Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
1
Draft Regulation on the Energy Conservation and Energy
Efficiency for the Textile Industry
1. The energy users applicable to this Regulation shall mean any entity that has
completed the company registration or business registration according to the law
and conducts in the business sector of the spinning of yarn, weaving of textiles,
manufacture of non-woven fabrics, and finishing of textiles.
2. The terms in this regulation shall be defined as follows:
2.1 Chiller: Equipment that uses a refrigerant as the working fluid, employs
mechanical work as the driving power, and achieves the result of refrigeration
with the refrigerant undergoing a process including compression, cooling,
expansion and evaporation. A chiller comprises elements such as refrigerant
compressors and driving units thereof, evaporators, condensers, and flow control
devices.
2.2 Condenser: A heat exchanger that condenses a gaseous refrigerant into a fluid
refrigerant to release heat.
2.3 Evaporator: A heat exchanger that causes a fluid refrigerant to evaporate to
become a gaseous refrigerant so as to absorb heat.
2.4 Load Management of a Chiller system: Management of a group of multiple
chillers that operate in parallel. As far as the air-conditioning load meets its
requirement, the optimal number of operating Chillers through running sequence
control or the minimum number of operating Chillers shall be implemented
according to the daily variation of the air-conditioning load.
2.5 Thermal Fluid Heater: A heater that uses gas phase or liquid phase of organic
heating medium as working fluid.
2.6 Total Nominal Amount of Combustion: The sum of the low heating value of the
maximum fuel usage in all burners in the Thermal Fluid Heater, but does not
include the low heating value of the fuel used in the burner that used only for the
purpose of ignition.
2.7 Existing Equipment: A Chiller or Thermal Fluid Heater that meets one of the
following conditions:
2.7.1 Installed before the regulation is in force.
2
2.7.2 Purchased before the regulation is in force but the equipment has not been
completely installed on the effective day. The energy users should provide the
supporting procurement contracts to prove it.
2.8 Newly-Installed Equipment: A Chiller or Thermal Fluid Heater other than the
Existing Equipment.
2.9 Diameter of Exhaust Duct: Inside diameter or inside equivalent diameter that
meets the following conditions:
2.9.1 It means the inside diameter if the exhaust duct is a round pipe.
2.9.2 It means the inside equivalent diameter if the exhaust duct is not a round pipe.
It is equal to four times of the cross-sectional area of the inside of the duct
divided by the circumference of the cross-sectional area of the inside of the
duct.
2.10 Exhaust Gas Temperature: Reading of the exhaust gas temperature measured in
the following monitoring point:
2.10.1 For the Thermal Fluid Heater without any heat recovery unit installed at the
exhaust gas outlet, the monitoring point located at the place that is within a
certain distance from the exhaust gas outlet of the Thermal Fluid Heater where
such distance should be within the length of five times of the duct diameter.
(see Figure 1).
2.10.2 For the Thermal Fluid Heater with heat recovery unit installed at the exhaust
gas outlet, the monitoring point located at the place that is within a certain
distance from the exhaust gas outlet of the last heat recovery unit where such
distance should be within the length of five times of the duct diameter. (see
Figure 2).
2.11 Exhaust Gas Concentration of Oxygen: Reading of the exhaust gas
concentration of oxygen measured in the monitoring points located at the
exhaust gas outlet of the Thermal Fluid Heater.
2.12 Normal Operating Period of Chiller: The time period that the Chiller is used
under normal operating condition.
2.13 Normal Operating Period of Thermal Fluid Heater: During the time period from
the discharge, the completion of the manufacture of qualified products by the
Thermal Fluid Heater, to the cease of the feed.
2.14 Continuous Monitoring: Measurements within a specific period of time during
3
the Normal Operating Period. In the event that an abnormal condition occurs,
the period from the time the abnormal condition begins to the time the abnormal
condition is removed may not be counted into the Normal Operating Period
provided that the energy user can submit relevant records for proof of the
abnormal condition.
2.15 Monthly Average Value: The arithmetic average of the data monitored during the
Normal Operating Period of the Chiller or the Thermal Fluid Heater from 0:00 of
the first day of the month to 24:00 of the last day of the same month.
2.16 Annual Average: Arithmetic average of the Monthly Average readings of each
month in such year.
2.17 Co-Firing: Use of two or more kinds of liquid, gas or solid fuels at the same time
in the Thermal Fluid Heater.
