Data Configuration Procedure

Embed Size (px)

Citation preview

  • 7/27/2019 Data Configuration Procedure

    1/80

    Data Configuration Procedure

    Prerequisites

    The following requirements must be met before data configuration:

    Operators must familiarize themselves with the base station system (BSS) and bewell trained.

    The software of the LMT and the OMU (on the GBAM) are installed.

    Configuration Procedure

    Figure 1 shows the basic procedure for data configuration.

    BSC configuration-BTS ConfigurationTRX configuration --Cell configuration.

    Figure 1 Basic procedure for data configuration

    BSC configuration, consisting of configuration of BSC basic Attributes, device

    data configuration, and link configuration.

    BTS configuration, consisting of configuration of BTS basic Attributes, deviceconfiguration, and timeslot configuration.

    Cell configuration, consisting of cell attributes configuration, neighboring cell

    configuration, and import and export of network optimization parameters.

    TRX configuration, consisting of channel attributes configuration and TRX

    attributes configuration.

    Number ConfigurationItem

    Description

    1SS7 signalingpoints

    The SS7 signaling points consist of the OSP, DSP,and STP. For details, refer to section " ConfiguringSS7 Signaling Points ."

    2 Cabinet

    The cabinet is of two types: local cabinet and remotecabinet.

    For details, refer to section "Adding a Cabinet ."

    3 Subrack

    The subrack is of two types: GEPS and GTCS.

    For details, refer to section "Adding a Subrack ."

    4Powerdistribution box

    For details, refer to section "Adding a PowerDistribution Box ."

    5Subrack-OSPmapping

    A subrack should be configured with signaling points.

    For details, refer to section " Configuring theSubrack-OSP Mapping ."

  • 7/27/2019 Data Configuration Procedure

    2/80

    6 BSC board

    The BM subrack must be configured with theGE(O)IUB and the GE(O)IUT.

    The TC subrack must be configured with theGE(O)IUA, GE(O)IUT, and GDPUC.

    For details, refer to section "Adding a Board ."

    The links on the Ater interface are configured on theE(O)IUT. These links connect the GMPS with theGTCS.

    The GMPS should be configured with the followinglinks:

    Ater connection path For details, refer tosection " Configuring an Ater Connection

    Path ." Ater OML (configured when the GTCS is

    placed on the MSC side). For details, refer tosection "Adding an Ater OML ."

    The GTCS should be configured with the Atersignaling link when the GTCS is placed on the MSCside. For details, refer to section Adding an AterSignaling Link ."

    7Transmissionlinks

    The links on the A interface are configured on theGE(O)IUA. These links consist of the following:

    E 1 on the A interface For details, refer tosection Configuring an E1 on the A Interface."

    SS7 signaling link For details, refer to "Configuring an SS7 Signaling Link ."

    Line clock

    For details, refer to section " Configuring the LineClock ."

    System clock

    For details, refer to section " Configuring the SystemClock ."

    9 Clock

    8K reference clock

    For details, refer to section " Configuring the 8KReference Clock ."

    10 BTS For details, refer to section "Adding a BTS ."

  • 7/27/2019 Data Configuration Procedure

    3/80

    1. Configuring SS7 Signaling Points

    Task Description

    Purpose To add the SS7 signaling points

    Mandatory or

    OptionalMandatory

    Prerequisites None

    Remarks

    The BSC6000 can be configured with a maximum of four

    Originating Signaling Points (OSPs) and one Destination

    Signaling Point (DSP).

    The OSP must be configured before the DSP is configured.

    The OSP must be configured before the Signaling TransferPoint (STP) is configured

    The names and codes of signaling points must be unique.

    Procedure

    Table 1 lists an example of the configurations of the SS7 signaling points.

    Table 1 Example of the configurations of the SS7 signaling points

    Parameter Configuration Source

    OSP Name 11 BSC internal planning

    OPC (Hex) 11 Network planning

    Encoding Scheme 14 Network planning

    Network Indicator NATB Network planning

    DSP Name C1 BSC internal planning

    DSP (Hex) C1 Network planning

    Using STP Yes Network planning

    STP (Hex) D1 Network planning

    Configuring an OSP

    To configure an OSP, do as follows:

    Step 1 On the Management Tree tab page, right-clickBSC6000.

  • 7/27/2019 Data Configuration Procedure

    4/80

    A shortcut menu is displayed, as shown in Figure 1 .

    Figure 1 Choosing Configure SS7 Signaling Point

    Step 2 Choose Configure SS7 Signaling Point.

    The Configure SS7 Signaling Point dialog box is displayed, as shown in Figure 2 .

    Figure 2 OSP tab page

    Step 3 ClickAdd OSP.

    The Add SS7 OSP dialog box is displayed, as shown in Figure 3 .

  • 7/27/2019 Data Configuration Procedure

    5/80

    Figure 3 Adding an SS7 OSP

    NOTE:

    If an OSP already exists before you add an OSP, Encoding Scheme andNetwork

    Indicator for the OSP to be added are the same as that for the existing OSP..

    Table 2 describes the parameters in the Add SS7 OSP dialog box.

    Table 2 Parameters in the Add SS7 OSP dialog box

    Parameter Default Value Description

    Osp Name 1 Name of the OSP

    OPC (Hex) -

    The originating signaling point code is of two

    types.

    If NI is set to INT, the range of the 14-bitsignaling point code is 0x1-0x3FF0, and the

    range of the 24-bit signaling point code is

    0x1-0xFFFFF0. If NI is set to other values, the range of the

    14-bit signaling point code is 0x1-0x3FFF,

    and the range of the 24-bit signaling point

    code is 0x1-0xFFFFFF.

    EncodingScheme

    24

    Coding scheme used by the originating signaling

    point.

  • 7/27/2019 Data Configuration Procedure

    6/80

    The network structure has two options: 24-bit

    signaling point code and 14-bit signaling point

    code.

    NetworkIndicator

    INT

    Network indicator of the OSP

    The network indicator identifies the network where

    the OSP is located.

    The SS7 signaling network is of four types.

    INT: International Network

    INTB: International Standby Network

    NAT: National Network

    NATB: National Standby Network

    Step 4 Set the parameters, and then clickOK to return to the Configure SS7 Signaling

    Point dialog box.

    Step 5 Click Finish.

    ----End

    NOTE:

    After adding an OSP, you can modify or delete it.

    Configuring a DSP

    To configure a DSP, do as follows:

    Step 1 After configuring a OSP, click the DSP tab in the Configure SS7 Signaling Point

    dialog box.

    The DSP tab page is displayed, as shown in Figure 4.

  • 7/27/2019 Data Configuration Procedure

    7/80

    Figure 4 DSP tab page

    Step 2 ClickAdd DSP.

    The Add SS7 DSP dialog box is displayed, as shown in Figure 5 .

    Figure 5 Adding an SS7 DSP

    NOTE:

  • 7/27/2019 Data Configuration Procedure

    8/80

    If an STP exists, you can set Using STP to Yes.

    Table 3 describes the parameters in the Add SS7 DSP dialog box.

    Table 3 Parameters in the Add SS7 DSP dialog box

    Parameter DefaultValue

    Description

    Dsp Name - Name of the DSP

    DPC (Hex) -

    The destination signaling point code (DPC) is of

    two types.

    If NI is set to INT, the range of the 14-bit

    signaling point code is 0x1-0x3FF0, andthe range of the 24-bit signaling point code

    is 0x1-0xFFFFF0.

    If NI is set to other values, the range ofthe 14-bit signaling point code is 0x1-

    0x3FFF, and the range of the 24-bit

    signaling point code is 0x1-0xFFFFFF.

    Using STP No

    Determines whether the SS7 signaling transmits

    through the signal transfer point (STP)

    This parameter is set on the basis of the networkplanning.

    Step 3 Set the parameters, and then clickOK to return to the Configure SS7 Signaling

    Point dialog box.

    Step 4 ClickFinish.

    ----End

    NOTE:

    After adding an DSP, you can modify or delete it.

    Configuring an STP

    NOTE:

    Before configuring an STP, ensure that the OSP already exists. The number of STPs

    should not exceed three.

    To configure an STP, do as follows:

  • 7/27/2019 Data Configuration Procedure

    9/80

    Step 1 After configuring an OSP, click the STP tab. The STP tab page is displayed, as

    shown in Figure 6.

    Figure 6 STP tab page

    Step 2 Click Add STP.

    The Add STP dialog box is displayed, as shown in Figure 7.

    Figure 7 Adding an STP

  • 7/27/2019 Data Configuration Procedure

    10/80

    Table 4 describes the parameters in the Add SS7 STP dialog box.

    Table 4 Parameters in the Add SS7 STP dialog box

    Parameter Description

    STP Name Name of the signaling transfer point

    STPC (Hex)The code of the STP must be the same as that of the signaling

    point on the peer end.

