CRHEATER101A00 --CRHEATER119A00,CRHEATER264A00 --CRHEATER269A00,CRHEATER288A00 --CRHEATER299A00CRHEATER301A00CRSINGLE037A00 --CRSINGLE054A00
Installation Instructions
SMALL ROOFTOP UNITSACCESSORY ELECTRIC HEATER
AND SINGLE POINT BOXELECTRIC COOLINGAND HEAT PUMP
3 to 15 TONS
TABLE OF CONTENTSSAFETY CONSIDERATIONS 1. . . . . . . . . . . . . . . . . . . . . . . . .
PACKAGE USAGE 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PACKAGE CONTENTS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL INSTALLATION SEQUENCE 8. . . . . . . . . . . . . . . .
All Units Except HP--1 Size 14 and 150 8. . . . . . . . . . . . . . . . .
Installing Single Point Box (CRSINGLE037A00--054A00) 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing Electric Heater (CRHEATER101A00--119A00,CRHEATER264A00--269A00, 299A00) 10. . . . . . . . . . . . . .
Installing Electric Heater (CRHEATER297A00, 298A00,301A00) 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat Pump Size 14 and 150 Only 15. . . . . . . . . . . . . . . . . . . . .
Installing Single Point Box (CRSINGLE047A00,050A00--054A00 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing Electric Heater (CRHEATER288A00--296A00) 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
APPENDIX A 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
APPENDIX B 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
APPENDIX C 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT: Read these instructions completely beforeattempting to install this accessory.
SAFETY CONSIDERATIONSInstallation and servicing of air--conditioning equipmentcan be hazardous due to system pressure and electricalcomponents. Only trained and qualified service personnelshould install, repair, or service air-conditioningequipment.Untrained personnel can perform the basic maintenancefunctions. All other operations should be performed bytrained service personnel.
When working on air-conditioning equipment, observeprecautions in the literature, tags and labels attached tothe unit, and other safety precautions that may apply.Follow all safety codes. Wear safety glasses and workgloves.Recognize safety information. This is the safety--alert
symbol . When you see this symbol on the unit and ininstructions or manuals, be alert to the potential forpersonal injury.Understand the signal words DANGER, WARNING, andCAUTION. These words are used with the safety--alertsymbol. DANGER identifies the most serious hazardswhich will result in severe personal injury or death.WARNING signifies a hazard which could result inpersonal injury or death. CAUTION is used to identifyunsafe practices which may result in minor personalinjury or product and property damage. NOTE is used tohighlight suggestions which will result in enhancedinstallation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personalinjury or death.
Turn off all power to unit and install lockout tag.Power can come to unit from from multiple sources.Verify power is off with a meter or probe.
! WARNING
CUT HAZARD
Failure to follow this caution may result in personalinjury. Sheet metal parts may have sharp edges orburrs. Use care and wear appropriate protectiveclothing, safety glasses and gloves when handlingparts and servicing units.
CAUTION!
Copyright 2012 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 01/12
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No:IIK---CRHTRSIN01---05
Replaces: IIK---CRHTRSIN01---04
2
PACKAGE USAGECARRIER MODELS
MODEL NUMBER CHASSISGROUP UNIT SIZES
50HC AC---2 04---1450HCQ HP---2 04---1250TC AC---1 04---1650TCQ HP---1 04---14
BRYANT MODELSMODEL NUMBER CHASSIS
GROUP UNIT SIZES
548J HP---1 04---14549J HP---2 04---12551J AC---2 04---14558J AC---1 04---16
ICP MODELSMODEL NUMBER CHASSIS
GROUP UNIT SIZES
RAS AC---1 036---180RHS HP---1 036---150
AC: Cooling Only (air conditioner)HP: Heat Pump
PACKAGE CONTENTS--ELECTRIC HEATERS
CRHEATER101A00--119A00,CRHEATER264A00--269A00
CRHEATER297A00, 298A00, 301A00QTY CONTENTS1 Heater module1 Heater slider track*4 Screws*1 Wiring label1 Red wire (10 gauge){1 Splice connector{1 Wire tie{1 Label, Max Temp/Static
*Not included with CRHEATER101A00---109A00, 297A00, 298A00, 301A00{Supplied with electric heater packages CRHEATER101A00,CRHEATER102A00, CRHEATER103B00, and CRHEATER104B00 only.
