24
Distribuon Transformers Sustainable and reliable a company of Rauscher & Stoecklin SERW ZREW Tesar

Distribution Transformer Product Brochure - The RS Group

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Distribution TransformersSustainable and reliable

a company of  Rauscher & Stoecklin SERW ZREW Tesar

2

3

Table of Contents

Rauscher & Stoecklin 4

Quality and experience 5

TransformerDesign 6

Main Features 7

DistributionTransformers 8

Designs 10

SpecialApplications 12

TestMethods 14

Accessories 16

CertifiedQuality 18

Services 19

ProductOverview 20

R & SGroup 21

4

Our production site in Sissach, Switzerland

Withalmostacenturyofexperience,wearetherightpart-ner for high-quality electrotechnical products and energydistributionsystems.

Our product portfolio

• Transformers• Railwayswitches• Highcurrentplug-inconnectors• Buildingjunctionboxes• LUswitchgearsystems

Our flexibility and commitment to innovation makes us areliablepartnerthatiscapableofsolvingallchallengespre-sentedtousbyourcustomers.Withourhigh-quality,elec-trotechnicalproductsandsustainable, innovativesolutions,weareatrustedpartnertoourcustomers.Experiencedlong-termemployeesandjunioremployeeswiththewillandam-bitiontocontinuouslylearnarethefoundationofourcom-pany.

Ourcompanyiscertifiedinaccordancewithallcurrentstan-dards.

Long TraditionFirmlyanchoredinSwitzerland

Electricityisoneofthemostimportantsourcesofenergyanddrivingforcesofmodernsociety.

5

Distribution transformers prior to delivery

Quality and ExperienceThekeytoreliability

Toprevailagainstfiercecompetitionoverthelongterm,yousimplyhavetobebetter.

Weareoneof the leadingmanufacturers in thefieldof li-quid-filleddistributiontransformers.Basedonourlongtimeexperiencewearealsoable todesignspecial low-radiationtransformerswhichfullycomplywiththeOrdinanceonPro-tectionagainstNon-IonizingRadiation.Liquid-filledtransfor-mersarealsoproducedforripplecontrolapplicationsandasoverheadlinetransformersforrailwaycompanies.

Distribution transformers from Rauscher & Stoecklin fullycomplywiththeapplicableinternationalstandardsandregu-lations.Thepowerrangeextendsfrom100 kVAto2500kVAwithamaximumratedvoltageof36kV.Wedesignfree-bre-athing or hermetically sealed transformers depending oncustomerrequirements.

6

Distribution transformer design1.Pressurereliefvalve2.USconnections3.High-voltageplug-inbushings4.High-voltagetapchanger5. Liftingeyes6.Thermometerwithtrailingpointer

7. Ironcoreclampingangle8. Tank9. High-voltagewinding10. Low-voltagewinding11. Ironcore12. Castorsforlongitudinalandlateraltravel

Transformer Design

Avariousnumberofapplicationsrequiretechnologiesthathelptoachievealongservicelife,lowoperatingcostsandensureenvironmentalsustainability.

Design of an oil-filled distribution transformer

1

2 3

4 5

6

7

8

9

10

11

12

7

Features of our distribution transformers• Ratedpowerrangingfrom100upto2,500 kVA,50 Hz• Operatingvoltageupto36kV• Max.lossesinaccordancewithEU548 / 2014• Regulationoftheprimaryvoltage±2x2.5 %oraccordingtocustomerspecifications

• Max.installationaltitude1,000 metersabovesealevel• High-voltagebushings:plug-inbushingsforouterconesystemterminalorwithporcelainbushingsforindoororoutdoorinstallation

• Low-voltagebushings:porcelainbushingswithorwithoutflatconnectionplate

• Compactandlightweightdesign• Low-radiationdesignwith8-pointsymmetriclow-voltagebushingsonrequest

• Integratedoilretentionvatavailableonrequest (mountedbetweentankandchassisframe)

• Reinforcedinsulationandgroundedshieldbetweenhigh-voltage/low-voltagewindingsfornon-sinusoidalloadavailableonrequest

Welding the low-voltage connection of the secondary coil

Main Features

8

Distribution TransformersDesignedinSwitzerland

Rauscher & Stoecklinstandsforinnovationandqualitysince1919.