2.18 Equipment Utilization Rate: Heat load rate of the Thermal Fluid Heater: The
calculating formula is as follows:
Equipment Utilization Rate = ∑ 𝑄𝑖𝐻𝑖
𝑛𝑖=1
𝑅× 100%
where
n: The number of types of fuels used;
Qi: The feeding rate of the i-th type of fuel. (unit: cubic meter/hour for gas
fuel, litre/hour for liquid fuel, and kilogram/hour for solid fuel);
Hi: The low heating value of the i-th type of fuel (unit: kilocalorie/cubic
meter for gas fuel, kilocalorie/litre for liquid fuel, and
kilocalorie/kilogram for solid fuel);
R: Total Nominal Amount of Combustion (unit: kilocalorie/hour).
2.19 Daily Average Equipment Utilization Rate: Arithmetic average of Equipment
Utilization Rate shall be calculated every hour from 0:00 to 24:00 of the same day
during the Normal Operating Period of the Thermal Fluid Heater.
3. Starting from January 1, 2016, when using the Group of multiple Chillers, the
energy user shall comply with the following:
4
3.1 Continuous Monitoring shall be performed to obtain temperatures (in centigrade)
of the supply chilled water and return chilled water of Evaporators (see Figure 3),
and temperatures (in centigrade) of the supply cooling water and return cooling
water of Condensers (see Figure 4). Temperature measurements shall be taken at
least once per hour and recorded to one decimal place.
3.2 The Monthly Average Value of temperature differences between the supply chilled
water and return chilled water of Evaporators, and the Monthly Average Value of
temperature differences between the supply cooling water and return cooling
water of Condensers shall comply with the requirements specified in Table 1.
3.3 If more than three continuously operating Chillers are installed within a single
factory and the total capacity of said Chillers is more than 180 tons of
refrigeration, Load Management must be implemented.
3.4 Thermometers used for Continuous Monitoring shall be calibrated or compared
according to the following provisions:
3.4.1 The thermometers shall be calibrated at least once every 12 months. The
calibration may be performed by the energy user itself or any other institution
retained to do so.
3.4.2 Where the energy user retains other institutions to conduct the calibration, the
laboratory of the institution retained shall be certified by Taiwan Accreditation
Foundation. Where the calibration is conducted by the energy user, the
calibration report of the standard equipment must be submitted for comparison,
provided that the day of the calibration conducted by the energy user must be
during the effective time period of the calibration report of the standard
equipment, and provided further that the laboratory issuing the report must be
certified by the Taiwan Accreditation Foundation.
3.4.5 In case of malfunction of the thermometer set forth in Paragraph 3.4, the
examination and repair must be completed within two months from the next
day of the malfunction.
5
4. Starting from January 1, 2016, when using the Thermal Fluid Heater, the energy
user shall comply with the following provisions:
4.1 The upper limit of the Annual Average of the Exhaust Gas Concentration of
Oxygen and the upper limit of the Annual Average of the Exhaust Gas
Temperature of the Thermal Fluid Heater shall comply with the values listed in
Table 2 and 3. Notwithstanding the foregoing, in the event there is Co-firing,
the Exhaust Gas Concentration of Oxygen and the Exhaust Gas Temperature
should comply with the limit of the Exhaust Gas Concentration of Oxygen and
the Exhaust Gas Temperature of the fuel that has the higher total heating value.
4.2 Continuously Monitor and record the Exhaust Gas Temperature at least once
every four hours. The record should include dates, time, and the Exhaust Gas
Temperature.
4.3 Monitor and record the Exhaust Gas Concentration of Oxygen of the Thermal
Fluid Heater at least once a week. The record should include dates, time, and
the Exhaust Gas Concentration of Oxygen.
4.4 The oxygen analyzer and thermometer should be calibrated according to the
following provisions:
4.4.1 The tolerance of the oxygen analyzer shall be less than 0.1 percent oxygen
by volume; the tolerance of the thermometer shall be less than 1% of the
reading value.
4.4.2 Calibration shall be accomplished by the energy user itself or by laboratory
which is entrusted by the energy user at least once every twelve months.
4.4.3 If the calibration is accomplished by an entrusted laboratory, the laboratory
should be certified by Taiwan Accreditation Foundation; when the calibration
is accomplished by the energy user, the following documents must be
submitted for inspection:
4.4.3.1 The calibration report of the standard equipment used for comparison; and
the energy user shall also accomplish the calibration of the standard
equipment used for comparison during the period of validity of the
calibration report of the standard equipment used for comparison.