PACKAGE CONTENTS--ELECTRIC HEATERS
CRHEATER288A00--296A00, 299A00QTY CONTENTS1 Heater module1 Heater slide track4 Screws1 Wiring label1 Label, Max Temp/Static
PACKAGE CONTENTS--CRSINGLE037A00
ITEM DESCRIPTION QUANTITYSingle Point Box Housing Assembly(Height 18--- in/449 mm) 1
Terminal block 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1
CRSINGLE038A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 18--- in/449 mm) 1
Terminal block/Fuse holder 1Fuse block 1Fuses, 60---A class RK5 6Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1
CRSINGLE039A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 18--- in/449 mm) 1
Terminal block/Fuse holder 1Fuse block 2Fuses, 60---A class RK5 9Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1
CRSINGLE040A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 18--- in/449 mm) 1
Terminal block/Fuse holder 1Fuse block 1Fuses, 60---A class RK5 4Power distribution harness 1Conductors, Tap, #10 2Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1
CRHTR,CRSIN
3
CRSINGLE041A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 18--- in/449 mm) 1
Terminal block/Fuse holder 1Fuse block 1Fuses, 60---A class RK5 6Power distribution harness 1Conductors, Tap, #10 2Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1
CRSINGLE042A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 25--- in/639 mm) 1
Terminal block 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE043A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 25--- in/639 mm) 1
Terminal block/Fuse holder 1Fuse block 1Terminal block (TB---10) 2Fuses, 60---A class RK5 6Power distribution harness 1Conductors, Tap, #10 6Screws, #8 x ½--- in 2Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE044A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 25--- in/639 mm) 1
Terminal block 1Fuse block 2Fuses, 60---A class T (600v) 6Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE045A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 25--- in/639 mm) 1
Terminal block/fuse holder 1Fuse block 2Fuses, 60---A class RK5 9Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE046A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 25--- in/639 mm) 1
Terminal block/fuse holder 1Fuse block 3Fuses, 60---A class RK5 12Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE047A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 33--- in/845 mm) 1
Terminal block 1Conductors, Tap, #10 3Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE048A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 25--- in/639 mm) 1
Terminal block 1Fuse block 3Fuses, 60---A class RK5 9Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRHTR,CRSIN
4
CRSINGLE049A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 33--- in/845 mm) 1
Terminal block/Fuse holder 1Fuse block 1Fuses, 60---A class RK5 6Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE050A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 33--- in/845 mm) 1
Terminal block 1Fuse block 2Fuses, 60---A class T (600v) 6Power distribution harness 1Conductors, Tap, #10 3Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE051A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 33--- in/845 mm) 1
Terminal block/fuse holder 1Fuse block 2Fuses, 60---A class RK5 9Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE052A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 33--- in/845 mm) 1
Terminal block 1Fuse block 3Fuses, 60---A class T (600v) 9Power distribution harness 1Conductors, Tap, #10 3Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE053A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 33--- in/845 mm) 1
Terminal block 1Fuse block 4Fuses, 60---A class RK5 12Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRSINGLE054A00ITEM DESCRIPTION QUANTITY
Single Point Box Housing Assembly(Height 33--- in/845 mm) 1
Terminal block 1Fuse block 5Fuses, 60---A class RK5 15Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1
CRHTR,CRSIN
5
GENERALPuronR UnitsThis installation instruction manual describes theinstallation of electric heaters and associated fuseblock/field power termination kits (single point box orSPB) on small rooftop units in nominal cooling capacitiesfrom 3 to 15 tons. These rooftop units use Puronrefrigerant (R-410A). See Package Usage tables on page2 for applicable unit models. Unit types include coolingunits (AC) and heat pumps (HP) distributed over severalchassis sizes. Unit AC--1, AC--2, HP--1, HP--2 areidentified.This information does not include selection data. Refer toproject plans, job submittals and selection programs forheater and field power termination/SPB kit usage.Some electric heaters used on these Puron (R-410A) unitsmay also be installed in earlier R-22 rooftop units. Referto Form 50-8SI or IIK-548-36-49 for installationinstructions on heater packages CRHEATER101A00through 119A00 with earlier models. Contact your localdistributor office for a copy of this form.
