218
Technical Data 1756 ControlLogix I/O Specifications Catalog Numbers 1756 series The ControlLogix® architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer-Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers. Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately. Additional Resources These documents contain additional information concerning related products from Rockwell Automation. You can view or download publications at http://www.rockwellautomation.com/literature/ . To order paper copies of technical documentation, contact your local Allen-Bradley® distributor or Rockwell Automation sales representative. Topic Page Additional Resources 1 Available 1756 I/O Modules 2 ControlLogix I/O Accessories 214 Resource Description Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.

Entrada Digital 125 vdc slc-500

Embed Size (px)

Citation preview

Technical Data

1756 ControlLogix I/O SpecificationsCatalog Numbers 1756 seriesTopic Additional Resources Available 1756 I/O Modules ControlLogix I/O Accessories Page 1 2 214

The ControlLogix architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer-Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers. Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.

Additional ResourcesThese documents contain additional information concerning related products from Rockwell Automation.Resource Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http://www.ab.com Description Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

1756 ControlLogix I/O Specifications

Available 1756 I/O ModulesYou can select these types of digital I/O modules.Digital I/O Type Diagnostic Electronic fusing Individually isolated Description These modules provide diagnostic features to the point level. These modules have a D at the end of the catalog number. These modules have internal electronic fusing to prevent too much current from flowing through the module. These modules have an E at the end of the catalog number. These modules have individually isolated inputs or outputs. These modules have an I at the end of the catalog number.

I/O Type AC digital

Cat. No. 1756-IA8D 1756-IA16 1756-IA16I 1756-IA32 1756-IM16I 1756-IN16 1756-IB16 1756-IB16D 1756-IB16I 1756-IB16IF 1756-IB16IOSE 1756-IB32 1756-IC16 1756-IG16 1756-IH16I 1756-IH16ISOE 1756-IV16 1756-IV32 1756-OB8 1756-OB8EI

Page 3 6 9 12 75 78 15 18 21 25 28 31 34 66 69 72 94 97 117 121

Cat. No. 1756-LSC8XIB8I 1756-OA8D 1756-OA8E 1756-OA16 1756-OA16I 1756-ON8 1756-OB8I 1756-OB16D 1756-OB16E 1756-OB16I 1756-OB16IEF 1756-OB16IS 1756-OB32 1756-OC8 1756-OG16 1756-OH8I 1756-OV16E 1756-OV32E

Page 205 103 106 109 113 178 125 128 132 135 138 142 146 150 172 175 182 186

DC digital

Contact Analog 1756-IF6CIS 1756-IF6I 1756-IF8 1756-IF16 1756-IF4FXOF2F 1756-IR6I 1756-IT6I 1756-IT6I2 1756-IF8H 1756-IF16H 1756-CFM 1756-HSC 38 42 47 55 62 81 86 90 51 59 196 201

1756-OW16I 1756-OX8I 1756-OF4 1756-OF6CI 1756-OF6VI 1756-OF8

190 193 154 158 161 165

HART interface Specialty

1756-OF8H 1756-LSC8XIB8I 1756-PLS

168 205 209

2

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

1756-IA8DControlLogix AC (79132V) diagnostic input moduleSimplified Schematic +5VNot Used Daisy Chain to Other RTBs 1756-IA8D2 4 1

L1-0 Loss of Field Power3

Input Display GND+5V ControlLogix Backplane Interface

L2-06 5

IN-0 IN-18 7

L2-0 Group 0 L2-010 9

IN-2 IN-312 11

Group 0

Open Wire Display GND ControlLogix Backplane InterfaceGroup 1

L2-0 L2-114 13

47 k, 1/2 W 5% Resistor

IN-4 IN-516 15

L2-1 L2-118 17

IN-6 IN-720 19

Group 1

47 k, 1/2 W, 5% Resistor

L2-1

AC INPUTST 0 1 2 3 4 5 6 7 O FL 0 1 2 3 4 5 6 7 K T

L2-1 L2 L1

L1-1 Loss of Field Power

DIAG STIC NO

Table 1 - Diagnostic Specifications - 1756-IA8DAttribute Open wire Loss of power Timestamp of diagnostics 1756-IA8D Off-state leakage current 1.5 mA min Transition range 4685V AC 1 ms

