Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 139Page
PROCURMENT AND FINANCE (P.F) OF
312 SUB-TRANSMISSION SUBSTATION(TECHNICAL DATA SHEET FOR
63/20 kV AIS SUBSTATIONS)
VOLUME 2 OF 4
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 2/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1392Page
ITEM DESCRIPTION PAGE
(TECHNICAL DATA SHEET FOR .......................................................................................... 1
63/20 kV AIS SUBSTATIONS) ............................................................................................ 1
1-GENERAL SCHEDULE DATA (I) ....................................................................................... 3
2- CIRCUIT BREAKER SCHEDULE DATA(I) ........................................................................... 7
3- DS/ES SCHEDULE DATA (I) ............................................................................................. 9
4- CT SCHEDULE DATA (I) ................................................................................................ 11
5- CVT SCHEDULE DATA (I) .............................................................................................. 13
6- LA SCHEDULE DATA (I) ................................................................................................ 14
7- INSULATOR SCHEDULE DATA (I) .................................................................................. 16
8- BUS WORK SCHEDULE DATA (I) .................................................................................. 18
9- EARTH SYSTEM SCHEDULE DATA (I) ............................................................................ 23
10- CAPACITOR SCHEDULE DATA (I) ................................................................................ 25
11- LIGHT SCHEDULE DATA (I) ......................................................................................... 31
12-METAL CLAD SCHEDULE(I) ......................................................................................... 33
13- STEEL STRUCTURE ..................................................................................................... 36
14- LVAC SCHEDULE DATA (I) .......................................................................................... 37
15- LVDC SCHEDULE DATA (I) .......................................................................................... 40
16- CABLE CHEDULE (I) .................................................................................................... 45
17-PROTECTION, CONTROL SCHEDULE PC (I) ................................................................. 48 18- RTU SCHEDULE DATA (I) ............................................................................................ 66
19- POWER TRANSFORMER SCHEDULE DATA (I) ............................................................ 69
20- AX/GRN TRANSFORMER SCHEDULE DATA (I) ........................................................... 74
21- DCS SCHEDULE DATA (I) ............................................................................................ 78
22- PLC SCHEDULE DATA (I) ............................................................................................ 84
23- SCHEDULE LINE TRAP AND LMU (I) ......................................................................... 113
24- SCHEDULE PABX (I) .................................................................................................. 113
25- TELEPHONE SCHEDULE DATA (I) ............................................................................. 134
26- SCHEDULE OPTICAL ACCESS MULTIPLEXER (I) ........................................................ 135
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 3/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1393Page
1-GENERAL SCHEDULE DATA (I)
ITEM DESCRIPTION TECHNICAL PARTICULARS
1 Applicable standard IEC
2 Altitude above the sea level m 1800
3 Ambient temperatures:
3.1 Maximum °C 55
3.2 Minimum °C -20
4 Relative humidity % More than 80
5 Maximum mean wind velocity m/s 45
6 Seismic acceleration m/sec2 0.45g
7 Pollution level L/M/H/VH H25 mm/kV,
8 Ice coating thickness mm 20
# : Line data on next sheets.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 4/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1394Page
CONTINUE OF SCHEDULE GS (I)
GENERAL RATING AND CHARACTERISTICS
ITEM DESCRIPTION UNIT
TECHNICAL
PARTICULARS
72.5 KV 24 KV
1 Applicable standard IEC standard of ministry
2 Substation name
3 Location of site
4 Nominal service voltage KV 63 20
5 Max. system voltage KV 72.5 24
6 Rating of busbars at site condition A 2000 2000
7 Rating of switchgear at site condition:
7.1 Line bays A 1250 1250
7.2 Transformer bays A 1250 1250
7.3 Bus section A 2000 2000
8 System Earthing SolidlyVia
groundingTransformer
9 Rated frequency HZ 50
10 Three phase short circuit:
10.1 Rated value KA 40 25
10.2 Dynamic value KA peak 100 62.5
109.3 Duration Sec 3 311 Number and rating of transformers No MVA ACC. to single line
12 Transformer ratio KV ACC. to single line
13 Number and rating of aux-earthing transformers No MVA ACC. to single line
14 Bus bar arrangement ACC. to single line
15 Number of feeders:
15.1 Line feeders ACC. to single line
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 5/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1395Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
15.2 Trans feeders ACC. to single line
15.3 Capacitor feeders ACC. to single line
16 Rated LIW voltage at site condition KV peak 325 125
17 Rated one min PFW voltage at site condition KV 140 50
18 Min external insulation creepage distance mm 2250 744
19 Colour of Porcelain Insulator Brown
20 Max. Radio. interference level measured at 1.1
highest system voltage µV ACC. TO IEC
RECOMMENDATION
21 Min clearance from ground level to the base of
insulation
mm 2500
22 Min clearance between live metal of different
phases in bay
mm 1500 500
23 Station service auxiliary AC supply:
23.1 Rated voltage V 400/230
23.2 Voltage variation % ±10
23.3 Phases and wire 3ph,4wires
23.4 Frequency HZ 50
23.5 Neutral earthing Solid
24 Station service auxiliary DC supply :
24.1 Rated voltage V 110
24.2 Voltage variation % -15,+10
24.3 Wires 2
24.4 Earthing Un-earthed
25 Min mechanical load of equipment terminals:
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 6/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1396Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
25.1 Static N 2000 1000
25.2 Dynamic N 3000 2000
26 Protection degree of cubicles:
26.1 Outdoor IP54
26.2 Indoor IP43
27 Current Transformer Secondary Current A 1
Unless otherwise specified the General Rating and Characteristics should be considered for all equipment.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 7/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1397Page
2- CIRCUIT BREAKER SCHEDULE DATA(I)
RATING AND CHARACTERISTICS OF CIRCUIT BREAKER
ITEM DESCRIPTION UNITTECHNICAL PARTICULARS
72.5 KV
1 Class (outdoor/indoor) Outdoor
2 Type of circuit breaker SF 6
3 No. of poles 3
4 Rated voltage KV 63
5 Rated normal current at IEC condition A 1250
6 Rated line-charge breaking current A 50
7 Rated cable charge breaking current A 125
8 Rated small inductive breaking current A 10
9 Rated short circuit breaking current :
9.1 AC component at rated voltage (Iscn ) KA 40
9.2 DC component % 35
10 First pole-to-clear factor 1.5
11 Rated transient recovery voltage for terminal faults KV 124
12 Rated short circuit making current KA 2.5 Iscn
13 Rated operating sequence O-0.3Sec-CO 3min-CO
14 Rated out of phase breaking current KArms 0.25 Iscn
15 Rated break time ms <= 50
16 Single pole or 3 pole operation 3poles
17 Requirement for simultaneity of poles:
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 8/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1398Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
17.1 Max. time interval between closure of the first and
last pole
msec 5
17.2 Max. time interval between opening of the first and
last pole
msec 2
18 Washable in service? (Yes/No) Yes
19 High speed auto reclosing (Yes/No) Yes
20 Operating mechanism:
20.1 Type of operating mechanism Spring
20.2 Type of operating mechanism motors (AC/DC) As Required
20.3 No. of independent trip coil 2
20.4 No. of independent closing coil 1
20.5 Variation of DC (aux. control) voltage required to
close C.B. %85-110
20.6 Variation of DC (aux. control) voltage required to
trip C.B. %70-110
20.7 Variation of AC supply voltage to trip and close C.B. % 85-110
20.8 Number of auxiliary switches:
20.8.1 Normally open 12
20.8.2 Normally close 12
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 9/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1399Page
3- DS/ES SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF DISCONNECTING & EARTHING SWITCHES
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
72.5 KV
1 Disconnecting Switch
1.1 Number of poles 3
1.2 Class (outdoor, indoor) outdoor
1.3 Rated voltage KV 63
1.4 Rated LIW voltage across the isolating distance at IEC
condition KV peak
325
1.5 Rated PFW voltage across the isolating distance at IEC
condition KV 140
1.6 Rated normal current at IEC condition A 1250
1.7 Type “vertical, pantograph, double break, center
break”
Center Break
1.8 Operating mechanism:
1.8.1 Method of operation Motor & Manual
1.8.2 Number and type of spare auxiliary switches:
a) Normally open 8
b) Normally close 8
c) No. Of easily contacts 4
d) No. Of late contacts 4
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 10/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1391Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
1.8.3 Max. operating time Secs 15
1.8.4 Type of motors AC/DC As Required
1.9 Control box Common for 3 phase
1.10 Max. inductive current breaking capacity A 2
1.11 Max. capacitive current breaking capacity A 1
2 Earthing Switch
2.1 Number of poles 3
2.2 Class (indoor, outdoor) outdoor
2.3 Rated voltage KV 63
2.4 Rated LIW voltage across the isolating distance at IEC
Condition
KV peak 325
2.5 Rated PFW voltage across the isolating distance at IEC
condition
KV 140
2.6 Operating mechanism :
2.6.1 Method of operation manual
2.6.2 Number and type of spare auxiliary switches:
a) Normally open 4
b) Normally close 4
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 11/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 139Page
4- CT SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF CURRENT TRANSFORMER
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
72.5 KV
1 Class (outdoor/indoor) Outdoor
2 Type Oil Immersed
3 Rated voltage KV 63
4 Rated primary current at IEC condition A *
5 Rated secondary current A 1
6 Rated continuous thermal current 1.2Inp
7 Number of cores: *
8 Accuracy class for measuring cores *
9 Accuracy class for protection cores *
10 Rated output :
10.1 For measuring *
10.2 For protection *
11 Max. temperature rise at rated continuous thermal
current
°C As per IEC, considering site
condition
12 Capacitive terminal provided Yes/No YES
13 Current terminal provided Yes/No YES
* : Detailed requirement of each CT is mentioned on item 13.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 12/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1392Page
14- Current & Output Data for Current transformers
Item No. Core No. Application CT ratio Rated burden Accuracy
class
14.1 Incoming Feeder
1 AS PER SLD AS PER SLD AS PER SLD
2 AS PER SLD AS PER SLD AS PER SLD
3 AS PER SLD AS PER SLD AS PER SLD
14.2 Outgoing Feeder
1 AS PER SLD AS PER SLD AS PER SLD
2 AS PER SLD AS PER SLD AS PER SLD
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 13/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1393Page
5- CVT SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF CAPACITIVE VOLTAGE TRANSFORMER
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
72.5 KV
1 Class (outdoor/indoor) Outdoor
2 Connection in system Phase to earth
3 Type Oil immersed, Capacitor
4 Rated primary voltage KV
5 Rated secondary voltage V
6 Rated voltage factor :
6.1 Continuous 1.2
6.2 30 sec. 1.9
7 Number of secondary windings 2
8 Accuracy class of each winding 0.2+3P
9 Rated output of each winding VA 50
10 Capacitive voltage divider :
10.1 Min. coupling capacitance PF Later
10.2 Natural frequency MHZ 1
10.3 Equivalent series resistance 40
11 Short circuit impedance of CVT 0.25
12 Power frequency test voltage on secondary KV 3
13 CVT designed for mounting of line trap on it? Yes/No Yes
3
63
3/110
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 14/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1394Page
6- LA SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF LIGHTNING ARRESTER
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
72.5 KV 24 KV
1 Arrester Duty
1.1 Class (outdoor/indoor) Outdoor
1.2 Connection in system Phase to Earth
1.3 Type of equipment being protected Power transformer /
Switchgear
2 Characteristics of Arresters
2.1 Location of arresterLine Entrance &
Near to Power Transformer
2.2 Rated volta e KV 60 20
2.3 Insulation Material Porcelain
2.4 Line discharge class according to IEC 60099-4 3 2
2.5 Continuous o eratin volta e KV
2.6 Nominal discharge current with 8/20 micro-second KA 10
2.7 Residual voltage :
2.7.1 Lightning impulse protection level at 10KA (LIPL) KV peak 290 70
2.7.2 Switching impulse protection level at 1KA (SIPL) KV eak 122 55
2.7.3 Max. steep current impulse protection level at 10KA KV eak 160 68
2.8 Pressure relief class KA-Sec 40/0.2 25/0.2
2.9 External insulation level of Silicon at IEC condition:
3
5.72
3
24
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 15/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1395Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
2.9.1 LIWL (1.2/50 s) KV peak 325 95
2.9.2 One min. PFWL KV rms 140
2.10 Washable in service Yes
2.11 Additional equipment :
2.11.
Surge counter Yes/No Yes
2.11.
Portable leakage current detector provided? One unit for each
2.11.