Electric HeatersHeaters are shipped with one heater per carton. Thecarton is marked with a Sales Package Number. On allheaters except CRHEATER101A00 through 119A00, theheater Model Number (as marked on the heater infoplate)is the same as the Sales Package number. OnCRHEATER101A00 through 119A00 heaters, the value inposition 9 of the part number differs between the salespackage part number (value is 1) and bare heater modelnumber (value is 0). (See Table 1.)The heaters are modular in design, with heater framesholding open coil resistance wires strung through ceramicinsulators, limit switches and one or two controlcontactors. Power conductors are attached. One or twoheater modules may be used in a unit.Heater modules are installed in the compartment belowthe indoor (supply) fan outlet. Access is through theindoor access panel. Heater modules slide into thecompartment on tracks along the bottom of the heateropening. (See Fig. 13.)NOTE: The following heaters do not use the slide track --CRHEATER101A00--109A00, 297A00, 298A00, and301A00.
Not all available heater modules may be used in everyunit. Use only those heater modules that are UL listed foruse in a specific size unit. Refer to the label on the unitcabinet for the list of approved heaters. (See Fig. 1 and2.) See Appendix C for electric heater module data.
Single Point Boxes and FusesThe Single Point Box kits provide a field powertermination location plus an enclosure for heater fuseswhen required by code. The SPBs are installed under theunit’s main control box and include a hinged cover plusall internal wiring. Minimum components of the SPB area field power terminal block with tap conductors (toconnect to the unit’s main control box field terminals).Maximum component population includes up to five fuseblocks.Fuses for electric heater circuits are required and providedwhen the unit’s MOCP exceeds 60-A or when the totalheater Full Load Amp value exceeds 48-A. When fusesare required and provided, the cooling circuit is alsoprovided with fuse protection; some units require minorwiring changes in the main control box (see section onTB10 terminal blocks).
No FusesIf the unit’s MOCP device rating is 60-A or less, then theMOCP device is recognized as providing the requiredovercurrent protection to the heater and no internal fusingis required. If two heater modules are installed, a singlepoint box that contains only a field power terminal blockis required. If only one heater module is installed, no fuseor single point box is required. Connect field power leadsand heater power leads to the unit’s field connectionterminals in the main control box. See tables at thebeginning of Appendix A and B for where-usedinformation on the single point boxes and for connectionsFigure number.
Units with Factory Installed HACRThe amp rating of the HACR factory installed option isbased on the size, voltage, indoor motor and otherelectrical options of the unit as shipped from the factory.When field installed accessory electric heaters are addedor changed in the unit, the HACR may no longer be of theproper amp rating and therefore will need to be removedfrom the unit. See unit nameplate and label on factoryinstalled HACR for the amp rating of the HACR that wasshipped with the unit from the factory. See unitnameplates for the proper fuse, HACR or maximumover--current protection device required on the unit withfield installed electric heat.
