Data Center Cabling Challenges Past, Present & FutureJONATHAN JEW – [email protected]
My Past ….
35 years 100+ data center projectsSmall computer rooms to mega data centers
Data Center and Telecom Cabling Standards
17 years TIA – US & Canadian standardsBICSI – International Best Practices ISO/IEC – International standards
In the beginning … 1970’s-1980’s Computer rooms commonly
located in converted office space Almost entirely mainframes and
minicomputers Communications cabling
No LAN or SAN Proprietary channel cabling Proprietary communications
cabling Standards-based CCITT X.21, CCITT
V.35, EIA RS-232 cabling 9600 bps common speed 56000 bps was a fast speed
Large Proprietary Point-to-Point Cabling
IEEE 802 LAN Standards
IEEE 802.3 Ethernet (mostly DEC) and IEEE 802.5 Token Ring (mostly IBM)
Higher Speeds – Initially 10 MbpsEthernet and 4 Mbps Token Ring
Smaller cable diameters Standards-based cabling Addressed large proprietary and
relatively slow cabling in data centers
TIA-568 Cabling Standards TIA/EIA-568-B:1995 defined
Category 3, 4, 5 cables Cat 3 (up to 10 Mbps) Cat 4 (up to 16 Mbps) Cat 5 (up to 100 Mbps) Replaced coaxial cable used for
Ethernet and Type 1 cable used for Token Ring
Solved single-use cabling problem - generic cabling usable in data centers for wide range of other applications (WAN, console, terminals, voice) and further reduced cable sizes
TIA-606 Administration Standard ANSI/TIA-606:1993 Provided standard for labeling and administration of structured cabling systems
Easy to troubleshoot and make changesDifficult to troubleshoot and make changes
All ports and cords labeled(with near and far end port IDs)
Only one label (ne pas disconnect )
Impact of Documentation, Labeling, & Equipment Refresh
Labeling and documentation substantially reduced outage time (addressed in TIA-606)
Equipment life cycle refresh reduced frequency of failures
TIA-942 Telecom Infrastructure Standard for Data Centers ANSI/TIA-942:2005 First structured cabling standard for data centers Addressed a wide range of other subjects
Ceiling & door heights Lighting Floor loading Cabinet design and placement Temperature & humidity Separation of power and twisted pair Circuit distances Site selection Tier/Rating
Corresponding ISO/IEC 11801-5 only addresses cabling
Point-to-point unstructured cablingH
eate
r - A
/C
Heater - A/CHeater - A/C Heater - A/C
247-7538
HALONABORTHALON
RELEASE
247-7543
HALONPANEL
LOCKER
TAPE RACK
NETWORKCABINET
H5
NETWORKCABINET
H4
NETWORKCABINET
H3
NETWORKCABINET
H2
NETWORKCABINET
H6
NETWORKCABINET
H7
NETWORKCABINET
H1
NETWORKCABINET
G4
NETWORKCABINET
G3
NETWORKCABINET
G2
NETWORKCABINET
G1
NETWORKCABINET
G5
TABL
E
TAPE RACK
NET
WO
RK
CAB
INET
I 8
NET
WO
RK
CAB
INET
I7
NET
WO
RK
CAB
INET
I6
NET
WO
RK
CAB
INET
I5
NET
WO
RK
CAB
INET
I4
NET
WO
RK
CAB
INET
I3
NET
WO
RK
CAB
INET
I2
NET
WO
RK
CAB
INET
I 1
TAPE RACK
NETWORKCABINET
H8
NETWORKCABINET
G6
NETWORKCABINET
G7
NETWORKCABINET
F4
NETWORKCABINET
F3
NETWORKCABINET
F2
NETWORKCABINET
F5
LANCABINET
F1
NETWORKCABINET
F6
NETWORKCABINET
E5
NETWORKCABINET
E4
NETWORKCABINET
E3
NETWORKCABINET
E2
NETWORKCABINET
E1
NETWORKCABINET
E6
SAACABINET
D2
NETWORKCABINET
E7IBMCAB