    Name of the signaling

    point transferred to

    Name of the DSP transferred by the STP This parameteridentifies the destination to which the signaling point is

    transferred

    Step 3 Configure the related parameters, and then click OK to return to the STP tab

    page.

    Step 4 Click Finish.

    2. Adding a Cabinet

    Task Description

    Purpose To add a BSC cabinet

    Mandatory or

    OptionalMandatory

    Prerequisites NoneRemarks None

    Procedure

    Table 1 lists an example of the configurations of a BSC cabinet.

    Table 1 Example of the configurations of a BSC cabinet

    Parameter Configuration Source

    Cabinet No. 1 BSC internal planning

    Cabinet Type Remote Cabinet BSC internal planning

    To add a cabinet, do as follows:

    Step 1 On the Management Tree tab page, right-clickBSC6000.

    A shortcut menu is displayed, as shown in Figure 1 .

  • 7/27/2019 Data Configuration Procedure

    11/80

    Figure 1 Choosing Add BSC Cabinet

    Step 2 Choose Add BSC Cabinet.

    The Add Cabinet dialog box is displayed, as shown in Figure 2 .

    Figure 2 Adding a cabinet

    Table 2 describes the parameters in the Add Cabinet dialog box.

    Table 2 Parameters in the Add Cabinet dialog box

    Parameter Default Value Description

    Cabinet No. - Logical number of the cabinet

    Cabinet Type Local CabinetCabinet Type consists ofLocal Cabinet andRemote

    Cabinet.

  • 7/27/2019 Data Configuration Procedure

    12/80

    Step 3 Set the parameters, and then clickFinish.

    ----End

    Adding a Subrack

    Task Description

    Purpose To add a subrack

    Mandatory or

    OptionalMandatory

    Prerequisites

    The cabinet where the subrack is to be added is alreadyconfigured.

    The BSC has at least one Originating Signaling Point

    (OSP).

    Remarks None

    Procedure

    Table 1 lists an example of the configurations of a subrack.

    Table 1 Example of the configurations of a subrack

    Parameter Configuration Source

    Subrack Type GTCS BSC internal planning

    OPC 11 Network planning

    Note

    This topic describes how to add a subrack for a local cabinet.

    A local cabinet can be configured with all types of subracks.

    A remote cabinet, placed on the MSC side, can be configured with only the GTCS

    subrack.

    To add a subrack, do as follows:

    Step 1 On the BSC Device Panel tab page, select the cabinet where the subrack is to be

    added from the Current Cabinet drop-down list.

    Step 2 Right-click in the area where the subrack is to be added in the cabinet.

    A shortcut menu is displayed, as shown in Figure 1 .

  • 7/27/2019 Data Configuration Procedure

    13/80

    Figure 1 Choosing Add Subrack

    Step 3 Choose Add Subrack.

    The Add Subrack dialog box is displayed, as shown in Figure 2 .

    Figure 2 Adding a subrack

    Table 2 describes the parameters in the Add Subrack dialog box.

    Table 2 Parameters in the Add Subrack dialog box

    ParameterDefault

    ValueDescription

    Subrack Type -

    Type of subrack

    The options are GEPS and GTCS.

    OPC - Originating signaling Point Code

  • 7/27/2019 Data Configuration Procedure

    14/80

    Step 4 Set Subrack Type andOPC, and then clickFinish.

    ----End

    Verification

    Additional Information

    The BSC6000 subrack consists of the GMPS, GEPS, and GTCS. The principles of

    subrack configuration are as follows:

    The GMPS, GEPS, and GTCS are configured in sequence.

    At least one GMPS and one GTCS must be configured.

    All the GTCSs must be configured in the local cabinet or in the remote cabinet.

    Each subrack must be configured with a fan box..

    3. Adding a Power Distribution Box

    Task Description

    Purpose To add a power distribution box

    Mandatory orOptional

    Mandatory

    PrerequisitesThe subrack that controls the power distribution box is already

    configured.

    Remarks None

    Procedure

    Table 1 lists an example of the configurations of a power distribution box.

    Table 1 Example of the configurations of a power distribution box

    Parameter Configuration Source

    Cabinet No. 0 BSC internal planning

    Management

    Subrack No.0 BSC internal planning

    To add a power distribution box, do as follows:

  • 7/27/2019 Data Configuration Procedure

    15/80

    Step 1 On the BSC Device Panel tab page, select a cabinet from the Current Cabinet

    drop-down list.

    Step 2 Right-click in the POWER BOX area.

    A shortcut menu is displayed, as shown in Figure 1 .

    Figure 1 Choosing Add Power

    Step 3 Choose Add Power.

    The Add PowerBox dialog box is displayed, as shown in Figure 2 .

    Figure 2 Adding a power distribution box

  • 7/27/2019 Data Configuration Procedure

    16/80

    Table 2 describes the parameters in the Add PowerBox dialog box.

    Table 2 Parameters in the Add Power Box dialog box

    Parameter Default Value Description

    Cabinet No. Current cabinet number Number of the cabinet where the currbox is located

    Management Subrack No.

    Minimum serial number ofthe subrack among all the

    subracks in the current

    cabinet

    Number of the subrack that manages t

    box

    Step 4 Set Cabinet No. andManage Subrack No., and then clickFinish.

    ----End

    Verification

    Additional Information

    Each cabinet is configured with a power distribution box. The power distribution box

    provides lightning protection and overcurrent protection for the two -48 V power inputs.It also provides six groups of -48 V and RTN power outputs for the functional modules in

    the cabinet. One -48 V output and one RTN output form a group.

    The power distribution box detects the input voltage and the output power, and generates

    an alarm when a fault occurs.

    4. Configuring the Subrack-OSP Mapping

    Task Description

    Purpose To configure an OSP for a subrack

    Mandatory or

    OptionalMandatory

    Prerequisites The OSPs exist.

    Remarks The OSP must be configured on the basis of the OSP planning.

    Procedure

    Table 1 lists an example of the configurations of the subrack-OSP mapping.

    Table 1 Example of the configurations of the subrack-OSP mapping

  • 7/27/2019 Data Configuration Procedure

    17/80

    Parameter Configuration Source

    Subrack No. 0 BSC internal planning

    OSP 11 Network planning

    Note

    You must configure the SS7 signaling points before configuring the subrack-OSP

    mapping.

    For details, refer to Configuring SS7 Signaling Points.

    To configure the subrack communication link, do as follows:

    Step 1 On the Management Tree tab page, right-clickBSC6000.

    A shortcut menu is displayed, as shown in Figure 1 .

    Figure 1 Choosing Configure Subrack-OSP Mapping

    Step 2 Choose Configure Subrack-OSP Mapping.

    The Configure Subrack-OSP Mapping is displayed, as shown in Figure 2 .

  • 7/27/2019 Data Configuration Procedure

    18/80

    Figure 2 Configuring the subrack-OSP mapping

    Step 3 Select an OSP, and then clickFinish

    5. Adding a Board

    Task Description

    Purpose To add a board

    Mandatory or

    OptionalMandatory

    PrerequisitesThe subrack where a board is to be added exists and the subrack

    has empty slots.

    Remarks None

    Procedure

    Table 1 lists an example of the configurations of a BSC board.

    Table 1 Example of the configurations of a BSC board

    Parameter Configuration Source

  • 7/27/2019 Data Configuration Procedure

    19/80

    Board Type GEIUB BSC internal planning

    Active/Standby

    ModeSelected BSC internal planning

    Caution:

    You can delete a board and then add a board to modify the active/standby attribute of a

    board. You need to pay attention to the following:

    When the BSC6000 internal network is normal, you need to synchronize data if

    the data does not take effect after you add a board. For details, refer to section"Checking Data Consistency and Synchronizing Data."

    When the BSC6000 internal network is disrupted or the Ethernet cable is not

    installed, you need to check data consistency if the network restores after youdelete a board and then add a board. If the data is inconsistent, you have to reset

    the board.

    NOTE:

    This topic describes how to add a board in the GMPS.

    To add a board in the GMPS, do as follows:

    Step 1 On the BSC Device Panel tab page, select a cabinet from the Current Cabinet

    drop-down list.

    Step 2 Right-click an empty slot in the subrack area.

    A shortcut menu is displayed, as shown in Figure 1 .

    Figure 1 Choosing Add Board

    Step 3 Choose Add Board.

    The Add Board dialog box is displayed, as shown in Figure 2 .

  • 7/27/2019 Data Configuration Procedure

    20/80

    Figure 2 Adding a board

    NOTE:

    The boards displayed in the Add Board dialog box depend on the boards already configured in the

    neighbor slots.

    Table 2 describes the parameters in the Add Board dialog box.