Table 2 - Technical Specifications - 1756-IA8DAttribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max 1756-IA8D 8 diagnostic (4 points/group) 120V AC 79132V AC, 4763 Hz 120V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 3 mA 0.58 W 4.5 W @ 60 C (140 F)

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

3

1756 ControlLogix I/O Specifications

Table 2 - Technical Specifications - 1756-IA8D (continued)Attribute Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IA8D 15.35 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 16 mA @ 132V AC 250 mA 8.25 k @ 132V AC, 60 Hz 200 s750 ms Software configurable 200 s 125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4A None (open-style)

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 3 - Environmental Specifications - 1756-IA8DAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions 1756-IA8D 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A

4

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 3 - Environmental Specifications - 1756-IA8D (continued)Attribute ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IA8D 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 Hz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 4 - Certifications - 1756-IA8DCertification(1) UL CSA CE 1756-IA8D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

5

1756 ControlLogix I/O Specifications

1756-IA16ControlLogix AC (79132V) input module1756-IA16

Simplified Schematic IN-O L2-0 GND ControlLogix Backplane Interface Display +5VGroup 0 Daisy Chain to Other RTBs

2

1

IN-14 3

IN-0 IN-26 5

IN-3 IN-58 7

IN-4 IN-610 9

Group 0

IN-7 L2-012 11

L2-0 IN-814 13

IN-9 IN-1116 15

IN-10 IN-1218 17

AC INPUTST 0 1 2 3 4 5 6 7 O FL 0 1 2 3 4 5 6 7 K T

Group 1

IN-13 IN-1520 19

Group 1

IN-14 L2-1

L2-1DIAG STIC NO

L2

L1

Table 5 - Technical Specifications - 1756-IA16Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max 1756-IA16 16 (8 points/group) 120V AC 74132V AC, 4763 Hz 120V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 2 mA 0.58 W 5.8 W @ 60 C (140 F) 18.41 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 13 mA @ 132V AC

6

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 5 - Technical Specifications - 1756-IA16 (continued)Attribute Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IA16 250 mA peak (decaying to 4 kHz 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1 on signal ports(1) T4A T4 None (open-style) Yes

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

26

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 25 - Environmental Specifications - 1756-IB16IFAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IB16IF 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

27

1756 ControlLogix I/O Specifications

Table 26 - Certifications - 1756-IB16IFCertification(1) c-UL-us CE 1756-IB16IF UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB16ISOEControlLogix DC (1055V) sequence of events input moduleSimplified Schematic Electronic Current Limit Circuit IN-0Isolated Wiring GND-0 GND-1 +5V GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar GND-9 (Cut to Length) ControlLogix Display GND-10 Backplane GND-11 Nonisolated Interface GND-12 Wiring GND-13 GND-14 GND-15 Additional jumper bars are available GND-15 DC (-) as cat. no. 1756-JMPR. Not Used DC-0 (-)2 4 6 8 1 3 5 7

1756-IB16ISOE

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

GND-0

Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)

Daisy Chain to Other RTBs

SOE INPUTST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

28

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 27 - Technical Specifications - 1756-IB16ISOEAttribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On 1756-IB16ISOE 16 individually isolated, sequence of events 24/48V DC sink/source 1055V DC 24V DC Hardware delay: 10 s nom/20 s max + firmware scan: up to 25 s + filter time: 050 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) Hardware delay: 25 s nom/50 s max + firmware scan: up to 25 s + filter time: 050 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) 320 mA 2 mA 1.7 W 5.5 W @ 60 C (140 F) 17.22 BTU/hr 5V 1.5 mA 2.0 mA @ 9V DC 4.5 mA @ 2431V DC 5.1 mA @ 4855V DC 10.8 k @ 55V DC 200 s750 ms Software configurable 100 s 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input-to-input Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4 None (open-style) Yes

On to Off

Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, nom On-state current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

29

1756 ControlLogix I/O Specifications

Table 28 - Environmental Specifications - 1756-IB16ISOEAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IB16ISOE 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 2.5 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

30

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 29 - Certifications - 1756-IB16ISOECertification(1) UL CSA CE 1756-IB16ISOE UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB32ControlLogix DC (1031.2V) input moduleSimplified Schematic IN-0 GND-0 GND ControlLogix Display Backplane Interface Current Limiter +5VIN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 GND-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 GND-1 1756-IB322 4 6 8 10 1 3 5 7 9

Group 0 Daisy Chain to Other RTBs

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Group 1

DC INPUTST 0 1 2 3 4 5 6 7

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 GND-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 GND-1

