4
Wire connections EJM30BSx: Switch wire range: #18-8 AWG, 60-75 °C, Cu only, solid or stranded Torque: 7 lb.in, use Pozi-drive #2 or flat blade screwdriver EJM60-80BSx: Switch wire range: #14-4 AWG, 60-75 °C, Cu only, solid or stranded Torque: 18 lb.in, use Pozi-drive #2 or flat blade screwdriver Auxiliary contacts, 10A, 600V, A600-R300 Switch wire range: #18-14 AWG, 60-75 °C, Cu only, solid or stranded Torque: 7 lb.in, use Pozi-drive #2 or flat blade screwdriver Optional Power Poles EJM30BSx: 4P40 4th pole NP40 Solid neutral pole Optional Auxiliary contacts OA1G10 (1 N.O.) Install on right side of switch. Max. 2 pcs on 3-pole switch, 1 pcs on 4-pole switch (EJM30BSx). OA1G01 (1 N.C.) Install on left side of switch. Max. 2 pcs. OA2G11 (1 N.O. + 1 N.C.) Install on right side of switch. O OFF I ON Installation instructions P/N AMPS Enclosure size VAC 200V 208V 240V 480V 600V EJM30BSx 40A Size 1 HP 10 10 10 20 25 EJM60Bxx 60A Size 2 HP 15 15 15 30 30 EJM80BPx 80A Size 3 HP 20 20 20 40 40 Ratings Applications The EJM series of enclosed manual motor controllers are rotary operated, 3 or 4 pole, up to 600V HP rated switches, housed in thermoplastic enclosures suitable for humid and corrosive environments. Rated NEMA 4X may be used for both indoor and outdoor applications. Products are properly installed on the load side of a branch circuit protective device and are suitable for use as motor disconnects. Disconnecting means Short circuit protective device Controller Overload protection Motor disconnection M WARNING To avoid hazard of electric shock, turn off and lock out all power sources before installing or performing maintenance on this equipment. EJM60-80Sx: 4P80 4th pole NP80 Solid neutral pole Document no. 34EJM30-80-A EJM Series Enclosed Manual Motor Controllers EJM30BSx, EJM60Bxx, EJM80BPx

EJM Series Enclosed Manual Motor Controllers · 7.44 1" 1 1/4" 1" 1 1/4" mm in 20 0.79. Title: 34EJM30-80-A.indd Author: hakkhele Keywords

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EJM Series Enclosed Manual Motor Controllers · 7.44 1" 1 1/4" 1" 1 1/4" mm in 20 0.79. Title: 34EJM30-80-A.indd Author: hakkhele Keywords

Wire connectionsEJM30BSx:Switch wire range: #18-8 AWG, 60-75 °C, Cu only, solid or strandedTorque: 7 lb.in, use Pozi-drive #2 or fl at blade screwdriverEJM60-80BSx:Switch wire range: #14-4 AWG, 60-75 °C, Cu only, solid or strandedTorque: 18 lb.in, use Pozi-drive #2 or fl at blade screwdriverAuxiliary contacts, 10A, 600V, A600-R300Switch wire range: #18-14 AWG, 60-75 °C, Cu only, solid or strandedTorque: 7 lb.in, use Pozi-drive #2 or fl at blade screwdriver

Optional Power PolesEJM30BSx:4P40 4th pole NP40 Solid neutral pole

Optional Auxiliary contactsOA1G10 (1 N.O.) Install on right side of switch. Max. 2 pcs on 3-pole switch, 1 pcs on 4-pole switch (EJM30BSx).OA1G01 (1 N.C.) Install on left side of switch. Max. 2 pcs.OA2G11 (1 N.O. + 1 N.C.) Install on right side of switch.

O O

FF

I ON

Installation instructions

P/N AMPS Enclosure size VAC 200V 208V 240V 480V 600VEJM30BSx 40A Size 1 HP 10 10 10 20 25EJM60Bxx 60A Size 2 HP 15 15 15 30 30EJM80BPx 80A Size 3 HP 20 20 20 40 40

Ratings

ApplicationsThe EJM series of enclosed manual motor controllers are rotary operated, 3 or 4 pole, up to 600V HP rated switches, housed in thermoplastic enclosures suitable for humid and corrosive environments. Rated NEMA 4X may be used for both indoor and outdoor applications. Products are properly installed on the load side of a branch circuit protective device and are suitable for use as motor disconnects.

