredportofdeviceawayfromanyotherinfraredsignals.

NOTE• Transmitterbecomesthestopstateaftersettingdeepsleepmodeandcannotreplyanyrequestfromthedeviceconfigurationtoolviawirelesscommunication.

• Forthisreason,thereisthecasethatanerrorisdisplayonthedeviceconfigurationtoolviawirelesscommunication.

• Towakeupfromdeepsleepmode,pleasepullbatterypackandwaitmorethan30secondsbeforeattachingbatterypackorturningonthepower.

8.3.17 Switching to Silence ModeThisisafunctiontopausetheinstrumentwhenitcannotjointhefieldwirelessnetworkafteraspecifiedtimehaselapsed.Thisfunctioniseffectiveinconservingbatterypowerwhen,forexample,theinstallationofthefieldwirelessintegratedgatewayisdelayedcomparedtothatoffieldwirelessdevices.Thedefaultvalueis28800seconds(8hours).Thereafter,acycleofaone-hourpauseandsix-minutesearchisrepeateduntiltheinstrumentcanjointhefieldwirelessnetwork.

• Proceduretocalluptheswitch-to-silenceparameter(RadioSilence)

UAPMOblock:RadioSilence

Set 0 to 231secondsfortheRadioSilenceparameteroftheUAPMOblock.If0isset,theRadioSilenceparameterisinvalid.Tostartfromdeep sleep mode, either remove and insert the batterypack,orusetheprovisioningdevicetoolordeviceconfigurationtoolviainfraredcommunication.

Page 58: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-17

IM 01C27B01-01EN

8.4 Self-Diagnostics8.4.1 Identify Problems by Using the

Device Configuration ToolFirst,checkDiagnosticStatusoftheself-diagnosticresult.

UAPMOblock:DiagnosticStatus

Anyofthefourcategories(Checkfunction,Maintenancerequired,Failure,andOffspecification)accordingtoNAMURNE107*issuppliedtoDiagnosticStatusofeachdiagnosticresult.

Table 8.2 Diagnostic Status

Bits ContentsExample

NAMUR NE107Categorization

Bit31(MSB) F: Failure status ---Bit30 C:Functioncheckstatus ---Bit29 O:Outofspecificationstatus ---Bit28 M:Maintenancerequiredstatus ---Bit27 Faultsinelectronics FBit26 Faultsinsensororactuatorelement FBit25 Installation,calibrationproblem CBit24 Outofservice CBit23 Outside sensor limits OBit22 Environmentalconditionsoutofdevicespecification OBit21 Faultprediction:Maintenancerequired MBit20 Poweriscriticallow:maintenanceneedshort-term MBit19 Powerislow:maintenanceneedmid-term MBit18 Softwareupdateincomplete CBit17 Simulationisactive CBit16 Faultsduetoprocessinfluence FBit15 Faultsduetonon-compliancewithspecifiedoperatingconditions FBit14 Other faults FBit13-Bit08 reserved by WCI ---Bit07-Bit01 vendorspecificarea ---Bit00 Detail information available

1: available0: no available

---

CheckingtheDiagnosticStatuscategoryallowstakingtheproperaction.TheDiagnosticStatuscontentsarecommonforallISAdevices,andthesettingfortheDiagnosticStatuscategorycanbechanged.Forfurtherdetails,refertoDiagnosticStatus Detail. InDiagnosticStatusContentsthatcanbediagnosedbytheEJX,thealertcategorysetinOutofServicecanbechangedtoCheckfunction.Todoso,followoneoftheproceduresbelow.

a)UAPMOblock:UAPOption,selectenable.b)UAPMOblock:DiagnosticConfiguration,changeOutofServicefromFailuretoCheckfunction.

c)UAPMOblock:UAPOption,selectdisable.

ThecontentsofdiagnosticstatusaredefinedeithervalidorinvalidatDiagnosticSwitchparameter.Followtheexamplebelowtochange“OutofService”toinvalid.

a)UAPMOblock:UAPOption,selectenable.b)UAPMOblock:DiagnosticSwitch,turnONTurnoff“OutofService”.OutofService.

c)UAPMOblock:UAPOption,selectdisable.Note:Becarefulwhenchangingthealertcategoryandturning

detectiononandoffasdescribedabove.BesuretosetUAP OPTION to disable again to prevent setting errors.

*: NAMURNE107“Self-MonitoringandDiagnosisofFieldDevices”

InDiagnosticConfigurationsetting,selectonefromthefollowings;F:Failurestatus,C:Functioncheckstatus,O:Outofspecificationstatus,orM:Maintenancerequired status.

Page 59: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-18

IM 01C27B01-01EN

8.4.2 Alert ReportEJX generates alert information related to DiagnosticStatusandautomaticallysendstoafieldwirelessgateway.Tousethisfunction,thefollowingalertsettingisnecessary.When“OutofService”forDiagnosticStatusalertisrequired,choose“FALSE”for[OutofService.AlertDisable]intheUAPMOblock.RefertothefieldwirelessgatewayUser’sManualforthesettingproceduretoobtainthealertinformationfromthegateway.ThealertreportconsistsofthelistofparameternamesasshownTable8.3below.Table 8.3 Contents of Alert Report

Parameter name DescriptionDetectObjectTLPort AlertdetectionportUAP(0xF0B2)

fixedDetectObject AlertdetectionblockUAPMO(1)

fixedDetectTime Time stampAlertDirection 1:generated,0:clearAlertPriority Alert priorities set by usersAlertType Alert types, see 8.4 Self-

DiagnosticsAlertValue NAMUR107category

0:Failure,1:checkFunction,2:OffSpec,3:MaintenaceRequired

CAUTIONForawirelessgatewaywhichdoesnotsupportthealertreportfunction,thealertsettinginUAPMOblockforthetransmittermustbesetto“Disable.”NotethatYFGW710fieldwirelessintegratedgatewaydoesnothavethealertreportfunction.

Page 60: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-19

IM 01C27B01-01EN

Table 8.4 Diagnostic Results Summary

Diagnostic Status Contents

AlertType

NAMUR NE107

CategoryDiagnostic Status Detail Description

Faultsinelectronics 78 F

AMP_EEPROM_FAIL AmplifierEEPROMfailureAMP_EEP_IRREGULAR AMPEEPROMversionnotcorrectG_A_COMM_FAIL G/A failureFC_DELTA_T_FAIL C-sidedeltaTcircuitfailureFR_DELTA_T_FAIL R-sidedeltaTcircuitfailure

WL_AD_FAIL Batteryvoltagenotdetected(AMPfailure)

Faultsinsensororactuatorelement 77 F

FC_SENSOR_FAIL CsensorfrequencyfailureFR_SENSOR_FAIL RsensorfrequencyfailureCAP_T_SENSOR_FAIL Capsule temperature sensor failureCAP_EEPROM_FAIL Capsule EEPROM failureCAP_EEP_IRREGULAR CAPEEPROMversionnotcorrectFC_UNOSC_FAIL CsensoroscillationstopfailureFR_UNOSC_FAIL Rsensoroscillationstopfailure

Installation,calibrationproblem 76 C

DP_TRIM_SPAN_OUTSIDE "Pressure span adjustment variable outside of range"

DP_TRIM_ZERO_OUTSIDE "Pressurezeroadjustmentvariable outside of range"

SP_TRIM_SPAN_OUTSIDE "Staticpressurespanadjustment variable outside of range"

SP_TRIM_ZERO_OUTSIDE "Staticpressurezeroadjustment variable outside of range"

LCD_OUTSIDE_LIMIT LCD display outside of limits

Outofservice 75 CAI1_OUT_OF_SERVICE AI1 O/S modeAI2_OUT_OF_SERVICE AI2 O/S modeAI3_OUT_OF_SERVICE AI3 O/S mode

Outside sensor limits 74 O

DP_OUTSIDE_LIMIT Pressure outside of rangeSP_OUTSIDE_LIMIT StaticpressureoutsideofrangeCAPT_OUTSIDE_LIMIT Capsule temperature outside of rangeAMPT_OUTSIDE_LIMIT Amplifiertemperatureoutsideofrange

Environmentalconditionsoutofdevicespecification. 73 O

DP_OUTSIDE_RANGE Pressure setting outside of range

SP_OUTSIDE_RANGE Staticpressuresettingoutsideofrange

Poweriscriticallow: maintenanceneedshort-term.

71 M CRITICAL_LOWBAT Detectionofanextremedecreaseinthe battery voltage

Powerislow: maintenanceneedmid-term 70 M WL_LOWBAT_ALM Detectionofadecreaseinthebattery

voltage

Simulationisactive 68 CAI1_SIMULATION_ACTIVE AI1 Simulation modeAI2_SIMULATION_ACTIVE AI2 Simulation modeAI3_SIMULATION_ACTIVE AI3 Simulation mode

NotapplicableforthediagnosticregardingAI2objectandstaticpressuremeasurement.

Page 61: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<8. Setting Parameters> 8-20

IM 01C27B01-01EN

8.4.3 Checking with Integral Indicator

NOTEIfanerrorisdetectedbyrunningself-diagnostics,an error number is displayed on the integral indicator.Ifthereismorethanoneerror,theerrornumberchangesatthree-secondintervals.SeeTable9.3regardingtheerrorcodes.

F0808.ai

Figure 8.5 Integral Indicator

Page 62: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-1

IM 01C27B01-01EN

9. Maintenance9.1 Overview

WARNING

Sincetheaccumulatedprocessfluidmaybetoxicorotherwiseharmful,takeappropriatecaretoavoidcontactwiththebodyorinhalationofvaporswhendrainingcondensateorventinggasfromthetransmitterpressure-detectorsectionand even after dismounting the instrument from theprocesslineformaintenance.

Maintenanceofthetransmitteriseasyduetoitsmodularconstruction.Thischapterdescribestheproceduresforcalibration,adjustment,andthedisassemblyandreassemblyproceduresrequiredforcomponentreplacement.

Transmittersareprecisioninstruments.Pleasecarefullyandthoroughlyreadthefollowingsectionsforinformationonhowtoproperlyhandlethemwhileperformingmaintenance.

IMPORTANT• Asarule,maintenanceofthistransmittershouldbedoneinamaintenanceroomthathasallthenecessarytools.

• The CPU assembly, RF assembly and Integralindicatorcontainsensitivepartsthatcanbedamagedbystaticelectricity.

Takeprecautionssuchasusingagroundedwriststrapwhenhandlingelectronicpartsortouchingtheboardcircuitpatterns.AlsobesuretoplacetheremovedCPUassembly,RFassemblyandIntegralindicatorintoabagwithanantistaticcoating.

9.2 Calibration Instruments Selection

Table9.1liststheinstrumentsthatcanbeusedtocalibrateatransmitter.Whenselectinganinstrument,considertherequiredaccuracylevel.Exercisecarewhenhandlingtheseinstrumentstoensuretheymaintainthespecifiedaccuracy.

9.3 CalibrationUsetheprocedurebelowtocheckinstrumentoperationandaccuracyduringperiodicmaintenanceortroubleshooting.

1) Insertthebatterypackorturnonthepowerand then perform provisioning to have the transmitterjointheFieldWirelessNetworkorpreparingtheinfraredcommunicationforcalibration.

2) Setmeasurementmodetocontinuoususingthefielddeviceconfigurationtoolandtheupdateperiodto1secondusingthefieldwirelessconfigurationtool.

3) ConnectthedevicesasshowninFigure9.1andallowthetransmittertowarmupforatleast5 minutes.

IMPORTANTIfthemeasurementrange0%pointis0kPaorshiftedinthepositivedirection(suppressedzero),thereferencepressureshouldbeappliedasshowninthefigure. If the measurement range 0% point is shifted inthenegativedirection(elevatedzero),thereferencepressureshouldbeappliedusingavacuumpump.

4) Applyreferencepressuresof0%,50%,and 100% of the measurement range to the transmitter.Calculatetheerrors(differencesbetweenthedeviceconfigurationtoolreadingsandreferencepressures)asthepressureisincreasedfrom0%to100%andisdecreasedfrom100%to0%,andconfirmthattheerrorsarewithintherequiredaccuracy.

(Note)Whentheoutputmodeissetto“Sgroot,”applyreferencepressures of 0, 6.25, 25, 56.25, and 100% instead.

5) Whenthetestisfinished,resetmeasurementmode and update time to the initial value using thefielddeviceconfigurationtoolandthefieldwirelessconfigurationtool.

Page 63: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-2

IM 01C27B01-01EN

Table 9.1 Instruments Required for Calibration

Name Yokogawa-recommended Instrument RemarksProvisioning devicetool

• FieldMate(R2.02.01orlater)• ProvisioningDeviceTool• InfraredAdaptercertifiedbyYokogawa Supplier:ACTiSYS Productname:IrDAInfraRedUSBAdaptor Productnumber:IR224UN

Fieldwirelessconfigurationtool

• FieldWirelessIntegratedGatewayattachedSoftware FieldWirelessConfigurator Field Wireless Management Tool• FieldWirelessSystemrelatedProduct PlantResourceManager(PRM)(R3.05orlater)• DeviceConfigurationToolviaISA100.11aWirelessCommunication FieldMate(R2.02.01orlater) DeviceFile(R3.01.01orlater)• DeviceConfigurationToolviaInfraredCommunication FieldMate(R2.03.00orlater) DeviceFile(R3.02.01orlater)

Digital manometer

ModelMT220precisiondigitalmanometer1)For10kPaclass Accuracy:±(0.015%ofrdg+0.015%ofF.S.). . . . for0to10kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for-10to0kPa2)For130kPaclass Accuracy:±0.02%ofrdg . . . . . . . . . . . . . . . . . . . . for25to130kPa ±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for0to25kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for-80to0kPa3)For700kPaclass Accuracy:±(0.02%ofrdg+3digits) . . . . . . . . . . . for100to700kPa ±5digits . . . . . . . . . . . . . . . . . . . . . . . . for0to100kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for-80to0kPa4)For3000kPaclass Accuracy:±(0.02%ofrdg+10digits) . . . . . . . . . . for0to3000kPa ±(0.2%ofrdg+0.1%ofF.S.) . . . . . . . . for-80to0kPa5)For130kPaabsclass Accuracy:±(0.03%ofrdg+6digits) . . . . . . . . . . . for0to130kPaabs

Selectamanometerhavingapressurerangeclosetothat of the transmitter.

Pressure generator

ModelMC100pneumaticpressurestandardfor200kPa{2kgf/cm2},25kPa{2500mmH2O}

Accuracy:±0.05%ofF.S.

Requires air pressure supply.

Deadweightgaugetester25kPa{2500mmH2O}Accuracy:±0.03%ofsetting

Selecttheonehavingapressurerangeclosetothatof the transmitter.

Pressure source

Model6919pressureregulator(pressurepump)Pressurerange:0to133kPa{1000mmHg}

Preparethevacuumpumpfor negative pressure ranges.

Note: Theabovetablecontainstheinstrumentscapableofperformingcalibrationtothe0.2%level.Sincespecialmaintenanceandmanagementproceduresinvolvingtraceabilityofeachinstrumenttohigher-levelstandardsarerequiredforcalibrationtothe0.1%orhigherlevel,theremaybedifficultiesincalibrationtothislevelinthefield.Forcalibrationtothe0.1%level,contactYokogawarepresentativesfromwhichtheinstrumentwaspurchasedorthenearestYokogawaoffice.

P

Using pressure generator

Reference pressure

High pressure side

Low pressure sideopen to atmosphere

Low pressure sideopen to atmosphere

Supply pressure

Pressure generator P

Using pressure source with manometer

Reference pressure

Pressure source

Precision digital manometer

F0901.aiL H L H

High pressure side

Figure 9.1 Instrument Connections

Page 64: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-3

IM 01C27B01-01EN

Table9.2showsthetoolsrequired.