Furthermore, the laboratory that issues the report has to be certified by
Taiwan Accreditation Foundation.
6
4.4.3.2 The oxygen concentration report of the standard reference gas issued by a
laboratory that is certified by Taiwan Accreditation Foundation.
4.5 When there are any malfunctions on the oxygen analyzer or the thermometer, the
examination and repair have to be completed within two months since the next
day of malfunction took place.
5. The energy user shall keep the records of the related calibration, recording and
calculations as set forth in Paragraph 3 and Paragraph 4 for at least 5 years.
6. By the end of March every year, the energy user shall report the usage of group of
multiple Chiller and Thermal Fluid Heater in the previous year, (in the format as
specified in Table 4 to Table 8), and shall upload relevant data to the designated
website (http://eei.itri.org.tw/) for inspection.
7. Paragraph 3 is not applicable to the group of multiple Chillers which is used
solely for the independent air condition operating system in the office areas.
8. When the energy user uses Thermal Fluid Heater in one of the following
circumstances that results in the non-compliance with the provisions regarding
the Exhaust Gas Concentration of Oxygen and the Exhaust Gas Temperature, the
energy user then does not have to follow Paragraph 4 of this Regulation after it has
submitted the relevant supporting documents to the central competent authority
and obtained the approval from the central competent authority:
8.1 The specification of the product or the manufacturing process is special and there
are special needs on the Exhaust Gas Temperature or Exhaust Gas Concentration
of Oxygen.
8.2 The Thermal Fluid Heater is operated in a batch production process.
8.3 The Daily Average Equipment Utilization Rate of the Thermal Fluid Heater is
lower than 50%.
8.4 Testing operation of a Newly-Installed Equipment, or an Existing Equipment
under modification or maintenance.
8.5 There is a clear difficulty in installing any heat recovery unit due to the space or
legal limitations.
7
Figure 1 The monitoring point of the Exhaust Gas Concentration of Oxygen and the
Exhaust Gas Temperature of the Thermal Fluid Heater (without any heat recovery unit
installed)
Figure 2 The monitoring point of the Exhaust Gas Concentration of Oxygen and the
Exhaust Gas Temperature of the Thermal Fluid Heater (with heat recovery unit
installed)
8
Figure 3 Measuring points for monitoring the temperature differences between
supply chilled water and return chilled water of Evaporators
Figure 4 Measuring points for monitoring the temperature differences between
supply cooling water and return cooling water of Condensers
9
Table 1 Mandatory requirements for temperature differences between the supply
chilled water and return chilled water of Evaporators, and temperature differences
between the supply cooling water and return cooling water of Condensers
Item Temperature
Difference Mandatory Requirement
Temperature difference
between the supply
chilled water and return
chilled water of
Evaporators
T2 - T1 More than 3°C
Temperature difference
between the supply
cooling water and return
cooling water of
Condensers
T4 - T3 More than 3°C; however, if there are
special operating requirements for
Condensers that require the Condensers
to maintain an operating temperature
difference of less than 3°C, the
mandatory requirement for the
temperature difference between the
Condensers’ supply cooling water and
return cooling water shall be 0.6 times of
the design temperature difference,
provided that the energy user must
submit supporting design documents for
proof.
