Ductboard PPT

Embed Size (px)

DESCRIPTION

Ductboard PPT

Citation preview

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Non-Metallic Duct Board

    U.P.Twiga Fiberglass Ltd.

    AIC Tech

    14th Sep.2013

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Purpose of A HVAC Duct

    To carry conditioned air from AHU to conditioned place without gaining much temperature/loosing energy.

    To deliver noise free air.

    To maintain quantity (flow rate) and quality of conditioned air:

    -Minimum leakage,

    -Minimum frictional loss,

    - Minimum pressure loss

    - No contamination

    All these above parameter can be met with Metallic and Non

    metallic HVAC ducts subjected to proper installation.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    How non metallic duct helps better

    High level of thermal and acoustic insulation according to required standards what conventional systems with lower thickness of insulation cannot achieve.

    Minimize leakage rate (< 1%, 80% better than Metal duct) hence provide better energy conservation.

    Duct fabrication and insulation in one single operation.

    Speedy execution with minimum wastage.

    Small modifications can be accommodated in fast and effective manner.

    Non Metallic insulated duct system is technologically more

    advanced and provide efficient ducting envelope in comparison

    to conventional metal ducting system.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Agenda

    Non metallic duct

    Product Features

    Application Features

    Performance

    Summary

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Non metallic duct

    Long insulation boards (typically 3 m) converted to rectangular ducts with the help of specially designed tools. Insulation material either High density Glass wool or Plastic foams suitably laminated with multilayer facings on both faces.

    Outer face is tough/reinforced and inner face is without reinforcement, designed to have grooving operation easily.

    Straight Duct modules can be joined through male-female edges to make longer ducts.

    External faces are cut/joined differently to produce Elbow, Offset, reducer.

    One or more elbow, straight ducts etc are cut and joined accordingly to produce- r-joint, triple-joint, and other complicated duct network.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Product Features: Duct joints

    Ship-lap joint to join two straight duct module.

    Perfect sealing

    Least leakage rate

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Product Features-Laminations

    Integrated Lamination options. Sometimes multicolor options.

    External side-Aluminum foil/ decorative laminations

    Internal side-Aluminum or Black glass cloth Textile

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Application Feature-Straight Duct Method

    (SDM)

    Single piece ducting- only one joint length wise.

    Multiple pieces for higher dimension duct. (external perimeter>3m).

    Wastage reduction is done by joining cut pieces from duct boards to make complete duct.

    Redpoint

    Redpoint

    Redpoint

    Bluepoint

    Bluepoint

    Red point

    Blue point tool to cut chair-shape joints and leave a flap for duct closure.

    Red point tool to cut chair-shape joints in order to foldduct boards to 90`.

    Black point tool to cutshiplaps for flat piecesfabrication.

    A

    A

    A A

    A A

    AA

    B

    B

    Two pieces in -L- duct

    -U- single piece andflat piece duct

    Single pieceduct

    Four piecesduct

    B

    B

    B

    B

    B

    B

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Application Feature- Sealing

    Stapling and Taping in Straight duct module and joining of two modules together.

    Adhesive and Taping for Elbow, Offset

    All joints are inspected from inside.

    Curing time need to be provided before going for test/operation.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Application Feature- Straight duct to Other

    shapes

    External guidelines to help proper cutting at 22.5o

    No/minimum wastage

    Elbow, Offset, r-joint, triple joint, double offset etc.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Application Feature-Reinforcement, metal

    profiles, fittings

    H-profile to join grill/diffuser.

    All sort of metallic air supply components can be fitted with non metallic ducts with the help of profiles.

    Reinforcement for bigger sized ducts at certain pitch.

    2

    3

    41.- CLIMAVER duct2.- U-shaped profile3. Sheet metal screws4.- Metal plate

    1

    CLIMA

    VER

    CLIMA

    VER

    CLIM

    VER

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Network with Non metallic ducts

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Performance

    Thermal

    Acoustic

    Fire

    Stiffness and Pressure

    Pressure Loss and Leakage

    Limitations

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Thermal Performance

    Thermal Conductivity = 0.75 sq.m.K/W

    ECBC/ASHRAE compliant.

    6-19 mm thick insulation does not comply ECBC. Non metallic ducts have 41 % more thermal resistance.

    Insulation efficiency (U-value improvement) of non metallic ducts : 28% w.r.t 19mm thick insulated metal ducts

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Acoustic Performance

    ACOUSTICAL ABSORPTION (dB/ m)

    Duct 400 x 500 mm

    Frequency (Hz)

    125 250 500 1.000 2.000 4.000

    Metal duct no insulation /Foam duct 0.07 0.07 0.19 0.19 0.1 0.07

    Metal duct External insulation 50 mm 0.14 0.14 0.38 0.38 0.2 0.14

    Non metallic fiberglass duct with

    aluminum lining1.26 1.26 1.26 4.99 3.97 3.01

    Non metallic fiberglass duct with textile

    lining1.67 4.99 5.52 8.86 9.45 8.86

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Fire Performance( glass wool ducts)

    Ducts made of inorganic glass fiber insulation is incombustible in nature.

