Data Center Telecom Cabling Standards – Justification & Update Update Jonathan Jew Jonathan Jew J&M Consultants, Inc. Vice-chair TIA TR-42.6 Telecom Administration Vice chair TIA TR 42.6 Telecom Administration Editor ISO/IEC TR 14763-2-1 Telecom Identifiers Co-editor TIA-942-A Data Centers Telecom Infrastructure Co chair BICSI Data Center Subcommittee Co-chair BICSI Data Center Subcommittee www.j-and-m.com

Data Center Telecom Cabling Standards – Justification & Update

Embed Size (px)

Citation preview

Page 1: Data Center Telecom Cabling Standards – Justification & Update

Data Center Telecom Cabling Standards – Justification &

UpdateUpdate

Jonathan JewJonathan JewJ&M Consultants, Inc.

Vice-chair TIA TR-42.6 Telecom AdministrationVice chair TIA TR 42.6 Telecom AdministrationEditor ISO/IEC TR 14763-2-1 Telecom Identifiers

Co-editor TIA-942-A Data Centers Telecom InfrastructureCo chair BICSI Data Center SubcommitteeCo-chair BICSI Data Center Subcommittee

www.j-and-m.com

Page 2: Data Center Telecom Cabling Standards – Justification & Update

WHY USE DATA CENTER TELECOM STANDARDS?TELECOM STANDARDS?

Page 3: Data Center Telecom Cabling Standards – Justification & Update

Point to Point Non Standard CablingPoint-to-Point Non-Standard CablingUnorganized, Single-Use

Page 4: Data Center Telecom Cabling Standards – Justification & Update

Structured Standards Based CablingStructured Standards Based Cabling- Organized, Reusable, Flexible

Page 5: Data Center Telecom Cabling Standards – Justification & Update

Standard/Structured vs. Proprietary/Pt-to-Pt Cabling

• Cabling can be used for multiple g papplications rather than installed for one application and then removed (or probably

f f )just left under the floor) – Saves money

Fl ibilit t d l ti i kl– Flexibility to deploy connections quickly– Helps minimize under floor mess

• Multiple sources vs single source• Multiple sources vs. single source• Support for future high speed protocols

Simpler troubleshooting & administration• Simpler troubleshooting & administration (improves availability)

Page 6: Data Center Telecom Cabling Standards – Justification & Update

WHAT ARE THE DATA CENTER TELECOMCENTER TELECOM STANDARDS?

Page 7: Data Center Telecom Cabling Standards – Justification & Update

Data Center Telecom StandardsData Center Telecom Standards• ANSI/TIA-942 Telecommunications Infrastructure

Standard for Data Centers (2005 – update in progress –( p p gUS & Canada)

• ISO/IEC 24764 Information Technology – Generic C bli f D t C t P i ( d 2/2010 I tl)Cabling for Data Centre Premises (approved 2/2010 Intl)

• CENELEC EN 50173-5 Information Technology –Generic Cabling Systems Part 5: Data Centres (2007 -Generic Cabling Systems Part 5: Data Centres (2007 Europe)

• NMX- I- xxx-NYCE 2010 Telecommunications - Data C S i bili d Hi h P f ( /2010Centers Sustainability and High Performance (7/2010 -Mexico)

• ANSI/BICSI-002 Data Center Design and• ANSI/BICSI-002 Data Center Design and Implementation Best Practices (2nd half 2010 - Intl)

Page 8: Data Center Telecom Cabling Standards – Justification & Update

ANSI/TIA-942ANSI/TIA-942• ANSI/TIA-942 Telecom Infrastructure

Standard for Data Centers (2005)• Revision is ANSI/TIA-942-A (2011/2012)Revision is ANSI/TIA 942 A (2011/2012)• Telecom cabling (topologies, cable types,

distances)distances)• Telecom spaces (design requirements –

height, lighting, doors, floor loading, HVAC, finishes, power, grounding, etc.)

Page 9: Data Center Telecom Cabling Standards – Justification & Update

ANSI/TIA-942ANSI/TIA-942• Telecom pathwaysp y• Redundancy• Annexes• Annexes

– Application distances for circuitsAccess provider coordination– Access provider coordination

– Administration (labeling)Sit l ti– Site selection

– Data center reliability tiers (telecom, architectural electrical mechanical)architectural, electrical, mechanical)

Page 10: Data Center Telecom Cabling Standards – Justification & Update

ISO/IEC 24764ISO/IEC 24764• ISO/IEC 24764 Information technology –

Generic Cabling for Data Centre PremisesGeneric Cabling for Data Centre Premises approved Feb 2010