High-voltage winding

The high-voltage layer winding is wound directly on thelow-voltagewindingwiththemainisolationchannel.State-of-the-artautomatedwindingmachineswithconstantwindingtension create compact coilswithmaximumstrength. Thelayerisolationmadeofhigh-qualityinsulatingpaperisdesi-gnedusingstripisolationtechnologyandmeetsthehighestdemandsinmoderndistributiongrids.

Low-voltage winding

Low-voltage stripwindings are used for transformers star-tingwithanoutputof160 kVA.Theaxialpowerdistributioncanbefreelyadjusted inthestripwindings.Thisminimizesthethrustforcesthatoccurduringshortcircuits.Duringthedryingprocess,theactivepartbondsthelayerisolationwiththeconductorstripintoacompactcoil.

Rauscher & Stoecklin offers a wide range of transformers.Free-breathingtransformers,whicharethepreferreddesigninSwissdistributionnetworks,offertheoperatingcompanyeasymaintenancewiththesmallestdimensionsand lowestweights possible. For export markets Rauscher & Stoecklinhasalonghistoryinproducinghermeticallysealedtransfor-mers.

Our production site in Sissach has around 95 trained andhighlyqualifiedemployeesandoffersgenuineSwissquality.

9

Assembling the active part

Usingclampingstrapsmadeofstripsteel,theironcoreyokeisoptimallypressedtogetherwiththecolumnsusingprofiledsteel.Thiseliminatestierodsthatadverselyaffectthemag-neticflux.Theactivepartissecurelyscrewedtothecoverandsupportedagainstthebaseofthetank.

Iron core

Thesemicircularorovalcoreshapeallowsforextensivestan-dardizationandoptimizationandmakesiteasytoadjustthecorecross-section.Thecoreisinterleavedinastep-lappro-cess.Thesheetmetaljointshaveseveraloffsets.Thistechno-logycoupledwiththeselectionofhigh-qualitymagneticsteelplateprovidesadditionalbenefitsintermsofno-loadlossesandalownoiselevel.Weoffertransformerswithamorphouscorematerialforapplicationsinwhichextremelylowno-loadlossesarerequired.

Corrosion protection

Thecorrosionprotectionisparticularlyimportant.Thetankand cover are sand-blasted and painted or power-coatedwithseverallayersinthestandardcolorRAL7033.Low-sol-ventpaintispreferredinordertoprotecttheenvironment.

Tank & cover

Thetransformertankmustwithstandallmechanicalandther-mal loads that occur during transport and operation. Rau-scher & Stoecklin uses corrugated tanksmade of cold-rolledstripsteelwithareinforcedbottomtrough.Alloftheheatlossisreleasedfromthetanksurfaceintotheambientair.Theco-ver isbenton the longitudinal sides foradditional reinforce-mentandscrewedtothetank.Twoliftingeyesareweldedtotheunittoliftthetransformerortheactivepart.

10

Free-breathing transformersOpen transformers have been adopted as the standard inSwitzerland.Thecoverhastwopressure-reliefvalveopeningsthroughwhichtheairisexchangedwiththeaircushionunderthecoverinsidethetransformer.Thisaircushionmakescon-tactwith thecooling liquidandanyabsorbedmoistureovertheentiresurfacecanescapeduringhighercoolanttempera-tures.The free-breathingdesign is characterizedby lowoilvolumeandextremely small dimensions.Duringoperation,thetransformeroperateswithoutanypressure.Inaddition,thetankisnotsubjectedtoadditionalmechanicalloads.Thefree-breathingdesignhasprovenitselfathousandtimesoverandiscost-effective.

Hermetically sealed transformersTransformerswithhermeticallysealedtanksarestandardininternationalmarkets. The unit is fully hermetically sealed,thuspreventingdirectcontactofthecoolingliquidwiththeair and further reducing maintenance costs thanks to thehigheroilquality.Theoilexpansionisabsorbedbythecoo-ling shaftsand thereforesubjects the tank toanadditionalmechanicalload.Inordertolimitthepressure,hermeticallysealedtransformersrequirelowershafts,whichresults inahigheroil volume.As a result, thedimensions andweightsincreaseaccordingly.

