47

Critical Room Design for Better

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Critical Room Design for Better
Page 2: Critical Room Design for Better

Critical Room Design for Better

Infection Prevention

Page 3: Critical Room Design for Better

Hospital Critical RoomDesign

▪Types of Isolation Rooms▪Codes/Standards/References▪Design Criteria▪Design Considerations▪Design Examples▪Clean Room design and Standard

Page 4: Critical Room Design for Better

Types of Isolation RoomsAirborne Infection Isolation (AII) Rooms

❖ Used to reduce the spread of airborne infectious diseases (TB) from the patient in the AII Room to the rest of the hospital.

❖ Most common type seen in hospitalsProtective Isolation/Environment Rooms

❖ Used to protect the patient (typically an immune suppressed patient) in the protective environment from common environmental airborne infectious microbes.

❖ Less common than AIIConvertible Isolation Rooms

❖ Rooms that can be converted from an AII Room (negative) to a Protective Environment Room (positive)❖ Out of date concept - not allowed by ASHRAE Standard 170

Combination AII/PE Rooms

❖ Used for an immune suppressed patient who has an infectious disease.❖ Protects both patient and rest of the hospital.

Contact Isolation Room ❖ Used for patients suffering from communicable disease that is not airborne ❖ This type of room is a standard patient room and should be treated as such. No special measures must be taken for

design of the HVAC system.

Page 5: Critical Room Design for Better

Codes/Standards/References

▪“Guidelines for Environmental Infection Control in Health-Care Facilities”, Recommendations of CDC and the Healthcare Infection Control Practices Advisory Committee (HICPAC), 2003

Codes:▪ Illinois Administrative Code – will refer to as IDPH▪ Title 77: Public Health Chapter I: Department Of Public Health▪ Subchapter B: Hospitals and Ambulatory Care Facilities Part 250 Hospital licensing Requirements for HVAC:

refer to Section 250.2480 Mechanical▪ International Mechanical Code (IMC) - applicable to most suburbs City of Chicago Building Code

Standard:

▪ ANSI/ASHRAE/ASHE Standard 170 – Ventilation of Health Care Facilities (2013)

▪ NFPA 101

Guidelines:

▪ Facility Guidelines Institute (FGI) Guidelines (2014) – for ventilation refers to ASHRAE Standard 170 – 2013

Page 6: Critical Room Design for Better

Airborne Infectious Isolation Room Design Step 1:Develop HVAC Design Criteria

Temperature, humidity, airflow and pressurization requirements

CDC

IDPH

ASHRAE

Standard 170-2013

(incorporates CDC)• Temp/humidity –

not addressed

• Min 12 ach exhaust for rooms constructedsince 2001

• Min 0.001”H2O pressure differential to achieve airflow into room (this is too low – need 0.01” wg)

• 75F

• 30% rh winter min,60% rhsummer max

• 15 cfm per bed/ 10 cfmper bed OA

• All air exhausted to outdoors

• Airflow into room

• 70F-75F – ability to maintain at alltimes

• 60%rh

• 12 ach minimum totalairflow/2 ach outside air

• All air exhausted to outside

• Negative pressure relative to adjacentspaces

Page 7: Critical Room Design for Better

Airborne Infectious Isolation Room Design Step 1:Develop HVAC Design Criteria

Use most stringent of IDPH/ASHRAE Standard 170

Temperature: 70F to 75F

Humidity: 30% rh winter min, 60% rh summer max

Airflow: 12 ach total/ 2 ach OA

Pressure: Negative to adjacent areas

Page 8: Critical Room Design for Better

Differential Room Pressure

Air moves to achieve pressure equilibrium. Consequently a room that is under positive pressure will have air moving out of it to equalize with the surrounding area. Conversely, a room under negative pressure will retain air in the space and draw air in from the surrounding areas. This differential in air pressure between spaces can be used to control airborne pathogens.

