10

Cyclic Loading Test s on Composite Joints with Flush End ...C).pdf · Cyclic Loading Tests on Composite Joints with Flush End Plate Connections 123 6. Test Phenomenon 6.1. Specimen

  • Upload
    others

  • View
    22

  • Download
    0

Embed Size (px)

Citation preview

  • Steel Structures 7 (2007) 119-128 www.kssc.or.kr

    Cyclic Loading Tests on Composite Joints

    with Flush End Plate Connections

    SHI Wen-long1*, LI Guo-qiang2, YE Zhi-ming1 and R. Y. Xiao3

    1Department of Civil Engineering, Shanghai University, Shanghai, 200072, China2Department of Structure Engineering, Tongji University, Shanghai, 200092, China

    3Department of Civil Engineering, University of Wales Swansea, UK

    Abstract

    The tests on composite joint specimens with flush end plate connections subjected to cyclic loads have been conducted inTongji University. One bare steel joint specimen has also been tested for comparison. Various instrumentations have been usedto measure: beam strains, column strains, rebar strains, connection deformations and deflections of specimens. The testobservations are reported in detail in this paper. The main results are as follows: (1) the moment-rotation relationships of theconnections are obtained from the tests, which demonstrate that the hysteretic loops are stable and show good energy dissipationability; (2) the composite joint specimens show large strength resistance and good ductility, and all the rotations of connectionare greater than 0.03rad as required by the FEMA-97; (3) similar failure modes have been identified from the observation ofthe composite specimens, which are found to be concentrated around the joint zone; and (4) the slippage between the concreteslab and steel beam is very small, which shows that between the concrete slab and steel beam the full composition can beobtained by the proper design for the shear connectors.

    Keywords: Flush endplate, Composite joint, Low cyclic loading, Joint behavior, Moment-rotational relationship

    1. Introduction

    It has been convenient to assume full rigid or pinned

    connections to simplify analysis for steel frame design.

    However, for the sake of cost and construction, a great

    number of connections have been designed as semi-rigid

    ones. Composite slab and semi-rigid connection constitute

    a new type of semi-rigid composite connection. Composite

    action of connection is achieved through longitudinal

    reinforcement and headed shear studs. A great deal of

    experiments and earthquake calamities have shown that

    semi-rigid composite connections have excellent mechanical

    and aseismic performance. In practical engineering, the

    using of semi-rigid composite connections can reduce

    steel consumption and expedite construction. In the last

    twenty years, a lot of tests (Silva and Simoes, 2001; Sun

    and Li, 2004; Laszlo Dunai, 2004; B. M. Broderick and

    A. W. Thomson, 2005) and theoretical studies on the bare

    steel and composite joints were carried out (Tsuji Bunzo,

    2001; Changbin Joh and Wai-Fah, 2001; Rene Maquoi

    and Jean-Pierre Jaspart, 2002). The previous experimental

    research on composite connections was carried out under

    symmetrical and monotonic loading (Xiao and Nethercot,

    1994; Anderson and Najafi, 1994). There has been

    limited research work conducted on composite joints

    under non-symmetrical loading and cyclic loading to

    quantify the hysteretic characteristics and the effects of

    unbalanced connection moments on the joint. In China,

    some semi-rigid bare steel and composite joints (Guo,

    2003; Yang, 2004; Gao, 2002), bare steel (Guan, 2003)

    and composite frames (Wang, 2005) with semi-rigid

    connections have been tested under static loads, cyclic

    loads (Guo, 2002) and fire (Lou, 2005) since 1992.

    In this paper, one bare steel joint and two composite

    joints were tested under cyclic loading. Special attention

    has been paid to: (1) stiffness, moment resistance, rotational

    capacity of composite joints; (2) hysteretic behavior of

    composite joints; (3) effect of stiffeners on behavior of

    joints; (4) moment-rotation relationship of composite

    joins and damage mode; (4) difference of performance

    between the bare steel and composite joints.

