383
 Catalogue 2010/2011 Surge Protection BITZDUCTOR ® XTU ML4 (2) BD 0-180 New combined lightning curre nt and surge arrester with actiVsense technology Automatically detec ts the operating voltage of the wanted signal Optimally adjusts the voltage protecti on level to the signal voltage currently applied DEHNguard ® M ... CI 275 (F M) No additional backup fuse required due to arrester backup fuse integrated in the protection module Prewired,modular surge arrester for 230 /400 V systems consisting of a base part and plug-in protectionmodules BXT ML4 BE C 12 BXT combined lightning curren t and surge arrester module with LifeCheck for protecting 2 pairs Specifically coordin ated with applications with diode circuit at the input,current loops (TTY) and opto- coupler inputs DRC LC M3+ Test Device For fast testing of LifeChec k-equipped SPDs Handheld device , easy transpor t and operation With database function for the documen tation of results BXT ML2 B 180 TYPE 1 lightning current arrester module, with LifeCheck monitoring system Two-pole device with direct shield earthing Suitable for almost all applica tions BXT ML2 BD HF EX 6 BXT surge arrester modul e with LifeCheck for use in hazardous areas For protecting one pair of intrinsicall y safe circuits and RS485 bus systems Self-capacitanc e and self-inductance negligibly small DEHNguard ® S CI 275 (FM) No additional backup fuse required due to arrester backup fuse integrated in the protection module Universal surge arrester consis ting of a base part and a plug-in protection module with integrate d backup fuse DEHNguard ® M YPV SC I ... FM Prewired,modular surge arrester for use in phot ovol- taic systems consisting of a base part and plug-in protectionmodules Combined disconnectio n and short-circuiting device with safe electrical isolation in the protection module prevents fire damage due to d.c.arcs See page 69 See page 75 See page 104 See page 179 See page 195 See page 362 See page 316 See page 191

Dehn Prenaponska zaštita

Embed Size (px)

DESCRIPTION

OO

Citation preview

Page 1: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 1/382

Catalogue 2010/2011

Surge Protection

BITZDUCTOR® XTU ML4 (2) BD 0-180

• New combined lightning current and surge arrester

with actiVsense technology

• Automatically detects the operating voltage of the

wanted signal

• Optimally adjusts the voltage protection level to the

signal voltage currently applied

DEHNguard® M ... CI 275 (FM)

• No additional backup fuse required due to arrester

backup fuse integrated in the protection module

• Prewired,modular surge arrester for 230/400 V

systems consisting of a base part and plug-in

protection modules

BXT ML4 BE C 12

• BXT combined lightning current and surge arrester

module with LifeCheck for protecting 2 pairs

• Specifically coordinated with applications with diode

circuit at the input,current loops (TTY) and opto-

coupler inputs

DRC LC M3+ Test Device

• For fast testing of LifeCheck-equipped SPDs

• Handheld device, easy transport and operation

• With database function for the documentation

of results

BXT ML2 B 180

• TYPE 1 lightning current arrester module,

with LifeCheck monitoring system

• Two-pole device with direct shield earthing

• Suitable for almost all applications

BXT ML2 BD HF EX 6

• BXT surge arrester module with LifeCheck for use in

hazardous areas

• For protecting one pair of intrinsically safe circuits

and RS485 bus systems

• Self-capacitance and self-inductance negligibly small

DEHNguard® S CI 275 (FM)

• No additional backup fuse required due to arrester

backup fuse integrated in the protection module

• Universal surge arrester consisting of a base part

and a plug-in protection module with integrated

backup fuse

DEHNguard® M YPV SCI ... FM

• Prewired,modular surge arrester for use in photovol-

taic systems consisting of a base part and plug-in

protection modules

• Combined disconnection and short-circuiting device

with safe electrical isolation in the protection module

prevents fire damage due to d.c.arcs

See page 69

See page 75

See page 104

See page 179

See page 195

See page 362

See page 316

See page 191

Page 2: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 2/382

DEHNguard® M ... 150/320/385/440 (FM)

• Prewired,modular surge arrester consisting of a base

part and plug-in protection modules

• New models with a max. continuous operating voltage

of 150 V,320 V,385 V and 440 V

BITZDUCTOR® VT ALD 36

• Energy coordinated combined lightning current and

surge arrester

• For protecting earth-free d.c.supply systems up to

nominal currents of 4 A

• Low voltage protection level,suitable for sensitive

terminal equipment

DPRO 230 LAN100

• Dual surge protection for power supply systems and

LAN interfaces

• Gigabit Ethernet protection (1000 Base-T) with an

elegant design

DEHNguard® S VA (FM)

• Universal surge arrester consisting of a base part and

a plug-in protection module

• Leakage-current-free series connection of a varistor

and a spark gap in the plug-in protection module

DK 25 Feed-Through Terminal

• For changing the wiring level

• Supports lightning-impulse-current-conform

installation of SPD combinations

NET PRO 10X TC1 RST

• Compact and cost-effective protective board with 10

RJ45 ports for the protection of telecommunications

systems

• Input equipped with cage spring terminals which can

be removed as a block for easy line measuring

• Integrated protection against power crossing

IGA 10 V2 IP54

• Enclosure for the installation of surge arresters,

tested with lightning impulse currents

• Degree of protection of IP54

• Sealable

EG NET PRO 10X 19”

• 19“ (482.6 mm) stainless steel enclosure for installati-

on into distribution cabinets

• For up to 5 NET PRO 10X TC1 RST protective boards

• Compact in design, protection of up to 50 ports over

a vertical module

EG NET PRO 10X 3HE

• Stainless steel enclosure,3 vertical modules for instal-

lation in 19“ (482.6 mm) distribution cabinets

• For NET PRO 10X TC1 RST protective boards

• Ideally suited for small-sized distribution boards

DEHNgate DGA LG 7 16 X

• Coaxial surge arrester for HF technology

• For multi-frequency applications with d.c. supply system

• Optionally available with self-extinguishing gas dischar-

ge capsule up to nominal currents of 2.5 A

• Maximum transmission and PIM performance

Pipe Clamp for Use in hazardous Areasfor Diameters from 26.9 mm to 500 mm

• For installation in potentially explosive atmospheres

(hazardous zones 1 and 2 as well as 21 and 22)

• Tested according to explosion group IIB

• Considerably reduced installation time

DEHNpipe DPI CD HF EXD 5 M

• Flameproof surge arrester for use in hazardous areas

• For protecting measuring circuits and bus systems

• Easy installation on field devices with a spare cable

gland

BXT ML2 BD DL S 15

• BXT combined lightning current and surge arrester

module with LifeCheck monitoring system

• Specifically coordinated with the requirements for

Dupline buses

• Terminals for direct and indirect shield earthing

DEHNbloc® Maxi NH00 255

• Coordinated, spark-gap-based lightning current arres-

ter with a discharge capacity up to 25 kA (10/350 µs)

• No tripping of 32 A gL/gG fuses up to short-circuit

currents of 50 kArms

DEHNbloc® M 1 320 (FM)

• Coordinated,spark-gap-based lightning current arres-

ter with a max. continuous operating voltage of 320 V

and a discharge capacity up to 25 kA (10/350 µs)

• No tripping of 32 A gL/gG fuses up to short-circuit

currents of 50 kArms

See page 49

See page 112

See page 252

See page 252

See page 46 (47)

See page 198

See page 252

See page 351

See page 76

See page 146

See page 276

See page 145

See page 223

See page 309

DEHNpipe DPI CD EXD 230 24 M (N)

• Dual surge protection for 230 V power supply systems

and data interfaces

• Easy installation on field devices with a spare cable

gland

• Approved for hazardous areas due to flameproof

enclosure

See page 341

See page 310

w

P

o

s

Page 3: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 3/3821

100th Anniversary of DEHN. 2

DEHN – Worldwide. 8

DEHN – Safety according to Specification. 10

Surge protection forPower Supply Systems 15

SPDs for low-voltage installations and equipment

Contents 17

General information 367

Index 372

Surge protection forInformation Technology Systems 153

SPDs for IT installations and equipment

Contents 155

Surge protection forPower Supply and Information Technology Systems 337Combined adapters

Lightning Equipotential Bonding 343Isolating spark gaps and components

Measuring and Test Devices 359

Contents

Valid from 1st April 2010This catalogue replaces the Surge Protection Main Catalogue published in 2008. We reserve the right to introduce changesin performance,dimensions and material in the course of technical progress.The figures shown are without obligation.Misprints,errors and alterations excepted.Reproduction in any form whatsoever is forbidden without our authorisation. Publication No.DS570/E/2010

Page 4: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 4/3822

100th Anniversary of DEHN....from a workshop to an

industrial enterprise

In our great-grandparents’ timeelectricity was by no means amatter of course. In the early20th century sufficient illumina-tion used to be a luxury and aprivilege of the upper class.

Electricity was at best availablein large cities but rarely in ruralareas. The first long-distancetransmission of alternating cur-rent took place in 1891.At that time Oskar von Millersucceeded in transporting elec-trical energy for the first timeover a distance of 176 kilome-tres from Lauffen / Neckar toFrankfurt / Main via a high-

voltage power line (20 kV).This marked the breakthroughof the transmission of alternat-ing current and was a signifi-cant step forward. But it wasstill a long way to go beforethe total population was effi-ciently and reliably suppliedwith electricity. It was only inthe early 1920s that electricitywas made accessible to manysmall towns for the first time.

During this eventful time, HansDehn founded his electricalinstallation company in Nurem-berg on 21st January 1910.

Now, many years later, and yetwithin a comparatively shortperiod of time, which was char-acterised like no other by thechangeful history of Germanyand its people, success and set-

back, war, reconstruction andeconomic crisis, DEHN celebrat-ed its 100th anniversary on21st January 2010.

Starting as a small electricalinstallation company, DEHNbecame a globally operatingfamily-owned company.

The following pages showsome milestones in the com-pany’s history of 100 years.

On 21st January 1910 the electrician Hans Dehnlaid the foundation for today’s company whenregistering an electrical installation business inNuremberg.

Since electric current had to be transported to theconsumer, building installation and particularlythe construction of overhead lines were the mainfields of activity for DEHN electricians under themanagement of Hans Dehn.

1910

After the first successful business years, a sub-sidiary is opened in Neumarkt i.d.Opf. locatedabout 45 km southeast of Nuremberg toadvance electrification in Upper Palatinate.

1921

Apart from overhead lineconstruction and building

installation, the installation of lightning protec-tion systems on buildings is an integral part of our business activities. Hans Dehn also starts todevelop and manufacture lightning protection

and earthing components.

1923

The company grows year after year and HansDehn’s sons Walter and Willy become partners.From now on, the family-owned company oper-ates under the name of DEHN + SÖHNE. In1941 the youngest son Richard becomes apartner.

1933

Hans Dehn quite early deals with lightning pro-tection. His first patent in this field is grantedin 1918.

1918

Page 5: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 5/3823

The Second World War inevitably slows downbusiness development. The premises in Nurem-

berg and Neumarkt are considerably damagedduring the war. Highly motivated, the familystarts reconstruction.The starting point for post-war activities inNeumarkt was a warehouse built in the lastmonths of the war near Hans-Dehn-Straßewhere our head office is located today.

1939 – 1945

The decision to builda hot dip galvanisingplant in Neumarkt

paves the way forthe extension of thesubsidiary to a pro-duction site.

1948

In the post-war period, businessbegins to pick up again:DEHN + SÖHNE presents light-ning protection and earthingproducts at the Hanover tradefair for the first time. Theincreasing market demand

requires a further extension of the production facilities inNeumarkt.

1952

DEHN seizes the opportunity to market itsproducts abroad: Austria becomes the firstexporting country.

1953

Due to our technical expertknowledge and entrepreneurialvision, we are the world’s first

manufacturer to realise thatexternal lightning protectionhas to be combined with inter-nal lightning protection.The first generation of surgeprotective devices is launched.

1954

The third product field besideslightning and surge protection -safety equipment - is launched.

The ball pin patented for DEHN+ SÖHNE in 1953 significantlyinfluences the state of the art.

Page 6: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 6/3824

The pioneering innovation of the separableearth rod considerably complements the rangeof earthing components and is still in greatdemand today.DEHN + SÖHNE becomes well-known in thefield of earthing technology.

1958

The product range is continuously complement-ed, especially in the field of surge protection.New protective devices such as VA 280 andBLITZDUCTOR are presented on the market.

1970 – 1980

The first lightning current carrying surgearrester enters the market: VGA 280/4, alsoknown as DEHNventil. It globally becomes asynonym for a new generation of surgearresters. DEHN + SÖHNE captures a leadingposition in the sector of surge protection.

1984

Foundation of DESITEK A/S in Denmark. It isthe first of today’s 10 sales companies in for-eign countries.

1988

The success story of surge protection startswith VM 280, the world’s first arrester with amodular width of 17.5 mm.

1986

The KS connector is devel-oped to reliably connectcircular conductors to flatprofiles.

1956

The universal MV clamp from our lightningprotection portfolio is launched.

In Switzerland DEHN + SÖHNE participates in theELVATEC AG, which has been distributing DEHNproducts on the Swiss market for several years.

1990

Page 7: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 7/3825

Development and implementation of the masterplan DEHN 2000.A milestone in the company’s history:DEHN+SÖHNE prepares for the future.National and international success requires com-prehensive restructuring, reorganisation andreorientation.

1991

The new energy-coordinated Red/Line arrester family for low-voltage consumer‘sinstallations is launched.Surge protective devices such as DEHNport and DEHNguard start their story ofsuccess.Red/Line becomes the general term for all protective devices for use in powersupply systems.

1993

The new energy-coordinated Yellow/Linearrester family for the protection of data tech-nology and automation systems, including thekey product BLITZDUCTOR CT, is another mile-stone of our research and development.

1996

The positive development in Spain requires newdistribution channels. DEHN IBERICA S.A. is found-ed in co-operation with our long-standing partner.

1992

In this year DEHN + SÖHNE is ready to makethe leap to America. DEHN Inc. is founded.

DEHN POLSKA Sp. z o.o. is founded in Warsawto serve the Polish market more efficiently.

1999

Foundation of DEHN & FILS in Strasbourg, laterrenamed in DEHN FRANCE S.a.r.l.

1998

To intensify our activities in England DEHN (UK)Ltd. is founded near Manchester.

1994

In co-operation with our long-time partner on the Italianmarket DEHN ITALIA S.p.A. is founded in Bozen.

After almost 50 years on the Austrian market, asubsidiary is founded, DEHN AUSTRIA GmbH.

2000

Page 8: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 8/3826

Safe and functional arresters with a unique design. The new Red/Line andYellow/Line product families are presented on international trade fairs in Hanoverand Frankfurt.

2006

In 2006 DEHN + SÖHNE was the first companyto obtain VdS certification for surge protective

devices.

DEHN Surge Protection(Shanghai) Co.Ltd is founded inShanghai to service the Chinesemarket, which has been workedby an agent since 1992.

2005

50 years of surge protection byDEHN + SÖHNE.In 1954 only few believed in thesuccess of surge protection.Today surge protective devicesare an essential part of electricalinstallations.

2004

The HVI conductor is a milestone in externallightning protection.The separation distance can be easily main-tained even in case of challenging architecturaldesign by using the new, high-voltage-resistantdown conductor.

2003

Completion of the new administration buildingon Hans-Dehn-Straße.

The successful DEHNventil has a strong succes-sor: The new DEHNventil.It is a perfect all-in-one solution with completedevices for all system configurations(TN-C, TN-S, TT).

2002

Moreover, the master plan is continued:Move into new production facilities for surgeprotective devices.

Page 9: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 9/3827

On 21st January 2010 DEHN + SÖHNE celebrates its 100th anniversary – a timefor joy, pride and review.During our history of 100 years, showing and pioneering new ways in the field of lightning protection has always been a major concern.

We provide protection against lightning, surges and possible hazards of electricity –a triumvirate of safety.

Lightning protection

Surge protectionSafety equipment

DEHN – your safety is our concern.

www.dehn.de

2010

Evolution of safety – DEHNguardSCI is a surge protective devicefor PV systems which combineseffective surge protection withthe protection of persons andfire protection.

2009

The new space-saving DEHNrecord MCM XTcondition monitoring system acts like an earlywarning system generating a fault messageeven in the event of imminent arrester over-load.Thus faults can be identified in advance andprecise status messages support maintenancestaff in diagnosing these faults.

2008

Completion of a new three-storey productionfacility. It stands for a further big step forwardin the scope of the master plan and providesthe company with more space for production.

2007

BLITZDUCTOR XTU is the firstarrester to automatically adjust itsnominal voltage. It does not havea specified nominal voltage andcan thus be used for any voltagein the range from 0 to 180 V d.c.thanks to actiVsense technology.

DEHN + SÖHNEproves for the firsttime absence of ignition sparkswhen lightningcurrent flowsthrough a pipeclamp.The newly

developed pipe clamp for hazardous areas canbe installed in potentially explosive areas withlittle effort.

Page 10: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 10/382

DEHN – Worldwide.

AlgeriaArgentinaAustraliaAustriaBelgiumBelizeBoliviaBrazilBulgariaCanadaCap VerdeChileChinaColumbiaCosta RicaCroatiaCubaCzech RepublicDenmarkEl SalvadorEstoniaF.Y.R.O.MFinland

FranceGreat BritainGreeceGuatemalaHondurasHungaryIcelandIndiaIranIrelandIsraelItalyJapanLatviaLebanonLithuaniaLuxembourgMalaysiaMauritiusMexico

NetherlandsNew ZealandNicaraguaNigeriaNorwayOmanPakistanPanamaPeruPolandPortugalRomaniaRussiaSaudi ArabiaSerbiaSingaporeSlovakiaSloveniaSouth AfricaSpainSri LankaSwedenSwitzerland

SyriaTaiwanThailandTurkeyUgandaUnited Arab EmiratesUSAVenezuela

We shall be pleased to name youthe right contact person of oursubsidiaries or representatives.

Please contact our ExportDepartment under

Tel. +49 9181 906 462Fax +49 9181 906 444

or send an e-mail [email protected]

8

Page 11: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 11/3829

Page 12: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 12/38210

Failures of technical systems and installations are very unpleasantfor the operators. These require faultless operation from theequipment both under “normal“ conditions and in case of thun-derstorms. Loss reports of insurance companies show clearly that

there is a backlog demand both in the private (Fig. 1) and com-mercial sector (Fig. 2). A comprehensive protection conceptwould help to achieve this aim.The Lightning Protection Zones Concept enables designers, con-structors and operators to plan, perform and control protectionmeasures.All relevant devices, installations and systems are thusreliably protected and furthermore with economically acceptableefforts.

Sources of interferenceSurges arising due to thunderstorms are caused by direct or closelightning strokes or distant lightning strokes (Fig. 3).Direct or close lightning strokes are strokes into the lightning pro-tection system of a structure, into its immediate surroundings orinto the conductive systems entering the structure (e.g. low-volta-ge power supply, telecommunications lines and control lines...).

Due to their amplitudes and energy loads, the arising impulse cur-rents and impulse voltages as well as the corresponding electro-magnetic field (LEMP) represent a special risk for the system tobe protected.

In case of a close or direct lightning strike, the surges (Fig. 3:

Case 1a) are caused by a voltage drop at the impulse earthingresistance and the resulting potential rise of the structure towardsthe distant surroundings. This is the maximum load on electricalinstallations in structures.

The characteristic parameters of flowing impulse currents (peakvalue, rate of current rise, load, specific energy) can be describedwith the impulse-current wave form 10/350 µs (Fig. 4) and aredefined in international, European and national standards as testcurrents for components and devices for protection against directlightning strokes.

In addition to the voltage drop at the impulse earthing resistance,surges arise in the electrical building installation and the systems

connected to it and equipment due to the induction effect of theelectromagnetic lightning field (Fig 3: Case 1b).The power of these induced surges and the resulting impulse cur-rents is considerably lower than the power of a direct lightningimpulse current and is therefore only described with the impulsecurrent wave 8/20 µs (Fig. 4). Components and equipment, whichdo not have to conduct currents from direct lightning strokes, aretherefore tested with impulse currents of 8/20 µs.

Protection philosophyDistant strokes are lightning strokes from a distance to the objectto be protected, lightning strokes into the medium voltage over-head line network or into its immediate surroundings or lightningdischarges from cloud to cloud (Fig. 3: Cases 2a, 2b and 2c).

In analogy to induced surges, the effects of distant lightning stro-kes on the electrical system of a structure are controlled by devi-ces and components, which are designed accordingly for impulsecurrent wave 8/20 µs.Surges due to switching operations (SEMP) are caused by e.g.

– switching off inductive loads(e.g. transformers, coils, motors),

– ignition and interruption of electric arcs(e.g. arc welding device),

– tripping of fuses.

The effects of switching operations in electrical installations of structures can also be simulated with impulse currents of waveform 8/20 µs for testing purposes.

DEHN – Safety according to Specification.

Lightning Protection Zones Concept

Fig. 1: Causes of damage to electronic equipment,Analysis of 7370 damage claims(Ref.:Württemberigsche Versicherung AG)

Fig. 2: Average damage causes during the last years(Ref.: Gesamtverband der Deutschen Versicherungswirtschaft e.V.)

Water5.6 %

Fire4.6 %

TheftVandalism

27.1 %

23.7 %Surges

(lightning dischargesswitching operations)

15.3 %Others

0.8 %Elemental

22.9 %Negligence

Others41 %

14 %Unknown 45 %

Lightning/Surges

Page 13: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 13/38211

To ensure continuous availability of complex power sup-ply and IT systems even in case of a direct lightningeffect, further measures for surge protection of electricaland electronic installations are necessary based on abuilding lightning protection system. Taking all causes of surges into consideration is very important. For this pur-pose, the Lightning Protection Zones Concept of IEC62305-4 is applied (Fig. 5).A structure is subdivided in different risk zones. These

zones help to define the necessary devices and compo-nents for lightning and surge protection.Part of an EMC-conform lightning protection zones con-cept is an external lightning protection system (includingair-termination system, down-conductor system, earth-ing), equipotential bonding, spatial shielding and surgeprotection for the power supply systems and IT systems.The lightning protection zones have to be definedaccording to Table 1.

In correspondence with the requirements and loads on

surge protective devices with respect to their installationsites, these are classified as lightning current arresters,surge arresters and combined lightning current andsurge arresters.The highest requirements for the discharge capacity aremade on lightning current and combined lightning cur-rent and surge arresters used for the transition fromLightning Protection Zone 0A to 1 or 0A to 2.

These SPDs must be able to conduct partial lightningcurrents (wave form 10/350 µs) several times withoutdestruction in order to prevent the penetration of

destructive partial lightning currents into the electricalinstallation of a building.At the boundary from LPZ 0B to 1 or downstream of thelightning current arrester at the boundary from LPZ 1 to2 and higher, surge arresters are used for protectionagainst surges. Their function is to further reduce boththe residual loads of the upstream protection levels andlimit the induced or own surges.

The aforementioned lightning and surge protectivemeasures at the boundaries of the lightning protection

zones apply to both power supply systems and IT sys-tems to the same extent.All measures described in the EMC-conform LightningProtection Zones Concept help to achieve a permanentsystem availability of a modern infrastructure.

low voltage powersupply system

20 kVL1L2L3

PEN2c

1 2a

2b

1b

1a

Rst

1a

Direct/Close lightning strike:

Lightning strike into the external lightningprotection system, process framework(in industrial installations), cables etc.

Voltage drop at the impulse earthingresistance Rst

Induced voltage in loops

1

1b

IT system

Distant lightning strike

Strike into medium volta-ge overhead lines

Surge travelling waves onoverhead lines due tocloud-to-cloud lightning

Fields of the lightningchannel

2a

2b

2c

Fig. 3: Causes of surges in case of lightning discharges

100 kA

80 kA

60 kA

50 kA

40 kA

20 kA

200 µs 350 µs 600 µs 800 µs 1000 µs

2

1

Wave form [µs] 10/350 8/20

imax [kA] 100 5

Q [As] 50 0.1

W/R [J/Ω] 2.5 · 106 0.4 · 103

Standard IEC 62305-1 EN 61000-4-5

t (µs)

(kA)

i

21

Fig. 4: Test impulse current for Test impulse current forlightning current arresters surge arresters21

ventilation

down-conductor

system

spatial shield

terminal device

steel reinforcement

IT system

foundation earth electrode

air-termination system

l.v. powersupply system

Lightning equipotential bondingLightning current arrester (SPD Type 1)

Local equipotential bondingSurge arrester (SPD Type 2, SPD Type 3)

Lightning equipotential bondingLightning current arrester

Local equipotential bondingSurge arrester

Lightning electro-magnetic pulse

Switching electro-magnetic pulse

Lightningprotection zone

Fig. 5: EMC-based lightning protection zones concept

Table 1: Definition of lightning protection zones (LPZ)

LEMP protection of structures with electrical and electronic systemsaccording to IEC 62305-4

Lightning Protection Zone Description

LPZ 0A Threat by direct lightning strokes, impulse currents up to complete lightningcurrents and the entire lightning field.

LPZ 0B Protected against direct lightning strokes. Threat by impulse currents up topartial lightning currents and the entire lightning field.

LPZ 1 Impulse currents are further limited by current distribution and SPDs situatedat the zone boundaries. The lightning field is mostly attenuated by spatialshielding.

LPZ 2 Impulse currents are further limited by current distribution and SPDs situatedat the zone boundaries. The lightning field is mostly attenuated by spatialshielding.

Page 14: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 14/38212

DEHN – Technical Definitions.

Surge Protective Devices (SPD)

Surge protective devices are items of equipmentwhose basic components are voltage-controlledresistors (varistors, suppressor diodes) and/orspark gaps (discharge paths). The function of surge protective devices is to protect other elec-trical equipment and installations against imper-missibly high surges and/or to establish theequipotential bonding.Surge protective devices are classified

a) according to their application in

– Surge protective devices for power sup-ply systems and equipmentfor nominal voltage ranges up to 1000 V

• according to EN 61643-1:2001 as SPD Types1/2/3

• according to IEC 61643-1:1998-02 as SPDsClass I / II / III

– Surge protective devices for IT systemsand equipmentfor protection of modern electronic systems intelecommunications and signal-processing net-works with nominal voltages up to 1000 V a.c.(root-mean-square value (rms)) and 1500 Vd.c. against indirect and direct effects of light-ning strokes and other transients.

• according to IEC 61643-21:2000 + Corrigen-dum:2001, EN 61643-21:2001 and DIN VDE0845 Part 3-1.

– Isolating spark gaps for earth-termina-tion systems or for equipotential bond-ing

b) according to their impulse current dis-charge capacity and their protective effectin

– Lightning current arresters /

Coordinated lightning current arrestersfor interference due to direct or close light-ning strokes for protection of installationsand equipment (for use at the boundaries of Lightning Protection Zones (LPZ) 0A and 1).

– Surge arrestersfor distant lightning strokes, switching over-voltages as well as electrostatic dischargesfor protection of installations, equipment andterminal devices (for use at the boundariesdownstream of LPZ 0B).

– Combined lightning current and surgearrestersfor interference due to direct or close light-ning strokes for protection of installations,equipment and terminal devices (for use atthe boundaries between LPZ 0A and 1 as wellas 0A and 2).

Technical data of surge protective devices

The technical data of surge protective devicescomprise information defining the applicationconditions upon

– application(e.g. installation, mains conditions,temperature)

– performance in case of interference(e.g. impulse current discharge capacity,follow current extinguishing capability,voltage protection level, response time)

– performance during operation(e.g. nominal current, attenuation,insulation resistance)

– performance in case of failure(e.g. backup fuse, disconnection device,fail-safe)

Categories according to IEC 61643-21: 2001(DIN VDE 0845 Part 3-1)

For testing the current carrying capability andvoltage limitation under influences of impulses,a variety of impulse voltages and impulse cur-rents is described in IEC 61643-21:2001 (DINVDE 0845 Part 3-1). They are sorted in Table 3

and provide preferred values. In table 2 of IEC61643-22 (DIN VDE 0845-3-2) the source of transients is assigned to the different impulsecategories according to the coupling mechanism.Category C2 includes inductive couplings(surges), category D1 galvanic couplings (light-ning currents). The relevant category is specifiedin the technical data.

Cut-off frequency fG

defines the frequency-dependent performanceof an SPD. Cut-off frequencies are frequencies

causing an insertion loss (aE) of 3 dB under cer-tain test conditions (see EN 61643-21:2001).If no other value is indi-cated, the frequencyvalue refers to a 50 Ωsystem.

Page 15: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 15/38213

DEHN + SÖHNE surge protective devicesexceed the values indicated in the categories.The explicit value for the impulse current carry-ing capability is therefore indicated by the

stated nominal discharge current (8/20 µs) andlightning impulse current (10/350 µs).

Combined impulse UOC

is generated by a hybrid generator (1.2/50 µs,8/20 µs) with a virtual impedance of 2 Ω.Theopen-circuit voltage of this generator is de-fined as UOC. UOC is especially indicated forSPDs Type 3.

Degree of protection

The degree of protection (IP) corresponds tothe subdivision into degrees of protection inaccordance with DIN EN 60529 (VDE 0470Part 1).

Disconnecting time ta

is the time passing until the automatic discon-nection from power supply of the electricalcircuit or equipment to be protected in case of a failure. The disconnecting time is an applica-tion-specific value resulting from the intensityof the fault current flowing and the character-

istics of the protective device.

Disconnection capacity / Follow currentextinguishing capability Ifi

The disconnection capacity is the uninterfered(prospective) rms value of the mains followcurrent, which can automatically be extin-guished by the surge protective device at pres-ence of UC. It can be proven in the scope of anoperating duty test according to EN 61643-11.

Frequency range

characterises the transmission band or let-through frequency of an SPD according tothe described attenuation characteristics.

Insertion loss

With an indicated frequency, the insertion lossof a surge protective device is defined by therelation of the voltage value at the installationsite before and after installing the SPD.If no other value is indicated, the value refersto a 50 Ω system.

LifeCheck®

Repeated discharges with values beyond thespecifications of the device may overload SPDsused in IT systems. In order to ensure a high

system availability, SPDs should therefore besubject to systematic tests. LifeCheck allowsfor quick and easy SPD testing (refer also topage 177).

Lightning impulse current Iimp

is a standardised impulse current curve, with awave form of 10/350 µs. Its parameters (peakvalue, charge, specific power) simulate theloads of natural lightning currents.Lightning current and combined lightningcurrent and surge arresters must be capable of discharging such lightning impulse currentsseveral times without consequential destruc-tion of the equipment.

Mains-side overcurrent protection /Backup fuse

is an overcurrent protective device (e.g. fuse orcircuit breaker), which is installed outside of the surge arrester on the supply side to inter-rupt the power-frequency follow currents, if the breaking capacity of the surge protectivedevice is exceeded.

Max. continuous operating voltage UC

is the root mean square (rms) value of themaximum voltage, which may be applied tothe correspondingly marked terminals of thesurge protective device during operation. It isthe maximum voltage on the SPD in thedefined non-conductive state, which ensuresthat this state is regained after response anddischarge.The value of UC shall be chosen in accordancewith the nominal voltage of the system to beprotected and the requirements of the installa-tion provisions (IEC 60364-5-534).

Max. discharge current Imax

is the maximum peak value of the impulse cur-rent (8/20 µs), which can be safely dischargedby the device.

Max. transmission capacity

defines the maximum RF capacity which canbe transmitted via a coaxial surge protectivedevice without interfering with the protectivecomponent.

Nominal discharge current In

is the peak value of an impulse current (waveform 8/20 µs), which the surge protectivedevice is rated for according to a certain testprogramme.

Page 16: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 16/38214

Nominal load current (nominal current) IL

is the highest permissible operating current,which may be permanently conducted via thecorrespondingly marked terminals.

Nominal voltage UN

corresponds to the nominal voltage of the sys-tem to be protected.The nominal voltage isoften indicated for surge protective devices usedin IT installations for type designation purposes.For a.c. voltages it is indicated as rms value.

N-PE surge arresters

are surge protective devices exclusively designedfor installation between the N and PE conductor.

Operating temperature range TU

indicates the range in which the devices can beused. For devices without self-heating, it is equalto the ambient temperature range. The tempera-ture rise of devices with self-heating must notexceed the maximum value indicated.

Protective circuit

Protective circuits are multi-stage, cascaded pro-tective devices. The individual protection stagescan consist of discharge paths, varistors, semi-conductor elements. The energy coordination of the individual protection stages is performedwith decoupling elements.

Protective conductor current IPE

is the current flowing through the PE connectionwhen the surge protective device is connected tothe maximum continuous operating voltage UC,corresponding to the installation instructionsand without load-side consumers.

Response time tA

Response times generally characterise theresponse performance of the individual protec-tion elements used in surge protective devices(refer also to page 371).Depending on the steepness du/dt of the im-pulse voltage or di/dt of the impulse current, theresponse times can change within certain limits.

Return loss

indicates for high-frequency applications, howmany rates of the “forward“ wave are reflectedat the protective device (“transition point“).It is a direct measure for rating the adjustment

of the protective device to the surge impedanceof the system.

Series impedance

is the impedance in the direction of the signalflow between input and output of the SPD.

Shield attenuation

Relation of the power fed into a coaxial cable tothe power radiated through the cable from thephase conductor.

Short-circuit withstand capability

is the value of the prospective power-frequencyshort-circuit current controlled by the surge pro-tective device if it is supplied with an upstreambackup fuse.

SPD class (Yellow/ Line)

All DEHN surge arresters for use in IT systemsare assigned a Yellow/Line SPD Class and aremarked correspondingly with a symbol in thetechnical data sheet and on the rating plate

(refer also to page 151).

Thermal disconnector

Surge protective devices for use in power supplysystems, which are supplied with voltage-con-trolled resistors (varistors), mostly have an inte-grated disconnection device, which isolates thesurge protective device from mains in case of overloads and indicates this operating state.The disconnector reacts to the “joule heat“generated by an overloaded varistor and discon-nects the surge protective device from mains, if a certain temperature is exceeded.The disconnection device is designed to discon-nect the overloaded surge protective device intime to avoid a fire hazard. It is not designed toensure the protective measure of “protectionagainst indirect contact“.The function of these thermal disconnectors canbe tested by simulated overloads/ageing of theSPD.

Voltage protection level Up

The voltage protection level of a surge protectivedevice is the maximum instantaneous value of

the voltage on the terminals of a surge protec-tive device, determined from the standardisedindividual tests for

– Lightning impulse sparkover voltage1.2/50 µs (100%)

– Response voltage for a steepness of 1 kV/µs

– Residual voltage for nominal dischargecurrent Ures

The voltage protection level characterises thecapability of a surge protective device to limitsurges to a residual level. If used in power sup-ply systems, the voltage protection level defines

the location of use by the overvoltage categoryaccording to DIN VDE 0110-1:2003-11 (DIN EN60664-1, IEC 60664-1). For surge protectivedevices designed for protection of IT systems,the voltage protection level has to be adaptedto the immunity of the equipment to be protect-ed (IEC 61000-4-5: 2001-12).

Page 17: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 17/382www.dehn.de 15

Surge protection for

POWER SUPPLY SYSTEMSSPDs for low-voltage installations and equipment

Page 18: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 18/382www.dehn.de16

Page 19: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 19/382

Easy choice 18

Combined SPDs – Type 1 31

Lightning Current Arresters – Type 1 45

N-PE Lightning Current Arresters – Type 1 63

Surge Arresters – Type 2 69

Surge Arresters – Type 3 119

Accessories 145

Measuring and Test Devices 365

POWER SUPPLY SYSTEMS

www.dehn.de 17

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

CONTENTS

Accessories

Surge Arresters –Type 3

Lightning CurrentArresters – Type 1

N-PE Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Surge Arresters –Type 2

Page 20: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 20/382

POWER SUPPLY SYSTEMS

www.dehn.de

Easy Choice

18

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

L1L2L3N PE

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PE

D E H N g u a r d

D G M O D 2 7 5

L3

D E H N g u a r d

D G M O D 2 7 5

N

9

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PE

D E H N g u a r d

D G M O D 2 7 5

L3

D E H N g u a r d

D G M O D 2 7 5

N

9

L1 L2 L3 PEN

L1 L1’ L2 L2’ L3 L3’

N ‘/PE N N/PEN

DEHNbloc DB 3 255 H

L1 L1‘ L2 L2‘

PEN

L3 L3‘

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

9

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

S-Schutz

DEHNflex

16 A

S o c k e t O u t l e t

1 x DSA 230 LA Part No. 924 370for cable ducts

1 x STC 230 Part No. 924 350for existing socket outlets

with remote signalling contact:1 x DG M TNS 275 FM Part No. 952 405

1 x DV M TNC 255 Part No. 951 300alt. 1 x DV M TNC 255 FM Part No. 951 305also available as

1 x DV M TNS 255 Part No. 951 400alt. 1 x DV M TNS 255 FM Part No. 951 405

1125 A 1125 A

1 x DG M TNS 275 Part No. 952 400

Cable length ≥ 15 m

1 x DB 3 255 H Part No. 900 120

alt. 3 x DB 1 255 H Part No. 900 2221 x MVS 1 6 Part No. 900 815

1315 A

3 x DB M 1 255 FM Part No. 961 1251 x MVS 1 6 Part No. 900 815

alt. 3 x DB M 1 255 Part No. 961 1201 x MVS 1 6 Part No. 900 815

S u b d i s t r i b u t i o n B o a r d

1315 A

1 x DFL M 255 Part No. 924 396for flush-mounted systems

1315 A

C ab l e l e n g t h ≥ 5 m

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

SPD Type 2(Surge arrester)

SPD Type 2(Surge arrester)

i n d i c a t i o n

o f i n t e r f e r e n c e

i n d i c a t i o n

o f i n t e r f e r e n c e

EBB

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

SPD Type 1(Combined lightning current

and surge arrester)

DEHNventil®

Directly coordinated toRed/Line SPDs Type 2 and 3

without additional cable length.

For serial connection please see also page 21

SPD Type 1(Coordinated lightning

current arrester)

DEHNbloc® MCoordinated to DEHNguard®

without additional cable length.

SPD Type 1(Lightning current arrester)

M a i n D i s t r i b u t i o n B

o a r d

TN systems: Office Building – Separation of the PEN in the main distribution board

Arrangement I Arrangement II Arrangement III

Page 21: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 21/382

POWER SUPPLY SYSTEMS

www.dehn.de

P R O T E C T O R

Überspannungsschutz

0 1

SFL-Protector

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PEN

D E H N g u a r d

D G M O D 2 7 5

L3

9

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PEN

D E H N g u a r d

D G M O D 2 7 5

L3

9

L1 L1’ L2 L2’ L3 L3’

N ‘/PE N N/PEN

DEHNbloc DB 3 255 H

L1 L1‘ L2 L2‘

PEN

L3 L3‘

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

9

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

L1 L2 L3 PEN

L1L2 L3 N PE

16 A

S o c k e t O u t l e t

M a i n D i s t r i b u t i o n B o a r d

S u b d i s t r i b u t i o n B o a r d

1 x NSM PRO EW Part No. 924 342 1 x DPRO 230 F Part No. 909 2401 x DPRO 230 Part No. 909 230

1 x SFL PRO Part No. 912 260

1 x DG M TNC 275 Part No. 952 300with remote signalling contact:1 x DG M TNC 275 FM Part No. 952 305

1 x DB 3 255 H Part No. 900 120

alt. 3 x DB 1 255 H Part No. 900 2221 x MVS 1 6 Part No. 900 815

1 x DV M TNC 255 Part No. 951 300

alt. 1 x DV M TNC 255 FM Part No. 951 305

1125 A 1125 A

1315 A 1315 A

3 x DB M 1 255 FM Part No. 961 1251 x MVS 1 6 Part No. 900 815

alt. 3 x DB M 1 255 Part No. 961 1201 x MVS 1 6 Part No. 900 815

1315 A

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

C ab l e l e n g t h ≥ 5 m

Cable length ≥ 15 m

SPD Type 2(Surge arrester)

SPD Type 2(Surge arrester)

SPD Type 1(Combined lightning current

and surge arrester)

DEHNventil®

Directly coordinated toRed/Line SPDs Type 2 and 3

without additional cable length.

For serial connection please see also page 21

SPD Type 1(Coordinated lightning

current arrester)

DEHNbloc® MCoordinated to DEHNguard®

without additional cable length.

SPD Type 1(Lightning current arrester)

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

i n d i c a t i o n

o f i n t e r f e r e n c e

i n d i c a t i o n

o f i n t e r f e r e n c e

EBB

Easy Choice

19

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

TN systems: Example: Office Building – Separation of the PEN in the subdistribution board

Arrangement I Arrangement II Arrangement III

Page 22: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 22/382

POWER SUPPLY SYSTEMS

www.dehn.de

L1 L2 L3 PEN

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PEN

D E H N g u a r d

D G M O D 2 7 5

L3

9

VNHVNH00280

VNHVNH00280

VNHVNH00280

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

DEHN SPD

SPS PRO

function

OUT / FM

99 / IN

D E H N r a i l

D R M 4

P 2 5 5 F M

L1 L2 L3 N 9

L1 L2 L3 N 9

L1 L1‘ L2 L2‘

PEN

L3 L3‘

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

9

D E H N r a i l

D R M 2 P 2 5 5 F M

4 3

2 1

9

9

NETZFILTER

L’ L’ N’ N’OUT

L L N NIN9 9

9 9

3 x V NH00 280 Part No. 900 261

3 x DBM NH00 255 Part No. 900 255

1315 A

1 x DV M TNC 255 FM Part No. 951 305

alt. 1 x DV M TNC 255 Part No. 951 300

1315 A

i n d i c a t i o n

o f i n t e r f e r e n c e

1 x DG M TNC 275 Part No. 952 300or with remote signalling contact:1 x DG M TNC 275 FM Part No. 952 305

1125 A

13 A

1 x SPS PRO Part No. 912 253 1 x DR M 4P 255 FM Part No. 953 405alt. 1 x DR M 4P 255 Part No. 953 400

125 A

electronicequipment

1 x DR M 2P 255 FM Part No. 953 2051 x NF 10 Part No. 912 254

L1L2L3N PE

C ab l e l e n g t h ≥ 5 m

32 A

S w i t c h g e a r / M a c h i n e

SPD Type 2(Surge arrester)

SPD Type 2(Surge arrester)

M a i n D i s t r i b u t i o n B o

a r d

S u b d i s t r i b u t i o n B o a r d

SPD Type 1(Combined lightning current

and surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

DEHNventil®

Directly coordinated toRed/Line SPDs Type 2 and 3

without additional cable length.

For serial connection please see also page 21

2

SPS

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.2) Without separate backup fuse in case of earth-fault- and short-circuit-proof installation.

SPD Type 1(Coordinated lightning

current arrester)

DEHNbloc® MCoordinated to DEHNguard®

without additional cable length.

3 x DB M 1 255 FM Part No. 961 1251 x MVS 1 6 Part No. 900 815

alt. 3 x DB M 1 255 Part No. 961 1201 x MVS 1 6 Part No. 900 815

i n d i c a t i o n

o f i n t e r f e r e n c e

i n d i c a t i o n

o f i n t e r f e r e n c e

1315 A

110 A

SPS

25 A alsopermissiblewithout NF 10

SPD Type 1(Coordinated lightning

current arrester)

DEHNblocMaxiDBMNH00255

DEHNblocMaxiDBMNH00255

DEHNblocMaxiDBMNH00255

EBB

TN systems: Example: Industry – Separation of the PEN in the subdistribution board

Easy Choice

20

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Arrangement I Arrangement II Arrangement III

Page 23: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 23/382

POWER SUPPLY SYSTEMS

www.dehn.de

P R O

T E C T O

R

D E H N r a i l

D R M 2

P 2 5 5 F M

21 9

DEHNventil ZP

DV ZP TNC 255

PEN9

PEN

L3

L2

L1

L1L2L3N PE

16 A

S o c k e t O u t

l e t

EBB

H e a t i n g C o n

t r o l

1 x DV ZP TNC 255 Part No. 900 390

also available for 5-wire systems1 x DV ZP TT 255 Part No. 900 391

Note:As an alternative, surge arresters can also beused downstream of meter panels

(e.g. DG M TNC 275 Part No. 952 300),if no

– lightning protection system,

– electrical power supply by the service entry mast,

– antenna of the roof

is available. C e n t r a l M

a i n a n d

S u b d i s t r i b u t

i o n B o a r d

1 x DPRO 230 Part No. 909 2301 x DPRO 230 F Part No. 909 2401 x SFL PRO Part No. 912 2601 x DR M 2P 255 Part No. 953 200

KW h

heating

315 A

L1L2L3PEN

SPD Type 1(Combined lightning current

and surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

C ab l e l e n g t h ≥ 5 m

TT system: Example: Single-family house

Easy Choice

21

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

TN systems: Example: Single-family house

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D N P E

5 0

L1 L2

PE

L3 N

9

D E H N r a i l

D R M 2

P 2 5 5 F M

21 9

RCD

L1L2L3N PE

16 A

S o c k e t O u t l e t

H e a t i n g C o n t r o l

1 x DV M TT 255 Part No. 951 310 C e n t r a l M a i n a n d

S u b d i s t r i b u t i o n B o a r d

1 x DR M 2P 255 Part No. 953 200

EBB

25 A

1 x DFL M 255 Part No. 924 396

heating

L1L2L3N

DEHNflex

C ab l e l e n g t h ≥ 5 m

Note:As an alternative, surge arresters can also beused downstream of meter panels(e.g. DG M TT 275 Part No. 952 310),if no

– lightning protection system,

– electrical power supply by the service entry mast,

– antenna of the roof

is available.

SPD Type 1(Combined lightning current

and surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

Page 24: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 24/382

POWER SUPPLY SYSTEMS

www.dehn.de

for cable ducts for existing socket outletsfor flush-mounted systems

C ab l e l e n g t h ≥ 5 m

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

N‘

EBB

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PE

D E H N g u a r d

D G M O D 2 7 5

L3 N

D E H N g u a r d

D G M O D N P E

9

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PE

D E H N g u a r d

D G M O D 2 7 5

L3 N

D E H N g u a r d

D G M O D N P E

9

DEHNflex

S-Schutz

D E H N v e n t i l

D V M O D 2 5 5

L1 L1‘ L2 L2‘

PE

L3 L3‘ N

9

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D N P E 5 0

N

PE

D E H N g a p

D G P M 2

5 5

9

D E H N b l o c

D B M 1

2 5 5

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5

N/PE(N)

L/N

L1L2 L3 N

3 x DB M 1 255 Part No. 961 1201 x DGP M 255 Part No. 961 1011 x MVS 1 8 Part No. 900 611

1 x DV M TT 255 FM Part No. 951 315

alt. 1 x DV M TT 255 Part No. 951 310

1315 A

L1L2L3N PE

16 A

S o c k e t O u t l e t

1 x DSA 230 LA Part No. 924 370 1 x STC 230 Part No. 924 350

with remote signalling contact:1 x DG M TT 275 FM Part No. 952 315

1125 A 1125 A

1 x DG M TT 275 Part No. 952 310

M a i n D i s t r i b u t i o n B o a r d

S u b d i s t r i b u t i o n B o a r d

1 x DFL M 255 Part No. 924 396

RCD

1315 A

1 x DB 3 255 H Part No. 900 120alt. 3 x DB 1 255 H Part No. 900 222

1 x DGP BN 255 Part No. 900 1321 x DK 25 Part No. 952 6991 x MVS 1 2 Part No. 900 617

L1 L1’ L2 L2’ L3 L3’

N ‘/PE N N/PEN

DEHNbloc DB 3 255 HDEHNgap B/nDGP BN 255

1315 A

F e e

d - T

h r o u g

h

T e r m i n a

l

D K 2 5

Cable length ≥ 15 m

SPD Type 1(Lightning current arrester)

DEHNbloc® MCoordinated to DEHNguard®

without additional cable length.

SPD Type 1(Coordinated lightning

current arrester)

DEHNventil®

Directly coordinated toRed/Line SPDs Type 2 and 3

without additional cable length.

For serial connection please see also page 21

SPD Type 1(Combined lightning current

and surge arrester)

indication of interference

SPD Type 2

(Surge arrester)

SPD Type 2

(Surge arrester)

i n d i c a t i o n

o f i n t e r f e r e n c e

TT systems: Example: Office Building

Easy Choice

22

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Arrangement I Arrangement II Arrangement III

Page 25: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 25/382

POWER SUPPLY SYSTEMS

www.dehn.de

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PE

D E H N g u a r d

D G M O D 2 7 5

L3 N

D E H N g u a r d

D G M O D N P E

9

D E H N g u a r d

D G M O D 2 7 5

D E H N g u a r d

D G M O D 2 7 5

L1 L2

PE

D E H N g u a r d

D G M O D 2 7 5

L3 N

D E H N g u a r d

D G M O D N P E

9

DEHNgapBNHDGPB NH00 N 255

D E H N v e n t i l

D V M O D 2 5 5

L1 L1‘ L2 L2‘

PE

L3 L3‘ N

9

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D 2 5 5

D E H N v e n t i l

D V M O D N P E 5 0

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

N

PE

D E H N g a p

D G P M 2

5 5 F M

9

D E H N r a i l

D R M 2 P 2 5 5 F M

4 3

2 1

9

9

NETZFILTER

L’ L’ N’ N’OUT

L L N NIN9 9

9 9

DEHN SPD

SPS PRO

function

OUT / FM

99 / IN

D E H N r a i l

D R M 4

P 2 5 5 F M

L1 L2 L3 N 9

L1 L2 L3 N 9

L1L2L3 N

3 x DB NH00 255 H Part No. 900 2731 x DGP B NH00 N 255 Part No. 900 269

1315 A

1 x DV M TT 255 FM Part No. 951 315

alt. 1 x DV M TT 255 Part No. 951 310

1315 A

3 x DB M 1 255 FM Part No. 961 1251 x DGP M 255 FM Part No. 961 1051 x MVS 1 8 Part No. 900 611

1315 A

L1L2L3N PE

32 A

EBB

with remote signalling contact:1 x DG M TT 275 FM Part No. 952 315

1125 A 1125 A

1 x DG M TT 275 Part No. 952 310

M a i n D i s t r i b u t i o n B o a r d

S u b d i s t r i b u t i o n B o a r d

13 A

1 x SPS PRO Part No. 912 253 1 x DR M 4P 255 FM Part No. 953 405alt. 1 x DR M 4P 255 Part No. 953 400

125 A

1 x DR M 2P 255 FM Part No. 953 2051 x NF 10 Part No. 912 254

110 A

S w i t c h g e a r / M a c h i n e

SPS SPS

RCD

C ab l e l e n g t h ≥ 5 m

SPD Type 2(Surge arrester)

SPD Type 2(Surge arrester)

SPD Type 1(Combined lightning current

and surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

SPD Type 3(Surge arrester)

DEHNventil®

Directly coordinated toRed/Line SPDs Type 2 and 3

without additional cable length.

For serial connection please see also page 21

SPD Type 1(Coordinated lightning

current arrester)

DEHNbloc® MCoordinated to DEHNguard®

without additional cable length.

i n d i c a t i o n

o f i n t e r f e r e n c e

SPD Type 1(Lightning current arrester)

electronicequipment

i n d i c a t i o n

o f i n t e r f e r e n c e

indication of interference

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

N‘

DEHNbloc NHDB NH00 255 H

DEHNbloc NHDB NH00 255 H

DEHNbloc NHDB NH00 255 H

Cable length ≥ 15 m

i n d i c a t i o n

o f i n t e r f e r e n c e

25 A alsopermissiblewithout NF 10

TT systems: Example: Industry

Easy Choice

23

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Arrangement I Arrangement II Arrangement III

Page 26: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 26/382

POWER SUPPLY SYSTEMS

www.dehn.de24

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Easy Choice

D E H N g u a r d

D G S 4 4 0 F M

D E H N g u a r d

D G S 4 4 0 F M

D E H N g u a r d

D G S 4 4 0 F M

N/PEN

L

D E H N b l o c

M a x i

D B M 1

4 4 0 F M

N/PEN

L

D E H N b l o c

M a x i

D B M 1

4 4 0 F M

N/PEN

L

D E H N b l o c

M a x i

D B M 1

4 4 0 F M

L

D E H N b l o c

M a x i

D B M 1

7 6 0 F M

L1 L2 L3 PEN

3 x DG S 440 FM Part No. 952 0951 x MVS 1 3 Part No. 900 615

125 A

EBB

250 A

3 x DBM 1 440 FM Part No. 961 145

alt. 3 x DBM 1 440 Part No. 961 1401 x EB DG 1000 1 3 Part No. 900 411

L1 L2 L3 PEN

SPD Type 2(Surge arrester)

i n d i c a t i o n

o f i n t e r f e r e n c e

SPD Type 1(Coordinated lightning

current arrester)

i n d i c a t i o n

o f i n t e r f e r e n c e

1 x EB DG 1000 1 3 Part No. 900 411

TN systems: Industry TN-C 400/690 V IT systems: Industry IT 690 V, without integrated neutral conductor

N/PEN

L

D E H N b l o c

M a x i

D B M 1

7 6 0 F M

N/PEN

L

D E H N b l o c

M a x i

D B M 1

7 6 0 F M

N/PEN

L

D E H N b l o c

M a x i

D B M 1

7 6 0 F M

DEHNguardDG 1000 FM

DEHNguardDG 1000 FM

DEHNguardDG 1000 FM

L1 L2 L3 PE

3 x DBM 1 760 FM Part No. 961 1751 x EB DG 1000 1 3 Part No. 900 411

3 x DG 1000 FM Part No. 950 1121 x EB DG 1000 1 3 Part No. 900 411

100 A aM

250 A

L1 L2 L3 PE

SPD Type 2(Surge arrester)

SPD Type 1(Coordinated lightning

current arrester)

i n d i c a t i o n

o f i n t e r f e r e n c e

i n d i c a

t i o n

o f i n t e r f e r e n c e

EBB

Page 27: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 27/382

POWER SUPPLY SYSTEMS

www.dehn.de 25

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Easy Choice

L1L2L3N PE

D E H N g u a r d

D G M O D C I

2 7 5

D E H N g u a r d

L1 L2

PE

D E H N g u a r d

L3

D E H N g u a r d

D G M O D 2 7 5

N

9

L1 L2 L3 PEN

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5 F M

N/PE(N)

L/N

DEHNflex

16 A

S o c k e t O u t l e t

with remote signalling contact:1 x DG M TNS CI 275 FM Part No. 952 406

3 x DB M 1 255 FM Part No. 961 1251 x MVS 1 6 Part No. 900 815

alt. 3 x DB M 1 255 Part No. 961 1201 x MVS 1 6 Part No. 900 815

M a i n D i s t r i b u t i o n B o a r d

S u b d i s t r i b u t i o n B o a r d

1 x DFL M 255 Part No. 924 396for flush-mounted systems

1315 A

C ab l e l e n g t h ≥ 5 m

SPD Type 3(Surge arrester)

SPD Type 2(Surge arrester)

i n d i c a t i o n

o f i n t e r f e r e n c e

i n d i c a t i o n

o f i n t e r f e r e n c e

EBB

1) Only required, if a fuse of the same or alower nominal value is not alreadyprovided in the upstream power supply.

SPD Type 1(Coordinated lightning

current arrester)

DEHNbloc® MCoordinated to DEHNguard®

without additional cable length.

D G M O D C I

2 7 5

D G M O D C I

2 7 5

IK ≤ 25 kA

TN systems TT systems

for flush-mounted systems

C ab l e l e n g t h ≥ 5 m

SPD Type 3(Surge arrester)

EBB

L1 L2

PE

L3 N

D E H N g u a r d

D G M O D N P E

9

DEHNflex

N

PE

D E H N g a p

D G P M 2

5 5

9

D E H N b l o c

D B M 1

2 5 5

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5

N/PE(N)

L/N

D E H N b l o c

D B M 1

2 5 5

N/PE(N)

L/N

L1L2 L3 N

3 x DB M 1 255 Part No. 961 1201 x DGP M 255 Part No. 961 1011 x MVS 1 8 Part No. 900 611

L1L2L3N PE

16 A

S o c k e t O u t l e t

with remote signalling contact:1 x DG M TT CI 275 FM Part No. 952 327

M a i n D i s t r i b u t i o n B o a r d

S u b d i s t r i b u t i o n B o a r d

1 x DFL M 255 Part No. 924 396

RCD

1315 A

DEHNbloc® MCoordinated to DEHNguard®

without additional cable length.

SPD Type 1(Coordinated lightning

current arrester)

SPD Type 2

(Surge arrester)

i n d i c a t i o n

o f i n t e r f e r e n c e

D E H N g u a r d

D G M O D C I

2 7 5

D E H N g u a r d

D E H N g u a r d

D G M O D C I

2 7 5

D G M O D C I

2 7 5

1) Only required, if a fuse of the same or alower nominal value is not alreadyprovided in the upstream power supply.I

K ≤ 25 kA

Page 28: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 28/382www.dehn.de26

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Easy Choice of SPDs for Use in Photovoltaic Systems

d.c. arresters

1

5Type 1 combined lightning currentand surge arrester for use in photo-voltaic systems

DLM PV 1000 Part No. 900 330

a.c. arresters

Modular surge arrester for use in single-phase230 V TN power supply systems

DG M TN 275 Part No. 952 200DG M TN 275 FM Part No. 952 205

2Modular surge arrester for use in single-phase230 V TT power supply systems

DG M TT 2P 275 Part No. 952 110DG M TT 2P 275 FM Part No. 952 115

2

Multipole combined lightning current and surgearrester for use in three-phase power supply sys-tems

DV M TNC 255 Part No. 951 300DV M TNC 255 FM Part No. 951 305

DV M TNS 255 Part No. 951 400DV M TNS 255 FM Part No. 951 405

DV M TT 255 Part No. 951 310DV M TT 255 FM Part No. 951 315

3

Modular combined lightning current and surgearrester for use in single-phase TN power supplysystems

DV M TN 255 Part No. 951 200DV M TN 255 FM Part No. 951 205

4 Modular combined lightning current and surgearrester for use in single-phase TT and TN-S powersupply systems

DV M TT 2P 255 Part No. 951 110DV M TT 2P 255 FM Part No. 951 115

4

Modular multipole surge arrester for use in three-phase power supply systems

DG M TNC 275 Part No. 952 300DG M TNC 275 FM Part No. 952 305

DG M TNS 275 Part No. 952 400DG M TNS 275 FM Part No. 952 405

DG M TT 275 Part No. 952 310DG M TT 275 FM Part No. 952 315

6

Modular surge arrester as complete unit for use inphotovoltaic systems

DG M YPV SCI 600 Part No. 952 511DG M YPV SCI 600 FM Part No. 952 516

DG M YPV SCI 1000 Part No. 952 510DG M YPV SCI 1000 FM Part No. 952 515

DG M YPV SCI 1200 Part No. 952 512DG M YPV SCI 1200 FM Part No. 952 517

max. PV voltage unearthed / functionally earthed

up to 600 V d.c. Part No. 952 511 (952 516)

up to 1000 V d.c. Part No. 952 510 (952 515)

up to 1200 V d.c. Part No. 952 512 (952 517)

Page 29: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 29/382www.dehn.de

PV system on a building with external lightning protection system.

27

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Equipotential bonding

For lightning and surge protection reasons, it is strongly recommended toconnect the PV frame as follows to the equipotential bonding system:

• Defined connection with at least 16 mm2 copper at the PV frame (b).

• Defined connection with at least 6 mm2 copper at the PV frame(a + c).

• Electrically conductive connection of the PV frames has to be ensured.

• The earth conductor is connected to the main earthing busbar of thebuilding on ground level.

• The earth conductor has to be installed in parallel and in close proxi-mity to the d.c. and a.c. cables / lines and accessory.

kWh kWh

s

s

=

~

SEB

a.c.output

d.c. input

meter/distribution board

power supply

≥ s 12

3

separationdistance OK

6

SEB

kWh kWh

power supply

< s< s

=

~

54

3

< s

a.c.output

d.c. input

meter/distribution board

separationdistancenot OK

3

kWh kWh

=

~

SEB

a.c.output

d.c. input

meter/distribution board

power supply

12

6

6

Easy Choice of SPDs for Use in Photovoltaic Systems

a) if the separation distance s is observed b) if the separation distance s is not observed

PV system on a building without external lightning protection system.

c)

Page 30: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 30/382

Power Supply Systems Worldwide

L1

L2

L3

PEN

RB

L1

L2

L3

N

RB

PE

L1

L2

L3

N

PE

RB

TN-C system TN-S system

L1

L2

L3

N

RB RA

PE

L1

L2

L3

RA

PE

TN-C system 230 / 400 V

TN-S system 230 / 400 V

TN-C-S system 230 / 400 V

TT system 230 / 400 V IT system 230 V, 400 V, 500 V, 690 V

L

N

G

L1

N

GL2

L1

G

L2

L3

L1

G

L2L3

N

L1

G

L2

L3

N

L1

G

L2

L3

L1

G

L2

L3

single-phase; 3 conductors

(1 Ph, 2 W + G)

110 V120 V220 V240 V

single-phase; 4 conductorsSplit Phase or Edison

(1 Ph, 3 W + G)

120 V / 240 V

3-phase; 4 conductors

(3 Ph Y, 3 W + G)

480 V

3-phase; 5 conductors

(3 Ph Y, 4 W + G)

120 V / 208 V277 V / 480 V

3-phase; 5 conductorsDelta ”Highleg“

(3 Ph ∆, 4 W + G)

120 V / 240 V

3-phase; 4 conductorsDelta ”Ungrounded“

(3 Ph ∆, 3 W + G)

240 V480 V

3-phase; 4 conductorsDelta ”Grounded Corner“

(3 Ph ∆, 3 W + G)

240 V480 V

R

N

100 V

R

T

200 V

R

N

100 V

100 V

200 V

T

single-phase; 2 conductors

(1 Ph, 2 W)

200 V

single-phase; 3 conductors

(1 Ph, 3 W)

100 V / 200 V

single-phase; 2 conductors

(1 Ph, 2 W)

100 V

R

S

200 V

200 V

200 V

T

R

S

100 V

100 V200 V

T

N200 V

200 V

3-phase; single-phase;

3 conductors+

3 conductors

100 V / 200 V; 200 V

3-phase; 3 conductors

(3 Ph, 3 W)

200 V

International system configurations* according to IEC 60364-1 (DIN VDE 0100-100)

Further system configurations* used worldwide

* System according to earth connection (according to DIN VDE 0100-100)

POWER SUPPLY SYSTEMS

www.dehn.de28

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Page 31: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 31/382

POWER SUPPLY SYSTEMS

www.dehn.de 29

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

Cross-reference

Combined SPDs – Type 1

900 370 DV 2P TT 255 951 110 DV M TT 2P 255 or

951 115 DV M TT 2P 255 FM

900 371 DV 2P TN 255 951 200 DV M TN 255 or

951 205 DV M TN 255 FM

900 373 DV TNC 255 951 300 DV M TNC 255 or

951 305 DV M TNC 255 FM

900 374 DV TNS 255 951 400 DV M TNS 255 or

951 405 DV M TNS 255 FM

900 375 DV TT 255 951 310 DV M TT 255 or

951 315 DV M TT 255 FM

Coordinated Lightning Current Arresters – Type 1

900 015 DBM 1 135 961 110 DB M 1 150 or

961 115 DB M 1 150 FM

900 016 DBM 1 320 961 130 DB M 1 320 or

961 135 DB M 1 320 FM

900 025 DBM 1 255 961 120 DB M 1 255

900 026 DBM 1 255 L 961 125 DB M 1 255 FM

900 044 DBM 440 961 140 DBM 1 440 or961 145 DBM 1 440 FM

900 055 DGPM 255 961 101 DGP M 255 or

961 105 DGP M 255 FM

Lightning Current Arresters – Type 1

900 100 DP 255 961 120 DB M 1 255 or

900 222 DB 1 255 H

900 101 DP 440 961 140 DBM 1 440 or

900 159 DB 1 440

900 110 DB 3 255 900 120 DB 3 255 H

900 111 DB 1 255 900 222 DB 1 255 H

900 260 DB NH00 255 900 273 DB NH00 255 H

Surge Arresters – Type 2

900 133 DGP C T 255 952 030 DGP C S or

952 035 DGP C S FM

900 265 V NH1 3 900 270 V NH1 280

900 266 VA NH1 3 900 271 VA NH1 280

900 506 DG TN 230 952 200 DG M TN 275

900 507 DG TN 230 FM 952 205 DG M TN 275 FM

900 508 DG TT 230 952 110 DG M TT 2P 275

900 509 DG TT 230 FM 952 115 DG M TT 2P 275 FM

900 510 DG TNC 230 400 952 300 DG M TNC 275

900 516 DG IT 500 952 302 DG M WE 600

900 517 DG Y PV 1000 952 510 DG M YPV SCI 1000952 511 DG M YPV SCI 6002x 950 500 2x DG PV 500 SCP

900 520 DG TT 230 400 952 310 DG M TT 275

900 530 DG TNS 230 400 952 400 DG M TNS 275900 540 DG TNC 230 400 FM 952 305 DG M TNC 275 FM

900 546 DG IT 500 FM 952 307 DG M WE 600 FM

900 547 DG Y PV 1000 FM 952 515 DG M YPV SCI 1000 FM952 516 DG M YPV SCI 600 FM2x 950 505 2x DG PV 500 SCP FM

900 550 DG TT 230 400 FM 952 315 DG M TT 275 FM

900 560 DG TNS 230 400 FM 952 405 DG M TNS 275 FM

900 600 DG 275 952 070 DG S 275

900 601 DG 600 952 076 DG S 600

900 602 DG 385 952 074 DG S 385

900 603 DG 150 952 072 DG S 150

900 604 DG 75 952 071 DG S 75

900 605 DG 320 952 073 DG S 320

900 607 DG 440 952 075 DG S 440

900 620 DG 275 FM 952 090 DG S 275 FM

900 621 DG 600 FM 952 096 DG S 600 FM

900 622 DG 385 FM 952 094 DG S 385 FM

900 623 DG 150 FM 952 092 DG S 150 FM

900 624 DG 75 FM 952 091 DG S 75 FM

900 625 DG 320 FM 952 093 DG S 320 FM

900 627 DG 440 FM 952 095 DG S 440 FM

900 641 DG T 385 952 074 DG S 385

900 650 DG T 275 952 070 DG S 275

900 651 DG T 600 952 076 DG S 600900 652 DG T 320 952 073 DG S 320

900 653 DG T 150 952 072 DG S 150

900 654 DG T 75 952 071 DG S 75

900 655 DG T 440 952 075 DG S 440

900 659 DG T 275 VA 952 082 DG S 275 VA

900 667 DG T 75 VA 952 080 DG S 75 VA

900 680 DG T 275 FM 952 090 DG S 275 FM

900 681 DG T 600 FM 952 096 DG S 600 FM

900 682 DG T 320 FM 952 093 DG S 320 FM

900 683 DG T 150 FM 952 092 DG S 150 FM

900 684 DG T 75 FM 952 091 DG S 75 FM

900 685 DG T 440 FM 952 095 DG S 440 FM

900 689 DG T 275 VA FM 952 087 DG S 275 VA FM900 691 DG T 385 FM 952 094 DG S 385 FM

900 692 DG T 75 VA FM 952 085 DG S 75 VA FM

901 000 VAV 1000 950 102 DG 1000 or

950 112 DG 1000 FM

902 375 VA NH00 280 3 IG FM –

902 376 VA NH00 280 4 IG FM –

902 385 VA NH00 280 3 IG –

902 386 VA NH00 280 4 IG –

950 220 DG T 48 952 078 DG S 48

950 225 DG T 48 FM 952 098 DG S 48 FM

Surge Arresters – Type 3

901 100 DR 230 FML 953 205 DR M 2P 255 FM or

953 200 DR M 2P 255901 101 DR 120 FML 953 209 DR M 2P 150 FM or

953 204 DR M 2P 150

901 102 DR 60 FML 953 208 DR M 2P 75 FM or

953 203 DR M 2P 75

901 103 DR 48 FML 953 207 DR M 2P 60 FM or

953 202 DR M 2P 60

901 104 DR 24 FML 953 206 DR M 2P 30 FM or

953 201 DR M 2P 30

901 130 DR 230 3N FML 953 405 DR M 4P 255 FM or

953 400 DR M 4P 255

909 820 SF PRO 909 240 DPRO 230 F

909 821 S PRO 909 230 DPRO 230

Mains Connection Boxes

900 964 NAK 63A 4 951 400 DV M TNS 255

900 965 NAK 63A 3 951 300 DV M TNC 255

900 966 NAK 35A 4 951 400 DV M TNS 255

900 967 NAK 35A 3+1 951 310 DV M TT 255

900 968 NAK 35A 3 951 300 DV M TNC 255

900 969 NAK 63A 3+1 951 310 DV M TT 255

902 492 NAK TAB 3 900 390 DV ZP TNC 255

902 493 NAK TAB 3+1 900 391 DV ZP TT 255

902 494 NAK TAB 4 900 391 DV ZP TT 255

Accessories

900 309 IGA 10 IP54 902 315 IGA 10 V2 IP54

902 480 IGA 10 IP55 902 315 IGA 10 V2 IP54

900 121 DBR 35 –

900 122 DBR 63 –

900 699 DK 35 952 699 DK 25

Isolating Spark Gaps

923 070 EXFS C1 923 100 EXFS 100

923 071 EXFS C1 KU 923 101 EXFS 100 KU

Discontinued Products AlternativesPart No. Type Part No. Type

Discontinued Products AlternativesPart No. Type Part No. Type

Page 32: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 32/382

POWER SUPPLY SYSTEMS

www.dehn.de30

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs –Type 1

www.dehn.de

Page 33: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 33/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

31www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

C o m b i n e

d S P D s T y p e 1

DEHNventil® modular

Multipole modular combined lightning current andsurge arresterSPD Type 1 according to EN 61643-11

SPD Class I according to IEC 61643-1

• Prewired spark-gap-based combined lightningcurrent and surge arrester, consisting of a basepart and plug-in protection modules

• Maximum system availability due to RADAXFlow follow current limitation

• No tripping of 20 A gL/gG fuses up to short-cir-cuit currents of 50 kArms

• Discharge capacity up to 100 kA (10/350 µs)

• Protection of terminal devices

• Operating state/fault indication by indicatorflag in the inspection window

• Easy replacement of protection modules with-out tools due to module locking system withmodule release button

• Vibration- and shock-tested according to EN60068-2

For protecting low-voltage consumer´s installations against surges andeven direct lightning strikes. For installation in conformity with the light-ning protection zones concept at the boundaries from 0A – 2.

With their functional Red/Line design, the devices of the modularDEHNventil family combine safety and innovation. Designed for ”all-in-one installation”, the SPDs integrate lightning equipotential bonding andprotection against surges in a single device.This function is particularly of advantage in compact electrical installations. The design of the SPDsaccording to energy coordination criteria even allows protection of termi-

nal devices if they are close to the consumers ( 5 m). With their light-ning current discharge capacity up to 100 000 A, the SPDs ensure highavailability of the electrical installation to be protected. Even for expand-ed electrical installations, the modular DEHNventil devices offer variousapplication possibilities. Red/Line surge arresters installed at the bound-aries of the individual lightning protection zones are already energy-coor-dinated with DEHNventil devices. By using encapsulated creepage dis-charge spark gaps, combined with a compact design, DEHNventil unitsare well suited for use in switchgear installations or distribution boards.A special feature of the new modular DEHNventil family is its functionaldesign.The module release button is a key element. It ensures reliable fix-ation of the protection module to keep the safe connection to the basepart even in case of maximum loads. If protection modules have to bereplaced, the module is released without tools and can be removed easi-ly.The devices incorporate double terminals which are suitable for all con-ductors, allowing series connection in a space- and cost-effective wayaccording to IEC 60364-5-53 requirements for nominal currents up to125 A. For connecting further DIN rail mounted devices, busbars of type

MVS 3 8 6 and MVS 4 11 8 can beused. The right DEHNventil devicescan be easily chosen according tothe system configuration of thelow-voltage consumer´s installa-tion and type designation of the

device.

The patented RADAX Flow technol-ogy ensures follow current limita-tion and extinction as well as max-imum system availability of electri-cal installations to be protected. Even in case of short-circuit currents ashigh as 50 kArms, mains follow currents are reduced in such a way thatthere is a selectivity to lower fuse values, i.e. upstream fuses will not tripdue to arising mains follow currents.

The operating state/fault indication of each protective circuit immediate-ly provides information on the operating state of the surge arrester evenif no operating current is present. Apart from the standard green and redindicator, DEHNventil M ... FM devices feature a three-pole terminal forremote signalling.With their floating changeover contact, the remote sig-nal can be used as a break or make contact according to the particular cir-cuit concept.

DEHNventil M TNC 255: Modular combined lightning current and surge arrester for use in TN-C systems

DEHNventil M TNS 255: Modular combined lightning current and surge arrester for use in TN-S systems

DEHNventil M TT 255: Modular combined lightning current and surge arrester for use in TT and TN-S systems

(”3+1” circuit)DEHNventil M TN 255: Modular combined lightning current and surge arrester for use in single-phase TN systems

DEHNventil M TT 2P 255: Modular combined lightning current and surge arrester for use in single-phase TT and TN systems(”1+1” circuit)

DEHNventil M ... FM: With remote signalling contact for monitoring device (floating changeover contact)

Page 34: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 34/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

32 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

DEHNventil® modular

DEHNventil M TNC (FM)951 300 DV M

TNC255

951 305 DV M

TNC255FM

DVM TN C2 5 5

951 300

DVM TN C2 5 5 FM

951 305

12

1114

L2 L2´

PEN

L1 L1´ L3 L3´

Basic circuit diagram DV M TNC 255 FM Dimension drawing DV M TNC 255 (FM)

DV M TNC 255 (FM): Modular combined lightning current and surge arrester for protecting TN-Csystems against surges

DV M TNC 255 DV M TNC 255 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I

Energy-coordinated protection effect with

regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2

Energy-coordinated protection effect with

regard to the terminal equipment ( 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3

Nominal a.c. voltage UN 230 / 400 V 230 / 400 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] Itotal 75 kA 75 kA

Lightning impulse current (10/350 µs) [L-PEN] Iimp 25 kA 25 kA

Nominal discharge current (8/20 µs) In 25 / 75 kA 25 / 75 kA

Voltage protection level UP 1.5 kV 1.5 kV

Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms

Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns

Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gG

Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) UT 440 V / 5 sec. 440 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C

Operating state/fault indication green / red green / red

Cross-sectional area (L1, L1 , L2, L2 , L3, L3 , PEN,9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (L1, L2, L3, PEN) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L1 , L2´, L3´,9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20Capacity 6 mods., DIN 43880 6 mods., DIN 43880

Approvals, Certifications KEMA,VDE, UL,VdS KEMA, VDE,UL, VdS

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DV M TNC 255 DV M TNC 255 FM

Part No. 951 300 951 305

Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular

Spark-gap-based protection modulePU Part

Type pc(s). No.

DV MOD 255 1 951 001

951 001 DV MOD

255

DVM O D2 5 5

951 001

Page 35: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 35/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

33www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

C o m b i n e

d S P D s T y p e 1

DEHNventil® modular

DEHNventil M TNS (FM)DV M TNS

DV M TNS

12

1114

L2 L2´ N N´

PE

L1 L1´ L3 L3´

Basic circuit diagram DV M TNS 255 FMDimension drawing DV M TNS 255 (FM)

DV M TNS 255 (FM): Modular combined lightning current and surge arrester for protecting TN-Ssystems against surges

DV M TNS 255 DV M TNS 255 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I

Energy-coordinated protection effect with

regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2

Energy-coordinated protection effect with

regard to the terminal equipment ( 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3

Nominal a.c. voltage UN 230 / 400 V 230 / 400 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] Itotal 100 kA 100 kA

Lightning impulse current (10/350 µs) [L, N-PE] Iimp 25 kA 25 kA

Nominal discharge current (8/20 µs) In 25 / 100 kA 25 / 100 kA

Voltage protection level [L-PE]/[N-PE] UP 1.5 kV / 1.5 kV 1.5 kV / 1.5 kV

Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms

Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns

Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gG

Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) [L-N] UT 440 V / 5 sec. 440 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C

Operating state/fault indication green / red green / red

Cross-sectional area (L1, L1 , L2, L2 , L3, L3 , N, N´, PE,9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (L1, L2, L3, N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L1´, L2´, L3´, N´,9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20Capacity 8 mods., DIN 43880 8 mods., DIN 43880

Approvals, Certifications KEMA, VDE, UL,VdS KEMA, VDE,UL, VdS

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DV M TNS 255 DV M TNS 255 FM

Part No. 951 400 951 405

Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular

951 001 DV MOD

255

DV MOD 255 Kombi-

Able it er- Schutzmodul 951 001

Spark-gap-based protection modulePU Part

Type pc(s). No.

DV MOD 255 1 951 001

Page 36: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 36/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

34 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

DEHNventil® modular

DEHNventil M TT (FM)951 310 DV M TT

255

951 315 DV M TT

255FM

DVM TT2 5 5

951 310

DVM TT2 5 5 FM

951 315

12

1114

L2 L2´ N N´

PE

L1 L1´ L3 L3´

NPE

Basic circuit diagram DV M TT 255 FM Dimension drawing DV M TT 255 (FM)

DV M TT 255 (FM): Modular combined lightning current and surge arrester for protecting TT andTN-S systems (”3+1” circuit) against surges

DV M TT 255 DV M TT 255 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I

Energy-coordinated protection effect with

regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2Energy-coordinated protection effect with

regard to the terminal equipment ( 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3

Nominal a.c. voltage UN 230 / 400 V 230 / 400 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] Itotal 100 kA 100 kA

Lightning impulse current (10/350 µs) [L-N]/[N-PE] Iimp 25 / 100 kA 25 / 100 kA

Nominal discharge current (8/20 µs) In 25 / 100 kA 25 / 100 kA

Voltage protection level [L-N]/[N-PE] UP 1.5 kV / 1.5 kV 1.5 kV / 1.5 kV

Follow current extinguishing capability [L-N]/[N-PE] Ifi 50 kArms / 100 Arms 50 kArms / 100 Arms

Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns

Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gGMax. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) [L-N] UT 440 V / 5 sec. 440 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand

Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C

Operating state/fault indication green / red green / red

Cross-sectional area (L1, L1 , L2, L2 , L3, L3 , N, N´, PE,9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (L1, L2, L3, N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L1´, L2´, L3´, N´,9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 8 mods., DIN 43880 8 mods., DIN 43880

Approvals, Certifications KEMA,VDE, UL,VdS KEMA, VDE,UL, VdS

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DV M TT 255 DV M TT 255 FM

Part No. 951 310 951 315

Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular

Spark-gap-based protection modulePU Part

Type pc(s). No.

DV MOD 255 1 951 001

951 001 DV MOD

255

DV MOD 255 Kombi-

A bleite r-Schutzmodul 951 001

Accessory part for DEHNventil® modular

N-PE spark-gap-based protection modulePU Part

Type pc(s). No.

DV MOD NPE 100 1 951 100

951 050 DV MOD NPE 50

951 100 DV MOD NPE 100

DVM O DN P E 5 0

951 050

DVMODNPE100

951 100

Page 37: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 37/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

35www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

C o m b i n e

d S P D s T y p e 1

DEHNventil® modular

DEHNventil M TN (FM)DV M TN

DV M TN

12

1114

L L´ N N´

PE

Basic circuit diagram DV M TN 255 FMDimension drawing DV M TN 255 (FM)

DV M TN 255 (FM): Modular combined lightning current and surge arrester for protecting single-phase TN systems against surges

DV M TN 255 DV M TN 255 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I

Energy-coordinated protection effect with

regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2Energy-coordinated protection effect with

regard to the terminal equipment ( 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3

Nominal a.c. voltage UN 230 V 230 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Lightning impulse current (10/350 µs) [L+N-PE] Itotal 50 kA 50 kA

Lightning impulse current (10/350 µs) [L, N-PE] Iimp 25 kA 25 kA

Nominal discharge current (8/20 µs) In 25 / 50 kA 25 / 50 kA

Voltage protection level [L-PE]/[N-PE] UP 1.5 kV / 1.5 kV 1.5 kV / 1.5 kV

Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms

Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns

Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gGMax. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) [L-N] UT 440 V / 5 sec. 440 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C

Operating state/fault indication green / red green / red

Cross-sectional area (L, L´, N, N´, PE,9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (L, N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L´, N´,9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 4 mods., DIN 43880 4 mods., DIN 43880

Approvals, Certifications KEMA, VDE, UL,VdS KEMA, VDE,UL, VdS

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DV M TN 255 DV M TN 255 FM

Part No. 951 200 951 205

Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular

951 001 DV MOD

255

DV MOD 255 Kombi-

Able it er- Schutzmodul 951 001

Spark-gap-based protection modulePU Part

Type pc(s). No.

DV MOD 255 1 951 001

Page 38: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 38/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

36 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

DEHNventil® modular

DEHNventil M TT 2P (FM)951 110 DV M TT

2P255

951 115 DV M TT

2P255FM

DVM TT2 P 2 5 5

951 110

DVM TT2 P 2 5 5 FM

951 115

12

1114

N N´

PE

L L´

NPE

Basic circuit diagram DV M TT 2P 255 FM Dimension drawing DV M TT 2P 255 (FM)

DV M TT 2P 255 (FM): Modular combined lightning current and surge arrester for protectingsingle-phase TT and TN systems (”1+1” circuit) against surges

DV M TT 2P 255 DV M TT 2P 255 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 1 / Class I Type 1 / Class I

Energy-coordinated protection effect with

regard to the terminal equipment Type 1 + Type 2 Type 1 + Type 2Energy-coordinated protection effect with

regard to the terminal equipment ( 5m) Type 1 + Type 2 + Type 3 Type 1 + Type 2 + Type 3

Nominal a.c. voltage UN 230 V 230 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Lightning impulse current (10/350 µs) [L+N-PE] I total 50 kA 50 kA

Lightning impulse current (10/350 µs) [L-N]/[N-PE] Iimp 25 / 50 kA 25 / 50 kA

Nominal discharge current (8/20 µs) In 25 / 50 kA 25 / 50 kA

Voltage protection level [L-N]/[N-PE] UP 1.5 kV / 1.5 kV 1.5 kV / 1.5 kV

Follow current extinguishing capability [L-N]/[N-PE] Ifi 50 kArms / 100 Arms 50 kArms / 100 Arms

Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns

Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG 315 A gL/gGMax. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) [L-N] UT 440 V / 5 sec. 440 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand

Operating temperature range [parallel]/[continuity] TU -40°C...+80°C / -40°C...+60°C -40°C...+80°C / -40°C...+60°C

Operating state/fault indication green / red green / red

Cross-sectional area (L, L´, N, N´, PE,9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (L, N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L´, N´,9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94-V-0 thermoplastic, red, UL 94-V-0

Degree of protection IP 20 IP 20

Capacity 4 mods., DIN 43880 4 mods., DIN 43880

Approvals, Certifications KEMA,VDE, UL,VdS KEMA, VDE,UL, VdS

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DV M TT 2P 255 DV M TT 2P 255 FM

Part No. 951 110 951 115

Packing unit 1 pc(s). 1 pc(s).

Accessory part for DEHNventil® modular

N-PE spark-gap-based protection modulePU Part

Type pc(s). No.

DV MOD NPE 50 1 951 050

DV MOD NPE 50 Kombi-

A bl ei te r- Sc hu tz mo du lN -P E5 0k A 9 51 05 0

Accessory part for DEHNventil® modular

Spark-gap-based protection modulePU Part

Type pc(s). No.

DV MOD 255 1 951 001

951 001 DV MOD

255

DV MOD 255 Kombi-

A bleite r-Schutzmodul 951 001

951 050 DV MOD NPE 50

Page 39: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 39/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

37www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

Protection Module for DEHNventil® modular

SPD Type 1 according to EN 61643-11SPD Class I according to IEC 61643-1

• High discharge capacity due to powerful creep-age discharge spark gap

• Maximum system availability due to RADAXFlow follow current limitation

• With module release button for replacing pro-tection modules without tools

• Operating state/fault indication by green/redindicator flag in the inspection window

• The plug-in protection module can be replacedwithout the need to de-energise and withoutremoving the cover plate of the distributionboard

DV MOD 255: Spark-gap-based protection module

DV MOD NPE 50: 50 kA N-PE spark-gap-based protection module

DV MOD NPE 100: 100 kA N-PE spark-gap-based protection module

For protecting low-voltage consumer´s installations against surges andeven direct lightning strikes. For installation in conformity with the light-ning protection zones concept at the boundaries from 0A – 2.

The spark-gap-based protection modules of the modular DEHNventilseries combine safety and innovation. Apart from the encapsulatedRADAX Flow spark gap technology, the compact protection componentsincorporate the complete monitoring circuit for controlling the energyflow of the spark gap, monitoring device and operating state/fault indica-tor.

The mechanical coding of the protection module prevents unintendedinterchanging of the N-PE protection modules with the spark-gap-basedmodule for the phase conductors.

The module locking device ensures safe fixation of the protection modulesin the base part. The protection modules are easily removed without theuse of tools by simply pressing the module release button.

C o m b i n e

d S P D s T y p e 1

Page 40: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 40/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

38 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

Protection Module for DEHNventil® modular

Spark-gap-based protection module951 001 DV MOD

255

DVMOD255

951 001

Basic circuit diagram DV MOD 255 Dimension drawing DV MOD 255

DV MOD 255: Spark-gap-based protection module

DV MOD 255

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) I imp 25 kA

Follow current extinguishing capability [L-N] a.c. Ifi 50 kArms

Follow current limitation/Selectivity no tripping of a 20 A gL/gG fuse up to 50 kA rms (prosp.)

Ordering information

Type DV MOD 255

Part No. 951 001

Packing unit 1 pc(s).

N-PE spark-gap-based protection module951 050 DV MOD

NPE50

951 100 DV MOD

NPE100

DVM O DN P E 5 0

951 050

DVMODNPE100

951 100

NPE

Basic circuit diagram DV MOD NPE ... Dimension drawing DV MOD NPE ...

DV MOD NPE 50: 50 kA N-PE spark-gap-based protection moduleDV MOD NPE 100: 100 kA N-PE spark-gap-based protection module

DV MOD NPE 50 DV MOD NPE 100

Max. continuous operating a.c. voltage UC 255 V 255 V

Lightning impulse current (10/350 µs) I imp 50 kA 100 kA

Follow current extinguishing capability [N-PE] a.c. Ifi 100 Arms 100 Arms

Ordering informationType DV MOD NPE 50 DV MOD NPE 100

Part No. 951 050 951 100

Packing unit 1 pc(s). 1 pc(s).

Page 41: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 41/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

39www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

C o m b i n e

d S P D s T y p e 1

DEHNventil® ZP

Multipole combined lightning current andsurge arrester for primary power systemsSPD Type 1 according to EN 61643-11

SPD Class I according to IEC 61643-1

• Combined lightning current and surge arrester based on RADAXFlow spark gap technology

• Fully compliant with all requirements of the national VDN*Directive on the use of SPDs upstream of the meter

• Quick and easy installation by snapping the SPD onto 40 mm bus-bar systems

• Test for correct operation by pressing the button with light indi-cator

• No tripping of fuses from 32 A gL/gG up to short-circuit currentsof 25 kArms

• Discharge capacity up to 100 kA (10/350 µs)

• Protection of terminal equipment

• Maximum system availability

For protecting low-voltage consumer´s installa-tions against surges and even direct lightningstrikes. For installation in conformity with thelightning protection zones concept at theboundaries from 0A – 2.

The DEHNventil ZP combined lightning currentand surge arrester is specifically designed forconnection to busbar panels of supply meters. Itcan be snapped directly onto the busbar systemwithout the need for tools. Its reduced sizeleaves enough space for connecting cables fromthe service entrance box (SEB), even if threeselective main circuit breakers are installed.The operating state of the SPD is indicated by alight indicator which is controlled by a button.

Both with this kind of operating state controland due to its design as a spark-gap-based SPD,the DEHNventil ZP device has no leakage andoperating currents.The RADAX Flow spark gap technology allowsthe required selectivity for follow currents evenfor small-sized fuses in the service entrancebox. Unwanted interruptions of the power sup-ply due to tripping of main fuses are thus avoid-ed.The dimensioning of the parameters as well asthe complete concept of the device are fullycompliant with all requirements of the new

German VDN* Directive on the use of surge protective devices in primary power systems.

* VDN ... Verband der Netzbetreiber VDN e.V. at BDEW[Association of German network operators]

DEHNventil ZP TNC 255: Three-pole combined lightning current and surgearrester for TN-C systems for use in primary power sys-tems

DEHNventil ZP TT 255: Four-pole combined lightning current and surge

arrester for TT and TN-S systems for use in primarypower systems

Page 42: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 42/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

40 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

DEHNventil® ZP

DEHNventil ZP TNC900 390 DV ZP

TNC255

DVZ P TN C2 5 5

900 390

L1

L2

L3

&

PEN

PEN

Basic circuit diagram DV ZP TNC 255 Dimension drawing DV ZP TNC 255

DV ZP TNC 255: Combined lightning current and surge arrester for TN-C systems for use in primarypower systems (”3-0” circuit)

DV ZP TNC 255

SPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Energy-coordinated protection effect with regard to the terminal equipment Type 1 + Type 2

Energy-coordinated protection effect with regard to the terminal equipment ( 5m) Type 1 + Type 2 + Type 3

Nominal a.c. voltage UN 230 / 400 V

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] Itotal 75 kA

Lightning impulse current (10/350 µs) [L-PEN] Iimp 25 kA

Nominal discharge current (8/20 µs) In 25 / 75 kA

Voltage protection level UP 1.5 kV

Follow current extinguishing capability a.c. Ifi 25 kArms

Follow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 25 kA rms (prosp.)

Response time tA 100 ns

Max. backup fuse up to I = 25 kArms 315 A gL/gG

Max. backup fuse for IK > 25 kArms 200 A gL/gG

Temporary overvoltage (TOV) UT 335 V / 5 sec.

TOV characteristics withstand

Operating temperature range TU -40°C...+80°C

Function control button with light indicator

Cross-sectional area (PEN,9) 10-35 mm2 flexible/50 mm2 stranded

For mounting on 40 mm busbar system

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 3 mods., DIN 43880

Certifications, Approvals VDE

Ordering information

Type DV ZP TNC 255

Part No. 900 390

Packing unit 1 pc(s).

Page 43: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 43/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

41www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

C o m b i n e

d S P D s T y p e 1

DEHNventil® ZP

DEHNventil ZP TTDV ZP TT

&

* in case of existing PE busbar

L1

L2

L3

N

PE*

PE

Basic circuit diagram DV ZP TT 255Dimension drawing DV ZP TT 255

DV ZP TT 255: Combined lightning current and surge arrester for TT and TN-S systems for use inprimary power systems (”3+1” circuit)

DV ZP TT 255

SPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Energy-coordinated protection effect with regard to the terminal equipment Type 1 + Type 2

Energy-coordinated protection effect with regard to the terminal equipment ( 5m) Type 1 + Type 2 + Type 3

Nominal a.c. voltage UN 230 / 400 V

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] I imp 100 kA

Lightning impulse current (10/350 µs) [L-N] Iimp 25 kA

Lightning impulse current (10/350 µs) [N-PE] Iimp 100 kA

Nominal discharge current (8/20 µs) In 25 / 100 kA

Voltage protection level [L-N] UP 1.5 kV

Voltage protection level [N-PE] UP 1.5 kV

Follow current extinguishing capability [L-N] a.c. Ifi 25 kArms

Follow current extinguishing capability [N-PE] a.c. Ifi 100 Arms

Follow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 25 kA rms (prosp.)

Response time tA 100 ns

Max. backup fuse up to I = 25 kArms 315 A gL/gG

Max. backup fuse for IK > 25 kArms 200 A gL/gG

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms

TOV characteristics withstand

Operating temperature range TU -40°C...+80°C

Function control button with light indicator

Cross-sectional area (PE,9) 10-35 mm2 flexible/50 mm2 stranded

For mounting on 40 mm busbar system

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 3 mods., DIN 43880

Certifications, Approvals VDE

Ordering information

Type DV ZP TT 255

Part No. 900 391

Packing unit 1 pc(s).

Page 44: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 44/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

42 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

DEHNlimit PV 1000

Type 1 combined lightning current andsurge arrester for use in photovoltaic systems SPD Type 1 classification according to EN 61643-11

SPD Class I classification according to IEC 61643-1

• Prewired combined lightning current and surgearrester for use in photovoltaic generator cir-cuits

• For use in photovoltaic installations up to1000 V UCPV

• High lightning current discharge capacity dueto approved spark gap technology

• Maximum system availability due to spark gaptechnology with d.c. current extinction

DEHNlimit PV 1000: Combined lightning current and surge arrester for use in photovoltaic power supply systems up to1000 V d.c.

For protecting photovoltaic inverters against surges and even direct light-ning strikes. For use in accordance with IEC 60364-7-712:2002-05(Installation of photovoltaic power supply systems).

The combined lightning current and surge arrester of type DEHNlimit PV1000 was specifically developed for use in photovoltaic power supply sys-tems. The approved encapsulated creepage discharge spark gap technol-ogy allows reliable protection of photovoltaic generators and inverterseven in the event of direct lightning impulse currents. It is the voltage pro-tection level of DEHNlimit PV 1000 and reduction of the impulse time dueto the spark gap technology that allow for coordination of the SPD withthe equipment to be protected.

The d.c. extinction by the spark gap is a unique feature of DEHNlimit PV1000. Potential short-circuit currents up to 100 A caused by a trippingspark gap are interrupted within only a fraction of a second in case of aphotovoltaic voltage up to 1000 V d.c.

The combination of lightning current carrying capability, protection capa-bility and follow current extinction provides maximum availability of thePV system protected by DEHNlimit PV 1000.

Page 45: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 45/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

43www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

C o m b i n e

d S P D s T y p e 1

DEHNlimit PV 1000

DEHNlimit PV 1000DLM PV

d.c. control bypass

L+ L–

Basic circuit diagram DLM PV 1000

(8 mods.)

Dimension drawing DLM PV 1000

DLM PV 1000: Combined lightning current and surge arrester for use in photovoltaic powersupply systems up to 1000 V d.c.

DLM PV 1000

SPD classification according to EN 61643-11 Type 1

SPD classification according to IEC 61643-1 Class I

Max. PV voltage [UCPV ] of the PV generator 1000 V

Max. continuous operating d.c. voltage Umax dc 1000 V

Min. continuous operating d.c. voltage Umin dc 100 V

Follow current extinguishing capability d.c. If i dc 100 A

Nominal discharge current (8/20 µs) In 100 kA

Lightning impulse current (10/350 µs) [L+/L- -> PE] Iimp 50 kA

Lightning impulse current (10/350 µs) [L+ -> L-] Iimp 25 kA

Voltage protection level [L+ -> L-] Up 3.3 kV

Voltage protection level [(L+/L-) -> PE] Up 4 kV

Operating current IIN dc 5 mA

Response time [L+ -> L-] tA 20 ns

Protective conductor current IPE 1 µA

Operating temperature range Tu -40°C...+60°C

Cross-sectional area (min.) 10 mm2 solid/flexible

Cross-sectional area (max.) 50 mm2 stranded/ 35 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 8 mods., DIN 43880

Ordering information

Type DLM PV 1000

Part No. 900 330Packing unit 1 pc(s).

Page 46: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 46/382

POWER SUPPLY SYSTEMS

COMBINED SPDs – TYPE 1

44 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

Combined SPDs–Type 1

www.dehn.dewww.dehn.dewww.dehn.de

Page 47: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 47/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

45www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNbloc® M

Single-pole modular coordinatedlightning current arresterSPD Type 1 according to EN 61643-11

SPD Class I according to IEC 61643-1

• Coordinated spark-gap-based lightning currentarrester consisting of a base part and plug-inprotection module

• Maximum system availability due to RADAXFlow follow current limitation

• No tripping of 32 A gL/gG fuses up to short-cir-cuit currents of 50 kArms

• Discharge capacity up to 50 kA (10/350 µs)

• Directly coordinated with DEHNguard surgeprotective devices without additional cablelength

• Low voltage protection level• Operating state/fault indication by indicator

flag in the inspection window

• Easy replacement of protection modules with-out tools due to module locking system withmodule release button

DEHNbloc M 1 ...: Single-pole modular coordinated lightning current arrester with high follow current limitation

DEHNbloc M 1 ... FM: With remote signalling contact for the monitoring system (floating changeover contact)

For protecting low-voltage consumer´s installations against surges andeven direct lightning strikes. For installation in conformity with the light-ning protection zones concept at the boundaries from 0A – 1.

The modular devices of the DEHNbloc M product family are coordinatedlightning current arresters with a functional design.

Energy coordination with Type 2 surge arresters of the DEHNguard fami-ly is ensured without additional cable lengths or decoupling coils. This isone of the most important characteristics of the Red/Line product family.

The DEHNbloc M devices stand for performance and user friendliness in aconcise form.Their electrical parameters were rated for maximum require-ments for lightning and surge protection systems. DEHNbloc M is the ideal

device for use in main distribution boards of low-voltage consumer´sinstallations of a building. Equipped with the latest RADAX Flow sparkgap technology, the most important goal of DEHNbloc M is to ensure pro-tection and availability of electrical installations.

Due to the unique follow current limitation and follow current extinction,a follow current breaking selectivity is ensured even for small-sized fusesin installations. DEHNbloc M is leakage-current-free and has a mechani-cal operating state indication, allowing the device to be installed evenupstream of meter panels in low-voltage consumer´s installations.

When installing this modular arrester, the user of DEHNbloc M has allsafety characteristics and features this design has to offer. The vibration-

proof module locking system, for example, is unique. Shock or vibration

during transport or operation orenormous mechanical impulseloads resulting from discharges donot affect the module locking sys-tem which ensures safe fixationboth for the base part and protec-tion module. Nevertheless, the pro-tection modules can be easilyreplaced without tools by simplypressing the user-friendly module

release button. In order to avoidincorrect insertion by the installeror user when replacing the modules, both the base part and protectionmodule are mechanically coded. DEHNbloc M devices incorporate doubleterminals which are suitable for all conductors, allowing series connectionof the SPDs in a space- and cost-saving way according to IEC 60364-5-53requirements for nominal currents up to 125 A.

The operating state/fault indication of DEHNbloc M immediately providesinformation on the availability of the device even if no operating currentis present. Apart from the standard red and green indicator, DEHNbloc M... FM devices have an additional remote signalling output. With theirfloating changeover contact, the remote signal can be used as a break or

make contact according to the particular circuit concept.

Page 48: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 48/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

46 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNbloc® M

DEHNbloc M 1 ...961 110 DB M 1150961 120 DB M 1255961 130 DB M 1320

DB M 1 1 5 0961 110DB M 1 2 5 5961 120DB M 1 3 2 0961 130

L/N

N/PE(N)

Basic circuit diagram DB M 1 ...

(2 mods.)

Dimension drawing DB M 1 ...

DB M 1 ...: Single-pole, modular, coordinated lightning current arrester with high follow currentlimitation

DB M 1 150 DB M 1 255 DB M 1 320

SPD according to EN 61643-11 Type 1 Type 1 Type 1

SPD according to IEC 61643-1 Class I Class I Class I

Max. continuous operating a.c. voltage UC 150 V 255 V 320 V

Lightning impulse current (10/350 µs) I imp 35 kA 50 kA 25 kA

Nominal discharge current (8/20 µs) In 35 kA 50 kA 25 kA

Voltage protection level UP 1.5 kV 2.5 kV 2.5 kV

Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms 50 kArms

Follow current limitation/Selectivity no tr ipping of a 32 A gL /gG no tripping of a 32 A gL/gG no tripping of a 32 A gL/gG

fuse up to 50 kArms (prosp.) fuse up to 50 kArms (prosp.) fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns 100 ns

Max. backup fuse (L) up to IK = 50 kArms (ta 0.2 s) 500 A gL/gG 500 A gL/gG 315 A gL/gG

Max. backup fuse (L) up to IK = 50 kArms (ta 5 s) 315 A gL/gG 315 A gL/gG 315 A gL/gG

Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG 200 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) UT 200 V / 5 sec. 440 V / 5 sec. 440 V / 5 sec.