DesignsYourSpecification–YourTransformer

Wehavebeenmanufacturingtransformerswithstate-of-the-artequipmentaccordingtocustomerrequirementsfornearly100years.

Free-breathing design

11

Industrial transformersWerecommendonlyoperatingspeciallydesigned transfor-mersinindustrialgridsinwhichhightransientinterferencevoltagesaretobeexpected,forexampleduetopowercon-vertersorfrequency-controlleddrives.

Frequentorconstanttransientinterferencevoltagesresultintheprematureageingof thepaper insulationandwirecoa-ting,bothonthetransformer'slow-voltageandhigh-voltageside.

Inordertopreventthis,additionalmeasuresmustbetaken;thelayerinsulationmustbereinforcedandagroundedshieldmustbeinstalledbetweenthehigh-voltageandlow-voltagewinding.

Cast resin transformersRauscher & Stoecklin offers cast resin transformers fromTesar,acompanyof theR&SGroup,asanalternative to li-quid-filleddistributiontransformers.Thecastresintransfor-merscomplywiththeapplicableinternationalstandardsandareusedwhereverliquid-filledtransformersareundesirable or wherever environmental or fire prevention regulationsexist. The power range extends from 160  kVA to 25  MVAwithamaximumratedvoltageof52kV.

High-qualitymaterialscoupledwithsolidworkmanshipensu-remaximumreliability.Thelow-voltagewindingisinsulatedwithresin.Thehigh-voltagewindingiscastwithoutanycavi-tiesinacompressionmoldundervacuumandhardenedwithnocracking.Fiberglassinsulationandepoxyresinareusedtoensurehighmechanicalstrength.

Due to the lowfire risk, cast resin transformers canbe in-stalledintheload'scenterofgravity.Theyeasilywithstandshort-termpeakloads,whichoccurwhenstartingmotorsorduringweldingoperations.Afancanbeinstalledtoallowforapermanentoverloadofupto40 %.Thefansarefastenedtothetransformerclampingstructureandcanberetrofittedatanytime.

Castresintransformerscanalsobeinstalledinhousingsonrequest.ProtectionclassesIP 21,IP 23andIP 31areavailable.

Cast resin transformer

12

Customized solutionsIf standard solutions cannot meet all application require-ments, we also produce customized solutions on request.Thecustomerisinvolvedineverydevelopmentsteptode-velop the perfect solution. Rauscher & Stoecklin has pro-found expertise and a series of reference projects in thisarea.

Dry-type transformersRauscher&Stoecklinair-cooledtransformersareusedwher-ever lowvoltagemustbe transformed into lowvoltage.Theunitsaremanufacturedaccordingtocustomerspecificationsasanautotransformerorisolatingtransformerandarealsobasedonindividualcustomerrequests.

Thepowerrangeforsingle-phasetransformersextendsfrom5 kVAto100 kVAandforthree-phasetransformersfrom10kVAto400kVAwithamaximumratedvoltageof1.1kV.

The transformers are designed with insulation class B or Fdependingonthesizeorcustomerrequirements. Insulationthatischaracterizedbyhighmechanicalandelectricstrengthandgoodthermalpropertiesisuseddependingontherequi-redthermalclass.Theactivepartisimpregnatedusingava-cuum-pressureorimmersiontechniquetoprotectitagainstmoisture.ItisthenpaintedinthecolorRAL 7032.

Dry-typetransformerscanalsobe installed inhousingsonrequest.ProtectionclassesfromIP 20toIP 22areavailable.

Single-phase transformer

Special-purpose transformersLoads in thedistributiongridarecontrolledremotelyusingaudiofrequencyripplecontrol.

Wesupplyaudio-frequencytransformersforthesimultaneoussupplyof ripplecontrol systems fora frequency range from200 Hzto2000 Hzandforamaximumratedvoltageofappro-ximately36 kV.

For railway companies, Rauscher & Stoecklin produces sing-le-phaseoverheadlinetransformersupto1000  kVAforsup-plyingloadsinrailwaygridswith15  kVand162/3 Hzor25 kVand50 Hz.