Corona ring Yes/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 16/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1396Page
7- INSULATOR SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF INSULATORS
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
1 Post Insulator :
1.1 Insulation material Porcelain
1.2 Min. dry LIWL at IEC conditions KV peak 325
1.3 Min. wet PFWL at IEC conditions KV 140
1.5 Electro-mechanical or mechanical failing load N 10000
1.6 color Brown
1.7 Top metal fitting pitch circle diameter mm 127
1.8 Bottom metal fitting pitch circle diameter mm 225
2 Suspension Insulator Unit
2.1 Type Ball & Socket
2.2 Insulation Material Porcelain
2.3 Min. dry LIWL at IEC conditions KV peak 110
2.4 Min. wet PFWL at IEC conditions KV peak 40
2.5 Min. power frequency puncture voltage KV 110
2.6 Min. electro-mechanical or mechanical failing load KN 70
2.7 Creepage distance mm 295
2.8 Nominal spacing mm 146
2.8 Ball and socket size According to IEC 60120
3 Insulator Suspension Set
3.1 Insulation Material Porcelain
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 17/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1397Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
3.2 Number of units per string As required
3.3 String arrangement Suspension /Tension set
3.4 Min. tensile strength for string set fittings KN 70
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 18/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1398Page
8- BUS WORK SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF HIGH VOLTAGE TERMINALS &
CONDUCTORS
ITEM DESCRIPTION UNITTECHNICAL
REQUIRMENT
1 System Characteristics
1.1 Nominal service voltage kV 63
1.2 Highest system voltage kV 72.5
1.3 Rated frequency Hz 50
1.4 Number of phases 3 phase
1.5 Type of neutral grounding Effective
2 General
2.1 Basic insulation level of equipment at site Condition kV peak 325
2.2Rated one minute power frequency withstand voltage
at site ConditionkV rms 140
2.3 Rated short circuit withstand current & it's duration kA/ S 40 / 1
2.4
Rated current of:
Line feeders
Transformer feeders
Busbars
AAcc. To SLD & Lay
out
2.5
Maximum permissible temperature of stranded
conductors at rated current and max. ambient
temperature
(C) 85
2.6Maximum permissible temperature of Tubular at
rated current and max. ambient temperature(C) 85
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 19/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1399Page
ITEM DESCRIPTION UNITTECHNICAL
REQUIRMENT
2.7
Minimum assumed tension for each stranded
conductor of incoming and outgoing over head lines
(per phase )
% of UTS 20
2.7Minimum tension of incoming and outgoing shield
wires% of UTS 10
2.9Maximum permissible surface gradient at IEC
condition kV/cm 21
2.10Maximum permissible angle for incoming and
outgoing over head linesDegree ±30
2.11
Ambient conditions:
Minimum ambient temperature
Maximum ambient temperature
Solar radiation
Seismic acceleration Wind speed
Ice thickness
Acc. To section 1
3
Minimum Clearances
(Not applicable for equipment subject to impulse
voltage tests )
3.1 Height of base of post insulator from ground mm 2500
3.2 Clearance between live parts and ground (Basic value ) mm 700
3.3 Minimum Spacing between different phases in bays mm 1500
3.4 Minimum Spacing between phases of rigid buses mm 1500
3.5 Minimum height of energized parts above ground mm 3200
3.6 Height of energized parts above access roads mm 6000
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 20/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13921Page
ITEM DESCRIPTION UNITTECHNICAL
REQUIRMENT
3.7 Minimum Distance between over-span phases mm 2500
3.8 Shield wire clearance over bus conductors mm 3000
4 Insulators
4.1 Insulator Units Standard Profile
4.1.1 Wet power frequency withstand voltage kV 40
4.1.2 lightning impulse withstand voltage kV 110
4.1.3 Electromechanical failing load kN 120
4.1.4 Power Frequency Puncture Voltage kV 110
4.1.5 Creepage distance mm 295
4.1.6 Nominal spacing mm 146
4.1.7 IEC coupling ball mmA 16
4.1.8 Type Ball & socket
4.1.9 Material Glazed porcelain
4.2 Complete Insulator String (if any)
4.2.1 Nominal phase to phase voltage kV 63
4.2.2 Min number of units 8
4.2.3 Power frequency withstand voltage at site condition kV 140
4.2.4 Lightning impulse withstand voltage at site condition kV 325
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 21/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1392Page
ITEM DESCRIPTION UNITTECHNICAL
REQUIRMENT
4.2.5 Total Creepage distance mm 2250
5 Post Insulator
5.1 Nominal phase to phase voltage kV 63
5.2 Rated lightning impulse voltage at site condition kV 325
5.3 Rated Power frequency voltage at site condition kV 140
5.4 Minimum Electromechanical failing load KN 8
5.5 Minimum creepage distance mm 2250
5.6 Maximum R.I.V. at 100 KHz v 500
5.7Whether corona ring for high voltage terminal
required? No
6 Overhead Shield Wire
6.1 Type of material Al. clad steel
6.2 Cross-section mm² 58.56 (7no.8)
7 Stranded conductor
7.1 Type of material AAC
7.2 Minimum cross section of conductor
Outgoing : 1*1000
Copular : 2*625
Incoming: 2*625
8 Rigid conductor
8.1 Type of material Aluminum alloy
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 22/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13922Page
ITEM DESCRIPTION UNITTECHNICAL
REQUIRMENT
8.2 Minimum cross section of Tubular*
Busbar : 160/8
Incoming: 100/6
Coupler: 100/6
Outgoing : 80/6
Note: The layout and section drawing also shall be consider.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 23/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13923Page
9- EARTH SYSTEM SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF EARTHING SYSTEM
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
1 Maximum shock duration Sec 1
2 Percentage of fault current through shield wire % 30
3 Depth of ground grid m 0.84 Assumption for calculation
4.1 Step length M 1
4.2 Body resistance Ω 1000
4.3 Weight Kg 70
5 Earthing grid conductors :
5.1 Type Stranded
5.2 Material Copper
5.3 Min cross section* mm2 120
6 Riser conductors :
6.1 Type Stranded
6.2 Material Copper
7 Earthing rod :
7.1 Material Copper clad steel
7.2 Min length/diameter L=3m, =20mm
8 Control building & cable trench earthing8.1 Type Stranded
8.2 Material Copper
8.3 Cross section mm2
50
9 Type of connectors & Joints :
9.1 Under ground connectors & joints Exothermic weld
9.2 Over ground connectors & joints Bolted-Pressure type
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 24/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13924Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
10 Rock surface height Cm 15
11 Rock surface resistivity .m 3000
* : calculation based on IEEE 80 shall be delivered for approval.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 25/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13925Page
10- CAPACITOR SCHEDULE DATA (I)
RATING AND CHRACTERISTICS OF CAPACITOR BANKS
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
1 Particular of systems
1.1 Nominal system voltage kV 20/33
1.2 Highest system voltage kV 24/36
1.3 Nominal system frequency Hz 50
1.4 Type of system neutral grounding Non effectively earthed
1.5 Rated short circuit current in capacitor
unit place
kArms *
1.6 Number of phases 3
2 Service condition
2.1 Max. ambient temperature °C 40/45/50/55
2.2 Min. ambient temperature °C -25/-30/-35/-402.3 Max. value of daily temperature °C *
2.4 Altitude above sea level m 1000/1500/2000/2500
2.5 Relative humidity % 90/95/more than 95
2.6 Seismic acceleration g 0.2/0.25/0.3/0.35/.45
2.7 Pollution level Low/medium/high/
very high/special
2.8 Max. wind velocity m/s 30/40/45
2.9 Wind velocity in ice condition m/s 20
2.10 Ice coating thickness mm 5 / 10 / 20 / 25
3 Capacitor
3.1 Rated voltage kV 3/20
3.2 Insulation level:
3.2.1 Power frequency kVrms 50 / 70
3.2.2 Lightning impulse kVpeak 125 / 170
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 26/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13926Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
3.3 Rated capacity of unit kVAR 100/125/150/200/250/300/4
00
3.4 Rated capacity of capacitor bank kVAR Depends on necessity and
bank's arrangement-Acc to
SLD
3.5 Method of fuse protection
(Internal/External fuse)
Internal / External
3.6 Bank’s arrangement type (single star with
external fuse/ single star with internal
fuse/ double star with external fuse/
double star with internal fuse)
*
3.7 Capacitor units considering with bushing
(One bushing/ Two bushings)
One /Two bushings
3.8 Type of protection for capacitor bank:
3.8.1 O/C protection Yes/No Yes
Yes3.8.2 O/L protection Yes/No
3.8.3 E/F protection Yes/No Yes
3.8.4 O/V protection Yes/No Yes
3.8.5 U/V protection Yes/No Yes
3.8.6 Unbalance Protection Yes/No Yes
3.9 Discharging resistor Yes/No Yes
3.10 Thermal class °C Depends on service condition
of installation place
3.11 Bushing of unit capacitors:
3.11.1 Material Porcelain
3.11.2 Rated one minute power frequency
withstand voltage
kVrms 50/70
3.11.3 Rated lightning impulse voltage at site
condition
kV peak 125/170
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 27/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13927Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
3.11.4 Min. creepage distance mm/kV 620
4 Series Reactor
4.1 One phase or three phase One phase
4.2 Type of core Air core
4.3 Insulation level (at site conditions):
4.3.1 One min. power frequency withstand
voltage of post insulator
kVrms 50/70
4.3.2 Lightning impulse kV peak 125/170
4.4 Inductance mH *
4.5 Continuous rated current (in site
condition)
Arms *
5 Current Transformer
5.1 Class Outdoor
5.2 Type Dry type
5.3 Rated insulation levels (at site conditions):5.3.1 One min. power frequency withstand
voltage
kVrms 50/70
5.3.2 Lightning impulse kV peak 125/170
5.4 Rated primary current Arms 2×75/2×150/2×250
5.5 Rated secondary current Arms 1/5
5.6 Rated short time current kArms *
5.7 Rated dynamic current kA peak 2.5 Isc
5.8 Rated continuous thermal current (% ofrated primary current)
100%
5.9 Number of secondary cores 2
5.10 Accuracy class (protection/measurement) 0.5/5P
5.11 Burden VA 15/30
5.12 Creepage distance mm/kV *
5.13 Type of mounting Mounted on structure
5.14 Neutral CT specification *
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 28/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13928Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
6 Voltage transformer
6.1 Class Outdoor
6.2 Type Dry type
6.3 Rated primary voltage kV 20/33
6.4 Rated secondary voltage V 100/110
6.5 Rated insulation level in standard
condition:6.5.1 One min. power frequency withstand
voltage
kVrms 50/70
6.5.2 Lightning impulse kV peak 125/170
6.6 Number of secondary cores 1
6.7 Accuracy class 0.2+3P
6.8 Rated output VA 50
6.9 Type of outer insulation Porcelain/resin insulator
6.10 Creepage distance mm/kV *6.11 Type of mounting On metal structure
6.12 Neutral PT specification *
7 Over voltage relay
7.1 Rated DC voltage V 110/125
7.2 Rated AC voltage Vrms 100/110
7.3 Setting range of voltage 90% to 130% Un, continues
7.4 Number of phases Connected between two
phases7.5 Time characteristic Inverse characteristic
8 Zero voltage relay
8.1 Rated DC voltage V 110/125
8.2 Rated AC voltage Vrms 100/110
8.3 Setting range of voltage 20% to 90% Un, continues
8.4 Number of phases Connected between two
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 29/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13929Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
phases
8.5 Time setting 0.2 sec. to 9.9 sec.
9 Over current relay
9.1 Rated DC voltage V 110/125
9.2 Rated AC voltage Vrms 5
9.3 Setting range of current (Inverse) 0.5 to 2.5 In
9.4 Setting range of current (Instantaneous) 3 Is and more
9.5 Number of phases 2 phase
10 Earth fault relay
10.1 Rated DC voltage V 110/125
10.2 Rated AC current Arms 5
10.3 Setting range of current (Inverse) 0.2 to 1.0 In
10.4 Setting range of current (Instantaneous) 3 Is and more
11 Unbalance protection relay (for doublestars capacitor banks)
11.1 Rated DC voltage V 110/125
11.2 Rated AC current Arms 1 / 5
11.3 Setting range of current (First stage) A 0.2 to 1.0 / 0.5 to 2.0 / 2.0 to
5.0
11.4 Time setting range (First stage) sec 0.0 to 3.0
11.5 Setting range of current (Second stage of
any)
A 0.2 to 1.0 / 0.5 to 2.0 / 2.0 to
5.011.6 Time setting range (Second stage) sec 0.0 to 3.0
12 Unbalance protection relay (for single
stars capacitor banks)
12.1 Rated DC voltage V 110/125
12.2 Rated AC current V 100/110
12.3 Setting range of voltage (First stage) V *
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 30/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13931Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
12.4 Time setting range (First stage) sec 0.0 to 3.0
12.5 Setting range of voltage (Second stage if
any)
V *
12.6 Time setting range (Second stage) sec 0.0 to 3.0
13 Tripping relays
13.1 Rated DC voltage V 110/125
13.2 Resetting type Hand reset
13.3 Number of contacts At least two N.O. and one
N.C.
13.4 Contact rating:
13.4.1 Breaking 10 A for L / R=<40 ms
13.4.2 Operating time =<20 msec
14 Time delay relays
14.1 Rated DC voltage V 110/125
14.2 Time setting range sec 0.02 to 0.99 / 1.0 to 99
14.3 Number of contacts At least two
15 Load Break Switch
15-1 Rated voltage kV (rms) 24 non-effectively earthed
15-2 Rated current A (rms) Acc. to SLD
15-3 Rated short circuit current and duration KA(rms)/s Acc. to SLD
15-4 Type designation Outdoor/ restrike free / single
pole16 Lightning arrester Acc. To L.A (I)
17 Post insulator Acc. To P.I (I)
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 31/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1393Page
11- LIGHT SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF LIGHTING
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
1 Minimum Illumination Levels
1.1 Switchyard at ground level horizontal Lux 30
1.2 Vertical surfaces of main equipment Lux 30
1.3 Streets & parking Lux 20
1.4 Main entrance & streets around control building Lux 50
1.5 Fence Lux 15
1.6 Out side of fence (10m) Lux 10
1.7 Transformers area Lux 40
1.8 Cable gallery Lux 200
1.9 Control building normal lighting Lux 300
1.10 Switchgear building emergency lighting Lux 50
2 Max. to Min. of illumination in each area
(uniformity factor) less than 3
3 Power factor not less than 0.8
4 Maintenance factor 0.7
5 Reflector Cut-Off
6 Type of AC lamps High pressure sodium
7 Type of lighting fixture Aluminum weather & dust
proof flood light
8 Position of ballasts :
8.1 For switchyard lighting Separate
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 32/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13932Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
8.2 For streets & fence lighting Built-In
9 Efficiency of lamps not less than LM/W 100
10 LAMP life not less than hr 20000
11 Min conductor size of buried cables mm2
16
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 33/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13933Page
12-METAL CLAD SCHEDULE(I)
RATING AND CHRACTERISTICS OF METAL CLAD SWITCHGEAR AND
COMPONENTS
ITEM DESCRIPTION UNIT TECHNICAL PARTICMPRS
1 Particulars of the installation and its components
1.1 Indoor or outdoor installation Indoor
1.2 Number of phases 3
1.3 Number of busbars 1
1.4 Rated voltage KV 24
1.5 Rated insulation levels
1.5.1 Lightning impulse withstand voltage KVpeak 125
1.5.2 1 min. power frequency withstand voltage KV 50
1.6 Rated normal currents (at standard
conditions):
1.6.1 Busbar A 2000
1.6.2 Transformer feeder circuit A 1250
1.6.3 Capacitor bank and line feeder circuit A 1250
1.7 Rated short time withstand current KA 25
1.8 Rated duration of short circuit Sec 3
1.9 Rated dynamic withstand current KApeak 40
1.10 Degree of protection:
1.10.1 With the door closed IP42
1.10.2 Between LV and HV compartments IP42
1.10.3 Between HV compartments IP42
2 Auxiliary voltages
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 34/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13934Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICMPRS
2.1 Motor of circuit breaker DC
2.2 Heaters and lights V AC 220/230
2.3 Control circuits V DC 110
3 Power Circuit Breaker
3.1 Fix or drawout Draw out
3.2 Type Vacuum
3.3 Number of trip/close coils 1/1
3.4 Rated normal current at standard
conditions
A 1250
3.5 Rated short circuit breaking current KA 20
3.6 Rated short circuit making current KA peak 2.5 Isc
3.7 Rated cable charging breaking current A 40
3.8 Rated operating sequence 0-0.3sec-Co-3 min. Co
3.9 Break time ms 65
3.10 First pole to clear factor 1.5
3.11 Operating counter is required Yes/No Yes
4 Current Transformers
4.1 Type Dry with Epoxy
4.2 Rated primary current Arms Refer to item 4.9
4.3 Rated secondary current Arms 1
4.4 Rated continuous thermal current
(% of rated primary current) % 120
4.5 Number of secondary cores:
4.5.1 For metering Refer to item 4.9
4.5.2 For protection Refer to item 4.9
4.6 Accuracy class:
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 35/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13935Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICMPRS
4.6.1 For metering Refer to item 4.9
4.6.2 For protection Refer to item 4.9
4.7 Burden:
4.7.1 For metering VA Refer to item 4.9
4.7.2 For protection VA Refer to item 4.9
4.8Max. temperature rise at rated Continuousthermal current
C Acc. to IEC considering siteconditions
5 Voltage Transformer
5.1 Type Dry with Epoxy resin conditions
5.2 Rated primary voltage KV
5.3 Rated secondary voltage V
5.4 Number of secondary windings
5.4.1 Incoming feeder 2
5.4.2 Busbar 2
5.5 Accuracy class 0.5+3P
5.6 Rated output VA 100
5.7 Rated voltage factor:
5.7.1 Continuous 1.2
3/20
3/110
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 36/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13936Page
13- STEEL STRUCTURE
RATINGS AND CHARACTERISTICS OF STRUCTURES AND LOADING
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
1 Steel type St 37 or higher
2 Minimum thickness of principal members in dry
conditions and without corrosion mm 5
3 Minimum thickness of principal members in other
Conditions mm 6
4 Minimum thickness of redundant members mm 3
5 Expansion coefficient/ C 11.5 10-6
6 Bolts and nuts shape Hexagon
7 Specification of welding AWS D1.1
8 Minimum thickness of galvanization
8.1 Steel structure m 90
8.2 Bolts and nuts m 65
9 Minimum weight of galvanization g/m2 500
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 37/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13937Page
14- LVAC SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF LVAC SYSTEM (LOW VOLTAGE AC)
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
1 LVAC Main Switch Board
1.1 Application LVAC Essential and
Nonessential System
1.2 Rated voltage V 400/230
1.3 Location Indoor
1.4 Type of mounting Floor
1.5 Finishing colour:
1.5.1 Outside RAL 7035
1.5.2 Inside Enamel White
1.6 Short time withstand rating KA/sec 16/1
1.7 Continuous rating of main buses and incomings A 4001.8 Number of out going feeders Acc. to single line diagram
1.9 Rating of outgoing feeders Acc. to single line diagram
1.10 Fully drawout/semidrawout/fixed type Fully Drawout
1.11 Padlocking facility required Yes/No Yes
2 LVAC Distribution Board
2.1 Rated voltage V 400/230
2.2 Location Outdoor/Indoor
2.3 Type of mounting Floor
2.4 Finishing colour:
2.4.1 Outside (indoor board/outdoor board) RAL 7035/ RAL 7038
2.4.2 Inside Enamel White
2.5 Short time withstand rating KA/sec 16/1
2.6 Continuous rating of busbars A 400
2.7 Fully drawout/semi drawout/fixed type Fixed
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 38/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13938Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
2.8 Padlocking facility is required? Yes/No Yes
2.9 Is back access required? Yes/No Yes
2.10 Number and rating of feedersacc.to LVAC single line
diagram
3 Auxiliary And Grounding Transformer Board
3.1 Rated voltage V 400/230
3.2 Location outdoor3.3 Type of mounting Floor
3.4 Finishing colour:
3.4.1 Outside RAL 7038/…
3.4.2 Inside Enamel White
3.5 Short time withstand rating KA/sec 16/1
3.6 Continuous rating of busbars and MCCB’s A 400
3.7 Fully drawout/fixed type Fixed
3.8 Padlocking facility is required? Yes/No Yes
4 ACB-Moulded Case Circuit Breakers (MCCB)
4.1 Number of poles 4
4.2 Type of operation
4.2.1 On main switchboard incomming & bus coupler Remot/Auto/Manual
4.2.2 On main switch board outgoing Auto/Manual control
4.2.3 On distribution board incomming Manual control
4.2.4 On aux. transformer board Auto/Manual control
4.3 Rated breaking capacity KA 16
4.4 Type of releases for auto control MCCB’s Over load and over current
4.5 Number of aux. Contacts NO/NC As per scheme
4.6 Max. breaking time for fault condition msec 25
5 Lighting Board
5.1 Rated voltage V 400/230
5.2 Location Indoor
5.3 Type of mounting Wall or Floor
5.4 Finishing colour:
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 39/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13939Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
5.4.1 Outside RAL 7035
5.4.2 Inside Enamel white
5.5 Short time withstand rating of busbar KA/sec 16/1
5.6 Continuous rating of busbar and outgoing feeders A As required
5.7 Padlocking facility is required? Yes/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 40/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13941Page
15- LVDC SCHEDULE DATA (I)
RATINGS AND CHARACTERISTICS OF LVDC SYSTEM (LOW VOLTAGE DC)
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
110 V 48V
1 Battery Charger And Accessories
1.1 Type Composite Float and Boost1.2 Number required 2 set 1 set
1.3 Out put current A 120 20
1.4 Period adjustable for boost charging Hour 8 to 12
1.5 Supply voltage V 400
1.6 Variation in supply voltage % 10
1.7 Variation in supply frequency % 5
1.8 Combined variation in supply voltage and frequency
% 10
1.9Short circuit level of 400V supply at charger
terminals for 1 secondsKA 16
1.10 Charger output voltage:
1.10.1 Boost mode V Acc. to battery
1.10.2 Float mode V Requirement
1.10.3 Equalize mode V
1.11 Charging current of the battery
1.11.1 Boost mode A Acc. to battery
1.11.2 Float mode A Requirement
1.11.3 Equalize mode A
1.12Whether automatic device for changing the
charging current of the battery from high level to
low and further, to very low level is required? Yes/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 41/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1394Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
1.13Maximum permissible variation in output DC
voltage
(No load to full load)
