InstallationandOperationManual

SLC 500� ModularHardware Style

(Cat. Nos. 1747-L511, 1747-L514,1747-L524, 1747-L531, 1747-L532,1747-L541, 1747-L542, 1747-L543,1747-L551, 1747-L552, and1747-L553)

Allen-Bradley

Page 4: Diagnostico SLC 500

Because of the variety of uses for the products described in thispublication, those responsible for the application and use of thiscontrol equipment must satisfy themselves that all necessary stepshave been taken to assure that each application and use meets allperformance and safety requirements, including any applicable laws,regulations, codes and standards.

The illustrations, charts, sample programs and layout examplesshown in this guide are intended solely for purposes of example.Since there are many variables and requirements associated with anyparticular installation, Allen-Bradley does not assume responsibilityor liability (to include intellectual property liability) for actual usebased upon the examples shown in this publication.

Allen-Bradley publication SGI-1.1, Safety Guidelines for theApplication, Installation, and Maintenance of Solid-State Control(available from your local Allen-Bradley office), describes someimportant differences between solid-state equipment andelectromechanical devices that should be taken into considerationwhen applying products such as those described in this publication.

Reproduction of the contents of this copyrighted publication, inwhole or in part, without written permission of Allen-BradleyCompany, Inc., is prohibited.

Throughout this manual we use notes to make you aware of safetyconsiderations:

!ATTENTION: Identifies information about practicesor circumstances that can lead to personal injury ordeath, property damage or economic loss.

Attention statements help you to:

• identify a hazard

• avoid the hazard

• recognize the consequences

Important: Identifies information that is critical for successfulapplication and understanding of the product.

PLC, PLC–2, PLC–3, and PLC–5 are registered trademarks of Rockwell Automation. SLC, SLC 500, SLC 5/01, SLC 5/02, SLC 5/03, SLC 5/04, SLC5/05, PanelView, PanelView 550, PanelView 900, RediPANEL, ControlView, PBASE, DH+, DTAM, DeviceNet, and Dataliner are trademarks ofRockwell Automation. RSLogix 500 and RSLinx are trademarks of Rockwell Software, Inc. Ethernet is a registered trademark of Digital EquipmentCorporation, Intel, and Xerox Corporation. IBM is a registered trademark of International Business Machines, Incorporated. Multimodem is atrademark of Multi–Tech Systems, Inc. Procomm is a registered trademark of Datastorm Technologies, Inc. Tandy is a trademark of the TandyCorporation. Gateway 2000 is a trademark of Gateway 2000, Inc. Toshiba is a trademark of Toshiba America, Inc. Compaq is a registered trademarkof Compaq Computer Corporation. Deskpro is a trademark of Compaq Computer Corporation. Intel is a trademark of Intel Corporation.

Important UserInformation

Page 5: Diagnostico SLC 500

6–8 Installing Your Hardware Components

Publication 1747-6.2

If you have multiple chassis configurations, install the chassisinterconnect cable before installing the power supply. (See page 6–10.) Also, the power supply terminals accept two #14AWG wires and are marked as shown in the figure on page 6–8. Toinstall the power supply, do the following:

1. Align the circuit board with the card guide on the left side of thechassis. Slide the power supply in until flush with the chassis.

19524

2. Fasten the power supply to the chassis with the two Phillips headscrews.

3. Place the jumper to match the input voltage. (This does not applyto 1746-P3 or 1746-P5, which do not have a jumper.)

!ATTENTION: Make jumper selection beforeapplying power. Hazardous voltage is present onexposed pins when power is applied.

Installing Your PowerSupply

Page 6: Diagnostico SLC 500

6–9Installing Your Hardware Components

Publication 1747-6.2

POWER

Fuse

POWER

100/120 Volts

200/240 Volts

Fuse

85–132V ac

170–265V ac

JumperSelection

JumperSelection

POWER POWER

120/240V ac

V ac NEUT

CHASSIS GROUND

dc NEUT

+ 24V dc

CHASSIS GROUND

JUMPER

170–265V ac

L2 NEUTRAL

L185–132/170–265

85–132V ac

CHASSIS GROUND

+125V dc

dc NEUT

CHASSIS GROUNDCHASSIS GROUND

PWR OUT COM

PWR OUT COM

PWR OUT +24V dc

PWR OUT +24V dc

PWR OUT +24V dc

PWR OUT COMMON

NOT USED

NOT USED

UserPower

UserPower

UserPower

1746-P1 and -P2

1746-P4 1746-P5

1746-P3

4. Remove the warning label from the top of the power supply.

5. Connect line power to the power supply.

!ATTENTION: If you have a 1746-P3, see page 3–5for special grounding considerations.