• Based on CENELEC EN 50173 5• Based on CENELEC EN 50173-5• Telecommunications cabling only• Data Center planning telecommunications• Data Center planning, telecommunications

pathways, spaces, and administration to be included in ISO/IEC 14763-2 Informationincluded in ISO/IEC 14763 2 Information technology – implementation and operation of customer premises cabling – Part 2 Planning and Installation (2011/2012)

Page 11: Data Center Telecom Cabling Standards – Justification & Update

CENELEC EN 50173-5CENELEC EN 50173-5• CENELEC EN 50173-5 Information Technology

– Generic Cabling Systems Part 5: Data Centres (2007)

• Telecommunications cabling only• Amendment 1 to include high density connecting

h d f ti l fib d b l ihardware for optical fiber and balance pair cabling (2nd half 2010)Data Center planning telecomm nications• Data Center planning, telecommunications pathways, spaces, and administration to be included in EN 50174-2 amendment 1 (2nd halfincluded in EN 50174 2 amendment 1 (2 half 2010)

Page 12: Data Center Telecom Cabling Standards – Justification & Update

NMX (México) Data Center StandardNMX (México) Data Center Standard• NMX- I- xxx-NYCE 2010 Data Centers

S t i bilit d Hi h P fSustainability and High Performance• Expected to be published July 2010• Main text - Governance /sustainability• Focused on: Design, Construction & OperationFocused on: Design, Construction & Operation• Annex

ArchitectureCooling

Transport SystemsSafetyg

Energyy

Security

Page 13: Data Center Telecom Cabling Standards – Justification & Update

NMX Data Center Scheme DriversNMX Data Center Scheme Drivers

• Governance • Sustaintability• Business Continuity

Managment (BCM) conceptsFour DC types tiers by

• Three levels (accomplish efficiency, excellency)

• Based on ideas from:• Four DC types –tiers- by system , so each one has a classification.

• Based on ideas from: EUROPEAN COMMISSION Institute for Energy; CoNUEE, EPA, LBL, GreenGrid, Uptime Institute

• Historical bldgs. projects• Based on ISO (38500, 27000, 24764)

+NOM+NMX+IMEI+NYCE+ ITIL +

p

• Energy using PUE concept (parámetro de uso eficiente de energía)+NOM+NMX+IMEI+NYCE+ ITIL +

SOX+NFPA+ASIS+ASHRAE+TIA and BICSI (10 RCDDs involved)

energía)

• Cooling hybrid (active, passive, liquid)

Page 14: Data Center Telecom Cabling Standards – Justification & Update

NMX DC ranking per TIPOS (tier)NMX DC ranking per TIPOS (tier)

Page 15: Data Center Telecom Cabling Standards – Justification & Update

Differences between standardsDifferences between standardsTIA ISO/IEC CENELEC NMX

Balanced Pair Cat 3 min, Cat Cat 6A, 7, 7A Cat 6, 6A, 7, Cat 6A (recom,6A recomm

, , , , ,7A

(shielded)

MultimodeFiber

OM1 min OM3 min OM2 min OM3 min

Coaxial cable 734/735 coax None None NoneHorizontalcable length

100 m 100 m copper300+ m for

100 m copper300+ m for

100 m copper300+ m for

from HC fiber fiber fiberMMF connector

Multiple LC or MPO LC or MPO LC or MPO

SMF connector at EDA

Multiple LC for 1 or 2MPO for 3+

LC-PC LC or MPO

SMF connector at Entrance Rm

Multiple Angled-LC Angled-LC LC or MPO

Page 16: Data Center Telecom Cabling Standards – Justification & Update

ANSI/BICSI-002 - ScopeANSI/BICSI-002 - Scope• ANSI/BICSI-002 Data Center Design and g

Implementation Best Practices Standard• An international standard, not just U.S.An international standard, not just U.S.• Meant to supplement, not replace existing

data center cabling standards such asdata center cabling standards such as TIA-942 and CENELEC EN 50173-5Large committee of e perts (150)• Large committee of experts (150)

• Large document (~500 pages) covering a wide range of subjects

Page 17: Data Center Telecom Cabling Standards – Justification & Update

BICSI-002 Subjects CoveredBICSI-002 Subjects Covered• Site Selection• Architectural and Structural Design• Electrical Systems• Electrical Systems• Mechanical Systems (i.e., HVAC)• Fire Protection and Security• Building Automation Systemsg y• Commissioning• Maintenance• Maintenance

Page 18: Data Center Telecom Cabling Standards – Justification & Update

BICSI-002 Subjects CoveredBICSI-002 Subjects Covered• Telecommunications

– Access Providers & Entrance Facilities– Telecom Spacesp– Cabinets & Racks– Cabling PathwaysCabling Pathways– Telecom Cabling– Field TestingField Testing– Telecom Administration