    Table 2 Parameters in the Add Board dialog box

    Parameter Default Value Description

    Board Type -

    The GMPS supports three types of boards:

    GEIUB/GEIUB, GEIUP/GEIUP, and

    GEIUT/GEIUT.

    Active/Standby

    Mode

    Selected

    When the check box is selected, itindicates that two boards are added.

    The board in the even number slot is

    the active board and the board in the

    odd number slot that follows the even

    number slot is the standby board. When the check box is deselected, it

    indicates that only one board is added

    in the selected slot.

    Step 4 Set Board Type andActive/Standby Mode, and then clickFinish.

    ----End

  • 7/27/2019 Data Configuration Procedure

    21/80

    Verification

    Additional Information

    Table 2 describes the BSC6000 board configuration.

    Table 2 Board configuration

    Board Configuration

    GGCUConfigured in slots 12 and 13 of the GMPSWorking in

    active/standby mode

    GSCUConfigured in slots 6 and 7 of the GMPS, GEPS, or

    GTCSWorking in active/standby mode

    GTNUConfigured in slots 4 and 5 of the GMPS, GEPS, or

    GTCSWorking in active/standby mode

    GXPUM Configured in slots 0 and 1 of the GMPS or GEPS

    GXPUC Configured in slots 8 and 9 of the GMPS

    GEIUB/GOIUB Configured in slots 18C27 of the GMPS or GEPS

    GEIUP/GOIUP Configured in slots 14 and 15 of the GMPS or GEPS

    GEIUT/GOIUTConfigured in slots 16 and 17 of the GMPS or GEPS, and slots

    14C17 of the GTCS

    GEIUA/GOIUA Configured in slots 18C25 of the GTCS

    GDPUC

    If the GTCS contains optical interface boards, the GDPUC can

    be configured in slots 0C3 and 8C13 of the GTCS.If the GTCScontains E1/T1 interface boards, the GDPUC can be configured

    in slots 9C13.

    The principles of board configuration are as follows:

    The GGCU, GTNU, and GSCU can be deleted only when their subracks are

    deleted.

    The boards in the GMPS, GEPS, and GTCS are configured in sequence.

    The GMPS or GEPS requires at least two GXPUMs, two GEIUBs or two

    GOIUBs, and two GEIUTs or two /GOIUTs.

    The GTCS requires at least two GDPUCs, two GEIUTs or two GOIUTs, and two

    GEIUAs or two GOIUAs.

  • 7/27/2019 Data Configuration Procedure

    22/80

    6. Configuring an Ater Connection Path

    Task Description

    Purpose To configure an Ater connection path

    Mandatory or

    OptionalMandatory

    Prerequisites

    The subrack where the Ater connection path is to beestablished exists.

    The GEIUT or GEIOT of the GMPS or GEPS exists.

    The GEIUT or GOIUT of the GTCS exists.

    The signaling points of the GMPS or GEPS are configured.

    RemarksThe configuration of the Ater connection path can be started only

    on the GEIUT or GEIOT of the GMPS or GEPS.

    Procedure

    Table 1 lists an example of the configurations of an Ater connection path for your

    reference.

    Table 1 Example of the configurations of an Ater connection path

    Parameter Configuration Source

    BM Subrack No. 0 BSC internal planning

    BM Slot No. 14 BSC internal planning

    BM Port No. 0 BSC internal planning

    TC Subrack No. 3 BSC internal planning

    TC Slot No. 14 BSC internal planning

    TC Port No. 0 BSC internal planning

    NOTE:

    This topic describes how to start the configuration of the Ater connection path on the

    GEIUT.

    To configure an Ater connection path, do as follows:

    Step 1 On the BSC Device Panel tab page, right-click the target GEIUT in the GMPS or

    GEPS.

    A shortcut menu is displayed, as shown in Figure 1 .

  • 7/27/2019 Data Configuration Procedure

    23/80

    Figure 1 Choosing Configure Ater Connection Path

    Step 2 Choose Configure Ater Connection Path.

    The Configure Ater Connection Path dialog box is displayed, as shown in Figure 2 .

    Figure 2 Configure Ater Connection Path dialog box

    Step 3 ClickAdd.

    The Add Ater Connection Path dialog box is displayed, as shown in Figure 3 .

  • 7/27/2019 Data Configuration Procedure

    24/80

    Figure 3 Adding an Ater connection path

    Table 2 describes the parameters in the Add Ater Connection Path dialog box.

    Table 2 Parameters in the Add Ater Connection Path dialog box

    Parameter Description

    BM Subrack No.Number of the subrack where the Ater connection path is

    to be established

    BM Slot No.Slot number of the GEIUT/GOIUT where the Ater

    connection path is to be configured

    BM Port No.Port number of the GEIUT/GOIUT on the GMPS or

    GEPS side

    TC Subrack No. Number of the TC subrack

    TC Slot No.Slot number of the GEIUT/GOIUT on the TC subrackside

    TC Port No.Port number of the GEIUT/GOIUT on the TC subrack

    side

    Step 4 Set the parameters, and then clickOK to return to the Configure Ater

    Connection Path dialog box.

    Step 5 ClickFinish.

  • 7/27/2019 Data Configuration Procedure

    25/80

    7. Adding an Ater OML

    Task Description

    Purpose To configure an Ater Operation and Maintenance Link (OML)

    Mandatory or

    OptionalMandatory

    Prerequisites

    The GTCS is configured on the MSC side..

    The Ater connection path is already configured.

    Remarks

    The Ater OML is not required when the GTCS is

    configured on the BSC side.

    The configuration of the Ater OML can be started only on

    the GEIUT or the GOIUT of the local GMPS.

    The entire BSC requires an active and a standby AterOMLs. The timeslot masks of the two OMLs must be the

    same.

    Procedure

    Table 1 lists an example of the configurations of an Ater OML for your reference.

    Table 1 Example of the configurations of an Ater OML

    Parameter Configuration Source

    Logical Group No. 0 BSC internal planning

    Ater Connection Path

    Index0 BSC internal planning

    BM Subrack No. of

    Ater ConnectionPath

    0 BSC internal planning

    Timeslot Mask TS1, TS2-TS17 BSC internal planning

    NOTE:

    This topic describes how to start the configuration of the Ater OML on the GEIUT.

    To configure an Ater OML, do as follows:

    Step 1 On the BSC Device Panel tab page, right-click the target GEIUT in the GMPS.

    A shortcut menu is displayed, as shown in Figure 1 .

  • 7/27/2019 Data Configuration Procedure

    26/80

    Figure 1 Choosing Configure Ater OML

    Step 2 Choose Configure Ater OML.

    The Configure Ater OML dialog box is displayed, as shown in Figure 2 .

    Figure 2 Configure Ater OML dialog box

    Step 3 ClickAdd.

    The Add Ater OML dialog box is displayed, as shown in Figure 3 .

  • 7/27/2019 Data Configuration Procedure

    27/80

    Figure 3 Adding an Ater OML

    NOTE:

    The recommended principle for selecting timeslots is as follows:

    If no more than two BM subracks are configured, select TS1 and any 16 consecutive

    timeslots.

    If more than two BM subracks are configured, select 31 timeslots except TS0.

    Table 2 describes the parameters in the Add Ater OML dialog box.

    Table 2 Parameters in the Add Ater OML dialog box

    Parameter Default Value Description

    Logical Group No. 0 Number of the logical group

    Ater Connection Path IndexIndex of the first Ater connection

    path configured in the current

    GEIUT

    Index of the connection path of the

    Ater OML

    BM Subrack No. of Ater

    Connection PathFlexible

    Number of the BM subrack where

    the Ater connection path is located

    Timeslot Mask -

    Timeslot mask of the Ater OML

    The number of timeslots is directly

    proportional to the system loading

    rate. The number of timeslots can

    be regulated if necessary.

  • 7/27/2019 Data Configuration Procedure

    28/80

    NOTE:

    For the description of the parameters in the Add Ater OML dialog box, refer to the

    HUAWEI BSC6000 Base Station Controller Data Configuration Reference.

    Step 4 Set the parameters, and then clickOK to return to the Configure Ater OMLdialog box.

    Step 5 ClickFinish.

    8. Adding an Ater Signaling Link

    Task Description

    Purpose To add an Ater signaling link

    Mandatory or

    OptionalMandatory

    Prerequisites

    The GTCS is configured on the MSC side..

    The Ater connection path is already configured.

    The DSP exists.

    The GXPUM in the GMPS or GEPS exists.

    Remarks

    The Ater signaling link is not required when the GTCS isconfigured on the BSC side.

    The configuration of the Ater signaling link can be started

    only on the GEIUT or GOIUTof the GTCS.

    Each signaling point can be configured with a maximum ofsixteen 64 kbit/s Ater signaling links.

