Fieldbus solutionswith the SIMATIC PCS 7distributed control system
Brochure April 2010
SIMATIC PCS 7
Answers for industry.
Siemens AG 2010
7/24/2019 DCS Simaticpcs71
2/8
Fieldbus solutions with SIMATIC PCS 72
Fieldbus solutions with SIMATIC PCS 7
Integration of PROFIBUS PA and FOUNDATION Fieldbus
PROFIBUS DP is used in many installations to connect drives,
pumps, remote I/O and analyzers. SIMATIC PCS 7 thus has auniform architecture for linking all distributed devices and
technologies. PROFIBUS DP is a fixed component of SIMATIC
PCS 7, and is transparent for the user. It is both a system bus
and an open communication system. This structure permits a
central or distributed configuration of all connected systems
and devices independent of the vendor.
In addition, PROFIBUS DP supports transmission of the
HART protocol, and is the link between fieldbus systems
such as PROFIBUS PA and FOUNDATION Fieldbus and the
SIMATIC PCS 7.
PROFIBUS DP has been able to prove its exceptional reliability
in the field for more than 10 years already, with an installedbasis of almost 30 million nodes.
The SIMATIC PCS 7 distributed control system (V7.1 Service
Pack 2 and higher) allows customers to freely select their field-
bus instrumentation as a result of seamless integration of
PROFIBUS PA and FOUNDATION Fieldbus.
PROFIBUS PA and FOUNDATION Fieldbus profit equally from
the host PROFIBUS architecture.
G_
PCS7_
XX_
00247
PROFIBUS PA FOUNDATION Fieldbus
PROFIBUS DP
FF linkPA link
Remote I/O
SIMATIC PCS 7
automation system
Maintenance/
OS server
OS multi-clients
Engineering
station
Drives
Siemens AG 2010
7/24/2019 DCS Simaticpcs71
3/8
Active field distributors 3
Active field distributors
The active field distributors (AFD) make a decisive contribution toward increasing availability, and permit both replacement of devices
and expansion of the plant during operation
The SIMATIC active field distributors provide maximumavailability, and open up new dimensions for online
modification of fieldbus segments.
With conventional fieldbus installations, modifications during
operation are only possible to a very limited extent. Great cau-
tion is necessary when connecting new devices. Short-circuits
or bouncing of the connections during installation can result
in failure of the complete segment. The design principle does
not allow removal, replacement or expansion of subsegments
of the main line during operation.
Thanks to the innovative properties of the SIMATIC active fielddistributors, these limitations belong to the past. The new dis-
tributors feature short-circuit-proof connections for the spur
lines. In the event of a wire break or short-circuit on the main
line, an intelligent logic circuit automatically isolates the
faulty subsegments and provides the automatic bus termina-
tion. These properties significantly increase the availability of
the fieldbus segment, and open up completely new dimen-
sions for modifications during operation:
Devices can be added or replaced.
The main line can be extended or shortened during
operation.
A flexible expansion fieldbus ring topology can be set up to
increase availability.
Unused spare connections need not be planned since a
segment can be expanded at any time by installing further
field distributors for additional field devices.
G_
PCS7_
XX_
00248
AFD AFDAFD
PROFIBUS PA / FOUNDATION Fieldbus H1
PROFIBUS DP
Automatic bus terminatorPA link / FF link,
redundant
Siemens AG 2010
7/24/2019 DCS Simaticpcs71
4/8
Architectures4
Architectures
Line architecture
In this case, the field devices are connected to a bus line seg-ment by means of the short-circuit-proof spur lines of up to
8 active field distributors AFD. The last AFD automatically
activates its bus terminating resistor.
Line architectures with redundant couplers
The active field splitter (AFS) connects a bus line segment to
two feeding field device couplers FDC 157. The AFS switches
over the fieldbus line to the active redundant coupler in each
case. Hot swapping of the couplers is possible.