Special ApplicationsNewChallenges– NewSolutions

Ourcustomizedsolutionsandspecialoptionssatisfyallcustomerrequire-ments

13

Amorphous transformersTomeettheconstantly increasingdemandsintermsof los-ses, Rauscher & Stoecklin also offers distribution transfor-merswithamorphouscores.

Amorphous transformerswithparticularly lowno-load los-sesareidealwhereversuchlossesplayamajorroleandtheassociatedcostsaretobeabsorbedoverthelongterm.Mostamorphoustransformersnowalreadysatisfythelimitvaluerequirementsthatwillcomeintoforcein2021.

The lower no-load losses compared to a convention trans-formeraretheresultofthecorematerial.Thecoreinamor-phoustransformers isproducedoutofverythinfoilsmadeofamorphousmaterials.

Thecrystallinestructureoftheamorphouscoreissignificant-lyeasiertomagnetizeanddemagnetizethanwithaconven-tionalcore.Thisproducesconsiderablyfewerno-loadlosses.

Theamorphoustransformersareavailableintheoutputran-gefrom400 kVAto1,000  kVA.Othersizesareavailableonrequest.Theyofferthesameequipmentoptionsasthestan-dardtransformers.

Distribution Transformer with on-load tap changerWhen planning and operating grids, there is an increasingnumberofobviousadvantagesachievedbydynamicallyad-justing the voltage in the distribution grid and thus also inmediumand lowvoltage.Asalreadymentioned in thehig-hervoltagelevels,vacuumon-loadtap-changersarethetoolofchoicehere–replacingthestatictransformersthathavebeenusedtodate–toexpandthevoltageadjustmentfunc-tionduringoperationinthedistributiongrid.

Controllabletransformersthatcandynamicallychangethetransformerratioandthus thevoltagesare theworldwidestandard in high-voltage and extra-high-voltage grid sys-tems. In the past, however,most transformers connectedtomediumvoltagecontaineda tapchanger,viawhich thevoltage could only be adjustedwhen the transformerwasswitchedoff.

ThisiswhyRauscher & Stoecklinoffersdistributiontransfor-merswithon-loadtapchanger.Withvacuumon-loadtapch-angers,werelyontheexperienceandproventechnologyofMaschinenfabrikReinhausen.Wewillbehappytoadviseyouaboutyourcustomizedsolution.

Low-radiation transformer

14

Test MethodsOurtestfacility

TestingAll transformers undergo standardized routine testing andatestreport isdrawnupatourtestfacility.Itcontainsthefollowingpoints:• Measurementofthewindingresistances• Measurementoftransformerratioanddeterminationofthevectorgroup

• Testwithappliedvoltage(externalvoltagetest)• Testwithinducedvoltage(internalvoltagetest)• Measurementofno-loadcurrentsandno-loadlosses• Measurementofwindinglossesandshort-circuitvoltage

Type and special testingTypetestsandspecialtestingarealsoperformedinourtestfacilityoranexternaltestfacilityoncustomerrequest:

• Noisemeasurement• Temperaturerisemeasurement• Short-circuitresistance• Surgevoltagetest• Oilanalyses

Our transformer test facility

15

Transformers shortly before delivery

Winding of a distribution transformer

16

Our AccessoriesCustomizedsolutions

Integrated oil retention vat

Thistransformerdesignisequippedwithanintegratedoilre-tentionvatmadeofsteel.Itissecurelyconnectedtothetrans-formerbetweenthetankandthechassisframe.Integratedoilretentionvatsmustbeincludedintheprojectfromthestart,sincethewidertransformerdimensionsmaynolongerallowinstallationthroughexistingdooropenings.

Stand-alone oil retention vat

Stand-aloneoil retention vats aremadeof lightweight alu-minumandaresuppliedseparately.Thestand-alonedesignoffersvariousadvantages.Theycanbesubsequentlyplacedundereverytransformerandinstalledseparatelyinthestati-on.Narrowdoorsnolongerpresentaproblem.Allstand-alo-neoiltroughscanbeconnectedonthelongitudinalornar-row side or completely sealed.With the EASY design, thetransformermust only be lifted a fewmillimeters and canthusberolledintothetrough.

