12
Installation and Operation Manual DHW HT# 059106-00C Energy Saver Domestic Hot Water Boiler or Direct or Indirect Water Heater and Recirculating Pump Control with Setback Schedule WaRnIng This Heat-Timer control is strictly an operating control; it should never be used as a primary limit or safety control. all equipment must have its own certified limit and safety controls required by local codes. The installer must verify proper operation and correct any safety problems prior to the installation of this Heat-Timer control. DHW Energy Saver Boiler Pump 6 7 8 9 COM 3 4 5 A GND B 16VAC 1 2 ~ ~ Typical Wiring for Platinum Serial Panel RS485 Plug

DHW Energy Saver - Heat-Timer® Corporation · 4 DHW Energy Saver Installation and Configuration Manual HT# 059106-00C Installation The DHW Energy Saver communicates with the Heat-Timer

  • Upload
    others

  • View
    14

  • Download
    0

Embed Size (px)

Citation preview

Installation and Operation Manual DHW

HT#

059

106-

00C

Energy SaverDomestic Hot Water Boiler or Direct or Indirect Water Heater and Recirculating Pump Control with Setback Schedule

WaRnIngThis Heat-Timer control is strictly an operating control; it should never be used as a primary limit or safety control. all equipment

must have its own certified limit and safety controls required by local codes. The installer must verify proper operation and correct any

safety problems prior to the installation of this Heat-Timer control.

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5A GND B

16VAC

1 2~ ~

Typical Wiring for PlatinumSerial Panel RS485 Plug

2 DHW Energy Saver Installation and Configuration Manual

HT#

059

106-

00C

ContentsOvERvIEW 3InSTallaTIOn 4WIRIng 4

Power Wiring 4Communication Wiring 4Boiler or Direct/Indirect Water Heater Wiring 5Domestic Hot Water Circulating Pump Wiring 5Temperature Sensor Wiring 5

Supply Temperature Sensor 5Return Temperature Sensor 5

PlaTInuM COnTROl MEnu SETTIngS 6ICMS WEB MEnu SETTIngS 6

using the Supply or Return Sensor 7Supply or Return Set Point 7Supply or Return Peak and light Differential 7Demand Schedule 8Copy Schedule 8

InTERnET alaRMS THROugH ICMS 8Sensor Fault 8Communication Error 8

TROuBlESHOOTIng anD lEDS 8PIPIng/WIRIng TO WaTER HEaTER 9PIPIng/WIRIng TO BOIlER anD InDIRECT WaTER HEaTER 10PIPIng/WIRIng TO BOIlER anD a TEMPERIng valvE 11SPECIFICaTIOn 12

DHW Energy Saver Installation and Configuration Manual 3

HT#

059

106-

00C

OverviewTheDHW(DomesticHotWater)EnergySaverconnectstoaHeat-TimerRINetPlatinumseriescontrol(allMPC,MPCQ,HWR,HWRQ,SRCRINetPlatinumcontrolswithsoftwareversion7.05orhigher)tooperateaboilerordirect/indirectwaterheaterandaDHWcirculatingpumpbasedontwosetpoints.Onesetpointisfortheboilerandtheotherisforthepump.TwosensorsconnectedtothePlatinumRINet(Internetcommunicationcapablecontrol)areused.AuxTemp0sensormeasuresthedomestichotboilersupplytemperature.AuxTemp1sensormeasuresthedomesticrecirculatinglinereturntemperature.

