7SA522- Practical Ref. For Testing 1 اﻟﺮﺣﻴﻢ اﻟﺮﺣﻤﻦ اﷲ ﺑﺴﻢ1. OPERATIONAL MEASUREMENTS: APPLIED : VPH - N = ……57.74…. I PH = ……1…. Φ V-I = ……45…. MEASURED VALUES IN THE RELAY S.N0 PARAMETER PRIMARY MEASUREMENT SECONDARY MEASUREMENT % 1. I A 2. I B 3. I C 4. 3IO 5. VA 6. V B 7. V C 8. V A-B 9. V B-C 10. V C-A 11. 3 VO 12. S 13. P 14. Q 15. FERQUENCY 16. P.F *INJECT 3 PHASES CURRENTS & VOLTAGES. *DITANCE PROTECTION = 1201=OFF. *The power measurements P, Q are positive, if real power or inductive reactive power flows into the protected object. This is assuming that this direction has been parameterized as “forward”. The sign of the power factor cos j corresponds to the sign of the real power. * ﻳﺠﺐ اﻟﺘﺄآﺪ ﻣﺎﻳﻠﻲ ﻣﻦ: - 1 - ѧѧѧ اﺗﺠﻮنѧѧѧ ﻳﻜﺎرﻳﺾѧѧѧ اﻟﺘﺎﺑﻖѧѧѧ ﻣﻄ وﻮﻣﺎتѧѧѧ ﻟﻠﺮﺳﻮنѧѧѧ اﻟﻤﺤﻘAD0201 ѧѧѧPOWERE SYSTEM DATA 1 2 - الѧ ﺗﺤﻮﻳﺴﺒﺔѧCT & PT ﻮدةѧ اﻟﻤﻮﺟѧPOWERE SYSTEM DATA 1 ﻣﻦAD0203 اﻟﻲAD0206 3 - ѧ اﻟﻘﻴﻤﺴﻮﺑﻪѧ أﻟﻤﻨѧ إﻟﻴﻬѧﺎدѧ إﻳﺠﺴﺒﺔѧ اﻟﻨѧ اﻟﻤﺆﻳﻮدةѧ اﻟﻤﻮﺟѧPOWERE SYSTEM DATA 2 ﺗﺤﺖSETTING GROUPA ﻓﻲAD1103&AD1104 * اﻟﻜﺎﺑﻞ ﺟﻬﺔ رﻳﺾ اﻟﺘﺎ اﺗﺠﺎﻩ آﺎن اذا: -

Distance Relay Test

Embed Size (px)

Citation preview

Page 1: Distance Relay Test

7SA522- Practical Ref. For Testing

1

بسم اهللا الرحمن الرحيم1. OPERATIONAL MEASUREMENTS: APPLIED : VPH - N = ……57.74…. I PH = ……1…. Φ V-I = ……45….

MEASURED VALUES IN THE RELAY

S.N0

PARAMETER

PRIMARY MEASUREMENT

SECONDARY MEASUREMENT

%

1. I A

2. I B

3. I C

4. 3IO

5. VA

6. V B

7. V C

8. V A-B

9. V B-C

10. V C-A

11. 3 VO

12. S

13. P

14. Q

15. FERQUENCY

16. P.F

*INJECT 3 PHASES CURRENTS & VOLTAGES. *DITANCE PROTECTION = 1201=OFF. *The power measurements P, Q are positive, if real power or inductive reactive power flows into the protected object. This is assuming that this direction has been parameterized as “forward”. The sign of the power factor cos j corresponds to the sign of the real power.

-: من مايليالتأآديجب *ا ه -1 ون اتج اريض يك ابق الت ومات و مط ونللرس ي AD0201 المحق POWEREف

SYSTEM DATA 1 ل ال -2 سبة تحوي POWERE SYSTEM DATA 1 في الموجودة CT & PT ن AD0206 الي AD0203منة -3 سوبه القيم ا ألمن ي إليه اد ف سبة إيج ه الن ودة المؤي يالموج POWERE SYSTEM ف

DATA 2 تحت SETTING GROUPA في AD1103&AD1104 -:اذا آان اتجاه التا ريض جهة الكابل*

Page 2: Distance Relay Test

7SA522- Practical Ref. For Testing

2

V1=57.74V-0 V2=57.74V-(-°120) V3=57.74V-(°120) I1=1A(-°45) I2=1A (-°165) I3=1A(°75)

-:BBاذا آان اتجاه التا ريض جهة *V1=57.74V-0 V2=57.74V-(-°120) V3=57.74V-(°120) I1=1A(°135) I2=1A (°15) I3=1A(-°105)

-:مثال

اريض °45عندما يكون التاريض جهة الكابل يكون التيار متاخر عن الجهد بي يصبح وعند عكس الت آما هو موضح في الرسم. °135متقدم بي

90°

135°

I

0° V 180°

360°

I

45°-

270° To test 3Io, 3Vo, inject: Ia=1A,∟0, Ib=2A, ∟180, Ic=0 →3Io=1A Va= 37V, ∟0, Vb= 57V, ∟180,Vc=0→3Vo= 20V This (3Vo) will not appear if the setting of AD210(U4 volt. Transformer is : Open delta) as the final setting, because the 3V0 is calculated in this case directly from the open delta. So to make the relay calculate the 3Vo you have to change the setting to be (Not connected). 2. IMPEDACE MEASUREMENTS: Injected Impedance Z = ………………..OHMS

