BS EN 12825 classificationsREG600/KH60WS9G
• Ultimate load ≥ 9kN therefore class 4
• Safety factor of 3 with deflection of less than 2.5mm
therefore a classification of 4/3/A/2 with a working
load of 3kN, KAF recommended classification
• Or a safety factor of 2 with deflection of less than
4mm therefore a classification of 4/2/C/2 with a
working load of 4.5kN
• These two classifications define the range that this
product can be used within, both will be shown on
data sheets
BS EN 12825 product classification
D-Lock30 – KH60W4L
• Recommended classification is 1/3/A/2 when used with Kped04
• Working point load of 1.5kN based on average ultimate load in excess of 4.5kN
• Alternative classification 1/2/C/2, working load 2kN
• UDL of 7.5kN/m2
BS EN 12825 product classification
D-Lock38 – KH60W6L
• Recommended classification is 2/3/A/2 when used with Kped04
• Working point load of 2kN based on average ultimate load in excess of 6kN
• Alternative classification 2/2/C/2, working load 3kN
• UDL of 10kN/m2
BS EN 12825 product classification
REG600 – KH60WS9G
• Recommended classification is 4/3/A/2 when used with Kped04
• Working point load of 3kN based on average ultimate load in excess of 9kN
• Alternative classification 4/2/C/2, working load 4.5kN
• UDL of 15kN/m2
BS EN 12825 product classification
REG600eb – KH60WS9Geb
• Recommended classification is 4/3/A/2 when used with Kped04
• Working point load of 3kN based on average ultimate load in excess of 9kN
• Alternative classification 4/2/C/2, working load 4.5kN
• UDL of 15kN/m2
BS EN 12825 product classification
RLG600 – KH60WS10G• Recommended
classification is 5/3/A/2 when used with Kped04
• Working point load of 3.3kN based on average ultimate load in excess of 10kN
• Alternative classification 5/2/C/2, working load 5kN
• UDL of 18kN/m2
• PSA light grade when used with Kped04
BS EN 12825 product classification
RLG600eb – KH60WS10Geb• Recommended
classification is 5/3/A/2 when used with Kped04
• Working point load of 3.3kN based on average ultimate load in excess of 10kN
• Alternative classification 5/2/C/2, working load 5kN
• UDL of 18kN/m2
• PSA light grade when used with Kped04
BS EN 12825 product classification
RMG600 – KH60WS13G• Recommended
classification is 6/3/A/2 when used with Kped04
• Working point load of 4.5kN based on average ultimate load in excess of 13.5kN
• Alternative classification 6/2/C/2, working load 6.75kN
• UDL of 20kN/m2
• PSA medium grade when used with Kped04
BS EN 12825 product classification
RMG600eb – KH60WS13Geb
• Recommended classification is 6/3/A/2 when used with Kped04
• Working point load of 4.5kN based on average ultimate load in excess of 13.5kN
• Alternative classification 6/2/C/2, working load 6.75kN
• UDL of 20kN/m2
• PSA medium grade when used with Kped04
BS EN 12825 product classification
RMG500 – KH50WS13G
• Recommended classification is 6/3/A/2 when used with Kped04
• Working point load of 4.5kN based on average ultimate load in excess of 13.5kN
• Alternative classification 6/2/C/2, working load 6.75kN
• UDL of 20kN/m2
• PSA medium grade when used with Kped04
BS EN 12825 product classification
CBX750 – KH75WS10G
• Recommended classification is 5/3/A/2 when used with Kped04
• Working point load of 3.3kN based on average ultimate load in excess of 10kN
• Alternative classification 5/2/C/2, working load 5kN
• UDL of 18kN/m2
• PSA medium grade when used with Kped04
BS EN 12825 product classification
TorLock – KH60WS12L
• Recommended classification is 6/3/A/2 when used with Kped04
• Working point load of 4kN based on average ultimate load in excess of 12kN
• Alternative classification 6/2/C/2, working load 6kN
• UDL of 20kN/m2
• PSA medium grade when used with Kped04
BS EN 12825 product classification
DRF600– KH60WS18G
• Recommended classification is 6/3/A/2 when used with Kped04
• Working point load of 6kN based on average ultimate load in excess of 18kN
• Alternative classification 6/2/C/2, working load 9kN
• UDL of 25kN/m2
• PSA heavy grade when used with Kped04
BS EN 12825 product classification
DRF600eb – KH60WS18Geb
• Recommended classification is 6/3/A/2 when used with Kped04
• Working point load of 6kN based on average ultimate load in excess of 18kN
• Alternative classification 6/2/C/2, working load 9kN
• UDL of 25kN/m2
• PSA heavy grade when used with Kped04
PSA certified pedestals• Pedestals are tested as part of all system testing
• Specific pedestal testing also undertaken– Horizontal load test– Vertical load test
• at centre of pedestal head• over one quadrant of pedestal head
• Horizontal load test measures the degree of free play in the pedestal when subject to a horizontal load at the pedestal head
• Vertical load at centre of pedestal head is 10.8kN for light grade and 18kN for medium, heavy and extra heavy
• Vertical load over one quadrant is 8.1kN for light grade and 13.5kN for medium, heavy and extra heavy
Pedestals;- Alpha I / Kped01
• All steel construction electro plated for corrosion protection
• Baseplate 100mm square as PSA, 2.5mm thick
• 90mm dia head, caps fitted for panel location
• Good electrical continuity from panel to earth
• Caters for floor heights from 55mm to 90mm by the use of three tube/socket lengths to give Kped01 A, B or C