AlltheDHWEnergySaversettingscanbeviewedandadjustedthroughthePlatinumcontrolmenusorthePlatinumcontrolpagesonICMSwebsite(http://www.htcontrols.com).Eachofthesupplyandreturntemperatureshaveasetpointandapeakdemandandlightloadconditiondifferentials.Thisoffersbetteroperationandsavingsthanonedifferential.Asthegoalistoreduceboiler/waterheaterandpumpoperationduringlightperiods.Thatcanbeachievedbyhavingslightlylongerboiler/waterheaterrunperiodsandlongeroffperiodsusingalargerdifferential.WhenthesupplytemperaturedropsbelowtheSupplySetPointanddifferential,theControlwillenergizetheboileroutput.TheboileroutputwillremainenergizeduntilthesupplytemperaturereachestheSupplySetPoint.WhenthereturntemperaturedropsbelowtheReturnSetPointlessthedifferential,theControlwillenergizethecirculatingpumpoutput.ThepumpoutputwillremainenergizeduntilthereturntemperaturereachestheReturnSetPoint.

WaRnIng• Make sure Recirculating Pump control does not adversely affect other equipment. I.e. tempering valve.• Make sure the boiler/water heater can operate properly at the lowest desired differential adjustment.

ThePlatinumcontrolhasaseparateDHWEnergySaverweeklyDay/NightschedulethatcanbesetusingtheInternetICMSwebsiteorthroughthePlatinumcontrolmenu.Itoffers4peakand4lightloadperiodsforeachdayoftheweek.Wheninthepeakperiod,thePlatinumcontrolwillusethePeakDifferentialsetting.Wheninthelightusageperiod,thePlatinumcontrolwillusetheLightDifferentialsetting.TheLightDifferentialmustbegreaterthanthePeakDifferentialtoprovidelongerboilerorpumpruntimeandlongeroffperiods.

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5A GND B

16VAC

1 2~ ~

Typical Wiring for PlatinumSerial Panel RS485 Plug

16 VAC(transformer

Provided)

Communication toHeat-Timer

Platinum Control

DHW boiler andDHW circulating

pump output relays

4 DHW Energy Saver Installation and Configuration Manual

HT#

059

106-

00C

InstallationTheDHWEnergySavercommunicateswiththeHeat-TimerPlatinumcontrolusingRS485(3-wireconnection).Thus,itneedstobeinstalledincloseproximitytothePlatinumcontroltoreducelongcommunicationwireruns.• MounttheDHWEnergySaveronaflatsurfacenexttothePlatinumcontrol.• TheModulecanbemountedhorizontallyorvertically.• Keepthecontrolawayfromextremeheat,cold,orhumidity.• Screwthemoduletotheflatsurfaceusingthetwosidetabswithholes.• NoneedtoremovetheDHWEnergySavercover.

Wiring• WhenwiringtheDHWEnergySaver,makesurethatthecoverwiththeterminallabelsisavailable.

• Allmoduleterminalsareoftheremovaltype.Thatfacilitateseasywiring.Justunscrewtheterminalblocksidescrewstoremovethefullterminalblock.

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5A GND B

16VAC

1 2~ ~

120VAC

16VACDedicatedTransformerPower Wiring

• TheDHWEnergySaverispoweredusing16VACtransformer.Transformermustbeaminimumof10VAandisincludedwithcontrol.

• ConnectthetransformeroutputstotheDHWEnergySaver’sleftmostterminals.Powerpolarityisnotobserved.

WaRnIngDO nOT share the DHW Energy Saver transformer with other devices. This may cause problem in the control operation or

permanent damage to the equipment.

Communication Wiring• TheDHWEnergySavercommunicatesallofitsinformationtothePlatinumcontrolusingRS485(3-wireconnection).

• TheDHWEnergySaverRS485terminalsarewiredtothePlatinummainboard’sRS485(underthePCBboard).

• Followthewiringasperthegraphontheright.

alERTDO nOT connect the DHW Energy Saver to the RS485 on the Platinum RI board. Instead, connect the DHW Energy Saver

RS485 to the Platinum main board.

• Maximumwiringlengthshouldnotexceed100Feet.Use18gauge2-conductorshieldedwire(#18).ConnecttheshieldtothemiddleterminalsonbothoftheRS485connections.Toeliminatecommunicationerrors,DONOTsplicethecommunicationcablewires.

