    MM // ss .. SS HH R R EE EE CCEEMMEENN TT SS LLII MM II TT EE DD

    11 XX22 33 .. 55 MM WW CCEE MM EE NN TT PP LLAANN TT WW HH R R PP OO WW EE R R

    PP LLAANN TT AATT R R AASS ,, R R AAJJ AASS TT HH AANN ..

    DD EE SS II GG NN BB AASS II SS R R EEPP OO R R TT

    (ELECTRICAL)

    DOC NO: DALIANEAST-CCE-20006-DBR-XXX-800

    JULY 2013

    EE PP CC CCOO NN TTR R AACCTT OO R R

    M/s. DALIAN EAST NEW ENERGY DEVELOPMENT CO., LTD.

    DALIAN, CHINA .

    EENN GG II NN EE EER R II NN GG CCOO NN SS UU LLTT AANN TT

    CETHAR CONSULTING ENGINEERS LIMITED .

    ( 100% Owned by TRACTEBEL Engineering Pvt. Ltd)No.672/476, Ground FLOOR, TEMPLE TOWER

    NANDANAM, CHENNAI- 600 035,INDIA.

  • 8/9/2019 Design basis report.pdf

    2/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    2 of 27

    DALIANEAST-CCE-20006-DBR-XXX-800 /REV 00

    26.07.13 00 C.Sudarmathi P.Manivannan S.Manivel

    Document No. IssueDateRevNo. Prepared By Reviewed By Approved By

  • 8/9/2019 Design basis report.pdf

    3/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    3 of 27

    1.00.00. INTRODUCTION

    This Design basis report covers the features of Electrical system/

    equipment and design philosophy to be adopted for 1 x 23.5MW WHRB

    Power Plant at Shree Cement Limited, Ras, and Pali District- Rajasthan

    State. Detail engineering works would be carried out in accordance with

    the concepts developed in this report. This report covers the major

    features and design philosophy proposed to be adopted for the following Power Generation System and Evacuation (Via Tie feeder) Generator

    AVR Panel LAVT Panel NGR Panel Generator relay and control panel Synchronizing Panel segregated phase bus duct 11kV Switchgear Auxiliary distribution transformers Non- segregated phase bus duct

    LT PCC / MCC / APFC/DBs DC System Cabling system Plant lighting system Plant earthing and Lightning protection system

    2.00.00. PROJECT SITE DATA:

    Location : BangurCity, RAS Pali District,Rajasthan

    Altitude : 378.0 m above MSLAmbient air temperature : (Dry)

    - Minimum: 9C

    - Maximum: 48C

    Design temperature for : 50C electrical equipment

    Design relative humidity : 40%

    Basic wind velocity : 4.7 m/s

  • 8/9/2019 Design basis report.pdf

    4/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    4 of 27

    Average annual rain fall : 368.34 mm

    Seismic zone : Zone III

    3.00.00. CODES & STANDARDS

    All the electrical equipment and materials shall generally conform to

    Indian Standards and CBIP recommendations for power station design.

    Statutory guidelines of the following will also be observed in

    implementation of Power plant.

    Indian Factories act Indian Electricity Act Indian Electricity rules TAC (Fire protection) Regulations for electrical equipment Indian Standard Code. CBIP Recommendations. IEC. IEEE.

    3.01.00. Standards in below to be followed for the Respective equipment asper contract.

    Transformer : IS 2026 Circuit Breaker : IEC - 56 / IS 13118 LT Switchgear : IS 4237 / IS 4047 LT Cables : IS 1554 / IS 7098 Part I Current Transformer : IS 2705 Potential Transformer : IS 3156

    Earthing : IS 3043 Lightning Protection : IS 2309 Motors : IS 325 / IS 4029 Insulation Rubber mates : IS15652-2006

  • 8/9/2019 Design basis report.pdf

    5/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    5 of 27

    4.00.00. DESIGN CONSIDERATIONS

    The Electrical system will be designed based on the requirements for the

    safe, reliable performance, easy operation and maintenance of all

    equipments covered in this report and the associated electrical system.

    4.01.00. Basic Design Basis Data:

    Proposed Capacity : 23.5 MW Configuration & rating : 1 x 23.5 MW

    System Frequency : 50 Hz 5% Generation voltage : 11kV CPP Auxiliary Voltage : 11000V & 415V ( 10% ) DC System Voltage : 110V Control Supply Voltage : 110 V 10% for AC,

    110 V, - 15% for DC Design Max. ambient temp : 50 deg C Design life : At least 30 years Periodic maintenance interval: Greater than 4 years

    Environment : Tropical,dusty,chemical,laden,atmosphere

    VFD selection : VFD power selection shall be

    considered after derating at

    max. ambient temp

    4.01.01. Following fault levels will be considered for design of all electrical

    equipment at various voltage levels. Fault levels shall be restricted

    to the same.