Group 0

Group 1

1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6

1 1 1 9 2 7

1 2 2 0 2 8

1 3 2 1 2 9

1 4 2 2 3 0

1 O 5 K 2 3 3 1

DC COM

+

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

31

1756 ControlLogix I/O Specifications

Table 30 - Technical Specifications - 1756-IB32Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IB32 32 (16 points/group) 12/24V DC sink 1031.2V DC 24V DC Hardware delay: 380 s max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 420 s max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 120 mA 2 mA 0.66 W 6.2 W @ 60 C (140 F) 21.1 BTU/hr @ 60 C (140 F) 5V 2.27 mA 4.8 mA @ 10V DC 5.5 mA @ 31.2V DC 250 mA (decaying to < 37% in 22 ms, without activation) 5.67 k @ 31.2V DC 200 s750 ms Software configurable 200 s 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1 - on signal ports(1) T4 T4 None (open-style) Yes

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

32

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 31 - Environmental Specifications - 1756-IB32Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IB32 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

33

1756 ControlLogix I/O Specifications

Table 32 - Certifications - 1756-IB32Certification(1) c-UL-us CSA CE 1756-IB32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IC16ControlLogix DC (3060V) input module1756-IC16

Simplified SchematicIN-1

2

1

IN-04 3

IN-0 GND-0 GND

+5VIN-3

IN-26 5

Group 0

IN-58 7

IN-4 IN-610 9

Group 0

IN-7 GND-012 11

ControlLogix Backplane Interface

Display

GND-0 IN-814 13

IN-9 IN-1116 15

IN-10 IN-1118 17

Group 1

IN-13 IN-15

Group 1

IN-1420 19

DC INPUTST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

GND-1

GND-1

Daisy Chain to Other RTBs

DC COM

+

34

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 33 - Technical Specifications - 1756-IC16Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IC16 16 (8 points/group) 48V DC sink 3055V DC @ 60 C (140 F) 3060V DC @ 55 C (131 F) 48V DC Hardware delay: 1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 100 mA 3 mA 0.58 W 5.2 W @ 60 C (140 F) 17.73 BTU/hr 10V 1.5 mA 2 mA @ 30V DC 7 mA @ 60V DC 250 mA 8.57 k @ 60V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s, inputs-to-backplane Routine tested @ 924V AC for 2 s, input group-to-group Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4 T4 None (open-style) Yes

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

35

1756 ControlLogix I/O Specifications

Table 34 - Environmental Specifications - 1756-IC16Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IC16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

36

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 35 - Certifications - 1756-IC16Certification(1) UL CSA CE 1756-IC16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

37

1756 ControlLogix I/O Specifications

1756-IF6CISControlLogix sourcing current loop analog input module1756-IF6CIS 2-wire Transmitter Connected to the Module and the Module Providing 24V DC Loop Power2 1

1756-IF6CIS 2-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power2 1

A

VOUT-14 3

VOUT-0 IN-0/I6 5

VOUT-14 3

VOUT-0 iA

IN-1/I RTN-18 7

A

IN-1/I6 5

IN-0/I RTN-08 7

RTN-0 VOUT-210 9

iRTN-1 VOUT-3 Shield Ground

A

24V DC +

2-wire Transmitter

VOUT-3 IN-3/I12 11

VOUT-210 9

IN-2/I RTN-214 13

IN-3/I12 11

IN-2/I RTN-214 13

RTN-3 Not Used16 15

RTN-3 Not Used16 15

Shield Ground

Not Used VOUT-418 17

Not Used VOUT-418 17

VOUT-5 IN-5/I20 19

VOUT-5 IN-5/I20 19

IN-4/I RTN-4

IN-4/I RTN-4

RTN-5

RTN-5

Place additional loop devices (such as strip chart recorders) at either A location in the current loop.1756-IF6CIS 4-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power2 1

VOUT-14 3

VOUT-0 IN-0/I6 5

iA + +

IN-1/I RTN-18 7

RTN-0 VOUT-210 9

A

4-wire Transmitter

24V DC

ANALOG INPUT CAL OK

VOUT-3 IN-3/I12 11

IN-2/I RTN-214 13

RTN-3 Not Used16 15

Shield Ground

Not Used VOUT-418 17

VOUT-5 IN-5/I20 19

IN-4/I RTN-4

RTN-5

Place additional loop devices (such as strip chart recorders) at either A location in the current loop. User-supplied power supply must not exceed 150VA.