Table 9.2 Tools for Disassembly and Reassembly

Tool Quantity RemarksPhillips screwdriver

1 JIS B4633, No. 2

Slotted screwdriver

1

Allenwrenches 3 JIS B4648 Oneeach,nominal3,4 and 2.5 mm Allen wrenches

Wrench 1 Widthacrossflats,17mmTorquewrench 1Adjustable wrench

1

Socketwrench 1 Widthacrossflats,16mmSocketdriver 1 Widthacrossflats,5.5mmTweezers 1

9.4.1 Replacing the Integral IndicatorThissubsectiondescribestheprocedureforreplacinganintegralindicator.(Seefigure9.2)

■ Removing the Integral Indicator

1) Removethecover.2) Whilesupportingtheintegralindicatorwithone

hand,loosenitstwomountingscrews.3) DismounttheintegralindicatorfromtheRF

assembly. Whendoingthis,carefullypulltheintegral

indicatorstraightforwardsoasnottodamagetheconnectorpinsbetweenitandtheRFassembly.

9.4 Disassembly and Reassembly

CAUTIONPrecautions for the intrinsic safety explosion prevention type instrument

Intrinsicsafetypetransmittersmustbe,asarule,removedtoanon-hazardousareaformaintenanceandbedisassembledandreassembledtotheoriginalstate.Checkandconfirmtheinsulationwhenitisreassembledtothe original state.Checkandconfirmtheinsulationwhenitisreassembled to the original state.Refertosection2.7“InsulationResistanceandDielectricStrengthTest”fordetailsofResistanceTest.

IMPORTANT• PerformtheprovisioningwhenreplacingtheRFassembly.Referto7.4ConnectingtotheFieldWirelessNetworkfordetails.

• ReplacethebatteriesandperformtheparametersettingswhenreplacingtheCPUassembly.Referto9.4.7ReplacingtheBatteries.TurnonthepowerandperformtheparametersettingsagainwhenreplacingtheCPUassemblyoftheexternalpoweredtype.Referto9.4.9ReplacingthePowerSupplyModule.

Thissectiondescribesproceduresfordisassemblyandreassemblyformaintenanceandcomponentreplacement.

CAUTIONAlwaysremovebatterypackorturnoffthepowerandshutoffpressuresbeforedisassemblyandassembly. Use proper tools for all operations.

Page 65: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-4

IM 01C27B01-01EN

■ Attaching the Integral Indicator

1) AlignboththeintegralindicatorandRFassemblyconnectorsandengagethem.

2) Insertandtightenthetwomountingscrews.3) Replacethecover.

Zeroadjustmentscrew

RF assembly

CPU assembly

Amplifier cover

Mounting screw

Integral indicator Boss

Stud

F0902.ai

PressForward

Power cable

Zero-adjustmentscrew pin

Figure 9.2 Removing and Attaching Integral indicator, RF assembly and CPU Assembly

9.4.2 Replacing the RF AssemblyThissubsectiondescribeshowtoreplacetheRFassembly(seeFigure9.2).

■ Removing the RF assembly

1) Removethecover.2) Removetheintegralindicator(referto

subsection9.4.1).3) Removethetwostudboltsbyusingasocket

driver(widthacrossflats:5.5mm).4) DisconnecttheRFassemblyfromtheCPU

assembly.Whendoingthis,carefullypulltheRFassemblystraightforwardsoasnottodamagetheconnectorpinsbetweenitandtheCPUassembly.

5) DisconnecttheantennacablethatconnectstheRF assembly and the antenna.

NOTEBecarefulnottoapplyexcessiveforcetotheRFassemblyandtheconnectoroftheantennacablewhenremovingit.

■ Mounting the RF assembly

1) ConnecttheantennacablebetweentheRFassembly and the antenna.

2) AlignboththeRFassemblyandCPUassemblyconnectorsandengagethem.

3) Tightenthetwostudbolts.4) Mounttheintegralindicator(refertosubsection

9.4.1).5) Replacethecover.

9.4.3 Replacing the CPU AssemblyThissubsectiondescribeshowtoreplacetheCPUassembly(seeFigure9.2).

■ Removing the CPU assembly

1) Removethecover. RemovetheintegralindicatorandtheRFassembly(refertosubsections9.4.1and9.4.2).

2) Turnthezero-adjustmentscrewtothepositionasshowninFigure9.2.

3) Disconnectthepowercable(cablewithbrownconnectorattheend). When doing this, lightly press the side of the CPUassemblyconnectorandpullthecableconnectortodisengage(seetheupperleftofFigure9.2).

4) Useasocketdriver(widthacrossflats,5.5mm)toloosenthetwobosses.

5) CarefullypulltheCPUassemblystraightforwardtoremoveit.

6) Disconnecttheflatcable(cablewithwhiteconnectorattheend)thatconnectstheCPUassemblyandthecapsule.

NOTEBecarefulnottoapplyexcessiveforcetotheCPUassemblywhenremovingit.

■ Mounting the CPU assembly

1) Connecttheflatcable(withwhiteconnector)betweentheCPUassemblyandthecapsule.

2) Connectthepowercable(withbrownconnector)totheCPUassembly.

NOTEMakecertainthatthecablesdonotgetpinchedbetweenthecaseandtheedgeoftheCPUassembly.

Page 66: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-5

IM 01C27B01-01EN

3) Alignandengagethezero-adjustmentscrewpinwiththegrooveonthebracketontheCPUassembly. Then insert the CPU assembly straightontothepostintheamplifiercase.

4) Tightenthetwobosses.MounttheRFassembly,andtheintegralindicator(refertosubsections9.4.1and9.4.2).

IMPORTANTConfirmthatthezero-adjustmentscrewpinisplacedproperlyinthegrooveonthebracketpriortotighteningthetwobosses.Ifitisnot,thezero-adjustmentmechanismwillbedamaged.

5) Replacethecover.

9.4.4 Cleaning and Replacing the Capsule Assembly

CAUTIONPrecautions for the intrinsic safety explosion prevention type instrumentModificationisnotpermittedbytheuserforintrinsicsafetyexplosionpreventiontypetransmitter.Ifyouwishtoreplacethecapsuleassemblywithoneofadifferentmeasurementrange,contactYokogawa.Theuserispermitted,however,toreplaceacapsuleassemblywithanotherofthesamespecificationandmeasurementrange.Aftercompletingmaintenance,besuretosecurelytightenthesetscrewsthatfastenthetransmittersectionandpressure-detectorsectiontogether.

Thissubsectiondescribestheproceduresforcleaningandreplacingthecapsuleassembly.(Seefigure9.3.)

■ Removing the Capsule Assembly

IMPORTANTExercisecareasfollowswhencleaningthecapsuleassembly.• Handlethecapsuleassemblywithcare,andbeespeciallycarefulnottodamageordistortthediaphragmsthatcontacttheprocessfluid.

• Donotuseachlorinatedoracidicsolutionforcleaning.

• Rinsewithcleanwateraftercleaning,pleasedryuntilcompletelydry.

1) RemovetheCPUassemblyasshowninsubsection9.4.3.

2) Removethefivesetscrews,thestopperbolt,andthestopperthatconnectthetransmittersectionandpressure-detectorsection.

3) Removethehexagon-headscrewandthestopper.

4) Separatethetransmittersectionandpressure-detectorsection.

5) Removethenutsfromthefourflangebolts.6) Whilesupportingthecapsuleassemblywith

onehand,removethecoverflange.7) Removethecapsuleassembly.8) Cleanthecapsuleassemblyorreplacewitha

newone.

■ Reassembling the Capsule Assembly

1) Insertthecapsuleassemblybetweentheflangebolts,payingcloseattentiontotherelativepositionsoftheH(highpressureside)andL(lowpressureside)marksonthecapsuleassembly.

Replacethetwocapsulegasketswithnewgaskets.

2) Installthecoverflangeonthehighpressureside,anduseatorquewrenchtotightenthefournutsuniformlytoatorqueshownbelow.

ModelEJX110B, EJX310B, EJX430BWetted parts material code

S H,M,T,A,D,B Torque(N·m)

{kgf·m}17*{1.7}

40{4.1}

*:40N·m(4.1kgf·m)formeasurementspancodeF,optioncode/HDor/HD2.

Page 67: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-6

IM 01C27B01-01EN

3) Afterthepressure-detectorsectionhasbeenreassembled,aleaktestmustbeperformedtoverifythattherearenopressureleaks.

4) Reattachthetransmittersectiontothepressure-detectorsection.

5) Reattachthestopperandstopperbolt.Tightenthefivesetscrews.(Tightenthescrewstoatorqueof1.5N·m)

6) InstalltheCPUassemblyaccordingtosubsection9.4.3.

7) Aftercompletingreassembly,adjustthezeropointandrechecktheparameters.

StopperStopper bolt

F0903.ai

Transmitter section

Pressure-detectorsectionCover flange

Capsulegasket

Flange bolt

Setscrew

Nut

Figure 9.3 Removing and Mounting the Pressure-detector Section

9.4.5 Replacing the Process Connector Gaskets

Thissubsectiondescribesprocessconnectorgasketreplacement.(Seefigure9.4.)

(a) Loosenthetwobolts,andremovetheprocessconnectors.

(b) Replacetheprocessconnectorgaskets.(c) Remounttheprocessconnectors.Tightenthe

boltssecurelyanduniformlytoatorqueshownbelow,andverifythattherearenopressureleaks.

Model EJX110B, EJX310B, EJX430BTorque(N·m)

{kgf·m} 39to49{4to5}

F0904.ai

Bolt

Process connector

Process connector gasket

Figure 9.4 Removing and Mounting the Process Connector

9.4.6 Replacing the Battery PackRegardingthetransmitterwithintrinsicallysafeapproval,thebatterypackcanbereplacedwithoutremovingthedeviceinhazardousarea.

■ Preparation

InitializetheremainingbatterylifebyusingtheparameterofResetEnergyLeftinUAPMOblock.Whenthebatterypowerisburnedandemptied,initializetheremainingbatteryafterpromptreplacementofthebatterypack.

■ Removing

1) Removetheterminalboxcover.2) Loosenthetwobatterypackmountingscrews

(seeFigure9.5).3) PullouttheBatterypack.

F0905.ai

The battery pack mounting screws cannot be separated from the battery pack so as to prevent drop-off.

Figure 9.5 Removing the Battery Pack

Page 68: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-7

IM 01C27B01-01EN

■ Remounting

1) Insertthenewbatterypacklightly.2) Pushthecenterofthebatterypackandinsertit

securely.3) Tightenthetwobatterypackmountingscrews

to a torque of approximately 0.7 N·m.4) Replacetheterminalboxcover.

CAUTIONDonotattachthepowersupplymoduletothebatterypoweredtype.

9.4.7 Replacing the BatteriesThebatteriesinthebatterypackcanbereplaced.Batteriesarenotinstalledwhenshippedfromthefactory.Assemblethebatterypackasfollows.

WARNING

Besuretoreplacethebatteriesordisassembleandassemblethebatterypackinasafelocation.Doingsoinanexplosiveareacouldcauseanexplosion.

CAUTIONWhenreplacingthebatteries,besuretoreplacethetwobatteriesatthesametimeanddonotuseanoldandanewbatterytogether.

■ Disassembling

1) Loosenthetwobatterycasemountingscrews(Figure9.6).

2) Separatethebatterycaseintotwoparts.3) Removetheoldbatteries.

■ Assembling

1) Insertnewbatteriesintothebatterycase.Becarefuloftheorientationofthebatteries.

2) Attachthetwopartsofthebatterycasetoeachother.

3) Tightenthetwobatterycasemountingscrewsto a torque of approximately 0.7 N·m.

F0906.ai

The battery pack mounting screws cannot be separated from battery pack so as to prevent drop-off.

Figure 9.6 Removing the Battery Pack

9.4.8 Handling BatteriesThisbatterypackusestwoprimarylithium/thionylchloridebatteries.Eachbatterycontainsapproximately 5 grams of lithium, for a total of 10 gramsineachpack.Undernormalconditions,thebatterymaterialsareself-containedandarenotreactiveaslongasthebatteriesandthepackintegrityaremaintained.Careshouldbetakentopreventthermal,electricalormechanicaldamage.Protecttheelectrodeofthebatterypacktoavoidrapidelectricaldischarge.Dischargedabatterymayleadtofluidleakageandexcessiveheat.Batteriesshouldbestoredinacleananddryarea.Formaximum battery life, storage temperature should notexceed30°C.

WARNING

HandlingthebatterypackThefollowingprecautionsmustbeobservedinordertosafelyandeffectivelyuseabatterypack.Improperusemayleadtofluidleakage,excessiveheat,ignition,orexplosion.• Neverchargeit.• Donotshort-circuitit.• Do not disassemble, transform, or modify it.• Donotheatitorthrowitintoafire.• Donotsoakitinfreshwaterorseawater.

CAUTIONObservethefollowingprecautionsforthesafedisposal of batteries.• Donotincineratethebattery,anddonotexposeittoahightemperatureof100°Cormore.Thismayleadtofluidleakageorexplosion.

• Disposeofthebatteryaccordingtolawsandregulations.

Page 69: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-8

IM 01C27B01-01EN

Usethefollowingdedicatedpartsforthebatterypackandbatteries.

■ Battery Pack

Partnumber:F9915NQ(withbatteries) Partnumber:F9915NK(withoutbatteries)

■ Batteries

Part number: F9915NR Alternatively, Tadiran SL-2780/S, TL-5930/S

or VITZROCELL SB-D02 batteries may be purchasedandused.

■ Transportation of products containing lithium batteries:

Batteriesusedforthistransmittercontainlithium. Primary lithium batteries are regulated in transportation by the U.S. Department of Transportation,andarealsocoveredbytheInternationalAirTransportAssociation(IATA),theInternationalCivilAviationOrganization(ICAO),andthe European Ground Transportation of Dangerous Goods(ARD).Itistheresponsibilityoftheshippertoensurecompliancewiththeseoranyotherlocalrequirements.Consultcurrentregulationsandrequirements before shipping. When transporting thistransmitterwiththebatterypackinserted,keepitindeepsleepmodeinordertoconservebatterypower.Fordetailsonhowtoswitchtodeepsleepmode,refertosubsection8.3.16“SwitchingtoDeepSleepMode.”

■ How to replace and dispose of the batteries:

ThisisanexplanationaboutthenewEUBatteryDirective(DIRECTIVE2006/66/EC).Thisdirectiveisonly valid in the EU.Batteriesareusedforthisproduct.Whenyouremovebatteriesfromthisproductanddisposethem,discardtheminaccordancewithdomesticlawconcerningdisposal.Takearightactiononwastebatteries,becausethecollectionsystemintheEUonwastebatteriesareregulated.

Batterytype:Primarylithium-thionylchloridebattery

CAUTIONThesymbol(seeabove),whichismarkedonthebatteries, means they shall be sorted out and collectedasordainedinANNEXIIinDIRECTIVE2006/66/EC.

■ Procedure to remove the batteries safely:

Refertosubsection9.4.6“ReplacingtheBatteryPack”andsubsection9.4.7“ReplacingtheBatteries.”

9.4.9 Replacing the Power Supply Module

■ Removing

1) Turnoffthepower.2) Removetheterminalboxcover.3) Loosenthetwopowersupplymodulemounting

screws(seeFigure9.5).4) Pulloutthepowersupplymodule.

■ Remounting

1) Insertthenewpowersupplymodulelightly.2) Pushthecenterofthepowersupplymodule

andinsertitsecurely.3) Tightenthetwopowersupplymodulemounting

screwstoatorqueofapproximately0.7N·m.4) Replacetheterminalboxcover.

CAUTIONDonotattachthebatterypacktotheexternalpoweredtype.

9.5 TroubleshootingIf any abnormality appears in the measured values, usethetroubleshootingflowchartbelowtoisolateandremedytheproblem.Sincesomeproblemshavecomplexcauses,theseflowchartsmaynotidentifyall.Ifyouhavedifficultyisolatingorcorrectingaproblem,contactYokogawaservicepersonnel.

Page 70: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-9

IM 01C27B01-01EN

9.5.1 Basic TroubleshootingFirstdeterminewhethertheprocessvariableisactuallyabnormaloraproblemexistsinthemeasurement system.

If the problem is in the measurement system, isolatetheproblemanddecidewhatcorrectiveactiontotake.