    System Fault Level Duration

    11 KV System 40KA 1 seconds

    415 V System 50KA 1 seconds

    110 V DC System 10 KA 1 seconds

  • 8/9/2019 Design basis report.pdf

    6/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    6 of 27

    4.01.02. The system details at various utilization equipment voltages will

    be as given below

    S.No. Service Voltage PhaseSystem Neutral

    Earthing

    01. Generation 11 KV AC, 3Ph Low Resistance

    02.HV

    Distribution11 KV AC, 3Ph

    Non Effectively

    Earthed

    04. LV Panels 415V AC, 3Ph

    Solidly earth at

    transformer starpoint

    05. LV Motors 415V AC, 3Ph Earthed

    06.

    Lighting /

    Space

    heater

    Circuits

    230V AC,1Ph&N Earthed

    07. UPS 230V AC, 1Ph&N Earthed

    08. DC System 110V DC DC (2 Wires) Unearthed

    4.01.03. The system details at various utilization equipment

    Auxiliary/Control voltages will be as given below

    Sl.

    No.Service Voltage Remarks

    01. Control Voltage(HT Panel)

    110V DC Protection, Breaker controland indication

    02.Aux. Voltage

    (HT Panel)230 V UPS Metering

    03.Control Voltage

    (PCC)

    110V DC /

    AC

    Protection, Breaker control

    and indication

  • 8/9/2019 Design basis report.pdf

    7/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    7 of 27

    04.Aux. Voltage

    (PCC)110 V AC Metering

    05.Control Voltage

    (MCC)230V AC

    Breaker control and its

    indication

    06.Aux. Voltage

    (MCC)

    110V AC (2

    Wire)

    Feeder Control and its

    indication

    07.Aux.Voltage

    (MCC)

    240 V

    AC (2 Wire)

    Space heater/cubicle lamp,

    etc.

    5.00.00. System Configuration

    5.01.00. Power Generation & Evacuation

    One no rated 25 MW, 11kV at 0.8 pf and synchronous generator with

    brush less excitation system will generate power for the plant with

    excitation transformer.

    One number Evacuation feeder in HT panel will be used for evacuation of

    power.

    The Plant auxiliary supply will be taken through 2 nos of 2.5 MVA 11/0.433kV auxiliary distribution transformers.

    5.02.00. Plant start up power & Normal Running

    The plant start up power is fed through customer 11 KV Cement plant

    panel in Evacuation feeder. The plant auxiliaries are started through by

    closing evacuation feeder breaker which is connected to customer 11kV

    cement plant panel.

    Once the STG is started, the incomer breaker of the generator feeder

    connecting to the 11 kV switchgear at CPP can be closed i.e. the generator

    will be synchronized with the start-up supply source. When the STG is in

    service it will feed its own auxiliary loads and excess power will be

    evacuated through evacuation breaker.

  • 8/9/2019 Design basis report.pdf

    8/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    8 of 27

    6.00.00. Equipment Design

    6.01.00. Generator:

    The generator will be 2 poles, 50Hz, star connected, 3 phase type and it is

    designed for continuous operation at its rated output of 25 MW at 0.8pf.

    The cooling system will be closed air circuit water cooled (CACW) type.

    The generator will be capable of continuous operation at rated MVA &

    power factor at any voltage from 90% to 110% of rated voltage and within

    a frequency range of 45 to 55 Hz.

    The generator will be of cylindrical rotor design, degree of protection

    conforming to IP 54 for alternator & IP 54 for exciter. The generator will

    be provided with brushless digital excitation system. The generator is resin

    rich type with class F insulation and class B temp rise.

    6.02.00. AVR panel:

    The excitation system shall be with Microprocessor based Digital AVR with2 nos auto channel and 2 nos manual channel. The digital Auto excitation

    regulator will be fed through excitation transformer.

    6.03.00. LASCPT PANEL

    11 KV HT LASCPT panel shall include Surge Capacitor, Lightning arrestor

    Excitation transformers, and Potential transformers. Degree of protection

    for LASCPT Panel shall be IP55.

    Surge Capacitor : 12kV, 0.25F Lightening arrestor : 12kV, 10kA Excitation Transformer : 11KV / 220V, YD11 Potential transformers : 11 kV/3 /110V/3/110V/3/110V/3

  • 8/9/2019 Design basis report.pdf

    9/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    9 of 27

    The following table illustrates the Potential Transformers considered in

    LASCPT Panel.