    2. Configurations of Specimens

    Under the action of lateral loading, typical moment-

    resisting frame structures may be simplified for analysis

    purposes into a series of two-dimensional sub-frames

    with interior joints as shown in Fig. 1, where the moment

    inflection points are assumed at the middle of beam spans

    and column heights, allowing sub assemblages with interior

    joints to be isolated for evaluating their performances.

    *Corresponding authorTel: +86-21-65985318; Fax: +86-21-65983431E-mail: [email protected]

  • 120 SHI Wen-long et al.

    2.1. Specimens description

    One bare steel joint and two composite joint specimens

    denoted as SJ1 and CJ3, CJ4, respectively, were tested.

    Two beams H300 × 150 × 6 × 10 of 1.6 m long were

    connected to a column H200 × 200 × 8 × 12 to form a

    cruciform specimen as shown in Fig. 2. The beams were

    connected to the column flanges by means of 10 mm

    thick end plate and M20 Grade 10.9 bolts, as shown in

    Fig. 2b. All standard steel members and end plates are

    made of Q345 steel. A common form of metal decking

    floor system, which comprises a concrete slab supported

    by profiled metal decking sitting on steel beams, was

    adopted for all composite specimens. The beam-to-slab

    connections are connected by welded-through shear

    connectors. Longitudinal reinforcement bars pass across

    the column line continuously. The longitudinal reinforcement

    consisted of Φ10@120 bars, while the transverse reinforcement

    consisted of Φ6@200 bars. The reinforcement ratio is

    0.8%, which is defined as the reinforcement area divided

    by the concrete area above the ribs of the metal sheeting.

    The common used 0.8 mm thick profiled steel sheeting

    DP688 was chosen as bottom shuttering for the specimens.

    The profiled steel sheeting was filled with cast-in-place

    normal weight concrete with design strength of 30 N/

    mm2. The composite slabs were 1,200 mm wide and

    140 mm thick. Spaces between column flanges at the slab

    level were solidly cast with concrete. CJ3 was similar to

    CJ4 except that the panel zone was stiffened with

    transverse plate welded to the column web.

    2.2. Specimen design and fabrication

    All specimens were fabricated in the Structural

    Laboratory at the Tongji University. The bare steel

    components were firstly assembled in situ. The profiled

    metal decking was then placed on the steel beams and

    shear studs were installed by welding. After the joint

    Figure 1. Location of specimen.

    Figure 2. Specimen of composite joint.

  • Cyclic Loading Tests on Composite Joints with Flush End Plate Connections 121

    assembly, formwork was set up with the metal decking as

    bottom shuttering, plywood as side shuttering. Concrete

    casting work was then carried out. The casting of cubes

    and cylinders for material tests was done at the same

    time. The cube and cylinder samples and the slab were

    cured under the same conditions.

    3. Instrument Arrangement

    Strains in the reinforcement and on the steel beam and

    column were measured using strain gauges. The

    arrangement of strain gauges is shown in Fig. 3. After

    assembly of the test specimens, all the instruments were

    mounted on the specimens. Inclinometers were used to

    measure the rotation of the column and the relative

    rotation of the beam so as to provide full information

    from which the moment-rotation relationship could be

    derived. The arrangement of inclinometers is shown in

    Fig. 4. Displacement transducers were used to measure

    the deflection of the specimens on the bottom flange of

    the beam and also to monitor slippage between steel

    beam and slab. The relative rotation of the beam to

    column can also be obtained from the deflection values

    within the calibrated horizontal length of the beam. The

    arrangement of LVDT is shown in Fig. 5.

    4. Loading Procedure

    The experimental set-up included a supporting frame

    and a loading system is shown in Fig. 6 and Fig. 7. The

    lateral loading was applied to the specimen at the top of

    the supporting frame by a computer-controlled hydraulic

    actuator with a maximum load capacity of ±1000 kN and

    available stroke of ±200 mm. The specimens were loaded

    until failure or when the maximum stroke of the actuator

    was reached.