Page 3: Distance Relay Test

7SA522- Practical Ref. For Testing

3

Φ = 60

Φ = 240

IMPEDANCE

CALCULATED MEASURED CALCULATED

MEASURED

RL1

XL1

RL2

XL2

RL3

XL3

RL12

XL12

RL23

XL23

RL31

XL31

R = Z * COS Φ , X = Z * SIN Φ

Note :- *Before this test check power system data 2 address (1116-1119) setting should be zero to get correct readings. !!!!!مش مهم *INJECT ( Z ) WITH ANGLE Φ

. هل هو صحيح ام خطاءR و X لتاآد من قراءة الريليه لل بزاويه ) Z( نحقن *

3. DIRECTIONAL TEST: 0112 PHASE DISTANCE: QUAD 0113 EARTH DISTANCE: QUAD

ANGLE DIRECTION FROM TO

FORWARD 339° 120°

UNDEFINED 121° 158°

159° 300°

Page 4: Distance Relay Test

7SA522- Practical Ref. For Testing

4

REVERSE

UNDEFINED 301° 338°

Note :- *3-PHASE FAULT INJECTION.1PHASE FAULT INJECTION & PH-PH FAULT INJECTION. (MUST BE SAME FOR ALL TYPS OF FAULTS) *PHASE DISTANCE: QUAD ,EARTH DISTANCE: QUAD, LED13 =3719= FORWARD (Unlatch u) LED14 = 3720=REVERSE (Unlatch u)

120°

FORWARD

159° 339° REVERSE 300°

. يجعله ال يعمل Bi التا آد من أن الريليه ال يدخل له* -:طريقة االختبار

.. ونغير في الزوايهzنثبت ال *

At isa: use z-Pro, insert z with any required angles by click & test

Page 5: Distance Relay Test

7SA522- Practical Ref. For Testing

5

if you want to use X-pro you have to calculate the Z value to be inside zone 5 at all angles, because if you changr the engle of the current only the impedance value will be changed and it does not give the right value of the Z angle- you can see it at the z-pro.

At OMICRON:

-:آما يلي )OMICRON(جهاز االختبار نختار من* *Distance..-- *Advanced Distance - *Check

أي قيمه zنضع قيمه ل * *Seguence

.في الزوايه تحديد المدي المراد اختباره وتحديد الزياده • 4. FAULT DETECTION TEST : (3 TYPES A,B AND C) A) PHASE OVER CURRENT DETECTION - I ph > :

Page 6: Distance Relay Test

7SA522- Practical Ref. For Testing

6

1201 : DISTANCE ON, 1202 : I ph > for Distance Measurement = 0.25

I ph > Setting

Pick up

0.25

0.26

Note:- *You must inject voltage more than the setting voltage at address (2913A) or make fuse fail (2915) OFF *MEASUREMENT SUPERVISION=2901 = OFF *INJECT CURRENT IN PHASE TO PHASE.

L-L بيخاصة الحالةشروط عمل الريليه وهذه * -: في الريليه ويكون ذلك اما بي L-Lويتم حقن * التأآدمع . L2و L1 وأدخلها للريليه عليN مع ال L1 واحده من جهاز الحقن بأخذ فيزه-1

الضبط قيمة يتعدى أنمن ان الجهد البد At isa: (X-pro) You have to choose the correct values and angles to simulate each fault type: L1-3: V2=57.7 V, angle: -120, V1=V3=30V, Ang.: 60 I2=0 , I1=I3(Ramp from 0: 0.26A),I1 Ang.(240:330) ,I3 Ang.(60:150) If these angles reversed , the direction will be reversed! These values extracted from Z-pro!. L1-2: V3=57.7 V, angle: +120, V1=V2=30V, Ang.: 300 I3=0 , I1=I2(Ramp from 0: 0.26A),I1 Ang.(300:390) ,I2 Ang.(120:210) L2-3: V1=57.7 V, angle: 0, V2=V3=30V, Ang.: 180 I1=0 , I2=I3(Ramp from 0: 0.26A),I2 Ang.(180:270) ,I3 Ang.( 0:90) 4. FAULT DETECTION TEST : B) 3I o DETECTION : 1202 : I ph > for Distance Measurement = ……0.25………

Page 7: Distance Relay Test

7SA522- Practical Ref. For Testing

7

1203 : 3Io for Neutral current pickup = ……0.30… 1209A : 3Io OR 3Vo

3Io > Setting (A)

Pick up (A)

Note:- * Make UN balance and check the measurements in the relay to see the 3Io values. *You must inject voltage more than the setting voltage at address (2913A) or make fuse fail (2910) OFF *KEEP 3Vo SETTING = 60V, *1202 : I ph > for Distance Measurement = ……0.1A……… *1203 : 3Io for Neutral current pickup = ……0.16A…….. * 1204 = 3 VO = 60V, INJECT CURRENT PHASE TO EARTH

. L-N شروط عمل الريليه وهذه الحاله خاصه بي*

ولن يظهر . الن الضبط اقل3Io قبل Ipسوف يعمل *

د البد ان يتعدي الضبطيجب مراعاة الجه* L-L تجد الجهاز ال يفصل إال عند هذه القيمة أما 0.15 ارفع الضبط بتاعه مثال 3I0والختبار ال