TOV characteristics withstand withstand withstand

Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C -40°C...+60°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (L/N, L´/N , N/PE (N)) min. 10 mm2 solid/flexible 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (L/N, N/PE(N)) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L´/N´) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880Test standards — VDE, KEMA —

Ordering information

Type DB M 1 150 DB M 1 255 DB M 1 320

Part No. 961 110 961 120 961 130

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNbloc® M

DB M spark-gap-based protection modulePU Part

Type pc(s). No.

DB M MOD 150 1 961 001

DB M MOD 255 1 961 002

DB M MOD 320 1 961 003

961 001 DB MMOD150961 002 DB MMOD255961 003 DB MMOD320

DB M M O D1 5 0961 001DB M M O D2 5 5961 002DB M M O D3 2 0961 003

N E W

Page 49: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 49/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

47www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNbloc® M

DEHNbloc M 1 ... FMDB M 1

DB M 1

DB M 1

12

1114

L/N

N/PE(N)

Basic circuit diagram DB M 1 ... FM

(2 mods.)

Dimension drawing DB M 1 ... FM

DB M 1 ... FM: Single-pole, modular, coordinated lightning current arrester with high follow cur-rent limitation; with remote signalling contact for the monitoring system (floatingchangeover contact)

DB M 1 150 FM DB M 1 255 FM DB M 1 320 FM

SPD according to EN 61643-11 Type 1 Type 1 Type 1

SPD according to IEC 61643-1 Class I Class I Class I

Max. continuous operating a.c. voltage UC 150 V 255 V 320 V

Lightning impulse current (10/350 µs) Iimp 35 kA 50 kA 25 kA

Nominal discharge current (8/20 µs) In 35 kA 50 kA 25 kA

Voltage protection level UP 1.5 kV 2.5 kV 2.5 kV

Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms 50 kArms

Follow current limitation/Selectivity no tripping of a 32 A gL/gG no tripping of a 32 A gL/gG no tripping of a 32 A gL/gG

fuse up to 50 kArms (prosp.) fuse up to 50 kArms (prosp.) fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns 100 ns

Max. backup fuse (L) up to IK = 50 kArms (ta 0.2 s) 500 A gL/gG 500 A gL/gG 315 A gL/gG

Max. backup fuse (L) up to IK = 50 kArms (ta 5 s) 315 A gL/gG 315 A gL/gG 315 A gL/gG

Max. backup fuse (L) for IK > 50 kArms 200 A gL/gG 200 A gL/gG 200 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) UT 200 V / 5 sec. 440 V / 5 sec. 440 V / 5 sec.

TOV characteristics withstand withstand withstand

Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C -40°C...+60°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (L/N, L´/N´, N/PE (N)) min. 10 mm2 solid/flexible 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (L/N, N/PE(N)) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L´/N´) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880Test standards — VDE, KEMA —

Type of remote signalling contact changeover contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DB M 1 150 FM DB M 1 255 FM DB M 1 320 FM

Part No. 961 115 961 125 961 135

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

N E W

Accessory Part for DEHNbloc® M

961 001 DB MMOD150961 002 DB MMOD255961 003 DB MMOD320

DB M MOD 150 ÜS-Modulfür DB M, 150 V 961 001DB M MOD 255 ÜS-Modulfür DB M, 255 V 961 002DB M MOD 320 ÜS-Modulfür DB M, 320 V 961 003

DB M spark-gap-based protection modulePU Part

Type pc(s). No.

DB M MOD 150 1 961 001

DB M MOD 255 1 961 002

DB M MOD 320 1 961 003

Page 50: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 50/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

48 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

Protection Module for DEHNbloc® M

SPD Type 1 according to EN 61643-11SPD Class I according to IEC 61643-1

• High discharge capacity due to powerful creep-age discharge spark gap

• Maximum system availability due to RADAXFlow follow current limitation

• With module release button for replacing pro-tection modules without tools

• Operating state / fault indication by green / redindicator flag in the inspection window

• The plug-in protection module can be replacedwithout the need to de-energise and removingthe vertical cover

For protecting low-voltage consumer´s installations against surges andeven direct lightning strikes. For installation in conformity with the light-ning protection zones concept at the boundaries from 0A – 1.

The spark-gap-based protection modules for DEHNbloc M devices providethe complete protective circuit including RADAX Flow spark gap andmonitoring circuit for controlling the energy flow.The spark gap monitoring system and operating state and fault indication

are also integrated in the protection module.

In order to avoid incorrect insertion when replacing the protection mod-ules, every protection module is mechanically coded.

Like with all modular protective devices, protection modules are easily

replaced without tools by simply pressing the module release button.

961 001 DB MMOD150961 002 DB MMOD255961 003 DB MMOD320

DB M M O D1 5 0961 001DB M M O D2 5 5961 002DB M M O D3 2 0961 003

Basic circuit diagram DB M MOD ... Dimension drawing DB M MOD ...

DB M MOD ...: Spark-gap-based mains protection module

DB M MOD 150 DB M MOD 255 DB M MOD 320

Max. continuous operating a.c. voltage UC 150 V 255 V 320 V

Lightning impulse current (10/350 µs) I imp 35 kA 50 kA 25 kA

Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms 50 kArms

Follow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 50 kA rms (prosp.)

Ordering informationType DB M MOD 150 DB M MOD 255 DB M MOD 320

Part No. 961 001 961 002 961 003

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

DB M MOD ...: Spark-gap-based mains protection module

N E W

Page 51: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 51/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

49www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNbloc® Maxi

Coordinated lightning current arresterSPD Type 1 according to EN 61643-11SPD Class I according to IEC 61643-1

• Encapsulated RADAX Flow spark gap with highfollow current limitation

• No tripping of 32 A gL/gG fuses up to short-cir-cuit currents of 50 kArms

• High discharge capacity of lightning currents

• Directly coordinated with DEHNguard ... or V(A)NH ... surge protective devices without addi-tional cable length

• ”NH00” versions

• Low voltage protection level

DBM NH00 255: Coordinated single-pole lightning current arrester in NH design size 00 with high follow current limitationfor UC = 255 V

For protecting low voltage consumer’s installations against surges andeven direct lightning strikes. For installation in conformity with the light-ning protection zones concept at the boundaries from 0A – 1.

The coordinated DEHNbloc Maxi ... lightning current arrester adapts toevery kind of application. Be it in exposed locations or harsh industrialenvironments: DEHNbloc Maxi ... always offers the adequate solution.Thesingle-pole device is coordinated with the approved DEHNguard or V(A)NH surge arresters of the Red/Line family. Independent of cable lengthsand without the need for additional decoupling coils, the surge protectionconcept can be individually adapted to all operating conditions of theinstallation.

DEHNbloc Maxi uses the patented technologies of encapsulated creepagedischarge spark gaps and RADAX Flow follow current limitation. There isno need for installers to worry about safety distances from busbars or

equipment. This arrangement also eliminates the risk of tripped backupfuses resulting from the lack of selectivity between the protective deviceand any overcurrent protection systems that may be in place, ensuring thehighest possible system availability.

DEHNbloc Maxi NH00 255 was specifically designed for use in industrialdistribution boards and supply systems and can be easily installed in size00 NH fuse holders or NH disconnectors in a compact and space-savingway.

Page 52: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 52/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

50 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNbloc® Maxi

DEHNbloc Maxi NH00 255900 255 DBM NH00 255

DBMNH00255900 255

Basic circuit diagram DBM NH00 255 Dimension drawing DBM NH00 255

DBM NH00 255: Coordinated single-pole lightning current arrester in NH design, size 00, withhigh follow current limitation for UC = 255 V

DBM NH00 255SPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) I imp 25 kA

Nominal discharge current (8/20 µs) In 25 kA

Voltage protection level UP 2.5 kV

Follow current extinguishing capability a.c. Ifi 50 kArms

Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kA rms (prosp.)

Response time tA 100 ns

Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG

Temporary overvoltage (TOV) UT 440 V / 5 sec.

TOV characteristics withstand

Operating temperature range (parallel connection) TUP -40°C...+80°C

For mounting on NH fuse holder size 00

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IPX4W

Ordering information

Type DBM NH00 255

Part No. 900 255

Packing unit 1 pc(s).

N E W

Page 53: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 53/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

51www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNbloc® Maxi 440 / 760

Coordinated lightning current arresterfor nominal voltages 400 V and 690 VSPD Type 1 according to EN 61643-11

SPD Class I according to IEC 61643-1

• Encapsulated non-exhausting spark gap

• High follow current extinguishing capability

and follow current limitation due to RADAXFlow technology

• Directly coordinated with DEHNguard surgeprotective devices without additional cablelength

• Operating state/fault indication by indicatorflag in window

DEHNbloc Maxi 1 440: Coordinated single-pole lightning current arrester with high follow current limitation forUC = 440 V

DEHNbloc Maxi 1 440 FM: With remote signalling contact for the monitoring system (floating changeover contact)DEHNbloc Maxi 1 760 FM: Coordinated single-pole lightning current arrester with high follow current limitation for

UC = 760 V; with remote signalling contact for the monitoring system (floating changeover con-tact)

For protecting low-voltage consumer´s installations against surges andeven direct lightning strikes. For installation in conformity with the light-ning protection zones concept at the boundaries from 0A – 1.

The coordinated DEHNbloc Maxi 440 and 760 lightning current arresterswere specifically designed for higher system voltages.This allows to reliably protect a variety of industrial applications againstdirect and indirect lightning currents.Be it in a wind turbine or isolated low-voltage installation of an industri-al enterprise, DEHNbloc Maxi devices excellently meet all requirements.

Both the design of the protective circuit and the enclosure specifically

designed for this type of devices are particularly adapted to high systemvoltages.The core of the coordinated DEHNbloc Maxi 440 and 760 lightning cur-rent arresters is the approved RADAX Flow technology.Their capability of considerably limiting mains-frequency follow currents and extinguishingthem within a matter of milliseconds places these devices in a specialposition.The patented RADAX Flow follow current limitation allows a follow cur-rent breaking selectivity, even for small-sized fuses in installations.Its capability to discharge lightning currents without damage and to sup-press mains follow currents without tripping of upstream overcurrent pro-tective devices ensures high availability of electrical installations.The operating state/fault indication of the coordinated lightning current

arresters immediately provides information on the availability of the

devices even if no operating current is present. Apart from the standardvisual green and red indication, DEHNbloc Maxi 1 ... FM features a three-pole remote signalling terminal.With its floating changeover contact, theremote signal can be used as a break or make contact according to theparticular circuit concept.

Page 54: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 54/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

52 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNbloc® Maxi 440 / 760

DEHNbloc Maxi 1 440 (FM)961 140 DBM 1 440961 145 DBM 1 440 FM

DB M 1 4 4 0961 140DB M 1 4 4 0 FM961 145

L L

N/PEN

12

1114

Basic circuit diagram DBM 1 440 FM

( 2 mods.)

Dimension drawing DBM 1 440 FM

DBM 1 440 (FM): Coordinated, single-pole lightning current arrester with high follow current lim-itation for UC = 440 V

DBM 1 440 DBM 1 440 FM

SPD according to EN 61643-11 Type 1 Type 1SPD according to IEC 61643-1 Class I Class I

Max. continuous operating a.c. voltage UC 440 V 440 V

Lightning impulse current (10/350 µs) I imp 35 kA 35 kA

Nominal discharge current (8/20 µs) In 35 kA 35 kA

Voltage protection level UP 2.5 kV 2.5 kV

Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms

Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns

Max. backup fuse (L) up to IK = 50 kArms (ta 0.2 s) 500 A gL/gG 500 A gL/gG

Max. backup fuse (L) up to IK = 50 kArms (ta 5 s) 250 A gL/gG 250 A gL/gG

Max. backup fuse (L) for IK > 50 kArms 160 A gL/gG 160 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) UT 690 V / 5 sec. 690 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C

Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C

Operating state/fault indication green / red green / red

Cross-sectional area (L, L´, N/PEN) min. 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (L, N/PEN) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L´) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Type of remote signalling contact — changeover contactSwitching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DBM 1 440 DBM 1 440 FM

Part No. 961 140 961 145

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNbloc® Maxi 440 / 760

900 411 EB DG1000 1 3

E B DG 1 0 0 0 1 3900 411

Accessory Part for DEHNbloc® Maxi 440 / 760

900 417 EB 1 4 9

E B 1 4 9900 417

EB DG, 3-pole, single-phaseEarthing clip for earth-side jumpering of e.g. 3 Type 1 SPDs in a 2-module enclosure with multifunctional terminal

PU PartType Dimension Terminal pc(s). No.

EB DG 1000 1 3 34 x 112 x 3 mm up to 25 mm2 1 900 411

Earthing Clip, 4-pole, single-phaseEarthing clip for earth-side jumpering of e.g. 4 Type 1 SPDs in a 2-module enclosure with multifunctional terminal

PU PartType Dimension Terminal pc(s). No.

EB 1 4 9 34 x 148 x 3 mm up to 25 mm2 1 900 417

Page 55: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 55/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

53www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNbloc® Maxi 440 / 760

DEHNbloc Maxi 1 760 FMDBM 1 760 FM

L

9

12

1114

Basic circuit diagram DBM 1 760 FM

( 2 mods.)

9

Dimension drawing DBM 1 760 FM

DBM 1 760 FM: Single-pole, coordinated lightning current arrester with high follow currentlimitation for UC = 760 V

DBM 1 760 FM

SPD according to EN 61643-11 Type 1SPD according to IEC 61643-1 Class I

Max. continuous operating a.c. voltage UC 760 V

Lightning impulse current (10/350 µs) Iimp 25 kA

Nominal discharge current (8/20 µs) In 25 kA

Voltage protection level UP 4 kV

Follow current extinguishing capability a.c. Ifi 25 kArms

Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 25 kA rms (prosp.)

Response time tA 100 ns

Max. backup fuse (L) up to IK = 25 kArms (ta 5 s) 250 A gL/gG

Max. backup fuse (L) up to IK > 25 kArms 100 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 25 kArms

Temporary overvoltage (TOV) UT 1000 V / 5 sec.

TOV characteristics withstand

Operating temperature range (parallel connection) TUP -40°C...+80°C

Operating temperature range (series connection) TUS -40°C...+60°C

Operating state/fault indication green / red

Cross-sectional area (L, L´,9) min. 10 mm2 solid/flexible

Cross-sectional area (L,9) max. 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L´) max. 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 2 mods., DIN 43880

Type of remote signalling contact changeover contactSwitching capacity a.c. 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information

Type DBM 1 760 FM

Part No. 961 175

Packing unit 1 pc(s).

Accessory Part for DEHNbloc® Maxi 440 / 760

900 411 EB DG1000 1 3

E B DG 1 0 0 0 1 3E rd un gs bü ge l 1- ph as ig , 3- po li g, 8 T E 9 00 4 11

Accessory Part for DEHNbloc® Maxi 440 / 760

900 417 EB 1 4 9

E B 1 4 9E rd un gs bü ge l 1- ph as ig , 4- po li g, 9 T E 9 00 4 17

Earthing Clip, 4-pole, single-phaseEarthing clip for earth-side jumpering of e.g. 4 Type 1 SPDs in a 2-module enclosure with multifunctional terminal

PU PartType Dimension Terminal pc(s). No.

EB 1 4 9 34 x 148 x 3 mm up to 25 mm2 1 900 417

EB DG, 3-pole, single-phaseEarthing clip for earth-side jumpering of e.g. 3 Type 1 SPDs in a 2-module enclosure with multifunctional terminal

PU PartType Dimension Terminal pc(s). No.

EB DG 1000 1 3 34 x 112 x 3 mm up to 25 mm2 1 900 411

Page 56: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 56/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

54 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNbloc® Maxi S

Coordinated lightningcurrent arrester for busbars SPD Type 1 according to EN 61643-11

SPD Class I according to IEC 61643-1

• Combination of spark gap and integrated back-up fuse

• For mounting directly onto PEN/N busbars• Low voltage protection level UP 2.5 kV

(80 cm connecting cable included)

• Directly coordinated with DEHNguard surgeprotective device without additional cablelength

• Short-circuit withstand capability of 100 kArms

(220 kApeak)

• High follow current extinguishing capability

and follow current limitation due to RADAXFlow technology

• High lightning current discharge capacity

• With optical-fibre interface for monitoring theSPD

DEHNbloc Maxi 1 255 S: Coordinated lightning current arrester with integrated backup fuse for busbars

For protecting low voltage consumer´s installations against surges. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 0A – 1.

DEHNbloc Maxi S allows to better integrate surge protective devices intoapplication environments of a low-voltage switchgear installation or dis-

tribution board.Due to its unique mechanical design, the coordinated DEHNbloc Maxi Slightning current arrester can be mounted directly onto the PEN/N busbarof a switchgear installation without requiring additional adapters.With the backup fuse integrated into the device, no further separate back-up fuses need to be installed.Installing the DEHNbloc Maxi S devices directly into the terminal panel of the switchgear installation upstream of the circuit breaker ensures shortcable lengths of the SPDs and a low voltage protection level for the instal-lation.With a discharge capacity of 25 kA (10/350 µs) DEHNbloc Maxi S fulfilsthe most stringent requirements of national and international lightningprotection standards for all three-phase current applications in TN and TTsystems.For “3+1“ circuits, DEHNgap Maxi S provides a powerful creepage dis-charge spark gap with a discharge capacity of 100 kA (10/350 µs).

DEHNbloc Maxi S also features the patented RADAX Flow follow currentlimitation thus allowing selectivity, even for small-sized fuses.

The capability of conducting lightning impulse currents without damageand suppressing mains follow currents without tripping upstream over-current protective devices ensures the availability of the switchgearinstallation in case of a lightning strike and considerably reduces the riskof arc formation in the installation.Combined with the DEHNsignal remote signalling system, the availabilityof DEHNbloc Maxi S devices can be monitored at any time.An optical fibre transmission to the DEHNsignal E 3 receiver module,which is easy to perform, ensuressafe electrical isolation betweenthe power circuit and the remotesignalling circuit.

!

L1 L2 L3

P E N b u s b a r

N ' N L

L N

p o w e r s u p p l y 2 3 0 V ~

m a x . 1 6 A g l / g G ( C 1 6 A )

o p t i c a l f i b r e L W L D S I p l a s t i c m a x . 6 m

F

m a i n c i r c u i t b r e a k e r

S N L

N L(PEN)

TN-CDSI E 3

power supply

withwire

jumperS/N

e q u i p o t e n t i a l b o n d i n g

*) *) *)

*) DEHbloc Maxi S DBM 1 255 S

All three optical fibresmust be connected!

m a i n c i r c u i t b r e a k e r

P E b u s b a r

L1 L2 L3

N b u s b a r

e q u i p o t e n t i a l b o n d i n g

p o w e r s u p p l y 2 3 0 V ~

m a x . 1 6 A g l / g G ( C 1 6 A )

L N

N ' N L

o p t i c a l f i b r e L W L D S I p l a s t i c m a x . 6 m

F

DEHNgap Maxi SDGPM 1 255 S

S N L

N L

TT / TN-SDSI E 3

power supply

withoutwire

jumperS/N

**) *) *) *)

!All three optical fibres

must be connected!

*) DEHbloc Maxi S DBM 1 255 S

**) DEHNgap Maxi S DGPM 1 255 S

Application in a TT / TN-S system Application in a TN-C system

Page 57: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 57/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

55www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNbloc® Maxi S

DEHNbloc Maxi 1 255 SDBM 1 255 S

N/PEN

L

optical fibre

Basic circuit diagram DBM 1 255 SDimension drawing DBM 1 255 S

DBM 1 255 S: Coordinated single-pole lightning current arrester with integrated backup fuse forbusbars

DBM 1 255 SSPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) Iimp 25 kA

Nominal discharge current (8/20 µs) In 25 kA

Voltage protection level UP 2.5 kV (includes 80 cm connecting cable)

Follow current extinguishing capability a.c. Ifi 50 kArms

Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kA rms (prosp.)

Response time tA 100 ns

Short-circuit withstand capability 100 kArms (220 kApeak)

Temporary overvoltage (TOV) UT 335 V / 5 sec.

TOV characteristics withstand

Operating temperature range TU -40°C...+80°C

For mounting on PEN / N busbar min. 35 mm2

Connection type cable lug min. 35 mm2/max. 50 mm2

Enclosure material thermoplastic, red, UL 94 V-0

Dimension (W x H x D) 72 x 89 x 100 mm

Operating state indication by optical fibres via DSI E 3

Ordering information

Type DBM 1 255 S

Part No. 900 220

Packing unit 1 pc(s).

Accessory Part for DEHNbloc® Maxi S

910 641 LWL STDSI

LWL ST DSI Plug forOptical Fibre 910 641

910 642 LWL DSI18M

LWL DSI18M910 642

LWL DSI 18M

18 metres of plastic optical fibre, preferably for use with DEHNbloc

Maxi SPU Part

Type Diameter Length pc(s). No.

LWL DSI 18M 2.2 mm 18 m 1 910 642

LWL ST DSI

Plug for plastic optical fibres

PU PartType Diameter pc(s). No.

LWL ST DSI 2.2 mm 1 910 641

Accessory Part for DEHNbloc® Maxi S

910 631 DSI E 3

DSI E 3910 631

DEHNsignal E 3

DSI E 3: Receiver module for optical fibre transmission for selectiveoperating state indication / centralised fault indication of 3 coordina-ted DEHNbloc Maxi S and, if required, DEHNgap Maxi S lightning cur-rent arresters in 5-conductor systems

PU PartType pc(s). No.

DSI E 3 1 910 631

Page 58: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 58/382

POWER SUPPLY SYSTEMS

ACCESSORIES FOR SPDs TYPE 1

56 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

The receiver module for opti-

cal fibre transmission of typeDEHNsignal E 3 transmitsremote signals of DEHNblocMaxi S and DEHNgap Maxi Ssurge protective devices.

The receiver module for opti-cal fibre transmission of typeDEHNsignal E 3 is particular-ly adapted to the place of installation of the coordinat-ed DEHNbloc Maxi S andDEHNgap Maxi S surge pro-tective devices.

The receiver module for opti-cal fibre transmission is ableto telemonitor three DEHN-bloc Maxi S SPDs and, if required, the N-PE protectivecircuit via optical fibre cables.

Considering the special installation environment of the surge protective

devices in a switchgear installation, communication via optical fibre cablebetween the protective devices and the DEHNsignal E 3 receiver moduleis a considerable benefit in terms of safety.The readiness for operation of the individual SPDs is transmitted to theDEHNsignal E 3 receiver module in the form of a visual signal via EMC-safe plastic optical fibre cables. The visual signals are evaluated in theDEHNsignal E 3 receiver module and are converted into an electrical sig-nal. The signal of the operating states can be directly read out at theDEHNsignal E 3 receiver module or is provided via a floating changeovercontact. The DEHNsignal E 3 receiver module features a green indicatorlamp to check its operating state. In addition to the function indication,the three indicator lamps of the selective operating state indication showthat the assigned protective devices are ready for operation. The receivermodule indicates if a protective device of a phase fails. The surge protec-

tive devices and the DEHNsignal E 3 receiver module are easily connect-ed via optical fibre cable by using the accessory parts described.

DEHNsignal

Remote signalling and receiver moduleEN 61010-1; EN 61010-1/A2

• Operating state indication of the surge protec-tive device connected to it

• Indication of phase failures• Floating changeover contact

• Selective operating state indication

• Centralised fault indication

DEHNsignal E 3: Receiver module for optical fibre transmission for selective operating state indication / centralised faultindication of three coordinated lightning current arresters of type DEHNbloc Maxi S and DEHNgap Maxi S,if any, in 5-conductor systems

Receiver module for optical fibre transmission for DEHNbloc Maxi S andDEHNgap Maxi S protective devices with floating changeover contact.

Page 59: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 59/382

POWER SUPPLY SYSTEMS

ACCESSORIES FOR SPDs TYPE 1

57www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNsignal

DEHNsignal E 3DSI E 3

LWL 1

1214

11

signal

evaluation

LWL 2

LWL 3

S

N

L

red

red

red

green

Note:

Change of contacts in case of present

voltage and optical fibre signal!

L1

L2

L3

Basic circuit diagram DSI E 3

S N L

Dimension drawing DSI E 3

DSI E 3: Receiver module for optical fibre transmission for selective operating state indication /centralised fault indication of 3 coordinated DEHNbloc Maxi S and, if required, DEHNgapMaxi S lightning current arresters in 5-conductor systems

DSI E 3Supply a.c. voltage UN 230 V

Power input P < 550 mW

Backup fuse for supply voltage 16 A gL/gG or C 16 A

Operating temperature range -40°C...+80°C

Signal input 3x via optical fibre plug-in system (LWL ST DSI)

Operating state indication green LED

Selective operating state indication 3 x red LEDs (L1, L2, L3)

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 1.5 mods., DIN 43880

Type of remote signalling contact floating changeover contact

Switching capacity a.c. 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area min. 0.5 mm2 solid/flexible; max. 4 mm2 solid/flexible

Max. distance with LWL DSI 18M 6 m

Test standards EN 61010-1:1993 and EN 61010-1/A2:1995

Ordering information

Type DSI E 3

Part No. 910 631

Packing unit 1 pc(s).

Accessory Part for DEHNsignal

910 641 LWL STDSI

LWL ST DSI Plug forOptical Fibre 910 641

Accessory Part for DEHNsignal

910 642 LWL DSI18M

LWLDSI 1 8 M910 642

LWL DSI 18M

18 metres of plastic optical fibre, preferably for use with DEHNblocMaxi S

PU PartType Diameter Length pc(s). No.

LWL DSI 18M 2.2 mm 18 m 1 910 642

LWL ST DSI

Plug for plastic optical fibres

PU PartType Diameter pc(s). No.

LWL ST DSI 2.2 mm 1 910 641

Page 60: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 60/382

The spark gaps of the DEHNbloc lightning current arresters allow for acompact structure of low-voltage distribution boards. Using pressurisedencapsulated creepage discharge spark gaps, safety distances from elec-trical busbars and special flameproof enclosures are not required.

With a lightning current discharge capacity up to 50 kA (10/350 µs) perpole, DEHNbloc devices fulfil the most stringent requirements of nationaland international lightning protection and application standards.

The consistent development of the integration concept has made theDEHNbloc devices even more powerful: With the product designationDEHNbloc ... H, the groundbreaking RADAX Flow spark gap technology

for follow current extinction and follow current limitation was integratedinto the DEHNbloc family.

The RADAX Flow technology prevents operational interruptions caused bytripping conductor protection due to responding SPDs. In times where allsystems increasingly depend on a functioning electrical infrastructure, thisis an indispensable product feature. Due to the patented RADAX Flowprinciple, even the amplitudes of short circuits in installations up to 50kArms can be limited to approx.500 A and extinguished after approx.5 ms.This performance allows a breaking selectivity of the SPD even in case of small-sized fuses.

But the concept of the DEHNbloc H family also stands out due to otherproduct features:With its phase-side and earth-side double terminals, thesingle-pole device of type DEHNbloc 1 255 H offers a wide range of appli-cation possibilities.

DEHNbloc incorporates double terminals which are suitable for all con-ductors, allowing a series connection of three-pole DEHNbloc 3 255 HSPDs in a space- and cost-saving way according to IEC 60364-5-53requirements for nominal currents up to 125 A.

For application with other DIN rail mounted devices, multifunctional ter-minals are ideally suited for providing connection for conductors and bus-

bars.

DEHNbloc NH00 255 H wasespecially developed for usein industrial distributionboards and in power supplysystems. It can be installedinto size 00 NH fuse holdersor NH disconnectors accor-ding to the particular sys-tem.

DEHNbloc 1 440 is suitable

for rated voltages of 440 V.

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

58 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

For protecting low voltage consumer’s installations against surges andeven direct lightning strikes. For installation in conformity with the light-ning protection zones concept at the boundaries from 0A – 1.

• Encapsulated, non-exhausting creepage dis-charge spark gap

• DEHNbloc ... H: RADAX Flow spark gap technol-ogy with high follow current limitation

• Energy-coordinated within the Red/Line pro-duct family

• High insulation resistance allows installationeven upstream of meter panels

• Multifunctional terminal for connecting con-ductors and busbars

• Single-pole and three-pole version (lightning

impulse currents up to 100 kA according to thesystem configuration)

• ”NH00” version also available

DEHNbloc 1 255 H: Single-pole lightning current arrester with high follow current limitation

DEHNbloc 3 255 H: Three-pole lightning current arrester with high follow current limitation

DEHNbloc NH00 H: Lightning current arrester, NH 00 design, with high follow current limitation

DEHNbloc 1 440: Single-pole lightning current arrester for UC = 440 V

DEHNbloc®

Lightning current arresterSPD Type 1 according to EN 61643-11SPD Class I according to IEC 61643-1

DB NH00 255 H in a busbar connectionpanel of a meter system

Page 61: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 61/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

59www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNbloc®

DEHNbloc ... 255 HDB 1 255

DB 3 255

900 222

900 120

N/PEN

L1 L2 L3

Basic circuit diagram DB 1 255 H / DB 3 255 HDimension drawing DB 1 255 H / DB 3 255 H

DB ... 255 H: Single-pole and three-pole lightning current arrester with high follow current limita-tion

DB 1 255 H DB 3 255 HSPD according to EN 61643-11 Type 1 Type 1

SPD according to IEC 61643-1 Class I Class I

Nominal a.c. voltage UN 230 V 230/400 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Lightning impulse current (10/350 µs) Iimp 50 kA —

Lightning impulse current (10/350 µs) [L-N/PEN] Iimp — 50 kA

Lightning impulse current (10/350 µs) [L1+L2+L3-N/PEN] Itotal — 100 kA

Nominal discharge current (8/20 µs) In 50 kA 50 / 100 kA

Voltage protection level UP 4 kV 4 kV

Follow current extinguishing capability a.c. Ifi 50 kArms 50 kArms

Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kA rms (prosp.) no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)

Response time tA 100 ns 100 ns

Max. backup fuse up to IK = 50 kArms (ta 0.2 s) 500 A gL/gG 500 A gL/gG

Max. backup fuse up to IK = 50 kArms (ta 5 s) 315 A gL/gG 315 A gL/gG

Max. backup fuse for IK > 50 kArms 200 A gL/gG 200 A gL/gG

Max. backup fuse (L-L´) 125 A gL/gG 125 A gL/gG

Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C

Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C

Cross-sectional area (L, L´, N/PEN, N´/PEN) min. 10 mm2 solid/flexible —

Cross-sectional area (L, N/PEN) max. 50 mm2 stranded/35 mm2 flexible —

Cross-sectional area (L´, N´/PEN) max. 35 mm2 stranded/25 mm2 flexible —

Cross-sectional area (L1, L1 , L2, L2 , L3, L3 , N/PEN, N´/PEN) — 10 mm2 solid/flexible

Cross-sectional area (L1, L2, L3, N/PEN) — 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (L1´, L2´, L3´, N´/PEN) — 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 6 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Ordering information

Type DB 1 255 H DB 3 255 H

Part No. 900 222 900 120

Packing unit 1 pc(s). 1 pc(s).

N/PEN

L L´

N´/PEN

Page 62: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 62/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

60 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNbloc®

DEHNbloc NH00 255 H900 273 DB NH00 255 H

DBNH00255H900 273

Basic circuit diagram DB NH00 255 H Dimension drawing DB NH00 255 H

DB NH00 255 H: Single-pole lightning current arrester in NH design, size 00, with high follow cur-rent limitation

DB NH00 255 HSPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) I imp 25 kA

Nominal discharge current (8/20 µs) In 25 kA

Voltage protection level UP 4 kV

Follow current extinguishing capability a.c. Ifi 50 kArms

Follow current limitation / Selectivity no tripping of a 32 A gL/gG fuse up to 50 kA rms (prosp.)

Response time tA 100 ns

Max. backup fuse up to IK = 50 kArms (ta 0.2 s) 315 A gL/gG

Max. backup fuse up to IK = 50 kArms (ta 5 s) 200 A gL/gG

Max. backup fuse for IK > 50 kArms 125 A gL/gG

Temporary overvoltage (TOV) UT 440 V / 5 sec.

TOV characteristics withstand

Operating temperature range TU -40°C...+80°C

For mounting on NH fuse holder, size 00

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IPX4W

Ordering information

Type DB NH00 255 H

Part No. 900 273

Packing unit 1 pc(s).

Page 63: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 63/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

61www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

L i g h t n .

C u r r . A r r . T y p e 1

DEHNbloc®

DEHNbloc 1 440DB 1 440

DEHNbloc/1

Basic circuit diagram DB 1 440Dimension drawing DB 1 440

DB 1 440: Single-pole lightning current arrester with high discharge capacity for UC = 440 V

DB 1 440SPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Max. continuous operating a.c. voltage UC 440 V

Lightning impulse current (10/350 µs) Iimp 50 kA

Nominal discharge current (8/20 µs) In 50 kA

Voltage protection level UP 4 kV

Follow current extinguishing capability a.c. Ifi 1.5 kArms

Response time tA 100 ns

Max. mains-side overcurrent protection 160 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 50 kArms

Temporary overvoltage (TOV) TN system UT 580 V / 5 sec.

Temporary overvoltage (TOV) IT system UT 1200 V + U0 / 200 ms

TOV characteristics withstand

Operating temperature range TU -40°C...+80°C

Cross-sectional area (min.) 10 mm2 solid/flexible

Cross-sectional area (max.) 50 mm2 stranded/35 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 2 mods., DIN 43880

Ordering information

Type DB 1 440

Part No. 900 159

Packing unit 1 pc(s).

Page 64: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 64/382

POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS – TYPE 1

62 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

www.dehn.de

Page 65: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 65/382

POWER SUPPLY SYSTEMS

N-PE LIGHTNING CURRENT ARRESTERS

63www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

N - P E A r r e s t e r s T y p e

1

www.dehn.dewww.dehn.dewww.dehn.dewww.dehn.de

DEHNgap

N-PE lightning current arresterSPD Type 1 according to EN 61643-11SPD Class 1 according to IEC 61643-1

• Discharge capacity up to 100 kA (10/350 µs)

• Total current arrester specifically designed for

installation in ”3+1” and ”1+1” circuits of TTsystems according to IEC 60364-5-53 betweenneutral conductor N and protective earth con-ductor PE

• Creepage discharge spark gap technology

• DEHNgap M model available with operatingstate/fault indication in the inspection window

DEHNgap M 255 (FM): Coordinated, single-pole, modular N-PE lightning current arrester

DEHNgap Maxi 1 255 S: Coordinated, single-pole N-PE lightning current arrester for busbars

DEHNgap BN 255: Single-pole N-PE lightning current arrester

DEHNgap B NH00 N 255: Single-pole N-PE lightning current arrester in NH designDEHNgap Maxi 440 (FM): Coordinated, single-pole N-PE lightning current arrester for UC = 440 V a.c.

For protecting low voltage consumer’s installations against surges andeven direct lightning strikes. For installation in conformity with the light-ning protection zones concept at the boundaries from 0A – 1 with 3+1 cir-cuits.

Being total current arresters between neutral and protective conductorsin TT systems, the single-pole N-PE lightning current arresters DEHNgapM, DEHNgap Maxi, DEHNgap Maxi S, DEHNgap BN and DEHNgap B NHare designed to meet the requirements for the protection of persons andmaterial assets in ”3+1 circuits”.The creepage discharge spark gaps werespecifically developed to meet this challenge. With a discharge capacityup to 100 kA (10/350 µs) they fulfil the highest requirements specified innational and international lightning protection standards. The leakage-current-free spark gap design allows the devices to be used upstream of

the meter according to national regulations (e.g. German VDN Directive).Being coordinated N-PE lightning current arresters, DEHNgap M,DEHNgap Maxi and DEHNgap Maxi S are different from other total cur-rent arresters. Due to their response performance, they can be coordinat-ed directly with N-PE surge arresters of the DEHNguard M family andDEHNgap S surge arresters without additional decoupling coil. If lightningcurrent and surge arresters have to be installed together at one site, noadditional DEHNgap S is required thanks to the low voltage protectionlevels of DEHNgap M and DEHNgap Maxi.The design and installation of DEHNgap Maxi S are adapted to the spe-cial characteristics of low voltage switchgear installations and entirelycomplement the application of DEHNbloc Maxi S.DEHNgap B NH was specifically developed for industrial plants as well asfor supply systems.This SPD can be easily integrated into existing size 00

NH fuse holders. The multifunctional terminals of the DIN rail mounteddevices DEHNgap M, DEHNgap Maxi and DEHNgap BN are suitable for

connecting conductorsand busbars, allowingwiring with other DINrail mounted terminals.The functional Red/Linedesign of DEHNgap Moffers many features forsafe and easy handling.The mechanical operat-

ing state and fault indi-cation, for example,stands for fulfilling the high safety requirements, just like the module lock-ing device which is unique for use with surge arresters. It fixes the protec-tion modules and the base part of the device firmly in place. Neither vibra-tion nor shock during transport nor the enormous electromagnetic forcesof lightning discharge can loosen the protection modules. Nevertheless,they can be easily replaced without tools by pressing the user-friendlymodule release button of the protection module. Each protection moduleis mechanically coded to avoid incorrect insertion by the installer or user.Apart from the standard visual indication of DEHNgap M, DEHNgap M ...FM features a three-pole remote signalling terminal. With its floatingchangeover contact, the remote signal can be used as a break or makecontact according to the particular circuit concept.

Page 66: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 66/382

POWER SUPPLY SYSTEMS

N-PE LIGHTNING CURRENT ARRESTERS

64 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNgap

DEHNgap M 255 (FM)961 101 DGP M255961 105 DGP M255FM

DGPM255961 101D G P M2 5 5 FM961 105

12

1114

PE

NPE

N

Basic circuit diagram DGP M 255 FM

(2 mods.)

N

PE 9

Dimension drawing DGP M 255 FM

DGP M 255 (FM): Single-pole, modular, coordinated N-PE lightning current arrester for UC = 255 V;also available with remote signalling contact for the monitoring system (floatingchangeover contact)

DGP M 255 DGP M 255 FM

SPD according to EN 61643-11 Type 1 Type 1

SPD according to IEC 61643-1 Class I Class I

Max. continuous operating a.c. voltage UC 255 V 255 V

Lightning impulse current (10/350 µs) I imp 100 kA 100 kA

Nominal discharge current (8/20 µs) In 100 kA 100 kA

Voltage protection level UP 1.5 kV 1.5 kV

Follow current extinguishing capability a.c. Ifi 100 Arms 100 Arms

Response time tA 100 ns 100 ns

Temporary overvoltage (TOV) 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand

Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C

Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C

Operating state/fault indication green / red green / red

Cross-sectional area (N, PE,9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Approvals, Certifications VDE, KEMA VDE, KEMA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DGP M 255 DGP M 255 FM

Part No. 961 101 961 105

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNgap

DGP M – 100 kA N-PE spark-gap-based protectionmodule

DGP M MOD ...: 100 kA N-PE spark-gap-based protection module foruse with all modular DEHNgap M devices

PU PartType pc(s). No.

DGP M MOD 255 1 961 010

961 010 DGP MMOD255

DGPMMOD255961 010

Page 67: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 67/382

POWER SUPPLY SYSTEMS

N-PE LIGHTNING CURRENT ARRESTERS

65www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

N - P E A r r e s t e r s T y p e

1

www.dehn.dewww.dehn.de

DEHNgap

DEHNgap Maxi 1 255 SDGPM 1 255 S

N/PEN

PE

S(DSI E 3)NPE

Basic circuit diagram DGPM 1 255 SDimension drawing DGPM 1 255 S

DGPM 1 255 S: Coordinated single-pole N-PE lightning current arrester for busbars

DGPM 1 255 S

SPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) Iimp 100 kA

Nominal discharge current (8/20 µs) In 100 kA

Voltage protection level UP 2.5 kV (includes 80 cm connecting cable)

Follow current extinguishing capability a.c. Ifi 100 Arms

Response time tA 100 ns

Temporary overvoltage (TOV) 1200 V / 200 ms

TOV characteristics withstand

Operating temperature range TU -40°C...+80°C

For mounting on N busbar min. 35 mm2

Connection via cable lug min. 35 mm2/max. 50 mm2

Operating state control via DEHNsignal DSI E 3

Connection for DSI E 3 (S) min. 1 mm2 solid/flexible

Connection for DSI E 3 (S) max. 2.5 mm2 solid/flexible

Enclosure material thermoplastic, red, UL 94 V-0

Dimension (W x H x D) 72 x 89 x 100 mm

Ordering information

Type DGPM 1 255 S

Part No. 900 050

Packing unit 1 pc(s).

Page 68: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 68/382

POWER SUPPLY SYSTEMS

N-PE LIGHTNING CURRENT ARRESTERS

66 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

www.dehn.dewww.dehn.de

DEHNgap

DEHNgap BN 255900 132 DGP BN255

DGP BN 255 DEHNgapB/n 900 132

Basic circuit diagram DGP BN 255 Dimension drawing DGP BN 255

DGP BN 255: Single-pole N-PE lightning current arrester

DGP BN 255

SPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) I imp 100 kA

Nominal discharge current (8/20 µs) In 100 kA

Voltage protection level UP 4 kV

Follow current extinguishing capability a.c. Ifi 100 Arms

Response time tA 100 ns

Temporary overvoltage (TOV) 1200 V / 200 ms

TOV characteristics withstand

Operating temperature range TU -40°C...+80°C

Operating state/fault indication green / red

Cross-sectional area (min.) 10 mm2 solid/flexible

Cross-sectional area (max.) 50 mm2 stranded/35 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 2 mods., DIN 43880

Ordering information

Type DGP BN 255

Part No. 900 132

Packing unit 1 pc(s).

Page 69: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 69/382

POWER SUPPLY SYSTEMS

N-PE LIGHTNING CURRENT ARRESTERS

67www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

N - P E A r r e s t e r s T y p e

1

www.dehn.dewww.dehn.de

DEHNgap

DEHNgap B NH00DGP B

DEHNgap900 269

Basic circuit diagram DGP B NH00 N 255Dimension drawing DGP B NH00 N 255

DGP B NH00 N 255: Single-pole N-PE lightning current arrester, NH design, size 00

DGP B NH00 N 255

SPD according to EN 61643-11 Type 1

SPD according to IEC 61643-1 Class I

Max. continuous operating a.c. voltage UC 255 V

Lightning impulse current (10/350 µs) Iimp 50 kA

Nominal discharge current (8/20 µs) In 50 kA

Voltage protection level UP 4 kV

Follow current extinguishing capability a.c. Ifi 100 Arms

Response time tA 100 ns

Temporary overvoltage (TOV) 1200 V / 200 ms

TOV characteristics withstand

Operating temperature range TU -40°C...+80°C

For mounting on NH fuse holder, size 00

Enclosure material thermoplastic, red, UL 94 V-0

Ordering information

Type DGP B NH00 N 255

Part No. 900 269

Packing unit 1 pc(s).

Page 70: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 70/382

POWER SUPPLY SYSTEMS

N-PE LIGHTNING CURRENT ARRESTERS

68 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNgap

DEHNgap Maxi 440 (FM)961 160 DGPM440961 165 DGPM440FM

DGPM440961 160DGPM440FM961 165

N

PE

12

1114

Basic circuit diagram DGPM 440 FM

( 2 mods.)

N

PE 9

Dimension drawing DGPM 440

DGPM 440 (FM): Coordinated, single-pole N-PE lightning current arrester for UC = 440 V

DGPM 440 DGPM 440 FM

SPD according to EN 61643-11 Type 1 Type 1

SPD according to IEC 61643-1 Class I Class I

Max. continuous operating a.c. voltage UC 440 V 440 V

Lightning impulse current (10/350 µs) I imp 100 kA 100 kA

Nominal discharge current (8/20 µs) In 100 kA 100 kA

Voltage protection level UP 2.5 kV 2.5 kV

Follow current extinguishing capability a.c. Ifi 100 Arms 100 Arms

Response time tA 100 ns 100 ns

Temporary overvoltage (TOV) 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand

Operating temperature range (parallel connection) TUP -40°C...+80°C -40°C...+80°C

Operating temperature range (series connection) TUS -40°C...+60°C -40°C...+60°C

Operating state/fault indication green / red green / red

Cross-sectional area (N, PE,9) min. 10 mm2 solid/flexible 10 mm2 solid/flexible

Cross-sectional area (N, PE) max. 50 mm2 stranded/35 mm2 flexible 50 mm2 stranded/35 mm2 flexible

Cross-sectional area (9) max. 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DGPM 440 DGPM 440 FM

Part No. 961 160 961 165

Packing unit 1 pc(s). 1 pc(s).

Page 71: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 71/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

69www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular CI

Modular surge arresterwith integrated backup fuseSPD Type 2 according to EN 61643-11

SPD Class II according to IEC 61643-1

• Arrester backup fuse integrated in the protec-tion module

• Prewired complete unit consisting of a basepart and plug-in protection modules

• Energy coordination within the Red/Line pro-duct family

• High discharge capacity

• High reliability due to ”Thermo DynamicControl” SPD monitoring device

• Easy replacement of protection modules with-out tools due to module locking system with

module release button

DEHNguard M TNC CI 275: modular surge arrester with integrated backup fuse for TN-C systems

DEHNguard M TNS CI 275: with integrated backup fuse for TN-S systems

DEHNguard M TT CI 275: with integrated backup fuse for TT and TN-S systems (”3+1” circuits)

DEHNguard M TN CI 275: with integrated backup fuse for 230 V TN systems

DEHNguard M TT 2P CI 275: with integrated backup fuse for 230 V TT and TN systems (”1+1” circuits)DEHNguard S CI 275: single-pole, modular surge arrester with integrated backup fuse

DEHNguard M ... CI 275 FM: with remote signalling contact for the monitoring device (floating changeover contact)

For protecting low-voltage consumer’s installations against surges. Foruse in conformity with the lightning protection zones concept at theboundaries from 0B – 1 and higher.

The modular surge arresters of the DEHNguard M ... CI family with theirfunctional Red/Line design combine short-circuit protection and surgeprotection in a single protection module.This sets new standards for user-friendly surge and short-circuit protection.The protective circuit with the arrester backup fuse integrated in the pro-tection module and the heavy-duty zinc oxide varistor in combinationwith the dual Thermo Dynamic Control monitoring device offer the advan-tage of easy installation and minimum space requirements.Due to the integrated arrester backup fuse the user does not have to

worry about arrester-specific dimensioning requirements such as backupprotection in case of short-circuits and impulse current carrying capacity.

The user has the possibility to implement space-saving surge protectionmeasures in installations up to short-circuit currents of 25 kArms whichcover all functions specified in the IEC 60364-5-53 installation standard.All circuits including the N-PE circuit feature an operating state indicationrequired in accordance with the IEC 60364-5-53 standard.The ”Thermo Dynamic Control“ monitoring device does not only evaluatethe surface temperature of the heavy-duty varistor but also the intensityof the discharge current. The mechanical visual indication with green andred flags, which is free of operating currents, shows if every protective cir-cuit is ready for operation. The visual indication indicates the activation of

the ”Thermo Dynamic Control“ monitoring device and the integratedarrester backup fuse.

Apart from the mechanical operating state/fault indication, the ...FM ver-sion of the DEHNguard M ...CI devices features a three-pole remote sig-nalling terminal. With its floating changeover contact, the remote signalcan be used as break or make contact according to the particular circuitconcept.

All benefits of the modular design of the DEHNguard M family were com-pletely integrated into the new DEHNguard M ... CI family.The system-configuration-specific product designation as well as the

”Thermo Dynamic Control“ monitoring device reflect the high safetyrequirements.The unique module locking system prevents the protection modules frombecoming loose due to shock during transport or due to the enormousforces of discharge. Nevertheless, the protection modules can be easilyreplaced without tools, the need to de-energise and removing the coverof the distribution board by simply pressing the user-friendly modulerelease button of the protection modules.To prevent incorrect insertion bythe installer or user, every protective circuit of the multipole and single-pole SPDs and every protection module is mechanically coded.

The surge arresters of the mutlipole modular DEHNguard M ... CI familyfeature multifunctional terminals on a standardised spacing of 1 module

for connecting conductors and busbars, allowing easy wiring with otherDIN rail mounted devices.Thus,a variety of applications can be easily con-nected in series in accordance with IEC 60364-5-53 for optimal protec-tion.

Page 72: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 72/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

70 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular with integrated backup fuse

DEHNguard M TNC CI 275 (FM)952 304 DG M TNC CI 275952 309 DG M TNC CI 275 FM

DG M TN C C I 2 7 5952 304DG M TN C C I 2 7 5 FM952 309

1211

14

L1 L2 L3

PEN9

Basic circuit diagram DG M TNC CI 275 FM Dimension drawing DG M TNC CI 275 FM

DG M TNC CI 275 (FM): Modular surge arrester with integrated backup fuses for TN-C systems

DG M TNC CI 275 DG M TNC CI 275 FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Nominal a.c. voltage UN 230/400 V 230/400 V

Max. continuous operating a.c. voltage UC 275 V 275 V

Nominal discharge current (8/20 µs) In 12.5 kA 12.5 kA

Max. discharge current (8/20 µs) Imax 25 kA 25 kA

Voltage protection level UP 1.5 kV 1.5 kV

Voltage protection level at 5 kA UP 1 kV 1 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection not required not required

Short-circuit withstand capability 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 3 mods., DIN 43880 3 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TNC CI 275 DG M TNC CI 275 FM

Part No. 952 304 952 309

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse

952 020 DG MODCI275

DG M O DC I 2 7 5952 020

Varistor-based protection module forDEHNguard M CI

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-prising a varistor connected in series with the integrated backup fuse

PU PartType pc(s). No.

DG MOD CI 275 1 952 020

N E W

N E W

Page 73: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 73/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

71www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular with integrated backup fuse

DEHNguard M TNS CI 275 (FM)DG M TNS C I 275DG M TNS C I 275 FM

L2 N

PE

L1 L3

121114

9

Basic circuit diagram DG M TNS CI 275 FMDimension drawing DG M TNS CI 275 FM

DG M TNS CI 275 (FM): Modular surge arrester with integrated backup fuses for TN-S systems

DG M TNS CI 275 DG M TNS CI 275 FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Nominal a.c. voltage UN 230/400 V 230/400 V

Max. continuous operating a.c. voltage UC 275 V 275 V

Nominal discharge current (8/20 µs) In 12.5 kA 12.5 kA

Max. discharge current (8/20 µs) Imax 25 kA 25 kA

Voltage protection level UP 1.5 kV 1.5 kV

Voltage protection level at 5 kA UP 1 kV 1 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection not required not required

Short-circuit withstand capability 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 4 mods., DIN 43880 4 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TNS CI 275 DG M TNS CI 275 FM

Part No. 952 401 952 406

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse

952 020 DG MODCI275

DG M O DC I 2 7 5952 020

N E W

Accessory Part for DEHNguard® modular with integrated backup fuse

952 010 DG MOD275

DGMOD275952 010

N E W Varistor-based protection module forDEHNguard M CI

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-prising a varistor connected in series with the integrated backup fuse

PU PartType pc(s). No.

DG MOD CI 275 1 952 020

Varistor-based protection module for N-PE circuits

DG MOD ...:Varistor-based protection module for DEHNguard M ... andDEHNguard S ... surge arresters

PU Part

Type pc(s). No.DG MOD 275 1 952 010

Page 74: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 74/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

72 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular with integrated backup fuse

DEHNguard M TT CI 275 (FM)952 322 DG M TT CI 275952 327 DG M TT CI 275 FM

DG M TTC I 2 7 5952 322DG M TTC I 2 7 5 FM952 327

L2 N

PE

L1 L3

121114

9

Basic circuit diagram DG M TT CI 275 FM Dimension drawing DG M TT CI 275 FM

DG M TT CI 275 (FM): Modular surge arrester with integrated backup fuses for TT and TN-S sys-tems (”3+1” circuits)

DG M TT CI 275 DG M TT CI 275 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II

Nominal a.c. voltage UN 230/400 V 230/400 V

Max. continuous operating a.c. voltage [L-N] UC 275 V 275 V

Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V

Nominal discharge current (8/20 µs) [L-N] In 12.5 kA 12.5 kA

Nominal discharge current (8/20 µs) [N-PE] In 20 kA 20 kA

Max. discharge current (8/20 µs) [L-N] Imax 25 kA 25 kA

Max. discharge current (8/20 µs) [N-PE] Imax 40 kA 40 kA

Lightning impulse current (10/350 µs) [N-PE] I imp 12 kA 12 kA

Voltage protection level [L-N] UP 1.5 kV 1.5 kV

Voltage protection level [L-N] at 5 kA UP 1 kV 1 kV

Voltage protection level [N-PE] UP 1.5 kV 1.5 kV

Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms

Response time [L-N] tA 25 ns 25 ns

Response time [N-PE] tA 100 ns 100 ns

Max. mains-side overcurrent protection not required not required

Short-circuit withstand capability 25 kArms 25 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20Capacity 4 mods., DIN 43880 4 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TT CI 275 DG M TT CI 275 FM

Part No. 952 322 952 327

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse

952 020 DG MODCI275

DG M O DC I 2 7 5952 020

Accessory Part for DEHNguard® modular with integrated backup fuse

952 050 DG MODNPE

DGMODNPE952 050

N-PE spark-gap-based protection module forDEHNguard M TT ...

DG MOD NPE: N-PE spark-gap-based protection module for two- andfour-pole DEHNguard DG M TT ... surge arresters

PU PartType pc(s). No.

DG MOD NPE 1 952 050

Varistor-based protection module forDEHNguard M CI

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-prising a varistor connected in series with the integrated backup fuse

PU PartType pc(s). No.

DG MOD CI 275 1 952 020

N E W

N E W

Page 75: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 75/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

73www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular with integrated backup fuse

DEHNguard M TN CI 275 (FM)DG M TN CI 275DG M TN CI 275 FM

NL

1211

14

PE9

Basic circuit diagram DG M TN CI 275 FMDimension drawing DG M TN CI 275 FM

DG M TN CI 275 (FM): Modular surge arrester with integrated backup fuse for single-phase230 V TN systems

DG M TN CI 275 DG M TN CI 275 FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Nominal a.c. voltage UN 230 V 230 V

Max. continuous operating a.c. voltage UC 275 V 275 V

Nominal discharge current (8/20 µs) In 12.5 kA 12.5 kA

Max. discharge current (8/20 µs) Imax 25 kA 25 kA

Voltage protection level UP 1.5 kV 1.5 kV

Voltage protection level at 5 kA UP 1 kV 1 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection not required not required

Short-circuit withstand capability 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TN CI 275 DG M TN CI 275 FM

Part No. 952 173 952 178

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse

952 020 DG MODCI275

DG M O DC I 2 7 5952 020

Varistor-based protection module forDEHNguard M CI

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-prising a varistor connected in series with the integrated backup fuse

PU Part

Type pc(s). No.DG MOD CI 275 1 952 020

N E W

Accessory Part for DEHNguard® modular with integrated backup fuse

952 010 DG MOD275

DG MOD 275 ÜS-Modulfür DG Mund DG S, 275 V 952 010

Varistor-based protection module for N-PE circuits

DG MOD ...:Varistor-based protection module for DEHNguard M ... andDEHNguard S ... surge arresters

PU PartType pc(s). No.

DG MOD 275 1 952 010

N E W

Page 76: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 76/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

74 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular with integrated backup fuse

DEHNguard M TT 2P CI 275 (FM)952 171 DG M TT 2P CI 275952 176 DG M TT 2P CI 275 FM

DG M TT2 P C I 2 7 5952 171DG M TT2 P C I 2 7 5 FM952 176

N

PE

L

121114

9

Basic circuit diagram DG M TT 2P CI 275 FM Dimension drawing DG M TT 2P CI 275 FM

DG M TT 2P CI 275 (FM): Modular surge arrester with integrated backup fuse for single-phase230 V TT and TN systems (”1+1” circuits)

DG M TT 2P CI 275 DG M TT 2P CI 275 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II

Nominal a.c. voltage UN 230 V 230 V

Max. continuous operating a.c. voltage [L-N] UC 275 V 275 V

Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V

Nominal discharge current (8/20 µs) [L-N] In 12.5 kA 12.5 kA

Nominal discharge current (8/20 µs) [N-PE] In 20 kA 20 kA

Max. discharge current (8/20 µs) [L-N] Imax 25 kA 25 kA

Max. discharge current (8/20 µs) [N-PE] Imax 40 kA 40 kA

Lightning impulse current (10/350 µs) [N-PE] I imp 12 kA 12 kA

Voltage protection level [L-N] UP 1.5 kV 1.5 kV

Voltage protection level [L-N] at 5 kA UP 1 kV 1 kV

Voltage protection level [N-PE] UP 1.5 kV 1.5 kV

Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms

Response time [L-N] tA 25 ns 25 ns

Response time [N-PE] tA 100 ns 100 ns

Max. mains-side overcurrent protection not required not required

Short-circuit withstand capability 25 kArms 25 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TT 2P CI 275 DG M TT 2P CI 275 FM

Part No. 952 171 952 176

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse

952 020 DG MODCI275

DG M O DC I 2 7 5952 020

Accessory Part for DEHNguard® modular with integrated backup fuse

952 050 DG MODNPE

DG MOD NPE ÜS-ModulN-PE für DG M TT 952 050

N-PE spark-gap-based protection module forDEHNguard M TT ...

DG MOD NPE: N-PE spark-gap-based protection module for two- andfour-pole DEHNguard DG M TT ... surge arresters

PU PartType pc(s). No.

DG MOD NPE 1 952 050

Varistor-based protection module forDEHNguard M CI

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-prising a varistor connected in series with the integrated backup fuse

PU PartType pc(s). No.

DG MOD CI 275 1 952 020

N E W

N E W

Page 77: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 77/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

75www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular with integrated backup fuse

DEHNguard S CI 275 (FM)DG S CI 275DG S CI 275 FM

121114

Basic circuit diagram DG S CI 275 FMDimension drawing DG S CI 275 FM

DG S CI 275 (FM): Single-pole, pluggable surge arrester consisting of a base part and plug-in pro-tection module; with integrated backup fuse; optionally available with floatingremote signalling contact

DG S CI 275 DG S CI 275 FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Max. continuous operating a.c. voltage UC 275 V 275 V

Nominal discharge current (8/20 µs) In 12.5 kA 12.5 kA

Max. discharge current (8/20 µs) Imax 25 kA 25 kA

Voltage protection level UP 1.5 kV 1.5 kV

Voltage protection level at 5 kA UP 1 kV 1 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection not required not required

Short-circuit withstand capability 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 1 mod., DIN 43880 1 mod., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG S CI 275 DG S CI 275 FM

Part No. 952 079 952 099

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular with integrated backup fuse

952 020 DG MODCI275

DG M O DC I 2 7 5952 020

Varistor-based protection module forDEHNguard M CI

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 com-prising a varistor connected in series with the integrated backup fuse

PU PartType pc(s). No.

DG MOD CI 275 1 952 020

N E W

N E W

Page 78: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 78/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

76 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular

Multipole, modular surge arresterSPD Type 2 according to EN 61643-11SPD Class II according to IEC 61643-1

• Prewired complete unit consisting of a basepart and plug-in protection modules

• Energy coordination within the Red/Line pro-duct family

• High discharge capacity due to heavy-duty zincoxide varistors/spark gaps

• High reliability due to ”Thermo DynamicControl” SPD monitoring device

• Easy replacement of protection modules due tomodule locking system with module releasebutton

• Vibration- and shock-tested according to EN60068-2

DEHNguard M TNC ...: Modular surge arrester for use in TN-C systems

DEHNguard M TNS ...: Modular surge arrester for use in TN-S systems

DEHNguard M TT ...: Modular surge arrester for use in TT and TN-S systems (”3+1” circuit)

DEHNguard M TN ...: Modular surge arrester for use in single-phase TN systemsDEHNguard M TT 2P ...: Modular surge arrester for use in single-phase TT and TN systems (”1+1” circuit)

DEHNguard M WE ...: Modular surge arrester especially for use in wind turbines

DEHNguard M ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

For protecting low-voltage consumer´s installations against surges. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 0B – 1 and higher.

The modular DEHNguard M ... surge arresters with their functionalRed/Line family design set new standards in terms of safety and user-friendliness. The approved protective circuit with heavy-duty zinc oxidevaristors in combination with the dual Thermo Dynamic Control monitor-ing device characterise the DEHNguard technology.

Many features of the device show that both safe surge protection and

reliability of the devices are the key element of the new modularDEHNguard. The application-oriented product designation, which makesthe choice of the adequate devices considerably easier, as well as themodule locking device, which is unique for use with surge protectivedevices, stand for fulfilling stringent safety requirements. It fixes the pro-tection modules and the base part of the device firmly in place. Neithervibration during transport nor the enormous electromagnetic forces of discharge can loosen the protection modules. Nevertheless, they can beeasily replaced without tools by simply pressing the user-friendly modulerelease button of the protection modules. In order to avoid incorrect inser-tion by the installer or user when replacing the modules, each protectivecircuit of the multipole surge arresters and each protection module aremechanically coded.

The dual Thermo Dynamic Control monitoring device was not only devel-oped on the basis of national and international product standards, but italso stands for experience of decades in the international use of surgeprotective devices and considers many fields of application where SPDsmight be damaged. Like with all DEHN surge arresters with ThermoDynamic Control, evaluation is based on the intensity of the dischargecurrent and the surface temperature of the heavy-duty varistor.The green

and red indicator shows if each protective circuit is ready for operation.Apart from this standard visual indication, DEHNguard M ... FM devicesfeature a three-pole terminal for remote signalling.

With their floating changeover contact, the remote signal can be used asa make or break contract according to the particular circuit concept. Thesurge arresters of the multipole modular DEHNguard M family featuremultifunctional terminals on a standardised spacing of 1 module for theconnection of conductorsand busbars, allowingeasy wiring with otherDIN rail mounted devices.Thus a variety of applica-tions can be connected inseries according to IEC60364-5-53 for optimalprotection.

Page 79: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 79/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

77www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular

DEHNguard M TNC ...DG M TNC 150DG M TNC 275DG M TNC 385DG M TNC 440

L1 L2 L3

PEN9

Basic circuit diagram DG M TNC ...Dimension drawing DG M TNC ...

DG M TNC ... : Modular surge arrester for TN-C systems

DG M TNC 150 DG M TNC 275 DG M TNC 385 DG M TNC 440

SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II Class II Class II

Nominal a.c. voltage UN 120/240 V 230/400 V 230/400 V 400/690 V

Max. continuous operating a.c. voltage UC 150 V 275 V 385 V 440 V

Nominal discharge current (8/20 µs) In 15 kA 20 kA 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA

Voltage protection level UP 0.7 kV 1.25 kV 1.75 kV 2 kV

Voltage protection level at 5 kA UP 0.55 kV 1 kV 1.35 kV 1.7 kV

Response time tA 25 ns 25 ns 25 ns 25 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability

for max. mains-side overcurrent protection 50 kArms 50 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec. 580 V / 5 sec.

TOV characteristics withstand withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20 IP 20

Capacity 3 mods., DIN 43880 3 mods., DIN 43880 3 mods., DIN 43880 3 mods., DIN 43880

Approvals, Certifications — KEMA, VDE,UL, VdS — —

Ordering informationType DG M TNC 150 DG M TNC 275 DG M TNC 385 DG M TNC 440

Part No. 952 313 952 300 952 314 952 303

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

N E W N E W

Accessory Part for DEHNguard® modular

952 012 DG MOD150952 010 DG MOD275952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DGMOD150952 012DGMOD275952 010DGMOD320952 013DGMOD385952 014DGMOD440952 015

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

PU PartType pc(s). No.

DG MOD 150 1 952 012DG MOD 275 1 952 010

DG MOD 385 1 952 014

DG MOD 440 1 952 015

Page 80: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 80/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

78 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular

DEHNguard M TNC ... FM952 318 DG M TNC 150 FM952 305 DG M TNC 275 FM952 319 DG M TNC 385 FM952 308 DG M TNC 440 FM

DG M TN C 1 5 0 FM952 318DG M TN C 2 7 5 FM952 305DG M TN C 3 8 5 FM952 319DG M TN C 4 4 0 FM952 308

121114

L1 L2 L3

PEN9

Basic circuit diagram DG M TNC ... F M Dimension drawing DG M TNC ... F M

DG M TNC ... FM: Modular surge arrester for TN-C systems; with floating remote signalling contact

DG M TNC 150 FM DG M TNC 275 FM DG M TNC 385 FM DG M TNC 440 FM

SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II Class II Class II

Nominal a.c. voltage UN 120/240 V 230/400 V 230/400 V 400/690 V

Max. continuous operating a.c. voltage UC 150 V 275 V 385 V 440 V

Nominal discharge current (8/20 µs) In 15 kA 20 kA 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA 40 kA 40 kA

Voltage protection level UP 0.7 kV 1.25 kV 1.75 kV 2 kV

Voltage protection level at 5 kA UP 0.55 kV 1 kV 1.35 kV 1.7 kV

Response time tA 25 ns 25 ns 25 ns 25 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability

for max. mains-side overcurrent protection 50 kArms 50 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec. 580 V / 5 V / 5 sec.

TOV characteristics withstand withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20 IP 20

Capacity 3 mods., DIN 43880 3 mods., DIN 43880 3 mods., DIN 43880 3 mods., DIN 43880

Approvals, Certifications — KEMA,VDE, UL,VdS — —

Type of remote signalling contact changeover contact changeover contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TNC 150 FM DG M TNC 275 FM DG M TNC 385 FM DG M TNC 440 FM

Part No. 952 318 952 305 952 319 952 308

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

N E W N E W

Accessory Part for DEHNguard® modular

952 012 DG MOD150952 010 DG MOD275952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DGMOD150952 012DGMOD275952 010DGMOD320952 013DGMOD385952 014DGMOD440952 015

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

PU PartType pc(s). No.

DG MOD 150 1 952 012

DG MOD 275 1 952 010

DG MOD 385 1 952 014

DG MOD 440 1 952 015

Page 81: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 81/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

79www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular

DEHNguard M TNS ...DG M TNS 150DG M TNS 275DG M TNS 385

L2 N

PE

L1 L3

9

Basic circuit diagram DG M TNS ...Dimension drawing DG M TNS ...

DG M TNS ... : Modular surge arrester for TN-S systems

DG M TNS 150 DG M TNS 275 DG M TNS 385

SPD according to EN 61643-11 Type 2 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II Class II

Nominal a.c. voltage UN 120/240 V 230/400 V 230/400 V

Max. continuous operating a.c. voltage UC 150 V 275 V 385 V

Nominal discharge current (8/20 µs) In 15 kA 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA 40 kA

Voltage protection level UP 0.7 kV 1.25 kV 1.75 kV

Voltage protection level at 5 kA UP 0.55 kV 1 kV 1.35 kV

Response time tA 25 ns 25 ns 25 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability

for max. mains-side overcurrent protection 50 kArms 50 kArms 25 kArms

Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.

TOV characteristics withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 4 mods., DIN 43880 4 mods., DIN 43880 4 mods., DIN 43880

Approvals, Certifications KEMA, UL KEMA, VDE,UL, VdS KEMA, UL

Ordering informationType DG M TNS 150 DG M TNS 275 DG M TNS 385

Part No. 952 403 952 400 952 404

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

N E W N E W

Accessory Part for DEHNguard® modular

952 012 DG MOD150952 010 DG MOD275952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DGMOD150952 012DGMOD275952 010DGMOD320952 013DGMOD385952 014DGMOD440952 015

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

PU Part

Type pc(s). No.DG MOD 150 1 952 012

DG MOD 275 1 952 010

DG MOD 385 1 952 014

Page 82: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 82/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

80 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular

DEHNguard M TNS ... FM952 408 DG M TNS 150 FM952 405 DG M TNS 275 FM952 409 DG M TNS 385 FM

DG M TN S1 5 0 FM952 408DG M TN S2 7 5 FM952 405DG M TN S3 8 5 FM952 409

L2 N

PE

L1 L3

121114

9

Basic circuit diagram D G M TNS ... F M Dimension drawing D G M TNS ... F M

DG M TNS ... FM: Modular surge arrester for TN-S systems; with floating remote signalling contact

DG M TNS 150 FM DG M TNS 275 FM DG M TNS 385 FM

SPD according to EN 61643-11 Type 2 Type 2 Type 2SPD according to IEC 61643-1 Class II Class II Class II

Nominal a.c. voltage UN 120/240 V 230/400 V 230/400 V

Max. continuous operating a.c. voltage UC 150 V 275 V 385 V

Nominal discharge current (8/20 µs) In 15 kA 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA 40 kA

Voltage protection level UP 0.7 kV 1.25 kV 1.75 kV

Voltage protection level at 5 kA UP 0.55 kV 1 kV 1.35 kV

Response time tA 25 ns 25 ns 25 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability

for max. mains-side overcurrent protection 50 kArms 50 kArms 25 kArms

Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.

TOV characteristics withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 4 mods., DIN 43880 4 mods., DIN 43880 4 mods., DIN 43880

Approvals, Certifications KEMA, UL KEMA,VDE, UL,VdS KEMA, UL

Type of remote signalling contact changeover contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 ACross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TNS 150 FM DG M TNS 275 FM DG M TNS 385 FM

Part No. 952 408 952 405 952 409

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). N E W N E W

Accessory Part for DEHNguard® modular

952 012 DG MOD150952 010 DG MOD275952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DGMOD150952 012DGMOD275952 010DGMOD320952 013DGMOD385952 014DGMOD440952 015

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

PU Part

Type pc(s). No.DG MOD 150 1 952 012

DG MOD 275 1 952 010

DG MOD 385 1 952 014

Page 83: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 83/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

81www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular

DEHNguard M TT ...DG M TT 275DG M TT 320DG M TT 385

L2 N

PE

L1 L3

9

DG M TT ... : Modular surge arrester for TT and TN-S systems (”3+1” circuits)

DG M TT 275 DG M TT 320 DG M TT 385

SPD according to EN 61643-11 Type 2 Type 2 Type 2SPD according to IEC 61643-1 Class II Class II Class II

Nominal a.c. voltage UN 230/400 V 230/400 V 230/400 V

Max. continuous operating a.c. voltage [L-N] UC 275 V 320 V 385 V

Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V 255 V

Nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA 40 kA

Lightning impulse current (10/350 µs) [N-PE] Iimp 12 kA 12 kA 12 kA

Voltage protection level [L-N] UP 1.25 kV 1.5 kV 1.75 kV

Voltage protection level [L-N] at 5 kA UP 1 kV 1.2 kV 1.35 kV

Voltage protection level [N-PE] UP 1.5 kV 1.5 kV 1.5 kV

Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms 100 Arms

Response time [L-N] tA 25 ns 25 ns 25 ns

Response time [N-PE] tA 100 ns 100 ns 100 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability

for max. mains-side overcurrent protection 50 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0Degree of protection IP 20 IP 20 IP 20

Capacity 4 mods., DIN 43880 4 mods., DIN 43880 4 mods., DIN 43880

Approvals, Certifications KEMA, VDE,UL, VdS KEMA KEMA

Ordering information

Type DG M TT 275 DG M TT 320 DG M TT 385

Part No. 952 310 952 320 952 311

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

952 050 DG MODNPE

DGMODNPE952 050

N-PE spark-gap-based protection module forDEHNguard M TT ...

DG MOD NPE: N-PE spark-gap-based protection module for two- andfour-pole DEHNguard DG M TT ... surge arresters

PU PartType pc(s). No.

DG MOD NPE 1 952 050

N E W N E W

Basic circuit diagram DG M TT ...Dimension drawing DG M TT ...

Accessory Part for DEHNguard® modular Accessory Part for DEHNguard® modular

952 012 DG MOD150952 010 DG MOD275952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DGMOD150952 012DGMOD275952 010DGMOD320952 013DGMOD385952 014DGMOD440952 015

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...and

DEHNguard S ... surge arrestersPU Part

Type pc(s). No.

DG MOD 275 1 952 010

DG MOD 320 1 952 013

DG MOD 385 1 952 014

Page 84: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 84/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

82 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular

DEHNguard M TT ... FM952 315 DG M TT 275 FM952 325 DG M TT 320 FM952 316 DG M TT 385 FM

DG M TT2 7 5 FM952 315DG M TT3 2 0 FM952 325DG M TT3 8 5 FM952 316

L2 N

PE

L1 L3

121114

9

Basic circuit diagram DG M TT ... FM Dimension drawing DG M TT ... FM

DG M TT ... FM: Modular surge arrester for TT and TN-S systems (”3+1” circuits); with floatingremote signalling contact

DG M TT 275 FM DG M TT 320 FM DG M TT 385 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II Type 2 / Class II

Nominal a.c. voltage UN 230/400 V 230/400 V 230/400 V

Max. continuous operating a.c. voltage [L-N] UC 275 V 320 V 385 V

Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V 255 V

Nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA 40 kA

Lightning impulse current (10/350 µs) [N-PE] I imp 12 kA 12 kA 12 kA

Voltage protection level [L-N] UP 1.25 kV 1.5 kV 1.75 kV

Voltage protection level [L-N] at 5 kA UP 1 kV 1.2 kV 1.35 kV

Voltage protection level [N-PE] UP 1.5 kV 1.5 kV 1.5 kV

Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms 100 Arms

Response time [L-N] tA 25 ns 25 ns 25 ns

Response time [N-PE] tA 100 ns 100 ns 100 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability

for max. mains-side overcurrent protection 50 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 4 mods., DIN 43880 4 mods., DIN 43880 4 mods., DIN 43880Approvals, Certifications KEMA,VDE, UL, VdS KEMA KEMA

Type of remote signalling contact changeover contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TT 275 FM DG M TT 320 FM DG M TT 385 FM

Part No. 952 315 952 325 952 316

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). N E W N E W

952 050 DG MODNPE

DGMODNPE952 050

N-PE spark-gap-based protection module forDEHNguard M TT ...

DG MOD NPE: N-PE spark-gap-based protection module for two- andfour-pole DEHNguard DG M TT ... surge arresters

PU PartType pc(s). No.

DG MOD NPE 1 952 050

Accessory Part for DEHNguard® modularAccessory Part for DEHNguard® modular

952 012 DG MOD150952 010 DG MOD275952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DGMOD150952 012DGMOD275952 010DGMOD320952 013DGMOD385952 014DGMOD440952 015

Varistor-based protection moduleDG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

PU PartType pc(s). No.

DG MOD 275 1 952 010

DG MOD 320 1 952 013

DG MOD 385 1 952 014

Page 85: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 85/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

83www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular

DEHNguard M TN ...DG M TN 150DG M TN 275

NL

PE9

Basic circuit diagram DG M TN ...Dimension drawing DG M TN ...

DG M TN ... : Modular surge arrester for single-phase TN systems

DG M TN 150 DG M TN 275

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Nominal a.c. voltage UN 120 V 230 V

Max. continuous operating a.c. voltage UC 150 V 275 V

Nominal discharge current (8/20 µs) In 15 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA

Voltage protection level UP 0.7 kV 1.25 kV

Voltage protection level at 5 kA UP 0.55 kV 1 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 50 kArms 50 kArms

Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Approvals, Certifications — KEMA, VDE,UL, VdS

Ordering information

Type DG M TN 150 DG M TN 275

Part No. 952 201 952 200

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular

952 010 DG MOD275952 012 DG MOD150952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DG MOD 275 ÜS-Modulfür DG Mund DG S, 275 V 952 010DG MOD 150 ÜS-Modulfür DG Mund DG S, 150 V 952 012DG MOD 320 ÜS-Modulfür DG Mund DG S, 320 V 952 013DG MOD 385 ÜS-Modulfür DG Mund DG S, 385 V 952 014DG MOD 440 ÜS-Modulfür DG Mund DG S, 440 V 952 015

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

PU PartType pc(s). No.

DG MOD 150 1 952 012

DG MOD 275 1 952 010

N E W

Page 86: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 86/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

84 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular

DEHNguard M TN ... FM952 206 DG M TN 150 FM952 205 DG M TN 275 FM

DG M TN 1 5 0 FM952 206DG M TN 2 7 5 FM952 205

NL

121114

PE9

Basic circuit diagram DG M TN ... FM Dimension drawing DG M TN ... FM

DG M TN ... FM: Modular surge arrester for single-phase TN systems; with floating remote sig-nalling contact

DG M TN 150 FM DG M TN 275 FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Nominal a.c. voltage UN 120 V 230 V

Max. continuous operating a.c. voltage UC 150 V 275 V

Nominal discharge current (8/20 µs) In 15 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA

Voltage protection level UP 0.7 kV 1.25 kV

Voltage protection level at 5 kA UP 0.55 kV 1 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 50 kArms 50 kArms

Temporary overvoltage (TOV) UT 175 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Approvals, Certifications — KEMA, VDE,UL, VdS

Type of remote signalling contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TN 150 FM DG M TN 275 FM

Part No. 952 206 952 205

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...and

DEHNguard S ... surge arrestersPU Part

Type pc(s). No.

DG MOD 150 1 952 012

DG MOD 275 1 952 010

952 010 DG MOD275952 012 DG MOD150952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DG MOD 275 ÜS-Modulfür DG M und DG S, 275 V 952 010DG MOD 150 ÜS-Modulfür DG M und DG S, 150 V 952 012DG MOD 320 ÜS-Modulfür DG M und DG S, 320 V 952 013DG MOD 385 ÜS-Modulfür DG M und DG S, 385 V 952 014DG MOD 440 ÜS-Modulfür DG M und DG S, 440 V 952 015

N E W

Page 87: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 87/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

85www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular

DEHNguard M TT 2P ...DG M TT 2P 275DG M TT 2P 320DG M TT 2P 385

N

PE

L

9

Basic circuit diagram DG M TT 2P ...Dimension drawing DG M TT 2P ...

DG M TT 2P ... : Modular surge arrester for single-phase TT and TN systems (”1+1” circuits)

DG M TT 2P 275 DG M TT 2P 320 DG M TT 2P 385

SPD according to EN 61643-11 Type 2 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II Class II

Nominal a.c. voltage UN 230 V 230 V 230 V

Max. continuous operating a.c. voltage [L-N] UC 275 V 320 V 385 V

Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V 255 V

Nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA 40 kA

Lightning impulse current (10/350 µs) [N-PE] Iimp 12 kA 12 kA 12 kA

Voltage protection level [L-N] UP 1.25 kV 1.5 kV 1.75 kV

Voltage protection level [L-N] at 5 kA UP 1 kV 1.2 kV 1.35 kV

Voltage protection level [N-PE] UP 1.5 kV 1.5 kV 1.5 kV

Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms 100 Arms

Response time [L-N] tA 25 ns 25 ns 25 ns

Response time [N-PE] tA 100 ns 100 ns 100 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability

for max. mains-side overcurrent protection 50 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880

Approvals, Certifications KEMA, VDE,UL, VdS KEMA KEMA

Ordering information

Type DG M TT 2P 275 DG M TT 2P 320 DG M TT 2P 385

Part No. 952 110 952 130 952 111

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular

952 010 DG MOD275952 012 DG MOD150952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DG MOD 275 ÜS-Modulfür DG Mund DG S, 275 V 952 010DG MOD 150 ÜS-Modulfür DG Mund DG S, 150 V 952 012DG MOD 320 ÜS-Modulfür DG Mund DG S, 320 V 952 013DG MOD 385 ÜS-Modulfür DG Mund DG S, 385 V 952 014DG MOD 440 ÜS-Modulfür DG Mund DG S, 440 V 952 015

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...and

DEHNguard S ... surge arrestersVPE

Typ Stk. Art.-Nr.

DG MOD 275 1 952 010

DG MOD 320 1 952 013

DG MOD 385 1 952 014

N E W N E W

952 050 DG MODNPE

DGMODNPE952 050

N-PE spark-gap-based protection module forDEHNguard M TT ...

DG MOD NPE: N-PE spark-gap-based protection module for two- andfour-pole DEHNguard DG M TT ... surge arresters

PU PartType pc(s). No.

DG MOD NPE 1 952 050

Accessory Part for DEHNguard® modular

Page 88: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 88/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

86 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® modular

DEHNguard M TT 2P ... FM952 115 DG M TT 2P 275 FM952 135 DG M TT 2P 320 FM952 116 DG M TT 2P 385 FM

DG M TT2 P 2 7 5 FM952 115DG M TT2 P 3 2 0 FM952 135DG M TT2 P 3 8 5 FM952 116

N

PE

L

121114

9

Basic circuit diagram D G M TT 2P ... F M Dimension drawing DG M TT 2P ... FM

DG M TT 2P ... FM: Modular surge arrester for single-phase TT and TN systems (”1+1” circuit);with floating remote signalling contact

DG M TT 2P 275 FM DG M TT 2P 320 FM DG M TT 2P 385 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II Type 2 / Class II

Nominal a.c. voltage UN 230 V 230 V 230 V

Max. continuous operating a.c. voltage [L-N] UC 275 V 320 V 385 V

Max. continuous operating a.c. voltage [N-PE] UC 255 V 255 V 255 V

Nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA 40 kA

Lightning impulse current (10/350 µs) [N-PE] I imp 12 kA 12 kA 12 kA

Voltage protection level [L-N] UP 1.25 kV 1.5 kV 1.75 kV

Voltage protection level [L-N] at 5 kA UP 1 kV 1.2 kV 1.35 kV

Voltage protection level [N-PE] UP 1.5 kV 1.5 kV 1.5 kV

Follow current extinguishing capability [N-PE] Ifi 100 Arms 100 Arms 100 Arms

Response time [L-N] tA 25 ns 25 ns 25 ns

Response time [N-PE] tA 100 ns 100 ns 100 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability

for max. mains-side overcurrent protection 50 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880Approvals, Certifications KEMA,VDE, UL, VdS KEMA KEMA

Type of remote signalling contact changeover contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG M TT 2P 275 FM DG M TT 2P 320 FM DG M TT 2P 385 FM

Part No. 952 115 952 135 952 116

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular

Varistor-based protection moduleDG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

VPETyp Stk. Art.-Nr.

DG MOD 275 1 952 010

DG MOD 320 1 952 013

DG MOD 385 1 952 014

952 010 DG MOD275952 012 DG MOD150952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440

DG MOD 275 ÜS-Modulfür DG M und DG S, 275 V 952 010DG MOD 150 ÜS-Modulfür DG M und DG S, 150 V 952 012DG MOD 320 ÜS-Modulfür DG M und DG S, 320 V 952 013DG MOD 385 ÜS-Modulfür DG M und DG S, 385 V 952 014DG MOD 440 ÜS-Modulfür DG M und DG S, 440 V 952 015

N E W N E W

952 050 DG MODNPE

DGMODNPE952 050

N-PE spark-gap-based protection module forDEHNguard M TT ...

DG MOD NPE: N-PE spark-gap-based protection module for two- andfour-pole DEHNguard DG M TT ... surge arresters

PU PartType pc(s). No.

DG MOD NPE 1 952 050

Accessory Part for DEHNguard® modular

Page 89: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 89/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

87www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® modular

DEHNguard M WE ... (FM)DG M WE 600DG M WE 600 FM

121114

L1 L2 L3

PEN9

Basic circuit diagram DG M WE ... FMDimension drawing DG M WE ... FM

DG M WE ... (FM): Three-pole modular surge arrester for use in wind turbines with a rated voltageof the varistor Umov = 750 V a.c.; FM version with floating remote signallingcontact

DG M WE 600 DG M WE 600 FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Nominal a.c. voltage UN 600 V 600 V

Max. continuous operating a.c. voltage UC 600 V 600 V

Rated voltage of varistor Umov 750 V 750 V

Nominal discharge current (8/20 µs) In 15 kA 15 kA

Max. discharge current (8/20 µs) Imax 25 kA 25 kA

Voltage protection level UP 3 kV 3 kV

Voltage protection level at 5 kA UP 2.5 kV 2.5 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection 100 A gL/gG 100 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 900 V / 5 sec. 900 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 3 mods., DIN 43880 3 mods., DIN 43880

Approvals, Certifications KEMA, UL,VdS KEMA, UL,VdS

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 ACross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG M WE 600 DG M WE 600 FM

Part No. 952 302 952 307

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® modular

Varistor-based protection module for DEHNguardM (S) WE

DG MOD 750: Varistor-based protection module for DEHNguard M WE... and DEHNguard S WE ... surge arresters with a rated varistor voltage

Umov = 750 V a.c.PU Part

Type pc(s). No.

DG MOD 750 1 952 017

952 017 DG MOD750

DGMOD750952 017

Page 90: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 90/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

88 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® S / DEHNguard® S FM

Single-pole, pluggable surge arresterSPD Type 2 according to EN 61643-11SPD Class II according to IEC 61643-1

• Multi-purpose surge arrester consisting of abase element and plug-in protection module

• High discharge capacity due to heavy-duty zincoxide varistor

• High reliability due to ”Thermo DynamicControl” SPD monitoring device

• Energy coordination within the Red/Line pro-duct family

• Narrow (modular) design acc. to DIN 43880

• Multifunctional terminals for connecting con-ductors and busbars

• Easy replacement of protection modules due tomodule locking system with module releasebutton

• Vibration- and shock-tested according to EN60068-2

DEHNguard S ...: Pluggable surge arrester consisting of a base part and plug-in protection module

DEHNguard S ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

For protecting low-voltage consumer´s installations against surges. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 0B – 1 and higher.

The universal features are characteristic of the single-pole devices of theDEHNguard S product family. Be it as a single device or in combinationwith other devices – DEHNguard S surge arresters always provide theright protective circuit. The modern Red/Line family design and its univer-sal features ensure safety and user-friendliness. The module release but-ton and the approved Thermo Dynamic Control SPD monitoring devicewith dual tripping performance characterise the devices of theDEHNguard S series.

Experience of decades in the international use of surge arresters has fur-

ther improved the latest DEHNguard generation compared to the previoustypes.

The module locking system, which is unique for use with surge protectivedevices, fixes the protection module and the base part firmly in place.Neither vibration during transport nor the enormous electromagneticforces of discharge can loosen this connection. Nevertheless, the modulescan be easily replaced without tools by simply pressing the user-friendlymodule release button of the protection modules.

In order to avoid incorrect insertion by the installer or user when replac-ing the protection modules, every base part and protection module ismechanically coded by the manufacturer.

Like with all DEHNguard surge arresters, the users of DEHNguard S canrely on the dual Thermo Dynamic Control SPD monitoring device. Thisensures maximum reliability of the devices, even under unfavourableenvironmental conditions. The green and red indicator shows if DEHNguard S is ready for operation.Apart from the standard visual indi-cator, DEHNguard S ... FM features a three-pole terminal for remote sig-nalling. With its floating changeover contact, the remote signal can beused as a break or make contact according to the particular circuit con-cept. The multifunctional terminals of DEHNguard S surge arresters aresuitable for connecting conductors and busbars, allowing an easy connec-

tion to other DIN rail mounted devices. Series connection according to IEC60364-5-53 for optimal protection is therefore possible for a wide rangeof applications.

Page 91: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 91/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

89www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® S / DEHNguard® S FM

DEHNguard S ...DG S 48DG S 75DG S 150DG S 275DG S 320DG S 385DG S 440DG S 600

Basic circuit diagram DG S ...Dimension drawing DG S ...

DG S ...: Single-pole, pluggable surge arrester consisting of a base part and plug-in protectionmodule

DG S 48 DG S 75 DG S 150 DG S 275 DG S 320 DG S 385 DG S 440 DG S 600

SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II Class II Class II Class II Class II Class II Class II

Max. continuous operat. a.c. volt. UC 48 V 75 V 150 V 275 V 320 V 385 V 440 V 600 V

Max. continuous operat. d.c. volt. UC 60 V 100 V 200 V 350 V 420 V 500 V 585 V 600 V

Nominal discharge current (8/20 µs) In 10 kA 10 kA 15 kA 20 kA 20 kA 20 kA 20 kA 15 kA

Max. discharge current (8/20 µs) Imax 25 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA

Voltage protection level UP 0.3 kV 0.4 kV 0.7 kV 1.25 kV 1.5 kV 1.75 kV 2 kV 2.5 kV

Voltage protection level at 5 kA UP 0.25 kV 0.35 kV 0.55 kV 1 kV 1.2 kV 1.35 kV 1.7 kV 2 kV

Response time tA 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 100 A gL/gG

Short-circuit withstand capability for max.

mains-side overcurrent protection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 70 V / 5 sec. 90 V / 5 sec. 175 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec. 580 V / 5 sec. 600 V / 5 sec.

TOV characteristics withstand withstand withstand withstand withstand withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red green / red green / red green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20

Capacity 1 mod., DIN 43880

Approvals, Certifications — KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE,

UL, CSA UL,VdS, CSA UL,VdS, CSA UL,VdS, CSA UL,VdS, CSA UL,VdS, CSA UL,VdS, CSA

Ordering information

Type DG S 48 DG S 75 DG S 150 DG S 275 DG S 320 DG S 385 DG S 440 DG S 600

Part No. 952 078 952 071 952 072 952 070 952 073 952 074 952 075 952 076

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® S / DEHNguard® S FM

952 018 DG MOD48952 011 DG MOD75952 012 DG MOD150952 010 DG MOD275952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440952 016 DG MOD600

DG M O D4 8952 018DG M O D7 5952 011DGMOD150952 012DGMOD275952 010DGMOD320952 013DGMOD385952 014DGMOD440952 015DGMOD600952 016

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

PU PartType pc(s). No.

DG MOD 48 1 952 018

DG MOD 75 1 952 011

DG MOD 150 1 952 012DG MOD 275 1 952 010

DG MOD 320 1 952 013

DG MOD 385 1 952 014

DG MOD 440 1 952 015

DG MOD 600 1 952 016

Page 92: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 92/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

90 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® S / DEHNguard® S FM

DEHNguard S ... FM952 098 DG S 48FM952 091 DG S 75FM952 092 DG S 150FM952 090 DG S 275FM952 093 DG S 320FM952 094 DG S 385FM952 095 DG S 440FM952 096 DG S 600FM

DG S4 8 FM952 098DG S7 5 FM952 091DG S1 5 0 FM952 092DG S2 7 5 FM952 090DG S3 2 0 FM952 093DG S3 8 5 FM952 094DG S4 4 0 FM952 095DG S6 0 0 FM952 09612

1114

Basic circuit diagram DG S ... FM Dimension drawing DG S ... FM

DG S ... FM: Single-pole, pluggable surge arrester consisting of a base part and plug-in protectionmodule; with floating remote signalling contact

DG S 48 FM DG S 75 FM DG S 150 FM DG S 275 FM DG S 320 FM DG S 385 FM DG S 440 FM DG S 600 FM

SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II Class II Class II Class II Class II Class II Class II

Max. continuous operat. a.c. volt. UC 48 V 75 V 150 V 275 V 320 V 385 V 440 V 600 V

Max. continuous operat. d.c. volt. UC 60 V 100 V 200 V 350 V 420 V 500 V 585 V 600 V

Nominal discharge current (8/20 µs) In 10 kA 10 kA 15 kA 20 kA 20 kA 20 kA 20 kA 15 kA

Max. discharge current (8/20 µs) Imax 25 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA

Voltage protection level UP 0.3 kV 0.4 kV 0.7 kV 1.25 kV 1.5 kV 1.75 kV 2 kV 2.5 kV

Voltage protection level at 5 kA UP 0.25 kV 0.35 kV 0.55 kV 1 kV 1.2 kV 1.35 kV 1.7 kV 2 kV

Response time tA 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG 100 A gL/gG

Short-circuit withstand capability for max.

mains-side overcurrent protection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 70 V / 5 sec. 90 V / 5 sec. 175 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec. 580 V / 5 sec. 600 V / 5 sec.

TOV characteristics withstand withstand withstand withstand withstand withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red green / red green / red green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20

Capacity 1 mod., DIN 43880

Approvals, Certifications — KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE, KEMA, VDE,

UL, CSA UL,VdS, CSA UL,VdS, CSA UL,VdS, CSA UL,VdS, CSA UL,VdS, CSA UL,VdS, CSA

Type of remote signalling contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 ACross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information

Type DG S 48 FM DG S 75 FM DG S 150 FM DG S 275 FM DG S 320 FM DG S 385 FM DG S 440 FM DG S 600 FM

Part No. 952 098 952 091 952 092 952 090 952 093 952 094 952 095 952 096

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Varistor-based protection module

DG MOD ...:Varistor-based protection module for DEHNguard M ...andDEHNguard S ... surge arresters

PU PartType pc(s). No.

DG MOD 48 1 952 018

DG MOD 75 1 952 011

DG MOD 150 1 952 012

DG MOD 275 1 952 010

DG MOD 320 1 952 013

DG MOD 385 1 952 014

DG MOD 440 1 952 015

DG MOD 600 1 952 016

952 018 DG MOD48952 011 DG MOD75952 012 DG MOD150952 010 DG MOD275952 013 DG MOD320952 014 DG MOD385952 015 DG MOD440952 016 DG MOD600

DG M O D4 8952 018DG M O D7 5952 011DGMOD150952 012DGMOD275952 010DGMOD320952 013DGMOD385952 014DGMOD440952 015DGMOD600952 016

Page 93: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 93/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

91www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® S / DEHNguard® S FM

DEHNguard S WE 600 (FM)DG S WE

DG S WE

121114

Basic circuit diagram DG S WE 600 FMDimension drawing DG S WE 600 FM

DG S WE 600 (FM): Single-pole, pluggable surge arrester with a rated varistor voltage Umov = 750 Va.c., consisting of base part and plug-in protection module; FM version withfloating remote signalling contact

DG S WE 600 DG S WE 600 FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Max. continuous operating a.c. voltage UC 600 V 600 V

Rated varistor voltage a.c. Umov 750 V 750 V

Nominal discharge current (8/20 µs) In 15 kA 15 kA

Max. discharge current (8/20 µs) Imax 25 kA 25 kA

Voltage protection level UP 3 kV 3 kV

Voltage protection level at 5 kA UP 2.5 kV 2.5 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection 100 A gL/gG 100 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 900 V / 5 sec. 900 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 1 mod., DIN 43880 1 mod., DIN 43880

Approvals, Certifications UL, CSA UL, CSA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG S WE 600 DG S WE 600 FM

Part No. 952 077 952 097

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® S / DEHNguard® S FM

952 017 DG MOD750

DGMOD750952 017

Varistor-based protection module forDEHNguard M (S) WE

DG MOD 750: Varistor-based protection module for DEHNguard M WE... and DEHNguard S WE ... with a rated varistor voltage Umov = 750 Va.c.

PU PartType pc(s). No.

DG MOD 750 1 952 017

Page 94: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 94/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

92 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNgap C S

N-PE surge arresterSPD Type 2 according to EN 61643-11SPD Class II according to IEC 61643-1

• Specifically designed for use in ”3+1” and”1+1” circuits of TT systems acc. to IEC 60364-5-53 between neutral conductor N and protec-tive earth conductor PE

• High discharge capacity

• Two-part unit consisting of a base part andspark-gap-based plug-in protection module

• Energy coordination within the Red/Line pro-duct family

• Operating state/fault indication by indicatorflag in the inspection window

• With remote signalling contact for SPD moni-toring device

• Easy replacement of protection modules with-out tools due to module release button

• Vibration- and shock-tested according to EN60068-2

DEHNgap C S: N-PE surge arrester consisting of a base part and plug-in protection module

DEHNgap C S FM: With remote signalling contact for monitoring device (floating changeover contact)

For protecting low-voltage consumer´s installations against surges. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 0B – 1 and higher.

The N-PE surge arrester DEHNgap C S ideally complements the single-poleDEHNguard S surge protective devices. Being a total current arresterbetween neutral conductor and protective conductor in TT systems, itsfunction is to ensure that the requirements for protection of persons andmaterial assets in so-called ”3+1” and ”1+1” circuits are fulfilled.

With the modern Red/Line design, DEHNgap C S provides safety and per-formance just like the DEHNguard S devices.The module locking system,which is unique for use with surge protective devices, combines the spark-gap-based module and base part to a powerful unit. Neither vibration

during transport nor the enormous electromagnetic forces of dischargecan loosen the protection module. Nevertheless, the protection modulescan be easily replaced without tools by simply pressing the modulerelease button of the protection module. The mechanical coding at theprotection module and base part prevents incorrect insertion by theinstaller or user.

Monitoring of the arrester temperature and an integrated disconnector,which is connected in series to the surge arrester, further increase thesafety of DEHNgap C S.

The green and red indicator shows if DEHNgap C S is ready for operation.

Apart from the standard visual indicator, DEHNgap C S ... FM incorporatesa three-pole terminal for remote signalling. With its floating changeovercontact, the remote signal can be used as a break or make contact accord-ing to the particular circuit concept. The N-PE surge arrester DEHNgap C

S features multifunctional terminals for connection of conductors andbusbars, allowing easy wiring with other DIN rail mounted devices. Seriesconnection according to IEC 60364-5-53 for optimal protection is there-fore possible for a wide range of applications.

Page 95: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 95/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

93www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNgap C S

DEHNgap C S (FM)DGP C SDGP C S

121114

Basic circuit diagram DGP C S FMDimension drawing DGP C S FM

DGP C S (FM): N-PE surge arrester; FM version with floating remote signalling contact

DGP C S DGP C S FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Max. continuous operating a.c. voltage UC 255 V 255 V

Nominal discharge current (8/20 µs) In 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 40 kA 40 kA

Follow current extinguishing capability Ifi 100 Arms 100 Arms

Lightning impulse current (10/350 µs) Iimp 12 kA 12 kA

Voltage protection level UP 1.5 kV 1.5 kV

Response time tA 100 ns 100 ns

Temporary overvoltage (TOV) UT 1200 V / 200 ms 1200 V / 200 ms

TOV characteristics withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 1 mod., DIN 43880 1 mod., DIN 43880

Approvals, Certifications KEMA, VDE, UL,VdS KEMA, VDE,UL, VdS

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DGP C S DGP C S FM

Part No. 952 030 952 035

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNgap C S

952 060 DGP CMOD

DG P C M O D952 060

N-PE spark-gap-based protection module forDEHNgap C S

DGP C MOD: N-PE spark-gap-based protection module for single-poleN-PE surge arresters of type DEHNgap DGP C S ...

PU Part

Type pc(s). No.DGP C MOD 1 952 060

Page 96: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 96/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

94 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

SPD Type 2 according to EN 61643-11SPD Class II according to IEC 61643-1

• High discharge capacity due to heavy-duty zincoxide varistors/spark gaps

• High reliability due to ”Thermo DynamicControl” SPD monitoring device

• Energy coordination within the Red/Line pro-duct family

• Operating state/fault indication by indicatorflag in the inspection window

• Easy replacement of protection modules with-out tools by module locking system with mod-ule release button

• The plug-in protection module can be replacedwithout the need to de-energise and withoutremoving the cover plate of the distributionboard

• Vibration- and shock-tested according to EN60068-2

DEHNguard MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard S

DEHNguard MOD 750: Varistor-based protection module for DEHNguard M WE 600 and DEHNguard S WE 600DEHNguard MOD NPE: N-PE spark-gap-based protection module for two- and four-pole DEHNguard M TT ... surge

arresters

DEHNgap C MOD: N-PE spark-gap-based protection module for single-pole DEHNgap C S ... N-PE surge arresters

DEHNguard MOD CI 275: Varistor-based protection module for DEHNguard M CI

DEHNguard MOD ... VA: Varistor- and spark-gap-based protection module for DEHNguard S ... VA

DEHNguard MOD PV SCI ...: Varistor-based protection module for DEHNguard M YPV SCI

For protecting low-voltage consumer´s installations against surges. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 0B – 1 and higher.

The varistor- and spark-gap-based protection modules of the DEHNguardM, DEHNguard S and DEHNgap C S devices distinguish themselves

through their outstanding performance and sophistication.The compact protection modules include the complete protective circuitas well as the monitoring device and disconnector.The green flag in the window indicates if the protection modules areready for operation.

In order to avoid incorrect insertion by the installer or user when replac-ing the modules, all protection modules are mechanically coded. The pro-

tection modules can be easily replaced without tools by simply pressingthe user-friendly module release button.