Thistransmitterisequippedwithaself-diagnosticfunctionwhichwillbeusefulintroubleshooting,andthetransmitterequippedwithanintegralindicatorwillshowanalarmcodeasaresultofself-diagnosis. Seesubsection9.5.3forthelistofalarms.

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support

Is process variableitself abnormal?

Inspect theprocess system.

Isolate problem inmeasurement system.

Does problem exist inreceiving instrument?

Check/correctenvironmental conditions.

Inspect receiver.

Check transmitter.

Check/correct operatingconditions.

Measurement system problem

F0907.ai

YES

NO

NO

YES

Environmental conditions

Operating conditions

Transmitter itself

Figure 9.7 Basic Flow and Self-Diagnostics

9.5.2 Troubleshooting Flowcharts

Check display of the error code.Check self-diagnostics by the device configuration tools.

Does the self-diagnosticindicate problem location?

Contact Yokogawa service personnel.

F0908.ai

The following sorts of symptoms indicate that transmitter may not be operating properly.Example : • There is no output signal. • Output signal does not change even though process variable is known to be varying. • Output value is inconsistent with value inferred for process variable.

Fix pressure leaks, paying particularattention to connections for impulsepiping,pressure-detector section, etc.

Fully close equalizing valve, and fullyopen high pressure and low pressurevalves.

Are valves opened orclosed correctly?

Is there any pressure leak?

YES

NO

YES

NO

NO

YES

Refer to Alarm Message Summary in Subsection 9.5.3.

Is the Field Wireless Networksetting correct?

NO

YES Reconnect to the Field Wireless Network.

Page 71: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-10

IM 01C27B01-01EN

Connect the device configuration tool and check self-diagnostics.

Does the self-diagnostic indicate problem

location?

Contact Yokogawa service personnel.F0909.ai

Are valves opened or closed correctly?

Refer to Alarm Message Summary in Subsection 9.5.3.

YES

NO

Refer to individual model user manualsand connect piping as appropriate for the measurement purpose.

Fix pressure leaks, paying particularattention to connections for impulsepiping, pressure-detector section, etc.

Fully close equalizing valve, and fullyopen high pressure and low pressurevalves.

NO

YES

YES

NO

YES

Adjust the zero point.

NO

NO

YES

Is there any pressure leak?

Is impulse piping to high pressure and lowpressure side correct?

Is zero point adjusted correctly?

Output travels beyond 0% or 100%.

Connect the device configuration tool and check self-diagnostics.

Contact Yokogawa service personnel.

F0910.ai

Are valves opened orclosed correctly?

Is impulse pipingconnected correctly?

Refer to Alarm Message Summary in Subsection 9.5.3.

Provide lagging and/or cooling, or allowadequate ventilation.

Refer to Section 9.2 "Calibration Instruments Selection".

Fully close equalizing valve, and fullyopen high pressure and low pressurevalves.

Refer to individual model user manualsand connect piping as appropriate for the measurement purpose.

Adjust the output.

Is transmitterinstalled where there is

marked variation intemperature?

Is output adjusted correctly?

Large output error.

Does the self-diagnostic indicate problem

location?

Were appropriateinstruments used for

calibration?

YES

NO

YES

NO

NO

YES

NO

YES

NO

YES

NO

YES

Page 72: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-11

IM 01C27B01-01EN

9.5.3 Errors and Countermeasures

Table 9.3 Error Message Summary (Causes and Actions)

Integral indicator

Factory NAMUR category Bit Diagnostic

Status Diagnostic Status Detail Cause

Release/recovery

conditions (except restart)

Action

AL. 01CAP. ERR *2

F Bit 26

Faults in sensor or actuatorelement

FC_SENSOR_FAIL

Pressure sensor failure

RecoversonlywhenAUTORECOVER is ONandwithinthe range

Replacethecapsule.

FR_SENSOR_FAIL

FC_UNOSC_FAIL RecoversonlywhenAUTORECOVER is ON and oscillationdoesnot stop

FR_UNOSC_FAIL

CAP_T_SENSOR_FAIL Capsule temperature sensor failure

None

CAP_EEPROM_FAIL Capsule EEPROM memory failure

Recoverswhenreturnstonormal.

CAP_EEP_IRREGULAR None

AL. 02AMP. ERR *2

F Bit 27 Faults in electronics

AMP_EEPROM_FAILAmplifierEEPROM failure

Recoverswhenreturnstonormal.

Replacetheamplifier.

AMP_EEP_IRREGULAR NoneFC_DELTA_T_FAIL

Amplifierfailure NoneFR_DELTA_T_FAILG_A_COMM_FAILWL_AD_FAIL

AL. 10 PRESS

O Bit 23 Outside sensor limits

DP_OUTSIDE_LIMIT Pressure outside of specifiedrange

Recoverswheninput pressure returnswithinthe range.

Checkthe input pressure.

AL. 11ST. PRSS

SP_OUTSIDE_LIMIT Staticpressureoutside of specifiedrange

Recoverswhenstaticpressurereturnswithinthe range.

Checkthe input pressure.

AL. 12CAP. TMP

CAPT_OUTSIDE_LMIT Capsule temperature outside of range (-50to130°C)

Recoverswhentemperature returnswithinthe range.

Retain heat or insulate so that temperature returnswithinthespecifiedrange.

AL. 13AMP. TMP

AMPT_OUTSIDE_LIMIT Amplifiertemperature outside of range (-50to95°C)

Recoverswhentemperature returnswithinthe range.

Retain heat or insulate so that temperature returnswithinthespecifiedrange.

Page 73: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-12

IM 01C27B01-01EN

Integral indicator

Factory NAMUR category Bit Diagnostic

Status Diagnostic Status Detail Cause

Release/recovery

conditions (except restart)

Action

AL.53P. ADJ

C Bit 25Installation, calibrationproblem

DP_TRIM_SPAN_OUTSIDE Pressure span adjustment variable outside of range

Recoverswhenspanadjustment variable/point returnswithinthe range.

Checkthe span adjustment variable for the Pressure.

AL.53P. ADJ

DP_TRIM_ZERO_OUTSIDE Pressurezeroadjustment variable outside of range

Recoverswhenzeroadjustment variable/point returnswithinthe range.

Checkthezeroadjustment variable for the Pressure.

AL. 55SP. ADJ

C Bit 25Installation, calibrationproblem

SP_TRIM_SPAN_OUTSIDE Staticpressurespan adjustment variable outside of range

Recoverswhenspanadjustment variable /point returnswithinthe range.

Checkthestaticpressure span adjustment variable.

AL. 55SP. ADJ

SP_TRIM_ZERO_OUTSIDE Staticpressurezeroadjustmentvariable outside of range

Recoverswhenzeroadjustment variable/point returnswithinthe range.

Checkthestaticpressurezeroadjustment variable.

AL. 79OV. DISP

LCD_OUTSIDE_LIMIT LCD display outside of specifiedrange

Recoverswhendisplay value returnswithinthe range.

Checkthedisplay setting.

AL. 30RANGE

O Bit 22

Environmental conditionsoutofdevicespecification

DP_OUTSIDE_RANGE Input pressure setting outside of range

Recoverswhensetting returns withintherange.

Checktheinput pressure setting.

AL. 31SP. RNG

SP_OUTSIDE_RANGE Staticpressuresetting outside of range

Recoverswhensetting returns withintherange.

Checkthestaticpressure setting.

AL. 70LOWBAT

M

Bit 20

Poweriscriticallow:maintenanceneed short - term

CRITICAL_LOWBAT Battery voltage isthelowest.

None Replacethebatteries.

AL. 70LOWBAT Bit 19

Powerislow:maintenanceneed mid - term

WL_LOWBAT_ALM Lowremainingbattery voltage None Replacethe

batteries.

AL. 60AI OOS

C Bit 24 O/S

AI1_OUT_OF_SERVICE AI1blockisO/Smode.

Returnswhenthe mode target ofAI1blockisother than O/S.

Set the mode target to AUTO.

AL. 61AI OOS

AI2_OUT_OF_SERVICE AI2blockisO/Smode.

Returnswhenthe mode target ofAI2blockisother than O/S.

Set the mode target to AUTO.

AL. 62AI OOS

AI3_OUT_OF_SERVICE AI3blockisO/Smode.

Returnswhenthe mode target ofAI3blockisother than O/S.

Set the mode target to AUTO.

Page 74: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-13

IM 01C27B01-01EN

Integral indicator

Factory NAMUR category Bit Diagnostic

Status Diagnostic Status Detail Cause

Release/recovery

conditions (except restart)

Action

AL. 63AI SIM

C Bit 17 Simulation is active

SimulationActive(AI1)

AI1blockissimulate mode.

Returnswhenthe simulate mode of AI1 blockissetto disable. 1 (Disable)

Checkthesimulate mode of AI1 block.

AL. 64AI SIM

SimulationActive(AI2)

AI2blockissimulate mode.

Returnswhenthe simulate mode of AI2 blockissetto disable. 1 (Disable)

Checkthesimulate mode of AI2 block.

AL. 65AI SIM C Bit 17 Simulation is

active

SimulationActive(AI3)

AI3blockissimulate mode.

Returnswhenthe simulate mode of AI3 blockissetto disable. 1 (Disable)

Checkthesimulate mode of AI3 block.

*1: "FactoryNAMURcategory”referstothefourcategories(C:Checkfunction,M:Maintenancerequired,F:Failure,andO:Offspecification)accordingtoNAMURNE107*.

*NAMURNE107“Self-MonitoringandDiagnosisofFieldDevices”*2: Whenthedevicedetects“AL01CAP.ERR”and“AL02AMP.ERR”,theLCDdisplaystaysonregardlessofthestatusinLCDmode.

Page 75: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-14

IM 01C27B01-01EN

Table 9.4 Error Message Summary (Output Actions)

Integral Indicator

Factory NAMUR category

Bit Diagnostic Status Diagnostic Status Detail

Output actions

Pressure Static Pressure

CapsuleTempValue

AmpTempValue

AL. 01CAP. ERR *2

F Bit 26

Faults in sensor or actuatorelement

FC_SENSOR_FAIL Output value(holdvalue)Output status (BAD:SensorFailure)

Output value(holdvalue)Output status (BAD:SensorFailure)

Normalaction

Normalaction

FR_SENSOR_FAIL

FC_UNOSC_FAIL

FR_UNOSC_FAIL

CAP_T_SENSOR_FAIL Normalaction Normalaction Output value (calculatedinanormalway)Output status (BAD:SensorFailure)

CAP_EEPROM_FAIL Output value (holdvalue)Output status (BAD:DeviceFailure)

Output value(holdvalue)Output status (BAD:DeviceFailure)

Output value (calculatedinanormalway)Output status (BAD:DeviceFailure)

Output value (calculatedinanormalway)Output status (BAD:DeviceFailure)

CAP_EEP_IRREGULAR

AL. 02AMP.ERR *2

F Bit 27 Faults in electronics

AMP_EEPROM_FAIL Output value(holdvalue)Output status (BAD:DeviceFailure)

Output value (holdvalue)Output status (BAD:DeviceFailure)

Output value (calculatedinanormalway)Output status (BAD:DeviceFailure)

Output value(calculatedinanormalway)Output status (BAD:DeviceFailure)

AMP_EEP_IRREGULAR

FC_DELTA_T_FAIL Output value (holdvalue)output status (BAD:DeviceFailure)

Output value (calculatedinanormalway)Output status (BAD:DeviceFailure)

Output value (holdvalue)Output status (BAD:DeviceFailure)

Normalaction

Output value(calculatedinanormalway)Output status (BAD:DeviceFailure)

FR_DELTA_T_FAIL

G_A_COMM_FAIL Output value (calculatedinanormalway)Output status (BAD:DeviceFailure)

Output value (calculatedinanormalway)Output status (BAD:DeviceFailure)

WL_AD_FAIL

Page 76: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-15

IM 01C27B01-01EN

Integral Indicator

Factory NAMUR category

Bit Diagnostic Status Diagnostic Status Detail

Output actions

Pressure Static Pressure

CapsuleTempValue

AmpTempValue

AL. 10 PRESS

O Bit 23 Outside sensor limits

DP_OUTSIDE_LIMIT Output value (calculatedinanormalway)Output status (UNCERTAIN:Sensor Conversion notAccurate)

Output value (calculatedinanormalway)Output status (UNCERTAIN:NonSpecific)

Normalaction Normalaction

AL. 11ST. PRSS

SP_OUTSIDE_LIMIT Output value (calculatedinanormalway)Output status (UNCERTAIN:NonSpecific)

Output value (calculatedinanormalway)Output status (UNCERTAIN:Sensor Conversion notAccurate)

Normalaction Normalaction

AL. 12CAP. TMP

CAPT_OUTSIDE_LIMIT Output value (calculatedinanormalway)Output status (UNCERTAIN:NonSpecific)

Output value (calculatedinanormalway)Output status (UNCERTAIN:NonSpecific)

Output value (calculatedinanormalway)Output status (UNCERTAIN:Sensor Conversion notAccurate)

Normalaction

AL. 13AMP. TMP

AMPT_OUTSIDE_LIMIT

Normalaction Normalaction Normalaction

Output value (calculatedinanormalway)Output status (UNCERTAIN:Sensor Conversion notAccurate)

AL. 53P. ADJ

C Bit 25Installation, calibrationproblem

DP_TRIM_SPAN_OUTSIDE

Output value (calculatedinanormalway)Output status (UNCERTAIN:Range Limits Exceeded)

Normalaction Normalaction Normalaction

AL. 53P. ADJ

DP_TRIM_ZERO_OUTSIDE

Output value (calculatedinanormalway)Output status (UNCERTAIN:Range Limits Exceeded)

Normalaction Normalaction Normalaction

AL. 55SP. ADJ

SP_TRIM_SPAN_OUTSIDE

Normalaction

Output value (calculatedinanormalway)Output status (UNCERTAIN:Range Limits Exceeded)

Normalaction Normalaction

AL. 55SP.ADJ

SP_TRIM_ZERO_OUTSIDE

Normalaction

Output value (calculatedinanormalway)Output status (UNCERTAIN:Range Limits Exceeded)

Normalaction Normalaction

AL. 79OV. DISP

LCD_OUTSIDE_LIMITNormalaction Normalaction Normalaction Normalaction

Page 77: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<9. Maintenance> 9-16

IM 01C27B01-01EN

Integral Indicator

Factory NAMUR category

Bit Diagnostic Status Diagnostic Status Detail

Output actions

Pressure Static Pressure

CapsuleTempValue

AmpTempValue

AL. 30RANGE

O Bit 22

Environmental conditionsoutofdevicespecification

DP_OUTSIDE_RANGE Normalaction Normalaction Normalaction Normalaction

AL. 31SP. RNG

SP_OUTSIDE_RANGENormalaction Normalaction Normalaction Normalaction

AL. 70*3

LOWBAT

M

Bit 20

Poweriscriticallow:maintenanceneed short - term

CRITICAL_LOWBAT

Normalaction Normalaction Normalaction Normalaction

AL. 70*3

LOWBAT Bit 19

Powerislow:maintenanceneed mid - term

WL_LOWBAT_ALM

Normalaction Normalaction Normalaction Normalaction

AL. 60AI OOS

C Bit 24 O/S

AI1_OUT_OF_SERVICE Output value(holdvalue)Output status(BAD:OutofService)

Normalaction Normalaction Normalaction

AL. 61AI OOS

AI2_OUT_OF_SERVICE

Normalaction

Output value(holdvalue)Output status(BAD:OutofService)

Normalaction Normalaction

AL. 62AI OOS

AI3_OUT_OF_SERVICE

Normalaction Normalaction

Output value(holdvalue)Output status(BAD:OutofService)

Output value(holdvalue)Output status(BAD:OutofService)

AL. 63AI SIM

C Bit 17 Simulation is active

SimulationActive(AI1) Normalaction Normalaction Normalaction Normalaction

AL. 64AI SIM

SimulationActive(AI2) Normalaction Normalaction Normalaction Normalaction

AL. 65AI SIM

SimulationActive(AI3) Normalaction Normalaction Normalaction Normalaction

*1: “FactoryNAMURcategory”referstothefourcategories(C:Checkfunction,M:Maintenancerequired,F:Failure,andO:Offspecification)accordingtoNAMURNE107*.