38

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 36 - Signal and User Counts - 1756-IF6CISRange 020 mA Low Signal and User Counts 0 mA -32768 counts High Signal and User Counts 21.09376 mA 32767 counts

Table 37 - Technical Specifications - 1756-IF6CISAttribute Inputs Input range Resolution Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Sourcing voltage, min Sourcing voltage, max Sourcing current, max Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C (77 F), nom Calibrated accuracy 25 C (77 F), max Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module input scan time, min On-board data alarming Scaling to engineering units Real-time channel sampling Data format 1756-IF6CIS 6 individually isolated current sourcing 021 mA (over-range indication when exceeded) 16 bits 0.34 A/bit 250 mA 275 mA 7.9 W 5.1 W @ 60 C (140 F) 17.4 BTU/hr 215 , approx 20V DC 30V DC Current limited to < 30 mA Zero reading within 5 s 30V AC/DC with PTC and sense resistor 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 3262 Hz (-3 dB)(1) 10 M Current: 249 Positive full scale reading within 5 s Voltage: 120V AC/DC Current: 8V AC/DC (with on-board current resistor) 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz (-3 dB)(1) 1 M Current: 249 Differential voltage: Positive full scale reading within 5 s Single-ended/diff. current: Negative full scale reading within 5 s Single-ended voltage: Even numbered channels go to positive full scale reading within 5 s, odd numbered channels go to negative full scale reading within 5 s Voltage: 30V DC Current: 8V DC >80 dB @ 50/60 Hz(1) >100 dB @ 50/60 Hz Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 45 V/C Voltage: 15 ppm/C Current: 20 ppm/C Voltage: 0.1% of range Current: 0.3% of range 8 pt single-ended (floating point): 16488 ms 4 pt differential (floating point): 8244 ms 2 pt differential (floating point): 5122 m(1) Yes Yes Yes Integer mode (left justified, 2s complement) IEEE 32-bit floating point Sigma-Delta 250V (continuous), reinforced insulation type, inputs-to-backplane. No isolation between individual inputs Routine tested at 1350V AC for 2 s

Input range

Resolution

Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time

Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min

On-board data alarming Scaling to engineering units Real-time channel sampling Data format Module conversion method Isolation voltage

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

49

1756 ControlLogix I/O Specifications

Table 44 - Technical Specifications - 1756-IF8 (continued)Attribute Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type 1756-IF8 Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 2(2) T4A T4 None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 45 - Environmental Specifications - 1756-IF8Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF8 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

50

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 46 - Certifications - 1756-IF8Certification(1) UL CSA CE 1756-IF8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IF8HControlLogix voltage/current analog input module with HART protocol1756-IF8H Current 1756-IF8H VoltageVoltage Input +V IN0+IN0+ IN0IN1+ 4 Wire Current Input IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN72 4 6 8 1 3 5 7 I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC

2 Wire Current Input2 Wire XMTR

24V DC Power Supply

+ -

+-

2 4 6 8

1 3 5 7

I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC

-V

IN0IN1+ IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN7-

ANALOG INPUT CAL OK HART

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

24V DC Power Supply

+ + Wire + 4 XMTR - - -

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

51

1756 ControlLogix I/O Specifications

Table 47 - Technical Specifications - 1756-IF8HAttribute Inputs Input range 1756-IF8H 8 differential voltage or current 10V 05V 15V 010V 020 mA 420 mA 1621 bits 300 mA 135 mA 4.77 W Voltage: 3.21 W Current: 4.01 W Voltage: 11.0 BTU/hr Current: 13.7 BTU/hr > 1 M voltage 250 current Positive full scale reading within 5 s Voltage: 30V DC Current: 8V DC > 80 dB @ 50/60 Hz > 100 dB @ 50/60 Hz Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 90 V/C Voltage: 10 ppm/C Current: 20 ppm/C Voltage: 0.1% of range Current: 0.3% of range 18488 ms (filter dependent) Typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time Integer mode (left justified, 2s complement) IEEE 32-bit floating point Successive approximation R-Ladder DAC, monotonicity with no missing codes 50V (continuous), basic insulation type, input channels-to-backplane, and input channelto-channel Type tested at 1500V AC for 60 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1

Resolution Current draw @ 5V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Module HART scan time