On the 1746-P1 and -P2 power supply, use the PWR OUT + 24 VDCand PWR OUT COM terminals to power sensors. The terminalsprovide an isolated, nonfused, 200 mA, 24V dc power supply.

Page 7: Diagnostico SLC 500

6–10 Installing Your Hardware Components

Publication 1747-6.2

Two cables are available to link modular hardware chassis. CatalogNumber 1746-C7 cable is 152.4 mm (6 in.) in length and used whenconnecting chassis side-by-side. Catalog Number 1746-C9 is 914.4 mm (36 in.) in length and used to link one chassis below theother.

!ATTENTION: Do not use any other cables than thoseprovided. Longer cables could affect the integrity ofdata communications between the chassis, possiblycausing unsafe operation. Also, make sure the cable isproperly secured to protect against the effects of shockand vibration.

Install the chassis interconnect cable before installing the powersupply in multiple chassis configurations.

The cables are “keyed” for proper installation. The end of the cablethat plugs into the right socket in the chassis has the “key” on the topof the connector. The opposite end of the cable has the “key” on theinside of the connector for insertion into the expansion chassis.

To remove the cable, move the tabs on the socket outward and theconnector pops out.

!ATTENTION: The expansion cable must always exitthe right end of the chassis with the processor. Refer tothe following figures.

CPU

Chassis 1

Chassis 2CORRECT INSTALLATION

CPU

Chassis 1

Chassis 2INCORRECT INSTALLATION

CPU

Chassis 1

Chassis 2INCORRECT INSTALLATION

Chassis 1

Chassis 2INCORRECT INSTALLATION

PS

PS

PS

PS

PS

PS

PS

PS

CPU

Installing Your ChassisInterconnect Cable

Page 8: Diagnostico SLC 500

���������

Publication 1747-6.2

�������������� �����

This chapter describes how to wire your I/O modules. It covers thefollowing:

• defining sinking and sourcing

• preparing your wiring layout

• features of an I/O module

• recommendations for wiring I/O devices

• wiring your I/O modules

• octal label kit installation

• using removable terminal blocks

Sinking and sourcing are terms used to describe a current signal flowrelationship between field input and output devices in a controlsystem and their power supply.

• Field devices connected to the positive side (+V) of the fieldpower supply are sourcing field devices.

• Field devices connected to the negative side (DC Common) of thefield power supply are called sinking field devices.

To maintain electrical compatibility between field devices and theprogrammable controller system, this definition is extended to theinput/output circuits on the discrete I/O modules.

• Sourcing I/O circuits supply (source) current to sinking fielddevices.

• Sinking I/O circuits receive (sink) current from sourcing fielddevices.

Europe: DC sinking input and sourcing output module circuits arethe commonly used options.

Defining Sinking andSourcing

Page 9: Diagnostico SLC 500

����������

Publication 1747-6.2

��������������

In this chapter, you will learn about:

• calling Allen-Bradley for assistance

• tips for troubleshooting your control system

• troubleshooting the SLC 5/01 and SLC 5/02 processors

• troubleshooting the SLC 5/03, SLC 5/04, and SLC 5/05processors

• troubleshooting your input modules

• troubleshooting your output modules

If you need to contact Allen-Bradley or local distributor forassistance, it is helpful to obtain the following (prior to calling):

• processor type, series letter, operating system (OS) number(obtained from the status file), firmware (FRN) number (see labelon side of processor module)

• processor LED status

• processor error codes (found in S:6 of status file)

• hardware types in system (I/O modules, chassis)

• revision of programming device (on the main menu of theHand-Held Terminal or programming software)

Calling Allen-Bradley forAssistance

Page 10: Diagnostico SLC 500

10–2 Troubleshooting

Publication 1747-6.2

When troubleshooting, pay careful attention to these generalwarnings:

!ATTENTION: Have all personnel remain clear of thecontroller and equipment when power is applied. Theproblem may be intermittent and sudden unexpectedmachine motion could result in injury. Have someoneready to operate an emergency-stop switch in case itbecomes necessary to shut off power to the controllerequipment. Also, see NFPA 70E Part II for additionalguidelines for safety related work practices.