• WhenconnectingtheDHWEnergySaverandaPlatinumExtensiontothesameconnector,makesuretosplicethecablesexternallybeforebringingthemtotheRS485PlugConnectoronthemainPlatinumBoard.

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5A GND B

16VAC

1 2~ ~

Use RS485Communication

on the back of thePlatinum main board

PCB board

Shield

DHW Energy Saver Installation and Configuration Manual 5

HT#

059

106-

00C

Boiler or Direct/Indirect Water Heater Wiring• TheDHWEnergySavercancontrolasingleboiler.Itturnsontheboiler/waterheaterwheneverthesupplytemperaturedropsbelowtheSupplySetPointlessthedifferential.

• Justwireterminal6and7totheboilerTTterminals.• Heat-Timerrecommendstheinstallationofabypassswitchformaintenanceandmanualoperationoftheboiler/waterheater.

• MakesuretosettheboilerlimitshigherthantheDHWEnergySaverSupplySetPoint.

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5A GND B

16VAC

1 2~ ~

TTBoiler/Water

Heater

BypassSwitch

(Optional)

Domestic Hot Water Circulating Pump Wiring• WhentheDHWReturnisactivated,theDHWEnergySaverwillenergizetheDHWcirculatingpumprelaywheneverthereturntemperaturedropsbelowtheReturnSetPointlessthedifferential

• TheDHWEnergySaverisequippedwithacirculatingpumprelayoutput.Therelaycanoperateupto⅛HPpumpat120VAC.

• ThePumpoutputrelaydoesnotsourceanypower.Aseparatepowersourceisrequiredforthepump.

• Heat-Timerrecommendstheinstallationofabypassswitchformaintenanceandmanualoperationofthepump.

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5A GND B

16VAC

1 2~ ~

DHWPump

L N

BypassSwitch

(Optional)

Temperature Sensor Wiring• OnlyuseaStandardBrassTubesensorprovided(HT#904250-00).• Thesensorwirescanbeextendedto500Ftbysplicingitto2-conductorshieldedcable(#18/2Shielded)(HT#703001-01).

• ConnecttheshieldatthePlatinumcontrolcircledterminal.TheshieldMUSTbecutatthesensorend.

• Thesensorsmustbeinsertedin⅜”IDNPTwell(HT#904011-00orequivalent).

AUXTEMP 0

AUXTEMP 1

A1

A2

A3

A4

A5

A6

A7

A8

A9

A10

A11

A12

AUXTEMP 2

A13

A14

A15

A16

A17

A18

NETWORK

PROVE

SHUTDOWN

OUTTEMP

T

T

T

T

PRESS4-20 mA

S

+

S

Shield

Supply Sensor

Shield

Return Sensor

Platinum Control

Supply Temperature Sensor• TheSupplyTemperatureSensorisrequiredtobeconnectedtothePlatinumAuxTemp0inputterminalsfortheDHWEnergySavertocontroltheboiler/waterheaterrelay.

• TheSupplysensormustbeinstalledinanyoftheboilerorwaterheateraquastatfittingsornomorethan10Ftpasttheoutletoftheboiler/waterheater,beforeanytakeoffs.

Return Temperature Sensor• ThereturnTemperatureSensorisincludedbutoptional.ItshouldbeconnectedtothePlatinumAuxTemp1inputterminalsfortheDHWEnergySavertocontrolthePumprelay.

• TheReturnsensorshouldbeinstalledlessthan3feetfromthereturncirculatoronthereturnline.