* NAMURNE107“Self-MonitoringandDiagnosisofFieldDevices”*2: Whenthedevicedetects“AL01CAP.ERR”and“AL02AMP.ERR”,theLCDdisplaystaysonregardlessofthestatusinLCDmode.*3: Whentheambienttemperatureishigherthan60°C,AL.70maybegenerateddespitetheindicationofEnergyLeftshowssufficiently

remained.However,itdoesnotaffectthedeviceoperation.Thisiscausedbythechangeofbatteryinnerstatuswithextremelylowpowerconsumptionunderhightemperatureenvironment.Itisrecommendedtosetthedataupdatingperiodto15secondsorshorter.

Page 78: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-1

IM 01C27B01-01EN

10. Parameter SummaryTable 10.1 Parameter

ObjectID

Attribute ID Label Description Default

value Handling

1.UAPMOblock

1 Version Revision IndicatestheapplicationrevisionofEJXThisrevisionwhentheapplicationsoftwareisdownloaded.

--- R

10 StaticRevision IndicatestherevisionlevelofthefixedparametersofUAPUsed,forexample,tocheckwhetherparametershavebeenchange.

0 R

64 IdentificationNumber

IndicatesthevenderID,modelID,andrevisionofthedevice.

--- R

65 CTS Version Indicatestheversionofthecommunicationstacktestsystem(CTS).

0 R

66 ITS Version Indicatestheversionoftheinteroperabilitytestsystem(ITS).

0 R

67 DiagnosticStatus Indicatesthediagnosticresultsofthedevicebasedonthe NAMUR NE107*1 model.SettingEnablediagnosticstatusconfigurationinUAPOptiontoEnableallowsturningOFFandONthedisplayofthediagnosticresultsforeachsummary,andchangingCategorizeForCategorizeatthetimeofshipment, refer to tables 8.3 and 10.2.

--- R

68 UAP Option AllowssettingtheDiagnosticStatusandwriteprotectionof UAP.Softwarewriteprotect

1:On,0:OffEnablehardwarewriteprotect

1:Enable,0:Disable(default)Enablediagnosticstatusconfiguration

1:Enable,0:Disable(default)Thefollowingtableshowstherelationshipbetweenthehardwarewriteprotectionandsoftwarewriteprotection.

Enable hardware

write protect

Hardware write

protect

Software write

protect

Write protect

Disable OfforOn Off No(Writable)

Disable OfforOn On Yes(Unwritable)

Enable Off OfforOn No(Writable)

Enable On OfforOn Yes(Unwritable)

0 W

69 DiagnosticSwitch

AllowssettingOn/OffforeachsummaryofDiagnosticStatuswhenEnablediagnosticstatusconfigurationinUAP Option is set to Enable.

On W

70 DiagnosticConfiguration

AllowsCategorizeforeachsummaryofDiagnosticStatuswhenEnablediagnosticstatusconfigurationinUAP Option is set to Enable.

Refer to Table 10.2.

W

102 DiagnosticStatusDetail[2]

DetailedinformationonDiagnosticStatus.ForCategorizeatthetimeofshipment,refertoTable10.2.

Refer to Table 10.2.

R

103 Energy Left Indicatesthenumberofdaysofremainingbatterylifeassumingambienttemperatureconditionas23degreesCelsius.The unit is day.

--- R

104 Reset Energy Left Initializetheremainingbatterylife(EnergyLeft)andresetitasnewbatteries.Performthebatteryreplacement.0=Continue(Cancel)1=Reset(Initialization)

0(readingvalueisalways0)

W

Page 79: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-2

IM 01C27B01-01EN

ObjectID

Attribute ID Label Description Default

value Handling

1.UAPMO block(continued)

105 PowerSupplyStatus

Indicatesthepredictedbatterylevelandthepowersupply method.0=externalpowersupply1 = battery level 75% or more2 = battery level 25% ~ 75%3 = battery level 25% or less

R

106 EHType Availabletowritenoteintothisparameter. --- W

107 PowerSupplyVoltage

Indicatesthemeasuredpowersupplyvoltage(V). --- R

110 HardwareWriteProtect

Allowsrecognizingthestatusofthehardwarewriteprotectionswitch.(SwitchOff,SwitchOn)

R

111 RadioSilence Repeatsacycleofa1-hourpauseand6-minutesearchiftheinstrumentcannotjointhenetworkafteratimespecifiedinRadioSilencehaselapsed.When0isset,theRadioSilenceisinvalid.

28800 W

112 SimulationActiveAlert

TheOn/OfforpriorityforSimulationActiveAlertcanbe set.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15

1. TRUE 2. 15

W

113 Soft Update incompleteAlert

TheOn/OfforpriorityforSoftUpdateincompleteAlertcanbeset.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15Not available for EJX.

1. TRUE 2. 15

W

114 PowerlowAlert TheOn/OfforpriorityforPowerlowAlertcanbeset.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15

1. TRUE 2. 15

W

115 PowerCriticallowAlert

TheOn/OfforpriorityforPowerCriticallowAlertcanbe set.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15

1. TRUE 2. 15

W

116 FaultpredictionAlert

TheOn/OfforpriorityforFaultpredictionAlertcanbeset.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15Not available for EJX.

1. TRUE 2. 15

W

117 Environmental conditionsAlert

TheOn/OfforpriorityforEnvironmentalconditionsAlertcanbeset.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15

1. TRUE 2. 15

W

118 Outside sensor limits Alert

TheOn/OfforpriorityforOutsidesensorlimitsAlertcanbeset.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15

1. TRUE 2. 15

W

119 OutofserviceAlert TheOn/OfforpriorityforOutofserviceAlertcanbeset.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15

1. TRUE 2. 15

W

120 Callibration problem Alert

TheOn/OfforpriorityforcallibrationproblemAlertcanbe set.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15

1. TRUE 2. 15

W

Page 80: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-3

IM 01C27B01-01EN

ObjectID

Attribute ID Label Description Default

value Handling

1.UAPMO block(continued)

121 Faults Sensor or actuatorAlert

TheOn/OfforpriorityforFaultsSensororactuatorAlertcanbeset.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15

1. TRUE 2. 15

W

122 FaultsElectronicsAlert

TheOn/OfforpriorityforFaultsElectronicsAlertcanbe set.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 1

1. TRUE 2. 15

W

123 FaultsprocessinfluenceAlert

TheOn/OfforpriorityforFaultsprocessinfluenceAlertcanbeset.1.On/Offsetting

0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15Not available for EJX.

1. TRUE 2. 15

W

124 Faults non-complianceAlert

TheOn/OfforpriorityforFaultsnon-complianceAlertcanbeset.1.On/Offsetting 0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15Not available for EJX.

1. TRUE 2. 15

W

125 Other faults Alert TheOn/OfforpriorityforOtherfaultsAlertcanbeset.1.On/Offsetting 0 = FALSE, 255 =TRUE2. Alert report priority: 0 to 15Not available for EJX.

1. TRUE 2. 15

W

2.UDOblock

2 DESCRIPTION Indicatestheversionandmodelinformationofthedownloadeddata.

--- R

3 STATE IndicatesthestatusofUAPblock.0 Idle1Downloading3 Applying4 DLComplete6 DLError

--- R

5 MAX_BLOCK_SIZE

Maximumblocksize.ThisvalueissmallerthanthemaximumdatasizeofAPDU.

--- R

14 LAST_BLOCK_DOWNLOADED

Indicatesthelastdownloadedblocknumber.0meansthatnoblockhasbeendownloaded.

--- R

16 ERROR_CODE IndicatestheerrorcodesforDLError.0 = noError1 = Timeout2 = ClientAbort64 = Apply failure

--- R

3.COblock

1 REVISION IndicatestherevisionnumbersuchasCOMM_ENDPOINT,etc.

--- R

2 COMM_ENDPOINT

IndicatestheEndpointinformation.Thefollowingshowsthecomponents.1.Networkaddressofremoteendpoint2. Transport layer port at remote endpoint3.ObjectIDatremoteendpoint4. Stale data limit5.Datapublicationperiod6.Idealpublicationphase7. PublishAutoRetransmit8.Configurationstatus

--- W

3 COMM_CONTRACT

IndicatestheContractinformation.Thefollowingshowsthecomponents.1.ContractID2.Contract_Status3.Actual_Phase

--- R

Page 81: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-4

IM 01C27B01-01EN

ObjectID

Attribute ID Label Description Default

value Handling

3.COblock(continued)

4 PUB_ITEM_MAX MaximumPUB_ITEMvalue --- R

5 PUB_ITEM_NUM PUB_ITEMnumber --- R

6 PUB_ITEM IndicatesthePUB_ITEMinformation.Thefollowingshowsthecomponents1.ObjectID2. AttributeID3. AttributeIndex4.Size

--- W

4.TRANSDUCERblock

1 TagDescription Memofieldavailabletowriteanything. Transducer W

2 AutoRecovery Allowsspecifyingtheactionwhenthecauseofasensor failure is removed.OFF(=0): ALcontinuestobeindicated evenafterthecauseofthesensor error is removed, and the BURN OUT state is not released.

ON(=1): TheALindicationforsensor failure disappears and normal actionisresumedwhenthecause of the sensor failure is removed.

ON W

3 Model Indicatesthemodelnameofthetransmitter. --- R

4 Sensor Serial Number

Indicatesthedevicenumberofthetransmitter. --- R

6 Measurement Mode

Measurementmodeselectscontinuousmodeorintermittent mode.Whentheupdatetimeissetto0.5secondinintermittentmode,themodeisautomaticallyswitchedtocontinuousmode.Whentheupdatetimeissetto0.5second,thecomputationprocessisincontinuousmode,regardless of the measurement mode.When 0 is set, measurement period is set to 30 secondsregardlessofmeasurementsetting.

intermittent mode

W

7 Wireless Status Indicatethecommunicationstatus.1.Indicatestheinitialidlestatusorjoinstatus. (idlestatus,joinstatus)2.IndicateswhetherContract(Pub)isestablished. (notestablishment,establishment)3.IndicateswhetherContract(R/W)is

established. (notestablishment,establishment)

1. idle status2. not estabilishment3. not esabilishment

R

8 DisplaySelection SelectPVValuedisplayingontheLCDindicator.1.IndicatesdisplaystatusofPVValueofAI1 (displayed,notdisplayed)2.IndicatesdisplaystatusofPVValueofAI2 (displayed,notdisplayed)3.IndicatesdisplaystatusofPVValueofAI3 (displayed,notdisplayed)

1. displayed2. not displayed3. not displayed

W

9 LCD Mode SelectthedisplaymodeontheLCDindicator.1.IndicatestheONmode.(OFF,ON)2.Indicatesthebargraphdisplay. (bargraphnotdisplayed,bargraphdisplayed)

1. OFF2. bar graph not displayed

W

10 SpecialCmd Specialfunctionparameter.0=initializevalueatREAD(None)1=Squawkstatus2 = deep sleep status

To start from deep sleep mode, either remove and insertthebatterypack,orusetheprovisioningdevicetoolorthedeviceconfigurationtoolviainfraredcommunication.

0 W

Page 82: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-5

IM 01C27B01-01EN

ObjectID

Attribute ID Label Description Default

value Handling

4.TRANSDUCERblock(continued)

11 SpecialOrderID Displaysthespecialordernumber,ifapplicable. --- R

12 Unit Sel1 Selectswhethertoautomaticallyapplytheunittothewordfortheparameterforwhichtheunitdisplayisselected,orapplythecharactersthatarewrittentoDisplayUnit1.(Auto,Custom)

Auto W

13 Display Unit11 WhenCustomisselectedinUnitSel1,setthedisplayunitusing6charactersorless.

NULL W

14 LCD Intermittetnt Time

SetthetimetoturnoffdisplayontheLCDindicator.When0isset,itisdiplayedincontinuousmode.Unit:second

60seconds W

15 XD Filter SetthedampingtimetoTranceducervalueintheAI1ansAI2blocks.Unit:secondWhenMeasurementmodeissettocontinuousmode,it is valid.

2seconds W

16 Measurement Rate

Indicatesthecycletopublishthemeasurementvalueand status

0 R

5.AI1block

1 ProcessValue AL1isapressureoutputobject.Indicatestheprimaryanalogvalue(orcorrespondingprocessvalue)andstatususedtoexecutethisfunction.AllowsupdatingdatabyspecifyingthisfortheConcentratorobject.1.Value:outputvalueofAlobject2.Status:SpecifyoutputstatusofAlobject.

1. Value = ---2. Status = ---

W

2 BlockMode Auniversalparametertoindicatetheblock’soperationstatus.EachO/S,Auto,andMancanselectfrom.1.Target:SpecifyAlobjectmode.2.Actual:IndicatescurrentmodeofAlobject.3.Permitted:Indicatesthemodeselectedby TargetofAlobject.

4.Normal:IndicatenormalstatusmodeofAl object.

1.Target=Auto2.Actual=Auto3.Permitted=Auto4.Normal=Auto

W

3 ConcentratorOID IndicatestheConcentratorobjectvaluethatcorrespondstothedataupdateofthePVvalue.

3 R

4 Scale AllowsspecifyingtheupperorlowerlimitforthePVscaling,unitcode,etc.1.EUat100%:IndicatetheupperlimitofthePV

value.2.EUat0%:IndicatethelowerlimitofthePVvalue.3.UnitsIndex:Indicatethesettingunitusedforthe

PV value.4.Decimal:IndicatethedigitnumberbelowthedecimalpointdisplayedintheLCDindicator.

1. EU at 100% = 1002. EU at 0% = 03. Units Index = %4.Decimal=2

W

26 TagDescription Auniversalparametertostorethecommentthatdescribesthetag

Al1:DifferentialPressure

W

27 ProcessValueFilter Time

AllowsadjustingthetimeconstantforfilteringthePVvalue.Settingunit:Second.ThisisenabledfortheContinuous mode.*2

0second W

28 SimulateSwitch AsimulationfunctionswitchfortheAIobjecttest(Disable,Enable)

1(Disable) W

29 TransducerValue WhenSimulateSwitchissettoDisable,thisvalueisusedastheinputvaluefortheAIobject.RefertoFigure 10.1.

Disable R

30 Simulate Value WhenSimulateSwitchissettoEnable,thisvalueisusedastheinputvaluefortheAIobject.Theinputvaluecanbechanged.

--- W

51 Upper Limit Indicatestheupperlimit(URL)forthepressure. --- R

Page 83: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-6

IM 01C27B01-01EN

ObjectID

Attribute ID Label Description Default

value Handling

5.AI1 block(continued)

52 LowerLimit Indicatesthelowerlimit(LRL)forthepressure. --- R

53 PV Range Sets the measurement range.1.EUat100%:Indicatesinputvalueoftheupper

limit.2.EUat0%:Indicatesinputvalueofthelowerlimit.3.UnitsIndex:Indicatestheunitsofthe

measurement range.4.Decimal:Indicatesthedigitnumberbelowthedecimalpoint.

EU at 100% = 100EU at 0% = 0Units Index=kPa(1133)Decimal = 2

W

54 LinearizationType SelecteitherNoLinearizationorSquarerootasasetting of the output range.0=NoLinearization: ProvidesanoutputvaluescaledaccordingtothePVRangeandScalerangesettings.

(TouseDirectwithFF,setthesamevalueforPVRangeandScale.)

10 = Square root : ProvidesasquarerootoutputcomputedforthevaluescaledaccordingtothePVRangeandScalerange settings.

0 W

55 FlowConstant Indicatestheflowcoefficient,whichshowsthecorrelationbetweentheflowratevalueandsquarerootvalueofthedifferentialpressure.

1.0 W

56 LowerCutoff Specifiesthelowcutvalue.TheunitissubjecttoScale.UnitsIndex.

10 W

57 Cal Cmd Specifiesthecalibrationmethod.0=CAL_NONE:Initialstateinwhichcalibrationis

not performed1=CAL_LOW:AppliesanactualinputandadjuststhelowerlimitusingthevaluespecifiedinCalibrationLowestPoint.

