  • Data Center Cabling Challenges Past, Present & FutureJONATHAN JEW – [email protected]

  • My Past ….

    35 years 100+ data center projectsSmall computer rooms to mega data centers

  • Data Center and Telecom Cabling Standards

    17 years TIA – US & Canadian standardsBICSI – International Best Practices ISO/IEC – International standards

  • In the beginning … 1970’s-1980’s Computer rooms commonly

    located in converted office space Almost entirely mainframes and

    minicomputers Communications cabling

    No LAN or SAN Proprietary channel cabling Proprietary communications

    cabling Standards-based CCITT X.21, CCITT

    V.35, EIA RS-232 cabling 9600 bps common speed 56000 bps was a fast speed

  • Large Proprietary Point-to-Point Cabling

  • IEEE 802 LAN Standards

    IEEE 802.3 Ethernet (mostly DEC) and IEEE 802.5 Token Ring (mostly IBM)

    Higher Speeds – Initially 10 MbpsEthernet and 4 Mbps Token Ring

    Smaller cable diameters Standards-based cabling Addressed large proprietary and

    relatively slow cabling in data centers

  • TIA-568 Cabling Standards TIA/EIA-568-B:1995 defined

    Category 3, 4, 5 cables Cat 3 (up to 10 Mbps) Cat 4 (up to 16 Mbps) Cat 5 (up to 100 Mbps) Replaced coaxial cable used for

    Ethernet and Type 1 cable used for Token Ring

    Solved single-use cabling problem - generic cabling usable in data centers for wide range of other applications (WAN, console, terminals, voice) and further reduced cable sizes

  • TIA-606 Administration Standard ANSI/TIA-606:1993 Provided standard for labeling and administration of structured cabling systems

    Easy to troubleshoot and make changesDifficult to troubleshoot and make changes

    All ports and cords labeled(with near and far end port IDs)

    Only one label (ne pas disconnect )

  • Impact of Documentation, Labeling, & Equipment Refresh

    Labeling and documentation substantially reduced outage time (addressed in TIA-606)

    Equipment life cycle refresh reduced frequency of failures

  • TIA-942 Telecom Infrastructure Standard for Data Centers ANSI/TIA-942:2005 First structured cabling standard for data centers Addressed a wide range of other subjects

    Ceiling & door heights Lighting Floor loading Cabinet design and placement Temperature & humidity Separation of power and twisted pair Circuit distances Site selection Tier/Rating