Page 9: Critical Room Design for Better

Airborne Infectious Isolation Room Architectural Design Considerations

➢Ante room with hand wash sink (IDPH Section 250-2440)

Note not required by FGI or ASHRAE

➢One toilet room per AII room

Page 10: Critical Room Design for Better

Airborne Infectious Isolation Room Architectural Design Considerations

➢ AII room constructedTo minimize leakage areas and allow for room pressurization

• Walls – slab-to-slab

• Ceilings – plaster or drywall

• Self-closing doors (swing out for negatively pressurized spaces;swing in for positively pressurized spaces) with door sweeps

• Finishes should be smooth and cleanable

• Label room use (signage)

• Seal all penetrations

Page 11: Critical Room Design for Better

Airborne Infectious Isolation Room PressurizationDesign Considerations

AII room negative to ante room/ante room

negative to corridor (ASHRAE)

Min ΔP between AII room and adjacent

rooms/corridor -0.01” wg(ASHRAE)

Min of 10% more EA than SA but no less than 50 cfm

•New tight construction -200cfm to 300 cfmdifferential

Permanently installed ΔP

monitoring device (ASHRAE)

Provide provisions to change HVAC for normal patient care room use (IDPH only/different than ASHRAE)

Page 12: Critical Room Design for Better

Airborne Infectious Isolation RoomRoom Supply and Exhaust Design Considerations➢Ante room airflow: 10 ach (ASHRAE)

➢Location of supply diffusers and exhaust grilles - CDC 2003 and ASHRAE Standard

170 disagree

o CDC 2003: Supply above patient, exhaust low on wall

o ASHRAE Standard 170 2008/2013: “Exhaust grilles or registers … shall be located directly above the patient bed on the ceiling or on the wall near the head of the bed…”

o Designer may consider discussing discrepancy with hospital infection

control.

o If chose to supply above patient use non-aspirating laminar flow type diffusers

Page 13: Critical Room Design for Better

Airborne Infectious Isolation Room Other DesignConsiderations

➢SA must be from AHU that has code-required filtration:

Min MERV 7 prefilters and MERV 14 final filters (IDPH/ASHRAE)

➢Exhaust air from AII/ante room/toilet room shall not mix with non-AII room exhaust (ASHRAE)

Page 14: Critical Room Design for Better

Diagram from CDC Guidelines

Page 15: Critical Room Design for Better

Airborne Infectious IsolationRoom Room HVAC Design Example

➢Exhaust system:

➢Design Calculation for 40m2 isolation room EA from AHII to maintain 12 ach: 350 cfmToilet exhaust: 50 cfmEA from ante room to maintain 10 ach: 140 cfmConstant volume exhaust box to maintain EA / Total EA = 350 cfm + 50 cfm + 140 cfm = 540 cfm

➢Supply system:• Isolation room Supply=EA isolation - 50 = 300 CFMConstant volume box to maintain total SA / Total SA = 300 cfm + 100 cfm = 400 cfm

Reheat coil to provide space temperature control

ACH= Q*60Volume

Q= Volume of air in CFM Volume= Volume of room in cubic feet

Page 16: Critical Room Design for Better

CONTROLS FOR CRITICAL ROOM CAN BE POSITIVE OR NEGATIVE PRESSURE

Page 17: Critical Room Design for Better

Room Pressure Monitorso Locate outside of anteroom door in corridor

o Alarms visually and audibly if negative pressure is not maintained.

o Tie-in alarm to building automation system

o To avoid nuisance alarms, control to a higher point ΔP than to the ΔP at which the alarm is set

• Control to 0.03” and alarm at 0.01”.

Page 18: Critical Room Design for Better

Airborne Infectious Isolation Room Central System Design

➢ Exhaust System

• Locate exhaust fan outside, if possible

• I f exhaust fan is inside, use welded duct construction downstream of fan

• Bag in/bag out prefilter/HEPA filter upstream of the exhaust fan

• VFDs for the exhaust fan to adjust fan speed as filters load up

• Locate fan discharge away from all intakes and above roof, if possible

• Consider large exhaust system to serve multiple rooms instead of multiple smaller exhaust systems

• Provide emergency power for fans

Page 19: Critical Room Design for Better

Bag In/ Bag Out Procedure

Page 20: Critical Room Design for Better

Airborne Infectious IsolationRoom Central System Design

➢ Supply System

• Can supply from same AHU system that serves adjacent patient rooms

• Must have Min MERV 7 prefilters and MERV 14 final filters (IDPH/ASHRAE)

• Must be able to humidify to IDPH required 30% rh

Page 21: Critical Room Design for Better

Protective Isolation Room

Design Step 1:

Develop HVAC Design Criteria

Use most stringent of IDPH/ASHRAE Standard 170

Temperature: 70F to 75F

Humidity: 30% rh winter min, 60% rh summer max

Airflow: 12 ach total/ 2 ach OA

Pressure: Positive to adjacent areas

Page 22: Critical Room Design for Better

Protective Environment Room Pressurization DesignConsiderations

PE room positive to ante

room/ante room positive to

corridor (ASHRAE)