% 0.5%
1.14 Type of tap changer for rectifier transformers Off load
1.15 Cable entry Bottom
1.16 Contacts for the event recording, scada and alarm
system requiredYes/No Yes
1.17 Finishing colour : 2 set
1.17.1 Outside RAL 7035
1.17.2 Inside Enamel white
2 Stationary Lead Acid Battery
2.1 Number of battery banks required 2 1
2.2 Number of cells in each bank in series 55 24
2.3 DC system voltage V 110 48
2.4 Rated voltage of each cell V 2
2.5 No load voltage of each cell V 2.1
2.6 Max. float charging cell voltage V 2.23
2.7 Max. boost charging time of battery H 8
2.8 Ampere hour capacity of each cell at 15 deg. Cen.
And 8 hour rate to give final cell voltage of 1.85 V AH 300 200
2.9 Discharge Duty :
2.9.1 Continuous load and duration A/H Acc. load calculation2.9.2 Emergency load and duration A/H Acc. load calculation
2.9.3 Momentary load and duration A/sec Acc. load calculation
2.9.4 Final cell voltage V 1.85
2.10 Type of cables to connect battery to external circuit Single core copper PVC
insulated unarmored
2.11 Charging method required Boost and float
3 DC Switchgear
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 42/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13942Page
ITEM DESCRIPTION UNIT TECHNICAL PARTICULARS
3.1 Location Indoor
3.2 Type of mounting Floor
3.3 Rated voltage V 110
3.4 Maximum working voltage V 125
3.5 Busbar material Copper
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 43/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13943Page
SCHEDULE LVDC (I)
RATINGS AND CHARACTERISTICS OF LVDC SYSTEM (LOW VOLTAGE DC)
ITEM DESCRIPTION UNIT TECHNICAL
PARTICULARS
3.6 Continuous current rating A 125
3.7 Short time rating and duration KA/sec 20/1
3.8 Single front/double front Single
3.9 Fully drawout/semi drawout/fixed Fixed
3.10 Number and rating of incomming feeders See single line
3.11 Number and rating of outgoing feeders See single line
3.12 Type of outgoing feeders MCCB
3.13 Type of incoming feeders MCCB
3.14 Finishing colour :
3.14.1 Outside RAL 7035
3.14.2 Inside Enamel white
4 DC Emergency Lighting Board
4.1 Location Indoor
4.2 Type of mounting Floor
4.3 Rated voltage V 110
4.4 Maximum working voltage V 125
4.5 Busbar material Copper
4.6 Continuous current rating A 200
4.7 Short time rating and duration KA/sec 10/1
4.8 Single front/double front Single front
4.9 Fully drawout/semi drawout/fixed Fixed
4.10 Number and rating of incomming feeders See single line
4.11 Number and rating of outgoing feeders See single line
4.12 Type of incomming feeders MCCB
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 44/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13944Page
ITEM DESCRIPTION UNIT TECHNICAL
PARTICULARS
4.13 Type of outgoing feeders MCCB
4.14 Finishing colour :
4.14.1 Outside RAL 7035
4.14.2 Inside Enamel white
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 45/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13945Page
16- CABLE CHEDULE (I)
RATINGS AND CHARACTERISTICS OF MEDIUM VOLTAGE, LOW VOLTAGE,
PROTECTION AND CONTROL CABLES
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
1 Low Voltage Power Cable
1.1 Voltage designation KV 0.6/1
1.2 Number of cores/size According to
Design
1.3 Conductor material (Al/Cu) Cu
1.4 Type of conductor Stranded
1.5 Type of insulation P.V.C
1.6 Type of armour and material Galvanised steelwire for multicore
cables and
aluminium strip
for single core
cables
1.7 Type of sheath material Extruded P.V.C
1.8 High voltage test KV 3.5
1.9 Conductor short circuit withstand current/time KA/sec 16/1
1.10 Armour short circuit withstand current/time KA/sec 16/0.5
2 Control And Protection Cables
2.1 Voltage grade :
2.1.1 VT and CT cable KV 0.6/1
2.1.2 Control cable V 450/750
2.2 Conductor material Cu
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 46/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13946Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
2.3 Number of cores/size According to
design
2.4 Type of conductor Stranded
2.5 Type of insulation P.V.C
2.6 Inner insulation Extruded P.V.C2.7 Type of shield Lead or Copper
2.8 Outer insulation around sheath Extruded P.V.C
2.9 T e o armour material Galvanised steel
2.10 Outer sheath P.V.C
2.11 Hi h volta e test or 5 min:
2.11.1 VT and CT cable KV 3.5
2.11.2 Control cable KV 2.5
2.12 Conductor short circuit withstand current/time KA/sec 16/12.13 Metal sheath short circuit withstand current/time KA/sec 16/0.5
2.14 Armour short circuit withstand current/time KA/sec 16/0.5
3 20KV Power Cable
3.1 Type of cable Single core
copper conductor,
XLPE insulated,
screened and DT
armoured
3.2 Voltage designation KV 12/20
3.3 Conductor material CU
3.4 Type of conductor Standard
3.5 Material of shield Lead or copper
3.6 Material of screen Copper
3.7 High voltage test for 5 min. KV 30
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 47/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13947Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
3.8 Basic insulation level KVpeak 125
3.9 Short circuit withstand:
3.9.1 Symmetrical current KA 16
3.9.2 Dynamic current KApeak 40
3.9.3 Time duration Sec 3
3.10 Short circuit withstand of sheald and armour KA/Sec 16/0.5
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 48/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13948Page
17-PROTECTION, CONTROL SCHEDULE PC (I)
RATINGS AND CHARACTERISTICS OF PROTECTION, CONTROL, MEASUREMENT
AND RECORDING EQUIPMENT & SYSTEM
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
1 Line Protection
1.1 Distance Relay :
1.1.1 Method of starting under-impedance
1.1.2 Whether direction discrimination for zone 3 unit
required
Yes/No Yes
1.1.3 Distance protection shall be suitable for lines with
following details:
- Line length Later
- Line conductor
- Line impedance :
* Positive sequence /Km
* Zero sequence /Km
* Zero sequence mutual impedance /Km
- Line characteristic angle Degress
1.1.4 Inter-tripping scheme Permissive under
reach
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 49/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13949Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
1.1.5 Tripping mode 3 phase and 1
phase
1.1.6 Test switch required Yes/No Yes
1.1.7 Number of zones : 3
- Forward reaching Yes
- Reverse reaching No
1.1.8 Time setting range
Maximum zone 1 operating time ms <25
- Zone 2 S 0.1 to 1
- Zone 3 S 0.3 to 3
1.1.9 Single and three phase voltage supervision required Yes/No Yes
1.2 Directional earth fault relay
1.2.1 Maximum torque phase angle in degree lagging 40 to 70
1.2.2 Current setting range A 0.1 to 0.3
1.2.3 Required characteristic of current unit
- Instantaneous Yes/No Yes
- Inverse time Yes/No Yes
1.2.4 Transient over reach % Less than 1
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 50/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13951Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
1.2.5 Drop off/pick-up ratio 97
1.3 Directional Over Current Relay
1.3.1 Maximum torque phase angle in degree lagging 40 to 70
1.3.2 Current setting range A 0.1 tp 0.3
1.3.3 Required characteristic of current unit
- Instantaneous Yes/No Yes
- Inverse time Yes/No Yes
1.3.4 Transient over each % Less than 1
1.3.5 Drop-off/pick-up ratio 97
1.4 Zero Voltage Relay :
1.4.1 Resetting ratio in percent of nominal voltage 79
1.4.2 Resetting time Very short
1.4.3 Time delay range S 2 to 10
1.4.4Contact data :
- NC On inst. U/V unit
- NO On timer unit
1.4.5 Indicator required Yes/No Yes on timer unit
1.5 Single And Three Phase Auto-Reclosing Equipment:
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 51/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1395Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
1.5.1 Speed of the auto-reclosing scheme :
- High speed Yes/No No
- Slow speed Yes/No No
- Slow and high speed Yes/No Yes
1.5.2 Number of auto-reclosing shots (one or two) Two
1.5.3 Manual close inhibit time Sec 3 to 5
1.5.4Whether hand reset lockout feature on permanent trip
RequiredYes/No Yes
1.5.5 Range of reclaim time adjustment S 20 to 120
1.5.6 C.B closing pulse time S 0.2 to 0.3
1.5.7 Trip pulse time S 0 to 0.4
1.5.8Whether heavy duty contacts with magnetic blow out
required for closing C.BYes/No Yes
1.5.9 Operation indicator Yes/No Yes
1.5.10 Operation counter Yes/No Yes
1.5.11
Whether features for annunciation of “C.B.