    Figure 3. Arrangement of strain gauges.

    Figure 4. Arrangement of inclinometers.

    Figure 5. Arrangement of LVDT.

    Figure 6. Test set-up.

    Figure 7. Photo of test set-up.

  • 122 SHI Wen-long et al.

    5. Material Tests

    5.1. Steel coupons

    Material for tensile test coupons was cut from the

    flanges and webs of the steel beams and columns. Values

    of yield strength and ultimate strength for steel members

    are listed in Table 1.

    5.2. Reinforcement bars

    Test specimens were cut from the 6 mm and 10 mm

    diameter rebars. The test results are listed in Table 2.

    5.3. Concrete

    Concrete work was carried out inside the laboratory

    with the specimen in the test position. Samples of

    concrete to be used for monitoring the concrete strength

    were cast at the same time to cast for composite joint

    specimens. The compressive and tensile strengths of all

    the samples are summarized in Table 3.

    Table 1. Measured tensile strengths of steel

    No.Yield strength

    (N/mm2)Tensile strength

    (N/mm2)Yield strain

    (%)Elastic modulus(×105 N/mm2)

    Extensibility(%)

    BW-1 383.9 564.5 0.195 1.97 28.40

    BW-2 387.4 559.9 0.190 2.04 32.54

    BW-3 401.1 563.5 0.196 2.05 35.46

    BF-1 435.8 509.3 0.206 2.12 29.88

    BF-2 402.2 495.4 0.199 2.02 29.78

    BF-3 431.9 509.2 0.196 2.20 31.19

    EP-1 391.9 498.4 0.190 2.06 29.93

    EP-2 436.2 507.6 0.209 2.09 29.89

    EP-3 428.1 502.9 0.193 2.22 31.34

    CW-1 406.3 505.9 0.189 2.15 30.54

    CW-2 405.6 489.9 0.167 2.43 31.79

    CW-3 397.7 480.5 0.214 1.86 33.40

    CF-1 417.0 500.5 0.216 1.93 30.33

    CF-2 414.5 497.7 0.192 2.16 30.58

    CF-3 397.6 496.9 0.192 2.07 30.26

    Average 0409.15 0512.14 0.200 2.09 31.02

    Table 2. Measured tensile strengths of rebar

    No. Diameter/mmYield strength

    (N/mm2)Tensile strength

    (N/mm2)Yield strain

    (%)Elastic modular(×105 N/mm2)

    Extensibility(%)

    GJ1-1 6.77 296.97 436.1 0.140 2.12 28.28

    GJ1-2 6.59 318.50 443.3 0.157 2.03 30.88

    GJ1-3 6.64 310.31 436.1 0.165 1.87 29.98

    Average 6.67 308.59 0438.50 0.154 2.01 29.71

    GJ2-1 9.92 462.70 607.7 0.248 2.02 33.02

    GJ2-2 10.160 433.50 575.2 0.236 1.85 31.94

    GJ2-3 10.070 444.10 581.6 0.248 1.90 29.54

    Average 10.050 446.77 0588.17 0.244 1.92 31.50

    Table 3. Measured strengths of concrete

    No. Size of samples (mm) Cube strength (N/mm2) Average

    H1-1 150×150×150 40.89

    41.48H1-2 150×150×150 40.89

    H1-3 150×150×150 42.67

    No. Size of samples (mm) Elastic modular (N/mm2) Average

    H2-1 100×100×300 40000

    41429H2-2 100×100×300 40000

    H2-3 100×100×300 42857

  • Cyclic Loading Tests on Composite Joints with Flush End Plate Connections 123

    6. Test Phenomenon

    6.1. Specimen SJ1

    SJ1 is a bare steel joint specimen used as a benchmark

    for comparison with other composite joint specimens. A

    gap between end plate and column flange was observed

    when the displacement of top of column reached ±25 mm

    (Fig. 8a). The obvious shearing deformation was observed

    in the panel zone when the displacement reached ±60 mm

    (Fig. 8b). The specimen was loaded until the maximum

    stroke of the actuator was reached. No local buckling was

    observed on the steel components and the lateral load was

    keeping on going up.

