  • Effective from dd.mm.yyyy RDSO/SPN/217/2016 (Draft) Version-0

    Specification for Automatic Fire Detection & Alarm Systems for Power Equipments & Relay Room of PI/RRI/EI Installations Page 1 of 24

    Signature

    Name & Designation

    Prepared By: P.K. Baidhya JE/D/Signal

    1 st level Check By: S.K. Jain

    SSE/Signal 2

    nd level Check By: G. Pavan Kumar

    Director/IV/Signal

    DRAFT SPECIFICATION FOR

    AUTOMATIC FIRE DETECTION & ALARM SYSTEM FOR

    POWER EQUIPMENT & RELAY ROOM OF

    PI/RRI/EI INSTALLATIONS

    SPECIFICATION No. RDSO/SPN/217/2016

    Version 0

    Number of Pages -24

    Issued by

    SIGNAL DIRECTORATE RESEARCH, DESIGNS & STANDARDS ORGANISATION

    MINISTRY OF RAILWAYS MANAK NAGAR

    LUCKNOW – 226 011

  • Effective from dd.mm.yyyy RDSO/SPN/217/2016 (Draft) Version-0

    Specification for Automatic Fire Detection & Alarm Systems for Power Equipments & Relay Room of PI/RRI/EI Installations Page 2 of 24

    Signature

    Name & Designation

    Prepared By: P.K. Baidhya JE/D/Signal

    1 st level Check By: S.K. Jain

    SSE/Signal 2

    nd level Check By: G. Pavan Kumar

    Director/IV/Signal

    DOCUMENT DATA SHEET

    RDSO/SPN/217/2016 Version 0.0

    Title of Document DRAFT SPECIFICATION FOR AUTOMATIC FIRE DETECTION & ALARM SYSTEM for POWER EQUIPMENTS & RELAY ROOM OF PI/RRI/EI INSTALLATIONS

    Authors See Document Control Sheet

    Approved by RDSO Name: Shri. Deepak Bansal Designation: Executive Director (Co-Ord)/Signal RDSO, Lucknow

    Abstract DRAFT SPECIFICATION FOR AUTOMATIC FIRE DETECTION & ALARM SYSTEM for POWER EQUIPMENTS & RELAY ROOM OF PI/RRI/EI INSTALLATIONS

  • Effective from dd.mm.yyyy RDSO/SPN/217/2016 (Draft) Version-0

    Specification for Automatic Fire Detection & Alarm Systems for Power Equipments & Relay Room of PI/RRI/EI Installations Page 3 of 24

    Signature

    Name & Designation

    Prepared By: P.K. Baidhya JE/D/Signal

    1 st level Check By: S.K. Jain

    SSE/Signal 2

    nd level Check By: G. Pavan Kumar

    Director/IV/Signal

    Document Control Sheet

    Name Organization Function Level

    Shri Purushottam Baidhya JE/D/Signal

    RDSO Member Prepare

    Shri Sunil Kumar Jain SSE/Signal

    RDSO Member 1st level Check

    Shri. G. Pavan Kumar Director/Signal

    RDSO Member 2nd level Check

  • Effective from dd.mm.yyyy RDSO/SPN/217/2016 (Draft) Version-0

    Specification for Automatic Fire Detection & Alarm Systems for Power Equipments & Relay Room of PI/RRI/EI Installations Page 4 of 24

    Signature

    Name & Designation

    Prepared By: P.K. Baidhya JE/D/Signal

    1 st level Check By: S.K. Jain

    SSE/Signal 2

    nd level Check By: G. Pavan Kumar

    Director/IV/Signal

    AMENDMENTS

    Number Chapter/ Annexure

    Amendments Date

    RDSO/SPN/201/2016 Version 0.0 DD/MM/YYYY

  • Effective from dd.mm.yyyy RDSO/SPN/217/2016 (Draft) Version-0

    Specification for Automatic Fire Detection & Alarm Systems for Power Equipments & Relay Room of PI/RRI/EI Installations Page 5 of 24

    Signature

    Name & Designation

    Prepared By: P.K. Baidhya JE/D/Signal

    1 st level Check By: S.K. Jain

    SSE/Signal 2

    nd level Check By: G. Pavan Kumar

    Director/IV/Signal

    TABLE OF CONTENTS 0.0 FOREWORD 6 1.0 SCOPE 6 2.0 GENERAL REQUIREMENTS 7 3.0 GENERAL ARRANGEMENT OF AUTOMATIC FIRE DETECTION & ALARM SYSTEM (AFDAS) 9 4.0 TECHNICAL REQUIREMENTS 9 4.2 GENERAL REQUIREMENT OF DETECTORS 9 4.3 PROBE TYPE BI-METALLIC HEAT DETECTOR FOR DIESEL GENERATOR/OIL STORAGE ROOM 10 4.4 HEAT & SMOKE MULTI SENSOR FOR POWER EQUIPMENT ROOM 10 4.6 ASPIRATING (AIR SAMPLING) TYPE SMOKE DETECTOR 12 4.7 PIPING STANDARDS 13 4.8 LINEAR HEAT SENSING (LHS) CABLE 13 4.9 LINEAR HEAT SENSING (LHS) INTERFACE MODULE 14 4.10 CONTROL UNIT 15 4.11 FIRE SURVIVAL CABLES 18 4.12 MANUAL CALL POINTS 19 5.0 FIRE SUPRESSION 19 6.0 REQUIREMENTS TO BE FULFILLED BY MANUFACTURER BEFORE APPROVAL 19 7.0 INSPECTION AND TESTING 20 8.0 TEST EQUIPMENT 21 9.0 TEST PROCEDURE 21 10.0 MARKING AND PACKING 23 11.0 DOCUMENTATION 23 12.0 WARRANTEE 24 13.0 TRAINING 24 14.0 INFRINGEMENT OF PATENT RIGHTS 24