CRHTR,CRSIN
6
Table 1 – Heater Model Number
Bare Heater ModelNumber C R H E A T E R 0 0 1 A 0 0
Heater Sales PackagePNOIncludes:Bare HeaterCarton and packingmaterialsInstallation sheet
C R H E A T E R 1 0 1 A 0 0
7310 West Morris StreetIndianapolis, IN 46231 U.S.A.
BREAKER PER NEC
MAX OVERCURRENT
MINIMUM UNIT DISCONNECT
FLA LRA
PROTECTION DEVICE
VOLT
OTHER
LBS kg
CAPACITY Btu/Hr CAPACITY kW EER COP
COOLING
HP HEATING
THIS EQUIPMENT COMPLIES WITH THE
2004 REQUIREMENTS OF ASHRAE 90.1
CarrierCorporation
MODEL
QTY VOLTS AC PH HZ RLA LRA REF. SYSTEM R410A TEST PRESSURE GAGE
COMPR A
COMPR B
LBS
LBS
kg
kg
HI
LO
PSI kPa
PSI kPa
FAN MTR QTY VOLTS AC PH HZ FLA
OUTDOOR
COMPR C
INDOOR
PWR.EXH.
ELC.HEATCHARGE SYSTEM PER INSTALLATION INSTRUCTIONS
SUITABLE FOR OUTDOOR INSTALLATION
POWER
SUPPLY PH HZ
PERMISSIBLEVOLTAGE AT UNIT MINMAX
DOWN SUPPLYMIN CLEARANCE TO COMBUSTIBLE MATERIALS _____INCHES ______mm.
FOR FIRST _____INCHES______mm. OF DUCT WHEN ELECTRIC HEATER IS INSTALLEDSIDE SUPPLY
MIN CLEARANCE TO COMBUSTIBLE MATERIALS _____INCHES ______mm.
FOR FIRST _____INCHES______mm. OF DUCT WHEN ELECTRIC HEATER IS INSTALLED
*FOR INSTALLATION ON COMBUSTIBLE FLOORING OR
CLASS A,B, OR C ROOFING MATERIAL
ACCESSORYHEATER MODEL
NUMBER
CHECK
HEREVOLTS PH HZ
HEATER FLA
MIN CKT AMPS
FUSE OR HACRBREAKERPER NEC
MAXIMUM OVERCURRENT PROTECTION DEVICE
SINGLE PT. BOX MODEL NUMBER
MINIMUM UNIT DISCONNECT
FLA LRA
INSTALLER NOTE: 1.INSTALL ACCESS HEATER PER INSTALL INSTR ENCLOSED WITH HEATER. MARKSPACE "CHECK HERE" FOR MODEL USED USE MIN CKT AMPS & MAX OVER-CURRENT DEVICE AMPS LISTED FOR HEATER. IF NO HEATER IS USEDMARK SPACE "CHECK HERE" FOR NONE.
2.HEATERS ARE MANUFACTURED BY EMERSON HEATING PRODUCTS OR TUTCO ELECTRIC.
MIN. CKT.AMPS
MAX FUSE OR HACR
50TC-A06A2A5A0A0A0
10.7 4.9 650 4482450 3103
1 208/230 3 60 15.6 110
1 208/230 1 60 1.51 208/230 3 60 5.2
208/230 3 60
253 187 26.2
40
26 144-
1 2512 305
1 2512 305
17.25900013
102A 208/240
3 60 13.6/15.6
26.2/26.2
40/40 -/- - 26/26 144/144
104B 208/240
3 60 21.9/25.3
33.9/38.1
40/40 -/- - 31/35 144/144
105A 208/240
3 60 33.4/38.5
48.3/54.6
50/60 -/- 037 44/50 144/144
104B+104B 208/240
3 60 43.8/50.5
61.3/69.6
70/70 -/- 038 56/64 144/144
104B+105A 208/240
3 60 55.2/63.8
75.5/86.3
80/90 -/- 038 69/79 144/144
C10531
Fig. 1 -- Unit Informative Data Label
CRHTR,CRSIN
7
BOX MODELNUMBER
SINGLE PTBOX MODELNUMBER
SINGLE PTBOX MODELNUMBER
1.INSTALL ACCESS. HEATER AND/OR POWER EXHAUST PER INSTALL INSTR ENCLOSED
USE MIN CKT AMPS AND MAX OVER CURRENT DEVICE AMPS LISTED FOR HEATER
HERE
CHECK
MODEL
REFRIGERANT CHARGE R410A
ELECTRICAL DATA FOR ACCESSORY POWER EXHAUST INSTALLED
IN COMBINATAION WITH ELECTRIC HEATER
ACCESSORYHEATER MODEL
NUMBER
HEATER
FLA
FLA
LRA
INSTALLER NOTE:
WITH HEATER AND POWER EXHAUST. MARKSPACE "CHECK HERE" FOR MODEL USED.