    6.2. Specimen CJ3

    The first cracking was observed on the right slab when

    the displacement of the top of column reached 25 mm.

    The crack started from the tip of column flange and

    extended towards the edge. The lateral load was then

    unloaded to zero and the cracks on right slab closed

    completely. A reversed loading was then applied, and the

    first cracking was also observed on the left slab. With the

    increasing in loads, the appeared cracks extended and

    widened gradually (Fig. 9a). When the displacement

    reached 80 mm, a wide gap between slab and column

    flange (Fig. 9b) was observed. When the displacement

    reached 120mm, the state of composite slab vicinity to

    the column is shown in Fig. 9b and Fig. 9c. It is noted

    that the slab around the column is badly damaged. A

    large shear distortion was observed in the column panel

    zone (Fig. 9d). When the displacement reached 160 mm,

    the debonding of the concrete from the metal decking and

    the inclined cracks starting from the ribs are visible, as

    illustrated in Fig. 9e. The former was due to the flexural

    deflection of the beam, while the latter was caused by the

    shear and bending action in the slab. When the

    displacement reached 200 mm, the damage of concrete

    slab continued and the crushed concrete was dropped off

    from the gap between the slab and column flange. A wide

    gap was observed between end plate and column flange

    Figure 8. Test photo of SJ1.

    Figure 9. Test photos of CJ3.

  • 124 SHI Wen-long et al.

    (Fig. 9f). After the test, the concrete slab vicinity to the

    column was cut and examined. It was found that the

    concrete at the back of column flange was completely

    crushed.

    6.3. Specimen CJ4

    The first cracking was observed on the right slab when

    the displacement of the top of column reached 25 mm in

    pull way. The lateral load was then unloaded to zero and

    the cracks on right slab closed completely. A reversed

    loading was then applied, and the first cracking was also

    observed on the left slab. With the increasing in loads, the

    appeared cracks were extended and widened gradually.

    When the displacement reached 80 mm, a wide gap

    between slab and column flange (Fig. 10a) was observed.

    The debonding of the concrete from the metal decking

    was visible (Fig. 10b). After the test, the cracks of

    concrete slab are shown in Fig. 10d. The concrete slab

    vicinity to the column was cut and examined. It was

    found that the concrete at the back of column flange was

    completely crushed (Fig. 10f).

    7. Test Results and Analysis

    In this section, the experimental results of all specimens

    under cyclic reversal loading will be described. For

    convenience of comparison, the values of the main

    parameters, such as cracking moment, yield moment and

    corresponding rotation, initial rotational stiffness, damage

    modes are listed in Table 4.

    7.1. Hysteretic curves of lateral load and corresponding

    displacement

    The hysteretic curves of lateral load and its displacement

    Figure 10. Test photos of CJ4.

    Table 4. Experimental results

    No. Type of joint Mcr (kN · m) My+ (kN · m) My

    − (kN · m) Pu (kN)

    SJ1 bare joint / 44.91 -44.91 /

    CJ3 composite joint 41.10 78.97 -102.160 64.83

    CJ4 composite joint 38.09 82.83 -98.81 60.06

    No. Ki+ ( kN · m/mrad) Ki

    − ( kN · m/mrad) θy+ (mrad) θy

    − ( mrad) Damage modes

    SJ1 06.93 0-6.93 42.11 -42.11 Not damaged

    CJ3 14.63 -19.51 12.02 -14.69 A, C, E

    CJ4 14.88 -17.72 11.25 -13.62 A, C, E

    Note: (1) Mcr: cracking moment; (2) My+, θy

    +: positive yield moment and corresponding rotation; (3) My−, θy

    −: positive yield momentand corresponding rotation; (4) Pu: the maximum lateral force; (5) Ki

    +: positive initial rotational stiffness; (6) Ki−: negative initial

    rotational stiffness; (7) In the ‘Damage modes’ column: A = reinforcement yielding; B = end plate yielding; C = yielding in shearpanel zone; D = bolt yielding or fracture; E = concrete cracking; F = welding fracture in column web; G = yielding in beam flange.