Data format Input conversion method Output conversion method Isolation voltage

Module keying Removable terminal block RTB keying Slot width

52

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 47 - Technical Specifications - 1756-IF8H (continued)Attribute Wire category North American temperature code IEC temperature code Enclosure type 1756-IF8H 2 - on signal ports(1) T4A T4 None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 48 - Environmental Specifications - 1756-IF8HAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF8H 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

53

1756 ControlLogix I/O Specifications

Table 49 - Certifications - 1756-IF8HCertification(1) c-UL-us CSA CE 1756-IF8H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR101622C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

54

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

1756-IF16ControlLogix voltage/current analog input module1756-IF16 Differential Current Channel 0 1756-IF16 Differential Voltage Channel 0 IN-0 IN-1 IN-2 Shield Ground Channel 3 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-152 4 6 8 10 1 3 5 7 9

iA i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

+

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

Jumper Wires Shield Ground

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

iA

Channel 3

+

Shield Ground

Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Uses these terminals IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6 IN-8 (+), IN-9 (-), i RTN-8 IN-10 (+), IN-11 (-), i RTN-10 IN-12 (+), IN-13 (-), i RTN-12 IN-14 (+), IN-15 (-), i RTN-14

Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Uses these terminals IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-) IN-8 (+), IN-9 (-) IN-10 (+), IN-11 (-) IN-12 (+), IN-13 (-) IN-14 (+), IN-15 (-)

All terminals marked RTN are connected internally. A 249 current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4, and 6.

All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or i RTN are not used for differential voltage wiring. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4, and 6.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

55

1756 ControlLogix I/O Specifications

1756-IF16 Single-ended Current

1756-IF16 Single-ended Voltage

iIN-0 IN-1 IN-2 Shield Ground 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-152 4 6 8 10 1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15 Jumper Wires Shield Ground

+

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

iA

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

+

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Shield Ground

All terminals marked RTN are connected internally. For current applications, all terminals marked i RTN must be wired to terminals marked RTN. A 249 current loop resistor is located between IN-x and iRTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop.

All terminals marked RTN are connected internally. Terminals marked i RTN are not used for single-ended voltage wiring.

ANALOG INPUT CAL OK HART

56

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 50 - Technical Specifications - 1756-IF16Attribute Inputs Input range 1756-IF16 16 single ended, 8 differential or 4 differential (high speed) 10.25V 010.25V 05.125V 020.5 mA 320 V/count (15 bits + sign bipolar) @ 10.25V 160 V/count (16 bits) @ 010.25V 80 V/count (16 bits) @ 05.125V 0.32 A/count (16 bits) @ 020.5 mA 150 mA 65 mA 2.33 W Voltage: 2.3 W Current: 3.9 W Voltage: 7.84 BTU/hr Current: 13.3 BTU/hr Voltage: >10 M Current: 249 Differential voltage - Positive full scale reading within 5 s Single-ended/differential current - Negative full scale reading within 5 s Single-ended voltage - Even numbered channels go to positive full scale reading within 5 s, odd numbered channels go to negative full scale reading within 5 s Voltage: 30V DC Current: 8V DC >80 dB @ 50/60 Hz(1) >100 dB @ 50/60 Hz 15 Hz (-3 dB)(1) 90 dB @ 50/60 Hz (15 and 20 Hz filters only) Better than 0.01% of range (15 and 20 Hz filters only) Better than 0.13% of range (all filters) 12 months 27 V/C 11ppm/C 0.3% of range 11328 ms (filter dependent) Typically 1 s Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time Integer mode (left justified, 2s complement) IEEE 32-bit floating point Successive approximation R-Ladder DAC, monotonicity with no missing codes 50V (continuous), basic insulation type, inputs-to-backplane No isolation between individual inputs Type tested at 1500V DC for 60 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 2 - on signal ports(1) T5 T4 None (open-style)

Data format Input conversion method Output conversion method Isolation voltage

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

60

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 54 - Environmental Specifications - 1756-IF16HAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF16H 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 3 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 55 - Certifications - 1756-IF16HCertification(1) c-UL-us CE 1756-IF16H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

61

1756 ControlLogix I/O Specifications

1756-IF4FXOF2FControlLogix high-speed input/output analog module1756-IF4FXOF2F Current(-) i(+) (+) User Analog Input Device (-) Shield Ground +IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used 1756-IF4FXOF2F Voltage

(+)