Never reach into a machine to actuate a switch sinceunexpected machine motion can occur and causeinjury.

Remove all electrical power at the main powerdisconnect switches before checking electricalconnections or inputs/outputs causing machine motion.

If installation and start-up procedures detailed in chapters 6, 7, and 8were followed closely, your SLC controller will give you reliableservice. If a problem should occur, the first step in thetroubleshooting procedure is to identify the problem and its source.

The SLC 500 controller has been designed to simplifytroubleshooting procedures. By observing the diagnostic indicatorson the front of the power supply, processor unit and I/O modules, themajority of faults can be located and corrected. These indicators,along with error codes identified in the programming device usermanual and programmer’s monitor, help trace the source of the faultto the user’s input/output devices, wiring, or the controller.

Removing Power

Before working on a SLC 500 modular system, always remove thepower supply input power at the main power disconnect switch.

The power LED on the power supply indicates that DC power isbeing supplied to the chassis. The LED could be off when incomingpower is present.

Tips for TroubleshootingYour Control System

Page 11: Diagnostico SLC 500

10–3Troubleshooting

Publication 1747-6.2

Replacing Fuses

When replacing a fuse, be sure to remove all power from the system.

Program Alteration

There are several causes of alteration to the user program, includingextreme environmental conditions, Electromagnetic Interference(EMI), improper grounding, improper wiring connections, andunauthorized tampering. If you suspect the memory has beenaltered, check the program against a previously saved program on anEEPROM, UVPROM or Flash EPROM module.

To receive the maximum benefit of this troubleshooting section, werecommend you follow these steps:

1. Identify the status of your processor LEDs. See chapter 5 for adescription of LEDs and their different states.

2. Using the tables on the following pages, match your processorand power supply LEDs with the status LEDs located in the firstcolumn.

3. Once the status LEDs are matched to the appropriate table,simply move across the table identifying error description andprobable causes.

4. Follow the recommended action steps for each probable causeuntil the error is corrected.

5. If recommended actions do not correct the error, contact yourlocal Allen-Bradley sales office or distributor.

Troubleshooting the SLC5/01 and SLC 5/02Processors

Page 12: Diagnostico SLC 500

10–4 Troubleshooting

Publication 1747-6.2

Identifying SLC 5/01 and SLC 5/02 Processor Errors

The following LEDs and tables provide you with informationregarding error messages, possible cause(s) for the error, andrecommended action to take to resolve the error.

The FollowingError Exists

Probable Cause Recommended Action

No Line Power

1. Verify proper line voltage and connections on thepower terminals.2. Verify proper 120/240V power supply jumperselection. See page 6–8.

Power SupplyFuse Blown

1. Check the incoming power fuse, check for properincoming power connections. Replace fuse.2. If fuse blows again, replace the power supply. Seepage 9–8 on fuse replacement.

InadequateSystem Power

Power SupplyOverloaded

1. Remove line power to power supply. Removeseveral output modules from the chassis. Wait fiveminutes. Reapply power.2. If condition reoccurs, re-calculate moduleconfiguration power required and verify proper powersupply selection. See page 2–11.This problem can occur intermittently if power supply isslightly overloaded when output loading andtemperature varies.

Defective PowerSupply

1. Recheck other probable causes.2. Monitor the line power to chassis power supply forpossible transient or shorting.3. Replace the power supply.

The FollowingError Exists

Probable Cause Recommended Action

InadequateSystem Power

Improper LinePower VoltageSelection

Verify proper 120/240V power supply jumper selection.See page 6–8.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The RUN LED on the SLC 5/01 processor is actuallylabeled “PC RUN.” Also, the SLC 5/01 processor doesnot have a COMM LED.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

Page 13: Diagnostico SLC 500

10–5Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

Either ImproperMode Selected orUser ProgramLogic Error

1. Verify selected processor mode.2. If in program/test modes attempt Run mode entry.3. If in suspend mode, check user program logic forsuspend instructions.Refer to either the Hand-Held Terminal User Manual(Catalog Number 1747-NP002) or your programmingsoftware user manual.

Line Power Out ofOperating Range

1. Check proper 120/240V power supply jumperselection and incoming power connections.2. Monitor for proper line voltage at the incomingpower connections.See page 6–8 for power supply installation.

Processor Not inRun Mode Improper Seating

of Power Supply,and/or Processorin the Chassis

1. Remove power and inspect the power supplychassis connections and the processor chassisconnections.2. Re-install the devices and re-apply power.Important: The processor only operates in slot 0 ofchassis #1.

