Page 1: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron Andersen, Deputy Director of Operations, National Center for Atmospheric Research(NCAR)

Page 2: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

“… to provide, or arrange for provision of facilities for the scientific community as a whole whose initial cost and upkeep lie beyond the capability of individual universities or research groups.”

Preliminary Plans for a National Institute for Atmospheric Research,

1959, NCAR Blue Book

NCAR’s Founding Mission

Page 3: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

History of Computing at NCAR

Exotic CoolingFreon R-22

Fluorinert

Water

Return of Liquid CoolingWater

Warm Water

FR3

Page 4: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

• Key to Optimum Performance (Three M’s)• Monitoring

• Measurement

• Maintenance

• Infrastructure Support Group – Cheyenne• Electricians

• Mechanics

• Building Automation Controls

• HVAC Technician

• Commissioning Agent• Measurement & Verification 12 months post completion

Page 5: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

Tuning the Facility – Student Interns

• Clair Christofersen - 2012• University of Miami Ohio

• BS Mechanical Engineering – Applied Math

• Air Flow Modeling (CFD Analysis)

• Jason Jones - 2012• Clemson University -> Georgia Tech

• BS Mechanical Engineering

• Air Flow, Water Flow and Total Energy

• Ademola Olarinde - 2013• Texas A&M Kingsville

• MS Mechanical Engineering

Page 6: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

65F (18.3 C) Degree Chilled Water

Evaporative Solution

Page 7: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

Liquid Cooling – ASHRAE 2011 Guidelines

121 hrs1.38%

8639 hrs98.62%

Page 8: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

Characterize Building Response

Page 9: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

• Saw an increase in mechanical consumption in winter months

• Energy Recovery Heat Pumps consuming way more electricity than expected

• Why do we care?• $5000 per month

• What is the root cause?

Mechanical Load in Winter

Page 10: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

• Heat Rejection from Yellowstone is too low 1.2MW vs. 4MW Design

• Significantly greater heating demand from the building during winter months

• Commissioning Agent identified the same problem and possible culprit, large Air Handling Units

Root Cause

Page 11: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

Why This Matters

Page 12: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

• UPS Efficiency• Only Critical Systems are Covered on UPS

• Disk• Network• AuthN/AuthZ• Login• Management

• Low load causes low efficiency

• Firmware upgrade moves UPS efficiency from 70% ~ 95%

• Maintenance really matters• Cleaning strainers improve pump energy by 20 KW

• More frequent maintenance than recommended

• Water Usage• Zero Blow down for Cooling Tower saving 40%

• Negotiated reduction in Sewer cost ~$2500/month

Other Issues

Page 13: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

PUE Trend Since Startup

Page 14: Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center

Aaron AndersenNov., 2013

PUE – One Year Aug 2012 – July 2013