  • Effective from dd.mm.yyyy RDSO/SPN/217/2016 (Draft) Version-0

    Specification for Automatic Fire Detection & Alarm Systems for Power Equipments & Relay Room of PI/RRI/EI Installations Page 6 of 24

    Signature

    Name & Designation

    Prepared By: P.K. Baidhya JE/D/Signal

    1 st level Check By: S.K. Jain

    SSE/Signal 2

    nd level Check By: G. Pavan Kumar

    Director/IV/Signal

    DRAFT SPECIFICATION FOR AUTOMATIC FIRE DETECTION & ALARM SYSTEM FOR POWER EQUIPMENT & RELAY ROOM OF PI/RRI/EI INSTALLATIONS 0.0 FOREWORD

    0.1 This specification is issued under the fixed serial number followed

    by the year of adoption as standard or in case of revision, the year of latest revision.

    0.2 This specification requires reference to the following specifications.

    IRS: S23 Electrical signaling and interlocking equipment. RDSO/SPN/144 Safety and Reliability requirement of electronic

    signaling equipment. IRS: S-93/96(A) Valve regulated (sealed) lead acid stationary

    battery for S&T installations. IS: 2175 Fixed Heat sensitive fire detector for use in

    automatic fire alarm system. IS: 11360 Smoke detectors for use in automatic electrical

    fire alarm system. IS: 2189 Selection Installation and Maintenance of

    automatic fire detection and alarm system- code of practice.

    IS: 2190 Selection, Installation and Maintenance of First-Aid Fire Extinguishers-Code of Practice.

    NFPA 72 National Fire Alarm and Signaling Code. NFPA 76 Standard for the Fire Protection of

    Telecommunication facilities.

    0.3 Whenever reference to any specification appears in this document, it shall be taken as a reference to the latest version of that specification unless the year of issue of the specification is specifically stated.

    1.0 SCOPE

    This document sets forth general, operational, technical and performance requirements of Automatic Fire Detection & alarm System (AFDAS) for power equipment & relay rooms of Panel Interlocking (PI), Route Relay Interlocking (RRI) & Electronic Interlocking (EI) signalling installations.

  • Effective from dd.mm.yyyy RDSO/SPN/217/2016 (Draft) Version-0

    Specification for Automatic Fire Detection & Alarm Systems for Power Equipments & Relay Room of PI/RRI/EI Installations Page 7 of 24

    Signature

    Name & Designation

    Prepared By: P.K. Baidhya JE/D/Signal

    1 st level Check By: S.K. Jain

    SSE/Signal 2

    nd level Check By: G. Pavan Kumar

    Director/IV/Signal

    2.0 GENERAL REQUIREMENTS

    2.1 Automatic Fire Detection & Alarm System (AFDAS) shall consist of the following: 2.1.1 Fire Detection & Alarm System (FDAS) - comprising of any

    or all of the following detection systems:- (a) Bimetallic Heat detectors for Diesel Generator/Oil

    Storage room. (b) Heat and Smoke multi sensors for Power Supply Room. (c) Linear Heat Sensing (LHS) cable along with its interface

    module (for cable trays, cable troughs & cable bunch etc.)

    (d) Aspirating (air sampling) type smoke detector for Relay Room.

    2.1.2 Alarm & Control Unit (ACU) - For reading the signals from sensors/detectors, giving audio/visual alarms.

    2.1.3 Other Items (OI) - like connecting cables, relays etc. necessary for commissioning & reliable operation of the AFDAS.

    2.2 The AFDAS shall be designed to work on power supply of 24 V DC ± 20% and also on 230 V AC± 20%. It shall have in-built charging facility to have 24V battery backup (VRLA as per IRS: S-93/96(A) or latest) for at least 24 hours. It shall power the Linear Heat Sensing Cables and all detectors, Manual Call Points etc., which constitute AFDAS.

    2.3 The AFDAS shall be self-checking & diagnostic type. It shall continuously monitor the health of the sensors/ detectors & the complete system including battery. The data regarding health & event shall be logged in the system with date & time stamp, which can be downloaded to a PC/ Laptop at later stage. The system should have capacity to store data for up to a minimum of 3000 fire events. The Alarm Control Unit (ACU) shall be networkable to the Zonal/Divisional Railway headquarters preferably over TCP/IP.

    2.4 The system shall be suitable for installation in electrical cabinets, transformers, invertors, cable trays, electronic equipments, power equipment rooms, relay rooms, or any other enclosed areas, which are vulnerable for fire as deemed fit by Indian Railways.

    2.5 The system shall be suitable to detect fire/ fire like situation in relay room, power equipment room, electronic equipment, electrical wiring etc., and generate audio/visual alarms.

    2.6 The AFDAS