Protection Module

for DEHNguard® M, ... S and DEHNgap C S

Page 97: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 97/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

95www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

Prot. Mod. f. DEHNguard® M, ... S and DEHNgap C S

Varistor-based protection moduleDG MOD

DG MOD

DG MOD

DG MOD

DG MOD

DG MOD

DG MOD

DG MOD

Basic circuit diagram DG MOD varistor-basedprotection module

Dimension drawing DG MOD varistor-basedprotection module

DG MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard S ... surgearresters

DG MOD 48 DG MOD 75 DG MOD 150 DG MOD 275 DG MOD 320 DG MOD 385 DG MOD 440 DG MOD 600

Nominal discharge current (8/20 µs) In 10 kA 10 kA 15 kA 20 kA 20 kA 20 kA 20 kA 15 kA

Max. discharge current (8/20 µs) Imax 25 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA

Max. continuous op. a.c. voltage UC 48 V 75 V 150 V 275 V 320 V 385 V 440 V 600 V

Max. continuous op. d.c. voltage UC 60 V 100 V 200 V 350 V 420 V 500 V 585 V 600 V

Ordering information

Type DG MOD 48 DG MOD 75 DG MOD 150 DG MOD 275 DG MOD 320 DG MOD 385 DG MOD 440 DG MOD 600

Part No. 952 018 952 011 952 012 952 010 952 013 952 014 952 015 952 016

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Varistor-based protection module for DEHNguard M (S) WEDG MOD

Basic circuit diagram DG MOD 750 varistor-basedprotection module

Dimension drawing DG MOD 750 varistor-basedprotection module

DG MOD 750: Varistor-based protection module for DEHNguard M WE ... and DEHNguard S WE ...surge arresters with a rated varistor voltage Umov = 750 V a.c.

DG MOD 750

Nominal discharge current (8/20 µs) In 15 kA

Max. discharge current (8/20 µs) Imax 25 kA

Max. continuous operating a.c. voltage UC 600 V

Max. continuous operating d.c. voltage UC 600 V

Rated varistor voltage Umov 750 V

Ordering information

Type DG MOD 750

Part No. 952 017

Packing unit 1 pc(s).

Page 98: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 98/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

96 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

Prot. Mod. f. DEHNguard® M, ... S and DEHNgap C S

N-PE spark-gap-based protection module

for DEHNguard M TT ...

952 050 DG MODNPE

DGMODNPE952 050

Basic circuit diagram DG MOD NPE Dimension drawing DG MOD NPE

DG MOD NPE: N-PE spark-gap-based protection module for two- and four-pole DEHNguard DG MTT ... surge arresters

DG MOD NPE

Nominal discharge current (8/20 µs) In 20 kAMax. discharge current (8/20 µs) Imax 40 kA

Max. continuous operating a.c. voltage UC 255 V

Ordering information

Type DG MOD NPE

Part No. 952 050

Packing unit 1 pc(s).

N-PE spark-gap-based protection module for DEHNgap C S952 060 DGP CMOD

DG P CM O D952 060

Basic circuit diagram DGP C MOD Dimension drawing DGP C MOD

DGP C MOD: N-PE spark-gap-based protection module for single-pole N-PE surge arresters of type DEHNgap DGP C S ...

DGP C MOD

Nominal discharge current (8/20 µs) In 20 kA

Max. discharge current (8/20 µs) Imax 40 kA

Max. continuous operating a.c. voltage UC 255 V

Ordering informationType DGP C MOD

Part No. 952 060

Packing unit 1 pc(s).

Page 99: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 99/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

97www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

Prot. Mod. f. DEHNguard® M, ... S and DEHNgap C S

Varistor-based protection module

for DEHNguard M YPV SCI

DG MOD PV SCI 300DG MOD PV SCI 500DG MOD PV SCI 600

Basic circuit diagram DG MOD PV SCIDimension drawing DG MOD PV SCI

DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ... comprising a varistor con-nected in parallel with a short-circuiting device with integrated back-up fuse

DG MOD PV SCI 300 DG MOD PV SCI 500 DG MOD PV SCI 600

Nominal discharge current (8/20 µs) In 12.5 kA 12.5 kA 12.5 kAMax. discharge current (8/20 µs) Imax 25 kA 25 kA 25 kA

Max. continuous operating d.c. voltage UC 300 V 500 V 600 V

Ordering information

Type DG MOD PV SCI 300 DG MOD PV SCI 500 DG MOD PV SCI 600

Part No. 952 053 952 051 952 054

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Varistor-and spark-gap-based protection module for DEHNguard S ... VADG MOD 75 VADG MOD 275 VADG MOD 385 VA

Basic circuit diagram DG S ... VADimension drawing DG MOD ...VA

DG MOD ... VA: Protection module for DEHNguard S ... VA comprising a varistor connected inseries with a spark gap

DG MOD 75 VA DG MOD 275 VA DG MOD 385 VA

Nominal discharge current (8/20 µs) In 10 kA 10 kA 10 kA

Max. discharge current (8/20 µs) Imax 20 kA 20 kA 20 kA

Max. continuous operating a.c. voltage UC 75 V 275 V 385 V

Max. continuous operating d.c. voltage UC 100 V 350 V 500 V

Ordering information

Type DG MOD 75 VA DG MOD 275 VA DG MOD 385 VA

Part No. 952 025 952 027 952 029

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Page 100: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 100/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

98 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

Prot. Mod. f. DEHNguard® M, ... S and DEHNgap C S

Varistor-based protection modulefor DEHNguard M CI

952 020 DG MOD CI 275

DG M O DCI 2 7 5952 020

Basic circuit diagram DG MOD CI 275 Dimension drawing DG MOD CI 275

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connectedin series with the integrated backup fuse

DG MOD CI 275

Nominal discharge current (8/20 µs) In 12.5 kA

Max. discharge current (8/20 µs) Imax 25 kA

Max. continuous operating a.c. voltage UC 275 V

Ordering information

Type DG MOD CI 275

Part No. 952 020

Packing unit 1 pc(s).

Page 101: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 101/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

99www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® ... H LI

Multipole surge arrester with

‘’Pro-Active Thermo Control’’SPD Type 2 according to EN 61643-11SPD Class II according to IEC 61643-1

• Prewired complete unit for standard systemconfigurations consisting of a base part andplug-in protection modules

• Clear operating state indication due to 3-stagevisual service life indicator <GREEN-YELLOW-RED> with linked remote signalling function

• ”Pro-Active Thermo Control” SPD monitoringdevice

• Recommends the user to replace the protectionmodule <YELLOW> before the SPD is threat-ened by overloads

• Energy coordination within the Red/Line pro-duct family

DEHNguard TNC H LI: Multipole surge arrester with service life indicator for use in TN-C systems

DEHNguard TNS H LI: Multipole surge arrester with service life indicator for use in TN-S systems

DEHNguard TT H LI: Multipole surge arrester with service life indicator for use in TT and TN-S systems (”3+1” circuit)

DEHNguard T H LI: Single-pole surge arrester with service life indicator

For protecting low-voltage consumer´s installations against surges. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 0B – 1 and higher.

The single-pole and multipole surge arresters of the DEHNguard ... H LIfamily provide maximum safety and user-friendliness and set new stan-dards in surge protection.With the Pro-Active Thermo Control concept, they are the first ”intelli-gent” surge arresters to warn the user of failures of the surge protectionsystem in due time. With this technique, this new SPD monitoring devicemeets the steadily increasing requirements on the availability of electricalsystems in industrial, commercial and domestic environments. The 3-stagevisual indicator along with a floating changeover contact for remote sig-

nalling always informs the user on the operating state of the SPD. If thereis a risk that the varistor might be irreversibly damaged due to anincreased energy load, the user is informed by the yellow indicator andthe remote signalling function that the surge protection module should bereplaced – before the installation is unprotected!Like the well-known multipole DEHNguard family, the application-basedtype designation makes the choice of products of the prewired completeunits considerably easier. Less installation errors and saving of installationwork at the same time are unbeatable advantages for the customer. Both

the triple monitoring device of each circuit with Pro-Active ThermoControl and the coding of the pluggable protection modules characterisethe maximum degree of safety of the devices. Damage caused by incor-rect subsequent insertion by the installer or the user is very unlikely.With DEHNguard T H LI, the user is also provided with a single-pole devicefor universal use.All types of DEHNguard ... H LI feature a three-pole terminal for remotesignalling. With their floating changeover contact, the remote signal canbe used as a make or break con-

tact according to the particularcircuit concept.All surge arrestersof the DEHNguard ... H LI familyincorporate multifunctional ter-minals for the connection of con-ductors and busbars, allowingeasy wiring with other DIN railmounted devices.

Yellow indicator flag: Replacement of the protection module recommended

Page 102: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 102/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

100 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® ... H LI

DEHNguard TNC H LI950 160 DG TNCH230 400 LI

DGTNCH230400LI950 160

PEN

L3L1 L2

121114

Basic circuit diagram DG TNC H230 400 LI Dimension drawing DG TNC H230 400 LI

DG TNC H LI: Multipole surge arrester for use in TN-C systems with ”Pro-Active Thermo Control”SPD monitoring device with 3-stage visual indicator.

DG TNC H230 400 LI

SPD according to EN 61643-11 Type 2

SPD according to IEC 61643-1 Class II

Nominal a.c. voltage 230/400 V

Max. continuous operating a.c. voltage UC 275 V

Nominal discharge current (8/20 µs) In 20 kA

Max. discharge current (8/20 µs) Imax 65 kA

Voltage protection level UP 1.25 kV

Voltage protection level at 5 kA UP 1 kV

Response time tA 25 ns

Max. mains-side overcurrent protection 160 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec.

TOV characteristics withstand

Operating temperature range -40°C...+55°C

Indication of disconnector green-yellow-red

Cross-sectional area (min.) 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 3 mods., DIN 43880

Approvals, Certifications KEMA

Type of remote signalling contact changeover contact

Switching capacity a.c. 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information

Type DG TNC H230 400 LI

Part No. 950 160

Packing unit 1 pc(s).

950 130 T H 275 L I950 131 T H 385 L I

TH2 7 5 L I950 130

TH3 8 5 L I950 131

Varistor-based protection module with Pro-ActiveThermo Control

PU PartType pc(s). No.

T H 275 LI 1 950 130

Accessory Part for DEHNguard® ... H LI

Page 103: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 103/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

101www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® ... H LI

DEHNguard TNS H LIDG TNS

PE

L1 NL2 L3

121114

Basic circuit diagram DG TNS H 230 400 LIDimension drawing DG TNS H230 400 LI

DG TNS H LI: Multipole surge arrester for use in TN-S systems with ”Pro-Active Thermo Control”SPD monitoring device with 3-stage visual indicator

DG TNS H230 400 LI

SPD according to EN 61643-11 Type 2

SPD according to IEC 61643-1 Class II

Nominal a.c. voltage 230/400 V

Max. continuous operating a.c. voltage UC 275 V

Nominal discharge current (8/20 µs) In 20 kA

Max. discharge current (8/20 µs) Imax 65 kA

Voltage protection level UP 1.25 kV

Voltage protection level at 5 kA UP 1 kV

Response time tA 25 ns

Max. mains-side overcurrent protection 160 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec.

TOV characteristics withstand

Operating temperature range -40°C...+55°C

Indication of disconnector green-yellow-red

Cross-sectional area (min.) 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20

Capacity 4 mods., DIN 43880

Approvals, Certifications KEMA

Type of remote signalling contact changeover contact

Switching capacity a.c. 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information

Type DG TNS H230 400 LI

Part No. 950 170

Packing unit 1 pc(s).

950 130 T H 275 LI950 131 T H 385 LI

TH2 7 5 L I950 130

TH3 8 5 L I950 131

Varistor-based protection module with Pro-ActiveThermo Control

PU PartType pc(s). No.

T H 275 LI 1 950 130

Accessory Part for DEHNguard® ... H LI

Page 104: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 104/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

102 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® ... H LI

DEHNguard TT H LI950 150 DG TTH230 400 LI950 151 DG TTH230 400 LI385

DG TTH2 3 0 4 0 0 L I950 150DG TTH230 400 LI385950 151

PE

L1 NL2 L3

121114

Basic circuit diagram DG TT H230 400 LI Dimension drawing DG TT H230 400 LI

DG TT H LI: Multipole surge arrester with ”Pro-Active Thermo Control” SPD monitoring devicewith 3-stage visual indicator for use in TT and TN-S systems (”3+1” circuit)

DG TT H230 400 LI DG TT H230 400 LI385

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class IINominal a.c. voltage 230/400 V 230/400 V

Max. continuous operating a.c. voltage [L-N] 275 V 385 V

Max. continuous operating a.c. voltage [N-PE] 255 V 255 V

Max. discharge current (8/20 µs) [L-N] Imax 65 kA 65 kA

Max. discharge current (8/20 µs) [N-PE] 65 kA 65 kA

Lightning impulse current (10/350 µs) [N-PE] 12 kA 12 kA

Voltage protection level [L-N] 1.25 kV 1.75 kV

Voltage protection level [L-N] at 5 kA 1 kV 1.35 kV

Voltage protection level [N-PE] 1.5 kV 1.5 kV

Follow current extinguishing capability [N-PE] 100 Arms 100 Arms

Response time [L-N] 25 ns 25 ns

Response time [N-PE]

100 ns

100 nsMax. mains-side overcurrent protection 160 A gL/gG 160 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms 20 kArms

TOV characteristics withstand withstand

Temporary overvoltage (TOV) [L-N] 335 V / 5 sec. 385 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] 1200 V / 200 ms 1200 V / 200 ms

Operating temperature range -40°C...+55°C -40°C...+55°C

Indication of disconnector green-yellow-red green-yellow-red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 4 mods., DIN 43880 4 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG TT H230 400 LI DG TT H230 400 LI385

Part No. 950 150 950 151

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® ... H LI

900 216 T C H 255

TCH2 5 5900 216

N-PE spark-gap-based protection module

PU PartType pc(s). No.

T C H 255 1 900 216

950 130 T H 275 L I950 131 T H 385 L I

TH2 7 5 L I950 130TH3 8 5 L I950 131

Varistor-based protection module with Pro-ActiveThermo Control

PU PartType pc(s). No.

T H 275 LI 1 950 130

T H 385 LI 1 950 131

Accessory Part for DEHNguard® ... H LI

Page 105: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 105/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

103www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® ... H LI

DEHNguard T H LIDG T H

DG T H

121114

Basic circuit diagram DG T H ... LIDimension drawing DG T H ... LI

DG T H LI: Single-pole, pluggable surge arrester with ”Pro-Active Thermo Control” SPD monitor-ing device with 3-stage visual indicator

DG T H 275 LI DG T H 385 LI

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class IINominal a.c. voltage 230 V 230 V

Max. continuous operating a.c. voltage UC 275 V 385 V

Nominal discharge current (8/20 µs) In 20 kA 20 kA

Max. discharge current (8/20 µs) Imax 65 kA 65 kA

Voltage protection level UP 1.25 kV 1.75 kV

Voltage protection level at 5 kA UP 1 kV 1.35 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection 160 A gL/gG 160 A gL/gG

Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms 20 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec. 385 V / 5 sec.

TOV characteristics withstand withstand

Operating temperature range -40°C...+55°C -40°C...+55°CIndication of disconnector green-yellow-red green-yellow-red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 1 mods., DIN 43880 1 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG T H 275 LI DG T H 385 LI

Part No. 950 120 950 121

Packing unit 1 pc(s). 1 pc(s).

950 130 T H 275 LI950 131 T H 385 LI

TH2 7 5 L I950 130TH3 8 5 L I950 131

Varistor-based protection module with Pro-ActiveThermo Control

PU PartType pc(s). No.

T H 275 LI 1 950 130

T H 385 LI 1 950 131

Accessory Part for DEHNguard® ... H LI

Page 106: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 106/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

104 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® M YPV SCI ... (FM)

Multipole arrester for use in photovoltaic systemswith three-step d.c. switching device SPD Type 2 classification according to EN 61643-11

SPD Class II classification according to IEC 61643-1

• Prewired modular complete unit for use in pho-tovoltaic systems consisting of a base part andplug-in protection modules

• Combined disconnection and short-circuitingdevice with safe electrical isolation in the pro-tection module prevents fire damage due tod.c. arcs

• Approved fault-resistant Y circuit preventsdamage to the surge protective devices in caseof insulation faults in the generator circuit

• Safe replacement of protection modules with-out arc formation due to integrated d.c. fuse

• Suitable for all PV systems in accordance withIEC 60364-7-712

DEHNguard M YPV SCI 600: Multipole, modular surge arrester with three-step d.c. switching device; for use in photo-voltaic systems up to 600 V

DEHNguard M YPV SCI 1000: For photovoltaic systems up to 1000 V

DEHNguard M YPV SCI 1200: For photovoltaic systems up to 1200 V

DEHNguard M YPV SCI ... FM: With remote signalling contact for a monitoring device (floating changeover contact)

For protecting low-voltage consumer’s installations against surges. Foruse in accordance with IEC 60364-7-712:2002-05 (installation of photo-voltaic power supply systems)

The modular surge arresters of type DEHNguard M YPV SCI ... (FM) werespecifically designed for protecting equipment in photovoltaic systems.The innovative three-step d.c. switching device makes these arrestersespecially safe so that they fulfil the requirements for modern photovolta-ic systems.The application features of the modular Red/Line family design are simi-larly unique as the three-step d.c. switching device. The module lockingsystem firmly fixes the protection modules in the base part of the arrester.Neither shock nor vibration nor the enormous forces of discharge affectthe safe connection to the protection module. Nevertheless, the protec-tion modules can be easily replaced without tools by simply pressing theuser-friendly module release button of the protection modules. Every pro-

tective circuit of the DEHNguard M YPV SCI ... (FM) and every protectionmodule is mechanically coded to avoid incorrect insertion by the installeror user.To fulfil the specific requirements for photovoltaic systems, the approvedsafety philosophies of the fault-resistant Y circuit consisting of three pro-tective circuits of the varistor and the combined disconnection and short-circuiting device were integrated in a single device.This synergy reduces the probability of an arrester failure in case of oper-ating and fault states which have to be considered in photovoltaic sys-tems.This ensures that the arrester is protected in case of overload with-out presenting a fire risk to the system. Even in case of voltages up to1200 V d.c. an arc, which is likely to occur in the surge protective deviceif a conventional disconnection device is activated, is extinguished imme-

diately and without risk. Fire protection is the top priority of theDEHNguard M YPV SCI ... (FM) arrester. A fuse particularly developed for

photovoltaic systems was integrated into the short-circuit path to ensuresafe electrical isolation in case of a faulty surge protection module, allow-ing de-energised replacement of the protection module without arc for-mation in case of a faulty surge protection module. This unique designcombines surge protection, fire protection and the protection of persons.DEHNguard M YPV SCI ... (FM) can be used in all low-, medium- and high-performance photovoltaic systems without backup fuse due to this inno-vative and unique design.

The green and red indicator flags show if every protective circuit is readyfor operation. Apart from this standard visual indication, DEHNguard MYPV SCI ... (FM) arresters also feature a three-pole terminal for remote

signalling. With their floating changeover contact, the remote signal canbe used as make or break contact according to the particular circuit con-cept. Like all surge arresters of the modular DEHNguard M family,DEHNguard M YPV SCI ... (FM) arresters incorporate multifunctional ter-minals on a standardised spacing of 1 module for connecting conductorsand busbars, allowing easy wiring with other DIN rail mounted devices.

SCI SCI SCI SCI

Switching stages:

1. 2. 3. Original state Response of the Arc extinction Safe electrical disconnection device isolation

Page 107: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 107/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

105www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® M YPV SCI ... (FM)

DEHNguard M YPV SCI ...DG M YPV SCI 600DG M YPV SCI 1000DG M YPV SCI 1200

DC+/– 9 DC–/+

Basic circuit diagram DG M YPV SCI ...

DC+/– DC–/+9

Dimension drawing DG M YPV SCI ...

DG M YPV SCI ...: Multipole, modular surge arrester with three-step d.c. switching device for usein PV systems.

DG M YPV SCI 600 DG M YPV SCI 1000 DG M YPV SCI 1200

SPD classification according to EN 61643-11 Type 2 Type 2 Type 2

SPD classification according to IEC 61643-1 Class II Class II Class II

Max. PV voltage UCPV 600 V 1000 V 1200 V

Max. continuous operating d.c. voltage [(DC+/DC-) —> PE] UC 300 V 500 V 600 V

Total discharge current (8/20 µs) Itotal 40 kA 40 kA 30 kA

Nominal discharge current (8/20 µs) [(DC+/DC-) —> PE] I n 12.5 kA 12.5 kA 12.5 kA

Max. discharge current (8/20 µs) [(DC+/DC-) —> PE] Imax 25 kA 25 kA 25 kA

Voltage protection level UP 2.5 kV 4 kV 4.5 kV

Voltage protection level at 5 kA UP 2 kV 3.5 kV 4 kV

Response time tA 25 ns 25 ns 25 ns

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Breaking capacity of the integrated fuse 30 kA / 1000 V d.c. 30 kA / 1000 V d.c. 30 kA / 1200 V d.c.

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 3 mod(s)., DIN 43880 3 mod(s)., DIN 43880 3 mod(s)., DIN 43880

Approvals, Certifications UL UL —

Ordering information

Type DG M YPV SCI 600 DG M YPV SCI 1000 DG M YPV SCI 1200

Part No. 952 511 952 510 952 512

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

N E W

Accessory Part for DEHNguard® M YPV SCI ... (FM)

952 010 DG MOD275952 015 DG MOD440952 016 DG MOD600

DGMOD275952 010DGMOD440952 015DGMOD600952 016

Varistor-based protection modulePU Part

Type pc(s). No.

DG MOD 275 1 952 010

DG MOD 440 1 952 015

DG MOD 600 1 952 016

Accessory Part for DEHNguard® M YPV SCI ... (FM)

952 053 DG MODPVSCI300952 051 DG MODPVSCI500952 054 DG MODPVSCI600

DG M O DP VSCI 3 0 0952 053DG M O DP VSCI 5 0 0952 051DG M O DP VSCI 6 0 0952 054

Varistor-based protection module for M YPV SCI

DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ...comprising a varistor connected in parallel with a short-circuitingdevice with integrated back-up fuse

PU PartType pc(s). No.

DG MOD PV SCI 300 1 952 053

DG MOD PV SCI 500 1 952 051DG MOD PV SCI 600 1 952 054

Page 108: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 108/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

106 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® M YPV SCI ... (FM)

DEHNguard M YPV SCI ... FM952 516 DG M YPV SCI 600 FM952 515 DG M YPV SCI 1000 FM952 517 DG M YPV SCI 1200 FM

DG M Y P VSCI 6 0 0 FM952 516DG M Y P VSCI 1 0 0 0 FM952 515DG M Y P VSCI 1 2 0 0 FM952 517

1211

14

DC+/– 9 DC–/+

Basic circuit diagram DG M YPV SCI ... FM

DC+/– DC–/+9

Dimension drawing DG M YPV SCI ... FM

DG M YPV SCI ... FM: Multipole, modular surge arrester with three-step d.c. switching device foruse in PV systems with remote signalling contact (floating changeovercontact).

DG M YPV SCI 600 FM DG M YPV SCI 1000 FM DG M YPV SCI 1200 FM

SPD classification according to EN 61643-11 Type 2 Type 2 Type 2

SPD classification according to IEC 61643-1 Class II Class II Class II

Max. PV voltage UCPV 600 V 1000 V 1200 V

Max. continuous operating d.c. voltage [(DC+/DC-) —> PE] UC 300 V 500 V 600 V

Total discharge current (8/20 µs) Itotal 40 kA 40 kA 30 kA

Nominal discharge current (8/20 µs) [(DC+/DC-) —> PE] In 12.5 kA 12.5 kA 12.5 kA

Max. discharge current (8/20 µs) [(DC+/DC-) —> PE] Imax 25 kA 25 kA 25 kA

Voltage protection level UP 2.5 kV 4 kV 4.5 kV

Voltage protection level at 5 kA UP 2 kV 3.5 kV 4 kV

Response time tA 25 ns 25 ns 25 ns

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Breaking capacity of the integrated fuse 30 kA / 1000 V d.c. 30 kA / 1000 V d.c. 30 kA / 1200 V d.c.

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 3 mod(s)., DIN 43880 3 mod(s)., DIN 43880 3 mod(s)., DIN 43880

Approvals, Certifications UL UL —

Type of remote signalling contact changeover contact changeover contact changeover contact

a.c. switching capacity 250 V/0.1 A 250 V/0.1 A 250 V/0.1 A

d.c. switching capacity 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG M YPV SCI 600 FM DG M YPV SCI 1000 FM DG M YPV SCI 1200 FM

Part No. 952 516 952 515 952 517

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

N E W

Accessory Part for DEHNguard® M YPV SCI ... (FM)

952 010 DG MOD275952 015 DG MOD440952 016 DG MOD600

DGMOD275952 010DGMOD440952 015DGMOD600952 016

Varistor-based protection modulePU Part

Type pc(s). No.

DG MOD 275 1 952 010

DG MOD 440 1 952 015DG MOD 600 1 952 016

Accessory Part for DEHNguard® M YPV SCI ... (FM)

952 053 DG MODPVSCI300952 051 DG MODPVSCI500952 054 DG MODPVSCI600

DG M O DP VSCI 3 0 0952 053DG M O DP VSCI 5 0 0952 051DG M O DP VSCI 6 0 0952 054

Varistor-based protection module for M YPV SCI

DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ...comprising a varistor connected in parallel with a short-circuitingdevice with integrated back-up fuse

PU PartType pc(s). No.

DG MOD PV SCI 300 1 952 053

DG MOD PV SCI 500 1 952 051

DG MOD PV SCI 600 1 952 054

Page 109: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 109/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

107www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® PV ... SCP (FM)

Single-pole arrester for use in

photovoltaic systems with short-circuiting deviceSPD Type 2 classification according to EN 61643-11SPD Class II classification according to IEC 61643-1

• For use in all types of PV systems in accordancewith IEC 60364-7-712

• High discharge capacity due to heavy-duty zincoxide varistor

• No fire risk in case of overload due to com-bined disconnection and short-circuiting device

• Continuous current carrying capacity of theshort-circuiting device of 80 A d.c.

• Indication of overload by red flag in the inspec-tion window and remote signalling function

DG PV ... SCP: Single-pole surge arrester with combined disconnection and short-circuiting device for use in photovoltaicgenerator circuits

DG PV ... SCP FM: With remote signalling contact for the monitoring device (floating changeover contact)

For protecting photovoltaic installations against surges. For use in accor-dance with IEC 60364-7-712:2002-05 (Installation of photovoltaic powersupply systems).

Single-pole surge arresters of type DEHNguard PV ... SCP (FM) are specif-ically designed for use in photovoltaic power supply systems.

Even the external design of the surge arresters (width of 2 modules) iscompletely adapted to the safety requirements of modern photovoltaicsystems with their high system voltages.

The approved dual ”Thermo Dynamic Control” monitoring and disconnec-tion device of the DEHNguard PV ... SCP (FM) Type 2 surge arresters wascombined with an additional short-circuiting device. This two-step d.c.switching device ensures safe operation, even in case of overloadeddevices, e.g. due to an insulation fault in the photovoltaic generator cir-

cuit, without presenting a fire risk to the installation. The combined dis-connection and short-circuiting device is capable of conducting the indi-cated short-circuit current independently until the PV installation is main-tained.

Apart from the standard green and red indi-cation, DEHNguard PV ... SCP FM devices fea-ture a three-pole remote signalling terminal.With their floating changeover contact, theremote signal can be used as a break or makecontact according to the particular circuitconcept.

SCP SCP SCP

Switching stages:

1. 2. Original state Response of the Arc extinction disconnection device

Page 110: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 110/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

108 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® PV ... SCP (FM)

DEHNguard PV ... SCP950 500 DG PV 500 SCP950 501 DG PV 700 SCP950 502 DG PV 1200 SCP

DG P V5 0 0 SCP950 500DG P V7 0 0 SCP950 501DG P V1 2 0 0 SCP950 502

Basic circuit diagram DG PV ... SCP Dimension drawing DG PV ... SCP

DG PV ... SCP: Single-pole surge arrester with combined disconnection and short-circuiting devicefor use in photovoltaic generator circuits

DG PV 500 SCP DG PV 700 SCP DG PV 1200 SCP

SPD classification according to EN 61643-11 Type 2 Type 2 Type 2

SPD classification according to IEC 61643-1 Class II Class II Class II

PV voltage of earth-free PV systems (2 x DG PV ...) UCPV 1000 V 1400 V 1400 V

PV voltage of functionally earthed PV systems (thin film) UCPV 500 V 700 V 1200 V

Max. continuous operating d.c. voltage UC 500 V 700 V 1200 V

Nominal discharge current (8/20 µs) In 20 kA 15 kA 15 kA

Max. discharge current (8/20 µs) Imax 30 kA 30 kA 30 kA

Voltage protection level for In UP 2 kV 2.5 kV 4.2 kV

Voltage protection level at 5 kA UP 1.7 kV 2 kV 3.5 kV

Response time tA 25 ns 25 ns 25 ns

Permanent short-circuit withstand capability IK 80 A d.c. 80 A d.c. 80 A d.c.

Reverse current withstand capability Ipmax 50 kA / 5 ms 50 kA / 5 ms 50 kA / 5 ms

Max. protection of the main d.c. line at the inverter 315 A gR 315 A gR 315 A gR

Operating temperature range TU -40°C...+65°C -40°C...+65°C -40°C...+65°C

Operating state/fault indication green / red green / red green/red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. t o EN 60715 35 mm DIN rail acc. t o EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880

Ordering information

Type DG PV 500 SCP DG PV 700 SCP DG PV 1200 SCP

Part No. 950 500 950 501 950 502Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Page 111: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 111/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

109www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® PV ... SCP (FM)

DEHNguard PV ... SCP FMDG PV 500 SCP FMDG PV 700 SCP FMDG PV 1200 SCP FM

121114

Basic circuit diagram DG PV ... SCP FMDimension drawing DG PV ... SCP FM

DG PV ... SCP FM: Single-pole surge arrester with combined disconnection and short-circuitingdevice for use in photovoltaic generator circuits; with floating remote sig-nalling contact

DG PV 500 SCP FM DG PV 700 SCP FM DG PV 1200 SCP FM

SPD classification according to EN 61643-11 Type 2 Type 2 Type 2

SPD classification according to IEC 61643-1 Class II Class II Class II

PV voltage of earth-free PV systems (2 x DG PV ...) UCPV 1000 V 1400 V 1400 V

PV voltage of functionally earthed PV systems (thin film) U CPV 500 V 700 V 1200 V

Max. continuous operating d.c. voltage UC 500 V 700 V 1200 V

Nominal discharge current (8/20 µs) In 20 kA 15 kA 15 kA

Max. discharge current (8/20 µs) Imax 30 kA 30 kA 30 kA

Voltage protection level for In UP 2 kV 2.5 kV 4.2 kV

Voltage protection level at 5 kA UP 1.7 kV 2 kV 3.5 kV

Response time tA 25 ns 25 ns 25 ns

Permanent short-circuit withstand capability IK 80 A d.c. 80 A d.c. 80 A d.c.

Reverse current withstand capability Ipmax 50 kA / 5 ms 50 kA / 5 ms 50 kA / 5 ms

Max. protection of the main d.c. line at the inverter 315 A gR 315 A gR 315 A gR

Operating temperature range TU -40°C...+65°C -40°C...+65°C -40°C...+65°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. t o EN 60715 35 mm DIN rail acc. t o EN 60715 35 mm DIN rail acc. t o EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880 2 mods., DIN 43880

Type of remote signalling contact changeover contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG PV 500 SCP FM DG PV 700 SCP FM DG PV 1200 SCP FM

Part No. 950 505 950 506 950 507

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Page 112: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 112/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

110 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard® 1000 (FM)

Single-pole, compact surge arresterSPD Type 2 according to EN 61643-11SPD Class II according to IEC 61643-1

• High discharge capacity due to heavy-duty zincoxide varistor

• Quick response• High reliability due to ”Thermo Dynamic

Control” disconnector

• Fault indication by red indicator flag in theinspection window

• Specifically designed for high system voltages

DEHNguard 1000: Single-pole, compact surge arrester with a rated voltage UC = 1000 V a.c.

DEHNguard ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

For protecting low voltage consumer´s installations against surges. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 0B – 1 and higher.

The compact and powerful DEHNguard ... 1000 (FM) surge arresters aredesigned for rated voltages of 1000 V. These single-pole devices can beused for a wide range of applications.

It is not only the flexibility that characterises the DEHNguard family, butespecially the striking performance parameters, setting trends worldwide:High discharge capacity, low voltage protection level and dual ”ThermoDynamic Control” monitoring and disconnection device stand for maxi-mum reliability.

Especially the DEHN-specific ”Thermo Dynamic Control” disconnectorensures that the arresters change to a safe isolated operating state evenin case of extreme overload. Apart from the surface temperature of theheavy-duty varistor, also the intensity of the discharge current is evaluat-ed.

Also the external design of the device is completely adapted to the fieldof application. DEHNguard 1000 (FM), with a width of 2 modules, entire-ly fulfils all mechanical requirements resulting from the high system volt-ages.

Apart from the standard green and red indication, DEHNguard ... FM fea-

tures a three-pole terminal for remote signalling. With its floatingchangeover contact, the remote signal can be used as a break or makecontact according to the particular circuit concept.

For earth-sided installation of DEHNguard (FM) devices, earthing bracketsof type EB DG 1000 1 3 and EB 1 4 9 can be used.

Page 113: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 113/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

111www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard® 1000 (FM)

DEHNguard 1000 (FM)DG 1000DG 1000 FM

DEHNguard, 1000 V

DEHNguard FM, 1000 V

121114

Basic circuit diagram DG 1000 FMDimension drawing DG 1000 FM

DG 1000 (FM): Single-pole, compact surge arrester with a rated voltage UC = 1000 V a.c.; FM ver-sion with floating remote signalling contact

DG 1000 DG 1000 FM

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II

Max. continuous operating a.c. voltage UC 1000 V 1000 V

Max. continuous operating d.c. voltage UC 1000 V 1000 V

Nominal discharge current (8/20 µs) In 15 kA 15 kA

Max. discharge current (8/20 µs) Imax 30 kA 30 kA

Voltage protection level Up 4.2 kV 4.2 kV

Voltage protection level at 5 kA UP 3.5 kV 3.5 kV

Response time tA 25 ns 25 ns

Max. overcurrent protection 100 A aM 100 A aM

Max. overcurrent protection for U 690 V a.c. 125 A gL/gG 125 A gL/gG

Short-circuit withstand capability for max. backup fuse 25 kArms 25 kArms

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DG 1000 DG 1000 FM

Part No. 950 102 950 112

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNguard® 1000 (FM)

900 411 EB DG1000 1 3

E B DG 1 0 0 0 1 3900 411

Accessory Part for DEHNguard® 1000 (FM)

900 417 EB 1 4 9

E B 1 4 9900 417

EB DG, 3-pole, single-phase

Earthing clip for earth-side jumpering of 3 DEHNguard 1000 (FM) surgearresters

PU PartType Dimension Terminal pc(s). No.

EB DG 1000 1 3 34 x 112 x 3 mm up to 25 mm2

1 900 411

Earthing Clip, 4-pole, single-phase

Earthing clip for earth-side jumpering of 4 DEHNguard 1000 (FM) surgearresters

PU PartType Dimension Terminal pc(s). No.

EB 1 4 9 34 x 148 x 3 mm up to 25 mm2

1 900 417

Page 114: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 114/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

112 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard S® ... VA (FM)

Single-pole, pluggable varistor- andspark-gap-based arrester SPD Type 2 according to EN 61643-11

SPD Class II according to IEC 61643-1

• All-purpose surge arrester consisting of a basepart and plug-in protection module

• Leakage-current-free series connection of avaristor and a spark gap in the pluggable pro-tection module

• High reliability due to ”Thermo DynamicControl” SPD monitoring device

• Energy coordination within the Red/Line pro-duct family

• Easy replacement of protection modules with-out tools due to module locking system withmodule release button

• Narrow (modular) design in accordance withDIN 43880

• Multifunctional terminal for connecting con-ductors and busbars

DEHNguard S ... VA: Modular, single-pole surge arrester with a varistor and a spark gap connected in series in the plug-

gable protection moduleDEHNguard S ... VA FM: With remote signalling contact for the monitoring device (floating changeover contact)

The single-pole DEHNguard S ... VA surge arresters complement the triedand tested DEHNguard product families. The special series connection of a spark gap and a varistor module in the protection module opens up newfields of application. It is advisable to use DEHNguard S ...VA devices e.g.in systems with permanent insulation monitoring and in e.g. railroad sys-tems for protecting the power supply of signal lines which have to be freeof leakage currents. DEHNguard S ... VA arresters are also suited for pro-

tecting power line communication applications.

The multifunctional terminals allow almost unlimited flexibility in terms of connection among one another, but also with other DIN rail mounteddevices in a distribution board. The DEHNguard S ... VA line is not onlycharacterised by flexibility. It are rather the distinctive performanceparameters which set standards worldwide:A high discharge capacity, complete absence of leakage currents, a lowvoltage protection level and the dual Thermo Dynamic Control monitoringand disconnection device describe the high degree of reliability.

Particularly the DEHN-specific Thermo Dynamic Control disconnectiondevice ensures that the arresters enter a safe, isolated state even in caseof extreme overload. For this purpose, the intensity of the discharge cur-rent is evaluated together with the surface temperature of the heavy-dutyvaristor. In addition to the standard red and green indicator, theDEHNguard S VA ... FM devices feature a three-pole remote signalling ter-minal. With their floating changeover contact, the remote signal can be

used as break or make contact according to the particular protection con-cept.

For protecting low-voltage consumer’s installations against overvoltage.For installation in conformity with the lightning protection zones conceptat the boundaries from 0B – 1 and higher.

Page 115: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 115/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

113www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

DEHNguard S® ... VA (FM)

DEHNguard S VADG S 75 VADG S 275 VADG S 385 VA

Basic circuit diagram DG S ... VADimension drawing DG S ...VA

DG S ... VA: Modular, single-pole surge arrester comprising a varistor and a spark gap connectedin series in the pluggable protection module

DG S 75 VA DG S 275 VA DG S 385 VA

SPD according to EN 61643-11 Type 2 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II Class II

Max. continuous operating a.c. voltage UC 75 V 275 V 385 V

Max. continuous operating d.c. voltage UC 100 V 350 V 500 V

Nominal discharge current (8/20 µs) In 10 kA 10 kA 10 kA

Max. discharge current (8/20 µs) Imax 20 kA 20 kA 20 kA

Voltage protection level UP 1.1 kV 1.5 kV 1.75 kV

Response time tA 100 ns 100 ns 100 ns

Max. supply side overcurrent protection 100 A gL/gG 100 A gL/gG 100 A gL/gG

Short-circuit withstand capability for

max. supply side overcurrent protection 25 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 75 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.

TOV characteristics withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880

Ordering information

Type DG S 75 VA DG S 275 VA DG S 385 VA

Part No. 952 080 952 082 952 084Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

N E W

N E W

Accessory Part for DEHNguard S® ... VA (FM)

952 025 DG MOD75 VA952 027 DG MOD275 VA952 029 DG MOD385 VA

DG M O D7 5 VA952 025DG M O D2 7 5 VA952 027DG M O D3 8 5 VA952 029

Varistor-and spark-gap-based protection modulefor DEHNguard S ... VA

DG MOD ... VA: Protection module for DEHNguard S ... VA comprising avaristor connected in series with a spark gap

PU PartType pc(s). No.

DG MOD 75 VA 1 952 025

DG MOD 275 VA 1 952 027

DG MOD 385 VA 1 952 029

Page 116: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 116/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

114 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

DEHNguard S® ... VA (FM)

DEHNguard S VA FM952 085 DG S 75 VA FM952 087 DG S 275 VA FM952 089 DG S 385 VA FM

DG S7 5 VAFM952 085DG S2 7 5 VAFM952 087DG S3 8 5 VAFM952 089

121114

Basic circuit diagram DG S ... VA FM Dimension drawing DG S ... VA FM

DG S ... VA FM: Modular, single-pole surge arrester with a varistor and a spark gap connected inseries in the pluggable protection module; with floating remote signalling contact

DG S 75 VA FM DG S 275 VA FM DG S 385 VA FM

SPD according to EN 61643-11 Type 2 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class II Class II

Max. continuous operating a.c. voltage UC 75 V 275 V 385 V

Max. continuous operating d.c. voltage UC 100 V 350 V 500 V

Nominal discharge current (8/20 µs) In 10 kA 10 kA 10 kA

Max. discharge current (8/20 µs) Imax 20 kA 20 kA 20 kA

Voltage protection level UP 1.1 kV 1.5 kV 1.75 kV

Response time tA 100 ns 100 ns 100 ns

Max. supply side overcurrent protection 100 A gL/gG 100 A gL/gG 100 A gL/gG

Short-circuit withstand capability for

max. supply side overcurrent protection 25 kArms 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 75 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.

TOV characteristics withstand withstand withstand

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red

Cross-sectional area (min.) 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible 1.5 mm2 solid/flexible

Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20

Capacity 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880

Type of remote signalling contact changeover contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible max. 1.5 mm2 solid/flexible

Ordering information

Type DG S 75 VA FM DG S 275 VA FM DG S 385 VA FM

Part No. 952 085 952 087 952 089

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

N E W

Accessory Part for DEHNguard S® ... VA (FM)

952 025 DG MOD75 VA952 027 DG MOD275 VA952 029 DG MOD385 VA

DG M O D7 5 VA952 025DG M O D2 7 5 VA952 027DG M O D3 8 5 VA952 029

Varistor-and spark-gap-based protection modulefor DEHNguard S ... VA

DG MOD ... VA: Protection module for DEHNguard S ... VA comprising avaristor connected in series with a spark gap

PU PartType pc(s). No.

DG MOD 75 VA 1 952 025

DG MOD 275 VA 1 952 027

DG MOD 385 VA 1 952 029

N E W

Page 117: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 117/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

115www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

V NH / VA NH

NH Surge arrestersSPD Type 2 according to EN 61643-11SPD Class II according to IEC 61643-1

• Surge arrester for use in size 00 and 1 NH fuseholders

• Zinc oxide varistor with monitoring device, dis-connector and integrated backup fuse (VA NHwith additional spark gap connected in series)

• Energy coordination within the Red/Line prod-uct family

• Fault indication by tripping indicator

V(A) NH00 280: Surge arrester for use in size 00 NH fuse holders

V(A) NH1 280: Surge arrester for use in size 1 NH fuse holders

V(A) NH00 280 FM: With fault indicator for remote signalling; allows for use of NH fuse holders with microswitch (tripping

distance of fault indicator max. 7 mm)

For protecting low voltage consumer´s installations against surges. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 0B – 1 and higher. German patented design.

The single-pole V NH and VA NH surge arresters show that surge protec-tive devices do not necessarily have to be designed exclusively for DINrails or socket outlets. Being adapted to the conditions in industrial sub-circuit distribution boards, V NH and VA NH devices are designed in theform of an NH fuse holder.This allows for easy integration into busbar sys-tems, as often applied in zones belonging to the operators of power sup-ply systems or in industrial installations. Thus, the advantages of busbarsystems such as easy installation, less installation time and reducedwiring also apply to surge protection. The idea of such a busbar system isconsistently continued with SPDs in NH design. V NH and VA NH surge

arresters can be installed and removed by means of a fuse switch discon-nector and a fuse handle.This makes it considerably easier to measure theisolation of the installation as the SPD does not have to be disconnectedany more.

Another considerable advan-tage of the V NH / VA NH fam-ily is the already integratedbackup fuse. If SPDs areinstalled in an earth fault- andshort-circuit-proof way, thisconsiderably saves space andcosts in distribution boards. In

case of type VA NH,a spark gap was connected in series to the heavy-dutyzinc oxide varistor with thermal monitoring and disconnection device of the V NH devices. VA NH devices provide reliable protection especially forlarge-scale systems with permanent isolation control. Apart from thestandard visual indication by a fault indicator, V(A) NH ... FM devices pro-vide a microswitch integrated into the NH fuse holder for remote sig-nalling.

S u r

g e A r r e s t e r s T y p e 2

Page 118: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 118/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

116 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

V NH / VA NH

V NH00 (FM)900 261 V NH00280900 263 V NH00280FM

V NH00 280 VNHSurge Ar reste r, Size 00 900 261V NH00 280 FM VNH FMSurge Ar reste r, Size 00 900 263

Basic circuit diagram V NH00 (FM), V NH1 Dimension drawingV NH00 (FM)

V NH00 (FM): Surge arrester for use in size 00 NH fuse holders; optionally available with indicatorfor remote signalling

V NH00 280 V NH00 280 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II

Max. continuous operating a.c. voltage UC 280 V 280 V

Nominal discharge current (8/20 µs) In 15 kA 15 kA

Max. discharge current (8/20 µs) Imax 30 kA 30 kA

Voltage protection level UP 1.25 kV 1.25 kV

Voltage protection level at 5 kA UP 1 kV 1 kV

Response time tA 25 ns 25 ns

Max. mains-side overcurrent protection not required not required

Short-circuit withstand capability 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Indication of the disconnector red fault indicator red fault indicator (tripping distance 7 mm)

Operating temperature range TU -40°C...+80°C -40°C...+80°CFor mounting on size 00 NH fuse holder size 00 NH fuse holder

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IPX4W —

Ordering information

Type V NH00 280 V NH00 280 FM

Part No. 900 261 900 263

Packing unit 1 pc(s). 1 pc(s).

900 270 V NH1280

V NH1 280 VNHSurge Arrester, Size 1 900 270

Dimension drawingV NH1

V NH1: Surge arrester for use in size 1 NH fuse holders

V NH1 280

SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II

Max. continuous operating a.c. voltage UC 280 V

Nominal discharge current (8/20 µs) In 15 kA

Max. discharge current (8/20 µs) Imax 30 kA

Voltage protection level UP 1.25 kV

Voltage protection level at 5 kA UP 1 kV

Response time tA 25 ns

Max. mains-side overcurrent protection not required

Short-circuit withstand capability 25 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec.

TOV characteristics withstand

Indication of the disconnector red fault indicator

Operating temperature range TU -40°C...+80°C

For mounting on size 1 NH fuse holder

Enclosure material thermoplastic, red, UL 94 V-0Degree of protection IPX4W

Ordering information

Type V NH1 280

Part No. 900 270

Packing unit 1 pc(s).

Page 119: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 119/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

117www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

S u r

g e A r r e s t e r s T y p e 2

V NH / VA NH

VA NH00 (FM)VA NH00

VA NH00

VANH900 262VANH FM900 264

Basic circuit diagram VA NH00 (FM), V NH1Dimension drawingVA NH00 (FM)

VA NH00 FM: Surge arrester with a varistor and a spark gap connected in series; for use in size 00NH fuse holders, optionally available with indicator for remote signalling

VA NH00 280 VA NH00 280 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II Type 2 / Class II

Max. continuous operating a.c. voltage UC 280 V 280 V

Nominal discharge current (8/20 µs) In 10 kA 10 kA

Max. discharge current (8/20 µs) Imax 20 kA 20 kA

Voltage protection level UP 1.5 kV 1.5 kV

Response time tA 100 ns 100 ns

Max. mains-side overcurrent protection not required not required

Short-circuit withstand capability 25 kArms 25 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec. 335 V / 5 sec.

TOV characteristics withstand withstand

Indication of the disconnector red fault indicator red fault indicator (tripping distance 7 mm)

Operating temperature range TU -40°C...+80°C -40°C...+80°C

For mounting on size 00 NH fuse holder size 00 NH fuse holderEnclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IPX4W IPX4W

Ordering information

Type VA NH00 280 VA NH00 280 FM

Part No. 900 262 900 264

Packing unit 1 pc(s). 1 pc(s).

VA NH1

VANH900 271

Dimension drawingVA NH1

VA NH1: Surge arrester with a varistor and a spark gap connected in series; for use in size 1NH fuse holders

VA NH1 280

SPD according to EN 61643-11 / ... IEC 61643-1 Type 2 / Class II

Max. continuous operating a.c. voltage UC 280 V

Nominal discharge current (8/20 µs) In 10 kA

Max. discharge current (8/20 µs) Imax 20 kA

Voltage protection level UP 1.5 kV

Response time tA 100 ns

Max. mains-side overcurrent protection not required

Short-circuit withstand capability 25 kArms

Temporary overvoltage (TOV) UT 335 V / 5 sec.

TOV characteristics withstand

Indication of the disconnector red fault indicator

Operating temperature range TU -40°C...+80°C

For mounting on size 1 NH fuse holder

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IPX4W

Ordering information

Type VA NH1 280

Part No. 900 271

Packing unit 1 pc(s).

Page 120: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 120/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 2

118 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

www.dehn.de

Page 121: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 121/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

119www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

DEHNrail modular

Two-pole, pluggable surge arresterSPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

• Two-pole surge arrester consisting of a basepart and plug-in protection module

• High discharge capacity due to heavy-duty zincoxide varistor/spark gap combination

• Energy coordination within the Red/Line pro-duct family

• Operating state/fault indication by indicatorflag in the inspection window

• Narrow (modular) design according to DIN43880

• Easy replacement of protection modules due to

module locking system with module releasebutton

• Vibration- and shock-tested according to EN60068-2

DEHNrail M 2P ...: Two-pole surge arrester consisting of a base element and plug-in protection module

DEHNrail M 2P ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

For protection of the power supply circuit of industrial electronics equip-ment against transient surges in switchboards. For installation accordingto the lightning protection zones concept at the boundaries from 1 – 2and higher.

The modular devices of the DEHNrail M product family stand out due totheir high performance parameters and new straightforward Red/Linedesign. The devices combine safety and user-friendliness in a single mod-ule.The low voltage protection level and comprehensive common and dif-ferential mode protection are ideally suited for the protection of terminaldevices in industrial electronic environments. The design of the deviceswith input and output terminals for series connection and the protectivecircuit designed for high load currents underline this concept.

Compact in design, DEHNrail M surge arresters feature a distinctive Y pro-

tection circuit and a combined SPD monitoring device and disconnectionmechanism.

The base part and protection module are coded thus preventing incorrectinsertion by the installer or user.

The new module locking system of the DEHNrail M product family isunique for surge protective devices. It fixes the surge protection moduleand the base part of the SPD firmly in place. Neither vibration duringtransport nor the electromagnetic forces of discharge can loosen the con-nection.

If the protective circuit is overloaded despite of the powerful characteris-tics of the devices, the module release button allows quick replacementof the protection modules without tools.

In addition to the standard greenand red indication, DEHNrail M ...FM devices feature a three-poleterminal for remote signalling.Withtheir floating changeover contact,the remote signal can be used as abreak or make contact according tothe particular circuit concept.

Page 122: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 122/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

120 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

DEHNrail modular

DEHNrail M 2P ...953 201 DR M 2P30953 202 DR M 2P60953 203 DR M 2P75953 204 DR M 2P150953 200 DR M 2P255

DR M 2 P 3 0953 201DR M 2 P 6 0953 202DR M 2 P 7 5953 203DR M 2P150953 204DR M 2P255953 200

1

3

2

4

Basic circuit diagram DR M 2P ... Dimension drawing DR M 2P ...

DR M 2P ...: Two-pole surge arrester consisting of a base element and plug-in protection module

DR M 2P 30 DR M 2P 60 DR M 2P 75 DR M 2P 150 DR M 2P 255

SPD according to EN 61643-11 / ... IEC 61643-1 Type 3 / Class III Type 3 / Class III Type 3 / Class III Type 3 / Class III Type 3 / Class III

Nominal a.c. voltage UN 24 V 48 V 60 V 120 V 230 V

Max. continuous operating a.c. voltage UC 30 V 60 V 75 V 150 V 255 V

Max. continuous operating d.c. voltage UC 30 V 60 V 75 V 150 V 255 V

Nominal load current a.c. IL 25 A 25 A 25 A 25 A 25 A

Nominal discharge current (8/20 µs) In 1 kA 1 kA 2 kA 2 kA 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 2 kA 2 kA 4 kA 4 kA 5 kA

Combined impulse UOC 2 kV 2 kV 4 kV 4 kV 6 kV

Combined impulse [L+N-PE] UOC total 4 kV 4 kV 8 kV 8 kV 10 kV

Voltage protection level [L-N] UP 180 V 350 V 400 V 640 V 1250 V

Voltage protection level [L/N-PE] UP 630 V 730 V 730 V 800 V 1500 V

Response time [L-N] tA 25 ns 25 ns 25 ns 25 ns 25 ns

Response time [L/N-PE] tA 100 ns 100 ns 100 ns 100 ns 100 ns

Max. mains-side overcurrent protection 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A

Short-circuit withstand capability for

mains-side overcurrent protection with 25 A gL/gG 6 kArms 6 kArms 6 kArms 6 kArms 6 kArms

Temporary overvoltage (TOV) [L-N] UT — — — — 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT — — — — 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT — — — — 1200 V + U0 / 200 ms

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red green / red green / red

Cross-sectional area (min.) 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible

Cross-sectional area (max.) 4 mm2 solid/2.5 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20 IP 20 IP 20

Capacity 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880Approvals, Certifications KEMA, VDE,UL, VdS, CSA

Ordering information

Type DR M 2P 30 DR M 2P 60 DR M 2P 75 DR M 2P 150 DR M 2P 255

Part No. 953 201 953 202 953 203 953 204 953 200

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNrail modular

Protection module for DEHNrail M 2P

DR MOD ...: Protection module with integrated Y protection circuit

PU Part

Type pc(s). No.DR MOD 30 1 953 011

DR MOD 60 1 953 012

DR MOD 75 1 953 013

DR MOD 150 1 953 014

DR MOD 255 1 953 010

953 011 DR MOD30953 012 DR MOD60953 013 DR MOD75953 014 DR MOD150953 010 DR MOD255

DR M O D3 0953 011DR M O D6 0953 012DR M O D7 5953 013DR M O D1 5 0953 014DR M O D2 5 5953 010

Page 123: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 123/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

121www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

DEHNrail modular

DEHNrail M 2P ... FMDR M 2P

DR M 2P

DR M 2P

DR M 2P

DR M 2P

1

3

2

4

121114

Basic circuit diagram DR M 2P ... FMDimension drawing DR M 2P ... FM

DR M 2P ... FM: Two-pole surge arrester consisting of a base element and plug-in protection mod-ule; with floating remote signalling contact

DR M 2P 30 FM DR M 2P 60 FM DR M 2P 75 FM DR M 2P 150 FM DR M 2P 255 FM

SPD according to EN 61643-11 / ... IEC 61643-1 Type 3 / Class III Type 3 / Class III Type 3 / Class III Type 3 / Class III Type 3 / Class III

Nominal a.c. voltage UN 24 V 48 V 60 V 120 V 230 V

Max. continuous operating a.c. voltage UC 30 V 60 V 75 V 150 V 255 V

Max. continuous operating d.c. voltage UC 30 V 60 V 75 V 150 V 255 V

Nominal load current a.c. IL 25 A 25 A 25 A 25 A 25 A

Nominal discharge current (8/20 µs) In 1 kA 1 kA 2 kA 2 kA 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 2 kA 2 kA 4 kA 4 kA 5 kA

Combined impulse UOC 2 kV 2 kV 4 kV 4 kV 6 kV

Combined impulse [L+N-PE] UOC total 4 kV 4 kV 8 kV 8 kV 10 kV

Voltage protection level [L-N] UP 180 V 350 V 400 V 640 V 1250 V

Voltage protection level [L/N-PE] UP 630 V 730 V 730 V 800 V 1500 V

Response time [L-N] tA 25 ns 25 ns 25 ns 25 ns 25 ns

Response time [L/N-PE] tA 100 ns 100 ns 100 ns 100 ns 100 ns

Max. mains-side overcurrent protection 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A 25 A gL/gG or B 25 A

Short-circuit withstand capability for

mains-side overcurrent protection with 25 A gL/gG 6 kArms 6 kArms 6 kArms 6 kArms 6 kArms

Temporary overvoltage (TOV) [L-N] UT — — — — 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT — — — — 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT — — — — 1200 V + U0 / 200 ms

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red green / red green / red green / red

Cross-sectional area (min.) 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible

Cross-sectional area (max.) 4 mm2 solid/2.5 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20 IP 20 IP 20 IP 20

Capacity 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880 1 mod., DIN 43880Approvals, Certifications KEMA,VDE, UL,VdS, CSA

Type of remote signalling contact changeover contact changeover contact changeover contact changeover contact changeover contact

Switching capacity a.c. 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Ordering information

Type DR M 2P 30 FM DR M 2P 60 FM DR M 2P 75 FM DR M 2P 150 FM DR M 2P 255 FM

Part No. 953 206 953 207 953 208 953 209 953 205

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

953 011 DR MOD30953 012 DR MOD60953 013 DR MOD75953 014 DR MOD150953 010 DR MOD255

DR MOD 30 ÜS-ModulDEHNrail, 2-polig, 30 V 953 011DR MOD 60 ÜS-ModulDEHNrail, 2-polig, 60 V 953 012DR MOD 75 ÜS-ModulDEHNrail, 2-polig, 75 V 953 013DR MOD 150 ÜS-ModulD EH Nr ai l, 2- po li g, 15 0 V 95 3 0 14DR MOD 255 ÜS-ModulD EH Nr ai l, 2- po li g, 25 5 V 95 3 0 10

Protection module for DEHNrail M 2P

DR MOD ...: Protection module with integrated Y protection circuit

PU PartType pc(s). No.

DR MOD 30 1 953 011

DR MOD 60 1 953 012

DR MOD 75 1 953 013

DR MOD 150 1 953 014

DR MOD 255 1 953 010

Page 124: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 124/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

122 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

DEHNrail modular, multipole

Four-pole, pluggable surge arresterSPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

• Four-pole surge arrester consisting of a baseelement and plug-in protection module

• High discharge capacity due to heavy-duty zincoxide varistor/spark gap combination

• Energy coordination within the Red/Line pro-duct family

• Operating state/fault indication by indicatorflag in the inspection window

• Easy replacement of protection modules with-out the use of tools due to module locking sys-tem with module release button

• Nominal load currents up to 25 A• Vibration- and shock-tested in accordance with

EN 60068-2

DEHNrail M 4P ...: Four-pole surge arrester consisting of a base element and plug-in protection module

DEHNrail M 4P ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

For protecting the power supply circuit of industrial electronics equipmentagainst transient surges in switchgear cabinets. For installation in con-formity with the lightning protection zones concept at the boundariesfrom 1 – 2 and higher.

The four-pole, modular DEHNrail M 4P ... (FM) surge arrester was specifi-cally developed for protecting three-phase industrial electronics terminalequipment. Adapted to this kind of environment, the SPD with the newRed/Line design is suitable for 35 mm DIN rails. The low voltage protec-tion level and the comprehensive common and differential mode protec-tion are characteristic of DEHNrail M 4P ... (FM). In order to provide opti-mal low voltage protection levels for the terminal equipment to be pro-tected, the device features input and output terminals for series connec-tion. DEHNrail M 4P ... (FM) devices ideally adapt to the cable runupstream of the terminal equipment therefore not requiring additionalterminal blocks for outgoing cables.The very compact design of DEHNrailM 4P ... (FM) already incorporates the tried and tested disconnector. It dis-connects an overloaded SPD circuit from the mains without interruptingthe supply circuit.

The base part and protection module of the device are coded thus pre-venting incorrect insertion by the installer or user.

The new module locking system of the DEHNrail M family is unique forsurge protective devices. It fixes the surge protection modules and thebase part of the SPD firmly in place. Neither vibrations during transportnor the electrodynamic forces of discharge can loosen the connection.

If the protective circuits, which are rated for high load currents up to25 A, are overloaded despite of the powerful characteristics of the device,the protection modules can be easily replaced without tools by simplypressing the module release button.

Apart from the standard green and red visual indication, DEHNrail M 4P

... FM devices feature a three-pole remote signalling terminal. With theirfloating changeover contact, the remote signal can be used as a break ormake contact according to the particular circuit concept.

Page 125: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 125/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

123www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

DEHNrail modular, multipole

DEHN rail M 4P ... (FM)DR M 4P

DR M 4P

L1 L1 L2 L2

N N

L3L3

121114

PE PE

Basic circuit diagram DR M 4P ... FMDimension drawing DR M 4P ... FM

DR M 4P ... (FM): Four-pole surge arrester consisting of a base element and plug-in protectionmodule; also available with floating remote signalling contact

DR M 4P 255 DR M 4P 255 FM

SPD according to EN 61643-11 Type 3 Type 3

SPD according to IEC 61643-1 Class III Class IIINominal a.c. voltage UN 230/400 V 230/400 V

Max. continuous operating a.c. voltage UC 255/440 V 255/440 V

Nominal load current a.c. IL 25 A 25 A

Nominal discharge current (8/20 µs) In 3 kA 3 kA

Total discharge current (8/20 µs) [L1+L2+L3+N-PE] Itotal 8 kA 8 kA

Combined impulse UOC 6 kV 6 kV

Combined impulse [L1+L2+L3+N-PE] UOC total 16 kV 16 kV

Voltage protection level [L-N] UP 1000 V 1000 V

Voltage protection level [L/N-PE] UP 1500 V 1500 V

Response time [L-N] tA 25 ns 25 ns

Response time [L/N-PE] tA 100 ns 100 ns

Max. mains-side overcurrent protection 25 A gL/gG or B 25 A 25 A gL/gG or B 25 AShort-circuit withstand capability for

mains-side overcurrent protection with 25 A gL/gG 6 kArms 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec.

Temporary overvoltage (TOV) [N-PE] UT 1200 V / 200 ms 1200 V / 200 ms

Operating temperature range TU -40°C...+80°C -40°C...+80°C

Operating state/fault indication green / red green / red

Cross-sectional area (min.) 0.5 mm2 solid/flexible 0.5 mm2 solid/flexible

Cross-sectional area (max.) 4 mm2 stranded/2.5 mm2 flexible 4 mm2 solid/2.5 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0

Degree of protection IP 20 IP 20

Capacity 2 mods., DIN 43880 2 mods., DIN 43880

Approvals, Certifications KEMA KEMA

Type of remote signalling contact — changeover contact

Switching capacity a.c. — 250 V/0.5 A

Switching capacity d.c. — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid/flexible

Ordering information

Type DR M 4P 255 DR M 4P 255 FM

Part No. 953 400 953 405

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNrail modular, multipole

953 020 DR MOD4P255

DRMOD4P255953 020

Protection module for DEHNrail M 4P

DR MOD 4P ...: 4-pole protection module with integrated protectivecircuit

PU PartType pc(s) No.

DR MOD 4P 255 1 953 020

Page 126: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 126/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

124 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

Protection Module for DEHNrail modular

Plug-in protection module for SPDs Type 3SPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

• The plug-in protection module can be replacedwithout the need to de-energise and withoutremoving the covering plate from the distribu-tion board

• Operating state and fault indication by indica-tor flag in the inspection window

• Easy replacement of the protection modulesdue to module locking system with modulerelease button

DEHNrail MOD ...: For all types of two-pole DEHNrail M2P ... surge arresters

DEHNrail MOD 4P...: For all types of four-pole DEHNrail M4P ... surge arresters

For protection of the power supply circuit of industrial electronics equip-ment against surges in switchboards. For installation in conformity withthe lightning protection zones concept at the boundaries from 1 – 2 andhigher.

Protection module for DEHNrail M 2P

953 011 DR MOD30953 012 DR MOD60953 013 DR MOD75953 014 DR MOD150953 010 DR MOD255

DR M O D3 0953 011DR M O D6 0953 012DR M O D7 5953 013DR M O D1 5 0953 014DR M O D2 5 5953 010

Basic circuit diagramDR MOD protection module

Dimension drawingDR MOD protection module

DR MOD ...: Protection module with integrated Y protection circuit

DR MOD 30 DR MOD 60 DR MOD 75 DR MOD 150 DR MOD 255

Nominal discharge current (8/20 µs) In 1 kA 1 kA 2 kA 2 kA 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 2 kA 2 kA 4 kA 4 kA 5 kA

Max. continuous operating a.c. / d.c. voltage UC 30 V 60 V 75 V 150 V 255 V

Ordering information

Type DR MOD 30 DR MOD 60 DR MOD 75 DR MOD 150 DR MOD 255

Part No. 953 011 953 012 953 013 953 014 953 010

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Protection module for DEHNrail M 4P

953 020 DR MOD4P255

DR M O D4 P 2 5 5953 020Basic circuit diagram

DR MOD 4P protection moduleDimension drawing

DR MOD 4P protection module

DR MOD 4P ...: Four-pole protection module with integrated protectivecircuit

DR MOD 4P 255

Nominal discharge current (8/20 µs) In 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 8 kA

Max. continuous operating a.c. / d.c. voltage UC 255 V

Ordering information

Type DR MOD 4P 255

Part No. 953 020

Packing unit 1 pc(s).

Page 127: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 127/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

125www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

• Protection of sensitive industrial electronicsequipment against balanced and unbalancedhigh-frequency interferences

• Completes surge protection,e.g. DEHNrail M 2P 255

• Easy installation on DIN rails in switchgears

Mains Filter

NF 10

The NF 10 mains filter is the ideal completion of surge protection for

industrial terminal equipment. Being a DIN rail mounted device, the mainsfilter is ideally suited for installation downstream of surge protectivedevices (e.g. DEHNrail M 2P 255). In addition to surge protection, thisensures protection against balanced and unbalanced high-frequency

interferences. The separate input and output terminals of the mains filter

ensure that an optimal protective effect of the device is provided for theequipment to be protected. This also allows to meet electromagnetic com-patibility requirements for constructing control systems and installationswhich do not relate to surge protection.

NF 10

Mains912 254

L1

N

PE

mains

L1

N

PE

SPD

Basic circuit diagram NF 10Dimension drawing NF 10

NF 10: Mains filter for protection against balanced and unbalanced interferences

NF 10

Nominal a.c. voltage UN 230 V

Nominal load current a.c. IL 10 A

Nominal frequency fN 50...60 Hz

Discharge current (for UN) 3.5 mAAttenuation for f = 1 MHz, balanced > 64 dB

Attenuation for f = 1 MHz, unbalanced > 69 dB

Total circuit capacitance [L-N] 660 nF

Total circuit capacitance [L (N)-PE] 66 nF

Total circuit inductance 1.8 mH per line

Backup fuse 10 A gL/gG

Operating temperature range -25°C...+40°C

Cross-sectional area min. 2.5 mm2 stranded, max. 4 mm2 flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material thermoplastic GF (polycarbonate)

Degree of protection IP 20

Dimension 110 x 45 x 75 mm

Ordering information

Type NF 10

Part No. 912 254

Packing unit 1 pc(s).

S u r g e A r r e s t e r s T y p e 3

Page 128: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 128/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

126 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

For protecting the power supply circuit of industrial electronics equipment(e.g. programmable logic controls/PLCs) against surges and high-frequen-cy interference voltages. For installation in conformity with the lightningprotection zones concept at the boundaries from 1 – 2 and higher.

• Combination of surge protection and filter

• Surge protection with monitoring device and

disconnector• Interference suppressor filter for protecting

sensitive industrial electronics equipmentagainst balanced and unbalanced high-frequen-cy interference

• Installed into a shielded enclosure

• Visual operating state indication (green) andfloating remote signalling contact (break con-tact) for fault indication

SPS Protector: Two-pole surge arrester with interference suppressor filter

SPS Protector

Two-pole surge arrester with filter

The SPS Protector combines surge protection and interference suppressorfilter in one compact device. This makes the device ideal for protectingsensitive terminal equipment in industrial automation systems (e.g. pro-grammable logic controls ”PLCs”). The coordinated surge protection andfilter functions complement one another and prevent core saturation of the filter in the event of high-energy transients. The separate input andoutput terminals ensure that an optimal protective effect is provided for

the device to be protected. The metal enclosure of the SPS Protectorensures that high-frequency interferences are discharged without interfer-ing with other devices close to the installation.The compact design of theSPS Protector already incorporates the approved disconnector. In case of overload, it disconnects the SPD from the mains without interrupting thesupply circuit. Apart from the green light, standard SPS Protector devicescan also be used for remote signalling.

SPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

Page 129: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 129/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

127www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

SPS Protector

SPS ProtectorSPS PRO

SPS-912 253

PE

N

L

PE

N'

L'

11 12FM

Basic circuit diagram SPS PRODimension drawing SPS PRO

SPS PRO: Surge arrester with interference suppressor filter

SPS PRO

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage UC 255 V

Nominal load current a.c. IL 3 A

Nominal discharge current (8/20 µs) In 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA

Combined impulse UOC 6 kV

Combined impulse [L+N-PE] UOC total 10 kV

Voltage protection level [L-N] UP 0.8 kV

Voltage protection level [L/N-PE] UP 1.0 kV

Response time [L-N] tA 25 ns

Response time [L/N-PE] tA 100 ns

Short-circuit withstand capability for max. mains-side overcurrent protection 6 kArms

Fault indication green light off

Operating state indication green light

Operating temperature range TU -10°C...+40°C

Cross-sectional area (min.) 0.14 mm2 solid/stranded/flexible

Cross-sectional area (max.) 2.5 mm2 solid/stranded/flexible

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material aluminium, red powder coating

Degree of protection IP 20

Capacity 7 mods., DIN 43880

Type of remote signalling contact break contact

Switching capacity a.c. 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible

Mains filter acc. to DIN VDE 0565 Part 3

Attenuation for f = 1 MHz, balanced 73 dB

Attenuation for f = 1 MHz, unbalanced 45 dB

Ordering information

Type SPS PRO

Part No. 912 253

Packing unit 1 pc(s).

Page 130: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 130/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

128 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

For protecting electronic devices against surges. For installation into elec-trical installation systems, e.g. cable ducts or flush-type boxes. For instal-lation in conformity with the lightning protection zones concept at theboundaries from 1 – 2 anf higher.

• Two-pole surge protective device for 230 V ter-minal devices

• For use in flush-type boxes and cable ducts• Enhanced safety due to distinctive Y protection

circuit

• Multiple visual operating state indication

• Programmable acoustic function

• Terminals for series connection

• Independent from the design of socket outlets

DEHNsafe 230 LA: Surge protective device for use in cable ducts

DEHNsafe

Surge arrester for use in cable ducts

The DEHNsafe surge arrester particularly stands out due to its flexibleapplication options. DEHNsafe is a two-pole surge protective device for230 V terminal equipment which can be installed into cable ducts, butalso into flat flush-type boxes due to the minimal installation depth of only 31 mm. DEHNsafe incorporates a monitoring device and a thermaldisconnector. In addition to a visual operating state indication, the devicefeatures a programmable acoustic fault indication. With such an acousticsignal, the fault indication can be programmed for three different operat-ing states:

– Acoustic fault indication,

– Test function,

– Muting of the acoustic signal.

A triple TAE cover plate of any switch pro-gramme manufacturer can be used for coveringit. Thus, DEHNsafe adapts ideally to any socketoutlet design.The two available terminals for L, N and PE allowfor series connection to ensure that the surgeprotection is situated in parallel to the circuit tobe protected. If DEHNsafe surge arresters are

overloaded, the surge protective device does not necessarily interrupt thecircuit to be protected. DEHNsafe surge arresters feature a green and redLED for visual indication of the protective device.

SPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

Page 131: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 131/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

129www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

DEHNsafe

DEHNsafeDSA 230

DEHNsafe

PEL N

Basic circuit diagram DSA 230 LADimension drawing DSA 230 LA

DSA 230 LA: Surge protective device for use in cable ducts and flush-type boxes

DSA 230 LA

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage UC 255 V

Nominal load current IL 16 A

Nominal discharge current (8/20 µs) In 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA

Combined impulse UOC 6 kV

Combined impulse [L+N-PE] UOC total 10 kV

Voltage protection level [L-N] UP 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV

Response time [L-N] tA 25 ns

Response time [L/N-PE] tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms

Fault indication red light + acoustic signal

Operating state indication green light

Switch function test / acoustic signal off

Operating temperature range TU -25°C...+40°C

Cross-sectional area (min.) 0.5 mm2 solid/stranded/flexible

Cross-sectional area (max.) 2.5 mm2 solid/stranded/flexible

For mounting on supporting ring (Ø60 mm) for installing into switch boxes, depth of 40 mm

Enclosure material thermoplastic, grey, UL 94 V-2

Degree of protection IP 20Cover TAE

Ordering information

Type DSA 230 LA

Part No. 924 370

Packing unit 1 pc(s).

Accessory Part for DEHNsafe

924 329 ZAP STW

ZAP STW CentralC ov er in gPl at ef or DE HN saf e 92 432 9

Accessory Part for DEHNsafe

924 328 AR1 STW

AR1 STW CoveringF ra me f or D EH Ns af e, st ud io wh it e 9 24 32 8

Covering frame

Single unit, alpha exclusive

PU PartType Colour pc(s). No.

AR1 STW studio white 1 924 328

Central covering plate

Single unit, alpha exclusive

PU PartType Colour pc(s). No.

ZAP STW studio white 1 924 329

Page 132: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 132/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

130 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

For protecting electronic devices against surges. For use with standardearthed socket outlets. For installation in conformity with the lightningprotection zones concept at the boundaries from 1 – 2 and higher.

• Two-pole surge arrester with monitoring deviceand disconnector

• Enhanced safety due to distinctive Y protectioncircuit

• Acoustic fault indication

• For installation in combination with standardearthed socket outlets

• Independent from the design of the socket out-lets

• Plastic supporting ring with latch for easyinstallation on already mounted socket outlets

STC 230: Snap-on module for standard earthed socket outlets

STC Module

Surge arrester for earthed socket outlets

The popular STC surge protection module can be installed inconspicuous-ly.Being a two-pole surge arrester, the module can be installed on the rearside of standard earthed socket outlets. The STC surge protection modulethus adapts to every type of socket outlet. The plastic supporting ring withlatch allows easy installation even on already mounted socket outlets. In

addition to a thermal disconnector, the protective device features anacoustic fault indication. As the surge protection module is installed inparallel to the socket outlet, the power supply of the connected con-sumers remains uninterrupted, even if the surge arrester is overloaded.

SPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

Page 133: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 133/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

131www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

STC Module

STC 230STC 230

N PE L

Basic circuit diagram STC 230

approx. 127

approx. 117

Dimension drawing STC 230

STC 230: Two-pole surge arrester for snapping onto earthed socket outlets

STC 230

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage UC 255 V

Nominal discharge current (8/20 µs) In 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA

Combined impulse UOC 6 kV

Combined impulse [L+N-PE] UOC total 10 kV

Voltage protection level [L-N] UP 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV

Response time [L-N] tA 25 ns

Response time [L/N-PE] tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms

Fault indication acoustic signal on

Operating temperature range TU -25°C...+40°C

Terminal wires 1 mm2, length:120 mm

For mounting on common socket outlets with earth contact

Enclosure material thermoplastic, red, UL 94 V-2

Degree of protection of installed device IP 20

Dimension 53 x 53 x 32 mm

Indication of disconnector acoustic signal on

Ordering information

Type STC 230

Part No. 924 350

Packing unit 1 pc(s).

Page 134: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 134/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

132 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

For protecting electronic equipment against surges. For installation intoelectrical installation systems, e.g. flush-mounted systems, cable ductsand flush-type boxes. German utility patent for DEHNflex A / ... D. Forinstallation in conformity with the lightning protection zones concept atthe boundaries from 1 – 2 and higher.

• Two-pole surge arrester with monitoring deviceand disconnector

• Enhanced safety due to distinctive Y protectioncircuit

• Acoustic fault indication

• Compact design

• For use in flush-mounted systems, cable ductsand flush-type boxes

DEHNflex M: More compact version; for use in cable duct systems and flush-mounted socket outlets

DEHNflex A: For use in any cable duct systems or flush-mounted socket outlets; with test function

DEHNflex D: Like DEHNflex A, but for series connection of several socket outlets

DEHNflex

Flexible protection of terminal equipment

The name of the DEHNflex family refers to the nearly unlimited applica-tion possibilities of the devices. Being 2-pole surge arresters, the compactmodules are ideally suited for protecting electronic consumers in final cir-cuits.The design was adapted to the most common installation locations,i.e. cable ducts and flush-type boxes. DEHNflex devices show that smalland compact sizes do not necessarily mean low-capacity performance.

The distinctive Y protection circuit always ensures safety even if the phaseand neutral conductors cannot be identified. Apart from the powerful Ycircuit, the compact enclosure also incorporates a disconnector and anacoustic fault indicator. In cable ducts, flush-mounted systems, branchingboxes or device tubs – DEHNflex can always be installed in the right placeclose to terminal equipment.

SPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

Page 135: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 135/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

133www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

DEHNflex

DEHNflex MDFL M

DEHNflex924 396

PEN L

Basic circuit diagram DFL MDimension drawing DFL M

DFL M: Surge arrester for use in all types of installation systems for terminal equipment; compactdimensions

DFL M 255

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage UC 255 V

Nominal discharge current (8/20 µs) In 1.5 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 3 kA

Combined impulse UOC 3 kV

Combined impulse [L+N-PE] UOC total 6 kV

Voltage protection level [L-N] UP 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV

Response time [L-N] tA 25 ns

Response time [L/N-PE] tA 100 ns

Max. mains-side overcurrent protection 32 A gL/gG or B 32 A

Short-circuit withstand capability for mains-side overcurrent protection with 32 A gL/gG 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms

Fault indication acoustic signal on

Operating temperature range TU -25°C...+40°C

Terminal wires 1 mm2 , length:120 mm

Enclosure material thermoplastic, red, UL 94 V-2

Degree of protection of installed device IP 20

Dimension 30 x 50 x 11 mm

Ordering informationType DFL M 255

Part No. 924 396

Packing unit 1 pc(s).

Page 136: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 136/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

134 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

DEHNflex

DEHNflex A924 389 DFL A 255

DFL A 255 DEHNf lexA 924 389

PE

NL

Basic circuit diagram DFL A Dimension drawing DFL A

DFL A: Surge arrester for use in all types of installation systems for terminal equipment; with testfunction

DFL A 255

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage UC 255 V

Nominal discharge current (8/20 µs) In 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA

Combined impulse UOC 6 kV

Combined impulse [L+N-PE] UOC total 10 kV

Voltage protection level [L-N] UP 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV

Response time [L-N] tA 25 ns

Response time [L/N-PE] tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms

Fault indication acoustic signal on

Operating temperature range TU -25°C...+40°C

Terminal wires 1 mm2 , length: 120 mm

Enclosure material thermoplastic, red, UL 94 V-2

Degree of protection of installed device IP 20

Dimension 36 x 62 x 19 mm

Ordering informationType DFL A 255

Part No. 924 389

Packing unit 1 pc(s).

Page 137: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 137/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

135www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

DEHNflex

DEHNflex DDFL D 255

DEHNflex924 395

PE

N

L

Basic circuit diagram DFL DDimension drawing DFL D

DFL D: Surge arrester for use in all types of installation systems for terminal equipment; allows forthrough-wiring; with test function

DFL D 255

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage UC 255 V

Nominal load current a.c. IL 16 A

Nominal discharge current (8/20 µs) In 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA

Combined impulse UOC 6 kV

Combined impulse [L+N-PE] UOC total 10 kV

Voltage protection level [L-N] UP 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV

Response time [L-N] tA 25 ns

Response time [L/N-PE] tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms

Fault indication acoustic signal on

Operating temperature range TU -25°C...+40°C

Terminal wires 2.5 mm2 , length: 120 mm

Enclosure material thermoplastic, red, UL 94 V-2

Degree of protection of installed device IP 20

Dimension 36 x 62 x 19 mm

Ordering information

Type DFL D 255

Part No. 924 395

Packing unit 1 pc(s).

Page 138: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 138/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

136 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

For protecting electronic equipment against surges. Earthed socket outletcontact and surge protective circuit for installation into electrical installa-tion systems. For installation according to the lightning protection zonesconcept at the boundaries from 1 – 2 and higher. German utility patent.

• Surge protection with monitoring device anddisconnector

• Maximum safety due to distinctive Y protectioncircuit

• Visual operating state (green) and fault indica-tion (red)

• With supporting ring (dimension 60 mm) forinstallation into switchboxes with a diameter of60 mm and a depth of 40 mm

NSM Protector: Earthed socket outlet with integrated surge protection

NSM Protector

Surge protective socket outlet

The devices of the NSM Protector family combine surge protection andearthed socket outlet in one single device. The two-pole surge arrestersare specifically designed for protecting electronic consumers in final cir-cuits.The very compact design of NSM Protector devices already includesthe approved disconnector. It isolates overloaded surge arresters withoutinterrupting the supply circuit. The low voltage protection level as well asthe comprehensive common and differential mode protection is typical of

the devices of the NSM Protector family. The distinctive Y protective cir-cuit ensures safety even if the phase and neutral conductors in final cir-cuits cannot be identified. The integrated disconnector makes a furthercontribution to the safety of devices and installations.The standard greenand red LEDs inform the user on the present operating state of the surgeprotective devices.

SPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

Page 139: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 139/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

137www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

NSM Protector

NSM PRONSM PRO

NSM PRO

NSM PRO

NSM PRO

NSM-i an w hi te 9 24 3 35

NSM-lv er 9 24 33 7

NSM-nt hr ac it e 9 24 3 39

NSM-tu di o wh it e 9 24 3 42

L/N L/N

PE

Basic circuit diagram NSM PRO ...Dimension drawing NSM PRO ...

NSM PRO ...: Surge protective socket outlet

NSM PRO TW NSM PRO SI NSM PRO AZ NSM PRO EW

SPD according to EN 61643-11 Type 3 Type 3 Type 3 Type 3

SPD according to IEC 61643-1 Class III Class III Class III Class III

Nominal a.c. voltage UN 230 V 230 V 230 V 230 V

Max. continuous operating a.c. voltage UC 255 V 255 V 255 V 255 V

Nominal discharge current (8/20 µs) In 3 kA 3 kA 3 kA 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA 5 kA 5 kA 5 kA

Combined impulse UOC 6 kV 6 kV 6 kV 6 kV

Combined impulse [L+N-PE] UOC total 10 kV 10 kV 10 kV 10 kV

Voltage protection level [L-N] UP 1.25 kV 1.25 kV 1.25 kV 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV 1.5 kV 1.5 kV 1.5 kV

Response time [L-N] tA 25 ns 25 ns 25 ns 25 ns

Response time [L/N-PE] tA 100 ns 100 ns 100 ns 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A

Short-circuit withstand capability for mains-side

overcurrent protection with 16 A gL/gG 6 kArms 6 kArms 6 kArms 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec. 440 V / 5 sec. 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms

Fault indication red light red light red light red light

Operating state indication green light green light green light green light

Operating temperature range TU -25°C...+40°C -25°C...+40°C -25°C...+40°C -25°C...+40°C

Cross-sectional area screwless double terminals up to 2.5 mm2 each, also suitable for series connection

For mounting on supporting ring (Ø60 mm) for installation into switchboxes, depth of 32 mm

Enclosure material thermoplastic, UL 94 V-2 thermoplastic, UL 94 V-2 thermoplastic, UL 94 V-2 thermoplastic, UL 94 V-2

Degree of protection IP 20 IP 20 IP 20 IP 20

DELTA type profile, titanium white profile, silver profile, anthracite plus, studio white

Ordering information

Type NSM PRO TW NSM PRO SI NSM PRO AZ NSM PRO EW

Part No. 924 335 924 337 924 339 924 342

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for NSM Protector

924 336 AR1 TW924 338 AR1 SI924 340 AR1 AZ924 343 AR1 EW

AR1 TW ProtectorC ov er ,s in gl e- pi ec e, ti ta nw hi te 9 24 33 6

AR1 SI ProtectorC ov er ,s ing le pie ce ,s il ve r 92 43 38AR1 AZ ProtectorC ov er ,s in gl ep ie ce ,a nt hr ac it e 9 24 34 0AR1 EW ProtectorC ov er ,s in gl ep ie ce ,s tu di ow hi te 9 24 34 3

S u r g e A r r e s t e r s T y p e 3

AR1 Covering Frame

Single unit, suitable for NSM Protector

PU PartType Profile pc(s). No.

AR1 TW DELTA profile, t itanium white 1 924 336

AR1 SI DELTA profile, silver 1 924 338

AR1 AZ DELTA profile, anthracite 1 924 340

AR1 EW DELTA plus, studio white 1 924 343

Page 140: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 140/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

138 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

DEHNprotector

Surge protective adapterType 3 according to EN 61643-11Class III according to EN 61643-1

• Surge protection with monitoring device anddisconnector

• Visual operating state (green) and fault indica-tion (red)

• Mains filter (DEHNpro 230 F-Protector only)

• Enhanced safety due to distinctive Y protectioncircuit

DEHNpro 230: Protection for terminal devices

DEHNpro 230 F: Protection for terminal devices with mains filter

Adapters for protecting the power supply circuit of electronic devicesagainst transient overvoltages as well as high-frequency interferencevoltages (DEHNpro 230 F-Protector). For installation in conformity withthe lightning protection zones concept at the boundaries from 1 – 2 andhigher.

The surge protective adapters of the DEHNpro family provide surge pro-tection for electronic consumers connected to final circuits. In theDEHNpro 230 F-Protector, the powerful surge protective circuit of DEHNpro 230 Protector was supplemented by an interference suppressorfilter with a balancing and unbalancing effect. This combination of surgeprotection and filter prevents a core saturation of the filter in case of high-energy transients. The nominal current carrying capability of 16 A forDEHNpro 230 and 10 A for 230 F-Protector allows flexible use of these

devices in final circuits.The distinctive Y protection circuit ensures protec-tion even if the phase and neutral conductors in standard earthed socketoutlets cannot be identified. The integrated disconnector also contributesto the safety of devices and installations.The standard green and red LEDsinform the user on the operating state of the surge protective devices.The modern design of DEHNpro devices and the use of high-quality mate-rials ensure safety in a sophisticated appearance. The DEHNpro devicesthus ideally adapt to the environment. They create the right technicalambience already at the socket outlet for connecting the latest communi-cation and multimedia systems. The curved enclosure surfaces and thesmooth surface structure ensure that the DEHNpro devices will not losetheir original properties even after several years of application.

Page 141: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 141/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

139www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

DEHNprotector

DPRO 230 ProtectorDPRO 230

N/L

PE

L/N

PE

red

green

L'/N'

N'/L'

Basic circuit diagram DPRO 230Dimension drawing DPRO 230

DPRO 230: Surge protective adapter

DPRO 230 DPRO 230 SE

SPD according to EN 61643-11 Type 3 Type 3

SPD according to IEC 61643-1 Class III Class III

Nominal a.c. voltage UN 230 V 230 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Nominal load current a.c. IL 16 A 16 A

Nominal discharge current (8/20 µs) In 3 kA 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA 5 kA

Combined impulse UOC 6 kV 6 kV

Combined impulse [L+N-PE] UOC total 10 kV 10 kV

Voltage protection level [L-N] UP 1.25 kV 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV 1.5 kV

Response time [L-N] tA 25 ns 25 ns

Response time [L/N-PE] tA 100 ns 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A

Short-circuit withstand capability for

mains-side overcurrent protection with 16 A gL/gG 6 kArms 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms

Fault indication red LED red LED

Operating state indication green LED green LED

Operating temperature range TU -25°C...+40°C -25°C...+40°C

For mounting on plug-in system with earth contact centre earthing contact system

according to DIN 49440 / DIN 49441 according to CEE 7, standard sheet V

Enclosure material thermoplastic, pure white, UL 94 V-2 thermoplastic, pure white, UL 94 V-2

Degree of protection IP 20 IP 20

Dimension 128 x 71 x 40 mm 128 x 71 x 40 mm

Ordering information

Type DPRO 230 DPRO 230 SE

Part No. 909 230 909 235

Packing unit 1 pc(s). 1 pc(s).

Page 142: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 142/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

140 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

DEHNprotector

DPRO 230 F-Protector909 240 DPRO 230F

DPRO230F909 240

N/L

PE

L/N

PE

red

green

L'/N'

N'/L'

L/N

Basic circuit diagram DPRO 230 F Dimension drawing DPRO 230 F

DPRO 230 F: Surge protective adapter with integrated mains filter

DPRO 230 F DPRO 230 SE F

SPD according to EN 61643-11 Type 3 Type 3

SPD according to IEC 61643-1 Class III Class III

Nominal a.c. voltage UN 230 V 230 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Nominal load current a.c. IL 10 A 10 A

Nominal discharge current (8/20 µs) In 3 kA 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA 5 kA

Combined impulse UOC 6 kV 6 kV

Combined impulse [L+N-PE] UOC total 10 kV 10 kV

Voltage protection level [L-N] UP 1.25 kV 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV 1.5 kV

Response time [L-N] tA 25 ns 25 ns

Response time [L/N-PE] tA 100 ns 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A

Short-circuit withstand capability for

mains-side overcurrent protection with 16 A gL/gG 6 kArms 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms

Fault indication red light red light

Operating state indication green light green light

Operating temperature range TU -25°C...+40°C -25°C...+40°C

For mounting on plug-in system with earth contact centre earthing contact system

according to DIN 49440 / DIN 49441 according to CEE 7, standard sheet V

Enclosure material thermoplastic, pure white, UL 94 V-2 thermoplastic, pure white, UL 94 V-2

Degree of protection IP 20 IP 20

Dimension 128 x 71 x 40 mm 128 x 71 x 40 mm

Mains filter acc. to DIN VDE 0565 Part 3 acc. to DIN VDE 0565 Part 3

Attenuation for f = 1 MHz, balanced 40 dB 40 dB

Attenuation for f = 1 MHz, unbalanced 30 dB 30 dB

Ordering information

Type DPRO 230 F DPRO 230 SE F

Part No. 909 240 909 245

Packing unit 1 pc(s). 1 pc(s).

Page 143: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 143/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

141www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

S u r g e A r r e s t e r s T y p e 3

Multiple socket outlet for protecting the power supply circuit of electron-ic devices against transient surges as well as high-frequency interference

voltages.For installation in conformity with the lightning protection zonesconcept at the boundaries from 1 – 2 and higher.

• Surge protection with monitoring device anddisconnector

• Interference suppressor filter• Enhanced safety due to distinctive Y protection

circuit

• Mains switch with operating state indication

• Visual fault indicator (red)

SFL Protector: Surge protective multiple socket outlet with interference suppressor filter

SFL Protector

Surge protective multiple socket outlet with filter

The SFL Protector compelements the wide range of Red/Line surge protec-tive devices. The combination of surge protection and mains filter makesthe 5-fold socket outlet a powerful device for protecting electronic con-sumers in final electrical circuits.The coordinated functions of surge pro-

tection and filter complement one another and prevent a core saturationof the filter in case of high-energy transients. The integrated mains filterwas optimised for protection against balanced and unbalanced high-fre-

quency interferences. With a nominal current carrying capability of 16 A,the SFL Protector can be used flexibly in final electrical circuits. The dis-tinctive Y protection circuit ensures protection even if the phase and neu-tral conductors in standard earthed socket outlets cannot be identified.

The standard green and red LEDs inform the user at a glance about thepresent operating state of the surge protective device.

SPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

Page 144: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 144/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

142 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

SFL Protector

SFL PRO912 260 SFL PRO

SFL PRO SFL-Protector 912 260

N/L

PE

L/N

Basic circuit diagram SFL PRO

approx.

Dimension drawing SFL PRO

SFL PRO: Surge protective multiple socket outlet with mains filter

SFL PRO SFL PRO SE

SPD according to EN 61643-11 Type 3 Type 3

SPD according to IEC 61643-1 Class III Class III

Nominal a.c. voltage UN 230 V 230 V

Max. continuous operating a.c. voltage UC 255 V 255 V

Nominal load current a.c. IL 16 A 16 A

Nominal discharge current (8/20 µs) In 3 kA 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA 5 kA

Combined impulse UOC 6 kV 6 kV

Combined impulse [L+N-PE] UOC total 10 kV 10 kV

Voltage protection level UP 1.5 kV 1.5 kV

Response time [L-N] tA 25 ns 25 ns

Response time [L/N-PE] tA 100 ns 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A

Short-circuit withstand capability for

mains-side overcurrent protection with 16 A gL/gG 1.5 kArms 1.5 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec. 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec. 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms 1200 V + U0 / 200 ms

Fault indication red light red light

Operating state indication green light green light

Operating temperature range TU -25°C...+40°C -25°C...+40°C

Connecting cable length: 200 cm length: 200 cm

Number of socket outlets 5 5

For mounting on plug-in system with earth contact centre earthing contact system

according to DIN 49440 / DIN 49441 according to CEE 7, standard sheet V

Enclosure material black/anthracite thermoplastic, UL 94 V-2 black/anthracite thermoplastic, UL 94 V-2

Degree of protection IP 20 IP 20

Dimension 513 x 55 x 47 mm 513 x 55 x 47 mm

Mains filter according to DIN VDE 0565 Part 3 according to DIN VDE 0565 Part 3

Attenuation for f = 1 MHz, balanced 54 dB 54 dB

Attenuation for f = 1 MHz, unbalanced 42 dB 42 dB

Ordering information

Type SFL PRO SFL PRO

Part No. 912 260 912 261

Packing unit 1 pc(s). 1 pc(s).

Page 145: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 145/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

143www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

For protecting electronic equipment against surges. For installation intothe enclosure or directly into the device to be protected. For installationin conformity with the lightning protection zones concept at the bound-aries from 1 – 2 and higher. German utility patent.

• Two-pole surge arrester with monitoring deviceand disconnector

• Complete surge protective circuit for deviceswith a.c. voltage power supply

• Enhanced safety due to distinctive Y protectioncircuit

• Floating remote signalling contact (break con-tact) with test option for fault indication

• For installation onto printed circuit boards

VC 280 2: Surge protective mains module for installation into the terminal device to be protected

VC 280 2

Compact protection for terminal equipment

Surge arresters of type VC 280 2 are small-sized, but still feature allrequired characteristics. The two-pole module includes a distinctive Y pro-tection circuit, monitoring device and disconnector as well as a floatingremote signalling contact ensuring maximum compact safety. The SPDs

even feature an integrated test option for testing the fault indicator.VC 280 2 reliably protects electronic equipment against surges.The solderpins allow the SPD to be installed directly onto the PCBs of the device tobe protected.

SPD Type 3 according to EN 61643-11SPD Class III according to IEC 61643-1

S u r g e A r r e s t e r s T y p e 3

Page 146: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 146/382

POWER SUPPLY SYSTEMS

SURGE ARRESTERS – TYPE 3

144 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters– Type 1

VC 280 2

VC 280 2900 471 VC 280 2

VC 280 2 MainsS ur ge Pr ot ec ti on Mo du le ,2 -p ol e 9 00 47 1

L/N L/N

11

12

Basic circuit diagram VC 280 2 Dimension drawing VC 280 2

VC 280 2: Surge protective mains module for installation into terminal devices to be protected

VC 280 2

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage UC 280 V

Nominal discharge current (8/20 µs) In 3 kA

Total discharge current (8/20 µs) [L+N-PE] Itotal 5 kA

Combined impulse UOC 6 kV

Combined impulse [L+N-PE] UOC total 10 kV

Voltage protection level [L-N] UP 1.25 kV

Voltage protection level [L/N-PE] UP 1.5 kV

Response time [L-N] tA 25 ns

Response time [L/N-PE] tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG 6 kArms

Temporary overvoltage (TOV) [L-N] UT 335 V / 5 sec.

Temporary overvoltage (TOV) [L/N-PE] UT 400 V / 5 sec.

Temporary overvoltage (TOV) [L+N-PE] UT 1200 V + U0 / 200 ms

Fault indication remote signalling contact

Operating temperature range UT -25°C...+40°C

For mounting on printed circuit board

Enclosure material thermoplastic, red, UL 94 V-2

Degree of protection IP 20

Dimension 32 x 24 x 15 mm

Type of remote signalling contact break contact

Switching capacity a.c. 250 V/0.5 A

Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Ordering information

Type VC 280 2

Part No. 900 471

Packing unit 1 pc(s).

Page 147: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 147/382

POWER SUPPLY SYSTEMS

ACCESSORIES

145www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

A c c e s s o r i e s

Wiring Accessories

DK 25 and STAK 2X16

• DK 25 allows to change the wiring level

• DK 25 supports lightning-impulse-current-con-

form installation of SPD combinations• STAK 2X16 allows to clamp cross sections that

are smaller than the defined minimum clamp-ing cross section of the surge protective device

• STAK 2X16 allows EMC-optimised series con-nection according to IEC 60364-5-53

EMC-optimised series connection of lightning current and surge arrestersaccording to IEC 60364-5-53 by means of STAK 2X16

STAK 2X16

STAK

DK 25

Dimension drawing DK 25

DK 25: Feed-through terminal for busbar wiringSTAK 2X16: Pin-shaped terminal

DK 25

DK 25 STAK 2X16

Nominal a.c./d.c. voltage UN 500 V —Nominal load current a.c. IL 100 A —

Test current according to EN 60947-7-1 100 A —

Lightning impulse current (10/350 µs) 100 kA —

Rated insulation voltage Ui 630 V —

Rated impulse withstand voltage Uimp 6 kV —

Operating temperature range TU -40°C...+80°C —

Cross-sectional area min. 1.5 mm2 solid/flexible, max. 25 mm2 stranded/16 mm2 flexible 2x min. 1.5 mm2, max. 16 mm2

For mounting on 35 mm DIN rail according to EN 60715 —

Type of connection — front (double terminal)

Enclosure material thermoplastic, red, UL 94 V-0 —

Degree of protection IP 20 —

Capacity 1 mod., DIN 43880 —

Ordering information

Type DK 25 STAK 2X16

Part No. 952 699 900 589

Packing unit 1 pc(s). 1 pc(s).

N E W

N E W

Page 148: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 148/382

POWER SUPPLY SYSTEMS

ACCESSORIES

146 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

Insulating Enclosure

• Enclosure for installing surge arresters testedwith lightning impulse currents

Application example: Modular DEHNventil® M TNC inIGA 10 V2 IP54 insulating enclosure

IGA 10 V2 IP54902 315 IGA 10 V2 IP54

IGA10V2IP54902 315

Dimension drawing IGA 10 V2 IP54

IGA 10 V2 IP54: Insulating enclosure for the installation of max. 10 modules; with membraneflange for 5 cables Ø7-30 mm EPDM and 3 mounted membrane openings M20with lock nut; ideally suited for through-wiring

IGA 10 V2 IP54

Degree of protection IP 54

Tested with lightning currents 3

Type of cover Transparent cover

Colour of enclosure grey

Quantity of cable entries 1 x for cables Ø7...10 mm; 2x for cables Ø10...14 mm or Ø15...30 mm each; 3 x for cables Ø8...13 mm

Available installation space 10 mods., DIN 43880

Dimension (W x H x D) 200 x 300 x 132 mm

Sealable 3

Ordering information

Type IGA 10 V2 IP54

Part No. 902 315

Packing unit 1 pc(s).

N E W

Page 149: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 149/382

POWER SUPPLY SYSTEMS

ACCESSORIES

147www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

A c c e s s o r i e s

Insulating Enclosure

IGA 12 IP54IGA 12

Dimension drawing IGA 12 IP54

IGA 12 IP54: Insulating enclosure for max. 12 modules, for non-exhausting SPDs

IGA 12 IP54

Degree of protection IP 54

Type of cover transparent cover

Colour of enclosure grey, RAL 7035

Cable entry integrated, elastic sealing membrane for entering cables

PE/N Quantity x Cross section 3 x 25 mm2, 12 x 4 mm2,Cu

Available installation space 12 mods., DIN 43880

Dimension (W x H x D) 295 x 333 x 129 mm

Ordering information

Type IGA 12 IP54

Part No. 902 471

Packing unit 1 pc(s).

IGA 24 IP54IGA 24

Dimension drawing IGA 24 IP54

IGA 24 IP54: Insulating enclosure for max. 2x 12 modules, for non-exhausting SPDs

IGA 24 IP54

Degree of protection IP 54

Type of cover transparent cover

Colour of enclosure grey, RAL 7035

Cable entry integrated, elastic sealing membrane for entering cables

PE/N Quantity x Cross section 6 x 25 mm2, 24 x 4 mm2,Cu

Available installation space 24 (2x 12) mods., DIN 43880

Dimension (W x H x D) 295 x 458 x 129 mm

Ordering informationType IGA 24 IP54

Part No. 902 472

Packing unit 1 pc(s).

Integrated plug-in terminal technology

for PE and N conductors

Integrated plug-in terminal technologyfor PE and N conductors

Page 150: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 150/382

POWER SUPPLY SYSTEMS

ACCESSORIES

148 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

Insulating Enclosure

IGA 6 IP54902 485 IGA 6IP54

IGA 6 IP54 InsulatingEnclosure 6mods. 902 485

Dimension drawing IGA 6 IP54

IGA 6 IP54: Enclosure for non-exhausting SPDs for max. 6 modules

IGA 6 IP54

Degree of protection IP 54

Type of cover transparent cover

Colour of enclosure grey

Quantity of cable entries 2 plug-in glands EST 21 for cables Ø9 ... 21 mm

Available installation space 6 mods., DIN 43880

Dimension (W x H x D) 165 x 255 x 115 mm

Sealable 3

Ordering information

Type IGA 6 IP54

Part No. 902 485

Packing unit 1 pc(s).