    The 64 kbit/s Ater signaling link and the 2 Mbit/s Ater

    signaling link cannot coexist. You have to select one of

    them.

    Each GEIUTor GOIUT can be configured with a maximum

    of eight 2 Mbit/s Ater signaling links. The total bandwidth

    cannot exceed 4 Mbit/s. The rate of the Ater signaling must be the same as that of

    the SS7.

    Procedure

    Table 1 lists an example of the configurations of an Ater signaling link for your

    reference.

  • 7/27/2019 Data Configuration Procedure

    29/80

    Table 1 Example of the configurations of an Ater signaling link

    Parameter Configuration Source

    Ater Connection Path

    Index

    0 BSC internal planning

    BM Subrack No. of

    Ater ConnectionPath

    0 BSC internal planning

    Rate Type 64 kbit/sNegotiated with the peer

    end

    Satellite Flag No BSC internal planning

    Timeslot Mask TS9 BSC internal planning

    CAUTION:

    If the rate type of the Ater signaling link is changed, the Ater interface board GEIUT or

    GOIUT of the GMPS, GEPS, and GTCS must be reset.

    NOTE:

    This topic describes how to start the configuration on the GEIUT.

    To add an Ater signaling link, do as follows:

    Step 1 On the BSC Device Panel tab page, right-click the target GEIUT in the GTCS.

    A shortcut menu is displayed, as shown in Figure 1 .

    Figure 1 Choosing Add Ater Signaling Link

    Step 2 Choose Add Ater Signaling Link.

    The Add Ater Signaling Link dialog box is displayed, as shown in Figure 2 .

  • 7/27/2019 Data Configuration Procedure

    30/80

    Figure 2 Add Ater Signaling Link dialog box

    Step 3 ClickAdd.

    The Add Ater Signaling Link dialog box the updated information, as shown in Figure 3

    .

    Figure 3 Adding an Ater signaling link

  • 7/27/2019 Data Configuration Procedure

    31/80

    NOTE:

    The added Ater signaling link can be configured with only one timeslot.

    Table 2 describes the parameters in the Add Ater Signaling Link dialog box.

    Table 2 Parameters in the Add Ater Signaling Link dialog box

    Parameter Default Value Description

    Ater Connection Path

    Index

    Index of the first Ater

    connection path configured in

    the current GEIUT

    Index of the connection path of

    the Ater signaling link

    BM Subrack No. of

    Ater Connection PathFlexible

    Number of the BM subrack

    where the Ater connection pathis located

    Rate Type 64 kbit/s or 2 Mbit/s Rate type of the Ater signalinglink

    Support Satellite Flag No

    Whether the satellite flag is

    supported or not

    The default value indicates thatsatellite transmission is not

    supported.

    Timeslot Mask -Timeslot mask of the Atersignaling link

    NOTE:

    For the description of the parameters in the Add Ater Signaling Link dialog box, refer to

    theHUAWEI BSC6000 Base Station Controller Data Configuration Reference.

    Step 4 Set the parameters, and then OK to return to the Add Ater Signaling Link dialog

    box.

    The Add Ater Signaling Link dialog box displays the information, as shown in Figure 4

  • 7/27/2019 Data Configuration Procedure

    32/80

    Figure 4 Added Ater signaling link

    Step 5 ClickFinish.

    ----End

    9. Configuring an E1 on the A Interface

    Task Description

    Purpose To configure an E1 on the A interface

    Mandatory or

    OptionalMandatory

    PrerequisitesThe GEIUA or GOIUA where the E1 is to be added is already

    configured.

    Remarks The configuration of an E1 on the A interface can be started only

  • 7/27/2019 Data Configuration Procedure

    33/80

    on the GEIUA or GOIUA of the GTCS.

    Procedure

    Table 1 lists an example of the configurations of an E1 on the A interface.

    Table 1 Example of the configurations of an E1 on the A interface

    Parameter Configuration Source

    Subrack No. 1 BSC internal planning

    Slot No. 21 BSC internal planning

    Port No. 0Negotiated with the peer

    end

    The Starting CIC 0 BSC internal planning

    To configure an E1 on the A interface, do as follows:

    Step 1 On the BSC Device Panel tab page, right-click the target GEIUA in the GTCS.

    A shortcut menu is displayed, as shown in Figure 1 .

    Figure 1 Choosing Configure A Interface E1

    Step 2 Choose Configure A Interface E1.

    The Configure A Interface E1 dialog box is displayed, as shown in Figure 2 .

  • 7/27/2019 Data Configuration Procedure

    34/80

    Figure 2 Configure A Interface E1 dialog box

    Step 3 ClickAdd.

    The Add A Interface E1 dialog box is displayed, as shown in Figure 3 .

    Figure 3 Adding an E1 on the A interface

    Table 2 describes the parameters in the Add A Interface E1 dialog box.

  • 7/27/2019 Data Configuration Procedure

    35/80

    Table 2 Parameters in the Add A Interface E1 dialog box

    Parameter Default Value Description

    Subrack No.Number of the subrack

    where the GEIUA islocated

    Number of the subrack where the E1 on

    the A interface is located

    Slot No.

    Number of the slot

    where the GEIUA is

    located

    Number of the slot where the E1 on theA interface is located

    Port No. -Number of the port assigned to the E1 onthe A interface

    The Starting CIC -

    The starting CIC identifies timeslot 0 of

    the E1.

    If you select Auto Calculate CIC, the

    starting CIC plus one successivelyidentifies timeslots 1-31 of the E1. Forexample, the starting CIC plus one

    identifies timeslot 1 and the starting CIC

    plus two identifies timeslot 2.

    If you deselect Auto Calculate CIC, you

    can specify a CIC number.

    NOTE:

    For the description of the parameters in the Add A Interface E1, refer to theHUAWEI

    BSC6000 Base Station Controller Data Configuration Reference.

    Step 4 Set the parameters in the Add A Interface E1 dialog box.

    Step 5 Click the CIC Prop tab.

    The CIC Prop tab page is displayed, as shown in Figure 4 .

  • 7/27/2019 Data Configuration Procedure

    36/80

    Figure 4 Configuring the CIC Attributes

    Step 6 Set the parameters, and then clickOK to return to the Configure A Interface E1

    dialog box.

    Step 7 ClickFinish.

    ----End

    10. Configuring an SS7 Signaling Link

    Task Description

    Purpose To configure an SS7 signaling link

    Mandatory or

    OptionalMandatory

    Prerequisites

    The SS7 signaling points, Ater connection path, and an E1 on the

    A interface are already configured.

    The GXPUM in the GMPS or GEPS to which the SS7 signalinglink connects is already configured.

    Remarks

    The configuration of the SS7 signaling link can be started only on

    the GEIUA or GOIUA of the GTCS.

    Each signaling point can be configured with a maximum of

    sixteen 64 kbit/s SS7 signaling links.

    Each GMPS or GEPS can be configured with a maximum of

    eight 2 Mbit/s SS7 signaling links.

  • 7/27/2019 Data Configuration Procedure

    37/80

    The rate of the SS7 must be the same as that of the Ater signaling.

    Procedure

    Table 1 lists an example of the configurations of an SS7 signaling link.

    Table 1 Example of the configurations of an SS7 signaling link

    Parameter Configuration Source

    Ater Connection Path

    Index1 BSC internal planning

    BM Subrack No. ofAter Connection Path

    0 BSC internal planning

    Rate Type 64 kbit/s Negotiated with the peerend

    A Subrack No. 3 BSC internal planning

    A Slot No. 21 BSC internal planning

    A Port No. 0Negotiated with the peer

    end

    Ater Timeslot Mask TS10 BSC internal planning

    A Timeslot Mask TS1Negotiated with the peer

    end

    SLC 1Negotiated with the peer

    end

    SLC Send 1Negotiated with the peerend

    CAUTION:

    If the rate type of the SS7 signaling link is changed, the Ater interface board GEIUT or

    GOIUT of the GMPS, GEPS, and GTCS must be reset.

    NOTE:

    This topic describes how to start the configuration on the GEIUA.

    It is recommended that the number of the timeslots of each 2 Mbit/s SS7 signaling link is

    the same, thus achieving optimal load sharing

    To configure an SS7 signaling link, do as follows:

  • 7/27/2019 Data Configuration Procedure

    38/80

    Step 1 On the BSC Device Panel tab page, right-click the target GEIUA in the GTCS.

    A shortcut menu is displayed, as shown in Figure 1 .

    Figure 1 Choosing Configure SS7 Signaling Link

    Step 2 Choose Configure SS7 Signaling Link.

    The Configure SS7 Signaling Link dialog box is displayed, as shown in Figure 2 .

    Figure 2 Configure SS7 Signaling Link dialog box

    Step 3 ClickAdd.

