Upload
phamphuc
View
238
Download
0
Embed Size (px)
Citation preview
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 1 of 17 Issue 2 20/10/2010
Contents
1 The eDIN DALI commissioning philosophy ............................................... 2
2 Requirements....................................................................................... 2
3 Notes .................................................................................................. 2
4 Pre-commissioning procedure ................................................................ 3
5 Creating an eDIN operational configuration.............................................. 5
6 Commissioning procedure...................................................................... 6
6.1 Finding ballasts .................................................................................... 6
6.2 Checking the search results ................................................................... 7
6.3 How to assign ballasts to eDIN channels.................................................. 8
6.4 How to test ballast assignment is correct ............................................... 11
6.5 How to re-assign ballasts that have been assigned incorrectly.................. 11
6.6 How to add more ballasts .................................................................... 12
6.7 How to replace a single ballast ............................................................. 13
6.8 How to replace multiple ballasts ........................................................... 13
6.9 How ballasts faults are detected/shown................................................. 14
7 Exporting and Importing DALI configuration........................................... 15
8 Advanced users who want to commission the system separately .............. 16
8.1 Importing DALI configuration into NPU once commissioning is complete .... 16
9 Document revision history ................................................................... 17
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 2 of 17 Issue 2 20/10/2010
1 The eDIN DALI commissioning philosophy
eDIN DALI commissioning using an eDIN NPU was designed to hide away the
complexities of the DALI protocol and to require no knowledge of the long
(random) address/short addresses that ballasts have to be allocated.
The eDIN NPU automates the process and hides the long/short addresses from
the user. For advanced users who want to commission the ballasts by some
other method, see section 8 which explains how to do this and tie it in with the
eDIN configuration.
The eDIN commissioning procedure uses an alternate method of allocating
ballasts to groups than that of many other systems. Instead of the time
consuming process of lighting a ballast and asking the user to search the building
to find it, the eDIN NPU approach is to allow the user to choose ballasts one at a
time and by answering a series of at most six ‘yes/no’ questions to identify and
commission the ballast.
The DALI protocol allows ballasts to be controlled in three ways: Individually, in
groups or all as one (broadcast). eDIN allows control in groups or broadcast only
Each DALI group is treated as an eDIN channel and can be controlled as per any
other eDIN output channel including it’s use in a virtually unlimited number of
scenes (Not just 16) and any fade time from 0 seconds to 24 hours (not just the
16 fixed DALI fade times where the maximum fade time is 90s).
2 Requirements
Before commissioning can commence, the following requirements must be met :
i) The ballasts have power.
ii) The DALI bus is connected between the UBC module and the ballasts.
iii) The eDIN NPU is connected via the M-Bus connection to the eDIN UBC
module.
iv) The eDIN modules are powered.
v) The eDIN NPU is connected via the Ethernet connection to a PC running a web
browser and that the NPU/PC are configured so that the eDIN web page is
accessible.
3 Notes
This document assumes that the eDIN NPU contains at minimum, software
version 1.2.0.13 and the eDIN UBC module contain at minimum, software version
1.20. Previous versions will look visibly different and have a reduced number of
features.
The use of the Firefox web browser (V3.5 or greater) is recommended. There are
some known issues when using certain versions of Internet Explorer.
For clarity in this document, the eDIN channels belonging to the UBC module
have not been named and remain as per the default ‘DALI:Group 1’ etc. If
required, they can be renamed as per any other channel belonging to an eDIN
module.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 3 of 17 Issue 2 20/10/2010
4 Pre-commissioning procedure
To be able to commission the DALI ballasts
using the eDIN NPU web application, there must
be an eDIN UBC module in the configuration and
the UBC module must be on the correct address
as defined in the configuration.
By default, when added to the configuration, the
UBC module will be split into two sections –
‘Inputs’ and ‘Outputs’.
The 4 configurable IOs of the module default to
contact inputs and are therefore shown in the
‘Inputs’ section.
The DALI universe (That controls the ballasts) is
shown in the ‘Outputs’ section.
To set up the DALI mode that the UBC module
is operating in and the number of DALI groups
required, click on the module in the
configuration page. A dialog box as per the
screenshot to the left will appear.
If control of the ballasts in groups is required,
the ‘groups’ radio button must be selected and
the tick box next to all required groups ticked.
The selection of required groups is a feature to
minimise the amount of room taken by the
ballast module in the configuration web page.
In the configuration page, each group is
represented by a row, so to reduce space, only
the groups selected in this dialog box are
shown. It does not matter if more groups are
selected than are actually needed.
If broadcast mode is all that is required (i.e. where all ballasts act as one)
commissioning is not required. In this case, the ‘Outputs’ section of the UBC
module will be shown with only one DALI channel in the configuration page (as
per the screenshot at the top of this page).