2-wire A TransmitterA

+IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used

2 4 6

1 3 5

+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 i I OUT-0 RTN-0 Not Used Not Used Not Used Not Used Not Used Not Used Not UsedA

2 4 6 8

1 3 5 7

+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 I OUT-0 RTN-0 Not Used (-) Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground (+)

8 7 10 9 12 11 14 13 16 15 18 17 20 19 22 24 26 28 21 23 25 27

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Curren Output Load Shield Ground

30 29 32 31 34 33 36 35

A = Inline field device (such as a strip chart recorder or meter)

ANALOG INPUT ANALOG OUTPUT CAL OK

Table 56 - Technical Specifications - 1756-IF4FXOF2FAttribute Current draw at 5.1V Current draw at 24V Total backplane power Power dissipation, max Thermal dissipation Data format Isolation voltage 1756-IF4FXOF2F 375 mA 100 mA 4.3 W Voltage: 4.3 W Current: 4.7 W Voltage: 14.66 BTU/hr Current: 16.02 BTU/hr Integer mode (left justified, 2s complement) IEEE 32-bit floating point 250V (continuous), basic insulation type, inputs and outputs to backplane No isolation between individual inputs or outputs Routine tested at 1350V AC for 2 s Electronic, software configurable

Module keying

62

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 56 - Technical Specifications - 1756-IF4FXOF2F (continued)Attribute Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type 1756-IF4FXOF2F 1756-TBCH 1756-TBS6H User-defined mechanical 1 2(1) T4A T4 None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 57 - Input Specifications - 1756-IF4FXOF2FAttribute Number Input range

1756-IF4FXOF2F4 high-speed, sub-millisecond, differential 10.5V 010.5V 05.25V 021 mA (over-range indication when exceeded) Approx 14 bits across 10.5V DC (21V total) 10.5V range: 1.3 mV/bit, 14-bit effective 010.5V range: 1.3 mV/bit, 13-bit effective 05.25V range: 1.3 mV/bit, 12-bit effective Approx 12 bits across 21 mA 021 mA range: 5.25 A/bit 1 Least Significant Bit (LSB)(1) Voltage: >1 M Current: 249 Positive full-scale reading within 1 s Voltage: 30V DC Current: 8V AC/DC 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval 12 months Voltage: 25 ppm/C max Current: 35 ppm/C max 0.2% of range 300 s min(2) Successive approximation

Resolution

Repeatability Input impedance Open circuit detection Overvoltage protection Calibrated accuracy @ 25 C (77 F) Calibration interval Gain drift with temperature Module error Module scan time Input conversion method

(1) Repeatability is defined as the stability of the input channel reading when a steady state signal is applied, for example, 1 LSB is one count (1.3 mV) from the nominal reading. (2) 300 s min for 1756-IF4FXOF2F, Series B, firmware revision 3.x or greater. 400 s min for 1756-IF4FXOF2F, Series A, firmware revision 1.x.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

63

1756 ControlLogix I/O Specifications

Table 58 - Output Specifications - 1756-IF4FXOF2FAttribute Number Output range Resolution Open circuit detection Overvoltage protection Short circuit protection Drive capability Output settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Update period for all channels (RPI), min Output conversion method

1756-IF4FXOF2F2 high-speed voltage or current 10.4V 021 mA 13 bits across 21 mA = 2.8 A/bit 14 bits across 21.8V = 1.3 mV/bit Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21 mA or less Voltage: >2000 Current: 0750 < 2 ms to 95% of final value with resistive loads 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval 12 months 50 V/ C 1 A/ C Voltage: 25 ppm/C max Current: 50 ppm/C max Voltage: 0.2% of range Current: 0.3% of range 1 ms R-Ladder DAC, monotonicity with no missing codes

Table 59 - Environmental Specifications - 1756-IF4FXOF2FAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 1756-IF4FXOF2F 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges

64

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 59 - Environmental Specifications - 1756-IF4FXOF2F (continued)Attribute Radiated RF immunity IEC 61000-4-3 1756-IF4FXOF2F 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 60 - Certifications - 1756-IF4FXOF2FCertification(1) UL CSA CE 1756-IF4FXOF2F UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