Page 151: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 151/382

POWER SUPPLY SYSTEMS

ACCESSORIES

149www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

MVS 1 4

Single-phase unit 3

Number of contact studs 4

Max. installation width 4 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 1 4

Part No. 900 610

Packing unit 1 pc(s).

MVS 4-pole, single-phaseMVS 1 4

Busbar900 610

Busbars / Modular Wiring System

• Allows for compact connection of SPDs with oneanother and to other DIN rail mounted devices

MVS 2-pole, single-phase

MVS 1 2

MVS 1 2

Single-phase unit 3

Number of contact studs 2

Max. installation width 2 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 1 2

Part No. 900 617

Packing unit 1 pc(s).

MVS 3-pole, single-phase

MVS 1 3

MVS 1 3

Single-phase unit 3

Number of contact studs 3

Max. installation width 3 mods.Nominal cross section 16 mm2

Ordering information

Type MVS 1 3

Part No. 900 615

Packing unit 1 pc(s).

MVS 6-pole, single-phase

MVS 1 6

MVS 1 6

Single-phase unit 3

Number of contact studs 6

Max. installation width 6 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 1 6

Part No. 900 815

Packing unit 1 pc(s).

A c c e s s o r i e s

Page 152: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 152/382

POWER SUPPLY SYSTEMS

ACCESSORIES

150 www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

MVS 3 6

Three-phase unit 3

Number of contact studs 6

Max. installation width 6 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 3 6

Part No. 900 595

Packing unit 1 pc(s).

MVS 6-pole, three-phase

900 595 MVS 3 6

MVS 3 6 Busbar 3-phase, 6-pole 900 595

MVS 6-pole, three-phase

900 813 MVS 3 68

MVS 3 6 8 Busbar 3-phase, 8-pole 900 813

MVS 3 6 8

Three-phase unit 3

Number of contact studs 6

Max. installation width 8 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 3 6 8

Part No. 900 813

Packing unit 1 pc(s).

Busbars / Modular Wiring System

MVS 1 8

Single-phase unit 3

Number of contact studs 8

Max. installation width 8 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 1 8

Part No. 900 611

Packing unit 1 pc(s).

MVS 8-pole, single-phase 900 611 MVS 1 8

MVS 1 8 Busbarsingle-phase, 8-pole 900 611

MVS 7-pole, single-phase

900 848 MVS 1 7

M VS1 7900 848

MVS 1 7

Single-phase unit 3

Number of contact studs 7

Max. installation width 7 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 1 7

Part No. 900 848

Packing unit 1 pc(s).

MVS 1 57

Single-phase unit 3

Number of contact studs 57

Max. installation width 57 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 1 57

Part No. 900 612

Packing unit 1 pc(s).

MVS 57-pole, single-phase900 612 MVS 1 57

MVS 1 57 Busbarsingle-phase, 57- pole 900 612

Page 153: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 153/382

POWER SUPPLY SYSTEMS

ACCESSORIES

151www.dehn.de

AccessoriesSurge Arresters –

Type 3Surge Arresters –

Type 2N-PE Lightning Current

Arresters – Type 1Lightning CurrentArresters – Type 1

CombinedArresters – Type 1

A c c e s s o r i e s

MVS 8-pole, four-phaseMVS 4 8

Busbar 4-900 814

MVS 4 8 11

Four-phase unit 3

Number of contact studs 8

Max. installation width 11 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 4 8 11

Part No. 900 814

Packing unit 1 pc(s).

MVS 56-pole, four-phaseMVS 4 56

Busbar 4-900 614

MVS 4 56

Four-phase unit 3

Number of contact studs 56

Max. installation width 56 mods.

Nominal cross section 16 mm2

Ordering information

Type MVS 4 56

Part No. 900 614

Packing unit 1 pc(s).

DG Earthing Clip, 3-pole,single-phase

EB DG

EB DG 1000 1 3

Single-phase unit 3

Number of contact studs 3

Dimension 34 x 112 x 3 mm

Terminal up to 25 mm2

Ordering information

Type EB DG 1000 1 3

Part No. 900 411

Packing unit 1 pc(s).

Busbars / Modular Wiring System

Earthing Clip, 4-pole,single-phaseEB 1

EB 1 4 9

Single-phase unit 3

Number of contact studs 4

Dimension 34 x 148 x 3 mm

Terminal up to 25 mm2

Ordering information

Type EB 1 4 9

Part No. 900 417

Packing unit 1 pc(s).

Page 154: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 154/382152 www.dehn.de

Page 155: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 155/382153www.dehn.de

Surge protection for

INFORMATIONTECHNOLOGY SYSTEMS

SPDs for installations and equipment

Page 156: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 156/382

INFORMATION TECHNOLOGY SYSTEMS

154 www.dehn.de

919 506 BCT BAS 920 300 BXT BAS919 310 BCT MLC B 110 920 310 BXT ML4 B 180

919 320 BCT MLC BE 5 920 220 BXT ML2 BE S 5 or

920 320 BXT ML4 BE 5

919 321 BCT MLC BE 12 920 222 BXT ML2 BE S 12 or

920 322 BXT ML4 BE 12

919 322 BCT MLC BE 15 920 222 BXT ML2 BE S 12 or

920 322 BXT ML4 BE 12

919 323 BCT MLC BE 24 920 224 BXT ML2 BE S 24 or

920 324 BXT ML4 BE 24

919 324 BCT MLC BE 30 920 224 BXT ML2 BE S 24 or

920 324 BXT ML4 BE 24

919 325 BCT MLC BE 48 920 225 BXT ML2 BE S 48 or

920 325 BXT ML4 BE 48

919 326 BCT MLC BE 60 920 326 BXT ML4 BE 60

919 327 BCT MLC BE 110 920 327 BXT ML4 BE 180

919 360 BCT MLC BE C 5 ––

919 361 BCT MLC BE C 12 920 362 BXT ML4 BE C 12

919 362 BCT MLC BE C 24 920 364 BXT ML4 BE C 24

919 363 BCT MLC BE C 30 920 364 BXT ML4 BE C 24

919 340 BCT MLC BD 5 920 240 BXT ML2 BD S 5 or

920 340 BXT ML4 BD 5

919 341 BCT MLC BD 12 920 242 BXT ML2 BD S 12 or

920 342 BXT ML4 BD 12

919 342 BCT MLC BD 15 920 242 BXT ML2 BD S 12 or

920 342 BXT ML4 BD 12

919 343 BCT MLC BD 24 920 244 BXT ML2 BD S 24 or

920 344 BXT ML4 BD 24

919 344 BCT MLC BD 30 920 244 BXT ML2 BD S 24 or

920 344 BXT ML4 BD 24919 345 BCT MLC BD 48 920 245 BXT ML2 BD S 48 or

920 345 BXT ML4 BD 48

919 346 BCT MLC BD 60 920 346 BXT ML4 BD 60

919 347 BCT MLC BD 110 920 247 BXT ML2 BD 180 or

920 347 BXT ML4 BD 180

919 349 BCT MLC BD 250 ––

919 370 BCT MLC BD HF 5 920 270 BXT ML2 BE HFS 5 or

920 370 BXT ML4 BE HF 5

919 371 BCT MLC BD HFD 5 920 271 BXT ML2 BD HFS 5 or

920 371 BXT ML4 BD HF 5

919 375 BCT MLC BD HFD 24 920 375 BXT ML4 BD HF 24

919 520 BCT MOD ME 5 920 220 BXT ML2 BE S 5 or

920 320 BXT ML4 BE 5

919 521 BCT MOD ME 12 920 222 BXT ML2 BE S 12 or920 322 BXT ML4 BE 12

919 522 BCT MOD ME 15 920 222 BXT ML2 BE S 12 or

920 322 BXT ML4 BE 12

919 523 BCT MOD ME 24 920 224 BXT ML2 BE S 24 or

920 324 BXT ML4 BE 24

919 524 BCT MOD ME 30 920 224 BXT ML2 BE S 24 or

920 324 BXT ML4 BE 24

919 525 BCT MOD ME 48 920 225 BXT ML2 BE S 48 or

920 325 BXT ML4 BE 48

919 526 BCT MOD ME 60 920 326 BXT ML4 BE 60

919 527 BCT MOD ME 110 920 327 BXT ML4 BE 180

919 560 BCT MOD ME C 5 ––

919 561 BCT MOD ME C 12 920 362 BXT ML4 BE C 12

919 562 BCT MOD ME C 24 920 364 BXT ML4 BE C 24

919 563 BCT MOD ME C 30 920 364 BXT ML4 BE C 24

919 540 BCT MOD MD 5 920 240 BXT ML2 BD S 5 or920 340 BXT ML4 BD 5

919 541 BCT MOD MD 12 920 242 BXT ML2 BD S 12 or

920 342 BXT ML4 BD 12

919 542 BCT MOD MD 15 920 242 BXT ML2 BD S 12 or

920 342 BXT ML4 BD 12

919 543 BCT MOD MD 24 920 244 BXT ML2 BD S 24 or

920 344 BXT ML4 BD 24

919 544 BCT MOD MD 30 920 244 BXT ML2 BD S 24 or

920 344 BXT ML4 BD 24

919 545 BCT MOD MD 48 920 245 BXT ML2 BD S 48 or

920 345 BXT ML4 BD 48

919 546 BCT MOD MD 60 920 346 BXT ML4 BD 60

919 547 BCT MOD MD 110 920 247 BXT ML2 BD 180 or

920 347 BXT ML4 BD 180

919 549 BCT MOD MD 250 ––919 570 BCT MOD MD HF 5 920 270 BXT ML2 BE HFS 5 or

920 370 BXT ML4 BE HF 5

919 571 BCT MOD MD HFD 5 920 271 BXT ML2 BD HFS 5 or

920 371 BXT ML4 BD HF 5

919 575 BCT MOD MD HFD 24 920 375 BXT ML4 BD HF 24

919 552 BCT MOD MD TC N ––

919 589 BCT MOD MY 250 920 389 BXT ML4 MY 250

919 502 GDT 90 ––

919 504 BCT MOD PTS 920 309 BXT M4 T

919 505 EKS BCT 920 308 BXT M4 E

919 508 EFK BCT 920 395 SAK BXT LR

Cross-reference

Accessories for compact SPDs for DIN rail mounting

919 885 KB 5 DCO RK ––

919 888 KB 8 DCO RK ––

SPDs for LSA technology

907 209 GDT 230 G3 FS 907 217 GDT 230 G3 FSD

907 215 DPL 10 G3 110 FS 907 216 DPL 10 G3 110 FSD

SPDs for data cabinets 482.6 mm (19 inch)

929 067 NET PRO ISDN 929 100 DPA M CAT6 RJ45S 48

929 068 NET PRO ISDN LSA 929 100 DPA M CAT6 RJ45S 48

929 069 NET PRO TC 1 929 071 NET PRO TC 2

929 070 NET PRO TC 1 LSA 929 072 NET PRO TC 2 LSA

SPDs for RJ connection

929 027 DLI TC 1 I 929 028 DLI TC 2 I

929 029 DLI TC DK ––

929 080 DLI TC ECO 929 028 DLI TC 2 I

SPDs for coaxial connection

929 041 DGA G 1.6 5.6 929 040 DGA F 1.6 5.6

929 058 DGA G N 3 929 044 DGA G N

SPDs for terminal connection

924 271 DSM TC 1 SK 924 272 DSM TC 2 SK

924 273 DSM TC DK SK ––

Accessories for screwable SPDs

929 981 KV S M20 MS 13 ––

929 985 KV M20 MS 8 ––

SPDs for potentially explosive areas919 507 BCT BAS EX 920 301 BXT BAS EX

919 580 BCT MOD MD EX 24 920 381 BXT ML4 BD EX 24

919 581 BCT MOD MD EX 30 920 381 BXT ML4 BD EX 24

919 583 BCT MOD MD HFD EX 6 920 538 BXT ML2 BD HF EX 6

Pluggable SPDs for DIN rail mountingBLITZDUCTOR CT BLITZDUCTOR XT

Pluggable SPDs for DIN rail mountingBLITZDUCTOR CT BLITZDUCTOR XT

Discontinued Products AlternativesPart No. Type Part No. Type

Discontinued Products AlternativesPart No. Type Part No. Type

Page 157: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 157/382

INFORMATION TECHNOLOGY SYSTEMS

155

www.dehn.de

CONTENTS

Easy choice according to Interface/ Signal 156

Pluggable SPDs for DIN rail mounting 179

Compact SPDs for DIN rail mounting 209

SPDs for LSA technology 229

SPDs for data cabinets 482.6 mm (19 inch) 247

SPDs for RJ connection 253

SPDs for BT Jack connection 265

SPDs for coaxial connection 267

SPDs for D-Sub connection 281

SPDs for terminal connection 289

Screwable SPDs 297

SPDs for use in potentially explosive areas 301

Accessories for terminal block systems 325

Combined adapters 337

Measuring and test devices 359

1 2 3 4 5 6 7 8 9 0

Page 158: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 158/382

INFORMATION TECHNOLOGY SYSTEMS

156 www.dehn.de

Easy Choice according to Interface / Signal

4-20 mA

(also with HART) acc.

to NAMUR recommen-

dation NE 21 or acc. to

EN 61000-4-5, open-circuit

voltage 1 kV A-PG

0-20 mA, 4-20 mA screw terminals 4 1 920 324 + 920 300 188

(also with HART)screw terminals 2 1 920 224 + 920 300 197

spring terminals 2 919 921 210

spring terminals 2 919 988 215

wires / terminals 2 929 921 293

screw terminals 4 1 920 344 + 920 300 189

screw terminals 2 1 920 244 + 920 300 196

spring terminals 2 919 941 211

screw terminals 4 918 407 220

wires / terminals 2 929 941 292

LSA 20

907 401

232+ 907 498 + 907 442

3/4 conductor measuring screw terminals 4 1 920 354 + 920 300 190

ADVANT screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

screw terminals 5 918 401 221

spring terminals 2 919 970 214

AS interface vampire taps 2 925 013 293

Binary signals screw terminals 4 1 920 320 – 327 + 920 300 188

screw terminals 2 1 920 220 – 225 + 920 300 197

spring terminals 2 919 920 – 923 210

spring terminals 2 919 987 – 990 215

LSA 20907 401

232+ 907 498 + 907 422

Bitbus screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 2142

1

1

1

3

2

1

1

2

2

2

1

1

1

1

2

2

2

1

1

2

3

2

1

1

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

Bus systems and measuring and control technology Page 156 – 165

Telecommunications, Telephony Page 166 – 169

Data networks Page 170 – 171

Antenna systems, Broadband systems,

Transmitting and receiving systems, Video systems Page 172 – 174

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

Page 159: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 159/382

INFORMATION TECHNOLOGY SYSTEMS

157www.dehn.de

Easy Choice according to Interface / Signal

BLN screw terminals 4 1 920 342 + 920 300 189(Building Level network)

screw terminals 2 1 920 242 + 920 300 196

screw terminals 4 1 920 345 + 920 300 189

screw terminals 2 1 920 245 + 920 300 198

CAN Bus screw terminals 4 1 920 370 + 920 300 192

(data line only)screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

LSA 20907 401

232+ 907 498 + 907 465

C Bus (Honeywell) screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

Control Net BNC 1 929 010 268

BNC 1 909 710 / 711 271

CP installations

Sensor circuit screw terminals 2 918 421 / 405 226

Anode circuit screw terminals 2 918 420 / 404 225

Data Highway Plus screw terminals 4 1 920 342 + 920 300 189

screw terminals 2 1 920 242 + 920 300 196

spring terminals 2 919 940 214

d.c. power supply screw terminals 2 918 402 222

+24/30 V d.c.screw terminals 2 918 408 223

Delta Net Peer Bus screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

Device Net screw terminals 4 1 920 370 + 920 300 192

(data line only)screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 2142

1

1

2

1

1

1

3

2

1

1

1

1

2

2

2

1

1

1

2

1

1

1

1

1

1

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

JokeractiVsense®

JJ

J JFor further details please refer to page 174

Page 160: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 160/382

INFORMATION TECHNOLOGY SYSTEMS

158 www.dehn.de

Easy Choice according to Interface / Signal

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

Dupline screw terminals 4 1 920 243 + 920 300 198

E-Bus (Honeywell) screw terminals 4 1 920 345 + 920 300 189

screw terminals 2 1 920 245 + 920 300 197

EIB screw terminals 4 1 920 310 + 920 300 187

screw terminals 2 1 920 211 + 920 300 195

wires 2 925 001 293

LSA 20 907 401 232

Electroacoustic screw terminals 4 1 920 327 + 920 300 188

system (ELA)spring terminals 2 919 923 210

LSA 20907 401

232+ 907 498 + 907 445

ET 200 screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 200

spring terminals 2 919 970 214

Ex(d) circuits

4-20 mA, NAMUR, wires 2 929 962 / 964 308

HART, PROFIBUS-PA, FF

Ex (i) circuits screw terminals 4 1 920 381 + 920 301 314

screw terminals 4 1 920 538 + 920 301 316

spring terminals 2 919 960 323

wires / terminals 2 929 960 303

wires 2 929 961 / 963 306

screw terminals 4 1 989 408 321

Fieldbus Foundation screw terminals 4 1 920 344 + 920 300 189

screw terminals 2 1 920 244 + 920 300 197

spring terminals 2 919 941 211

wires / terminals 2 929 941 298

LSA 20 907 401 232+ 907 498 + 907 4421

2

2

1

1

2

2

2

2

2

2

2

2

1

1

1

2

1

1

2

1

1

1

1

1

Page 161: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 161/382

INFORMATION TECHNOLOGY SYSTEMS

159www.dehn.de

Easy Choice according to Interface / Signal

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

Fieldbus Foundation screw terminals 4 1 920 381 + 920 301 314Ex (i)

screw terminals 4 1 920 538 + 920 301 316

spring terminals 2 919 960 323

wires / terminals 2 929 960 303

wires 2 929 961 / 963 306

wires 2 929 971 309

screw terminals 4 1 989 408 321

FIPIO/FIPWAY screw terminals 4 1 920 344 + 920 300 189

screw terminals 2 1 920 244 + 920 300 196

FIP I/O screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

FSK screw terminals 4 1 920 371 + 920 300 193

screw terminals 2 1 920 271 + 920 300 199

spring terminals 2 919 970 214

Genius I/O Bus screw terminals 4 1

920 342 + 920 300 189

screw terminals 2 1 920 242 + 920 300 196

IEC Bus (RS 485) screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

Industrial Ethernet LSA 20907 401

232+ 907 498 + 907 470

RJ45 8 929 100 / 110 254

RJ45 8 929 121 255

RJ45, LSA / RJ45 8 x 8 929 035 / 036 249

RJ45 8 x 8 929 037 249

RJ45 4 909 321 337

INTERBUS INLINE (I/O) screw terminals 4 1 920 345 + 920 300 189

screw terminals 4 1 920 325 + 920 300 1881

1

2

4

3

2

2

1

2

1

1

1

1

2

1

1

1

1

1

1

2

2

2

2

2

2

2

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J JFor further details please refer to page 174

Page 162: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 162/382

INFORMATION TECHNOLOGY SYSTEMS

160 www.dehn.de

Easy Choice according to Interface / Signal

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

INTERBUS Loop spring terminals 2 919 988 215

Interbus INLINE screw terminals 4 1 920 371 + 920 300 193

Long-distance busscrew terminals 2 1 920 271 + 920 300 2199

screw terminals 5 918 401 221

K Bus screw terminals 4 1 920 344 + 920 300 189

screw terminals 2 1 920 244 + 920 300 196

spring terminals 2 919 941 211

KBR Energy bus screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

KNX Bus screw terminals 4 1 920 310 + 920 300 187

screw terminals 2 1 920 211 + 920 300 200

wires 2 925 001 291

LSA 20 907 401 232

LON

– TP/XF 78 screw terminals 4 1 920 340 + 920 300 189

screw terminals 2 1 920 240 + 920 300 196

–TP/FTT10 (up to 1 A) screw terminals 4 1 920 345 + 920 300 189

and TP/LPT10(up to 1 A) screw terminals 2 1 920 245 + 920 300 196

(up to 1.7 A) spring terminals 2 919 942 212

(up to 0.4 A) LSA 20907 401

232+ 907 498 + 907 443

– TP/FTT 10 screw terminals 4 1 920 371 + 920 300 193

screw terminals 2 1 920 271 + 920 300 199

LUXMATE Bus screw terminals 4 1 920 344 + 920 300 189

screw terminals 2 1 920 244 + 920 300 196

M Bus screw terminals 4 1 920 345 + 920 300 189

screw terminals 2 1 920 245 + 920 300 196

spring terminals 2 919 942 212

LSA 20907 401

232+ 907 498 + 907 4431

2

1

1

1

1

1

1

1

2

1

1

1

1

1

2

1

1

2

1

1

2

1

1

2

1

1

3

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

Page 163: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 163/382

INFORMATION TECHNOLOGY SYSTEMS

161www.dehn.de

Easy Choice according to Interface / Signal

Melsec Net 2 BNC 1 929 010 268

BNC 1 909 710 / 711 271

MODBUS screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

LSA 20907 401

232+ 907 498 + 907 465

MPI Bus screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

N1 LAN screw terminals 4 1 920 371 + 920 300 193

screw terminals 2 1 920 271 + 920 300 199

screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

BNC 1 909 710 / 711 271

N2 Bus (Johnson Controls, screw terminals 4 1 920 371 + 920 300 193

LON, FTT 10)screw terminals 2 1 920 271 + 920 300 199

Optocoupler screw terminals 4 1 920 364 + 920 300 191

Interfacescrew terminals 4 918 400 219

Procontic CS31 (RS 232) screw terminals 4 1 920 322 + 920 300 188

Procontic T200 (RS 422) screw terminals 4 1 920 371 + 920 300 193

screw terminals 5 918 401 221

PROFIBUS DP/FMS screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

D-Sub, 9-pole 4 924 017 282

spring terminals 2 919 970 214

LSA 20907 401

232+ 907 498 + 907 4651

2

4

1

1

2

1

1

2

1

1

1

2

2

1

1

1

1

2

1

1

1

2

1

1

2

2

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J JFor further details please refer to page 174

Page 164: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 164/382

INFORMATION TECHNOLOGY SYSTEMS

162 www.dehn.de

Easy Choice according to Interface / Signal

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

PROFIBUS PA screw terminals 4 1 920 344 + 920 300 189

screw terminals 2 1 920 244 + 920 300 196

spring terminals 2 919 941 211

wires / terminals 2 929 941 294

LSA 20907 401

232+ 907 498 + 907 442

PROFIBUS PA Ex (i) screw terminals 4 1 920 381 + 920 301 314

screw terminals 4 1 920 538 + 920 301 316

spring terminals 2 919 960 323

wires / terminals 2 929 960 303

wires 2 929 961 / 963 306

wires 2 929 971 309

screw terminals 4 1 989 408 321

PROFIBUS SIMATIC NET screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

PSM EG RS 422 screw terminals 4 1 920 371 + 920 300 193

screw terminals 5 918 401 221

PSM EG RS 485 screw terminals 4 1 920 371 + 920 300 193

screw terminals 2 1 920 271 + 920 300 199

screw terminals 5 918 401 221

Rackbus (RS 485) screw terminals 4 1 920 371 + 920 300 193

screw terminals 2 1 920 271 + 920 300 199

screw terminals 5 918 401 221

R Bus screw terminals 4 1 920 340 + 920 300 189

screw terminals 2 1 920 240 + 920 300 196

spring terminals 2 919 970 2142

1

1

2

1

1

2

1

1

2

1

1

1

2

2

2

2

2

2

2

1

2

2

1

1

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

Page 165: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 165/382

INFORMATION TECHNOLOGY SYSTEMS

163www.dehn.de

Easy Choice according to Interface / Signal

RS 485 screw terminals 4 1 920 370 + 920 300 192

screw terminals 4 1 920 538 + 920 301 316

screw terminals 2 1 920 270 + 920 300 198

screw terminals 5 918 401 221

spring terminals 2 919 970 214

LSA 20907 401

232+ 907 498 + 907 442

wires 2 929 971 309

RS 422, V11 screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

screw terminals 5 918 401 221

spring terminals 2 919 970 214

D-Sub, 15-pole 6 924 051 287

D-Sub, 15-pole 6 924 016 284

LSA 20907 401

232+ 907 498 + 907 465

S Bus screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

SafetyBUS p screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

SDLC screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

SDLS RJ45, screw terminals 4 918 410 257

LSA 20907 401

232+ 907 498 + 907 470

1

2

2

1

1

2

1

1

2

1

1

1

4

2

2

2

1

1

2

1

2

2

1

2

1

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J JFor further details please refer to page 174

Page 166: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 166/382

INFORMATION TECHNOLOGY SYSTEMS

164 www.dehn.de

Easy Choice according to Interface / Signal

screw terminals 4 1 920 340 + 920 300 189

screw terminals 2 1 920 240 + 920 300 196

spring terminals 2 919 970 214

SIGMASYS screw terminals 4 1 920 345 + 920 300 189

(Siemens firescrew terminals 2 1 920 245 + 920 300 196

alarm system)

screw terminals 4 1 920 325 + 920 300 188

screw terminals 2 1 920 225 + 920 300 197

LSA 20907 401

232+ 907 498 + 907 423

SINEC L1 screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

SINEC L2 screw terminals 4 1 920 370 + 920 300 192

screw terminals 2 1 920 270 + 920 300 198

spring terminals 2 919 970 214

D-Sub, 9-pole 4 924 017 282

SS97 SIN/X (RS 232) screw terminals 4 1

920 322 + 920 300 188

screw terminals 2 1 920 222 + 920 300 197

SUCONET screw terminals 4 1 920 340 + 920 300 189

screw terminals 2 1 920 240 + 920 300 196

Temperature screw terminals 4 1 920 350 + 920 300 190

measuringscrew terminals 4 1 920 354 + 920 300 190

PT 100, PT 1000

screw terminals 4 1

920 320 + 920 300 188

Ni 1000, NTC, PTC

screw terminals 2 1 920 220 + 920 300 197

spring terminals 2 919 970 214

Temperature

measuring Ex (i) screw terminals 4 1 920 384 + 920 301 315

PT 100, PT 1000,

Ni 1000, NTC, PTC

2

2

1

1

1

1

1

1

1

1

4

2

1

1

1

1

1

1

1

1

1

2

1

1

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

Securilan LON Bus(LONWORKS Technology

Standard Bus based on

Echelon)

JokeractiVsense®

JJ

J J

Page 167: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 167/382

INFORMATION TECHNOLOGY SYSTEMS

165www.dehn.de

Easy Choice according to Interface / Signal

TTL screw terminals 4 1 920 322 + 920 300 188

screw terminals 2 1 920 222 + 920 300 197

spring terminals 2 919 920 210

D-Sub, 25-pole 4, 9 924 046 288

D-Sub, 9-pole 9 924 019 283

TTY screw terminals 4 1 920 364 + 920 300 191

screw terminals 2 1 920 362 + 920 300 191

screw terminals 4 918 400 219

TTY 4 – 20 mA screw terminals 4 1 920 324 + 920 300 188

screw terminals 2 1 920 224 + 920 300 197

spring terminals 2 919 921 210

spring terminals 2 919 988 215

wires / terminals 2 929 921 2952

3

2

1

1

2

1

1

4

2

2

1

1

Bus systems and measuring and control technology

LifeCheck SPD

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

JokeractiVsense®

JJ

J JFor further details please refer to page 174

Page 168: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 168/382

INFORMATION TECHNOLOGY SYSTEMS

166 www.dehn.de

Easy Choice according to Interface / Signal

Telecommunications, Telephony

LifeCheck SPD-

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

a/b wires LSA 20907 401

232+ 907 498 + 907 430

RJ45, LSA / RJ45 8 x 2 929 071 / 072 250

screw terminals 4 1 920 347 + 920 300 189

RJ45, screw terminals 2 918 411 258

TAE, RJ12 2 909 310 339

spring terminals / RJ45 2 929 230 252

BT jack 6 929 026 266

ADSL screw terminals 4 1 920 347 + 920 300 189

screw terminals 2 1 920 247 + 920 300 196

LSA 20907 401

232+ 907 498 + 907 430

wires 2 924 272 291

TAE, RJ12 2 909 310 339

RJ45, LSA / RJ45 8 x 2 929 071 / 072 250

RJ45, screw terminals 2 918 411 258

spring terminals / RJ45 2 929 230 252

BT jack 6 929 026 266

ADSL 2+ LSA 20907 401

232+ 907 498 + 907 430

screw terminals 4 1 920 347 + 920 300 189

Datex P screw terminals 4 1 920 375 + 920 300 193

E1 RJ45 8 x 2 929 100 / 110 254

LSA 20907 401

232+ 907 498 + 907 470

LSA / RJ45 8 x 4 929 075 251

screw terminals 4 1 920 375 + 920 300 193

G.703 koax 1.6/5.6 connector 1 929 040 273

G.703 / G.704 2 907 214 240

LSA / RJ45 8 x 4 929 075 251

RJ45 8 x 2 929 100 / 110 254

LSA 20907 401

232

+ 907 498 + 907 470

screw terminals 4 1 920 375 + 920 300 1931

1

2

2

2

3

1

2

1

2

1

1

1

2

2

2

2

2

2

1

1

1

2

2

2

2

1

2

1

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

insulation displacementterminal

Page 169: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 169/382

INFORMATION TECHNOLOGY SYSTEMS

167www.dehn.de

Easy Choice according to Interface / Signal

HDSL screw terminals 4 1 920 375 + 920 300 193up to 30 dBm for 600 W

LSA 20907 401

232+ 907 498 + 907 470

RJ45 8 x 2 929 100 / 110 254

LSA / RJ45 8 x 4 929 075 251

ISDN S0 screw terminals 4 1 920 375 + 920 300 193

RJ45 4 929 024 262

LSA 20907 401

232+ 907 498 + 907 470

wires 4 924 270 290

RJ45 4 909 320 340

RJ45 8 x 2 929 100 / 110 254

RJ45, screw terminals 4 918 410 257

RJ45, screw terminals 4 924 274 260

ISDN S2m / U2m screw terminals 4 1 920 375 + 920 300 193

LSA 20907 401

232+ 907 498 + 907 470

RJ45 8 x 2 929 100 / 110 254

LSA / RJ45 8 x 4 929 075 251

ISDN UK0 / UP0 screw terminals 4 1 920 347 + 920 300 189

screw terminals 2 1 920 247 + 920 300 196

spring terminals 2 919 943 213

LSA 20907 401

232+ 907 498 + 907 430

RJ45, LSA / RJ45 8 x 2 929 071 / 072 250

TAE, RJ12 2 909 310 339

RJ45, screw terminals 2 918 411 258

spring terminals / RJ45 10 x 2 929 230 252

Modem M1 screw terminals 4 1 920 322 + 920 300 188

screw terminals 2 1 920 222 + 920 300 199

SDSL RJ45 8 x 2 929 100 / 110 254

LSA 20907 401

232+ 907 498 + 907 470

screw terminals 4 1 920 375 + 920 300 193

LSA / RJ45 8 x 4 929 075 2512

1

1

2

1

1

2

2

2

2

1

2

1

1

2

2

1

1

2

2

2

2

2

1

2

1

2

2

1

1

Telecommunications, Telephony

LifeCheck SPD-

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J JFor further details please refer to page 174

Page 170: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 170/382

INFORMATION TECHNOLOGY SYSTEMS

168 www.dehn.de

Easy Choice according to Interface / Signal

Telecommunications, Telephony

LifeCheck SPD-

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

SHDSL screw terminals 4 1 920 371 + 920 300 193

screw terminals 4 1 920 375 + 920 300 193

RJ45 8 x 2 929 100 / 110 254

LSA 20907 401

232+ 907 498 + 907 470

screw terminals 4 1 920 310 + 920 300 187

screw terminals 2 1 920 211 + 920 300 195

LSA / RJ45 8 x 4 929 075 251

Telephony screw terminals 2 1 920 247 + 920 300 196

System Telephonyspring terminals 2 919 943 213

e. g. Siemens, HICOM,

RJ45, RJ11 4 929 028 263Alcatel

RJ12 2 929 081 264

LSA 20907 401

232+ 907 498 + 907 430

LSA 20907 401

232+ 907 498 + 907 445

wires 4 924 272 291

RJ45, LSA / RJ45 8 x 2 929 071 / 072 250

TAE, RJ12 2 909 310 339

RJ45, screw terminals 2 918 411 258

spring terminals / RJ45 10 x 2 929 230 252

T-DSL screw terminals 4 1 920 347 + 920 300 189

screw terminals 2 1 920 247 + 920 300 196

LSA 20907 401

232+ 907 498 + 907 430

wires 2 924 272 291

TAE, RJ12 2 909 310 339

RJ45, LSA / RJ45 8 x 2 929 071 / 072 250

RJ45, screw terminals 2 918 411 258

spring terminals / RJ45 10 x 2 929 230 252

Telecommunication LSA 20907 401

232

systems+ 907 498 + 907 430

RJ45, LSA / RJ45 8 x 2 929 071 / 072 250

screw terminals 2 1 920 347 + 920 300 189

RJ45, screw terminals 2 918 411 258

TAE, RJ12 2 909 310 339

spring terminals / RJ45 10 x 2 929 230 252

BT jack 6 929 026 2662

2

2

2

1

2

1

2

2

2

2

2

1

1

1

2

2

2

2

2

1

1

2

2

2

1

2

1

1

1

2

1

1

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

JokeractiVsense®

JJ

J J

Page 171: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 171/382

INFORMATION TECHNOLOGY SYSTEMS

169www.dehn.de

Easy Choice according to Interface / Signal

Universal lightning screw terminals 4 1 920 310 + 920 300 187equipotential bonding

screw terminals 2 1 920 211 + 920 300 200

LSA 20 907 400 231

LSA 20 907 401 232

20 907 214 240

20 907 216 240

VDSL LSA 20 907 401 232

screw terminals 4 1 920 310 + 920 300 187

screw terminals 4 1 920 211 + 920 300 2001

1

1

2

2

1

1

1

1

JokeractiVsense®

JJ

J J

Telecommunications, Telephony

LifeCheck SPD-

Protected class

Interface/Signal For mounting on Ex Connection system lines SPD Part No. PageTYPE

JokeractiVsense®

JJ

J JFor further details please refer to page 174

insulation displacementterminal

insulation displacementterminal

Page 172: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 172/382

INFORMATION TECHNOLOGY SYSTEMS

170 www.dehn.de

Easy Choice according to Interface / Signal

Arcnet BNC 1 929 010 268

BNC 1 909 710 / 711 271

ATM RJ45 8 929 100 / 110 254

RJ45 8 929 121 255

RJ45, LSA / RJ45 8 x 8 929 035 / 036 249

RJ45 8 x 8 929 037 249

RJ45 4 909 321 337

Ethernet 10/100/1000 RJ45 8 929 100 / 110 254

RJ45 8 929 121 255

RJ45, LSA / RJ45 8 x 8 929 035 / 036 249

RJ45 8 x 8 929 037 249

RJ45 4 909 321 337

10 Base T RJ45, screw terminals 4 924 274 260

RJ45 4 909 320 336

LSA 20 907 401 232

+ 907 498 + 907 470

FDDI, CDDI RJ45 8 929 100 / 110 254

RJ45 8 929 121 255

RJ45, LSA / RJ45 8 x 8 929 035 / 036 249

RJ45 8 x 8 929 037 249

RJ45 4 909 321 337

Industrial Ethernet LSA 20907 401

232+ 907 498 + 907 470

RJ45 8 929 100 / 110 254

RJ45 8 929 121 255

RJ45, LSA / RJ45 8 x 8 929 035 / 036 249

RJ45 8 x 8 929 037 249

RJ45 4 909 321 337

Power over Ethernet RJ45 8 929 100 / 110 254

PoVRJ45 8 929 121 255

RJ45 8 x 8 929 037 2494

2

2

2

4

3

2

2

1

2

4

3

2

2

1

2

2

2

4

3

2

2

2

4

3

2

2

2

2

Data networks

LifeCheck SPD-

Protected class

Interface/Signal For mounting on Connection system lines SPD Part No. PageTYPE

Page 173: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 173/382

INFORMATION TECHNOLOGY SYSTEMS

171www.dehn.de

Easy Choice according to Interface / Signal

Token Ring LSA 20907 401

232+ 907 498 + 907 470

RJ45 8 929 100 / 110 254

RJ45 8 929 121 255

RJ45, LSA / RJ45 8 x 8 929 035 / 036 249

RJ45 8 x 8 929 037 249

RJ45 4 909 321 337

V 24 (RS 232 C) screw terminals 4 1 920 322 + 920 300 188

spring terminals 2 919 921 210

LSA 20907 401

232+ 907 498 + 907 421

D-Sub 9-, 25-pole 4, 9 924 046 / 061 288

D-Sub 9-, 25-pole 9 924 018 / 019 283

VG AnyLAN RJ45 8 929 100 / 110 254

RJ45 8 929 121 255

RJ45, LSA / RJ45 8 x 8 929 035 / 036 249

RJ45 8 x 8 929 037 249

RJ45 4 909 321 337

Voice over IP RJ45 8 929 100 / 110 254

RJ45 8 x 8 929 037 249

RJ45 4 909 321 3372

4

2

2

4

3

2

2

4

2

1

2

1

2

4

3

2

2

1

Data networks

LifeCheck SPD-

Protected class

Interface/Signal For mounting on Connection system lines SPD Part No. PageTYPE

JokeractiVsense®

JJ

J JFor further details please refer to page 174

Page 174: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 174/382

INFORMATION TECHNOLOGY SYSTEMS

172 www.dehn.de

Easy Choice according to Interface / Signal

AMPS, NADAC BNC 1 d.c. – 4 GHz 929 042 274(824 – 894 MHz)

BNC 1 d.c. – 1 GHz 929 043 275

N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 d.c. – 2.5 GHz 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 929 446 276

7/16 Connector 1 880 – 2200 MHz 929 048 277

BWA (Broadband BNC 1 d.c. – 4 GHz 929 042 274

Wireless Access) N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 2.0 – 6.0 GHz 929 059 278

CATV F Connector 1 d.c., 5 – 2400 MHz 909 705 272

IEC / F Connector 1 d.c. – 2400 MHz 909 300 334

DCS 1800 B162 BNC 1 d.c. – 4 GHz 929 042 274

(1710 – 1880 MHz)N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 d.c. – 2.5 GHz 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 929 446 276

7/16 Connector 1 880 – 2200 MHz 929 048 277

DCF 77 BNC 1 d.c. – 4 GHz 929 042 274

BNC 1 d.c. – 1 GHz 929 043 275

GPS (1565 – 1585 MHz) BNC 1 d.c. – 4 GHz 929 042 274

N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 d.c. – 2.5 GHz 929 045 275

7/16 Connector 1 d.c., 806 – 2300 MHz 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 929 446 276

7/16 Connector 1 880 – 2200 MHz 929 048 277

GSM 900, GSMR BNC 1 d.c. – 4 GHz 929 042 274

(876 – 960 MHz)BNC 1 d.c. – 1 GHz 929 043 275

N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 d.c. – 2.5 GHz 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 929 446 276

7/16 Connector 1 880 – 2200 MHz 929 048 2771

1

1

1

2

1

2

1

1

1

1

2

2

1

2

1

1

1

1

2

2

2

1

1

2

2

1

1

1

1

2

1

2

Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems

SPD-

Protected Frequency class

Interface/Signal For mounting on Connection system lines range SPD Part No. PageTYPE

Page 175: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 175/382

INFORMATION TECHNOLOGY SYSTEMS

173www.dehn.de

Easy Choice according to Interface / Signal

Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems

SPD-

Protected Frequency class

Interface/Signal For mounting on Connection system lines range SPD Part No. PageTYPE

PCS 1900 BNC 1 d.c. – 4 GHz 929 042 274(1850 – 1990 MHz)

N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 d.c. – 2.5 GHz 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 929 446 276

7/16 Connector 1 880 – 2200 MHz 929 048 277

Radio systems BNC 1 d.c. – 4 GHz 929 042 274

BNC 1 d.c. – 1 GHz 929 043 275

N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 d.c. – 2.5 GHz 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 929 446 276

U Connector 1 d.c. - 300 MHz 929 057 235

7/16 Connector 1 380 – 512 MHz 929 047 277

7/16 Connector 1 880 – 2200 MHz 929 048 277

N Connector 1 2,0 – 6,0 GHz 929 059 278

SAT F Connector 1 d.c., 5 – 2400 MHz 909 705 272

Sky DSL F Connector 1 d.c., 5 – 2400 MHz 909 705 272

TETRA, NMT 450 BNC 1 d.c. – 4 GHz 929 042 274

(380 – 512 MHz)BNC 1 d.c. – 1 GHz 929 043 275

N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 d.c. – 2.5 GHz 929 045 275

7/16 Connector 1 380 – 512 MHz 929 047 277

TV F Connector 1 d.c., 5 – 3000 MHz 909 703 272

F Connector 1 d.c. – 2400 MHz 909 704 272

F Connector 1 d.c., 5 – 2400 MHz 909 705 272

IEC / F Connector 1 d.c. – 2400 MHz 909 300 3342

1

1

3

1

1

2

1

2

1

1

1

1

1

1

1

1

1

2

1

2

1

1

1

1

2

2

JokeractiVsense®

JJ

J JFor further details please refer to page 174

Page 176: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 176/382

INFORMATION TECHNOLOGY SYSTEMS

174 www.dehn.de

JokeractiVsense®

JJ

J J

BLITZDUCTOR® XTUUniversal lightning current / surge arrester with actiVsense® technology

• Automatically detects the operating voltage• Optimally adjusts the voltage protection level to the voltage currently applied

Application:

• Suitable fo the vast majority of applications in information technology systems

• Ideally suited for telecommunications systems, bus systems and measuring and control equipment

The nominal current of the SPD is limited to 100 mA, allowing the device to be used for the vast majority of applicationsin information technology systems. In some applications where the signal line is also used for power supply the currentmay exceed 100 mA.

All signals are transmitted with signal frequencies up to 25 MHz.

In bus systems the SPD can be used for applications based on RS 485 / RS 422 interfaces (not RS 232).

For more detailed information, please refer to page 179.

Easy Choice according to Interface / Signal

Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems

SPD-

Protected Frequency class

Interface/Signal For mounting on Connection system lines range SPD Part No. PageTYPE

UMTS BNC 1 d.c. – 4 GHz 929 042 274

N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 d.c. – 2.5 GHz 929 045 275

7/16 Connector 1 d.c., 806 – 2200 MHz 929 046 276

7/16 Connector 1 d.c., 806 – 2200 MHz 929 446 276

7/16 Connector 1 880 – 2200 MHz 929 048 277

WiMax N Connector 1 2.0 – 6.0 GHz 929 059 278

WLAN (2.4 GHz band) BNC 1 d.c. – 4 GHz 929 042 274

N Connector 1 d.c. – 5.8 GHz 929 044 274

WLAN (5 GHz band) N Connector 1 d.c. – 5.8 GHz 929 044 274

N Connector 1 2.0 – 6.0 GHz 929 059 278

Video (2-wire) screw terminals 4 d.c. – 100 MHz 920 370 + 920 300 192

RJ45 8 d.c. – 250 MHz 929 100 / 110 254

RJ45 8 d.c. – 250 MHz 929 121 255

screw terminals 2 d.c. – 100 MHz 920 270 + 920 300 198

RJ45 4 909 321 337

Video (coax) BNC 1 d.c. – 300 MHz 929 010 268

BNC 1 0 – 300 MHz 909 710 / 711 2712

2

2

1

2

2

1

1

2

2

2

1

1

1

1

1

2

2

Page 177: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 177/382175www.dehn.de

SPDs for Information Technology Systems

General

The surge protection components of SPDs have no radioactive isotopesand usually consist of at least one voltage-limiting or voltage-switchingdevice, and sometimes of overcurrent-limiting components as well. SPDsconsisting of several stages, must be designed without blind spot, i.e. it hasto be ensured that the different protective stages are fully coordinatedwith each other. Otherwise, the protective stages will respond only partial-ly and lead to faults within the surge protective device.

Selection of SPDs

When selecting SPDs, the following aspects must be especially taken into

consideration:– Protective effect [Yellow/Line SPD class (discharge capacity and protec-

tion level)]

– System parameters (system voltage, nominal current and transmissionparameters)

– Installation environment (design, connection conditions and certifica-tions)

The selection guide according to interface/signal on pages 156 to 174 shallfacilitate the choice of the right SPD.

Relevant product standard for the SPDs:

IEC 61643-21 / EN 61643-21Low voltage surge protective devices – Part 21: Surge protective devicesconnected to telecommunications and signalling networks – Performancerequirements and testing methods.

Discharge capacity

According to IEC 61643-21 / EN 61643-21, SPDs must be tested with atleast one impulse voltage or impulse current as mentioned in thefollowing table, with the indicated number of impulses. Further tests canbe performed – even with different pulse amplitudes or quantities. Themaximum protection level during this or these tests is indicatedas voltage protection level UP measured at the output of the device.Category C represents especially disturbing pulses with a steep rate of rise

and less energy, compared to the disturbing pulses of category D, which issupposed to simulate high energy loads due to induced partial lightningcurrents.The category is also indicated in the technical data of the SPDs –both in the description of the discharge capacity (In, Iimp) and protectionlevel (UP).

Cate- Type of Impulse Impulse Minimum quan- Test

gory test voltage current tity of impulses for

C1 0.5 kV or 0.25 kA or 300

1 kV, 1.2/50 µs 0.5 kA, 8/20 µs

C2 steep 2 kV, 4 kV, 1 kA, 2 kA 10

rate of or 10 kV, or 5 kA,

rise 1.2/50 µs 8/20 µs

C3 1 kV, 10 A, 25 A 300

1 kV/µs or 100 A,

10/1000 µs

D1 high 1 kV 0.5 kA, 1 kA 2

energy or 2.5 kA, *)

10/350 µs

*) Lightning current arrester / Combined lightning current and surge arrester

Voltage and current impulses (preferred values) for determining the voltage limiting

characteristics (based on Table 3 of IEC 61643-21 / EN 61643-21)

Immunity of terminal devices to be protected

Within the scope of the test for electromagnetic compatibility (EMC), elec-trical and electronic equipment (devices) must have a predefined immuni-ty against conducted pulse interferences (surges).Requirements for the immunity and test set-up are specified in EN 61000-4-5.Different electromagnetic environmental conditions make different de-mands on the immunity of the devices. The immunity of a device is linkedto the test level applied. For classifying the different immunities of termi-nal devices, the test levels are subdivided into four different stages. Testlevel 1 includes the minimum requirements for the immunity of the termi-

nal device. Generally, the test level can be taken from the documentationon the device or requested from its manufacturer.

Test levels Corresponds to charging voltage

according to EN 61000-4-5 of the test generator

1 0.5 kV

2 1 kV

3 2 kV

4 4 kV

Protective effect of SPDs

Yellow/Line SPDs for use in IT systems can limit conducted interferences to

safe values to ensure that the immunity of the terminal device is notexceeded. For protecting a terminal device tested for test level 2, a surgearrester with a let-through value below the EMC test values of the termi-nal device has to be chosen:Impulse voltage < 1 kV in combination with a pulse current of someamperes (depending on the coupling network).

S u r g e

a r r e s t e r

INFORMATION TECHNOLOGY SYSTEMS

Page 178: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 178/382176 www.dehn.de

Yellow/Line SPD Classes – Symbols INFORMATION TECHNOLOGY SYSTEMS

terminaldevice

1

lightning currentimmunity severity

acc. to EN 61000-4-5

Use of a combined lightning current and surge arrester

terminaldevice

1

surgeimmunity severity

acc. to EN 61000-4-5

Cascaded use of SPDs

lightning current

M

G O

Energy coordination of Yellow/Lineis independent from the conductor length GO

discharge capacity

G O

SPD suitable for coordinationwith another SPD ( )

decoupling for coordinationwith a further SPD ( )

specific protection of terminal equipment

EN 61000-4-5

Examples for energy coordination of SPDs according to Yellow/Line SPD classes:

All SPD types of the Yellow/Line family for IT systems are assigned a Yellow/Line SPD class and marked correspondingly with a symbol in the technicaldata sheet and on their rating plates. The symbol for the Yellow/Line SPD class graphically connects 3 important characteristics of the SPD and can beone single symbol or a combination of individual symbols:

Characteristics Single symbol Definition

Discharge capacity of an SPDA

Impulse D1 (10/350 µs), lightning impulse current 2.5 kA/ line or 5 kA/total(according to categories from • exceeds the discharge capacity ofB –DIEC 61643-21 / EN 61643-21)

BImpulse C2 (8/20 µs), increased impulse load 2.5 kA/line or 5 kA/total• exceeds the discharge capacity ofC –D

CImpulse C1 (8/20 µs), impulse load 0.25 kA/line or 0.5 kA/total• exceeds the discharge capacity ofD

D Load <C

Protective effect of an SPD Required test level of the terminal device: 1 or higher

(limitation below the test levels

Required test level of the terminal device: 2 or higheraccording to EN 61000-4-5)

Required test level of the terminal device: 3 or higher

Required test level of the terminal device: 4

Energy coordinationk

SPD with decoupling impedance, suitable(with a further Yellow/Line SPD) for coordination with an SPD marked

SPD is suitable for coordination with an SPDwith decoupling impedance k

Page 179: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 179/382

INFORMATION TECHNOLOGY SYSTEMS

177www.dehn.de

LifeCheck® SPD Test

Testing an SPD module via RFID technology (LifeCheck)

SPDdiagnostics with early

warning function!

Regular testing of SPDs installed

During operation, an SPD can be overloaded by discharge processesexceeding the equipment specification. In order to ensure high systemavailability, it is therefore essential to test SPDs on a regular basis.DIN EN 62305-3, supplement 3 (see table excerpt) specifies the maximumintervals between tests of external and internal lightning protection sys-tems.

Protection Visual Complete Complete inspection

level inspection inspection of critical systems

I and II 1 year 2 years 1 year

III and IV 2 years 4 years 1 year

Easy testing with LifeCheck

Maintenance of BLITZDUCTOR XT with integrated LifeCheck is particular-ly easy.LifeCheck uses modern RFID (Radio Frequency Identification) tech-nology for monitoring the protective circuit and for communication.Irrespective of downtimes of the system, LifeCheck allows for quick andeasy testing of SPDs by means of the hand-held DRC LC M3+ reader or astationary DRC MCM XT condition monitoring unit.

Signal before arrester failure

The 3-stage LifeCheck monitoring circuit with early warning functiondetects the extreme electrical or thermal load of all protection elements

of an SPD below their destruction limit. This can be read out within sec-onds and without contact by means a RFID reader. If the reader displays“OK“, no extreme load was detected. If the contrary is the case, the mod-ule has to be replaced as soon as possible in order not to threaten theavailability of the protected circuit.

Functional principal of the LifeCheck diagnostics systems

The diagnostics system consists of two functional units:

1. RFID reading and signalling device (reader)

Combined with a visual and electrical display, an electronic systemtransmits energy without contact to the RFID transponder in the SPD

via antenna. If the operating state can be read out, an “OK“ messageis displayed.

2. Monitoring unit within the SPD:

Diagnostics of the 3-stage LifeCheck monitoring circuit is combinedwith communication of the RFID transponder:

• Diagnostics of electrical overload (impulse current)

Lightning strikes or overvoltage exceeding the specified dischargecapacity of the SPD will damage or even destroy the protection ele-ments.This electrical overload is detected by the LifeCheck monitor-ing device. When reading out the transponder, the ”Replace SPD!”message appears.

• Diagnostics of thermal overload (overheating)

Active and passive protection elements which are operated in the

critical temperature range will be pre-damaged or even destroyeddepending on the type and duration. This overload is detected by theLifeCheck monitoring device.When reading out the transponder, the”Replace SPD!” message appears.

SPD

indicationof operating

state

i d e n t i f i c a t i o n

I C

reader IC micro-controller

power communication

energy

data

Transponder (SPD) Reader (test device)

Principle of communication of an SPD a test device

If LifeCheck monitors a protectivecircuit of an SPD, this is showngraphically in the basic circuit dia-gram. For BXT, the complete protec-tive circuit is monitored.

1

2

protected

3

4

3‘

4‘

• Higher protection and availability of installa-tions and systems due to integrated LifeCheckmonitoring system

– Integrated three-stage monitoring of all circuit

components

– Quick diagnostics of surge protective devices

– Easy testing of SPD modules without downtime via

contactless RFID technology– Even detects previously damaged SPDs

Page 180: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 180/382

INFORMATION TECHNOLOGY SYSTEMS

www.dehn.de178

Page 181: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 181/382179www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XTU

Universal lightning current /surge arrester

• With actiVsense technology

– Automatically detects the operating voltage of

the wanted signal from 0 to 180 V– Optimally adjusts the voltage protection level to

the operating voltage currently applied

– Low voltage protection level, also suited for the

protection of terminal equipment

• Eases your processes

– Reduction of the variety of types

– Only one type of SPD for different signal lines

– Easy planning and storage

– Can be easily retrofitted

Example of use of BLITZDUCTOR XTU.

BLITZDUCTOR XTU combined lightning current and surge arresters for theprotection of information and automation systems stand out due to theirnew, revolutionary technology: The nominal voltage is not specified thus

the arrester can be used for any voltage in the range from 0 to 180 V d.c.Its innovative technology allows the arrester to automatically detect thesignal voltage of the wanted signal and to adjust its protection perform-ance to this voltage. Moreover, it continuously adjusts its voltage protec-tion level to the operating voltage currently applied and is thus ideallysuited for all applications where changing voltages occur.

In case of interference, BLITZDUCTOR XTU arresters always have anadjusted, minimal residual voltage for every signal voltage thus providingmaximum protection for the devices and systems connected to them.

BLITZDUCTOR XTU arresters also considerably reduce planning effortsand minimise storage requirements. Even if it is not known at the plan-

ning stage which voltages are used for signal transmission, BLITZDUCTORXTU arresters now allow to specify a concrete protective device even atthe planning stage thus facilitating procurement and storage at the exe-cution stage of the project.BLITZDUCTOR XTU arresters are also ideally suited to be retrofitted intoexisting systems or to replace existing arresters as it is frequently notentirely clear which types of nominal voltage are to be used.This does notmatter if BLITZDUCTOR XTU arresters are used.

Completely mounted BLITZDUCTOR XTU.Two-part design with base part and SPDmodule. Particularly space-saving, for DIN

rail mounting.

c l i c k

The function-optimised design of the arrester allows both to safely plugthe arrester module into the base part and to remove it without problems.The module is secured in the base part by snapping it in (audible click).When pressing the grey buttons, the module can be removed with littleeffort. This is ensured by the laminated contacts in the base part and therelease spring of the module. A mechanical reverse voltage protectionensures that the module is installed in the correct position.

Page 182: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 182/382180 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

www.dehn.dewww.dehn.de

• Combined lightning current and surge arrester

– Capable of carrying lightning currents up to 10 kA

(10/350 µs)– Low voltage protection level, also suited for the

protection of terminal equipment

– For use in conformity with the lightning protec-

tion zones concept at the boundaries from 0A – 2

and higher

• SPD consists of a protection module and basepart

– Easy replacement of protection modules

– Make-before-break switch contact in the base

part allows removal and insertion without inter-ruption

• With integrated LifeCheck monitoring function

– SPDs can be tested without downtime

– Even detects previously damaged arresters

BLITZDUCTOR XTU arresters are pluggable, multipole and universal DINrail mounted lightning current and surge arresters for the protection of measuring and control circuits, bus systems and telecommunication sys-

tems in which high levels of availability are essential. For effective pro-tection of terminal equipment against lightning effects and surges, BLITZ-DUCTOR XTU arresters combine the permanently high impulse currentdischarge capacity of a lightning current arrester with the low voltageprotection level of a surge arrester which is optimally adjusted to theoperating voltage currently applied.

LifeCheck allows easy and fast testing of SPDs without removing themodule from the system circuit. Integrated into the SPD modules,LifeCheck permanently monitors the proper condition of the SPD and actslike an early warning system, detecting imminent electrical or thermaloverload of the protection components. The LifeCheck status can be readout within a matter of seconds via contactless RFID technology by means

of the portable DEHNrecord LC reader and shows the date of the last testof the SPD module.Stationary installed, a condition monitoring system allows condition-based maintenance of 10 BXT arresters (for more detailed information,please refer to page 359).

The module locking mechanism ensures safe operation, thus the arresterprovides protection against vibration effects and shock loads up to a 30-fold acceleration of gravity.The function-optimised design of the arresterensures both fast and easy replacement of the arrester module whichhouses all relevant protection elements.

A wide range of accessories makes the BLITZDUCTOR XTU arrester partic-ularly user-friendly. Elements for labelling, earthing of unused lines or

easy testing of lines complete the product range.

Testing of an SPD module via RFID technology (LifeCheck)

LifeCheckRFID Symbol

1'3'2'4'

2 4

1 3

Up to four lines can be connected on two levels. For DIN rail mountingpurposes, lines of a pair belonging to each other are connected on top of one another.

2

4

13

2’

4’

1’

3’

1 2 3 4 1´ 2´ 3´ 4´

LifeCheck moduleBXTU ML2 ... S ...

Base partBXT BAS 9

If the line shield cannot be directly earthed on both sides for technical rea-

sons, one-sided indirect shield earthing might be advisable. This can beperformed by using arrester modules of type BXTU ML2 ... S.The terminal3, 3’ is connected to a gas discharge tube which is capable of carryinglightning currents and prevents compensating currents. Transient impulsecurrents on the shield are discharged via indirect shield earthing.

BLITZDUCTOR® XTU

Universal lightning current /surge arrester

Page 183: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 183/382181www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

www.dehn.dewww.dehn.de

BLITZDUCTOR® XTU

BXTU ML4 BD 0-180BXTU ML4 BD 0-180

• Universal voltage type withactiVsense technology

• For installation in compliance withthe lightning protection zones con-cept at the boundaries from 0A – 2and higher

• With integrated LifeCheck monitoring

function

1‘

protected

i

i

i

i

2‘

3‘

4‘

1

2

3

4

9

U>UN

U>UN

Basic circuit diagram BXTU ML4 BD 0-180Dimension drawing BXTU ML4 BD 0-180

Space-saving combined SPD module with actiVsense and LifeCheck technology for protecting2 pairs with the same operating voltage or with a different operating voltage of balanced inter-faces which are galvanically isolated. Automatically detects the operating voltage of the wantedsignal and optimally adjusts the voltage protection level to it.

BXTU ML4 BD 0-180

SPD class MSPD monitoring system LifeCheck

Operating voltage UN 0 - 180 V

Frequency of the operating voltage fUN 400 Hz

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Permissible superimposed signal voltage USignal +/- 5 V

Cut-off frequency line-line (Usignal, balanced 100 ohms) fG 25 MHz

Nominal current at 80° C IL 100 mA

D1 Total lightning impulse current (10/350 µs) I imp 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for In C2 Up see diagram on page 183, line C2

Voltage protection level line-line at 1 kV/µs C3 Up see diagram on page 183, line C3

Voltage protection level line-line for Iimp D1 Up UN + 53 V

Voltage protection level line-PG for C2/C3/D1 550 V

Series impedance per line R 10 ohms; typically 7.5 ohms

Capacitance line-line C 200 pF

Capacitance line-PG C 16 pF

Operating temperature range -40°C...+80°C

Degree of protection (SPD plugged-in) IP 20

Pluggable into BXT BAS base part

Earthing via BXT BAS base part

Enclosure material polyamide PA 6.6Colour yellow

Test standards EN 61643-21

Approvals, Certifications GOST

Ordering information

Type BXTU ML4 BD 0-180

Part No. 920 349

Packing unit 1 pc(s).

N E W

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 183/360/362.

Accessory Part for BLITZDUCTOR® XTU

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BXT BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XTU

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT C onditionMo nit or in gS ys te mL if eC he ck 9 10 69 5

Accessory Part for BLITZDUCTOR® XTU

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of LifeCheck-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC LCM3+

DR C L C M 3 +A bl ei te rp rü fg er ät L if eC he ck 9 10 65 3

Page 184: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 184/382182 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

www.dehn.de

BLITZDUCTOR® XTU

BXTU ML2 BD S 0-180920 249 BXTU ML 2 BD S 0-180

B X TU M L 2 B DS0 -18 0920 249

• Universal voltage type withactiVsense technology

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

• With integrated LifeCheck monitoringfunction

1‘

protected

i

i2‘

3‘

4‘

1

2

3

4

9

U>UN

Basic circuit diagram BXTU ML2 BD S 0-180 Dimension drawing BXTU ML2 BD S 0-180

Space-saving combined SPD module with actiVsense and LifeCheck technology for protecting1 pair. Direct or indirect shield earthing. Automatically detects the operating voltage of the want-ed signal and optimally adjusts the voltage protection level to it.

BXTU ML2 BD S 0-180

SPD class MSPD monitoring system LifeCheck

Operating voltage UN 0 - 180 V

Frequency of the operating voltage fUN 400 Hz

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Permissible superimposed signal voltage USignal +/- 5 V

Cut-off frequency line-line (Usignal, balanced 100 ohms) fG 25 MHz

Nominal current at 80° C IL 100 mA

D1 Total lightning impulse current (10/350 µs) Iimp 9 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kAC2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for In C2 Up see diagram page on 183, line C2

Voltage protection level line-line at 1 kV/µs C3 Up see diagram page on 183, line C3

Voltage protection level line-line for Iimp D1 Up UN + 53 V

Voltage protection level line-PG for C2/C3/D1 550 V

Series impedance per line R 10 ohm(s); typically 7.5 ohm(s)

Capacitance line-line C 200 pF

Capacitance line-PG C 25 pF

Operating temperature range -40°C...+80°C

Degree of protection (SPD plugged-in) IP 20

Pluggable into BXT BAS base part

Earthing via BXT BAS base part

Enclosure material polyamide PA 6.6

Colour yellow

Test standards EN 61643-21

Approvals, Certifications GOST

Ordering information

Type BXTU ML2 BD S 0-180

Part No. 920 249

Packing unit 1 pc(s).

N E W

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 183/360/362.

Accessory Part for BLITZDUCTOR® XTU

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BXT BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XTU

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT Condit ionM on it or in gS ys te mL if eC he ck 91 069 5

Accessory Part for BLITZDUCTOR® XTU

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of LifeCheck-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC LCM3+

DR C L C M 3 +A bl ei te rp rü fg er ät L if eC he ck 9 10 65 3

Page 185: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 185/382183www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

www.dehn.dewww.dehn.de

BLITZDUCTOR® XTU

Diagrams

t [time]

USignal

Operating voltage UN

U

UN

Operating voltage UN and superimposed signal voltageUSignal

20 V 40 V 60 V 80 V 100 V 120 V 140 V 160 V 180 V

50 V

100 V

150 V

200 V

250 V

0 V

C2

UN

C3

Up

UN

Up line-line for In (8/20 µs) C2

Up line-line for 1 kV/µs C3

Operating voltage UN

Voltage protection level Up as a function of the operating voltage UN

BLITZDUCTOR® XT Base Part

BXT BASBXT BAS

• Four-pole version for universal usewith all types of SPD modules

• Allows to plug in and remove themodules without signal interruption

• Universal design without protectionelements

Basic circuit diagram with and without plug-inmodule

Dimension drawing BXT BAS

The BLITZDUCTOR XT base part is a very space-saving, four-pole, universal feed-through terminalfor the insertion of SPD modules without signal interruption. The snap-in mechanism at the sup-porting foot of the base part allows the device to be safely earthed via the DIN rail.As no compo-nents of the protective circuit are situated in the base part, maintenance operation is only requiredfor the protection modules.

BXT BAS

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection type input / output screw / screw

Cross-sectional area, solid 0.08 - 4 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Tightening torque (terminals) 0.4 Nm

Earthing via 35 mm DIN rail acc. to EN 60715

Enclosure material polyamide PA 6.6

Colour yellow

Ex certifications *) ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 Gc

Approvals, Certifications CSA,VdS, UL, GOST

Ordering information

Type BXT BAS

Part No. 920 300

Packing unit 1 pc(s).

*) In combination with certified module

protected

BXT BAS

BXT ML4...

13

1´ 3´

24

2´ 4´

1 2 3 4 1´ 2´ 3´ 4´

BXT BAS protected

13

1´ 3´

24

2´ 4´

1 32 4´ 2´ 3´ 1´ 4

Page 186: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 186/382184 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT

Lightning current / surge arrester

Example of use of BLITZDUCTOR XT with an earthing module (grey). Thelines can be measured by means of the measuring module (grey strings)without disconnecting the clamps.

BLITZDUCTOR XT combined arresters are pluggable, multipole, universalDIN rail mounted lightning current and surge arresters for the protectionof measuring and control circuits, bus systems and telecommunicationsystems. They are particularly suited for installations and systems in whichhigh levels of availability are essential. For effective protection of termi-nal equipment against the effects of lightning and overvoltages, BLITZ-DUCTOR XT arresters combine the permanently high impulse current dis-charge capacity of a lightning current arrester with the low protectionlevel of a surge arrester.LifeCheck allows quick and easy SPD testing without removing the mod-ule. Integrated into the SPD modules, LifeCheck permanently monitors the

proper condition of the SPD and acts like an early warning system,detect-ing imminent electrical or thermal overload of the protection components.The status of the SPD can be read out within a matter of seconds via con-tactless RFID technology by means of the portable DEHNrecord LC read-er. The LifeCheck feature also saves the date of the last test of the SPD

module and indicates it. Stationary installed, the condition monitoringsystem permanently monitors the condition of up to 10 BXT devices (formore detailed information, please refer to page 359).The module locking system ensures safe operation; thus the SPD providesprotection against vibration effects and shock up to a 30-fold accelerationof gravity.The function-optimised design of the device ensures both quickand easy replacement of SPD modules which house all relevant protectionelements.A wide range of accessories makes BLITZDUCTOR XT arresters especiallyuser-friendly. Elements for easy labelling, earthing of unused lines or easytesting of lines complete the product range.

Completely installed BLITZDUCTOR XT.Two-part design with universal base partand application-specific SPD module.Especially space-saving design, for DINrail mounting.

Universal base part accommodates alltypes of SPD modules thereby minimisingstorage requirements and easing prewiringand maintenance operations. The modulescan be easily removed from the base partwithout signal interruption due to make-before-break switch contacts.

Dimension drawing of BLITZDUCTOR XTbase part with plugged-in SPD module.Width: 2/3 modules (12 mm), for DIN rail

mounting in distribution boards.

BXT ML4 B ...:

LifeCheck-equipped SPD modules for 4 sin-gle lines or 2 pairs for high partial lightningcurrents.

BXT ML2 B:LifeCheck-equipped SPD modules for 2 sin-gle lines or 1 pair for high partial lightningcurrents. Type BXT ML2 ... S additionallyprovides contacts for direct or indirectshield earthing.

• Combined lightning current and surge arrester– Maximum discharge capacity for two-, three- or

four-pole interfaces

– Lightning current carrying capacity up to 10 kA

(10/350 µs)

– Low voltage protection level, also suited for the

protection of terminal equipment

• SPD consists of a protection module and basepart– Easy replacement of protection modules with

little effort

– Base part incorporates make-before-break switch

contact for insertion and removal without inter-ruption

– All protection components integrated in the pro-

tection module

• Functional and appealing design– DIN rail mounting with integrated earthing

– Minimum space requirements, 2 pairs over

a width of 2/3 modules

– Vibration- and shock-proof for safe operation

Page 187: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 187/382www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

185www.dehn.de

BLITZDUCTOR® XT

Lightning current / surge arrester

– 20 0 20 40 60 80– 40

N o m i n a l

c u r r e n t I L i n A

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

Ambient temperature in °C

Colour-coded characteristic curves:

BXT ML4 / ML2 ...

BE 5 12 24 36 48 60 180

BD 5 12 24 48 60 180

BC 5 24BE HF 5

BD HF 5 24

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2.0

Maximum nominal current at ambient temperature

c l i c k

The function-optimised design of the device allows both to safely plug theSPD module into the base part and to remove it without problems. Themodule is secured in the base part by snapping it in (audible click). Whenpressing the grey buttons, the module can be removed with little effort.This is ensured by the laminated spring contacts and the module releasespring. A mechanical reverse voltage protection ensures that the moduleis installed in the correct position.

1'3'

2'4'

2 4

1 3

Up to 4 lines can be connected on 2 levels. For DIN rail mounting purpos-

es, lines of a pair belonging to each other are connected on top of oneanother.

ok

protected

!

The protected lines alwayshave to be assigned to termi-nals 1´ to 4´ (protected) of thebase part. In order not to

reduce the protective effect,protected and unprotectedlines have to be installed sep-arately.

The terminals integrated into the basepart can be used with many two-polemodules for shield earthing. Especially forbus systems, the EMC spring terminal

should be used for large-area connectionof line shields.

24

13

2’

4’

1’3’

1 2 3 4 1´ 2´ 3´ 4´

Earthing ModuleBXT M4 E

Base PartBXT BAS 9

In case of a stranded cable,unused lines should be laid and earthed. If theunused lines are connected to base parts, earthing modules of type BXTM4 E should be used. These reserve space for retrofitting the SPD mod-ules and the lines can be integrated efficiently into the equipotentialbonding.

2

4

13

2’

4’

1’

3’

1 2 3 4 1´ 2´ 3´ 4´

LifeCheck moduleBXTU ML2 ... S ...

Base partBXT BAS 9

If the line shield cannot be earthed on both sides for technical reasons,one-sided indirect shield earthing might be advisable. This can be per-

formed by using SPD modules of type BXT ML2 ... S. The terminal 3, 3´ isconnected to a gas discharge tube which is capable of carrying lightningcurrents and prevents compensating currents. Transient impulse currentson the shield are discharged via indirect shield earthing.

General Technical Data for BLITZDUCTOR XT LifeCheck Modules

Degree of protection (plugged-in) IP 20

Pluggable into BLITZDUCTOR XT base part

Earthing by BLITZDUCTOR XT base part

Enclosure material polyamide PA 6.6

Colour yellow

For further types of ”BLITZDUCTOR XT for intrinsically safe circuits" please refer to pages 311-316.

Page 188: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 188/382186 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

www.dehn.de

Module release spring for removing the protectionmodule without problems

The earthing foot ensures cost-effective installation. No additionalearth connection is required since thedevice is safely earthed via the DIN rail

Clear identification of the“protected“ side forfaultless installation

Designation spacefor marking the circuits

Lightning current carryinglaminated contacts

High-quality, four-pole screw terminals for the following cross-sections:stranded: 2.5 mm2

solid: 4 mm2

Reverse polarity protection preventsincorrect insertion of the protectionmodule

Leading/retarded make-before-breakswitch contacts for uninterruptedremoval and insertion without downtime

*) in combination with certified module

BLITZDUCTOR® XT Base Part

BXT BAS920 300 BXT BAS

B X TB AS920 300

• Four-pole version for universal usewith all types of SPD modules

• Allows to plug in and remove themodules without signal interruption

• Universal design without protectionelements

Basic circuit diagram with and without plug-inmodule

Dimension drawing BXT BAS

The BLITZDUCTOR XT base part is a very space-saving, four-pole, universal feed-through terminalfor the insertion of SPD modules without signal interruption. The snap-in mechanism at the sup-porting foot of the base part allows the device to be safely earthed via the DIN rail. As no compo-nents of the protective circuit are situated in the base part, maintenance operation is only requiredfor the protection modules.

BXT BAS

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection type input / output screw / screw

Cross-sectional area, solid 0.08 - 4 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Tightening torque (terminals) 0.4 Nm

Earthing via 35 mm DIN rail acc. to EN 60715

Enclosure material polyamide PA 6.6

Colour yellow

Ex certifications *) ATEX:KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 Gc

Approvals, Certifications CSA,VdS, UL, GOST

Ordering information

Type BXT BAS

Part No. 920 300

Packing unit 1 pc(s).

protected

BXT BAS

BXT ML4...

13

1´ 3´

24

2´ 4´

1 2 3 4 1´ 2´ 3´ 4´

BXT BAS protected

13

1´ 3´

24

2´ 4´

1 32 4´ 2´ 3´ 1´ 4

Page 189: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 189/382187www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

www.dehn.de

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML4 B 180BXT ML4

• LifeCheck SPD monitoring function

• Four-pole lightning equipotentialbonding

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 1 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 B

Space-saving four-pole lightning current arrester module with LifeCheck monitoring function foralmost all types of applications. For use in connection with downstream surge arresters Qor combined lightning current and surge arresters with a lower or equal voltage level.

BXT ML4 B 180

SPD class HSPD monitoring system LifeCheck

Nominal voltage UN 180 V

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Nominal current at 45°C IL 1.2 A

D1 Total lightning impulse current (10/350 µs) I imp 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for Iimp D1 Up 600 V

Voltage protection level line-PG for Iimp D1 Up 550 V

Voltage protection level line-line at 1 kV/µs C3 Up 650 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V

Series impedance per line 0.4 ohm(s)

Capacitance line-line C 16 pF

Capacitance line-PG C 16 pF

Operating temperature range -40°C...+80°C

Test standards IEC 61643-21, UL 497B

SIL classification SIL2 / SIL3

for more details see: www.dehn.de/en/sil/

Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 GcApprovals, Certifications CSA,VdS, GOST

Ordering information

Type BXT ML4 B 180

Part No. 920 310

Packing unit 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BXT BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT C onditionMo nit or in gS ys te mL if eC he ck 9 10 69 5

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of LifeCheck-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC LCM3+

DR C L C M 3 +A bl ei te rp rü fg er ät L if eC he ck 9 10 65 3

Page 190: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 190/382188 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML4 BE 5 – BE 180920 320 BXT ML 4BE5920 322 BXT ML 4BE12920 324 BXT ML 4BE24920 336 BXT ML 4BE36920 325 BXT ML 4BE48920 326 BXT ML 4BE60920 327 BXT ML 4BE180

B X TM L 4 B E 5920 320B X TM L 4 B E 1 2920 322B X TM L 4 B E 2 4920 324B X TM L 4 B E 3 6920 336B X TM L 4 B E 4 8920 325B X TM L 4 B E 6 0920 326B X TM L 4 B E 1 8 0920 327

• LifeCheck SPD monitoring function

• Optimal protection of 4 single lines

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

3‘

4‘

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 BE

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring func-tion for protecting 4 single lines with common reference potential as well as unbalanced interfaces.

BXT ML4 ... BE 5 BE 12 BE 24 BE 36 BE 48 BE 60 BE 180

SPD class M M M M M M LSPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck

Nominal voltage UN 5 V 12 V 24 V 36 V 48 V 60 V 180 V

Max. continuous operating d.c. voltage UC 6.0 V 15 V 33 V 45 V 54 V 70 V 180 V

Max. continuous operating a.c. voltage UC 4.2 V 10.6 V 23.3 V 31 V 38.1 V 49.5 V 127 V

Nominal current at 45°C IL 1.0 A 0.75 A 0.75 A 1.8 A 0.75 A 1.0 A 1.0 A

D1 Total lightning impulse current (10/350 µs) Iimp 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

Voltage protection level line-line for Iimp D1 Up 29 V 50 V 102 V — 160 V 220 V 520 V

Voltage protection level line-PG for Iimp D1 Up 27 V 37 V 66 V 85 V 95 V 125 V 300 V

Voltage protection level line-line at 1 kV/µs C3 Up 18 V 38 V 90 V 112 V 140 V 180 V 500 V

Voltage protection level line-PG at 1 kV/µs C3 Up 9 V 19 V 45 V 56 V 70 V 90 V 250 V

Series impedance per line 1.0 ohm(s) 1.8 ohm(s) 1.8 ohm(s) 0.43 ohm(s) 1.8 ohm(s) 1.0 ohm(s) 1.0 ohm(s)

Cut-off frequency line-PG fG 1.0 MHz 2.7 MHz 6.8 MHz 3.8 MHz 8.7 MHz 9.0 MHz 25.0 MHz

Capacitance line-line C 2.7 nF 1.0 nF 0.5 nF 0.8 nF 0.35 nF 250 pF 120 pF

Capacitance line-PG C 5.4 nF 2.0 nF 1.0 nF 1.6 nF 0.7 nF 500 pF 240 pF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Test standards IEC 61643-21, IEC 61643-21, IEC 61643-21, IEC 61643-21 IEC 61643-21, IEC 61643-21, IEC 61643-21,

UL 497B UL 497B UL 497B –– UL 497B UL 497B UL 497B

SIL classification SIL2 / SIL3

for more details see: www.dehn.de/en/sil/

Ex certifications ATEX:KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 Gc

Approvals, Certifications CSA, VdS, CSA, VdS, CSA, VdS, VdS, CSA, VdS, CSA, VdS, CSA, VdS,

UL, GOST UL, GOST UL, GOST GOST UL, GOST UL, GOST UL, GOST

Ordering information

Type BXT ML4 BE 5 BXT ML4 BE 12 BXT ML4 BE 24 BXT ML4 BE 36 BXT ML4 BE 48 BXT ML4 BE 60 BXT ML4 BE 180

Part No. 920 320 920 322 920 324 920 336 920 325 920 326 920 327

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BX T BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT Condit ionM on it or ing Sy st em Li fe Che ck 91 069 5

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of Life-Check-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC L CM3+

DR C L C M 3 +A bl ei te rp rü fg er ät Li fe Ch ec k 9 10 65 3

Page 191: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 191/382189www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML4 BD 5 – BD 180BXT ML4

BXT ML4

BXT ML4

BXT ML4

BXT ML4

BXT ML4

• LifeCheck SPD monitoring function

• Optimal protection of 2 single pairs

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 BD

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 2 pairs of balanced interfaces which are galvanically isolated.

BXT ML4 ... BD 5 BD 12 BD 24 BD 48 BD 60 BD 180

SPD class M M M M M LSPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck

Nominal voltage UN 5 V 12 V 24 V 48 V 60 V 180 V

Max. continuous operating d.c. voltage UC 6.0 V 15 V 33 V 54 V 70 V 180 V

Max. continuous operating a.c. voltage UC 4.2 V 10.6 V 23.3 V 38.1 V 49.5 V 127 V

Nominal current at 45°C IL 1.0 A 1.0 A 1.0 A 1.0 A 1.0 A 0.75 A

D1 Total lightning impulse current (10/350 µs) I imp 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

Voltage protection level line-line for Iimp D1 Up 25 V 26 V 52 V 80 V 110 V 270 V

Voltage protection level line-PG for Iimp D1 Up 550 V 550 V 550 V 550 V 550 V 550 V

Voltage protection level line-line at 1 kV/µs C3 Up 9 V 19 V 45 V 70 V 90 V 250 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V 550 V 550 V 550 V 550 V 550 V

Series impedance per line 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s) 1.8 ohm(s)

Cut-off frequency line-line fG 1.0 MHz 2.8 MHz 7.8 MHz 8.7 MHz 11.0 MHz 25.0 MHz

Capacitance line-line C 5.4 nF 2.0 nF 1.0 nF 0.7 nF 500 pF 240 pF

Capacitance line-PG C 16 pF 16 pF 16 pF 16 pF 16 pF 16 pF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Test standards IEC 61643-21, IEC 61643-21, IEC 61643-21, IEC 61643-21, IEC 61643-21, IEC 61643-21,

UL 497B UL 497B UL 497B UL 497B UL 497B UL 497B

SIL classification SIL2 / SIL3

for more details see: www.dehn.de/en/sil

Ex certifications ATEX:KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 Gc

Approvals, Certifications CSA, VdS, CSA, VdS, CSA, VdS, CSA, VdS, CSA, VdS, CSA, VdS,

UL, GOST UL, GOST UL, GOST UL, GOST UL, GOST UL, GOST

Ordering information

Type BXT ML4 BD 5 BXT ML4 BD 12 BXT ML4 BD 24 BXT ML4 BD 48 BXT ML4 BD 60 BXT ML4 BD 180

Part No. 920 340 920 342 920 344 920 345 920 346 920 347

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Test / Disconnection ModuleModule for testing lines, to be plugged into

the BLITZDUCTOR XT base part.PU Part

Type pc(s). No.

BXT M4 T 1 920 309

920 309 BXT M4 T

BXT M4 T BXT-Prüf-

/Trennm odul 920 309

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Earthing moduleFor direct earthing of lines connected to the

BLITZDUCTOR XT base part.

PU PartType pc(s). No.

BXT M4 E 1 920 308

920 308 BXT M4 E

BXT M4 E BXT-

Erdungsm odul 920 308

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Marking system BA1-BA152 x 165 adhesive labels for labelling DRC MCM

XT monitoring devices with their bus addresses.

PU PartType pc(s). No.

BS BA1 BA15 BXT 1 920 398

920 398 BS BA1BA15BXT

BSBA1BA15BXTB ez ei ch nu ng ss ys te mf ür BX T 9 20 39 8

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Page 192: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 192/382190 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML4 BC 5 / 24920 350 BXT ML 4BC5920 354 BXT ML 4B C 2 4

B X TM L 4 B C 5920 350B X TM L 4 B C 2 4920 354

• LifeCheck SPD monitoring function

• Optimal protection of max. 4 lines

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 BC

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting max. 4 earth-potential-free single lines with common reference potential.

BXT ML4 BC 5 BXT ML4 BC 24

SPD class M MSPD monitoring system LifeCheck LifeCheck

Nominal voltage UN 5 V 24 V

Max. continuous operating d.c. voltage UC 6.0 V 33 V

Max. continuous operating a.c. voltage UC 4.2 V 23.3 V

Nominal current at 45°C IL 1.0 A 0.75 A

D1 Total lightning impulse current (10/350 µs) Iimp 10 kA 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA 10 kA

Voltage protection level line-line for Iimp D1 Up 25 V 55 VVoltage protection level line-PG for Iimp D1 Up 550 V 550 V

Voltage protection level line-line at 1 kV/µs C3 Up 9 V 45 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V 550 V

Series impedance per line 1.0 ohm(s) 1.8 ohm(s)

Cut-off frequency line-line fG 1.0 MHz 5.7 MHz

Capacitance line-line C 5.4 nF 1.0 nF

Capacitance line-PG C 16 pF 16 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Test standards IEC 61643-21,UL 497B IEC 61643-21,UL 497B

SIL classification SIL2 / SIL3 SIL2 / SIL3

for more details see: www.dehn.de/en/sil/ for more details see: www.dehn.de/en/sil/

Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4 ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 Gc IECEx KEM 09.0053X: Ex nA II T4 GcApprovals, Certifications CSA,VdS, GOST CSA,VdS, GOST

Ordering information

Type BXT ML4 BC 5 BXT ML4 BC 24

Part No. 920 350 920 354

Packing unit 1 pc(s). 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BX T BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT Condit ionM on it or ing Sy st em Li fe Che ck 91 069 5

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of Life-Check-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC L CM3+

DR C L C M 3 +A bl ei te rp rü fg er ät Li fe Ch ec k 9 10 65 3

Page 193: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 193/382191www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML4 BE C 12 / 24BXT ML4

BXT ML4

• LifeCheck SPD monitoring function

• Additional decoupling to the terminalequipment

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 BE C

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 2 pairs of balanced interfaces with protective diode circuit at the input, cur-rent loops (TTY) and optocoupler inputs.

BXT ML4 BE C 12 BXT ML4 BE C 24

SPD class M MSPD monitoring system LifeCheck LifeCheck

Nominal voltage UN 12 V 24 V

Max. continuous operating d.c. voltage UC 15 V 33 V

Max. continuous operating a.c. voltage UC 10.6 V 23.3 V

Nominal current at 80°C IL 0.1 A 0.1 A

D1 Total lightning impulse current (10/350 µs) I imp 10 kA 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA 10 kA

Voltage protection level line-line for Iimp D1 Up 30 V 52 VVoltage protection level line-PG for Iimp D1 Up 35 V 66 V

Voltage protection level line-line at 1 kV/µs C3 Up 19 V 45 V

Voltage protection level line-PG at 1 kV/µs C3 Up 19 V 45 V

Series impedance per line 13.8 ohm(s) 28.8 ohm(s)

Cut-off frequency line-PG fG 1.57 MHz 1.7 MHz

Capacitance line-line C 3.2 nF 1.5 nF

Capacitance line-PG C 3.2 nF 1.5 nF

Operating temperature range -40°C ... +80°C -40°C...+80°C

Test standards IEC 61643-21 IEC 61643-21,UL 497B

SIL classification SIL2 / SIL3 SIL2 / SIL3

for more details see: www.dehn.de/en/sil/ for more details see: www.dehn.de/en/sil/

Ex certifications ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4 ATEX:KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 Gc IECEx KEM 09.0053X: Ex nA II T4 GcApprovals, Certifications GOST CSA,VdS, GOST

Ordering information

Type BXT ML4 BE C 12 BXT ML4 BE C 24

Part No. 920 362 920 364

Packing unit 1 pc(s). 1 pc(s).

N E W

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Test / Disconnection ModuleModule for testing lines, to be plugged into

the BLITZDUCTOR XT base part.PU Part

Type pc(s). No.

BXT M4 T 1 920 309

920 309 BXT M4 T

BXT M4 T BXT-Prüf-

/Trennm odul 920 309

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Earthing moduleFor direct earthing of lines connected to the

BLITZDUCTOR XT base part.

PU PartType pc(s). No.

BXT M4 E 1 920 308

920 308 BXT M4 E

BXT M4 E BXT-

Erdungsm odul 920 308

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Marking system BA1-BA152 x 165 adhesive labels for labelling DRC MCM

XT monitoring devices with their bus addresses.

PU PartType pc(s). No.

BS BA1 BA15 BXT 1 920 398

920 398 BS BA1BA15BXT

BSBA1BA15BXTB ez ei ch nu ng ss ys te mf ür BX T 9 20 39 8

Page 194: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 194/382192 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML4 BE HF 5920 370 BXT ML 4B E HF5

B X TM L 4 B E HF5920 370

• LifeCheck SPD monitoring function

• Optimal protection of 4 single lines

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 BE HF

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 4 single lines with common reference potential as well as high-frequencytransmissions without electrical isolation.

BXT ML4 BE HF 5

SPD class MSPD monitoring system LifeCheck

Nominal voltage UN 5 V

Max. continuous operating d.c. voltage UC 6.0 V

Max. continuous operating a.c. voltage UC 4.2 V

Nominal current at 45°C IL 1.0 A

D1 Total lightning impulse current (10/350 µs) Iimp 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for Iimp D1 Up 26 VVoltage protection level line-PG for Iimp D1 Up 40 V

Voltage protection level line-line at 1 kV/µs C3 Up 11 V

Voltage protection level line-PG at 1 kV/µs C3 Up 11 V

Series impedance per line 1.0 ohm(s)

Cut-off frequency line-PG fG 100.0 MHz

Capacitance line-line C 20 pF

Capacitance line-PG C 25 pF

Operating temperature range -40°C...+80°C

Test standards IEC 61643-21, UL 497B

SIL classification SIL2

for more details see: www.dehn.de/en/sil/

Ex certifications ATEX:KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 GcApprovals, Certifications CSA,VdS, UL, GOST

Ordering information

Type BXT ML4 BE HF 5

Part No. 920 370

Packing unit 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BX T BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT Condit ionM on it or ing Sy st em Li fe Che ck 91 069 5

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of Life-Check-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC L CM3+

DR C L C M 3 +A bl ei te rp rü fg er ät Li fe Ch ec k 9 10 65 3

Page 195: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 195/382193www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML4 BD HF 5 / 24BXT ML4

BXT ML4

• LifeCheck SPD monitoring function

• Minimum signal disturbance

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 BD HF

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 2 pairs in high-frequency bus systems or video transmission systems.

BXT ML4 BD HF 5 BXT ML4 BD HF 24

SPD class M MSPD monitoring system LifeCheck LifeCheck

Nominal voltage UN 5 V 24 V

Max. continuous operating d.c. voltage UC 6.0 V 33 V

Max. continuous operating a.c. voltage UC 4.2 V 23.3 V

Nominal current at 45°C IL 1.0 A 1.0 A

D1 Total lightning impulse current (10/350 µs) I imp 10 kA 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA 10 kA

Voltage protection level line-line for Iimp D1 Up 25 V 65 VVoltage protection level line-PG for Iimp D1 Up 550 V 550 V

Voltage protection level line-line at 1 kV/µs C3 Up 11 V 47 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V 550 V

Series impedance per line 1.0 ohm(s) 1.0 ohm(s)

Cut-off frequency line-line fG 100.0 MHz 100.0 MHz

Capacitance line-line C 25 pF 25 pF

Capacitance line-PG C 16 pF 16 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Test standards IEC 61643-21,UL 497B IEC 61643-21,UL 497B

SIL classification SIL2 SIL2

for more details see: www.dehn.de/en/sil/ for more details see: www.dehn.de/en/sil/

Ex certifications ATEX:KEMA 09ATEX0114 X: II 3 G Ex nA II T4 c ATEX:KEMA 09ATEX0114 X: II 3 G Ex nA II T4

IECEx KEM 09.0053X: Ex nA II T4 Gc IECEx KEM 09.0053X: Ex nA II T4 GcApprovals, Certifications CSA,VdS, UL, GOST CSA,VdS, UL, GOST

Ordering information

Type BXT ML4 BD HF 5 BXT ML4 BD HF 24

Part No. 920 371 920 375

Packing unit 1 pc(s). 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Test / Disconnection ModuleModule for testing lines, to be plugged into

the BLITZDUCTOR XT base part.PU Part

Type pc(s). No.

BXT M4 T 1 920 309

920 309 BXT M4 T

BXT M4 T BXT-Prüf-

/Trennm odul 920 309

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Earthing moduleFor direct earthing of lines connected to the

BLITZDUCTOR XT base part.

PU PartType pc(s). No.

BXT M4 E 1 920 308

920 308 BXT M4 E

BXT M4 E BXT-

Erdungsm odul 920 308

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Marking system BA1-BA152 x 165 adhesive labels for labelling DRC MCM

XT monitoring devices with their bus addresses.

PU PartType pc(s). No.

BS BA1 BA15 BXT 1 920 398

920 398 BS BA1BA15BXT

BSBA1BA15BXTB ez ei ch nu ng ss ys te mf ür BX T 9 20 39 8

Page 196: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 196/382194 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML4 MY 250920 389 BXT ML4 MY 250

B X TM L 4 M Y 2 5 0920 389

• LifeCheck SPD monitoring function

• Distinctive “Y” circuit

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 MY

Space-saving surge arrester module with LifeCheck monitoring function for protecting 4 lines of stranded signal interfaces up to 250 V a.c.

BXT ML4 MY 250

SPD class VSPD monitoring system LifeCheck

Nominal voltage UN 250 V

Max. continuous operating d.c. voltage UC line - PG 320 V

Max. continuous operating a.c. voltage UC line - PG 250 V

Nominal current at 45°C IL 3.0 A

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 2.5 kA

Voltage protection level line-line for In C2 Up 1700 V

Voltage protection level line-PG for In C2 Up 1300 VVoltage protection level line-line at 1 kV/µs C3 Up 1100 V

Voltage protection level line-PG at 1 kV/µs C3 Up 1200 V

Cut-off frequency line-line fG 20 MHz

Capacitance line-line C 300 pF

Capacitance line-PG C 16 pF

Operating temperature range -40°C...+80°C

Test standards IEC 61643-21

SIL classification SIL2

for more details see: www.dehn.de/en/sil/

Approvals, Certifications GOST

Ordering information

Type BXT ML4 MY 250

Part No. 920 389

Packing unit 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BX T BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT Condit ionM on it or ing Sy st em Li fe Che ck 91 069 5

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of Life-Check-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC L CM3+

DR C L C M 3 +A bl ei te rp rü fg er ät Li fe Ch ec k 9 10 65 3

Page 197: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 197/382195www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML2 B 180BXT ML2 B 180

• LifeCheck SPD monitoring function

• Two-pole lightning equipotentialbonding with 4 terminals for shieldand/or functional earthing

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 1 and higher

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 B

Space-saving two-pole lightning current arrester module with LifeCheck monitoring function andshield earthing for almost all applications. For use in connection with downstream surge arresters

Q or combined lightning current and surge arresters with a lower or equal voltage level.

BXT ML2 B 180

SPD class HSPD monitoring system LifeCheck

Nominal voltage UN 180 V

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Nominal current at 45°C IL 1.2 A

D1 Total lightning impulse current (10/350 µs) I imp 10 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kAVoltage protection level line-line for Iimp D1 Up 600 V

Voltage protection level line-PG for Iimp D1 Up 550 V

Voltage protection level line-line at 1 kV/µs C3 Up 650 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V

Series impedance per line 0.4 ohm(s)

Capacitance line-line C 16 pF

Capacitance line-PG C 16 pF

Operating temperature range -40°C...+80°C

Test standards IEC 61643-21

SIL classification SIL2 / SIL3

for more details see: www.dehn.de/en/sil/

Approvals, Certifications CSA, GOST

Ordering information

Type BXT ML2 B 180

Part No. 920 211

Packing unit 1 pc(s).

N E W

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Test / Disconnection ModuleModule for testing lines, to be plugged into

the BLITZDUCTOR XT base part.PU Part

Type pc(s). No.

BXT M4 T 1 920 309

920 309 BXT M4 T

BXT M4 T BXT-Prüf-

/Trennm odul 920 309

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Earthing moduleFor direct earthing of lines connected to the

BLITZDUCTOR XT base part.

PU PartType pc(s). No.

BXT M4 E 1 920 308

920 308 BXT M4 E

BXT M4 E BXT-

Erdungsm odul 920 308

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Marking system BA1-BA152 x 165 adhesive labels for labelling DRC MCM

XT monitoring devices with their bus addresses.

PU PartType pc(s). No.

BS BA1 BA15 BXT 1 920 398

920 398 BS BA1BA15BXT

BSBA1BA15BXTB ez ei ch nu ng ss ys te mf ür BX T 9 20 39 8

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Page 198: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 198/382196 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML2 BD 180920 247 BXT ML2BD180

B X TM L 2 B D1 8 0920 247

• LifeCheck SPD monitoring function

• Optimal protection of 1 pair

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

3

4

protected

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BD

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 1 pair of balanced interfaces which are galvanically isolated.

BXT ML2 BD 180

SPD class LSPD monitoring system LifeCheck

Nominal voltage UN 180 V

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Nominal current at 45°C IL 0.75 A

D1 Total lightning impulse current (10/350 µs) Iimp 5 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kAVoltage protection level line-line for Iimp D1 Up 270 V

Voltage protection level line-PG for Iimp D1 Up 550 V

Voltage protection level line-line at 1 kV/µs C3 Up 250 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V

Series impedance per line 1.8 ohm(s)

Cut-off frequency line-line fG 25.0 MHz

Capacitance line-line C 240 pF

Capacitance line-PG C 16 pF

Operating temperature range -40°C...+80°C

Test standards IEC 61643-21

SIL classification SIL2 / SIL3

for more details see: www.dehn.de/en/sil/

Approvals, Certifications CSA,GOST

Ordering information

Type BXT ML2 BD 180

Part No. 920 247

Packing unit 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BX T BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT Condit ionM on it or ing Sy st em Li fe Che ck 91 069 5

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of Life-Check-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC L CM3+

DR C L C M 3 +A bl ei te rp rü fg er ät Li fe Ch ec k 9 10 65 3

Page 199: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 199/382197www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML2 BD S 5 – BD S 48BXT ML2

BXT ML2

BXT ML2

BXT ML2

• LifeCheck SPD monitoring function

• Optimal protection of 1 pair andshield

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BD

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 1 pair of balanced interfaces which are galvanically isolated, available withdirect or indirect shield earthing.

BXT ML2 BD S 5 BXT ML2 BD S 12 BXT ML2 BD S 24 BXT ML2 BD S 48

SPD class M M M MSPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck

Nominal voltage UN 5 V 12 V 24 V 48 V

Max. continuous operating d.c. voltage UC 6.0 V 15 V 33 V 54 V

Max. continuous operating a.c. voltage UC 4.2 V 10.6 V 23.3 V 38.1 V

Nominal current at 45°C IL 1.0 A 1.0 A 1.0 A 1.0 A

D1 Total lightning impulse current (10/350 µs) I imp 9 kA 9 kA 9 kA 9 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA 10 kA 10 kA 10 kAVoltage protection level line-line for Iimp D1 Up 25 V 26 V 52 V 80 V

Voltage protection level line-PG for Iimp D1 Up 550 V 550 V 550 V 550 V

Voltage protection level line-line at 1 kV/µs C3 Up 9 V 19 V 45 V 70 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V 550 V 550 V 550 V

Series impedance per line 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s) 1.0 ohm(s)

Cut-off frequency line-line fG 1.0 MHz 2.8 MHz 7.8 MHz 8.7 MHz

Capacitance line-line C 5.4 nF 2.0 nF 1.0 nF 0.7 nF

Capacitance line-PG C 25 pF 25 pF 25 pF 25 pF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21

SIL classification SIL2 / SIL3

for more details see: www.dehn.de/en/sil/

Approvals, Certifications CSA,GOST CSA, GOST CSA, GOST CSA, GOST

Ordering information

Type BXT ML2 BD S 5 BXT ML2 BD S 12 BXT ML2 BD S 24 BXT ML2 BD S 48

Part No. 920 240 920 242 920 244 920 245

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Test / Disconnection ModuleModule for testing lines, to be plugged into

the BLITZDUCTOR XT base part.PU Part

Type pc(s). No.

BXT M4 T 1 920 309

920 309 BXT M4 T

BXT M4 T BXT-Prüf-

/Trennm odul 920 309

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Earthing moduleFor direct earthing of lines connected to the

BLITZDUCTOR XT base part.

PU PartType pc(s). No.

BXT M4 E 1 920 308

920 308 BXT M4 E

BXT M4 E BXT-

Erdungsm odul 920 308

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Marking system BA1-BA152 x 165 adhesive labels for labelling DRC MCM

XT monitoring devices with their bus addresses.

PU PartType pc(s). No.

BS BA1 BA15 BXT 1 920 398

920 398 BS BA1BA15BXT

BSBA1BA15BXTB ez ei ch nu ng ss ys te mf ür BX T 9 20 39 8

Page 200: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 200/382198 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML2 BD DL S 15920 243 BXT ML 2 BD DL S 15

B X TM L 2 B DDL S1 5920 243

• Suitable for Dupline buses

• LifeCheck SPD monitoring function

• Effective protection for 1 pair andshield

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BD

Space-saving LifeCheck-equipped combined SPD module for protecting 1 pair of balanced and gal-vanically isolated interfaces, which specifically fulfils the requirements of Dupline buses, direct orindirect shield earthing.

BXT ML2 BD DL S 15

SPD class MSPD monitoring system LifeCheck

Nominal voltage UN 15 V

Max. continuous operating d.c. voltage UC 17 V

Max. continuous operating a.c. voltage UC 12 V

Nominal current at 70° C IL 0.4 A

D1 Total lightning impulse current (10/350 µs) Iimp 9 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for Iimp D1 Up 30 V

Voltage protection level line-PG for Iimp D1 Up 550 V

Voltage protection level line-line for In C2 Up 35 V

Voltage protection level line-PG for In C2 Up 600 V

Voltage protection level line-line at 1 kV/µs C3 Up 24 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V

Series impedance per line 2.2 ohm(s)

Cut-off frequency line-line fG 2.7 MHz

Capacitance line-line C 1.9 nF

Capacitance line-PG C 25 pF

Operating temperature range -40°C...+80°C

Test standards IEC 61643-21

SIL classification SIL2 / SIL3for more details see: www.dehn.de/en/sil/

Approvals, Certifications GOST

Ordering information

Type BXT ML2 BD DL S 15

Part No. 920 243

Packing unit 1 pc(s).

N E W

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BX T BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT Condit ionM on it or ing Sy st em Li fe Che ck 91 069 5

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of Life-Check-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC L CM3+

DR C L C M 3 +A bl ei te rp rü fg er ät Li fe Ch ec k 9 10 65 3

Page 201: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 201/382199www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML2 BE S 5 – BE S 48BXT ML2

BXT ML2

BXT ML2

BXT ML2

• LifeCheck SPD monitoring function

• Optimal protection of 2 single linesand shield

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BE

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 2 single lines with common reference potential as well as unbalanced inter-faces, available with direct or indirect shield earthing.