2=CAL_HIGH:AppliesanactualinputandadjuststhehigherlimitusingthevaluespecifiedinCalibration Highest Point.

5=CAL_CLEAR:Clearstheadjustmentvariable.

0(readingvalue is always0)

W

58 Cal Status Indicatesthecalibrationstatus.0=CAL_NONE:Start-upanddefaultvalue1=CAL_SUCCESS:Indicatesthatcalibrationwassuccessful.

7=CAL_BAD_TRIM_POINT:Indicatesthisstatuswhentheadjustmentvariableisoutsideofrange.

--- R

59 Calibration Highest Point

Specifiesthehigherlimitadjustmentvariableforadjustmentbetweentwopoints.

--- W

60 CalibrationLowestPoint

Specifiesthelowerlimitadjustmentvariablefortheadjustmentbetweentwopoints.

--- W

61 Calibration Minimum Span

Indicatestheminimumspanoftheadjustmentvariable.

--- R

104 External Zero Trim Allowsperformingexternalzeroadjustment.(Trimon,Trimoff)

Trim on W

105 LowCutMode Specifiesthelowcutmode.(Linear,Zero)

Linear W

106 H/LSwap Allowsperformingreverseconnectionoftheimpulseline.(NORMAL,REVERSE:reverseconnection)Usedwhenthelowerpressuresideandhigherpressuresideoftheimpulselinewereconnectedwronglywheninstallingthepressuretransmitter.

Normal W

Page 84: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-7

IM 01C27B01-01EN

ObjectID

Attribute ID Label Description Default

value Handling

5.AI1 block(continued)

107 T Zero Cmp Parametertoselectthetemperaturezeroshiftcompensationmode0=OFF:Doesnotperformtemperaturezeroshiftcompensation.

1=ON:Performstemperaturezeroshiftcompensation.

Off w

108 Temp Zero Parameter to set the temperature gradient value for the temperaturezeroshiftcompensation

0 w

109 TempSelect Parametertoselectthetemperature(amplifier-side/capsule-side)usedforthetemperaturezeroshiftcompensation.0=AMPTEMP:thevalueoftheamplifier-side

temperature sensor is used.1=CAPTEMP:thevalueofthecapsule-side

temperature sensor is used.

1 w

6.AI2block

1 ProcessValue AI2isastaticpressureoutputobject.Indicatestheprimaryanalogvalue(orcorrespondingprocessvalue)andstatususedtoexecutethisfunction.AllowsupdatingdatabyspecifyingthisfortheConcentratorobject.1.Value:outputvalueofAlobject2.Status:SpecifyoutputstatusofAlobject.

--- W

2 BlockMode Auniversalparametertoindicatetheblock’soperationstatus.O/S,Auto,andMancanbeselected.1.Target:SpecifyAlobjectmode.2.Actual:IndicatescurrentmodeofAlobject.3.Permitted:IndicatesthemodeselectedbyTargetofAlobject.

4.Normal:IndicatenormalstatusmodeofAlobject.

1.Target = O/S2.Actual= O/S3.Permitted = O/S4.Normal = O/S

W

3 ConcentratorOID IndicatestheConcentratorobjectvaluethatcorrespondstothedataupdateofthePVvalue.

3 R

4 Scale AllowsspecifyingtheupperorlowerlimitforthePVscaling,unitcode,etc.1.EUat100%:IndicatetheupperlimitofthePV

value.2.EUat0%:IndicatethelowerlimitofthePVvalue.3.UnitsIndex:Indicatethesettingunitusedforthe

PV value.4.Decimal:IndicatethedigitnumberbelowthedecimalpointdisplayedintheLCDindicator.

1. EU at 100% = 1002. EU at 0% = 03. Units Index = %4.Decimal = 2

W

26 TagDescription Auniversalparametertostorethecommentthatdescribesthetag.

AI2:StaticPressure

W

27 ProcessValueFilter Time

AllowsadjustingthetimeconstantforfilteringthePVvalue.Settingunit:Second.ThisisenabledfortheContinuous mode.*2

0second W

28 SimulateSwitch AsimulationfunctionswitchfortheAIobjecttest(Disable,Enable)

Disable W

29 TransducerValue WhenSimulateSwitchissettoDisable,thisvalueisusedastheinputvaluefortheAIobject.

--- R

30 Simulate Value WhenSimulateSwitchissettoEnable,thisvalueisusedastheinputvaluefortheAIobject.Theinputvaluecanbechanged.

--- W

51 Upper Limit Indicatestheupperlimit(URL)forthepressure. --- R

52 LowerLimit Indicatesthelowerlimit(LRL)forthepressure. --- R

Page 85: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-8

IM 01C27B01-01EN

ObjectID

Attribute ID Label Description Default

value Handling

6.AI2 block(continued)

53 PV Range Sets the measurement range.1.EUat100%:Indicatesinputvalueoftheupper

limit.2.EUat0%:Indicatesinputvalueofthelowerlimit.3.UnitsIndex:Indicatestheunitsofthe

measurement range.4.Decimal:Indicatesthedigitnumberbelowthedecimalpoint.

1. EU at 100% = 25000.000000EU at 0% = 0Units Index=kPaDecimal = 2

W

54 LinearizationType SelecteitherNoLinearizationorSquarerootasasetting of the output range.0=NoLinearization: ProvidesanoutputvaluescaledaccordingtothePVRangeandScalerangesettings.

(TouseDirectwithFF,setthesamevalueforPVRangeandScale.)

0 W

55 FlowConstant Indicatestheflowcoefficient,whichshowsthecorrelationbetweentheflowratevalueandsquarerootvalue of the pressure.

1.0 W

56 LowerCutoff Specifiesthelowcutvalue.TheunitissubjecttoScale.UnitsIndex.

10 W

57 Cal Cmd Specifiesthecalibrationmethod.0=CAL_NONE:Initialstateinwhichcalibrationis

not performed1=CAL_LOW:AppliesanactualinputandadjuststhelowerlimitusingthevaluespecifiedinCalibrationLowestPoint.

2=CAL_HIGH:AppliesanactualinputandadjuststhehigherlimitusingthevaluespecifiedinCalibration Highest Point.

5=CAL_CLEAR:Clearstheadjustmentvariable.

0(readingvalue is always0)

W

58 Cal Status Indicatesthecalibrationstatus.0=CAL_NONE:Start-upanddefaultvalue1=CAL_SUCCESS:Indicatesthatcalibrationwassuccessful.

7=CAL_BAD_TRIM_POINT:Indicatesthisstatuswhentheadjustmentvariableisoutsideofrange.

R

59 Calibration Highest Point

Specifiesthehigherlimitadjustmentvariableforadjustmentbetweentwopoints.

--- W

60 CalibrationLowestPoint

Specifiesthelowerlimitadjustmentvariablefortheadjustmentbetweentwopoints.

--- W

61 Calibration Minimum Span

Indicatestheminimumspanoftheadjustmentvariable.108 = Gauge pressure109 = Absolute pressure

--- R

102 StaticProcessType

Selectsthegaugepressureortheabsolutepressure. Abs W

103 SPSelect ParametertoselecttheHigh-sidepressureortheLow-sidepressureasthestaticpressureoutput.0=High:DisplaystheH-sidepressureasthestatic

pressure1=Low:DisplaystheL-sidepressureasthestatic

pressure

High W

7.AI3 block

1 ProcessValue Al3isatemperaturepressureoutputobject.Indicatestheprimaryanalogvalue(orcorrespondingprocessvalue)andstatususedtoexecutethisfunction.AllowsupdatingdatabyspecifyingthisfortheConcentratorobject.1.Value:outputvalueofAlobject2.Status:SpecifyoutputstatusofAlobject.

1. Value = ---2. Status = ---

W

Page 86: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-9

IM 01C27B01-01EN

ObjectID

Attribute ID Label Description Default

value Handling

7.AI3 block(continued)

2 BlockMode Auniversalparametertoindicatetheblock’soperationstatus.O/S,Auto,andMancanbeselected.1.Target:SpecifyAlobjectmode.2.Actual:IndicatescurrentmodeofAlobject.3.Permitted:IndicatesthemodeselectedbyTargetofAlobject.

4.Normal:IndicatenormalstatusmodeofAlobject.

1. Target = Auto2.Actual=Auto3. Permitted = O/S+Auto +Man4. Normal = Auto

W

3 ConcentratorOID IndicatestheConcentratorobjectvaluethatcorrespondstothedataupdateofthePVvalue.

3 R

4 Scale AllowsspecifyingtheupperorlowerlimitforthePVscaling,unitcode,etc.1.EUat100%:IndicatetheupperlimitofthePV

value.2.EUat0%:IndicatethelowerlimitofthePVvalue.3.UnitsIndex:Indicatethesettingunitusedforthe

PV value.4.Decimal:IndicatethedigitnumberbelowthedecimalpointdisplayedintheLCDindicator.

1. EU at 100% = 1002. EU at 0% = 03. Units Index = %4.Decimal=2

W

26 TagDescription Auniversalparametertostorethecommentthatdescribesthetag

AI3: Capsule temperature

W

27 ProcessValueFilter Time

AllowsadjustingthetimeconstantforfilteringthePVvalue. Settingunit:Second.ThisisenabledfortheContinuous mode.

0second W

28 SimulateSwitch AsimulationfunctionswitchfortheAIobjecttest(Disable,Enable)

Disable W

29 TransducerValue WhenSimulateSwitchissettoDisable,thisvalueisusedastheinputvaluefortheAIobject.

--- R

30 Simulate Value WhenSimulateSwitchissettoEnable,thisvalueisusedastheinputvaluefortheAIobject.Theinputvaluecanbechanged.

--- W

53 Sensor Range Parametertonondimensionalizethesensoroutputvalue. KanddegCareselectableforthetemperatureunit.1.EUat100%:Indicatesinputvalueoftheupper

limit.2.EUat0%:Indicatesinputvalueofthelowerlimit.3.UnitsIndex:Indicatestheunitsofthe

measurement range.4.Decimal:Indicatesthedigitnumberbelowthedecimalpoint.

1. EU at 100% = 1302. EU at 0% = -503. Units Index = deg C4.Decimal=0

W

102 Tertiary Value Select

Specifieseitherthecapsuletemperatureoramplifiertemperature as the output value.(CAP,AMP)

CAP W

(Note)Handling:R=Readonly,W=Read&Write(Note)“FactoryNAMURcategory”referstothefourcategories(C:Checkfunction,M:Maintenancerequired,F:Failure,andO:Off

specification)accordingtoNAMURNE107*.

*1: NAMURNE107“Self-MonitoringandDiagnosisofFieldDevices”*2: Itisvalidfornotonlycontinuousmodebutalsointermittentmode.

Page 87: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<10. Parameter Summary> 10-10

IM 01C27B01-01EN

Table 10.2 Diagnostic Status Detail[0]

Bit Diagnostic Status Detail Description Diagnostic Status assignment bit NAMUR

DiagnosticDetail_131 FC_SENSOR_FAIL Csensorfrequencyerror Bit26 F30 FR_SENSOR_FAIL Rsensorfrequencyerror Bit26 F29 CAP_T_SENSOR_FAIL Capsule temperature sensor failure Bit26 F28 CAP_EEPROM_FAIL Capsule EEPROM failure Bit26 F27 CAP_EEP_IRREGULAR CAPEEPROMversionnotcorrect Bit26 F25 AMP_EEPROM_FAIL AmplifierEEPROMfailure Bit27 F24 AMP_EEP_IRREGULAR AMPEEPROMversionnotcorrect Bit27 F22 G_A_COMM_FAIL G/A failure Bit27 F21 FC_UNOSC_FAIL Csensoroscillationstopfailure Bit26 F20 FC_DELTA_T_FAIL C-sidedeltaTcircuitfailure Bit27 F19 FR_DELTA_T_FAIL R-sidedeltaTcircuitfailure Bit27 F18 WL_AD_FAIL Batteryvoltagenotdetected(AMPfailure) Bit27 F17 FR_UNOSC_FAIL Rsensoroscillationstopfailure Bit26 F15 DP_OUTSIDE_LIMIT Pressureoutsideofspecifiedrange Bit23 O14 SP_OUTSIDE_LIMIT Staticpressureoutsideofspecifiedrange Bit23 O13 CAPT_OUTSIDE_LIMIT Capsuletemperatureoutsideofspecifiedrange Bit23 O12 AMPT_OUTSIDE_LIMIT Amplifiertemperatureoutsideofspecifiedrange Bit23 O7 DP_OUTSIDE_RANGE Input pressure setting outside of range Bit22 O6 SP_OUTSIDE_RANGE Staticpressuresettingoutsideofrange Bit22 ODiagnosticDetail_231 AI1_OUT_OF_SERVICE AI1 O/S mode Bit24 C30 AI2_OUT_OF_SERVICE AI2 O/S mode Bit24 C29 AI3_OUT_OF_SERVICE AI3 O/S mode Bit24 C28 AI1_SIMULATION_ACTIVE AI1 simulation mode Bit17 C27 AI2_SIMULATION_ACTIVE AI2 simulation mode Bit17 C26 AI3_SIMULATION_ACTIVE AI3 simulation mode Bit17 C20 DP_TRIM_SPAN_OUTSIDE Pressure span adjustment variable outside of range Bit25 C19 DP_TRIM_ZERO_OUTSIDE Pressurezeroadjustmentvariableoutsideofrange Bit25 C15 SP_TRIM_SPAN_OUTSIDE Staticpressurespanadjustmentvariableoutsideof

rangeBit25 C

14 SP_TRIM_ZERO_OUTSIDE Staticpressurezeroadjustmentvariableoutsideofrange

Bit25 C

13 WL_LOWBAT_ALM*1 Detectionofadecreaseinthebatteryvoltage Bit19 M12 CRITICAL_LOWBAT*1 Detectionofanextremedecreaseinthebattery

voltageBit20 M

8 LCD_OUTSIDE_LIMIT LCDdisplayoutsideofspecifiedrange Bit25 C

*1: Onlyapplicableforthebatterypoweredtype.

F1001.ai

AI algoritm

MODE Targetfrom operator

from operator

from operator

from transducer

SIMULATE

On

Off

AIalgorithm

Linearizationscaling,

filter

Alertreport

HiHi etc

PV

Auto

O/S

Man

PublishValue

& StatusPV

PV

Value& Status

Value& Status

Value& Status

Mode andPV.Status handling

SWITCHSIMULATE

_VALUE

Figure 10.1 Example schema of analog input object

Page 88: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-1

IM 01C27B01-01EN

11. General Specifications11.1 Standard SpecificationsCommunication protocol

ISA100.11aprotocol

Data rate250kbps

Frequency2400-2483.5MHzlicensefreeISMband

Radio security AES128bitcodified

RF Transmitter power Max. 11.6 dBm

Antenna +2dBiOmnidirectionalmonopoletype

Span and range limits

EJX110BMeasurement Span/Range kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)

FSpan 0.1 to 5 0.4 to 20 1 to 50 10 to 500

Range -5 to 5 -20 to 20 -50 to 50 -500 to 500

LSpan 0.1 to 10 0.4 to 40 1 to 100 10 to 1000

Range -10 to 10 -40 to 40 -100 to 100 -1000 to 1000

MSpan 0.5 to 100 2 to 400 5 to 1000 50 to 10000

Range -100 to 100 -400 to 400 -1000 to 1000-10000 to

10000

HSpan 2.5 to 500 10 to 2000 25 to 5000

0.025 to 5 kgf/cm2

Range -500 to 500 -2000 to 2000 -5000 to 5000-5 to 5 kgf/cm2

VSpan

0.07 to 14 MPa

10 to 2000 psi 0.7 to 140 bar0.7 to 140 kgf/cm2

Range-0.5 to 14

MPa-71 to 2000

psi-5 to 140 bar

-5 to 140 kgf/cm2

EJX310BMeasurement Span/Range kPa abs psi abs(/D1) mbar abs

(/D3)mmHg abs

(/D4)

LSpan 0.5 to 10

0.15 to 2.95 inHg

5 to 100 3.8 to 75

Range 0 to 10 0 to 2.95 inHg 0 to 100 0 to 75

MSpan 1.3 to 130

0.39 to 38 inHg

13 to 1300 9.8 to 970

Range 0 to 130 0 to 38 inHg 0 to 1300 0 to 970

ASpan

0.0175 to 3.5 MPa

2.5 to 5000.175 to 35

bar0.175 to 35 kgf/cm2

Range0 to 3.5

MPa0 to 500 0 to 35 bar

0 to 35 kgf/cm2

BSpan

0.08 to 16 MPa

12 to 2300 0.8 to 160 bar0.8 to 160 kgf/cm2

Range 0 to 16 MPa 0 to 2300 0 to 160 bar0 to 160 kgf/cm2

EJX430BMeasurement Span/Range MPa psi(/D1) bar(/D3) kgf/cm2(/D4)

HSpan

2.5 to 500 kPa

10 to 2000 inH2O

0.025 to 5 0.025 to 5

Range-100 to 500

kPa-400 to 2000

inH2O-1 to 5 -1 to 5

ASpan

0.0175 to 3.5

2.5 to 500 0.175 to 35 0.175 to 35

Range -0.1 to 3.5 -14.5 to 500 -1 to 35 -1 to 35

BSpan 0.08 to 16 12 to 2300 0.8 to 160 0.8 to 160

Range -0.1 to 16 -14.5 to 2300 -1 to 160 -1 to 160

Performance specificationsRefer to GS01C27B01-01EN.