  • Cyclic Loading Tests on Composite Joints with Flush End Plate Connections 125

    at the top of column (P-∆) are shown in Fig. 11. It can be

    seen that the P-∆ hysteretic curves are symmetrical about

    centerline of column cross section because of the

    symmetry of specimens about centerline of column cross

    section. For specimens CJ3 and CJ4, the maximum lateral

    force ratio between push and pull is 0.93 and 1.06

    respectively.

    7.2. Hysteretic curves of moment-rotation of the

    connections

    The hysteretic curves of moment-rotation for left and

    right connections are shown in Fig. 12. It can be seen that

    the hysteretic loops are stable and ductile and show good

    energy dissipation capacity. The hysteretic curves for left

    and right connections are nearly same because of

    symmetry of left and right connections. For the specimen

    SJ1, the maximum moment is corresponding to the

    maximum rotation under positive and negative moment.

    It indicated that no strength degradation was achieved for

    the specimen SJ1.

    The curves for left and right connections are in good

    agreement because of the symmetrical construction

    details. For the specimens CJ3 and CJ4, pinching, indicated

    by the reduction of stiffness, is noted. In composite joints,

    pinching is mainly caused by the opening and closure of

    the cracks in the concrete slab. The slippage between

    steel components and the slippage between the composite

    slab and steel beam also contribute to the pinching effect.

    For the specimens CJ3 and CJ4, the maximum moment is

    not corresponding to the maximum rotation under positive

    and negative moment respectively. This phenomenon

    indicated that strength degradation was achieved for the

    specimens CJ3 and CJ4. In addition, the hysteretic curves

    of moment-rotation for specimens CJ3 and CJ4 are the

    nearly same as that of specimen SJ1 after these two

    composite joint specimens reached their maximum lateral

    force. It indicated that the performance of composite

    joints is in agreement with that of bare steel joint because

    of losing composite action of concrete slab.

    Figure 11. Hysteretic curves of P-∆.

    Figure 12. Moment-rotation curve of the connections.

    Figure 13. Shear force-rotation curve in the column panel zone.

  • 126 SHI Wen-long et al.

    7.3. Hysteretic curves of shear force and corresponding

    rotation

    Under a lateral loading, the connection on one side was

    subjected to a hogging moment, while the connection on

    the other side was subjected to a sagging moment. In

    consequence, the column panel zone bore a large shear

    distortion. The hysteretic curves of shear force and

    corresponding rotation in the column panel zone for all

    three specimens are shown in Fig. 13.

    7.4. Energy dissipation

    The energy dissipation capacity is the factor of utmost

    importance when evaluating the performance of a structure

    subjected to seismic attacks. Its value is generally

    deformation-dependent and serves as an indication of

    dissipation energy for the structure through the inelastic

    range. The dissipated energy Ji in the ith loading cycle is

    defined as the area encircled by the restoring force-

    deformation curve. The energy per cycle may be further

    separated into two parts, Ji+ for positive loading and Ji

    for negative loading. Since the asymmetrical characteristics

    of a composite connection under sagging and hogging

    actions, the moment-rotation response is thus non-

    symmetrical. This may lead different values of dissipated

    energy for positive and negative loading semi-cycles.