• Information Technology• Information Technology

Page 19: Data Center Telecom Cabling Standards – Justification & Update

TIA-942-A ChangesTIA-942-A Changes- Compatibility with 568-C series (references,

terms cabling infrastructure description)terms, cabling infrastructure description)- Incorporate TIA-942 Addendum 1 (coaxial

cables and E1 T1 E3 T3 circuit distances)cables and E1, T1, E3, T3 circuit distances)- Incorporate TIA-942 Addendum 2 (RF

interference lighting levels revised temperatureinterference, lighting levels, revised temperature & humidity, addition of Cat 6A, revised Tiering)Labeling superseded by TIA 606 A 1- Labeling superseded by TIA-606-A-1

- Grounding to be superseded by TIA-607-B - Cabinets to be moved to TIA-569-C

Page 20: Data Center Telecom Cabling Standards – Justification & Update
Page 21: Data Center Telecom Cabling Standards – Justification & Update

TIA-942-A ChangesTIA-942-A Changes• Energy efficiency• Remove Cat 3 and 5e horizontal cabling• Remove Cat 3 and 5e horizontal cabling• Remove 62.5/125 (OM1) and add OM4

R d LC f 1 2 SM MM fib d• Recommend LC for 1 or 2 SM or MM fibers and MPO for more than 2 fibersRemove 100 m horizontal cabling length for• Remove 100 m horizontal cabling length for optical fiber cabling

• Larger data center topologies• Larger data center topologies• Telecom redundancy at various tiers

Page 22: Data Center Telecom Cabling Standards – Justification & Update
Page 23: Data Center Telecom Cabling Standards – Justification & Update

Energy Efficiency – TemperatureEnergy Efficiency Temperature & Humidity

C t R E i t R• Computer Rooms, Equipment Rooms, Access/Service Provider Spaces

T t 18 27 C (64 81 F)– Temperature: 18 – 27 °C (64 – 81 °F)– Max Relative Humidity: 60%

Max dew point: 15 °C (59 °F)– Max dew point: 15 C (59 F) – Min dew point: 5.5 °C (42 °F) to control ESD– Dew point temperature to which air must be cooled toDew point temperature to which air must be cooled to

reach saturation– Old values 68 to 77 °F with 40% to 55% RH for

tcomputer rooms

Page 24: Data Center Telecom Cabling Standards – Justification & Update

Energy Efficiency – TemperatureEnergy Efficiency Temperature & Humidity

• TRs, Common TRs, TEs, Entrance Rooms– Temperature: 5 – 35 °C (41 – 95 °F)p ( )– Relative Humidity: 8 - 80%– Max dew point: 28 °C (82 °F) p ( )– TR original requirements were to ‘maintain a

temperature the same as the adjacent office p jarea’. Other spaces had no requirements other than those required by the active

i tequipment.

Page 25: Data Center Telecom Cabling Standards – Justification & Update

Energy Efficiency - LightingEnergy Efficiency - Lighting• 3 Level lighting protocol by zone for data g g p y

centers depending on human occupancy– Level 1 – no occupants - just high enough for p j g g

monitoring by surveillance cameras– Level 2 – motion detectors used to initiate

higher level access to provide safe passage & ID by cameras

– Level 3 – 500 lux (1 m/3 ft AFF in aisle) when space is occupied for working on equipment

Page 26: Data Center Telecom Cabling Standards – Justification & Update

Energy Efficiency - PathwaysEnergy Efficiency - Pathways• Overhead cabling is a best practice where

ceiling heights permit (reduces losses due to airflow obstruction and turbulence)

• If cabling is under floor consider smaller diameter cables or alternative network

hit t t d bli larchitectures to reduce cabling volumes• Avoid blocking airflow to/from cabinets,

til t d til A/C IT d t l iventilated tiles, A/C, IT, and telecom equip• Minimize loss of air thru tile cuts

Page 27: Data Center Telecom Cabling Standards – Justification & Update

Energy Efficiency - SpacesEnergy Efficiency - Spaces• Consider using enclosures or enclosure systems

that improve cooling efficiencythat improve cooling efficiency• Cabling and cabling pathways should not

compromise efficiency of enclosure systemcompromise efficiency of enclosure system• Blanking panels & no unused cabinet positions

that compromise hot/cold aislesthat compromise hot/cold aisles• Segregate equip with different environmental

requirementsrequirements• Build in modules/phases• Remove equipment that is no longer neededRemove equipment that is no longer needed• Monitor power levels

Page 28: Data Center Telecom Cabling Standards – Justification & Update

TIA-606-A-1 Computer Room Administration

• Identification/labeling scheme in TIA• Identification/labeling scheme in TIA-606-A Addendum 1 will replace administration guidelines in TIA-942g