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 4 of 17 Issue 2 20/10/2010
To begin commissioning, click the
‘DALI management’ button on the
Monitor page (This button will
only be present if there is a UBC
module in the configuration)
A dialog as per the screenshot to the left will then
be shown which contains the number of groups as
previously selected.
To carry out commissioning, all ballasts must be
powered, as must the UBC module. The UBC
module must be connected to the NPU via the
M-Bus and be on the correct address as set in the
configuration. If the NPU cannot communicate with
the UBC module, an error message will be displayed
as show in the picture to the left.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 5 of 17 Issue 2 20/10/2010
5 Creating an eDIN operational configuration
Once a UBC module has been added to an eDIN configuration and the number of
eDIN channels (DALI groups) required have been selected, the operational
configuration (Adding scenes, setting dim levels, triggers etc.) can be modified
either before or after the DALI commissioning has been completed.
The operational configuration is separate from the DALI commissioning in that the
DALI channels belonging to the UBC module are treated as any other output
channel in the eDIN system. The difference is that they are linked to a DALI
group (Even if no ballasts have been commissioned and assigned to that group
yet.)
This means that the operational configuration can be written off-site if required
and the DALI ballasts commissioned and assigned to eDIN channels (DALI
Groups) later, once on-site.
The only thing to bear in mind is that the scenes/channel levels etc. cannot be
tested with the ballasts until the DALI commissioning has been completed.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 6 of 17 Issue 2 20/10/2010
6 Commissioning procedure
6.1 Finding ballasts
The first stage of the DALI commissioning
process is to find and identify all the ballasts
that are connected to the DALI bus.
Assuming that the NPU is as new and has not
been used previously to commission ballasts
and that section 4 has been completed, the
user will be presented with a web page as per
the picture on the left.
Only one button will exist in the
‘Commissioning tasks’ box, ‘Find all ballasts’.
Clicking this button starts a search procedure
which can take up to 15 minutes dependant
upon the number of ballasts on the bus
(Maximum of 64 as defined by the DALI
standard).
A warning box will then appear warning that
all existing data (held in the eDIN NPU) will be
lost. Click ‘OK’ and the search will begin.
As the ballasts are found they will appear in
the ‘new’ column. Assuming that the ballasts
have never been commissioned before, they
will appear in the unassigned row. If they
have been previously commissioned and
assigned a group (perhaps because they have
been previously used on a different system),
they will appear in one of the other rows. See
sections 6.6 and 6.7 for more information on
commissioning a system where ballasts have
been previously allocated to a group.
The ‘Commissioning tasks’ box at the bottom
will show the total number of ballasts found
so far.
If ‘Abort’ is pressed during the search, the
number of ballasts found so far will remain in
the ‘New’ column. To restart the search and
find all ballasts, click the ‘Wipe all ballasts and
re-find’ button that will now be present.
If the search is aborted and some ballasts have then been assigned groups as per
section 6.3. The remaining ballasts not found during the initial search can be
added as per section 6.6 (How to add more ballasts).
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 7 of 17 Issue 2 20/10/2010
Once the search is complete, the
‘Commissioning tasks’ box will show two
buttons, the first to assign the ballasts found
to eDIN channels (DALI groups). The second,
to remove all ballasts previously found from
the NPU’s memory and start the search again.
This does not remove any group allocation
that has previously been programmed into the
ballasts
6.2 Checking the search results
It is important at the end of the search to check that the number of ballasts found
is the total expected. If any ballasts are not communicating due to wiring faults
etc., they cannot be commissioned. Faults should be rectified before
commissioning commences.
To test which ballasts are working, the DALI test menu on the UBC module can be
used. From this menu, all ballasts can be turned on and off (using broadcast
mode) to help find faults.
This diagram shows only the DALI test sub menu,
for the full diagram refer to the UBV module
installation guide.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 8 of 17 Issue 2 20/10/2010
6.3 How to assign ballasts to eDIN channels
Each DALI group is treated as an individual eDIN channel which can be controlled
as per any other eDIN output channel.
eDIN can control up to 16 channels/groups, a DALI group can contain any
number of ballasts (Up to the maximum of 64 defined by the DALI standard). For
eDIN to be able to control the ballasts and recall scenes etc. the ballasts must be
assigned to an eDIN channel (DALI group).
Once the ballasts have been found (Section 6.1), click the ‘Assign the xx ballasts
found’ button to begin the assignment process.
The NPU will then assign addresses to the
ballasts so it can talk to them individually.
During this process, a dialog box will appear
as per the picture to the left. The number of
programming operations left will be shown
until complete.
The ballast locator dialog will then be
shown.
6.3.1 Choose a ballast to assign
As described in Section 1, the user must first choose a physical ballast to assign.
The ballast must be visible during the next steps.
