Upload
danielalejandroramosquero
View
217
Download
2
Embed Size (px)
DESCRIPTION
Distance Relaying (Documento)
Citation preview
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:09 No:09 20
1917091-IJECS-IJENS © October 2009 IJENS I J E N S
CT Compensation of Numerical Distance Relaying
Algorithm
Abdullah Assuhaimi Mohd Zin , Nur ‘Ain Maiza Ismail , Zaniah Muda and Mohamad Jalalian 1,2,3,4
Faculty of Electrical Engineering Universiti Teknologi Malaysia from Johor, Malaysia [email protected],
Abstract— In this paper a prototype algorithm for Numerical
Distance relay is developed in order to pre vent mal -operation
of relays when Current Transformer (CT) saturation occurs.
Saturation of CT causes errors in reproduction of the current
fundamental harmonic. The design of CT(s), which never saturate would end in bulky and expensive units. Therefore
most of the protective CTs that are in service saturate during
severe transients. Distorted secondary current due to CT
saturation is detected and compensated by the algorithm in
order to obtain correct operation of Distance relay in saturation area. Third-difference function and Auto Regressive
(AR) model are employed in developing the saturation
detection and compensation algorithm. The algorithm is
developed using C++ language. Then the performance of the
algorithm is evaluated through simulation of case studies in Alternative Transient Program (ATP) simulator. Finally, the
Numerical Distance Relaying algorithm with CT saturation
compensation is successfully developed.
Index Term-- Numerical Distance Relay; CT saturation; CT
compensation; ATP
I. INTRODUCTION
Numerical t ransmission line d istance protection systems
have been widely applied in recent years. This is due to their
monitoring and communications capabilities as a protection
system. Typically, t ripping t imes for d igital d istance relays
range from one to three cycles. Meanwhile, relays using
analogue signal processing techniques offer tripping times of one-quarter to one cycle [1]. Recent developments in
combination of adaptive algorithms and higher sampling rates have lead to the development of secured high-speed
protection, which is not availab le in prev ious distance protection systems [1, 2, 3]. Improvement of the distance
protection system is made both in the area o f phasor calculation and the p rotective algorithm implementation [1].
Improvements are made due to the protective relays demand on a reasonable accurate replica of the primary current and
voltage especially during fau lt event. Therefore, for this
reason current transformer (CT) is employed in the distance protection system in order to perform primary current
reduction for the relays usage [2, 3].However, relay performance is affected by CT installat ion. Rat io error
becomes severe during CT saturation condition which leads to mal-operation of protective relay. The conventional way
employed by earlier researchers is by over dimensioning the
core of CT. It is said that the CTs can carry up to 20 times the rated current without exceeding 10% of rat io correction
[3]. On the other hand, the large cross-section area of CT creates space and economic problems as it results in bulky
CTs.
As mention previously, the mal-operation of protection relay
is caused by ratio error which occurs due to the CT
saturation condition. Therefore, the mal-operation of
distance protection relay can be avoided by preventing the
saturation of CT. This can be achieved by constructing
compromise algorithms for the distance protection system,
[4, 5].Th is paper describes a design of suitable CT
Compensation algorithm for Distance Relay, which is used
to overcome the saturation effects and prevents the mal-
operation of a Distance Relay. The design algorithms will
include current compensation, anti-aliasing filter, dc-
removal and digital filter. Besides that, this paper describes
the simulation test conducted using ATP power simulator in
order to evaluate the proposed designed algorithm
performance under various faults conditions.
II. METHODOLOGY
The proposed algorithms start with the process of voltage
and current sampling. After sampling process, inflection
points are detected by saturation detector. If saturation level
is sensed to be more than the threshold value and inflection
point detected is the first inflection po int, the current is
compensated by current compensation and return the values
to the main program. However, if second point of inflection
is sensed and confirmed by end of saturation detection then
the compensation algorithm would end and continue to the
main program. After that, anti-aliasing filter is implemented
to remove all harmonics higher than sixth harmonic and,
Direct Current (DC) removal is applied to eliminate the DC
components in sampling data. The basic fundamentals of
current and voltage are extracted using DFT function.
Calculating the sine and cosine elements of current and
voltage performs DFT function. Finally, the developed
program ends with calcu lation of monitoring point
impedance.
A. Sampling Rates
Generally, dig ital relays sample waveforms between 4 and
64 t imes per cycle. A high sampling rate will produce more
accurate result. However, there must be enough time
between samples to perform relay calculation. Normally, the
implementation of all steps in Distance Relay takes longer
time compared to the sampling period in order to let the
program to analyze all sampling data.