AND POWER EXHAUST.
2.HEATERS ARE MANUFACTURED BY EMERSON HEATING PRODUCTS OR TUTCO ELECTRIC.
ELECTRICAL DATA FOR ACCESSORY POWER EXHAUST ONLY
ACCESSORYPOWER EXHAUST
MODEL NUMBER
CHECK
HERE
VOLTS PH HZ MIN CKTAMPS
FUSE ORHACR
BREAKERPER NEC
MAXIMUMOVERCURRENTPOROTECTION
DEVICE
MINIMUMUNIT
DISCONNECT
FLA
LRA
FLA
EXHAUSTPOWER
FUSE ORHACR
BREAKERPER NEC
MAXIMUMOVERCURRENTPOROTECTION
DEVICE
MINIMUMUNIT
DISCONNECT
SINGLE PTBOX MODELNUMBER
FLA
LRA
FLA
LRA
FLA
LRA
FLA
LRA
FLA
LRA
VOLTS PH HZ MIN CKTAMPS
SINGLE PTBOX MODELNUMBER
SINGLE PTBOX MODELNUMBER
SINGLE PT
50TC-A06A2A5A0A0A0
28.128
146
-/-
-/-
-/-
-/-
-/-
40 -/-
40/40
40/45
60/60
70/80
80/90
146/146
CRPWREXH_
146/146
146/146
28/28
33/37
146/146
47/52
59/66
146/146
72/82
28.1/28.4
36.3/40.5
50.6/57.0
63.6/72.0
77.9/88.6
102A208/240
3 60 13.6/15.6
-
104B208/240
3 60 21.9/25.3
-
105A208/240
3 60 33.4/38.5
037
104B+104B208/240
3 60 43.8/50.5
038
104B+105A208/240
3 60 55.2/63.8
038
*50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0*
C10532
Fig. 2 -- Unit Informative Data Label, Power Exhaust Installed
CRHTR,CRSIN
8
TB10NOTE: TB10’s are not used on AC--1 size 16 and 180,HP--1 size 14 and 150, AC--2 size 14, and HP--2 size 12.
On larger 208/230-3-60 units, the MOCP rating for thebase cooling circuit exceeds 60-A. On these applications,the single point box kit contains two small single-poleterminal blocks that are installed in the main control box.Minor relocation of wiring results in separating the indoorfan motor load from the main power circuit, allowing thisload to be protected with a second fuse set. See singlepoint box kits CRSINGLE043A00, 045A00, 049A00,051A00, 053A00 and 054A00. (Units AC--1 size 14 and150 and HP--1 size 12 and 121, AC--2 size 12, HP--2 size09 use only one TB10 block to separate Compressor 2 andoutdoor fan motor loads from main unit circuit).
Single Point Box ContentsSee Package Content tables for a list of componentsincluded in each single point box kit. Note the heightdifferences and their use in specific size units.
Control WiringHeater modules contain one or two heater controlcontactors. If two heater modules are installed, or atwo-circuit heater module is installed, the cooling unit(AC type) can be connected for one-stage or two-stageheating control. On all heat pump units (HP type), allheater contactors will be connected to providesecond-stage heating control.
GENERAL INSTALLATIONSEQUENCE
1. Pre-stage heater packages and single point boxes byplacing the required component cartons at each unit.
2. Check the heater sales package number and singlepoint box part number (if used) against the partnumbers on the unit’s infoplate. See Fig. 1 and 2for typical data.