maintenance” after preset number of A/R scheme
operation is required
Yes/No Yes
1.5.12 Method of Reclosing :
- Single phase (SPAR) Yes/No No
- Three phase (TPAR) Yes/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 52/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13952Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
- Single or three phase (SPAR or TPAR) Yes/No No
- Single and three phase (SPAR and TPAR) Yes/No No
1.5.13Whether provision is provided for blocking and
switching-in the A/R equipment from:Yes
- Control relay panel Yes/No Yes
- Remote control Yes/No Yes
1.5.14 Range of dead time adjustment S 0.25 to 3
1.5.15 Whether following features is required for each C.B:
- Synchronising check Yes/No Yes
- Live line/dead bus Yes/No Yes
- Live bus/dead line Yes/No Yes
2 Power Transformer Protection
2.1 Differential Relay:
2.1.1 Setting range % 15 to 50
2.1.4 Hand reset operation indicator required Yes/No Yes
2.1.5 Bias setting reange % 15 to 50
2.2 Restricted Earth Fault Relay:
2.2.1 Voltage setting range V 5 to 200
2.2.2 Time setting range Sec 0.1 to 99
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 53/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13953Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
2.2.3 Resetting ratio % 95
2.2.4 Metrosil :
- Whether metrosil required Yes/No Yes
- Characteristics of metrosil To suit relay
scheme
2.3 Inverse Time Over Current Relay With Instantaneous
Unit
2.3.1 Current setting range A 1 to 5
2.3.2 Current setting range of the instantaneous unit A 4 to 20
2.4 Neutral Inverse Time Over Current Relay
2.4.1 Current setting range A 0.2 to 2
2.5 Under Voltage Relay :
2.5.1 Resetting ratio in percent of nominal voltage 79
2.5.2 Resetting time Very short
2.5.3 Time delay range S 2 to 10
2.5.4 Contact data :
- NC On inst. U/V unit
- NO On timer unit
2.5.5 Indicator required Yes/No Yes on timer unit
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 54/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13954Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
2.6 Over Voltage Relay
2.6.1 Voltage setting range in percent of rated voltage % 80 to 110
2.6.2 Resetting ratio % 125
2.6.3 Time setting range Sec 2 to 10
3 Circuit Breaker Protection
3.1 Breaker Failure Relay:
3.1.1 Number of instantaneous over current unit per phase 2
3.1.2Current setting range in percent of correponding class of
accuracy in percent20 to 300 (+10, -
10)
3.1.3 Drop off current as percent of pick up current Msec than 98
3.1.4 Resetting time msec 10
3.1.5Operating time for current detectors at 2 times
minimum operating currentmsec 10
3.1.6 Number of timers 2
3.1.7 Timer setting range msec 20 to 500
3.2 Trip coil supervision relay :
3.2.1 Circuit breaker trip coil current mA 30
3.2.2 Supervision for both open and close position of circuit
breaker requiredYes
3.3 Fuse Failure Relay :
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 55/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13955Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
3.3.1 Application One & three phase
monitoring
3.3.2 Operating time msec <8
3.3.3 Operating voltage V 20 (Ph-N)
3.3.4 Resetting time msec 25
3.4 Self Reset Trip Relay :
3.4.1 Number of contacts 8 pairs of 12 paires
3.4.2 Pick up time :
a) make contact (No) ms 5
b) beak contact (No) ms 5
3.4.3 Contact details :
a) duty range in percent of rated voltage:
- pick up value % 50 to 120
- drop out value % 5 to 20
b) current carrying capacity (for already closed contact):
- 200 msec/1 sec A 90/50
- continuously A 5
c) making capacity:
- 200 msec/1 sec A 30/10
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 56/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13956Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
- for 0.5 sec A 5
d) Breaking capacity :
- AC PF>0.1 max. 250V A 10
- DC L/R<40 msec A 2
- single contacts A 0.4
3.5 Elec/Hand Reset Trip Relay (Lock Out) :
3.5.1 Number of contacts 8,12,14 or 18 pairs
3.5.2 Pick up time :
a) make contact msec 10
b) break contact msec 10
3.5.3 Voltage for :
- pick up % 50 to 120
- reset % 80 to 120
3.5.4 Contact details :
a) max. System voltage:
- within a contact set V 450/400
- between sets of contact V 900/800
b) current carrying capacity for already closed contact:
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 57/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13957Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
- 200 msec/1 sec A 90/50
- continuously A 10
c) making capacity (L/R > 10 m.sec):
- 200 msec/1 sec A 30/20
- 1 sec 2 contacts in paraller A 20
d) Breaking capacity :
- AC PF>0.1 max. 250V A 20
- DC L/R<40 msec A 2
- single contacts A 3
4 20KV Outgoing Feeders Buscoupler and Capacitor
Bank Protection
4.1 Inverse Time Over Current Relay With Instantaneous
Unit:
4.1.1 Current setting range A 1 to 5
4.1.2 Current setting range of the instantaneous unit A 4 to 20
4.2 Neutral Inverse Time Over Current Relay with instantaneous unit :
4.2.1 Current setting range A 0.2 to 2
4.2.2 Current setting range of the instantaneous unit A 1 to 8
4.3 Auto-Reclosing Equipment:
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 58/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13958Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
4.3.1 Speed of the auto-reclosing scheme:
- High speed Yes/No No
- Slow speed Yes/No No
- Slow and high speed Yes/No Yes
4.3.2 Number of auto-reclosing shots (one or two) Two
4.3.3 Manual close inhibit time Sec 3 to 5
4.3.4Whether hand reset lockout feature on permanent trip
requiredYes/No Yes
4.3.5 Range of reclaim time adjustment S 20 to 120
4.3.6 C.B closing pulse time S 0.2 to 0.3
4.3.7 Trip pulse time S 0 to 0.4
4.3.8Whether heavy duty contacts with magnetic blow out
required for closing C.BYes/No Yes
4.3.9 Operation indicator Yes/No Yes
4.3.10 Operation counter Yes/No Yes
4.3.11
Whether features for annunciation of “C.B
maintenance” after preset number of A/R scheme
operation is required
Yes/No Yes
4.3.12 Method of reclosing:
- Single phase (SPAR) Yes/No No
- Three phase (TPAR) Yes/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 59/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13959Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
- Single or three phase (SPAR or TPAR) Yes/No No
- Single and three phase (SPAR and TPAR) Yes/No No
4.3.13Whether provision is provided for blocking and
switching-in the A/R equipment from:
- Control relay panel Yes/No Yes
- Remote control Yes/No Yes
4.3.14 Range of dead time adjustment S 0.25 to 3
4.3.15 Following features is required for each C.B:
- Synchronising check relay Yes/No No
- Live line/dead bus Yes/No Yes
- Live bus/dead line Yes/No Yes
4.4 Over Voltage Relay
4.4.1 Voltage setting range in percent of rated voltage % 80 to 110
4.4.2 Resetting ratio % 125
4.4.3 Time setting range Sec 2 to 10
4.5 Zero Voltage Relay
4.5.1 Voltage setting range in percent of rated voltage % 30 to 60
4.5.2 Resetting ratio % 125
4.5.3 Time setting range Sec 2 to 10
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 60/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13961Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
4.6 Capacitor Star-Point O/C Relay
4.6.1 Rated D.C voltage V 110
4.6.2 Setting range of current A 0.2-5A
4.6.3 Time setting range Sec 0.0 to 3.0
4.7 Sensitive earth fault relay
4.7.1 Min current setting range %1In
5 Check-Synchronising Equipment/Relay
5.1 Check-Synchronsiing Relay
5.1.1Maximum phase difference at which circuit breaker
closure is permitted Degrees 30
5.1.2 Accuracy of phase difference in item 5.1.1 above Degrees +0%, -5%
5.1.3Maximum slip frequency at which circuit breaker closure
is permittedHZ 0.003
5.1.4 Setting of undervoltage inhibit elements 80 to 90% of Un
5.1.5 Pick-up/drop off ratio of undervoltage inhibit elements 80%
5.1.6 Rated P.T secondary voltage Volts 110/ 3
5.1.7 Contacts details 2 No
5.2 Check-Synchronsiing Guard Relay
5.2.1 Application To guard C.B
closing such that
C.B can not be
closed by check
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 61/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1396Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
relay alone, both
check relay &
operator must to
close C.B
6 Control, relay and other associated indoor/outdoor panels
6.1 Type of sheet steel Cold rolled mild
steel
6.2 Thickness of sheet steel:
6.2.1 Front mm 2
6.2.2 Rear mm 2
6.2.3 Sides mm 2
6.3 Type of panels required:
6.3.1 Control panels Yes/No Yes
6.3.2 Relay panels Yes/No Yes
6.3.3 Energy meter panels Yes/No Yes
6.3.4 Fault recorder/locator panels Yes/No No
6.3.5 Event recorder panels Yes/No No
6.3.6 Interface panels for scada Yes/No Yes
6.3.7 AVR panel Yes/No Yes
6.4 Cable galanding for all panels or boxes required Yes/No Yes
6.5 Test socket for current and voltage feeders required Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 62/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13962Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
7 Measurement Equipment
7.1 Measuring Center :
7.1.1 Functions should be mesured :
- Amper (A) Yes/No Yes
- Voltage (V) Yes/No Yes
- Active power (MW) Yes/No Yes
- Reactive power (MVAR) Yes/No Yes
- Active energy (MWH) Yes/No Yes
- Reactive energy (MVARH) Yes/No Yes
- Min No. of rates (TRAFF) for MWH & MVARH 4
- Accuracy class of MWH & MVARH 0.5
7.2 Ammeter :
7.2.1 Range
- 63 Trans feeder A 1250
- 20KV Outgoing A 1250
7.2.2 Accuracy class 1.5
7.2.3Continuous overload rating of current coil in percent of
rated current200
7.2.4 Short time rating in percent of rated current for 5 sec 1000
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 63/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13963Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
7.2.5 CT ratio See single line
diagram
7.3 Volt Meter :
7.3.1 Range
- 63 KV KV 0 to 72.5
7.3.2 Accuracy class 1.5
7.3.3 Continuous over voltage rating of voltage coil in percent
of rated voltage120
7.3.4 Short time rating in percent of rated voltage for 5 sec 200
8 Indication equipment
8.1 Annunciator
8.1.1 Speed of operation of the annunciator msec 10
8.1.2 Whether urgent and non – urgent alarm discrimination
required :
- Audible alarm Yes/No Yes
- Visible alarm Yes/No Yes
8.1.3 Colour of visible alarm for :
- Urgent alarm Red
- Non urgent alarm Orange
8.1.4 Number of alarm window per feeder acc. Spec.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 64/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13964Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
8.1.5 Number of lamps in each annunciator window 2
8.1.6 Type of reset (manual/self) Manual
9 Event Recorder As required
9.1 Number of channels Acc. spec
9.2 Individual recording channel for each event input is
required Yes/No Yes
9.3 Method of recording for indication:
- Function In the form of line
- Time In the form of
point
10 Fault Recorder As required
10.1 Number of recording channels:
- number of analog channels Acc. spec
- number of contact channels Acc. spec
10.2 Number of DC analog channels per feeder:
- Line Acc. spec
- Transformer Acc. spec
10.3 Number of DC contact channels per feeder:
- Line Acc. spec
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 65/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13965Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
- Transformer Acc. spec
10.4 Number of current recorder channels per feeder:
- Line 4
- Transformer 2
10.5 Number of voltage recorder channels per feeder:
- Line 4
- Transformer ---
10.6 Duration of timing for which the recorder shall be
reading after the appearance of fault Sec 5
10.7 Duration of timing for which the recorder shall be
reading before the appearance of fault Sec 0.5
10.8 Data, time (hour, minute & second) marker required Yes/No Yes
10.9 End of paper alarm contact required Yes/No Yes
10.10 Recorder “In operation” indication required Yes/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 66/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13966Page
18- RTU SCHEDULE DATA (I)
ITEM DESCRIPTION TECHNICAL
PARTICULARS
1 CLOCK :
- Accuracy ±2 PPM. 7.2msec per
hour or better
- Resolution 1 msec
2 Resolution of time tag for RTU inputs 1 msec
3 Time-tagged sequential memory to store 512 events
4 Each pulse counter input 16-bit counter
5 Power supply voltage 48 VDC+20%, -15%
6 Interruption of power supply voltage < 20 msec
7 Ambient temperature From -20˚c to +55˚c
8 Relative humidity From -10% to 95%
9
DC analog inputs :
- The Total number of AI 89 input *
- A/D conversion linearity 1/2 LSB *
- A/D quantizing error 1/2 LSB *
- Accuracy from input terminal <0.1% of full scale at
25˚c
- To digital value <0.005% per ˚c
temperature error
- Common mode rejection 90 dB dc to 50HZ
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 67/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13967Page
ITEM DESCRIPTION TECHNICAL
PARTICULARS
- Normal mode rejection 60 dB at 50HZ
- Rang of analog inputs 0-10mA , 4-40mA
±20mA, ±5volts,
±10volts
10 DC analog outputs resolution of the D/A 12bits plus sign
11 The Total number of digital output > 152 output *
12 The total number of digital inputs > 528 input *
13 Number of communication ports (for scada center)14 (expandable up to
2)
14 - Number of communication ports (for communication with
RTU)1
15 -Protocol for communication with Scada center IEC 60870-5-101
16 - Protocol for communication with Other RTU IEC 60870-5-101
17 Rate of these ports from 100 to 9600 bps
18
MODEM :
- Type of modem Multi, four wire (data
and voice)
- Terminal impedance 600Ω±10%
- Transmit level0dBm nominal
adjustable to – 12dBm
- Receive level 0 to – 30 dBm
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 68/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13968Page
ITEM DESCRIPTION TECHNICAL
PARTICULARS
- Bit error rate 10-5
if S/N = 15 dB
19 The total number of pulse input > 53 *
* : Specified values are the minimum requirement and the exact values will be
finalized during project progress.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 69/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13969Page
19- POWER TRANSFORMER SCHEDULE DATA (I)
RATING AND CHARACTERISTIC OF POWER TRANSFORMER
(a) If no value indicated it shall be designed by manufacturer to limit
the short circuit strength of TV system ace. To chapter DATA.
Item
No.Description (POWER TRANSFORMER) Unit Type I
15 Max. Temp rise at rated power
(corrected for ambined condition as chapterDATA and IEC 60076-2
1-winding deg. C 56
2-Top oil deg. C 51
3-Hot spot deg. C 69
16 OFF circuit tap changer (YES 1 NO) No
1-Winding Location
2-Rated current Amp
3-Tapping Range %
17 ON-Load tap changer Yes
1-winding Location HV-N
2-Rated current Amp >=6353-Voltage class ( I or II ) I
4-Position of tappings HV-N
5-Tapping Range (+a% ....... -b%) % (+-9*1.67%)
6-Number Of Steps 19(+-9)
7-Mid tap position 63/20
8-Remote OL TC Control panel Yes
9-Parallel operation control required for
of transformers 2
10-Automatic voltage regulator Yes
11-Line Drop Compensation No
18 Vector group (HV/LV) YNd11
19 Impedance voltage on principal tap
1-Reference power MVA 40
2-HV/LV %(a) 13.5
3-HV/TV (a) N.A
4-LV/TV (a) N.A
Item Description (POWER TRANSFORMER) Unit Type I
1 Substation name(s) .............Substation
2 Installation ( outdoor indoor) Outdoor
3 Three phase or Single phase Three Phase
4 Separate winding or auto-transformer Separate
5 Number of transformers 2
6 Rated Frequency Hz 50
7 Rated full load power output
HV MVA 40
LV MVA 40
TV MVA N.A
8 Rated Voltage (UN)
HV kVrms 63
LV kVrms 20
TV kVrms N.A
9 Highest voltage for equipment ( Um )
HV kVrms 72.5
LV kVrms 24
TV kVrms N.A 10 Cooling system(Air cooled or Water cooled) Cooled
11 System grounding:
HV system Solid
LV system G.T.r
TV system N.A
12 Evaluation rate of no load loss
-Foreign currency portion
-Rial portion RLS/KW
- Total Converted
13 Evaluation rate of load loss
-Foreign currency portion
-Rial portion RLS/KW
- Total Converted
14 Nominal rating (HV/LV)
1-0NAN MVA
2-0NAN/ONAF(ONAF1 if No oil pump) MVA 40/40
3-0NAN/ONAF/OFAF(ONAF2 if No oil
pump)
MVA N.A
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 70/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13971Page
Item
No.Description (POWER TRANSFORMER) Unit Type I
15 Max. Temp rise at rated power
(corrected for ambient condition as chapter
DATA and IEC 60076-2)
1-winding deg. C 562-Top oil deg. C 51
3-Hot spot deg. C 6916 OFF circuit tap changer (YES NO) No
1-Winding Location
2-Rated current Amp
3-Tapping Range %
17 ON-Load tap changer Yes
1-winding Location HV-N
2-Rated current Amp >=635
3-Voltage class ( I or II ) I
4-Position of tappings HV-N
5-Tapping Range (+a% ....... -b%) % (+-9*1.67%)
6-Number Of Steps 19(+-9)
7-Mid tap position 63/20
8-Remote OL TC Control panel
required(Yes/No)Yes
9-Parallel operation control required for
of transformers 2
10-Automatic voltage regulator
required(Yes/No)
Yes
11-Line Drop Compensation
required(Yes/No)No
18 Vector group (HV/LV) YNd11
19 Impedance voltage on principal tap
1-Reference power MVA 402-HV/LV %(a) 13.5
3-HV/TV (a) N.A
4-LV/TV (a) N.A
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 71/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1397Page
Item Description (POWER TRANSFORMER) Unit Type I
20 INSULATION LEVELS AT SEA LEVEL AND
STANDARD1-Lightning Impulse withstand voltage
-LIWV(HV) kVpeak 325/450
-LIWV(LV) kVpeak 125/170
-LIWV(TV) kVpeak N.A
-LIWV(N) kVpeak 125/170
2-Switching Impulse withstand voltage
-SIWV(HV) kVpeak N.A
-SIWV(LV) kVpeak N.A-SIWV(TV) kVpeak N.A
-SIWV(N) kVpeak N.A
3-One minute power frequency (a)
-PFWV(HV) kVrms 140/185
-PFWV(LV) kVrms 50/70
-PFWV(TV) kVrms N.A
-PFWV(N) kVrms 50/70
21 Bushing Data
Min. Rated Current(HV/LV) Amp >=635/>= 2000
Min. Short Circuit Current(HV/LV) kA 40/25
test tap required (Yes/No) Yes
Oil level indicator (Magnetic/Prismatic) Magnetic
Bushing type current transformers
1-Required ( Yes / No ) Yes
2-No of cores (HV-LV-HVN) N.A-3-N.A
3-Specification
21.1 Inside HV Bushings
A) Core 1 N.A
B) Core 2 N.A
C) Core 3 N.A21.2 Inside LV Bushings
A) Core 1 N.A
B) Core 2 N.A
C) Core 3 N.A
(a) The separate-source power frequency voltage withstand testfor the winding is the same as for the graded insulated neutralend 50 kVrms
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 72/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13972Page
Item Description (POWER TRANSFORMER) Unit Type I
22 Minimum external creepage distance
-HV bushing mm 2250-LV bushing mm 744-TV bushing mm N.A-Neutral bushing mm 744
23 Sound level (ace, To IEC 60076-10) dBA <7524 Max vibration (at rated condition) P-P micron 100
25 Type of tank ( bell or conventional) Conv.26 Wheels are required (Yes / No) (a) Yes
27 Winding and Oil temp. (Dial Type Indicator or Temp. Monitoring) Dial Type
(see clause 11-5 of chapter PRTR) Indicator
28 Magnetic oil level indicator for main tank
(see clause 11-4 of chapter PRTR) Yes
29 Type of conservator ( Air bag / Conventional) Air Bag
30 Hydraulic jacks required (Yes / No) Yes
31 Oil test kit required ( Yes / No) No32 Oil purification plant required ( Yes / No) No
33 Is On Line Gas Monitoring(OLGM) No
If no, is there need to provision for OLGM
prediction(Yes/No)
-HV Air Bushing-LV Cable Box-TV N.A
35 Lightning arrester supports (required)-HV ( Yes / No) Yes-LV (Yes / No) Yes
-TV (Yes / No) NoFor all cable boxes lightning arrester shall also be in scope of supply.