B. Current Saturation Detection and Compensation
Normally, when CT saturation occur the magnetizing
current increases and causes severe ratio error [4]. The
higher ratio error increases the probability of distance relay
to mal-operate. Therefore, the saturation current needs to be
compensated in order to obtain minimum ratio error.
Besides that, compensation process is needed to provide
correct RMS current during saturation condition. The Auto
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:09 No:09 21
1917091-IJECS-IJENS © October 2009 IJENS I J E N S
Regressive (AR) model is employed in this paper to
compensate the saturation current.
Unfortunately, the saturation area needs to be determined
before compensation process can be performed. The third-
difference function is employed in determin ing the
saturation area. The third-difference function converts the
inflection points sensed at the waveform of secondary
current into pulses. The first inflection point indicates the
start of saturation condition where compensation algorithm
will begin. Then, the second inflect ion point sensed by the
compensation algorithm will end the compensation process.
In other words, the point of inflection determines the
saturation area and also starting and ending of compensation
algorithm.
In this proposed algorithm, the saturation detection area is
identified using equation (1), meanwhile the RMS current
during saturation is determined from equation (2). Equation
(1) is obtained from third-difference function and equation
(2) is computed from the simplified equation of AR model.
The last three samples of current are used to compute the
value of third differential of sample (del3[i]) and current
during saturation condition (I[i]).
del3[i]= I[i]-3I[i-1]+3I[i-2]-I[i-3] (1)
I[i]=2.9683117.I[i-1]-2.94647423.I[i-2]+0.97794999.I[i-3]
(2)
C. Anti Aliasing Filter
The anti-aliasing filter of a dig ital relay removes the
unwanted frequencies from a sampled waveform. Normally,
the anti-aliasing filter removes harmonics above ω0N/2 to
prevent corruption of the desired phasor which is based on
Nyquist frequency theorem [1, 7]. There are two issues that
need to be considered in selecting the anti-aliasing filter [1].
The first issue is the frequency response of the filter, and the
second issue is the time domain response of the filter. A
sharp frequency response of filter is desirable to completely
remove the unwanted harmonics. However, as the frequency
response of a filter becomes sharper, the time domain
response becomes worse. Therefore a balance must be
achieved between the frequency and time domain response
of the filter.
In this proposed algorithm, a fifth order Butterworth filter is
designed as anti-aliasing filter using WFILTER-filter design
software. The order of the Butterworth filter is obtained
based on the distorted secondary current data. From the
data, the sixth harmonic is determined to be less than 5% of
the fundamental frequency, which results to 300 Hz of cut
off frequency. The system is assumed to be operated at 50
Hz. The other design specifications of Butterworth filter are
tabulated in Table I. Meanwhile, the filtered current
produced by the Butterworth anti-aliasing filter is calculated
based on the last five samples of current as in equation (3).
]5[[5582.0]4[1159.3]3[9779.6
]2[8385.7]1[41821.4])5[]4[5
]3[10]2[10]1[5][(000044529.0][
iIiIiI
iIiIiIiI
iIiiIiIiI
fff
ff
f
𝐼𝑓𝑖=0.0000044529.𝐼𝑖+5𝐼𝑖−1+10𝑈𝑖−2+10𝑖−3+5𝐼𝑖−4+𝐼𝑖−5+4.4182𝐼𝑓𝑖−1−7.8385𝐼𝑓𝑖−2+6.9779𝐼𝑓𝑖−3−3.115
9𝐼𝑓𝑖−4+0.5582𝐼 (3)
T ABLE I
T HE ANTI-ALIASING BUTTERWORTH FILTER SPECIFICATIONS Selectivity Low-pass
Approximation Butterworth
Implementation IIR (digital)
Pass band gain (dB) -0.01
Stop band gain (dB) -40.0
Pass band freq (Hz) 50.0
Stop band freq (Hz) 300.0
Sampling freq (Hz) 3200.0
D. DC Removal
When faults or disturbances occur, a dc-offset is generated
in an electrical power system. The generated dc-offset will
affect the accuracy of the DFT algorithm results [8].
Therefore, the DC removal algorithm is designed in o rder to
eliminate the dc-offset. The dc-offset component is assumed
to be in exponential form when a fault occurs.