    The energy dissipation of all three specimens is shown

    in Fig. 14. It can be seen that in the first eight cycles, the

    energy dissipation is very small. This indicates that the

    specimens are in elastic state. After the eighth cycle, the

    energy dissipation of specimens keeps on going up with

    the increasing in cycles.

    7.5. Skeleton curves

    The skeleton curves of P-∆ are shown in Fig. 15. It can

    be seen that the composite joint specimens have larger

    strength resistance and stiffness than the bare steel joint

    specimen does owing to the presence of reinforcement

    bars and concrete slab. The composite joint specimens

    show the nearly same performance as the bare steel joint

    does after reaching maximum lateral force.

    7.6. Strain of beams

    The strain of left steel beam of specimens SJ1 and CJ4

    is shown in Fig. 16. For the specimen SJ1, No. 2 and No.

    6 strain gauge readings are much higher than the other

    strain gauges’. The maximum data obtained from No. 2

    strain gauge is nearly 1000 µε, while that of No. 6 strain

    gauge is nearly 2000 µε. The readings of No. 1 and No.

    7 strain gauge located on the beam flanges are very small.

    Figure 14. Cumulative energy dissipation of specimen.

    Figure 15. Skeleton curves of P-∆.

    Figure 16. Strain of left beam of specimen SJ1 and CJ4.

  • Cyclic Loading Tests on Composite Joints with Flush End Plate Connections 127

    From the data obtained from these strain gauges, the

    follow conclusions can be drawn: (1) For the flush end

    plate connection, the strain of beam flanges is very small

    because of lack of restriction, especially for the bare steel

    joint; (2) The strain of beam web in level of bolts is large

    because of strong restriction of bolts; (3) There is a gap

    between end plate and column flange because of

    pretension of bolts. Thus, the beam flanges begin to bear

    load after these gaps disappear when loading. (4) The

    steel beam of specimen SJ1 is yielding while the steel

    beam of specimen CJ4 is still elastic.

    7.7. Slippage between steel beam and concrete slab

    The slip between steel beam and concrete slab versus

    displacement of the top of column is shown in Fig. 17. It

    can be seen that the readings of LVDT7 and LVDT8 keep

    on going up with the increasing in the lateral displacement.

    There is no obvious difference in readings between

    LVDT7 and LVDT8 during the whole test. For the

    specimen CJ3, the maximum readings of LVDT7 and

    LVDT8 are 0.22 mm and 0.275 mm respectively. The

    reading ratio is 0.8. The slippage strain is 159 µε, which

    is defined as the difference in reading of LVDT7 and

    LVDT8 divided by the spacing between this two LVDT.

    For specimen CJ4, the maximum readings of LVDT7 and

    LVDT8 are 0.165 mm and 0.146 mm respectively. The

    reading ratio is 1.13, while the slippage strain is 55 µε.

    8. Conclusions

    Through the experimental studies, the concluding remarks

    may be summarized as:

    (1) The composite joints with flush end plate connection

    have good moment resistance and rotational capacity

    under cyclic loading. The ultimate rotations of all three

    specimens are beyond 0.03rad, as required by the FEMA-

    97 for earthquake-resistance.

    (2) The cyclic test results indicated that the hysteretic

    loops of the connection moment-rotation curves are stable

    and plummy, even though pinching in large inelastic

    ranges was observed.

    (3) The presence of the column web stiffener can increase

    the moment capacity and initial rotational stiffness of the

    connection, but not very much.

    (4) Failures of composite joints are observed to be

    concentrated in the nodal zone.

    (5) By a proper full shear design, the slippage between

    slab and steel beam is so small that these two components

    can be assumed to work well together.

    Acknowledgment

    The studies presented in this paper are sponsored by the

    Natural Science Foundation of China through the

    Outstanding Youth Project (No. 50225825). The financial

    support from NSFC is especially acknowledged.

    References

    Anderson, D. and Najafi, A. A. (1994). “Performance of

    composite connections: major axis end plate joints”, J.