36 Access ladder required ( Yes / No ) Yes37 Fire protection system required ( Yes / No ) No38 Oil ( Class ace. To IEC 60296) (b)
39 Whether Radiators shall be seperately
40 Radiators ( painted or Hot dip Galvanized) (c)Hot dip
Galvanized
41 Size of copper ground conductor sq. mm >=18542 ACSD test Required (Yes/No) (d)
43 Short circuit mechanical test shall be consider asoptional ( Yes / No) (d) YES
44 Test with LI Chopped on tail included (Yes / No) (d) YES
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 73/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13973Page
Note:
(a) Only for pulling on foundation
(b) The oil selected should have the characteristics of class I and class II oils.
(c) Acc to MFG practice but Hot dip galvanized, spray galvanized are preffered
respectively. (d) All above tests shall be regarded as optional and prices shall be
indicated in schedule of prices for type test and at the option of owner shall be
performed.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 74/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13974Page
20- AX/GRN TRANSFORMER SCHEDULE DATA (I)
RATING AND CHARACTERISTIC OF AX/GRN TRANSFORMER
Item Descripti
(AX/GRN TRANSFORMER) Uni
1 Substation name(s) ...........Substation2 Instaliation(lndoor/Outdoor) Outdoor
3 Three phase or Single phase Three Phase4 Type (Core or Shell) Core5 Number of transformers 26 Pollution Heavy7 Rated Hz 508 Nominal service voltage of windings kVr
20/0.49 Highest of windings ( Um ) kVr
24/1.110 Type of ONAN
11 Vector ZNyn1112 INSULATION LEVELS AT SEA LEVEL m 1500
STANDARD
1-Lightning Impulse withstand-
kVp
125/170-
kVp
N.A2-One minute power frequency (a)
-
kVr
50/70-
kVr
3/-13 External secondary load kVA 25014 Evaluation rate of no load loss
-Foreign currency portion $/k
-Rial portion RLS
- Total Converted $/k
15 Evaluation rate of load loss-Foreign currency portion $/k
-Rial portion RLS
- Total Converted $/k
16 Rated interconnected star winding-
A 385-
A 1154-
s 3017 Off circuit Tap changer
-
HV-N- Total range +- 2*2.5%
(a) The separate-source power frequency voltage withstandtest for the winding is the same as for the graded insulatedneutral end 50 kVrms
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 75/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13975Page
Item Description (AX/GRN TRANSFORMER) Uni
18 Max. temperature rise at rated powerprefault ambient temp. of :
1-winding deg
572-Top oil deg
523-Hot deg
7019 Im edance volta e at rated current
low voltage side power rating ( HV Il V ) % 4to 6
20 Zero sequence impedance of HV winding O/
4021 Sound level (ace, To IEC 60076-10) dB
<=5522 Oil ( Class ace. To IEC 60296) (a)23 Method of terminal connections:
-HV terminals (Air bushing or Cable box) Cable Box-HV (Air bushing or Cable box) Air Bushing-LV (Air bushing or Cable box) Cable Box
24 Bushing
Min. Rated Current(HV/HV Neutral /LV) Am
1000
Min. Short Circuit Current(HV) kA 25
test tap required (Yes/No) YesBushing type current transformers
-Required ( Yes 1 No ) Yes-No of cores (HV-HVN-LV) N.A-2-N.A-
Inside HV-N Bushings
N.A
A) Core 1
N.A
B) Core 2
25 Minimum external creepage distance-HV m
600-Neutral bushing m
60026 Max vibration (at rated condition) P-P mic
5027 Type of tank ( bell or conventional) Conv.28 Wheels are required (Yes 1 No) (b) Yes
29 Type of conservator ( Air bag / Conv.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 76/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13976Page
30 Lightning arrester supports (required)
-HV ( Yes 1 No) No-LV (Yes 1 No) No
For all cable boxes lightning arrester shall also
be in scope of supply.
31 Access ladder required ( Yes 1 No ) No
32 Radiators ( painted or Hot dipGalvanized) (c) Hot dipGalvanized
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 77/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13977Page
(a) The oil selected should have the characteristics of class I and class II oils.(b) Only for pulling on foundation
(c)Acc to MFG practice but Hot dip galvanized, spray galvanized are preffered
respectively.
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 78/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13978Page
21- DCS SCHEDULE DATA (I )
RATING AND CHARACTERISTICS OF DI STRIBUTED CONTROL SYSTEM
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
1 System functional requirements
1-1Capability of levels of system access
protectionYes/No
Yes
1-2 Multiple passwords available within each level
of system access Yes/No Yes
1-3 Single line display Yes/No Yes
1-4 Event processing facility Yes/No Yes
1-5 Alarm processing facility Yes/No Yes
1-6 Analogue measurement handling (e.g.
"change of state or other methods" Yes/No Yes
1-7 Scheduled logging facility Yes/No Yes
1-8 Page logging facility to hard copy color printer Yes/No Yes
1-9 Sequence display Yes/No Yes
1-10 Plant database schedule Yes/No Yes
1-11 Operator manual entry facility Yes/No Yes
1-12 Equipment status display Yes/No Yes
1-13 Fault incident record facility Yes/No Yes
1-14 Tap position by binary or digital input Both is possible1-15 Provision of simple method of database and
display updating, also system manager tasks.
Details of proposals included? Yes/No Yes
1-16 Tagging facility Yes/No Yes
1-17 Interlocking /redundancy feature Yes/No Optional
1-18 Synchro check Yes/No Yes
1-19 Automatic and manual tap changer control Yes/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 79/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13979Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
2 Hardware and software
2-1 Computer equipping for ultimate system Yes/No Yes
2-2 Editing tools for sequential/logic functions Yes/No Yes
2-3 Analogue accuracy form bay unit to display <0.5%
2-4 Automatic/manual diagnostics provided for all
SCS & SMS equipment Yes/No Yes2-5 Automatic system restart following power
interruption Yes/No Yes
2-6 Fault/event recorder files auto upload to
SCMSYes/No
Yes
2-7 Redundant station computer configuration Yes/No Optional
3 Station computer
3-1 Type industrial
3-2 Architecture *
3-3 Hard disc storage *
4 Peripheral server
4-1 Type Acc .to topology
4-2 AC voltage working range volts Acc .to topology
4-3 Service conditions Acc .to topology
4-4 Power consumption Acc .to topology
4-5 Number of LAN connections 2
4-6 Number of peripheral ports Acc .to requirement
4-7 Protocols supported TCP/IP
5 Operator workstation
5-1 Type Industrial/Normal pc5-2 Architecture Acc .to topology
5-3 Operating system software *
5-4 Method of processor expansion *
5-5 Supplied size main memory *
5-6 Hard disc storage *
5-7 Clock *
5-7-1Drift per day (when not synchronized master
clock) 3 sec/day
5-7-2 Method of synchronization with master clock by servers
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 80/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13981Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
5-8Processing system intercommunications
interface LAN
5-8-1 Number supported *
5-8-2 Speed *
5-9 VDU *
5-9-1 Number to be supplied at a workstation *
5-9-2 Complacence with recognized EMC and safety
standards Yes
6 Laptop workstation and SCS & SMS dial in
fault analysis facility Acc .to topology
6-1 Service conditions *
6-2 Method of processor expansion *
6-3 Amount of main memory *
6-4 Size of hard disc *
6-5 Processor speed *
6-6 Operating system software *6-7 SCS & SMS application software *
6-8 Relay and fault recorder analysis software *
6-9 Details of SCS gateway *
7 Event printer Yes/No Yes
8 Hard copy color laser printer Yes
9 Master clock Yes/NTP/SNTP
9-1 type *
9-2 Drift per day *
9-3 Local alarms and contacts for alarms to SCS &SMS. Yes/No Yes
10 Furniture
10-1 Workstation desk Yes/No *
11 Workstation LAN Acc .to topology
11-1 Type LAN
11-2 Coaxial/ optical fiber cable *
11-3 Operating speed HZ *
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 81/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1398Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
11-4 Protocols TCP/IP-IEC61850
11-5 Network management software *
11-6 Dual redundant configuration YES
12 Real time LAN Acc .to topology
12-1 Type Ethernet
12-2 Coaxial optical fiber cable Fiber optic
12-3 Operating speed HZ *
12-4 Dual redundant configuration Yes/Nooptional
13 Communications
13-1 Protocol between station commputer and
BCU/BCPUIEC61850
13-1-1 Info. transfer efficiency (data bits/total bits) No loss of data
13-1-2 Security of control messages Yes/NoYes
13-1-3 Interface Fiber optic/RJ45 Cat6
13-1-4 Transmission rate *
13-2 Type and No. of communication cables to
BCU/BCPU *
13-3 Type & No. of communication cables to
protection relay and disturbance recorder *
13-4 Laptop workstation and SCS & SMS fault
analysis *
13-5 Communications with adjacent SCS & SMS
system *
13-5-1 protocol *
13-5-2 Transmission rate *
14 BCU
14-1 DC voltage working range volts *
14-2 service conditions *
14-3 Architecture *
14-4 System bus interface/speed *
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 82/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13982Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
14-5 Provision of two redundant interfaces to LAN Yes/No Optional
14-6 Logic functions & sequences Yes/No Yes
14-8 Digital inputs
14-8-1 Number of inputs per module *
14-8-2 Digital/software filtering to suppress plant
contact bounce Yes/ No Yes
14-8-3 Time tagging resolution *
14-9 Digital outputs
14-9-1 Number of inputs per module *
14-9-2 Select/check back/ execute facility Yes/No Yes
15 System software
15-1 Make and version of operating system(s) *
15-2 Details of programming language(s) *
15-3 Release versions of software Latest version
16 Performance/availability
16-1 Compliance with performance requirements(start and restart) Yes/No Yes
16-2 Time for redundant station computer to
assume online duties *
16-3 Time for full updating of information *
16-4 Inclusion of availability calculations *
17 Inverter
17-1 Type online
17-2 Input dc voltage and range volts *
17-3 Output Ac voltage range. volts *
17-4 Output rating watts *18 Static switch
18-1 Type Static
18-2 Input dc voltage and range volts *
18-3 Input frequency range Hz *
18-4 Services conditions (temperature and RH) *
18-5 Rating Amps *
19 Power supply housing
19-1 Forced cooling/alarming Yes/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 83/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13983Page
ITEM DESCRIPTION UNITTECHNICAL
PARTICULARS
20 BCR
20-1 Dimension *
20-2 Number of BCRS Acc. to requirement
21 Fiber optics
21-1 Type *
21-2 Class *
21-3 Band width MHZ *
21-4 Min. loss at nominal wavelength dB/km *
21-5 Min. breaking strength N *
*These will be specified by engineer
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 84/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13984Page
22- PLC SCHEDULE DATA (I )
RATING AND CHARACTERISTICS OF PLC
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
1 Power supply
1.1 Nominal supply voltage (Grounded positive pole) VDC -48 ±15%
2 HF
2.1 Carrier
2.1.1 Frequency Range kHz 40 ~ 500
2.1.2 Number of HF frequency modules in the total range Max 2 modules
2.1.3 Frequency allocation step kHz 4
2.1.4Frequency tuning by software and jumper setting
without additional hardwareYES/No YES
2.2 Power output
2.2.1
Tx power output available:
- Single unit Watt 2,10,20,40
- With additional stage Watt 80
2.2.2 Harmonic distortion ≤ 2 %
2.2.3 Return loss on line dB ≥ 14
2.2.4 HF Impedance Ω 50 / 75 / 125 / 150
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 85/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13985Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
2.3 HF Oscillator
2.3.1 Frequency stability Hz ± 10 (-5 ~ +45 °C)
2.3.2 Frequency accuracy Hz ± 2 (@200 kHz)
2.4 HF receiver selectivity
2.4.1 300 Hz Out of band dB 65
2.4.2 4000 Hz Out of band dB 75
2.4.3 6000 Hz Out of band dB 100
2.5 Receiver
2.5.1 Minimum receiver S / N dB 10
2.5.2 Receiver sensitivity dBm -30
2.5.3 Maximum level receiver dBr 4
2.6 Line Filter
2.6.1 Adjustable in the full band YES/No Yes
2.6.2 Adjustable at site YES/No Yes
3 LF
3.1 Voice
3.1.1 2W/4W E & M YES/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 86/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13986Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
3.1.2 Balanced Impedance Ω 600
3.1.3 Return Loss dB ≥ 14
3.1.4
Nominal Level 2W/4W
- Input
- Output
dBm
-7 / 3.5
0 / -3.5
3.1.5
Level Range 2W/4W
- Input
- Output
dBm0 ~ -20 / 0 ~ +20
0 ~ -20 / -20 ~ +8
3.1.6
Programming level rang:
2-wire Tx
2-wire Rx
4-wire Tx
4-wire Rx
dBm
0 to -10
0 to -15
0 to -20
+8 to -10
3.2 Compandor
3.2.1 Compression and Expansion Ratio Compliant ITU-T , G.162
3.2.2 Distortion OF 800 Hz Test Tone Over Link ≤ 2%
3.2.3 Absolute signal level without compression input /
output dBm -8 / 0
3.2.4 Level range input / output dBm -5 ~ -20 /
3.2.5 Impedance Ω 600
3.2.6 Equalized YES/No Yes
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 87/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13987Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
