Earthing Guidelines

Embed Size (px)

Citation preview

  • 8/11/2019 Earthing Guidelines

    1/20

    1 EarthingR

    ecomendations-PLC

    Earthing RecommendationsFor Programmable Controller Systems

    ES30001 (Part-I)

    ES30001 Part-I (Rev.-2) JULY 2001

  • 8/11/2019 Earthing Guidelines

    2/20

    2

    Earthing Recomendations - PLC

  • 8/11/2019 Earthing Guidelines

    3/20

    3 EarthingR

    ecomendations-PLC

    Contents

    1. Scope.........................................................................................................................................5

    2. Definitions...............................................................................................................................5

    3. Function of Plant Earth........................................................................................................5

    4. Function of Primary Earth.....................................................................................................6

    5. Function of Secondary Earth.................................................................................................9

    6. Earthing of Multiple panels.................................................................................................12

    7. Earthing of Panels with Multiple Power feeds..................................................................14

    8. Earthing of Remote Stations...............................................................................................14

    9. Connecting MMI, Peripherals..............................................................................................14

    10. Cables and Conduits ............................................................................................................15

    11. Verification of Earth Connections......................................................................................15

    12. Earth pit.................................................................................................................................17

    13. Summary................................................................................................................................18

    Notes......................................................................................................................................19

  • 8/11/2019 Earthing Guidelines

    4/20

    4EarthingR

    ecomendations-PLC

    Disclaimer

    "Larsen&Toubro Limited, its affiliates and employees disclaimall liabilities & warranties (includinglost

    profits or any other incidental damages) for accuracy, currency, completeness of theinformation contained

    herein

    In linewith thecompanys policy of continuous development. Theinformation contained in this document is

    subject to changewithout prior notice.

    Selection of materials and/ or equipment is at thesolerisk of theuser of this publication.

    Thecontents of this document areproperty of Larsen&Toubro Limited. No part of this document may be

    copied, distributed, transcribed, or translated into any formor by any means, or disclosed to any third party

    without theexpress written permission of Larsen&Toubro Limited."

    Document Information

    Document #: ES30001-Part-I

    Revision: 2

    Release date: July 2001

    Credits

    Technical team: Revised by (Rev. -2)

    Omkar Saroop R.K.Pandagare

    Sujit Dey R.M.Karlekar

    A A Samson

  • 8/11/2019 Earthing Guidelines

    5/20

    5 EarthingR

    ecomendations-PLC

    1. Scope

    The Part 1 recommendations apply primarily to the Programmable Logic Controller (PLC), their

    Remote Stations and associated peripherals, such as MMIs and are primarily for addressing

    Electromagnetic interference and Electromagnetic compatibility (EMI/ EMC)

    Part 1 does not address the Drives and their interconnections with the PLC systems.

    2. Definitions

    2.1 Panel: The metal enclosure in which the PLC and the associated equipment are

    mounted and housed.

    2.2 PLC System: Comprises of the Power supply Units, CPU, I/ Os, Mountbases.

    Communication Interfaces &remote stations.

    2.3 Primary Earth: The earth connected to the Panel.

    2.4 Secondary Earth: The earth connected to the PLC system.

    2.5 Plant Earth: The earth to which the lightning conductor, earth conductors of other

    equipment in the Plant are connected. (E.g. MCC , PCC, H.T Switchgear)

    2.6 Equipotential Ground Plane : Ground plane exhibiting zero potential difference

    between any two points on it. It does not matter what the absolute potential of the

    ground plane to the earth may be at.

    2.7 Cable Shield: The metal braid cover on the cables carrying communication signals and

    instrumentation signals i.e. analog signal, low voltage digital signal etc.

    2.8 Cable Armor: The metal stripes covering the high power cables.

    2.9 Signal Ground: This is the return path associated with an analog signal.

    2.10 Digital Ground: This is the return path associated with the digital logic signal.

    3. Function of Plant Earth

    The function of the plant earth is to limit over-voltages on the plant structure, equipment and

    exposed metal sections. These surfaces may get electrically elevated from the zero potential of

    earth due to high fault currents or due to lightning strikes. The plant earth conductor providesa path for these currents to the earth.