    Sl.No PTs CORE 1 CORE 2 CORE 3

    1 PT 1

    CL 0.2, 100VA

    (For AVR Panel

    metering)

    CL 3P, 100VA

    (For GPR -2)

    CL 3P , 100VA

    (For GPR-2)

    2 PT 2

    CL 0.2, 100VA

    (For Generator

    Metering cum Syn

    Panel)

    CL 3P , 100VA

    (For GPR -1)

    CL 3P , 100VA

    (For GPR-1)

    3PT 3

    (Spare PT)

    CL 0.2, 100VA

    (Spare)

    CL 3P , 100VA

    (Spare)

    CL 3P , 100VA

    (Spare)

    6.04.00. NGR Panel :

    11 KV HT NGR panel having Current transformers for phase and standby

    E/F,63.51 Ohm Resistance , 100 Amps , for 30 sec, max limit up totemperature rise 375 deg C and Motorized neutral isolator with vacuum

    contactor. Degree of protection for NGR Panel shall be IP55 for enclosure

    and IP42 for resistance.

    Resistance : 11kV, 63.51 Ohm, 100A for 30 sec Vacuum contactor : 12kV, 400A

  • 8/9/2019 Design basis report.pdf

    10/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    10 of 27

    The following table illustrates the Current Transformers considered in NGR

    Panel.

    CTs RATIO CORE 1 CORE 2 CORE 3

    CT-1 100 / 1A

    CL : 0. 2, 10VA

    (Generator

    Metering Cum

    Syn Panel)

    CL:5P20,10VA

    (GPR-1)

    CL:5P20,10VA

    ( For GPR-2)

    CT - 2 2500 / 1A

    CL : 0. 2, 30VA ,

    Imag 15 (ForAVR Metering)

    CL : PS , KPV

    250 ( For GPR-2)

    -

    CT - 3 2500 / 1A

    CL : 0. 2, 30VA ,

    Imag 15

    (Spare)

    CL : PS , KPV

    250 (For GPR-1)-

    CT - 4 2500 / 1A

    CL : 0. 2, 30VA ,

    Imag 15

    (Spare)

    CL : PS , KPV

    250 (For

    Generator

    Metering cum

    Syn Panel)

    -

    6.05.00. Generator Relay panel.

    Protection of the generator shall be achieved through microprocessor

    based, 2 Nos Numerical relay (P-343), one as primary and the other as

    back up. This panel shall be of free standing, floor mounting, sheet steel

    enclosed type. Degree of protection shall be of IP55. The panel mainlyconsists of:

    Metering for Generator. Generator protection relay. Auxiliary relays for protection.

  • 8/9/2019 Design basis report.pdf

    11/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    11 of 27

    6.05.01. The following protections are envisaged in protection relay of

    generator-

    Generator Differential Relay (87G) Over Fluxing (24) Negative Phase Sequence (46) Non directional phase over current ( 50) Inadvertent Energisation (Dead machine) (50/27) Neutral voltage displacement / Residual over voltage (59N) Voltage restrained over current (51V)

    Non directional earth fault (51) Loss of Excitation (40) Generator VT fuse failure protection (60) Reverse power Relay (32 ) Low Forward Power protection (37) Under & over Frequency Relay (81U / 81O) Thermal over load relay ( 49) Rotor earth fault Relay (I & II stage) (64R) Stator earth fault Relay(51N)

    Circuit breaker failure protection Relay (CBFP) AC control Supply Failure Relay DC control supply Failure Relay 100% stator earth fault relay (27TN) Under Voltage Relay(27) Over voltage relay (59) Earth fault relay (64F) Master trip relay (86-T A&B, 86-G A&B, 86C) Trip circuit supervision relays (95)

    Check synchronizing relay(25C) Guard relay (25G) No volt relay (27 I) Auto synchronizer (25A) PT protection & supervision relay (60) CT protection & supervision relay MRU -4 relay far sensing HT Bus PT for df/dt

  • 8/9/2019 Design basis report.pdf

    12/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    12 of 27

    6.06.00. Generator Control , Metering cum Synchronizing Panel

    Considering various operating conditions of power plant Synchronizing

    facility will be provided as under:

    Auto, Manual synchronizing facility shall be provided for Generator

    breaker, evacuation feeder breaker, Spare Power Evacuation Feeder

    breaker and Generator incomer breaker will be provided through

    Auto/Manual selector switch in Generator Control, metering &

    synchronizing panel (GCMSP). Degree of protection shall be of IP55.