65

1756 ControlLogix I/O Specifications

1756-IG16ControlLogix TTL input moduleStandard Wiring1756-IG16 DC2 1

CE Compliant Wiring1756-IG16I/O Wire

2

1

IN-1

IN-04 3

IN-14 3

IN-0 IN-26 5

IN-36 5

IN-2 IN-48 7

5V DC

IN-3 IN-58 7

IN-5

IN-4 IN-610 9

I/O Wire

+ TTL Input Device

+

IN-7+ DC

DC Power Wire

IN-710 9

IN-6DC COM 012 11

DC-0(+) IN-914 13

DC-0(+)12 11

DC COM 0

IN-8 IN-1016 15

IN-914 13

IN-8 IN-1016 15

IN-115V DC Power

IN-11 IN-1318 17

IN-1318 17

IN-12 IN-1420 19

IN-12IN-15

Capacitor 0.01 F Typical (See notes below.)

IN-1520 19

IN-14DC COM 1

DC-1(+)

DC COM 1

DC-1(+)

Simplified Schematic+5 DC 1.5 K IN 1K 74HCT14 560

IMPORTANT: I/O cables must be shielded type and cable length must be 50 mA 0.2V/s for loads < 50 mA(1) Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s Zero crossing 60V peak Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(2) T4A None (open style)

(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

114

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 112 - Environmental Specifications - 1756-OA16IAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OA16I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

115

1756 ControlLogix I/O Specifications

Table 113 - Certifications - 1756-OA16ICertification(1) UL CSA CE 1756-OA16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

116

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

1756-OB8ControlLogix DC (1030V) output moduleSimplified Schematic DC-0(+) +5V OUT-0Group 0 Daisy Chain to Other RTBs2

1756-OB81

DC-0 (+)4 3

OUT-0 OUT-16 5

DC-0 (+) DC-0 (+)

Group 0

OUT-28 7

ControlLogix Backplane Interface Display

RTN OUT-0

DC-0 (+)10 9

OUT-3 RTN OUT-012 11

RTN OUT-0

Surge Current ChartDC-1 (+)

4A

SurgeDC-1 (+) Group 1

OUT-414 13

OUT-516 15

Group 1 OUT-6

Current

Continuous @ 60 C (140 F) 2A

DC-1 (+)18 17

DC-1 (+)20 19

OUT-7 RTN OUT-1

RTN OUT-1

0 Time

10 msDaisy Chain to Other RTBs

+

DC COM

DC OUTPUTST 0 1 2 3 4 5 6 7 O K

Table 114 - Technical Specifications - 1756-OB8Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V 1756-OB8 8 (4 points/common) 2A 12/24V DC source 1030V DC 1 ms max 2 ms max 165 mA 2 mA

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

117

1756 ControlLogix I/O Specifications

Table 114 - Technical Specifications - 1756-OB8 (continued)Attribute Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OB8 0.89 W 2.5 W @ 60 C (140 F) 8.53 BTU/hr 1 mA per point 1.2V DC @ 2A 2 A @ 60 C (140 F) 8 A @ 60 C (140 F) 4 A for 10 ms each, repeatable every 1 s @ 60 C (140 F) 2 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4A T4 None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

118

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 115 - Environmental Specifications - 1756-OB8Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB8 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

119

1756 ControlLogix I/O Specifications

Table 116 - Certifications - 1756-OB8Certification(1) UL CSA CE 1756-OB8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

120

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

1756-OB8EIControlLogix DC (1030V) electronically-fused, isolated output module1756-OB8EI

+5V

Simplified Schematic DC-0(+)Isolated Wiring + DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-11 3 5 7 10 9 2 4 6 8

+

OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used

OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0Nonisolated Wiring

-

DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Surge Current Chart 4A Surge

Daisy Chain to Other RTBs

Daisy Chain to Other RTBs

Current

Continuous @ 60 C (140 F) 2A

0 Time

10 ms

+

DC COM

DC OUTPUTST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7 K

ELECTRONICALLY FUSED

Table 117 - Diagnostic Specifications - 1756-OB8EIAttribute Short trip Timestamp of diagnostics 1756-OB8EI > 4.5 A for 500 s max (output on, then short) > 4.5 A for 1.5 ms max (output on into short) 1 ms

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

121

1756 ControlLogix I/O Specifications

=

Table 118 - Technical Specifications - 1756-OB8EIAttribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type 1756-OB8EI 8 individually isolated 2A 12/24V DC source 1030V DC 1 ms max 5 ms max 250 mA 2 mA 1.30 W 4.7 W @ 60 C (140 F) 16.03 BTU/hr 1 mA per point 1.2V DC @ 2 A 2 A @ 60 C (140 F) 10 A @ 60 C (140 F) 16 A @ 55 C (131F) linear derating 4 A for 10 ms each, repeatable every 2 s 3 mA Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Electronically fused per point 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A T4 None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