    Constr. Steel Res., 31, 31-57.

    B. M. Broderick and A. W. Thomson, Moment-Rotation

    Response of Flush End-Plate Joints Under Cyclic

    Loading, International Journal of Steel Strucutures, Vol.

    5(5), 441-451.

    Changbin Joh and Wai-Fah (2001), Seismic Behavior of

    Steel Moment Connections with Composite Slab,

    International Journal of Steel Strucutures, Vol. 1(3), 175-

    183.

    Chen yu, Dong shimim, Li liping (1995), “Introduction to

    pseudo dynamic test method in the code of aseismic test

    on building structures”, Building Science, Vol. 2, pp. 52-

    57.

    Gao huajie (2002), Experimental study on the semi-rigid

    composite joints with seating cleat connection, Master

    Thesis.

    Guan kejian (2003), Experimental study and non-linear

    analysis on the steel frame buildings, PHD Thesis.

    Guo Bing (2002), Collapse Mechanism and Design

    Criterion of Steel Beam-to-column Extended End-plate

    Connections under Cyclic Load, PHD Thesis.

    Guo Yiqing (2003), Experimental Study of Semi-rigid End-

    plate Composite Joints, Master Thesis.

    Laszlo Dunai (2004), Experimental and Numerical Studies

    on the Cyclic Behavior of Steel and Composite Joints,

    International Journal of Steel Strucutures, Vol. 4(4), 197-

    208.

    Figure 17. Slippage between slab and beam.

  • 128 SHI Wen-long et al.

    L.Simoes da Silva, Rui D. Simoes, Paulo J.S. Cruz (2001),

    “Experimental behavior of end-plate beam-to-column

    composite joints under monotonical loading”, Engineering

    Structures, 1383-1409.

    Lou Guobiao (2005), Behavior and Design of Extended

    Endplate Moment Connections with High-strength Bolts

    in Fire, PHD Thesis.

    Rene Maquoi and Jean-Pierre Jaspart (2002), A Simple

    Approach for the Design of Steel and Composite Frames

    accounting for Effective Overall Stability, International

    Journal of Steel Strucutures, Vol. 2(1), 1-11.

    Shi Wenlong, Theoretical and Experimental Research on

    Composite Joint with Flush Endplate Connections, PHD

    Thesis.

    Sun Feifei, Li Guoqiang, Hu Linghua (2004), “New

    Development in Experimental Research on Beam-to-

    column Composite Joints”, Progress in Steel Building

    Structures, Vol. 6, No. 2, pp. 37-42.

    Tian shizhu, Zhao tong (2001), “Research on pseudo

    dynamic test”, World information on earthquake

    engineering, Vol. 17(4), 60-66.

    Tsuji Bunzo (2001), Ultimate Strength and Collapse

    Mechanism of Steel Concrete Composite Moment

    Frames under Seismic Loading, International Journal of

    Steel Strucutures, Vol. 1(2), 91-94.

    Wang Jingfeng (2005), the Practical Design Approach of

    Semi-rigidly Connected Composite Frames under

    Vertical Loads, PHD Thesis.

    Wang rui, Zai houqin, Wang yuda (2001), “an experimental

    study on pseudo dynamic testing technique of structures”,

    Jiangshu Building, 18-22.

    Xiao, Y., Choo, B. S. and Nethercot, D. A. (1994),

    “Composite Connections in Steel and Concrete. Part 1-

    Experimental behavior of composite beam-column

    connections”, Journal of Constructional Steel Research,

    Volume 31, Pages 3-30.

    Yang Li (2004), Behaviors Study on Semi-rigid Composite

    Joints under Low Cyclic Loading, Master Thesis.

    Yao zhengang, Liu zhuhua (1996), Test on Building

    Structures, Tongji University Press, Shanghai.

    Zhu bolong (1989), Aseismic Test on Structures, Bei Jing,

    Earthquake Press of China.