  • 7/27/2019 Data Configuration Procedure

    39/80

    The Add SS7 Signaling Link dialog box is displayed, as shown in Figure 3 .

    Figure 3 Adding an SS7 signaling link

    NOTE:

    The number of timeslots on the A interface must be the same as that on the Ater interface.

    Table 2 describes the parameters in the Add SS7 Signaling Link dialog box.

    Table 2 Parameters in the Add SS7 Signaling Link dialog box

    Parameter Default Value Description

    Ater Connection

    Path Index

    Ater connection path

    index configured inthe current TC subrack

    The index of the first Ater connection

    path connecting to the GMPS or GEPS

    BM Subrack No. of

    Ater ConnectionPath

    FlexibleNumber of the BM subrack where theAter connection path is located

    Rate TypeRate of the configured

    Ater signaling linkRate type of the SS7 signaling link

    A Subrack No. Subrack number of the Number of the subrack where the GEIUA

  • 7/27/2019 Data Configuration Procedure

    40/80

    GEIUA/GOIUA is located

    A Slot No.Slot number of the

    GEIUA/GOIUA

    Number of the slot where the GEIUA is

    located

    A Port No.

    First E1 port

    configured on the Ainterface

    Port number of the GEIUA

    Ater TS Set -Ater interface timeslots used by the SS7

    signaling link

    A TS Set -A interface timeslots used by the SS7

    signaling link

    NOTE:

    For the description of the parameters in the Add SS7 Signaling Link, refer to the

    HUAWEI BSC6000 Base Station Controller Data Configuration Reference.

    Step 4 Set the parameters in the Add SS7 Signaling Link dialog box.

    Step 5 Click the MTP3 tab.

    The MTP3 tab page is displayed, as shown in Figure 4 .

  • 7/27/2019 Data Configuration Procedure

    41/80

    Figure 4 MTP3 tab page

    Table 3 describes the parameters on the MTP3 tab page.

    Table 3 Parameters on the MTP3 tab page

    Parameter Default Value Description

    GXPUM Slot No. 0 Slot number of the GXPUM

    SLC - Signaling Link Code

    Satellite Flag No

    Whether satellite transmission is

    supported .

    The default value indicates that

    satellite transmission is not supported.

    SLC Send - Sending the SLC

    Priority 0 -

    Congestion Start Thrsh. 80 Start threshold of congestion

    Congestion End Thrsh 70 End threshold of congestion

    Test Code 165 -

    Test Code Length 6 Length of the test code

    NOTE:

    For the description of the parameters in the MTP3, refer to theHUAWEI BSC6000 BaseStation Controller Data Configuration Reference.

    Step 6 Set the parameters, and then clickOK to return to the Configure SS7 Signaling

    Link dialog box.

    Step 7 ClickFinish.

  • 7/27/2019 Data Configuration Procedure

    42/80

    11. Configuring the Line Clock

    Task Description

    Purpose

    To configure the line clock for a subrack

    For the TC subrack, the line clock extracted on the A

    interface is used as the reference clock of this subrack.

    For the GMPS subrack, the line clock extracted on the Ater

    interface is used as the reference clock of this subrack or the

    system clock.

    Mandatory or

    Optional

    When the GTCS is placed on the BSC side: optional .

    When the GTCS is placed on the MSC side: mandatory.

    Prerequisites

    The subrack is already configured with the required interfaceboard.

    The interface board has a sub board.

    Before configuring the line clock for the GTCS subrack, you

    need to configure the GEIUA or GOIUA interface board.

    Before configuring the line clock for the GMPS subrack,

    you need to configure the GEIUT or GOIUT interface board.

    Remarks None

    Procedure

    Table 1 lists an example of the configurations of the line clock parameters for yourreference.

    Table 1 Example of the configurations of line clock parameters

    Parameter Configuration Source

    Line No. LINE0 BSC internal planning

    Line Clock Type 8K BSC internal planningBoard Slot No. 26 BSC internal planning

    Board Port No. 11 BSC internal planning

    NOTE:

    This topic describes how to configure the line clock for the GTCS.Before configuring theline clock for the GTCS subrack, you need to configure the GEIUA or GOIUA interface

    board

  • 7/27/2019 Data Configuration Procedure

    43/80

    The line clock of a GMPS subrack must be configured on the Ater connection path of this

    subrack.

    The line clock of a GTCS subrack must be configured on the A interface E1 of this

    subrack.

    The E1 interface board can be configured with two line clocks: line 0 and line 1. The

    optical interface board can be configured with only one line clock and the line clock must

    be configured on port 0.

    To configure the line clock for the GTCS, do as follows:

    Step 1 On the BSC Device Panel tab page, right-click the edge of the GTCS.

    A shortcut menu is displayed, as shown in Figure 1.

    Figure 1 Choosing Configure Line Clock

    Step 2 Choose Configure Line Clock.

    The Configure Line Clock dialog box is displayed, as shown in Figure 2.

    Figure 2 Configuring the line clock

  • 7/27/2019 Data Configuration Procedure

    44/80

    Table 2describes the parameters in the Configure Line Clock dialog box.

    Table 2 Parameters in the Configure Line Clock dialog box

    Parameter Default Value Description

    Line No. LINE0 Number of the line clock

    Board Slot No.

    Minimum number of

    the slot in which theGEIU or GOIU is

    located

    Number of the slot where the interface

    board in which the line clock is configured

    resides

    Board Port No. 0Number of the port on the interface board

    This port is used as the port of the lineclock.

    Backup Port No. 1

    Number of the backup port on the

    interface board .

    This port is used as the backup port of the

    line clock.

    Step 3 Set the parameters, and then clickAdd.

    NOTE:

    The Add button changes into the Delete button. You can clickDelete to delete a line

    clock.

    ----End

    Verification

    On the BSC Device Panel tab page, double-click the interface board to check whetherthe board Attributes, such as Line0 Port No., Line1 Port No., Line0 Bkp Port No., and

    Line1 Bkp Port No., are consistent with the required settings.

    Additional Information

    The principles of line clock configuration are as follows:

    One subrack can be configured with a maximum of two line clocks. Huawei recommends that the line clock be configured in a cascade interface

    board.

    The active port and standby port of each line clock cannot be the same one.

    Do not configure line clocks for GEPS subrack.

  • 7/27/2019 Data Configuration Procedure

    45/80

    12.Configuring the System Clock

    Task Description

    Purpose To configure the system clock

    Mandatory or

    OptionalMandatory

    Prerequisites

    The GGCU is functional.

    The GMPS is configured with the line clock.

    Remarks All the configured data takes effect in the GGCU.

    Procedure

    Table 1 lists an example of the configurations of system clock parameters for yourreference.

    Table 1 Example of the configurations of system clock parameters

    Parameter Configuration Source

    Source No. 1 BSC internal planning

    Source Type LINE0 BSC internal planning

    Source Sub-type 8K_HZ BSC internal planning

    To configure the system clock, do as follows:

    Step 1 On the Management Tree tab page, right-clickBSC6000.

    A shortcut menu is displayed, as shown in Figure 1.

    Figure 1 Choosing Configure System Clock

  • 7/27/2019 Data Configuration Procedure

    46/80

    Step 2 Choose Configure System Clock.

    The Configure System Clock dialog box is displayed, as shown in Figure 2.

    Figure 2 Configuring the system clock

    Caution

    Do no set Source Type and Work Mode in one operation.

    After setting Source Type, click Finish to exist, and then enter the Configure System

    Clock dialog box again to set Work Mode.

    Table 1 describes the parameters in the Configure System Clock dialog box.

    Table 1 Parameters in the Configure System Clock dialog box

    Parameter Default Value DescriptionSource No. 1234 Number of the clock source

    Source Type NONE

    Type of the clock source Source Type

    consists ofBITS0, BITS1, LINE0, and

    LINE1. NONE means that this parameter

    is not configured.

    Source Sub-type NONE IfSource Type is set to BITS0 or

    BITS1, the options ofSource

  • 7/27/2019 Data Configuration Procedure

    47/80

    SubType are 2M_HZ and

    2M_Bps.

    IfSource Type is set to LINE0 orLINE1, the option ofSource

    SubType is 8K_HZ.

    NONE means that this parameter isnot configured.

    Work Mode AutomaticConsists ofAutomatic, Manual, andFree

    Run

    Priority - Consists of1, 2, 3, and4

    Step 3 Set the related parameters, and then clickFinish.

    ----End

    Verification

    Enter the Configure System Clock dialog box again, and the configured data isdisplayed. Check the data.

    Additional Information

    Clock Source

    The BSC6000 provides two types of clock source.

    Building Integrated Timing Supply (BITS) clock

    Line clock

    Table 2 describes the clock source.

    Table 2 Clock source

    Clock Source Description

    BITS0

    BITS1

    Consists of2M_HZ and2M_Bps The anti-interference ability of2M_Bps is higher

    than that of2M_HZ.