SAACABINET
D1
NETWORKCABINET
B5
NETWORKCABINET
B4
NETWORKCABINET
B3
NETWORKCABINET
B2
NETWORKCABINET
B1
NETWORKCABINET
B6
NETWORKCABINET
C5
NETWORKCABINET
C4
NETWORKCABINET
C3
NETWORKCABINET
C2
NETWORKCABINET
C1
NETWORKCABINET
C6
NETWORKCABINET
B7
CD ROMSCANNER
AT&TDEFINITY
UNIT
HPPRINTER
NETWORKCABINET
A6
NETWORKCABINET
A5
NETWORKCABINET
A4
NETWORKCABINET
A3
NETWORKCABINET
A2
TABLE247-7589
TABLE
CISC
O
RO
UTER
CO
NSO
LE
F/X
IBMDASD
IBMDASD
IBMAS-400
IBMAS-400
IBMS-390R34
IBM3746-900
IBM3745-17A
IBM3745-L13
IBM
3745-41D
IBM3745-A11
POM
ON
AA/
C U
NIT
#8
STO
RAG
EC
ABIN
ET
DES
K
DESKSTORAGECABINET
PAC
BEL
LC
ABIN
ETA 1
3174CABINET
TABLE STORAGECABINET
STORAGECABINET
LIEBERTPDU-C
3174CABINET
3174CABINET
3174CABINET
3174CABINET
3174CABINET
POMONAA/C UNIT
#6
POMONAA/C UNIT
#7
FILECABINET
FILECABINET
FILECABINET
FILECABINET
G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ AK AL AM AN AO AP AQ AR ASC D E FBA
2
1
3
4
5
6
7
8
9
10
11
12
13
14
15
16
NETWORK
INSTALL A CABLE WHEN YOU NEED IT (SINGLE-USE, UNORGANIZED CABLING)
Entrance Room(Carrier Equip &
Demarcation)
Access Providers
HDA(LAN/SAN/KVM
Switches)
EDA(Rack/Cabinet)
ComputerRoom
HDA(LAN/SAN/KVM
Switches)ZDA
Work Areas in Offices, Operations
Center, Support Rooms
TR(Office & Operations
Center LAN Switches)
MDA(Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes)
HDA(LAN/SAN/KVM
Switches)
EDA(Rack/Cabinet)
EDA(Rack/Cabinet)
Backbone cabling
Horizontal cabling Horizontal cabling Horizontal cabling
Horizontal cabling
Backbone cabling
Backbonecabling
Horizontal cabling
Access Providers
HDA(LAN/SAN/KVM
Switches)
EDA(Rack/Cabinet)
Horizontal cabling
TIA-942Data CenterTopology
Structured cabling – faster deployment, easier to manage & troubleshoot
Hea
ter -
A/C
Heater - A/CHeater - A/C Heater - A/C
247-7538
HALONAB ORTHALON
RELE ASE
247-7543
HALONPA NEL
LOCKE R
TAPE RACK
NETWORKCABINET
H5
NETWORKCABINET
H4
NETWORKCABINET
H3
NETWORKCABINET
H2
NETWORKCABINET
H6
NETWORKCABINET
H7
NETWORKCABINET
H1
NETWORKCABINET
G4
NETWORKCABINET
G3
NETWORKCABINET
G2
NETWORKCABINET
G1
NETWORKCABINET
G5
TABL
E
TAPE RACK
NETW
ORK
CABI
NET
I8
NETW
ORK
CABI
NET
I7
NETW
ORK
CABI
NET
I6
NETW
ORK
CABI
NET
I5
NETW
ORK
CABI
NET
I4
NETW
ORK
CABI
NET
I3
NETW
ORK
CABI
NET
I2
NETW
ORK
CABI
NET
I1
TAPE RACK
NETWORKCABINET
H8
NETWORKCABINET
G6
NETWORKCABINET
G7
NETWORKCABINET
F4
NETWORKCABINET
F3
NETWORKCABINET
F2
NETWORKCABINET
F5
LANCABINET
F1
NETWORKCABINET
F6
NETWORKCABINET
E5
NETWORKCABINET
E4
NETWORKCABINET
E3
NETWORKCABINET
E2
NETWORKCABINET
E1
NETWORKCABINET
E6
SA ACABINET
D2
NETWORKCABINET
E7IBMCAB
SA ACABINET
D1
NETWORKCABINET
B5
NETWORKCABINET
B4
NETWORKCABINET
B3
NETWORKCABINET
B2
NETWORKCABINET
B1
NETWORKCABINET
B6
NETWORKCABINET
C5
NETWORKCABINET
C4
NETWORKCABINET
C3
NETWORKCABINET
C2
NETWORKCABINET
C1
NETWORKCABINET
C6
NETWORKCABINET
B7
CD ROMSCANNE R
AT&TDEF INITY
UNIT
HPPRINTER
NETWORKCABINET
A6
NETWORKCABINET
A5
NETWORKCABINET
A4
NETWORKCABINET
A3
NETWORKCABINET
A2
TABLE247-7589
TABLE
CIS
CO
RO
UTERC
ONS
OLE
F/X
IBMDASD
IBMDASD
IBMAS-400
IBMAS-400
IBMS-390R34
IBM3746-900
IBM3745-17A
IBM3745-L13
IBM
3745-41D
IBM3745-A11
POM
ON
AA/
C U
NIT
#8
STO
RAG
EC
ABIN
ET
DES
K
DESKSTORAGECABINET