Update TimeMeasurement

modeDifferentialpressure Pressure

Continuous 100 ms 100 ms

Intermittent 0.5 to 3600 sselectable

0.5 to 3600 sselectable

Thetransmittershiftstothecountinuousmodewhentheupdatetimeissetto0.5second.

Power Supply SpecificationsBattery:Usethededicatedbatterypack.Rated voltage: 7.2 VRatedcapacity:19Ah

ExternalPowerSource:Rated voltage: 10.5 to 30 V DCRatedcurrent:36mA

OutputISA100.11aprotocol

Output mode (EJX110B) linear or square root

Ambient Temperature Limits-40to85°C(-40to185°F)-30to80°C(-22to176°F)LCDvisiblerange

Process Temperature Limits-40to120°C(-40to248°F)-40to100°C(-40to212°F) –EJX310BwithcapsulecodeL0to120°C(32to248°F) –Withoptioncode/HD

Ambient Humidity Limits0 to 100% RH

Page 89: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-2

IM 01C27B01-01EN

Working Pressure Limits (Silicone oil)Maximum Pressure Limits:EJX110B

Capsule PressureF, L 16MPa(2300psi)

M, H, V 25MPa(3600psi)* *16MPaforwettedpartsmaterialcodeH,M,T,A,D,and

B,optioncode/HDor/HD2.

EJX310BCapsule Pressure

L 10kPaabs(2.95inHgabs)M 130kPaabs(38inHgabs)A 3.5MPaabs(500psia)B 16MPaabs(2300psia)

EJX430BCapsule Pressure

H 500kPa(2000inH2O)A 3.5MPa(500psi)B 16MPa(2300psi)

Zero Adjustment LimitsZerocanbefullyelevatedorsuppressed,withinthelowerandupperrangelimitsofthecapsule.

External Zero AdjustmentExternalzeroiscontinuouslyadjustablewith0.01%incrementalresolutionofspan.Re-rangecanbedonelocallyusingthedigitalindicatorwithrangesettingswitch.

Integral Indicator (LCD display)5-digitnumericaldisplay,6-digitunitdisplayandbar graph.Theindicatorisconfigurabletodisplayoneoruptothreeofthefollowingvariablesperiodically.;Differentialpressure,staticpressure,temperature.

EMC Conformity StandardsEN61326-1ClassA,Table2(Foruseinindustriallocations),EN61326-2-3Immunity influence during the testDifferentialpressure/pressure:Outputshiftisspecifiedwithin±1%of1/10Maxspan.Staticpressure:Outputshiftisspecifiedwithin±5%of1MPaspan.

Radio Equipment Directive (RE) ETSI EN 300 328, ETSI EN 301 489-1, ETSI EN 301 489-17, EN61010-1, EN61010-2-030, EN62311• Indoor/Outdoor use

Regulation Conformity of the Wireless Module• FCC Approval• IC Approval

Safety Requirement StandardsEN61010-1, EN61010-2-030• Altitude of installation site:

Max. 2,000 m above sea level•Installationcategory:I (Anticipatedtransientovervoltage330V)

• Pollution degree: 2• Indoor/Outdoor use

Degrees of ProtectionIP66/IP67, NEMA4X

ConnectionsReferto“MODELANDSUFFIXCODES.”

Wetted Parts MaterialsDiaphragm, Cover Flange, Process Connector, Capsule Gasket, and Vent/Drain PlugReferto“MODELANDSUFFIXCODES.”

Process Connector GasketPTFETeflonFluorinatedrubberforoptioncodeN2andN3

Non-wetted Parts MaterialsBoltingASTM-B7carbonsteel,316LSSTstainlesssteel, or ASTM grade 660 stainless steel

HousingLowcoppercastaluminumalloywithpolyurethane,mint-greenpaint(Munsell5.6BG3.3/2.9oritsequivalent)

Name plate and tag316SSTtagplatewiredontotransmitter

Weight4.9kg(10.8lb)*-Wettedpartsmaterialcode:S(exceptforMeasurementspancodeF,optioncode/HDor/HD2)

5.8kg(12.8lb)*-Wettedpartsmaterialcode:H,M,T,A,B,D,Measurementspancode:F,optioncode/HDor /HD2

*Theweightdoesnotincludethatofbatterypack,mountingbracketandprocessconnector. Add0.3kgfortheexternalpoweredtype.

Page 90: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-3

IM 01C27B01-01EN

Minimum Pressure LimitSeegraphbelow

EJX110B and EJX430B

Atmosphericpressure

-40(-40)

0(32)

40(104)

80(176)

120(248)

1(0.14)

2.7(0.38)

10(1.4)

(psi abs)

100(14.5)

Process temperature °C (°F)

WorkingpressurekPa abs

Applicable range

F1101.ai

EJX310B

-40(-40)

0(32)

40(104)

80(176)

120 (248)

0.1(0.75)0.13(1)

1(7.5)

100(750)

10(75)

2.7(20)

0.46(3.45)

0.01(0.075) 0.013(0.1)

85 (185)

(mmHg abs)

WorkingpressurekPa abs

Process temperature °C (°F)

M,A and B capsule

L capsule

F1102.ai

Applicable range

Figure 1. Working pressure and Process Temperature

Page 91: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-4

IM 01C27B01-01EN

11.2 Model and Suffix CodesModel EJX110B

Model Suffix Codes DescriptionEJX110B . . . . . . . . . . . . . . . . . . . . . . Differentialpressuretransmitter

Output signal -L . . . . . . . . . . . . . . . . . . . .-1 . . . . . . . . . . . . . . . . . . . .

Wirelesscommunication(ISA100.11aprotocol)Wirelesscommunication(ISA100.11aprotocol);successorofcode-L

Measurementspan(capsule)

F . . . . . . . . . . . . . . . . . . .L . . . . . . . . . . . . . . . . . . .

M . . . . . . . . . . . . . . . . . .H. . . . . . . . . . . . . . . . . . .V . . . . . . . . . . . . . . . . . . .

0.1to5kPa(0.4to20inH2O)(ForwettedpartsmaterialcodeS)0.1to10kPa(0.4to40inH2O)(ForwettedpartsmaterialcodeM,H,T,A,

DandB)0.5to100kPa(2to400inH2O)2.5to500kPa(10to2000inH2O)0.07to14MPa(10to2000psi)

Wetted partsmaterial *1

. . . . . . . . . . . . . . . . . Referto“WettedPartsMaterials”Table1.

Processconnections

0 . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . .2 . . . . . . . . . . . . . . . .3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

withoutprocessconnector(Rc1/4femaleonthecoverflanges)withRc1/4femaleprocessconnectorwithRc1/2femaleprocessconnectorwith1/4NPTfemaleprocessconnectorwith1/2NPTfemaleprocessconnectorwithoutprocessconnector(1/4NPTfemaleonthecoverflanges)

Bolts and nuts material J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7carbonsteel316L SST stainless steelASTM grade 660 stainless steel

Installation

-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-B . . . . . . . . . . .-U . . . . . . . . . . .

Verticalpiping,leftsidehighpressure,andprocessconnectiondownsideHorizontalpipingandrightsidehighpressureHorizontalpipingandleftsidehighpressureBottomProcessConnection,leftsidehighpressure*2

Universalflange*2

Amplifierhousing 8 . . . . . . . . . .9 . . . . . . . . . .

Castaluminumalloywithdetachableantenna(2dBi)*4Castaluminumalloywithoutantenna(Nconnector)*3*4

Electricalconnection J . . . . . . . . .

0 . . . . . . . . .

2 . . . . . . . . .

4 . . . . . . . . .

5 . . . . . . . . .

7 . . . . . . . . .

9 . . . . . . . . .

A. . . . . . . . .

C. . . . . . . . .

D. . . . . . . . .

Noelectricalconnection,batterypoweredtype(batterycaseonly;batterycellsnotincluded)

G1/2female,oneelectricalconnectionwithoutablindplug,andexternalpoweredtype

1/2NPTfemale,twoelectricalconnectionswithoutablindplug,andexternalpoweredtype

M20female,twoelectricalconnectionswithoutblindplugs,externalpoweredtype

G1/2female,twoelectricalconnectionswithablindplug,andexternalpoweredtype*5

1/2NPTfemale,twoelectricalconnectionswithablindplug,andexternalpoweredtype*5

M20female,twoelectricalconnectionsandablindplug,externalpoweredtype*5

G1/2female,twoelectricalconnectionswitha316SSTblindplug,andexternalpoweredtype

1/2NPTfemale,twoelectricalconnectionswitha316SSTblindplug,andexternalpoweredtype

M20female,twoelectricalconnectionsanda316SSTblindplug,externalpoweredtype

Integralindicator ► D. . . . . . . DigitalindicatorMountingbracket ► B. . . . .

D. . . . .K. . . . .M . . . .

N. . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304SSTorSCS13A2-inchpipemounting,Ltype(forverticalpiping)316SSTorSCS14A2-inchpipemounting,Ltype(forverticalpiping)316SSTorSCS14A2-inchpipemounting(forbottomprocess

connectiontype)None

Optionalcodes / OptionalspecificationThe“►”marksindicatethemosttypicalselectionforeachspecification.

Page 92: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-5

IM 01C27B01-01EN

*1: ! Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandtheinfluenceofprocessfluids.Theuseofinappropriatematerialscanresultintheleakageofcorrosiveprocessfluidsandcauseinjurytopersonneland/ordamagetoplantfacilities.Itisalsopossiblethatthediaphragmitselfcanbedamagedandthatmaterialfromthebrokendiaphragmandthefillfluidcancontaminatetheuser’sprocessfluids.

Beverycarefulwithhighlycorrosiveprocessfluidssuchashydrochloricacid,sulfuricacid,hydrogensulfide,sodiumhypochlorite,andhigh-temperaturesteam(150°C[302°F]orabove).ContactYokogawafordetailedinformationofthewettedpartsmaterial.

*2: ApplicableforwettedpartsmaterialcodeS.*3: Ordertheantennaseparatelyfromaccessaryoption.*4: Remoteantennacablescanbeattached.Orderseparatelyfromaccessaryoption.*5: Materialofablindplug;aluminumalloyforcode5and9,and304SSTforcode7.

Table 1. Wetted Parts Materials

Wetted partsmaterial code

Cover flange andprocess connector Capsule Capsule gasket Vent/Drain plug

S ASTM CF-8M *1 Hastelloy C-276 *2(Diaphragm)F316LSST,316LSST(Others) Teflon-coated316LSST 316 SST

H ASTM CF-8M *1 Hastelloy C-276 *2 PTFETeflon 316 SSTM ASTM CF-8M *1 Monel PTFETeflon 316 SSTT ASTM CF-8M *1 Tantalum PTFETeflon 316 SST

A Hastelloy C-276 equivalent *3 Hastelloy C-276 *2 PTFETeflon Hastelloy C-276 *2

D Hastelloy C-276 equivalent *3 Tantalum PTFETeflon Hastelloy C-276 *2

B Monel equivalent *4 Monel PTFETeflon Monel

*1: Cast version of 316 SST. Equivalent to SCS14A.*2: Hastelloy C-276 or ASTM N10276.*3: IndicatedmaterialisequivalenttoASTMCW-12MW.*4: IndicatedmaterialisequivalenttoASTMM35-2.

Page 93: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-6

IM 01C27B01-01EN

Model EJX310BModel Suffix Codes Description

EJX310B . . . . . . . . . . . . . . . . . . . . . . Absolute pressure transmitterOutput signal

-L . . . . . . . . . . . . . . . . . . . .-1 . . . . . . . . . . . . . . . . . . . .

Wirelesscommunication(ISA100.11aprotocol)Wirelesscommunication(ISA100.11aprotocol);successorofcode-L

Measurementspan(capsule)

L . . . . . . . . . . . . . . . . . . .M . . . . . . . . . . . . . . . . . .A. . . . . . . . . . . . . . . . . . .B. . . . . . . . . . . . . . . . . . .

0.5to10kPaabs(0.15to2.95inHgabs)1.3to130kPaabs(0.39to38inHgabs)0.0175to3.5MPaabs(2.5to500psia)0.08to16MPaabs(12to2300psia)

Wetted partsmaterial *1

S. . . . . . . . . . . . . . . . . . Referto“WettedPartsMaterials”Table2.

Processconnections

0 . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . .2 . . . . . . . . . . . . . . . .3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

withoutprocessconnector(Rc1/4femaleonthecoverflanges)withRc1/4femaleprocessconnectorwithRc1/2femaleprocessconnectorwith1/4NPTfemaleprocessconnectorwith1/2NPTfemaleprocessconnectorwithoutprocessconnector(1/4NPTfemaleonthecoverflanges)

Bolts and nuts material

J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7carbonsteel316L SST stainless steelASTM grade 660 stainless steel

Installation

-3 . . . . . . . . . . .-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-B . . . . . . . . . . .-U . . . . . . . . . . .

Verticalpiping,rightsidehighpressure,andprocessconnectiondownsideVerticalpiping,leftsidehighpressure,andprocessconnectiondownsideHorizontalpipingandrightsidehighpressureHorizontalpipingandleftsidehighpressureBottomProcessConnection,leftsidehighpressureUniversalflange

Amplifierhousing 8 . . . . . . . . . .9 . . . . . . . . . .

Castaluminumalloywithdetachableantenna(2dBi)*3Castaluminumalloywithoutantenna(Nconnector)*2*3

Electricalconnection J . . . . . . . . .

0 . . . . . . . . .

2 . . . . . . . . .

4 . . . . . . . . .

5 . . . . . . . . .

7 . . . . . . . . .

9 . . . . . . . . .

A. . . . . . . . .

C. . . . . . . . .

D. . . . . . . . .

Noelectricalconnection,batterypoweredtype(batterycaseonly;batterycellsnotincluded)

G1/2female,oneelectricalconnectionwithoutablindplug,andexternalpoweredtype

1/2NPTfemale,twoelectricalconnectionswithoutablindplug,andexternalpoweredtype

M20female,twoelectricalconnectionswithoutblindplugs,externalpoweredtype

G1/2female,twoelectricalconnectionswithablindplug,andexternalpoweredtype*4

1/2NPTfemale,twoelectricalconnectionswithablindplug,andexternalpoweredtype*4

M20female,twoelectricalconnectionsandablindplug,externalpoweredtype*4

G1/2female,twoelectricalconnectionswitha316SSTblindplug,andexternalpoweredtype

1/2NPTfemale,twoelectricalconnectionswitha316SSTblindplug,andexternalpoweredtype

M20female,twoelectricalconnectionsanda316SSTblindplug,externalpoweredtype

Integralindicator D. . . . . . . DigitalindicatorMountingbracket ► B. . . . .