6 DHW Energy Saver Installation and Configuration Manual

HT#

059

106-

00C

Platinum Control Menu Settings

------ SETTINGS ------

Shift

<System Settings>

<Schedules>

<Maintenance>

<System Startup>

- MAINTENANCE MENU-

System Trim +0 F

Outdoor Trim +0 F

Password

<DHW Settings>

--- DHW SETTINGS ----

<Supply Settings>

<Return Settings>

Demand Schedule

Copy Schedule

DHW Settings

DHW SUPPLY SETTINGS

Use Sensor? Yes

Setpoint 140 F

Peak Diff 20 F

Light Diff 40 F

DHW RETURN SETTINGS

Use Sensor? Yes

Setpoint 120 F

Peak Diff 20 F

Light Diff 40 F

- DHW DEMAND SCHED -

MON#1

Peak Time 6:00Am

Light Time 10:00Pm

ICMS Web Menu Settings

DHW Mode = Peak

Supp 165 F Ret OPEN

DISABLED

Press the BaCK button twice from the Main Display to show DHW Status

DHW Energy Saver Installation and Configuration Manual 7

HT#

059

106-

00C

using the Supply or Return SensorYes, No Default: NoSELECTMaintenance/DHW Settings/Supply Settings/Use Sensor Supply SensorSELECTMaintenance/DHW Settings/Return Settings/Use Sensor Return Sensor• ByactivatingtheSupplySensorfeature,thePlatinumcontrolwillutilizeAuxTemp0inputastheSupplySensor.

• ByactivatingtheReturnSensorfeature,thePlatinumcontrolwillutilizeAuxTemp1inputastheReturnSensor.

• AnyofthetwofeaturescanbeenabledeitherusingthePlatinumcontrolmenusorthePlatinumcontrolICMSwebpageat(http://www.htcontrols.com).

USE SUPPLY SENSOR

No

Yes

USE RETURN SENSOR

No

Yes

Supply or Return Set PointBoiler is adjustable from 60°F/16°C to 200F°/93°C Boiler Default: 140°F/60°CPump is adjustable from 60°F/16°C to 200F°/93°C Pump Default: 120°F/49°CSELECTMaintenance/DHW Settings/Supply Settings/Setpoint Supply SensorSELECTMaintenance/DHW Settings/Return Settings/Setpoint Return Sensor• TheSupplySetPointdeterminesthemaximumtemperatureatwhichtheboiler/waterheaterrelaywillde-energize.ItisthemaximumDHWtargettemperaturetheDHWEnergySaverwilltrytoachieve.Therelaywillenergizewheneverthesupplytemperaturedropsbelowthissetpointlessthedifferential.Seenextsetting.

• TheReturnSetPointdeterminesthemaximumtemperatureatwhichtheDHWpumprelaywillde-energize.Thecirculatingpumprelaywillenergizewheneverthereturntemperaturedropsbelowthissetpointlessthedifferential.Seenextsetting.

DHW SUPPLY SETPOINT

140 F

[ ]

DHW RETURN SETPOINT

120 F

[ ]

Supply or Return Peak and light DifferentialPeak is adjustable from 5F°/3C° to 100F°/56C° Peak Default: 10F°/6C°Light is adjustable from 5F°/3C° to 100F°/56C° Light Default: 20F°/11C°SELECTMaintenance/DHW Settings/Supply Settings/Peak Diff or Light Diff Supply SensorSELECTMaintenance/DHW Settings/Return Settings/Peak Diff or Light Diff Return Sensor• Anyofthedifferentialsissubtractedfromthesetpointtodeterminethetemperatureatwhichtheboiler/waterheaterorpumprelaywillenergize.

• TheDHWEnergySaverhastwoindependentdifferentialsforeachofthesupplyandreturn.ThePeakDifferentialisusedtokeepatightcontrolovertheDHWtemperatureduringheavyusage.ThisdifferentialisusedwhentheDHWScheduleisinthePeakperiod.ItsvaluemustbelessthanorequaltotheLightDifferentialforthesamesensor.

• TheLightDifferentialisusedduringthenight,lowDHWusage,orwhenatightcontrolofthetemperatureisnotrequired.Itallowstheboilerorpumprelaytoturnonforaslightlylongerperiod.However,duetothereducedusage,therelaywillremainoffforamuchlongerperiod.ThistypeofdifferentialisusedwhentheDHWScheduleisintheLightperiod.ItsvaluemustbegreaterthanorequaltothePeakDifferentialforthesamesensor.