BXT ML2 BE S 5 BXT ML2 BE S 12 BXT ML2 BE S 24 BXT ML2 BE S 48

SPD class M M M MSPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck

Nominal voltage UN 5 V 12 V 24 V 48 V

Max. continuous operating d.c. voltage UC 6.0 V 15 V 33 V 54 V

Max. continuous operating a.c. voltage UC 4.2 V 10.6 V 23.3 V 38.1 V

Nominal current for 45°C IL 1.0 A 0.75 A 0.75 A 0.75 A

D1 Total lightning impulse current (10/350 µs) I imp 9 kA 9 kA 9 kA 9 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA 10 kA 10 kA 10 kA

Voltage protection level line-line for Iimp D1 Up 29 V 50 V 102 V 160 V

Voltage protection level line-PG for Iimp D1 Up 27 V 37 V 66 V 95 V

Voltage protection level line-line at 1 kV/µs C3 Up 18 V 38 V 90 V 140 V

Voltage protection level line-PG at 1 kV/µs C3 Up 9 V 19 V 45 V 70 V

Series impedance per line 1.0 ohm(s) 1.8 ohm(s) 1.8 ohm(s) 1.8 ohm(s)

Cut-off frequency line-PG fG 1.0 MHz 2.7 MHz 6.8 MHz 8.7 MHz

Capacitance line-line C 2.7 nF 1.0 nF 0.5 nF 0.35 nF

Capacitance line-PG C 5.4 nF 2.0 nF 1.0 nF 0.7 nF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21

SIL classification SIL2 / SIL3

for more details see: www.dehn.de/en/sil/

Approvals, Certifications CSA, GOST CSA, GOST CSA, GOST CSA, UL, GOST

Ordering information

Type BXT ML2 BE S 5 BXT ML2 BE S 12 BXT ML2 BE S 24 BXT ML2 BE S 48

Part No. 920 220 920 222 920 224 920 225

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Test / Disconnection ModuleModule for testing lines, to be plugged into

the BLITZDUCTOR XT base part.PU Part

Type pc(s). No.

BXT M4 T 1 920 309

920 309 BXT M4 T

BXT M4 T BXT-Prüf-

/Trennm odul 920 309

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Earthing moduleFor direct earthing of lines connected to the

BLITZDUCTOR XT base part.

PU PartType pc(s). No.

BXT M4 E 1 920 308

920 308 BXT M4 E

BXT M4 E BXT-

Erdungsm odul 920 308

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Marking system BA1-BA152 x 165 adhesive labels for labelling DRC MCM

XT monitoring devices with their bus addresses.

PU PartType pc(s). No.

BS BA1 BA15 BXT 1 920 398

920 398 BS BA1BA15BXT

BSBA1BA15BXTB ez ei ch nu ng ss ys te mf ür BX T 9 20 39 8

Page 202: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 202/382200 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML2 BE HFS 5920 270 BXT ML2B E HFS5

B X TM L 2 B E HFS5920 270

• LifeCheck SPD monitoring function

• Optimal protection of 1 pair andshield

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BE HFS

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 1 pair in high-frequency transmissions without electrical isolation; availablewith direct or indirect shield earthing.

BXT ML2 BE HFS 5

SPD class MSPD monitoring system LifeCheck

Nominal voltage UN 5 V

Max. continuous operating d.c. voltage UC 6.0 V

Max. continuous operating a.c. voltage UC 4.2 V

Nominal current at 45°C IL 1.0 A

D1 Total lightning impulse current (10/350 µs) Iimp 9 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for Iimp D1 Up 26 V

Voltage protection level line-PG for Iimp D1 Up 40 V

Voltage protection level line-line at 1 kV/µs C3 Up 11 V

Voltage protection level line-PG at 1 kV/µs C3 Up 11 V

Series impedance per line 1.0 ohm(s)

Cut-off frequency line-PG fG 100 MHz

Capacitance line-line C 20 pF

Capacitance line-PG C 30 pF

Operating temperature range -40°C...+80°C

Test standards IEC 61643-21

SIL classification SIL2

for more details see: www.dehn.de/en/sil/

Approvals, Certifications CSA,UL, GOST

Ordering information

Type BXT ML2 BE HFS 5

Part No. 920 270

Packing unit 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

BXT BASBase part for use as very space-saving,

four-pole, universal feed-through terminal forinsertion of SPD modules without signal inter-ruption.

PU PartType pc(s). No.

BXT BAS 1 920 300

920 300 BXT BAS

BX T BAS BXT-Basisteil 920 300

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC MCM XTDIN rail mountable device with integrated

LifeCheck sensor for condition monitoring of max. 10 BXT devices with LifeCheck function.

PU PartType pc(s). No.

DRC MCM XT 1 910 695

910 695 DRCM C M X T

DRC MCM XT Condit ionM on it or ing Sy st em Li fe Che ck 91 069 5

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing of Life-Check-equipped arresters.

PU PartType pc(s). No.

DRC LC M3+ 1 910 653

910 653 DRC L CM3+

DR C L C M 3 +A bl ei te rp rü fg er ät Li fe Ch ec k 9 10 65 3

Page 203: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 203/382201www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT LifeCheck® Modules

BXT ML2 BD HFS 5BXT ML2

• LifeCheck SPD monitoring function

• Minimum signal interference

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

1

2

protected

3

4

If LifeCheck detects thermal and electrical overload,the SPD has to be replaced.This status is indicated

contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BD HFS

Space-saving combined lightning current and surge arrester module with LifeCheck monitoringfunction for protecting 1 pair in high-frequency bus systems or video transmission systems, avail-able with direct or indirect shield earthing.

BXT ML2 BD HFS 5

SPD class MSPD monitoring system LifeCheck

Nominal voltage UN 5 V

Max. continuous operating d.c. voltage UC 6.0 V

Max. continuous operating a.c. voltage UC 4.2 V

Nominal current at 45°C IL 1.0 A

D1 Total lightning impulse current (10/350 µs) I imp 9 kA

D1 Lightning impulse current (10/350 µs) per line Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for Iimp D1 Up 25 V

Voltage protection level line-PG for Iimp D1 Up 550 V

Voltage protection level line-line at 1 kV/µs C3 Up 11 V

Voltage protection level line-PG at 1 kV/µs C3 Up 550 V

Series impedance per line 1.0 ohm(s)

Cut-off frequency line-line fG 100 MHz

Capacitance line-line C 25 pF

Capacitance line-PG C 25 pF

Operating temperature range -40°C...+80°C

Test standards IEC 61643-21

SIL classification SIL2

for more details see: www.dehn.de/en/sil/

Approvals, Certifications CSA,UL, GOST

Ordering information

Type BXT ML2 BD HFS 5

Part No. 920 271

Packing unit 1 pc(s).

For further technical details about ”Accessories for BLITZDUCTOR XT LifeCheck modules“ please also refer to pages 186/202/203/204/360/362.

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Test / Disconnection ModuleModule for testing lines, to be plugged into

the BLITZDUCTOR XT base part.PU Part

Type pc(s). No.

BXT M4 T 1 920 309

920 309 BXT M4 T

BXT M4 T BXT-Prüf-

/Trennm odul 920 309

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Earthing moduleFor direct earthing of lines connected to the

BLITZDUCTOR XT base part.

PU PartType pc(s). No.

BXT M4 E 1 920 308

920 308 BXT M4 E

BXT M4 E BXT-

Erdungsm odul 920 308

Accessory Part for BLITZDUCTOR® XT

LifeCheck® Module

Marking system BA1-BA152 x 165 adhesive labels for labelling DRC MCM

XT monitoring devices with their bus addresses.

PU PartType pc(s). No.

BS BA1 BA15 BXT 1 920 398

920 398 BS BA1BA15BXT

BSBA1BA15BXTB ez ei ch nu ng ss ys te mf ür BX T 9 20 39 8

Page 204: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 204/382202 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

Accessories for BLITZDUCTOR® XT

Earthing module920 308 BXT M4 E

B X TM 4 E920 308

• For plugging onto BLITZDUCTOR XTbase parts

• Easy handling

• Quick replacement when retrofittingan SPD module

1

2

protected

3

4

Basic circuit diagram BXT M4 E Dimension drawing BXT M4 E

The plugged-in earthing module short-circuits all l ines connected to the BLITZDUCTOR XT base partto PG. It directly earths initially used cable cores, which are already connected to the base part.

BXT M4 E

D1 Total lightning impulse current (10/350 µs) Iimp 10 kA

Operating temperature range -40°C...+80°C

Degree of protection (plugged-in) IP 20

For plugging into base part

Enclosure material polyamide PA 6.6

Colour grey

Ordering information

Type BXT M4 E

Part No. 920 308

Packing unit 1 pc(s).

EMC spring terminals920 395 SAK BXTLR

SAK B X TL R920 395

• Lightning current carrying capability

• Flat conductor with low impedance

• Flexible spring terminal

Dimension drawing SAK BXT LR

Two spring terminals for permanent low-impedance shield contact with the protected and unpro-tected side of a BXT device. With integrated terminal coding for direct or indirect shield earthing,cable ties and insulating strips included.

SAK BXT LR

D1 Lightning impulse current (10/350 µs) 5 kA

For plugging into clamp connection BXT BAS

Clamping range 3 - 10 mm

Colour bare

Accessories cable tie, insulating strips

Ordering information

Type SAK BXT LR

Part No. 920 395

Packing unit 1 pc(s).

Page 205: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 205/382203www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

Accessories for BLITZDUCTOR® XT

Test / Disconnection ModuleBXT M4 T

• For plugging into the BLITZDUCTOR XTbase parts

• Easy maintenance and troubleshooting

• Measuring lines included

1

2

3

4

Dimension drawing BXT M4 T

The plugged-in test/disconnection module interrupts the cable run of the lines connected to the BLITZ-DUCTOR XT base part and leads them to a test socket at the front side of the module. This allows tocarry out measurements in the installation without removing the lines from the base part.

BXT M4 T

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Nominal current at 80° C IL 1.0 A

Volume resistance 0.1 ohm

Operating temperature range -40°C ... +80°C

Degree of protection (plugged-in) IP 20

For plugging into base part

Test sockets gold-plated, 1 mm

Enclosure material polyamide PA 6.6

Colour grey

Accessories 2 measuring lines (1 m), protective bag

Ordering information

Type BXT M4 T

Part No. 920 309

Packing unit 1 pc(s).

Basic circuit diagram BXT M4 T

Page 206: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 206/382204 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

Accessories for BLITZDUCTOR® XT

Marking system BA1-BA15920 398 BS BA1 BA15 BXT

B SB A1 B A1 5 B X T920 398

• For DRC MCM XT condition monitor-ing system

• Abrasion-proof

• Pre-printed

• Transparent

2 x 165 adhesive labels for labelling DRC MCM XT monitoring devices with their bus addresses (BA1to BA15) and with consecutive numbers of the assigned BXT base parts or modules (1.1-1.10 to15.1-15.10)

BS BA1 BA15 BXT

Dimension W x H 13 x 7 mm

Ordering information

Type BS BA1 BA15 BXT

Part No. 920 398

Packing unit 1 pc(s).

N E W

Marking system 1-50920 399 BS 1 50 BXT

B S1 5 0 B X T920 399

• Abrasion-proof

• Pre-printed Plate with 2 plate numbers from 1 to 50 for attaching to BXT base parts or modules.

BS 1 50 BXT

Dimension W x H 11 x 4 mm

Ordering information

Type BS 1 50 BXT

Part No. 920 399

Packing unit 1 pc(s).

Page 207: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 207/382205www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT

ATEX Certificate

Page 208: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 208/382206 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT

IECEx Certificate

Page 209: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 209/382207www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® XT

Information on SIL

The term safety integration level (SIL) is defined in the internationalIEC 61508 and IEC61511 standards and is used in the field of functionalsafety. It is intended for assessing the reliability and safety of electrical,

electronic or programmable electronic systems. "Functional safety"describes the safety level of a system or installation, which depends onthe correct operation of sub-systems and external installations to reduce

the risk. The aim of functional safety is to minimise the risk of failure of the individual sub-systems so that the risk for the entire system or instal-lation is reduced to an acceptable level.The values in the table below can

be used for calculating the functional safety of systems with the surgeprotective devices used.

λSD SU DD DU Total SFF *3 SIL AC *4

Surge Protection Device Failure rates according to IEC 61508 in FIT Safe Failure Fraction SIL

*1 *2 *1 *2 *1 *2 *1 *2

BXT ML2(4) B 180 0 21 0 1 3 2 24 86.8% 92.7% SIL2 SIL3

BXT ML4(2) BD *, BXT ML2 BD S * 0 21 0 4 6 2 27 78.2% 92.8% SIL2 SIL3

BXT ML4 BD HF *, BXT ML2 BD HFS * 0 29 0 4 14 10 43 67.7% 76.8% SIL2 SIL2

BXT ML2 BD DL S 15 0 21 0 4 6 2 27 78.2% 92.8% SIL2 SIL3

BXT ML4 BE *, BXT ML2 BE S * 0 21 0 7 9 2 30 71.4% 93.0% SIL2 SIL3

BXT ML4 BE HF *, BXT ML2 BE HFS * 0 33 0 8 18 10 51 64.9% 80.4% SIL2 SIL2

BXT ML4 BE C * 0 23 0 9 12 3 35 65.4% 91.3% SIL2 SIL3

BXT ML4 BC EX 24 0 39 0 8 11 3 50 78.8% 93.7% SIL2 SIL3

BXT ML4 BD EX 24 0 57 0 6 10 4 67 85.3% 94.1% SIL2 SIL3

BXT ML2 BD HF EX 6 0 28 0 1 16 15 44 64.0% 67.2% SIL2 SIL2

BXT ML4 BC * 0 21 0 7 9 2 30 71.4% 93.0% SIL2 SIL3

BXT ML4 MY 250 0 20 0 0.5 10 9.5 30 66.6% 67.9% SIL2 SIL2

* All voltages available

*1 Analysis 1 represents a worst-case analysis

*2 Analysis 2 represents an analysis with the assumption that line short circuits and short circuits to GND are detectable or do not have an effect.

*3 The complete sensor or final element subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only.

*4 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not

imply all related IEC 61508 requirements are fulfilled. See also previous footnote.

Page 210: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 210/382208 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

PLUGGABLE SPDs FOR DIN RAIL MOUNTING

Page 211: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 211/382www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

209www.dehn.de

DEHNconnect RK

Terminal block with integratedsurge protection

• Minimum installation width of only 6 mm

• Quick installation with jumper bar

(accessory part)• Spring-loaded connection system

6 mm two-pole terminal block with integrated surge protection and cageclamp terminal. Earthing via DIN rail or clamp.

DEHNconnect RK is a 6 mm terminal block with integrated surge protec-tion and has five spring-loaded cage clamp terminals allowing two linesto be protected and equipotential bonding to the terminal equipment tobe established.The snap-in fixing at the supporting foot allows the device

to be safely earthed via the DIN rail. For reduced wiring, jumper bars canbe plugged into the protected side of the SPD to transmit signals.As theenclosure of the SPDs is open on one side to minimise the width, a cov-ering plate should be used at the end of every SPD block.

DEHNconnect RK is available in two per-formance classes:DCO RK M:

Surge arrester with energy-coordinatedprotection stagesDCO RK E (D):

Surge arrester with diodes only, forimproving the electromagnetic compati-bility (EMC) of terminal equipment

DCO RK

A wide range of accessories such as jumper bars, marking plates or coveringplates make DCO RK a system easy tooperate, which has been specificallydesigned for use in industrial environ-ments.

DCO RK Accessories

IP 20

In order to minimise the width, the enclo-sure is open to one side. For protection

against electrical shock, the SPD can beclosed with a covering plate (accessories).If several devices are arranged next toeach other, one covering plate could besufficient.

DCO RK with covering plate

3

2

3

OUT 3

KB 10 DCO RK

marking platesok

Operating state controls of switch contacts in industrial environments areoften fed by a common power source. If several DCO RK units are used,wiring can be reduced by bridging the feeding signal on the protected side(accessories).

Use of jumper bars

Page 212: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 212/382210 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

DEHNconnect RK

DCO RK ME919 920 DCO RKME12919 921 DCO RKME24919 922 DCO RKME48919 923 DCO RKME110

DC O R K M E 1 2DEHNconnect RK 12 V 919 920DC O R K M E 2 4DEHNconnect RK 24 V 919 921DC O R K M E 4 8DEHNconnect RK 48 V 919 922DCORKME110DEHNconnect RK 110 V 919 923

• Standard protection with modular ter-minal blocks

• Low series impedance

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

3

4

IN OUT

Energy-coordinated gas discharge tubes anddiodes to earth

Dimension drawing DCO RK ME

2-stage SPD for protecting 2 single lines with common reference potential as well as unbalancedinterfaces.

DCO RK ME 12 DCO RK ME 24 DCO RK ME 48 DCO RK ME 110

SPD class Q Q Q RNominal voltage UN 12 V 24 V 48 V 110 V

Max. continuous operating d.c. voltage Uc 14 V 33 V 55 V 170 V

Max. continuous operating a.c. voltage Uc 9.5 V 23 V 38.5 V 120 V

Nominal current IL 0.5 A 0.5 A 0.5 A 0.5 A

C2 Total nominal discharge current (8/20 µs) In 10 kA 10 kA 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA 5 kA 5 kA 5 kA

Voltage protection level line-line for In C2 Up 55 V 110 V 175 V 500 V

Voltage protection level line-PG for In C2 Up 40 V 65 V 100 V 270 V

Voltage protection level line-line at 1 kV/µs C3 Up 36 V 90 V 160 V 460 V

Voltage protection level line-PG at 1 kV/µs C3 Up

19 V

45 V

80 V

230 VSeries impedance per line 1.8 ohms 1.8 ohms 1.8 ohms 1.8 ohms

Cut-off frequency line-PG fG 2.5 MHz 6 MHz 10 MHz 16 MHz

Capacitance line-line C 1.2 nF 0.5 nF 0.3 nF 0.2 nF

Capacitance line-PG C 2.4 nF 1 nF 0.6 nF 0.4 nF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Degree of protection IP 00, with cover IP 20 IP 00, with cover IP 20 IP 00, with cover IP 20 IP 00, with cover IP 20

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60175

Connection input/output spring / spring spring / spring spring / spring spring / spring

Cross-sectional area, solid 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2

Earthing via DIN rail / terminal DIN rail / terminal DIN rail / terminal DIN rail / terminal

Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6

Colour yellow yellow yellow yellow

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST GOST GOST

Ordering information

Type DCO RK ME 12 DCO RK ME 24 DCO RK ME 48 DCO RK ME 110

Part No. 919 920 919 921 919 922 919 923

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNconnect RK

Covering plateFor DCO RK

PU PartType Enclosure material Colour pc(s). No.

AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

919 979 AD DCOR K G E

AD DCO RK GE CoveringPlate for DCO, yellow 919 979

Accessory Part for DEHNconnect RK

Quick marking system, horizontal imprintPlate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint

PU PartType Material pc(s). No.

BS 1 50 DCO RK plastic 1 919 977

919 977 BS 1 50DC O R K

BS 1 50 DCO RK QuickM ar ki ng Sy st em fo rD CO RK 9 19 97 7

Page 213: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 213/382211www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

DEHNconnect RK

DCO RK MD 12 / MD 24DCO RK

DCO RK

919 940

919 941

• Standard protection with modular ter-minal blocks

• Low series impedance

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

3

4

IN OUT

Protective circuit, no leakage currents to earth,energy-coordinated

Dimension drawing DCO RK MD 12 / MD 24

2-stage SPD for protecting a floating pair as well as balanced interfaces.

DCO RK MD 12 DCO RK MD 24

SPD class Q QNominal voltage UN 12 V 24 V

Max. continuous operating d.c. voltage Uc 14 V 33 V

Max. continuous operating a.c. voltage Uc 9.5 V 23 V

Nominal current IL 0.5 A 0.5 A

C2 Total nominal discharge current (8/20 µs) In 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA 5 kA

Voltage protection level line-line for In C2 Up 25 V 50 V

Voltage protection level line-PG for In C2 Up 750 V 750 V

Voltage protection level line-line at 1 kV/µs C3 Up 19 V 45 V

Voltage protection level line-PG at 1 kV/µs C3 Up

650 V

650 VSeries impedance per line 1.8 ohms 1.8 ohms

Cut-off frequency line-line fG 2.5 MHz 6 MHz

Capacitance line-line C 2.4 nF 1 nF

Capacitance line-PG C 5 pF 5 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Degree of protection IP 00, with cover IP 20 IP 00, with cover IP 20

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Connection input/output spring / spring spring / spring

Cross-sectional area, solid 0.08 - 2.5 mm2 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2 0.08 - 2.5 mm2

Earthing via DIN rail / terminal DIN rail / terminal

Enclosure material polyamide PA 6.6 polyamide PA 6.6

Colour yellow yellow

Test standards IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST

Ordering information

Type DCO RK MD 12 DCO RK MD 24

Part No. 919 940 919 941

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for DEHNconnect RK

Quick marking system, vertical imprintPlate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint

PU PartType Material pc(s). No.

BS 1 50 S DCO RK plastic 1 919 976

919 976 BS 1 50 SDC O R K

B S1 5 0 SDC O R K919 976

N E W

Accessory Part for DEHNconnect RK

Covering plateFor DCO RK

PU PartType Enclosure material Colour pc(s). No.

AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

919 979 AD DCORKGE

AD DCO RK GE Cover ingPlate for DCO, yellow 919 979

Page 214: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 214/382212 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

DEHNconnect RK

DCO RK MD 48919 942 DCO RKM D4 8

DC O R K M D4 8DEHNconnect RK 48 V 919 942

• Standard protection with modular ter-minal blocks

• Extremely low series impedance

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

3

4

IN OUT

Protective circuit, no leakage currents to earth,energy-coordinated

Dimension DCO RK MD 48

2-stage SPD for protecting a floating pair as well as balanced interfaces up to 1.7 A.

DCO RK MD 48

SPD class QNominal voltage UN 48 V

Max. continuous operating d.c. voltage Uc 55 V

Max. continuous operating a.c. voltage Uc 38.5 V

Nominal current IL 1.7 A

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 Up 100 V

Voltage protection level line-PG for In C2 Up 750 V

Voltage protection level line-line at 1 kV/µs C3 Up 70 V

Voltage protection level line-PG at 1 kV/µs C3 Up

650 VSeries impedance per line 0.4 ohms

Cut-off frequency line-line fG 10 MHz

Capacitance line-line C 0.6 nF

Capacitance line-PG C 10 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 00, with cover IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output spring / spring

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Earthing via DIN rail / terminal

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type DCO RK MD 48

Part No. 919 942

Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK

Covering plateFor DCO RK

PU PartType Enclosure material Colour pc(s). No.

AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

919 979 AD DCOR K G E

AD DCO RK GE CoveringPlate for DCO, yellow 919 979

Accessory Part for DEHNconnect RK

Quick marking system, horizontal imprintPlate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint

PU PartType Material pc(s). No.

BS 1 50 DCO RK plastic 1 919 977

919 977 BS 1 50DC O R K

BS 1 50 DCO RK QuickM ar ki ng Sy st em fo rD CO RK 9 19 97 7

Page 215: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 215/382213www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

DEHNconnect RK

DCO RK MD 110DCO RK

919 943

• Standard protection with modular ter-minal blocks

• Low series impedance

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

3

4

IN OUT

Protection circuit, free of leakage currents toearth, energy-coordinated

Dimension drawing DCO RK MD 110

2-stage SPD for protecting a floating pair, telecommunications.

DCO RK MD 110

SPD class RNominal voltage UN 110 V

Max. continuous operating d.c. voltage Uc 170 V

Max. continuous operating a.c. voltage Uc 120 V

Nominal current IL 0.5 A

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 Up 260 V

Voltage protection level line-PG for In C2 Up 750 V

Voltage protection level line-line at 1 kV/µs C3 Up 230 V

Voltage protection level line-PG at 1 kV/µs C3 Up

650 VSeries impedance per line 1.8 ohms

Cut-off frequency line-line fG 16 MHz

Capacitance line-line C 0.4 nF

Capacitance line-PG C 5 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 00, with cover IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output spring / spring

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Earthing via DIN rail / terminal

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type DCO RK MD 110

Part No. 919 943

Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK

Quick marking system, vertical imprintPlate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint

PU PartType Material pc(s). No.

BS 1 50 S DCO RK plastic 1 919 976

919 976 BS 1 50 SDC O R K

B S1 5 0 SDC O R K919 976

N E W

Accessory Part for DEHNconnect RK

Covering plateFor DCO RK

PU PartType Enclosure material Colour pc(s). No.

AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

919 979 AD DCORKGE

AD DCO RK GE Cover ingPlate for DCO, yellow 919 979

Page 216: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 216/382214 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

DEHNconnect RK

DCO RK MD HF919 970 DCO RKM DHF5

DC O R K M DHF5DEHNconnect RK MD HF, 5V 919 970

• Low self-capacitance

• Very good transmission performance

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

3

4

IN OUT

The capacitance of the protective circuit can beminimised by combining several diodes to one

matrix.

Dimension drawing DCO RK MD HF

2-stage SPD for protecting balanced or unbalanced interfaces with extra-low voltages. Can also beused for high transmission rates. For shielded bus lines, SAK shield connection systems should be used.

DCO RK MD HF 5

SPD class QNominal voltage UN 5 V

Max. continuous operating d.c. voltage Uc 6.0 V

Max. continuous operating a.c. voltage Uc 4.2 V

Nominal current IL 0.1 A

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 Up 27 V

Voltage protection level line-PG for In C2 Up 50 V

Voltage protection level line-line at 1 kV/µs C3 Up 14 V

Voltage protection level line-PG at 1 kV/µs C3 Up

14 VSeries impedance per line 1.0 ohm

Cut-off frequency line-line fG 250 MHz

Cut-off frequency line-PG fG 180 MHz

Capacitance line-line C 19 pF

Capacitance line-PG C 16 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 00 with cover IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output spring / spring

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Earthing via DIN rail / terminal

Enclosure material thermoplastic PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type DCO RK MD HF 5

Part No. 919 970

Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK

Covering plateFor DCO RK

PU PartType Enclosure material Colour pc(s). No.

AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

919 979 AD DCOR K G E

AD DCO RK GE CoveringPlate for DCO, yellow 919 979

Accessory Part for DEHNconnect RK

Quick marking system, horizontal imprintPlate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint

PU PartType Material pc(s). No.

BS 1 50 DCO RK plastic 1 919 977

919 977 BS 1 50DC O R K

BS 1 50 DCO RK QuickM ar ki ng Sy st em fo rD CO RK 9 19 97 7

Page 217: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 217/382215www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

DEHNconnect RK

DCO RK EDCO RK E

DCO RK E

DCO RK E

DCO RK E

919 987

919 988

919 989

919 990

• Protection with modular terminalblocks

• High nominal current

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

1

2

3

4

IN OUT

Powerful diodes limit surges to earth.Dimension drawing DCO RK E

Fine limiting surge protective device for 2 single lines with common reference potential as well asunbalanced interfaces.

DCO RK E 12 DCO RK E 24 DCO RK E 48 DCO RK E 60

SPD class W W [ [Nominal voltage UN 12 V 24 V 48 V 60 V

Max. continuous operating d.c. voltage Uc 13 V 28 V 58 V 70 V

Max. continuous operating a.c. voltage Uc 9 V 19.5 V 41 V 49.5 V

Nominal current IL 10 A 10 A 10 A 10 A

C1 Total nominal discharge current (8/20 µs) In 0.8 kA 0.6 kA 0.3 kA 0.24 kA

C1 Nominal discharge current (8/20 µs) per line In 0.4 kA 0.3 kA 0,15 kA 0.12 kA

Voltage protection level line-line for In C1 Up 50 V 96 V 180 V 220 V

Voltage protection level line-PG for In C1 Up 25 V 48 V 90 V 110 V

Voltage protection level line-line at 1 kV/µs C3 Up 36 V 76 V 156 V 190 V

Voltage protection level line-PG at 1 kV/µs C3 Up

18 V

38 V

78 V

95 VCut-off frequency line-PG fG 2.5 MHz 5.5 MHz 11 MHz 14 MHz

Capacitance line-line C 1.2 nF 0.6 nF 0.3 nF 0.25 nF

Capacitance line-PG C 2.5 nF 1.2 nF 0.6 nF 0.5 nF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Degree of protection IP 00, with cover IP 20 IP 00, with cover IP 20 IP 00, with cover IP 20 IP 00, with cover IP 20

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Connection input/output spring / spring spring / spring spring / spring spring / spring

Cross-sectional area, solid 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2 0.08 - 2.5 mm2

Earthing via DIN rail / terminal DIN rail / terminal DIN rail / terminal DIN rail / terminal

Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6

Colour yellow yellow yellow yellow

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST GOST GOST

Ordering information

Type DCO RK E 12 DCO RK E 24 DCO RK E 48 DCO RK E 60

Part No. 919 987 919 988 919 989 919 990

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHNconnect RK

Quick marking system, vertical imprintPlate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint

PU PartType Material pc(s). No.

BS 1 50 S DCO RK plastic 1 919 976

919 976 BS 1 50 S

DC O R K

B S1 5 0 SDC O R K919 976

N E W

Accessory Part for DEHNconnect RK

Covering plateFor DCO RK

PU PartType Enclosure material Colour pc(s). No.

AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

919 979 AD DCORKGE

AD DCO RK GE Cover ingPlate for DCO, yellow 919 979

Page 218: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 218/382216 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

DEHNconnect RK

DCO RK D919 986 DCO RK D5 24

DC O R K D5 2 4DEHNconnect RK 5/24 V 919 986

• EMC protection with modular termi-nal blocks

• High nominal current

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

1

2

3

4

IN OUT

Powerful diodes limit surges between the signallines.

Dimension drawing DCO RK D

Surge protective device for SIEMENS-SPS S7-300 output digital modules (laboratory tested). Theterminal allows for increased EMC protection. No connection to PG.

DCO RK D 5 24

SPD class [Nominal voltage UN +24 V / -5 V

Max. continuous operating d.c. voltage Uc +30 V / -6 V

Nominal current IL 10 A

C1 Total nominal discharge current (8/20 µs) In 0.3 kA

C1 Nominal discharge current (8/20 µs) per line In 0.3 kA

Voltage protection level line-line for In C1 Up 70 V

Voltage protection level line-line at 1 kV/µs C3 Up 45 V

Cut-off frequency line-line fG 3.5 MHz

Capacitance line-line C 2 nF

Operating temperature range -40°C...+80°CDegree of protection IP 00, with cover IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output spring / spring

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type DCO RK D 5 24

Part No. 919 986Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK

Covering plateFor DCO RK

PU PartType Enclosure material Colour pc(s). No.

AD DCO RK GE polyamide PA 6.6 yellow 1 919 979

919 979 AD DCOR K G E

AD DCO RK GE CoveringPlate for DCO, yellow 919 979

Page 219: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 219/382217www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

www.dehn.de

Covering plateAD DCO

Cover ing919 979

• Easy to open

AD DCO RK GE

Enclosure material polyamide PA 6.6

Colour yellow

Ordering information

Type AD DCO RK GE

Part No. 919 979

Packing unit 1 pc(s).

Jumper barKB 10

Jum per919 880

• Reduced wiring

• Use at protected outputs of DCO RKonly

Multipole unit for DCO RK

KB 10 DCO RK

Poles 10

Ordering information

Type KB 10 DCO RK

Part No. 919 880

Packing unit 1 pc(s).

Quick marking system, horizontal imprintBS 1 50

QuickOR K 9 19 977

• Pre-printed marking for DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint

BS 1 50 DCO RK

Material plastic

Ordering information

Type BS 1 50 DCO RK

Part No. 919 977

Packing unit 1 pc(s).

Quick marking system, vertical imprintBS 1 50 S DCO RK

• Pre-printed marking for DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint

BS 1 50 S DCO RK

Material plastic

Ordering information

Type BS 1 50 S DCO RK

Part No. 919 976

Packing unit 1 pc(s).

N E W

Accessories for DEHNconnect RK

Page 220: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 220/382218 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® VT

Lightning current / Surge arrester

• Cost-effective protection of multi-core signallines

• Interface-specific types, e.g. TTY, RS 485• Types for d.c. power supply systems

Compact protection with screw terminals for multi-core lines for DIN railmounting.

BLITZDUCTOR VT is a family of compact DIN rail mounted SPDs and con-sists of different types of enclosures. Most of the SPDs protect 4-wire sig-

nal lines or special applications. The equipment is earthed via a screw ter-minal.

BVT enclosure family

The enclosure concept of BLITZDUCTOR VTis variable. Depending on the application,SPDs are distinguished between

– width: 1.5 modules,4 protected signal lines

– width: 1.5 modules,2 protected lines for d.c. power supplysystems

– width: 3 modules,6 protected lines for RS 485/422

Connection to the ground has to be performedwith a terminal instead of the snap-on DIN rail.Direct equipotential bonding can be establishedto the terminal device with the second terminalcompartment of this double terminal.

Connection

Page 221: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 221/382219www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® VT

BVT TTYBVT TTY

BLITZ-918 400

• Simultaneous protection of two TTYloops

• Additional decoupling to the terminaldevice

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

4

1

2

3 3

4

IN OUT

The resistors at the circuit output protect theoptocoupler and protective diodes in the terminal

equipment against overloads.

Dimension drawing BVT TTY

Owing to the additional decoupling resistors at the output, only diodes in the terminal equipment,which can withstand loads only to a certain extent, are integrated into the energy coordination of the protective stages. This is especially important for optocoupler interfaces.

BVT TTY 24

SPD class QNominal d.c. voltage UN 24 V

Max. continuous operating d.c. voltage UC 26.8 V

Max. continuous operating a.c. voltage UC 18.9 V

Nominal current IL 0.1 A

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection line-line for In C2 Up 65 V

Voltage protection level line-PG for In C2 Up 700 V

Voltage protection level line-line at 1 kV/µs C3 Up 36 VVoltage protection level line-PG at 1 kV/µs C3 UP 600 V

Series impedance per line 17.2 ohms per pair

Cut-off frequency line-line fG 8 MHz

Capacitance line-line C 1 nF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Tightening torque (terminals) 0.5 Nm

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21, UL 497B

Approvals, Certifications CSA, GOST

Ordering information

Type BVT TTY 24

Part No. 918 400

Packing unit 1 pc(s).

Page 222: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 222/382220 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® VT

BVT MTTY918 407 BVT MTTY24

B V TM TTY 2 4918 407

• Cost-effective compact protection

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

4

3

1

4

3

2 2

1

IN OUT

Protection circuit with simple decoupling, no leak-age currents to earth, energy-coordinated.

Dimension drawing BVT MTTY

Surge arrester for two floating pairs. Unbalanced use of the decoupling impedance.

BVT MTTY 24

SPD class QNominal d.c. voltage UN 24 V

Max. continuous operating d.c. voltage UC 26.8 V

Max. continuous operating a.c. voltage UC 18.9 V

Nominal current IL 0.1 A

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection line-line for In C2 Up 65 V

Voltage protection level line-PG for In C2 Up 700 V

Voltage protection level line-line at 1 kV/µs C3 Up 36 V

Voltage protection level line-PG at 1 kV/µs C3 UP

600 VSeries impedance per line 2.2 ohms per pair

Cut-off frequency line-line fG 10 MHz

Capacitance line-line C 1 nF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Tightening torque (terminals) 0.5 Nm

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type BVT MTTY 24

Part No. 918 407

Packing unit 1 pc(s).

Page 223: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 223/382221www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

www.dehn.de

BLITZDUCTOR® VT

BVT RS485BVT

BLITZ-918 401

• Terminals for 4 bus lines and SG

• Direct or indirect shield earthing

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

6

5

12

12

4

7

8

3

6

5

4

7

8

3IN OUT

Circuiting diodes to a common reference pointallows for a low protection level between the

signal lines.

Dimension drawing BVT RS485

Surge arrester for a wide range of applications, e.g. for balanced 4-wire RS 485/422 interfaces ortemperature sensors. Allows for either direct or indirect shield earthing and connection of a signalground (SG).

BVT RS485 5

SPD class QNominal d.c. voltage UN 5 V

Max. continuous operating d.c. voltage UC 6 V

Max. continuous operating a.c. voltage UC 4.2 V

Nominal current IL 0.5 A

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection line-line for In C2 Up 20 V

Voltage protection level line-PG for In C2 Up 700 V

Voltage protection level line-line at 1 kV/µs C3 Up 8.5 V

Voltage protection level line-PG at 1 kV/µs C3 UP

600 VSeries impedance per line 1.8 ohms

Cut-off frequency line-line fG 1.7 MHz

Capacitance line-line C 5 nF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Tightening torque (terminals) 0.5 Nm

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21, UL 497B

Approvals, Certifications CSA, GOST

Ordering information

Type BVT RS485 5

Part No. 918 401

Packing unit 1 pc(s).

Page 224: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 224/382222 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® VT

BVT AD918 402 BVT AD24

BVT AD 24 BLITZ-DUCTOR VT 24 V 918 402

• EMC protection for PLC 24 V powersupply

• Especially low protection level

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

0 V

+24 V

0 V

+24 V

IN OUT

As a unipolar diode is used, negative operatingvoltages are not permissible.

Dimension drawing BVT AD

Quickly responding surge protective device, for e.g. Siemens SPS S7-300 with d.c. power supply.Especially for use in electromagnetically harsh environments where common varistor-based surgearresters do not limit sufficiently.

BVT AD 24

SPD class WNominal d.c. voltage UN 24 V

Max. continuous operating d.c. voltage UC 35 V

Nominal current IL 10 A

C2 Total nominal discharge current (8/20 µs) In 2 kA

C2 Nominal discharge current (8/20 µs) per line In 1 kA

Voltage protection line-line for In C2 Up 70 V

Voltage protection level line-PG for In C2 Up 700 V

Voltage protection level line-line at 1 kV/µs C3 Up 50 V

Voltage protection level line-PG at 1 kV/µs C3 UP 700 V

Capacitance line-line C

7 nFCapacitance line-PG C 10 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.5 - 4.0 mm2

Cross-sectional area, flexible 0.5 - 4.0 mm2

Tightening torque (terminals) 0.8 Nm

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21, UL 497B

Approvals, Certifications CSA,GOST, UL

Ordering information

Type BVT AD 24

Part No. 918 402

Packing unit 1 pc(s).

Page 225: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 225/382223www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® VT

BVT ALDBVT ALD 36

• For d.c. supplies up to nominal cur-rents of 4 A

• Low voltage protection level

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A - 2 and higher

1

2

1

2

protected

Basic circuit diagram BVT ALDDimension drawing BVT ALD

Energy-coordinated combined lightning current and surge arrester for protection of unearthed d.c.supplies for DIN rail mounting

BVT ALD 36

SPD class MNominal d.c. voltage UN 36 V

Max. continuous operating d.c. voltage UC 45 V

Nominal current at 80°C IL 4 A

D1 Lightning impulse current (10/350 µs) per line I imp 2.5 kA

D1 Total lightning impulse current (10/350 µs) I imp 5 kA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection line-line for In C2 Up 80 V

Voltage protection level line-PG for In C2 Up 1000 V

Voltage protection level line-line at 1 kV/µs C3 Up

60 VVoltage protection level line-PG at 1 kV/µs C3 UP 650 V

Series impedance per line 22 µH

Capacitance line-line C 1.5 pF

Capacitance line-PG C 100 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.5 - 6.0 mm2

Cross-sectional area, flexible 0.5 - 4.0 mm2

Tightening torque (terminals) 0.8 Nm

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type BVT ALD 36

Part No. 918 408

Packing unit 1 pc(s).

N E W

Page 226: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 226/38222 4 www.dehn.de

INFORMATION TECHNOLOGY SYSTEM S

COM PACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR ® VT KKS

Combined lightning current and

surge arrester for cathodic corrosion prot ect ion systems

• M aximum efficiency due to high dischargecapacity

• Easy maintenance due to remote signallingcontact

• Resistant to permanent interference voltagesup to 65 V a.c.

SPD for protecting active cathodic corrosion protection systems.

Integrated floating remote signalling contact (break contact) for function

monitoring.

The protective circuit and voltage measuring circuit are protected against

surge impulses caused by atmospheric discharges (lightnin g) or swi tching

operations (in power supply lines).

The devices are designed for operation at permanent interference volt-

ages up to 65 V a.c. betw een pipelines and earth. If thi s value is exceed-

ed, the relevant regulations for protection against electrical shock have to

be considered and further measures have to be taken.

The devices can be overloaded by overcurrents caused by mains faults

(short circuits or earth faults). Therefore, they should be installed into a

separate metallic enclosure or a prewired terminal unit (ITAK) should be

used.The integrated remote signalling contact ind icates thermal overload

of the discharge paths.

In cathodic corrosion protection systems,

SPDs for protective circuits and voltage

measuring circuits are often used at the

same t ime. For easy identi f icat ion, the

SPDs have different colours, i.e. yellow f or

voltage measuring circuits and red for

protective circuits.

BVT KKS surge arr ester fam ily

Experience has shown that the installa-

tion of SPDs into a separate metal enclo-

sure is reasonable as the enclosure pro-

vides additional protection from over-

loads caused by short circuit s. Wit h ITAK,

DEHN provides adequate prewired units

for cathod ic corrosion prot ection systems.

The ITAK serial number serves as refer-

ence number for ordering.

ITAK, Serial No. 4305

DEHN has long-

standing experience

in using SPDs for

p ipel ine networks

and wou ld bepleased to assist

you to f ind the

appropriate protec-

tion for your appli-

cations.

Application example

Page 227: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 227/382225www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® VT KKS

BVT KKS ALDBVT KKS

BLITZ-918 420

• For protective circuits

• High nominal current

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

K−

K+

Kp−

Kp+

FM

Thermal fuses monitor the varistors. Capacitivecontrol for a low impulse sparkover voltage.

Dimension drawing BVT KKS ALD

Energy-coordinated combined lightning current and surge arrester for protecting the inverter in theprotective circuit (red colour). Plug-in remote signalling contact (break contact) for indicating over-loads. Installation into the steel plate enclosure recommended.

BVT KKS ALD 75

SPD class MNominal voltage UN 70 V

Max. continuous operating d.c. voltage Uc 75 V

Nominal current IL 12 A

D1 Total lightning impulse current (10/350 µs) I imp 7 kA

D1 Lightning impulse current (10/350 µs) per line I imp 3.5 kA

C2 Total nominal discharge current (8/20 µs) In 40 kA

C2 Nominal discharge current (8/20 µs) per line In 20 kA

Voltage protection level line-line for Iimp D1 Up 400 V

Voltage protection level line-PG for Iimp D1 Up 400 V

Voltage protection level line-line at 1 kV/µs C3 Up

350 VVoltage protection level line-PG at 1 kV/µs PG Up 350 V

A2 Total a.c. current carrying capacity 20 A

Series impedance per line 5 µH

Cut-off frequency line-line fG 1 MHz

Capacitance line-line C 2 nF

Capacitance line-PG C 2 nF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.5 - 6 mm2

Cross-sectional area, flexible 0.5 - 4 mm2

Tightening torque (terminal) 0.8 Nm

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour red

Test standards IEC 61643-21

Approvals, Certifications GOST

Type of remote signalling contacts break contact

Switching capacity d.c. 250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A

Switching capacity a.c. 250 V/0.5 A

Cross-sectional area for remote signalling terminals max 1.5 mm2

Ordering information

Type BVT KKS ALD 75

Part No. 918 420

Packing unit 1 pc(s).

Page 228: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 228/382226 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® VT KKS

BVT KKS APD918 421 BVT KKSAP D3 6

B V TK K SAP D3 6918 421

• For voltage measuring circuits

• Plug-in remote signalling contact

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

M−

M+

Mp−

Mp+

FM

Thermal fuses monitor the discharge circuits.Capacitive control for a low impulse sparkover

voltage.

Dimension drawing BVT KKS APD

Energy-coordinated combined lightning current and surge arrester for protecting voltage measur-ing circuits (yellow colour). Plug-in remote signalling contact (break contact) for indicating over-loads. Installation into a steel plate enclosure recommended.

BVT KKS APD 36

SPD class MNominal voltage UN 36 V

Max. continuous operating d.c. voltage Uc 36.8 V

Nominal current IL 0.05 A

D1 Total lightning impulse current (10/350 µs) I imp 7 kA

D1 Lightning impulse current (10/350 µs) per line I imp 3.5 kA

C2 Total nominal discharge current (8/20 µs) In 40 kA

C2 Nominal discharge current (8/20 µs) per line In 20 kA

Voltage protection level line-line for Iimp D1 Up 65 V

Voltage protection level line-PG for Iimp D1 Up 800 V

Voltage protection level line-line at 1 kV/µs C3 Up

48 VVoltage protection level line-PG at 1 kV/µs PG Up 600 V

A2 Total a.c. current carrying capacity 20 A

Series impedance per line 70 ohms

Cut-off frequency line-line fG 4.5 dB at 1 MHz (100 ohms)

Capacitance line-line C 1 nF

Capacitance line-PG C 10 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.5 mm - 6 mm2

Cross-sectional area, flexible 0.5 mm - 4 mm2

Tightening torque (terminal) 0.8 Nm

Earthing via screw terminal

Enclosure material thermplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Type of remote signalling contacts break contact

Switching capacity d.c. 250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A

Switching capacity a.c. 250 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2

Ordering information

Type BVT KKS APD 36

Part No. 918 421

Packing unit 1 pc(s).

Page 229: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 229/382227www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

BLITZDUCTOR® VT KKS

BVT KKS ALD SNBVT KKS

BLITZ-918 404

• For protective circuits

• Device acc. to SNAM specification

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

M

D

Mp

Dp

FM

Thermal fuses monitor the varistors. Capacitivecontrol for a low impulse sparkover voltage.

Dimension drawing BVT KKS ALD SN

Energy-coordinated combined lightning current and surge arrester for protecting the inverter in theprotective circuit (red colour). Plug-in remote signalling contact (break contact) for indicating over-loads. Installation into steel plate enclosure recommended. Device according to SNAM specification.

BVT KKS ALD SN

SPD class MNominal voltage UN 70 V

Max. continuous operating d.c. voltage Uc 75 V

Nominal current IL 12 A

D1 Total lightning impulse current (10/350 µs) I imp 7 kA

D1 Lightning impulse current (10/350 µs) per line I imp 3.5 kA

C2 Total nominal discharge current (8/20 µs) In 40 kA

C2 Nominal discharge current (8/20 µs) per line In 20 kA

Voltage protection level line-line for Iimp D1 Up 400 V

Voltage protection level line-PG for Iimp D1 Up 400 V

Voltage protection level line-line at 1 kV/µs C3 Up

350 VVoltage protection level line-PG at 1 kV/µs PG Up 350 V

A2 Total a.c. current carrying capacity 20 A

Series impedance per line 5 µH

Cut-off frequency line-line fG 1 MHz

Capacitance line-line C 2 nF

Capacitance line-PG C 2 nF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.5 - 6 mm2

Cross-sectional area, flexible 0.5 - 4 mm2

Tightening torque (terminal) 0.8 Nm

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour red

Test standards IEC 61643-21

Approvals, Certifications SNAM specification, GOST

Type of remote signalling contacts break contact

Switching capacity d.c. 250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A

Switching capacity a.c. 250 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2

Ordering information

Type BVT KKS ALD SN

Part No. 918 404

Packing unit 1 pc(s).

Page 230: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 230/382228 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

COMPACT SPDs FOR DIN RAIL MOUNTING

www.dehn.de

BLITZDUCTOR® VT KKS

BVT KKS APD SN918 405 BVT KKSAP DSN

BVT KKS APD SN BLITZ-DUCTOR VT 918 405

• For voltage measuring circuits

• Device acc. to SNAM specification

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 2 and higher

E

M

Ep

Mp

FM

Thermal fuses monitor the discharge circuits.Capacitive control for a low impulse sparkover

voltage.

Dimension drawing BVT KKS APD SN

Energy-coordinated combined lightning current and surge arrester for protecting the voltage meas-uring circuit (yellow colour). Plug-in remote signalling contact (break contact) for indicating over-loads. Installation into steel plate enclosure recommended. Device according to SNAM specification.

BVT KKS APD SN

SPD class MNominal voltage UN 36 V

Max. continuous operating d.c. voltage Uc 36.8 V

Nominal current IL 0.1 A

D1 Total lightning impulse current (10/350 µs) I imp 7 kA

D1 Lightning impulse current (10/350 µs) per line I imp 3.5 kA

C2 Total nominal discharge current (8/20 µs) In 40 kA

C2 Nominal discharge current (8/20 µs) per line In 20 kA

Voltage protection level line-line for Iimp D1 Up 65 V

Voltage protection level line-PG for Iimp D1 Up 900 V

Voltage protection level line-line at 1 kV/µs C3 Up

48 VVoltage protection level line-PG at 1 kV/µs PG Up 600 V

A2 Total a.c. current carrying capacity 20 A

Series impedance per line 10 ohms

Cut-off frequency line-line fG 6 MHz

Capacitance line-line C 1 nF

Capacitance line-PG C 10 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.5 - 6 mm2

Cross-sectional area, flexible 0.5 - 4 mm2

Tightening torque (terminal) 0.8 Nm

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications SNAM specification, GOST

Type of remote signalling contacts break contact

Switching capacity d.c. 250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A

Switching capacity a.c. 250 V/0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2

Ordering information

Type BVT KKS APD SN

Part No. 918 405

Packing unit 1 pc(s).

Page 231: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 231/382www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

229

DEHNrapid® LSA

Lightning current / surge arrester

• Variable protection for 1 – 10 pairs for LSA sys-tems, type series 2/10

• LSA disconnection block function integrated inthe lightning current arrester provides protec-tion for testing, disconnecting and patching

• Modular system of lightning current and surgearresters, allows also for combination to onecombined SPD

DRL plug-in SPD block (10 pairs):

Lightning current arrester for 10 pairs.DRL plug (1 pair):Surge protective plug for 1 pair, energy-coordinated withDRL plug-in SPD blocks.

Lightning current arrester, surge arrester or combined lightning currentand surge arrester, pluggable into type 2 LSA disconnection blocks. The10-pair plug-in SPD block with lightning current carrying capacity incor-porates gas discharge tubes (optional visual fault indication) and discon-nection block contacts. This allows for testing, disconnecting or patching

of pairs with plugged-in protection or the additional attachment of single-pair surge arresters for optimal protection of terminal equipment. Thesurge arresters snap into the earthing frame and can be removed as ablock, whenever required.

DRL XX XXX ...

EF 10 DRL

DRL 10 B 180

TL 2 10DA LSA

MB 2 10DA LSA

surge arrester

O

+

lightning

current

arrester

G

= c o m b i n e d l i g h t n i n g

c u r r e n t a n d

s u r g e a r r e s t e r

G O

DRL system design

The DEHNrapid LSA lightning current arrester for LSA disconnection blockseffectively protects sensitive hardware from surges and allows for simul-taneous testing, disconnecting and patching of connected lines. The mod-ular SPD system for LSA disconnection blocks can be extended to a com-bined lightning current and surge arrester and features fail-safe overloadprotection with visual fault indication of the discharge elements.

5 2 .

5 7 2 .

2 8 2 .

9 9 1 .

4

DRL assembly with the relevant heights

Page 232: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 232/382230 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

DRL protective plugs with earthing frame

DRL combined lightning current and surge arrester

a ba’b’

a a'

a ba’b’

a a'

TL 2 10DA LSADRL 10 B 180...

The plug-in SPD block has disconnection contacts that are compatiblewith the disconnection block. A measuring or disconnection adapter canbe plugged into the DRL in the same way as a disconnection block toensure protection during maintenance operation.

With the appropriate earthing frame, the fine limiting DEHNrapid LSA sin-gle-pair surge arresters can be plugged directly into the DRL plug-in SPDblock or optionally into LSA disconnection blocks.The decoupling imped-

ances integrated in the protective plugs allow energy coordination withthe DRL plug-in SPD block irrespective of the cable length. The single-pairplug also allows partial insertion of disconnection blocks including thepossibility to plug protective plugs with different circuits or nominal volt-ages into one block.

The integrated unit of plug-in SPD block, earthing frame and protectiveplug (combined lightning current and surge arrester) can be completelyremoved and plugged in. The combined lightning current and surgearrester corresponds to SPD Class GO.

Disconnection block function

DEHNrapid® LSA

Lightning current / surge arrester

fail-safe

light pink fail-safe

dark purple

ok replace

new

DRL 10 B 180 FSDA fail-safe function short-circuits the lines to earth to protect the gas dis-charge tube from a possible burn-off due to overcurrents. In the event of an overcurrent, the disconnecting solder between the spring and the SPDmelts, the lines are short-circuited and the temperature-sensitive colouron the spring changes from light pink to dark purple, signalling the userto replace the SPD.

Replace the faulty gas discharge tube

Page 233: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 233/382231www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

DEHNrapid® LSA

DRL 10 BDRL 10 B

• Lightning current arrester for use asplug-in SPD block with integrated LSAdisconnection block function

• Extendible to a combined lightningcurrent and surge arrester

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 1 and higher

1 2 3 4 5 6 7 8 9 10

IN

OUT

a b

a’ b’

SPD block with 3-pole gas discharge tubes.Integrated isolating contacts for plugging

additional elements.

Dimension drawing DRL 10 B

DRL plug-in SPD block (10 pairs) with lightning current carrying capacity, for nearly all kinds of appli-cations. Extendible with DRL protective plug to a combined lightning current and surge arrester. Theintegrated disconnection block contacts allow for testing, measuring and patching in case of plugged-in protection.

DRL 10 B 180

SPD class GNominal voltage UN 180 V

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Nominal current IL 0.4 A

D1 Total lightning impulse current (10/350 µs) I imp 5 kA

D1 Lightning impulse current (10/350 µs) per line I imp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for Iimp D1 Up 500 V

Voltage protection level line-PG for Iimp D1 Up

500 VVoltage protection level line-line at 1 kV/µs C3 Up 500 V

Voltage protection level line-PG at 1 kV/µs C3 Up 450 V

Series impedance per line 0.005 ohms

Capacitance line-line C 5 pF

Capacitance line-PG C 5 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 10

Pluggable into LSA disconnection block 2/10

Earthing via mounting frame

Enclosure material polyamide PA 6.6

Colour grey

Test standards IEC 61643-21

Approvals, Certifications VdS, GOST

Ordering information

Type DRL 10 B 180

Part No. 907 400

Packing unit 10 pc(s).

Accessory Part for DEHNrapid® LSA

Gas discharge tubeHigh-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Three-pole unit with common arc chamber for a constant voltage protection levelfor line-line and line-ground.Type GDT 230 B3 GDT 230 B3 FSD

Integrated into Part No. 907 400 907 401

Visual fault indicator — 3

Fail-safe spring — 3

PU PartType pc(s). No.

GDT 230 B3 1 907 218

GDT 230 B3 FSD 1 907 219

907 218 GDT 230B3907 219 GDT 230B 3 FSD

GDT230B3907 218G DT2 3 0 B 3 FSD907 219

Accessory Part for DEHNrapid® LSA

Label holderUniversal label holder made of stainless steel, for clear marking of LSA connections. Can be snapped onto DEHNrapid LSA plug-inSPD blocks, earthing frames with protective plug or mountingframes with LSA SPD blocks, 2/10 series.

PU PartType pc(s). No.

SR DRL 1 907 497

907 497 SR DRL

SR DR L907 497

Page 234: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 234/382232 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

DEHNrapid® LSA

DRL 10 B FSD907 401 DRL 10 B180FSD

DR L 1 0 B 1 8 0 FSD907 401

• Lightning current arrester for use asplug-in SPD block with integrated LSAdisconnection block function

• Visual fault indicator of the gasdischarge tubes

• Extendible with DRL protective plugsto a combined lightning current andsurge arrester

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 1 and higher

1 2 3 4 5 6 7 8 9 10

IN

OUT

a b

a’ b’

SPD block with 3-pole gas discharge tubes withfail-safe function. Integrated isolating contacts

for plugging additional elements.

Dimension drawing DRL 10 B FSD

DRL plug-in SPD block (10 pairs) with lightning current carrying capacity, for nearly all types of appli-cations. Extendible with DRL protective plug to a combined lightning current and surge arrester. Theintegrated disconnection block contacts allow for testing, measuring and patching in case of plugged-in protection.The gas discharge tubes have a fail-safe function with visual indicator for potential faults.

DRL 10 B 180 FSD

SPD class GFault indication visually by colour change

Nominal voltage UN 180 V

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Nominal current IL 0.4 A

D1 Total lightning impulse current (10/350 µs) I imp 5 kA

D1 Lightning impulse current (10/350 µs) per line I imp 2.5 kA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for Iimp D1 Up

500 VVoltage protection level line-PG for Iimp D1 Up 500 V

Voltage protection level line-line at 1 kV/µs C3 Up 500 V

Voltage protection level line-PG at 1 kV/µs C3 Up 450 V

Series impedance per line 0.005 ohms

Capacitance line-line C 5 pF

Capacitance line-PG C 5 pF

Fail-safe performance gas discharge tube with spring contacts

Operating temperature range -40°C...+80°C

Degree of protection IP 10

Pluggable into LSA disconnection block 2/10

Earthing via mounting frame

Enclosure material polyamide PA 6.6

Colour greyTest standards IEC 61643-21

Approvals, Certifications VdS, GOST

Ordering information

Type DRL 10 B 180 FSD

Part No. 907 401

Packing unit 10 pc(s).

Gas discharge tubeHigh-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Three-pole unit with common arc chamber for a constant voltage protection levelfor line-line and line-ground.Type GDT 230 B3 GDT 230 B3 FSD

Integrated into Part No. 907 400 907 401Visual fault indicator — 3

Fail-safe spring — 3

PU PartType pc(s). No.

GDT 230 B3 1 907 218

GDT 230 B3 FSD 1 907 219

907 218 GDT 230B3907 219 GDT 230B 3 FSD

GDT230B3907 218G DT2 3 0 B 3 FSD907 219

Label holderUniversal label holder made of stainless steel, for clear marking of LSA connections. Can be snapped onto DEHNrapid LSA plug-inSPD blocks, earthing frames with protective plug or mountingframes with LSA SPD blocks, 2/10 series.

PU PartType pc(s). No.

SR DRL 1 907 497

907 497 SR DRL

SR DR L907 497

Page 235: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 235/382233www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

DEHNrapid® LSA

DRL REDRL RE 5DRL RE

DRL RE

DRL RE

DRL RE

DRL RE

• Low voltage protection level for theprotection of terminal equipment

• Energy-coordinated with DRL plug-inSPD block

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

a

b

a

b

IN OUT

Protective circuit energy-coordinated with DRL 10 Bfor protecting terminal equipment, fine limitation

between line and PG

9.422

3 3

. 4

8 . 5

Dimension drawing DRL RE

Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block, for use as single-stageprotection for terminal equipment with decoupling impedances. Ideally suited for signal circuitswith common potential. Earthing via EF 10 DRL. For disconnection blocks or DRL plug-in SPD blocksonly.

DRL RE 5 DRL RE 12 DRL RE 24 DRL RE 48 DRL RE 60 DRL RE 180

SPD class O O O O O ONominal voltage UN 5 V 12 V 24 V 48 V 60 V 180 V

Max. continuous operating d.c. voltage UC 6 V 14 V 28 V 54 V 70 V 180 V

Max. continuous operating a.c. voltage UC 4.2 V 9.5 V 19.5 V 38 V 49.5 V 127 V

Nominal current IL 0.4 A 0.4 A 0.4 A 0.4 A 0.4 A 0.1 A

D1 Total lightning impulse current (10/350 µs)

in combination with DRL 10 B... Iimp 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA

D1 Lightning impulse current (10/350 µs) per line

in combination with DRL 10 B... Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs)

in combination with DRL 10 B... In 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) per line

in combination with DRL 10 B... In 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA

Voltage protection level line-PG for Iimp D1

in combination with DRL 10 B... Up 40 V 45 V 65 V 95 V 115 V 280 V

Voltage protection level line-line at 1 kV/µs C3 Up 17.0 V 36 V 72 V 135 V 185 V 500 V

Voltage protection level line-PG at 1 kV/µs C3 Up 9.5 V 19 V 38 V 70 V 95 V 270 V

Series impedance per line 4.7 ohms 4.7 ohms 4.7 ohms 6.8 ohms 6.8 ohms 4.7 ohms

Cut-off frequency line-PG fG 0.95 MHz 2.7 MHz 4.5 MHz 7.35 MHz 10.5 MHz 42 MHz

Capacitance line-line C 3 nF 1 nF 0.55 pF 350 pF 250 pF 50 pF

Capacitance line-PG C 6 nF 2 nF 1.1 nF 700 pF 500 pF 80 pF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Degree of protection IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in

Pluggable into LSA disconnection block 2/10 or DRL 10 B ... plug-in SPD block

Earthing via earthing frame earthing frame earthing frame earthing frame earthing frame earthing frameEnclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6

Colour yellow yellow yellow yellow yellow yellow

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21

Approvals, Certifications VdS, GOST VdS, GOST VdS, GOST VdS, GOST VdS, GOST VdS, GOST

Ordering information

Type DRL RE 5 DRL RE 12 DRL RE 24 DRL RE 48 DRL RE 60 DRL RE 180

Part No. 907 420 907 421 907 422 907 423 907 424 907 425

Packing unit 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

Earthing frameEarthing frame with snap-on mechanism, required for earthing andmounting max. 10 DRL protective plugs. Pluggable onto a 10-pair dis-connection block or DRL plug-in SPD block.

PU PartType pc(s). No.

EF 10 DRL 1 907 498

907 498 EF 10 DRL

E F1 0 DR L907 498

Label holderUniversal label holder made of stainless steel, for clear marking of LSAconnections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks,earthing frames with protective plug or mounting frames with LSA SPDblocks, 2/10 series.

PU PartType pc(s). No.

SR DRL 1 907 497

907 497 SR DRL

SR DR L907 497

Page 236: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 236/382234 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

DEHNrapid® LSA

DRL RD907 440 DRL RD 5907 441 DRL RD12907 442 DRL RD24907 443 DRL RD48907 444 DRL RD60907 445 DRL RD110

DR L R D5907 440DR L R D1 2907 441DR L R D2 4907 442DR L R D4 8907 443DR L R D6 0907 444DR L R D1 1 0907 445

• Low voltage protection level line/linefor the protection of terminal equip-ment

• Energy-coordinated with DRL plug-inSPD block

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

a

b

IN OUT

Line-line protective circuit, energy-coordinatedwith DRL 10 B for protecting terminal equipment.

9.422

3 3

. 4

8 . 5

Dimension drawing DRL RD

Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block for use as single-stage pro-tection for terminal equipment. Low voltage protection levels line-line for electrically isolated inter-faces. For mounting with EF 10 DRL. Installation recommended only in combination with DRL plug-in SPD block.

DRL RD 5 DRL RD 12 DRL RD 24 DRL RD 48 DRL RD 60 DRL RD 110

SPD class O O O O O ONominal voltage UN 5 V 12 V 24 V 48 V 60 V 110 V

Max. continuous operating d.c. voltage UC 6 V 14 V 28 V 54 V 70 V 180 V

Max. continuous operating a.c. voltage UC 4.2 V 9.5 V 19.5 V 38 V 49.5 V 127 V

Nominal current IL 0.4 A 0.4 A 0.4 A 0.4 A 0.4 A 0.4 A

D1 Total lightning impulse current (10/350 µs)

in combination with DRL 10 B... Iimp 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA

D1 Lightning impulse current (10/350 µs) per line

in combination with DRL 10 B... Iimp 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs)in combination with DRL 10 B... In 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) per line

in combination with DRL 10 B... In 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA

Voltage protection level line-PG for Iimp D1

in combination with DRL 10 B... Up 500 V 500 V 500 V 500 V 500 V 500 V

Voltage protection level line-line at 1 kV/µs C3 Up 8.5 V 18 V 36 V 70 V 95 V 250 V

Series impedance per line 2.2 ohms 2.2 ohms 2.2 ohms 4.7 ohms 4.7 ohms 4.7 ohms

Cut-off frequency line-line fG 1 MHz 2.7 MHz 5.4 MHz 7.8 MHz 11 MHz 20 MHz

Capacitance line-line C 5.5 nF 2.0 nF 1.1 nF 700 pF 500 pF 200 pF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

Degree of protection IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in IP 20 plugged in

Pluggable into LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block

Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6

Colour yellow yellow yellow yellow yellow yellow

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21 IEC 61643-21

Approvals, Certifications VdS, GOST VdS, GOST VdS, GOST VdS, GOST VdS, GOST GOST

Ordering information

Type DRL RD 5 DRL RD 12 DRL RD 24 DRL RD 48 DRL RD 60 DRL RD 110

Part No. 907 440 907 441 907 442 907 443 907 444 907 445

Packing unit 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

Earthing frameEarthing frame with snap-on mechanism, required for earthing and

mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pairdisconnection block or DRL plug-in SPD block.PU Part

Type pc(s). No.

EF 10 DRL 1 907 498

907 498 EF 10 DRL

E F1 0 DR L907 498

Label holderUniversal label holder made of stainless steel, for clear marking of LSA

connections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks,earthing frames with protective plug or mounting frames with LSA SPDblocks, 2/10 series.

PU PartType pc(s). No.

SR DRL 1 907 497

907 497 SR DRL

SR DR L907 497

Page 237: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 237/382235www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

DEHNrapid® LSA

DRL PDDRL PD

• For maximum transmission rates –combined with overcurrent protection

• Energy-coordinated with DRL plug-inSPD block

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

a

b

IN OUT

Protective circuit, energy-coordinated with DRL 10 Bfor protecting terminal equipment, fine limitation

between the lines and additional overcurrentprotection.

9.422

3 3

. 4

8 . 5

Dimension drawing DRL PD

Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block for use as single-stage pro-tection for terminal equipment. Low voltage protection level line-line and integrated overcurrent pro-tection for ADSL, ISDN Uk0 or a/b lines. For mounting with EF 10 DRL. Installation recommended only

in combination with DRL plug-in SPD block.

DRL PD 180

SPD class ONominal voltage UN 180 V

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Nominal current IL 0.1 A

D1 Total lightning impulse current (10/350 µs)

in combination with DRL 10 B... Iimp 5 kA

D1 Lightning impulse current (10/350 µs) per line

in combination with DRL 10 B... Iimp 2.5 kA

C2 Total nominal discharge current (8/20 µs)in combination with DRL 10 B... In 10 kA

C2 Nominal discharge current (8/20 µs) per line

in combination with DRL 10 B... In 5 kA

Voltage protection level line-PG for Iimp D1

in combination with DRL 10 B... Up 500 V

Voltage protection level line-line at 1 kV/µs C3 Up 270 V

Series impedance per line 10 ohms

Cut-off frequency line-line fG 61 MHz

Capacitance line-line C 80 pF

Integrated overcurrent protection 3

Operating temperature range 0°C...+70°C

Degree of protection IP 20 plugged in

Pluggable into LSA disconnection block 2/10 or DRL 10 B... plug-in SPD blockEnclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type DRL PD 180

Part No. 907 430

Packing unit 10 pc(s).

Earthing frameEarthing frame with snap-on mechanism, required for earthing and

mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pairdisconnection block or DRL plug-in SPD block.PU Part

Type pc(s). No.

EF 10 DRL 1 907 498

907 498 EF 10 DRL

E F1 0 DR L907 498

Label holderUniversal label holder made of stainless steel, for clear marking of

LSA connections. Can be snapped onto DEHNrapid LSA plug-inSPD blocks, earthing frames with protective plug or mountingframes with LSA SPD blocks, 2/10 series.

PU PartType pc(s). No.

SR DRL 1 907 497

907 497 SR DRL

SR DR L907 497

Page 238: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 238/382236 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

DEHNrapid® LSA

DRL HD907 465 DRL HD 5907 470 DRL HD24

DR L HD5907 465DR L HD2 4907 470

• For maximum transmission rates

• Energy-coordinated with DRL plug-inSPD block

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

a

b

IN OUT

Protective circuit, energy-coordinated with DRL 10 B,with low capacitance for protection of terminal

equipment line-line.

9.422

3 3

. 4

8 . 5

Dimension drawing DRL HD

Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block, for use as single-stageprotection for terminal equipment for high-frequency transmissions such as G.703 or ISDN U2m, S2m

and S0. To be mounted with EF 10 DRL. Installation recommended only in combination with DRLplug-in SPD block.

DRL HD 5 DRL HD 24

SPD class O ONominal voltage UN 5 V 24 V

Max. continuous operating d.c. voltage UC 6.5 V 28 V

Max. continuous operating a.c. voltage UC 4.6 V 19.5 V

Nominal current IL 0.4 A 0.4 A

D1 Total lightning impulse current (10/350 µs)

in combination with DRL 10 B... Iimp 5 kA 5 kA

D1 Lightning impulse current (10/350 µs) per line

in combination with DRL 10 B... Iimp 2.5 kA 2.5 kA

C2 Total nominal discharge current (8/20 µs)

in combination with DRL 10 B... In 10 kA 10 kAC2 Nominal discharge current (8/20 µs) per line

in combination with DRL 10 B... In 5 kA 5 kA

Voltage protection level line-PG for Iimp D1

in combination with DRL 10 B... Up 500 V 500 V

Voltage protection level line-line at 1 kV/µs C3 Up 25 V 46 V

Series impedance per line 2.2 ohms 4.7 ohms

Cut-off frequency line-line fG 90 MHz 94 MHz

Capacitance line-line C 22 pF 22 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Degree of protection IP 20 plugged in IP 20 plugged in

Pluggable into LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block

Enclosure material polyamide PA 6.6 polyamide PA 6.6

Colour yellow yellow

Test standards IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST VdS, GOST

Ordering information

Type DRL HD 5 DRL HD 24

Part No. 907 465 907 470

Packing unit 10 pc(s). 10 pc(s).

Earthing frameEarthing frame with snap-on mechanism, required for earthing and

mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pairdisconnection block or DRL plug-in SPD block.PU Part

Type pc(s). No.

EF 10 DRL 1 907 498

907 498 EF 10 DRL

E F1 0 DR L907 498

Label holderUniversal label holder made of stainless steel, for clear marking of LSA

connections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks,earthing frames with protective plug or mounting frames with LSA SPDblocks, 2/10 series.

PU PartType pc(s). No.

SR DRL 1 907 497

907 497 SR DRL

SR DR L907 497

Page 239: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 239/382237www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

Accessories for DEHNrapid® LSA

Earthing frameEF 10 DRL

Dimension drawing EF 10 DRL

Earthing frame with snap-on mechanism, required for earthing and mounting of max. 10 DRL pro-tective plugs. Pluggable onto a 10-pair disconnection block or DRL plug-in SPD block.

EF 10 DRL

Pluggable into LSA disconnection blocks or DRL plug-in block

Earthing via mounting frame or DRL plug-in block

Enclosure material polyamide PA 6.6

Colour yellow

Ordering information

Type EF 10 DRL

Part No. 907 498

Packing unit 1 pc(s).

Page 240: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 240/382238 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

DEHNrapid® LSA Plug-in SPD Block

(without SPDs)907 499 BM 10DRL

B M 1 0 DR L907 499

• Integrated disconnection contacts

• For LSA disconnection blocks of type2/10

• Individual insertion of SPDs

1 2 3 4 5 6 7 8 9 10

IN

OUT

a b

a’ b’

SPD block for 3-pole gas discharge tubes.Integrated disconnection contacts for plugging

additional elements.

Dimension drawing BM 10 DRL

Plug-in SPD block (without SPDs) for 1 to max. 10 gas discharge tubes of type GDT 230 B3 ... .Can also be used for inserting DRL protective plugs with earthing frame.

BM 10 DRL

Pluggable into LSA disconnection blocks

Earthing via mounting frame

Enclosure material polyamide PA 6.6

Colour grey

Ordering information

Type BM 10 DRL

Part No. 907 499

Packing unit 10 pc(s).

Accessory Part for DEHNrapid® LSA Plug-in SPD Block(without SPDs)

Gas discharge tubeHigh-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Three-pole unit with common arc chamber for a constant voltage protection levelfor line-line and line-ground.

Type GDT 230 B3 GDT 230 B3 FSD

Integrated into Part No. 907 400 907 401

Visual fault indicator — 3

Fail-safe spring — 3

PU PartType pc(s). No.

GDT 230 B3 1 907 218GDT 230 B3 FSD 1 907 219

907 218 GDT 230B3907 219 GDT 230B 3 FSD

GDT230B3907 218G DT2 3 0 B 3 FSD907 219

Accessory Part for DEHNrapid® LSA Plug-in SPD Block(without SPDs)

Label holderUniversal label holder made of stainless steel, for clear marking of LSA connections. Can be snapped onto DEHNrapid LSA plug-inSPD blocks, earthing frames with protective plug or mountingframes with LSA SPD blocks, 2/10 series.

PU PartType pc(s). No.

SR DRL 1 907 497

907 497 SR DRL

SR DR L907 497

Page 241: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 241/382239www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

DPL 10 G3

Surge arrester

• Suitable for terminal and disconnection blocksof LSA systems, type series 2/10

• For 10 pairs with individually tested gas dis-charge tubes

• Individually replaceable protection elements(gas discharge tubes)

Pluggable SPDs for use in LSA systems, type series 2/10.Unit for use as protection block for 10 pairs with individually replaceableprotection elements.

Pluggable surge arresters for use as protection blocks in IT installationsand devices, which have to be connected via terminal or disconnectionblocks with LSA IDC terminal. Installation onto terminal blocks, however,is the preferred method, as their contact forces provide better fixation –

even in case of slight vibrations.

The surge arresters for 10 pairs can be easily installed and removed fortesting purposes.The contact to earth via the mounting frame is automat-ically established when plugging in the SPD. After being overloaded, theprotection elements can be individually replaced.

The protection blocks consist of simi-lar basic SPD blocks, which are sup-plied and tested with different pro-tection elements according torequirements.DPL 10 G3:

10 standard gas discharge tubesDPL 10 G3 FSD:

10 gas discharge tubes with fail-safefunction and visual indicator

DPL 10 G3 family

DPL 10 G3 ...

AL 2 10DA LSA or

TL 2 10DA LSA

MB 2 10DA LSA

Installation of DPL

Page 242: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 242/382240 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

DPL 10 G3

DPL 10 G3907 214 DPL 10G3110907 216 DPL 10G3110FSD

DPL 10 G3 110 LSA-PlusTechnology, 10 TC 907 214DPL 10 G3 110 FSD907 216

• Powerful SPD block

• Types with/without fail-safe functionor visual indicator

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 1 and higher

1 2 3 4 5 6 7 8 9 10

IN

OUT

Block with 3-pole gas discharge tubes. As soon asthe fail-safe function is activated, the relevant

lines are short-circuited to earth.

Dimension drawing DPL 10 G3

Protective plug for 10 pairs with tripod gas discharge tubes for nearly all types of applications. SPDsof type FSD have a fail-safe function and provide additional visual indication after the fail-safe fea-ture has been activated. This helps to recognise immediately if an SPD has to be replaced.

DPL 10 G3 110 DPL 10 G3 110 FSD

SPD class B BFault indicator — visually by colour change

Nominal voltage UN 110 V 110 V

Max. continuous operating d.c. voltage Uc 180 V 180 V

Max. continuous operating a.c. voltage Uc 127 V 127 V

Nominal current IL 0.4 A 0.4 A

C2 Total nominal discharge current (8/20 µs) In 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA 5 kA

Voltage protection level line-line for In C2 UP 600 V 600 V

Voltage protection level line-PG for In C2 Up 600 V 600 V

Voltage protection level line-line at 1 kV/µs C3 Up

600 V

600 VVoltage protection level line-PG at 1 kV/µs C3 Up 600 V 600 V

Capacitance line-line C 5 pF 5 pF

Capacitance line-PG C 5 pF 5 pF

Fail-safe performance — gas discharge tube with spring contacts

Operating temperature range -40°C...+80°C -40°C...+80°C

Pluggable into LSA disconnection and terminal blocks (type 2) LSA disconnection and terminal blocks (type 2)

Earthing via mounting frame mounting frame

Enclosure material polyamide polyamide

Colour grey grey

Test standards IEC 61643-21 IEC 61643-21

Ordering information

Type DPL 10 G3 110 DPL 10 G3 110 FSDPart No. 907 214 907 216

Packing unit 10 pc(s). 10 pc(s).

Accessory Part for DPL 10 G3

Gas discharge tubeHigh-capacity spare gas discharge tube for DPL 10 G3. Three-pole typewith common arc chamber for a constant protection level for bothline/line and line/earth.

Type GDT 230 G3 GDT 230 G3 FSD

Integrated into Part No. 907 214 907 216

Visual fault indicator — 3

Fail-safe spring — 3PU Part

Type pc(s). No.

GDT 230 G3 1 907 208

GDT 230 G3 FSD 1 907 217

907 208 GDT 230G3907 217 GDT 230G3FSD

GDT230 G3907 208G DT2 3 0 G 3 FSD907 217

Page 243: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 243/382241www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

DEHN Enclosure for Equipotential Bonding

Enclosure system for SPDs protecting IT equipment

• Premounted enclosure system for wiring andprotection components

• Tested lightning impulse current carryingcapacity

• Optimised for equipotential bonding (surgearrester and shield connection)

• Metal enclosure, lockable against unauthorisedaccess

DEHN enclosures for equipotential bonding (DPG) are lockable metalenclosures and intended for installation of wiring and protection compo-nents. Available in four different sizes, the enclosures which are capableof carrying lightning currents provide terminals to integrate surgearresters and shields into the equipotential bonding.

Enclosure with lightning current carrying capacity, IP 40, for differentdesigns of distribution boards and for the insertion of surge arresters. Thecover can be removed from the wall plate without tools and is equipped

with a lock with cylinder quarter turn and a key. The C-shaped design of the wall plate facilitates installation work by sidewise or front access. LSAmounting frames or DIN rails can be attached to the wall plate by meansof cable entry plates and cable rails.

Despite of a high packing density, a structured cabling management isensured – crossings between cabling and wiring are avoided and thecabling of e.g. the LSA blocks becomes concise due to the 30 mm grid. For

this kind of cabling, an optional shield connection system is available(constant force spring). The sophisticated earthing system permanentlyconnects all conductive components of the enclosure system by mechan-ical contacting or earth conductors by means of an earthing block.

DEHN enclosures for equipotential bonding (DPG) are available in 4 dif-ferent sizes, allowing for the insertion of 3/6/12/22 LSA blocks. Even if 20/50/100/200 pairs are used, enough space is provided for the earth con-ductor block for supporting shielded sheath wires.

DEHN enclosures for equipotential bonding (DPG) in 4 different sizes

The shields of incoming conduc-tors can be contacted with con-stant force springs of type SA KRFin a space-saving way and withlightning current capacity. All

equipotential bonding conductorsare led together in the centralearthing block.

Shield connection with SA KRF

Page 244: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 244/382242 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

DEHN Enclosure for Equipotential Bonding

DPG LSA906 100 DPG LSA30 P906 101 DPG LSA60 P906 102 DPG LSA120 P906 103 DPG LSA220 P

DPG LSA30 P906 100DPG LSA60 P906 101DPG LSA120 P906 102DPG LSA220 P906 103

• Earthing system with lightning currentcarrying capacity for SPDs and shieldconnection

• Integrated mounting frame for LSAblocks with a grid dimension of 30 mm

• Reserved space for uninterferedcabling and surge arresters

DPG LSA is a completely premounted enclosure system with LSA mounting frame and allows opti-mised use of SPDs and shield connection systems (constant force spring).

DPG LSA 30 P DPG LSA 60 P DPG LSA 120 P DPG LSA 220 P

Carrying capacity of connection components

D1 Total lightning impulse current (10/350 µs) I imp 15 kA 30 kA 50 kA 50 kA

LSA mounting frame for 1 x 3 blocks 2/10 1 x 6 blocks 2/10 2 x 6 blocks 2/10 2 x 11 blocks 2/10

Grid dimension of mounting frame 30 mm 30 mm 30 mm 30 mm

Wirings 1 pc(s). 2 pc(s). 2 pc(s). 3 pc(s).

Cable entries top / bottom top / bottom top / bottom top / bottom

Cable rail top / bottom top / bottom top / bottom top / bottom

Lock yes yes yes yes

For mounting on wall wall wall wall

Degree of protection IP 40 IP 40 IP 40 IP 40

Earthing via earthing block earthing block earthing block earthing block

Dimension W x H x D 240 x 260 x 130 mm 240 x 350 x 130 mm 330 x 350 x 130 mm 330 x 500 x 130 mm

Enclosure material steel plate steel plate steel plate steel plate

Colour RAL 9002 RAL 9002 RAL 9002 RAL 9002

Ordering information

Type DPG LSA 30 P DPG LSA 60 P DPG LSA 120 P DPG LSA 220 P

Part No. 906 100 906 101 906 102 906 103

Packing unit 1 pc(s). 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for DEHN Enclosure for Equipotential Bonding

Constant force springConstant force springs allow solderless shield connections for equipo-tential bonding or lightning equipotential bonding.They can be instal-led subsequently without interrupting the conductor shield or requiringtools for installation. Approved for nuclear installations according toTÜV Certificate No. T12-04-ETL003 (TÜV = German TechnicalInspectorate).

PU PartType Clamping range Material pc(s). No.

SA KRF 10 V2A 4 - 10 mm StSt 20 919 031

SA KRF 15 V2A 9 - 15 mm StSt 20 919 032

SA KRF 22 V2A 14 - 22 mm StSt 20 919 033

S A KRF 29 V2A 18.5 - 29 mm StSt 10 919 034

S A KRF 37 V2A 23.5 - 37 mm StSt 10 919 035

919 031 SA KRF10 V2A919 032 SA KRF15 V2A919 033 SA KRF22 V2A919 034 SA KRF29 V2A919 035 SA KRF37 V2A

SA KRF 10 V2A ContactF or ce S pr in g fo r sh ie ld c on ne c ti on 9 19 0 31SA KRF 15 V2A ContactF or ce S pr in g fo r sh ie ld c on ne c ti on 9 19 0 32SA KRF 22 V2A ContactF or ce S pr in g fo r sh ie ld c on ne c ti on 9 19 0 33SA KRF 29 V2A ContactF or ce S pr in g fo r sh ie ld c on ne c ti on 9 19 0 34SA KRF 37 V2A ContactF or ce S pr in g fo r sh ie ld c on ne c ti on 9 19 0 35

Accessory Part for DEHN Enclosure for Equipotential Bonding

Self-bonding rubber tapeReel with 9 m self-bonding rubber tape for wrapping around constantforce springs for permanent corrosion protection.

PU PartType pc(s). No.

SKB 19 9M SW 1 919 030

919 030 SKB 199MSW

SK B 1 9 9 M SWS elfbonding Rubbe rTape 919 030

Page 245: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 245/382243www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

Accessories for LSA Technology

• Proven quality

• 45° angled blades in the contact for a lower

cross-sectional variation in the conductor– Enhanced stability of the conductor

– Enhanced corrosion resistance

• Further accessories available on request

The IDC method is used for installing many lines quickly and economical-ly. This method is commonly used in telecommunications (e.g. DeutscheTelekom AG).The blocks are suitable for connecting plastic-insulated wires with copperconductor material:Conductor diameter: 0.4-0.8 mmOuter diameter: 0.7-1.5 mm

After using wires with a diameter of 0.65 mm, rewiring to smaller diam-eters is no longer possible.

Mounting frame

MB2 10

Mounting907 995

Monuting frame for 10 LSA blocks, type series 2/10. Total width: 104.5 mm

MB2 10 LSA

Ordering information

Type MB2 10 LSA

Part No. 907 995

Packing unit 1 pc(s).

Insertion toolsAW2 LSA

Insertion907 994

Insertion tools with sensor for LSA technology for connecting the wires and simultaneously cuttingresidual lengths.With extractor hook and unlatching blade.

AW2 LSA

Ordering information

Type AW2 LSA

Part No. 907 994

Packing unit 1 pc(s).

Page 246: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 246/382244 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

Disconnection block907 996 TL2 10DALSA

TL2 10DALSAD is co nn ec t io n Mo du le s 10 T C LS A -P LU S 9 07 9 96

Type series 2 for LSA technology for connecting 10 pairs, each on the cable and routing side. Byplugging in DRL, the protection is serially provided between the disconnection contacts.Allows alsofor plugging in DPL 10 G3 arresters.

TL2 10DA LSA

Enclosure material PBT

Test standards DIN 47608-1, -2

Standards, Certifications corresponds to DTAG TS 0272/96

IPC terminal for solid conductor diameters 0.40 - 0.80 mm

Outer diameter via insulation of IPC terminal 0.70 - 1.50 mm

Contacting frequency 0.65 conductor diameter > 50 x

Contacting frequency 0.8 conductor diameter 50 x

Contact material special brass

Contact surface silver

Flame protection UL 94 V-0

Insulation resistance 5 x 10.000 mohms

Volume resistance of IPC terminal < 10 mohms

Electric strength 2 kV / 50 Hz

Ordering information

Type TL2 10DA LSA

Part No. 907 996

Packing unit 1 pc(s).

Earth conductor block907 993 EL2 38EALSA

EL2 38EA LSA EarthC on du ct or B lo ck , 38 -p ol e LS A -P LU S 9 07 9 93

Type series 2 for LSA technology for connecting 38 earth wires or shields.

EL2 38EA LSA

Ordering information

Type EL2 38EA LSA

Part No. 907 993

Packing unit 1 pc(s).

Terminal block907 997 AL2 10DALSA

AL2 10DA LSA Term inalBlock 10TC LSA-PLUS 907 997

Type series 2 for LSA technology for connecting 10 pairs, each to a non-open termination on thecable and routing side. Allows to plug in DPL 10 G3 arresters. Parallel protective circuit only.

AL2 10DA LSA

Enclosure material PBT

Test standards DIN 47608-1, -2

IPC terminal for solid conductor diameters 0.40 - 0.80 mm

Outer diameter via insulation of IPC terminal 0.70 - 1.50 mm

Contacting frequency 0.65 conductor diameter > 50 x

Contacting frequency 0.8 conductor diameter 50 x

Contact material special brass

Contact surface silver

Flame protection UL 94 V-0

Insulation resistance 5 x 10.000 mohms

Volume resistance of IPC terminal < 10 mohmsElectric strength 2 kV / 50 Hz

Ordering information

Type AL2 10DA LSA

Part No. 907 997

Packing unit 1 pc(s).

Accessories for LSA Technology

Page 247: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 247/382245www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

1

2

3

4

5

6

7

8

9

0

Routing module with LSA spring-loaded terminalfor disconnection blocks

TL2 10DA

• Optional connection to LSA or spring-loaded terminals

• Routing of different wire diameters

• DRL adapted to DIN rail systems

Dimension drawing

DIN rail mounted routing module for disconnection blocks with LSA disconnection block of typeseries 2/10 as well as spring-loaded terminals for variable wire connection. DPL and DEHNrapidLSA surge arresters can be plugged into the routing module.

TL2 10DA CC

Carrying capacity of connection components

D1 Total lightning impulse current (10/350 µs) I imp 5 kA

Operating temperature range -40°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input / output spring or LSA / spring or LSA

Cross-sectional area of spring terminal, solid 0.08 mm2 - 2.5 mm2

Cross-sectional area of spring terminal, flexible 0.08 mm2 - 2.5 mm2

Earthing via DIN rail / flat connector 6.3 mm

Enclosure material PA / PBT

IPC terminal for solid conductor diameters 0.40 - 0.80 mm

Outer diameter via insulation of IPC terminal 0.70 - 1.60 mm

Volume resistance of IPC terminal < 10 mohms

Ordering information

Type TL2 10DA CC

Part No. 907 991

Packing unit 1 pc(s).

Accessories for LSA Technology

Page 248: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 248/382246 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR LSA TECHNOLOGY

Page 249: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 249/382www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

1 2 3 4 5 6 7 8 9 0

247

NET Protector

Surge arrester

• Protects switches, HUBs and telecommunica-tion systems

• Allows for class D according to EN 50173(Gigabit Ethernet)

• Patch panels allow for flexible equipment

• Retrofit versions with plug-in inputs and out-puts

The 482.6 mm (19 inch) enclosure can be supplied with surge protectiveboards for protecting network components (class D) or telecommunica-tion systems.

The 482.6 mm (19 inch) enclosure can be equipped with up to 3 surgeprotection boards to protect active network components such as HUBs,switches (class D) or telecommunication systems. Typical applications:Ethernet, Token Ring, E1 and telephones.

The NET Protector surge arresters require the space of only one verticalmodule and are generally installed in terminal boards. They are insertedas a patch panel with surge protection or as a retrofit version for patch-ing between the patch panel and the device to be protected.

3

b

a

c

c

2

8

4

7

3

9

7

1

NET PRO is modular in design. The empty enclosure can be optionallyequipped with 1, 2 or 3 surge protective panels.

Assembly drawing

The fully shielded 482.6 mm (19 inch) enclosure and its 4TPcircuit board allow class D networks to be established. Thishas been confirmed by the independent GHMT test institute.

GHMT Certificate

Page 250: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 250/382248 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

1 2 3 4 5 6 7 8 9 0

NET Protector

Surge arrester

NET PRO ... LSA

active component

patch panel

NET PRO

active component

EBB min.2.5 mm2

NET PRO ... LSA active component

protectedpatch cable

EBB min.2.5 mm2

protectedpatch cable

19" distribution board

EBB min.2.5 mm2

active componentNET PRO

protectedpatch cable

EBBmin.2.5 mm2

protected cable

19" distribution board

patch cable

The protective boards do not only provide adifferent protective circuit, but also a differentconnection. While the protected output is

always an RJ45 unit, the input can be an IDCterminal or RJ45 unit. The IDC terminal isoften used for the first equipment in a newinstallation, which does not include any patchpanel. The RJ45 unit is a retrofit version forexisting systems and it is patched easily be-tween the patch panel and the active compo-nent.

LSA type as patch panel (left) / retrofit version (right)

Page 251: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 251/382249www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

1 2 3 4 5 6 7 8 9 0

NET Protector

NET PRO 4TPNET PRO

NET PRO

NET PRO

NET-929 035NET-9 29 036NET-929 037

• GHMT certificate for class D channellink

• Low protection level for all lines

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

8

75

46

32

1

8

75

46

32

1

Surge protection for all pairs due to lowcapacitance diode matrix for each pair.

Dimension drawing NET PRO 4TP

Surge protective board fitted with 8-way shielded ports for universal cablings (class D). For univer-sal use as all 4 pairs (4 TP) are protected. To be installed into EG NET PRO 19“ and mounted intodistribution cabinets as a patch panel or retrofit version.

NET PRO 4TP NET PRO LSA 4TP NET PRO 4TP 30

SPD class W W [Nominal voltage UN 5 V 5 V 24 V

Max. continuous operating d.c. voltage Uc 6 V 6 V 30 V

Max. continuous operating a.c. voltage Uc 4.2 V 4.2 V 21.1 V

Nominal current IL 100 mA 100 mA 100 mA

C2 Nominal discharge current (8/20 µs) per port In 2.4 kA 2.4 kA 0.8 kA

C2 Nominal discharge current (8/20 µs) per line In 0.3 kA 0.3 kA 0.1 kA

Voltage protection level line-line for In C2 Up 35 V 35 V 60 V

Voltage protection level line-PG for In C2 Up 35 V 35 V 60 V

Voltage protection level line-line at 1 kV/µs C3 Up 13 V 13 V 40 V

Voltage protection level line-PG at 1 kV/µs C3 Up

13 V

13 V

40 VCut-off frequency line-line at 100 ohms fG 165 MHz 170 MHz 300 MHz

Insertion loss at 100 MHz < 0.4 dB < 0.3 dB < 0.4 dB

Capacitance line-line C 35 pF 35 pF 16 pF

Capacitance line-PG C 50 pF 50 pF 20 pF

Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C

Degree of protection IP 00 IP 00 IP 00

For installation into enclosure enclosure enclosure

Connection input/output RJ45 shielded / RJ45 shielded LSA / RJ45 shielded RJ45 shielded / RJ45 shielded

Pinning 1/2, 3/6, 4/5, 7/8 1/2, 3/6, 4/5, 7/8 1/2, 3/6, 4/5, 7/8

Earthing via enclosure enclosure enclosure

Dimension W x L 135 x 77 mm 135 x 107 mm 135 x 77 mm

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21

Approvals, Certifications Class D, GOST GOST GOST

Ordering information

Type NET PRO 4TP NET PRO LSA 4TP NET PRO 4TP 30

Part No. 929 035 929 036 929 037

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Accessory Part for NET Protector

482.6 mm (19 Inch) EnclosureFully shielded empty enclosure for max. 3 NET Protector protectiveboards.

Type EG NET PRO 19”

Capacity 1 vertical module

Enclosure material stainless steel front / galvanised sheet metal

PU PartType pc(s). No.

EG NET PRO 19” 1 929 034

929 034 EG NETPRO19”

EGNETPRO19”929 034

Page 252: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 252/382250 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

1 2 3 4 5 6 7 8 9 0

NET Protector

NET PRO TC929 071 NET PROTC2929 072 NET PROTC2 LSA

NET PRO TC 2 NET-Protector TC 2, 110 V 929 071NET PRO TC 2 LSA NET-P ro te ct or TC 2 LS A, +B 43 31 10 V 9 29 07 2

• Patch panel or retrofit version

• Protection against power crossingintegrated

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

4

5

3

6

4

5

3

6

PTC thermistors decouple the protective stages andthus provide additional protection against “power

crossings“ for terminal equipment.

Dimension drawing NET PRO TC

Protective board fitted with 8-way unshielded ports for protection against surges and a.c. interfer-ences, for protecting telecommunication systems with analogue or system transmission technology.For installation into EG NET PRO 19“ as retrofit or patch panel version (LSA).

NET PRO TC 2 NET PRO TC 2 LSA

SPD class R RNominal voltage UN 130 V 130 V

Max. continuous operating d.c. voltage Uc 170 V 170 V

Max. continuous operating a.c. voltage Uc 120 V 120 V

Nominal current IL 150 mA 150 mA

C2 Nominal discharge current (8/20 µs) per port In 10 kA 20 kA

C2 Nominal discharge current (8/20 µs) per line In 2.5 kA 5 kA

Voltage protection level line-line for In C2 Up 250 V 275 V

Voltage protection level line-PG for In C2 Up 600 V 600 V

Voltage protection level line-line at 1 kV/µs C3 Up 230 V 230 V

Voltage protection level line-PG at 1 kV/µs C3 Up

600 V

600 VSeries impedance per line 10 ohms 10 ohms

Cut-off frequency line-line fG 10 MHz 10 MHz

Capacitance line-line C 300 pF 300 pF

Capacitance line-PG C 15 pF 15 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Degree of protection IP 00 IP 00

For installation into enclosure enclosure

Connection input/output RJ45 / RJ45 LSA / RJ45

Pinning 4/5,3/6 4/5,3/6

Earthing via enclosure enclosure

Dimension W x L 135 x 77 mm 135 x 107 mm

Test standards IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST

Ordering information

Type NET PRO TC 2 NET PRO TC 2 LSA

Part No. 929 071 929 072

Packing unit 1 pc(s). 1 pc(s).

Accessory Part for NET Protector

482.6 mm (19 Inch) EnclosureFully shielded empty enclosure for max. 3 NET Protector protectiveboards.

Type EG NET PRO 19”

Capacity 1 vertical module

Enclosure material stainless steel front / galvanised sheet metal

PU PartType pc(s). No.

EG NET PRO 19” 1 929 034

929 034 EG NETPRO19”

EGNETPRO19”929 034

Page 253: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 253/382251www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

1 2 3 4 5 6 7 8 9 0

NET Protector

NET PRO E1 LSANET PRO

• Patch panel version

• Corresponds to G.703 specification

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

4

5

1

2

4

5

Energy-coordinated 2-pair protective circuit for E1interfaces

Dimension drawing NET PRO E1 LSA

Surge protective board, patch panel version, fitted with 8-way unshielded ports for E1 interfaces.Installation into EG NET PRO 19“ and mounting in distribution boards upstream of the telecom-munication system. For 2 MBit/s transmissions according to G.703.

NET PRO E1 LSA G703

SPD class TNominal voltage UN 5 V

Max. continuous operating d.c. voltage Uc 6 V

Max. continuous operating a.c. voltage Uc 4.2 V

Nominal current IL 200 mA

C2 Nominal discharge current (8/20 µs) per port In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 Up 40 V

Voltage protection level line-PG for In C2 Up 500 V

Voltage protection level line-line at 1 kV/µs C3 Up 15 V

Voltage protection level line-PG at 1 kV/µs C3 Up

450 VSeries impedance per line 1 ohm

Cut-off frequency line-line at 100 ohms fG 210 MHz

Capacitance line-line C 20 pF

Capacitance line-PG C 25 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 00

For installation into enclosure

Connection input/output LSA / RJ45 socket

Pinning 1/2,4/5

Earthing via enclosure

Dimension W x L 135 x 108 mm

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type NET PRO E1 LSA G703

Part No. 929 075

Packing unit 1 pc(s).

Accessory Part for NET Protector

482.6 mm (19 Inch) EnclosureFully shielded empty enclosure for max. 3 NET Protector protectiveboards.

Type EG NET PRO 19”

Capacity 1 vertical module

Enclosure material stainless steel front / galvanised sheet metal

PU PartType pc(s). No.

EG NET PRO 19” 1 929 034

929 034 EG NETPRO19”

EGNETPRO19”929 034

Page 254: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 254/38225 2 www.dehn.de

INFORMATION TECHNOLOGY SYSTEM S

SPDs FOR 482.6 M M (19 INCH) DATA CABINETS

NET Prot ector

NET PRO 10X TC1 RST92 9 23 0 NET PRO 1 0 X TC1 RST

NETPRO 10X TC1 RST

9 2 9 2 3 0

• Particularly compact design

• Power crossing protection integrated

• Installation in conformity with the

lightning protection zones concept at

the boundaries from 0 B – 2 and higher

4

5

a

b

RJ45

Protective board with 10 ports for protecting telecommunications systems with analogue or sys-

tem t ransmission against overvoltage and a.c. interference.

Input equipped w ith cage spring terminals which can be removed from the PCB as a block. This

allow s to test the lines. For installation i nto EG NET PRO 10X 19" or EG NET PRO 10X. Enclosure

for 3 vertical m odules.

NET PRO 10X TC1 RST

SPD class RNominal voltage UN 180 V

Ma x. continuous operating d.c. voltage Uc 180 V

Ma x. continuous operating a.c. voltage Uc 120 V

Nominal current at 20°C / 50°C / 70°C I L 120 mA / 100 mA / 60 mA

C2 Nominal discharge current (8/20 µs) per port In 10 kA

C2 Nominal discharge current (8/20 µs) per line I n 5 kA

Voltage protection level line-line for In C2 Up ≤ 275 V

Voltage protection level line-PG for In C2 Up ≤ 800 V

Voltage protection level line-line at 1 kV/µs C3 Up ≤ 250 V

Voltage protection level line-PG at 1 kV/µs C3 U p ≤

600 VSeries impedance per line 3 ohms to 12 ohms

Cut-off frequency at 100 ohms fG 55 MHz

Capacitance line-line C ≤ 50 pF

Capacitance line-PG C ≤ 25 pF

Operating temperature range -40°C...+70°C

Degree of protection IP 00

For installation into enclosure

Connection type input/output plug-in spring terminal / RJ45

Pinning 4/5

Earthing via enclosure

Dimension W x L 75 x 73 mm

Test standards IEC 61643-21

Ordering information

Type NET PRO 10X TC1 RST

Part No. 929 230

Packing unit 1 pc(s).

Accessory Part for NET Protector

Unshielded 4 82.6 mm (1 9 Inch) EnclosureUnshielded 19 inch enclosure with a capacity of 5 NET PRO 10X verti-ca l modules, two ear th connect ions and cab le anchor ing ra i l .Accessories: tw o nuts, tw o f lat washers and tw o toothed lock washersfor instal l ing the earth connect ion.

Type EG NET PRO 10X 19”

Capacity 1 vertical module

Enclosure material StSt (V2A)

PU PartType pc(s). No.