0.1فيفصل عادي عند . يتحقق Iphالحظ في الكتالوج مكتوب االرضي لوحده ما يفصلش لكن الزم

كتالوج انظر معناها بالAD 1207A 3I0 stablization/Iph maxأيضا هناك 4. FAULT DETECTION TEST : C)3 V o DETECTION : 1204 : 3 Vo Threshold zero sequence pick up = ……………

Page 8: Distance Relay Test

7SA522- Practical Ref. For Testing

8

1209A : 3Io or 3Vo

3 Vo > Setting (v)

Pick up(v)

Note:- 1204 = 3 VO Threshold zero sequence pick up = …5V………… Vrn=6v, Vyn=10V, Vbn=10V,Ang. 0,240,120 INJECT 3PHASE CURRENT =Not RATED CURRENT, because if you inject the rated the relay will trip directly! REDUCE SLOWLY Vrn voltage till relay E/F element operates.

. L-N شروط عمل الريليه وهذه الحاله خاصه بي* تيار وجهد مع مراعاة رفع التيار المحقون لكي يتعدي الضبط الخاص بالـ N-Lحقن *

O/c(Iph) and to be <3Io setting . 3(وفرق جهدUo ( اقل من الضبط ثم ارفعلي فالفرق يزداد ويظهر وذلك بإنقاص جهد الفازة األو3Uo ارفع الجهد المقصود بها جهد (الجهد

TRIPالي ان يعمل الريليه ) 3Uoفي الـ

All these steps dependent on the pre-mentioned note (U4 volt. Transformer is : not connected (not Open delta) so that the 3Uo can be calculated!

Also if you want to set the AD 1209A : 3Io AND 3Vo, you have to inject the current > 3Io setting

5. ZONE CHECK: (A &B) A) QUAD CHARECTERISTIC:

Page 9: Distance Relay Test

7SA522- Practical Ref. For Testing

9

TYPE OF FAULTS

ZONE

TIM

E

SE

TT

ING

AX

ES

A-N

B-N

C-N

A-B

B-C

C-A

ABC

TIME

1

R

Z1

FO

RW

AR

D

0

2.5

X

1.3

R

Z1B

FO

RW

AR

D

0.3

3.5

X

2

R

Z2

FOR

WA

RD

0.5

5

X

3

R

Z3

RE

VE

RSE

1.0

6

X

5

R

Z4

FOR

WA

RD

1.5

10

X

7

R

12

X

7

R

Z5

NO

N D

IRE

CT

ION

AL

2.5

12

X

0013 ثم الي Setting Group A ثم الي Settings من ZONE يتم ضبط ال ZONEألختبار ال Distance zones

ثم إلى Settings وذلك آما يلي من Quadrilateral واختيار Distanceونقوم قبل ذلك بي ضبط ال

Device configuration

Quadrilateral بي Earth Distance 0113 و Phase Distance 0112ثم نضبط

وهذا 90 بي زاويه Z تكون ال X وعند اختبار ال 0 بي زاويه Z تكون ال Rعند اختبار

وعند 180 بي زاويه Z تكون ال Rتبار عند اخReverse اما في ال Forward في ال

270 بي زاويه Z تكون ال X اختبار ال

Page 10: Distance Relay Test

7SA522- Practical Ref. For Testing

10

-:ملحوظه*

. ولكن نعكس التا ريض في الريليه او اتجاه الحقن Forward يمكن حقن بنفس زوايه ال Reverseفي

- :OMCRONطريقة االختبار بي *

1- .Distance 2- Shot . بحي. النقاط نضع-34- Add To ALL نختار -5 OK نعمل -6 وهكذا -7 . ان يكون التاريض مطابق للواقع Parameterالتاآد من ال *

By isa: Using Z-pro لوتيار الحقن ثابت على قيمة (BACKUP E/Fالحظ أن بعد المرحلة الخامسة يفصل : ملحوظة 0.25 أما األرضي 1.22فصل ألن الضبط أعلى من ما ي L-Lأما لو حقنت ) 0.25Aأآبر من

5. ZONE CHECK: B) POLAR CHARECTERISTIC

LINE ANGLE = ……….

TYPE OF FAULTS

ZONE

TIME

Z set

A-N

B-N

C-N

A-B

B-C

C-A

ABC

TIME

Page 11: Distance Relay Test

7SA522- Practical Ref. For Testing

11

Z1

FOR

WA

RD

0

2.5

Z1B

FOR

WA

RD

0.3

3.0

Z2

FOR

WA

RD

0.5

5.0

Z3

RE

VE

RSE

1.0

6.0

Z4

FOR

WA

RD

1.5

10.0

Z5

FOR

WA

RD

2.5

12.0

85بزاويه z حقن * 6 BACK UP OVER CURRENT TEST : (A &B) DISTANCE PROTECTION : 1201=OFF BACKUP O/C PROTECTION :2601=ON

. وتتأآد أن الجهاز ما يفصلO/Cل تحقن بعد المرحلة الخامسة بتيار أقل من ضبط الـ األفض

Page 12: Distance Relay Test

7SA522- Practical Ref. For Testing

12

وتتأآد أن الجهاز فصل به وآذلك في األرضي وبدون O/Cمن ضبط الـ ثم تحقن قيمة أعلى DISTANCE PROTECTION : 1201=OFFأن تعمل