DefectiveProcessor, PowerSupply or Chassis

1. Attempt Run mode selection of Processor inexisting chassis.2. Place processor in another chassis not in theexisting system. Apply power, reconfigure and attemptRun mode selection. If unsuccessful, replaceprocessor.3. Try existing power supply in test chassis. Ifunsuccessful, replace power supply. If entry into theRun mode is allowed, replace the existing chassis.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The RUN LED on the SLC 5/01 processor isactually labeled “PC RUN.” Also, the SLC 5/01 processor does not have a COMMLED.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

Page 14: Diagnostico SLC 500

10–6 Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

SystemInoperable,No Major CPU

ault t ct

User ProgramLogic Error

1. Monitor logic in Run mode and verify desired I/Ostatus.2. Check for minor CPU faults.Refer to either the Hand-Held Terminal User Manual(Catalog Number 1747-NP002) or your programmingsoftware user manual

Faults DetectedDefective I/ODevices or I/OWiring

Test inputs and outputs according to I/O troubleshootingprocedures starting on page 10–26.

The FollowingError Exists

Probable Cause Recommended Action

CPU MemoryError

Cycle power.

PU ault

Faulty MemoryModule

1. Remove power and then remove the memory modulefrom the processor.2. Re-install the processor and re-apply power to thepower supplyIf steady CPU FAULT LED changes to flashing, replace theexisting memory module with a replacement module.

Refer to chapter 6 for removing and installing memorymodules.

CPU Fault

Faulty CPU/PowerSupply

1. Place the processor in another chassis not in theexisting system and cycle power.If steady CPU FAULT LED reappears, replace theprocessor.2. If CPU FAULT LED clears, monitor the line powergoing to the power supply in existing system.3. Replace existing system power supply if line power

checks OK.

ProcessorFirmware InstalledIncorrectly

If upgrading the processor to a different firmware level,verify firmware chip orientation matches the upgrade kitdirections.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The RUN LED on the SLC 5/01 processor isactually labeled “PC RUN.” Also, the SLC 5/01 processor does not have a COMMLED.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

Page 15: Diagnostico SLC 500

10–7Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

Initial CPU FactoryPower-upCondition

1. Refer to chapter 8 and follow the start-up procedures.2. Clear processor memory to get rid of the flashing CPUFAULT LED.

CPU MajorFault

Hardware/SoftwareMajor FaultDetected

Erratic repetitivepower cycling cancause a processormajor hardwarefault.

1. Monitor Status File Word S:6 for major error code.2. Refer to either the Hand-Held Terminal User Manual(Catalog Number 1747-NP002) or the Instruction SetReference Manual for error codes and additionaltroubleshooting information.3. Remove hardware/software condition causing fault.4. Clear Status File S:1/13 major error bits, if set.5. Clear Status File S:5 minor error bits, if set.6. Clear Status File S:6 major error code (optional).7. Attempt a processor Run mode entry.If unsuccessful, repeat recommended action steps above.

The FollowingError Exists

Probable Cause Recommended Action

System doesnot operate perladder logic.

User Forced I/ODisablingOperation

1. Monitor program file online and identify forced I/O.2. Disable appropriate forces and test system conditionsagain.Refer to either the Hand-Held Terminal User Manual(Catalog Number 1747-NP002) or your programmingsoftware user manual.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The RUN LED on the SLC 5/01 processor isactually labeled “PC RUN.” Also, the SLC 5/01 processor does not have a COMMLED.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

Page 16: Diagnostico SLC 500

10–8 Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

System doesnot operate perprogrammedforces.

User ProgrammedForces are NotEnabled

1. Monitor program file online and identify programmedforces.2. Enable appropriate forces and test system conditionsagain. Once forces are enabled, the FORCED I/O LEDgoes on steady.Refer to either the Hand-Held Terminal User Manual(Catalog Number 1747-NP002) or your programmingsoftware user manual.