  • 8/11/2019 Earthing Guidelines

    6/20

    6EarthingR

    ecomendations-PLC

    4. Function of Primary Earth

    The aim of the Primary Earth is to limit over-voltages, due to fault currents etc., on the

    exposed Panel surface to ensure the personnels safety against electric shock hazards, refer

    figure1& 1a. The Primary earth pit is a separate pit. The Plant earth pit must not be used asPrimary earth pit. This is to ensure that the momentary changes in the plant earth potential do

    not directly reflect on the panel.

    4.1 The Panel accessible parts, i.e. Panel chassis, framework & fixed metal parts, shall be

    connected to the Primary Earth busbar within the Panel. This requirement can be met

    by the normal structural parts providing electrical continuity. Paint may be scrapped at

    the metallic joints to provide a good continuity.

    4.2 Connections to Primary Earth busbar within the panel shall be such that connection is

    maintained even when the Panel is opened or any removable part is removed.

    4.3 Primary Earth pit shall be connected to the Plant Earth. This connection shall not be

    just by the virtue of mounting of the Panel on the mounting rail or support on thefloor of the Plant. A cable shall provide connection between the Panel Primary Earth

    bus bar and a separate earth pit. This earth pit shall be called Primary Earth pit. The

    connection between the Primary earth pit and the Plant earth is described in section 6.

    4.4 All the connections to the Primary Earth bus bar within the panel shall be of screw type

    of brass or other non corrosive metal. The clamping means shall be adequately locked

    against accidental loosening and it shall not be possible to loosen them without the aid

    of a tool.

    4.5 The Primary Earth pit shall have no other functions than those described above.

    4.6 The Primary Earth pit shall be graphically represented as

    4.7 Within the panel the Primary Earth wire shall be of color green with yellow stripes.

    4.8 The gauge of the Primary Earth wire shall be,

    ! Within the Panel: 1.5 mm2, multistrand copper wire with insulation.

    ! Panel to pit: 10 mm2, multistrand copper or equivalent

    aluminium wire, with insulation.

    4.9 The following are connected to the Primary Earth:

    4.9.1 The Panel.

    4.9.2 The primary neutral terminal of all input/ isolation transformers.

    4.9.3 Primary shield of all input/ isolation transformers.

    4.9.4 Earth terminal of all Field Power supplies I/ O (External to the PLC System),

    Displays, Switch matrix.

    4.9.5 Incandescent Lamps & sockets.

    4.9.6 All other parts of the Panel which are electrically isolated.

  • 8/11/2019 Earthing Guidelines

    7/20

    7 EarthingR

    ecomendations-PLC

    Legend

    1 Panel2 Primary earth busbar3 Secondary earth busbar4 Primary earth pit5 Control transformer6 Shorting of the primary sheild7 Plant earth8 Field power supply9 CPU power supply10 I/O ModulesP1, N1, E1 Primary power (100V/230V)P2, N2, E2 Seondary power (100VAC)P, N, E Auxillary power (230VAC)Dashed lines Not connected to primary earthSolid lines Connected to primary earth

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    Figure 1: Primary Earth

    P2N2E2

    P2N2E2

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    P1

    N1

    E1

    P2

    N2

    E2

    P N E

    8

    1

    3

    2

    4

    5

    6

    7

    10

    9

  • 8/11/2019 Earthing Guidelines

    8/20

    8EarthingR

    ecomendations-PLC

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4

    Figure 1a: Primary Earth (Multiple feeds)

    PS

    P2N2E2

    PS

    P2N2E2

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6

    P N E

    8

    1

    3

    2

    4

    7A

    P1

    N1

    E1

    P2

    N2

    E2

    5A

    6A

    P1

    N1

    E1

    P2

    N2

    E2

    5B

    6B

    10

    9

    Legend

    1 Panel2 Primary earth busbar3 Secondary earth busbar4 Primary earth pit5A, 5B Control transformer6A, 6B Shorting of the primary sheild7A Plant earth8 Field power supply9 CPU power supply10 I/O ModulesP1, N1, E1 Primary power (100V/230V)P2, N3, E2 Secondary power (CPU)P3, N3, E3 Secondary power (I/O)P, N, E Auxillary p ower (230VAC)Dashed lines Not connected to primary earthSolid lines Connected to primary earth

  • 8/11/2019 Earthing Guidelines

    9/20

    9 EarthingR

    ecomendations-PLC

    5. Function of Secondary Earth

    Primary aim of the Secondary Earth is to provide low impedance path to the noise currents

    induced by RFI/ EMI and the leakage currents in the PLC system. Refer to figure 2 & 2a.