3. Install the SPB and connect power wiring tap con-ductors to field power terminals in main controlbox.
4. Install the electric heater module(s) and connectheater power conductors to single point box or mainunit control box per appropriate connections figure.(See Appendix A and B.) On AC--1 15 ton, AC--212--1/2 ton, HP--1 12--1/2 ton and HP--2 10 tonmodels with factory installed non--fused disconnectremove lead side factory wiring. Re--size wires perunit nameplate data with accessory electric heat.
5. Connect the heater control contactors to unit termin-al block TB4.
6. Mark the unit infoplate to indicate which heatermodule(s) have been installed.
7. Note the required wire size ampacity (WSA) for thefield power supply conductors. Select and installsuitable field power conductors from external safetydisconnect to unit power connection points, or con-firm wiring already provided is suitable for requiredWSA.
All Units Except HP--1 Size 14 and 150, HP--2Size 12,AC--1 Size 16 and 180, AC--2 Size 14The following text covers installation of single pointboxes and electric heaters in all units EXCEPT the HP-1size 14 and 150, HP--2 Size 12, AC--1 Size 16 and 180,AC--2 Size 14. For instructions on these units, skip topage 14.Check sales packages – Following the project drawingschedule tables or submittal documents, select thescheduled heaters and single point boxes (if used) andplace at each unit.Compare the sales package number(s) for scheduledheater modules against the approved usage table on theunit’s infoplate. See Fig. 1 and 2 for typical plate data. Ifthe scheduled heater usage does not appear on the unitinfoplate label, STOP. Contact the project engineer or thelocal distributor sales office for clarification.Open the cartons and inspect for damage.
Installing Single Point Box(CRSINGLE037A00--054A00)
1. If power is already connected to unit, disconnect allpower to the unit per correct lock--out/tag--out pro-cedures.
2. Remove indoor and outdoor access panel. (See Fig.3 and 4.) Save panel and screws.
DISCONNECT MOUNTINGLOCATION
UNIT BLOCK-OFFPANEL
OUTDOORACCESS PANEL
INDOORACCESSPANEL
MAX. TEMP/STATIC LABEL
C11510
Fig. 3 -- Typical Access Panel Location(AC--1/HP--1 3 to 6 Ton, AC--2/HP--2 3 to 5 Ton)
DISCONNECT MOUNTINGLOCATION
UNITBLOCK-OFFPANEL
OUTDOORACCESS PANEL
INDOORACCESSPANELMAX. TEMP/
STATIC LABEL
C11511
Fig. 4 -- Typical Access Panel Location(AC--1 71/2 to 121/2 Ton, AC--2 6 to 10 Ton,HP--1 71/2 to 10 Ton, HP--2 6 to 8.5 Ton )
CRHTR,CRSIN
9
HEATERMOUNTINGBRACKET
HEATERMODULE(LOCATION 2)
HEATERMODULE(LOCATION 1)
SINGLE POINT BOX(NOT SHIPPED WITHUNIT)
HEATERCOVERS
MAINCONTROLBOX
CENTERPOST
C11514
(Size 04--06 and 036--060)
HEATERCOVERS
HEATERMOUNTINGBRACKETHEATER
MODULE(LOCATION 2)
HEATERMODULE(LOCATION 1)
MAINCONTROLBOX
SINGLE POINT BOX(NOT SHIPPED WITHUNIT)
CENTERPOST
C11515
(Size 07--15 and 072--180)
Fig. 5 -- Typical Component Location
ALLIED PA
MODEL NO.
ERIAL NO.
CORP.
1113
2123
OD
22.2
3123
ISTED AIRNDITIONINGUIP ACCESS 346N.