A. DEFINITE TIME TEST

SETTING

MEASURED VALUES

CURRENT TIME A-N B-N C-N TIME

I >

Io >

I >>

I o >> I I

I o

سوف يفصل في زمن لحظي عيب مع أي ) (Bi CRعندما يأتي ا ل*B. INVERSE TIME TEST: I p > = A , I o > = A

CHARECTERISTIC

PHASE

T.M.S

CALCULATED TIME

MEASURED VALUE

A B C

NORMAL INVERSE

N

A B C

VERY

INVERSE N

A B C

EXTREMELY

INVERSE N

A B C

LONG INVERSE

N

سوف يفصل في زمن لحظي عيبمع أي ) (Bi CRعندما يأتي ا ل* 7. SOTF FUNTION (1 & 2A,2B) 1. SOTF SEPATATE FUNCTION {AD 2401) LED 13= 4295=SOTF TRIP SHOULD GLOW ON SOTF. CB MANULE CLOSE BINARY INPUT = 356.

Page 13: Distance Relay Test

7SA522- Practical Ref. For Testing

13

ADDRESS NO 2404 SETTING = 2 A ADDRESS NO1232 Dis. = OFF ADDRESS NO2615 O/C I> = OFF ADDRESS NO2625 O/C I>> = OFF ADDRESS NO2671 O/C Ip = OFF ADDRESS NO2601 SOTF WITH O/C = OFF ADDRESS NO1201 SOTF WITH Dis. = OFF ADDRESS NO1143= manual close

شاط ال يتم التحكم في وقت ن* BINARY INPUT ADDRESS NO 1150A بي (…2.1. ) MORE THAN THE SETTING ADDRESS NO 2404 W/O BINARY INPUT : NO TRIP (…2.1.. ) MORE THAN THE SETTING ADDRESS NO 2404 + BINARY INPUT : TRIP (…2.1…) LESS THAN THE SETTING ADDRESS NO 2404 + BINARY INPUT : :NO TRIP

AD1150A نشط من Biل الذي يكون ال يمكن التحكم في الزمن* بان الريليه ال يراى CB MANULE CLOSE BINARY INPUTيمكن االستغناء عن * وبذلك يعرف الريليه ان الفيدر مفصول ويساهم ms 250 لمدة ADDRESS NO 1130A تيار اعلي من

راقب زيادة التياربعد اعادة تشغيل الفيدرفلو حدث اثناء هذا بي جعل الريليه يADDRESS NO1132الزمن -: وبذلك تختبر آما يلي الزمن زياده تصل لقيمة الضبط يفصل بلخا صيه

ADDRESS NO1143=Current flow OR manual close ADDRESS NO 1132 SETTING = 2 S

:isaفي الـ يفصل الجهاز بالخاصية حتى لو جعلت الطبيعي قيمته أعلى من ضبط التيار يفصل آذلك prefault تحقن تيار مباشرة بدون x-proبرنامج الجهاز

ثم نحقن s 2 ثم نحقن طبيعي زمن اقل من ms 250زمن اعلي من ل الحقننحقن طبيعي ثم نفصل *

لخاصيه ا سوف يفصل بA 2تيار اعلي من ثانية فيفصل ومرة أعلى فال يفصل2أقل من مرة prefault تجعل زمن الisa في -

Also prefault value should be > AD 1130A: pole open current threshold(0.1A), otherwise the relay don’t detect that the line is live.

ثم نحقن s 2 ثم نحقن طبيعي زمن اعلي من ms 250زمن اعلي من ل الحقننحقن طبيعي ثم نفصل * سوف ال يفصل بلخاصيه A 2تيار اعلي من

ثم نحقن تيار s 2 ثم نحقن طبيعي زمن اقل من ms 250زمن اقل من ل الحقننحقن طبيعي ثم نفصل *

سوف ال يفصل بلخاصيه A 2اعلي من جهاز مازال يري الخط شغاال يعني ستكون الخاصية لم تفعل بعد ألن ال250ms احقن طبيعي ثم قبل ال-ثانية وتحقن ثم توقف حقن قبل تمام الوقت ثم تحقن 2 مرة أقل من prefault تجعل زمن الisa في -

فال يفصلms 250بسرعة في خالل ال 7. SOTF FUNTION 2) SWITCH ON TO FAULT (SOTF) A) SOTF WITH BACKUP O/C: ADDRESS NO2615 O/C I> = ON ADDRESS NO2625 O/C I>> = ON

Page 14: Distance Relay Test

7SA522- Practical Ref. For Testing

14

ADDRESS NO2671 O/C Ip = ON ADDRESS NO2601 SOTF WITH O/C = ON AD 2625 SOTF WITH ( I >>) T W/O SOTF = Sec I set = ………. (Manual close)T WITH SOTF = Sec T set = ……… (Current flow )T WITH SOTF = Sec

فيفصل ومرة أعلى AD 1132A)ثانية2( مرة أقل من prefault تجعل زمن الisaفي - فال يفصل

وتحقن ثم توقف حقن قبل AD 1132A)ثانية2 مرة أقل من prefault تجعل زمن الisa في - فال يفصلms 250تمام الوقت ثم تحقن بسرعة في خالل ال

AD 2615 SOTF WITH ( I >) T W/O SOTF = Sec I set = ………. (Manual close)T WITH SOTF = Sec T set = ……… (Current flow )T WITH SOTF = Sec AD 2617 SOTF WITH ( Ip) T W/O SOTF = Sec I set = ……… (Manual close)T WITH SOTF = Sec TMS = ……… (Current flow )T WITH SOTF = Sec Note:- -LED: SOTF P/U. because the trip is not tagged(SOTF) but still(O/C)! but with 0 sec not 2.5 sec.so this led will inform you the cause of accelerating the time. But the led did not pick up?!