3.2.7 Inherent noise without compandor dBm0p ≤ -55
3.2.8NEAR– END and FAR– END Crosstalk Without
Compandor dBm0p ≤ -50
3.2.9 Inter channel cross talk dBm0p ≤ -60
4 Software Facilities
4.1Platform:
UNIX / WINDOWS XP or 2000YES/No YES
4.2 Equipment Monitoring YES/No YES
4.3 Performance Monitoring YES/No YES
4.4 Fault Localization YES/No YES
5 Local telephone set Provided
6 Environmental conditions for operation and storage
6.1
Temperature range:
Operation
Storage
°C
0 to + 45
- 5 to + 55
6.2 Relative humidity ≤ 95% at 40°C
6.3 Class of standard for mechanicalIEC-721-3-3
Class 3K5
7 Electromagnetic and insulation
7.1 HF Disturbance IEC-255-22-1
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 88/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13988Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
7.2 Fast transient burst IEC-801-4
7.3 Electrostatic discharge IEC-801-2
7.4 Impulse voltage withstand IEC-255-4
7.5 Insulation resistance IEC – 255-5
7.6 ACCORDING TO IEC-60495 OR OTHER RELATIVE
STANDARDSYES/No YES
8 AGC
8.1 OPERATION RANGE dB 50
8.2 ACCURACY dB 1
9 DIAGNOSTIC
9.1 TEST FACILITIES :
9.1.1 LOCAL TEST YES/No YES
9.1.2 REMOTE LOOP TEST YES/No YES
9.1.3 ONLINE MAINTENANCE AND DIAGNOSTIC YES/No YES
9.2 Checking Facilities:
9.2.1 Power Supply YES/No YES
9.2.2 CPU YES/No YES
9.3 Measurement :
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 89/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13989Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
9.3.1 Tx – HF POWER YES/No YES
9.3.2 Rx – CARRIER LEVEL YES/No YES
9.3.3 S/N RATIO YES/No YES
9.3.3 SUPPLY TOLERANCE YES/No YES
10 CAPABILITY OF CONNECTIONG TO OTHER EQUIPMENT
10.1 a)
Tele-protection signaling equipment YES/No YES
10.2 b) PABX YES/No YES
10.3 c) 2 wire (telephone set or PABX) YES/No YES
10.4 d) Synchronous data YES/No YES
10.5 e)
Asynchronous data YES/No YES
10.6 f)
Telegraphy channels YES/No YES
10.7 g)
Alarms YES/No YES
10.8 h) Service terminal YES/No YES
11 Interfaces
11.1 Fiber optic interface YES/No YES
11.2 Asynchronous data interface YES/No YES
11.3 Synchronous data interface YES/No YES
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 90/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13991Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
11.4 G.703 data interface YES/No YES
11.5 LAN data interface YES/No YES
11.6 E1 interface for VOIP YES/No YES
11.7 Serial data interface YES/No YES
11.8 Four wire line interface YES/No YES
11.9 Two wire line interface YES/No YES
11.10 Programming and supervision interface YES/No YES
11.11 Support V.35 protocol YES/No YES
11.12 FAX recognition YES/No YES
11.13 VF telephone channel YES/No YES
11.14 VF data channel (4-wire) YES/No YES
12 Mechanical protection class IP42
13 Upgradable software YES/No YES
14 Full configuration software license Provided
15 Analogue PLC
15.1 Channel transceiver
15.1.1 Single channel extendable to double channel YES/No YES
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 91/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1399Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
15.2 Minimum Channeling Requirement
15.2.1
300 ~ 2000 Hz Voice
2160 ~ 3400 Hz Data
3660 Hz ± 30 Hz FSK Signaling
YES/No YES
15.2.2300 ~ 3400 Hz Voice
3660 Hz ± 30 Hz FSK SignalingYES/No YES
15.2.3 300 ~ 3400 Hz Data YES/No YES
15.2.4 300 ~ 3720 Hz Wideband Transit YES/No YES
15.2.5 Nominal level input/output dBm -12 / -15
15.2.6 Level range input / output dBm -5 / -20
15.2.7 Balanced impedance Ω 600
15.2.8 Return loss dB ≥ 14
15.3 E & M Signaling
15.3.1 Modulation FSK
15.3.2 Bandwidth 120 Hz
15.3.3 Pulse Distortion ≤ 5%
16Standard RS232 interface facility for diagnostic and
maintenance purposesYES/No YES
17 Digital PLC
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 92/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13992Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
17.1 Multiplexing Method in DPLC's TDM
17.2 Automatic Frequency Control (AFC)Elimination VF
variation
17.3 Signal transmission time ms
< 5 (single purpose
mode)
17.4 Data Transmission:
17.4.1
a)
Asynchronous:
Bit rate
Modulation
Interface
bps
50,100,200,600,1
200
FSK
ITU – T, V.24 /
EIA RS 232
17.4.2
b)
Synchronous data transmission
Interface
Bit rate
Modulation
Bit rate
Modulation
Bps
Bps
ITU – T, V.24 / EIA
RS 232
1200 , 2400
QPSK
4800,9600
QAM
17.5 Real-time clock integrated and synchronizable YES/No YES
17.6 Direct connection to SDH & PDH multiplexer YES/No YES
17.7 Capability of Baud Rate changes according to signal to
noise ratioYES/No YES
18 Alarms
18.1 Power supply failure YES/No YES
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 93/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13993Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
18.2 Door open / Cabinet alarm YES/No YES
18.3 Link alarm YES/No YES
18.4 Low S/N ratio on data channels YES/No YES
18.5 Interface alarm YES/No YES
18.6 Warning feature YES/No YES
18.7 Absence of transmit signal output YES/No YES
18.8 Absence of receive signal input YES/No YES
18.9 Fuse break YES/No YES
18.10 Power amplifier failure YES/No YES
18.11 Excessive receive level YES/No YES
18.12 Low receive level YES/No YES
18.13 Frequency synthesizer failure YES/No YES
18.14 Loss of synchronism YES/No ESY
18.15 Card out YES/No YES
18.16 BER < 10-3 YES/No YES
18.17 Failure of auto-test YES/No YES
18.18 Pilot signal level low or fail YES/No YES
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 94/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13994Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
18.19 Any disconnection between terminals YES/No YES
PABX SCHEDULE DATA (I)
RATING AND CHARACTERISTICS OF DISTRIBUTED CONTROL SYSTEM
PABX
NO DESCRIPTION
TECHNICAL
REQUIRMENT
1 GENERAL
1.1 Manufacturer (Name & Country) —
1.2 Manufacturer's Model Designation —
1.3 Designation technology Converged
technology
1.4 PABX basis TDM-PCM
& IP & ISDN
1.5 Call processing performanceNon-
blocking
1.6 Hardware cards Hot-plugging Yes
1.7 Redundancy
• DC -DC converter Yes
• Other (must be mentioned) Yes
1.8 System remoting
• Relative to central switch Yes
• Unrelated to central switch Yes
1.9 Busy Hour Call Attempts (BHCA) ≥ 250000
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 95/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13995Page
1.10Stand alone extending up to 5000
portYes
1.11 PABX Operating System (OS) :
• BasisOpen
Source
• Man Machine Interface (MMI) Windows
1.12 Supported Carriers :
• E1 optical
& electrical
• Ethernet IEEE 802.3
• Cable6 wire and 2
wire
o Input VF level 0 dBm
o Output VF level 0 dBm
• Microwave 6 wire
o Input VF level -16dBm
• QSIG Yes
• R2 Yes
• CAS Yes
1.13 IP trunking protocolsmust be
mentioned
1.14 Time limitation for trunk access Yes
(programm
able)
1.15 Automatic attendant Yes
1.16 Voice mail Yes
1.17 Cabinet color code RAL 7032
1.18 Cabinet painting typeas
mentioned
in tender
doc
1.19 IP code for cabinet must be
mentioned
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 96/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13996Page
1.20 Dimensions (HxWxD) in cmmust be
mentioned
2 Management and accounting
2.1Supervision and programming for
digital trunksFull
2.2 List Cost Routing (LCR) Yes
2.3
Accounting management & Call
charge & Traffic Yes
report must be
mentioned
2.4PABX software and database
backup
flash
memory
& CD ROM
& flappy
disk
mention
other media
2.5 Fault declaration and warning :Programma
ble
• System level Yes
• Card level Yes
• Port level Yes
• Other levelsmust be
mentioned
2.6Real time alarm, event, status and
system states:
• Representation Yes
• Saving Yes
• Management Yes
2.7 Software offline working Yes
3 Analog extensions
3.1 Line type Twisted pair
3.2 Line loop resistance ≤ 2000Ω
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 97/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13997Page
• Min. distance 6km
(0.4mm
diameter)
• Max. distance 12km
(0.6mm
diameter)
3.3 Line insulation ≥ 50 KΩ
3.4 Earth recall recognized by resistanceto ground
≤ 30 Ω
3.5Line seizure (off-hook) recognition
time≥ 100ms
3.6 DialingDTMF and
Pulse
3.7 Line release (on hook) recognition
time> 200 ms
3.8Resistance between the two line
terminals during> 100KΩ
the break (loop open)
3.9Voltage drop between the two line
terminals≤ 5.5V
during the make (loop close) for 18mA ≤ I
≤ 28 mA
3.10Stabilization time of the line current
for values≤ 15 ms
greater than 15 mA
3.11 Attenuation on dialing impulses
during
≥ 85 dB
conversation
3.12 Call signaling :
• Maximum voltage output 75 Vrms
• Frequency 25Hz
• Normal charge 2REN
3.13 Twisted pair powering :
• Idle current ≤ 100µA
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 98/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13998Page
• Loop current with loop resistance
< 1 KΩ≥ 22mA
• Current with loop in short circuit ≤ 28mA
3.14 Caller ID:
• Subscriber line protocol over the
local for
On hook
data
display (and related) servicestransmissio
n
• Method for CLI transmissionData
transmission
prior to
ringing
• Terminal Equipment Alerting
Signal
Ringing
Pulse
3.15 Expandability (Up to 48 port) Yes
4 Digital extensions
4.1 Line type Twisted pair
4.2MULTI-CALL Key system for
telephone setYes
4.3 Local power for telephone set No
4.4 Facilities of telephone setmust be
mentioned
4.5Minimum distance for digital phone
0.6 mm600m
twisted pair
4.6 Power supply• Current consumption 50mA Max.
4.7 Expandability (Up to 48 port) Yes
5 IP extensions
5.1Technical characteristics of IP
phone:
5.1.1 LCDWith
backlit, min 20
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 99/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13999Page
character in
two lines
5.1.2 Function-Key Min 12 keys
with LED
5.1.3 Adjustable keysRing tone ,
voices
and
disconnection
5.1.4 Hands-free possibility Yes (full
duplex)
5.1.5 Interactive user Min 2
dialog keys
5.1.6 Port Dual ,
10/100 Mbps
6 ISDN
6.1 Protocol PRI
6.2The impedance to ground at both
the input & output:
• For freq. from 0 Hz to 1 MHz > 1000Ω
6.3Maximum line length such that the
maximum
attenuation does not exceed 6 dB at
1 MHz
6.4Characteristics of the transmitted
signal
6.4.1 Frequency2048KHz ±
50ppm
6.4.2 Line coding HDB3
6.4.3Number of couplings for each
transmission direction :
• Coaxial One
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 100/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13911Page
o Impedance 75 Ω
o Impulse nominal peak voltage 2.37 V
o Maximum voltage in impulse
absence± 237 mV
• Balanced twisted pair One
o Impedance 120 Ω
o Impulse nominal peak voltage 3.0V
o Maximum voltage in impulse
absence± 300 mV
6.4.4 Nominal duration of impulse 244 nsec
6.4.5 Amplitude ratio between positive
and negative1±0.05
impulses with reference to ground
6.4.6Ratio of duration between positive
and negative1±0.05
impulses at 50%
6.4.7 Rise-time64 nsec
Max.
6.4.8 Overshoot 20% Max.
6.4.9Output signal balancing, using
120Ω connection :
• Up to 1MHz ≥ 40 dB
• From 1MHz to 30MHz Atten.20dB/
decade
6.5 Characteristics of received signal
6.5.1 Impedance characteristic75Ω or
120Ω
6.5.2Max. attenuation with variations
proportional to6 dB
square root of f
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 101/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1391Page
6.5.3 Return loss:
• From 512KHz to 1024KHz 12dB
• From 1024 KHz to 2048 KHz 18dB
• From 2048 KHz to 3072 KHz 14dB
6.6 Jitter in reception
(Freq. = 2048 KHz ± 32 ppm; 1UI =
488 nsec):
• 0 to 12x10-6
Hz 20.5 UI
• 12x10-6
to 20Hz Atten.20dB/
decade
• 20 to 2400Hz 1.5UI
• 2400 to 18KHz Atten.20dB/
decade
• 18KHz to 100KHz 0.2UI
6.7 Jitter in transmission
(Freq. = 2048 KHz ±32 ppm);(Band-pass filter with cut off
frequencies f1, f2):
• f1 = 20Hz , f2 = 100KHz B1 = 1.6UI
• f1 = 700Hz , f2 = 100KHz B2 = 0.11 UI
7 E1 link
7.1 ProtocolsPRI (other
protocols
must be
mentioned)
7.2R2 MF Transmitter and receiver
characteristicsComply
with CCITT
Q.454
7.3 Expandability (Up to 4 card) YES
7.4 R2 REGISTER
7.4.1 Group monitoring LEDITU-T
G.712
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 102/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13912Page
7.4.2 AvailabilityEvery
individual
2Mb/s card
7.4.3 Settings for Vector alarm wire:
• Applicable input standardsGround /
Open
• Applicable standardGround
<200Ω& Open
>50KΩ
7.4.4 Setting for compander exclusion:
• Output standard Ground /
Open
• Output contact typeOpen
collector
• Applicable negative voltage < 60V
(absolute
value)
• Max. Current with residual voltage
< 3V 30mA
between contact and ground
7.4.5Modem characteristics (data
channel of 2/4 wire):
• Standard ITU-T V.32
• Data rate14400 bps
max.
• Modulation type FSK
• Recognition threshold of carrier
detect for a
(-43) ~ (-
45.5)
change from OFF to ON dBm
• Recognition threshold of carrier
detect for a
(-45.5) ~ (-
48)
change from ON to OFF dBm
7.4.6RS232 V24(data channel of
multiplexer)
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 103/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13913Page
• Standard EIA
• Data rate19200bps
Max.