    5.1 All the metallic parts of the PLC hardware and the earth terminals on the I/ O modules

    of the PLC system shall be connected to the Secondary Earth bus bar.

    5.2 The PLC hardware must be isolated from the Panel by means of insulating spacers.

    5.3 The Secondary Earth conductor from the Panel must be connected to a separate Earth

    pit. This Earth pit is called Secondary Earth .Within the Panel the Secondary Earth bus

    bar shall be isolated from the Primary Earth bus bar by mounting it on insulating

    bushes.

    5.4 All the connections of the Secondary Earth within the panel shall be of screw type of

    brass or other non corrosive metal. The clamping means shall be adequately locked.

    5.5 The Secondary Earth shall be graphically be represented as5.6 Within the panel the Secondary Earth wire shall be of color green.

    5.7 The gauge of the Secondary Earth wire shall be:

    ! Within the Panel: 1.5 mm2, multistrand copper wire with insulation.

    ! Panel to pit: 6 mm2, multistrand copper or equivalent

    aluminium wire, with insulation.

    5.8 The following are connected to the Secondary Earth bus bar .

    5.8.1 Secondary Shield of the transformer feeding the PLC Power supply Units.

    5.8.2 Earth terminal of the Power Supplies for the PLC system (local I/ O, remote I/ O

    interfaces & commutation devices).

    5.8.3 All Mountbases, chassis of devices in 5.8.2.

    5.8.4 Earth terminal of power line filter.

  • 8/11/2019 Earthing Guidelines

    10/20

    10EarthingR

    ecomendations-PLC

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    Figure 2: Secondary Earth (Single feed)

    P2N2E2

    P2N2E2

    P1

    N1

    E1

    P N E

    1

    3

    2

    4

    P2

    N2

    E2

    65

    8

    7

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2

    10

    9

    11

    Legend

    1 Panel2 Primary earth busbar3 Secondary earth busbar4 Secondary earth pit5 Control transformer6 Shorting of the secondary sheild7 Mountbase8 Basic power supply9 I/O Module10 Sheilded I/O wire11 Sheild terminal on the I/O moduleP1, N1, E1 Primary power (100V/230V)P2, N2, E2 Seondary power (100VAC)P, N, E Auxillary p ower (230VAC)Dashed lines Not connected to secondary earthSolid lines Connected to secondary earth

  • 8/11/2019 Earthing Guidelines

    11/20

    11 EarthingR

    ecomendations-PLC

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0

    Figure 2a: Secondary Earth (Multiple feeds)

    P2N2E2

    P2N2E2

    P N E

    1

    3

    2

    4

    8

    7

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1

    10

    9

    11

    Legend

    1 Panel2 Primary earth busbar3 Secondary earth busbar4 Secondary earth pit5A,5B Control transformer6A, 6B Shorting of the secondary sheild7 Mountbase8 Basic power supply9 I/O Module10 Sheilded I/O wire11 Sheild terminal on the I/O moduleP1, N1, E1 Primary power (100V/230V)P2, N2, E2 Seondary power (100VAC)P3, N3, E3 Secondary power (I/O)P, N, E Auxillary power (230VAC)Dashed lines Not connected to secondary earthSolid lines Connected to secondary earth

    P1

    N1

    E1

    P3

    N3

    E3

    6B5B

    P1

    N1

    E1

    P2

    N2

    E2

    6A5A

  • 8/11/2019 Earthing Guidelines

    12/20

    12EarthingR

    ecomendations-PLC

    6. Earthing of Multiple panels

    6.1 Separate Primary and Secondary Earth conductor shall run from the Panel to the

    Primary and Secondary earth pits respectively. Refer figures 3 , 4, 5 & 6.

    6.2 In case of multiple adjacent Panels. The earth conductors of the non powered cabinets

    must be connected to the respective earth busbar in the powered cabinet that hasconnection to the Primary and the Secondary earth pits respectively.

    6.3 The earth conductors from the adjacent Panels shall be connected in a single point

    termination. Daisy chaining of connection is not permitted. See figure 3.

    6.4 Each Panel with separate power feed, on the same floor, shall run separate Primary &

    Secondary earth conductors from the Panel to respective earth pits. See figure 4.