    Corresponding ISO/IEC 11801-5 only addresses cabling

  • Point-to-point unstructured cablingH

    eate

    r - A

    /C

    Heater - A/CHeater - A/C Heater - A/C

    247-7538

    HALONABORTHALON

    RELEASE

    247-7543

    HALONPANEL

    LOCKER

    TAPE RACK

    NETWORKCABINET

    H5

    NETWORKCABINET

    H4

    NETWORKCABINET

    H3

    NETWORKCABINET

    H2

    NETWORKCABINET

    H6

    NETWORKCABINET

    H7

    NETWORKCABINET

    H1

    NETWORKCABINET

    G4

    NETWORKCABINET

    G3

    NETWORKCABINET

    G2

    NETWORKCABINET

    G1

    NETWORKCABINET

    G5

    TABL

    E

    TAPE RACK

    NET

    WO

    RK

    CAB

    INET

    I 8

    NET

    WO

    RK

    CAB

    INET

    I7

    NET

    WO

    RK

    CAB

    INET

    I6

    NET

    WO

    RK

    CAB

    INET

    I5

    NET

    WO

    RK

    CAB

    INET

    I4

    NET

    WO

    RK

    CAB

    INET

    I3

    NET

    WO

    RK

    CAB

    INET

    I2

    NET

    WO

    RK

    CAB

    INET

    I 1

    TAPE RACK

    NETWORKCABINET

    H8

    NETWORKCABINET

    G6

    NETWORKCABINET

    G7

    NETWORKCABINET

    F4

    NETWORKCABINET

    F3

    NETWORKCABINET

    F2

    NETWORKCABINET

    F5

    LANCABINET

    F1

    NETWORKCABINET

    F6

    NETWORKCABINET

    E5

    NETWORKCABINET

    E4

    NETWORKCABINET

    E3

    NETWORKCABINET

    E2

    NETWORKCABINET

    E1

    NETWORKCABINET

    E6

    SAACABINET

    D2

    NETWORKCABINET

    E7IBMCAB

    SAACABINET

    D1

    NETWORKCABINET

    B5

    NETWORKCABINET

    B4

    NETWORKCABINET

    B3

    NETWORKCABINET

    B2

    NETWORKCABINET

    B1

    NETWORKCABINET

    B6

    NETWORKCABINET

    C5

    NETWORKCABINET

    C4

    NETWORKCABINET

    C3

    NETWORKCABINET

    C2

    NETWORKCABINET

    C1

    NETWORKCABINET

    C6

    NETWORKCABINET

    B7

    CD ROMSCANNER

    AT&TDEFINITY

    UNIT

    HPPRINTER

    NETWORKCABINET

    A6

    NETWORKCABINET

    A5

    NETWORKCABINET

    A4

    NETWORKCABINET

    A3

    NETWORKCABINET

    A2

    TABLE247-7589

    TABLE

    CISC

    O

    RO

    UTER

    CO

    NSO

    LE

    F/X

    IBMDASD

    IBMDASD

    IBMAS-400

    IBMAS-400

    IBMS-390R34

    IBM3746-900

    IBM3745-17A

    IBM3745-L13

    IBM

    3745-41D

    IBM3745-A11

    POM

    ON

    AA/

    C U

    NIT

    #8

    STO

    RAG

    EC

    ABIN

    ET

    DES

    K

    DESKSTORAGECABINET

    PAC

    BEL

    LC

    ABIN

    ETA 1

    3174CABINET

    TABLE STORAGECABINET

    STORAGECABINET

    LIEBERTPDU-C

    3174CABINET

    3174CABINET

    3174CABINET

    3174CABINET

    3174CABINET

    POMONAA/C UNIT

    #6

    POMONAA/C UNIT

    #7

    FILECABINET

    FILECABINET

    FILECABINET

    FILECABINET

    G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ AK AL AM AN AO AP AQ AR ASC D E FBA

    2

    1

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    NETWORK

    INSTALL A CABLE WHEN YOU NEED IT (SINGLE-USE, UNORGANIZED CABLING)

  • Entrance Room(Carrier Equip &

    Demarcation)

    Access Providers

    HDA(LAN/SAN/KVM

    Switches)

    EDA(Rack/Cabinet)

    ComputerRoom

    HDA(LAN/SAN/KVM

    Switches)ZDA

    Work Areas in Offices, Operations

    Center, Support Rooms

    TR(Office & Operations

    Center LAN Switches)

    MDA(Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes)

    HDA(LAN/SAN/KVM

    Switches)

    EDA(Rack/Cabinet)

    EDA(Rack/Cabinet)

    Backbone cabling

    Horizontal cabling Horizontal cabling Horizontal cabling

    Horizontal cabling

    Backbone cabling

    Backbonecabling

    Horizontal cabling

    Access Providers

    HDA(LAN/SAN/KVM

    Switches)

    EDA(Rack/Cabinet)

