E-FlexTM Enclosed Drive Controllers
For Schneider Electric Internal Use Only
2For Schneider Electric Internal Use Only
E-E-FlexFlex™ ™ Enclosed Drive ControllerEnclosed Drive Controller
Today, we will discuss:
• E-Flex as an HVAC Drive Solution
• E-Flex Design Concepts
• E-Flex Type 3R Design
• E-Flex Power Options
• E-Flex Control Options
• E-Flex meets HVAC application requirements
3For Schneider Electric Internal Use Only
Fully Enclosed AC Drive Solution
– 1 to 50 HP @ 208 - 230 VAC
• meets HVAC retrofit applications
– 1 to 100 HP @ 460 VAC
• meets HVAC new construction needs
– With and Without Bypass contactors
– HVAC specific controls and network serial communications connectivity
– Pre-wired for easy installation
– Pre-programmed for quick start up
– Type 1, 12/12K Indoor & 3R Outdoor Enclosures
– Target Market Segments
• Commercial Buildings
• Healthcare/Hospitals
• Education/Schools/Universities
E-E-FlexFlex™ ™ HVAC Drive SolutionHVAC Drive Solution
4For Schneider Electric Internal Use Only
Details Make a Difference
E-Flex™will provide you
with more than just energy savings
E-E-FlexFlex™™ Design ConceptsDesign Concepts
5For Schneider Electric Internal Use Only
E-E-FlexFlex™™ Design ConceptsDesign Concepts• ALTIVAR® 61 AC Variable Torque Drive
– Large, easy to use Graphic Display on door mounted keypad
– Quick start-up menu with macro-configuration for HVAC Pumps and Fans
– Network connectivity for building automation networks
• Thermal Management System– 1-50 HP Type 1 - No internal fans
– 1-7.5 HP Type 1 - No heat sink fan
• Front accessible heat sink fans– Eliminates rear access requirements
– Ease of repair / service
6For Schneider Electric Internal Use Only
E-E-FlexFlex™™ Design ConceptsDesign Concepts
• Enclosure Designs– Type 1 rated construction
• Designed for indoor use -- enclosure protects components from physical contact with operating personnel
• Top and bottom conduit entry with knockouts
– Type 12K rated construction• Designed for indoor use environments containing dust, dirt, fibers, lint, and non-
corrosive dripping liquids
• Top and bottom conduit entry with knockouts
– Type 3R rated construction• Designed for outdoor use -- protection from rain, sleet, and ice formation
• Ideal for ground level or rooftop applications
• Bottom conduit entry with knockouts
7For Schneider Electric Internal Use Only
E-FlexE-FlexTMTM Design Concepts Design Concepts
Seismic Qualification Option for Ground and Roof Level Applications
• Meets 2003 IBC and ASCE 7 standards for seismic qualification in accordance with ICC ES AC156 testing protocol with an Importance Factor of 1.5 for 42 states.
• Some exceptions include California, Alaska, Hawaii, Kentucky, Tennesse, and Arkansas which are site specific.
• When mounted in accordance with published guidelines, the E-FlexTM enclosure is designed and constructed to withstand violent vibration loads.
• E-FlexTM Drives have been subjected to actual shaker table tests and not just theoretical anchorage and bolt-hole calculations for seismic ratings.
8For Schneider Electric Internal Use Only
E-E-FlexFlex™™ - - Type 3RType 3R
• Complete Type 3R Product Lineup
– 1 to 100 HP @ 460 VAC
– 1 to 50 HP @ 208/230 VAC
– Compact Design
• 4 physical frame sizes
• Same mounting size as Type 1 and 12K Indoor Enclosures
9For Schneider Electric Internal Use Only
E-E-FlexFlex™™ - - Type 3RType 3R
• Lower Installed Cost– Shorter conduit runs to motor
• Reduces motor lead lengths by mounting drive closer to motor
• Reduces need for motor protection filter
– Ideal for retrofit installations• Relieves overcrowding in mechanical
rooms
• Reduces heat load in mechanical rooms by mounting outdoors
10
For Schneider Electric Internal Use Only
E-E-FlexFlex™™ - - Type 3RType 3R
• Thermal Management System– +14 to 122F (-10 to 50C) ambient
temperature rating • Thermostatically controlled space heater
• No air conditioner or special heat exchanger required
– Vermin filters on inlet and outlet ventilation openings
– “It can handle the weather”
11
For Schneider Electric Internal Use Only
E-E-FlexFlex™™ - - Power OptionsPower Options
• Circuit Breaker Disconnect (standard)
– UL 508C listed
• Short circuit protection for both drive and bypass
• Eliminates expensive and non-stock, current limiting type fuses
– Coordination with NEMA ICS 7.1
• Worse case short circuit protection
• Enhanced personnel safety exceeds minimum UL requirements
12
For Schneider Electric Internal Use Only
E-E-FlexFlex™™ - - Power OptionsPower Options
• Emergency Full Speed Bypass Option
– Mechanical & Electrical interlocked-improved reliability
• Prevents accidental back feeding of line voltage to drive
– Sequenced to provide motor isolation in drive ready state
– Bypass and Isolation contactors fully rated
– Class 20 overload in bypass mode• Provides longer acceleration
time for high inertia fans
13
For Schneider Electric Internal Use Only