• Async. Parameters 8N2
• Clock from DCE
• Code NRZ
• Protocol HDLC sync
8 Analog 6 wired E&M Trunks
8.1 signaling protocols:
• Immediate dial trunks Yes
• Delay dial trunks
Yes
(Programmabl
e)
• E&M continues signaling trunks Yes
• Wink start trunks
Yes
(Programmabl e)
• E&M pulse signaling trunks
Yes
(Programmabl
e)
8.2 Expandability (Up to 700 port) Yes
8.3 Analog tie-line interface with E&M
signaling
8.3.1 Output signaling (M wire):
• Output standardsGround /
open
• Output contact typeOpen
collector
• Applicable negative voltage < 60V
(absolute
value)
• Max. Current between contact and
ground30mA
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 104/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13914Page
(with residual voltage < 3V)
• Pulse repetition rateProgramma
ble
• Break / make ratioProgramma
ble
• Break / make ratio tolerance ± 1ms
8.3.2Output signaling (compander
exclusion wire):
• Output standardsGround /
open
• Output contact typeOpen
collector
• Applicable negative voltage < 60V
(absolute
value)
• Max. Current between contact and
ground30mA
(with residual voltage < 3V)
8.3.3 Input signaling (E wire):
• Applicable incoming standards
o Ground R < 200Ω
o Open R > 50 KΩ
• Pulse repetition rateProgramma
ble
• Break / make ratioProgramma
ble
• Minimum duration of break /
make allowed
Programma
ble
• input signaling filter Digital
• Assured recognition of break > 10ms
• Assured non-recognition of break < 6ms
8.3.4 Input signaling (vector alarm wire):
• Applicable incoming standards
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 105/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13915Page
o Ground R < 200Ω
o Open R > 50KΩ
9 Analog CO. trunks
9.1 Type Twisted pair
(comply
with Iran
Telecommunication
Cornpany)
9.2 Features:
• Tone / DP Yes
• Caller -ID Yes
• Pulse metering Yes
• Timer abilities Yes
9.3DTMF transmitter and receiver
characteristicsITU-T Q23
10 Wire-Less extension
10.1 Features All PABX
supported
features
10.2 Data / voice 64Kb/s
on B
channel
10.3
Signaling / commands toward
terminations 16Kb/son D
channel
10.4Signaling / commands toward TDM
proc.37440 Kb/s
on
asynchronous
serial
fullduplex
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 106/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13916Page
10.5 Max. distance 1000 m
10.6 Max. current consumption 100 mA
CONSOLE
NO DESCRIPTION
TECHNICAL
REQUIRMENT
1 Console
1.1 Facilities:
• TENANT Yes
• Hands free Yes
• Headset Yes • Hold Yes
• Call transfer and intercom
between consolesYes
• Station name, time and date
displayingYes
• Out of service displaying Yes
1.2Sending emergency signal from
stationYes
1.3 Dialling over trunk Yes
SCHEDULE MDF & DDF (I)
MAIN & DIGITAL DISTRIBUTION FRAME (MDF & DDF)
NO DESCRIPTION
TECHNICAL
REQUIRMENT
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 107/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13917Page
NO DESCRIPTION TECHNICAL
1 MDF
1.1 Manufacturer (Name &
Country)
—
1.2 Manufacturer's Model
Designation
—
1.3 Mounting style stand alone rack mount
2 MDF CABINET
2.1 Material
2.2 Color code RAL 7032
2.3 Painting type as mentioned
in tender doc
2.4 IP code for cabinet must be mentioned
2.5 Weight must be mentioned
2.6 Dimensions (HxWxD) in
cm
must be mentioned
2.7 Capacity of terminal
blocks
must be mentioned
3 MDF TERMINAL BLOCK
3.1 Connection capacity per
block
must be mentioned
3.2 Connection type :
Normally close Yes
Normally open Yes
3.3 Protection for
connections :
Over voltage Yes
Over current Yes
4 Accessories must be mentioned
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 108/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13918Page
NO DESCRIPTION TECHNICAL
5 DDF
5.1 DDF(cabinet & terminal
connections) for any type
of 2Mbps trunk Yes
SCHEDULE TPS (I )
TPS TECHNI CAL SCHEDULES
TECHNICAL
REQUIRMENT
PARAMETERROW
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 109/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13919Page
TECHNICAL
REQUIRMENT
PARAMETERROW
MANUFACTURER1
NAME AND COUNTRY1-1
TYPE REFERENCE1-2
VALID TEST REFERENCE FOR2
YES ACCORDING TO IEC-60834 AND OTHER RELATIVE
STANDARDS
2-1
INTERFACE3
ANALOG ,600Ω,
300~2400Hz
INTERFACE TYPE BETWEEN TPS AND PLC3-1
OPTICAL INTERFACE /
G.703-64Kbps
INTERFACE TYPE BETWEEN TPS AND OTHER
TELECOMMUNICATION SYSTEMS SUCH AS FIBER
OPTIC AND DIGITAL CHANNEL
3-2
COMMANDS4
4≥ NUMBER OF INDEPENDENT COMMANDS4-1
2≥ NUMBER OF SIMULTANEOUS COMMANDS4-2
YESCOMMAND PRIORITY4-3
YES
YES - FSK
TYPE OF COMMAND TRANSMISSION:
CODED
NONCODED
4-4
TYPE OF TPS SCHEMS5
YESINTER TRIPPING (DIRECT)5-1
YESPERMISSIVE TRIPPING (UNDER REACH)5-2
YESPERMISSIVE TRIPPING (OVER REACH)5-3
YESBLOCKING5-4
OPERATION TIME6
DIRECT TRIPPING (msec)6-1
PERMISSIVE TRIPPING (msec)6-2
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 110/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1391Page
TECHNICAL
REQUIRMENT
PARAMETERROW
BLOCKING TRIPPING (msec)6-3
2MINIMUM INITALIZATION TIME FOR COMMAND
(mesc)
6-4
100MAXIMUM ACCEPTABLE PROPAGATION TIME FOR
TELECOMMUNICATION LINK (mesc)
6-5
40 ADDITIONAL DELAY BY NOISE RANGE (mesc)6-6
TRANSMITTER 7
Tx LEVEL RANGE FOR COMMAND / GUARD (dBm)7-1
≥20RETURN LOSS (dBm)7-2
1NUMBER OF SIGNALS FOR EACH COMMAND7-3
≤ 5% HARMONIC DISTORTION7-4
10≥ LEVEL BOOSTING OF COMMANDS(dB)7-5
RECEIVER 8
Rx LEVEL RANGE FOR COMMAND / GUARD (dBm)8-1
≥20RETURN LOSS (dB)8-2
≥ 25DYNAMIC RANGE (dB)8-3
≥ 55RECEIVER SELECTIVITY – 300 Hz OUT OF GUARD'S
AND COMMAND'S RANGE (dBm0)
8-4
≥ 5S/N RATIO (dB)8-5
HIGH VOLTAGE INTERFACES 9
48 ~ 220COMMAND AND START INPUT VOLTAGE RANGES
(Vdc)
9-1
≥ 2NUMBER OF CONTACTS FOR EACH COMMAND9-2
≥ 1NUMBER OF ALARM CONTACT FOR EACH
COMMAND
9-3
250COMMAND AND ALARM CONTACTS RATINGS (VA)9-4
TYPE OF COMMAND CONTACTS9-5
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 111/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 139Page
TECHNICAL
REQUIRMENT
PARAMETERROW
TYPE OF ALARM CONTACTS9-6
DURATION TIME BEFORE OPERATING OF ALARM
RELAYS (msec)
9-7
ALARM CONDITIONS 10
YESTRANSMITTER FAILED10-1
YESPLC FAILED10-2
YESGUARD SIGNAL ABSENCE10-3
YESLOW S/N RATIO10-4
YESNO CARD LOCATED10-5
YES ANY DAMAGE OF BOARDS10-6
YESFAR-END TPS TURNED OFF10-7
YESPRESENCE OF GUARD AND COMMON SIGNAL
SIMULTANEOUSLY
10-8
YESPRESENCE OF COMMAND SIGNAL CONTINUOUSLY10-9
YESWATCH DOG ACTIVATION ALARM10-10
SOFTWARE FACILITIES11
YESTPS HARDWARE ASSIGNMENT11-1
YESTPS CONFIGURATION11-2
YESCOMMAND ASSIGNMENT11-3
YESCOMMAND AND ALARM ASSIGNMENT11-4YESOPERATION TIME ASSIGNMENT FOR EACH
COMMAND INDEPENDENTLY
11-5
YESDURATION AND DELAY TIME ASSIGNMENT FOR
EACH COMMAND INDEPENDENTLY
11-6
YESRECORDE FOR COUNTERS , EVENTS AND FAULTS
WITH TIME TAG
11-7
YESREMOTE TPS CONFIGURATION AND MONITORING11-8
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 112/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1392Page
TECHNICAL
REQUIRMENT
PARAMETERROW
BASIS OF TIME12
YESINTERNAL TIME BASE12-1
YESEXTERNAL TIME BASE – REAL TIME
CLOCK SUCH AS GPS INTERFACE
12-2
DEPENDABILITY AND SECURITY (FOR 10 exp -3)13
≥ 5S / N RATIO (dB)13-1
≤ 15 OPERATION TIME (msec)13-2
TYPE AND BANDWIDTH OF NOISE13-3
TEST FACILITIES14
YESLOCAL TEST14-1
YESLOCAL LOOP TEST14-2
YESREMOTE LOOP TEST14-3
YESPERIODICALLY AUTO TEST14-4
POWER SUPPLY15
-48 VCDNOMINAL SUPPLY VOLTAGE15-1
-15%,+20%SUPPLY TOLERANCE15-2
5%< POWER SUPPLY RIPPLE15-3
15≤ POWER CONSUMPTION w15-4
ENVIRONMENTAL CONDITION16
OPERATION16-1
-5 ~+55°CTEMPERATURE RANGE C°16-1-1
40°C 95% at ≤ RELATIVE HUMIDITY %16-1-2
IEC 721 -3-3
CLASS 3 M 1
CLASS OF STANDARD FOR MECHANICAL16-1-3
STORAGE16-2
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 113/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1393Page
TECHNICAL
REQUIRMENT
PARAMETERROW
-40 ~ +70°CTEMPERATURE RANGE C°16-2-1
40°C 95% at ≤ RELATIVE HUMIDITY %16-2-2
IEC-721-3-1
CLASS 1 K 5
CLASS OF STANDARD FOR MECHANICAL16-2-3
DIAGNOSTIC17
YES
YES
ONLINE MAINTENANCE AND DIAGNOSTIC17-1
YES
YES
CHECKING FACILITIES :
POWER SUPPLY
OTHERS
17-2
ELECTROMAGNETIC AND INSULATION18
2500 V / IEC-255-22-1HF DISTURBANCE18-1
2000 V / IEC-801-4FAST TRANSIENT BURST18-2
8000 V / IEC-801-2ELECTROMAGNETIC DISCHARGE18-3
YES ALL OF THE PERIPHERAL EQUIPMENTS , TOOLS ,
HARDWARE , SOFTWARE AND TECHNICAL
DOCUMENTS INCLUDED WITH EACH TPS
TERMINAL
19
23- SCHEDULE LI NE TRAP AND LMU (I )
LI NE TRAP AND LMU TECHNICAL SCHEDULES
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 114/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1394Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
System Characteristics
1 Nominal service voltage kV 63
2 Highest system voltage kV 72.5
3 Rated frequency Hz 50
4 Number of phases 3 phase
5 Type of neutral grounding Effective
6 Surge impedance of power transmission lines Ω 400
Line Trap Characteristics
7 Type Outdoor, Air core, Dry,
single phase
8 Basic Insulation Level. kV peak As per IEC 60353
/19.3.1
9 One minute power frequency withstand voltage kV rms As per IEC 60353
/10.1
10 Continuous current of line trap at IEC 353 A 1250
11 Rated short circuits withstand current kA rms 40
12 Rated asymmetrical short time current kA peak 100
13 Rated duration of short circuit Sec. 1
14 Inductance of main coil m.H 0.5
15 Required blocking bandwidth for line trap kHz 60- 400
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 115/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1395Page
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
16 Max. Tapping loss within the specified band width db 2.6
17 Max. R.I.V. level measured at 1.15 * Um KV & 1 MHz v -
18 Type & Rated discharge current of protective device kA Zno / 10
19 Whether bird barrier is required? Yes
20 Method of the line trap installation suspension
21 Blocking Impedance of line trap within the specified
bandwidth
Ω 600
Line matching Unit
22 Type of coupling. Phase- Ground
23 Degree of protection of line matching unit cabinet IP55
24 Drain coil to connect output lead of CVT to ground Yes
25 Whether disconnect and ground switch for
grounding the L.M.U is required?
Yes
24- PABX SCHEDULE DATA (I)RATING AND CHARACTERISTICS OF DISTRIBUTED CONTROL SYSTEM
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 116/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1396Page
PABX
NO DESCRIPTION
TECHNICAL
REQUIRMENT
1 GENERAL
1.1 Manufacturer (Name & Country) —
1.2 Manufacturer's Model Designation —
1.3 Designation technology Converged
technology
1.4 PABX basis TDM-PCM
& IP & ISDN
1.5 Call processing performance Non-blocking
1.6 Hardware cards Hot-plugging Yes
1.7 Redundancy
• DC -DC converter Yes
• Other (must be mentioned) Yes
1.8 System remoting
• Relative to central switch Yes
• Unrelated to central switch Yes
1.9 Busy Hour Call Attempts (BHCA) ≥ 250000
1.10
Stand alone extending up to 5000
port Yes
1.11 PABX Operating System (OS) :
• Basis Open Source
• Man Machine Interface (MMI) Windows
1.12 Supported Carriers :
• E1 optical
& electrical
• Ethernet IEEE 802.3
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 117/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1397Page
• Cable6 wire and 2
wire
o Input VF level 0 dBm
o Output VF level 0 dBm
• Microwave 6 wire
o Input VF level -16dBm
• QSIG Yes
• R2 Yes
• CAS Yes
1.13 IP trunking protocolsmust be
mentioned
1.14 Time limitation for trunk access Yes
(programmable)
1.15 Automatic attendant Yes
1.16 Voice mail Yes
1.17 Cabinet color code RAL 70321.18 Cabinet painting type as mentioned
in tender doc
1.19 IP code for cabinet must be
mentioned
1.20 Dimensions (HxWxD) in cmmust be
mentioned
2 Management and accounting
2.1
Supervision and programming for
digital trunks Full
2.2 List Cost Routing (LCR) Yes
2.3 Accounting management & Call
charge & TrafficYes
report must be
mentioned
2.4PABX software and database
backup flash memory
& CD ROM
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 118/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1398Page
& flappy disk
mention other
media
2.5 Fault declaration and warning : Programmable
• System level Yes
• Card level Yes
• Port level Yes
• Other levelsmust be
mentioned
2.6Real time alarm, event, status and
system states:
• Representation Yes
• Saving Yes
• Management Yes
2.7 Software offline working Yes
3 Analog extensions
3.1 Line type Twisted pair
3.2 Line loop resistance ≤ 2000Ω
• Min. distance 6km
(0.4mm
diameter)
• Max. distance 12km
(0.6mm
diameter)
3.3 Line insulation ≥ 50 KΩ
3.4Earth recall recognized by resistance
to ground≤ 30 Ω
3.5Line seizure (off-hook) recognition
time≥ 100ms
3.6 Dialing DTMF and Pulse
3.7 Line release (on hook) recognition
time> 200 ms
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 119/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1399Page
3.8Resistance between the two line
terminals during> 100KΩ
the break (loop open)
3.9Voltage drop between the two line
terminals≤ 5.5V
during the make (loop close) for 18mA ≤ I ≤
28 mA
3.10 Stabilization time of the line current for values
≤ 15 ms
greater than 15 mA
3.11 Attenuation on dialing impulses
during≥ 85 dB
conversation
3.12 Call signaling :
• Maximum voltage output 75 Vrms
• Frequency 25Hz
• Normal charge 2REN
3.13 Twisted pair powering :
• Idle current ≤ 100µA
• Loop current with loop resistance
< 1 KΩ≥ 22mA
• Current with loop in short circuit ≤ 28mA
3.14 Caller ID:
• Subscriber line protocol over the
local forOn hook data
display (and related) services transmission
• Method for CLI transmissionData
transmission
prior to ringing
• Terminal Equipment Alerting
SignalRinging Pulse
3.15 Expandability (Up to 48 port) Yes
4 Digital extensions
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 120/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13921Page
4.1 Line type Twisted pair
4.2MULTI-CALL Key system for
telephone setYes
4.3 Local power for telephone set No
4.4 Facilities of telephone setmust be
mentioned
4.5Minimum distance for digital phone
0.6 mm600m
twisted pair
4.6 Power supply
• Current consumption 50mA Max.