PAC
BELL
CAB
INET
A1
3174CABINET
TABLE STORAGECABINET
STORAGECABINET
LIEBERTPDU-C
3174CABINET
3174CABINET
3174CABINET
3174CABINET
3174CABINET
POMONAA/C UNIT
#6
POMONAA/C UNIT
#7
FILECABINET
F ILECABINET
F ILECABINET
F ILECABINET
G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ AK AL AM AN AO AP AQ AR ASC D E FBA
2
1
3
4
5
6
7
8
9
10
11
12
13
14
15
16
FIBER MDA
COPPER MDA
IDFIDF
IDF
IDF
IDF
STRUCTURED CABLING SYSTEM (ORGANIZED, REUSABLE, FLEXIBLE CABLING)
HDA
HDA
HDAMainframe
IBM 3745s
HDA
HDA
Building Automation Systems
TIA-862 addresses structured cabling for a wide variety of other systems in data centers. Common examples: Security camerasAccess controlHVAC & electrical systems Lighting
Much more common now than in the past International equivalent ISO/IEC 11801-6:2017
Grounding & Bonding ANSI/TIA-607-B:2011 Addressed bonding and
grounding in data centers Long development (2007-2011)
because of disagreement on approaches to grounding
ANSI/NECA/BICSI-607:2011 Grounding and bonding
planning and installation methods that complements TIA-607-B
International equivalent ISO/IEC 30129:2015
Larger & Container Data Centers
TIA-942-A revision added Intermediate
Distribution Area (IDA) for large data centers
Allowed >100m distance for horizontal fiber
Support for outdoor container modules
CURRENT CHALLENGES
Energy Efficiency Much more important now than in the past Addressed in a wide variety of standards
TIA-942-A added section on energy efficiency
TIA-569 revisions adopted wider range of temperatures & humidity recommended by ASHRAE
BICSI-002:2014 revision ASHRAE TC 9.9 publications (Thermal
Guidelines) Future ISO/IEC TS 22237
Physical Security ANSI/TIA-5017:2016 & Future ISO/IEC
standard Telecommunications Physical Network
Security Standard TIA standard developed in response to
request by US Government Developed in conjunction with specialist
that design secure installations for the US government and military
Three levels of security1. basic,2. tamper resistant, 3. critical security installation
Replacement of traditional 3-tier network architecture with spine-leaf architecture
3-Tier Network Architecture Spine-Leaf Switch Fabric
• Provides non-blocking, low latency switch fabric for cloud computing• Cabling for switch fabrics addressed in TIA-942-A Addendum 1• Requires more cabling and higher speed switch-to-switch cabling –
40G, 100G, 400G
Higher Speeds Need Multiple Fibers
12-fiber MPO use 8 of 12 fibers for 40G, 100G and 200G Ethernet
400GBASE-SR16 (400G Ethernet) will use 32-fiber MPO and waste no OM3/OM4 fibers
May also be used for 800GBASE-SR16 (800G Ethernet)
Faster Deployment Added recommendation to consider preterminated cabling to
reduce installation time and improve consistency and quality of terminations
Higher Densities Changed maximum 2.1 m (7 ft) maximum cabinet/rack height
from a requirement to a recommendation permitting use of taller cabinets and racks
Higher Densities - Cautions Added recommendation to consider needs for proper labeling, cable
routing, cable management, and ability to insert and remove cords without disrupting existing or adjacent connections when selecting patch panels.