    6.5 Each Panel with a separate power feed, on different floors / buildings shall run

    separate Primary & Secondary earth conductors from the Panel to separate set of earth

    pits or to common earth pits depending on the distance between the two locations. See

    figure 5. (Minimum distance between Primary & Secondary Earth pits shall be > = 30

    Meters.6.6 The Primary, Secondary and the Plant earth pits shall be shorted with each other. The

    shorting shall be a single point connection. Daisy chaining of connections is not

    permitted.

    6.7 The wire gauge for interconnection of earth pits shall be 25 mm2, multistrand copper

    or equivalent aluminum wire, with insulation.

    Figure 3: Earthing of adjacent panels (With same power feed)

    P2

    N2

    P1

    N1

    7

    12

    4 3 5

    6

    6Legend for figures 3, 4 & 5

    1. Primary earth busbar2. Secondary earth busbar3. Secondary earth

    4. Primary earth5. Plant earth6. Pit level earth short7. Transformer

  • 8/11/2019 Earthing Guidelines

    13/20

    13 EarthingR

    ecomendations-PLC

    Figure 4: Earthing of adjacent panels (With different power feed)

    Figure 5: Panels on different floors (With same or different power feeds)

    4 3 5

    6

    6

    3 54

    6

    6

    1

    2

    1

    2

    1

    2

    P2

    N2

    P1

    N1

    7P2

    N2

    P1

    N1

    7

  • 8/11/2019 Earthing Guidelines

    14/20

    14EarthingR

    ecomendations-PLC

    7. Earthing of Panels with MultiplePower feeds

    7.1 Same procedure as in section 6 to be followed.

    8. Earthing of Remote Stations

    8.1 Each Panel of the Remote station shall be individually earthed as in section 4, 5 & 6.

    Refer figure 6.

    9. Connecting MMI, Peripherals

    This is aimed at the RS232 connection on the Modules used for interfacing PLC system to a

    MMI, peripherals or other RS232 based system.

    The aim is to isolate the ground/earth of the two system with the intention of breaking the

    ground current loops formed by the potential differences between the two Systems ground/

    earth.

    The isolation may be achieved by means of intermediate device providing isolation betweenthe PLC and MMI system. This device may be external to the PLC / MMI System. E.g. RS232

    optical isolators.

    3 5

    6

    6

    1

    2

    3 5

    6

    6

    1

    2

    Distance between

    two panels > 30m

    7

    44

    Figure 6: Earthing of two remote panels

    Legend

    1. Primary earth busbar2. Secondary earth busbar3. Secondary earth4. Primary earth5. Plant earth6. Pit level earth short7. Communication cable

  • 8/11/2019 Earthing Guidelines

    15/20

    15 EarthingR

    ecomendations-PLC

    10. Cables and Conduits

    All communication cables should be run in conductive metallic conduits. The conduit should be

    connected to the Plant earth not just by the virtue of its contact with the building steel. It

    should be intentionally connected to the Plant earth at least at one location, preferably at

    multiple locations. The conduits must not be directly connected to the Primary earth as they may

    be prone to lightning strikes.

    The Cable shields of the all the I/ O cables (analog signals, digital signals) shall be connected to

    the Shield terminal identified on the respective I/ O module. They shall not be connected to any

    other point in the System.

    11. Verification of Earth Connections

    11.1 Within the Panel

    11.1.1 At the input of transformers the voltage across L to N & L to E should be same.

    11.1.2 Measure the continuity of grounding electrode conductor from the earth pit (for

    Primary & Secondary earth).

    11.1.2.1 Disconnect the cabinet power supplies i.e. Complete shut down.

    11.1.2.2 Lay a separate cable X1 from the primary earth bus bar in panel up to

    the primary earth pit & ensure the continuity of X1 w.r.t. X

    11.1.2.3 Lay a separate cable X2 from the Secondary earth bus bar in panel

    upto the Secondary earth pit & ensure continuety of X2 w.r.t. X

    11.1.3 Check the pit level continuity between Primary & Secondary earth.

    11.1.4 Conduct megger test at 500V dc. This is to be conducted before mounting I/ Omodules or any other modules.

    11.1.5 Measure the insulation between primary & secondary earth bus bars in panel,

    these test should be reapeted at site with multimeter.

    11.1.5.1 Disconnect Primary as well as Secondary earth out going grounding

    conductor.

    11.1.5.2 Connect a resistance meter (ohm meter) between Primary earth &

    Secondary earth bus bar.