D. . . . .K. . . . .M . . . .

N. . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304SSTorSCS13A2-inchpipemounting,Ltype(forverticalpiping)316SSTorSCS14A2-inchpipemounting,Ltype(forverticalpiping)316SSTorSCS14A2-inchpipemounting(forbottomprocessconnection

type)None

Optionalcodes / OptionalspecificationThe“►”marksindicatethemosttypicalselectionforeachspecification.*1: ! Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandinfluenceofprocessfluids.Specifyinginappropriate

materialshasthepotentialtocauseseriousdamagetohumanbodyandplantfacilitiesresultedfromanunexpectedleakofthecorrosiveprocessfluids.

*2: Ordertheantennaseparatelyfromaccessaryoption.*3: Remoteantennacablescanbeattached.Orderseparatelyfromaccessaryoption.*4: Materialofablindplug;aluminumalloyforcode5and9,and304SSTforcode7.

Page 94: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-7

IM 01C27B01-01EN

Table 2. Wetted Parts MaterialsWetted partsmaterial code

Cover flange andprocess connector Capsule Capsule gasket Vent/Drain plug

S ASTM CF-8M *1 Hastelloy C-276 *2(Diaphragm)316LSST(Others) Teflon-coated316LSST 316 SST

*1: Cast version of 316 SST. Equivalent to SCS14A.*2: Hastelloy C-276 or ASTM N10276.

Page 95: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-8

IM 01C27B01-01EN

Model EJX430BModel Suffix Codes Description

EJX430B . . . . . . . . . . . . . . . . . . . . . . Gauge pressure transmitterOutput signal

-L . . . . . . . . . . . . . . . . . . . .-1 . . . . . . . . . . . . . . . . . . . .

Wirelesscommunication(ISA100.11aprotocol)Wirelesscommunication(ISA100.11aprotocol);successorofcode-L

Measurementspan(capsule)

H. . . . . . . . . . . . . . . . . . .A. . . . . . . . . . . . . . . . . . .B. . . . . . . . . . . . . . . . . . .

2.5to500kPa(10to2000inH2O)0.0175to3.5MPa(2.5to500psi)0.08to16MPa(12to2300psi)

Wetted partsmaterial *1

. . . . . . . . . . . . . . . . . Referto“WettedPartsMaterials”Table3.

Processconnections

0 . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . .2 . . . . . . . . . . . . . . . .3 . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . .

withoutprocessconnector(Rc1/4femaleonthecoverflanges)withRc1/4femaleprocessconnectorwithRc1/2femaleprocessconnectorwith1/4NPTfemaleprocessconnectorwith1/2NPTfemaleprocessconnectorwithoutprocessconnector(1/4NPTfemaleonthecoverflanges)

Bolts and nuts materia

J . . . . . . . . . . . . . .G. . . . . . . . . . . . . .C. . . . . . . . . . . . . .

ASTM-B7carbonsteel316L SST stainless steelASTM grade 660 stainless steel

Installation

-3 . . . . . . . . . . .-7 . . . . . . . . . . .-8 . . . . . . . . . . .-9 . . . . . . . . . . .-B . . . . . . . . . . .-U . . . . . . . . . . .

Verticalpiping,rightsidehighpressure,andprocessconnectiondownsideVerticalpiping,leftsidehighpressure,andprocessconnectiondownsideHorizontalpipingandrightsidehighpressureHorizontalpipingandleftsidehighpressureBottomProcessConnection,leftsidehighpressure*2Universalflange*2

Amplifierhousing 8 . . . . . . . . . .9 . . . . . . . . . .

Castaluminumalloywithdetachableantenna(2dBi)*4Castaluminumalloywithoutantenna(Nconnector)*3*4

Electricalconnection J . . . . . . . . .

0 . . . . . . . . .

2 . . . . . . . . .

4 . . . . . . . . .

5 . . . . . . . . .

7 . . . . . . . . .

9 . . . . . . . . .

A. . . . . . . . .

C. . . . . . . . .

D. . . . . . . . .

Noelectricalconnection,batterypoweredtype(batterycaseonly;batterycellsnotincluded)

G1/2female,oneelectricalconnectionwithoutablindplug,andexternalpoweredtype

1/2NPTfemale,twoelectricalconnectionswithoutablindplug,andexternalpoweredtype

M20female,twoelectricalconnectionswithoutblindplugs,externalpoweredtype

G1/2female,twoelectricalconnectionswithablindplug,andeexternalpoweredtype*5

1/2NPTfemale,twoelectricalconnectionswithablindplug,andexternalpoweredtype*5

M20female,twoelectricalconnectionsandablindplug,externalpoweredtype*5

G1/2female,twoelectricalconnectionswitha316SSTblindplug,andexternalpoweredtype

1/2NPTfemale,twoelectricalconnectionswitha316SSTblindplug,andexternalpoweredtype

M20female,twoelectricalconnectionsanda316SSTblindplug,externalpoweredtype

Integralindicator D. . . . . . . DigitalindicatorMountingbracket ► B. . . . .

D. . . . .K. . . . .M . . . .

N. . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304SSTorSCS13A2-inchpipemounting,Ltype(forverticalpiping)316SSTorSCS14A2-inchpipemounting,Ltype(forverticalpiping)316SSTorSCS14A2-inchpipemounting(forbottomprocessconnection

type)None

Optional Codes / OptionalspecificationThe“►”marksindicatethemosttypicalselectionforeachspecification.*1: ! Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandtheinfluenceofprocessfluids.Theuseof

inappropriatematerialscanresultintheleakageofcorrosiveprocessfluidsandcauseinjurytopersonneland/ordamagetoplantfacilities.Itisalsopossiblethatthediaphragmitselfcanbedamagedandthatmaterialfromthebrokendiaphragmandthefillfluidcancontaminatetheuser’sprocessfluids.

Beverycarefulwithhighlycorrosiveprocessfluidssuchashydrochloricacid,sulfuricacid,hydrogensulfide,sodiumhypochlorite,andhigh-temperaturesteam(150°C[302°F]orabove).ContactYokogawafordetailedinformationofthewettedpartsmaterial.

*2: ApplicableforWettedpartsmaterialcodeS.*3: Ordertheantennaseparatelyfromaccessaryoption.*4: Remoteantennacablescanbeattached.Orderseparatelyfromaccessaryoption.*5: Materialofablindplug;aluminumalloyforcode5and9,and304SSTforcode7.

Page 96: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-9

IM 01C27B01-01EN

Table 3. Wetted Parts MaterialsWetted partsmaterial code

Cover flange andprocess connector Capsule Capsule gasket Vent/Drain plug

S ASTM CF-8M *1 Hastelloy C-276 *2(Diaphragm)316LSST(Others) Teflon-coated316LSST 316 SST

H ASTM CF-8M *1 Hastelloy C-276 *2 PTFETeflon 316 SSTM ASTM CF-8M *1 Monel PTFETeflon 316 SSTT ASTM CF-8M *1 Tantalum PTFETeflon 316 SST

A Hastelloy C-276 equivalent *3 Hastelloy C-276 *2 PTFETeflon Hastelloy C-276 *2

D Hastelloy C-276 equivalent *3 Tantalum PTFETeflon Hastelloy C-276 *2

B Monel equivalent *4 Monel PTFETeflon Monel

*1: Cast version of 316 SST. Equivalent to SCS14A.*2: Hastelloy C-276 or ASTM N10276.*3: IndicatedmaterialisequivalenttoASTMCW-12MW.*4: IndicatedmaterialisequivalenttoASTMM35-2.

11.3 Optional Specifications OPTIONAL SPECIFICATIONS (For Explosion Protected type)

Item Description CodeFactoryMutual(FM) FMIntrinsicallysafeApproval FS17*ATEX ATEXIntrinsicallysafeApproval KS27*CanadianStandardsAssociation(CSA) CSAIntrinsicallysafeApproval CS17*IECEx IECExIntrinsicallysafeApproval SS27*

*OnlyapplicableforselectingElectricalconnectioncodeJ.

Page 97: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-10

IM 01C27B01-01EN

OPTIONAL SPECIFICATIONSItem Description Code

Painting Colorchange Amplifiercoveronly PCoatingchange Anti-corrosioncoating*1 X2

Oil-prohibited use*2 Degreasecleansingtreatment K1Degreasecleansingtreatmentandwithfluorinatedoilfilledcapsule.Operatingtemperature-20to80°C(-4to176°F) K2

Oil-prohibited usewithdehydratingtreatment*2

Degreasecleansingtreatmentanddehydratingtreatment K5Degreasecleansingtreatmentanddehydratingtreatmentwithfluorinatedoilfilledcapsule.Operatingtemperature-20to80°C(-4to176°F)

K6

Capsulefillfluid FluorinatedoilfilledincapsuleOperatingtemperature-20to80°C(-4to176°F) K3

Calibration units*3 Pcalibration(psiunit)(SeeTableforSpanandRangeLimits.)

D1barcalibration(barunit) D3Mcalibration(kgf/cm2unit) D4

Long vent*4 Totallength:119mm(standard:34mm);TotallengthwhencombiningwithoptioncodeK1,K2,K5,andK6:130mm.Material:316SST U1

Gold-platedcapsulegasket*5 Gold-plated316LSSTcapsulegasket.Withoutdrainandventplugs. GSGold-plated diaphragm*6 Surfaceofisolatingdiaphragmsaregoldplated,effectiveforhydrogen

permeation. A1

130Paabscalibration*7 Minimuminputpuressureatcalibrationtesting:130Paabs(1mmHgabs) S1Body option*8 Without drain and vent plugs. N1

N1andProcessconnection,basedonIEC61518withfemalethreadonbothsidesofcoverflange,withblindkidneyflangesonback. N2

N2andMaterialcertificateforcoverflange,diaphragm,capsulebody,andblindkidneyflange. N3

European Pressure Directive*9

PED 2014/68/EUCategoryIII,ModuleH,TypeofEquipment:PressureAccessory-Vessel,Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2.

PE3

Materialcertificate*10 Coverflange*11 M01Coverflange,Processconnector*12 M11

Pressure test/Leaktestcertificate

TestPressure:16MPa(2300psi)*13

Nitrogen(N2)Gas*18

Retention time: one minute

T12TestPressure:25MPa(3600psi)*14 T13TestPressure:3.5MPa(500psi)*15 T01TestPressure:500kPa(2000inH2O)*16 T11TestPressure:50kPa(200inH2O)*17 T04

Highdampingcapsule*19 HighviscosityoilfilledLowerlimitofprocesstemperature:0°CApplicableforEJX110BwithmeasurementspancodeMorHandwettedpartsmaterialcodeS.

HD

Highdampingcapsule(General)*19

ApplicableforEJX110BwithmeasurementspancodeMorHandwettedpartsmaterialcodeS. HD2

*1: Notapplicablewithcolorchangeoption.*2: ApplicableforWettedpartsmaterialcodeS,H,M,andT.*3: TheunitofMWP(Max.workingpressure)onthenameplateofthehousingisthesameunitasspecifiedbyOptioncodeD1,D3,

and D4.*4: Applicableforverticalimpulsepipingtype(Installationcode-7)andWettedpartsmaterialcodeS,H,M,andT.*5: ApplicableforwettedpartsmaterialcodeS;processconnectioncode0and5;andinstallationcode-8and-9.Notapplicablefor

optioncodeU1,N2,N3andM11.NoPTFEisusedforwettedparts.*6: ApplicableforwettedpartsmaterialcodeS.

OverpressureeffectsforEJX110BM,H,andVcapsules:±0.06%ofURL.*7: ApplicableonlyforEJX310BMandAcapsuleswhoseupperrangevalueissetassmallerthan53.3kPaabs.*8: ApplicableforWettedpartsmaterialcodeS,H,M,andT;Processconnectioncode3,4,and5;Installationcode-9;andMounting

bracketcodeN.Processconnectionfacesontheothersideofzeroadjustmentscrew.*9: ApplicableforM,HandVcapsulesofEJX110BwithwettedpartsmaterialcodeS.*10: Materialtraceabilitycertification,perEN102043.1B.*11: ApplicableforProcessconnectionscode0and5.*12: ApplicableforProcessconnectionscode1,2,3,and4.*13: ApplicableforCapsulecodeLoroptioncode/HDand/HD2ofEJX110B,CapsulecodeBofEJX430BandEJX310B,andallthe

capsulesofEJX110BwithwettedpartsmaerialcodeH,M,T,A,D,andB.*14: ApplicableforCapsulecodeM,H,andVofEJX110BwithwettedpartsmaterialcodeS.Notapplicablewith/HDand/HD2.*15: ApplicableforCapsulecodeAofEJX430BandEJX310B.*16: ApplicableforCapsulecodeHofEJX430B.*17: ApplicableforCapsulecodeLandMofEJX310B.*18: Purenitrogengasisusedforoil-prohibiteduse(OptioncodeK1,K2,K5,andK6).*19: Notapplicableforoptioncode/K2,/K3,/K6,and/PE3.

Page 98: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-11

IM 01C27B01-01EN

OPTIONAL ACCESSORIESProduct Part number Specification

Batterypackassembly F9915NQ*1 Batterycase,Lithium-thionylchloridebatteries2piecesBatteries*2 F9915NR Lithium-thionylchloridebatteries,2piecesBatterycase F9915NK*3 BatterycaseonlyRemoteantennacable F9915KU 3mwithmountingbracket

F9915KV 13m(3m+10m),withasurgeprotectivedeviceandmountingbracketAntenna F9915KW 2 dBi standard antenna

F9915KY 6 dBi high gain antenna*4*5

*1: IfyouneedF9915MA,pleasepurchaseF9915NQ.F9915NQisasetofF9915MAandinstructionmanual.*2: Alternatively,TadiranSL-2780/S,TL-5930/SorVITZROCELLSB-D02batteriescanbepurchasedfromyourlocaldistributor.*3: IfyouneedF9915NS,pleasepurchaseF9915NK.F9915NKisasetofF9915NSandinstructionmanual.*4: Useofhighgainantennaislimitedbylocalregulationofradioandtelecommunicationlaw.ConsultYokogawafordetails.*5: Itcannotbeusedbyconnectingdirectlytothemainunit.Remoteantennacablethatseparatelyarrangedisneededtoconnect.

Page 99: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-12

IM 01C27B01-01EN

11.4 Dimensions

Horizontal impulse piping type (Installation code -9) *1

*1: When installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.*3: When option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value in the figure.*4: When amplifier housing code 9 is selected, the value is 114 mm (4.49 inch). In this case, the figure is shown as A.*5: When amplifier housing code 9 is selected, the value is 240 mm (9.45 inch). In this case, the figure is shown as A.*6: Applicable for the external powered type.*7: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm (0.31 inch) from the electrical connection.