EG NET PRO 10X 19” 1 929 234

9 2 9 2 3 4 EG N ET

PRO 10X 19”

EG NETPRO 10X 19”

9 2 9 2 3 4

Accessory Part for NET Protector

Enclosure 482,6 mm (19 inches), 3 vertical modulesUnshielded 19 inch enclosure for vert ical instal lat ion. 3 vert ical modu-les for the insert ion of a NET PRO 10X, with earth connect ion.Accessories: nut, f lat washer, toothed lock washer for instal l ing theearth connect ion.

Type EG NET PRO 10X 3HE

Capacity 1 vertical module

Enclosure material StSt (V2A)

PU PartType pc(s). No.

EG NET PRO 10X 3HE 1 929 235

9 29 2 35 EG N ET

PRO 10X 3HE

EG NETPRO 10X 3HE

9 2 9 2 3 5

N E W

N E W

N E W

avai lable from May 2010

Basic circuit d iagram per pair Dim ension draw ing NET PRO 10X TC1 RST

Page 255: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 255/382www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

253

DEHNpatch

Surge arrester

• Patch cable with built-in surge protection

• Cat. 6 according to ISO/IEC 11801

• For universal use up to 48 V

• Easy to retrofit

DEHNpatch is the first Cat. 6 certified patch cable with built-in surge pro-tection that can be used universally according to EN 50173 for voltagesup to 48 V d.c.

Designed as a patch cable, DEHNpatch is easy to install.The unit is equal-ly suited for use in new installations or retrofitting into existing installa-tions at any time with little effort.DEHNpatch is simply plugged in between the patch panel and the activecomponent (a switch for example) instead of the conventional patch

cable.The snap-in mechanism of the supporting foot allows the device tobe safely earthed via the DIN rail. For single applications, a section of DINrail and a fixing device are included as a standard while for multiple appli-cations in 19“ distribution boards an optional DEHNpatch mounting setis available as an accessory. DEHNpatch fulfils the requirements of

Category 6 and can be universally used for all data services up to nomi-nal voltages of 48 V. It is equally applicable to existing services in officesand industrial environments such as Gigabit Ethernet, ATM or ISDN aswell as future systems such as Voice over IP and Power over Ethernet.Thanks to its fully shielded design, DEHNpatch can be used in shielded

and unshielded networks. Its width is similar to that of an RJ45 socketthus allowing up to 24 devices to be installed in one series and integrat-ed into a 19” rack.DEHNpatch is supplied with a standard patch cable length of 3 m and 5 m(other lengths available on request).

GHMT Certificate DPA M CAT6 RJ45S 48 GHMT Certificate DPA M CAT6 RJ45H 48

Page 256: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 256/382254 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

DEHNpatch

DPA M CAT6929 100 DPA MCAT6 RJ45S48929 110 DPA MCAT6RJ45H48

DPA M CAT6 RJ45S 48 Patchc ab le wi th sur ge pr ot ec ti on 92 910 0DPA M CAT6 RJ45H 48 Patchc ab le wi th sur ge pr ot ec ti on 92 911 0

• Ideally suited for retrofitting, protec-tion of all lines

• Cat. 6 according to ISO/IEC 118001

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1234

5678

1234

5678

Protection of all pairs due to heavy-duty gas dis-charge tubes and an adapted filter matrix per pair.

Dimension drawing DPA M CAT6 RJ45S 48

Universal SPD ideal for use as a patch cable in Ethernet and similar applications in universally struc-tured cabling systems. Certified according to Category 6 and class E. Fully shielded.

DPA M CAT6 RJ45S 48 DPA M CAT6 RJ45H 48

SPD class T TNominal voltage UN 48 V 48 V

Max. continuous operating d.c. voltage Uc 48 V 48 V

Max. continuous operating a.c. voltage Uc 34 V 34 V

Nominal current IL 1 A 1 A

C2 Nominal discharge current (8/20 µs) line-line In 150 A 150 A

C2 Total nominal discharge current (8/20 µs) line-PG In 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) line-PG In 2.5 kA 2.5 kA

Voltage protection level line-line for In C2 UP 190 V 190 V

Voltage protection level line-PG for In C2 UP 600 V 600 V

Voltage protection level line-line at 1 kV/µs C3 UP

145 V

145 VVoltage protection level line-PG at 1 kV/µs C3 UP 500 V 500 V

Insertion loss at 250 MHz 2 dB 3 dB

Capacitance line-line C 165 pF 250 pF

Capacitance line-PG C 255 pF 400 pF

Operating temperature range -20°C ...+60°C -20°C ...+60°C

Degree of protection IP 20 IP 20

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Connection input/output RJ45 connecting lead / RJ45 connecting lead RJ45 connecting lead / RJ45 connecting lead

Pinning 1/2, 3/6, 4/5, 7/8 1/2, 3/6, 4/5, 7/8

Connecting lead Cat.6,L1 = approx.0.5 m, L2 = approx. 3 m Cat.6, L1 = approx. 1 m, L2 = approx. 5 m

Connector Stewart 39 series Hirose TM 21P

Earthing via 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Enclosure material zinc die casting zinc die casting

Colour bare bare

Test standards IEC 61643-21 IEC 61643-21

Approvals, Certifications Cat. 6 acc. to ISO/IEC 11801, GOST Cat. 6 acc. to ISO/IEC 11801, GOST

Accessories fixing material fixing material

Ordering information

Type DPA M CAT6 RJ45S 48 DPA M CAT6 RJ45H 48

Part No. 929 100 929 110

Packing unit 1 pc(s). 1 pc(s).

Mounting set for DEHNpatch

The set comprises a DIN rail for up to 24 DEHNpatch devices and differentdistance bolts with sliding nuts for installation into data distributors. TheDIN rail can be mounted in a space-saving way at the panel of the distri-butor or even in front of the mounting stations according to a 19” grid.

PU PartType pc(s). No.

MS DPA 1 929 199

929 199 MS DPA

MS DPA MountingSet for DEHNpatch 929 199

Page 257: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 257/382255www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

Mounting set for DEHNpatch

The set comprises a DIN rail for up to 24 DEHNpatch devices and differentdistance bolts with sliding nuts for installation into data distributors. TheDIN rail can be mounted in a space-saving way at the panel of the distri-butor or even in front of the mounting stations according to a 19” grid.

PU PartType pc(s). No.

MS DPA 1 929 199

929 199 MS DPA

MS DPA Mount ingSet for DEHNpatch 929 199

DEHNpatch

DEHNpatch Class EDPA M

• Ideally suited for retrofitting, protec-tion of all lines

• Cat. 6 in channel (class E)

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1234

5678

1234

5678

Protection of all pairs due to heavy-duty gasdischarge tubes and an adapted filtering matrix

per pair.

(1 mod.)

Dimension drawing DPA CLE

Universal SPD ideal for use in Industrial Ethernet and similar applications in structured cabling systemsaccording to class E up to 250 MHz. Fully shielded adapter with sockets for DIN rail mounting.

DPA M CLE RJ45B 48

SPD class TNominal voltage UN 48 V

Max. continuous operating d.c. voltage Uc 48 V

Max. continuous operating a.c. voltage Uc 34 V

Nominal current IL 1 A

C2 Nominal discharge current (8/20 µs) line-line In 150 A

C2 Total nominal discharge current (8/20 µs) line-PG In 10 kA

Voltage protection level line-line at 1 kV/µs C3 UP 180 V

Voltage protection level line-PG at 1 kV/µs C3 UP 500 V

Capacitance line-line C 30 pF

Capacitance line-PG C

25 pFOperating temperature range -40°C ...+80°C

Degree of protection IP 10

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output RJ45 socket / RJ45 socket

Pinning 1/2, 3/6, 4/5, 7/8

Earthing via 35 mm DIN rail acc. to EN 60715

Enclosure material zinc die casting

Colour bare

Test standards IEC 61643-21

Approvals, Certifications GOST

Accessories fixing material

Ordering informationType DPA M CLE RJ45B 48

Part No. 929 121

Packing unit 1 pc(s).

Page 258: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 258/382256 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

BLITZDUCTOR® VT

Surge arrester

• Ideally suited for DIN rail mounted modems orgateways

• Ease of installation due to RJ sockets• Adaptable to the environment of the installa-

tion with additional screw terminals

DIN rail mounted surge arrester for telecommunications terminal devicesand telephone systems with RJ connector.

DIN rail mounted surge arrester for telecommunications terminal devicesand telephone systems with RJ connector.They are often used in installa-

tions upstream of residential gateways (TK/EiB interface) or for protectingindustrial DIN rail mounted modems.

The DIN rail mounted SPD was developedfor installation-friendly protection of theS0 input of residential gateways.The inte-grated distribution function at the pro-tected output allows wiring of two pro-tected outgoing ISDN bus circuits.

BLITZDUCTOR VT ISDN

RJ sockets and screw terminals at theinput and output of BVT TC 1 surgearresters allow for universal use, e.g. forinstallation upstream of NTBAs withscrew wiring or screw/plug-in connectionupstream of modems and telecommuni-cation systems.

BLITZDUCTOR VT TC1

Page 259: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 259/382257www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

BLITZDUCTOR® VT

BVT ISDNBVT ISDN

BLITZ-918 410

• RJ45 sockets

• Additional screw terminals for theISDN lines

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

3

6

4

5

3

6

4

5

IN OUT

a2a1b1

b2

Energy-coordinated ISDN 4-wire protective circuitwith additional protection for the remote power

supply.

Dimension drawing BVT ISDN

For ISDN S0 buses with RJ45 connections.The additional screw terminal connection at the protect-ed output allows for double wiring of the S0 bus (distribution function).

BVT ISDN

SPD class QNominal voltage UN 5 V

Nominal voltage pa-pa UN 40 V

Max. continuous operating d.c. voltage UC 7.5 V

Max. continuous operating d.c. voltage pa-pa UC 60 V

Nominal current IL 200 mA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 2.5 kA

Voltage protection level line-line for In C2 Up 30 V

Voltage protection level line-PG for In C2 Up 600 V

Voltage protection level pa-pa for In C2 Up

130 VVoltage protection level line-line at 1 kV/µs C3 Up 17 V

Voltage protection level line-PG at 1 kV/µs C3 Up 600 V

Voltage protection level pa-pa at 1 kV/µs C3 Up 100 V

Series impedance per line 1.0 ohm

Cut-off frequency line-line fG 1.7 MHz

Capacitance line-line C 3.3 nF

Capacitance line-PG C 15 pF

Capacitance pa-pa C 600 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 10

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output RJ45 / RJ45 or terminals

Pinning 3/6,4/5

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Earthing via terminal

Enclosure material thermoplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type BVT ISDN

Part No. 918 410

Packing unit 1 pc(s).

Page 260: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 260/382258 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

BLITZDUCTOR® VT

BVT TC918 411 BVT TC 1

BVT TC 1 BLITZ-DUCTOR VT 918 411

• RJ sockets, compatible with RJ12 pins

• Additional screw terminals for a/blines

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

4

5

4

5

IN OUT

a1

b1

a1

b1

Energy-coordinated protective circuit, no leakagecurrents to earth.

Dimension drawing BVT TC

For a/b lines, ISDN Uk0 or ADSL with RJ45 connections and additional screw terminal connections.Pinning of the RJ45 sockets is compatible with RJ11/12. The parallel screw terminals are morerobust than the RJ45 sockets and increase In to 10 kA.

BVT TC 1

SPD class RNominal voltage UN 130 V

Max. continuous operating d.c. voltage UC 170 V

Nominal current IL 200 mA

C2 Total nominal discharge current (8/20 µs) In 5 kA

C2 Nominal discharge current (8/20 µs) per line In 2.5 kA

Voltage protection level line-line for In C2 Up 275 V

Voltage protection level line-PG for In C2 Up 600 V

Voltage protection level line-line at 1 kV/µs C3 Up 240 V

Voltage protection level line-PG at 1 kV/µs C3 Up 600 V

Series impedance per line 4.7 ohmsCut-off frequency line-line fG 17 MHz

Capacitance line-line C 300 pF

Capacitance line-PG C 15 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 10

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output RJ45 or terminals / RJ45 or terminals

Pinning 4/5

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Earthing via screw terminal

Enclosure material thermoplastic, UL 94 V-0

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type BVT TC 1

Part No. 918 411

Packing unit 1 pc(s).

Page 261: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 261/382259www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

DSM TM

Surge arrester

• Surge arrester for ISDN or Ethernet applica-tions

• Minimum space required for flush mounting• Ideal for Touch Manager wave (Residential

Gateway)

Surge arrester for flush mounting used in LAN interfaces.

DSM TM is a surge arrester which is installed close to terminal devicesand designed for Touch Manager wave (Siemens).The SPD is ideally suit-ed for installation into flush-mounted or small-sized distribution boardsand connected to the local equipotential bonding of the terminal device.

Because of the universal reservation of the pluggable RJ45 output, it canbe used for protecting both ISDN S0 and Ethernet 10 BT (class C cabling)applications. As screw terminals are available at the input, they can beconnected to both rigid and flexible conductors or shields.

A self-adhesive fixing strip and a 4-poleplug-in distribution terminal are includedin delivery.

Scope of delivery of DSM TM

Page 262: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 262/382260 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

DSM TM

DSM TM924 274 DSM TM

DSM TM SPD forData Sockets 924 274

• Indirect shield earthing

• Installation accessories included

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

123456

78

a1

b1

a2

b2SHL

Low-capacitance design with high dischargecapacity and low protection level between the

signal lines.

Dimension drawing DSM TM

For IT installations, class C, or services such as Ethernet 10 BT or ISDN S0 interfaces.Transition fromscrew terminal to RJ45 plug. No leakage pickups are generated due to indirect shielding.

DSM TM

SPD class QNominal voltage UN 5 V

Max. continuous operating d.c. voltage UC 6 V

Max. continuous operating a.c. voltage UC 4.2 V

Nominal current IL 200 mA

C1 Nominal discharge current (8/20 µs) line-line In 500 A

C2 Nominal discharge current (8/20 µs) line-PG In 5 kA

C2 Total nominal discharge current (8/20 µs) line-PG In 10 kA

Voltage protection level line-line for In C1 Up 28 V

Voltage protection level line-PG for In C2 UP 600 V

Voltage protection level shield-PG for In C2 UP

600 VVoltage protection level line-line at 1 kV/µs C3 UP 11 V

Voltage protection level line-PG at 1 kV/µs C3 UP 380 V

Voltage protection level shield-PG at 1 kV/µs C3 UP 600 V

Cut-off frequency fG 55 MHz

Capacitance line-line C 75 pF

Capacitance line-PG C 20 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output screw terminal / RJ45 connecting lead

Pinning Ethernet 1/2, 3/6 or ISDN 4/5, 3/6

Cross-sectional area, solid 0 - 1.0 mm2

Cross-sectional area, flexible 0 - 1.0 mm2

Tightening torque (terminal) 0.3 Nm

Earthing via lead 1.0 mm2

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Accessories adhesive pad, socket terminal

Ordering information

Type DSM TM

Part No. 924 274

Packing unit 1 pc(s).

Page 263: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 263/382261www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

DEHNlink

Surge arrester

• Surface-mounted surge protective device fortelecommunication systems

• Quick installation due to plug-in terminals• Different interface-specific types

Surge arrester for telecommunications terminal devices and telephonesystems with RJ plug-in connector for surface mounting.

Surge arrester for surface mounting with a modern design. It protectsespecially modems and telephone systems with RJ plug-in connectors. Theplug-in connectors allow for easy installation.

Compared to conventional devices( ... ECO), the different SPD units with ...Itype designation have an additional LEDindication of the supply voltage. Thishelps to immediately recognise systemfailures. Furthermore, they provide a widerange of accessories such as connectingcables or fixing material.

Devices with and without oper-ating state indication

DLI ISDN I can protect two terminal devices at the same time due to theintegrated distribution function. The operating state indicator is only illu-minated if the NTBA is also connected to the power supply and not incase of emergency operation (remote supply of telecommunication net-work operators).

Wiring of DLI ISDN I

ISDN SO Interface

OK

State

LED on

LED off

State

NT NT

Service

Faulty

The operating state indicator informs on the proper condition of thedevice. In the event of a fault, the connections and cables have to bechecked. If no installation fault can be detected, the SPD has been over-loaded and has to be replaced.

Operating state indication DLI ISDN I

Page 264: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 264/382262 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

DEHNlink

DLI ISDN I929 024 DLI ISDN I

DLI ISDN I DEHNlinkISDN/I 929 024

• 2 protected outputs

• Surge protection and LED indicationfor the remote supply included

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

3

6

4

5

3

6

4

5

3

64

5

protected

Energy-coordinated ISDN 4-wire protective circuitwith additional protection and indication of the

remote power supply.

Dimension drawing DLI ISDN I

SPD with two protected ISDN S0 outputs (distribution function) and operating state indication (LED)of the remote supply voltage. No indication during emergency operation (supply from telephonesystem only). Connecting cable and mounting material included.

DLI ISDN I

SPD class QNominal voltage UN 5 V

Nominal voltage pa-pa UN 40 V

Max. continuous operating d.c. voltage Uc 7.5 V

Max. continuous operating a.c. voltage Uc 5.2 V

Max. continuous d.c. voltage pa-pa UC 45 V

Nominal current IL 200 mA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 2.5 kA

Voltage protection level line-line for In C2 Up 30 VVoltage protection level line-PG for In C2 Up 600 V

Voltage protection level pa-pa for In C2 Up 180 V

Voltage protection level line-line at 1 kV/µs C3 Up 17 V

Voltage protection level line-PG at 1 kV/µs C3 Up 600 V

Voltage protection level pa-pa at In C2 Up 100 V

Series impedance per line 1 ohm

Cut-off frequency line-line 2 MHz

Capacitance line-line C 3 nF

Capacitance line-PG C 15 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output RJ45 / 2 x RJ45

Pinning 3/6,4/5

Earthing via flat connector 6.3 mm

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Accessories connecting cable, mounting material

Ordering information

Type DLI ISDN I

Part No. 929 024

Packing unit 1 pc(s).

Page 265: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 265/382263www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

DEHNlink

DLI TC IDLI TC 2 I

DEHNlink929 028

• LED indicates supply voltage

• Protection against power crossingintegrated

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

3

6

4

5

3

6

4

5

protected

2-stage protective circuit with overcurrent protec-tion and system voltage indication of DLI TC 2 I.

Dimension drawing DLI TC I

Protective device for analogue or system telephones with operating state indication (LED). Protectseven against alternating current interference. Compatible with pins of RJ11/12 plugs. Connectingcable and mounting material included.

DLI TC 2 I

SPD class RNominal voltage UN 110 V

Max. continuous operating d.c. voltage Uc 170 V

Max. continuous operating a.c. voltage Uc 120 V

Nominal current IL 150 mA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 2.5 kA

Voltage protection level line-line for In C2 Up 250 V

Voltage protection level line-PG for In C2 Up 600 V

Voltage protection level line-line at 1 kV/µs C3 Up 230 VVoltage protection level line-PG at 1 kV/µs C3 Up 600 V

Series impedance per line 10 ohms

Cut-off frequency line-line 10 MHz

Capacitance line-line C 0.3 nF

Capacitance line-PG C 15 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output RJ45 / RJ 45 (compatible with RJ12)

Pinning 3/6, 4/5 (3/4, 2/5 for RJ12)

Earthing via flat connector 6.3 mm

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Accessories connecting cable, mounting material

Ordering information

Type DLI TC 2 I

Part No. 929 028

Packing unit 1 pc(s).

Page 266: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 266/382264 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR RJ CONNECTION

1 2 3 4 5 6 7 8 9 0

DEHNlink

DLI TC929 081 DLI TCECORJ12

DLI TC ECO RJ12 DEHNlink-Denm ark 929 081

• Economical protection for 1 pair

• Modern design

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

3

4

3

4

protected

Using a high-capacity varistor makes decouplingto the gas discharge tube unnecessary.

Dimension drawing DLI TC

Protective device for analogue or system telephones, RJ12 unit.

DLI TC ECO RJ12

SPD class RNominal voltage UN 130 V

Max. continuous operating d.c. voltage Uc 170 V

Max. continuous operating a.c. voltage Uc 120 V

Nominal current IL 200 mA

C2 Total nominal discharge current (8/20 µs) In 5 kA

C2 Nominal discharge current (8/20 µs) per line In 2.5 kA

Voltage protection level line-line for In C2 Up 480 V

Voltage protection level line-PG for In C2 Up 600 V

Voltage protection level line-line at 1 kV/µs C3 Up 280 V

Voltage protection level line-PG at 1 kV/µs C3 Up

600 VCut-off frequency line-line 10 MHz

Capacitance line-line C 0.7 nF

Capacitance line-PG C 15 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output RJ12 / RJ12

Pinning 3/4

Earthing via flat connector 6.3 mm

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Accessories mounting material

Ordering information

Type DLI TC ECO RJ12

Part No. 929 081

Packing unit 1 pc(s).

Page 267: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 267/382265www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR BT JACK CONNECTION

DEHNlink TC BT

Surge arrester

• Surface-mountable protective device for tele-communication systems

• Quick installation due to plug-in terminals• Device acc. to British Telecom requirements

Surge arrester for telecommunications terminal equipment and telephonesystems with BT plug-in connection for surface mounting.

Surge arrester for telecommunications terminal equipment and telephonesystems with BT plug-in connection for surface mounting. The devicemeets the requirements of Oftel NS/G/23/L/100005 for connections

between a terminal point of a public telephone installation and anytelecommunications terminal equipment.Fulfils BS6651:1992,Appendix C,Category C-High and CCITT K17.

Page 268: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 268/382266 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR BT JACK CONNECTION

DEHNlink TC BT

DLI TC BT929 026 DLI TC BT

DLI TC BT DEHNlinkBT 929 026

• Device acc. to British Telecom require-ments

• Protection for all lines

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

4

35

2

6

1

4

35

2

6

1

protected

Energy-coordinated protective circuit for all pairs,free of leakage currents to earth.

Dimension drawing DLI TC BT

Protective device for analogue or system telephones in accordance with British Telecom require-ments. Pluggable terminals for easy installation.

DLI TC BT

SPD class RNominal voltage UN 130 V

Max. continuous operating d.c. voltage UC 145 V

Nominal current IL 125 mA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 Up 210 V

Voltage protection line-PG for In C2 Up 550 V

Voltage protection level line-line at 1 kV/µs C3 UP 185 V

Voltage protection level line-PG at 1 kV/µs C3 UP 450 V

Series

impedance per l

ine 4.7 ohms

Bandwidth fG 13 MHz

Capacitance line-line C 400 pF

Capacitance line-PG C 10 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output BT jack / BT jack

Pinning 1/6,2/5, 3/4

Earthing by flat connector 6.3 mm

Enclosure thermoplastic

Colour black

Test standards IEC 61643-21

Accessories connecting cable, mounting material

Ordering information

Type DLI TC BT

Part No. 929 026

Packing unit 1 pc(s).

Page 269: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 269/382267www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

www.dehn.de

UGKF

Surge arrester

• Plug-in surge protective adapter for easy retro-fitting

• Integrated indirect shield earthing avoids leak-age pickups

Surge arrester for use as cable adapter to protect coaxial systems such asvideo and camera systems from potential damage.

UGKF BNC surge arresters are shielded devices for plugging into coaxialterminal devices or connections. Frequent fields of application are the pro-tection of outdoor or central video surveillance systems. In order to avoid

being influenced by leakage pickups, the cable shield is earthed indirect-ly via a gas discharge tube. The SPD inputs are used as sockets and theprotected outputs as plugs.

Devices for protecting video surveillance systems with higher supply volt-age or with a two-sided socket connection are also available on request.

UGKF BNC types

DGA BNC VC ... surge arresters of the DEHNgate familiy can be easilyinstalled on supporting rails.

DGA BNC VC ...

Page 270: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 270/382268 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

UGKF

UGKF BNC929 010 UGKFBNC

UGKF BNC SPD forComupter System s 929 010

• Easily adaptable

• Avoids leakage pickups

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

protected

Low-capacitance, 2-stage protective circuit withindirect shield earthing to avoid leakage pickups.

Dimension drawing UGKF BNC

UGKF BNC surge arresters are suitable for protecting video cameras and Arcnet with BNC connec-tion. Special versions for video cameras with higher nominal voltage available on request.

UGKF BNC

SPD class TNominal voltage UN 5 V

Max. continuous operating d.c. voltage UC 8 V

C2 Nominal discharge current (8/20 µs) per line In 2.5 kA

C2 Nominal discharge current (8/20 µs) shield-PG In 10 kA

Voltage protection level line-shield for In C2 UP ≤ 25 V

Voltage protection level line-shield at 1 kV/µs C3 UP ≤ 15 V

Voltage protection level shield-PG at 1 kV/µs C3 Up ≤ 600 V

Series impedance per line 10 ohms

Cut-off frequency fG 300 MHz

Return loss≥

20 dB up to 40 MHzCapacitance line-shield C ≤ 50 pF

Operating temperature range -40°C...+80°C

Connection input/output BNC socket / BNC connector

Earthing via outgoing earth conductor 0.75 mm2

Shield earthing via indirectly by an integrated spark gap

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type UGKF BNC

Part No. 929 010

Packing unit 1 pc(s).

Page 271: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 271/382269www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

www.dehn.de

DEHNgate

Lightning current and surge arrester

• Application-specific SPD designs

• SPD for use in satellite and cable TV systems

with measuring output• Combined lightning current and surge arrester

with a high discharge capacity and low protec-tion level

• Contact materials with extremely highendurance

Lightning current and surge arrester for use as cable adapter to protectcoaxial systems such as CCTV, mobile radio stations and antenna systemsfrom potential damage.

DEHNgate is a family of lightning current and surge arresters with a cableadapter design for protecting coaxial systems such as mobile radio sta-

tions and antenna systems from potential damage. Depending on theapplication, different mechanical and electrical types are available.

DGA FF TV can be mounted onto a DIN railin a space-saving way to protect satellitesystems with several outputs. For singleapplications such as cable TV, the devicecan be simply snapped into a wall-mount-ed adapter. 2 F cable connectors are alsoincluded.

Delivery of DGA FF TV

The coaxial DGA arrester family comes indifferent designs for different applica-tions. Different types of plugs and arrestertechnologies allow for optimised solu-tions. Further types are available onrequest.

DGA arrester family

If high partial lightning currents can becoupled into antenna lines or if very high

transmission performances are required,the use of Lambda/4 surge arresters isadvisable. If additional remote supply isneeded for the antenna, a combination of a gas discharge tube and Lambda/4 tech-nology (DGA LG) should be used. Thesurge arresters are made of top-qualitymaterial and provide excellent endurance.

Application of Lambda/4arresters

The Lambda/4 surge arresters of typeDGA L4 feature an internal coaxial con-nection of the inner conductor as a band-pass. Only frequencies within this bandare transmitted. For low-frequency

impulses, such as lightning currents, theycause a short circuit. This makes themmechanically very robust and mainte-nance-free. Due to their low protectionlevel and high discharge capacity, theycan be used as combined lightning cur-rent and surge arresters.

Principle of Lambda/4

Spark-gap-based surge arresters have an internal gas-filled surge arrester and can bedefined as a low pass.This also allows for d.c. transmission (antenna supply). Peak volt-ages exceeding the threshold value of the gas discharge tube are discharged.These surgearresters provide extensive contact surfaces from the inner conductor to the gas dis-charge tube. This minimises burn-off of the material during the discharge process andensures a constant transmission performance.

Principle of a spark-gap-based SPD

Page 272: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 272/382270 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

DEHNgate

Lightning current and surge arresters

DGA FF TV SPD

No.909 703

IN 2A

UC 24V

DEHNgate

TP

5 -2 40 0 MH z - 20 d B

protected

ACLASS

K L A S S E

5-3000MHz

D G A

F F

T V

S P D

N o

.

9 0 9

7 0 3

I N

2 A

U

C

2 4

V

D E H N

g a t e

DGA FF TV SPD

No. 909703

IN 2A

UC24V

DEHNgate

TP

5-2400MHz -20 dB

protected

ACLASS

K L A S S E

5-3000 MHz

D G A

F F

T V

S P D

N o

.

9 0 9

7 0 3

I N

2 A

U

C

2 4

V

D E H N

g a

t e

DGA FF TV SPD

No.909 703

IN 2A

UC 24 V

DEHNgate

TP

5-2400 MHz -20 dB

protected

ACLASS

K L A S S E

5-3000MHz

D G A

F F

T V

S P D

N o

.

9 0 9

7 0 3

I N

2 A

U

C

2 4

V

D E H N

g a

t e

1

input

TP = test point

signal test

2

3

protected output

HF test signal

meter

HF test signal

meter

ok

checksystem

signal test for DGA FF TV

cable lengthmax. 0.5 m

AWG 6/16 mm2

EB

EB

Earthing of the surge arresters is differentaccording to the various designs. For details,please see the relevant technical data.

Earthing of DGA AG N and DGA L ...

The DGA FF TV arrester is the first of its kindto have an integrated measuring output for

antenna signals allowing the system to beeasily tested.

Page 273: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 273/382271www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

www.dehn.de

DEHNgate

DGA BNC VCDGA BNC

DGA BNC

• Easily adaptable due to BNC sockets

• Available with direct or indirect shieldearthing, according to type

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

protected

protected

DGA BNC VCDPart No. 909 710

DGA BNC VCIDPart No. 909 711

( 1 m o d . )

Space-saving surge arrester with BNC socket for mounting on supporting rails for protecting videoand camera systems.Available with direct (VCD) or indirect shield connection (VCID), according totype, to avoid leakage pickups.

DGA BNC VCD DGA BNC VCID

SPD class T TNominal voltage UN 5 V 5 V

Max. continuous operating d.c. voltage UC 6.4 V 6.4 V

Nominal current IL 0.1 A 0.1 A

C2 Nominal discharge current (8/20 µs) shield-PG In 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) In 5 kA 5 kA

C2 Nominal discharge current (8/20 µs) line-shield In 5 kA 5 kA

Voltage protection level line-shield for In C2 Up 35 V 35 V

Voltage protection level shield-PG for In C2 Up — 650 V

Voltage protection level line-shield at 1 kV/µs C3 Up 13 V 13 VVoltage protection level shield-PG at 1 kV/µs C3 Up — 600 V

Frequency range 0 - 300 MHz 0 - 300 MHz

Insertion loss at 160 MHz 0.4 dB at 160 MHz 0.4 dB

Return loss at 130 MHz 20 dB at 130 MHz 20 dB

Capacitance line-shield C 25 pF 25 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Degree of protection IP 10 IP 10

For mounting on 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715

Connection input/output BNC socket / BNC socket BNC socket / BNC socket

Earthing via 35 mm DIN rail according to EN 60715 35 mm DIN rail according to EN 60715

Enclosure material zinc die casting zinc die casting

Colour bare bare

Test standards IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST

Ordering information

Type DGA BNC VCD DGA BNC VCID

Part No. 909 710 909 711

Packing unit 1 pc(s). 1 pc(s).

2-stage protective circuit with low capacitance.DGA BNC VCD with direct shield earthing andDGA BNC VCID with indirect shield earthing.

Dimension drawing DGA BNC VC ...

Page 274: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 274/382272 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

DEHNgate

DGA TV909 703 DGA FFTV909 704 DGA GFTV909 705 DGA GFFTV

DGA FF TV DEHNgate909 703DGAGFTV909 704DGAGFFTV909 705

• Frequency range for analogue and digitalTV, also suitable for reverse LAN channels

• SPDs of type FF and GFF with integratedmeasuring output

• 3 types for adapted use for installation inconformity with the lightning protectionzones concept at the boundaries from0A – 2 (combined lightning current

and surge arresters of type GFF),0

A– 1 (lightning current arresters of

type GF)1 – 2 (surge arresters of type FF)

DGA GFF TV

DGA GF TV DGA FF TV

TP

protected

Schematic diagram of the protective circuit of DGA GFF TV consisting of lightning currentarrester of type DGA GF TV and terminal

equipment protection DGA FF TV.

DGA GFF TV DGA FF TV DGA GF TV

Dimension drawing DGA GFF TV – Combinationof DGA GF TV and DGA FF TV

DGA ... TV are SPDs with F connector for remote supply for 75 ohm satellite and cable TV systems.The SPDs fulfil the high shielding requirements of class A according to EN 50083-2. They allow forspace-saving installation into all common TV and satellite applications and are available as light-

ning current arresters, surge arresters as well as combined lightning current and surge arresterswith integrated measuring output for testing installations.

DGA FF TV DGA GF TV DGA GFF TV

SPD class _ H H_Max. continuous operating d.c. voltage UC 24 V 60 V 24 V

Nominal current IL 2 A 2 A 2 A

D1 Lightning impulse current (10/350 µs) I imp 0.2 kA 2.5 kA 2.5 kA

C2 Nominal discharge current (8/20 µs) In 1.5 kA 10 kA 10 kA

Voltage protection level for Iimp D1 UP 230 V 700 V 230 V

Voltage protection level for In C2 UP 300 V 700 V 300 V

Voltage protection level at 1 kV/µs C3 UP 60 V 600 V 60 V

Frequency range d.c., 5-3000 MHz d.c. - 2400 MHz d.c., 5-2400 MHzInsertion loss — 0.5 dB —

Insertion loss 5 - 862 MHz 1.2 dB — 1.7 dB

Insertion loss 862 - 2400 MHz 1.4 dB — 1.9 dB

Insertion loss 2400 - 3000 MHz 2 dB — —

Return loss 14 dB 18 dB (-1.5 dB/octave) dB —

Return loss (5 - 8 MHz) — — 10 dB

Return loss (8 - 47 MHz) — — 14 dB

Return loss (47 - 2400 MHz) 18 dB (-1.5 dB/octave) — 18 dB (-1.5 dB/octave)

Return loss test socket (5 - 47 MHz) 18 dB — 18 dB

Test socket connection loss 20 dB — 20 dB

Shield attenuation 5 - 300 MHz 85 dB 85 dB 85 dB

Shield attenuation 300 - 470 MHz 80 dB 80 dB 80 dB

Shield attenuation 470 - 1000 MHz

75 dB

75 dB

75 dBShield attenuation 1000 - 2400 MHz 55 dB 55 dB 55 dB

Impedance Z 75 ohms 75 ohms 75 ohms

Operating temperature range -40°C...+80°C -20°C...+55°C -20°C...+55°C

Degree of protection IP 30 IP 30 IP 30

For mounting on 35 mm DIN rail acc. to EN 60715 earthing bracket 35 mm DIN rail acc. to EN 60715

or wall mounting or wall mounting

Connection input/output F socket / F socket F socket / F connector F socket / F socket

Earthing via DIN rail or screw connection earthing bracket with screw connection DIN rail or screw connection

Enclosure material metal metal metal

Colour bare bare bare

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST GOST

Accessories 2 x F connector earthing bracket and 2 x F connector 2 x F connector

Ordering information

Type DGA FF TV DGA GF TV DGA GFF TV

Part No. 909 703 909 704 909 705

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

Page 275: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 275/382273www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

www.dehn.de

DEHNgate

DGA FDGA F 1.6

DEHNgate

• For easy retrofitting

• For high transmission rates

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

Low-capacitance diode matrix for optimisedtransmission performance.

Dimension drawing DGA F

Quickly responding surge arrester for G.703 interfaces. Earthing via enclosure. 1.6/5.6 connector.

DGA F 1.6 5.6

SPD class WNominal voltage UN 5 V

Max. continuous operating d.c. voltage UC 6 V

Nominal current IL 0.25 A

C2 Nominal discharge current (8/20 µs) In 0.3 kA

Voltage protection level for In C2 UP 30 V

Voltage protection level at 1 kV/µs C3 UP 12 V

Frequency range d.c. -80 MHz

Insertion loss 0.2 dBImpedance Z 75 ohms

Capacitance line-shield C 50 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output 1.6/5.6 connector / 1.6/5.6 socket

Earthing via externally via shield earthing

Enclosure material metal

Colour bare

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type DGA F 1.6 5.6

Part No. 929 040

Packing unit 1 pc(s).

Page 276: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 276/382274 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

DEHNgate

DGA G929 042 DGA GBNC929 044 DGA G N

DGA G BNC DEHNgate929 042DGA G N DEHNgate929 044

• Minimal dimensions

• Extremely wide transmission range

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 1 and higher

Built-in coaxial gas discharge tube. Dimension drawingDGA G BNC

Surge arrester for remote power supply with integrated gas discharge tube. Especially adapted towireless LAN and wireless local loop applications in BNC, N or 1.6/5.6 connectors for bushinginstallation.

DGA G BNC DGA G N

SPD class B BMax. continuous operating d.c. voltage UC 135 V 135 V

Nominal current IL 3.5 A 6 A

Max. transmission capacity 25 W 25 W

D1 Lightning impulse current (10/350 µs) I imp 1 kA 1 kA

C2 Nominal discharge current (8/20 µs) In 5 kA 5 kA

Voltage protection level for In C2 UP 500 V 500 V

Frequency range d.c. - 4 GHz d.c. - 5.8 GHz

Insertion loss < 0.2 dB < 0.2 dB

Return loss 20 dB 20 dBImpedance Z 50 ohms 50 ohms

Operating temperature range -40°C...+85°C -40°C...+85°C

Degree of protection IP 20 IP 65

Connection input/output BNC socket / BNC connector N socket / N connector

Earthing via bushing Ø12.9 mm bushing Ø16.2 mm

Enclosure material brass, refined surface with trimetal plating brass, refined surface with trimetal plating

Colour gold gold

Test standards IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST

Ordering information

Type DGA G BNC DGA G N

Part No. 929 042 929 044Packing unit 1 pc(s). 1 pc(s).

Dimension drawingDGA G N

Page 277: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 277/382275www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

www.dehn.de

DEHNgate

DGA AGDGA AG

DGA AG

DGA AG

DEHNgate

DEHNgate

• Large surface for connecting gas dis-charge tubes

• Longevity due to minimum contactburn-off at the inner conductor

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 1 and higher

Replaceable gas discharge tubeDimension drawings DGA AG

Surge arrester suitable for remote supply with replaceable gas discharge tube. Excellent RF servicelife due to minimum contact burn-off and large-area contact surface of the gas discharge tube ina special cage.

DGA AG BNC DGA AG N DGA AG U

SPD class A A AMax. continuous operating d.c. voltage UC 180 V 180 V 180 V

Nominal current IL 3.5 A 6 A 10 A

Max. transmission capacity 150 W 150 W 150 W

D1 Lightning impulse current (10/350 µs) I imp 5 kA 5 kA 5 kA

C2 Nominal discharge current (8/20 µs) In 20 kA 20 kA 20 kA

Voltage protection level for In C2 UP 750 V 750 V 750 V

Frequency range d.c. - 1 GHz d.c. - 2.5 GHz d.c. - 300 MHz

Insertion loss < 0.1 dB < 0.2 dB < 0.1 dB

Return loss 20 dB 20 dB 20.8 dBImpedance Z 50 ohms 50 ohms 50 ohms

Operating temperature range -40°C...+85°C -40°C...+85°C -40°C...+85°C

Degree of protection IP 20 IP 65 IP 20

Connection input/output BNC socket / BNC connector N socket / N connector UHF socket / UHF connector

Earthing via bushing Ø16.1 mm bushing Ø16.1 mm or earthing screw bushing Ø19.3 mm

Enclosure material brass, refined surface with trimetal plating brass, refined surface with trimetal plating brass, refined surface with trimetal plating

Colour bare bare bare

Replaceable gas discharge tube yes yes yes

Test standards IEC 61643-21 IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST GOST

Ordering information

Type DGA AG BNC DGA AG N DGA AG UPart No. 929 043 929 045 929 057

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

DGA AG BNC DGA AG N DGA AG U

Accessory Part for DEHNgate

Gas discharge tubeSpare gas discharge tube for DEHNgate with lightning current carryingcapability. High quality with especially low capacitance.

Type GDT DGA 230

Lightning impulse currentcarrying capability (10/350 µs) 5 kA

Design H 8 x 6 mm

PU PartType pc(s). No.

GDT DGA 230 1 929 498

929 498 GDT DGA230929 499 GDT DGA470

GDTDGA230929 498GDTDGA470929 499

Page 278: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 278/382276 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

DEHNgate

DGA LG929 046 DGA LG 716929 446 DGA LG 716X

DGA LG 7 16 DEHNgate929 046D G A LG 7 1 6 X929 446

• For multi-frequency applications withd.c. power supply

• Optionally available with self-extin-guishing gas discharge capsule up toa nominal current of 2.5 A

• Maximum transmission and PIM per-formance

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0A – 1 and higher

/4

Quarterwave arrester combined with gas dis-charge tube

Dimension drawingDGA LG 7 16

Quarterwave arrester combined with a spark gap suitable for remote supply for multi-frequencyapplications (multi-carrier systems) due to minimum passive intermodulation. Broadband devicefor all 4+3G services.

DGA LG 7 16 X with self-extinguishing gas discharge capsule with automatic reset function for ahigh degree of safety and negligible system downtimes.

DGA LG 7 16 DGA LG 7 16 X

SPD class A AMax. continuous operating d.c. voltage UC 65 V 65 V

Nominal current IL 13 A 2.5 A

Max. transmission capacity 500 W 500 W

D1 Lightning impulse current (10/350 µs) I imp 5 kA 5 kA

C2 Nominal discharge current (8/20 µs) In 20 kA 20 kA

Voltage protection level for In C2 UP 1000 V 1000 V

Frequency range d.c., 806 MHz - 2.2 GHz d.c., 806 MHz - 2.2 GHz

Insertion loss

0.15 dB

0.15 dBInsertion loss 2176 MHz typically 0.1 dB typically 0.1 dB

Return loss 20 dB 20 dB

Return loss 2176 MHz typically 20.0 dB typically 20.0 dB

Impedance Z 50 ohms 50 ohms

Intermodulation typically -150 dBc @ 2*43 dBm typically -150 dBc @ 2*43 dBm

Operating temperature range -40°C...+85°C -20°C...+85°C

Degree of protection IP 65 IP 65

Connection input/output 7/16 socket / 7/16 connector 7/16 socket / 7/16 connector

Earthing via earthing screw earthing screw

Enclosure material brass, refined surface with trimetal plating brass, surface-coated with trimetal plating

Colour bare bare

Replaceable gas discharge tube yes Part No. 929496

Test standards IEC 61643-21 IEC 61643-21Approvals, Certifications GOST GOST

Ordering information

Type DGA LG 7 16 DGA LG 7 16 X

Part No. 929 046 929 446

Packing unit 1 pc(s). 1 pc(s).

Zubehör für DEHNgate

Gas discharge tubeSpare gas discharge tube for DEHNgate with lightningcurrent carrying capability. High quality with especiallylow capacitance.

Type GDT DGA 90

Lightning impulse currentcarrying capability (10/350 µs) 5 kA

Design H 8 x 6 mm

Integrated into (Part No.) 929 046

PU PartType pc(s). No.

GDT DGA 90 1 929 497

929 497 GDT DGA90

GDTDGA90929 497

Dimension drawingDGA LG 7 16 X

Gas discharge tube with screw capSpare gas discharge tube capable of carrying lightning currents with screw cap forDEHNgate LG 7 16 X. Self-extinguishing gas capsule with automatic reset function incase of d.c. feeding currents up to 2.5 A or higher HF performances.

Also suited for retrofitting DEHNgate LG 7 16 with conventional gas capsule technolo-gy (replacement of the complete capsule unit!).

Type GDT DGA 90 XLightning impulse current carrying capability (10/350 µs) 5 kA

Integrated into Part No. 929 446

Can be retrofitted into Part No. 929 046

PU PartType pc(s). No.

GDT DGA 90 X 1 929 496

929 496 GDT DGA90X

GDTDGA90X929 496 N E W

N E W

N E W

Page 279: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 279/382277www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

www.dehn.de

DEHNgate

DGA L4DGA L4 7

DGA L4 7

DEHNgate

• Maintenance-free combined lightningcurrent and surge arrester (high dis-charge capacity and low voltage pro-tection level)

• Maximum transmission and PIM per-formance

• For installation in conformity with the

lightning protection zones concept atthe boundaries from 0A – 2 and higher

/4

Maintenance-free quarterwave SPD withoutdiscrete components.

Dimension drawingDGA L4 7 16 S

Combined lightning current and surge arrester with maintenance-free quarterwave technologywith adapted frequency band. The SPDs can also discharge high partial lightning currents. Noremote supply possible as the SPD represents an electrical short circuit for low-frequency signals.

DGA L4 7 16 S DGA L4 7 16 B

SPD class M MMax. continuous operating d.c. voltage UC 0 V 0 V

Nominal current IL 0 V 0 V

Max. transmission capacity 3000 W 1700 W

D1 Lightning impulse current (10/350 µs) I imp 25 kA 40 kA

C2 Nominal discharge current (8/20 µs) In 50 kA 80 kA

Voltage protection level for In C2 UP 130 V 180 V

Frequency range 380 MHz - 512 MHz 880 MHz - 2.2 GHz

Insertion loss < 0.1 dB < 0.15 dBReturn loss 20 dB 20 dB

Impedance Z 50 ohms 50 ohms

Intermodulation — typically -150 dBc @ 2*43 dBm

Operating temperature range -40°C...+85°C -40°C...+85°C

Degree of protection IP 65 IP 65

Connection input/output 7/16 socket / 7/16 connector 7/16 socket / 7/16 connector

Earthing via earthing screw earthing screw

Enclosure material brass, refined surface with trimetal plating brass, refined surface with trimetal plating

Colour bare bare

Test standards IEC 61643-21 IEC 61643-21

Approvals, Certifications GOST GOST

Ordering information

Type DGA L4 7 16 S DGA L4 7 16 B

Part No. 929 047 929 048

Packing unit 1 pc(s). 1 pc(s).

Dimension drawingDGA L4 7 16 B

Page 280: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 280/382278 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

DEHNgate

DGA L4 N EB929 059 DGA L4 NEB

DGAL4NEB929 059

• Maintenance-free combined lightningcurrent and surge arrester, optimisedbandwidth and dimensions

• Maximum transmission performancefor WiMax and Wi-Fi applications

• For installation in conformity with thelightning protection zones concept at

the boundaries from 0A – 2 and higher

/4

Especially broadband combined lightning current and surge arrester with maintenance-free quar-terwave technology, adapted frequency band for Broadband Wireless Access applications and smalldimensions of the enclosure. No remote supply possible as the SPD represents an electrical shortcircuit for low-frequency signals.

DGA L4 N EB

SPD class MNominal voltage UN 0 V

Max. continuous operating d.c. voltage UC 0 V

Nominal current IL 0 V

Max. transmission capacity 300 W

D1 Lightning impulse current (10/350 µs) I imp 25 kA

C2 Nominal discharge current (8/20 µs) In 50 kA

Voltage protection level for Iimp D1 UP 18 V

Voltage protection level for In C2 UP 30 V

Frequency range 2.0 GHz - 6.0 GHzInsertion loss 0.2 dB

Return loss 20 dB

Impedance Z 50 ohms

Operating temperature range -40°C...+85°C

Degree of protection IP 65

Connection input/output N socket / N socket

Earthing via bushing Ø19.3 mm

Enclosure material aluminium

Colour bare

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering informationType DGA L4 N EB

Part No. 929 059

Packing unit 1 pc(s).

Maintenance-free quarterwave SPD withoutdiscrete components.

Dimension drawing DGA L4 N EB

Page 281: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 281/382279www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

www.dehn.de

Accessories for DEHNgate

N E W

Gas discharge tubeSpare gas discharge tube for DEHNgate with lightning current carryingcapability. High quality with especially low capacitance.

Type GDT DGA 90 GDT DGA 230 GDT DGA 470

Lightning impulse currentcarrying capability (10/350 µs) 5 kA 5 kA 5 kA

Design H 8 x 6 mm H 8 x 6 mm H 8 x 6 mm

Integrated into Part No. 929 046 929 043, 929 045 —

PU PartType pc(s). No.

GDT DGA 90 1 929 497

GDT DGA 230 1 929 498

GDT DGA 470 1 929 499

929 497 GDT DGA90929 498 GDT DGA230929 499 GDT DGA470

G DTDG A9 0G as en tl ad un gs ab le it er f ür D EH Ng at e 9 29 4 97G DTDG A2 3 0G as en tl ad un gs ab le it er f ür D EH Ng at e 9 29 4 98G DTDG A4 7 0G as en tl ad un gs ab le it er f ür D EH Ng at e 9 29 4 99

Cable lug with earth conductorCable lug with highly flexible black copper earth conductor for earthingof DEHNgate, Part No. 929 043, 929 044 or 929 045.

PU Part

Type pc(s). No.EL 16 B17 1 929 096

929 096 EL 16 B17

EL16B17929 096

Angled fixing plate for HF arrestersMade of stainless steel, with 3 mounting holes for 3 different sizes of DEHNgate, e. g. 1x 929 042 + 1x 929 057 + 1x (929 043, 929 044,929 045 or 929 058).

PU Partpc(s). No.

1 106 329

106 329

106 329

Equipotential bonding bars for industrialinstallations

Made of stainless steel, suitable for direct screwing of 3 DEHNgatedevices, Part No. 929 045 – 929 049, 929 446.

PU PartType pc(s). No.

PAS I 6AP M10 V2A 1 472 209

472 209 PAS I 6APM10 V2A

P ASI 6 AP M 1 0 V 2 AP ot en ti al au sg le ic hs sc hi en e 4 72 20 9

Earthing block 4xFFour-pole earthing block with F sockets, for equipotential bonding of satellite cable shields or DGA GF TV lightning current arresters.

Type EB 4 F

Max. continuous operating d.c. voltage 65 V

D1 Lightning impulse current (10/350 µs) 10 kA

Frequency range d.c. - 2400 MHz

PU PartType pc(s). No.

EB 4 F 1 929 095

929 095 EB 4 F

E B 4 F929 095

Earth conductor, open / closed cable lugsCable lug, 1x open M8/M10 and 1x closed M8, suitable for combina-tion with Part No. 106 310, 106 329 and 472 209.

PU Partpc(s). No.

1 416 411

416 411

416 411

Angled fixing plateMade of stainless steel, suitable for installation of DEHNgate,Part No. 929 045 – 929 048.

PU Partpc(s). No.

20 106 310

106 310

106 310

Gas discharge tube with screw capSpare gas discharge tube capable of carrying lightning currents withscrew cap for DEHNgate LG 7 16 X. Self-extinguishing gas capsule withautomatic reset function in case of d.c. feeding currents up to 2.5 A orhigher HF performances.

Also suited for retrofitting DEHNgate LG 7 16 with conventional gascapsule technology (replacement of the complete capsule unit!).

Type GDT DGA 90 X

Lightning impulse current carrying capability (10/350 µs) 5 kA

Integrated into Part No. 929 046

Can be retrofitted into Part No. 929 046

PU PartType pc(s). No.

GDT DGA 90 X 1 929 496

929 496 GDT DGA90X

G DTDG A9 0 XG a s ent l a d un g s ab l ei ter fü rDE HN g atem i tSc h rau b versc h l u ss 9 2 9 4 9 6

Page 282: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 282/382280 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR COAXIAL CONNECTION

Page 283: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 283/382281www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR D-SUB CONNECTION

FS / USD

Surge arrester

• Surge protective adapter for easy retrofitting

• 9-pole, 15-pole or 25-pole shielded types avail-

able• Adapter with single-stage (FS) and 2-stage

(USD) protective circuit

Surge protective adapter, D-Sub plug-in connection, socket-pin type.

Surge protective adapter available in a shielded enclosure with D-Subplug-in connection, socket-pin type.The UNC screws of the protection forterminal equipment (FS) can be exchanged in any way. The thread is thussituated either on the pin or socket side,depending on the application.For

use in switchgear cabinets, the powerful USD surge arrester can besnapped onto DIN rails. Special types with other pinnings or circuits arealso available.

The surge arresters are availablein three different designs cover-ing the most frequent applica-tions. Due to their small size, theycan be easily integrated into thecabling.

9-pole, 15-pole and 25-poleFS surge arrester

USD devices can besnapped onto a DIN railwhich is supposed to dis-charge surges.Three plug-in types are available.

9-pole, 15-pole and 25-pole USD surge arrester

Page 284: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 284/382282 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR D-SUB CONNECTION

FS / USD

FS 9E PB924 017 FS 9E PB6

FS 9E PB 6 FineS ur ge Pr ot ec ti on Ad ap te rF S 6V 9 24 01 7

• Adapted to Profibus-DP

• Transmission up to 12 MBit/s

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

1

5

8

3

6

1

5

8

3

6

Diode protective circuit with very low capacity.Pin 6 without protection for the

programming interface.

Dimension drawing FS 9E PB

9-pole D-Sub, for Profibus-DP applications.

FS 9E PB 6

SPD class [Nominal voltage UN 6 V

Max. continuous operating d.c. voltage Uc 7 V

C2 Nominal discharge current (8/20 µs) line-line In 0.2 kA

C2 Nominal discharge current (8/20 µs) line-SG I n 0.2 kA

C2 Nominal discharge current (8/20 µs) SG-PG In 0.4 kA

Voltage protection level line-line for In C2 UP ≤ 25 V

Voltage protection level line-SG for In C2 Up ≤ 25 V

Voltage protection level SG-PG for In C2 Up ≤ 25 V

Voltage protection level line-line at 1 kV/µs C3 UC ≤ 18 V

Voltage protection level line-SG at 1 kV/µs C3 Up ≤ 18 V

Voltage protection level SG-PG at 1 kV/µs C3 U p ≤ 18 V

Cut-off frequency fG 90 MHz

Capacitance line-line C 25 pF

Capacitance line-SG C 35 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 40

For mounting on D-Sub (2 threaded screws 4/40 UNC)

Connection input/output D-Sub 9 plug / D-Sub 9 socket

Pinning Line: 3/8, SG: 5, PG: 1, 6: unprotected

Earthing via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)

Enclosure material plastic, metallised

Colour silver

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type FS 9E PB 6

Part No. 924 017

Packing unit 1 pc(s).

Page 285: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 285/382283www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR D-SUB CONNECTION

FS / USD

FS 9E HSFS 9E HS

Finer FS 12 V 9 24 01 9

• All pins protected

• Low voltage protection level

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

9 9

21

3

4

5

6

7

8

21

3

4

5

6

7

8

8-pole fine protection to common SG.Dimension drawing FS 9E HS

9-pole D-Sub. V-24 version with handshake function.

FS 9E HS 12

SPD class [Nominal voltage UN 12 V

Max. continuous operating d.c. voltage Uc 15 V

C2 Nominal discharge current (8/20 µs) line-SG I n 0.1 kA

C2 Nominal discharge current (8/20 µs) SG-PG In 0.1 kA

Voltage protection level line-SG for In C2 Up 24 V

Voltage protection level SG-PG for In C2 Up 200 V

Voltage protection level line-SG at 1 kV/µs C3 Up 21 V

Voltage protection level SG-PG at 1 kV/µs C3 U p 90 V

Cut-off frequency fG 10 MHz

Capacitance line-SG C 700 pF

Capacitance SG-PG C 350 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 40

For mounting on D-Sub (2 threaded screws 4/40 UNC)

Connection input/output D-Sub 9 plug / D-Sub 9 socket

Pinning line: 1/2/3/4/6/7/8/9, SG: 5

Earthing via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)

Enclosure material plastic, metallised

Colour silver

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type FS 9E HS 12Part No. 924 019

Packing unit 1 pc(s).

Page 286: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 286/382284 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR D-SUB CONNECTION

FS / USD

FS 15E924 016 FS 15E 5

FS 15E 5 FineS ur ge Pr ot ec ti on Ad ap te rF S 5V 9 24 01 6

• For 4-wire interfaces

• Low voltage protection level

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

1

8

11

4

9

2

1

8

11

4

9

2

Fine protection for 2 pairs to common SG. Dimension drawing FS 15E

15-pole D-Sub. RS-422, V.11 version.

FS 15E 5

SPD class [Nominal voltage UN 5 V

Max. continuous operating d.c. voltage Uc 8 V

C2 Nominal discharge current (8/20 µs) line-SG In 0.2 kA

C2 Nominal discharge current (8/20 µs) SG-PG In 0.6 kA

Voltage protection level line-line for In C2 UP 16 V

Voltage protection level line-SG for In C2 Up 16 V

Voltage protection level SG-PG for In C2 Up 16 V

Voltage protection level line-line at 1 kV/µs C3 UC 11 V

Voltage protection level line-SG at 1 kV/µs C3 Up 11 V

Voltage protection level SG-PG at 1 kV/µs C3 U p 11 V

Cut-off frequency fG 4 MHz

Capacitance line-line C 1500 pF

Capacitance line-SG C 1600 pF

Capacitance line-PG C 1200 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 40

For mounting on D-Sub (2 threaded screws 4/40 UNC)

Connection input/output D-Sub 15 plug / D-Sub 15 socket

Pinning line: 2/9, 4/11, SG: 8, PG: 1

Earthing via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)

Enclosure material plastic, metallised

Colour silver

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type FS 15E 5

Part No. 924 016

Packing unit 1 pc(s).

Page 287: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 287/382285www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR D-SUB CONNECTION

FS / USD

FS 25E HSFS 25E HS

Finer FS 12 V 9 24 01 8

• All lines interconnected

• Low voltage protection level

• For installation in conformity with thelightning protection zones concept atthe boundaries from 1 – 2 and higher

20 20

8 8

6 6

5 5

4 4

3 3

2 2

7 7

1 1

8-pole fine protection to common SG.Dimension drawing FS 25E HS

25-pole D-Sub. V.24 version with handshake function.

FS 25E HS 12

SPD class [Nominal voltage UN 12 V

Max. continuous operating d.c. voltage Uc 15 V

C2 Nominal discharge current (8/20 µs) line-SG I n 0.1 kA

C2 Nominal discharge current (8/20 µs) SG-PG In 0.1 kA

Voltage protection level line-SG for In C2 Up 24 V

Voltage protection level SG-PG for In C2 Up 200 V

Voltage protection level line-SG at 1 kV/µs C3 Up 21 V

Voltage protection level SG-PG at 1 kV/µs C3 U p 90 V

Cut-off frequency fG 10 MHz

Capacitance line-SG C 700 pF

Capacitance SG-PG C 350 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 40

For mounting on D-Sub (2 threaded screws 4/40 UNC)

Connection input/output D-Sub 25 plug / D-Sub 25 socket

Pinning line: 2/3/4/5/6/8/20, SG: 7, other lines are unprotected

Earthing via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)

Enclosure material plastic, metallised

Colour silver

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type FS 25E HS 12Part No. 924 018

Packing unit 1 pc(s).

Page 288: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 288/382286 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR D-SUB CONNECTION

FS / USD

USD 9 V24924 061 USD 9V2 4 SB

USD 9 V24 S B CableAdapter 924 061

• Plug-in surge arrester with 2-stageprotective circuit

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

5

3

2

5

3

2

protected

Combination of gas discharge tubes, decouplingresistors and diodes to PG.

Dimension drawing USD 9 V24

9-pole D-Sub. V.24 version.

USD 9 V24 S B

SPD class TNominal voltage UN 12 V

Max. continuous operating d.c. voltage Uc 12.5 V

C2 Nominal discharge current (8/20 µs) line-PG In 2.5 kA

C2 Nominal discharge current (8/20 µs) SG-PG In 7.5 kA

Voltage protection level line-SG for In C2 Up 20 V

Voltage protection level SG-PG for In C2 Up 250 V

Voltage protection level line-SG at 1 kV/µs C3 Up 18 V

Voltage protection level SG-PG at 1 kV/µs C3 U p 180 V

Series impedance per line 15 ohms

Operating temperature range -40°C...+80°C

For mounting on D-Sub or 35 mm DIN rail acc. to EN 60715

Connection input/output D-Sub 9 plug / D-Sub 9 socket

Pinning Line: 2/3, SG: 5

Earthing via earthing screw or DIN rail

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type USD 9 V24 S B

Part No. 924 061

Packing unit 1 pc(s).

Page 289: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 289/382287www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR D-SUB CONNECTION

FS / USD

USD 15 V11USD 15

Cable924 051

• Plug-in surge arrester with 2-stageprotective circuit

• Integrated decoupling of the protec-tive circuit to the terminal equipment

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

8

2

9

4

11

1

8

2

9

4

11

1

protected

The resistors at the output of the circuit protectoptocoupler and protective diodes in the terminal

equipment against overloads.

Dimension drawing USD 15 V11

15-pole D-Sub. RS 422,V.11 version.

USD 15 V11 S B

SPD class TNominal voltage UN 8 V

Max. continuous operating d.c. voltage Uc 8.5 V

C2 Nominal discharge current (8/20 µs) line-PG I n 2.5 kA

C2 Nominal discharge current (8/20 µs) SG-PG In 7.5 kA

Voltage protection level line-line/line-SG C2 Up 15 V

Voltage protection level SG-PG for In C2 Up 20 V

Voltage protection level line-line/line-SG at 1 kV/µs C3 Up 11 V

Voltage protection level SG-PG at 1 kV/µs C3 U p 15 V

Series impedance per line 37 ohms

Operating temperature range -40°C...+80°C

For mounting on D-Sub or 35 mm DIN rail acc. to EN 60715

Connection input/output D-Sub 15 plug / D-Sub 15 socket

Pinning Line: 2/9/4/11, SG: 8, PG: 1

Earthing via earthing screw or DIN rail

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type USD 15 V11 S B

Part No. 924 051

Packing unit 1 pc(s).

Page 290: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 290/382288 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR D-SUB CONNECTION

FS / USD

USD 25 V24924 046 USD 25V2 4 HSSB

USD 25 V24 HS S B CableAdapter 924 046

• Plug-in surge arrester with 2-stageprotective circuit

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

protected

20

234568

7

1

20

234568

7

1

Combination of gas discharge tubes, decouplingresistors and diodes to signal ground (SG).

Dimension drawing USD 25 V24

25-pole D-Sub.V.24 version, HS type with handshake function.

USD 25 V24 HS S B

SPD class TNominal voltage UN 12 V

Max. continuous operating d.c. voltage Uc 12.5 V

C2 Nominal discharge current (8/20 µs) line-PG In 2.5 kA

C2 Nominal discharge current (8/20 µs) SG-PG In 7.5 kA

Voltage protection level line-SG for In C2 Up 20 V

Voltage protection level SG-PG/line-PG for In C2 Up 250 V

Voltage protection level line-SG at 1 kV/µs C3 Up 18 V

Voltage protection level SG-PG at 1 kV/µs C3 U p 180 V

Series impedance per line 15 ohms

Operating temperature range -40°C...+80°C

Connection input/output D-Sub 25 plug / D-Sub 25 socket

Pinning Line: 2/3/4/5/6/8/20, SG: 7, PG:1

Earthing via earthing screw or DIN rail

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type USD 25 V24 HS S B

Part No. 924 046

Packing unit 1 pc(s).

Page 291: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 291/382289www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR TERMINAL CONNECTION

DSM

Surge arrester

• SPD for telecommunications equipment

• For space-saving flush mounting

• Easy installation due to plug-in terminals

Surge arrester for protection of telecommunications equipment for instal-lation into flush-type boxes or small-sized distribution boards. Plug-in ter-minals at the input.

In a typical installation, DSM surge arresters are integrated into the dis-tribution socket downstream of the socket outlet of the terminal equip-ment or into the cable duct. This makes them independent from the switchor box programme and protect, invisibly for the user, telecommunications

systems or devices. Of course, the SPDs can also be integrated into small-sized distribution boards. The use of the removable plug-in terminalsmakes the installation of DSM easier. As each plug-in terminal is designedfor four lines, through-wiring of an S0 bus, for example, is possible.

DSM is compact enough to allow forthe types to be installed easily eveninto small-sized distribution boards

situated in damp rooms.

DSM installed into a surface-mounted distribution board

1 2 3 4

R D B K W H Y

E

I S D

N S

0 - >

p r o t e c t e d

a 1 b 1 a 2 b 2

S P D

D S M

I S D N

S K

S P D N

o . 9 2 4 2 7 0

U C

7 , 5

V

i s n 5

k A

1 2 3

4

l = 500 mm

min. 1.0 mm2

5 - 6 m m 0 . 5 - 1 m

m

Apart from plug-in terminals, delivery alsoincludes a prewired earth conductor. Delivery (example)

Prewired cables

The plug-in connectors are prewired.Through-wiring of the ISDN bus is possible.

Installation – Step 1

Connecting DSM ... SK to thetelecommunications box

The lines fixed at DSM are connected tothe telecommunications box and DSMis placed at the rear panel of the box.Then, the prewired connectors can beplugged in.

Installation – Step 2

Final installation

The telecommunications box is insertedinto the mounting panel together withthe DSM surge arrester. Now, only anadequate cover has to be mounted.

Installation – Step 3

Page 292: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 292/382290 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR TERMINAL CONNECTION

DSM

DSM ISDN924 270 DSM ISDNSK

DSM ISDN SK SPD fort el ec om m. te rm in al eq ui pm en t 9 24 27 0

• Optional through-wiring of the ISDNbus via plug-in terminals

• Integrated protection for the remotesupply

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

protected

1

2

RD

BK

3

4

WH

YE

Energy-coordinated ISDN 4-wire protective circuitwith additional protection of the remote supply.

Dimension drawing DSM ISDN

For ISDN S0 interfaces.Through-wiring of the ISDN bus possible by means of four-pole terminal.

DSM ISDN SK

SPD class QNominal voltage UN 5 V

Nominal voltage pa-pa UN 40 V

Max. continuous operating d.c. voltage UC 7.5 V

Max. continuous operating d.c. voltage pa-pa UC 45 V

Nominal current IL 200 mA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 UP 30 V

Voltage protection level line-PG for In C2 UP 600 V

Voltage protection level pa-pa for In C2 UP 180 V

Voltage protection level line-line at 1 kV/µs C3 UP 17 V

Voltage protection level line-PG at 1 kV/µs C3 UP 600 V

Voltage protection level pa-pa at 1 kV/µs C3 UP 100 V

Series impedance per line 4.7 ohms

Cut-off frequency fG 4 MHz

Capacitance line-line C 1.5 nF

Capacitance line-PG C 15 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output quad pillar terminals / stranded conductors 0.25 mm2

Pinning 2 pairs

Termination diameter, solid 0.5 - 1.0 mmEarthing via flat connector 2.8 mm

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Accessories flat connector, earth conductor 500 mm

Ordering information

Type DSM ISDN SK

Part No. 924 270

Packing unit 1 pc(s).

Page 293: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 293/382291www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR TERMINAL CONNECTION

DSM

DSM TCDSM TC 2

SPD forpm en t 9 24 27 2

• Excellent transmission performance

• Also suitable for installation into dis-tribution boards

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

protected

1

2

RD

BK

3

4

WH

YE

Energy-coordinated protective circuit, free of leak-age currents to earth.

Dimension drawing DSM TC

For (system) telephones, Uk0, ADSL, for use with 2 pairs.

DSM TC 2 SK

SPD class RNominal voltage UN 110 V

Max. continuous operating d.c. voltage UC 170 V

Nominal current IL 200 mA

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 UP 275 V

Voltage protection level line-PG for In C2 UP 600 V

Voltage protection level line-line at 1 kV/µs C3 UP 220 V

Voltage protection level line-PG at 1 kV/µs C3 UP 600 V

Series impedance per line 4.7 ohmsCut-off frequency fG 17 MHz

Capacitance line-line C 300 pF

Capacitance line-PG C 10 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output quad pillar terminals / stranded conductors 0.25 mm2

Pinning 2 pairs

Termination diameter, solid 0.5 - 1.0 mm

Earthing via flat connector 2.8 mm

Enclosure material polyamide PA 6.6

Colour yellow

Test standards IEC 61643-21

Approvals, Certifications GOST

Accessories flat connector, earth conductor 500 mm

Ordering information

Type DSM TC 2 SK

Part No. 924 272

Packing unit 1 pc(s).

Page 294: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 294/382292 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR TERMINAL CONNECTION

BUStector

Surge arrester

• Extremely space-saving due to EIB / KNX busterminal design

• System-tested with EIBA certification• Also suitable for KNX buses

Surge arrester for EIB / KNX buses with connecting leads.

The discharge capacity, protective effect and mechanical design of BUStector surge arresters is adapted to the installation environment of EIB / KNX buses. Like a bus terminal it can be plugged onto the bus ter-

minal pins of a terminal device and can be wired with the existing con-necting cables. It protects especially line and area couplers as well asgateways and sensors installed at outer walls of buildings.

Page 295: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 295/382293www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR TERMINAL CONNECTION

BUStector

BTBT 24

BUStector

• Suitable for EIB / KNX systems

• Minimum space requirements

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 1 and higher

+

Heavy-duty gas discharge tube, adapted to thewithstand capability of the equipment of KNX

systems.

Dimension drawing BT

SPD with the design of a bus terminal. Approved by EIBA.

BT 24SPD class BNominal voltage Un 24 V

Max. continuous operating d.c. voltage UC 45 V

Nominal current IL 6 A

C2 Nominal discharge current per line In 5 kA

Voltage protection level for In C2 1200 V

Voltage protection level line-PG for In C2 650 V

Voltage protection level line-line at 1 kV/µs C3 750 V

Voltage protection level line-PG at 1 kV/µs C3 500 V

Cut-off frequency line-line 70 MHz

Capacitance line-line 10 pF

Capacitance line-PG 10 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 20

Connection input/output spring contacts Ø1 mm / connecting leads Ø0.8 mm

Earthing via lead 0.75 mm2, length 200 mm

Enclosure material thermoplastic

Colour blue

Test standards IEC 61643-21

Approvals, Certifications EIBA Certification No. Z 32/1399/95

Ordering information

Type BT 24

Part No. 925 001

Packing unit 1 pc(s).

Page 296: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 296/382294 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR TERMINAL CONNECTION

AS IBAS

Surge arrester

• Protects the data line of AS interfaces

• No bus address required

• Easy installation for use as coupling module

Surge arrester for devices with AS interface connection.

Surge arrester for devices with AS interface connection according to therequirements of AS interface buses. The surge arresters are adapted to theinstallation environment of the bus systems and require no bus address.

Due to the low self-impedance, the grey-coloured coupling module withintegrated surge protection can be inserted even into well-extended bussegments. In addition, it provides a distribution function for data trans-mission.

Page 297: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 297/382295www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR TERMINAL CONNECTION

AS IBAS

AS IBASAS IBAS

• Also protects ESD and switching peakvoltages

• Replaces coupling module with distri-bution function

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

3

4

The especially low-capacitance protective circuithardly stresses the AS interface

(1/6 bus equivalent).

Dimension drawing of coupling module

The coupling module protects the yellow data line of the AS interface. In addition, it provides a dis-tribution function. Earthing via DIN rail or plug-in contact.

AS IBAS YE

SPD class TMax. continuous operating d.c. voltage Uc 36 V

Nominal current IL 0.3 A

C2 Nominal discharge current (8/20 µs) line-line In 0.15 kA

C2 Nominal discharge current (8/20 µs) line-PG I n 5 kA

Voltage protection level line-line for In C2 UP 60 V

Voltage protection level line-PG for In C2 UP 1100 V

Voltage protection level line-line at 1 kV/µs C3 UP 50 V

Voltage protection level line-PG at 1 kV/µs C3 UP 900 V

Capacitance line-line C < 13 pFOperating temperature range -40°C...+80°C

Degree of protection for coupling module construction with AS interface module IP 67

For mounting on DIN rail or plane surface

Connection input/output yellow AS interface line

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type AS IBAS YE

Part No. 925 013

Packing unit 1 pc(s).

Page 298: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 298/382296 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR TERMINAL CONNECTION

Page 299: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 299/382297www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SCREWABLE SPDs

DEHNpipe

Surge arrester

• Maximum protection due to installation intothe cable run

• Surges are discharged via the enclosure of thefield device

• For nearly all types of two-conductor fielddevices with suitable cable gland

Surge arrester for outdoor use to be screwed onto two-conductor fielddevices. Stainless steel, IP 67.

DEHNpipe is made of corrosion-resistant stainless steel and is screwedonto the field device instead of a conventional cable gland. The perma-nently installed lines are then connected to the terminals of the fielddevice. Thus the protective components are directly situated in the cablerun. This provides an energy-coordinated surge protection. The SPD pro-

tects the inside of the field device against dangerous overvoltage with theinterfering impulses being discharged via the metal enclosure only andnot via the inside of the field device. Earthing accessories are also avail-able for plastic field enclosures.

DEHNpipe is designed for two-conductormeasuring sensors with 4-20 mA inter-faces.The surge arresters provide energy-coordinated surge protection for space-limited field devices in outdoor areas andreduce installation work.

DPI types

The universal surgearrester is even suitablefor applications allowingonly for a single assign-ment of the terminals of field devices, or providingonly one terminal forcable glands.Advantages for installation

max. 10 Nm

removal

installation1 2 3 4

4 3 2 1

Due to the two-part design of the SPD, the field cable can be connectedas usual, just like being connected to a measuring sensor.

Thanks to the cable gland a degree of protection of IP 67 is achieved.DEHNpipe supports common earthing concepts for cable shield treatmentof field cables. Depending on the cable gland used, the cable shield isearthed directly or indirectly or is not earthed at all. Indirect earthing inte-grates the shield into the protective concept – without leakage pickups.

Installation of DPI MD 24 M 2S

+

GNYE

receiver

GNYE cable(green/yellow)

BK cable (black)

RD cable (red)tauten

the cabletransmitter

The type for installation into pipes provides …-14 NPT male threads and per-manently installed lines.The device is installed as shown in the above figure.

Installation of DPI ME 24 N A2G

Page 300: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 300/382298 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SCREWABLE SPDs

DEHNpipe

DPI MD929 941 DPI MD2 4 M 2 S

DPI MD 24 M 2S DEHNpipe929 941

• Easy installation due to 2-part design

• Suitable for 3 shielding concepts

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

SHL

RD

BK

protected

Energy-coordinated protective circuit, no leakagecurrents to earth, with gas discharge tube for

indirect shield earthing.

Dimension drawing DPI MD

For 4-20 mA interfaces with thread M20 x 1.5 (female/male). Direct, indirect or no shield earthing.Cable gland available as accessory part.

DPI MD 24 M 2S

SPD class QNominal voltage UN 24 V

Max. continuous operating d.c. voltage UC 34.8 V

Max. continuous operating a.c. voltage UC 24.5 V

Nominal current IL 0.5 A

D1 Lightning impulse current (10/350 µs) per line I imp 1 kA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

C2 Nominal discharge current (8/20 µs) shield-PG In 20 kA

Voltage protection level line-line for In C2 UP 65 VVoltage protection level line-PG for In C2 UP 650 V

Voltage protection level shield-PG for In C2 UP 650 V

Voltage protection level line-line at 1 kV/µs C3 UP 50 V

Voltage protection level line-PG at 1 kV/µs C3 UP 500 V

Voltage protection level shield-PG at 1 kV/µs C3 UP 600 V

Series impedance per line 2.2 ohms

Cut-off frequency line-line fG 14 MHz

Capacitance line-line C 400 pF

Capacitance line-PG C 20 pF

Capacitance shield-PG C 15 pF

Operating temperature range -40°C ...+80°C

Degree of protection IP 67

For mounting on the field/device side M20 x 1.5 female thread / M20 x 1.5 male thread

Connection input/output screw/connecting leads 1.5 mm2, length of 200 mm

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 1.5 mm2

Earthing via enclosure or earthing ring (accessories)

Enclosure material V2A

Colour bare

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type DPI MD 24 M 2S

Part No. 929 941Packing unit 1 pc(s).

Page 301: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 301/382299www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SCREWABLE SPDs

DEHNpipe

DPI MEDPI ME

DEHNpipe

• Robust design

• Encapsulated protective circuit

• Single-ended type available onrequest

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

RD BU

GNYE

protected

BK BK

GNYE

Gas discharge tube and diodes,energy-coordinated to earth.

Dimension drawing DPI ME

For unbalanced interfaces with thread …-14 NPT (male/male). Earth conductor led through thesurge arrester.

DPI ME 24 N A2G

SPD class QNominal voltage UN 24 V

Max. continuous operating d.c. voltage UC 34.8 V

Max. continuous operating a.c. voltage UC 24.5 V

Nominal current IL 0.5 A

D1 Lightning impulse current (10/350 µs) per line I imp 1 kA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for In C2 UP 120 V

Voltage protection level line-PG for In C2 UP 65 VVoltage protection level line-line at 1 kV/µs C3 UP 98 V

Voltage protection level line-PG at 1 kV/µs C3 UP 49 V

Series impedance per line 4.7 ohms

Capacitance line-line C 250 pF

Capacitance line-PG C 450 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 67

For mounting on the field/device side …-14 NPT male thread / …-14 NPT male thread

Connection input/output connecting leads AWG 16, length of 500 mm

Earthing via enclosure and connecting lead

Enclosure material V2A

Colour bare

Test standards IEC 61643-21

Approvals, Certifications GOST

Ordering information

Type DPI ME 24 N A2G

Part No. 929 921

Packing unit 1 pc(s).

Page 302: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 302/382300 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SCREWABLE SPDs

Cable gland929 984 KV M20MS10.5

KV M20 MS 10.5 EMCCable Gland 929 984

• No direct shield connection

• Tested with DEHNpipe

Brass gland without shield connection.

KV M20 MS 10.5

Sealing range Rd 7.0 - 10.5 mm

For mounting on M20 x 1.5

Degree of protection IP 68

Material nickel-plated brass

Ordering information

Type KV M20 MS 10.5

Part No. 929 984

Packing unit 1 pc(s).

EMC cable gland929 982 KV S M20M S9 . 5

KV S M20 MS 9.5 EMCCable Gland 929 982

• For direct shield earthing

• Tested with DEHNpipe

Brass gland with shield connection.

KV S M20 MS 9.5

Sealing range Rd 6.5 - 9.5 mm

Shield diameter 3.2 - 6.5 mm

For mounting on M20 x 1.5

Degree of protection IP 68

Material nickel-plated brass

Ordering information

Type KV S M20 MS 9.5

Part No. 929 982

Packing unit 1 pc(s).

MS earthing ring929 996 ER DPI

M20

ER DPI M20 Set of Ea rt hi ng Ri ng sf or DE HN pi pe 92 999 6

• Recommended for mountingDEHNpipe in an insulating enclosure

Earthing ring made of nickel-plated brass, for external earthing of DPI.

ER DPI M20

For mounting on DPI M20 x 1.5

Material nickel-plated brass

Ordering information

Type ER DPI M20

Part No. 929 996

Packing unit 1 pc(s).

Accessories for DEHNpipe

Page 303: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 303/382301www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe MD Ex (i)

Surge arrester

• Maximum protection due to installation intothe cable run

• For all field devices with suitable cable gland• Two-part design for easy installation

• Tested according to ATEX and FISCO require-ments

Surge arrester for outdoor use to be screwed onto two-conductor fielddevices. Stainless steel, installation up to IP 67.

DEHNpipe is made of corrosion-resistant stainless steel and is screwedonto the field device instead of the conventional cable gland. The perma-nently installed lines are then connected to the terminals of the field

device. Thus, the protective components are directly situated in the cablerun. This provides an energy-coordinated surge protection. The SPD pro-

tects the inside of the field device against dangerous surges with theinterfering impulses being discharged via the metal enclosure only andnot via the inside of the field device. DEHNpipe MD Ex (i) can be either

used in Ex zone 1 or 2.

DEHNpipe is designed for intrinsically safetwo-conductor measuring sensors with4-20 mA or Profibus PA interfaces. Thesurge arresters provide energy-coordinat-ed surge protection for space-limited fielddevices in outdoor areas and reduceinstallation work.DPI MD EX

The universal surgearrester covers even appli-cations allowing only sin-gle assignment of the ter-minals of field devices orproviding only one termi-nal for cable glands.

Advantages for installation

max. 10 Nm

removal

mounting1 2 3 4

4 3 2 1

Due to the two-part design of the protective device, the field cable can beconnected as usual, like being connected to a measuring sensor.Thanks to the cable gland a degree of protection of IP 67 is achieved.DEHNpipe supports common earthing concepts for cable shield treatmentof field cables. Depending on the cable gland used, the cable shield isearthed directly or is not earthed at all.

Installation of DPI MD EX

Page 304: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 304/382302 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe MD Ex (i)

Surge arrester

EC-Type Examination Certificate DPI MD EX

Page 305: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 305/382303www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe MD Ex (i)

DPI MD EXDPI MD

DEHNpipe

• Easy installation due to two-partdesign

• Self-capacitance and self-inductancenegligibly small

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

RD

BK

protected

Low-capacitance, energy-coordinated protective cir-cuit with an insulation resistance > 500 V to earth.

Dimension drawing DPI MD EX

Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCOrequirements. Cable gland must be ordered separately.

DPI MD EX 24 M 2

SPD class TNominal voltage UN 24 V

Max. continuous operating d.c. voltage Uc 34.8 V

Max. continuous operating a.c. voltage UC 24.5 V

Max. input voltage acc. to EN 50020 Ui 30 V

Max. input current acc. to EN 50020 Ii 0.5 A

Nominal current IL 0.5 A

D1 Lightning impulse current (10/350 µs) per line I imp 1 kA

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kAVoltage protection level line-line for In C2 UP 55 V

Voltage protection level line-PG for In C2 UP 1100 V

Voltage protection level line-line at 1 kV/µs C3 UP 49 V

Voltage protection level line-PG at 1 kV/µs C3 UP 1000 V

Series impedance per line 1.8 ohms

Cut-off frequency line-line fG 7 MHz

Capacitance line-line C 850 pF

Capacitance line-PG C 15 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 67

For mounting on field/device side M20 x 1.5 female thread / M20 x 1.5 male thread

Connection input/output screw / connecting leads 1.5 mm2, length of 200 mm

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 1.5 mm2

Earthing via enclosure

Enclosure material V2A

Colour bare

Test standards IEC 61643-21

Ex certifications ATEX: KEMA 09ATEX0122 X: II 2 (1) G Ex ia IIC T4 ... T6

Approvals, Certifications GOST

Ordering information

Type DPI MD EX 24 M 2

Part No. 929 960

Packing unit 1 pc(s).

Page 306: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 306/382304 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

Cable gland929 984 KV M20MS10.5

KV M20 MS 10.5 EMCCable Gland 929 984

• No direct shield connection

• Tested with DEHNpipe

Brass gland without shield connection.

KV M20 MS 10.5

Sealing range Rd 7.0 - 10.5 mm

For mounting on M20 x 1.5

Degree of protection IP 68

Material nickel-plated brass

Ordering information

Type KV M20 MS 10.5

Part No. 929 984

Packing unit 1 pc(s).

EMC cable gland 929 982 KV S M20M S9 . 5

KV S M20 MS 9.5 EMCCable Gland 929 982

• For direct shield earthing

• Tested with DEHNpipe

Brass gland with shield connection.

KV S M20 MS 9.5

Sealing range Rd 6.5 - 9.5 mm

Shield diameter 3.2 - 6.5 mm

For mounting on M20 x 1.5

Degree of protection IP 68

Material nickel-plated brass

Ordering information

Type KV S M20 MS 9.5

Part No. 929 982

Packing unit 1 pc(s).

Accessories for DEHNpipe MD Ex (i)

Page 307: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 307/382305www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe CD Ex (i)

Surge arrester

• Economical SPD for field devices with sparecable gland

• Easy to retrofit and extremely space-saving• Tested according to ATEX and FISCO require-

ments

Surge arrester for outdoor use to be screwed onto two-conductor fielddevices. Stainless steel, installation up to a degree of protection of IP 67.

DEHNpipe C is made of corrosion-resistant stainless steel and is screweddirectly onto the field device. Like a field cable, the permanently installedlines are connected to the terminals of the field device.Thus, the protectivecomponents are situated in parallel to the cable run. The connection withthe metal or plastic enclosures can be carried out easily as the earth wireof the protective device can be connected to the earth terminal of a fielddevice.

A degree of protection of IP 67 can be achieved due to the design of thesurge arrester.Intrinsically safe surge arresters are typically used in 4-20 mA measuringcircuits or bus systems up to 30 V. According to the type used, DEHNpipe Cis designed for measuring sensors with M20 x 1.5 or…-14 NPT cable glandconnections. DEHNpipe CD Ex (i) can be either installed in Ex zones 1 or 2.

EC-Type Examination Certificate DPI CD Ex(i)

Page 308: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 308/382306 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe CD Ex (i)

DPI CD EXI929 961 DPI CDEXI24 M929 963 DPI CDEXI24N

DPI CD EXI 24 M DEHNpipe929 961DPI CD EXI 24 N DEHNpipe929 963

• Easy installation on field devices withspare cable gland

• Self-capacitance and self-inductancenegligibly small

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

RD

BK

GNYE

Low-capacitance protective circuit with aninsulation strength > 500 V to earth.

Dimension drawing DPI CD EXI 24 M

Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCOrequirements.

DPI CD EXI 24 M DPI CD EXI 24 N

SPD class T TNominal voltage UN 24 V 24 V

Max. continuous operating d.c. voltage UC 32 V 32 V

Max. continuous operating a.c. voltage UC 22.6 V 22.6 V

Max. input voltage acc. to EN 50020 Ui 30 V 30 V

Max. input current acc. to EN 50020 Ii 0.55 A 0.55 A

Nominal current IL 0.55 A 0.55 A

D1 lightning impulse current (10/350 µs) line-PG I imp 1 kA 1 kA

C2 Total nominal discharge current (8/20 µs) In 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) line-line In 150 A 150 AC2 Nominal discharge current (8/20 µs) line-PG In 10 kA 10 kA

Voltage protection level line-line for In C2 UP 58 V 58 V

Voltage protection level line-PG for In C2 UP 1700 V 1700 V

Voltage protection level line-line at 1 kV/µs C3 UP 50 V 50 V

Voltage protection level line-PG at 1 kV/µs C3 UP 1200 V 1200 V

Cut-off frequency line-line fG 67 MHz 67 MHz

Capacitance line-line C 25 pF 25 pF

Capacitance line-PG C 15 pF 15 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Degree of protection design in IP 67 design in IP 67

For mounting on field/device side M20 x 1.5 male thread …-14 NPT male thread

Connection input/output connecting leads 1.3 mm2, length of 250 mm connecting leads 1.3 mm2, length of 250 mm

Earthing via connecting lead connecting lead

Enclosure material V4A V4A

Colour bare bare

Test standards IEC 61643-21 IEC 61643-21

Ex certifications ATEX: KEMA 04ATEX1189 X: II 2 (1) G Ex ia IIC T5 ... T6 ATEX: KEMA 04ATEX1189 X: II 2 (1) G Ex ia IIC T5 ... T6

Approvals, Certifications GOST GOST

Ordering information

Type DPI CD EXI 24 M DPI CD EXI 24 N

Part No. 929 961 929 963

Packing unit 1 pc(s). 1 pc(s).

Page 309: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 309/382307www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe CD Ex (d)

Surge arrester

• Economical SPD for field devices with sparecable gland or field bus distributors in haz-ardous areas

• Easy to retrofit and extremely space-saving

• ATEX certification

Surge arrester for outdoor use to be screwed onto two-conductor fielddevices. Stainless steel. Installation up to a degree of protection of IP 67.

The flameproof DEHNpipe C surge arrester is made of corrosion-resistantstainless steel and is directly screwed onto the field device. Like a fieldcable, the permanently installed lines are connected to the terminals of the field device. Thus, the protection components are situated in parallelto the cable run. The device can be easily installed into metal or plasticfield enclosures as the earth wire of the protective device can be connect-ed to the earth terminal of a field device.

A degree of protection of IP 67 can be achieved due to the design of thesurge arrester. These flameproof SPDs are typically used in 4-20 mA meas-uring circuits or bus systems up to 30 V. According to the type used,DEHNpipe C is designed for measuring sensors with M20 x 1.5 or …-14NPT cable gland connection. DEHNpipe CD Ex (d) can be either installedin Ex zone 1 or 2.

EC-Type Examination Certificate DPI CD Ex (d)

Page 310: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 310/382308 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe CD Ex (d)

DPI CD EXD929 962 DPI CDEXD24 M929 964 DPI CDE X D2 4 N

DPI CD EXD 24 M DEHNpipe929 962DPI CD EXD 24 N DEHNpipe929 964

• Easy installation on the spare cablegland of field devices

• Type Ex(d) for universal use

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

RD

BK

GNYE

Low-capacitance protective circuit with aninsulation resistance > 500 V to earth.

Dimension drawing DPI CD EXD 24 M

Flameproof surge arrester for use in potentially explosive atmospheres for protecting measuringcircuits and bus systems.

DPI CD EXD 24 M DPI CD EXD 24 N

SPD class T TNominal voltage UN 24 V 24 V

Max. continuous operating d.c. voltage Uc 32 V 32 V

Max. continuous operating a.c. voltage Uc 22.6 V 22.6 V

Nominal current IL 0.55 A 0.55 A

D1 Lightning impulse current (10/350 µs) line-PG I imp 1 kA 1 kA

C2 Total nominal discharge current (8/20 µs) In 10 kA 10 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA 10 kA

Voltage protection level line-line for In C2 UP 58 V 58 V

Voltage protection level line-PG for In C2 UP 1700 V 1700 VVoltage protection level line-line at 1 kV/µs C3 UP 50 V 50 V

Voltage protection level line-PG at 1 kV/µs C3 UP 1200 V 1200 V

Cut-off frequency line-line fG 67 MHz 67 MHz

Capacitance line-line C 25 pF 25 pF

Capacitance line-PG C 15 pF 15 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Degree of protection design in IP 67 design in IP 67

For mounting on field/device side M20 x 1.5 male thread …-14 npt male thread

Connection input/output connecting leads 1.3 mm2, length of 250 mm connecting leads 1.3 mm2, length of 250 mm

Earthing via connecting lead connecting lead

Enclosure material V4A V4A

Colour bare bare

Test standards IEC 61643-21 IEC 61643-21

Ex certifications ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6 ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6

Approvals, Certifications GOST GOST

Ordering information

Type DPI CD EXD 24 M DPI CD EXD 24 N

Part No. 929 962 929 964

Packing unit 1 pc(s). 1 pc(s).

Page 311: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 311/382309www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe CD Ex (d)

DPI CD HF EXDDPI CD HF EXD 5 M

• Easy installation on the spare cablegland of field devices

• Ex (d) version for a variety of applica-tions

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

RD

BK

BN

BU

GNYE

S W 2 7

M 2

0 x 1 . 5

approx.

300 55

75

Dimension drawing DPI CD HF EXD 5 M

Flameproof surge arrester for use in potentially explosive atmospheres for protecting measuringcircuits and bus systems.

DPI CD HF EXD 5 M

SPD class TNominal voltage UN 5 V

Max. continuous operating d.c. voltage Uc 6 V

Max. continuous operating a.c. voltage Uc 4.2 V

Nominal current at 80° C IL 0.1 A

C2 Total nominal discharge current (8/20 µs) In 20 kA

C2 Nominal discharge current (8/20 µs) per line In 10 kA

Voltage protection level line-line for In C2 UP 55 V

Voltage protection level line-PG for In C2 UP 1000 V

Voltage protection level line-line at 1 kV/µs C3 UP 12 VVoltage protection level line-PG at 1 kV/µs C3 UP 700 V

Series impedance per line 4.7 ohms

Cut-off frequency line-line fG 100 MHz

Capacitance line-line C 40 pF

Capacitance line-PG C 30 pF

Operating temperature range -40°C...+80°C

Degree of protection design in IP 67

For mounting on field/device side M20 x 1.5 male thread

Connection input/output connecting cables 1.3 mm2, length of 300 mm

Earthing via connecting cable

Enclosure material V4A

Colour bare

Test standards IEC 61643-21

Ex certifications ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6

Approvals, Certifications GOST

Ordering information

Type DPI CD HF EXD 5 M

Part No. 929 971

Packing unit 1 pc(s).

Low-capacitance, energy-coordinated protectivecircuit.

N E W

Page 312: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 312/38231 0 www.dehn.de

INFORM ATION TECHNOLOGY SYSTEM S

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe CD Ex (d)

DPI CD EXD 230 24929 969 DPI CD EX D 230 24 M

929 970 DPI CD EX D 230 24 N

DPI CD EXD 230 24 M

929 969

DPI CD EXD 230 24 N

929 970

• Dual surge protection for 120/230 V

power supplies and 0/4-2 0 m A inter-

faces

• Easy installation on field devices with

a spare cable gland

• Increased safety due to distinctive Y

circuit for 120/2 30 V power supplies

RD

BK

GN/YE

BL

BR

120 V /230 V

24 V approx.

250 83

63 S W 2 7

M 2

0 x 1 . 5

Dimension drawing DPI CD EXD 230 24 M /N

Flameproof surge arrester for use in potential-

ly explosive areas for pro tecting 1 20/230 V ter-

minal equipment and 0/4-20 mA interfaces

ATEX certifi cation (Ex d IIC T5 or T6) pendin g

Protection for the data side DPI CD EXD 230 24 M DPI CD EXD 230 24 N

SPD class U UNominal voltage UN 24 V 24 V

Ma x. continuous operating d.c. voltage Uc 32 V 32 V

Ma x. continuous operating a.c. voltage Uc 22.6 V 22.6 V

Nominal current at 80° C IL 0.55 A 0.55 A

D1 Lightning impulse current (10/350 µs) line-PG I imp 1 kA 1 kA

C2 Total nominal discharge current (8/20 µs) In 10 kA 10 kA

Voltage protection level line-line for In C2 UP ≤ 58 V ≤ 58 V

Voltage protection level line-PG for In C2 UP ≤ 900 V ≤ 900 V

Voltage protection level line-line at 1 kV/µs C3 UP ≤ 50 V ≤ 50 V

Voltage protection level line-PG at 1 kV/µs C3 U P ≤ 850 V ≤ 850 V

Capacitance line-line C ≤ 25 pF ≤ 25 pFCapacitance line-PG C ≤ 15 pF ≤ 15 pF

Operating temperature range -40°C...+80°C -40°C...+80°C

Degree of protection design in IP 67 design in IP 67

For mounting on field/device side M20 x 1.5 male thread …-14 NPT male thread

Connection input/output connecting leads 1.3 mm 2, length of 250 mm connecting leads 1.3 mm 2, length of 250 mm

Earthing via connecting lead connecting lead

Enclosure mater ial V4A V4A

Colour bare bare

Test standards IEC 61643 -21 IEC 61643 -21

Approvals, Certifications GOST GOST

Protection for the power side DPI CD EXD 230 24 M DPI CD EXD 230 24 N

SPD according to EN 61643-11 Type 2 Type 2

SPD according to IEC 61643-1 Class II Class IINominal a.c. voltage UN 120/230 V 120/230 V

Ma ximum continuous operating a.c. voltage Uc 255 V 255 V

M ax. discharge current L-N I max 3 kA 3 kA

Nominal discharge current (8/20 µs) I n 3 kA 3 kA

Total discharge current (8/2 0) L+N-PE I total 5 kA 5 kA

Voltage protection level L-N Up ≤ 1.4 kV ≤ 1.4 kV

Voltage protection level L/N-PE Up ≤ 1.5 kV ≤ 1.5 kV

M ax. supply-side overcurrent protection 16 A gL/gG or B 16 A 16 A gL/gG or B 16 A

Short-circuit current withstand capability in case

of supply-side overcurrent protection with 16 A gL/gG 6 kA rms 6 kA rms

TOV L-N UT 335 V/5 sec 335 V/5 sec

TOV L/N-PE (1) UT 400 V/5 sec 400 V/5 sec

TOV L/N-PE (2) UT 1200 V+U0 /2 00 ms 12 00 V+ U0 /2 00 ms

Indication of the disconnection device upstream fuse element upstream fuse element

Ordering information

Type DPI CD EXD 230 24 M DPI CD EXD 230 24 N

Part No. 929 969 929 970

Packing unit 1 pc(s). 1 pc(s).

• II 2 G Ex... version can be used for all

types of applications

• For installation in conformity with the

lightning protection zones concept at

the boundaries from 0 B – 2 and higher

N E W

Available by mid 2010

Basic circuit diagram DPI CD EXD 230 24 M/N

Page 313: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 313/382311www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

BLITZDUCTOR® XT Ex (i)

Surge arrester

• Effective protection with minimum spacerequirements

• For use with 2-pole, 3-pole or 4-pole intrinsical-ly safe interfaces

• Function-optimised design for safe handlingand easy installation

• Quick testing of LifeCheck-equipped SPD mod-ules

• ATEX approval, FISCO

Pluggable, multipole, universal surge arrester for use in intrinsically safesystems with integrated LifeCheck monitoring device.

BLITZDUCTOR XT EX is a pluggable, four-pole, universal DIN rail mountedsurge arrester designed for the most stringent requirements on the avail-ability of intrinsically safe measuring and control circuits and bus systems.With regard to intrinsic safety, the SPD is considered earth-free and itsself-inductance and self-capacitance are negligibly small. The high

impulse current discharge capacity (min. 10x) and the low voltage protec-tion level are supported by the low-impedance design of the device.LifeCheck allows for quick and easy testing of SPDs. However, the SPDmodules may only be read out by means of the hand-held DRC LC readerin non-explosive atmospheres.Integrated into the SPD modules, LifeCheck permanently monitors the

proper condition of the SPD. Like an early warning system, LifeCheck reli-ably detects potential electrical and thermal overloads of the protectioncomponents. The LifeCheck status can be read out within a matter of sec-onds by means of DEHNrecord LC via contactless RFID technology andalso shows the date of the last test of the SPD module. A stationary con-

dition monitoring system allows status-oriented maintenance of 10 BXT.To ensure safe operation, the SPD provides protection against vibrationeffects and shock up to a 30-fold acceleration of gravity. The function-optimised design of the devices allows both quick and easy replacementof SPD modules which house all relevant protection elements. The SPDmodule and the base part must be ordered separately.

Completely installed BLITZDUCTOR XT EX.Two-part design with universal base partand application-specific SPD module.Particularly space-saving, for DIN railmounting.

BLITZDUCTOR XT EX

Dimension drawing of a BLITZDUCTOR XTEX base part with plugged-in SPD module.Width: 2/3 mods. (12 mm), for use in dis-tribution boards with DIN rails.

Dimension drawing

Universal base part accommodates alltypes of SPD modules. The SPD modulescan be easily removed from the base partwithout signal interruption thereby min-imising storage requirements as well as

prewiring and maintenance operations.

Base part

BXT ML4 BD EX 24:

Universal LifeCheck-equipped SPD modulefor 2 intrinsically safe circuits such as 4-20mA, HART, PROFIBUS-PA, FF, NAMUR.BXT ML4 BC EX 24:

For protection of e.g.3-wire or 4-wire tem-perature measuring systems.BXT ML2 BD HF EX 6:

Protection of a pair for fast data transmis-sion and a feeding currents up to 4.8 A.

3 basic types

Page 314: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 314/382312 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

BLITZDUCTOR® XT Ex (i)

Surge arrester

EC-Type Examination Certificate BXT EX

Page 315: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 315/382313www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

BLITZDUCTOR® XT Ex (i) Base Part

BXT BAS EXBXT BAS

• Four-pole and universal device for alltypes of intrinsically safe SPD mod-ules

• Insertion and removal without signalinterruption

• Universal design without protectioncomponents

protected

BXT BAS

BXT ML4...

13

1´ 3´

24

2´ 4´

1 2 3 4 1´ 2´ 3´ 4´

BXT BAS protected

13

1´ 3´

24

2´ 4´

1 32 4´ 2´ 3´ 1´ 4

Basic circuit diagram with and withoutplugged-in module

Dimension drawing BXT BAS EX

BLITZDUCTOR XT base part for use as very space-saving, four-pole, universal feed-through termi-nal for intrinsically safe circuits for the insertion of SPD modules without signal interruption. Thesnap-in mechanism at the supporting foot of the base part allows the device to be safely earthedvia the DIN rail. As no components of the protective circuit are situated in the base part, mainte-nance operation is only required for the protection modules.

BXT BAS EX

Operating temperature range -50°C...+80°C

Degree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output screw / screw

Cross-sectional area, solid 0.08 - 4 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Tightening torque (terminals) 0.4 Nm

Earthing via 35 mm DIN rail acc. to EN 60715

Enclosure material polyamide PA 6.6

Colour blue

Ex certifications ATEX: KEMA 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6Approvals, Certifications CSA, GOST

Ordering information

Type BXT BAS EX

Part No. 920 301

Packing unit 1 pc(s).