    To facilitate auto synchronizing one number Auto synchronizer shall be

    provided.

    To facilitate manual synchronizing of breakers, double voltmeter, double

    frequency meter, Synchroscope with cutoff switch, Synchro check relay,

    Live/ Dead bus synchronizing switch and necessary lamps will be provided.

    2 Nos 24 window annunciator shall be considered foe alarm and indication

    purpose. Emergency push button for Generator and turbine trip shall beprovided. All the meters shall be digital with 0.5 accuracy class.

    Transducers for 3P-4Wire MW (4 output), MVAr (2 Output), 3 Nos Voltage

    (Two output), Frequency (Two Output), 3 Nos Current (2 Output) shall

    be provided. It shall be programmable type with accuracy class 0.5%,

    4-20 milli Amps output & auxiliary supply shall be 230V AC.

    6.07.00. GENERATOR BUS DUCT ( SPBD)

    11 KV, 3 Phase 3200 Amps, Segregated Phase Bus dud (SPBD) shall be

    provided for generator Phase terminal to LASCPT Panel and Generator

    Neutral terminal lo NGR panel. Maximum allowable temperature rise on

    bus duct shall be 40 deg C and enclosure shall be 25 deg C. The degree of

    protection for enclosure shall be IP55.

  • 8/9/2019 Design basis report.pdf

    13/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    13 of 27

    6.08.00. High Voltage Switchgear:

    The following High Voltage switchgear is envisaged. The design basis of

    High Voltage switchgear will be as follows.

    Type : Metal clad, draw out Service : Indoor Rated voltage : 11kV rated current : 3200A Bus Bar Material : Copper

    Degree of protection : IP4X for enclosure Type of circuit breaker : VCB Duty cycle of breaker : O-0.3sec-CO-3min-CO Closing mechanism at CB : Spring charged stored energy Short Circuit Rating : 40kA for 1 sec

    6.08.01. FEEDER DETAILS

    Generator Feeder with PT 1 No. + 1 SPARE

    Transformer feeder (2.5 MVA) 2 Nos + 1 SPARE Power Evacuation feeder with PT 1 No. + 1 SPARE Bus PT 1 NO

    6.08.02. Protection & Metering Envisaged:

    The protections envisaged for different feeders are listed below. Main

    protective relays will be Numerical fixed type. However auxiliary relays will

    be electromechanical type only .

    A) 11 KV Incomer feeders:

    Instantaneous and definite time over current protection. (50/51) Directional over current and earth fault protection. (67/67N) Under voltage protection with timer (27+2) Trip circuit supervision relay(74)

  • 8/9/2019 Design basis report.pdf

    14/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    14 of 27

    Master trip relay(86)

    Anti pumping relay(94) DC Fail relay(27D)

    B) 11 KV Power evacuation feeder:

    Instantaneous and IDMT over current protection.(50/51) Directional over current and earth fault protection. ((67/67N) Cable differential protection (87C) Under voltage protection with timer (27+2)

    Trip circuit supervision relay(74) Master trip relay(86) Anti pumping relay(94) Neutral voltage displacement (59N) DC Fail relay(27 D)

    C) Auxiliary transformer feeder:

    Instantaneous and definite time over current protection.

    Instantaneous and definite time earth fault protection. Winding temperature protection (49 WT) Oil temperature protection (49 OT) Bucholz relay (63). Trip circuit supervision relay(74) Master trip relay(86) Anti pumping relay(94) DC Fail relay(27 D)

    D) Bus PT feeder

    Under voltage relay with timer (27+2) DC Fail relay(27 D) Voltage balance relay 60)

  • 8/9/2019 Design basis report.pdf

    15/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    15 of 27

    6.08.03. Metering:

    Incoming feeder shall be provided with energy meters of class 0.5

    accuracy, Digital Ammeter & Digital voltmeter. Auxiliary transformer

    feeder shall be provided with Energy meter and Ammeter. However

    evacuation feeder shall be provided with 0.2 accuracy class Trivector

    meter & Digital ammeter.

    6.09.00. LV Transformers:

    6.09.01. LV Auxiliary Transformers

    Auxiliary Transformers are Oil impressed type, 2.5 MVA rated ,2 x 100%

    capacity, 11/ 0.433kV, ONAN cooled, Dyn11 vector group, 8.25 %

    impedance, 99.5% efficiency at 50% load, 99.0% efficiency at 100% load,

    outdoor type. This transformer will be provided with off load tap switch

    having +5 to -5 % taps in steps of 2.5% on HV side. The LV side neutral

    of this transformer will be solidly grounded.