- also you can read the EVENT LOG, TRIP LOG but you can not see any thing about SOTF like the first case.only if you open the fault recorder(oscillograph) you will find the pulse (Line closure).

Page 15: Distance Relay Test

7SA522- Practical Ref. For Testing

15

-BI: MANUAL CLOSED. -MAKE FAULT WITH ALL TYPE OF O/C. -CHECK THE SEAL-IN TIME SETTING FOR MANUAL CLOSE.

وسوف O/Cوبذلك سوف يعتمد ضبط التيار هو ضبط ال OFF = ADDRESS NO 2404عمل ال * عام مع الخاصية سوئ تم تشغيلها ADDRESS NO 1132 وال ADDRESS NO1134يكون ال

.DIS او O/Cمنفصله او تم تشغيلها مع

.DISومع ال ، منفصله :التاآد ان الخاصيه مغلقه* \ : isaفي الـ

BI وال بدون فال يفصل بـ –وإال يفصل باألرضي – تحقن أقل من ضبط األرضي - يكون اقل من prefaultالحظ ان ال. فيفصل باألرضي بزمنهBIمن ضبط األرضي بدون تحقن أعلى -

!ضبط األرضي وإال يحسبها من الزمن وحصلت .0ms فيفصل باألرضي بزمن BIمن ضبط األرضي ب تحقن أعلى -

7. SOTF FUNCTION 2) SWITCH ON TO FAULT (SOTF) B) SOTF WITH DISTANCE PROTECTION: (1232 = ZONE PICK UP ) ADDRESS NO1201 Dis. = ON

Page 16: Distance Relay Test

7SA522- Practical Ref. For Testing

16

ADDRESS NO1232 SOTF WITH Dis. = ON هذه لها اختيارات: - with Z1B : the trip time on the relay is 0ms so OK, but

the contact working with the zone time??!because the contact must be programmed to close also with Z1B because the tripping now is with Z1B 1-phase or 3-ph

- with pick up (non- directional) results is ok with this option. - with Z1B un directional

SOTF WITH Z1 T W/O SOTF = Sec (Manual close)T WITH SOTF = Sec (Current flow )T WITH SOTF = Sec

SOTF WITH Z1B T W/O SOTF = Sec

(Manual close)T WITH SOTF = Sec (Current flow )T WITH SOTF = Sec

SOTF WITH Z2 T W/O SOTF = Sec

(Manual close)T WITH SOTF = Sec (Current flow )T WITH SOTF = Sec

SOTF WITH Z3 T W/O SOTF = Sec

(Manual close)T WITH SOTF = Sec (Current flow )T WITH SOTF = Sec

SOTF WITH Z4 T W/O SOTF = Sec

(Manual close)T WITH SOTF = Sec (Current flow )T WITH SOTF = Sec

Note:- -LED: SOTF P/U. -BI: MANUAL CLOSED -BO: GENERAL TRIP OR SOTF. -MAKE FAULT WITH ALL

-NO SOTF TRIP LED WILL GLOW . BUT ZONE TRIP TIME WILL BE BYPASSED)

وسوف DISوبذلك سوف يعتمد ضبط التيار هو ضبط ال OFF = ADDRESS NO 2404عمل ال * عام مع الخاصية سوئ تم تشغيلها ADDRESS NO 1132 والADDRESS NO1134يكون ال .DIS أو O/C او تم تشغيلها مع منفصلة

O/C ألومع ، منفصلة : مغلقهالخاصية أن التأآد*

8. VT MCB TRIP :(00361) power syst.Data2:- ZONE 1: WITH OUT VT MCB TRIP : Distance trip ………….

WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

Page 17: Distance Relay Test

7SA522- Practical Ref. For Testing

17

ZONE 1B WITH OUT VT MCB TRIP : Distance trip …………. WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

ZONE 2: WITH OUT VT MCB TRIP : Distance trip ………….

WITH VT MCB TRIP : Distance blocked (O/C trip) …..……… ZONE 3: WITH OUT VT MCB TRIP : Distance trip ………….

WITH VT MCB TRIP : Distance blocked (O/C trip) …..……… ZONE 4: WITH OUT VT MCB TRIP : Distance trip ………….

WITH VT MCB TRIP : Distance blocked (O/C trip) …..……… ZONE 5: WITH OUT VT MCB TRIP : Distance trip ………….

WITH VT MCB TRIP : Distance blocked (O/C trip) …..………

Note:- -LED: FAILURE FEEDER VT MCB TRIP.(AD3615) -BI: FAILURE FEEDER VT MCB TRIP.(AD3615) -LED: Distance Block (AD3652) - MAKE FAULT WITH ALL ZONES WITH AND WITHOUT (BI) -DISTANCE PROTECTION WILL BLOCK.