6.3.2 Answer ‘Yes’ or ‘No’ dependant upon whether the ballast is lit at full brightness.
Throughout a series of yes/no questions (maximum 6 per ballast to be identified)
a selection of ballasts are lit. Each time, the user must answer whether the
ballasts selected in section 6.3.1 is lit at full brightness or not.
Note that some ballasts (particularly fluorescent ballasts) can take a little while to
respond to the DALI commands. The NPU has no way of knowing whether a
ballast has reacted or not it is therefore advisable to wait a few seconds at each
new yes/no question to allow the ballasts brightness levels to stabilise.
If at the end of the set of questions, the selected ballasts is not lit, it is possible
that the ballast has a fault which must be rectified before it can be commissioned.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 9 of 17 Issue 2 20/10/2010
To do this, the group allocation can be aborted so that the fault can be found as
per section 6.2. In that case, once the fault(s) is rectified the allocation can
continue by clicking the ‘Assign the xx unassigned ballasts’ button that will now
be present on the DALI commissioning page.
Otherwise clicking the ‘Ok’ button will instruct the NPU to ignore the missing
ballast for the time being and will allow you to proceed to the next ballast.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 10 of 17 Issue 2 20/10/2010
6.3.3 Allocate selected ballast to a group
Through the process of questions in section xx the NPU identifies the ballast
chosen by the user which should still be lit at full brightness.
The user is then presented with a dialog
box where the located ballast can be
allocated to one of the eDIN channels
(DALI Group).
Select the eDIN channel(DALI Group) to assign the ballast to and click the ‘OK’
button.
If for some reason you do not want to
allocate this ballast to an eDIN channel
(DALI Group), you can choose the ‘Skip’
option. This will leave the ballast with
its existing assignment and the ballast
locator dialog box will proceed to the
next ballast.
If there are more ballasts to assign, the user is returned to step 6.3.1 where the
next ballast is chosen. The process is repeated until all ballasts are assigned.
If at any point the ‘Abort’ button is pressed, the user will be taken back to the
DALI commissioning page but there will now be two assignment buttons, one to
‘Re-assign any of the xx already assigned ballasts’ and the second to ‘Assign the
xx unassigned ballasts’. The unassigned ballasts can then be allocated (or the
already assigned ballasts be re-assigned) by clicking the appropriate button and
assigning the ballasts as per section 0.
The system of answering a series of yes/no questions was designed to prevent
the commissioner having to search the building to find a particular ballast. If all
ballasts can be seen from the commissioning location, the process can be
speeded up by answering yes to all questions until the one remaining ballast is lit
at full brightness and then choosing the eDIN channel (DALI group) to assign it
to.
Once complete, the allocated ballasts will appear
in the ‘Ok’ column next to the eDIN
channel/group they have been assigned to.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 11 of 17 Issue 2 20/10/2010
6.4 How to test ballast assignment is correct
Once the ballasts are assigned to groups (Section 0). They can be tested to
ensure the group allocation is correct.
To the left of each row in the Module Summary box is a ‘ ‘ symbol. Clicking this
symbol sets all ballasts in that group to full brightness. The symbol then changes
to a ‘ ‘. Clicking the symbol again will set that group to dim and back to a ‘ ‘
symbol.
6.5 How to re-assign ballasts that have been assigned
incorrectly
If any ballasts needs to be re-assigned to a different eDIN channel (DALI Group),
the ‘Re-assign any of the xx assigned ballasts’ button can be used. The
procedure is as per section 0 except that the ballast(s) selected is the one that is
to be-reassigned.
When there are no more ballasts to be re-assigned, the ‘ABORT’ button can be
used to return to the main DALI management page.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 12 of 17 Issue 2 20/10/2010
6.6 How to add more ballasts
If more ballasts are added to the bus, the ‘Check for added or removed ballasts’
button can be used, this will search the bus for ballasts unknown to the NPU (As
per section 6.1) and add them to the unassigned row of the Module summary in
the New column, unless they have been previously programmed/used in which
case they will show up in the row corresponding to their previous group
assignment.
If the new ballast(s) appear in the unassigned
row, they will have a ‘+’ symbol next to the
number of ballasts found.
Clicking the ‘+’ symbol adds the ballast(s) into
the DALI configuration as ‘Unassigned’ so they
can be assigned to an eDIN channel (DALI
group) as per Section 0
If the new ballast(s) appear in any other row,
they will still have the ‘+’ symbol which will add
them to the DALI configuration as unassigned.
They will also have a ‘ ’ symbol, clicking this
will automatically assign the ballasts to the
eDIN channel/group according to the row that
they are displayed in.
The new ballasts must be added to the DALI configuration (ie. appear in the OK
column) before they can be allocated to an eDIN channel (DALI group).