Contact dial thermometer

• Instainlesssteel• ProtectionclassIP54• Measuringrange0–120°C• Accuracyclass1.5• ScrewconnectionG1• Withtrailingpointer(standardfrom400kVA)• Withtrailingpointerandswitchingoutput (2microswitches)

17

Castors

• AccordingtoEN50216-4withframe,switchableforlongi-tudinal and transverse travel

• Sizesupto400 kVA:Ø125 x 40 mm,nylon,bracketM16• Sizesupto630 kVA:Ø125 x 40 mm,castiron,bracketM16

• Sizesupto1600 kVA:Ø125 x 40 mm,castiron,bracketM24,colorRAL7033

• WheellockcanbefixedwithM12screws• Wheellockfornylonorcastironcastors,Ø125 x 40 mm

Additional accessories and options

Rauscher & Stoecklinoffersthefollowingcustomizedsolu-tions:• Specialdimensions• Specialaltituderequirements• Measuresforseismicsafety• Additionalmonitoringdevices(PT100,RIS,etc.)

Pleasedonothesitatetotellusaboutyourindividualrequi-rements.

Vibrastop & wheel locks

Vibrastop:• Fortransformersfrom500upto2,500 kg• Fortransformersfrom2,500upto12,000 kg

Connecting plates

• AccordingtoDIN42530• DT630hole1xØ14 mm• DT1000hole2xØ14 mm• DT2000hole3xØ14 mm• DT3150hole4xØ14 mm

18

AtRauscher & Stoecklin,weareproudofourtestfacility,aswell as the regular routine testing andwide variety of ad-ditionalmeasurementsthatweofferinaccordancewithIECstandards(seealsoourtestmethods).

Wecanalsoperformallthestandardoilinspectionsforourcustomersinourlaboratory.

Ofcourse,Rauscher & Stoecklincontinuouslymonitors,regu-larlycalibratesandcertifiesthetestequipment.Certificatescanbeprovidedonrequest.Rauscher & Stoeckliniscertifiedinaccordancewith ISO9001, ISO14001andOHSAS18001standards.

Certified Quality

Weinsistonthehighestqualitystandardsbothforourcompanyaswellasourproducts.

Michael DrechselPresident of IQNet

Roland GlauserCEO SQS

CERTIFICATEIQNet and SQS

hereby certify that the organisation

has implemented and maintains a

Management Systemwhich fulfills the requirements of the following standard(s)

ISO 9001:2015 / ISO 14001:2015 / OHSAS 18001:2007Scope No(s): 19

Issued on: 2015-10-26Validity date: 2018-10-25

Registration Number: CH-11250

IQNet Partners*:AENOR Spain AFNOR Certification France AIB-Vinçotte International Belgium APCER Portugal CCC Cyprus

CISQ Italy CQC China CQM China CQS Czech Republic Cro Cert Croatia DQS Holding GmbH GermanyFCAV Brazil FONDONORMA Venezuela ICONTEC Colombia IMNC Mexico Inspecta Certification Finland INTECO Costa Rica

IRAM Argentina JQA Japan KFQ Korea MIRTEC Greece MSZT Hungary Nemko AS Norway NSAI Ireland PCBC PolandQuality Austria Austria RR Russia SIGE Mexico SII Israel SIQ Slovenia SIRIM QAS International Malaysia

SQS Switzerland SRAC Romania TEST St Petersburg Russia TSE Turkey YUQS SerbiaIQNet is represented in the USA by: AFNOR Certification, CISQ, DQS Holding GmbH and NSAI Inc.

* The list of IQNet partners is valid at the time of issue of this certificate. Updated information is available under www.iqnet-certification.com

Rauscher & Stoecklin AGReuslistrasse 32

4450 SissachSwitzerland

Certified area

Whole company

Field of activity

Electrotechnical components and systems

Certified in accordance with the latest standards

19

ServicesMaintenance

Ourservicesalsoincludeoilanalyses,overhauls,repairs,retrofilling,anddis-posal.