BICSI-002 Data Center Design & Implementation Best Practices
Goes beyond what is provided in the cabling standards by TIA, CENELEC, and ISO/IEC Complements the national standard for telecom cabling by providing information on a wide
range of subjects not covered in the telecom standards and provide more information
BICSI Best Practices
(e.g., TDMM, BICSI-002)
Codes(e.g., NFPA 70
NEC)
Company Standards
National Standards
TIA for US & CanadaNational
StandardsCENELEC for
Europe
National StandardsISO/IEC for many other
Pages
114 Pages 503 Pages
BICSI-002 provides information on a wide range of subjects not covered in TIA-942
BICSI-002 mostly deals with aspects of data center design other than telecomBICSI-002 PagesElectrical 120
Telecommunications 84Security 44Mechanical 40Space Planning 32Maintenance 29Commissioning 28General 25Availability 23Site Selection 20Architectural 16Fire Protection 10DCIM & BAS 8Design Process 8Structural 4Outsourcing 4Multiple Data Centers 4Energy Efficiency 4
BICSI-009 Data Center Operations & Maintenance Best Practices
Companion standard to BICSI-002, but for data centers when they are in operation Another large and comprehensive standard, that also covers a wide range of subjects, but
instead related to operations and maintenance of data centers: Governance and Assessment – Compliance, Assessment Program
Operating Procedures
Security
Maintenance Procedures
Emergency Procedures
Management
EN 50600
Structure of the standard
Positioning of BICSI-002 and BICSI-009 relative to EN 50600 & ISO/IEC TS 22237
Edge Data Centers
Future Challenges Increasing consolidation of SAN and LAN traffic (higher traffic loads and
need for less delay) Higher Speeds 800G, 1TB (8 x OM5, 32 x OM4, multi-pair single-mode?) Edge data centers (computer rooms in new environments) Smart cities, IoT (Internet of Things), smart cars, streaming replacing TV,
and other applications increasing processing, storage, and bandwidth demands of the data center
IoT and single-pair cabling bringing more devices into the structured cabling of the data center
Questions?Jonathan JewPresident J&M Consultants, Inc.Website: www.j-and-m.comEmail: [email protected]
Secretary TIA TR-42Vice-Chair TIA TR-42.3 pathways & spacesCo-chair BICSI data center subcommitteeVice-chair USTAG to ISO/IEC JTC 1 SC 25 WG 3Editor ISO/IEC TR 14763-2-1 telecom admin identifiersSME BICSI TI&M Telecommunications Administration
Data Center Cabling Challenges Past, Present & FutureMy Past ….Data Center and Telecom Cabling StandardsIn the beginning … Large Proprietary Point-to-Point CablingIEEE 802 LAN StandardsTIA-568 Cabling StandardsTIA-606 Administration StandardImpact of Documentation, Labeling, & Equipment RefreshTIA-942 Telecom Infrastructure Standard for Data CentersPoint-to-point unstructured cablingSlide Number 12Structured cabling – faster deployment, easier to manage & troubleshootBuilding Automation SystemsGrounding & BondingLarger & Container Data CentersCURRENT CHALLENGESEnergy EfficiencyPhysical SecurityReplacement of traditional 3-tier network architecture with spine-leaf architectureHigher Speeds Need Multiple FibersFaster DeploymentHigher DensitiesHigher Densities - CautionsBICSI-002 Data Center Design & Implementation Best PracticesSlide Number 26BICSI-002 mostly deals with aspects of data center design other than telecomBICSI-009 Data Center Operations & Maintenance Best Practices Slide Number 29Positioning of BICSI-002 and BICSI-009 relative to EN 50600 & ISO/IEC TS 22237 Edge Data CentersFuture ChallengesQuestions?