4.7 Expandability (Up to 48 port) Yes
5 IP extensions
5.1Technical characteristics of IP
phone:
5.1.1 LCD With backlit,min 20
character in two
lines
5.1.2 Function-Key Min 12 keys
with LED
5.1.3 Adjustable keysRing tone ,
voices
and
disconnection
5.1.4 Hands-free possibility Yes (full duplex)
5.1.5 Interactive user Min 2 dialog
keys
5.1.6 Port Dual , 10/100
Mbps
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 121/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1392Page
6 ISDN
6.1 Protocol PRI
6.2The impedance to ground at both
the input & output:
• For freq. from 0 Hz to 1 MHz > 1000Ω
6.3Maximum line length such that the
maximumattenuation does not exceed 6 dB at
1 MHz
6.4Characteristics of the transmitted
signal
6.4.1 Frequency2048KHz ±
50ppm
6.4.2 Line coding HDB3
6.4.3Number of couplings for each
transmission direction :
• Coaxial One
o Impedance 75 Ω
o Impulse nominal peak voltage 2.37 V
o Maximum voltage in impulse
absence± 237 mV
• Balanced twisted pair One
o Impedance 120 Ω
o Impulse nominal peak voltage 3.0V
o Maximum voltage in impulse
absence ± 300 mV
6.4.4 Nominal duration of impulse 244 nsec
6.4.5 Amplitude ratio between positive
and negative1±0.05
impulses with reference to ground
6.4.6Ratio of duration between positive
and negative1±0.05
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 122/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13922Page
impulses at 50%
6.4.7 Rise-time 64 nsec Max.
6.4.8 Overshoot 20% Max.
6.4.9Output signal balancing, using
120Ω connection :
• Up to 1MHz ≥ 40 dB
• From 1MHz to 30MHz Atten.20dB/dec
ade
6.5 Characteristics of received signal
6.5.1 Impedance characteristic 75Ω or 120Ω
6.5.2Max. attenuation with variations
proportional to6 dB
square root of f
6.5.3 Return loss:• From 512KHz to 1024KHz 12dB
• From 1024 KHz to 2048 KHz 18dB
• From 2048 KHz to 3072 KHz 14dB
6.6 Jitter in reception
(Freq. = 2048 KHz ± 32 ppm; 1UI =
488 nsec):
• 0 to 12x10-6
Hz 20.5 UI
• 12x10
-6
to 20Hz
Atten.20dB/dec
ade
• 20 to 2400Hz 1.5UI
• 2400 to 18KHz Atten.20dB/dec
ade
• 18KHz to 100KHz 0.2UI
6.7 Jitter in transmission
(Freq. = 2048 KHz ±32 ppm);
(Band-pass filter with cut off
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 123/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13923Page
frequencies f1, f2):
• f1 = 20Hz , f2 = 100KHz B1 = 1.6UI
• f1 = 700Hz , f2 = 100KHz B2 = 0.11 UI
7 E1 link
7.1 ProtocolsPRI (other
protocols
must bementioned)
7.2R2 MF Transmitter and receiver
characteristicsComply
with CCITT
Q.454
7.3 Expandability (Up to 4 card) YES
7.4 R2 REGISTER
7.4.1 Group monitoring LED ITU-T G.712
7.4.2 Availability Every individual2Mb/s card
7.4.3 Settings for Vector alarm wire:
• Applicable input standards Ground / Open
• Applicable standard Ground <200Ω
& Open >50KΩ
7.4.4 Setting for compander exclusion:
• Output standard Ground / Open
• Output contact type Open collector • Applicable negative voltage < 60V
(absolute value)
• Max. Current with residual voltage
< 3V 30mA
between contact and ground
7.4.5Modem characteristics (data
channel of 2/4 wire):
• Standard ITU-T V.32
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 124/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13924Page
• Data rate 14400 bps max.
• Modulation type FSK
• Recognition threshold of carrier
detect for a(-43) ~ (-45.5)
change from OFF to ON dBm
• Recognition threshold of carrier
detect for a(-45.5) ~ (-48)
change from ON to OFF dBm
7.4.6RS232 V24(data channel of
multiplexer)
• Standard EIA
• Data rate 19200bps Max.
• Async. Parameters 8N2
• Clock from DCE
• Code NRZ
• Protocol HDLC sync
8 Analog 6 wired E&M Trunks
8.1 signaling protocols:
• Immediate dial trunks Yes
• Delay dial trunksYes
(Programmable)
• E&M continues signaling trunks Yes
• Wink start trunksYes
(Programmable)
• E&M pulse signaling trunksYes
(Programmable)
8.2 Expandability (Up to 700 port) Yes
8.3 Analog tie-line interface with E&M
signaling
8.3.1 Output signaling (M wire):
• Output standards Ground / open
• Output contact type Open collector
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 125/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13925Page
• Applicable negative voltage < 60V
(absolute value)
• Max. Current between contact and
ground30mA
(with residual voltage < 3V)
• Pulse repetition rate Programmable
• Break / make ratio Programmable
• Break / make ratio tolerance ± 1ms
8.3.2Output signaling (compander
exclusion wire):
• Output standards Ground / open
• Output contact type Open collector
• Applicable negative voltage < 60V
(absolute value)
• Max. Current between contact and
ground
30mA
(with residual voltage < 3V)
8.3.3 Input signaling (E wire):
• Applicable incoming standards
o Ground R < 200Ω
o Open R > 50 KΩ
• Pulse repetition rate Programmable
• Break / make ratio Programmable
• Minimum duration of break /make allowed Programmable
• input signaling filter Digital
• Assured recognition of break > 10ms
• Assured non-recognition of break < 6ms
8.3.4 Input signaling (vector alarm wire):
• Applicable incoming standards
o Ground R < 200Ω
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 126/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13926Page
o Open R > 50KΩ
9 Analog CO. trunks
9.1 Type Twisted pair
(comply with
Iran
Telecommunicat
ion
Cornpany)
9.2 Features:
• Tone / DP Yes
• Caller -ID Yes
• Pulse metering Yes
• Timer abilities Yes
9.3DTMF transmitter and receiver
characteristicsITU-T Q23
10 Wire-Less extension
10.1 Features All PABX
supported
features
10.2 Data / voice 64Kb/s
on B channel
10.3Signaling / commands toward
terminations16Kb/s
on D channel
10.4Signaling / commands toward TDM
proc.37440 Kb/s
on asynchronous
serial full-duplex
10.5 Max. distance 1000 m
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 127/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13927Page
10.6 Max. current consumption 100 mA
CONSOLE
NO DESCRIPTION
TECHNICAL
REQUIRMENT
1 Console
1.1 Facilities:
• TENANT Yes
• Hands free Yes
• Headset Yes
• Hold Yes
• Call transfer and intercombetween consoles
Yes
• Station name, time and date
displayingYes
• Out of service displaying Yes
1.2Sending emergency signal from
stationYes
1.3 Dialling over trunk Yes
SCHEDULE MDF & DDF (I)
MAIN & DIGITAL DISTRIBUTION FRAME (MDF & DDF)
NO DESCRIPTION
TECHNICAL
REQUIRMENT
1 MDF
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 128/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13928Page
NO DESCRIPTION TECHNICAL
1.1 Manufacturer (Name &
Country)
—
1.2 Manufacturer's Model
Designation
—
1.3 Mounting style stand alone
rack mount
2 MDF CABINET
2.1 Material
2.2 Color code RAL 7032
2.3 Painting type as mentioned
in tender doc
2.4 IP code for cabinet must be mentioned
2.5 Weight must be mentioned
2.6 Dimensions (HxWxD) incm
must be mentioned
2.7 Capacity of terminal
blocks
must be mentioned
3 MDF TERMINAL BLOCK
3.1 Connection capacity per
block
must be mentioned
3.2 Connection type :
Normally close Yes
Normally open Yes
3.3 Protection for
connections :
Over voltage Yes
Over current Yes
4 Accessories must be mentioned
5 DDF
5.1 DDF(cabinet & terminal
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 129/139
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 130/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13931Page
TECHNICAL
REQUIRMENT
PARAMETERROW
YESPERMISSIVE TRIPPING (UNDER REACH)5-2
YESPERMISSIVE TRIPPING (OVER REACH)5-3
YESBLOCKING5-4
OPERATION TIME6
DIRECT TRIPPING (msec)6-1
PERMISSIVE TRIPPING (msec)6-2
BLOCKING TRIPPING (msec)6-3
2MINIMUM INITALIZATION TIME FOR COMMAND
(mesc)
6-4
100MAXIMUM ACCEPTABLE PROPAGATION TIME FOR
TELECOMMUNICATION LINK (mesc)
6-5
40 ADDITIONAL DELAY BY NOISE RANGE (mesc)6-6
TRANSMITTER 7
Tx LEVEL RANGE FOR COMMAND / GUARD (dBm)7-1
≥20RETURN LOSS (dBm)7-2
1NUMBER OF SIGNALS FOR EACH COMMAND7-3
≤ 5% HARMONIC DISTORTION7-4
10≥ LEVEL BOOSTING OF COMMANDS(dB)7-5
RECEIVER 8
Rx LEVEL RANGE FOR COMMAND / GUARD (dBm)8-1≥20RETURN LOSS (dB)8-2
≥ 25DYNAMIC RANGE (dB)8-3
≥ 55RECEIVER SELECTIVITY – 300 Hz OUT OF GUARD'S
AND COMMAND'S RANGE (dBm0)
8-4
≥ 5S/N RATIO (dB)8-5
HIGH VOLTAGE INTERFACES 9
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 131/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 1393Page
TECHNICAL
REQUIRMENT
PARAMETERROW
48 ~ 220COMMAND AND START INPUT VOLTAGE RANGES
(Vdc)
9-1
≥ 2NUMBER OF CONTACTS FOR EACH COMMAND9-2
≥ 1NUMBER OF ALARM CONTACT FOR EACH
COMMAND
9-3
250COMMAND AND ALARM CONTACTS RATINGS (VA)9-4
TYPE OF COMMAND CONTACTS9-5
TYPE OF ALARM CONTACTS9-6
DURATION TIME BEFORE OPERATING OF ALARM
RELAYS (msec)
9-7
ALARM CONDITIONS 10
YESTRANSMITTER FAILED10-1
YESPLC FAILED10-2
YESGUARD SIGNAL ABSENCE10-3
YESLOW S/N RATIO10-4
YESNO CARD LOCATED10-5
YES ANY DAMAGE OF BOARDS10-6
YESFAR-END TPS TURNED OFF10-7
YESPRESENCE OF GUARD AND COMMON SIGNAL
SIMULTANEOUSLY
10-8
YESPRESENCE OF COMMAND SIGNAL CONTINUOUSLY10-9YESWATCH DOG ACTIVATION ALARM10-10
SOFTWARE FACILITIES11
YESTPS HARDWARE ASSIGNMENT11-1
YESTPS CONFIGURATION11-2
YESCOMMAND ASSIGNMENT11-3
YESCOMMAND AND ALARM ASSIGNMENT11-4
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 132/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13932Page
TECHNICAL
REQUIRMENT
PARAMETERROW
YESOPERATION TIME ASSIGNMENT FOR EACH
COMMAND INDEPENDENTLY
11-5
YESDURATION AND DELAY TIME ASSIGNMENT FOR
EACH COMMAND INDEPENDENTLY
11-6
YESRECORDE FOR COUNTERS , EVENTS AND FAULTS
WITH TIME TAG
11-7
YESREMOTE TPS CONFIGURATION AND MONITORING11-8
BASIS OF TIME12
YESINTERNAL TIME BASE12-1
YESEXTERNAL TIME BASE – REAL TIME
CLOCK SUCH AS GPS INTERFACE
12-2
DEPENDABILITY AND SECURITY (FOR 10 exp -3)13
≥ 5S / N RATIO (dB)13-1
≤ 15 OPERATION TIME (msec)13-2
TYPE AND BANDWIDTH OF NOISE13-3
TEST FACILITIES14
YESLOCAL TEST14-1
YESLOCAL LOOP TEST14-2
YESREMOTE LOOP TEST14-3
YESPERIODICALLY AUTO TEST14-4
POWER SUPPLY15-48 VCDNOMINAL SUPPLY VOLTAGE15-1
-15%,+20%SUPPLY TOLERANCE15-2
5%< POWER SUPPLY RIPPLE15-3
15≤ POWER CONSUMPTION w15-4
ENVIRONMENTAL CONDITION16
OPERATION16-1
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 133/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13933Page
TECHNICAL
REQUIRMENT
PARAMETERROW
-5 ~+55°CTEMPERATURE RANGE C°16-1-1
40°C 95% at ≤ RELATIVE HUMIDITY %16-1-2
IEC 721 -3-3
CLASS 3 M 1
CLASS OF STANDARD FOR MECHANICAL16-1-3
STORAGE16-2
-40 ~ +70°CTEMPERATURE RANGE C°16-2-1
40°C 95% at ≤ RELATIVE HUMIDITY %16-2-2
IEC-721-3-1
CLASS 1 K 5
CLASS OF STANDARD FOR MECHANICAL16-2-3
DIAGNOSTIC17
YES
YES
ONLINE MAINTENANCE AND DIAGNOSTIC17-1
YES
YES
CHECKING FACILITIES :
POWER SUPPLY
OTHERS
17-2
ELECTROMAGNETIC AND INSULATION18
2500 V / IEC-255-22-1HF DISTURBANCE18-1
2000 V / IEC-801-4FAST TRANSIENT BURST18-2
8000 V / IEC-801-2ELECTROMAGNETIC DISCHARGE18-3
YES ALL OF THE PERIPHERAL EQUIPMENTS , TOOLS ,
HARDWARE , SOFTWARE AND TECHNICAL
DOCUMENTS INCLUDED WITH EACH TPS
TERMINAL
19
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 134/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13934Page
25- TELEPHONE SCHEDULE DATA (I )
RATING AND CHARACTERISTICS OF LI GHTI NG AND TELEPHONE
ITE
M
DESCRIPTION UNIT TECHNICAL
REQUIREMENTS
1. Telephone system
1.1 Type of control & communication cable in telephone
system
PVC or XLPE insulated with wire
or interlocking type armour &
overall fire retardantthermoplastic jacket
1.2 Degree of protection for terminal boxes
1.2.1 Indoor IP42
1.2.2 Outdoor IP55
1.3 Type of telephone Desk mounted / wall mounted
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 135/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13935Page
2. Type of incoming circuit breaker in panel MCCB
3. Type of outgoing circuit breakers in panel (MCCB or MCB)
4. Rating of socket
4.1 Single phase A >16
4.2 Three phase A Acc. To calculation
5. Minimum cross section of outdoor lighting cables mm² 4
6. Minimum cross section of indoor lighting cables mm² 1.5
7. Minimum cross section of socket cables mm² 2.5
8. Type of equipments in battery room explosion proof
26- SCHEDULE OPTICAL ACCESS MULTIPLEXER (I )
OPTICAL ACCESS MULTIPLEXER TECHNI CAL SCHEDULES
ITEM DESCRIPTION UNIT TECHNICAL
REQUIRMENT
1 Applicable Standards
ITU-T G,Q,V
2Configurations
Terminal with Multiplexing & Submultiplexing YES
ADM in Linear & Ring
YES
CXC in Mesh & Tree
YES
3General functionalities
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 136/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13936Page
Time multiplexing/demultiplexing of all voice
and data channels
YES
Subrate data multiplexing based on ITU-T V-
Series synch/async data
YES
Cross-Connecting
at STM-1, E1, n×64 Kbps, 64
Kbps, Time slot and bit levels
Cross-connect capacity
252*VC-12
Drop/Insert
YES
VF operation
YES
Signaling
ITU-T G.704, G.706, G.732
E&M,CAS
Transmission delay µs
<250
4Redundancy
Line card redundancy
1+1
Power supply redundancy
1+1
Cross Connection redundancy
1+1
Redundancy of processor
1+1
Clock
1+1
5Line Interface
E1YES
STM-1 (up to 90 Km)
YES
6Interfaces
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 137/139
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 138/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13938Page
2/4W FXO/FXS
6
0.3-64 Kbps (Sync./Async.) V.24/V.28
4
64 Kbps Co/Contra-directional G.703
4
Ethernet
4
10 Minimum ports per shelf
E1
21
2/4W E&M Signaling
30
2/4W FXO/FXS
30
0.3-64 Kbps (Sync./Async.) V.24/V.28
30
64 Kbps Co/Contra-directional G.703 30
Ethernet
16
11 Management System
Maximum number of supported NEs
XXX
Operation, Administration,
Maintenance and Provisioning (OAM&P)
YES
Configuration Management YES
Remote control, monitoring and configuration
YES
Remote commissioning
YES
configuration information storage in a non-
volatile memory
YES
Alarm Management
YES
8/18/2019 Data Sheet 6320 Ais
http://slidepdf.com/reader/full/data-sheet-6320-ais 139/139
Namdaran Transmission
System Eng. Co
Procurement and Finance (P.F) of 312
Sub-Transmission Substations
(Technical Data Sheet for
63/20 kV AIS Substations)
Tehran Regional Electric
Company (T.R.E.C)
Technical Specification for Schedule Data Rev- 0 of 13939Page
Management Port
YES
Performance Management
G.821
ES, SES,CRC Errors ,Remote Alarm Indications
YES
Graphical performance report
YES
Periodical PM info. YES
12LCT Hardware (Laptop Specification)
Type & CPU
Sony/DELL Core i7
HHD Capacity GB
>500
RAMGB
6
LCD sizeinch