DHW SUPPLY PEAK DIFF

20 F

[ ]

DHW SUPPLY LIGHT DIFF

40 F

[ ]

DHW RETURN PEAK DIFF

20 F

[ ]

DHW RETURN LIGHT DIFF

40 F

[ ]

8 DHW Energy Saver Installation and Configuration Manual

HT#

059

106-

00C

Demand ScheduleSELECTMaintenance/DHW Settings/Demand Schedule• ThePeakandLightDemandScheduleactivatestherespectivedifferential.Eachdayoftheweekhas4PeakTimesand4LightTimesthatcanbesetdifferently.

• WhenintheDHWSchedule,pressingtheNEXTbuttononthePlatinumcontroldisplaysthenextScheduleentry.

• PressingtheDAYbuttononthePlatinumcontroldisplaysthenextweekdayentry.• DomestichotwaterDemandSchedulecanbeaccessedontheICMSwebsitebyselectingSchedulesfromthePlatinumcontrolLiveSessionthenselectingtheDHWDemand.

- DHW DEMAND SCHED -

MON#1

Peak Time 6:00Am

Light Time 10:00Pm

Copy ScheduleSELECTMaintenance/DHW Settings/Copy Schedule• AftersettingtheMondaySchedule,theusercancopyitssettingstotherestofthedaysoftheweek.Thisreducessetuptime.

- DHW DEMAND SCHED -

Copy Mon Schedule

to all other days

(SELECT to Execute)

Internet alarms Through ICMSSensor Fault• IfanyofthesensorsfailedorweredisconnectedfromthePlatinumControl,thecontrolwillenergizetherespectiverelay.Makesurethattheboiler/waterheaterhasitsoperatingandlimitcontrolsinstalledandabletocontroltheboiler/waterheatertemperatureduringsensorfailuretoavoidhazardoussituations.

• Tosetupanalarmdeliveryforasensorfaultsituation,selectthesensorontheICMSwebsite.SelectAlarmDeliverySetupandthenAddDeliveryfortheSensorFault.

WaRnIngThe boiler/water heater must have its operating and limit controls installed and wired in a way so that the Supply sensor fault or DHW Energy Saver communication Error will

not cause a hazardous situation. It is the responsibility of the installer to make sure of the system operation and users safety during sensor fault or communication error.

Heat-Timer recommends the installation of a precision tempering valve, ETv, or TMC to help protect the output from excessive temperatures.

Communication Error• IftheDHWEnergySaverlostitscommunicationtothePlatinumcontrolformorethan1minute,itwillenergizebothoutputrelays.Makesurethattheboiler/waterheaterhasitsoperatingandlimitcontrolsinstalledandabletocontroltheboiler/waterheatertemperatureduringCommunicationErrorstoavoidhazardoussituations.

Troubleshooting and lEDsWhentheDHWEnergySavercoverisremoved,severalLEDswillbeavailableforviewing.TheseLEDsareusedfordiagnosingandtroubleshootingmanycommunicationandrelayoperation.• ApowerRedLEDindicatesthattheunithasthepropervoltagetooperate.• AGreenLEDblinkseverysecondtoindicatethereiscommunicationbetweentheDHWEnergySaverandthePlatinumcontrol.Ifthatcommunicationfails,thisLEDwillkeepblinkingfor15secondsthenitwillturnoff.Afteranadditional45seconds,thecontrolwillenergizebothoutputrelays.

• EachoftheoutputrelayshasaRedLEDthatisturnedonwheneverthatrelayisenergized.

DHW Energy Saver Installation and Configuration Manual 9

HT#

059

106-

00C

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5B A GND

16VAC

1 2~ ~

Typical Wiring for PlatinumSerial Panel TS485 Plug

HWRPlatinum

MADE IN U.S.A.