- MAKE O/C = ON 9. FUSE FAIL MONITOR:( 2910) WE HAVE 4 CASES:( A,B,C &D) A)FUSE FAILURE MONITORING FUNCTION (3Io & 3Vo) B)VOLTAGE ABSENT MONITORING FUNCTION (3 phase voltages) C)FUSE FAILURE MONITORING FUNCTION (3 phase voltages & ∆ I )

Page 18: Distance Relay Test

7SA522- Practical Ref. For Testing

18

D)BROKEN CONDUCTOR Note:- - LED 14 = FUSE FAILURE=169, -LED: DISTANCE BLOCK AD 3652. -INJECTION VOLTAGE LESS THAN(2913A)-MAX. VOLTAGE THRESHOLD V (< 3-PHASES) -DISTANCE WILL BLOCK AFTER TIME (2916A) DELAY TIME VOLTAGE FAILURE SUPERVISION. -APPLY FAULT AT ANY ZONE (Z1….Z5)BEFORE TIME (2916A)THE RELAY SHOULD OPERATE. -2916A=0 SECS. 9. FUSE FAIL MONITOR:( 2910) -A) 1 PHASE SETTING = 30V, Vrn = 31v,Vyn=Vbn=60V, 3 PHASE CURRENT = 0.5A. SLOWLY DECREASE RN VOLTAGE & CHECK AT WHICH VOLTAGE FUSE FAIL LED APPEARS

Pdfعلى 316 ،406موجود صفحه ،*

نحقق واحد 3Vo>(AD2911A) و 3Io<(AD2912A)شرطان البد من تحقيقها وهي اما * آما يلي . الثاني وننتظر

وتشيل فازة جهد healthyممكن ببساطة اختبار ها بأن تحقن -

مرة أعلى healthy ممكن تخلي ال) V 30(ام ولو عايز تختبر تلقط عند آ - ، ومرة تخلي 3Vo > 30v فولت فلما تشيل فازة تبقى حققت 30من الـ

healthy 3 فولت فلما تشيل فازة تبقى ما حققت 30 أقل من الVo > 30v

وإال رغم أنك تشيل الفازة لكن الجهاز ما يعملش 3Io<(AD2912A)ولكن الزم تراعي أن - ,بلوك

فالجهاز آان شايف 120صلت آانت التيارات متساوية لكن الزوايا بينهم ليست ح -

3Io>(AD2912A) هام جدا .وسهل أن تحقن أي عيب بهذه الطريقة - : isaفي الـ

فازات متزن مثال نصف امبير والجهد بتاع فازة نجعله يقل لحد ما يوصل الفرق بينها وبين باقي 3 نحقن تيار - )<AD 2911A min. volt threshold u(وهو قيمة الضبط –لت فو30الفازات

prefaultنتخطي الـ : نحقن آما بالصورة -

Page 19: Distance Relay Test

7SA522- Practical Ref. For Testing

19

عشر ثوان آالبرمجة ( بعدها fuse failلكن المالحظ أن لمبة البلوك تنزل أول ما نصل للضبط وتنزل لمبة ال ) ثوان فينزالمعا بدون العشر LED 14 = FUSE FAILURE=1670أما لو اخترت برمجة اللمبة

وهذا نحققه بأن تجعل . الجهاز يراه عيب فتختفي اللمبة ألن3Io بعد ما تنزل نزل تيار نفس الفازة فتسبب - هو حالة البلوك ثم تحقن آما قلنا prefaultالة المفروض تحقن عيب وتتأآد أن الجهاز بلوك تحقن تيار عالي زاويته بالسالب عن الجهد وتظبط من قراء-

.المعاوقة على الجهاز وتتأآد أنه لوحده عيب ثم تحقنه بعد البلوك فالجهاز ما يفصلش يعني أقل من الضبط يعني التيار مسموح 3Io = 0وي نحقق ا بقيمه صغيره ونحقن تيار متس 3Io ضبط -1

الي اعلي 3Voد ذللك نرفع وبعأن يحدث به عدم اتزان بحد أقصى الضبط وإال أعلى من ذلك يعتبره عيب حقيقي وبذلك سوف يعمل الريله .3Vo آيف ذلك؟ بأن تقلل جهد فازة والباقي آالسليم فالفرق بينها وبينهم هو الـ من الضبط

S 10 تنزل بعد زمن fuse failولمبة الـ فورابلوك اآبر من الضبط 3Ioوبعد ذلك نحقن اعلي من الضبط بقيمه صغيره ونحقق الفرق بالحقن 3Vo ضبط -2

S 10وبذلك سوف يعمل الريله بلوك زمن . وننزل بلحقن AD 2912A max I (0.1 أقل من 3Io متحقق لكن شرط أن 3Voيعني تخلي شرط أنه يوجد

Thresd. ( 3تجعله غير متحقق يعن تجعلIo>0.1A فالجهاز ال يعمل بلوك يعتبرها حالة faulty ثم تقلل3Io 0.1تيار آما بالصورة فتجد الجهاز يعمل بلوك عند بأن تنزل باA