    LINE0

    LINE1

    The clock extracted from the A interface is 8K_HZ. The8K_HZ signal transmits through the backplane of the

    GGCU.

    Priority of the Clock Source

  • 7/27/2019 Data Configuration Procedure

    48/80

    The BSC6000 provides four levels of clock source priority. Level 1 clock source has the

    highest priority.

    When configuring the clock source, pay attention to the following:

    There is a one-to-one relationship between the clock source and the priority. The priority of a BITS clock is usually higher than that of a line clock.

    If the system clock uses a line clock, the GMPS must have been configured with

    the corresponding line clock.

    The BSC6000 usually uses the line clock.

    Current Clock Source and Clock Switch Policies

    The BSC6000 requires only one clock source during operation. If the current clock

    source fails, it has to be switched to a normal clock source. The clock source has three

    work modes: AUTO, Manual, andFree Run.

    Automatic: The system automatically selects the clock source that has the highest

    priority.

    For example, if the level 3 clock source fails, the level 4 clock source is used. When the

    level 3 clock source recovers, the system automatically switches to the level 3 clocksource. If all the clock sources fail, the system retains the current state and switches to

    AUTO mode after the clock sources recover.

    Manual: The user specifies a clock source.

    The system is not allowed to switch the clock resource even if the current clock sourcefails.

    Free Run: initial work status of the system clock

    13. Configuring the 8K Reference Clock

    Task Description

    Purpose To configure a reference clock for a subrack

    Mandatory or

    OptionalMandatory

    Prerequisites

    The GSCU exists.

    The related line clock is configured.

    The GTCS is configured with an A interface board and an A

    interface E1.

  • 7/27/2019 Data Configuration Procedure

    49/80

    Remarks

    A reference clock must be configured after the GSCU in a

    subrack is configured. If the clock is not configured, the

    services on the subrack will be affected.

    The configuration of the 8K reference clock is based on the

    network planning.

    Procedure

    Table 1 lists an example of the configuration of the 8K reference clock for your

    reference..

    Table 1 Example of the configuration of the 8K reference clock

    Parameter Configuration Source

    8K Reference Clock

    Type

    GGCUBackplane

    BSC

    internal planning

    NOTE:

    This topic describes how to configure the 8K reference clock for the GMPS.

    To configure the 8K reference clock for the GMPS, do as follows:

    Step 1 On the BSC Device Panel tab page, right-click the edge of the GMPS.

    A shortcut menu is displayed, as shown in Figure 1.

    Figure 1 Choosing Configure 8K Reference Clock

  • 7/27/2019 Data Configuration Procedure

    50/80

    Step 2 Choose Configure 8K Reference Clock.

    The Configure GSCU 8K Reference Clock dialog box is displayed, as shown in Figure

    2.

    Figure 2 Configuring the GSCU 8K reference clock

    Step 3 Set 8K Reference ClockType, and then clickFinish.

    ----End

    Verification

    On the BSC Device Panel tab page, double-click the GSCU to check the setting of the8K reference clock.

    Additional Information

    Different subracks have different 8K reference clocks.

    Table 2 lists the subracks and their 8K reference clocks.

    Table 2 Subracks and their 8K reference clocks

    Subrack 8K Reference Clock

    Local GMPS GGCU BACK

    Local GEPS GGCU FACE

    Remote GTCS Line clock configured in the subrack

    When configuring the 8K reference clock for the TC subrack, you can select Invalid orLINE CLOCK. If you select LINE CLOCK, none of the line clocks can be deleted.

  • 7/27/2019 Data Configuration Procedure

    51/80

    Adding BTS

    Task Description

    Purpose To add a BTS

    Mandatory or

    OptionalMandatory

    Prerequisites

    The upper-level BTS must have idle ports.

    IIf you want to add a BTS on the GEIUB or GOIUB boards

    of the BSC, the GEIUB or GOIUB boards must beconfigured on the BSC and there must be idle ports on the

    GEIUB or GOIUB boards. In addition, the subrack where

    the GEIUB boards are located must have GXPUM boards,and the subrack must be configured with original signaling

    points (OSPs).

    Remarks

    The number of BTS levels cannot exceed seven.

    The number of cells under a BTS cannot exceed 12. A cell

    supports a maximum of 24 TRXs.

    The maximum number of TRXs that a BTS supports varies

    with the BTS type.

    Procedure

    Table 1 lists an example of the configurations of a BTS for your reference.

    Table 1 Example of the configurations of a BTS

    Parameter Configuration Source

    Site Name BTS1 Network planning

    Site Type BTS3012 Network planning

    Upper-Level PortNo.

    1 Network planning

    Multiplexing Mode 4:1 Network planning

    Site Attributes

    Configuredaccording to

    actual

    situations

    Network planning

    Cell Name Cell1 Network planning

  • 7/27/2019 Data Configuration Procedure

    52/80

    Frequency Band GSM900 Network planning

    MCC 460 Network planning

    MNC 10 Network planning

    LAC 6 Network planningCI 123 Network planning

    BCC 0 Network planning

    NCC 0 Network planning

    Cell ExtType Normal Cell Network planning

    Cell Type Normal Cell Network planning

    Freq Config 2, 3 Network planning

    TRX ConfigTRX 1, TRX

    22 Network planning

    Frequency Hopping No FH Network planning

    8PSK Power Level 0 Network planning

    NOTE:

    This topic describes how to add a BTS3012 BTS1 on the GEIUB board.

    To add a BTS, do as follows:

    Step 1 Log in to the BSC6000 Local Maintenance Terminal in online mode.

    The BSC6000 Local Maintenance Terminal window is displayed.

    Step 2 On the Management Tree tab page, right-click a BTS.

    A shortcut menu is displayed, as shown in Figure 1 .

  • 7/27/2019 Data Configuration Procedure

    53/80

    Figure 1 Choosing Add Site (1)

    NOTE:

    You can also right-click a GEIUB/GOIUB board and choose Add Site on the shortcut

    menu to add a BTS, as shown in Figure 2 .

    Figure 2 Choosing Add Site (2)

    Step 3 Choose Site Operation > Add Site.

    The Add Site dialog box is displayed, as shown in Figure 3 .

    Figure 3 Add Site dialog box

    Step 4 ClickAdd Site.

    The Add New Site dialog box is displayed, as shown in Figure 4 .

  • 7/27/2019 Data Configuration Procedure

    54/80

    Figure 4 Add New Site dialog box

    Table 2 describes the parameters in the Add New Site dialog box.

    Table 2 Parameters in the Add New Site dialog box

    Parameter Default Value Description

    Site IndexAn unique integer

    ranging from 0 to 2047

    A unique index number of the BTS

    under the BSC

    The number cannot be modified.

    Site Name None

    A unique name of the BTS under the

    BSC

    The name contains a maximum of 33

    characters and the name can be

    modified.

    Site Type BTS30

    There are nine BTS types: BTS30,

    BTS312, BTS3012A, BTS3001C,BTS3002C, BTS3012, BTS3012AE,

    BTS3006C and BTS3006A. The BTS

    type cannot be modified after setup.

    Upper-Level Port

    No.GEIUB/GOIUB port 1

    Indicates the idle ports of the upper-level object, that is, the GEIUB/GOIUB

    ports or the ports of the upper-level

    BTS.

    MultiplexingMode

    4:1There are four multiplexing modes: 1:1,2:1, 3:1, and 4:1.

  • 7/27/2019 Data Configuration Procedure

    55/80

    NOTE:

    Generally, you need to set only Site Name andSite Type. For other parameters, retain

    the default settings.

    Step 5 Set the parameters.

    NOTE:

    For example, type BTS1 in the Site Name textbox and set the Site Type to BTS3012, as

    shown in Figure 5 .

    Figure 5 Setting parameters

    Step 6 ClickOK.

    The Add Site dialog box displays the updated information, as shown in Figure 6 .

  • 7/27/2019 Data Configuration Procedure

    56/80

    Figure 6 Added BTS in the Site View box

    Step 7 ClickNext.

    The Add Site Wizard dialog box displays the updated information, as shown in Figure 7

    .

    Figure 7 Updated information in the Add Site dialog box

  • 7/27/2019 Data Configuration Procedure

    57/80

    Step 8 Select BTS1 and clickAdd Cell.

    The Add New Cell dialog box is displayed.

    Step 9 Set the parameters according to the actual situation.

    NOTE:

    Generally, you need to set only Cell Name andCell Type.

    For example, set Cell Name to Cell1 andCell Type to GSM900. For other parameters,

    retain the default settings, as shown in Figure 8 .

    Figure 8 To add more than one cell at a time, set Number of Cells.

    NOTE:

    To add more than one cell at a time, set Number of Cells.