PREV.(DEL)

SAFETYGROUNDMUST BE

CONNECTED

OUTTEMP

DHWCAL

AUXTEMP 0

AUXTEMP 1

MENU FUNCTIONS

SELECT enters menus or accepts changes

ADJUST selects menu items or changes settings

BACK returns to previous menu

DAY selects next day

PREV./NEXT steps through output status

PUMP

LIN

E

NE

UTR

AL

DAYHELP NEXT

PRESS TOSELECT

BACK

MON 12/28/04 10:43Am

ADJUST

A1

A2

A3

A4

A5

A6

A7

A8

A9

A10

A11

A12

AUXTEMP 2

DO NOT APPLY ANY VOLTAGETO SENSOR TERMINALS

A13

A14

A15

A16

A17

A18

NETWORK

PROVE

SHUTDOWN

SYSTEMTEMP

CLOSE

OPEN(BYPASS)

ALL SENSORS MUST BEGOLD SERIES SENSORS

INPUTS

ROUTE SENSOR AND AUXILIARY WIRESTHROUGH THIS KNOCKOUT ONLY

BURNER

MOTORIZEDVALVE

CLOSE OPENOPTION

1OPTION

2

T

T

T

TGT= 126oF

Cut= 55oF Day

OD= 31oF SYS= 125oF

AUTO

AUXCLOCK

PUMP BURNERMOTORIZED

VALVE

CLOSE OPEN OPTION1

OPTION2

AUXCLOCK

T

TC O R P O R A T I O N

R

2 3 4 5 5A 6 7 8 9 11 12 13 14 15 16 17

OUTPUT RATINGS:120VAC, 6A RESISTIVE1A PILOT DUTY15A TOTALFOR ALL CIRCUITS

INPUT RATINGS:115VAC 60Hz30VA MAX

USE COPPER WIRE,CLASS 1 WIRE ONLY

ENCLOSEDENERGY

MANAGEMENTEQUIPMENT

99RA

PREV.(DEL)

OUTTEMP

DHWCAL

AUXTEMP 0

AUXTEMP 1

PUMP

DAYHELP NEXT

PRESS TOSELECT

BACK

A9

A10

A11

A12

AUXTEMP 2

A13

A14

A15

A16

A17

A18

BURNER

MOTORIZEDVALVE

CLOSE OPENOPTION

1OPTION

2

T

T

T

TGT= 126oF

Cut= 55oF Day

OD= 31oF SYS= 125oF

AUXCLOCK

PUMP BURNERMOTORIZED

VALVE

CLOSE OPEN OPTION1

OPTION2

AUXCLOCK

T

5 5A 6 7 8 9 11 12 13 14 15 16 17

Supply Sensor

Return SensorSensorShield

RecirculatingPump

ReturnSensor

SupplySensor

WaterHeater

Cold

Suggested Settings:Supply Set Point 130°FPeak Differential 5°FLight Differential 15°F

Return Set Point 120°FPeak Differential 5°FLight Differential 10°F

Heat-Timer is aware that each installation is unique Thus, is not responsible for any installation related to any electrical or plumbing diagram generated by Heat-Timer The provided illustrations are to demonstrate Heat-Timer’s control operating concept only

Piping/Wiring to Water Heater

Control Valve

Check ValveSensor Shield (Connect to O)

10 DHW Energy Saver Installation and Configuration Manual

HT#

059

106-

00C

10

Piping/Wiring to Boiler and Indirect Water Heater

Suggested Settings:Supply Set Point 180°FPeak Differential 10°FLight Differential 20°F (Steel Boiler)Light Differential 40°F (Cast Iron Boiler)Light Differential 60°F (Condensate Boiler)

Return Set Point 120°FPeak Differential 5°FLight Differential 10°F

Heat-Timer is aware that each installation is unique Thus, is not responsible for any installation related to any electrical or plumbing diagram generated by Heat-Timer The provided illustrations are to demonstrate Heat-Timer’s control operating concept only

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5B A GND

16VAC

1 2~ ~

Typical Wiring for PlatinumSerial Panel TS485 Plug

HWRPlatinum

MADE IN U.S.A.