Ring architecture with bus coupler and media redundancy
Active field distributors (AFD) integrate the connected field
devices via short-circuit-proof spur line connections into a
fieldbus ring. The ring is closed by the redundant bus cou-
plers.
Hot swapping of the couplers and AFDs is possible. The
function of the field devices on the non-affected AFD is not
restricted.
The bus termination of the complete segment is carried out
fully automatically.
Possible architectures of PROFIBUS PA and FOUNDATION Fieldbus
Advantages
Automatic termination
Ease and safe installation
Fault-tolerant ring architecture including redundant
fieldbus couplers avoids unplanned plant downtimes
The topology can be extended or repaired during
operation
G_
PCS7_
XX_
00249
AFD
AFS
AFD AFD AFDiS
AFDiS
AFDiSAFDAFD
PROFIBUS PA /
FOUNDATION Fieldbus H1
PROFIBUS PA /
FOUNDATION Fieldbus H1
PROFIBUS PA /FOUNDATION Fieldbus H1
PROFIBUS
DP
SIMATIC PCS 7
automation system
PA link / FF link
PA link / FF link
PA link / FF link
Siemens AG 2010
7/24/2019 DCS Simaticpcs71
5/8
Products 5
Products
Active field distributor (AFD) of the new generation: AFDiS for use in Zones 1 and 2
The new 6-channel field barrier SIMATIC AFDiS now also
facilitates fault-tolerant, intrinsically-safe fieldbus instal-
lations
The AFDiS limits the energy on the spur lines in hazardousareas, and electrically isolates these from the main line. There-
fore intrinsically-safe field devices can also be supplied from
a high-power fieldbus coupler via the AFDiS, thus allowing
significantly larger quantity frameworks than with an intrinsi-
cally-safe fieldbus supply. The AFDiS can be installed in Zones
1 and 2 (or Zones 21 and 22). All spur lines are of EEx ia design
and can even be routed into Zone 0. Thus explosion protec-
tion in accordance with the FISCO model can be implicitly
proven without complex calculations.
First field barrier with integral repeater function for even
more rugged fieldbus communication
An integral fieldbus repeater is used with the SIMATIC AFDiS.
The communication signals between main line and spur lineare reproduced in both directions. This results in significantly
higher signal quality and absence of reactions between the
main and spur lines. In addition to the substantial increase
in the ruggedness of fieldbus segments, this design also has
other positive features:
All spur lines can be designed with the maximum permissi-
ble length of 120 m (60 m with FISCO), independent of the
number of devices connected on the segment.
The main line can be dimensioned up to a maximum of
1 900 m independent of the spur line lengths.
The first spur line outgoing feeder can be operated as a
spur line or as a subsegment with a length of up to 500 m. The quantity framework of up to 32 nodes permissible for
PROFIBUS PA and FOUNDATION Fieldbus H1 can also be
fully utilized for intrinsically-safe installations.
The AFDiS is suitable both for line topologies and for
designing redundant rings in safe and hazardous areas.
Siemens AG 2010
7/24/2019 DCS Simaticpcs71
6/8
Products6
Products
Easy installation
Internal view of AFDiS
The active field distributor AFDiS is designed for use in harsh
environments, and can be installed simply and safely.
Die-cast aluminum housing with IP66 protection for use
outdoors at temperatures from -40 to +70 C Approved for operation in Zones 1 and 2 (or Zones 21
and 22)
Corrosion-resistant cable glands (M16) prevent the pene-
tration of moisture even in harsh environments.
Screw terminals for secure connection of fieldbus cables
Integral rail for simple connection of shield
Active protection
In addition to the mechanical design, the intelligent elec-
tronics include various unique mechanisms to guarantee
availability of the fieldbus segment:
Automatic bus termination and isolation of faulty sub-
segments
6 short-circuit-proof spur line connections. Reduction to
test current (only 5 mA) in event of fault
The intelligent debouncing logic protects the main and
spur lines from reactions when connecting and disconnect-
ing field devices.