    The following assumptions as per normal power plant practice had beenmade in sizing the transformer

    Load factor = 0.8 for continuous load, 0.2 for intermittent load

    Coincidence factor = 0.05 for motorized valves, 0.5 for AC & heater

    unit, 1 for continuous load

    General:

    The flux density considered is 1.67 T for the core and yoke at the rated

    MVA, voltage & frequency. The transformer & all its accessories includingCTs shall be designed to withstand without any injury the thermal &

    mechanical effects caused due to short circuit fault. Transformers shall

    withstand, without injurious heating, the combined voltage & frequency

    fluctuations.

  • 8/9/2019 Design basis report.pdf

    16/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    16 of 27

    The transformer will be provided with following accessories and fittings:

    Double float type buchholz relay having alarm and trip contacts Dial type (150 mm) oil temperature indicator with alarm and trip

    contacts. Dial type (150 mm) winding temperature indicator (WTI) with

    alarm and trip contacts. Magnetic oil level gauge, with low level alarm contact. Tap position indicator (Local ) Jacking pads.

    Bi-directional flange wheels with suitable locking arrangement. LV neutral CT for LV REF protection and standby earth fault

    protection. Rating & Diagram Plate Earthing Terminals Lifting Lugs Radiators Silica Gel Breather Explosion Vent with Diaphragm

    Bottom drain cum Filter Valve Top Filter Valve Pressure relief valve.

    6.09.02. Lighting Transformers:

    Two no 2X100% dry type lighting transformer of 100 KVA, 415/415,

    Dyn11, AN, 8.25 % impedance, greater than 99.5% efficiency at 50%

    load, 99.0% efficiency at 100% load, 10% variations on secondary side

    in 2.5% steps shall be provided. Lighting transformer shall be of class Hinsulation with temperature rise limited to class F.

    6.10.00. NSPBD:

    415 V, 3 Phase + Neutral 4000 Amps TPN Sand witch type Non

    Segregated Phase Bus duct (NSPBD) shall be considered for connecting

  • 8/9/2019 Design basis report.pdf

    17/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    17 of 27

    between auxiliary distribution transformer and 415V PCC. Maximum

    allowable temperature rise on bus duct is 40 deg C and enclosure is 25deg C. The degree of protection for enclosure shall be IP54.Bus conductor

    & Bus enclosure shall be Electrolytic grade Aluminum & MS respectively.

    Bus bar material shall be of Aluminum flats grade 83401 WP, IS 5082

    6.11.00. Low Voltage Switchgear - 415V

    6.11.01. LTPCC:

    Type : Fixed type Service : Indoor Current Rating : 4000 A Short circuit Rating : 50kA for 1 Sec. Protection : IP4X Busbar material : Aluminium Maximum current density : 0.8A/mm2 Incomers : Two with 4000 A ACB breaker Closing/tripping of ACB : 110 V DC / AC

    The protections envisaged for different feeders were listed below.

    a) LTPCC Incomers:

    Instantaneous and IDMT over current protection (50/51) Instantaneous and IDMT earth fault protection (50/51N) Restricted earth fault relay (64R) Standby earth fault Relay (51N)

    Under voltage protection with timer(27+2) DC failure relay (27 D)

    b) LTPCC outgoing feeders

    Thermal & magnetic releases for overcurrent & short circuit

    protection shall be provided.

  • 8/9/2019 Design basis report.pdf

    18/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    18 of 27

    c) LTPCC Bus PT feeders

    Under voltage relay (27)

    Metering:

    Energy meter shall be provided in the all incoming and outgoing feeders of

    PCC. Analog type ammeter and voltmeter with selector switch shall be

    provided on the incoming feeders. For Bus PT feeders voltmeter with

    selector switch will be provided

    6.11.02. MCC

    MCC shall be double front as per the contract. MCC shall have uniform

    height placed side by side.

    Type : Free standing fixed type Service : Indoor Short circuit Rating : 50kA for 1 Sec.

    Current Rating : as per requirement Enclosure : IP 52 Rated voltage : 415V Maximum current density : 0.8A/mm2 Bus bar Material : Aluminum Incomers : Two

    The CPP shall have following MCCs:

    TG MCC

    Boiler MCC (1 No for each PH + 1 No for each AQC) A/C, P&V MCC ACC & CWS MCC WTP MCC ACDB, MLDB, DCDB APFC MCC Emergency MCC

  • 8/9/2019 Design basis report.pdf

    19/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    19 of 27

    6.12.00. 415V Motors

    Motors are of TEFC IP55 enclosure with Class `F insulation with a

    temperature rise limited to Class `B. LT motors shall have premium

    efficiency (IE-3 type). Protection class shall be IP65. All the S1 Duty Cycle

    (continuous running) motors shall be compatible with VFD (Inverter grade

    for VFD application).