10
Table 2 The upper limit of the Annual Average Value of the Exhaust Gas
Concentration of Oxygen and the Exhaust Gas Temperature of the Thermal Fluid
Heater (Existing Equipment)
Type of fuel
Controlled
items
Gas Fuel Liquid
Fuel
Solid Fuel
Total Nominal
Amount of
Combustion:
more than 9
million Kcal/hr
Total Nominal
Amount of
Combustion:
Less than 9
million Kcal/hr
Exhaust Gas
Concentration
of Oxygen (%)
5.2 5.7 7.2 14
Exhaust Gas
Temperature
(°C)
220 250 250 250
11
Table 3 The upper limit of the Annual Average Value of the Exhaust Gas
Concentration of Oxygen and the Exhaust Gas Temperature of the Thermal Fluid
Heater (Newly-Installed Equipment)
Type of fuel
Controlled items
Gas Fuel Liquid Fuel
Solid Fuel
Total Nominal
Amount of
Combustion:
less than 9
million Kcal/hr,
and installed
before June 30,
2017
The equipment
which is not
applicable to the
condition listed
in the left
column
Exhaust Gas
Concentration of
Oxygen (%)
4.7 5.1 11 6.5
Exhaust Gas
Temperature (°C) 200 230 210 230
12
Table 4 The application form for temperature differences between the supply
chilled water and return chilled water of Evaporators in a Chiller system
Name of the energy user: ________________________
Reporting period: Year of_______ (Recording period starts on January 1 of the year
and ends on December 31 of the same year)
Chilled
water
cycle
Design value Measured value (Monthly Average
Value)
Explain the reason if any
abnormal condition has
occurred
Temperature
difference
between the
supply chilled
water and return
chilled water of
Evaporators (℃)
Month
Temperature difference
between the supply
chilled water and return
chilled water of
Evaporators (℃)
January
February
March
April
May
June
July
August
September
October
November
December
Note: If there is more than one chilled water circulation system, please continue to fill
out the form by adding extra rows.
Prepared by: ___________ Title: ___________ Tel: _________
Supervisor: ___________ Title: ___________ Tel: _________
13
Table 5 The application form for temperature differences between the supply
cooling water and return cooling water of Condensers in a Chiller system
Name of the energy user: _________________
Reporting period: Year of___________ (Recording period starts on January 1 of the
year and ends on December 31 of the same year)
Cooling
water
cycle
Design value Measured value (Monthly Average
Value)
Explain the reason if any
abnormal condition has
occurred
Temperature
difference between
the supply cooling
water and return
cooling water of
Condensers (℃)
Month
Temperature difference
between the supply cooling
water and return cooling
water of Condensers (℃)
January
February
March
April
May
June
July
August
September
October
November
December
Note: If there is more than one cooling water circulation system, please continue to
fill out the form by adding extra rows.
Prepared by: ___________ Title: ___________ Tel: _________
Supervisor: ___________ Title: ___________ Tel: _________
14
Table 6 The application form for Load Management of a Chiller system
Name of the energy user:_______________________
Reporting period: Year of____________ (Recording period starts on January 1 of the
year and ends on December 31 of the same year)
Chiller
group
number
Amount of
Chillers in
the group
(unit)
Rated total
cooling
capacity
(RT)
Was load
management
implemented?
Method of load
management Note
Yes,
□ Automatic
control
□ Manual meter
reading
No,
Reason:
Central monitoring
software
Programmable logic
controller (PLC)
Others
Note: If there is more than one Chiller group, please continue to fill out the form by
adding extra rows.
Prepared by: ___________ Title: ___________ Tel: _________
Supervisor: ___________ Title: ___________ Tel: _________
15
Table 7 The application form of the usage of Thermal Fluid Heater by energy user
Name of the energy user: _______________________
Application Year: Year of____________ (the recording time starts from January 1 to December 31 of the application year)
Equipment
number
Total
Nominal
Amount of
Combustion
(kcal/hr)
Fuel used Annual fuel
consumption
Annual Average of
Exhaust Gas
Temperature (°C)
Annual Average of
Exhaust Gas
Concentration of Oxygen
(%)
Explain the reasons and the responses, if
there is any abnormal situation. Type Fuel
Lower calorific
value
Gas kcal/m3 m
3
Liquid kcal/L kL
Solid
(Coal) kcal/kg kg
Gas kcal/m3 m
3
Liquid kcal/L kL
Solid
(Coal) kcal/kg kg
Prepared by: ______________ Title: ______________ Tel: __________
Supervisor: ______________ Title: ______________ Tel: __________
16
Table 8 The application form of the Exhaust Gas Temperature and the Exhaust
Gas Concentration of Oxygen of the Thermal Fluid Heater by energy user
Name of the energy user: _______________________
Type of fuel:□ gas fuel □ liquid fuel □ solid fuel(coal)
Equipment No.:
Total Nominal Amount of Combustion: ____________million kcal /hr
Application Year: _____ (the recording time starts from January 1 of the year to
December 31)
Month Exhaust Gas
Temperature(℃)
Exhaust Gas Concentration
of Oxygen (%)
If there is any abnormal situation,
please explain the reasons and the
responses
January
February
March
April
May
June
July
August
September
October
November
December
Prepared by: ______________ Title: ______________ Tel: __________
Supervisor: ______________ Title: ______________ Tel: _____________