F1103.ai

6(0

.24)

76(2

.99)

For electricalconnection code5,9,A and D

A*4*5

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

124

(4.8

8)47

(1

.85)

41(1.61)

181

(7.1

3)

211

(8.3

1)

140(5.51)

67(2.64)

122(4.80)

148(5.83)

Process connection

Process connector(Optional)

Mounting bracket(Flat-type, optional)

Integral indicator

67 (2

.64)

41(1

.61)

97 (3

.82)

52(2

.05)

91 (3.58)

211 (8.31)

140

(5.5

1)

223

(8.7

8)

97 (3.82)

Process connector(Optional)

Process Connection

Mounting bracket(L-type, optional)

Ground terminal

Zero adjustment

Integral indicator

64(2.52)

138

(5.4

3)*2

191 (7.52)39

(1.54)24(0.94)

Ø11

0 (4

.33)

Highpressureside

Lowpressureside

2-inch pipe(O. D. 60 mm)

Vent/Drain plugs

191 (7.52)

64(2.52)

39(1.54)

24(0.94)

Ø11

0 (4

.33)

54(2.13)

130*3

(5.12)

Drain plug

Vent plug

Ground terminal

Zero adjustment

Highpressureside

Lowpressureside

Vent plug

Drain plug

2-inch pipe(O. D. 60 mm)

237 (9.33)304 (11.97)

234*

4 (9

.21)

360*

5 (14

.17)

41(1.61)

Vertical impulse piping type (Installation code -7)Wetted Parts Material Code S (Except for Measurement Span Code F and Option Code /HD, /HD2)

[EJX110B] Unit: mm (approx. inch)

Electrical connection*6

Electrical connection*6

Page 100: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-13

IM 01C27B01-01EN

Unit: mm (approx. inch)

Wetted Parts Material Code: H, M, T, A, B, D, Measurement Span Code F or Option Code /HD, /HD2 Vertical impulse piping type (Installation code -7)

Horizontal impulse piping type (Installation code -9) *1

F1104.ai

*1: When installation code -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.*3: When option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value in the figure.*4: 42 mm (1.65 inch) for right side high pressure.*5: 21 mm (0.83 inch) for right side high pressure.*6: When amplifier housing code 9 is selected, the value is 114 mm (4.49 inch). In this case, the figure is shown as A.*7: When amplifier housing code 9 is selected, the value is 254 mm (10.00 inch). In this case, the figure is shown as A.*8: Applicable for the external powered type.*9: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm (0.31 inch) from the electrical connection.

A*6*7

6(0

.24)

76(2

.99)

For electricalconnection code5,9,A and D

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

64(2.52)

148

(5.8

3)*2

191 (7.52)36*4

(1.42)27*5

(1.06)

Ø11

0 (4

.33)

2-inch pipe(O. D. 60 mm)

Vent/Drain plugs

Highpressureside

Lowpressureside

230 (9.06)

105 (4.13)

72 (2

.83)

46(1

.81)

102

(4.0

2)52

(2.0

5)

140

(5.5

1)

234

(9.2

1)

97 (3.82)

Process connector(Optional)

ProcessConnection

Integral indicator

Mounting bracket(L-type, optional)

Ground terminal

Zero adjustment

64(2.52)

191 (7.52)

36*4

(1.42)

27*5

(1.06)

133*3

(5.24)

Process connection

Ø11

0 (4

.33)

Drain plug

Vent plug

Ground terminal

Zero adjustment

Highpressureside

Lowpressureside

Vent plug

Drain plug

2-inch pipe(O. D. 60 mm)

54(2.13)

46(1.81)

47

(1.8

5)

Process connector(Optional)

Mounting bracket(Flat-type, optional)

Integral indicator

124

(4.8

8)19

6 (7

.72)

230

(9.0

6)

140(5.51)

72(2.83)

127(5.00)

158(6.22)

318 (12.52)256 (10.08)

234*

6 (9

.21)

46(1.81)

374*

7 (1

4.72

)

Electrical connection*8

Electrical connection*8

Page 101: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-14

IM 01C27B01-01EN

Universal flange type (Installation code -U) Measurement span code M, H and V

Measurement span code F

Unit: mm (approx. inch)

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

191 (7.52)

64(2.52)

39(1.54)

24(0.94)

Ø11

0 (4

.33)

54(2.13)130*1

(5.12)

Highpressureside

Lowpressureside

Zero adjustment

181

(7.1

3)

41(1.61)

211

(8.3

1)

140(5.51)

67(2.64)

115(4.53)

58(2.28)

Process connection

Process connector(Optional)

Drain plug

Drain plug

Vent plug

81 (3.19)

390*

2 (15

.35)

*1: When option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value in the figure..*2: When amplifier housing code 9 is selected, the value is 270 mm (10.63 inch). In this case, the figure is shown as A.*3: When amplifier housing code 9 is selected, the value is 289 mm (11.38 inch). In this case, the figure is shown as A.*4: Applicable for the external powered type.*5: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm (0.31 inch) from the electrical connection.

F1105-01.ai

A*2*3

196

(7.7

2)

46(1.81)

230

(9.0

6)

140(5.51)

72(2.83)

125(4.92)

63(2.48)

Process connection

Process connector(Optional)

191 (7.52)

64(2.52)

36(1.42)

27(1.06)

Ø11

0 (4

.33)

54(2.13)133*1

(5.24)

Highpressureside

Lowpressureside

Zero adjustment

Drain plug

Drain plug

Vent plug

81 (3.19)

409*

3 (16

.10)

Electrical connection*4

Electrical connection*4

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

Integral indicator

Integral indicator

Page 102: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-15

IM 01C27B01-01EN

*1: When amplifier housing code 9 is selected, the value is 314 mm (12.36 inch). In this case, the figure is shown as A.*2: When amplifier housing code 9 is selected, the value is 334 mm (13.15 inch). In this case, the figure is shown as A.*3: When option code K1, K2, K5 or K6 is selected, add 30 mm (1.18 inch) to the value in the figure.*4: Applicable for the external powered type.*5: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm (0.31 inch) from the electrical connection.

Bottom process connection type (Installation code -B) Measurement span code M, H and V, except for option code /HD, /HD2

Measurement span code F or option code /HD, /HD2

F1105-02.ai

Unit: mm (approx. inch)

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

A*1*2

129 (5.08)

255

(10.

04)

93 (3

.66)

140(5.51)

54(2.13)130*3

(5.12)

Mounting bracket(Optional)

Zero adjustment

Ground terminal

HighPressureSide

Vent plug

LowPressureSide

191 (7.52)

64(2.52)

79(3.11)

39(1.54)

24(0.94)

Ø11

0 (4

.33)

Process connection

Process connector(Optional)

274

(10.

79)

129 (5.08)

140(5.51)

Vent plug

Integral indicator

Zero adjustment

Ground terminal

HighPressureSide

LowPressureSide

133*3 (5.24)

54(2.13)

191 (7.52)

64(2.52)

39(1.54)

24(0.94)

Ø11

0 (4

.33)

Ø11

0 (4

.33)

184

(7.2

4)

79 (3

.11)

2-inch pipe(O. D. 60 mm) 95 (3.74)

Mounting bracket(Optional)

Process connector(Optional)

Process connection

81 (3.19)

434*

1 (1

7.09

)

81(3.19)

454*

2 (17

.87)

Electrical connection*4

Electrical connection*4

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

Integral indicator

Page 103: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-16

IM 01C27B01-01EN

Vertical impulse piping type (Installation code -7) *1

Unit: mm (approx. inch)[EJX310B and EJX430B]Wetted parts material code: S

Horizontal impulse piping type (Installation code -9) *1

F1106.ai

*1: When installation code -3 and -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.*3: Applicable for EJX430B.*4: When amplifier housing code 9 is selected, the value is 114 mm (4.49 inch). In this case, the figure is shown as A.*5: When amplifier housing code 9 is selected, the value is 240 mm (9.45 inch). In this case, the figure is shown as A.*6: Applicable for the external powered type.*7: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm (0.31 inch) from the electrical connection.

A*4*5

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

6(0

.24)

76(2

.99)

For electricalconnection code5,9,A and D

64(2.52)

138

(5.4

3)*2

191 (7.52)39

(1.54)24(0.94)

27(1.06)

Ø11

0 (4

.33)

Highpressureside

Lowpressureside

2-inch pipe(O. D. 60 mm)

Vent/Drain plugs

Open to atmosphereØ10 (0.39)*3

67 (2

.64)

41(1

.61)

97 (3

.82)

52(2

.05)

91 (3.58)

211 (8.31)

140

(5.5

1)

223

(8.7

8)

97 (3.82)

Process connector(Optional)

ProcessConnection

Mounting bracket(L-type, optional)

Ground terminal

Zero adjustment

Integral indicator

191 (7.52)

64(2.52)

39(1.54)

24(0.94)

Ø11

0 (4

.33)

27(1.06)

65*2

(2.56)

91 (3

.58)

Drain plug

Vent plug

Ground terminal

Zero adjustment

Highpressureside

Lowpressureside

2-inch pipe(O. D. 60 mm)

Open toatmosphereØ5 (0.20)*3

124

(4.8

8)47

(1

.85)

41(1.61)

181

(7.1

3)

211

(8.3

1)

140(5.51)

67(2.64)

122(4.80)

148(5.83)

Process connection

Process connector(Optional)

Mounting bracket(Flat-type, optional)

Integral indicator

237 (9.33)304 (11.97)

234*

4 (9

.21)

41(1.61)

360*

5 (14

.17)

Electrical connection*6

Electrical connection*6

Page 104: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-17

IM 01C27B01-01EN

Vertical impulse piping type (Installation code -7) *1

Horizontal impulse piping type (Installation code -9) *1

*1: When installation code -3 and -8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.*3: Applicable for EJX430B.*4: When amplifier housing code 9 is selected, the value is 114 mm (4.49 inch). In this case, the figure is shown as A.*5: When amplifier housing code 9 is selected, the value is 254 mm (10.00 inch). In this case, the figure is shown as A.*6: Applicable for the external powered type.*7: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm (0.31 inch) from the electrical connection.

F1107.ai

Unit: mm (approx. inch)

Wetted parts material code: H, M, T, A, B, and D*36

(0.2

4)

76(2

.99)

For electricalconnection code5,9,A and D

A*4*5

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

64(2.52)

148

(5.8

3)*3

191 (7.52)39

(1.54)24(0.94)

Ø11

0 (4

.33)

2-inch pipe(O. D. 60 mm)

Highpressureside

Lowpressureside

27(1.06)

Vent/Drain plugs

Open to atmosphereØ10 (0.39)

64(2.52)

191 (7.52)

39(1.54)

24(0.94)

Ø11

0 (4

.33)

Drain plug

Vent plug

Ground terminal

Zero adjustment

Highpressureside

Lowpressureside

2-inch pipe(O. D. 60 mm)

27(1.06)

67*2

(2.64)

Open toatmosphereØ5 (0.20)

230 (9.06)

105 (4.13)

72 (2

.83)

46(1

.81)

102

(4.0

2)52

(2.0

5)

140

(5.5

1)

234

(9.2

1)

97 (3.82)

Process connector(Optional)

ProcessConnection

Integral indicator

Ground terminal

Zero adjustment

46(1.81)

47

(1.8

5)

Process connection

Process connector(Optional)

Mounting bracket(Flat-type, optional)

Integral indicator

124

(4.8

8)19

6 (7

.72)

230

(9.0

6)

140(5.51)

72(2.83)

127(5.00)

158(6.22)

318 (12.52)256 (10.08)

234*

4 (9

.21)

46(1.81)

374*

5 (1

4.72

)

Electrical connection*6

Mounting bracket(L-type, optional)

Electrical connection*6

Page 105: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11. General Specifications> 11-18

IM 01C27B01-01EN

Universal flange type (Installation code -U)Unit: mm (approx. inch)

Bottom process connection type (Installation code -B)

F1108.ai

*1: Applicable for EJX430B.*2: When option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.*3: When amplifier housing code 9 is selected, the value is 270 mm (10.63 inch). In this case, the figure is shown as A.*4: When amplifier housing code 9 is selected, the value is 314 mm (12.36 inch). In this case, the figure is shown as A.*5: Applicable for the external powered type.*6: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm (0.31 inch) from the electrical connection.

A*3*4

191 (7.52)

64(2.52)

39(1.54)

24(0.94)

Ø11

0 (4

.33)

Highpressureside

Lowpressureside

65*1

(2.56)

Open toatmosphereØ5 (0.20)*1

27(1.06)

Open to atmosphereØ10 (0.39)

181

(7.1

3)

41(1.61)

211

(8.3

1)

140(5.51)

67(2.64)

115(4.53)

58(2.28)

Process connection

Process connector(Optional)

Drain plug

Drain plug

Vent plug

129 (5.08)

255

(10.

04)

93 (3

.66)

140(5.51)

Integral indicator

Mounting bracket(Optional)

Zero adjustment

Ground terminal

HighPressureSide

Vent plug

LowPressureSide

Open to atmosphereØ10 (0.39)*1

65*1

(2.56)

27(1.06)

191 (7.52)

64(2.52)

79(3.11)

39(1.54)

24(0.94)

Ø11

0 (4

.33)

Process connection

Process connector(Optional)

81(3.19)

390*

3 (15

.35)

81 (3.19)

434*

4 (1

7.09

)

Electrical connection*5

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

For electricalconnection code5,9,A and D

76(2.99)

6(0.24)

Electrical connection*5

Integral indicator

Page 106: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

<11.GeneralSpecifications> 11-19

IM 01C27B01-01EN

Infrared port

Infrared Configuration Terminal Configuration for the External Powered type

Terminal Wiring Example for the External Power Source Terminal

Ground terminalPower supply terminal +

Power supply terminal –

Power supply

Connection terminal

Shield cable

External power source

Use shield cables if it is affected by electrical noise.

10.5-30V DC

F1109.ai

.

Page 107: EJX110B, EJX310B and EJX430B Differential Pressure and ... · User’s ana Yoo gaa Electric Corporation EJX110B, EJX310B and EJX430B Differential Pressure and Pressure Transmitters

Rev-1

IM 01C27B01-01EN

Revision Information Title : EJX110B, EJX310B and EJX430B DifferentialPressureandPressureTransmitters Manual No. : IM 01C27B01-01EN

Edition Date Page Revised Item1st May 2009 — Newpublication2nd Aug. 2010 — ReleaseofISA100.11aprotocol3rd Oct.2010 2-5 2.8.3 AdddescriptionofCENELECATEX(KEMA)Certification)

2-6 2.8.4 AdddescriptionofIECExCertification11-6 11.3 Addoptioncode/KS27and/SS27.

4th Apr. 2011 — • Adaptedtodeviceconfigurationtoolwithinfraredcommunicationfunction.• Partnumberchange Batterypack:F9915MAà F9915NQ Delete F9915MX Battery: A1133EB à F9915NR Deletebatterycasepartnumber

5th Dec.2011 9-7 9.4.8 AddbatterycasepartnumberofF9915NK.6th Aug. 2012 — Releaseofamplifierhousingcode8and9.7th Oct.2012 — ReleaseofATEX/IECExintrinsicsafeforamplifierhousingcode8and9.

2-5, 2-6 2.8.3,2.8.4Changethedescriptionsandtheinstallationdiagram.11-2 11.1 DeletethelimitationuseforFrance.

8th June 2013 — ReleaseofCSAintrinsicsafeforamplifierhousingcode8and9.9th Jan. 2014 — ReleaseofFMintrinsicsafeforamplifierhousingcode8and9.10th July 2015 11-2

11-4, 11-6, 11-711-9

RevisedescriptionsforEMCconformitystandards.ChangeofthematerialformountingbracketDandK.Addnotestothetableofoptionalaccessories.

11th Oct.2015 2-1, 2-2, 4-2, 5-2, 7-2

9-5, 11-1, 11-2, 11-8, 11-9, 11-10

to 11-1311-4, 11-1311-10 to 16

Lbracketchange.

Add /HD.

AddBottomprocessconnectionformeasurementcodeF.Correctdimensions.

12th May 2017 ——

1-1, 1-2, 2-101-21-21-5

2-8,11-82-611-9

ChangeduetoYFGW710discontinuation.Changedueto“AmplifierCode7”discontinuation.Change due to RoHS.AdditionofPatentMaking.AdditionofProductDisposalinformation.Addition of China RoHS.RevisionofPEDdescriptions.RevisionoftheapplicablestandardforATEX.DeletionofF9915KXduetoRoHS.

13th Dec.2018 ———2-42-52-52-7

2-9, 2-10

Release of output signal -1.Releaseofexternalpoweredtype.Changethedescription:Arrester à SurgeProtectiveDeviceRevisedthedescriptionofFMApproval.RevisedthedescriptionofCSACertification.RevisedthedescriptionofATEXCertification.RevisedthedescriptionofIECExCertification.RevisedthedescriptionofRegulatoryComplianceforRadioandTelecommunication.

14th Mar. 2019 11-4,11-6,11-811-11

Releaseofelectricalconnectioncode4,9,D.Added the battery : VITZROCELL SB-D02

15th July 2019 11-10 11.3 ReleaseofoptionalcodeHD2.