    Step 10 ClickOK.

    The Add Site dialog box displays the updated information, as shown in Figure 9 .

  • 7/27/2019 Data Configuration Procedure

    58/80

    Figure 9 Added cell in the Cell View box

    Step 11 ClickNext.

    The Add Site dialog box displays the Cell List box, as shown in Figure 10 .

    Figure 10 Configuring cell attributes

    Step 12 ClickCell Attributes.

  • 7/27/2019 Data Configuration Procedure

    59/80

    The Set Attributes of Cell dialog box is displayed, as shown in Figure 11 .

    Figure 11 Set Attributes of Cell dialog box

    Step 13 Set the parameters.

    NOTE:

    For example, set the Cell Identity (CI) ofCell1 to 123, add two TRXs (TRX 1 andTRX

    22) to Cell1, and assign frequencies 2 and3 to TRX 1 and TRX 22 respectively. Figure12 shows the Set CellAttributes dialog box after the previous settings.

    The CI of a cell in a BTS must be unique.

    For the settings of TRXs and frequencies, refer to Cell Data Configuration.

    If you select GPRS Support, you must ensure that the PCU is configured. If the BTS

    version does not support the GPRS or the GPRS service is not available, do no select

    GPRS Support.

  • 7/27/2019 Data Configuration Procedure

    60/80

    Figure 12 Adding TRXs

    Step 14 ClickOK to return to the Add Site dialog box.

    Step 15 ClickNext.

    The Add Site dialog box displays the updated information, as shown in Figure 13 .

  • 7/27/2019 Data Configuration Procedure

    61/80

    Figure 13 Added site in the Site List box

    NOTE:

    For details about configuring secondary chains, refer to "Adding or Deleting a

    Secondary Chain."

    For details about configuring timeslots manually, refer to "Assigning Abis Timeslots

    Manually."

    Step 16 Select a BTS from the Site List box, and then clickSite Attributes.

    The Site Device Attributes dialog box is displayed, as shown in Figure 14 .

  • 7/27/2019 Data Configuration Procedure

    62/80

    Figure 14 Site Device Attributes dialog box

    NOTE:

    The downlink TRXs of the DDPU must be configured. For combined cabinets or cabinet

    groups, the BTS inner connections must be configured.

    In the Site Device Attributes dialog box, you can configure BTS inner connections and

    BTS attributes, add or delete boards, and configure board attributes.

    For details about adding or deleting boards, refer to "Adding or Deleting a BTS

    Board."

    For details about configuring board attributes, refer to "Configuring BTS BoardAttributes."

    For details about configuring BTS inner connection, refer to "Establishing

    Connections Between BTS Cabinet Groups."

    For details about configuring BTS attributes, refer to "Configuring BTS

    Attributes."

  • 7/27/2019 Data Configuration Procedure

    63/80

    Step 17 Set the related attributes, and then clickOK to return to the Add Site Wizard

    dialog box.

    Step 18 ClickFinish.

    The GBAM checks the configured data.

    If the data passes the check, the data takes effect on each service board.

    If the check fails, error information is displayed. You can modify the settings

    according to the error information.

    ----End

    Verification

    To verify the configuration, do as follows:

    Step 1 On the Management Tree tab page, click the root node ofBSC6000.

    The added BTS is displayed.

    Step 2 Click the added BTS.

    The Site Device Panel tab page is displayed.

    Step 3 Check whether the displayed configurations meet your requirements.

    ----End

    Additional Information

    You can refer to the following documents or sections when adding a BTS.

    To configure cell attributes, refer to "configure cell Attributes."

    To configure TRX attributes, refer to "Adding TRXs"

    For the details about manual assignment of Abis timeslots, refer to "Assigning

    Abis Timeslots Manually."

    Adding or Deleting a Secondary Chain

    Task Description

    Purpose To add or delete an secondary chain for a BTS

    Mandatory or

    OptionalOptional

  • 7/27/2019 Data Configuration Procedure

    64/80

    Prerequisites

    The BTS has idle ports.

    The GEIUB or GOIUB board of the BSC or the upper-level

    BTS has idle ports..

    Remarks Secondary chains cannot be added between the BTSs that areestablished on the GEIUB or GOIUB board in different subracks.

    Procedure

    Adding a Secondary Chain

    Table 1 lists an example of the configurations of a site chain for your reference.

    Table 1 Example of the configurations of a site chain

    Parameter Configuration Source

    GE(O)IUB Subrack

    No.0 BSC internal planning

    GE(O)IUB Slot No. 16 BSC internal planning

    GE(O)IUB Port No. 0 BSC internal planning

    Site Port No. 1 BSC internal planning

    NOTE:

    This topic describes how to add a secondary chain to the GEIUB board ofBTS1.

    To add a secondary chain, do as follows:

    Step 1 On the Management Tree tab page, right-click a BTS.

    A shortcut menu is displayed, as shown in Figure 1 .

  • 7/27/2019 Data Configuration Procedure

    65/80

    Figure 1 Choosing Add or Delete Site Multiple Chain

    Step 2 Choose Add or Delete Site Multiple Chain.

    The Add & Delete Site Chain dialog box is displayed, as shown in Figure 2 .

    Figure 2 Add & Delete Site Chain dialog box

    Step 3 Select the BTS, and then clickAdd Delete Chain.

    The Add and Delete Site Chain dialog box is displayed, as shown in Figure 3 .

  • 7/27/2019 Data Configuration Procedure

    66/80

    Figure 3 Add and Delete Site Chain dialog box

    Step 4 ClickNew Port.

    NOTE:

    The Site Port button and the GEIUB Port button are not available in this operation.

    To configure the site port and the GEIUB port, refer to "Adding a BTS."

    The Add Site Slave Chain dialog box is displayed, as shown in Figure 4 .

    Figure 4 Add Site Slave Chain dialog box

    NOTE:

    The first-level BTS can be connected to only the GEIUB board of the BSC.

    A non-first-level BTS can be connected to the idle ports of only a single GEIUB

    board.

    Step 5 Set GEIUB Port No. andSite Port No., and then clickOK.

    The Add and Delete Site Chain displays the updated information, as shown in Figure 5 .

  • 7/27/2019 Data Configuration Procedure

    67/80

    Figure 5 Adding a secondary chain

    Step 6 ClickOK to return to the Add & Delete Site Chain dialog box.

    Step 7 ClickFinish.

    ----End

    Deleting a Secondary Chain

    NOTE:

    This topic describes how to delete SitePort 1 shown in Figure 5.

    To delete a secondary chain, do as follows:

    Step 1 Perform steps 1 through 3 described in Adding a Secondary Chain.

    Step 2 In the Add and Delete Site Chain dialog box, select SitePort 1 from the Site

    Port List box, and then clickDelete Port.

    An information box is displayed.

    Step 3 ClickYes.

    ----End

    Verification

    To verify the configuration, do as follows:

  • 7/27/2019 Data Configuration Procedure

    68/80

    Step 1 Perform steps 1 through 3 described in Adding a Secondary Chain.

    The Add and Delete Site Chain dialog box is displayed.

    Step 2 In the Site Port List box, check whether the added port is displayed.

    ----End

    Assigning Abis Timeslots Manually

    Task Description

    Purpose To manually assign Abis timeslots

    Mandatory orOptional Optional

    Prerequisites

    Each BTS cabinet has in-port objects.

    There are required timeslot resources.

    RemarksYou need to reset the BTS after clearing the timeslots that are

    assigned manually.

    Procedure

    Table 1 lists an example of the configurations of the Abis timeslots.

    Table 1 Example of the configurations of the Abis timeslots

    Parameter Configuration Source

    Timeslot No. 10 BSC internal planning

    Sub-Timeslot No. 2 BSC internal planning

    NOTE:

    This topic describes how to manually assign the timeslots of TCH2 forBTS1.

    To manually assign Abis timeslots, do as follows:

    Step 1 On the Management Tree tab page, right-clickBTS1.

    A shortcut menu is displayed, as shown in Figure 1 .

  • 7/27/2019 Data Configuration Procedure

    69/80

    Figure 1 Choosing Manually Assign Site Abis Timeslot

    Step 2 Choose Manually Assign Site Abis Timeslot.

    The Manual Allocate TS dialog box is displayed, as shown in Figure 2 .

    Figure 2 Manual Allocate TS dialog box

    Step 3 Select BTS1, and then clickManually Assign Timeslots.

    The Manually Set Site TS dialog box is displayed, as shown in Figure 3 .

  • 7/27/2019 Data Configuration Procedure

    70/80

    Figure 3 Manually Set site TS dialog box (1)

    Step 4 Click the root node ofRSL1.

    RSL1 expands, as shown in Figure 4 .