    11.1.5.3 Observe the resistance. It shall be greater than 1 Megohm.

    11.1.5.4 Re connect the Primary & Secondary Earth Conductors to theirrespective earth bus bars.

  • 8/11/2019 Earthing Guidelines

    16/20

    16EarthingR

    ecomendations-PLC

    11.2 Outside the Panel

    11.2.1 Fall of potential method. (Refer figure 7)

    Two auxiliary earth electrodes, are placed at a distance of 15m from the test

    electrodes as shown in the figure 7. The test electrodes and the current

    electrodes shall be so placed that they are independent of the resistance area of

    each other. If the test electrode is in the form of rod or pipe ,the auxiliary

    current electrode C shall be placed at least 30 meters away from it and theauxiliary potential electrode B shall be placed midway between them.

    A known current is passed between the electrodes A & C and the potential

    difference between the electrodes A & B is measured.

    The resistance of the test electrodes A is then given by R = V/ I. The auxiliary

    electrodes B & C usually consists of 12.5mm diameter mild steel rod driven up

    to 1m into ground.

    11.2.2 Impedance of earth electrode shall be less than 5 ohms.

    11.2.3 Impedance of earth pit must be checked once in a year.

    Figure 7: Fall of potential method(For measuring earth electrode resistance. Refer IEEE-344)

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    1 2

    A

    V~

    Electrode "A"Test electrode

    Electrode "B"Potentialelectrode

    Electrode "C"Current electrode

    " 15m #" 15m #

    Above earth level

    Below earth level

    CurrentSource

  • 8/11/2019 Earthing Guidelines

    17/20

    17 EarthingR

    ecomendations-PLC

    12. Earth pit

    12.1 Typical installation of pipe earth electrode is shown in figure 8.

    12.2 The distance between any two earth pits should be greater than 30 meters.

    12.3 Keep the surrounding soil of the earth pit moist.

    12.4 The effect of soil temperature on soil resistivity is more influencing near and below

    freezing point, necessitating the installation of earth electrode at depths to which frost

    will not penetrate. The minimum depth of the earth rod must be 2.5 meters.

    Figure 8: Typical installation of earth pipe electrode(For detailed dimensions refer IS3043)

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    6 6

    3 3

    2

    4 4

    5

    1

    Above earth level

    Below earth level

    # "

    ID=100mm

    " 400mm #

    "

    2500mm

    #

    Legend

    1. Concrete structure with lid2. Cast iron or copper pipe3. Homogeneous layer of

    coke, charcoal, salt &sand4. Earth conductor (inter-pit

    & equipment)5. Funnel for watering soil6. Exothermic bond or

    brazing or connection bynon-ferrous, non-corrosive clamping device.

  • 8/11/2019 Earthing Guidelines

    18/20

    18EarthingR

    ecomendations-PLC

    13. Summary

    13.1 Primary Earth connections:

    13.1.1 The Panel.

    13.1.2 The primary neutral terminal of all input/ isolation transformers.

    13.1.3 Primary shield of all input/ isolation transformers.

    13.1.4 Earth terminal of all Field Power supplies I/ O (External to the PLC System),

    Displays, Switch matrix.

    13.1.5 Incandescent Lamps.

    13.2 Secondary Earth connections:

    13.2.1 Secondary Shield of the transformer feeding the PLC Power supply Units.

    13.2.2 Earth terminal of the Power Supplies for the PLC system (local I/ O, remote I/

    O interfaces & commutation devices).

    13.2.3 All Mountbases chassis devices in 12.2.3.

    13.2.4 Earth terminal of the power line filters.

    13.3 Dos:

    13.3.1 Isolate the Mountbase from the Panel.

    13.3.2 Run separate earth conductors to Primary & Secondary earth pits.

    13.3.3 Short Primary, Secondary and Plant earth pits at pit level only.

    13.3.4 Make Earth connections for Remote station similar to CPU stations.

    13.3.5 Short the Remote stations & CPU station earth at the pit level.

    13.3.6 Use port Isolators for RS232 communication port.

    13.4 Donts:

    13.4.1 Short Primary & Secondary earth bus bars within the Panel.

  • 8/11/2019 Earthing Guidelines

    19/20

    19

    Earthing Recomendations - PLC

  • 8/11/2019 Earthing Guidelines

    20/20

    20EarthingR

    ecomendations-PLC

    ES3000

    1Part-I(Rev.-

    2)JULY2001

    Control & Automation SectionLARSEN & TOUBRO LIMITED