    How Do You Size an

    Adjustable Frequency

    Drive?

  • 7/28/2019 Drives 1

    3/14

    Sizing AFDs

    Key elements The load

    The motor

    The power supply The environment

    The duty cycle

    The mounting space The budget

  • 7/28/2019 Drives 1

    4/14

    Sizing AFDs - The Load (1)

    How much starting torque? Centrifugal pump or fan?

    110% starting torque usually adequate (VT)

    Conveyor? 150% starting torque (CT)

    Is 200% breakaway torque required?

    The AFD industry conveniently has (2)ratings: 110% or 150% for 60 seconds

  • 7/28/2019 Drives 1

    5/14

    Sizing AFDs - The Load (2)

    High inertia load (centrifuge?)A centrifuge needs 40HP @ 1160RPM to run

    Centrifuge weighs 6000 lbs empty, 3 feetdiameter; Wk2= 11,760 lb-ft2

    Std motor starter 650% inrush until 65% speed, set time at 30 secs

    120% average torque until 65% speed

    Tq = (Wk2 x N) / (308 x t)

    Tq = 11,760 x .65 x 1160 / 308 x 30 = 960

    960 ft-lbs / 120% / 4.5 ft-lbs/HP = 178HP

    Voltage drop, stiction, loaded -- 200HP min

  • 7/28/2019 Drives 1

    6/14

    Sizing AFDs - The Load (3)

    But with an AFD . Goal is to get motor to 70% speed in 60

    seconds while limiting inrush to 150%

    Tq = (Wk2 x N) / (308 x t)

    Tq = 11760 x .70 x 1160 / 308 x 60 = 517 Ft-lbs

    517 / 150% = 345 Ft-lbs continuous

    345 ft-lbs / 4.5 ft-lbs/hp = 76 HP -- use 100HP

    t = 11760 x .30 x 1160 / 308 x 345 = 39 secs

    Total time = 60 + 39 secs = 99 secs (76 secsusing 100HP)

  • 7/28/2019 Drives 1

    7/14

    Sizing AFDs - The Load (4)

    Compare motor heating . (I2

    r)t watt-seconds of energy -- I

    2t (Figure of

    Merit)

    FV start

    (650%)2x 30 sec = 1267

    AFD start

    (150%)2x 60 sec = 135

    Both FofMs ignore the last part of eachstarting cycle which are comparable

  • 7/28/2019 Drives 1

    8/14

    Sizing AFDs - The motor

    Sizing AFDs based on motor HP ishazardous to your pocketbook!!

    AFDs are current rated - HPs are assigned

    Typical example, 150HP AFD is rated 189A 150HP, 450RPM motor rated 224A

    always check motor NP current rating

    And, many machinery OEMs use part ofthe motors service factor to reduce cost

  • 7/28/2019 Drives 1

    9/14

    Sizing AFDs - The power supply (1)

    Voltages: 208V, 230V, 380V, 460V, 575V, 2300V, etc

    Single and three phase

    50 and 60 HertzAvailable short circuit current

    65,000A ?

    Higher ?

    Harmonic Distortion issue?

  • 7/28/2019 Drives 1

    10/14

    Sizing AFDs - The power supply (2)

    Harmonic distortion IEEE-519 (latest edition) is the Guideline

    Typically recommends 5% THD (V and I)

    Point of Common Coupling (PCC) is key With 3% choke, < 35% AFD load at PCC