PREV.(DEL)

SAFETYGROUNDMUST BE

CONNECTED

OUTTEMP

DHWCAL

AUXTEMP 0

AUXTEMP 1

MENU FUNCTIONS

SELECT enters menus or accepts changes

ADJUST selects menu items or changes settings

BACK returns to previous menu

DAY selects next day

PREV./NEXT steps through output status

PUMP

LIN

E

NE

UTR

AL

DAYHELP NEXT

PRESS TOSELECT

BACK

MON 12/28/04 10:43Am

ADJUST

A1

A2

A3

A4

A5

A6

A7

A8

A9

A10

A11

A12

AUXTEMP 2

DO NOT APPLY ANY VOLTAGETO SENSOR TERMINALS

A13

A14

A15

A16

A17

A18

NETWORK

PROVE

SHUTDOWN

SYSTEMTEMP

CLOSE

OPEN(BYPASS)

ALL SENSORS MUST BEGOLD SERIES SENSORS

INPUTS

ROUTE SENSOR AND AUXILIARY WIRESTHROUGH THIS KNOCKOUT ONLY

BURNER

MOTORIZEDVALVE

CLOSE OPENOPTION

1OPTION

2

T

T

T

TGT= 126oF

Cut= 55oF Day

OD= 31oF SYS= 125oF

AUTO

AUXCLOCK

PUMP BURNERMOTORIZED

VALVE

CLOSE OPEN OPTION1

OPTION2

AUXCLOCK

T

TC O R P O R A T I O N

R

2 3 4 5 5A 6 7 8 9 11 12 13 14 15 16 17

OUTPUT RATINGS:120VAC, 6A RESISTIVE1A PILOT DUTY15A TOTALFOR ALL CIRCUITS

INPUT RATINGS:115VAC 60Hz30VA MAX

USE COPPER WIRE,CLASS 1 WIRE ONLY

ENCLOSEDENERGY

MANAGEMENTEQUIPMENT

99RA

PREV.(DEL)

OUTTEMP

DHWCAL

AUXTEMP 0

AUXTEMP 1

PUMP

DAYHELP NEXT

PRESS TOSELECT

BACK

A9

A10

A11

A12

AUXTEMP 2

A13

A14

A15

A16

A17

A18

BURNER

MOTORIZEDVALVE

CLOSE OPENOPTION

1OPTION

2

T

T

T

TGT= 126oF

Cut= 55oF Day

OD= 31oF SYS= 125oF

AUXCLOCK

PUMP BURNERMOTORIZED

VALVE

CLOSE OPEN OPTION1

OPTION2

AUXCLOCK

T

5 5A 6 7 8 9 11 12 13 14 15 16 17

Supply Sensor

Return SensorSensorShield

DHWPump

Boiler

RecirculatingPump

ReturnSensor

SupplySensor

Cold

Indirect

Control Valve

Check ValveSensor Shield (Connect to O)

DHW Energy Saver Installation and Configuration Manual 11

HT#

059

106-

00C

11

DHW Energy Saver

Boiler Pump

6 7 8 9

COM

3 4 5B A GND

16VAC

1 2~ ~

Typical Wiring for PlatinumSerial Panel TS485 Plug

HWRPlatinum

MADE IN U.S.A.