    Local Push Button Station (LPBS) shall be provided for all the motors and

    MOV's (for VFD LPBS shall have RPM meter and raise lower push buttons).

    For motors 3.7 kW and above ,LPBS shall be equipped with Ammeter.

    All motors below 75 kW: 415V rated, 3 phase/SFU+110 V (from MCC) AC

    control contactor + O/L relay with single phase preventer

    From 75 kW and above : 415 V rated, 3 phase contactor/ circuit controlled

    from MCC through Digital motor protection relay with bearing temp.

    For above 22kW motors ammeters shall be provided. For above 30kW

    motors Space heaters shall be provided. For 75kW and above motorsbearing & winding temperature monitoring shall be provided.

    7.00.00. DC system

    One no 800AH 1X100% (2V X 55), 110 Volts , 2 wire ungrounded system ,

    four (4) hours back up Vented type Plante Lead acid Battery of adequate

    capacity with their Float cum Boost charger shall be considered for DC

    loads with associated FRP battery racks etc..

    110 V DC power supply is the most reliable source of power supply for

    control, protection, interlock and annunciation requirements of the power

    station.

  • 8/9/2019 Design basis report.pdf

    20/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    20 of 27

    The rating of charger will be calculated as below:

    Float charger:

    Continuous DC load + trickle charging current of battery +15 % margin.

    Boost charger

    Boost charging current of battery+ continuous DC load.

    Float cum Boost charger:

    Boost charging current of battery.

    Battery Charger

    Type - One float and float cum Boost charger Voltage regulation - 110V 1% Service - Indoor Enclosure - Sheet steel Degree of protection - IP 42 AC input - 415V, 3ph, 3W, 50Hz, 50kA

    Busbar Material Aluminum

    7.00.01. DC Distribution Board

    DC Distribution Board constructional features will be given below

    Type - Fixed type NON-Compartmentalized Service - Indoor Enclosure - Sheet steel

    Degree of protection - IP 42 Short circuit rating - 10kA for 1 sec (Tentative) Bus bar Material Aluminium

  • 8/9/2019 Design basis report.pdf

    21/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    21 of 27

    8.00.00. Auto Power Factor Correction Panel

    2 Nos x 500 WAR , 113 STEPS (50 KVAR OF -10 Nos ) capacitor units shall

    be hermetically sealed type, with two bushings and shall be designed to

    carry a minimum of 1 .5 times the rated current at 110% of rated voltage

    and 1.35 times rated reactive power, continuously. The capacitors should

    be of non PCB type, suitable for operation in tropical areas

    9.00.00. Cabling System:

    9.01.00. Cables:

    9.01.01. HT Power cable

    HT power cable used for 11 kV systems will be 12.7/22kV (E) grade.

    The cable will be heavy-duty, stranded Aluminum conductor with FRLS,

    conductor screened with semiconductor, extruded XLPE insulation and

    insulation screen (semiconductor +copper tape), extruded PVC inner

    sheath, G.S flat (for multi-core)/aluminium wire (for single core) armoured

    and extruded PVC (ST-2) outer sheathed conforming to IS7098 part-II.Maximum operating temperature under normal condition for XLPE

    insulation cables will be 90C. Trefoil Clamps for HT Cable shall be

    provided.

    The following rating of HT cable XLPE (UE) insulated shall be

    envisaged for the Plant

    LASCPT panel to HT switch gear panel - 4RX 1C X 630 Sq.mm/ph

    GPP-4 HT panel to Existing HT Panel for power evacuation - 4R X1C X 630 Sq.mm/ph

    GPP-4 HT Panel to Auxiliary transformer 1 & 2 - 1R X 3C X 300

    Sq.mm

  • 8/9/2019 Design basis report.pdf

    22/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    22 of 27

    9.01.02. LT Power cable

    LT power cable used for 415V AC, 230VAC, 110V AC & 110 V DC system

    will be 1.1kV (E) grade, stranded aluminum conductor with FRLS, XLPE

    insulated, not extruded PVC inner sheath, G.S. Flat/round wire with

    armoured, extruded PVC (ST-2) outer sheath conforming to IS 7098 part-

    I. Maximum operating temperature under normal condition for XLPE

    insulation cables will be 90C. Cables less than 10 sq.mm shall be of

    copper conductor. DC Power cables for EOP will be UNINYVIN CABLE &

    Cable for UPS will be Copper armour cable. Separate earthing cable shall

    be laid from each VFD to respective Motor.