Page 20: Distance Relay Test

7SA522- Practical Ref. For Testing

20

9. FUSE FAIL MONITOR:( 2910) B) 3 PHASE SETTING = 5V, DISTANCE BLOCKED

SPONTANEOUS INDICATION APPEARS ON FUSE FAILURE OPERATION. LED 14 = FUSE FAILURE=168, 2916A=0 SECS,

Vrn = Vyn=Vbn=6V, 3 PHASE CURRENT = 0.5A. SLOWLYDECREASE 3 PHASE VOLTAGE & CHECK AT WHICH VOLTAGE FUSE FAIL LED APPEARS

408موجود صفحه * او بوضعية )(AD1130Aفي فيزه علي االقل اعلي من ويمكن في هذه الحاله معرفة ان الفيدر موصل اما بالتيار*

وبعد ذلك نحقن تيار )(3V=5 )AD1130Aونختبر هذه الحاله بضبط ال . (AD1135) وذلك من CBال .جهد للفيزات الثالثه معاطبيعي لجميع الفيزات وجهد اعلي من الضبط وننزل بل

Page 21: Distance Relay Test

7SA522- Practical Ref. For Testing

21

9. FUSE FAIL MONITOR:( 2910) C)FUSE FAILURE MONITORING FUNCTION (3 phase voltages & ∆I)

407موجود صفحه •

ونحقن طبيعي وبعد ذلك نحقن جهد متساوي للفيزات اقل من (AD2915= OFF)نعمل * (AD2914A) .ينه وبين الحاله الطبيعيه ونحقن تيار للفيزات يحقق الفرق ب(AD2913A)الضبط

في الفيزات الثالثه اقل من الضبط و الفرق بين التيارات في حالة الجهد طبيعي والجهد تحت الضبطVشرطان البد ان تتحقق ان يكون ال *

: شروط3هذه الوظيفة تستعمل التيار المخزن وتشترط ).5V(آل الجهود مع األرضي أقل من الضبط -1

. (AD2914A) من أقلوق التيارات آل فر -2

.Distance الخاصة بالـ <Iph من أآبرآل قيم التيارات -3

: شروط االتية3وإال لو آان التيار المخزن غير موجود فالبد من تحقق ال

).5V( آل الجهود مع األرضي أقل من الضبط -4

.Distance الخاصة بالـ <Iph من أقلآل قيم التيارات -5 .40mAتيارات أآبر من آل قيم ال -6

لم تنزل ونزل في سجل األحداث Fuse failureتنزل البلوك لكن voltage absent

(AD2913A=5V) . (AD2914A=0.2A) STAT1 STAT2

L1 I=1 V=30

L1 I=0.9 V=5

L2 I=1 V=30

L2 I=0.9 V=5

L3 I=1 V=30

L3 I=0.9 V=5

اذا الفرق بين التيار في الحلتانن اقل من الضبط والجهد اقل من الضبط •

9. FUSE FAIL MONITOR:( 2910) D)BROKEN CONDUCTOR.

405 صفحه موجود*

وهو اشاره فقط. حنقن جهد طبيعي وتيار طبيعي مث نفتح دائرة تيار احد الفيزات •

10. SCHEME CHECK:( 0121): (A,B,C,D,E,F &G)

Page 22: Distance Relay Test

7SA522- Practical Ref. For Testing

22

A) PERMISSIVE UNDER REACH (PUTT) SEND LOGICCS = Z1 FAULT TRIP LOGIC TRIP = Z1B FAULT+CR NO TRIP LOGIC = Z1B FAULT + NO CARRIER RECEIVED Note CARRIER RECEIVE BI = 4006, TRIP WITH TELE PROTECTION SCHEME = 3850 -LED 13 =SIGNAL SEND=4056. -LED 14 =SIGNAL RECEIVE=4054, -CASE1#:- FAULT AT Z1 (S/S#1) *RELAY TRIP CB (S/S#1) + SEND (S/S#2) -CASE2#:- FAULT AT Z1 (S/S#2) *RELAY TRIP CB (S/S#2) + SEND (S/S#1) *RECIVED (S/S#1) +FD (Z1B) (S/S#1)-TRIB

(AD0121) في ال…DEVICE CONF من ال SCHEMEيتم اختيار ال * -: يكون آما يلي Zعند اختبار ال *

(( setting Group A)) من -1 (AD0121) اختيار -2

3 - Export ثم OK ثم احفظ باسم في المكان المراد حفظه (Extended) فنضع اشاره في Advanced Distance في Setting في Omicronاما في ال *

(inpout) (Parameters) ونفتح الملف بي Z1Bوذلك الظهار

10 .SCHEME CHECK: B) PERMISSIVE OVER REACH (POTT)

SEND LOGIC = Z1B FAULT : TRIP LOGIC = Z1B FAULT+CR :

Page 23: Distance Relay Test

7SA522- Practical Ref. For Testing

23

Note:- CARRIER RECEIVE BI = 4006, TRIP WITH TELE PROTECTION SCHEME = 3850, - LED 13 =SIGNAL SEND=4056 -LED 14 =SIGNAL RECEIVE=4054

-CASE1#:- FAULT AT Z1B (S/S#1) * SEND (S/S#2) -CASE2#:- FAULT AT Z1B (S/S#2) * SEND (S/S#1) *RECIVED (S/S#1) +FD (Z1B) (S/S#1)-TRIB -ECHO SEND SIGNAL 4246 TOBE CONNECTED IN PARALLEL WITH 4056, 10 .SCHEME CHECK:

C) WEAK INFEED = ECHO ONLY WHEN CB OPEN(with pott) WEAK END INFEED = ECHO ONLY ECHO SEND SIGNAL IMMEDIATE WHEN CB OPEN, …………

Note:- WEAK INFEED =2501= ECHO CB OPEN BI =380, ECHO SIGNAL (Fn. 4246) must be allocated to the O/p relays, ECHO SEND SIGNAL IMMEDIATE WHEN CB OPEN, ECHO SEND SIGNAL AFTER TIME DELAY WHEN CB CLOSED,

فيرسلCB OPEN فير ان المقابلة المحطة الي إشارة يرسل Z1Bلفولت بي ايحس ب* -: آما يليالخاصية فسوف نختبر هذه المرسلة المحطةإلى أيضا إشارة

. CS سوف يرسل CR مفتوح نعطيه CB ال -1 . CS سوف يرسل Z1B في عيب موصل ويري CB ال -2

10 .SCHEME CHECK: D) WEAK INFEED = TRIP ONLY WHEN CB CLOSES (with pott)

ECHO SEND SIGNAL & TRIP AFTER TIME DELAY WHEN CB CLOSED …………

UNDER VOLTAGE SETTING VALUE =………….V

Page 24: Distance Relay Test

7SA522- Practical Ref. For Testing

24

MEASUREDUNDER VOLTAGE VALUE =………….V

Note:- WEAK INFEED = 2501=ECHO & TRIP ONLY WHEN CB CLOSE CB CLOSE BINARY =379, ECHO SENDS SIGNAL & TRIP AFTER TIME DELAY WHEN CB CLOSED. UNDER VOLTAGE CONDITIONS ARE SATISFIED.

CB CLOSES أن ى فيرالمقابلة المحطة إلى إشارة يرسل Z1B داخل بوجود عيبيحس * CBفيفصل ال

-: آما يليالخاصية فسوف نختبر هذه المرسلة المحطة إلى أيضا إشارةفيرسل

اقل منبشرط ان يكون الجهد وذلك سوف يفصل CR موصل نعطيه CB ال -1

(AD2505) ثم يرسل CS بعد زمن.

10 .SCHEME CHECK: E) BLOCKING SCHEME

فاز لماذا؟؟؟؟؟؟؟؟؟؟؟3لم يصدر فصل مع عيب : ملحوظة

SEND LOGIC CS = Z3 FAULT (REVERSE) :

TRIP LOGIC = Z1B FAULT+ NO CR : NO TRIP LOGIC = Z1B FAULT+ CR : Note:- LED 13 =SIGNAL SEND=4056, LED 14 =SIGNAL RECEIVE=4054,

Page 25: Distance Relay Test

7SA522- Practical Ref. For Testing

25

CARRIER RECEIVE BI = 4006, TRIP WITH TELE PROTECTION SCHEME = 3850 10. SCHEME CHECK:

F ) UNBLOCKING SCHEME SEND LOGIC CS = Z1B FAULT

TRIP LOGIC = Z1B FAULT+ CR 10. SCHEME CHECK:

G) DIRECT TRANSFER TRIP SEND LOGICCS = (Z1) FD FAULT→TRIP+CS : TRIPLOGIC TRIP = CR : Note:- ( CARRIER RECEIVE BINARY INPUT = 4417 ) TRIP OUTPUT = 4435, ALSO PUTT SCHEME TOBE SELECTED TO SEND SIGNAL IN ZONE - 1. SEND LOGIC CS= (Z1) FAULT→TRIP+CS : TRIPLOGIC CR = TRIP :

11. POWER SWING SCHME(AD0020)

At isa tester: Choose: - transit time 0.2, Z start= 40.55 Ohm, Zend=0.5Ohm. ok psw block and the led is on,now you have tested Z1 For Z2: Zend= 2.5,Z3:Zend =4.5, Z5:Zend=8.5( According to you settings!)

Page 26: Distance Relay Test

7SA522- Practical Ref. For Testing

26

if more rapid (t=0.175 for Z1 and 0.14 for Z5) the relay make trip after the time at AD2007 (trip delay after PS blocking) The max. limit is about:

If dZ/Sec>(-229) Ohm/sec, the relay trip (AD2002)ALL ZONE BLOCK ……………….. Z2 → Z5 BLOCK ……………….. OUT OF STEP TRIPPING ………………..

وهي قبل ) وهنا سيعمل تايمر PPOL (لجهد وسيدخل في ال انحقن تيار وجهد طبيعي ثم ننزل ب* هة من الجت خرجإذا أما. اوم ببطء سوف يعمل بلوكالخمسة ت بي خمسه اوم فلو قطعZ5ال

OUT OF STEP TRIPPING بي TRIP سيعملةالمعاآس ?????OUT OF STEP TRIPما عرفتش أعمل

12. FAULT LOCATOR CHECK SETTING:

X=…….0.1……..Ohms / Km: Line Length = …1…….. Km X injected Expected length Measured length

1 1KM 0.9 KM

Page 27: Distance Relay Test

7SA522- Practical Ref. For Testing

27

. بعد وضع الضبطXنحقن * 13. EXTERNAL START FOR FAULT RECORDER

FAULT RECORDER يشغل ال Biوهو عباره عن *