    Horizontal cabling

    TIA-942Data CenterTopology

  • Structured cabling – faster deployment, easier to manage & troubleshoot

    Hea

    ter -

    A/C

    Heater - A/CHeater - A/C Heater - A/C

    247-7538

    HALONAB ORTHALON

    RELE ASE

    247-7543

    HALONPA NEL

    LOCKE R

    TAPE RACK

    NETWORKCABINET

    H5

    NETWORKCABINET

    H4

    NETWORKCABINET

    H3

    NETWORKCABINET

    H2

    NETWORKCABINET

    H6

    NETWORKCABINET

    H7

    NETWORKCABINET

    H1

    NETWORKCABINET

    G4

    NETWORKCABINET

    G3

    NETWORKCABINET

    G2

    NETWORKCABINET

    G1

    NETWORKCABINET

    G5

    TABL

    E

    TAPE RACK

    NETW

    ORK

    CABI

    NET

    I8

    NETW

    ORK

    CABI

    NET

    I7

    NETW

    ORK

    CABI

    NET

    I6

    NETW

    ORK

    CABI

    NET

    I5

    NETW

    ORK

    CABI

    NET

    I4

    NETW

    ORK

    CABI

    NET

    I3

    NETW

    ORK

    CABI

    NET

    I2

    NETW

    ORK

    CABI

    NET

    I1

    TAPE RACK

    NETWORKCABINET

    H8

    NETWORKCABINET

    G6

    NETWORKCABINET

    G7

    NETWORKCABINET

    F4

    NETWORKCABINET

    F3

    NETWORKCABINET

    F2

    NETWORKCABINET

    F5

    LANCABINET

    F1

    NETWORKCABINET

    F6

    NETWORKCABINET

    E5

    NETWORKCABINET

    E4

    NETWORKCABINET

    E3

    NETWORKCABINET

    E2

    NETWORKCABINET

    E1

    NETWORKCABINET

    E6

    SA ACABINET

    D2

    NETWORKCABINET

    E7IBMCAB

    SA ACABINET

    D1

    NETWORKCABINET

    B5

    NETWORKCABINET

    B4

    NETWORKCABINET

    B3

    NETWORKCABINET

    B2

    NETWORKCABINET

    B1

    NETWORKCABINET

    B6

    NETWORKCABINET

    C5

    NETWORKCABINET

    C4

    NETWORKCABINET

    C3

    NETWORKCABINET

    C2

    NETWORKCABINET

    C1

    NETWORKCABINET

    C6

    NETWORKCABINET

    B7

    CD ROMSCANNE R

    AT&TDEF INITY

    UNIT

    HPPRINTER

    NETWORKCABINET

    A6

    NETWORKCABINET

    A5

    NETWORKCABINET

    A4

    NETWORKCABINET

    A3

    NETWORKCABINET

    A2

    TABLE247-7589

    TABLE

    CIS

    CO

    RO

    UTERC

    ONS

    OLE

    F/X

    IBMDASD

    IBMDASD

    IBMAS-400

    IBMAS-400

    IBMS-390R34

    IBM3746-900

    IBM3745-17A

    IBM3745-L13

    IBM

    3745-41D

    IBM3745-A11

    POM

    ON

    AA/

    C U

    NIT

    #8

    STO

    RAG

    EC

    ABIN

    ET

    DES

    K

    DESKSTORAGECABINET

    PAC

    BELL

    CAB

    INET

    A1

    3174CABINET

    TABLE STORAGECABINET

    STORAGECABINET

    LIEBERTPDU-C

    3174CABINET

    3174CABINET

    3174CABINET

    3174CABINET

    3174CABINET

    POMONAA/C UNIT

    #6

    POMONAA/C UNIT

    #7

    FILECABINET

    F ILECABINET

    F ILECABINET

    F ILECABINET

    G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ AK AL AM AN AO AP AQ AR ASC D E FBA

    2

    1

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    FIBER MDA

    COPPER MDA

    IDFIDF

    IDF

    IDF

    IDF

    STRUCTURED CABLING SYSTEM (ORGANIZED, REUSABLE, FLEXIBLE CABLING)

    HDA

    HDA

    HDAMainframe

    IBM 3745s

    HDA

    HDA

  • Building Automation Systems

    TIA-862 addresses structured cabling for a wide variety of other systems in data centers. Common examples: Security camerasAccess controlHVAC & electrical systems Lighting

    Much more common now than in the past International equivalent ISO/IEC 11801-6:2017

  • Grounding & Bonding ANSI/TIA-607-B:2011 Addressed bonding and

    grounding in data centers Long development (2007-2011)

    because of disagreement on approaches to grounding

    ANSI/NECA/BICSI-607:2011 Grounding and bonding

    planning and installation methods that complements TIA-607-B

    International equivalent ISO/IEC 30129:2015

  • Larger & Container Data Centers

    TIA-942-A revision added Intermediate

    Distribution Area (IDA) for large data centers

    Allowed >100m distance for horizontal fiber

    Support for outdoor container modules

  • CURRENT CHALLENGES

  • Energy Efficiency Much more important now than in the past Addressed in a wide variety of standards

    TIA-942-A added section on energy efficiency

    TIA-569 revisions adopted wider range of temperatures & humidity recommended by ASHRAE

    BICSI-002:2014 revision ASHRAE TC 9.9 publications (Thermal

    Guidelines) Future ISO/IEC TS 22237

  • Physical Security ANSI/TIA-5017:2016 & Future ISO/IEC

    standard Telecommunications Physical Network

    Security Standard TIA standard developed in response to

    request by US Government Developed in conjunction with specialist

    that design secure installations for the US government and military

    Three levels of security1. basic,2. tamper resistant, 3. critical security installation

  • Replacement of traditional 3-tier network architecture with spine-leaf architecture

    3-Tier Network Architecture Spine-Leaf Switch Fabric

    • Provides non-blocking, low latency switch fabric for cloud computing• Cabling for switch fabrics addressed in TIA-942-A Addendum 1• Requires more cabling and higher speed switch-to-switch cabling –