Min ΔP between PE room

and adjacent

rooms/corridor

+0.01” wg (ASHRAE

Min of 10% more SA than

EA but no less than 50 cfm

•New tight construction -

200cfm to 300 cfm differential

•Poorly constructed - 300 cfm to

500 cfm

Permanently installed ΔP

monitoring device (ASHRAE)

Provide provisions to change HVAC for normal patientcare room use

(IDPH only/different thanASHRAE)

Page 23: Critical Room Design for Better

Combination Airborne Infectious Isolation/Protective Environment Rooms

Page 24: Critical Room Design for Better

Clean Room Standard

ISO -14644-1

USP 797

Page 25: Critical Room Design for Better
Page 26: Critical Room Design for Better
Page 27: Critical Room Design for Better
Page 28: Critical Room Design for Better
Page 29: Critical Room Design for Better
Page 30: Critical Room Design for Better
Page 31: Critical Room Design for Better
Page 32: Critical Room Design for Better

Critical room design for better infection prevention

Standards for the design of ventilation system in operating rooms

Filtration system

Operation block planning

Construction requirements for operating rooms

Interesting facts and Best practice

CONTENT

Speaker:Helena [email protected]

Page 33: Critical Room Design for Better

EU-DIN

▪ DIN 1946-4: 2018/06

Ventilation in buildings and rooms of health care

USA

▪ ASHRAE 2008 standard 170

Ventilation of health care facilities

UK

▪ HTM 2025, HTM 03-01

Ventilation in health care premises

STANDARDS AND GUIDELINES FOR THE DESIGN OF

VENTILATION SYSTEM IN OPERATING ROOMS

Page 34: Critical Room Design for Better

One goal to all Standards and Guidelines…

…TO PROTECT THE OPERATING ROOM

FROM HOSPITAL INFECTION

Page 35: Critical Room Design for Better

CLASS I

3 stage filtration

CLASS II

2 stage filtration

MEDICALYUSED SPACE

Low turbulent ventilation system, operating area protection,

instrument tables protection, possitive pressure

All other spaces

FILTRATION SYSTEM

Page 36: Critical Room Design for Better

FILTRATION SYSTEM – Laminar flow ceiling

Page 37: Critical Room Design for Better

BEST PRACTICE – Laminar flow ceiling

Page 38: Critical Room Design for Better

Main flows in operation block

Location inside the hospital

Areas in the operation block

Hygienic requirements

Operating rooms

Construction requirements

OPERATION BLOCK - Planning

Page 39: Critical Room Design for Better

PATIENT FLOW

PERSONNEL FLOW

GOODS

SUPPLY

OPERATION BLOCK – Main function flows

Page 40: Critical Room Design for Better

ROOMS

• Operating rooms

• Staff changing rooms

• Staff rest room

• Dirty utility

• Disposal hold

• Cleaners room

• (Last 3 rooms can be combined)

AREAS

• Anaesthesia introduction

• Disposal of dirty goods from OR

• Hands washing and desinfection

• Storage for clean devices, sterile material

• Patient transfer

• Beds – waiting

• Transfer of clean goods

• Emergency lab.

• Reporting room

• Administration

IF NECESSARY

• Room for preparing of instrument tables

OPERATION BLOCK - Areas

Page 41: Critical Room Design for Better

OPERATING ROOM – Construction requirements

Page 42: Critical Room Design for Better

Construction requirements

▪ All finishes – no dirt accomulation▪ Sealed joints▪ Smooth surfaces▪ Antibacterial and resistant surfaces▪ Built-in installations (lights…)▪ Floor to suspended ceiling min. 3 m▪ Revision openings to minimum▪ Automatic doors▪ Radiation protection – if needed▪ Day light – desirable▪ Windows not opening, protection

OPERATING ROOM – Construction requirements

Page 43: Critical Room Design for Better

OPERATING ROOM – Size of protected area

Protected area

▪ Standard size from the practice 9 m²▪ Laminar flow ceiling size 3,2 x 3,2 m▪ Mandatory position analysis

Page 44: Critical Room Design for Better

Interesting facts

▪ The largest germ load comes from operating team▪ Organizational preventive measures are the

most important▪ Information deficit on the work flow▪ Operating rooms are air-conditioned

to prevent infection

Page 45: Critical Room Design for Better

Best practice

Page 46: Critical Room Design for Better

Best practice

Page 47: Critical Room Design for Better

Thank you for Attention!

Helena Hrastnik

[email protected]