MaintenanceInadditiontomanufacturinghigh-qualityproducts,wealsoof-ferourcustomersproduct-relatedservices,eitheratourcom-panyoron-site.Amongotherthings,thisincludes:

• Consultationandtechnicalsupport• Optimumavailabilityandshortdeliverytimes• Specialdesignsbasedoncustomerrequests

• Transporttotheplaceofuse,installation,and commissioning

• Insulationoilanalysiswithoilsampling• Maintenance,repairs,overhauls,andconversions• Consignmentwarehouse• Cranetransport & integration• Disposal

Transformers from Rauscher & Stoecklin are the right choice.

20

High-current connectorsPlug-inconnectorsandjunctionboxesfrom200A-400Aandupto1,000V

• Tunnelconstruction /  mining

• Marineapplications• Infrastructure / transport• Militaryapplications• Buildingsites

Railway switchesOverheadlineswitchesfrom15kVto25kVACandupto2,000A.Ourproductportfolioincludes:

• Loadbreakswitches• Disconnectors• Groundingswitches• Motordrivesand rodlinkages

Distribution TransformersOil-immerseddistributiontransformerswithupto36kVand2.5 MVA(max.3.15 MVA).

• Hermeticallysealedorfree-breathingdesign

• Optionallyavailablewithstepswitch

Power transformersPowertransformerswithupto170kVand125MVA.TestedinaccordancewithIECandGOST

• Stepup / Stepdown• Convertertransformers• Furnacetransformers

3-phase outdoor switches• Outdoorpole-mountedloadbreakswitcheswitharcingchamber

• Outdoorpole-mountedloadbreakswitcheswitharcinghorns

ProductoverviewofRauscher&Stoecklin

Building connection sys-temsUpto400A,suitableforT+TandTV.

• Buildingconnectionsys-tems,surface-mounted

• Buildingconnectionsys-tems,flush-mounted

• Buildingconnectioncolumns

Switchgear systemsLow-voltageswitchandcontrolsystems,testedinaccordancewithEN61439andEN60204.

• Distributionsystems• Testingsystems• Controlsystems• Invertersystems

Cast resin transformersCastresintransformerswithupto52kVand25MVAforvariousapplica-tionssuchas:

• Energydistribution• Industrialapplications• Railwayapplications

21

A company of R&SAninternationalorientedGroup

ThecompaniesofR&Sareunitedbytheirlong-standingexperienceinthepro-ductionofpowerproductsandtheirhungerforprogress.

Foundedin2012,R&Sisaninternationalgroupheadquarte-redinSissach,Switzerlandwithbranchesallovertheworld.

The success of R&S is built on:

• long-standingexperienceoftheassociatedcompaniesintheirrespectiveproductsectors

• ahighlymotivatedandexcellentlytrainedworkforce• productsbasedonproventechnologiesthatgohandinhandwithinnovativeandefficientmanufacturingproces-ses

This results in premium-quality products and the highestpossibledegreeofreliabilityforourcustomers.

Companies of R&S

• Rauscher & Stoecklin:Distributiontransformers, overheadlineswitches,high-currentconnectors

• SERW:High-voltageandmedium-voltageswitchgear• ZREW:Powertransformers• Tesar:Cast-resintransformers,instrumenttransformers

Our branches worldwide

SERW – Czech Republic

ZREW Transformers - Poland

Tesar – Poland

Tesar – Italy

Rauscher & Stoecklin – Switzerland

Tesar – Dubai

R&S Sales Office – Germany

Tesar – UAE

Direct sales by R&S

or partners

R&S Headquarters – Switzerland

22

Notes

Rauscher & StoecklinReuslistrasse324450SissachSwitzerlandinfo@raustoc.chwww.raustoc.ch

SERWTymákovská42,Sedlec33202Starý[email protected]

ZREW Transformersul.Rokicińska14492-412Łódź[email protected]

TesarLoc.Chiaveretto52010Subbiano–[email protected]

Tesar Polskaul.Skarbowa3432-005Niepoł[email protected]

CompaniesoftheR&SGroup

R&S International HoldingReuslistrasse324450SissachSwitzerlandinfo@the-rsgroup.comwww.the-rsgroup.com

Rauscher & Stoecklin AG Reuslistrasse 32, CH-4450 Sissach

T +41 61 976 34 00 F +41 61 976 34 22

[email protected] www.raustoc.ch

a company of  Rauscher & Stoecklin SERW ZREW Tesar Vers

ion:

120

4201

8