  • 7/27/2019 Data Configuration Procedure

    71/80

    Figure 4 Manually Set site TS dialog box (2)

    NOTE:

    TCH0 andTCH1 are concealed because they are occupied by a BCCH and SDCCHrespectively.

    The general principles of BTS timeslot assignment are as follows:

    Timeslots 0C7 of in-ports cannot be used.

    The timeslots of different BTSs cannot be assigned in one continuous 64 kbit/s

    bandwidth.

    Table 2 lists the detailed principles of BTS timeslot distribution.

    Table 2 BTS timeslots and their assignment principlesTimeslot

    TypeAssignment Principle

    OML

    Operation and maintenance linkOne BTS is assigned with one 64 kbit/s

    OML. The OML timeslot in a cabinet group is always set to timeslot

    248 on port 0. The OML can be multiplexed with the RSL only.

    RSLRadio signaling linkOne TRX is assigned with one 64 kbit/s RSLTheRSL can be multiplexed with OML and RSL in a cabinet group. The

  • 7/27/2019 Data Configuration Procedure

    72/80

    RSL always connects to the in-port of the cabinet where the TRX

    resides.

    TCHTraffic channelRate: 16 kbit/sIn transparent transmission, the positions

    of TCH timeslots in a 64 kbit/s link must be consistent.

    Idle Idle timeslotRate: 16 kbit/sIdle timeslots and TCH timeslots can beassigned in a 64 kbit/s bandwidth.

    SemiMonitor timeslot Rate: 8 kbit/s, 16 kbit/s, 32 kbit/s, or 64 kbit/sMonitor

    timeslots cannot be multiplexed.

    Step 5 Select TCH2, and then clickManual Set.

    The Set TS: TRX No. [1] Channel No. [2], TS Type: TCH, as shown in Figure 5 .

    Figure 5 Setting the OML (1)

    Step 6 Set Timeslot No. to 10 and set Sub-Timeslot No. to 2, as shown in Figure 6 .

  • 7/27/2019 Data Configuration Procedure

    73/80

    Figure 6 Setting the OML (2)

    NOTE:

    If the timeslot that you select is occupied, a system message will be displayed.

    Step 7 ClickAssign Timeslot..

    Step 8 ClickOK to return to the Manually Assign Site Timeslot dialog box.

    Step 9 ClickOK to return to the Manually Assign Site Abis Timeslot dialog box.

    Step 10 ClickFinish.

    ----End

    Verification

  • 7/27/2019 Data Configuration Procedure

    74/80

    After the previous setup is complete, repeat steps 1 through 2 to display the Manually

    Assign Site Abis Timeslot dialog box. Then check whether the settings of the manually

    assigned timeslots are consistent with your requirements.

    Additional Information

    After the timeslots are manually assigned, browse the configured timeslots as follows:

    Step 1 In the Manually Assign Site Timeslot dialog box, select TCH2 and clickBrowse

    Timeslot,

    The Set TS: TRX No. [1] Channel No. [2], TS Type: TCH, as shown in Figure 7.

    Figure 7 Browsing all the BTS timeslots

    Step 2 View the settings of the timeslot.

    Step 3 ClickOK to return to the Manually Assign Site Timeslot dialog box.

    Step 4 ClickBrowse All Timeslot to view all the timeslots.

  • 7/27/2019 Data Configuration Procedure

    75/80

    The Browse All Site's Timeslot dialog box is displayed, as shown in Figure 8

    .

    Figure 8 Browsing BTS port timeslots

    Step 5 Select Port 0 ofTS and clickBrowse Port Timeslots.

    The Site Port TS Browse dialog box is displayed, as shown in Figure 9.

    Figure 9 Browsing BTS port timeslots

    Table 3 describes the parameters in the Site Port TS Browse dialog box.

    Table 3 Parameters in the Site Port TS Browse dialog box

  • 7/27/2019 Data Configuration Procedure

    76/80

    Parameter Description

    Index Index of a timeslot on the E1 portValue range: 0C255

    Belong Site BTS where a timeslot belongs

    Port No. Number of a BTSTS No. Number of a timeslot on the E1 port (in 64 kbit/s)

    SubTS No. Number of a sub-timeslot (in 8 kbit/s) under a 64 kbit/s timeslot

    TRX No. Number of a TRX255 stands for a non-TRX object.

    Chan No. Number of a channel255 stands for a non-channel object.

    OUT Port No. Number of an out-port255 stands for an invalid parameter.

    OUT TS No. Number of a timeslot on an out-port

    TS TypeConsists of the following:TCH: Traffic ChannelOML: Operation

    and Maintenance LinkRSL: Radio Signaling LinkSemi: monitortimeslotIdle: idle timeslot

    Vol Type Rate type of a timeslotUnit: kbit/s

    Abis Mode Consists of manual mode and auto mode.

    ----End

    Establishing Connections between BTS Cabinet Groups

    Task Description

    Purpose To establish connections between BTS cabinet groups

    Mandatory or

    OptionalMandatory

    Prerequisites The BTS has at least two cabinet groups.

    Remarks

    For cabinet groups, the inner connection of the BTS is required.

    For combined cabinets, the inner connection of the BTS is not

    required.

    Each cabinet group has at least one idle E1 port.

    Procedure

    Table 1 lists examples of the configurations of the connections between BTS cabinet

    groups.

    Table 1 Examples of the configurations of the connections between BTS cabinet groups

  • 7/27/2019 Data Configuration Procedure

    77/80

    Parameter Configuration Source

    Out-Port/In-Port 2/8 BSC internal planning

    Out-Port/In-Port 3/10 BSC internal planning

    Out-Port/In-Port 4/16 BSC internal planningOut-Port/In-Port 5/17 BSC internal planning

    NOTE:

    The configuration principle for internal connections is as follows:

    The cabinet groups are connected in one-to-one port mode.

    The connections are led from the main cabinet group to the extension cabinet group.

    At least one connection must be established between the main cabinet group and each

    extension cabinet group.

    To establish connections between cabinet groups in a BTS, do as follows:

    Step 1 In the Site Device Attributes dialog box refer to , clickSite Inn Connect.

    Note

    If the added TRXs are in different cabinet groups, you must configure the inner

    connection of the cabinet groups.

    When adding TRXs, you can clickSite Inner Connection in the Site Device Attributes

    dialog box to configure the inner connection.

    If the added TRXs are in different cabinet groups, you must configure the innerconnection of the cabinet groups. When adding TRXs, you can click Site Inner

    Connection in the Site Device Attributes dialog box to configure the inner connection.

    The Configure cabinet connection dialog box is displayed, as shown in Figure 1 .

  • 7/27/2019 Data Configuration Procedure

    78/80

    Figure 1 Establishing internal connections

    NOTE:

    You can also clickInner Connection in the Add and Delete Site Chain dialog box

    shown in Figure 1 to establish internal connections.

    NOTE:

    The Out Port andIn Port drop-down list boxes list all the idle ports in the main cabinet

    group and in the extension cabinet group respectively.

    The main control board of the BTS decides the ports of the inner connection.

    Step 2 Select a port number from the Out Port drop-down list box, as shown in Figure 2

    .

    Figure 2 Selecting an output port

    NOTE:

    The figure shown in Figure 1-30 stands for the port number of the cabinet group.

    Step 3 Select a port number from the In Port drop-down list box, as shown in Figure 3 .

  • 7/27/2019 Data Configuration Procedure

    79/80

    Figure 3 Selecting an input port

    NOTE:

    If you want to establish multiple connections, repeat steps 2 and 3.

    For example, establish four connections, as shown in Figure 4 .

    Figure 4 Establishing multiple connections

    NOTE:

    If you want to delete connections, select None from the In Port drop-down list box.

    Step 4 ClickOK.

    ----End

  • 7/27/2019 Data Configuration Procedure

    80/80

    Verification

    To verify the configuration, do as follows:

    Step 1 On the Management Tree tab page, click the added BTS.

    The Site Device Panel tab page is displayed.

    Step 2 ClickInn Connect Browse to check whether the established connections meet

    your requirements.

    ----End

    Additional Information

    BTS inner connections are configured in cabinet groups. Each cabinet group of the BTSmust have at least one incoming port that connects the inside or outside of the BTS. The

    BSC6000 supports eight types of BTSs.

    Table 2 lists the distribution of ports in different types of cabinet groups.

    Table 2 Distribution of ports in cabinet groups

    BTS Type Cabinet Group 0 Cabinet Group 1 Cabinet Group 2

    BTS30 0C7 8C11 16-19

    BTS312 0C7 8C11 16-19

    BTS3012A 0C4 8C11 16-19BTS3001C 0C1 - -

    BTS3002C 0C1 - -

    BTS3012 0C7 8C15 16C23

    BTS3012AE 0C7 8C15 16C23

    BTS3006C 4C7 12C15 20C23