    9.01.03. Control cable

    Control cables will be 1100V (E) grade, multi-core with stranded 1.5 mm

    and copper conductor with FRLS, PVC insulated, extruded PVC inner

    sheath, G.S. flat / round wire armoured and extruded sheath of PVC (ST-

    1) with numbering of all cores, conforming to IS 1554 part-I/IS 5831.

    9.02.00. Cable Tagging

    Cable tagging shall be at both end & at every 20 meter considered for all

    cable. Anodised type tagging plate will be provided.

    9.03.00. Cable Trays

    Cables laid in overhead racks shall be GI ladder/perforated type trays for

    electrical/instruments with proper prefabricated bends respectively in

    outdoor areas and supports shall be MS (painted). The top cable tray shallbe covered with GI sheet canopy/GI sheet covering in outdoor cable racks.

    All outdoor cable racks shall be vertically oriented. Galvanized cable trays

    for Boiler, Turbine, ACC and BOP area shall be supplied. For WTP area all

    cable tray shall be FRP type only.

  • 8/9/2019 Design basis report.pdf

    23/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    23 of 27

    Separate cable tray for HT Power, LT Power, Control Cable, Instt. Analog

    Input/output cable each, Instt. Digital Input/output cables each &Compensating Cable shall be considered.

    No. Of Cable layers per Cable tray shall be as follows:

    HT Power Cable & LT Power(up to 120 mm2) Cable - One Layer LT Power Cable (below 120mm2) - Two Layer Control Cable - Three Layer Instt. Cables - Three Layer

    10.00.00. llumination System:

    10.01.00. Basic Concept

    The system provides lighting and service power at 240V, single phase 50

    Hz to receptacles and single phase feeders in plant areas. The plant

    illumination system includes normal cum Emergency lighting and critical

    DC lighting.

    10.02.00. 100 % Normal cum Emergency A.C lighting

    Normal cum Emergency A.C. lighting will be provided by lighting fixtures

    distributed throughout the plant. Separate circuits with timers will be

    provided where round the clock lighting is not required. Lighting fixtures

    will be fed from respective area lighting panels, which in turn receive

    supply from lighting distribution board. MLDB shall be provided with Dual

    incomer. LDBs shall be equipped with 30 mA ELCB. In Normal condition

    the Main lighting distribution board will be fed from 415V PCC &Emergency MCC through 2 x 100%, lighting transformer. In blackout

    condition then the supply for MLDB shall be fed from Emergency MCC

    (which is connected to Customer DG set) through lighting transformer .

  • 8/9/2019 Design basis report.pdf

    24/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    24 of 27

    10.03.00. Emergency DC Lighting

    Critical DC lighting will be provided with bulk head lamps at Cable Cellar

    MCC room, CCR, TG house, stair cases, steam drums on all boilers & Start

    up vents. This DC lighting will remain OFF normally and will be switched

    ON automatically when main AC supply fails. The power supply for lighting

    will be fed from 110V DCDB. FL DC lamp with integral battery shall be

    provided for Boiler area MCC room.

    10.04.00. Power Receptacles / Welding Sockets

    1 Phase & 3 Phase power receptacles will be provided for alternative floors

    of Boiler area, each floor ACC areas and at least 3 Nos in TG building, MCC

    room, cable cellar area. 3 Phase Welding Sockets will be provided at each

    stage of boiler, TG Floor & as required in ACC area etc. 24 Volt AC power

    receptacles with transformers and proper distribution at all location of

    boilers, ACC floors will be provided.

    10.05.00. The type of fixtures & type of luminaries for different areas is

    listed below:

    Area Description Type of Fixture Type of LuminariesCable gallery,Transformer AreaCompressor room,Battery charger room,P&V room & Storeroom

    Industrial Trough Type 2x28 W FluorescentLamp

    MCC Switchgear roomIndustrial Trough typewith ReflectorArrangement

    2x36 W FluorescentLamp

    Battery rooms Corrosion Proof 2x36 W FluorescentLampControl Rooms & Officerooms

    Industrial Trough typewith mirror optics

    2x28 W FluorescentLamp

    Turbine houses Integral Well glassIndustrial type 1 X 80W HPMV

    TG Building Operatingfloor

    Industrial type highbay 1x400 W MH Lamp

    TG Building Staircases Industrial Trough Type 2x36 W FluorescentLamp

  • 8/9/2019 Design basis report.pdf

    25/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    25 of 27

    Boiler area, Boilerplatforms ACC, & WTP

    Integral Well glassIndustrial type

    1x70 W MH Lamp

    Toilet areas Integral Well glassIndustrial type1 X 36 W Fluorescent

    Lamp

    Street Lights & Outdoorlights

    Integral Well glassIndustrial type withtimer arrangement

    1 x 150 W MH Lamp

    DC lights in TG Building Bulk head type 1X 100W GLSDC lights in Boiler areaMCC room