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 13 of 17 Issue 2 20/10/2010
6.7 How to replace a single ballast
Once a ballast has been replaced, click the
‘Check for added or removed ballasts’ button.
As per the screenshot to the left, the removed
ballast will appear in the ‘Lost’ column as the
eDIN NPU can no longer communicate with it
and the new ballast will appear in the ‘New’
column.
Click the ‘ ’ symbol next to the ‘Lost’ ballast
to remove it from the configuration. Then
click the ‘+’ symbol next to ‘New’ ballast and
assign it to the correct eDIN channel (DALI
group) as per Section 6.3.
As per Section 6.6, if the new ballast has already been assigned a group by an
external DALI commissioning tool, the new ballast will appear in one of the
assigned rows and will have a ‘ ’ symbol in addition to the ‘+’ symbol. Clicking
the ‘ ’ symbol will automatically add it to the NPU configuration in it’s pre-
programmed group. Clicking the ‘+’ symbol will add it the configuration as
unassigned so that it can be allocated a group later.
6.8 How to replace multiple ballasts
The replacement of multiple ballasts is the same as that of single ballasts (Section
6.7) except that multiple ballasts will appear in the ‘Lost’ and ‘New’ columns.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 14 of 17 Issue 2 20/10/2010
6.9 How ballasts faults are detected/shown
DALI ballasts faults are shown in the main
‘Monitor’ page, not in the DALI management
page.
Faults are only shown per group. Individual
ballasts faults are not shown in eDIN, only
that one of the ballasts in that group has a
problem. The group(s) with the fault is
indicated in yellow in the web page.
A ballast that has a lamp fault (detected and
reported by the ballast) are shown with a ‘ ’
icon next to the group name as per the first
screenshot on this page.
A ballast that will not communicate with the
UBC module will be shown with a ‘ ’ symbol
next to the group name as per the second
screenshot.
Note that the existence of faults will only be updated when the faulty ballast is set
to a dim level (ie. not 0%). Most ballasts cannot detect and therefore report a
fault when the lamp is off. Equally it cannot be determined if the fault has been
corrected when the lamp is off.
The monitor page will not continuously update, to see the latest status, the web
page must be refreshed.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 15 of 17 Issue 2 20/10/2010
7 Exporting and Importing DALI configuration
The NPU has the ability to export/import the DALI configuration (ie. ballast
addresses and group allocation) to a file that can be stored and retrieved. This is
not required in normal use as the NPU retains this data, even during power cuts.
This feature is useful if an NPU ever needs replacing as the DALI commissioning
data can then be imported into the new NPU without re-commissioning.
Note that this DALI configuration is only of any use to the specific set of ballasts
used for commissioning as it contains data specific to those ballasts.
The export/import function is found in the DALI management page toolbar as
shown in the screenshot below.
In addition to exporting the DALI configuration as a .bin (binary) file that the
eDIN NPU can import later, the configuration can be exported as a CSV file which
can be viewed in an application such as Microsoft Excel.
The CSV file contains the following data :
The UBC module’s M-Bus address.
The name of the eDIN channels within the UBC module.
The long (random) address, short address and group number of each ballast
known to the UBC module.
DALI Commissioning Guide (Using a NPU)
Mode Lighting (UK) Ltd. 2010 Page 16 of 17 Issue 2 20/10/2010
8 Advanced users who want to commission the
system separately
As described in section 5, the operational configuration and the DALI
commissioning are not explicitly linked. Therefore if required, the DALI
commissioning can be carried out using external DALI commissioning tools.
If DALI fault reporting is not required, the eDIN NPU does not care what the long
(random)/short address of the ballasts are, only what group they are in as the
group is linked to an eDIN channel in the UBC module.
Therefore if commissioning externally, the group allocation of the ballasts must
match the eDIN channels as defined in the NPU’s operational configuration (i.e.
eDIN UBC Module Channel 5 = DALI Group 1, eDIN UBC Module Channel 6 =
DALI Group 2 etc.)
Note that the eDIN UBC module’s channels start from number 5 because channels
1-4 are the configurable channels of the module.
This means that as per section 4, there must be as many eDIN channels (DALI
groups) in the UBC module configuration as DALI groups that are going to be
externally allocated.
8.1 Importing DALI configuration into NPU once commissioning is complete
If the DALI commissioning has been carried out externally and fault reporting is
required, the externally commissioned ballast data can be read by NPU to enable
this.
As per section 6.1, carry out a search of the bus. The pre-commissioned ballasts
will appear in the ‘New’ column in whichever row they have been externally
allocated to.
Once the search is complete, simply click
the ‘ ’ symbol next to each number of
ballasts appearing in the ‘New’ column to
add them to the eDIN NPU DALI
configuration.
Once in the NPU’s DALI configuration, they will be periodically queried for lamp
faults etc. and any faults will be reported on the monitor page as per section 6.9.