Pedestals;- Alpha IV / Kped04
• All steel construction electro plated for corrosion protection
• Baseplate 100mm square as PSA, 2.5mm thick
• 90mm dia head, caps fitted for panel location
• Good electrical continuity from panel to earth
• Caters for floor heights from 80mm to 600mm
• Replaces Alpha II / Kped02
• Wide adjustment range, up to 85mm
Pedestals;- Alpha III / Kped03
• All steel construction electro plated for corrosion protection
• Baseplate 120mm square, 3mm thick
• 90mm dia head, caps fitted for panel location
• Good electrical continuity from panel to earth
• Caters for floor heights from 600mm to 1200mm
Pedestal Caps
• Fit all pedestal types• Incorporate copper
electrical continuity links were required
• Caps provide location and lateral stability for the panels
Stringers
• Steel construction, snap into pedestal head
• Used to provide lateral stability at increased floor heights, 600mm upwards for bare panels
• Introduced with factory finished panels at floor heights of 450mm upwards, help to maintain tight grid on finished floor surface
• Used to increase the structural performance of the floor, heavy to extra heavy, localised heavy equipment, rolling loads etc
BS EN 12825 pedestals
• Pedestals are tested as part of all system testing
• Specific pedestal testing also undertaken
– Vertical load test at centre of pedestal head• This load is 4 times the working load of the
system
BS EN 12825 product classification
Pedestals
• Kped05 is tested to 4 times the working load of KH60WS10G
• FFH from 80mm to 350mm
• 50mm adjustment• 90mm dia head,
standard caps fit• 100mm square baseplate
• Use Kped01, 04 and 03 as previously outlined
BS EN 12825 product applicationApplication BS EN 12825 classification and suggested products Floor finishesarea Light use Standard use Heavy use
1/3/A/2 4/3/A/2 6/3/A/2General office 1.5kN working load 3kN working load 4.5kN working load
D-Lock 30 REG600 RMG600, TorLock Carpet tiles2/3/A/2 4/3/A/2 6/3/A/2
Service 2kN working load 3kN working load 4.5kN working loadareas
D-Lock 38 REG600 RMG600, TorLock Carpet tiles4/3/A/2 6/3/A/2 6/3/A/2
Computer 3kN working load 4.5kN working load 6kN working loadrooms
REG600eb RMG600eb DRF600eb Vinyl / HPLInternet 4/3/A/2 6/3/A/2 6/3/A/2Data centre 3kN working load 4.5kN working load 6kN working loadTelecom switch
REG600eb RMG600eb DRF600eb Vinyl / HPL4/3/A/2 6/3/A/2 6/3/A/2
Comms room 3kN working load 4.5kN working load 6kN working load
REG600eb RMG600eb DRF600eb Vinyl / HPL2/3/A/2 4/3/A/2 6/3/A/2
Reception 2kN working load 3kN working load 4.5kN working loadareas
D-Lock 38 REG600 RMG600, TorLock Carpet tiles
BS EN 12825 product applicationApplication BS EN 12825 classification and suggested products Floor finishesarea Light use Standard use Heavy use
1/3/A/2 4/3/A/2 6/3/A/2Educational 1.5kN working load 3kN working load 4.5kN working load
D-Lock 30 REG600 RMG600, TorLock Carpet tiles4/3/A/2 6/3/A/2 6/3/A/2
Print rooms 3kN working load 4.5kN working load 6kN working load
REG600eb RMG600eb DRF600eb Vinyl, rubber1/3/A/2 4/3/A/2 6/3/A/2
Call centres 1.5kN working load 3kN working load 4.5kN working load
D-Lock 30 REG600 RMG600, TorLock Carpet tiles4/3/A/2 6/3/A/2 6/3/A/2
Trading floors 3kN working load 4.5kN working load 6kN working load
REG600 RMG600, TorLock DRF600 Carpet tiles4/3/A/2 6/3/A/2 6/3/A/2
Retail 3kN working load 4.5kN working load 6kN working load
REG600eb RMG600eb DRF600eb Vinyl4/3/A/2 6/3/A/2 6/3/A/2
Light 3kN working load 4.5kN working load 6kN working loadindustrial
REG600eb RMG600eb DRF600eb Vinyl / HPL
Alternative specifications
• Assume a working load of 3kN is required with a deflection of less than 2.5mm
• KAF offer REG600 (KH60WS9G), classification of 4/3/A/2
• Alternative product offered with classification of 2/2/A/2
• This product offers a ultimate load of ≥ 6kN, safety factor of 2 and a deflection of less than 2.5mm at a 3kN working load
Alternative specifications• At present we compete primarily on price
• BS EN 12825 raises the possibility that we will also have to compete on specification
• There will be a need to develop strategies to protect our product specifications from alternative product specifications
• However once specification is written by the design team there is a reluctance to re-visit without significant savings
Summary• PSA specification is a comprehensive
document that covers all aspects of raised access flooring
• PSA and K41 makes the specification process of raised access flooring very straightforward in many cases
• BS EN 12825 is primarily a means of allowing selection on the basis of product classification
• The test methods of BS EN are significantly different to those of the PSA spec
• Product classifications are primarily based on KAF recommendations of a safety factor of 3 and a deflection of 2.5
Summary• Alternative classifications to give range over
which products can be used
• Looked at KAF products with their performance against BS EN and PSA specifications
• Application charts to provide guidance on areas of use
• Opportunities provided by BS EN to maintain specification, however strategies needed to defend from alternative specifications