    FL with integral batterytype

    2x28 W FluorescentLamp

    11.00.00. Earthing & Lightning Protection System

    11.01.00. Plant Earthing:

    System earthing will be adopted to facilitate earth fault relaying and to

    reduce the magnitude of transient over-voltage. The system earthing

    involves earthing of the neutrals of generator. Low impedance earthing is

    used for 11 KV system to limit the earth fault current to about 100 A by

    grounding generator neutral by means of Neutral Grounding Resistor

    (NGR).

    A ground grid of 32mm MS Rod will be provided encircling the plantthrough a system of grounding electrodes and pits to keep ground

    resistance less than one ohm. Earth mat shall be laid below 500mm below

    absolute ground level and earth pits shall be 1.5 meter away from nearby

    building walls. Every electrical system will have dual earthing.

    Treated earth pits will be considered for generator NGR, Aux. Transformer

    Neutral, lightning arrestor & equipments. All Earthing electrodes shall be

    of Gel type maintenance free (homogeneous readymade mixture).

    All instrument earth pits shall be maintenance free and configuring delta

    spaced by 6 meter with redundant copper cable connection.The underground grid shall be connected with lightning protection earth

    electrodes below ground at average depth of 500 mm.

  • 8/9/2019 Design basis report.pdf

    26/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    DALIANEAST-CCE-20006-DBR-XXX-800 / REV 00

    DESIGN BASIS REPORT(ELECTRICAL ) Page

    26 of 27

    11.01.01. Equipment Earthing:

    Electrical equipment shall be provided with two separate and distinct

    grounding pads, each complete with tapped hole, galvanized bolt and

    spring washer for connection to station ground conductors.

    The neutral of generator and transformer shall be earthed through two

    dedicated earth pits.

    Flat from the main earthing grid to local network and electrical equipment

    will be GI flats of suitable size, except for smaller items, which will beconnected using steel wire. However, for portable equipment, if one of the

    conductors of the connecting cable/plug socket is earthed, no other earth

    connection is required.

    An earthing conductor will be installed along the entire length of top most

    power cable trays. The tray earth will be connected at various locations to

    the station earth grid. The offsite areas will be connected through the

    earth flats running along the cable trays. Earth continuity will be provided

    for all cable trays & conduits. The following aspects will be addressedduring design, of the equipment earthing system to be adopted.

    Availability of sufficient earth current for effective relaying. Stabilization of circuit potential with respect to earth.

    The size of earth conductor used for individual equipment earthing

    Main Ground Conductor: 32 mm MS rod

    Earth Electrodes : MS Rod 32 mm dia, 3 m long pipe Generator and Transformer Body: 75 mm x 10 mm GI Flat. Transformer and Generator Neutral: 75 mm x 10 mm GI Flat. HT switchgear Panels: 50 mm x 6 mm GI Flat. 415V PMCC, MCC, DCDB, MLDB Structures, Bus duct, Control

    Panel, Cable Trays: 50 mm x 6 mm GI Flat.

  • 8/9/2019 Design basis report.pdf

    27/27

    M/s DALIAN EAST NEW ENERGY DEVELOPMENTCO.LTD

    1X23.5 MW WASTE HEAT RECOVERY POWER PLANT

    FOR SHREE CEMENTS LIMITED, RAS, RAJASTHAN

    LT AC Motors from 110kW up to 132 KW: 50 mm x 6 mm GI Flat.

    LT AC Motors above 30kW up to 90 KW: 25 mm x 6 mm GI Flat. LT AC Motors from 5.5kW up to 30 KW: 25 mm x 3 mm GI Flat. LT AC Motors below 5.5 KW : 8 SWG GI wire Local Panels, LPBS, Switch sockets, LDBs, JB,Receptacles: 8 SWG

    GI wire

    11.02.00. Lightning Protection:

    The main purpose of the lightning protection system is to provide

    protection to structures from lightning strokes and provide a lowresistance-conducting path for lightning discharge to earth. For metal

    structures, which are continuous down to the ground level, no lightning

    protection is required except adequate grounding connections. Air

    termination network with down conductor and earthing electrodes will be

    provided on the basis of IS-2309 recommendations.

    The zone of protection will depend on each structure height, overall shape,

    and physical location in relation to other structures.