Module release spring for removing the protectionmodule without problems

The earthing foot ensures cost-effective installation. No additionalearth connection is required since thedevice is safely earthed via the DIN rail

Clear identification of the“protected“ side forfaultless installation

Designation spacefor marking the circuits

Lightning current carryinglaminated contacts

High-quality, four-pole screw terminals for the following cross-sections:stranded: 2.5 mm2

solid: 4 mm2

Reverse polarity protection preventsincorrect insertion of the protectionmodule

Leading/retarded make-before-break switch contacts for uninterruptedremoval and insertion without downtime

Page 316: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 316/38231 4 www.dehn.de

INFORM ATION TECHNOLOGY SYSTEM S

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

BLITZDUCTOR ® XT Ex (i) LifeCheck ® Modules

BXT M L4 BD EX 24920 381 BXT ML4BD EX 24

BXTML4 BD EX 24920 381

• For universal use, with LifeCheck SPD

monitoring function

• Self-capacitance and self-inductance

negligibly small

• For installation in conformity with the

lightning protection zones concept at

the boundaries from 0 B – 2 and higher

1

2

protected

3

4

The RFID chip of the LifeCheck SPD monit oringdevice can be read out with out contact via

DEHNrecord LC. Insulation resistance > 500 Vline-earth.

Dimension draw ing BXT ML4 BD EX

Space-saving LifeCheck-equipped surge arrester module for prot ecting 2 pairs in intrinsically safe

measuring circuit s and bus system s, meets FISCO requirement s.

BXT ML4 BD EX 24

SPD class TSPD monitoring LifeCheck

Nominal voltage UN 24 V

Ma x. continuous operating d.c. voltage Uc 33 V

Ma x. continuous operating a.c. voltage Uc 23 V

Max. input voltage acc. to EN 60079-11 U i 30 V

Max. input current acc. to EN 60079-11 I i 0.5 A

D1 Total lightning impulse current (10/350 µs) I imp 4 kA

D1 Lightning impulse current (10/350 µs) per line I imp 1 kA

C2 Total nominal discharge current (8/20 µs) I n 20 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for I imp D1 Up ≤ 50 V

Voltage protection level line-PG for I imp D1 Up ≤ 1300 VVoltage protection level line-line for In C2 Up ≤ 52 V

Voltage protection level line-PG for In C2 Up ≤ 1400 V

Voltage protection level line-line at 1 kV/µs C3 U p ≤ 45 V

Voltage protection level line-PG at 1 kV/µs C3 U p ≤ 1100 V

Series impedance per line 1.0 ohm

Cut-off frequency line-line fG 7.7 MHz

Capacitance line-line C ≤ 0.8 nF

Capacitance line-PG C ≤ 16 pF

Operating temperature range -40°C...+80°C

Degree of protection (plugged-in) IP 20

For plugging into base part

Earthing via base part

Enclosure mater ial polyamide PA 6.6Colour blue

Test standards IEC 61643-21, UL 497B

SIL classification SIL2 / SIL3 f or m ore details see: ww w.dehn.de/en/sil/

Ex certifications ATEX: KEM A 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6

Approvals, Certifications CSA, GOST

Ordering information

Type BXT ML4 BD EX 24

Part No. 920 381

Packing unit 1 pc(s).

DRC MCM XTDIN rail mounted device wi th integrated

LifeChec

k sensor for status-oriented monitor-ing of max. 10 BXT devices with LifeCheckfu nct ion.

PU PartType pc(s). No.

DRC M CM XT 1 910 695

910 695 DRCM CM X T

DRCM CM X T910 695

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing ofLifeCheck-equipped arresters.

PU PartType pc(s). No.

DRC LC M 3+ 1 910 653

910 653 DRC LCM3

DRCLCM 3Ableiterprüfgerät LifeCheck 910 653

BXT BAS EXBase part for use as a feed-through terminal inintrinsically safe circuits for the insertion ofSPD modules without signal interruption.

PU PartType pc(s). No.

BXT BAS EX 1 920 301

920 301 BXT BASEX

BXTBASEX920 301

For further te c hn i c al detai ls about ” Acc essories for BLITZDUCTOR XT LifeChe c k modules“ please also refer to pages 313/317/318/319/360/362.

Page 317: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 317/38231 5www.dehn.de

INFORMATION TECHNOLOGY SYSTEM S

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

BLITZDUCTOR ® XT Ex (i) LifeCheck ® Modules

BXT ML4 BC EX 24BXT M L4

• For multi-wire measuring systems,

with LifeCheck SPD monitoring device

• Self-capacitance and self-inductance

negligibly small

• For installation in conformity with the

lightning protection zones concept at

the boundaries from 0 B – 2 and higher

1

2

protected

3

4

The RFID chip of the LifeCheck SPD monit oringdevice can be read out w ithout contact via

DEHNrecord LC. Insulation resistance > 500 Vline-earth.

Dimension draw ing BXT ML4 BC EX

Space-saving LifeCheck-equipped surge arrester module for protecting up to 4 earth-potential-free

single lines wit h common reference potential in int rinsically safe circuits, meets FISCO requirement s.

BXT ML4 BC EX 24

SPD class TSPD monitoring LifeCheck

Nominal voltage UN 24 V

Max. continuous operating d.c. voltage Uc 33 V

Max. continuous operating a.c. voltage Uc 23.3 V

Max. input voltage acc. to EN 60079-11 U i 30 V

Max. input current acc. to EN 60079-11 I i 0.5 A

D1 Total lightning impulse current (10/350 µs) I imp 4 kA

D1 Lightning impulse current (10/350 µs) per line I imp 1 kA

C2 Total nominal discharge current (8/20 µs) I n 20 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for I imp D1 Up ≤ 53 V

Voltage protection level line-PG for I imp D1 Up ≤ 1300 VVoltage protection level line-line for In C2 Up ≤ 55 V

Voltage protection level line-PG for In C2 Up ≤ 1400 V

Voltage protection level line-line at 1 kV/µs C3 U p ≤ 45 V

Voltage protection level line-PG at 1 kV/µs C3 U p ≤ 1100 V

Series impedance per line 1 ohm

Cut-off frequency line-line fG 6.4 MHz

Capacitance line-line C ≤ 0.8 nF

Capacitance line-PG C ≤ 16 pF

Operating temperature range -40°C...+80°C

Degree of protection (plugged-in) IP 20

For plugging into base part

Earthing via base part

Enclosure materi al polyamide PA 6.6Colour blue

Test standards IEC 61643-21, UL 497B

SIL classification SIL2 / SIL3 f or m ore details see: ww w.dehn.de/en/sil/

Ex certifications ATEX: KEM A 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6

Approvals, Certifications CSA, GOST

Ordering information

Type BXT ML4 BC EX 24

Part No. 920 384

Packing unit 1 pc(s).

Earthing moduleFor direct earthing of l ines connected to the

BLITZDUCTOR XT base part.PU Part

Type pc(s). No.

BXT M 4 E 1 920 308

920 308 BXT M4 E

BXT M 4 E BXT-Erdungsm odu l 920 308

Test / D isconnection M oduleModule for testing l ines, to be plugged intothe BLITZDUCTOR XT base part.

PU PartType pc(s). No.

BXT M 4 T 1 920 309

920 309 BXT M 4 T

BXT M4 T BXT- Pr üf- /Trennmodul 920 309

PartitionFor DRC MCM XT

PU PartType pc(s). No.

TW DRC M CM EX 1 910 697

910 697 TW DRCMCM EX

TW DRC M CM EX Ex i -Trennwand f. DRC MCM 910 697

For further te c hn i c al details about ” Acc essories for BLITZDUCTOR XT LifeChe c k modules“ please also refer to pages 313/317/318/319/360/362.

Page 318: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 318/38231 6 www.dehn.de

INFORM ATION TECHNOLOGY SYSTEM S

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

N E W

BLITZDUCTOR ® XT Ex (i) LifeCheck ® Modules

BXT M L2 BD HF EX 6920 538 BXT M L2 BD HF EX 6

BXTML2 BD HFEX 6920 538

• Universal use, with LifeCheck SPD

monitoring de vice

• Self-capacitance and self-inductance

negligibly small

• For installation in conformity with the

lightning protection zones concept at

the boundaries from 0 B – 2 and higher

1

2

protected

3

4

The RFID chip of the LifeCheck SPD monit oringdevice can be read out with out contact via

DEHNrecord LC. Insulat ion strength> 500 V l ine-earth.

Dimension draw ing BXT ML2 BD HF EX 6

Space-saving LifeCheck-equipped surge arrester module for protecting 1 pair in intrinsically safe

measuring circuit s and RS485 bus system s.

BXT ML2 BD HF EX 6

SPD class TSPD monitoring LifeCheck

Nominal voltage UN 6 V

Ma x. continuous operating d.c. voltage Uc 6 V

Ma x. continuous operating a.c. voltage Uc 4.2 V

Max. input voltage acc. to EN 60079-11 U i 4.2 V

Max. input current acc. to EN 60079-11 I i 4.8 A

Max. input current acc. to EN 60079-11

(without protection module only up to 60°C) I i 4.8 A

D1 Lightning impulse current (10/350 µs) per line I imp 1 kA

C2 Total nominal discharge current (8/20 µs) I n 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for I imp D1 Up ≤ 35 VVoltage protection level line-PG for I imp D1 Up ≤ 1600 V

Voltage protection level line-line for In C2 Up ≤ 35 V

Voltage protection level line-PG for In C2 Up ≤ 1800 V

Voltage protection level line-line at 1 kV/µs C3 U p ≤ 20 V

Voltage protection level line-PG at 1 kV/µs C3 U p ≤ 1400 V

Cut-off frequency line-line fG 100 MHz

Capacitance line-line C ≤ 25 nF

Capacitance line-PG C ≤ 20 pF

Operating temperature range -40°C...+80°C

Degree of protection (plugged-in) IP 20

For plugging into base part

Earthing via base part

Enclosure mater ial polyamide PA 6.6

Colour blue

Test standards IEC 61643-21

SIL classification SIL2 for more details see: ww w.dehn.de/en/sil/

Ex certifications ATEX: KEM A 06ATEX0274 X: II 2 G Ex ib IIC T4 ... T6

Ordering information

Type BXT ML2 BD HF EX 6

Part No. 920 538

Packing unit 1 pc(s).

For further te c hn i c al detai ls about ” Acc essories for BLITZDUCTOR XT LifeChe c k modules“ please also refer to pages 313/317/318/319/360/362.

DRC MCM XTDIN rail mounted device wi th integrated

LifeChec

k sensor for status-oriented monitor-ing of max. 10 BXT devices with LifeCheckfu nct ion.

PU PartType pc(s). No.

DRC M CM XT 1 910 695

910 695 DRCM CM X T

DRCM CM X T910 695

DRC LC M3+Portable device with LifeCheck sensor for

flexible use. For fast and easy testing ofLifeCheck-equipped arresters.

PU PartType pc(s). No.

DRC LC M 3+ 1 910 653

910 653 DRC LCM3

DRCLCM 3Ableiterprüfgerät LifeCheck 910 653

BXT BAS EXBase part for use as a feed-through terminal inintrinsically safe circuits for the insertion ofSPD modules without signal interruption.

PU PartType pc(s). No.

BXT BAS EX 1 920 301

920 301 BXT BASEX

BXTBASEX920 301

Page 319: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 319/382317www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

Accessories for BLITZDUCTOR® XT Ex (i)

Earthing moduleBXT M4 E

• For plugging onto BLITZDUCTOR XTbase parts

• Easy handling

• Quick replacement when retrofittingan SPD module

1

2

protected

3

4

Basic circuit diagram BXT M4 EDimension drawing BXT M4 E

The plugged-in earthing module short-circuits all lines connected to the BLITZDUCTOR XT base partto PG. It directly earths initially used cable cores, which are already connected to the base part.

BXT M4 E

D1 Total lightning impulse current (10/350 µs) I imp 10 kA

Operating temperature range -40°C...+80°C

Degree of protection (plugged-in) IP 20

For plugging into base part

Enclosure material polyamide PA 6.6

Colour grey

Ordering information

Type BXT M4 E

Part No. 920 308

Packing unit 1 pc(s).

Marking system BA1-BA15BS BA1 BA15 BXT

• For DRC MCM XT condition monitor-ing systems

• Abrasion-proof

• Pre-printed

• Transparent

2 x 165 adhesive labels for labelling DRC MCM XT monitoring devices with their bus address(BA1 to BA15) and BXT base parts or modules with consecutive numbers (1.1-1.10 to 15.1-15.10)

BS BA1 BA15 BXT

Dimension W x H 13 x 7 mm

Ordering information

Type BS BA1 BA15 BXT

Part No. 920 398

Packing unit 1 pc(s).

N E W

Page 320: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 320/382318 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

Accessories for BLITZDUCTOR® XT Ex (i)

Test / Disconnection Module920 309 BXT M4 T

B X TM 4 T920 309

• For plugging into the BLITZDUCTOR XTbase part

• Easy maintenance and troubleshooting

• Measuring lines included

1

2

3

4

Basic circuit diagram BXT M4 T Dimension drawing BXT M4 T

The plugged-in test/disconnection module interrupts the cable run of the lines connected to theBLITZDUCTOR XT base part and leads them to a test socket at the front side of the module. Thisallows to carry out measurements in the installation without removing the lines from the base part.

BXT M4 T

Max. continuous operating d.c. voltage UC 180 V

Max. continuous operating a.c. voltage UC 127 V

Nominal current at 80° C IL 1.0 A

Volume resistance 0.1 ohm

Operating temperature range -40°C ... +80°C

Degree of protection (plugged-in) IP 20

For plugging into base part

Test sockets gold-plated, 1 mm

Enclosure material polyamide PA 6.6

Colour grey

Accessories 2 measuring lines (1 m), protective bag

Ordering informationType BXT M4 T

Part No. 920 309

Packing unit 1 pc(s).

Marking system 1-50920 399 BS 1 50 BXT

B S1 5 0 B X T920 399

• Abrasion-proof

• Pre-printed Plate with 2 plate numbers from 1 to 50 for attaching to BXT base parts or modules.

BS 1 50 BXT

Dimension W x H 11 x 4 mm

Ordering information

Type BS 1 50 BXT

Part No. 920 399

Packing unit 1 pc(s).

Page 321: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 321/382319www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

Accessories for BLITZDUCTOR® XT Ex (i)

PartitionTW DRC MCM EX

• Allows non-intrinsically circuits to beplaced directly next to Ex i circuits(space gain)

• Increase of the thread measure to 50 mm in accordance with

EN 60079-11

• Suitable for mounting rails with

a height of 7.5 mm and 15 mm• Easy installation by simply snapping

the partition onto a mounting rail

137

9 0 7

6

2.5

Dimensional drawing of the partition

For DRC MCM XTCertain installation instructions have to be observed when using Blitzductor XT Ex (i) surge protectivedevices in intrinsically safe circuits.In accordance with EN 60079-11;2007 a minimum distance (thread measure) of 50 mm has to bemaintained between intrinsically and non-intrinsically safe circuits (connecting parts, e.g. terminals)!When using the Ex i partition of type TW DRC MCM EX, this distance is also maintained if the surge

protective devices are arranged directly next to one other.

TW DRC MCM EX

Material polyamide PA 6.6

Colour blue

For mounting on 35 mm DIN rail according to EN 60715

Ordering information

Type TW DRC MCM EX

Part No. 910 697

Packing unit 1 pc(s).

N E W

Page 322: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 322/382320 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

ITAK Ex (i)

Surge arrester

• Prewired unit

• Built-in SPD, tested according to ATEX and FISCO

requirements• Further customised versions available on request

Example: ITAK for use in intrinsically safe circuits.

ITAK stands for the German designation “Informationstechnik-Anschaltkasten“ [English: switchbox for information technology systems].Generally, ITAKs are a combination of enclosure, SPDs and terminals orshield terminals. These switchboxes can be produced according to cus-

tomer specifications. Our standard product range includes e.g. ITAK EXIBXT 24, a combination of ALGA 5 X enclosure and BXT BD EX 24 for pro-tecting two intrinsically safe measuring circuits in outdoor systems.

Page 323: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 323/382321www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

Accessory Part for ITAK Ex (i)

Mounting setFor ALGA 5 X enclosures for fixing at masts and pipes.

Enclosure PU PartType material pc(s). No.

MS ALGA 5 X StSt 1 906 059

906 059 MS ALGA5 X

MS ALGA 5 X MountingSet for Enclosures 906 059

ITAK Ex (i)

ITAK EXI BXTITAK EXI

• Prewired unit for 2 Ex(i) circuits

• Self-capacitance and self-inductancenegligibly small

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B - 2 and higher

1

2

3

4

The RFID chip of the LifeCheck SPD monitoringsystem can be read out without contact via

DEHNrecord LC. Insulation resistance> 500 V line-earth.

Dimension drawing ITAK EXI BXT

BXT ML4 BD EX 24 and BXT BAS EX – Completely mounted, meets FISCO requirements.

ITAK EXI BXT 24

SPD class TSPD monitoring system LifeCheck

Nominal voltage UN 24 V

Max. continuous operating d.c. voltage Uc 33 V

Max. input voltage acc. to EN 50020 Ui 30 V

Max. input current acc. EN 50020 Ii 0.5 A

Total nominal discharge current (8/20 µs) In 20 kA

Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 Up 52 V

Voltage protection level line-PG for In C2 Up 1400 V

Voltage protection level line-line at 1 kV/µs C3 Up 45 V

Voltage protection level line-PG at 1 kV/µs C3 UP 1100 V

Series impedance per line 1.0 ohm

Cut-off frequency line-line fG 7.7 MHz

Capacitance line-line C 0.8 nF

Operating temperature range -40°C...+80°C

Degree of protection IP 65

For mounting on wall in Ex zones 1, 2

Connection input/output cable gland M20 x 1.5

Cross-sectional area, solid 0.08 - 4 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Cross-sectional area of equipotential bonding 4 mm2

Tightening torque (terminal) 0.4 NmEarthing via screw terminal at enclosure panel

Enclosure material grey aluminium

Test standards for installed BXT IEC 61643-21, UL 497B

Approvals, Certifications for installed BXT ATEX, CSA

Ordering information

Type ITAK EXI BXT 24

Part No. 989 408

Packing unit 1 pc(s).

Page 324: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 324/382322 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNconnect RK Ex (i)

Terminal block with integratedsurge protection

• Extremely space-saving (only 6 mm in width)

• Spring pressure connection system

• Tested by KEMA according to ATEX and FISCOrequirements

6 mm two-pole terminal block with integrated surge protection and cageclamp terminal. Earthing via DIN rail or terminal.

DEHNconnect RK MD EX is a 6 mm terminal block with integrated surgeprotection for intrinsically safe circuits. 2 lines can be protected with the5 cage clamp spring measuring connections and additional equipotential

bonding to the terminal equipment can be established.The snap-in fixing

mechanism at the supporting foot of the base part allows the arrester tobe safely earthed via the DIN rail. As the enclosure of the arrester is opento one side to minimise the width, it is advisable to use a cover plate at

the end of each terminal block.

DCO RK MD EX with cover

application

Zones 1, 2

DEHNconnect RK EX 24

min. 4 mm2

EB

cable length max. 1m

min. 4 mm2 Zone 0

Application in an Ex(i) circuit

Page 325: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 325/382323www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNconnect RK Ex (i)

DCO RK MD EXDCO RK

919 960

• For universal use

• Self-capacitance and self-inductancenegligibly small

• For installation in conformity with thelightning protection zones concept atthe boundaries from 0B – 2 and higher

1

2

3

4

IN OUT

Low-capacitance, energy-coordinated protectivecircuit with an insulation resistance > 500 V to

earth.

Dimension drawing DCO RK MD EX

Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCOrequirements.

DCO RK MD EX 24

SPD class TNominal voltage UN 24 V

Max. continuous operating d.c. voltage Uc 33 V

Max. continuous operating a.c. voltage Uc 23 V

Max. input voltage acc. to EN 50020 Ui 30 V

Max. input current acc. to EN 50020 Ii 0.5 A

Nominal current IL 0.5 A

C2 Total nominal discharge current (8/20 µs) In 10 kA

C2 Nominal discharge current (8/20 µs) per line In 5 kA

Voltage protection level line-line for In C2 Up 50 V

Voltage protection level line-PG for In C2 Up 1500 V

Voltage protection level line-line at 1 kV/µs C3 Up 45 VVoltage protection level line-PG at 1 kV/µs C3 Up 1400 V

Series impedance per line 1.8 ohms

Cut-off frequency line-line fG 6 MHz

Capacitance line-line C 1 nF

Capacitance line-PG C 6 pF

Operating temperature range -40°C...+80°C

Degree of protection IP 00, with cover IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection input/output spring / spring

Cross-sectional area, solid 0.08 - 2.5 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Earthing via DIN rail / terminal

Enclosure material polyamide PA 6.6

Colour blue

Test standards IEC 61643-21

Ex certifications ATEX: KEMA 09ATEX0124 X: II 2 (1) G Ex ia IIC T4 ... T6

Approvals, Certifications GOST

Ordering information

Type DCO RK MD EX 24

Part No. 919 960

Packing unit 1 pc(s).

Accessory Part for DEHNconnect RK Ex (i)

Quick marking system, horizontal imprintPlate with 2 plate numbers from 1 to 50 for DCO RK,horizontal imprint

PU PartType Material pc(s). No.

BS 1 50 DCO RK plastic 1 919 977

919 977 BS 1 50DC O R K

BS 1 50 DCO RK QuickM ar ki ng Sy st em for DC OR K 9 19 977

Accessory Part for DEHNconnect RK Ex (i)

Covering plateFor DCO RK

PU PartType Enclosure material Colour pc(s). No.

AD DCO RK BL polyamide PA 6.6 blue 1 919 978

919 978 AD DCOR K B L

AD DCO RK BL CoveringPlate for DCO, blue 919 978

Page 326: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 326/382324 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNconnect RK Ex (i)

Terminal block with integratedsurge protection

EC-Type Examination Certificate for DCO RK MD EX

Page 327: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 327/382www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

325

Shield Connection on Anchor Bars

• Tested with lightning impulse currents up to10 kA (10/350 µs)

• Corrosion-resistant stainless steel material• Permanent shield connection due to spring ele-

ment

Shield connection system for anchor bars which is capable of carryinglightning currents. The yield of the cable materials used is compensatedby a slipping spring element.

Shield connection system, tested with lightning currents, for specific useon anchor bars. As, in the course of time, the conductor materials are sub- ject to a yield, this yield is compensated by a slipping spring element. Theshield connection of the rail types can also be installed using adequate

insulating elements after isolating it from local potential.

This very robust shield connectionsystem is particularly suited forcables with medium-sized diame-ters. It has been tested with light-ning currents and was approvedfor nuclear installations.

Application on anchor bars

Page 328: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 328/382326 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Anchor bar308 421 AS SAK1000 V2A

AS SAK 1000 V2A AnchorB ar ,s ta inl es ss te el, 1m lo ng 30 842 1

• Can be cut to length according torequirements

Mounting rail for earthing and fixing the shield terminals.

AS SAK 1000 V2A

Material StSt

Dimension W x L x H 29 x 1000 x 15 mm

Approvals, Certifications ETL 10/PB 301/97

Ordering information

Type AS SAK 1000 V2A

Part No. 308 421

Packing unit 10 pc(s).

Dimension drawing AS SAK 1000 V2A

Shield Connection on Anchor Bars

Shield terminals308 403 SAK 10 AS V4A308 404 SAK 14 AS V4A308 405 SAK 18 AS V4A308 406 SAK 21 AS V4A308 407 SAK 26 AS V4A308 408 SAK 33 AS V4A

SAK 10 AS V4A Shielding Term inal,stainle ss ste el, Rd 5-10 308 403SAK 14 AS V4A Shielding Term inal,stainle ss ste el, Rd 8-14 308 404SAK 18 AS V4A Shielding Term inal,s tai nle ss st ee l, Rd 13 -18 30 840 5SAK 21 AS V4A Shielding Term inal,s tai nle ss st ee l, Rd 17 -21 30 840 6SAK 26 AS V4A Shielding Term inal,s tai nle ss st ee l, Rd 19 -26 30 840 7SAK 33 AS V4A Shielding Term inal,s tai nle ss st ee l, Rd 25 -33 30 840 8

• System for anchor bars which is capa-ble of carrying lightning currents

• Shield support with large surface

• Compensates the yield of cablematerials

Dimension drawing SAK

Shield terminals for earthing cable shields on anchor bars. Suitable for lightning equipotentialbonding purposes. Allows for subsequent use without interrupting the cable shield – no toolsrequired for installation. Approved for use in nuclear facilities with TÜV test certificate ETL 10/PB301/97 (TÜV = German Technical Inspectorate).

SAK 10 AS V4A SAK 14 AS V4A SAK 18 AS V4A SAK 21 AS V4A SAK 26 AS V4A SAK 33 AS V4A

Lightning impulse current capacity (10/350 µs) 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

Clamping range Rd 5 - 10 mm 8 - 14 mm 13 - 18 mm 17 - 21 mm 19 - 26 mm 25 - 33 mm

Material StSt StSt StSt StSt StSt StSt

Spring pressure 21 - 27 N 30 - 76 N 34 - 73 N 30 - 63 N 90 - 124 N 76 - 137 N

For mounting on anchor bar anchor bar anchor bar anchor bar anchor bar anchor bar

Dimension W x L x H 16 x 40 x 48 mm 19.5 x 40 x 50 mm 24 x 40 x 56 mm 29 x 40 x 59 mm 36.5 x 40 x 74 mm 45 x 40 x 82 mm

Approvals, Certifications ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97

Ordering information

Type SAK 10 AS V4A SAK 14 AS V4A SAK 18 AS V4A SAK 21 AS V4A SAK 26 AS V4A SAK 33 AS V4A

Part No. 308 403 308 404 308 405 308 406 308 407 308 408

Packing unit 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

Page 329: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 329/382327www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Shield Connection on Anchor Bars

Insulated busbar supportST AS

Bar308 425

• Non-conductive connection of mount-ing plate and anchor bar

• Equipotential bonding via AK 16 ASSAK MS terminal

Busbar support for insulated fixing of the AS SAK 1000 V2A anchor bar, with M4 threaded socket.

ST AS SAK K

Material plastic

Approvals, Certifications ETL 10/PB 301/97

Ordering information

Type ST AS SAK K

Part No. 308 425

Packing unit 10 pc(s).

TerminalAK 16 AS

Protectivemm 308 411

• Space-saving

• 2 fixing screws for conductor includedFor connecting equipotential bonding conductors to AS SAK 1000 V2A anchor bars.

AK 16 AS SAK MS

Cross-sectional area, solid 16 mm2

For mounting on anchor bar

Approvals, Certifications ETL 10/PB 301/97

Ordering information

Type AK 16 AS SAK MS

Part No. 308 411

Packing unit 5 pc(s).

Dimension drawing ST AS SAK K

Dimension drawing AK 16 AS SAK MS

Page 330: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 330/382328 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Shield Connection on DIN Rails

• Tested with lightning impulse currents up to5 kA (10/350 µs)

• Corrosion-resistant stainless steel material• Permanent shield connection with spring ele-

ment

Shield connection system with lightning current carrying capability,partic-ularly suited for smaller cables, for DIN rails with slipping spring elementfor compensating the yield of the cable materials.

Shield connection system, tested with lightning currents, for versatileapplications in DIN rail installations. Suitable especially for smaller cablediameters such as bus cables. As, in the course of time, the conductor

materials are subject to a yield, this is compensated by a slipping springelement.The shield connection of the rail types can also be installed usingadequate insulating elements after isolating it from local potential.

Page 331: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 331/382329www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

BusbarSN 18X3

Busbar,919 016

• Can be cut to length according torequirements

• Can be mounted onto busbar supportsMounting rail for shield terminals. Can be mounted onto the busbar supports.

SN 18X3 CU 1000

Material tin-plated copper

For mounting on bar holder

Dimension W x L x H 18 x 1000 x 3 mm

Ordering information

Type SN 18X3 CU 1000

Part No. 919 016

Packing unit 1 pc(s).

Shield Connection on DIN Rails

Shield terminalsSAK 6.5

SAK 11

Shielding91 901 0Shielding919 011

• Lightning current carrying system forbusbars

• Shield support with large surface

• Compensates the yield of cable mate-rials

Dimension drawing SAK

Shield terminals for earthing cable shields on busbars (18x3). Suitable for lightning equipotentialbonding purposes. Allows for subsequent use without interruption of the cable shield – no toolsrequired for installation.

SAK 6.5 SN MS SAK 11 SN MS

Lightning impulse current capacity (10/350 µs) 5 kA 5 kA

Clamping range Rd 1.5 - 6.5 mm 5 - 11 mm

Material nickel-plated brass nickel-plated brass

Spring pressure 8 - 13 N 22 - 31 N

For mounting on SN 18x3 CU 1000 SN 18x3 CU 1000

Dimension W x L x H 10 x 25 x 40 mm 17 x 25 x 47 mm

Ordering information

Type SAK 6.5 SN MS SAK 11 SN MS

Part No. 919 010 919 011

Packing unit 10 pc(s). 10 pc(s).

Dimension drawing SN 18X3 CU 1000

Page 332: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 332/382330 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Insulated rail support919 014 SH 18X3K

SH 18X3 K BarHolder, plastic 919 014

• No conductive connection from bus-bar to DIN rail

• Equipotential bonding via AK 35 SN18X3 GG terminal Rail support for insulated installation, for DIN rail mounting or screw connection.

SH 18X3 K

Material plastic

Colour black

For mounting on DIN rail or mounting plate

Ordering information

Type SH 18X3 K

Part No. 919 014

Packing unit 10 pc(s).

Dimension drawing SH 18X3 K

Shield Connection on DIN Rails

Rail support919 012 SH1 18X3ST919 013 SH2 18X3ST

SH1 18X3 ST BarHolder, steel 919 012SH2 18X3 ST BarHolder ISO 919 013

• Extremely space-saving

• With one or two shield terminals

• For 35 mm DIN rails acc. to EN 60715Rail support for earthed construction, suitable for DIN rail mounting. Low-impedance connectionof the shield terminals to the DIN rail via the busbar.

SH1 18X3 ST SH2 18X3 ST

Version 1 shield terminal 2 shield terminals

Material tin-plated steel tin-plated steel

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715

Ordering information

Type SH1 18X3 ST SH2 18X3 ST

Part No. 919 012 919 013

Packing unit 1 pc(s). 1 pc(s).

Dimension drawing SH2 18X3 STDimension drawing SH1 18X3 ST

Page 333: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 333/382331www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Shield Connection on DIN Rails

TerminalAK 35 SN

Term inal919 015

• Wide cross-sectional area

• For insulated shield construction withSH 18X3 KParticularly suited for insulated busbar constructions, e.g. for indirect shield earthing.

AK 35 SN 18X3 GG

Cross-sectional area, solid 35 mm2

For mounting on busbar

Ordering information

Type AK 35 SN 18X3 GG

Part No. 919 015

Packing unit 1 pc(s).

Dimension drawing AK 35 SN 18X3 GG

Page 334: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 334/382332 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Shield Connection for Cables

• Tested with lightning impulse currents up to10 kA (10/350 µs)

• Extremely space-saving• Permanent shield connection with spring ele-

ment

Extremely space-saving shield connection system for use as constantforce spring. A spring element compensates the yield of the cable materi-als used.

The shields of incoming IT and power supply lines can be contacted bymeans of constant force springs of type SA KRF in a space-saving way andwith lightning current carrying capability. As, in the course of time, the

conductor materials are subject to a yield, this can be compensated by aspring element. For permanent corrosion protection of the clamping point,it is wrapped with a self-bonding SKB rubber tape.

Test certificate for constant force spring of type SA KRF ...

Page 335: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 335/382333www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Shield Connection for Cables

Constant force springSA KRF

SA KRF

SA KRF

SA KRF

SA KRF

SA KRF

SA KRF

SA KRF

Contactne ct io n 9 19 0 31

Contactne ct io n 9 19 0 32

Contactne ct io n 9 19 0 33

Contactne ct io n 9 19 0 34

Contactne ct io n 9 19 0 35

Contactne ct io n 9 19 0 36

Contactne ct io n 9 19 0 37

Contactne ct io n 9 19 0 38

• For solderless connection of a con-ductor to the shield

• For use with all plastic and lead-sheathed cables

• Also suitable for steel-reinforcedlead-sheathed cables

Constant force springs allow solderless shield connections for equipotential bonding or lightningequipotential bonding. They can be installed subsequently without interrupting the conductorshield or requiring tools for installation. Approved for nuclear installations according to TÜVCertificate No. T12-04-ETL003 (TÜV = German Technical Inspectorate).

SA KRF ... 10 V2A 15 V2A 22 V2A 29 V2A 37 V2A 50 V2A 70 V2A 94 V2A

Lightning impulse currentcapacity (10/350 µs)

10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA

Clamping range Rd 4 - 10 mm 9 - 15 mm 14 - 22 mm 18.5 - 29 mm 23.5 - 37 mm 31 - 50 mm 44 - 70 mm 58 - 94 mm

Material StSt StSt StSt StSt StSt StSt StSt StSt

Colour bare bare bare bare bare bare bare bare

For mounting on cable shield cable shield cable shield cable shield cable shield cable shield cable shield cable shield

Approvals, Certifications T12-04-ETL 003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003

Ordering information

Type SA KRF 10 V2A SA KRF 15 V2A SA KRF 22 V2A SA KRF 29 V2A SA KRF 37 V2A SA KRF 50 V2A SA KRF 70 V2A SA KRF 94 V2A

Part No. 919 031 919 032 919 033 919 034 919 035 919 036 919 037 919 038

Packing unit 20 pc(s). 20 pc(s). 20 pc(s). 10 pc(s). 10 pc(s). 25 pc(s). 20 pc(s). 10 pc(s).

Self-bonding rubber tapeSKB 19

919 030

• Self-bonding

• Flexible

Roll with 9 m self-bonding rubber tape forwrapping around constant force springs forpermanent corrosion protection.

SKB 19 9M SW

Colour black

Dimension W x L x H tape: 9 m x 19 mm

Ordering information

Type SKB 19 9M SWPart No. 919 030

Packing unit 1 pc(s).

Page 336: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 336/382334 www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Enclosure / Protective Conductor Terminal

Aluminium enclosure906 055 ALGA 5

AL G A5A lu mi niu mE nc lo sur eI P6 5 9 06 05 5

• DIN rail integrated

• Different types available on request

Dimension drawing of aluminium enclosure

For installing DIN rail mounted devices. With2 brass glands PG 11.

ALGA 5

Degree of protection IP 65

For mounting on wallDimension W x H x D 100 x 200 x 81 mm

Installation space 6 mods.

Enclosure material aluminium

Ordering information

Type ALGA 5

Part No. 906 055

Packing unit 1 pc(s).

Aluminium enclosure for Ex(i) surge arresters906 058 ALGA 5 X

ALGA5 XA lu mi ni um En cl os ur e IP 65 fo rB CT 9 06 05 8

• DIN rail integrated

• All cables entering from below

Dimension drawing of aluminium enclosure forEx(i) surge arresters

With 4 plastic glands M20 x 1.5, sealable,pressure compensating membrane.

ALGA 5 X

Degree of protection IP 65

For mounting on wall

Dimension W x H x D 160 x 100 x 85 mm

Installation space 6 mods., DIN 43880

Enclosure material aluminium

Ordering information

Type ALGA 5 X

Part No. 906 058

Packing unit 1 pc(s).

Page 337: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 337/382335www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Enclosure / Protective Conductor Terminal

Mounting setMS ALGA

Mount ing906 059

• Stainless steel

• For rough environmental conditions

For ALGA 5 X enclosures for fixing at mastsand pipes.

MS ALGA 5 X

For mounting on mast, pipe for diameters 25 - 140 mm

Enclosure material StSt

Ordering information

Type MS ALGA 5 X

Part No. 906 059

Packing unit 1 pc(s).

Protective conductor terminalSLK 16

PE910 099

• With lightning current carrying capa-bility

Dimension drawing of protective conductor terminal

For installing DIN rail mounted devices. Forearthing DIN rails, width: 12 mm.

SLK 16

Cross-sectional area, flexible 6 - 16 mm2

Cross-sectional area, solid 6 - 25 mm2

For mounting on DIN rail acc. to EN 60715

Enclosure material green-yellow polyamide 6.6

Ordering informationType SLK 16

Part No. 910 099

Packing unit 1 pc(s).

Page 338: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 338/382336 www.dehn.de

Page 339: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 339/382

INFORMATION TECHNOLOGY SYSTEMS

COMBINED ADAPTERS

337www.dehn.de

DEHNprotector

Surge arrester

• Surge protective adapter with a modern designfor quick retrofitting

• Easy integration of the power supply and dataside of a terminal device into equipotentialbonding

Combined surge protective adapter for plugging into earthed socket out-lets, with visual operating state and fault indication.

The SPDs of the Protector family for plugging into earthed socket outletsprotect consumers with additional data interfaces. Surges will be dischar-ged via the PE pin of the socket outlet. The plug-in installation makes

retrofitting of SPDs easier. The surge protection of the power supply sideprovides a visual operating state and fault indicator to facilitate mainten-ance.

P R O

T E C T O R

TAE/Fsocket outletearth contact

telephonesystems

orrouter

NTBAor

splitter

TAE/F

Application of DPRO 230 NT

P R O

T E C T O R

ISDNfax / telephone

ISDN S0RJ 45

socket outlet withearth contact

Application of DPRO 230 ISDN

P R O

T E C T O

R

PCLAN

socket outlet withearth contact

Application of DPRO 230 LAN100

P R O

T E C T O

R

TV

TV

socket outlet withearth contact

Application of DPRO 230 TV

NoteFor further types of surge protective adapters for protecting the mainssupply of electronic devices please also refer to pages 138 – 140.

Page 340: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 340/382

INFORMATION TECHNOLOGY SYSTEMS

COMBINED ADAPTERS

338 www.dehn.de

DEHNprotector

DPRO 230 TV909 300 DPRO 230

TV

DPRO230TV

909 300

• Protection for TV or radio applicati-ons with a modern design

• Adapter for F sockets to IEC terminalsincluded

• For installation in conformity with thelightning protection zones concept at

the boundaries from 2 – 3 and higher

Protection for the data side:A gas discharge tube

discharges potential surges to PE.

Dimension drawing DPRO TV

Combined surge protection for power andantenna sides of TV, radio or video systems.With visual operating state and fault indica-tion.

Protection for the data side DPRO 230 TV / DPRO 230 SE TV

SPD class BMax. continuous operating d.c. voltage UC 60 V

C2 Nominal discharge current (8/20 µs) line-shield (PE) In 5 kA

Voltage protection level line-shield (PE) at 1 kV/µs C3 Up 600 VInsertion loss 0-2400 MHz 1.5 dB

Operating temperature range -25°C...+40°C

Degree of protection IP 20

Connection input / output F socket / F socket

Earthing via protective conductor connection

Enclosure material thermoplastic, UL 94 V-2

Colour pure white

Test standards IEC 61643-21

Protection for the power side DPRO 230 TV / DPRO 230 SE TV

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage Uc 255 V

Nominal load current IL 16 A

Nominal discharge current (8/20 µs) L-N In 3 kA

Nominal discharge current (8/20 µs) L/N-PE In 5 kA [(L+N)-PE]

Combined impulse (1.2/50 µs - 8/20 µs) L-N Uoc 6 kV

Combined impulse (1.2/50 µs - 8/20 µs) L/N-PE Uoc 10 kV [(L+N)-PE]

Voltage protection level L-N Up 1.25 kV

Voltage protection level L/N-PE Up 1.5 kV

Response time L-N tA 25 ns

Response time L/N-PE tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short-circuit withstand capabilityfor max. mains-side overcurrent protection 6 kArms a.c.

Temporary overvoltage (TOV) L-N UT 335 V/5 sec

Temporary overvoltage (TOV) L/N-PE (1) UT 400 V/5 sec

Temporary overvoltage (TOV) L/N-PE (2) UT 1200 V+U0 /200 ms

Fault indication red light

Operating state indication green light

For mounting on plug-in system with centre earthing contact system

earth contact according to CEE 7,

DIN 49440/DIN 49441 standard sheet V

Test standards IEC 61643-11

Ordering information

Type DPRO 230 TV DPRO 230 SE TVPart No. 909 300 909 305

Packing unit 1 pc(s). 1 pc(s).

N/L

PE

L/N

PE

red

greenL'/N'

N'/L'

Page 341: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 341/382

INFORMATION TECHNOLOGY SYSTEMS

COMBINED ADAPTERS

339www.dehn.de

DEHNprotector

DPRO 230 NTDPRO 230

• Protection for a telecommunicationterminal device with a modern design

• Includes accessories, suitable for RJ11/12 and TAE connections

• For installation in conformity with thelightning protection zones concept at

the boundaries from 2 – 3 and higher

2’

5’

2

5

N/L

PE

L/N

PE

red

green

L'/N'

N'/L'

3

4

3’

4’

Protection for the data side:Also suitable for

digital interfaces due to low-capacitance circuitdesign

Dimension drawing DPRO NT

Combined surge protection for power anddata sides of a digital network termination(NT). Also suitable for telephones and faxmachines. With visual operating state andfault indication.

Protection for the data side DPRO 230 NT / DPRO 230 SE NT

SPD class RMax. continuous operating d.c. voltage UC 180 V

C2 Nominal discharge current (8/20 µs) per line C2 I n 2.5 kA

Voltage protection level line-line for In C2 Up 300 VVoltage protection level line-PE for In C2 Up 500 V

Voltage protection level line-line at 1 kV/µs C3 Up 300 V

Voltage protection level line-PE at 1 kV/µs C3 Up 500 V

Cut-off frequency line-line fG 50 MHz

Operating temperature range -25°C...+40°C

Degree of protection IP 20

Connection input / output RJ12 socket / RJ12 socket

Pinning 3/4

Earthing via protective conductor connection

Enclosure material thermoplastic, UL 94 V-2

Colour pure white

Test standards IEC 61643-21Protection for the power side DPRO 230 NT / DPRO 230 SE NT

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage Uc 255 V

Nominal load current IL 16 A

Nominal discharge current (8/20 µs) L-N In 3 kA

Nominal discharge current (8/20 µs) L/N-PE In 5 kA [(L+N)-PE]

Combined impulse (1.2/50 µs - 8/20 µs) L-N Uoc 6 kV

Combined impulse (1.2/50 µs - 8/20 µs) L/N-PE Uoc 10 kV [(L+N)-PE]

Voltage protection level L-N Up 1.25 kV

Voltage protection level L/N-PE Up 1.5 kVResponse time L-N tA 25 ns

Response time L/N-PE tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short-circuit withstand capability

for max. mains-side overcurrent protection 6 kArms a.c.

Temporary overvoltage (TOV) L-N UT 335 V/5 sec

Temporary overvoltage (TOV) L/N-PE (1) UT 400 V/5 sec

Temporary overvoltage (TOV) L/N-PE (2) UT 1200 V+U0 /200 ms

Fault indication red light

Operating state indication green light

For mounting on plug-in system with centre earthing contact system

earth contact according to CEE 7,

DIN 49440/DIN 49441 standard sheet V

Test standards IEC 61643-11

Ordering information

Type DPRO 230 NT DPRO 230 SE NT

Part No. 909 310 909 315

Packing unit 1 pc(s). 1 pc(s).

Page 342: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 342/382

INFORMATION TECHNOLOGY SYSTEMS

COMBINED ADAPTERS

340 www.dehn.de

DEHNprotector

DPRO 230 ISDN909 320 DPRO 230

ISDN

DPRO230ISDN

909 320

• Protection of ISDN or Ethernet appli-cations with a modern design

• Shielded patch cable (1.5 m) included

• For installation in conformity with thelightning protection zones concept atthe boundaries from 2 – 3 and hig-

her

N/L

PE

L/N

PE

red

green

L'/N'

N'/L'

1

2

5

4

3

6

1’

2’

5’

4’

3’

6’

Protection of the data side: Low-capacitance4-wire protective circuit for ISDN and

Ethernet pin assignment.

Dimension drawing DPRO ISDN

Combined surge protection for the powerand ISDN S0 side of ISDN systems and devi-ces. Shielded port allows for protection of Ethernet 10 BT. With visual operating stateand fault indication.

Protection for the data side DPRO 230 ISDN / DPRO 230 SE ISDN

SPD class QMax. continuous operating d.c. voltage UC 48 V

C2 Nominal discharge current (8/20 µs) line-line In 120 A

C2 Nominal discharge current (8/20 µs) line-PE In 2.5 kAC2 Total nominal discharge current (8/20 µs) In 10 kA

Voltage protection level line-line for In C2 Up 100 V

Voltage protection level line-PE for In C2 Up 500 V

Voltage protection level line-line at 1 kV/µs C3 Up 80 V

Voltage protection level line-PE at 1 kV/µs C3 Up 500 V

Cut-off frequency line-line fG 50 MHz

Operating temperature range -25°C...+40°C

Degree of protection IP 20

Connection input / output RJ45 shielded socket / RJ45 shielded socket

Pinning 1(5)/2(4), 3/6

Earthing via protective conductor connection

Enclosure material thermoplastic, UL 94 V-2Colour pure white

Test standards IEC 61643-21

Protection for the power side DPRO 230 ISDN / DPRO 230 SE ISDN

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage Uc 255 V

Nominal load current IL 16 A

Nominal discharge current (8/20 µs) L-N In 3 kA

Nominal discharge current (8/20 µs) L/N-PE In 5 kA [(L+N)-PE]

Combined impulse (1.2/50 µs - 8/20 µs) L-N Uoc 6 kV

Combined impulse (1.2/50 µs - 8/20 µs) L/N-PE Uoc 10 kV [(L+N)-PE]Voltage protection level L-N Up 1.25 kV

Voltage protection level L/N-PE Up 1.5 kV

Response time L-N tA 25 ns

Response time L/N-PE tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short-circuit withstand capability

for max. mains-side overcurrent protection 6 kArms a.c.

Temporary overvoltage (TOV) L-N UT 335 V/5 sec

Temporary overvoltage (TOV) L/N-PE (1) UT 400 V/5 sec

Temporary overvoltage (TOV) L/N-PE (2) UT 1200 V+U0 /200 ms

Fault indication red light

Operating state indication green light

For mounting on plug-in system with centre earthing contact system

earth contact according to CEE 7,

DIN 49440/DIN 49441 standard sheet V

Test standards IEC 61643-11

Ordering information

Type DPRO 230 ISDN DPRO 230 SE ISDN

Part No. 909 320 909 325

Packing unit 1 pc(s). 1 pc(s).

Page 343: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 343/382

INFORMATION TECHNOLOGY SYSTEMS

COMBINED ADAPTERS

341www.dehn.de

DEHNprotector

DPRO 230 LAN100DPRO 230 LAN100

• Protection of Ethernet applications(1000 BASE-T) with an elegant design

• Shielded Cat 5e patch cable (1.5 m)included

• For installation in conformity with thelightning protection zones concept at

the boundaries from 2 – 3 and higher

N/L

PE

L/N

PE

red

green

L'/N'

N'/L'

1

2

3

6

4

5

7

8

1'

2'

3'

6'

4'

5'7'

8'

Data side: Low-capacitance protective circuit of all pairs for Ethernet pin assignment

Dimension drawing DPRO LAN100

Combined surge protection for the powerside and data input for the protection of LANcomponents.Meets the requirements for Channel Class Din accordance with EN 50173 and is thussuitable for 1000Base-T (Gigabit Ethernet).

Protection for the data side DPRO 230 LAN100 / DPRO 230 SE LAN100

SPD class QMax. continuous operating d.c. voltage UC 58 V

C2 Nominal discharge current (8/20 µs) line-line In 30 A

C2 Nominal discharge current (8/20 µs) line-PE In 2.5 kAC2 Total nominal discharge current (8/20 µs) In 10 kA

Voltage protection level line-line for In C2 Up 100 V

Voltage protection level line-PE for In C2 Up 500 V

Voltage protection level line-line at 1 kV/µs C3 Up 90 V

Voltage protection level line-PE at 1 kV/µs C3 Up 500 V

Operating temperature range -20°C...+40°C

Degree of protection IP 20

Connection input / output RJ45 shielded socket / RJ45 shielded socket

Pinning 1/2, 3/6, 4/5, 7/8

Earthing via protective conductor connection

Enclosure material thermoplastic, UL 94 V-2

Colour pure whiteTest standards IEC 61643-21

Protection for the power side DPRO 230 LAN100 / DPRO 230 SE LAN100

SPD according to EN 61643-11 Type 3

SPD according to IEC 61643-1 Class III

Nominal a.c. voltage UN 230 V

Max. continuous operating a.c. voltage Uc 255 V

Nominal load current IL 16 A

Nominal discharge current (8/20 µs) L-N In 3 kA

Nominal discharge current (8/20 µs) L/N-PE In 5 kA [(L+N)-PE]

Combined impulse (1.2/50 µs - 8/20 µs) L-N Uoc 6 kV

Combined impulse (1.2/50 µs - 8/20 µs) L/N-PE Uoc 10 kV [(L+N)-PE]

Voltage protection level L-N Up 1.25 kVVoltage protection level L/N-PE Up 1.5 kV

Response time L-N tA 25 ns

Response time L/N-PE tA 100 ns

Max. mains-side overcurrent protection 16 A gL/gG or B 16 A

Short-circuit withstand capability

for max. mains-side overcurrent protection 6 kArms a.c.

Temporary overvoltage (TOV) L-N UT 335 V/5 sec

Temporary overvoltage (TOV) L/N-PE (1) UT 400 V/5 sec

Temporary overvoltage (TOV) L/N-PE (2) UT 1200 V+U0 /200 ms

Fault indication red light

Operating state indication green light

For mounting on plug-in system with centre earthing contact system

earth contact according to CEE 7,

DIN 49440/DIN 49441 standard sheet V

Test standards IEC 61643-11

Ordering information

Type DPRO 230 LAN100 DPRO 230 SE LAN100

Part No. 909 321 909 326

Packing unit 1 pc(s). 1 pc(s).

N E W

Page 344: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 344/382342 www.dehn.de

Page 345: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 345/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

343www.dehn.de

For lightning equipotential bonding according to IEC 62305 as well as foruse in IT installations according to IEC 60364-5-54.

• For indirect connection/earthing of functionallyisolated installation components when beingaffected by lightning

• For lightning equipotential bonding applicationaccording to IEC 62305

• With corrosion-resistant stainless steel connec-tions

• For mounting inside of buildings, outdoors, indamp rooms as well as for underground instal-lation

• Extremely heavy-duty devices

TFS: High-capacity isolating spark gap

KFSU: Isolating spark gap

Isolating Spark Gap

For lightning equipotential bonding

TFS / KFSU

TFSKFSU

Isolat ing923 023Ex-923 021

Basic circuit diagram TFS / KFSUDimension drawing TFS / KFSU

TFS / KFSU: Isolating spark gaps with plastic coating and 2 connections (Rd 10 mm) made of stain-less steel

TFS KFSU

Lightning impulse current (10/350 µs) Iimp 100 kA —Class of lightning current carrying capability acc. to EN 50164-3 H —

Nominal discharge current (8/20 µs) In 100 kA 100 kA

Rated power-frequency withstand voltage (50 Hz) UW/AC 300 V 300 V

100% Lightning impulse sparkover voltage Urimp 4 kV 4 kV

Power frequency sparkover voltage (50 Hz) Uaw 2.5 kV 2.5 kV

Operating temperature range TU -20°C...+80°C -20°C...+80°C

Degree of protection IP 65 IP 65

Length 160 mm 160 mm

Diameter of enclosure 43 mm 43 mm

Enclosure material steel-plastic coating steel-plastic coating

Connection Rd 10 mm Rd 10 mm

Material (connection) stainless steel stainless steel

Ordering information

Type TFS KFSU

Part No. 923 023 923 021

Packing unit 1 pc(s). 1 pc(s).

Page 346: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 346/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

344 www.dehn.de

EXFS 100 / EXFS 100 KU

For explosion-hazard areas

• For indirect connection/earthing of functionallyisolated installation components when beingaffected by lightning

• Device for lightning equipotential bondingaccording to IEC 62305 in explosion-hazardareas

• For bridging insulating pieces, insulatingflanges etc. in cathodically corrosion-protectedpipe sections

• For safe installation in explosion protected zone1 (gas) or 21 (dust)

• Especially low sparkover voltage

• Especially high a.c. current withstand capability

EXFS 100: Isolating spark gap for use in explosion-hazard areas with plastic coating and M10 connecting thread nut

EXFS 100 KU: Isolating spark gap for use in explosion-hazard areas with 2 m connecting cable for underground installation

ATEX-certified isolating spark gap for lightning equipotential bondingaccording to IEC 62305 with low sparkover voltage

The Ex isolating spark gaps of the EXFS 100 / EXFS 100 KU product fam-ily are used when conductive installation components situated in explo-

sion-hazard areas cannot be connected directly with each other.The spark gaps with low sparkover voltage are especially efficient for iso-lated installation components with little insulation resistance.No special regulations have to be observed for safe application in zone 1with gases or zone 21 with dusts.With a maximum lightning impulse current of 100 kA (10/350 µs), EXFS100 and EXFS 100 KU meet class H according to EN 50164-3 ”LightningProtection Components (LPC) – Part 3: Requirements for isolating sparkgaps”.The ATEX-certified spark gaps EXFS 100 and EXFS 100 KU provideapproved safety according to harmonised European standards.For connecting EXFS 100 spark gaps, prewired connecting cables with dif-ferent lengths are available as accessories.Flat and angled connection brackets (IF) make it easier to connect thespark gaps to pipe flanges.EXFS 100 KU types are enclosed by a damp-proof plastic coating and cantherefore be ideally used for underground installation at insulating cou-plings.

Type examination certificate

Page 347: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 347/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

345www.dehn.de

EXFS 100 / EXFS 100 KU

EXFS 100EXFS 100

Installation of EXFS 100Dimension drawing EXFS 100

EXFS 100: Ex isolating spark gap with plastic coating and M10 connecting thread nuts

EXFS 100

Lightning impulse current (10/350 µs) Iimp 100 kA

Class of lightning current carrying capability acc. to EN 50164-3 H

Nominal discharge current (8/20 µs) In 100 kA

Rated power-frequency withstand voltage (50 Hz) UW/AC 250 V

100% Lightning impulse sparkover voltage Urimp 1.25 kV

Power-frequency sparkover voltage (50 Hz) Uaw 0.5 kV

Rated discharge current (50 Hz) Imax 500 A / 0.5 sec. (TU: 45°C)

(Ex) marking acc. to EN 60079 (gases) II 2G Ex d IIC T6

(Ex) marking according to EN 61241 (dusts) II 2D Ex tD A21 IP67 T 80°C

Operating temperature range TU -20°C...+60°C

Degree of protection IP 67

Approvals, Certifications BVS 06 ATEX E 099, IECEx KEM 09.0051...

Length of enclosure 100 mm

Diameter of enclosure 45,5 mm

Enclosure material plastic coating

Connection of enclosure thread nut M10, 2x M10x25 mm, 2x spring washer

Ordering information

Type EXFS 100

Part No. 923 100

Packing unit 1 pc(s).

Accessory Part for EXFS 100 / EXFS 100 KU

Pair of angled connection brackets – IF 1 –

Pair of angled connection brackets for EXFS ...; diameter corre-sponds to bolt diameter of the bolted flange joint (d1 up to max.60 mm, please indicate the diameter required when placingyour order)

PU PartType Material pc(s). No.

IF1 St/tZn 1 923 011

923 011

C on ne ct io nB ra ck et Ty pe IF - SE T- 9 23 01 1

Pair of flat connection brackets – IF 3 –

Pair of flat connection brackets for EXFS ...; diameter corre-sponds to bolt diameter of the bolted flange joint (d1 up to max.60 mm, please indicated the diameter required when placing

your order)PU Part

Type Material pc(s). No.

IF3 St/tZn 1 923 016

923 016

C on ne ct io nB ra ck et T yp eI F- SE T- 9 23 01 6

Accessory Part for EXFS 100 / EXFS 100 KU

EXFS 100: Connecting cable, Cu 25 mm2

Connecting cable for EXFS 100; 2 cable lugs Ø10.5 mm, hexa-gon screw and nut (M10), StSt and spring washer

Cable lug C ross Cable PU PartType material section length pc(s). No.

AL EXFS L100 KS Cu/gal Sn 25 mm2 100 mm 1 923 025

AL EXFS L200 KS Cu/gal Sn 25 mm2 200 mm 1 923 035

AL EXFS L300 KS Cu/gal Sn 25 mm2 300 mm 1 923 045

923 025 AL EXFSL100KS923 035 AL EXFSL200KS923 045 AL EXFSL300KS

AL E X FSL 1 0 0 K S923 025AL E X FSL 2 0 0 K S923 035AL E X FSL 3 0 0 K S923 045

Page 348: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 348/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

346 www.dehn.de

EXFS 100 / EXFS 100 KU

EXFS 100 KU923 101 EXFS 100KU

EXFS100KU923 101

insulating piece/Isolierstück

isolating spark gap/Funkenstrecke

insulation / Isolierung

Installation of EXFS 100 KU Dimension drawing EXFS 100 KU

EXFS 100 KU: Ex isolating spark gap with connecting cable for aboveground and undergroundinstallation

EXFS 100 KU

Lightning impulse current (10/350 µs) I imp 100 kA

Class of lightning current carrying capability acc. to EN 50164-3 H

Nominal discharge current (8/20 µs) In 100 kA

Rated power-frequency withstand voltage (50 Hz) UW/AC 250 V

100% Lightning impulse sparkover voltage Urimp 1.25 kV

Power-frequency sparkover voltage (50 Hz) Uaw 0.5 kV

Rated discharge current (50 Hz) Imax 500 A / 0.5 sec. (TU: 45°C)

(Ex) marking acc. to EN 60079 (gases) II 2G Ex d IIC T6

(Ex) marking according to EN 61241 (dusts) II 2D Ex tD A21 IP67 T 80°C

Operating temperature range TU -20°C...+60°C

Degree of protection IP 67

Approvals, Certifications BVS 06 ATEX E 099, IECEx KEM 09.0051...

Length of enclosure 123 mm

Diameter of enclosure 34 mm

Enclosure material plastic coating; water-proof coating

Connection of enclosure NYY-J-1x25 mm2, approx. 2 m long

Ordering information

Type EXFS 100 KU

Part No. 923 101

Packing unit 1 pc(s).

Page 349: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 349/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

347www.dehn.de

ATEX-certified isolating spark gap for lightning equipotential bondingaccording to IEC 62305, approved device with flexible conductor connec-tion

• For indirect connection/earthing of functionallyisolated installation components when beingaffected by lightning

• Device for lightning equipotential bonding acc.to IEC 62305 in explosion-hazard areas (Zone 2)

• According to ”ATEX Directive” 94/9/EC

• Corrosion-resistant zinc diecasting enclosurewith plastic cover and flexible conductor con-nection

• For bridging insulating pieces, insulatingflanges etc. in cathodically corrosion protectedpipe sections

• Extremely heavy-duty device

EXFS L ...: Isolating spark gap for use in explosion-hazard areas with flexible connecting cable

EXFS KU: Isolating spark gap for use in explosion-hazard areas with 1.5 m connecting cable for underground installation

EXFS L / EXFS KU

For use in explosion-hazard areas

Ex isolating spark gaps of the EXFS L / EXFS KU product family are usedwhen the direct interconnection of electrically conductive installationcomponents in Ex areas is not applicable. As, for example, in case of cathodically corrosion protected pipeline sections.ATEX-certified EXFS L and EXFS KU spark gaps provide approved and test-ed safety in accordance with harmonised European standards.The arc-resistant tungsten-copper electrodes ensure a long service life of the Ex spark gaps.The approved type EXFS L with flexible conductor connection quicklyadapts to any application environment. The prewired spark gaps provideconnecting cables with different lengths with cable lugs, screws and M10nut. The flat or angled connection brackets (IF), which are available as

accessories, allow for easy connection of the spark gap to pipelineflanges.The EXFS KU type is enclosed in a damp-proof PVC enclosure and is idealfor underground installation at insulating couplings.

Page 350: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 350/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

348 www.dehn.de

EXFS L100 EXFS L200 EXFS L300

Lightning impulse current (10/350 µs) I imp 50 kA 50 kA 50 kA

Class of lightning current carrying capability acc. to EN 50164-3 N N N

Nominal discharge current (8/20 µs) In 100 kA 100 kA 100 kA

Rated power-frequency withstand voltage (50 Hz) UW/AC 300 V 300 V 300 V

100% Lightning impulse sparkover voltage Urimp 2.5 kV 2.5 kV 2.5 kV

Power frequency sparkover voltage (50 Hz) Uaw 1.2 kV 1.2 kV 1.2 kV

Type of protection acc. to EN 50014, EN 50021 II 3 G EEx nC II T4 II 3 G EEx nC II T4 II 3 G EEx nC II T4

Operating temperature range TU -20°C...+80°C -20°C...+80°C -20°C...+80°C

Degree of protection IP 54 IP 54 IP 54

Approvals, Certifications ZELM 03 ATEX 3192X ZELM 03 ATEX 3192X ZELM 03 ATEX 3192X

Length of enclosure 90 mm 90 mm 90 mm

Diameter of enclosure 63 mm 63 mm 63 mm

Enclosure material zinc diecasting, plastic zinc diecasting, plastic zinc diecasting, plastic

Connecting cable H01N2-D 25 mm2 with cable lug and screw/nut (M10)

Cable length 100 mm 200 mm 300 mm

Suitable for flange size 20-130 mm 120-230 mm 220-320 mm

Ordering information

Type EXFS L100 EXFS L200 EXFS L300

Part No. 923 060 923 061 923 062

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

EXFS L / EXFS KU

EXFS L923 060 EXFSL100923 061 EXFSL200923 062 EXFSL300

EXFS L100 Ex-Isolating Spark Gap 923 060EXFS L200 Ex-Isolating Spark Gap 923 061EXFS L300 Ex-Isolating Spark Gap 923 062

lmax = 300 mm(avoid loopswhere possible)

Dimension drawing EXFS

EXFS L ...: Ex isolating spark gap for aboveground installation

Installation of EXFS

Accessory Part for EXFS L / EXFS KU

Pair of angled connection brackets – IF 1 –

Pair of angled connection brackets for EXFS ...; diameter corre-sponds to bolt diameter of the bolted flange joint (d1 up to max.60 mm, please indicate the diameter required when placingyour order)

PU PartType Material pc(s). No.

IF1 St/tZn 1 923 011

923 011

C on ne ct io nB ra ck et Ty pe IF - SE T- 9 23 01 1

Accessory Part for EXFS L / EXFS KU

Pair of flat connection brackets – IF 3 –

Pair of flat connection brackets for EXFS ...; diameter corre-sponds to bolt diameter of the bolted flange joint (d1 up to max.60 mm, please indicated the diameter required when placingyour order)

PU PartType Material pc(s). No.

IF3 St/tZn 1 923 016

923 016

C on ne ct io nB ra ck et T yp eI F- SE T- 9 23 01 6

Page 351: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 351/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

349www.dehn.de

EXFS L / EXFS KU

EXFS KUEXFS KU

Ex-923 019

Dimension drawing EXFS KU

EXFS KU: Ex isolating spark gap with connecting cables for abovegroundand underground installation

EXFS KU

Lightning impulse current (10/350 µs) Iimp 50 kA

Class of lightning current carrying capability acc. to EN 50164-3 N

Nominal discharge current (8/20 µs) In 100 kA

Rated power-frequency withstand voltage (50 Hz) UW/AC 300 V

100% Lightning impulse sparkover voltage Urimp 2.5 kV

Power frequency sparkover voltage (50 Hz) Uaw 1.2 kV

Type of protection acc. to EN 50014, EN 50021 II 3 G EEx nC II T4

Operating temperature range TU -20°C...+80°C

Degree of protection IP 67

Approvals, Certifications ZELM 03 ATEX 3192X

Length of enclosure 90 mm

Diameter of enclosure 63 mm

Enclosure material zinc diecasting, plastic

Connecting cable NYY-J-1x25 mm2

Cable length 2 x approx. 1500 mm

Ordering information

Type EXFS KU

Part No. 923 019

Packing unit 1 pc(s).

Page 352: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 352/382

LIGHTNING EQUIPOTENTIAL BONDING

350 www.dehn.de

Pipe Clamp for Explosion Hazard Areas

For fixing at pipes in explosion hazard areas

• For use in explosion hazard areas Ex zones 1and 2 (gases, vapours, fogs) as well as Ex zones21 and 22 (dusts)

• Tested for explosion group IIB

• Time-saving installation – deactivation of thesystem/areas for welding or drilling work notnecessary

Pipe clamp for explosion hazard areas from Ø26.9 mm(¬”) to Ø88.9 mm (3”); Ø88.9 mm (3”) to 300 mm andfrom Ø300 to 500 mm.

Separate clamping body for endless tightening strap (PartNo. 540 901) from Ø26.9 mm (¬”) to 500 mm.

Pipe clamp for electrical contacting of pipes in explosion hazard areas, for

implementing of lightning equipotential bonding according to EN 62305-3(VDE 0185-305-3)

So far, the method of choice for implementing equipotential bonding andlightning equipotential bonding terminals in explosion hazard areas hasbeen welding or threaded bushings. Using pipe clamps was only permit-ted if there was proof of ignition spark immunity in case of lightning cur-rent loading. DEHN + SÖHNE has now provided evidence of ignition sparkabsence for a pipe clamp at lightning current loading. By realising the testaccording to EN 50164-1 (VDE 0185-201): Requirements for connectioncomponents (clamps and connectors) in a potentially explosive atmos-phere, absence of ignition sparks was proved for the test sample with alightning current carrying capability up to 50 kA (10/350 µs). The designof this novel pipe clamp for explosion risk areas not only provides a safeelectrical contact by means of two contact clips, but also the mechanicalfixing by an electrically insulated clamping body.

The Ex pipe clamp can be connected by

– round conductor, Cu, St/tZn,Al, StSt with Ø8/10 mm or flexible / strand-ed copper conductors, cross section 16-35 mm2

, with E-Cu crimpedcable lug (DIN 46235)

– flat copper conductor with minimum dimension 20x2.5 mm and aØ10.5 mm bore hole

c:\dokume~1\drb\lokale~1\temp\xpgrpwise\herstellererklärung bandrohrschelle ex-bereiche upd ate ausführung klein und groß engl. .docPage 1

DECLARATION OF MANUFACTURER

Product: Pipe clamp for explosive zones

Product description: Part No. 540 821Part No. 540 801Part No. 540 803Part No. 540 805Part No. 540 810

Manufacturer: DEHN + SÖHNE GmbH + Co.KG.Hans-Dehn-Str. 192318 Neumarkt i.d.OPf., Germany

Application:

The pipe clamp for explosive zones is used for connecting pipes of different materials anddiameters to the lightning equipotential bonding structure in explosive atmospheres.

Lightning currents are discharged without formation of sparks as specified in the technicaldata sheet.

We herewith confirm that the pipe clamp for explosive zones is suitable for the use in explo-sive zones 1 and 2 (gas, vapour, mist) and explosive zones 21 and 22 (combustible dust) inconnection with the installation instructions, P

not legally admissi-ble and not necessary with respect to explosion protection.

Neumarkt i.d.OPf., 12 Okt. 2009Dr.-Ing. Ralph BrockeDirector R&D

Attached to a StSt pipe

Page 353: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 353/382

LIGHTNING EQUIPOTENTIAL BONDING

351www.dehn.de

Pipe Clamp for Explosion Hazard Areas

Ex Pipe Clamp for Ø6 mm to 26.9 mmEX BRS

Type EX BRS 27 clamping range from Ø6 mmto 26.9 mm (¬”)

EX BRS 27

Lightning impulse current (10/350 µs) for Cu Iimp 10 kA-> Ø6-12 mm I 20 kA-> Ø12-26.9 mm (¬’’) I 25 kA-> Ø26.9 mm (¬’’)

Lightning impulse current (10/350 µs) for St/tZn Iimp 25 kA-> Ø17.2-26.9 mm (¬’’)

Lightning impulse current (10/350 µs) for StSt Iimp 10 kA-> Ø6-12 mm I 12 kA-> Ø12-26.9 mm (¬’’) I 25 kA-> Ø26.9 mm (¬’’)

Clamping range Ø6 - 26.9 mm (¬’’)

Dimension tensioning strap (l1 x w x d) 190x10x0.25 mm

Clamping body material polyamide

Grip head/strap material StSt

Contact angle material Ms/gal Sn

Ordering information

Type EX BRS 27

Part No. 540 821

Packing unit 1 pc(s).

Ex Pipe Clamp for Ø26.9 mm to 500 mm

Type EX BRS 90, Part No. 540 801, clampingrange from Ø26.9 mm (¬”) to 88.9 mm (3”)

Type EX BRS 300, Part No. 540 803, clampingrange from Ø88.9 mm (3”) to 300 mm and

Type EX BRS 500, Part No. 540 805, clamping

range from Ø300 to 500 mm

EX BRS 90 EX BRS 300 EX BRS 500

Lightning impulse current (10/350 µs) for Cu Iimp 50 kA 50 kA 50 kA

Lightning impulse current (10/350 µs) for St/tZn Iimp 50 kA 50 kA 50 kA

Lightning impulse current (10/350 µs) for StSt Iimp 25 kA 50 kA 50 kA

Class of lightning current carrying capability acc. to DIN EN 50164-1 N N N

Clamping range Ø26.9 (¬”) - 88.9 mm (3”) Ø88.9 (3”) - 300 mm Ø300 - 500 mm

Dimension tensioning strap (l1 x w x d) 410x25x0.3 mm 1100x25x0.3 mm 1850x25x0.3 mm

Clamping body material polyamide polyamide polyamide

Grip head/strap material StSt StSt StSt

Contact angle material Cu/gal Sn Cu/gal Sn Cu/gal Sn

Ordering information

Type EX BRS 90 EX BRS 300 EX BRS 500

Part No. 540 801 540 803 540 805

Packing unit 1 pc(s). 1 pc(s). 1 pc(s).

N E W

Page 354: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 354/382

LIGHTNING PROTECTION

TECHNOLOGY SYSTEMS

352 www.dehn.de

Pipe Clamp for Explosion Hazard Areas

Separate clamping body for endless tightening strap540 810

540 810

Separate clamping body with endless strap (PartNo. 540 901)Clamping ranges from Ø26.9 mm (¬”) to 500 mm

Lightning impulse current (10/350 µs) for Cu Iimp 50 kA

Lightning impulse current (10/350 µs) for St/tZn Iimp 50 kA

Lightning impulse current (10/350 µs) for StSt Iimp 25 kA

Class of lightning current carrying capability acc. to DIN EN 50164-1 N

Clamping range Ø26.9 mm (¬”) - 500 mm

Clamping body material polyamide

Grip head/strap material StSt

Contact angle material Cu/gal Sn

Ordering information

Part No. 540 810

Packing unit 1 pc(s).

Accessory Part for Pipe Clamp for Explosion Hazard Areas

Tensioning strap

Endless tensioning strap (100 m long)Strap dimension PU Part

Material (l x w x d) pc(s). No.

StSt (V2A) ... x 25 x 0.3 mm 1 540 901

540 901

540 901

Page 355: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 355/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

353www.dehn.de

SDS

Voltage Limiting Device

• Electrical isolation of insulated track sectionsand earthed parts of installations

• Safe equipotential bonding in case of a shortcircuit or earth fault at the overhead contactline due to high-current-resistant welding ofthe electrodes

• Discharge of surges without formation of shortcircuits due to lightning-resistant SDS ... volt-age limiting device

• Short-circuit withstand capability 25 kArms /100 ms; 36 kArms / 75 ms

SDS ...: Cylindrical SDS spark gap unit for insertion into rail adapter Siemens No. 8WL6503-xx

DIN EN 50122-1 describes the use of voltage limiting devices for d.c. anda.c. railways for so-called ”open earthing of railways” for live compo-nents of overhead contact lines and current collectors.In order to prevent the occurrence of hazardous surges between the insu-

lated tracks or track sections of electrical railways and earthed parts of the installation, voltage limiting devices (SDS ...) are used.

Their function is to connect parts of the installation in overhead contactlines and current collectors permanently to the return circuit, as soon asthe threshold voltage is exceeded.

In case of atmospheric overvoltages, the lightning-resistant SDS ...voltagelimiting device is capable of returning to its initial state after dischargingthe impulse current. Only if the specified lightning current loads areexceeded, a permanent short circuit is initiated by heavy-current-resistantwelding of the electrodes and the fuse link has to be replaced.

The SDS voltage limiting device consists of a spark gap unit and therespective connecting kit for direct connection to the rail or overhead con-tact line tower.

The spark gap unit type SDS 1, Part No. 923 110, developed by DEHN +SÖHNE, has also been approved by the German Federal Railway Authority(EBA).

SDS spark gap unit for use with rail adapter, Siemens No. 8WL6503-xx

mostly unnecessary

Page 356: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 356/382

LIGHTNING EQUIPOTENTIAL BONDING

ISOLATING SPARK GAPS

354 www.dehn.de

SDS

SDS ...923 110 SDS 1

SDS1Sicherungseinsatz SDS 1 923 110

Basic circuit diagram SDS ... Dimension drawing SDS ...

SDS 1 SDS 2 SDS 3 SDS 4 SDS 5

Power frequency sparkover voltage Uaw 940 V –– –– –– ––

d.c. sparkover voltage Uag 600 V +/- 20 % 350 V +/- 20 % 550 V 230 V +/- 20 % 120 V +/- 20 %

Impulse sparkover voltage 1400 V (1 kV/µs) 900 V (1 kV/µs) 1000 V (1 kV/µs) 650 V (1 kV/µs) 600 V (1 kV/µs)

Self-extinguishing capability 300 A / 65 V –– –– –– ––

Lightning current discharge capacity

(10/350 µs) 0.1x / 0.5x / 1x 5 kA 2 kA 2.5 kA 2.5 kA 2 kA

Lightning current withstand capability (10/350 µs) 25 kA 25 kA 25 kA 25 kA 25 kA

Impulse current discharge capacity

(8/20 µs) 0.1x / 0.5x / 1x –– –– –– 20 kA 20 kA

Safe short circuit due to welding of the

electrodes for alternating currents @ 100 ms 1.5 kA / 1000 V / 100 ms –– –– –– ––

Safe short circuit due to welding of the

electrodes for alternating currents @ 30 ms 2.5 kA / 1000 V / 30 ms –– –– –– ––

Safe short circuit due to welding of the

electrodes for direct currents 750 A / 250 ms 600 A / 250 ms –– 600 A / 250 ms 600 A / 250 ms

Short circuit withstand capability 25 kArms / 100 ms; 25 kArms / 100 ms; 25 kArms / 100 ms; 25 kArms / 100 ms; 25 kArms / 100 ms;

36 kArms / 75 ms 36 kArms / 75 ms –– 36 kArms / 75 ms 36 kArms / 75 ms

Long-term current 1 kArms for t 120 s 1 kArms for t 120 s –– 1 kArms for t 120 s 1 kArms for t 120 s

Leakage current Ilc < 1 µA for 100 V d.c. < 1 µA for 100 V d.c. –– < 1 µA for 100 V d.c. < 1 µA for 100 V d.c.

Operating temperature range TU -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C

For mounting on allows for installation into voltage breakdown protector/SIEMENS rail adapter No. 8WL6503-xx

Tightening torque of the fuse link

in the busbar adapter 15 Nm 15 Nm 15 Nm 15 Nm 15 Nm

Approvals, Certifications EBA –– –– –– ––

DB Drawing No. 4 Ebs 15.13.20 Sheet 2 –– –– –– ––

Ordering information

Type SDS 1 SDS 2 SDS 3 SDS 4 SDS 5

Part No. 923 110 923 117 923 116 923 118 923 119

Packing unit 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

Page 357: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 357/382

LIGHTNING EQUIPOTENTIAL BONDING

355www.dehn.de

Equipotential Bonding

Equipotential Bonding Bars

Accessories / Construction Kit

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, whichcan be requested from Export Department.

Equipotential busbar K12,with snap-on terminals

For equipotential bonding according to DIN VDE 0100 Part410/540 and the lightning equipotential bonding according toEN 62305-3 (VDE 0185-305-3)

Type K12 with 12 contact studs:

10 terminals for Rd 2.5 – 95 mm2 or Rd 10 mm conductorsand 1 terminal for Fl -30x4 mm conductors

Contact Cross PU PartType bar section pc(s). No.

PAS 11AK Cu/gal Sn 30 mm2 1 563 200

563 200 PAS 11AK

PAS 11AK EarthingBusbar 563 200

Type K12 with 12 contact studs, UV-stabilised:

10 terminals for Rd 2.5 – 95 mm2 or Rd 10 mm conductorsand 1 terminal for Fl –30x4 mm

Contact Cross PU PartType bar section pc(s). No.

PAS 11AK UV Cu/gal Sn 30 mm2 1 563 201

563 201 PAS 11AKUV

PAS11AKUV563 201

Accessories –Snap-on Terminal for Fl 40 Conductors

PU PartType pc(s). No.

AK FL40 PAS 50 563 222

563 222 AK FL40PAS

AK FL40 PAS Terminalfor Fl 40 563 222

Equipotential Bonding Bar MS

For equipotential bonding

Connections for:

7 Rd conductors Rd 2.5 – 16 mm2

1 Rd conductor 7 – 10 mm1 Fl conductor –30x3.5 mm or Rd conductor 8 – 10 mmContact Cross PU Part

Type bar section pc(s). No.

PAS 9AK Ms 50 mm2 1 563 050

563 050 PAS 9AK

PAS 9AK EarthingBusbar 563 050

Equipotential Bonding Bars R15,with Terminal Block System

For main equipotential bonding according to DIN VDE 0100 Part410/540 and lightning equipotential bonding according to EN62305-3 (DIN VDE 0185-305-3)

Type A:

7 terminal blocks 2.5 – 25 mm2

2 terminal blocks 16 – 95 mm2 or Rd 8 – 10 mm1 terminal block Fl -30x4 mm

Clamping Cross PU PartType bar section pc(s). No.

PAS 10RK Ms/gal Sn 100 mm2 1 563 010

563 010

563 010

Type B:

5 terminal blocks 2.5 – 25 mm2

3 terminal blocks 16 – 95 mm2 or Rd 8 – 10 mm1 terminal block Fl –30x4 mmClamping Cross PU Part

Type bar section pc(s). No.

PAS 9RK Ms/gal Sn 100 mm2 1 563 020

563 020

563 020

Type C:

13 terminal blocks 2.5 – 25 mm2

1 terminal block 16 – 95 mm2 or Rd 8 – 10 mmClamping Cross PU Part

Type bar section pc(s). No.

PAS 14RK Ms/gal Sn 100 mm2 1 563 030

563 030

563 030

Terminal Block2.5 to 25 mm2

PU PartType Material Connection Modules pc (s). No.

RK 16 PAS St/gal Zn 2.5-25 mm2 1 200 563 011

563 011 RK 16

PAS

RK 16 PAS ModularTerminal,-16mm for EB 563 011

Terminal Block

Up to 95 mm2 or Rd 8-10 mmPU Part

Type Material Connection Modules pc (s). No.

RK 95 PAS St/gal Zn 16-95 mm2 2 100 563 013

563 013

563 013

Terminal Block

Flat conductor 30 mm

PU PartType Material Connection Modules pc (s). No.

RK FL30 PAS St/gal Zn -30x4 mm 4 25 563 012

563 012 RK FL30PAS

RK FL30 PAS ModularT er mi na l, fl at st ri p- 30 mm fo rE B 5 63 01 2

Terminal Block

Flat conductor 40 mmPU Part

Type Material Connection Modules pc(s ). No.

RK FL40 PAS St/gal Zn -40x5 mm 5 25 563 019

563 019 RK FL40PAS

RK FL40 PAS ModularT er mi na l, fl at st ri p- 40 mm fo rE B 5 63 01 9

Cover

to snap on / to be labelled

PU PartType Material Modules pc(s). No.

AH PAS RK Plastic 15 10 563 015

563 015 AH PASRK

AH PAS RK Plastic

cover, grey 563 015

Bar Frame

Fixing PU PartType Material holes pc(s). No.

SB PAS RK Plastic 6x4 mm 50 563 014

563 014 SB PASRK

SB PAS RK Bar hol-der, plast ic, grey 563 014

Clamping BarPU Part

Type Material Length Modules pc(s). No.

KS 198 PAS Ms/gal Sn 198 mm 15 10 563 016

KS 398 PAS Ms/gal Sn 398 mm 30 10 563 017

KS 798 PAS Ms/gal Sn 798 mm 60 10 563 018

563 016 KS 198PAS563 017 KS 398PAS563 018 KS 798PAS

KS 198 PAS Term inalBar, brass, 198 mm long 563 016KS 398 PAS Term inalbar, brass, 398 mm long 563 017KS 798 PAS Term inalbar, brass, 798 mm long 563 018

Equipotential Bonding Busbar,with miniature terminal block system

Miniature unit: For surface mounting without coverClamping Cross PU Part

Type bar Connection section pc(s). No.

PAS 6RK OH Ms/gal Sn 6 x 2.5-25 mm2 100 mm2 10 563 105

563 105 PAS 6RKOH

PAS 6RK OH EarthingBusbar 563 105

Page 358: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 358/382

Equipotential Bonding LIGHTNING EQUIPOTENTIAL BONDING

356 www.dehn.de

Equipotential Bonding Barsfor industial use

Earthing Busbars

Equipotential Bonding Busbar for industrial useFor main equipotential bonding according to DIN VDE 0100 Part410/540 and lightning equipotential bonding according to EN62305-3 (DIN VDE 0185-305-3)

Also for use in hazardous zones (screws protected against self-loosening)

6 connections with insulatorsDimension Cross PU Part

Type Material (l x w x d) section pc(s). No.

PAS I 6AP M10 CU Cu 295x40x5 mm 200 mm2 1 472 207

PAS I 6AP M10 V2A StSt 295x40x6 mm 240 mm2 1 472 209

472 207 PAS I 6APM10CU

472 209 PAS I 6APM10 V2A

PAS I 6AP M10 CU EarthingBusbar 472 207PAS I6AP M10 V2A EarthingBusbar 472 209

8 connections with insulatorsDimension Cross PU Part

Type Material (l x w x d) section pc(s). No.

PAS I 8AP M10 CU Cu 365x40x5 mm 200 mm2 1 472 227PAS I 8AP M10 V2A StSt 365x40x6 mm 240 mm2 1 472 229

472 227 PAS I 8APM10CU472 229 PAS I 8APM10 V2A

PAS I 8AP M10 CU EarthingBusbar 472 227PAS I8AP M10 V2A EarthingBusbar 472 229

10 connections with insulatorsDimension Cross PU Part

Type Material (l x w x d) section pc(s). No.

PAS I 10AP M10 CU Cu 435x40x5 mm 200 mm2 1 472 217

PAS I 10AP M10 V2A StSt 435x40x6 mm 240 mm2 1 472 219

472 217 PAS I10APM10CU472 219 PAS I10APM10 V2A

PAS I10AP M10 CU EarthingBusbar 472 217PAS I10AP M10 V2A EarthingBusbar 472 219

12 connections with insulatorsDimension Cross PU Part

Type Material (l x w x d) section pc(s). No.

PAS I 12AP M10 CU Cu 505x40x5 mm 200 mm2 1 472 237

PAS I 12AP M10 V2A StSt 505x40x6 mm 240 mm2 1 472 239

472 237 PAS I12APM10CU472 239 PAS I12APM10 V2A

P ASI 1 2 AP M 1 0 C U472 237PASI12AP M10 V2A472 239

Accessories – Insulator for EBB (Industry)

Material Terminal PU PartType Isolator thread pc(s). No.

IS PAS M10 UP (thermoset) M10 1 472 210

472 210 IS PASM10

IS PAS M10 Isolatorfür PAS Industr ie 472 210

Accessories – Fixing Set for EBB (Industry)

Screw Screw Plastic PU PartType material type dowel pc(s). No.

BS M10 PAS St/ tZn 45 mmc M10x20 mm Ø12x60 mm 1 472 201

472 201 BS M10PAS

BS M10 PAS Fixing Setfor EB 472 201

Accessories – Cover for EBB (Industry)

Covers for EBB with insulatorsMaterial EBB Dimension PU Part

Type screw/nut type (l x w x d) pc(s). No.

AD PAS 6AP V2A StSt 6 connections 301x60x0.8 mm 1 472 279

AD PAS 8AP V2A StSt 8 connections 371x60x0.8 mm 1 472 269

AD PAS 10AP V2A StSt 10 connections 441x60x0.8 mm 1 472 289

AD PAS 12AP V2A StSt 12 connections 511x60x0.8 mm 1 472 299

472 279 AD PAS6APV2A472 269 AD PAS8APV2A472 289 AD PAS10APV2A472 299 AD PAS12APV2A

AD PAS 6AP V2A CoverNIRO, for 6-pole EB 472 279AD PAS 8AP V2A CoverNIRO, for 8-pole EB 472 269AD PAS 10AP V2A CoverNIRO, for 10-pole EB 472 289AD PAS 12AP V2A CoverNIRO, for 12-pole EB 472 299

Earthing BusbarsTo be screwed or welded to steel structures

Borehole distance 50 mm

2x2 connectionsDimension Cross PU Part

Type Material (l x w x d) section pc(s). No.

ES 2X2AP 10 ST St/tZn 196x60x4 mm 240 mm2 1 472 023

ES 2X2AP 10 V2A StSt 196x60x5 mm 300 mm2 1 472 109

472 023 ES 2X2AP1 0 ST

472 109 ES 2X2AP10 V2A

ES2X2AP10Stk.472 023ES2X2AP10V2A472 109

2x3 connectionsDimension Cross PU Part

Type Material (l x w x d) section pc(s). No.

ES 2X3AP 10 ST St/tZn 242x60x4 mm 240 mm2 1 472 022

ES 2X3AP 10 V2A StSt 242x60x5 mm 300 mm2 1 472 119

472 022 ES 2X3AP1 0 ST472 119 ES 2X3AP10 V2A

ES2X3AP10Stk.472 022ES2X3AP10V2A472 119

2x4 connectionsDimension Cross PU Part

Type Material (l x w x d) section pc(s). No.

ES 2X4AP ST St/tZn 293x60x4 mm 240 mm2 1 472 024

ES 2X4AP 10 V2A StSt 293x60x5 mm 300 mm2 1 472 129

472 024 ES 2X4APST472 129 ES 2X4AP10 V2A

ES2X4APStk.472 024ES2X4AP10V2A472 129

2x6 connectionsDimension Cross PU Part

Type Material (l x w x d) section pc(s). No.

ES 2X6AP 10 ST St/tZn 393x60x4 mm 240 mm2 1 472 021

ES 2X6AP 10 V2A StSt 393x60x5 mm 300 mm2 1 472 139

472 021 ES 2X6AP1 0 ST472 139 ES 2X6AP10 V2A

ES2X6AP10Stk.472 021ES2X6AP10V2A472 139

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, whichcan be requested from Export Department.

Page 359: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 359/38235 7www.dehn.de

LIGHTNING EQUIPOTENTIAL BONDING Equipot ent ial Bonding

Connect ing Clamps Componentsfor ring equipotential bonding

Connecting Clamp, for reinforcementsFor connecting reinforced concrete mats or reinforcements toround and flat conductors

For T, cross and parall el connection s

Clamping range PU PartType M aterial Rd / Rd Rd / Fl Fl / Fl pc(s). No.

VK A UNI ST St /t Zn (+ ) 6-10 / (+ ) 6-10 / (II) 30 / 50 308 025

6-10 m m 30 m m 30 mm

308 025 VK A UNIST

VK A UNI Stk.Co nne cti on Cl am p St/tZn 3 08 025

Connecting Clamp, for Foundation EarthElectrodes

For connecting round and f lat conductors in the concrete foun-dation

For T, cross and parallel connections, no threading of the con-

ductors requiredClamping range mm PU Part

Type M at erial Rd / Fl Fl / Fl pc(s). No.

VK EH R10 F30 ST St /t Zn (+ ) 10 / 30 (+ /II) 30 / 30 25 308 120

VK EH R1 0 F3 0 V 2A St St (+ ) 1 0 / 3 0 (+ / II ) 3 0 / 3 0 2 5 308 129

308 120 VK EHR10 F30 ST308 129 VK EHR10 F30 V2A

VK EH R10 F30 Stk.Co nne cti on Cl am p St/tZn 3 08 120VK EH R10 F30 V2AC on ne ct io n C la mp St St (V 2A ) 3 08 12 9

For T, cross and parall el connection s

Clamping range PU PartType M at erial Rd / Fl Fl / Fl pc(s). No.

VK A UNI V2 ST St /t Zn (+ ) 6-10 / (+ / II) 30 / 25 308 026

30 m m 30 m m

308 026 VK A UNIV2 ST

VK A UNI V2 Stk.Co nne cti on Cl am p St/tZn 3 08 026

For T and cross connectio nsClamping range PU Part

Type M aterial Rd / Fl pc(s). No.

VK A R2 2 F40 STBL St /ba re (+ ) 6 -2 2 / 4 0 m m 2 5 308 030

308 030 VK A R22F40 STBL

VK A R22 F40 STBLCo nne cti on Cl am p St/b are 3 08 030

M AXI M V Clamp for T, cross and parallel connections

Part No. 308 040 wit h UL certification

Clamping range PU PartType M at erial Rd/Rd pc(s). No.

M MVK R16 R25 ST St /tZn (+ /II) 8-16 / 15-25 mm 20 308 041

M M VK R1 6 R2 5 STBL St /b are (+ /II) 8-1 6 / 15 -2 5 m m 2 0 308 040

308 041 M M VKR16 R25 ST308 040 M M VKR16 R25 STBL

M M VK R16 R25 Stk . M AXI M Vt erm ina l, St /ba re 308 041M M VK R16 R25 STBL M AX I M Vt erm ina l, St /tZn 308 040

Strip Holder, with t hrust padFor wall mounting

Thrust pad with M8 screw for strip conductor up to 11 mm andround conductor 6-10 mm.

11 mm distance from the wall

M aterial M at erial PU PartType CH screw pc(s). No.

FBH 6 ST St /t Zn StSt 25 277 230

FBH 6 CU Cu StSt 25 277 237

FBH 6 V2A StSt StSt 25 277 239

277 230277 237

277 239

277 230

277 237

277 239

Terminal Clamp

For universal connection to the ring equipotential bonding forSt/t Zn, copper or stainless steel (StSt)

CH Cross-sect ional PU PartType M at erial Rd / Fl area pc(s). No.

A K RPA V 2A St St 8 -1 0 / 3 -1 1x 30 m m 2 .5 -9 5 m m2 50 563 169

563 169 AK RPAV2A

AK RPA V2A563 169

15 mm distance from the wall

M aterial M at erial PU PartType CH screw pc(s). No.

FBH 11 ST St /t Zn StSt 25 277 240

277 240

TapeC on du ct or sw it h P re ss ur e P la te 2 77 2 40

Componentsfor foundation earthing electrodes

Spacer

Reinforced angled type

Support Support PU PartType M aterial Fl Rd pc(s). No.

AH FE RF V G St /t Zn 40 m m 8-10 m m 25 290 001

290 001 AH FE RFV G

A H FE RF V G DistanceH o ld e r S t/ tZ n, re i nf . v er si o n 3 0 0 m m 2 9 0 0 0 1

Spacer

Straight type

Support Support PU PartType M aterial Fl Rd pc(s). No.

AH FE RF St /t Zn 40 m m 8-10 m m 50 290 002

290 002 AH FE RF

A H FE RF DistanceH ol de r S t/ tZ n, DI N 48 83 3 A, 2 80 m m 2 90 0 02

Expansion Strap for Foundation Earth Electrodes

For leading the fou ndation earth electrode in extended founda-tions (several sections) through the expansion or isolating

jo in ts. Thus no need to lea d th e e art h ele ctr od e o ut of th e b aseplate.

St rap Dimension Block PU Partmat erial (l x w x d) mat erial pc(s). No.

StSt (V2A) approx. 700x30x(4x1) mm styrene 1 308 150

308 150

308 150

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, w hich

can be requested from Export Department.

Page 360: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 360/382358 www.dehn.de

Page 361: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 361/382

MEASURING AND TEST DEVICES

359www.dehn.de

Condition Monitoring System LifeCheck®

• Maximum protection and availability of sys-tems by means of permanent condition moni-toring of LifeCheck-equipped SPDs

• The early detection system already detectsarrester overload and warns of imminent fail-ure of the arrester

– Visual indication of faulty or previously dam-aged SPDs

– Compact dimensions and minimum wiring

– Monitoring of up to 10 SPDs (40 signal lines)

– Remote signalling contact

– Remote signalling also via RS 485 interfaceand PC software

Example of use of the DEHNrecord condition monitoring system.

Condition Monitoring:

The DRC MCM XT condition monitoring system is a compact DIN railmounted device for monitoring the condition of up to 10 pre-programmedBXT arresters with integrated LifeCheck monitoring circuit.

ntegrated into the SPD modules, LifeCheck permanently monitors the

proper condition of the SPD and acts like an early warning system,detect-ing imminent electrical or thermal overload of the protection components.The LifeCheck status can be read out within a matter of seconds via con-tactless RFID technology by means of the portable DEHNrecord LC deviceand also shows the date of the last test of the SPD module. Stationaryinstalled, the condition monitoring system supports condition-basedmaintenance of 10 BXT.

The unit acts like an early warning system, generating a fault messageeven in case of imminent arrester overload, indicates it by means of theintegrated three-colour LED and transmits it to one of the two integratedremote signalling contacts. Failure of the monitoring unit, e.g. due to avoltage breakdown, is also indicated via the remote signalling contact.The Show function integrated into the DRC MCM system allows to detect

previously damaged SPDs in the monitoring group.

If several condition monitoring systems are used in one switchgear cabi-net, these systems are connected via the integrated RS 485 interfaces tosynchronise the monitoring cycles. Up to 15 DRC MCM systems can beconnected to the RS 485 bus. Thus, up to 150 BLITZDUCTORs or 300 pairscan be monitored simultaneously with minimum wiring effort.

The ”Status Display and Service Console” PC software

is an optional user software for the DRC MCM XT condition monitoringsystem which indicates the status of the SPDs and addresses LifeCheck-equipped BLITZDUCTOR modules.The software can be installed on a standard PC using an RS485/USB inter-face converter of type ”USB-NANO 485” which is available as accessory.

The software can be downloaded free of charge fromwww.dehn.de/download/ or is available as CD for a nominal fee.

Graphical status indication of DRC MCM XT monitoring devicesand of all programmed protection modules assigned to them.

The Service functions allow to switch to the ”Service Console”function complex. The protection modules can be easily addressed,

tested and reset due to the user-friendly user interface.

Page 362: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 362/382

MEASURING AND TEST DEVICES

360 www.dehn.de

Condition Monitoring System LifeCheck®

DRC MCM XT910 695 DRCM CM XT

DR CM CM XT910 695

• Monitoring the condition of Life-Check-equipped SPDs

• Permanent monitoring of up to10 SPDs (40 signal lines)

• Minimum wiring effort

• Optional remote signalling via RS 485or remote signalling contacts

The DRC MCM XT Status Display software allowsPC-aided remote indication of the status of all

SPDs monitored.

The Service Console offers various service func-tions, e.g. SPDs can be parameterised or reset

by means of the address data.

DIN rail mounted device with integrated LifeCheck sensor for monitoring the condition of max. 10LifeCheck-equipped ”BLITZDUCTOR XT” devices. Visual three-coloured SPD operating state indica-tion combined with remote signalling function (break or make contact). The free ”Status Displayand Service Console” software can be optionally used via an RS 485 interface converter.

DRC MCM XT

For testing up to 10 BLITZDUCTOR XT ML devices

up to 10 BLITZDUCTOR XT ML EX devices; for use in non-hazardous atmospheres only! Observe thread measure!

Operating elements multiway button, DIP switch

Indicator element 3-coloured LED (green, orange, red)

Input d.c. voltage range UIN 18...48 V

Max. nominal current input IIN 100 mA

RFID transmission frequency 125 kHz

Message: Replacing of SPD recommended LED, remote signalling contact (break and make contact)

Test cycle continuous

Operating temperature range for monitoring 10 BXT devices -20°C...+60°C

Operating temperature range for monitoring 8 BXT devices -40°C...+80°CDegree of protection IP 20

For mounting on 35 mm DIN rail acc. to EN 60715

Connection type screw

Cross-sectional area, solid 0.08 - 4 mm2

Cross-sectional area, flexible 0.08 - 2.5 mm2

Tightening torque (terminal) 0.4 Nm

Enclosure material polyamide PA 6.6

Colour grey

Test standards EN 61010-1, 61000-6-2/4

Type of remote signalling contact make (no) and break contact (nc)

Switching capacity d.c. 350 V/0.12 A

Switching capacity a.c. 250 V/0.07 A

Delivery includes base part, monitoring module, quick guide and marking system

Ordering information

Type DRC MCM XT

Part No. 910 695

Packing unit 1 pc(s).

Accessory Part for Condition Monitoring System LifeCheck®

USB interface converter of type USB NANO 485USB NANO 485 converts signals between USB and RS-485.The interface conver-ter is specifically designed for 2-wire RS-485 buses. LEDs indicate operation (yel-low), Rx (green) and Tx (red).

USB NANO 485 is ideally suited for use with notebooks due to its small size.Stationary use is also possible.

PU PartType pc(s). No.

USB NANO 485 1 910 486

910 486 USBNANO485

USBNANO485910 486

Accessory Part for Condition Monitoring System LifeCheck®

Marking system BA1-BA152 x 165 adhesive labels for labelling DRC MCM XT monito-ring devices with their bus address (BA1 to BA15) and BXTbase parts or modules with consecutive numbers (1.1-1.10

to 15.1-15.10)PU Part

Type pc(s). No.

BS BA1 BA15 BXT 1 920 398

920 398 BS BA1BA15BXT

B SB A1 B A1 5 B XT920 398

Page 363: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 363/382

MEASURING AND TEST DEVICES

361www.dehn.de

LifeCheck® SPD Test Device

• A higher degree of protection and availability isachieved by preventive maintenance.

– The LifeCheck monitoring device detectsthermal or electrical overload of all compo-nents.

– To avoid imminent failure and thus systemdowntime, the SPD module should bereplaced as soon as possible.

• This type of SPD testing has the following ben-efits:

– Very easy and within a matter of seconds

– Module does not have to be removed duringsystem operation

– Detection of thermal or electrical overload ofall components

Preventive maintenance:

When using this maintenance strategy, SPDs are tested and measured at

regular intervals. The SPDs are assessed according to certain criteria and,if required, replaced.

In the past, this was very time consuming, expensive and required down-time of the system.For some years, SPDs with LifeCheck feature have been available whichallow to determine the status of the SPD via RFID technology. A monitor-ing circuit with a transponder in the SPD permanently monitors the pro-tective circuit for impermissible overload due to thermal overheating orelectrical impulse currents.

Information is read out via a hand-held tester. This tester incorporates thereader, an RFID reader unit.It contactlessly transmits electromagnetic energy to the transponder in

the SPD, reads out the status and displays it. Information is simple: "SPDOK" or "Replace SPD!". This test is carried out easily within a matter of seconds and without removing the SPD.The test can be carried out at anytime without interruption as it does not interrupt signal transmission.

This type of monitoring reliably detects thermal and electrical overload of all components, generally before the SPD fails and the availability of thesystem to be protected is limited. In addition, no expertise is required fortesting. The reader also facilitates documentation of the test results,which is mandatory in compliance with the EN 62305-3 standard.The test data (date, time, results) of all SPDs are saved and can be trans-mitted to a PC for printing or storage via USB interface. Thus a higher

degree of protection and availability is achieved by means of preventivemaintenance with LifeCheck as it already detects overload of componentsbefore the protection of the system circuit fails.

SPD

indicationof operating

state

i d e n t i f i c a t i o n

I C

reader IC micro-controller

power communication

energy

data

Transponder (SPD) Reader (test device)

Principle of operation of the LifeCheck diagnostic system

DIN EN 62305-3, supplement 3 (see table excerpt) specifies maintenancetests and intervals of a lightning protection systems. However, these spec-ifications are only normative minimum requirements.

Protection Visual Complete Complete inspection

level inspection inspection of critical systems

I and II 1 year 2 years 1 year

III and IV 2 years 4 years 1 year

It makes no sense to inspect SPDs for information technology systemsvisually since the status of the devices is generally not visible. For this pur-pose, another method has to be selected as is the case for completeinspections. In the past, measurement equipment was used to test SPDs.These measurements were very time consuming, required expertise andthe measurements did not provide sufficient information.