    40G, 100G, 400G

  • Higher Speeds Need Multiple Fibers

    12-fiber MPO use 8 of 12 fibers for 40G, 100G and 200G Ethernet

    400GBASE-SR16 (400G Ethernet) will use 32-fiber MPO and waste no OM3/OM4 fibers

    May also be used for 800GBASE-SR16 (800G Ethernet)

  • Faster Deployment Added recommendation to consider preterminated cabling to

    reduce installation time and improve consistency and quality of terminations

  • Higher Densities Changed maximum 2.1 m (7 ft) maximum cabinet/rack height

    from a requirement to a recommendation permitting use of taller cabinets and racks

  • Higher Densities - Cautions Added recommendation to consider needs for proper labeling, cable

    routing, cable management, and ability to insert and remove cords without disrupting existing or adjacent connections when selecting patch panels.

  • BICSI-002 Data Center Design & Implementation Best Practices

    Goes beyond what is provided in the cabling standards by TIA, CENELEC, and ISO/IEC Complements the national standard for telecom cabling by providing information on a wide

    range of subjects not covered in the telecom standards and provide more information

    BICSI Best Practices

    (e.g., TDMM, BICSI-002)

    Codes(e.g., NFPA 70

    NEC)

    Company Standards

    National Standards

    TIA for US & CanadaNational

    StandardsCENELEC for

    Europe

    National StandardsISO/IEC for many other

  • Pages

    114 Pages 503 Pages

    BICSI-002 provides information on a wide range of subjects not covered in TIA-942

  • BICSI-002 mostly deals with aspects of data center design other than telecomBICSI-002 PagesElectrical 120

    Telecommunications 84Security 44Mechanical 40Space Planning 32Maintenance 29Commissioning 28General 25Availability 23Site Selection 20Architectural 16Fire Protection 10DCIM & BAS 8Design Process 8Structural 4Outsourcing 4Multiple Data Centers 4Energy Efficiency 4

  • BICSI-009 Data Center Operations & Maintenance Best Practices

    Companion standard to BICSI-002, but for data centers when they are in operation Another large and comprehensive standard, that also covers a wide range of subjects, but

    instead related to operations and maintenance of data centers: Governance and Assessment – Compliance, Assessment Program

    Operating Procedures

    Security

    Maintenance Procedures

    Emergency Procedures

    Management

  • EN 50600

    Structure of the standard

  • Positioning of BICSI-002 and BICSI-009 relative to EN 50600 & ISO/IEC TS 22237

  • Edge Data Centers

  • Future Challenges Increasing consolidation of SAN and LAN traffic (higher traffic loads and

    need for less delay) Higher Speeds 800G, 1TB (8 x OM5, 32 x OM4, multi-pair single-mode?) Edge data centers (computer rooms in new environments) Smart cities, IoT (Internet of Things), smart cars, streaming replacing TV,

    and other applications increasing processing, storage, and bandwidth demands of the data center

    IoT and single-pair cabling bringing more devices into the structured cabling of the data center

  • Questions?Jonathan JewPresident J&M Consultants, Inc.Website: www.j-and-m.comEmail: [email protected]

    Secretary TIA TR-42Vice-Chair TIA TR-42.3 pathways & spacesCo-chair BICSI data center subcommitteeVice-chair USTAG to ISO/IEC JTC 1 SC 25 WG 3Editor ISO/IEC TR 14763-2-1 telecom admin identifiersSME BICSI TI&M Telecommunications Administration

    Data Center Cabling Challenges Past, Present & FutureMy Past ….Data Center and Telecom Cabling StandardsIn the beginning … Large Proprietary Point-to-Point CablingIEEE 802 LAN StandardsTIA-568 Cabling StandardsTIA-606 Administration StandardImpact of Documentation, Labeling, & Equipment RefreshTIA-942 Telecom Infrastructure Standard for Data CentersPoint-to-point unstructured cablingSlide Number 12Structured cabling – faster deployment, easier to manage & troubleshootBuilding Automation SystemsGrounding & BondingLarger & Container Data CentersCURRENT CHALLENGESEnergy EfficiencyPhysical SecurityReplacement of traditional 3-tier network architecture with spine-leaf architectureHigher Speeds Need Multiple FibersFaster DeploymentHigher DensitiesHigher Densities - CautionsBICSI-002 Data Center Design & Implementation Best PracticesSlide Number 26BICSI-002 mostly deals with aspects of data center design other than telecomBICSI-009 Data Center Operations & Maintenance Best Practices Slide Number 29Positioning of BICSI-002 and BICSI-009 relative to EN 50600 & ISO/IEC TS 22237 Edge Data CentersFuture ChallengesQuestions?