Disconnecting means

Short circuit protective device

Controller

Overload protection

Motor disconnection

M

WARNINGTo avoid hazard of electric shock, turn off and lock out all power sources before installing or performing maintenance on this equipment.

EJM60-80Sx:4P80 4th poleNP80 Solid neutral pole

Document no. 34EJM30-80-A

EJM SeriesEnclosed Manual Motor ControllersEJM30BSx, EJM60Bxx, EJM80BPx

Page 2: EJM Series Enclosed Manual Motor Controllers · 7.44 1" 1 1/4" 1" 1 1/4" mm in 20 0.79. Title: 34EJM30-80-A.indd Author: hakkhele Keywords

InstallationOperate switch to the OFF position and loosen the cover screws, remove the cover.

EJM30BSxTwo concentric 1/2" & 3/4" K.O.s are provided in the top and bottom of the enclosure (size 1).

EJM60BxxTwo concentric 3/4" & 1" K.O.s are provided in the top and bottom of the enclosure (size 2).

EJM80BPxTwo concentric 1" & 1 1/4" K.O.s are provided in the top and bottom of the enclosure (size 3).

EJM Series Enclosed Manual Motor Controllers

An internal metallic plate bonds together all conduit hubs installed, without the need for additional bonding jumpers.

• Drill proper holes for conduit hubs or use K.O.s• Install conduit hubs• Install enclosure size 1 and 2 using (2) #8 or M4 screws• Install enclosure size 3 using (4) 1/4" or M6 screws

WiringFor ease of wiring, it is recommended to remove the switch from the enclosure before pulling the wire. A small fl at blade screwdriver may be used to release the DIN rail clip at the bottom of the switch, allowing it to be removed.

Connect power wires to switch terminal and attach ground wire to the ground terminal block inside the enclosure. Reinstall the switch in the enclosure. Reference the National Electric Code and all local codes for appropriate wire size and grounding requirements.

Pozi-drive #2 or flat blade screwEJM30BSx: Torque 7 lbs/inEJM60-80Bxx: Torque 18 lbs/inAuxiliary contacts: Torque 7 lbs

Ground terminal block:Torque 7 lbs/in

EJM30BSx:9-10 mm0.35 - 0.39 inEJM60Bxx:10 - 12 mm0.39 - 0.47 in

EJM30BSx:0.75...10mm2

18...8 AWGEJM60Bxx:1.5...25 mm2

14...4 AWG

A07

199

Page 3: EJM Series Enclosed Manual Motor Controllers · 7.44 1" 1 1/4" 1" 1 1/4" mm in 20 0.79. Title: 34EJM30-80-A.indd Author: hakkhele Keywords

Operating handleOperating handle may be padlocked in the OFF-position with up to three padlocks. When locked, the enclosure cover is interlocked and can not be removed. All padlocks must be opened to gain entry to the enclosure.

A00

323A

Ø 5...8 mm / 0.20...0.32 in

Reinstall enclosure cover, note that both the switch and the operating handle on the cover must be in the OFF-position. Tighten the cover screws.

O O

FF

I ON

!

A00

322A

Ø 5...10 mm / 0.20...0.39 in

EJM Series Enclosed Manual Motor Controllers

Page 4: EJM Series Enclosed Manual Motor Controllers · 7.44 1" 1 1/4" 1" 1 1/4" mm in 20 0.79. Title: 34EJM30-80-A.indd Author: hakkhele Keywords

ep.mersen.com

1525.98

501.97

161.46.35

mmin

1405.51

762.99

4.50.18

7.400.29

1003.94

ONI

O O

FF

1525.98

3/4 "1/2 "M25

Selector type handle Pistol type handle

R2.50.09

45

126 1.77

4.96

361.42

240.94

250.98

34.51.36

115.54.55

1.830

1.1830

200.79

Metric M20(0.79 dia)

Metric M20(0.79 dia)

200.79

190.75

501.97

EJM60BSx (enclosure size 2)

EJM30BSx (enclosure size 1)

EJM80BPx (enclosure size 3)

EJM60BPx (enclosure size 2)

EJM Series Enclosed Manual Motor Controllers

2108.27 189

7.44

30011.81

2389.37

1505.91

1054.13

Ø6.6 0.26

1817.12

1365.35

451.77

20.50.81

602.36

2389.37

1897.44

1" 1 1/4"

1" 1 1/4"

mmin

200.79