• Provides guidance for identifiers and labeling in computer rooms and

i tequipment rooms

Page 29: Data Center Telecom Cabling Standards – Justification & Update

Cabinet Naming SchemeCabinet Naming Scheme

AE AF AG AH AI AJAC ADABAA

"X" COORDINATE

01

02

03

AD02

AD03 AG04

AG03CO

LD

HO

HO

04

05

06

07

AD03

AD04

AD05

AG04

AG05

AG06

D A

ISLE

(CA

B

OT A

ISLE

(CA

OT A

ISLE

(CA

09

10

07

08

AD07

AD08

AD09

AG08

AG09

AG10B

INE

T FRO

N

AB

INE

T RE

AR

AB

INE

T RE

AR10

11

12

13

AD10 AG11

AG13AD12

NTS

)

R)

R)

"Y" COORDINATE

= cabinet corner used for grid location ID (right front facing the cabinet)

Page 30: Data Center Telecom Cabling Standards – Justification & Update

606-A-1Patch Panel

IDSchemeScheme

Page 31: Data Center Telecom Cabling Standards – Justification & Update

TIA 606-A-1 Patch Panels & CablesTIA 606 A 1 Patch Panels & Cables

At minimum label patch panel with ID of patch panel and 1st or last port of every subpanelpanel and 1 or last port of every subpanelIdentifier of cable on port 1 is:

AG03-35:01 / AD03-35:01

Page 32: Data Center Telecom Cabling Standards – Justification & Update

• Jonathan JewJonathan Jew• President J&M Consultants, Inc.• Website: www.j-and-m.com• Email: [email protected]

• Vice-Chair TIA TR-42.6 telecom administration b ittsubcommittee

• Editor ISO/IEC TR 14763-2-1 telecom administration identifiersadministration identifiers

• US National Committee Project Manager ISO/IEC 24764 data center standard

• Data Center & Administration Section Editor –ISO/IEC 14763-2 cabling planning & installation

• Co-chair BICSI data center subcommitteeCo chair BICSI data center subcommittee• Co-editor TIA-942-A

Page 33: Data Center Telecom Cabling Standards – Justification & Update

EXTRA MATERIAL AS TIME PERMITSPERMITS

Page 34: Data Center Telecom Cabling Standards – Justification & Update

Equipment Cabinets• Front rails of cabinets• Front rails of cabinets

must be recessed to provide adequate room for patch cables and wire managers

• Adequate space forAdequate space for cable management

• Arrange switches and t h l tpatch panels to

minimize patching between cabinets &

kracks• Perforated tiles at front

of cabinetsof cabinets• One edge of cabinets

placed at edge of tile

Page 35: Data Center Telecom Cabling Standards – Justification & Update

Plan for growth & consider airflow

SDSDSDSDSD

1

2

3

4

5

6

7

1

2

3

4

5

6

7

7 FOOT RACK7 FOOT RACK7 FOOT RACK7 FOOT RACK7 FOOT RACK

Power Supply 1 Power Supply 2

Catalyst 6500 SERIES

8

9

10

11

12

13

Power Supply 1 Power Supply 2

Catalyst 6500 SERIES

8

9

10

11

12

13

7 FOOT RACK7 FOOT RACK7 FOOT RACK7 FOOT RACK7 FOOT RACK

Page 36: Data Center Telecom Cabling Standards – Justification & Update

Space impact of cabling systems• Allocate adequate space and

carefully plan location of Telecommunications areas MDATelecommunications areas MDA HDAs, Entrance Rooms, Telecom Rooms

• Provide adequate space and coordinate location of cabling pathwayspathways

• Space in server cabinets for patch panels and cable management

• Distance restrictions affect the dimensions of the computer room, location of telecom spaces andlocation of telecom spaces, and location of equipment 18”x6” 1100 Cat 6

Page 37: Data Center Telecom Cabling Standards – Justification & Update

Spacing between trays not 12”in this data center in Tokyo

Page 38: Data Center Telecom Cabling Standards – Justification & Update

These electrical trays commonly used in Europe have sharp edges that damage cablesEurope have sharp edges that damage cables

Page 39: Data Center Telecom Cabling Standards – Justification & Update

More than 40% fill and more than 6” depth of bl t i th lid b tt t i S dcable tray in these solid bottom trays in Sydney

Page 40: Data Center Telecom Cabling Standards – Justification & Update

Unshielded Power Cables(and non locking plugs in this data center(and non-locking plugs in this data center

in Sydney)

Page 41: Data Center Telecom Cabling Standards – Justification & Update

Cable ties instead of listed hardware for SRG, non locking receptacles in this Paris DClocking receptacles in this Paris DC