In this algorithm, the dc-offset is removed by computing the
value of sampled current after anti-aliasing filtering and dc-
removal; Ifdc. Value of Ifdc is calculated using equation (4)
with an assumption of sampling interval (∆t) of 0.00031 and
time constant (τ) of 0.04653.
nkfdc ayiI /][ (4)
Where;
)1
22)/(
)/(
)/(
/(tan
,)(),/2sin(]./1[
),/2cos(]./1[1),]1[
(][
nnn
nnnt
n
tnt
f
fk
EF
FEaNneF
NneEe
iIiIy
𝐼𝑓𝑑𝑐𝑖=𝑦𝑘𝑎Where, 𝑦𝑘=𝐼𝑓𝑖−𝐼𝑓𝑖−1𝑒E. Discrete
Fourier Transform (DFT)
In a distance relay system, the impedance value detected
will determine the distance relay operation. In this design,
the impedance value is computed from the magnitude of
basic fundamental of current and voltage. The magnitude of
basic fundamental of current and voltage is extracted using
DFT method.
The complete flow chart of the developed distance relay
algorithm is shown in Appendix 1. The constructed C++
language of numerical distance relaying algorithm with
current compensation is based on the flow chart.
III. CASE STUDY
In order to evaluate the performance of the developed
algorithm, two case studies have been setup. The case
studies are conducted during normal and saturation
condition for all types of faults. Both of the case studies
employed ATP in generating the transients current and
voltage.
Power system model in Fig. 1 is used to evaluate the
performance of developed algorithm during normal
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:09 No:09 22
1917091-IJECS-IJENS © October 2009 IJENS I J E N S
condition. The sampling frequency employed for the
simulation is 3200 Hz or 64 samples per cycle in a 50 Hz
system with total length of 200 km. Besides that, the value
of positive and zero sequence of line impedance have been
fixed to Z0= (30.34+j123.6) Ω and Z1= (3.347+j56.15) Ω
respectively.
Fig. 1. Power system configuration in normal condition
Fig. 2. Power system configurations for CT saturation simulation
Fig. 2 is used in evaluating the proposed algorithm
performance under saturation condition. The saturation
condition is created by adding a synchronous generator to an
existing bus to replace a weak source. This is because high
magnitude of fau lt current with DC components is produced
during high X/R rat io, which leads to CT saturation.
Therefore, a 15750 V synchronous ALESTOM generator
connected to Y-Y step-up transformer has been selected as a
power source. The output voltage subjected to the secondary
part of the Y-Y transformer is 132000 V.
IV. SIMULATION RESULT AND DISCUSSIONS
All results obtained for the designed distance relaying
algorithm with current compensation are presented here.
A. During Normal Condition
Fig. 3 shows the fault current during the occurrence of
three-phase fault on the system. Meanwhile, the current after
filtering and dc-removal is shown in Fig. 4. Comparing both
figures (Fig. 3 and Fig. 4), it can be seen that the current has
been smoothen and balanced after the application of an anti-
aliasing filter and dc removal. Therefore, the designed
algorithms have removed the high frequency and DC-offset
components occurred in the system successfully.
Fig. 3. Current before anti-aliasing and DC removal
Fig. 4. Current After Anti-Aliasing and DC Removal
The voltage waveforms for the three phase faults before and
after the application of anti-aliasing low-pass filtering are
shown in Fig. 5 and Fig. 6. The occurrence of h igh harmonic
components in the voltage waveform can be seen clearly in
Fig. 5. But, after the filter is applied, the harmonics
components have been filtered out as shown in Fig. 6.
Therefore, Fig. 6 reveals the filter effect in removing the
high frequency components. The phase delay can be seen
from the two figures (Fig. 5 and Fig. 6).
T ABLE II MEASURING IMPEDANCE IN NORMAL CONDITION
Fig. 5. Voltages before filtering (symmetrical fault)
Fault Type
Current RMS(A)
Voltage
RMS(V)
Measured Z(Ω)
Real Z (Ω)
Error (%)
A-B-C-G
61953.8 1056.22 58.6561 56.4040 3.9928
A-G 914.933 66726.3 51.000 56.4040 9.5808
A-B 1889.78 105021 55.5731 56.4040 1.4731
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:09 No:09 23
1917091-IJECS-IJENS © October 2009 IJENS I J E N S
Fig. 6. Voltages after filtering
Fig. 7 shows the measuring impedance according to the
previous voltage and current. Meanwhile, Table II indicates
the measured impedance and the error for symmetrical and
unsymmetrical fau lts in normal condition. As it can be seen,
the maximum error is 9.58%, which occurred during the
single phase faults.