122

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 119 - Environmental Specifications - 1756-OB8EIAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB8EI 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

123

1756 ControlLogix I/O Specifications

Table 120 - Certifications - 1756-OB8EICertification(1) UL CSA CE 1756-OB8EI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

124

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

1756-OB8IControlLogix DC (1030V) isolated output module+5V Simplified Schematic DC-0(+)Isolated Wiring 1756-OBI

OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0

Surge Current Chart 4A SurgeNonisolated Wiring

Daisy Chain to Other RTBs

Current

Continuous @ 60 C (140 F) 2A

Daisy Chain to Other RTBs

DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used

2 4 6 8

1 3 5 7

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used

0 Time

10 ms

DC OUTPUTST 01234567 O K

Table 121 - Technical Specifications - 1756-OB8IAttribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V 1756-OB8I 8 individually isolated 2A 12/24V DC source 1030V DC 1 ms max 2 ms max 165 mA

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

125

1756 ControlLogix I/O Specifications

Table 121 - Technical Specifications - 1756-OB8I (continued)Attribute Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OB8I 2 mA 0.89 W 4.6W @ 60 C (140 F) 15.70 BTU/hr 0.5 mA per point 0.5V DC @ 2 A 2 A @ 60 C (140 F) 16 A @ 60 C (140 F) 4 A for 10 ms each, repeatable every 1 s @ 60 C (140 F) 2 mA Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 122 - Environmental Specifications - 1756-OB8IAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) 1756-OB8I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz

126

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 122 - Environmental Specifications - 1756-OB8I (continued)Attribute Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB8I 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8k V air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 123 - Certifications - 1756-OB8ICertification(1) UL CSA CE 1756-OB8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

127

1756 ControlLogix I/O Specifications

1756-OB16DControlLogix DC (19.230V) diagnostic output moduleSimplified schematic +5V +5V Short Circuit Detect Optoisolation +5V + DCDaisy Chain to Other RTBs +DC-0 +DC-0 +DC-0 +DC-0 Group 0 +DC-0 +DC-0 +DC-0 GND-0 +DC-1 +DC-1 +DC-1 +DC-1 +DC-1 Group 1 +DC-1 +DC-1 GND-1 GND-1 Not Used Daisy Chain to Other RTBs 1756-OB16D

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used Group 1 Group 0

OUT ControlLogix Backplane Interface RTN Display Output Verify/No Load Surge Current Chart 4A Surge

Current

2A

Continuous @ 30 C (86 F) Continuous @ 60 C (140 F)

3234 36

0 Time

10 ms

+

DC COM

DC OUTPUTST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC

Table 124 - Diagnostic Specifications - 1756-OB16DAttribute Short trip No load Output verification Pulse test Time stamp of diagnostics 1756-OB16D 8 A for 180 ms, min 10 A for 120 ms, min Off-state detection only On-state detection only Configurable maximum pulse width 1 ms

128

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 125 - Technical Specifications - 1756-OB16DAttribute Outputs Pilot duty 1756-OB16D 16 diagnostic (8 points/group) 2 A @ 30 C (86 F) DC-13SQ 1 A @ 60 C (140 F) linear derating 8 A combined continuous max @ 30 C (86 F) 4 A @ 60 C (140 F) 24V DC source 19.230V DC 60 s nom/1 ms max 630 s nom/5 ms max 250 mA 140 mA 4.64 W 3.3 W @ 60 C (140 F) 11.25 BTU/hr 1 mA per point 1.2V DC @ 2A 2 A @ 30 C (86 F) linear derating 1 A @ 60 C (140 F) linear derating 8 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 4 A for 10 ms per point, repeatable every 1 s 3 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Electronically fused per point 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A T4 None (open-style)

Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

129

1756 ControlLogix I/O Specifications

Table 126 - Environmental Specifications - 1756-OB16DAttribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB16D 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11: Group 1, Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

130

Rockwell Automation Publication 1756-TD002E-EN-E - April 2012

1756 ControlLogix I/O Specifications

Table 127 - Certifications - 1756-OB16DCertification(1) UL CSA CE 1756-OB16D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Uni