The FollowingError Exists

Probable Cause Recommended Action

CPU MajorError with Lowor No BatteryBack-up

Loss of RAMduring PowerDown Period

1. Verify battery is connected. See pages 6–1 and 9–4.2. Replace the battery if you want RAM battery backup.See page 9–4. If you want to back up RAM with thecapacitor in a SLC 5/01 (1747-L511), add or replace theBATTERY LOW LED jumper.3. Refer to processor major fault recommended actionsteps.Refer to either the Hand-Held Terminal User Manual(Catalog Number 1747-NP002) or your programmingsoftware user manual.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The RUN LED on the SLC 5/01 processor isactually labeled “PC RUN.” Also, the SLC 5/01 processor does not have a COMMLED.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

Page 17: Diagnostico SLC 500

10–9Troubleshooting

Publication 1747-6.2

Identifying SLC 5/02 Processor Communication Errors

The FollowingError Exists

Probable Cause Recommended Action

The SLC 5/02processor is notreceiving data.

DH-485communicationparameters areimproperly set up.

1. Check communication parameters of programmer.Programmer and processor baud rate must match.Programmer and processor node addresses must bedifferent.2. Try different combinations of:a. baud rate (Processor default is 19200.)b. node address (Processor default is 1.)3. Try to increase the maximum node address. (Defaultis 31.)

receiving data.Nocommunicationto theprogrammer.

Bad Connection ofCommunicationDevice

1. Check cable continuity.2. Check cable connections between programmer andprocessor.3. Check communication device (for example, the1747-PIC). Replace if necessary.

Low or No Powerto CommunicationDevice

1. Verify proper power supply selection and backplaneloading. (1747-PIC and 1747-AIC draw power off thebackplane.)2. Verify proper 120/240V power supply jumper selection.See page 6–8.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The RUN LED on the SLC 5/01 processor isactually labeled “PC RUN.” Also, the SLC 5/01 processor does not have a COMMLED.

Indicates the LED is FLASHING.

Status of LED does not matter.

ÉÉÉÉ

Indicates the LED is FLASHING or OFF.

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

ÉÉÉÉ

COMM

If the LEDs indicate:➀

Page 18: Diagnostico SLC 500

10–10 Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

The SLC 5/02processor isreceiving data,but is notcommunicatingwith theprogrammer.

DH-485communicationparameters areimproperly set up.

1. Check communication parameters of programmer.Programmer and processor baud rate must match.Programmer and processor node addresses must bedifferent.2. Try different combinations of:a. baud rate (Processor default is 19200.)b. node address (Processor default is 1.)3. Try to increase the maximum node address. (Defaultis 31.)

The FollowingError Exists

Probable Cause Recommended Action

A fatal error hasoccurred.

Excessive noise ora faulty SLC 5/02processor.

1. Cycle power to obtain flashing CPU FAULT LED anddefault program.2. Examine the error code following the power cycle.Take appropriate action.3. Reload your program.4. Contact your local Allen-Bradley representative if theerror persists.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The RUN LED on the SLC 5/01 processor isactually labeled “PC RUN.” Also, the SLC 5/01 processor does not have a COMMLED.

Indicates the LED is FLASHING.

Status of LED does not matter.

ÉÉÉÉ

Indicates the LED is FLASHING or OFF.

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

ÉÉCOMM

If the LEDs indicate:➀

POWER RUN

CPU FAULT

FORCED I/O

BATTERY LOW

COMM

If the LEDs indicate:➀

Page 19: Diagnostico SLC 500

10–11Troubleshooting

Publication 1747-6.2

Between the time you apply power to an SLC 5/03, SLC 5/04, orSLC 5/05 processor and the communications are established via aconnected programming device, the only form of communicationbetween you and the processor is through the LED display.

When power is applied, all of the LEDs flash on and then off whilethe processor conducts hardware tests. This is part of the normalpowerup sequence. Following the selftest by the processor, all theLEDs again flash on momentarily. If a user program is in a runningstate, the RUN LED will be on. If a fault exists within the processor,the FLT LED is on.

To receive the maximum benefit of this troubleshooting section, werecommend you follow these steps:

1. Identify the status of your processor LEDs. See chapter 5 fordescription of LEDs and their different states.

2. Using the tables on the following pages, match your processorand power supply LEDs with the status LEDs located in the firstcolumn.

3. Once the status LEDs are matched to the appropriate table,simply move across the table identifying error description andprobable causes.

4. Then follow the recommended action steps for each probablecause until the cause is identified.

5. If recommended actions do not identify the trouble cause, contactyour local Allen-Bradley sales office or distributor.

Clearing SLC 5/03, SLC 5/04, and SLC 5/05 Processor FaultsUsing the Keyswitch

Toggle the keyswitch from RUN to PROG and then back to RUN;this clears the fault. If the keyswitch is left in the RUN position, theprocessor mode cannot be changed from a programmer/operatorinterface device. If you return the keyswitch to the REM position,you can then use a programmer/operator interface device to changethe processor mode.