E-E-FlexFlex™™ - - Power OptionsPower Options
• Input Line Contactor– Automatically removes power from
drive controller when in ready state• Competition offers only manual
isolation
– Used with bypass to meet 3-contactor bypass requirements
– Not available with Type 3R• Necessary to maintain input
power to prevent condensation build up
• Power requirement for space heaters
14
For Schneider Electric Internal Use Only
E-E-FlexFlex™™ - - Power OptionsPower Options
• Enclosed Line Reactor– 3% reactor is standard
– 5% line reactor is optional
– Reduces input line RMS currents to match output current
– Provides additional transient protection from over voltages, power factor capacitor switching
15
For Schneider Electric Internal Use Only
E-E-FlexFlex™ ™ - - Control OptionsControl Options
• Control Functions and Options– HAND-OFF-AUTOMATIC Selector Switch
• Provides remote operation of drive and bypass
• Auto Restart capability with 2-wire control
– 3 to 15 PSI Pressure Transducer Pneumatic Interface• For retrofit applications using pneumatically controlled devices
– TEST-NORMAL Selector Switch (available only with Bypass package)• Allows the user to test drive operation without turning the motor
• Allows the user to test drive operation while running in bypass
– Pilot Light Options• POWER ON • AUTO MODE
• DRIVE RUN • BYPASS RUN
• FAULT
16
For Schneider Electric Internal Use Only
E-E-FlexFlex™™ - - Control OptionsControl Options
• Control Functions and Options– Smoke Purge Relay
• Provides interface to building fire protection system
• Overrides operator controls and runs motor at full speed on bypass for smoke evacuation
• Operates drive at high speed setting when bypass is not supplied
– Freeze / Fire Stat Interlocks• User provided contact (normally closed) from HVAC system
• Prevents drive or bypass operation in the event of excessive heating or cooling by the HVAC system
– Auxiliary Contacts• Form C relays for drive run and fault indication
– Building Automation Network Communication Capability• LonWorks, Modbus, BACnet, Metasys N2, Apogee P1 and Ethernet
17
For Schneider Electric Internal Use Only
E-E-FlexFlex™™ Drive SolutionsDrive Solutions
Features
Benefits Savings $$
Circuit breakerprotection
No need for sparefuses
Saves spareparts costs
Top & bottomconduit entry
Fasterinstallations
ReducedInstallation costs
Conduitknockouts
Fasterinstallations
ReducedInstallation costs
Industrial terminalblocks
No requirementfor ring or spadelugs
SavesInstallation costs
Bypassmechanicallyinterlock
Prevents voltageback-feeding
Saves cost ofnew drive
You get more than just energy savings . . .
Quality Reliability ValueQuality Reliability Value
18
For Schneider Electric Internal Use Only
E-E-FlexFlex™™ Drive SolutionsDrive Solutions
Features
Benefits Savings $$
Front RemovableHeat Sink Fans
Ease of fanmaintenance
ReducedService time
costs
UL 508C & NEMAICS7.1 Listings
Worse case shortcircuit protection
IncreasedPersonnel safety
Bypasssequenced toprovide motorisolation
When drive is off,motor isolation isprovided
IncreasedPersonnel safety
Pre-paid shipping
No secondinvoice
Saves shippingcosts
Factory support24/7
One point forproduct support
Increased Peaceof Mind
You get more than just energy savings . . .
Quality Reliability ValueQuality Reliability Value
19
For Schneider Electric Internal Use Only
E-E-FlexFlex™ ™ Delivery and Product SupportDelivery and Product Support• E-Flex Type 1 &12K
– 10 working day lead-time
• E-Flex Type 3R
– 20 working day lead-time
• Regional Application Support with Product Application Engineers
– Drive Specialists
• Factory Support 24/7 with Phone Support Group 1-888-SQUARED (778-2733)
• Visit our website
www.us.squared.com
20
For Schneider Electric Internal Use Only
ResourcesResources
• E-Flex Instruction Manual – Technical Library Literature Number 30072-451-51A
• HVAC Drive Guide Spec for Consulting Engineer• HVAC Drive Guide Spec Presentation• E-Flex Product Presentation • Altivar 61 Quick Reference Guide
– Available in Technical Library• E-Flex CAD Drawings
– Available in Technical Library• HVAC Drive Competitive Comparison Guide• E-Flex 8 Page Color Product Sales Brochure• E-Flex Price Page• E-Flex Cut Sheet• E-Flex Engineering Submittal Guide • E-Flex Web Page
21
For Schneider Electric Internal Use Only
E-Flex SummaryE-Flex Summary
• The E-Flex utilizes the Altivar 61 Drive Power Convertor with
– pre-programmed Pump and Fan macro configuration for fast and easy start-up, – easy to use graphic display terminal, “easy start” menu and navigation wheel,– serial communications cards for Ethernet, LonWorks, BACnet, Modbus, Metasys
N2, Apogee P1 and Modbus
• The E-Flex provides 100K AIC short circuit protection rating as standard
• The E-Flex includes 3% line reactor as standard – 5% line reactor is optional
• Seismic Qualification certification option
22
For Schneider Electric Internal Use Only
Questions?