Page 364: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 364/382

MEASURING AND TEST DEVICES

362 www.dehn.de

LifeCheck® SPD Test Device

DRC LC M3+910 653 DRC LC M3+

DR CLCM 3 +910 653

• Fast testing of LifeCheck-equippedSPDs

• Hand-held device, easy transport andoperation

• With database function for documen-tation

• Easy and fast parameterisation of

SPDs for condition monitoring withLifeCheck

The database function allows easy documentationof the test results on the PC

Snap-on LifeCheck sensor

Portable device with LifeCheck sensor for flexible use. For fast and easy testing of LifeCheck-equipped arresters. Visual and acoustic indication. With additional USB connection and databasesoftware for PC-aided management of test objects and documentation of the test results. DRC LCM3+ features a new snap-on LifeCheck sensor, allowing to test the SPD without holding the sen-sor. The handheld device allows parameterisation of SPDs for condition monitoring.

DRC LC M3+

For testing BLITZDUCTOR XT ML

BLITZDUCTOR XT ML EX; for use in non-hazardous atmospheres only!

Voltage supply (included in delivery) Li-ion battery

RFID transmission frequency 125 kHz

Measured value indication beep and LCD

Testing period typically 3 to 10 sec.

Operating temperature range -10°C...+65°C

Battery test automatic switch-off in case of flat battery

Cable length to LifeCheck sensor approx. 1000 mm

Dimensions of LifeCheck sensor 90 x 51 x 12 mm

Dimensions of handheld device 166 x 95 x 30 mm

Delivery includes handheld device, LifeCheck sensor BXT, charging device, USB cable,

test module for reference, software CD, storage case

Dimensions of storage case 340 x 275 x 83 mm

Ordering information

Type DRC LC M3+

Part No. 910 653

Packing unit 1 pc(s).

Accessory Part for LifeCheck® SPD Test Device

LifeCheck Sensor for DRC BXT / BCTLifeCheck sensor and test module for use as spare part / extension forportable LifeCheck test devices.

PU PartType Testing of pc(s). No.

LCS DRC BXT BLITZDUCTOR XT ML 1 910 652

LCS DRC BCT BLITZDUCTOR CT MLC 1 910 654

910 652 LCS DRCBXT910 654 LCS DRCBCT

LCS DRC BXT LifeCheck-Sensor für DRC BXT 910 652LCS DRC BCT LifeCheck-Sensor für DRC BCT 910 654

N E W

N E W

Page 365: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 365/382

MEASURING AND TEST DEVICES

363www.dehn.de

SPD Test Device

• For routine tests of surge protective devices

• Compact dimensions

• Suitable for mains and battery operation

• Low-battery indicator

• Test cables included in delivery

• Test adapter included as accessory part,protected against accidental contact

For testing the sparkover voltage of surge arresters.The sample to be test-ed is connected via the included test cables or special test adapters.

The PM 20 SPD test device with integrated sparkover detection allows totest Yellow/Line or Red/Line surge arresters with integrated varistor, Zenerdiode or gas discharge tube. Both the response performance between theconnections of the SPDs as well as the continuity can be tested. Theresults can be compared to reference values. In case of deviations, the SPDor SPD module has to be replaced. Test adapters with a correspondingsupport make testing of the SPD modules easier.

Scope of the delivery of PM20 SPD test device

Page 366: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 366/382

MEASURING AND TEST DEVICES

364 www.dehn.de

SPD Test Device

PM 20910 511 PM 20

PM 20910 511

• Combined testing of protective cir-cuits with gas discharge tubes, varis-tors and zener diodes

• Easy handling and flexible use

• For use with PA BXT and PA DRL testadapters

Combined device for testing the sparkover voltage of surge arresters (with gas dischargetubes/varistors/zener diodes). Storage bag and measuring accessories included.

PM 20

Nominal d.c. voltage UN 8-12 V d.c.

Test parameter: Test voltage max. 1250 V d.c.

Test parameter:Test current (reference voltage) 1 mA d.c., constant

Measured value indication alphanumeric, 8-digit LCD display

Test output sockets safety pole terminals (4 mm), positive pole: red colour, negative pole: black colour

Testing period ≤ 1.5 sec.

Number of individual tests during battery operation typically 2000

Accessories included in delivery 2 test cables, each 1 m long, 2 safety tapping test clips, 1 plug-in power supply unit (230 V a.c.), 1 storage bag

Dimension of storage bag 300x 110 x 110 mm

Ordering information

Type PM 20

Part No. 910 511

Packing unit 1 pc(s).

Accessory Part for SPD Test Device

PA DRL test adapterFor connecting to PM 10 / PM 20 and for plugging in and testing SPDmodules

PU PartType Plug-in SPD modules pc(s). No.

PA DRL DEHNrapid LSA and DPL 1 910 507

910 507 PA DRL

P ADR L910 507

Accessory Part for SPD Test Device

PA BXT test adapterFor connecting to PM 10 / PM 20 and for plugging in and testing SPDmodules

PU PartType Plug-in SPD modules pc(s). No.

PA BXT BLITZDUCTOR XT and BLITZDUCTOR CT 1 910 508

910 508 PA BXT

P AB XT910 508

Page 367: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 367/382

MEASURING AND TEST DEVICES

365www.dehn.de

DEHNisola

SPD monitoring device

• SPD monitoring device for potential-free meas-uring of leakage currents of surge arresters

• Measuring and evaluation device with a com-pact DIN rail mounted enclosure (1.5 modules)

• 3 hard-wired winding-type transformers

• Self-test and reset function

• Battery supply

• 2 limit values for the leakage currents to bemonitored

• LED indication on site and remote signallingcontact

DEHNisola: Measuring and evaluation device with 3 hard-wired winding-type transformers and fixingmaterial

Continuous function test of installed lightning current and surge arrestersby DEHNisola monitoring device.

DISO 3

910 600

Dimension drawing DISO 3 DISO 3: Measuring and evaluation unit with 3 winding-type transformers

DISO 3

Indication of limit value 1 IL 0.5 mArms (indication only on site, will be reset when the value falls below the limit value)

Indication of limit value 2 IL 5 mArms (indication on site and remote signalling, will be reset only by pushing the reset button at the device)

Measuring cycle every hour or acyclically after every discharge process of the protective device to be monitored

Self-test generation of fault currents in each sensor for testing the measur ing unit, ‘’reset’’ > 2 sec.

Battery supply battery life: approx. 10 years, LowBatt indication and remote signalling

Remote signalling contact: Max. a.c. switching voltage 125 VRemote signalling contact: Max. d.c. switching voltage 110 V

Remote signalling contact: Max. switching capacity 30 W

Remote signalling contact: Max. switching current 1 A

Remote signalling contact: Cross-sectional area 0.5 to 4 mm2

Operating temperature range -25°C...+60°C

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material of measuring and evaluation device thermoplastic, red, UL 94 V-0

Degree of protection of measuring and evaluation device IP 20

Dimension of measuring and evaluation device 1.5 mods., DIN 43880

Dimension of sensors inner Ø11 mm, outer Ø33 mm

Length of the sensor lines 300 mm each

Weight 0.23 kg

Ordering information

Type DISO 3

Part No. 910 600

Packing unit 1 pc(s).

Page 368: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 368/382

MEASURING AND TEST DEVICES

366 www.dehn.de

Impulse Meter

Registration of discharges

• Potential-free registration of discharge cur-rents of surge protective devices

• Easy installation by enclosing the earth conduc-tor of the arrester with an open toroidal core

• Counter in a DIN rail mounted enclosure(2 modules)

• Twisted sensor cable, 1 m long

P2 Impulse Meter: Counter, sensor cable and toroidal corewith fixing material

Counter with integrated battery supply (9 V) and batterycharge control. Indication by 2-digit LCD display with settingand resetting buttons.

910 502 P 2

P 2 ImpulseMeter P2 910 502

Impulszähler P2

L1

Dimension drawing P2

P 2

Response wave for impulse currents (rise time ≥ 8 µs) > 1 kA

Sequence of impulses > 1 s

LCD display electronic counter 0...99

Power supply 9 V battery, IEC 6LR61 included in delivery, replaceable, battery life > 1 year

Battery charge control button and LED situated at device

Setting device button at device for setting the counter (e.g. after replacing a battery)Resetting device button at device for resetting the counter to 0

Operating temperature range -10°C...+50°C

For mounting on 35 mm DIN rail acc. to EN 60715

Enclosure material (counter) thermoplastic, red, UL 94 V-0

Enclosure material (sensor) PA 6, grey colour

Degree of protection IP 20

Dimension (counter) 2 mods., DIN 43880

Dimension (sensor) inner Ø 15 mm, outer Ø 36 mm

Length of the connecting cable (between sensor and counter) max. 1 m, twisted

Weight (counter, sensor and connecting cable) 0.2 kg

Accessories included in delivery 9 V battery, IEC 6LR61; cable tie (fixing of sensors)

Ordering information

Type P 2

Part No. 910 502

Packing unit 1 pc(s).

Page 369: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 369/382

www.dehn.de

More Information and Documentation

Publications

DS103 DEHN protects Wind Turbines.

DS104 DEHN protects Cell Sites.

DS107 Surge Protection: Safety for SewagePlants.

DS109 DEHN protects Photovoltaic Systems.

DS113 DEHN tests and analyses.

DS122 DEHN protects the Oil and GasIndustry.

DS137 DEHN protects Antenna Feeders.

DS143 BLITZDUCTOR® XT with LifeCheck®.

DS144 DEHN protects Biogas Plants.

DS145E LSA with Lightning Current CarryingCapacity.

DS164E BLITZDUCTOR XTUDS150 Easy choice surge protection.

DS509 DEHN protects.

DS614E DEHN stops Surges.

DS641E Coordinated Surge Protection.

DS649E Surge Protection – Easy choice.

DS702E Lightning Protection Guide

Further main catalogues

DS396E Safety EquipmentDS427E Lightning Protection

DEHN CD

DS707 DEHNtourDEHN + SÖHNE – CompanyPresentation

DS708 3D Animated films

– DEHN protects photovoltaic systems– DEHNguard T H...LIwith Pro-Active-Thermo-Control

– New Red/Line-DEHNventil modular– DEHN protects Cell Sites– Protection of Ex (i) circuits– Maintenance strategy with

BLITZDUCTOR XT

Reprints

61E Surge Protection – Practice-Oriented andStandard-Conform; from etz, 10/2006

63E Lightning and Surge Protection forTelecommunications and SignallingNetworks; from etz, 02/2007

Seminars

We also give seminars about

– Lightning Protection

– Surge Protection

– Safety Equipmentas well as protection for special applicationslike cell sites, photovoltaics, wind turbines, etc.

For more information regarding topics, dates,locations, etc., please contact the responsiblerepresentative of DEHN + SÖHNE in yourcountry. They shall be pleased to give you therequested information.

Note

Like our catalogues and publications, ourinstallation and mounting instructions

can also be downloaded from our websitewww.dehn.de.

Contact

The printed publications can be ordered free of charge from our Export DepartmentFax +49 9181 [email protected]

367

Page 370: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 370/382

368 www.dehn.de

Literature

DIN VDE Standards, VDE-Verlag, Berlin

DIN VDE 0100-100:2009-06

Low-voltage electrical istallations - Part 1:Fundamental principles, assessment of generalcharacteristics, definitions (IEC 60364-1:2005,modified);

German implementation HD 60364-1:2008

DIN VDE 0100-410:2007-06

Low-voltage electrical installations – Part 4-41:Protection for safety – Protection againstelectric shock(IEC 60364-4-41:2005, modified);German implementation HD 60364-4-41:2007

DIN VDE 0100-540:2007-06

Low-voltage electrical installations – Part 5-54:Selection and erection of electrical equipment– Earthing arrangements, protective conduc-

tors and protective bonding conductors(IEC 60364-5-54:2002, modified);German implementation HD 60364- 5-54:2007

DIN VDE 0100-443:2007-06

Low-voltage electrical installations – Part 4-44:Protection for safety – Protection againstvoltage disturbances and electromagneticdisturbances – Clause 443: Protection againstovervoltages of atmospheric origin or due toswitching(IEC 60364-4-44:2001 + A1:2003, modified);German implementation HD 60364-4-443:2006

DIN VDE 0100-534:2009-02

Low-voltage electrical installations - Part 5-53:Selection and erection of electrical equipment -Isolation, switching and control - Clause 534:Devices for protection against overvoltages(IEC 60364-5-53:2001/A1:2002 (Clause 534),modified);German implementation HD 60364-5-534:2008

DIN EN 60664-1

DIN VDE 0110-1:2008-01Insulation coordination for equipment withinlow-voltage systems – Part 1: Principles,requirements and tests(IEC 60664-1:2007) German versionEN 60664-1:2007

DIN VDE 0141:2000-01

Earthing system for special power installationswith nominal voltages above 1 kV

DIN EN 50178

DIN VDE 0160:1998-04Electronic equipment for use in power installa-tionsGerman version EN 50178:1997

DIN EN 62305-1

VDE 0185-305-1:2006-10Protection against lightning – Part 1:General principles (IEC 62305-1:2006);German version EN 62305-1:2006

DIN EN 62305-2VDE 0185-305-2:2006-10Protection against lightning – Part 2:Risk management (IEC 62305-2:2006);German version EN 62305-2:2006

DIN EN 62305-3

VDE 0185-305-3:2006-10Protection against lightning – Part 3:Physical damage to structures and live hazard(IEC 62305-3:2006, modified);German version EN 62305-3:2006

DIN EN 62305-4VDE 0185-305-4:2006-10Protection against lightning – Part 4: Electricaland electronic systems within structures(IEC 62305-4:2006);German version EN 62305-4:2006

DIN EN 50164-1

DIN VDE 0185-201:2009-03Lightning protection components (LPC) –Part 1: Requirements for connection compo-nentsGerman version EN 50164-1:2008

DIN IEC 60060-1

DIN VDE 0432-1:1994-06High voltage test techniques – Part 1: Generalspecifications and test requirements(IEC 60060-1:1989 + corrigendum March1990); German version HD 588.1 S1:1991

DIN VDE 0618-1:1989-08

Equipment for equipotential bonding; equipo-tential bonding busher for main equipotentialbonding

DIN EN 60099-1

DIN VDE 0675-1:2000-08Surge arresters – Part 1: Non-linear resistortype gapped surge arresters for a.c. systems(IEC 60099-1:1991)German version EN 60099-1:1994 + A1:1999

DIN EN 61643-11

VDE 0675-6-11:2007-08Low-voltage surge protective devices –Part 11: Surge protective devices connected tolow-voltage power systems; Requirements andtests(IEC 61643-1:1998 + corrigendum 1998, modi-fied); German version EN 61643-11:2002 +A11:2007

DIN VDE 0800-1:1989-05

Telecommunications;General concepts; requirements and tests forthe safety of facilities and apparatus

DIN VDE 0800-2:1985-07

Telecommunications;Earthing and equipotential bonding

DIN VDE 0800-10:1991-03

Telecommunications;Transitional requirements on erection andoperation of installations

DIN EN 50114

DIN VDE 0805-514:2009-04Audio, video and information technologyequipment - Routine electrical safety testingin production;

German version EN 50514:2008

DIN EN 41003

DIN VDE 0804-100:2009-04Particular safety requirements for equipment tobe connected to telecommunication networks;German version EN 41003:2008

DIN VDE 0845-1:1987-10

Protection of telecommunication systemsagainst lightning, electrostatic discharges andovervoltages from electric power installations;provisions against overvoltages

E DIN VDE 0845-2:1993-10

Protection of information technology andtelecommunication against lightning, electro-static discharges and overvoltages from electricpower installations; requirements and tests of overvoltage protection devices

DIN EN 60728-11

VDE 0855-1:2005-10Cable networks for television signals, soundsignals and interactive services –Part 11: Safety (IEC 60728-11:2005);German version EN 60728-11:2005

remain valid alongside this standard until2008-04-01.

DIN 18014:2007-09

Foundation earth electrode – General planningcriteria

IEC 60664-1:2007-04

Insulation coordination for equipment withinlow-voltage systems; part 1: principles,requirements and tests

IEC 61643-1:2005-03

Low-voltage surge protective devices – Part 1:Surge protective devices connected to low-voltage power distribution systems –Requirements and tests

Page 371: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 371/382

369www.dehn.de

Legal Notes

Since we do not carry out the design of systemsor system components, the suggested applica-tion of our products should be regarded as prod-uct information and for advisory purposes only.Our oral and written advice on application isbased on experience and given to the best of ourknowledge. However, it must be also consideredas not binding. This particularly applies to the

different conditions of use which are beyond ourcontrol. We recommend to check whether therespective DEHN product is suitable for theintended application.Application, use and processing of our productstake place beyond our control. Therefore, theproduct is completely subject to the user’s res-ponsibility.

Trademarks

– actiVsense®

– BLITZDUCTOR®

– DEHNbloc®

– DEHNguard®

– DEHNport®

– DEHNrapid®

– DEHNventil®

– LifeCheck®

– ...MIT SICHERHEIT DEHN.

and our brand

are registered trademarks ofDEHN + SÖHNE GMBH + CO. KG.in Germany

Books

– Hasse P., Wiesinger J., Zischank W.:"Handbuch für Blitzschutz und Erdung"[Lightning Protection and Earthing Guide]Pflaum Verlag GmbH & Co.KG, Munich,5th edition of 2006, ISBN 3-7905-0931-0

– Hasse P., Landers U., Wiesinger J.,Zahlmann P.:"EMV-Blitzschutz von elektrischen undelektronischen Systemen in baulichenAnlagen – Risiko-Management, Planen undAusführen nach den neuen Normen derReihe VDE 0185-305”2. vollständig überarbeitete und erweiterteAuflage 2007, [EMC-based lightning pro-tection for electrical and electronic systemsinstalled into structures – Risk manage-ment, design and performance accordingto new standard series DIN VDE 0185-305,

2nd completely revised and amendededition of 2007], series volume No. 185,Berlin-Offenbach: VDE Verlag GmbH,ISBN 9-783800-730018

– Raab V.:"Überspannungsschutz in Verbraucher-anlagen – Auswahl, Errichtung, Prüfung"[Surge protection for consumer’s installati-ons – Selection, Installation and Testing],

Huss-Medien GmbH Verlag Technik, Berlin2nd updated and amended edition of 2003ISBN 3-341-01347-4

– Raab P., Zahlmann P.:"Loseblattsammlung VDE-Kompass"[VDE Guide – Loose leaf collection]InfoPLUS-Paket 6 (12th supplemental set)"Neue Blitzschutz-Normen in der Praxis",[New lightning protection standards inpractice],VDE Verlag, Berlin Offenbach

IEC 61643-21:2000-09

Low voltage surge protective devices –Part 21: Surge protective devices connected totelecommunications and signalling networks –Performance requirements and testing methods

IEC 62305-1:2006-01Protection against lightning – Part 1:General principles

IEC 62305-3:2006-01

Protection against lightning – Part 2:Riskmanagement

IEC 62305-3:2006-01

Protection against lightning – Part 3:Physical damage to structures and life hazard

IEC 62305-4:2006-01Protection against lightning – Part 4: Electricaland electronic systems within structures

VG Standards, Beuth-Verlag GmbH

VG 95 372:2009-04

Electromagnetic Compatibility (EMC) includingElectromagnetic Pulse (EMP) and LightningProtection – Survey

VG 95 371-10:2003-08

Electromagnetic compatibility (EMC) including

electromagnetic pulse (EMP) and lightning pro-tection – Fundamentals – Part 10: Threat levelsfor NEMP and lightning

VG 96 907-1:2006-10

Nuclear Electromagnetic Pulse (NEMP) andlightning protection – Design guidelines andprotective devices – Part 1: Fundamentals

Further Standards

DVGW GW 309: Elektrische Überbrückung beiRohrtrennungen [Electrical bridging of separatepipe sections]. ZfGW-Verlag GmbH, Frankfurt.

Arbeitsgemeinschaft DVGW/VDE für Korrosions-fragen (AfK): AfK-Empfehlung Nr. 5/02.86,Kathodischer Korrosionsschutz in Verbindungmit explosionsgefährdeten Bereichen [GermanCorrosion Protection Committee (AfK): AfK rec-ommendation No. 5/02.86, Cathodic corrosionprotection in connection with potentially explo-sive areas] ZfGW-Verlag GmbH, Frankfurt

KTA 2206/2000-06:Auslegung von Kernkraft-werken gegen Blitzeinwirkung [Protection fornuclear power plants against lightning effects]

Page 372: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 372/382

370 www.dehn.de

General Terms of Sale

1. General,Scope

1.1 All deliveries and services in business dealings withentrepreneurs take place exclusively under our generalterms of sale (hereinafter “terms of sale”). We opposedeviating regulations,especially conflicting terms of pur-chase of the customer, unless we expressly agreed to thevalidity in writing. Our terms of sale apply even if wecomplete unconditional delivery to the customer whileknowing that the terms of sale of the customer are in

conflict with our own.1.2 Our terms of sale only apply to entrepreneurs within the

meaning of section 310, paragraph 1 of the German CivilCode (BGB), to current business relationships and to allfuture transactions with the customer.

2. Offer and Order, Reservation of Right of Modifi-

cation and Copyright

2.1 Insofar as not expressly indicated by us as binding, doc-uments such as diagrams, drawings, and measurementsare only roughly binding.

2.2 Should our order confirmation contain reasonable expan-sions, limitations, or other modifications with respect tothe order, then the customer’s agreement is implied, if itdoes not immediately, at the latest however within 3business days from receipt of the order confirmation,oppose it.

2.3 Any order placed in our web shop shall be regarded as anoffer to conclude a sales contract. A sales contract only

comes into existence if the customer receives a writtenorder confirmation or the goods are delivered / servicesare rendered.

2.4 Our goods are only delivered in the packaging units indi-cated in the catalogues. If a different number of items isordered, the amount and price of the next larger packag-ing unit is considered agreed upon.

2.5 We reserve the right to make technical modifications toour services, insofar as such modifications promote tech-nical progress or are unavoidable based on other circum-stances and are reasonable for the customer.

2.6 We reserve ownership and copyright rights to diagrams,drawings, calculations, and other documents; these maynot be made available to third parties without ourexpress written consent.

3. Prices, Value-Added Tax, Packaging Costs

3.1 Our prices are subject to change without notice.3.2 Prices include, insofar as nothing else is arranged, cus-

tomary packaging from our plant without value-addedtax. On the day of invoicing, the legally identified VATamount is to be reimbursed to us.

3.3 The cost of non-customary packaging, e.g., collective orseaworthy packaging, is invoiced separately. The custo-mer bears the cost of the disposal or return of packaging.

4. Passing of Risk, Optional Insurance

The risk of accidental loss, destruction, or deteriorationpasses to the customer upon dispatch to the customerfrom our plant, even if carriage-paid delivery is agreedupon. At the request and expense of the customer, wewill insure the delivery against breakage, damage togoods in transit and fire damage.

5. Payment Due Dates, Discounts, Right of Refusal,

Default, Small Order Quantity Surcharge

5.1 Unless otherwise agreed, invoices are payable net 10days. Purchaser shall pay the costs of payment. Discount

amounts are deductible only if they have been agreed onwith us and all accounts payable due have been paid.

5.2 If purchaser is in default with his payments, interest onthe outstanding amount shall be payable at the rate of 8 % above the base interest rate. We reserve the right toprove and allege higher default damages. We reserve theright to cause default by demanding early payment. If weare required to advance performance and, if after theexecution of the contract, it becomes apparent that ourclaim, in particular for payment, may be jeopardised bypurchaser’s inability to perform we may refuse perform-ance.

5.3 The customer cannot charge counter-claims against ourdue payment claims or exercise a right of retention,unless the customer is entitled to a claim recognised bydeclaratory judgement that is not contested by us and if,while exercising the right of retention, the counter-claimfrom the customer is based on the same contractual rela-tionship.

5.4 Orders, with the exception of cash sales, for which thenet amount (invoiced amount without shipping costs andvalue-added tax) is less than € 75.00, a small order sur-charge of € 25.00 will be charged.

6. Retention of Title, Assignment, Release of Securities

6.1 Delivered goods remain our property until the paymentof all open business claims up to the point of invoicing.The claims of the customer including value-added taxfrom the resale of reserved goods, i.e., from a work per-formance using our goods, should already be transferredto us in the amount of the open invoice. In the case thatthe reserved goods from the customer are sold togetherwith other goods that do not belong to us, whether it be

without or after processing, or are delivered within theframework of a working contract, the assignment of theresulting claim of the reserve buyer is calculated in theamount of the value of the reserved goods.

6.2 Should the value of the granted securities exceed theclaims by more than 10 %, we are obliged to retransferor release the securities upon request. We shall select thesecurities to be released.

6.3 Our goods may only be transferred within the frameworkof proper business activity. The customer is not allowedto pawn or transfer the ownership of goods that are stillin our possession.

6.4 At our request, the customer is obliged to inform us of the purchaser and the arranged price and to show theassignment to its debtor.

7. Delivery Period and Appointment

7.1 The start of the delivery period presupposes the involve-ment of the customer for the clarification of all technical

questions.7.2 Delivery periods as well as delivery schedules will be

appropriately extended if they cannot be adhered to as aresult of military mobilisation, war, uprising, strike orlockout, delayed delivery of raw and auxiliary materials,late delivery by our suppliers, or similar circumstancesbeyond our control.A lasting obstruction under these cir-cumstances gives us the right to withdraw from the con-tract without liability for damages.

8. Liability for Material and Title Defects

8.1 Insofar as there exists a defect of the contract subjectthat was beyond our control, we can choose to fix thedefect or provide a defect-free contract subject (replace-ment).

8.2 Should the replacement (No. 8.1) not function properly,or should it be unreasonable to the customer, or shouldwe seriously and conclusively refuse it or unreasonablydelay it, or if other circumstances exist that,upon weigh-

ing mutual interests, justify immediate resignation orcompensation, then the customer is entitled to choose tolower the contract price or to withdraw from the contractand/or demand compensation (No. 8.3). The customer isnot entitled to withdraw from the contract if onlyinsignificant contract inconformities exist, especiallyinsignificant defects.

8.3 Should the customer exclusively choose compensationafter proper replacement (No. 8.2), the contract subjectremains with the customer,if it considers this reasonable.Compensation is limited to the difference between thepurchase price (without value-added tax) and the valueof the defective subject of the contract that remains withthe customer.

8.4 Material and title defect claims, including claims for com-pensation due to material and title defects, with theexception of claims under the Product Liability Act, lapse12 months after delivery of the goods.

8.5 Numbers 8.1 through 8.4 do not impair the customer’s

rights if we maliciously concealed a defect or if weoffered a quality guarantee.

9. Liability for Other Reasons

9.1 Our liability is excluded for slightly negligent infringe-ment of immaterial contractual obligations. Our liabilityis limited to the contractual, foreseeable damage fornegligent infringement of other obligations.

9.2 The above regulation does not apply to claims under theProduct Liability Act. Insofar as the limitation on liabilitypursuant to No. 9.1 for claims from the producer’s liabil-ity pursuant to § 823 of the German Civil Code does notinterfere, our liability is limited to the replacement of theinsurance. Insofar as this does not occur or does notoccur in full, we are liable up to the insured amount.

9.3 Insofar as our liability is excluded or limited, this alsoapplies for the personal liability of all of our employees,representatives, and vicarious agents.

9.4 Our liability is unrestricted if the customer loses his/her

life or suffers a bodily or health injury due to an action orfailure attributable to us.

10. Return of Goods without Legal Liability

10.1 If no legal claim to return exists, delivered goods willbe accepted only with previous agreement from us.Returns without previous agreement will be send back– postage-due – to the sender without inspection. Thecustomer bears the shipping costs for the return deliveryin No. 10.1.

10.2 The goods must still be in their original packaging.Special orders or deliveries, which date back more than

three months or the net value of which is less than€ 75.00, cannot be returned.A processing fee of 15 % of the net value of the goods will be charged to cover thecost of the return. If the goods can no longer be resold atthe list price at the time of the return, an additionaldeduction (old goods deduction) will be made in additionto the processing fee. If we make an exception and agreeto accept the return of parts that are unpackaged or thatare no longer in their original packaging, an expenseremuneration of at least 15 % will be charged forreworking and repackaging in addition to the processingfee and, if applicable, the old goods deduction.

10.3 Returned goods will only be credited to a new invoice.Credits cannot be used to clear invoices due at the timeof the return.

11. Product Information, No Advisory Obligation

Our deliveries are intended only for speciality stores orskilled users. Our user information and instructions are

limited to the details of each written product information(e.g., installation instructions, catalogues, data sheets).Further advisory obligations do not exist. Application,use, and processing of the products lie solely in the cus-tomer’s realm of responsibility.

12. Use and Protection of Customer Data

We use customer data, which concern the business deal-ings with the customer, in terms of the Federal DataProtection Act.

13. Applicable Law, Jurisdiction

13.1 German law applies to the mutual contractual obliga-tions, their materialisation, interpretation, and imple-mentation as well as all resulting contractual and busi-ness relationships. The application of the UN Agreementon Contracts on the International Purchase of Goods andthe thereafter enacted laws of the Federal Republic of Germany is excluded.

13.2 Place of performance and jurisdiction for delivery, pay-ment, and for all obligations, including those from ex-change and cheque payments, is exclusively Nuremberg.We reserve the right to file a complaint against the cus-tomer at its official location.

14. VAT Identification Number

VAT ID No. DE 133251475

DEHN + SÖHNE GmbH + Co. KG.Nürnberg – Neumarkt

Update July 2009

Page 373: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 373/382

371www.dehn.de

Key to Symbols used in Basic Circuit Diagrams

Symbol Description Standard

Creepage discharge spark gap,energy-controlled, encapsulated(DEHNventil® TNC/TNS/TT/2P/2P TT)

Creepage discharge spark gap,non-exhausting, encapsulated(DEHNbloc®, DEHNbloc® NH)

Creepage discharge spark gap

EN 60617Varistor Part 4tA ≤ 25 ns 04-01-04

EN 60617Thermal disconnector Part 7

07-09-03

EN 60617Thermo Dynamic Control Parts 7 + 11

07-09-03111-07-02

EN 60617Spark gap, general Part 7

07-22-01

EN 60617Fuse Part 7

07-21-01

Temperature fuse

EN 60617Filter, general Part 10

10-16-03

EN 60617LED, general Part 8

08-10-01

EN 60617Suppressor diode, bipolar Part 5tA ≤ 1 ns 05-03-07

EN 60617Z diode, unipolar Part 5tA ≤ 1 ns 05-03-06

Symbol Description Standard

Gas discharge tube EN 60617(single) Part 7tA ≤ 100 ns 07-22-04

Gas discharge tube EN 60617(balanced) Part 7tA ≤ 100 ns 07-22-05

Resistor, EN 60617Decoupling element, Part 4general 04-01-01

EN 60617Capacitor Part 4

04-02-01

Inductor

Resistor,temperature-controlled

EN 60617Socket and plug connector Part 3

03-03-05

EN 60617Break contact Part 7

07-02-03

EN 60617Changeover contact Part 7

07-02-04

EN 60617Close contact Part 7

07-02-01

EN 60617Enclosure with Parts 2 + 3terminals 02-01-07

03-02-02

EN 60617Acoustic signal Part 8

08-10-05

Page 374: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 374/382

372 www.dehn.de

Part No. Index

106 310 – 279

106 329 – 279

277 230 FBH 6 ST 357

277 237 FBH 6 CU 357

277 239 FBH 6 V2A 357

277 240 FBH 11 ST 357

290 001 AH FE RF V G 357

290 002 AH FE RF 357

308 001 KV FE UNI 357

308 025 VK A UNI ST 357

308 026 VK A UNI V2 ST 357

308 030 VK A R22 F40 STBL 357

308 040 MMVK R16 R25 STBL 357

308 041 MMVK R16 R25 ST 357

308 120 VK EH R10 F30 ST 357

308 129 VK EH R10 F30 V2A 357

308 150 – 357

308 403 SAK 10 AS V4A 326

308 404 SAK 14 AS V4A 326

308 405 SAK 18 AS V4A 326

308 406 SAK 21 AS V4A 326

308 407 SAK 26 AS V4A 326

308 408 SAK 33 AS V4A 326

308 411 AK 16 AS SAK MS 327

308 421 AS SAK 1000 V2A 326

308 425 ST AS SAK K 327

416 411 – 279

472 021 ES 2X6AP 10 ST 356

472 022 ES 2X3AP 10 ST 356

472 023 ES 2X2AP 10 ST 356

472 024 ES 2X4AP ST 356

472 109 ES 2X2AP 10 V2A 356

472 119 ES 2X3AP 10 V2A 356

472 129 ES 2X4AP 10 V2A 356

472 139 ES 2X6AP 10 V2A 356

472 201 BS M10 PAS 356

472 207 PAS I 6AP M10 CU 356

472 209 PAS I 6AP M10 V2A 356

472 210 IS PAS M10 356

472 217 PAS I 10AP M10 CU 356472 219 PAS I 10AP M10 V2A 356

472 227 PAS I 8AP M10 CU 356

472 229 PAS I 8AP M10 V2A 356

472 237 PAS I 12AP M10 CU 356

472 239 PAS I 12AP M10 V2A 356

472 269 AD PAS 8AP V2A 356

472 279 AD PAS 6AP V2A 356

472 289 AD PAS 10AP V2A 356

472 299 AD PAS 12AP V2A 356

540 801 EX BRS 90 351

540 803 EX BRS 300 351

540 805 EX BRS 500 351540 810 – 352

540 821 EX BRS 27 351

540 901 – 352

563 010 PAS 10RK 355

563 011 RK 16 PAS 355

563 012 RK FL30 PAS 355

563 013 RK 95 PAS 355

563 014 SB PAS RK 355563 015 AH PAS RK 355

563 016 KS 198 PAS 355

563 017 KS 398 PAS 355

563 018 KS 798 PAS 355

563 019 RK FL40 PAS 355

563 020 PAS 9RK 355

563 030 PAS 14RK 355

563 050 PAS 9AK 355

563 105 PAS 6RK OH 355

563 169 AK RPA V2A 357

563 200 PAS 11AK 355

563 201 PAS 11AK UV 355

563 222 AK FL40 PAS 355

900 050 DGPM 1 255 S 65

900 120 DB 3 255 H 59

900 132 DGP BN 255 66

900 159 DB 1 440 61

900 216 T C H 255 102

900 220 DBM 1 255 S 55

900 222 DB 1 255 H 59

900 255 DBM NH00 255 50

900 261 V NH00 280 116

900 262 VA NH00 280 117

900 263 V NH00 280 FM 116

900 264 VA NH00 280 FM 117

900 269 DGP B NH00 N 255 67

900 270 V NH1 280 116

900 271 VA NH1 280 117

900 273 DB NH00 255 H 60

900 330 DLM PV 1000 43

900 390 DV ZP TNC 255 40

900 391 DV ZP TT 255 41

900 411 EB DG 1000 1 3 151

900 417 EB 1 4 9 151

900 471 VC 280 2 144

900 589 STAK 2X16 145

900 595 MVS 3 6 150

900 610 MVS 1 4 149

900 611 MVS 1 8 150

900 612 MVS 1 57 150

900 614 MVS 4 56 151

900 615 MVS 1 3 149

900 617 MVS 1 2 149

900 813 MVS 3 6 8 150

900 814 MVS 4 8 11 151

900 815 MVS 1 6 149

900 848 MVS 1 7 150

902 315 IGA 10 V2 IP54 146

902 471 IGA 12 IP54 147

902 472 IGA 24 IP54 147

902 485 IGA 6 IP54 148

906 055 ALGA 5 334

906 058 ALGA 5 X 334

906 059 MS ALGA 5 X 335

906 100 DPG LSA 30 P 242

906 101 DPG LSA 60 P 242

906 102 DPG LSA 120 P 242906 103 DPG LSA 220 P 242

907 208 GDT 230 G3 240

907 214 DPL 10 G3 110 240

907 216 DPL 10 G3 110 FSD 240

907 217 GDT 230 G3 FSD 240

907 218 GDT 230 B3 238

907 219 GDT 230 B3 FSD 238

907 400 DRL 10 B 180 231

907 401 DRL 10 B 180 FSD 232

907 420 DRL RE 5 233

907 421 DRL RE 12 233

907 422 DRL RE 24 233907 423 DRL RE 48 233

907 424 DRL RE 60 233

907 425 DRL RE 180 233

907 430 DRL PD 180 235

907 440 DRL RD 5 234

907 441 DRL RD 12 234

907 442 DRL RD 24 234

907 443 DRL RD 48 234

907 444 DRL RD 60 234

907 445 DRL RD 110 234

907 465 DRL HD 5 236

907 470 DRL HD 24 236

907 497 SR DRL 238

907 498 EF 10 DRL 237

907 499 BM 10 DRL 238

907 991 TL2 10DA CC 245

907 993 EL2 38EA LSA 244

907 994 AW2 LSA 243

907 995 MB2 10 LSA 243

907 996 TL2 10DA LSA 244

907 997 AL2 10DA LSA 244

909 230 DPRO 230 139

909 235 DPRO 230 SE 139

909 240 DPRO 230 F 140

909 245 DPRO 230 SE F 140909 300 DPRO 230 TV 338

909 305 DPRO 230 SE TV 338

909 310 DPRO 230 NT 339

909 315 DPRO 230 SE NT 339

909 320 DPRO 230 ISDN 340

909 325 DPRO 230 SE ISDN 340

909 321 DPRO 230 LAN100 341

909 326 DPRO 230 SE LAN100 341

909 703 DGA FF TV 272

909 704 DGA GF TV 272

909 705 DGA GFF TV 272

909 710 DGA BNC VCD 271

909 711 DGA BNC VCID 271

910 099 SLK 16 335

910 486 USB NANO 485 360

910 502 P 2 366

910 507 PA DRL 364

910 508 PA BXT 364

910 511 PM 20 364

910 600 DISO 3 365910 631 DSI E 3 57

910 641 LWL ST DSI 57

910 642 LWL DSI 18M 57

910 652 LCS DRC BXT 362

910 653 DRC LC M3+ 362

910 654 LCS DRC BCT 362

910 695 DRC MCM XT 360

910 697 TW DRC MCM EX 319

912 253 SPS PRO 127

912 254 NF 10 125

912 260 SFL PRO 142

912 261 SFL PRO SE 142

918 400 BVT TTY 24 219

918 401 BVT RS485 5 221

918 402 BVT AD 24 222

918 404 BVT KKS ALD SN 227

918 405 BVT KKS APD SN 228

918 407 BVT MTTY 24 220

918 408 BVT ALD 36 223

918 410 BVT ISDN 257

918 411 BVT TC 1 258

918 420 BVT KKS ALD 75 225

918 421 BVT KKS APD 36 226

919 010 SAK 6.5 SN MS 329

919 011 SAK 11 SN MS 329

919 012 SH1 18X3 ST 330

919 013 SH2 18X3 ST 330

919 014 SH 18X3 K 330

919 015 AK 35 SN 18X3 GG 331

919 016 SN 18X3 CU 1000 329

919 030 SKB 19 9M SW 333

919 031 SA KRF 10 V2A 333

919 032 SA KRF 15 V2A 333

919 033 SA KRF 22 V2A 333

919 034 SA KRF 29 V2A 333

919 035 SA KRF 37 V2A 333919 036 SA KRF 50 V2A 333

919 037 SA KRF 70 V2A 333

919 038 SA KRF 94 V2A 333

919 880 KB 10 DCO RK 217

919 920 DCO RK ME 12 210

919 921 DCO RK ME 24 210

919 922 DCO RK ME 48 210

919 923 DCO RK ME 110 210

919 940 DCO RK MD 12 211

919 941 DCO RK MD 24 211

919 942 DCO RK MD 48 212

919 943 DCO RK MD 110 213

919 960 DCO RK MD EX 24 323919 970 DCO RK MD HF 5 214

919 976 BS 1 50 S DCO RK 217

919 977 BS 1 50 DCO RK 217

Part No. Type Page Part No. Type Page Part No. Type Page Part No. Type Page

Page 375: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 375/382

373www.dehn.de

Part No. Index

919 978 AD DCO RK BL 323

919 979 AD DCO RK GE 217

919 986 DCO RK D 5 24 216

919 987 DCO RK E 12 215

919 988 DCO RK E 24 215919 989 DCO RK E 48 215

919 990 DCO RK E 60 215

920 211 BXT ML2 B 180 195

920 220 BXT ML2 BE S 5 199

920 222 BXT ML2 BE S 12 199

920 224 BXT ML2 BE S 24 199

920 225 BXT ML2 BE S 48 199

920 240 BXT ML2 BD S 5 197

920 242 BXT ML2 BD S 12 197

920 243 BXT ML2 BD DL S 15 198

920 244 BXT ML2 BD S 24 197

920 245 BXT ML2 BD S 48 197920 247 BXT ML2 BD 180 196

920 249 BXTU ML2 BD S 0 -180 182

920 270 BXT ML2 BE HFS 5 200

920 271 BXT ML2 BD HFS 5 201

920 300 BXT BAS 183

920 301 BXT BAS EX 313

920 308 BXT M4 E 202

920 309 BXT M4 T 203

920 310 BXT ML4 B 180 187

920 320 BXT ML4 BE 5 188

920 322 BXT ML4 BE 12 188

920 324 BXT ML4 BE 24 188

920 325 BXT ML4 BE 48 188

920 326 BXT ML4 BE 60 188

920 327 BXT ML4 BE 180 188

920 336 BXT ML4 BE 36 188

920 340 BXT ML4 BD 5 189

920 342 BXT ML4 BD 12 189

920 344 BXT ML4 BD 24 189

920 345 BXT ML4 BD 48 189

920 346 BXT ML4 BD 60 189

920 347 BXT ML4 BD 180 189

920 349 BXTU ML4 BD 0-180 181

920 350 BXT ML4 BC 5 190

920 354 BXT ML4 BC 24 190

920 362 BXT ML4 BE C 12 191

920 364 BXT ML4 BE C 24 191

920 370 BXT ML4 BE HF 5 192

920 371 BXT ML4 BD HF 5 193

920 375 BXT ML4 BD HF 24 193

920 381 BXT ML4 BD EX 24 314

920 384 BXT ML4 BC EX 24 315

920 389 BXT ML4 MY 250 194

920 395 SAK BXT LR 202

920 398 BS BA1 BA15 BXT 204

920 399 BS 1 50 BXT 204

920 538 BXT ML2 BD HF EX 6 316

923 011 IF1 345

923 016 IF3 345

923 019 EXFS KU 349

923 021 KFSU 343

923 023 TFS 343

923 025 AL EXFS L100 KS 345

923 035 AL EXFS L200 KS 345

923 045 AL EXFS L300 KS 345923 060 EXFS L100 348

923 061 EXFS L200 348

923 062 EXFS L300 348

923 100 EXFS 100 345

923 101 EXFS 100 KU 346

923 110 SDS 1 354

923 116 SDS 3 354

923 117 SDS 2 354

923 118 SDS 4 354

923 119 SDS 5 354

924 016 FS 15E 5 284

924 017 FS 9E PB 6 282924 018 FS 25E HS 12 285

924 019 FS 9E HS 12 283

924 046 USD 25 V24 HS S B 288

924 051 USD 15 V11 S B 287

924 061 USD 9 V24 S B 286

924 270 DSM ISDN SK 290

924 272 DSM TC 2 SK 291

924 274 DSM TM 260

924 328 AR1 STW 129

924 329 ZAP STW 129

924 335 NSM PRO TW 137

924 336 AR1 TW 137

924 337 NSM PRO SI 137

924 338 AR1 SI 137

924 339 NSM PRO AZ 137

924 340 AR1 AZ 137

924 342 NSM PRO EW 137

924 343 AR1 EW 137

924 350 STC 230 131

924 370 DSA 230 LA 129

924 389 DFL A 255 134

924 395 DFL D 255 135

924 396 DFL M 255 133

925 001 BT 24 293

925 013 AS IBAS YE 295

929 010 UGKF BNC 268

929 024 DLI ISDN I 262

929 026 DLI TC BT 266

929 028 DLI TC 2 I 263

929 034 EG NET PRO 19” 249

929 035 NET PRO 4TP 249

929 036 NET PRO LSA 4TP 249

929 037 NET PRO 4TP 30 249

929 040 DGA F 1.6 5.6 273

929 042 DGA G BNC 274

929 043 DGA AG BNC 275

929 044 DGA G N 274929 045 DGA AG N 275

929 046 DGA LG 7 16 276

929 047 DGA L4 7 16 S 277

929 048 DGA L4 7 16 B 277

929 057 DGA AG U 275

929 059 DGA L4 N EB 278

929 071 NET PRO TC 2 250929 072 NET PRO TC 2 LSA 250

929 075 NET PRO E1 LSA G703 251

929 081 DLI TC ECO RJ12 264

929 095 EB 4 F 279

929 096 EL 16 B17 279

929 100 DPA M CAT6 RJ45S 48 254

929 110 DPA M CAT6 RJ45H 48 254

929 121 DPA M CLE RJ45B 48 255

929 199 MS DPA 254

929 230 NET PRO 10X TC1 RST 252

929 234 EG NET PRO 10X 19” 252

929 235 EG NET PRO 10X 3HE 252

929 446 DGA LG 7 16 X 276

929 496 GDT DGA 90 X 279

929 497 GDT DGA 90 279

929 498 GDT DGA 230 279

929 499 GDT DGA 470 279

929 921 DPI ME 24 N A2G 299

929 941 DPI MD 24 M 2S 298

929 960 DPI MD EX 24 M 2 303

929 961 DPI CD EXI 24 M 306

929 962 DPI CD EXD 24 M 308

929 963 DPI CD EXI 24 N 306

929 964 DPI CD EXD 24 N 308

929 969 DPI CD EXD 230 24 M 310

929 970 DPI CD EXD 230 24 N 310

929 971 DPI CD HF EXD 5 M 309

929 982 KV S M20 MS 9.5 300

929 984 KV M20 MS 10.5 300

929 996 ER DPI M20 300

950 102 DG 1000 111

950 112 DG 1000 FM 111

950 120 DG T H 275 LI 103

950 121 DG T H 385 LI 103

950 130 T H 275 LI 103

950 131 T H 385 LI 103

950 150 DG TT H230 400 LI 102

950 151 DG TT H230 400 LI385 102

950 160 DG TNC H230 400 LI 100

950 170 DG TNS H230 400 LI 101

950 500 DG PV 500 SCP 108

950 501 DG PV 700 SCP 108

950 502 DG PV 1200 SCP 108

950 505 DG PV 500 SCP FM 109

950 506 DG PV 700 SCP FM 109

950 507 DG PV 1200 SCP FM 109

951 001 DV MOD 255 38

951 050 DV MOD NPE 50 38

951 100 DV MOD NPE 100 38

951 110 DV M TT 2P 255 36

951 115 DV M TT 2P 255 FM 36

951 200 DV M TN 255 35

951 205 DV M TN 255 FM 35

951 300 DV M TNC 255 32

951 305 DV M TNC 255 FM 32

951 310 DV M TT 255 34

951 315 DV M TT 255 FM 34951 400 DV M TNS 255 33

951 405 DV M TNS 255 FM 33

952 010 DG MOD 275 95

952 011 DG MOD 75 95

952 012 DG MOD 150 95

952 013 DG MOD 320 95

952 014 DG MOD 385 95

952 015 DG MOD 440 95

952 016 DG MOD 600 95

952 017 DG MOD 750 95

952 018 DG MOD 48 95

952 020 DG MOD CI 275 98952 025 DG MOD 75 VA 97

952 027 DG MOD 275 VA 97

952 029 DG MOD 385 VA 97

952 030 DGP C S 93

952 035 DGP C S FM 93

952 050 DG MOD NPE 96

952 051 DG MOD PV SCI 500 97

952 053 DG MOD PV SCI 300 97

952 054 DG MOD PV SCI 600 97

952 060 DGP C MOD 96

952 070 DG S 275 89

952 071 DG S 75 89

952 072 DG S 150 89

952 073 DG S 320 89

952 074 DG S 385 89

952 075 DG S 440 89

952 076 DG S 600 89

952 077 DG S WE 600 91

952 078 DG S 48 89

952 079 DG S CI 275 75

952 080 DG S 75 VA 113

952 082 DG S 275 VA 113

952 084 DG S 385 VA 113

952 085 DG S 75 VA FM 114

952 087 DG S 275 VA FM 114

952 089 DG S 385 VA FM 114

952 090 DG S 275 FM 90

952 091 DG S 75 FM 90

952 092 DG S 150 FM 90

952 093 DG S 320 FM 90

952 094 DG S 385 FM 90

952 095 DG S 440 FM 90

952 096 DG S 600 FM 90

952 097 DG S WE 600 FM 91

952 098 DG S 48 FM 90

952 099 DG S CI 275 FM 75

952 110 DG M TT 2P 275 85

952 111 DG M TT 2P 385 85952 115 DG M TT 2P 275 FM 86

952 116 DG M TT 2P 385 FM 86

952 130 DG M TT 2P 320 85

Part No. Type Page Part No. Type Page Part No. Type Page Part No. Type Page

Page 376: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 376/382

374 www.dehn.de

Part No. Index

952 135 DG M TT 2P 320 FM 86

952 171 DG M TT 2P CI 275 74

952 173 DG M TN CI 275 73

952 176 DG M TT 2P CI 275 FM 74

952 178 DG M TN CI 275 FM 73952 200 DG M TN 275 83

952 201 DG M TN 150 83

952 205 DG M TN 275 FM 84

952 206 DG M TN 150 FM 84

952 300 DG M TNC 275 77

952 302 DG M WE 600 87

952 303 DG M TNC 440 77

952 304 DG M TNC CI 275 70

952 305 DG M TNC 275 FM 78

952 307 DG M WE 600 FM 87

952 308 DG M TNC 440 FM 78

952 309 DG M TNC CI 275 FM 70

952 310 DG M TT 275 81

952 311 DG M TT 385 81

952 313 DG M TNC 150 77

952 314 DG M TNC 385 77

952 315 DG M TT 275 FM 82

952 316 DG M TT 385 FM 82

952 318 DG M TNC 150 FM 78

952 319 DG M TNC 385 FM 78

952 320 DG M TT 320 81952 322 DG M TT CI 275 72

952 325 DG M TT 320 FM 82

952 327 DG M TT CI 275 FM 72

952 400 DG M TNS 275 79

952 401 DG M TNS CI 275 71

952 403 DG M TNS 150 79

952 404 DG M TNS 385 79

952 405 DG M TNS 275 FM 80

952 406 DG M TNS CI 275 FM 71

952 408 DG M TNS 150 FM 80

952 409 DG M TNS 385 FM 80

952 510 DG M YPV SCI 1000 105

952 511 DG M YPV SCI 600 105

952 512 DG M YPV SCI 1200 105

952 515 DG M YPV SCI 1000 FM 106

952 516 DG M YPV SCI 600 FM 106

952 517 DG M YPV SCI 1200 FM 106

952 699 DK 25 145

953 010 DR MOD 255 124

953 011 DR MOD 30 124

953 012 DR MOD 60 124

953 013 DR MOD 75 124

953 014 DR MOD 150 124

953 020 DR MOD 4P 255 124

953 200 DR M 2P 255 120

953 201 DR M 2P 30 120

953 202 DR M 2P 60 120

953 203 DR M 2P 75 120

953 204 DR M 2P 150 120

953 205 DR M 2P 255 FM 121

953 206 DR M 2P 30 FM 121

953 207 DR M 2P 60 FM 121

953 208 DR M 2P 75 FM 121953 209 DR M 2P 150 FM 121

953 400 DR M 4P 255 123

953 405 DR M 4P 255 FM 123

961 001 DB M MOD 150 48

961 002 DB M MOD 255 48

961 003 DB M MOD 320 48

961 010 DGP M MOD 255 64

961 101 DGP M 255 64961 105 DGP M 255 FM 64

961 110 DB M 1 150 46

961 115 DB M 1 150 FM 47

961 120 DB M 1 255 46

961 125 DB M 1 255 FM 47

961 130 DB M 1 320 46

961 135 DB M 1 320 FM 47

961 140 DBM 1 440 52

961 145 DBM 1 440 FM 52

961 160 DGPM 440 68

961 165 DGPM 440 FM 68

961 175 DBM 1 760 FM 53

989 408 ITAK EXI BXT 24 321

Part No. Type Page Part No. Type Page Part No. Type Page Part No. Type Page

Page 377: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 377/382

375www.dehn.de

Type / Product Index

Type Product Part No. Page Type Product Part No. Page

– Angled fixing plate for DEHNgate 106 310 279

– Angled fixing plate for DEHNgate 106 329 279

– Expansion strap f. foundation earthing electrodes 308 150 357

– Earth conductor, open/closed cable lugs 416 411 279

– Separate clamping element 540 810 352– Tensioning strap 540 901 352

AD DCO RK BL Covering Plate for DCO, blue 919 978 323

AD DCO RK GE Covering Plate for DCO, yellow 919 979 217

AD PAS 6AP V2A Cover NIRO, for 6-pole EB 472 279 356

AD PAS 8AP V2A Cover NIRO, for 8-pole EB 472 269 356

AD PAS 10AP V2A Cover NIRO, for 10-pole EB 472 289 356

AD PAS 12AP V2A Cover NIRO, for 12-pole EB 472 299 356

AH FE RF Distance Holder St/tZn, DIN 48833 A, 280 mm 290 002 357

AH FE RF V G Distance Holder St/tZn, r einf. v ersion 300 mm 290 001 357

AH PAS RK Plastic cover, grey 563 015 355

AK 16 AS SAK MS Protective Conductor Terminal, -16 mm√ 308 411 327

AK 35 SN 18X3 GG Terminal for Busbar 919 015 331AK FL40 PAS Terminal for Fl 40 563 222 355

AK RPA V2A Terminal St/tZn 563 169 357

AL EXFS L100 KS Connect ing cable fo r EXFS 100, length: 100 mm 923 025 345

AL EXFS L200 KS Connect ing cable fo r EXFS 100, length: 200 mm 923 035 345

AL EXFS L300 KS Connect ing cable fo r EXFS 100, length: 300 mm 923 045 345

AL2 10DA LSA Terminal Block 10TC LSA-PLUS 907 997 244

ALGA 5 Aluminium Enclosure IP65 906 055 334

ALGA 5 X Aluminium Enclosure IP65 for BCT 906 058 334

AR1 AZ Protector Cover, single piece, anthracite 924 340 137

AR1 EW Protector Cover, single piece, studio white 924 343 137

AR1 SI Protector Cover, single piece, silver 924 338 137

AR1 STW Covering Frame for DEHNsafe, studio white 924 328 129

AR1 TW Protector Cover, single-piece, titan white 924 336 137

AS IBAS YE Coupling Module 925 013 295

AS SAK 1000 V2A Anchor Bar, stainless steel, 1 m long 308 421 326

AW2 LSA Insertion Tool LSA-PLUS 907 994 243

BM 10 DRL Plug-in SPD Block (without SPDs) 907 499 238

BS 1 50 BXT Labelling System, p rinted with numbers 1-50 920 399 204

BS 1 50 DCO RK Quick Marking System for DCO RK 919 977 217

BS 1 50 S DCO RK Quick Marking System for DCO RK 919 976 217

BS BA1 BA15 BXT Marking System for BXT 920 398 204

BS M10 PAS Fixing Set for EB 472 201 356

BT 24 BUStector 925 001 293

BVT AD 24 BLITZDUCTOR VT 918 402 222

BVT ALD 36 BLITZDUCTOR VT 918 408 223BVT ISDN BLITZDUCTOR VT 918 410 257

BVT KKS ALD 75 BLITZDUCTOR VT 918 420 225

BVT KKS ALD SN BLITZDUCTOR VT 918 404 227

BVT KKS APD 36 BLITZDUCTOR VT 918 421 226

BVT KKS APD SN BLITZDUCTOR VT 918 405 228

BVT MTTY 24 BLITZDUCTOR VT 918 407 220

BVT RS485 5 BLITZDUCTOR VT 918 401 221

BVT TC 1 BLITZDUCTOR VT 918 411 258

BVT TTY 24 BLITZDUCTOR VT 918 400 219

BXT BAS BXT Base Part 920 300 183

BXT BAS EX BXT Base Part Ex(i) 920 301 313

BXT M4 E BXT Earthing Module 920 308 202

BXT M4 T BXT Testing / Disconnecting Module 920 309 203

BXT ML2 B 180 BXT Protection Module LifeCheck B, 1 80 V 920 211 195

BXT ML2 BD 180 BXT Protection Module LifeCheck BD, 1 80 V 920 247 196

BXT ML2 BD DL S 15 BXT Protection Module LifeCheck BD DL, 17 V 920 243 198

BXT ML2 BD HF EX 6 BXT Protection Module LifeCheck BD HF EX, 6 V 920 538 316

BXT ML2 BD HFS 5 BXT Protection Module LifeCheck BD, 6 V 920 271 201

BXT ML2 BD S 5 BXT Protection Module LifeCheck BD, 6 V 920 240 197

BXT ML2 BD S 12 BXT Protection Module LifeCheck BD, 1 5 V 920 242 197BXT ML2 BD S 24 BXT Protection Module LifeCheck BD, 3 3 V 920 244 197

BXT ML2 BD S 48 BXT Protection Module LifeCheck BD, 5 4 V 920 245 197

BXT ML2 BE HFS 5 BXT Protection Module LifeCheck BE, 6 V 920 270 200

BXT ML2 BE S 5 BXT Protection Module LifeCheck BE, 6 V 920 220 199

BXT ML2 BE S 12 BXT Protection Module LifeCheck BE, 1 5 V 920 222 199

BXT ML2 BE S 24 BXT Protection Module LifeCheck BE, 3 3 V 920 224 199

BXT ML2 BE S 48 BXT Protection Module LifeCheck BE, 5 4 V 920 225 199

BXT ML4 B 180 BXT Protection Module LifeCheck B, 1 80 V 920 310 187

BXT ML4 BC 5 BXT Protection Module LifeCheck BC, 6 V 920 350 190

BXT ML4 BC 24 BXT Protection Module LifeCheck BC, 3 3 V 920 354 190

BXT ML4 BC EX 24 BXT Protection Module Li feCheck BC EX,24 V 920 384 315

BXT ML4 BD 5 BXT Protection Module LifeCheck BD, 6 V 920 340 189

BXT ML4 BD 12 BXT Protection Module LifeCheck BD, 1 5 V 920 342 189

BXT ML4 BD 24 BXT Protection Module LifeCheck BD, 3 3 V 920 344 189

BXT ML4 BD 48 BXT Protection Module LifeCheck BD, 5 4 V 920 345 189

BXT ML4 BD 60 BXT Protection Module LifeCheck BD, 7 0 V 920 346 189

BXT ML4 BD 180 BXT Protection Module LifeCheck BD, 1 80 V 920 347 189

BXT ML4 BD EX 24 BXT Protection Module Li feCheck BD EX,24 V 920 381 314

BXT ML4 BD HF 5 BXT Protection Module LifeCheck BD HF, 6 V 920 371 193

BXT ML4 BD HF 24 BXT Protection Module Li feCheck BD HF, 24 V 920 375 193

BXT ML4 BE 5 BXT Protection Module LifeCheck BE, 6 V 920 320 188

BXT ML4 BE 12 BXT Protection Module LifeCheck BE, 1 5 V 920 322 188

BXT ML4 BE 24 BXT Protection Module LifeCheck BE, 3 3 V 920 324 188

BXT ML4 BE 36 BXT Protection Module LifeCheck BE, 4 5 V 920 336 188

BXT ML4 BE 48 BXT Protection Module LifeCheck BE, 5 4 V 920 325 188

BXT ML4 BE 60 BXT Protection Module LifeCheck BE, 7 0 V 920 326 188

BXT ML4 BE 180 BXT Protection Module LifeCheck BE, 1 80 V 920 327 188

BXT ML4 BE C 12 BXT Protection Module LifeCheck BE C ,12 V 920 362 191

BXT ML4 BE C 24 BXT Protection Module LifeCheck BE C ,33 V 920 364 191

BXT ML4 BE HF 5 BXT Protection Module LifeCheck BE HF, 6 V 920 370 192

BXT ML4 MY 250 BXT Protection Module LifeCheck MY, 320 V 920 389 194

BXTU ML4 BD 0-180 BXT Protection Module LifeCheck BD, 0-180 V 920 349 181

BXTU ML2 BD S 0-180 BXT Protection Module LifeCheck BD S, 0-180 V 920 249 182

DB 1 255 H DEHNbloc 1 255 H 900 222 59

DB 1 440 DEHNbloc 1 440 900 159 61

DB 3 255 H DEHNbloc 3 255 H 900 120 59

DB M 1 150 DEHNbloc Maxi modular 1 150 961 110 46

DB M 1 150 FM DEHNbloc Maxi modular 1 150 FM 961 115 47

DB M 1 255 DEHNbloc Maxi modular 1 255 961 120 46

DB M 1 255 FM DEHNbloc Maxi modular 1 255 FM 961 125 47

DB M 1 320 DEHNbloc Maxi modular 1 320 961 130 46

DB M 1 320 FM DEHNbloc Maxi modular 1 320 FM 961 135 47

DB M MOD 150 Protection module for DB M, 150 V 961 001 48

DB M MOD 255 Protection module for DB M, 255 V 961 002 48

DB M MOD 320 Protection module for DB M, 320 V 961 003 48

DB NH00 255 H DEHNbloc NH00 255 H 900 273 60

DBM 1 255 S DEHNbloc Maxi S 900 220 55

DBM 1 440 DEHNbloc Maxi 1 440 961 140 52

DBM 1 440 FM DEHNbloc Maxi 1 440 FM 961 145 52

DBM 1 760 FM DEHNbloc Maxi 1 760 FM 961 175 53DBM NH00 255 DEHNbloc Maxi NH00 900 255 50

DCO RK D 5 24 DEHNconnect RK D, +24/-5 V 919 986 216

DCO RK E 12 DEHNconnect RK E, 12 V 919 987 215

Page 378: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 378/382

376 www.dehn.de

DCO RK E 24 DEHNconnect RK E, 24 V 919 988 215

DCO RK E 48 DEHNconnect RK E, 48 V 919 989 215

DCO RK E 60 DEHNconnect RK E, 60 V 919 990 215

DCO RK MD 12 DEHNconnect RK MD, 12 V 919 940 211

DCO RK MD 24 DEHNconnect RK MD, 24 V 919 941 211DCO RK MD 48 DEHNconnect RK MD, 48 V 919 942 212

DCO RK MD 110 DEHNconnect RK MD, 110 V 919 943 213

DCO RK MD EX 24 DEHNconnect RK MD EX, 24 V 919 960 323

DCO RK MD HF 5 DEHNconnect RK MD HF, 5 V 919 970 214

DCO RK ME 12 DEHNconnect RK ME, 12 V 919 920 210

DCO RK ME 24 DEHNconnect RK ME, 24 V 919 921 210

DCO RK ME 48 DEHNconnect RK ME, 48 V 919 922 210

DCO RK ME 110 DEHNconnect RK ME, 110 V 919 923 210

DFL A 255 DEHNflex A 924 389 134

DFL D 255 DEHNflex D 924 395 135

DFL M 255 DEHNflex M 924 396 133

DG 1000 DEHNguard 1000 950 102 111

DG 1000 FM DEHNguard 1000 FM 950 112 111

DG M TN 150 DEHNguard modular TN, 2-pole 952 201 83

DG M TN 150 FM DEHNguard modular TN FM, 2-pole 952 206 84

DG M TN 275 DEHNguard modular TN, 2-pole 952 200 83

DG M TN 275 FM DEHNguard modular TN FM, 2-pole 952 205 84

DG M TN CI 275 DEHNguard modular TN CI, 2-pole 952 173 73

DG M TN CI 275 FM DEHNguard modular TN CI FM, 2-pole 952 178 73

DG M TNC 150 DEHNguard modular TNC, 3-pole 952 313 77

DG M TNC 150 FM DEHNguard modular TNC FM, 3-pole 952 318 78

DG M TNC 275 DEHNguard modular TNC, 3-pole 952 300 77

DG M TNC 275 FM DEHNguard modular TNC FM, 3-pole 952 305 78

DG M TNC 385 DEHNguard modular TNC, 3-pole 952 314 77

DG M TNC 385 FM DEHNguard modular TNC FM, 3-pole 952 319 78

DG M TNC 440 DEHNguard modular TNC, 3-pole 952 303 77

DG M TNC 440 FM DEHNguard modular TNC FM, 3-pole 952 308 78

DG M TNC CI 275 DEHNguard modular TNC CI, 3-pole 952 304 70

DG M TNC CI 275 FM DEHNguard modular TNC CI FM, 3 -pole 952 309 70

DG M TNS 150 DEHNguard modular TNS, 4-pole 952 403 79

DG M TNS 150 FM DEHNguard modular TNS FM, 4-pole 952 408 80

DG M TNS 275 DEHNguard modular TNS, 4-pole 952 400 79

DG M TNS 275 FM DEHNguard modular TNS FM, 4-pole 952 405 80

DG M TNS 385 DEHNguard modular TNS, 4-pole 952 404 79

DG M TNS 385 FM DEHNguard modular TNS FM, 4-pole 952 409 80

DG M TNS CI 275 DEHNguard modular TNS CI, 4-pole 952 401 71

DG M TNS CI 275 FM DEHNguard modular TNS CI FM, 4 -pole 952 406 71

DG M TT 2P 275 DEHNguard modular TT, 2-pole 952 110 85DG M TT 2P 275 FM DEHNguard modular TT FM, 2-pole 952 115 86

DG M TT 2P 320 DEHNguard modular TT, 2-pole 952 130 85

DG M TT 2P 320 FM DEHNguard modular TT FM, 2-pole 952 135 86

DG M TT 2P 385 DEHNguard modular TT, 2-pole 952 111 85

DG M TT 2P 385 FM DEHNguard modular TT FM, 2-pole 952 116 86

DG M TT 2P CI 275 DEHNguard modular TT CI, 2-pole 952 171 74

DG M TT 2P CI 275 FM DEHNguard modular TT CI FM, 2 -pole 952 176 74

DG M TT 275 DEHNguard modular TT, 4-pole 952 310 81

DG M TT 275 FM DEHNguard modular TT FM, 4-pole 952 315 82

DG M TT 320 DEHNguard modular TT, 4-pole 952 320 81

DG M TT 320 FM DEHNguard modular TT FM, 4-pole 952 325 82

DG M TT 385 DEHNguard modular TT, 4-pole 952 311 81

DG M TT 385 FM DEHNguard modular TT FM, 4-pole 952 316 82DG M TT CI 275 DEHNguard modular TT CI, 4-pole 952 322 72

DG M TT CI 275 FM DEHNguard modular TT CI FM, 4-pole 952 327 72

DG M WE 600 DEHNguard modular M WE, 3-pole 952 302 87

DG M WE 600 FM DEHNguard modular M WE FM, 3-pole 952 307 87

DG M YPV SCI 600 DEHNguard M YPV SCI 600 952 511 105

DG M YPV SCI 600 FM DEHNguard M YPV SCI 600 FM 952 516 106

DG M YPV SCI 1000 DEHNguard M YPV SCI 1000 952 510 105

DG M YPV SCI 1000 FM DEHNguard M YPV SCI 1000 FM 952 515 106DG M YPV SCI 1200 DEHNguard M YPV SCI 1200 952 512 105

DG M YPV SCI 1200 FM DEHNguard M YPV SCI 1200 FM 952 517 106

DG MOD 48 Protection Module for DG M and DG S, 48 V 952 018 95

DG MOD 75 Protection Module for DG M and DG S, 75 V 952 011 95

DG MOD 75 VA Protection Module for DG S VA, 75 V 952 025 97

DG MOD 150 Protection Module for DG M and DG S, 150 V 952 012 95

DG MOD 275 Protection Module for DG M and DG S, 275 V 952 010 95

DG MOD 275 VA Protection Module for DG S VA, 275 V 952 027 97

DG MOD 320 Protection Module for DG M and DG S, 320 V 952 013 95

DG MOD 385 Protection Module for DG M and DG S, 385 V 952 014 95

DG MOD 385 VA Protection Module for DG S VA, 385 V 952 029 97

DG MOD 440 Protection Module for DG M and DG S, 440 V 952 015 95

DG MOD 600 Protection Module for DG M and DG S, 600 V 952 016 95

DG MOD 750 Protection Module for DG M and DG S, 750 V 952 017 95

DG MOD CI 275 Protection Module for DG M CI, 275 V 952 020 98

DG MOD NPE N-PE Spark-gap-based prot. module, 255 V 952 050 96

DG MOD PV SCI 300 Protection Module for DG M YPV SCI, 300 V 952 053 97

DG MOD PV SCI 500 Protection Module for DG M YPV SCI, 500 V 952 051 97

DG MOD PV SCI 600 Protection Module for DG M YPV SCI, 600 V 952 054 97

DG PV 500 SCP DEHNguard PV 500 SCP 950 500 108

DG PV 500 SCP FM DEHNguard PV 500 SCP FM 950 505 109

DG PV 700 SCP DEHNguard PV 700 SCP 950 501 108

DG PV 700 SCP FM DEHNguard PV 700 SCP FM 950 506 109

DG PV 1200 SCP DEHNguard PV 1200 SCP 950 502 108

DG PV 1200 SCP FM DEHNguard PV 1200 SCP FM 950 507 109

DG S 48 DEHNguard S, 48 V 952 078 89

DG S 48 FM DEHNguard S FM, 48 V 952 098 90

DG S 75 DEHNguard S, 75 V 952 071 89

DG S 75 FM DEHNguard S FM, 75 V 952 091 90

DG S 75 VA DEHNguard S VA, 75 V 952 080 113

DG S 75 VA FM DEHNguard S VA FM, 75 V 952 085 114

DG S 150 DEHNguard S, 150 V 952 072 89

DG S 150 FM DEHNguard S FM, 150 V 952 092 90

DG S 275 DEHNguard S, 275 V 952 070 89

DG S 275 FM DEHNguard S FM, 275 V 952 090 90

DG S 275 VA DEHNguard S VA, 275 V 952 082 113

DG S 275 VA FM DEHNguard S VA FM, 275 V 952 087 114

DG S CI 275 DEHNguard S CI, 275 V 952 079 75DG S CI 275 FM DEHNguard S CI FM, 275 V 952 099 75

DG S 320 DEHNguard S, 320 V 952 073 89

DG S 320 FM DEHNguard S FM, 320 V 952 093 90

DG S 385 DEHNguard S, 385 V 952 074 89

DG S 385 FM DEHNguard S FM, 385 V 952 094 90

DG S 385 VA DEHNguard S VA, 385 V 952 084 113

DG S 385 VA FM DEHNguard S VA FM, 385 V 952 089 114

DG S 440 DEHNguard S, 440 V 952 075 89

DG S 440 FM DEHNguard S FM, 440 V 952 095 90

DG S 600 DEHNguard S, 600 V 952 076 89

DG S 600 FM DEHNguard S FM, 600 V 952 096 90

DG S WE 600 DEHNguard S WE, 600 V 952 077 91

DG S WE 600 FM DEHNguard S WE FM, 600 V 952 097 91DG T H 275 LI DEHNguard T H LI, single-pole, 275 V 950 120 103

DG T H 385 LI DEHNguard T H LI, single-pole, 385 V 950 121 103

DG TNC H230 400 LI DEHNguard TNC H LI, 3-pole 950 160 100

Type Product Part No. Page Type Product Part No. Page

Type / Product Index

Page 379: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 379/382

377www.dehn.de

DG TNS H230 400 LI DEHNguard TNS H LI, 4-pole 950 170 101

DG TT H230 400 LI DEHNguard TT H LI, 4-pole 950 150 102

DG TT H230 400 LI385 DEHNguard TT H LI, 4-pole, 385 V 950 151 102

DGA AG BNC DEHNgate 929 043 275

DGA AG N DEHNgate 929 045 275DGA AG U DEHNgate 929 057 275

DGA BNC VCD DEHNgate 909 710 271

DGA BNC VCID DEHNgate 909 711 271

DGA F 1.6 5.6 DEHNgate 929 040 273

DGA FF TV DEHNgate 909 703 272

DGA G BNC DEHNgate 929 042 274

DGA G N DEHNgate 929 044 274

DGA GF TV DEHNgate 909 704 272

DGA GFF TV DEHNgate 909 705 272

DGA L4 7 16 B DEHNgate 929 048 277

DGA L4 7 16 S DEHNgate 929 047 277

DGA L4 N EB DEHNgate 929 059 278

DGA LG 7 16 DEHNgate 929 046 276

DGA LG 7 16 X DEHNgate 929 446 276

DGP B NH00 N 255 DEHNgap B/NH00/n 900 269 67

DGP BN 255 DEHNgap B/n 900 132 66

DGP C MOD N-PE Spark-gap-based prot. module f. DGP C S 952 060 96

DGP C S DEHNgap C S 952 030 93

DGP C S FM DEHNgap C S FM 952 035 93

DGP M 255 DEHNgap M 255 961 101 64

DGP M 255 FM DEHNgap M 255 FM 961 105 64

DGP M MOD 255 N-PE Spark-gap-based prot. module for DGP M 961 010 64

DGPM 1 255 S DEHNgap Maxi 1 255 S 900 050 65

DGPM 440 DEHNgap Maxi 440 961 160 68

DGPM 440 FM DEHNgap Maxi 440 FM 961 165 68

DISO 3 DEHNisola, SPD monitoring device 910 600 365

DK 25 Feed-through Terminal, 25 mm2 952 699 145

DLI ISDN I DEHNlink ISDN/I 929 024 262

DLI TC 2 I DEHNlink TC 2 929 028 263

DLI TC BT DEHNlink BT 929 026 266

DLI TC ECO RJ12 DEHNlink-Denmark 929 081 264

DLM PV 1000 DEHNlimit 900 330 43

DPA M CAT6 RJ45H 48 Patch cable with surge protection 929 110 254

DPA M CAT6 RJ45S 48 Patch cable with surge protection 929 100 254

DPA M CLE RJ45B 48 Patch cable with surge protection 929 121 255

DPG LSA 30 P DEHN enclosure for equ ipotent ial bonding,15 kA 906 100 242

DPG LSA 60 P DEHN enclosure for equ ipotent ial bonding,30 kA 906 101 242

DPG LSA 120 P DEHN enclosure for equ ipotent ial bonding,50 kA 906 102 242DPG LSA 220 P DEHN enclosure for equ ipotent ial bonding,50 kA 906 103 242

DPI CD EXD 230 24 M DEHNpipe 929 969 310

DPI CD EXD 230 24 N DEHNpipe 929 970 310

DPI CD EXD 24 M DEHNpipe 929 962 308

DPI CD EXD 24 N DEHNpipe 929 964 308

DPI CD EXI 24 M DEHNpipe 929 961 306

DPI CD EXI 24 N DEHNpipe 929 963 306

DPI CD HF EXD 5 M DEHNpipe 929 971 309

DPI MD 24 M 2S DEHNpipe 929 941 298

DPI MD EX 24 M 2 DEHNpipe 929 960 303

DPI ME 24 N A2G DEHNpipe 929 921 299

DPL 10 G3 110 LSA-Plus Technology, 10 DA 907 214 240

DPL 10 G3 110 FSD LSA-Plus Technology, 10 DA 907 216 240DPRO 230 DEHNpro 909 230 139

DPRO 230 SE DEHNpro 909 235 139

DPRO 230 F DEHNpro integrated mains filter 909 240 140

DPRO 230 SE F DEHNpro integrated mains filter 909 245 140

DPRO 230 ISDN Protection adapter for ISDN/Ethernet applications 909 320 340

DPRO 230 SE ISDN Protection adapter for ISDN/Ethernet applications 909 325 340

DPRO 230 LAN100 Protection adapter for LAN applications 909 321 341

DPRO 230 SE LAN100 Protection adapter for LAN app lications 909 326 341DPRO 230 NT Prot. adapter for NTBA/DSL splitter applications 909 310 339

DPRO 230 SE NT Prot .adapter for NTBA/DSL spli tte r appl ications 909 315 339

DPRO 230 TV Protection adapter for TV/radio applications 909 300 338

DPRO 230 SE TV Protection adapter for TV/rad io applications 909 305 338

DR M 2P 30 DEHNrail modular, 2-pole, 24 V 953 201 120

DR M 2P 30 FM DEHNrail modular FM, 2-pole, 24 V 953 206 121

DR M 2P 60 DEHNrail modular, 2-pole, 48 V 953 202 120

DR M 2P 60 FM DEHNrail modular FM, 2-pole, 48 V 953 207 121

DR M 2P 75 DEHNrail modular, 2-pole, 60 V 953 203 120

DR M 2P 75 FM DEHNrail modular FM, 2-pole, 60 V 953 208 121

DR M 2P 150 DEHNrail modular, 2-pole, 120 V 953 204 120

DR M 2P 150 FM DEHNrail modular FM, 2-pole, 120 V 953 209 121

DR M 2P 255 DEHNrail modular, 2-pole, 230 V 953 200 120

DR M 2P 255 FM DEHNrail modular FM, 2-pole, 230 V 953 205 121

DR M 4P 255 DEHNrail modular, 4-pole 953 400 123

DR M 4P 255 FM DEHNrail modular FM, 4-pole 953 405 123

DR MOD 30 Protection module for DR M 2P, 2 -pole, 30 V 953 011 124

DR MOD 60 Protection module for DR M 2P, 2 -pole, 60 V 953 012 124

DR MOD 75 Protection module for DR M 2P, 2 -pole, 75 V 953 013 124

DR MOD 150 Protection module for DR M 2P, 2 -pole, 1 50 V 953 014 124

DR MOD 255 Protection module for DR M 2P, 2 -pole, 2 55 V 953 010 124

DR MOD 4P 255 Protection module for DR M 4P, 4-pole, 255 V 953 020 124

DRC LC M3+ LifeCheck SPD test device 910 653 362

DRC MCM XT Condition Monitoring System LifeCheck 910 695 360

DRL 10 B 180 DRL plug-in SPD block (10 pairs), 180 V 907 400 231

DRL 10 B 180 FSD DRL plug-in SPD block (10 pairs),fault indication 907 401 232

DRL HD 5 DEHNrapid LSA HD, 6 V 907 465 236

DRL HD 24 DEHNrapid LSA HD, 28 V 907 470 236

DRL PD 180 DEHNrapid LSA PD, 180 V 907 430 235

DRL RD 5 DEHNrapid LSA RD, 6 V 907 440 234

DRL RD 12 DEHNrapid LSA RD, 14 V 907 441 234

DRL RD 24 DEHNrapid LSA RD, 28 V 907 442 234

DRL RD 48 DEHNrapid LSA RD, 54 V 907 443 234

DRL RD 60 DEHNrapid LSA RD, 70 V 907 444 234

DRL RD 110 DEHNrapid LSA RD, 110 V 907 445 234

DRL RE 5 DEHNrapid LSA RE, 6 V 907 420 233

DRL RE 12 DEHNrapid LSA RE, 14 V 907 421 233

DRL RE 24 DEHNrapid LSA RE, 28 V 907 422 233DRL RE 48 DEHNrapid LSA RE, 54 V 907 423 233

DRL RE 60 DEHNrapid LSA RE, 70 V 907 424 233

DRL RE 180 DEHNrapid LSA RE, 180 V 907 425 233

DSA 230 LA DEHNsafe 924 370 129

DSI E 3 Optical-Fibre-Based Receiver Module 910 631 57

DSM ISDN SK SPD for telecomm. terminal equipment 924 270 290

DSM TC 2 SK SPD for telecomm. terminal equipment 924 272 291

DSM TM SPD for Data Sockets 924 274 260

DV M TN 255 DEHNventil modular TN, 2-pole 951 200 35

DV M TN 255 FM DEHNventil modular TN FM, 2-pole 951 205 35

DV M TNC 255 DEHNventil modular TNC, 3-pole 951 300 32

DV M TNC 255 FM DEHNventil modular TNC FM, 3-pole 951 305 32

DV M TNS 255 DEHNventil modular TNS, 4-pole 951 400 33DV M TNS 255 FM DEHNventil modular TNS FM, 4-pole 951 405 33

DV M TT 255 DEHNventil modular TT, 4-pole 951 310 34

DV M TT 255 FM DEHNventil modular TT FM, 4-pole 951 315 34

Type Product Part No. Page Type Product Part No. Page

Type / Product Index

Page 380: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 380/382

378 www.dehn.de

Type / Product Index

DV M TT 2P 255 DEHNventil modular TT 2P, 2-pole 951 110 36

DV M TT 2P 255 FM DEHNventil modular TT 2P FM, 2-pole 951 115 36

DV MOD 255 Spark-gap-based protection module 951 001 38

DV MOD NPE 50 N PE Spark-gap-based protect ion module, 50 kA 951 050 38

DV MOD NPE 100 N PE Spark-gap-based protection module, 190 kA 951 100 38DV ZP TNC 255 DEHNventil ZP TNC 255 900 390 40

DV ZP TT 255 DEHNventil ZP TT 255 900 391 41

EB 1 4 9 Earthing clip, 4-pole, single-phase 900 417 151

EB 4 F Earthing blocks 4xF 929 095 279

EB DG 1000 1 3 DB Earthing clip, 3-pole, single-phase 900 411 151

EF 10 DRL Earthing frame 907 498 237

EG NET PRO 10X 19” Enclosure for NET Protector 929 234 252

EG NET PRO 10X 3HE Enclosure for NET Protector 929 235 252

EG NET PRO 19” Enclosure for NET Protector 929 034 249

EL 16 B17 Cable Lug with Earth Conductor 929 096 279

EL2 38EA LSA Earth Conductor Block, 38-pole LSA-PLUS 907 993 244

ER DPI M20 Set of Earthing Rings for DEHNpipe 929 996 300ES 2X2AP 10 ST Earthing busbars St/tZn, 2 x2 connections 472 023 356

ES 2X2AP 10 V2A Earthing busbars St/St, 2 x2 connections 472 109 356

ES 2X3AP 10 ST Earthing busbars St/tZn, 2 x3 connections 472 022 356

ES 2X3AP 10 V2A Earthing busbars St/St, 2 x3 connections 472 119 356

ES 2X4AP 10 V2A Earthing busbars St/tZn, 2 x4 connections 472 129 356

ES 2X4AP ST Earthing busbars St/tZn, 2x4 connections 472 024 356

ES 2X6AP 10 ST Earthing busbars St/tZn, 2 x6 connections 472 021 356

ES 2X6AP 10 V2A Earthing busbars St/tZn, 2 x6 connections 472 139 356

EX BRS 27 Pipe clamp for use in hazardous areas 540 821 351

EX BRS 90 Pipe clamp for use in hazardous areas 540 801 351

EX BRS 300 Pipe clamp for use in hazardous areas 540 803 351

EX BRS 500 Pipe clamp for use in hazardous areas 540 805 351

EXFS 100 Ex Isolating Spark Gap, 100 kA 923 100 345

EXFS 100 KU Ex Isolating Spark Gap, 100 kA 923 101 346

EXFS KU Ex Isolating Spark Gap, 50 kA 923 019 349

EXFS L100 Ex Isolating Spark Gap, 50 kA 923 060 348

EXFS L200 Ex Isolating Spark Gap, 50 kA 923 061 348

EXFS L300 Ex Isolating Spark Gap, 50 kA 923 062 348

FBH 6 CU Tape conductors with pressure plate 12 mm, C u 277 237 357

FBH 6 ST Tape conductors with pressure plate 12 mm, S t/tZn 277 230 357

FBH 6 V2A Tape conductors with pressure p late 12 mm,St/St 277 239 357

FBH 11 ST Tape conductors with pressure plate 11 mm,S t/tZn 277 240 357

FS 9E HS 12 Fine Surge Protection Adapter FS 12 V 924 019 283

FS 9E PB 6 Fine Surge Protection Adapter FS 6 V 924 017 282

FS 15E 5 Fine Surge Protection Adapter FS 5 V 924 016 284FS 25E HS 12 Fine Surge Protection Adapter FS 12 V 924 018 285

GDT 230 B3 Gas Discharge Tube for DRL 10 907 218 238

GDT 230 B3 FSD Gas Discharge Tube for DRL 10 907 219 238

GDT 230 G3 Gas Discharge Tube for DPL 10 G3 907 208 240

GDT 230 G3 FSD Gas Discharge Tube for DPL 10 G3 907 217 240

GDT DGA 90 Gas Discharge Tube for DEHNgate 929 497 279

GDT DGA 90 X Gas Discharge Tube for DEHNgatewith screw cap 929 496 279

GDT DGA 230 Gas Discharge Tube for DEHNgate 929 498 279

GDT DGA 470 Gas Discharge Tube for DEHNgate 929 499 279

IF1 Connection Bracket Type IF -SET- 923 011 345

IF3 Connection Bracket Type IF -SET- 923 016 345

IGA 6 IP54 Insulating Enclosure 6 mods. 902 485 148

IGA 10 V2 IP54 Insulating Enclosure 10 mods. 902 315 146

IGA 12 IP54 Insulating Enclosure 12 mods. 902 471 147

IGA 24 IP54 Insulating Enclosure 24 mods. 902 472 147

IS PAS M10 Isolator for PAS Industry 472 210 356

ITAK EXI BXT 24 IT Connection Box 989 408 321

KB 10 DCO RK Jumper Bar for DEHNconnect RK 919 880 217

KFSU Ex-Isolating Spark Gap 923 021 343

KS 198 PAS Terminal Bar, brass, length 198 mm 563 016 355

KS 398 PAS Terminal bar, brass, length 398 mm 563 017 355

KS 798 PAS Terminal bar, brass, length 798 mm 563 018 355

KV FE UNI Wedge Connector St/tZn, with grid position 308 001 357

KV M20 MS 10.5 EMC Cable Gland 929 984 300

KV S M20 MS 9.5 EMC Cable Gland 929 982 300

LCS DRC BCT LifeCheck-Sensor für DRC BCT 910 654 362

LCS DRC BXT LifeCheck-Sensor für DRC BXT 910 652 362

LWL DSI 18M Optical fibre, length 18 m 910 642 57

LWL ST DSI Plug for Optical Fibre 910 641 57

MB2 10 LSA Mounting Frame 10 DA LSA-PLUS 907 995 243

MMVK R16 R25 STBL MAXI MV clamp, St/tZn 308 040 357

MMVK R16 R25 ST MAXI MV clamp, St/bare 308 041 357MS ALGA 5 X Mounting Set for Enclosures 906 059 335

MS DPA Mounting Set for DEHNpatch 929 199 254

MVS 1 2 Busbar single-phase, 2-pole 900 617 149

MVS 1 3 Busbar single-phase, 3-pole 900 615 149

MVS 1 4 Busbar single-phase, 4-pole 900 610 149

MVS 1 6 Busbar single-phase, 6-pole 900 815 149

MVS 1 7 Busbar single-phase, 7-pole 900 848 150

MVS 1 8 Busbar single-phase, 8-pole 900 611 150

MVS 1 57 Busbar single-phase, 57-pole 900 612 150

MVS 3 6 Busbar 3-phase, 6-pole 900 595 150

MVS 3 6 8 Busbar 3-phase, 8-pole 900 813 150

MVS 4 8 11 Busbar 4-phase, 11-pole 900 814 151

MVS 4 56 Busbar 4-phase, 56-pole 900 614 151

NET PRO 10X TC1 RST NET Protector 10X TC1 RST 929 230 252

NET PRO 4TP NET Protector 4TP 929 035 249

NET PRO 4TP 30 NET Protector 4TP 30 929 037 249

NET PRO E1 LSA G703 NET Protector E1 LSA G703 929 075 251

NET PRO LSA 4TP NET Protector/LSA-PLUS/4TP 929 036 249

Type Product Part No. Page Type Product Part No. Page

Page 381: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 381/382

379www.dehn.de

Type / Product Index

Type Product Part No. Page Type Product Part No. Page

NET PRO TC 2 NET Protector TC 2, 110 V 929 071 250

NET PRO TC 2 LSA NET Protector TC 2 LSA,+B433 110 V 929 072 250

NF 10 Mains Filter 10 A 912 254 125

NSM PRO AZ NSM Protector DELTA profile, anthracite 924 339 137

NSM PRO EW NSM Protector DELTA profile, studio white 924 342 137NSM PRO SI NSM Protector DELTA profile, silver 924 337 137

NSM PRO TW NSM Protector DELTA profile, t itanium white 924 335 137

P 2 Impulse Meter P2 910 502 366

PA BXT Test adapter for BXT 910 508 364

PA DRL Test adapter for BCT 910 507 364

PAS 9AK Earthing Busbar 563 050 355

PAS 11AK Earthing Busbar 563 200 355

PAS 11AK UV Earthing Busbar 563 201 355

PAS 6RK OH Earthing Busbar 563 105 355

PAS 9RK Earthing Busbar 563 020 355

PAS 10RK Earthing Busbar 563 010 355

PAS 14RK Earthing Busbar 563 030 355PAS I 10AP M10 CU Earthing Busbar 472 217 356

PAS I 10AP M10 V2A Earthing Busbar 472 219 356

PAS I 12AP M10 CU Earthing Busbar 472 237 356

PAS I 12AP M10 V2A Earthing Busbar 472 239 356

PAS I 6AP M10 CU Earthing Busbar 472 207 356

PAS I 6AP M10 V2A Earthing Busbar 472 209 356

PAS I 8AP M10 CU Earthing Busbar 472 227 356

PAS I 8AP M10 V2A Earthing Busbar 472 229 356

PM 20 SPD Test Device 910 511 364

RK 16 PAS Modular Terminal, -16 mm2 for EB 563 011 355

RK 95 PAS Modular Terminal, 16-95 mm2 for EB 563 013 355

RK FL30 PAS Modular Terminal, flat strip -30 mm for EB 563 012 355RK FL40 PAS Modular Terminal, flat strip -40 mm for EB 563 019 355

SA KRF 10 V2A Contact Force Spring f. shield connection 4-10 mm 919 031 333

SA KRF 15 V2A Contact Force Spring f. shield connection 9-15 mm 919 032 333

SA KRF 22 V2A Contact Force Spring f. shield connection 14-22 mm 919 033 333

SA KRF 29 V2A Contact Force Spring f. shield connection 18,5-29mm919 034 333

SA KRF 37 V2A Contact Force Spring f. shield connection 23,5-37mm919 035 333

SA KRF 50 V2A Contact Force Spring f. shield connection 31-50 mm 919 036 333

SA KRF 70 V2A Contact Force Spring f. shield connection 44-70 mm 919 037 333

SA KRF 94 V2A Contact Force Spring f. shield connection 58-94 mm 919 038 333

SAK 10 AS V4A Shield ing Terminal, stainless steel, Rd 5-10 mm 308 403 326

SAK 14 AS V4A Shield ing Terminal, stainless steel, Rd 8-14 mm 308 404 326

SAK 18 AS V4A Shielding Terminal, s ta inless steel ,Rd 13-18 mm 308 405 326SAK 21 AS V4A Shielding Terminal, s ta inless steel ,Rd 17-21 mm 308 406 326

SAK 26 AS V4A Shielding Terminal, s ta inless steel ,Rd 19-26 mm 308 407 326

SAK 33 AS V4A Shielding Terminal, s ta inless steel ,Rd 25-33 mm 308 408 326

SAK 6.5 SN MS Shielding Terminal, s ta inless steel ,Rd 1,5-6,5 mm 919 010 329

SAK 11 SN MS Shield ing Terminal, stainless steel, Rd 5-11 mm 919 011 329

SAK BXT LR EMC spring terminals 920 395 202

SB PAS RK Bar Holder, plastic, grey 563 014 355

SDS 1 Voltage limiting device, SDS 1 923 110 354

SDS 2 Voltage limiting device, SDS 2 923 117 354

SDS 3 Voltage limiting device, SDS 3 923 116 354SDS 4 Voltage limiting device, SDS 4 923 118 354

SDS 5 Voltage limiting device, SDS 5 923 119 354

SFL PRO SFL Protector 912 260 142

SFL PRO SE SFL Protector 912 261 142

SH 18X3 K Bar Holder, plastic 919 014 330

SH1 18X3 ST Bar Holder, steel 919 012 330

SH2 18X3 ST Bar Holder ISO 919 013 330

SKB 19 9M SW Selfbonding Rubber Tape 919 030 333

SLK 16 PE Terminal 910 099 335

SN 18X3 CU 1000 Busbar, tinned 919 016 329

SPS PRO SPS Protector 912 253 127

SR DRL Label Holder 907 497 238

ST AS SAK K Bar Support, plastic 308 425 327

STAK 2X16 Pin-shape terminal 900 589 145

STC 230 STC Surge Protection Module 924 350 131

T C H 255 N-PE Spark-gap-based-Protection Module 900 216 102

T H 275 LI Protection Module with Pro-Aktive Thermo Control 950 130 103

T H 385 LI Protection Module with Pro-Aktive Thermo Control 950 131 103

TFS Isolating Spark Gap 923 023 343

TL2 10DA CC Routing module with LSA tension spring 907 991 245

TL2 10DA LSA Disconnection Modules 10 TC LSA-PLUS 907 996 244

TW DRC MCM EX Partition 910 697 319

UGKF BNC SPD for Comupter Systems 929 010 268

USB NANO 485 USB interface converter o f type USB NANO 485 910 486 360USD 9 V24 S B Cable Adapter 924 061 286

USD 15 V11 S B Cable Adapter 924 051 287

USD 25 V24 HS S B Cable Adapter 924 046 288

V NH00 280 VNH Surge Arrester, Size 00 900 261 116

V NH00 280 FM VNH FM Surge Arrester, Size 00 900 263 116

V NH1 280 VNH Surge Arrester, Size 1 900 270 116

VA NH00 280 VANH Surge Arrester, Size 00 900 262 117

VA NH00 280 FM VANH FM Surge Arrester, Size 00 900 264 117

VA NH1 280 VANH 280, Size 1 900 271 117

VC 280 2 Mains Surge Protection Module, 2-pole 900 471 144

VK A R22 F40 STBL Connection Clamp St/bare 308 030 357

VK A UNI ST Connection Clamp St/tZn 308 025 357VK A UNI V2 ST Connection Clamp St/tZn 308 026 357

VK EH R10 F30 ST Connection Clamp St/tZn 308 120 357

VK EH R10 F30 V2A Connection Clamp StSt (V2A) 308 129 357

ZAP STW Central Covering Plate for DEHNsafe 924 329 129

Page 382: Dehn Prenaponska zaštita

7/18/2019 Dehn Prenaponska zaštita

http://slidepdf.com/reader/full/dehn-prenaponska-zastita 382/382

Key Words

Accessories / Construction Kit 355

Accessories for BLITZDUCTOR® XT 202

Accessories for BLITZDUCTOR® XTEx (i) 317

Accessories for DEHNconnect 217

Accessories for DEHNgate 279

Accessories for DEHNpipe 300

Accessories for DEHNpipe MD Ex (i) 304

Accessories for LSA Technology 243

Accessories for terminal blocksystems 325

Accessories Red/Line 145

Aluminium enclosure 334

Aluminium enclosure for Ex(i)-surge arresters 334

Anchor bar 326

AS IBAS 294

BLITZDUCTOR® VT 218/256

BLITZDUCTOR® VT KKS 224

BLITZDUCTOR® XT 184BLITZDUCTOR® XT Ex (i) 311

BLITZDUCTOR® XTU 179

Busbar 329

Busbars / Modular wiring system 149

BUStector 292

Combined adapters 337

Combined lightning current and surgearrester for cathodic corrosionprotection systems 224

Combined SPDs – Type 1 31

Compact protection for terminalequipment 143

Compact SPDs for DIN railMounting 209

Components for foundationearthing electrodes 357

Components for ring equipotentialbonding 357

Condition monitoring systemLifeCheck® 359

Connecting clamps 357

Constant force spring 333

Coordinated lightning current arrester 49

Coordinated lightning currentarrester for busbars 54

Cross-reference Red/Line 29

Cross-reference Yellow/Line 154

DEHNbloc® 58

DEHNbloc® M 45

DEHNbloc® Maxi 49

DEHNbloc® Maxi S 54

DEHNbloc® Maxi 440/760 51

DEHNconnect RK 209

DEHNconnect RK E (i) 322

DEHNgate 269

DEHNguard® ... H LI 99

DEHNguard® modular 76

DEHNguard® modular CI,with integrated backup fuse 69

DEHNguard® S 88

DEHNguard® S ... VA 112

DEHNguard® PV ... SCP 107

DEHNguard® M YPV SCI 104

DEHNguard® 1000 FM 110

DEHNisola 365

DEHNlimit 42

DEHNlink 261

DEHNlink TC BT 265

DEHNpatch 253

DEHNpipe 297

DEHNpipe CD Ex (d) 307

DEHNpipe CD Ex (i) 305

DEHNpipe MD Ex (i) 301

DEHN enclosure for equipotential bon-

ding 241DEHNprotector 138/337

DEHNrail modular 119

DEHNrail modular, multipole 122

DEHNrapid® LSA 229

DEHNrapid® LSA plug-in SPD block(without SPDs) 238

DEHNsafe 128

DEHNsignal 56

DEHNventil® modular 31

DEHNventil® ZP 39

Disconnection block 244

Discontinued products RL/YL 29/154

DPL 10 G3 239

DSM 289

DSM TM 259

Earthing busbars 356

Earth conductor block 244

Earthing module 202

Easy choice Red/Line 18

Easy choice according toInterface / Signal 156

EMC spring terminals 202

Enclosure / Protective conductorterminal 334

Enclosure system for SPDs

protecting IT equipment 241Equipotential bonding 355

Equipotential bonding bars 355/356

EXFS 100 / EXFS 100 KU 344

EXFS L / EXFS KU 347

Flexible protection of terminalequipment 132

FS / USD 281

Impulse meter 366

Information technology systems 153

Insertion tools 243

Insulating enclosure 146

Insulated rail support 330

Insulated busbar support 327

Isolating spark gaps 343ITAK Ex (i) 320

Key to symbols used inbasic circuit diagrams 371

LifeCheck® SPD test 177

LifeCheck® SPD test device 361

Lightning current arresters – Type 1 45

Lightning equipotential bonding 343

Literature 368

Mains filter 125

Marking system 204

Measuring and test devices 359Modular surge arrester with

integrated backup fuse 69

More information anddocumentation 367

Mounting frame 243

Mounting set 335

Multipole combined lightning currentand surge arrester for primarypower systems 39

Multipole modular combined lightningcurrent and surge arrester 31

Multipole, modular surge arrester 76

Multipole surge arrester with

‘Pro-Active Thermo Control’ 99

N-PE Lightning current arresters 63

N-PE spark-gap-based protectionmodule 38/96

N-PE surge arrester 92

NET Protector 247

NH Surge arresters 115

NSM Protector 136

Part No. Index 372

Photovoltaic systems 42/104

Pipe clamp for explosion hazardareas 350

Pluggable SPDs for DIN railmounting 179

Power supply systems 15

Power supply systems worldwide 28

Protection module for DEHNbloc® M 48

Protection module for DEHNguard® M,... S and DEHNgap C/ S 94

Protection module for DEHNrailmodular 124

Protective adapter for LAN 341

Protective adapter forNTBA/DSL splitter applications 339

Protective adapter forTV/radio applications 338

Protective conductor terminal 335

Rail support 330

Registration of discharges 366

Screwable SPDs 297

SDS 353

Self-bonding rubber tape 333

SFL Protector 141

Shield connection on anchor bars 325

Shield connection on DIN rails 328

Shield connection on cables 332

Shield terminals 326/329

SPDs for D-Sub connection 281

SPDs for BT Jack connection 265

SPDs for coaxial connection 267SPDs for LSA technology 229

SPDs for RJ connection 253

SPDs for use in potentiallyexplosive areas 301

SPDs for 482.6 mm (19 inch)data cabinets 247

SPD monitoring device 365

SPD test device 363

SPS Protector 126

STC Module 130

Surge arresters – Type 2 69

Surge arresters – Type 3 119

Surge arresters for earthed socket

outlets 130Surge arresters for use in cable ducts128

Surge protective adapter 138

Surge protective multiple socketoutlet with filter 141

Surge protective socket outlet 136

Terminal 327/331

Terminal block 244

Terminal block with integratedsurge protection 209

Test / Disconnection module 203

TFS / KFSU 343

Type / Product index 375

UGKF 267

V NH / VA NH 115

Varistor-based protection module 95

VC 280 2 143

Wiring accessories 145