!ATTENTION: If you clear a processor fault using thekeyswitch, the processor immediately enters the Runmode.

Troubleshooting theSLC 5/03, SLC 5/04, andSLC 5/05 Processors

Page 20: Diagnostico SLC 500

10–12 Troubleshooting

Publication 1747-6.2

Identifying SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors

The following LEDs and tables provide you with informationregarding error messages, possible cause(s) for the error, andrecommended action to take to resolve the error.

The FollowingError Exists

Probable Cause Recommended Action

No Line Power

1. Verify proper line voltage and connections on thepower terminals.2. Verify proper 120/240V power supply jumperselection. See page 6–8.

Power SupplyFuse Blown

1. Check the incoming power fuse, check for properincoming power connections. Replace fuse.2. If fuse blows again, replace the power supply. Seepage 9–8 on fuse replacement.

InadequateSystem Power

Power SupplyOverloaded

1. Remove line power to power supply. Removeseveral output modules from the chassis. Wait fiveminutes. Reapply power.2. If condition reoccurs, re-calculate moduleconfiguration power required and verify proper powersupply selection. See page 2–11.This problem can occur intermittently if power supply isoverloaded when output loading and temperaturevaries.

Defective PowerSupply

1. Recheck other probable causes.2. Monitor the line power to chassis power supply forpossible transient or shorting.3. Replace the power supply.

The FollowingError Exists

Probable Cause Recommended Action

InadequateSystem Power

Improper LinePower VoltageSelection

Verify proper 120/240V power supply jumper selection.See page 6–8.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

Page 21: Diagnostico SLC 500

10–13Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

Either ImproperMode Selected orUser ProgramLogic

1. Verify selected processor mode.2. If the processor is in the Program/Test modes,attempt Run mode entry:• If keyswitch is in the REM position and

there is no key, use the programmer.• If keyswitch is in REM or PROG position,

and you have the key, toggle to the RUN position.

3. If in the suspend mode, check user program logicfor suspend instructions.Refer to your programming software user manual.

Line Power Out ofOperating Range

1. Check proper 120/240V power supply jumperselection and incoming power connections.2. Monitor for proper line voltage at the incomingpower connections.See page 6–8 for power supply installation.

Processor Not inRun Mode Improper Seating

of Power Supply,and/or Processorin the Chassis

1. Remove power and inspect the power supplychassis connections and the processor chassisconnections.2. Re-install the devices and re-apply power.Important: The processor only operates in slot 0 ofchassis #1.

DefectiveProcessor, PowerSupply, or Chassis

1. Attempt Run mode selection of Processor inexisting chassis:• If keyswitch is in the REM position and there is

no key, use the programmer.• If keyswitch is in REM or PROG position, and you have the key, toggle to the RUN position.2. Place processor in another chassis not in theexisting system. Apply power, reconfigure and attemptRun mode selection. If unsuccessful, replaceprocessor.3. Try existing power supply in test chassis. Ifunsuccessful, replace power supply. If entry into theRun mode is allowed, replace the existing chassis.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

Page 22: Diagnostico SLC 500

10–14 Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

SystemInoperable,No a o PU

User ProgramLogic Error

1. Monitor logic in Run mode and verify desired I/Ostatus.2. Check for minor CPU faults.Refer to your programming software user manual.

No Major CPUFaults Detected Defective I/O

Devices or I/OWiring

Test inputs and outputs according to I/O troubleshootingprocedures starting on page 10–26.

The FollowingError Exists

Probable Cause Recommended Action

CPU MemoryError

Cycle power.

CPU Fault

Faulty MemoryModule

1. Remove power and then remove the memory modulefrom the processor.2. Re-install the processor and re-apply power to thepower supply.If steady FLT LED changes to flashing, replace the existingmemory module with a replacement module.

Refer to chapter 6 for removing and installing memorymodules.CPU Fault

Faulty CPU/PowerSupply

1. Place the processor in another chassis not in theexisting system and cycle power. If steady FLT LEDreappears, replace the processor.2. If FLT LED clears, monitor the line power going to thepower supply in existing system.3. Replace existing system power supply if line powerchecks OK.

