• Distribution
• Motor control
• Package substations
Capitole
Low voltage switchgear and
control gear assemblies
• Flexibility
• Reliability
• Availability
• Value for money,
whatever the application
8/3/2019 Eaton Capitole Salesaid ENG
http://slidepdf.com/reader/full/eaton-capitole-salesaid-eng 2/8
• Type tested AN D certified only!
• Mod ular b uild - Pl ug -in - M IN IM UM
foot print b ut not compromise cabling
• Meters - need analog ue and digital
options - digital m ust comm unicate!
• C ustomers need locking facilities!!
• fast deli very
Distrib ution
• M ust ha ve f ull range of de vices - A C Bs
- M C C Bs - F used -switc hes - M C Bs
(SP/ TP + ne utral links/4 pole)
• C hange -o ver and interlocks essential
• C Ts ha ve to be incorporated in
str uct ure - easy to fit e ven in ser vice
• Constr uction m ust be rigid - end frame type best!!
• Ne utrals ha ve to be f ully rated
• Cabling - has to be fast and easy, m ust
ha ve plenty of space, access from front,
remo vable gland plates
• M C C Bs - want c hoice of toggle or rotary
handle
L V Sys tem wis h lis t
8/3/2019 Eaton Capitole Salesaid ENG
http://slidepdf.com/reader/full/eaton-capitole-salesaid-eng 3/8
Notes
Motor control and distrib ution• Mod ular b uild -
• m ust incorporate motor control
and/or distrib ution as req uired -
incl uding b uilding ser vices!!!
• Arc -free design
• safe to modify li ve - absol ute M US T HA VE
• O utgoing fixed/wit hdrawable/
pl ug -in options
• Compact starters - excellent
space usage - N B cabling m ust
still be easy
• Con ventional and intelligent motor control essential
• S h utters m ust be a vailable for
wit hdrawable starters - PER IO D..
• IP41 minim um, IP54 option
• Pl ug -in de vices essential for M C Cs and switc hboards
• Rigid constr uction using end -frames best for strengt h and *
flexibility of application
8/3/2019 Eaton Capitole Salesaid ENG
http://slidepdf.com/reader/full/eaton-capitole-salesaid-eng 4/8
Capitole 40
Electrical data
Rated operational voltage 690 V
Rated frequency 50/60 Hz
Main busbar data
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated current 6300 A
Rated short-time withstand current 80 kA 1s
Rated peak withstand current 220 kA
Vertical distribution busbar data
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated current 1420 A
Rated short-time withstand current 80 kA 1s
Rated peak withstand current 176 kA
Outgoing units withdrawable / fixed / plug-in
Enclosure data
Degree of protection IP41 (IP54 on request)
Form of separation Form 4a Type 2,
Form 4b Types 3, 6 and 7
Entry of cables Top and/or bottom
Access Front or rear
Standard Colour RAL 7035
Standards IEC 60439-1, BS EN 60439-1
Certifications KEMA-Keur, Lloyd's Register of shipping
Technical data
8/3/2019 Eaton Capitole Salesaid ENG
http://slidepdf.com/reader/full/eaton-capitole-salesaid-eng 5/8
System flexibility
• Compartments for withdrawable units may be
modified without process supply interruption
• Standard and reduced height cubicle designs
with configurations for front/rear connection,
top/bottom cable entry
• Corner cubicle facilitates right-angled assemblies
• Up to 32 units per column
• Wide range of optional modules
- Clink motor management system
- Soft starters
- Frequency converters (variable speed drives)
- PLC controlled change-over systems
- Power factor correction
Maintenance
• Low maintenance design
• All components/connections accessible
from the front
except for rear cable connections
• Maintenance-free withdrawable unit contacts
• Contact blocks may be quickly changed
Optional fully insulated mainbusbar system
Safe connection of outgoing cables evenunder live busbar conditions
Fully withdrawable motor starter
Capitole 40LV Distribution and Motor Control System
Certified to national
Personal safety
• Form 4a Type 2, Form 4b Types 3, 6 and 7 internal
segregation
• Shutters guard the distribution busbars when
drawers are removed
• Designed to limit effects of internal arcing faults
- Possible to connect outgoing cables with
switchboard live
• Fault-free zone option:
- Insulated main busbars
- Incomer – busbar connections insulated
- Phase segregation of incoming and busbar side
terminals of incoming devices
Operational reliability
• Unique plug-in contacts for withdrawable units –
prevent wear, short-circuit damage and welding
• Vertical busbars enclosed in insulated chamber
• Segregation continuous up to and including
withdrawable main contacts – precludes faults
• Quality controlled manufacturing guarantees all
fixings, including terminations, correctly tightened
8/3/2019 Eaton Capitole Salesaid ENG
http://slidepdf.com/reader/full/eaton-capitole-salesaid-eng 6/8
Rotary handle operated MCCBs andfused switches
Toggle operated MCCBsKema Keur CertifiedType Tested Assembly
and international standards
Capitole 20LV Distribution System
Reliability by design
• Designs for IEC, Euro-norm and British
Standard markets
• Kema Certified as a Type Tested Assembly
• On-going build quality and compliance with the
Type Tested design monitored by Kema under
the Kema Keur scheme
Safe to use, easy to maintain
• Form 4a Type 2 – Form 4b Type 6 segregation
using rigid metallic or insulating materials
• Door-interlocked operating handles, locked
doors and screw-fixed cover plates
• Minimum IP2x shrouding internally
• Plug-in MCCB and fused-switch disconnector
modules up to 1000 A
• ACBs withdrawable or fixed
Functionally flexible
• Modular design provides maximum flexibility
and minimum build time
• May be re-configured on-site if necessary
• Top and/or bottom cable entry
• Full spectrum of protection, metering, Building
Management System and supply change-over
options
Wide choice of modules
• Standard devices in a modular design ensure
perfect balance between size, electrical capacity,
and cost
• Modular design is ideal for use with the Eaton
Bid Manager software which provides price
and size data in a matter of minutes for most
assemblies
• Complete spectrum of Eaton distribution and
control devices
- Air circuit breakers
- Moulded case circuit breakers
- Fused switches
- Switch disconnectors
- Power factor correction
High Density Device Mounting
• Minimised switchboard size whilst maintaining
both excellent cabling access and flexibility
- Up to 24 devices in one column
- Feeder modules up to 250 A
twin device plug-in
- Feeder modules up to 1000 A
single device plug-in
- Feeder modules above 1000 A
single or twin device
8/3/2019 Eaton Capitole Salesaid ENG
http://slidepdf.com/reader/full/eaton-capitole-salesaid-eng 7/8
Capitole 20
Electrical data
Rated operational voltage 690 V
Rated frequency 50/60 Hz
Main busbar data
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated current 3200 A
Rated short-time withstand current 50 kA and 65 kA 1s
Rated peak withstand current 110 kA
Vertical distribution busbar data
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated current 2x1250 A (centre fed)
Rated short-time withstand current 50 kA 1s
Rated peak withstand current 110 kA
Outgoing units plug-in
Enclosure data
Degree of protection IP31
Form of separation Form 4a Type 2, Form 4b Type 6
Entry of cables Top and/or bottom
Access Front
Standard Colour RAL 7035
Standards IEC 60439-1, BS EN 60439-1
Certifications KEMA-Keur
Technical data
8/3/2019 Eaton Capitole Salesaid ENG