    Minimum/Zero smoke emission.

    No incandescent droplets.

    Complies/Supersede International Mechanical Code- limited spread of fire/ flame/toxic fumes.

    Unlike rubber/polyethylene based external insulation it is completely safe at core and least potential to fire hazard.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Stiffness and Pressure

    Stiffness:

    Class R5 according to EN-13403 (MAXIMUM LEVEL)

    Tested in accordance with EN-13403

    Pressure:

    Ductboards can stand pressure up to 800 Pa with no evidence of breaks(Tested at 2000 Pa, derated by 2.5)

    Tested in accordance with EN-13403

    Classification for board stiffness

    Stiffness class Flexural rigidity [EI] N

    mm2

    R 1 55,000

    R 2 90,000

    R 3 160,000

    R 4 200,000

    R 5 300,000

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Pressure Drops and Leakage

    Similar to Metal ducts owing to its aluminum facing based surface backed with rigid and flat insulation boards . ASHRAE charts for metal ducts can be consultant pressure drop.

    Leakage rate is quite low than metal ducts( less than 1%, best/D category) owing to its ship lap joints tight fit and more area contact. (Ref: Test report extract).

    Conventional Metal ducts have approx. 5% leakage rate.

    PRESSURE DROPS IN CURVED ELBOWS AND IN

    THREE-PIECE DUCT ELBOWS

    0

    10

    20

    30

    40

    0 1.75 3.5 5.25 7 8.75 10.5 12.25 14

    Speed in m/ s

    Pre

    ssure

    dro

    p in

    mm

    c.a

    .

    Curved

    Elbow

    300x300

    Three-

    pieces Duct

    300x300

    Curved

    Elbow

    390x320

    Three-

    pieces Duct

    390x320

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Erosion/Particle Migration(IAQ requirement)

    18 m/s for 5 Hr.

    0.022gm/cu.m against maximum

    limit of 60gm/cu.m

    EN 13403 / UL

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Limitations

    Smoke or gasses evacuation.

    Outside placed ducts, or buried, without protection.

    Vertical ducts 3 m without reinforcements

    USE LIMITS

    - Static pressure >800 Pa (80 mm c.a.)

    - Air speed > 18 m/s

    - Internal air temperature > 90C

    - External air temperature > 65C

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Summary

    Parameter Non Metallic-

    Glass Wool

    ducts

    Non Metallic-

    Foam Ducts

    Metallic Ducts+

    19mm Insulation

    Thermal

    Resistance

    High (ECBC

    compliant)

    High (ECBC

    compliant)

    Low (Non

    compliant)

    Acoustic

    Parameter

    High absorption Low absorption Low absorption

    Frictional Loss of

    Pressure

    Meets ASHRAE

    requirement

    At bends/Elbow

    slightly better than

    metal duct

    Same as Metal

    duct

    Meets ASHRAE

    requirement

    Leakage Rate

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Summary, cont.

    Parameter Non Metallic-

    Glass Wool

    ducts

    Non Metallic-

    Foam Ducts

    Metallic Ducts+

    19mm Insulation

    Fire Parameter Best in class. Non

    combustible at

    core. No

    incandescent

    droplets

    Plastic foam is

    combustible in

    nature. Fire

    droplets possible.

    PIR ducts are

    comparative

    better than PUF

    Combustible with

    plastic/rubber

    based insulation.

    Fire safe with

    Glass wool

    insulation

    Stiffness/Rigidity Meets Highest

    class (R5)as per

    EN std.

    Rigid Highest rigidity,

    better than non

    metallic ducts

    Erosion Zero erosion Zero Erosion Depends on

    proper installation

    of acoustic lining.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Summary, cont.

    Parameter Non Metallic-

    Glass Wool

    ducts

    Non Metallic-

    Foam Ducts

    Metallic Ducts+

    19mm Insulation

    Application Need better

    skilled applicators

    Need better

    skilled applicators

    Factory made

    ducts. Installation,

    insulation

    application does

    not need mush

    skilled applicators

    Ease of operation Duct making and insulation in a single

    operation at much faster speed and

    less number of persons

    Two different

    operation with

    different set of

    applicators. Noisy

    and jobs need

    much more

    manual labor.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-

    Summary, cont.

    Parameter Non Metallic-

    Glass Wool

    ducts

    Non Metallic-

    Foam Ducts

    Metallic Ducts+

    19mm Insulation

    Adaptability at site High, minor changes can be

    accommodated with minimum

    resource.

    Low, difficult to

    modify once duct

    is fabricated.

    Cost Competitive. Low cost for

    transportation. Indirect cost saving-like

    installation/labor cost, speedy

    execution etc.

    Similar to Non

    metallic duct.

    Suitability/

    Limitation

    Upto 800 Pa and 18 m/s , Not for

    buried and external ducts.

    No limitation for

    pressure or

    velocity. Used as

    Buried and

    external ducts.

  • TWIGA

    IMO certified by-

    SAINT GOBAIN

    A Technical Licensee of-