ProcessorFirmware InstalledIncorrectly

If upgrading the processor to a different firmware level,verify firmware chip orientation matches the upgrade kitdirections.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

Page 23: Diagnostico SLC 500

10–15Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

Initial CPU FactoryPower-upCondition in Effect

1. Refer to chapter 8 and follow the start-up procedures.2. Clear processor memory to get rid of the flashing FLTLED.

CPU MajorFault

Hardware/Software MajorFault Detected

Erratic repetitivepower cycling cancause a CPUmajor hardwarefault.

1. Use programmer to monitor and clear the fault (or ifkeyswitch in REM):a. Monitor Status File Word S:6 for major error code.b. Refer to your programming software user manual forerror codes and additional troubleshooting information.c. Remove hardware/software condition causing fault.d. Clear Status File S:1/13 major error bits, if set.e. Clear Status File S:5 minor error bits, if set.f. Clear Status File S:6 major error code (optional).g. Attempt a processor Run mode entry.If unsuccessful, repeat recommended action steps above.2. Use the keyswitch to clear the fault. Toggle thekeyswitch to PROG and back to RUN. (See page 10–11.)If FAULT occurs again, use programmer to get error codeand determine the source of problem.

The FollowingError Exists

Probable Cause Recommended Action

System doesnot operate perladder logic.

User Forced I/ODisablingOperation

1. Monitor program file online and identify forced I/O.2. Disable appropriate forces and test system conditionsagain.Refer to your programming software user manual.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

Page 24: Diagnostico SLC 500

10–16 Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

System doesnot operate perprogrammedforces.

User programmedforces are notenabled.

1. Monitor program file online and identify programmedforces.2. Enable appropriate forces and test system conditionsagain. Once forces are enabled, the FORCE LED goes onsteady.Refer to your programming software user manual.

The FollowingError Exists

Probable Cause Recommended Action

CPU MajorError with Lowor No BatteryBack-up

Loss of RAMduring PowerDown Period

1. Verify battery is connected. See pages 6–1 and 9–5.2. Replace the battery if you want RAM battery backup.See page 9–5.3. Refer to processor major fault recommended actionsteps.Refer to your programming software user manual.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀

Page 25: Diagnostico SLC 500

10–17Troubleshooting

Publication 1747-6.2

Identifying SLC 5/03, SLC 5/04, and SLC 5/05 ProcessorCommunication Errors

The FollowingError Exists

Probable Cause Recommended Action

InadequateSystem Power

1. Check line power.2. Check 120/240V power supply jumper selection. Seepage 6–8. Also, see the recommended actions forinadequate system power on page 10–12.

Fatal Error andNoCommunication

Communicationchannel is “shutdown.”

Check communication channel configuration with yourprogramming software. Also, see “Returning the SLC 5/03,SLC 5/04, and SLC 5/05 Processors to ‘Initial FactoryConditions’” on page 10–25.

Communicationchannel isdamaged.

Replace processor.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.ÉÉ Indicates the LED is FLASHING or OFF.

POWER RUN

FLT

BATT

ÉÉ

FORCE

DH485

RS232

If the LEDs indicate:➀

Page 26: Diagnostico SLC 500

10–18 Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

The SLC 5/03and SLC 5/04processors aretrying toestablishcommunication,but cannot findot acti

DH-485 or DH+communicationparameters areimproperly set up.

1. Check communication parameters of programmer.Programmer and processor baud rate must match.Programmer and processor node addresses must bedifferent.2. Try different combinations of:a. baud rate (Processor default is 19.2K for DH-485 onthe SLC 5/03, and 57.6K for DH+ on the SLC 5/04.)b. node address (Processor default is 1.)3. Try to increase the maximum node address. (Defaultis 31 for the SLC 5/03 processor only.)See your programming software user manual for channelconfiguration information.

other activenodes. (TheLED is flashinggreen on theSLC 5/03 andSLC 5/04.)

Bad Connection ofCommunicationDevice

1. Check cable continuity.2. Check cable connections between programmer andprocessor.3. Check communication device (for example, the1747-PIC). Replace if necessary.

SLC 5/04.)

Low or No Powerto CommunicationDevice

1. Verify proper power supply selection and backplaneloading. (The 1747-PIC and 1747-AIC draw power off thebackplane.)2. Verify proper 120/240V power supply jumper selection.See page 6–8.

Duplicate dropis detected.(The LED isflashing red onthe SLC 5/04.)

Another DH+device is alreadyon the DH+network at thenode address ofthis same device.