PREV.(DEL)

SAFETYGROUNDMUST BE

CONNECTED

OUTTEMP

DHWCAL

AUXTEMP 0

AUXTEMP 1

MENU FUNCTIONS

SELECT enters menus or accepts changes

ADJUST selects menu items or changes settings

BACK returns to previous menu

DAY selects next day

PREV./NEXT steps through output status

PUMP

LIN

E

NE

UTR

AL

DAYHELP NEXT

PRESS TOSELECT

BACK

MON 12/28/04 10:43Am

ADJUST

A1

A2

A3

A4

A5

A6

A7

A8

A9

A10

A11

A12

AUXTEMP 2

DO NOT APPLY ANY VOLTAGETO SENSOR TERMINALS

A13

A14

A15

A16

A17

A18

NETWORK

PROVE

SHUTDOWN

SYSTEMTEMP

CLOSE

OPEN(BYPASS)

ALL SENSORS MUST BEGOLD SERIES SENSORS

INPUTS

ROUTE SENSOR AND AUXILIARY WIRESTHROUGH THIS KNOCKOUT ONLY

BURNER

MOTORIZEDVALVE

CLOSE OPENOPTION

1OPTION

2

T

T

T

TGT= 126oF

Cut= 55oF Day

OD= 31oF SYS= 125oF

AUTO

AUXCLOCK

PUMP BURNERMOTORIZED

VALVE

CLOSE OPEN OPTION1

OPTION2

AUXCLOCK

T

TC O R P O R A T I O N

R

2 3 4 5 5A 6 7 8 9 11 12 13 14 15 16 17

OUTPUT RATINGS:120VAC, 6A RESISTIVE1A PILOT DUTY15A TOTALFOR ALL CIRCUITS

INPUT RATINGS:115VAC 60Hz30VA MAX

USE COPPER WIRE,CLASS 1 WIRE ONLY

ENCLOSEDENERGY

MANAGEMENTEQUIPMENT

99RA

PREV.(DEL)

OUTTEMP

DHWCAL

AUXTEMP 0

AUXTEMP 1

PUMP

DAYHELP NEXT

PRESS TOSELECT

BACK

A9

A10

A11

A12

AUXTEMP 2

A13

A14

A15

A16

A17

A18

BURNER

MOTORIZEDVALVE

CLOSE OPENOPTION

1OPTION

2

T

T

T

TGT= 126oF

Cut= 55oF Day

OD= 31oF SYS= 125oF

AUXCLOCK

PUMP BURNERMOTORIZED

VALVE

CLOSE OPEN OPTION1

OPTION2

AUXCLOCK

T

5 5A 6 7 8 9 11 12 13 14 15 16 17

Supply Sensor

Return SensorSensorShield

RecirculatingPump

Boiler

Boiler HeatExchanger

ReturnSensor

SupplySensor

TemperingValve

Cold

Control Valve

Check ValveSensor Shield (Connect to O)

Piping/Wiring to Boiler and a Tempering valve

Suggested Settings:Supply Set Point 180°FPeak Differential 10°FLight Differential 20°F (Steel Boiler)Light Differential 40°F (Cast Iron Boiler)

Return Set Point 120°FPeak Differential 5°FLight Differential 10°F

Heat-Timer is aware that each installation is unique Thus, is not responsible for any installation related to any electrical or plumbing diagram generated by Heat-Timer The provided illustrations are to demonstrate Heat-Timer’s control operating concept only

Control Valve

Check ValveSensor Shield (Connect to O)

20 New Dutch Lane, Fairfield, NJ 07004 Ph: (973) 575-4004 • Fax: (973) 575-4052

http://www.heat-timer.comHT#

059

106-

00C

SpecificationVoltageInput . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16VAC(transformerprovidedminimum10VA)OutputRelays . . . . . . . 2N.O.(SPST).Eachamaximum⅛HPpumpor6Ampresistiveloadat120VAC/60HzOutputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DHWboiler/waterheaterandDHWpumpCommunication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RS485(3-wireA,Ground,andB)LEDs . . . . . . . . . . . . . . . . . . . . . . . 4(1Power(Red),2RelayOutputs(Red),1communication(Green))Dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-¾”x3-⅝”x1”Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Pound