Externally visible LED displays for fast diagnostics of line
status
Sensor-monitored coverage of main line connections with
automatic load shedding allows opening of the main line in
the ring into Zone 2 even without a fire certificate
All standard grounding concepts supported
The shield connection can be made either directly via the rail
or capacitively via a separate terminal.
Siemens AG 2010
7/24/2019 DCS Simaticpcs71
7/8
FOUNDATION Fieldbus link 7
FOUNDATION Fieldbus link
Foundation Fieldbus is now integrated seamlessly into
SIMATIC PCS 7 analogous to the PA link. The FF Link with the
field device coupler FDC 157 provides integral power condi-tioning.
Parameterization and configuration are carried out centrally.
In addition, FOUNDATION Fieldbus is supported by SIMATIC
PCS 7 asset management. The diagnostics screens are auto-
matically generated by the system.
The same architectures can be implemented with the active
field distributors as with PROFIBUS PA. All advantages of the
field distributors can be used.
The field devices are integrated using the SIMATIC Manager
and SIMATIC PDM. The following steps are required:
Import of device description into the catalog using the
Device Integration Manager
Configuration of FF link
Configuration of FF device
Parameterization with SIMATIC PDM
The process values can be connected to the application in the
normal way using the channel drivers of the SIMATIC PCS 7
Advance Process Library (APL). The associated diagnostics
drivers are automatically generated by the system.
Control in the field
In addition to operator control and monitoring of process
values, the user can connect FF function blocks together into
control loops using the interconnection editor ("control in the
field").
Applications generated in this manner are executed indepen-
dent of the host controller and link master.
Device management
Device management is integrated in SIMATIC PDM and com-
prises functions and tasks such as:
Management of the device description
Device parameterization
Device status indication
LifeList
Document management
SIMATIC Process Device Manager PDM supports HART, PROFIBUS and
FOUNDATION Fieldbus
Summary
SIMATIC PCS 7 seamlessly integrates the two fieldbussystems PROFIBUS PA and FOUNDATION Fieldbus.
SIMATIC PCS 7 customers can freely select the field-
bus communication system with the most suitable
instrumentation.
Additional software or third-party infrastructure
components are not required.
The scalable redundancy model with the unique ring
redundancy concept offers a maximum degree of
ruggedness and availability.
The fast and reliable PROFIBUS DP backbone allows
central or distributed system configurations with
simultaneous linking of further cross-vendor compo-
nents.
Integral asset management permits fast and reliable
diagnostics.
Siemens AG 2010
7/24/2019 DCS Simaticpcs71
8/8
The information provided in this brochure contains descriptions
or characteristics of performance which in case of actual use do
not always apply as described or which may change as a result
of further development of the products. An obligation to provide
the respective characteristics shall only exist if expressly agreed
in the terms of contract. Availability and technical specifications
are subject to change without notice.
All product designations may be trademarks or product names
of Siemens AG or supplier companies whose use by third
parties for their own purposes could violate the rights of
the owners.
Get more information
For further details, see SIMATIC Guide manuals:
www.siemens.com/simatic-docu
You can order further publications about SIMATIC from:
www.siemens.com/simatic/printmaterial
Further technical documentation in our
Service& Support Portal:
www.siemens.com/automation/support
For a personal discussion, you can find your nearest contact at:
www.siemens.com/automation/partner
In the Industry Mall you can place orders electronically via the Internet:
www.siemens.com/industrymall
Siemens AG
Industry Sector
Industrial Automation Systems
PO Box 4848
90026 NUREMBERG
GERMANY
Subject to change without prior notice
Order No.: E86060-A4678-A271-A1-7600
3P.8215.15.12 / Dispo 09508
BR 0410 0.1 ROT 8 En
Printed in Germany
Siemens AG 2010
www.siemens.com/simatic-pcs7
Siemens AG 2010