1. Remove this device from the DH+ network.2. Cycle power.3. Reset the node address to an unused node beforereconnecting device to the DH+ network. (Can performreset if on-line via channel 0 RS-232 port withoutdisconnecting from DH+.)

An ENET fault isbeing reportedvia a code.(The LED isflashing red onthe SLC 5/05.)

A hardware orsoftware fault hasoccured.

Contact Allen-Bradley Global Technical Services forassistance.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.

ÉÉÉÉ

Indicates the LED is FLASHING or OFF.

POWER RUN

FLT

BATTÉ

FORCE

DH485

RS232

If the LEDs indicate:➀

Page 27: Diagnostico SLC 500

10–19Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

InadequateSystem Power

1. Check line power.2. Check 120/240V power supply jumper selection. Seepage 6–8. Also, see the recommended action forInadequate System Power on page 10–12.

Fatal Error andNo

o unication

Communicationchannel is “shutdown.”

Check communication channel configuration with yourprogramming software. Also, see “Returning the SLC 5/03,SLC 5/04, and SLC 5/05 Processors to ‘Initial FactoryConditions’” on page 10–25.

CommunicationCommunicationchannel isdamaged.

Replace processor.

Channelconfigured forDF1.

See your programming software user manual for channelconfiguration information.

The FollowingError Exists

Probable Cause Recommended Action

The SLC 5/03,SLC 5/04, orSLC 5/05processor istrying toestablishco unication

DH-485communicationparameters areimproperly set up.

1. Check communication parameters of programmer.Programmer and processor baud rate must match.Programmer and processor node addresses must bedifferent.2. Try different combinations of:a. baud rate (Processor default is 19200.)b. node address (Processor default is 1.)3. Try to increase the maximum node address. (Defaultis 31.)See your programming software user manual for channelconfiguration information.

communication,but cannot findother activenodes.

Bad Connection1. Check cable continuity.2. Check cable connections between programmer andprocessor.

nodes.

Low or No Powerto CommunicationDevice

1. Verify proper power supply selection and backplaneloading. (The 1747-PIC and 1747-AIC draw power off thebackplane.)2. Verify proper 120/240V power supply jumper selection.See page 6–8.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.

ÉÉÉÉ

Indicates the LED is FLASHING or OFF.

POWER RUN

FLT

BATT

ÉFORCE

DH485

RS232

If the RS232 Channelis in DH485 Modeand the LEDsindicate:➀

If the RS232 Channelis in DH485 Modeand the LEDsindicate:➀

POWER RUN

FLT

BATTÉ

FORCE

DH485

RS232

Page 28: Diagnostico SLC 500

10–20 Troubleshooting

Publication 1747-6.2

The FollowingError Exists

Probable Cause Recommended Action

Channel isconfigured forDH485 mode.

Check communication parameters of channelconfiguration. Also, see your programming software usermanual.

The SLC 5/03,SLC 5/04, or RS232/DF1

a a t

Check communication parameters of programmer andchannel configuration:a. baud rateb. DF1 node addresses (Processor default is 1 for DF1half-duplex, and 9 for DF1 full-duplex.)c. o c ckinSLC 5/05

processor is nottransmitting.

parametersimproperly set up.

c. error checkingd. number of data bitsProgrammer and processor baud rate must match.Programmer and processor addresses must be different.

See your programming software user manual.

Hardware Problem1. Check cable connections.2. Check cable pinouts. Also, see appendix B forRS-232 pinouts.

The FollowingError Exists

Probable Cause Recommended Action

A fatal error hasoccurred.

Excessive noise ora faulty SLC 5/03,SLC 5/04, orSLC 5/05processor.

1. Cycle power to obtain flashing FLT LED and defaultprogram.2. Examine the error code following the power cycle.Take appropriate action.3. Reload your program.4. Contact your local Allen-Bradley representative if theerror persists.

Refer to the following key to determine the status ofthe LED indicators:

Indicates the LED is OFF.

Indicates the LED is ON.

➀ The DH485 LED on the SLC 5/03 processor is labeled DH+ onthe SLC 5/04 processor, and ENET on the SLC 5/05 processor.

Indicates the LED is FLASHING.

Status of LED does not matter.

ÉÉÉÉ

Indicates the LED is FLASHING or OFF.

If the RS232 Channelis in DH485 Modeand the LEDsindicate:➀

POWER RUN

FLT

BATT

ÉFORCE

DH485

RS232

POWER RUN

FLT

BATT

FORCE

DH485

RS232

If the LEDs indicate:➀