Fig. 7. Measuring impedance by algorithm for three phase fault
B. Saturation Condition
Fig. 8 depicts the results obtained after the implementation
of compensation algorithm with the signal which comprises
of the dc-offset and power frequency component. The first
graph shows the scaled primary current (a) and the
measured secondary current (b). Meanwhile, the second and
third graphs show the detection signal and the transient error
compensated secondary current and scaled primary current.
Based on the transient error graph, it can be stated that the
maximum transient error is less than 0.2%.
Fig. 8. Compensated current and transient error
The basic fundamental phasor of current and voltage is
shown in Fig. 9 and Fig. 10 respectively. The waveform is
obtained by DFT algorithm which has extracted the basic
fundamental phasor of current and voltage after the
compensation process has been completed.
Fig. 9. Current phasor for single phase fault in saturation condition
Fig. 10. Voltage phasor for single phase fault in saturation condition
The results for saturation condition including RMS
values of compensated current and measured impedance are
displayed in Table III and Table IV. These tables display the
results and verify the performance of Distance Relay
algorithm. Furthermore, it shows the valid ity of the
proposed algorithm in compensating the saturation current
for Distance Relay applicat ion. Based on both tables (Table
III and Table IV), it can be seen that the value of error is
very small (1.15% for compensated current and 1.1723% for
measured impedance).
T ABLE III. T HE REAL AND MEASURED CURRENT RMS VALUES ONE AND HALF CYCLE
AFTER FAULT Fault Type Real Current
RMS Compensation Current RMS
Error (%)
A-B-C-G 25.8916 25.5919 1.1575
T ABLE IV T HE REAL AND MEASURED IMPEDANCE FOR THREE PHASE FAULT
ONE AND HALF CYCLE AFTER FAULT Fault Type Real Z(Ω) Measured Z( Ω) Error (%)
A-B-C-G 39.0158 39.4727 1.1710
CONCLUSIONS
DISTANCE RELAY OPERATION DEPENDS ON THE VALUE OF
FAULT CURRENT AND FAULT IMPEDANCE. THE SMALL VALUE
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:09 No:09 24
1917091-IJECS-IJENS © October 2009 IJENS I J E N S
OF IMPEDANCE ERROR SHOWS THE HIGH SENSIT IVITY OF THE
PROPOSED NUMERICAL DISTANCE RELAY ALGORITHM IN
FAULT DETECTION. MEANWHILE, SMALL CURRENT ERROR
INDICATES THE ABILITY OF THE PROPOSED ALGORITHM IN
PREVENTING THE MAL-OPERATION OF DISTANCE RELAY
EVEN DURING SATURATION CONDITION. THEREFORE, AS A
CONCLUSION, A C++ NUMERIC DISTANCE RELAY
ALGORITHM WHICH IS IMMUNED FROM CT SATURATION
CONDITION HAS BEEN SUCCESSFULLY DEVELOPED.
REFERENCES [1] M.G.Adamaik, G.E.Alexander, Malvern, PA Dr.W.Premerlani and
Schenectady NY. Advancements in Adaptive Algorithms for Secure High Speed Distance Protection T.S
[2] E. E. CONNER, E. C. WENTZ and D. W. ALLEN. Methods for Estimating Transient Performance of Practical Current Transformer for Relaying. IEEE PES Summer Meeting & Energy Resources Conf. July 14-19, 1974. Anaheim, Cal:IEEE. 1974. 116-122.
[3] Y. C. Kang, S. H. Kang, J. K. Park, A. T . Johns and R. K. Aggarwal. Development and hardware implementation of a compensation algorithm for the secondary current of current transformers .IEE. 1996. 143(1): 41-49.
[4] Sidhu, M.Hfuda and M. S. Sachdev. A Technique for Generating Computer Models of Microprocessor–Based Relays. Conference on Communication Power and Computing. May 22-23, 1997. Winnipeg: IEEE .1997.191-196.
[5] Yong-Cheol Kang, Sang-Hee Kang and Peter Crossley. An algorithm for detecting CT saturation using the secondary current third-difference function. IEEE. Bogotá , Italy. IEEE:2003
[6] S. H. Kang, D. K. Lee S. H. Hyun and Y. C. Kang, A Compensation Algorithm For The Distored Secondary Current Of A Current Transformer. IEE, 2004:140-143
[7] Chul-Hwan Kim. Myung-Hee Lee. Raj K. Aggarwal and Allan .T .Johns. Educational Use of EMTP MODELS for the study of Distance Relaying Algorithm for protecting Transmission Lines. IEEE. 2000. 15(1): 9-15.
[8] T.S.Sidhu, X.Zhang, F.Albasri and M.S.Sachdev. Discrete-Fourier-Transform Based Technique for Removal Of Decaying Dc Offset From Phasor Estimates, IEEE Proc-Gener. Transm. Distrib, 2003. 150(6): 745-752
[9] Les Thede. PRACTICAL ANALOG AND DIGITAL FILTER DESIGN. Norwood,MA:Artech House, INC. 2005
[10] Gabriel Bermonouyal. Removal Of DC-Offset In Current Waveforms Using Digital Mimic Filtering. IEEE Transactions on power Delivery, 1995. 10(2): 621-630
[11] Li-Cheng Wu, Chih-Wen Liu and Ching-Shan Chen. Modeling and Testing of a Digital Distance Relay Using MATLAB/SIMULINK.IEEE.2005:253-259
[12] T Rasheek M. Rifaat. Considerations in Applying EMTP to Evaluate Current Transformer Performance under Transient and High Current Fault Conditions. International Conference on Power systems Transients. June 19-23, 2005. Montreal, Canada: IEEE. 2005. 206.
[13] Hector J Altuve,Ismael Diaz and Jose A .de la O. A New Digital Filter for Phasor Computation .IEEE .1998. 13(3): 1032-1037
[14] R. K. Aggarwal, D. v Coury, A.T. Johns and A.Kalam. A Practical Approach to Accurate Fault Location on Extra High Voltage Teed Feeders. IEEE. 1993. 8(3): 874-883
[15] H. khorashadi-Zade and H. Daneshi, Evaluation and Performance Comparisons of Digital Distance Protection Algorithms. IEEE. 2004: 2463-2468
[16] M. Khederzade, A. Safarnourollah, M. Mortajeee and M. E. Hamedanigolshan, Fundamentals of Power System Protection, Iran. Power Ministry .2005
[17] Adly. A. Girgis and Christopher. M. Fallon. Fault Location Techniques For Radial And Loop Transmission Systems Using Digital Fault Recorded Data. 1992.7(4):1936-1945
[18] M. KEZUNOVIC, M. Lj. KoJoVIC, A. ABUR, C. W. Fromen and F.Pillips. Experimental Evaluation Of EMTP-Based Current
[19] R. K. Aggarwal, D. v Coury, A.T. Johns and A.Kalam. A Practical Approach to Accurate Fault Location on Extra High Voltage Teed Feeders. IEEE. 1993. 8(3): 874-883
[20] H. khorashadi-Zade and H. Daneshi, Evaluation and Performance Comparisons of Digital Distance Protection Algorithms. IEEE. 2004: 2463-2468
[21] M. Khederzade, A. Safarnourollah, M. Mortajeee and M. E. Hamedanigolshan, Fundamentals of Power System Protection, Iran. Power Ministry .2005
[22] Adly. A. Girgis and Christopher. M. Fallon. Fault Location Techniques For Radial And Loop Transmission Systems Using Digital Fault Recorded Data. 1992.7(4):1936-1945
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:09 No:09 25
1917091-IJECS-IJENS © October 2009 IJENS I J E N S
INDEX 1
S
[23] ransformer Models For Protective Relay Transient Study. IE
nded
End of saturatio
n
Sampling of voltage and current
Saturation
detection
Saturation
level>TH
Second
Inflection
point
Current
compensation
Anti aliasing filter
DC Removal
Enter new sample and remove the old one 𝑉𝑛=𝑉𝑛+1 𝐼𝑛=𝐼(𝑛+1)
Calculation of sine and cosine elements of voltage and current
𝑉1𝑠=1𝑛Σ𝑤𝑛𝑠 𝑉1𝑐=1𝑛Σ𝑤𝑛𝑐
𝐼1𝑠=1𝑛Σ𝑤𝑛𝑠 𝐼1𝑐=1𝑛Σ𝑤𝑛𝑐
𝑉<𝜙𝑣=𝑉1𝑠2+𝑉1𝑐2∠𝛼 𝑡𝑎𝑛𝑉1𝑠𝑉1𝑐 𝐼<𝜙𝐼=𝐼1𝑠2+𝐼1𝑐2∠𝛼 𝑡𝑎𝑛𝐼1𝑠𝐼1𝑐
𝑍=𝑉𝐼 ; ∅=∅𝑉−∅𝐼 𝑋= 𝑍𝑠𝑖𝑛∅ ; 𝑅=𝑍𝑐𝑜𝑠∅
YES
NO
YES
YES