P / N 2- 5610-4 REV
1113
2123
CONTROLBOX
BUSHING
SINGLEPOINT BOXMOUNTINGSCREWS
FOAMBUSHING
DRIP BOOTBRACKETMOUNTINGSCREWS
HEATERRELAYS
POWERWIRES
HEATERMOUNTINGSCREWS
C08136
Fig. 6 -- Typical Single Point Kit Installation
3. Remove control box cover and center post. Savescrews. (See Fig. 5.)
4. If unit does not have the factory--installed discon-nect or HACR option or has not had field powerwiring connected, skip to Step 5.When unit is equipped with factory--installed dis-connect or HACR or has field power wiring connec-ted, disconnect the power leads at the control boxterminals and withdraw the conductors from thecontrol box.
5. Add seal strip to the rear bottom corner of the con-trol panel as shown in Fig. 7. Foil tape open screwholes on the back of the single point box as shownin Fig. 7. Different single point boxes will have dif-ferent screw holes open.
6. All bushings in the area of the control box wherethe single point box (SPB) mounts, must be re-moved prior to securing the SPB to the control box.(See Fig. 8.) Also, for units installed in the snowbelt, all unplugged holes in the bottom of the con-trol box which are not used must be plugged beforeinstalling the SPB. Use foil tape or reinstall thebushings from the outside of the control box prior tosecuring the SPB. (See Fig. 9.)
7. Remove the single point box cover. Secure singlepoint box to the underside of the control box withthe 2 screws provided. (See Fig. 6.) Re--install bush-ing on the SPB tap conductors. (See Fig. 9.)
8. Secure the rainshield (conduit drip boot bracket) as-sembly to the back of the single point box with 2 ofthe screws provided. (See Fig. 6.) The channel por-tion of the bracket assembly extends to the top pan-el behind the control box. Secure all wires to brack-et with field--supplied wire tie as shown. (See Fig.11.)
Seal Bottom Corner
Seal Back Corner
Foil Tape LocationsC101085
Fig. 7 -- Seal Strip and Foil Tape Locations
CRHTR,CRSIN
10
C09005
Fig. 8 -- Control Box -- Bushings to Remove
C09006
Fig. 9 -- Bushings Replaced from Outside Control Box
9. Connect power tap conductors to unit main controlbox.a. Single point boxes with two or three tap con-
ductors--Route the tap conductors (with bushingadded per Step 5) into the unit main control box.Connect the power tap conductors to the desig-nated terminals in the unit’s control box for fieldpower connections. Refer to the wiring diagramin the unit, to unit installation instructions forField Power Wiring Connections or to AppendixA or B.
b. Single point boxes with six tap conductors(CRSINGLE043A00, 045A00, 049A00, 051A00,053A00 and 054A00)(1.) All units EXCEPT AC--1 size 14 and 150
and HP--1 size 12 and 121These single point boxes include two sets ofthree--lead power tap conductors connectedto two separate fuse blocks. These kits alsoinclude two terminal blocks (TB10A andTB10B) and attachment screws. Mount
these terminal blocks in the unit’s controlbox next to compressor contactor C1. (SeeAppendix A or B.)S Relocate these wires:
At IFC terminal 13, disconnectCompressor 1 BLU and Compressor 2ORN leads; reconnect at TB10A.At C1 terminal 13, disconnect ID FanYEL lead; reconnect at TB10B.At C1 terminal 11, disconnect BLKjumper; reconnect to IFC terminal 11.
S Route the first set of tap conductors(attached at upper fuse block, withbushing per Step 5) into the main controlbox; connect at:BLK: C1 terminal 11YEL: C1 terminal 13BLU (long lead with terminal): TB10A
S Route the second set of tap conductors(attached at second fuse block) into themain control box; connect at:BLK: IFC terminal 11YEL (long lead with terminal): TB10BBLU: IFC terminal 13
(2.) Units AC--1 size 14 and 150 and HP--1 Size12 and 121, AC--2 size 12, HP--2 size 09OnlyMount one TB10 terminal block in theunit’s control box between compressor con-tactors C1 and C2. (See Fig. 10.)S Relocate these wires:
At IFC terminal 13, disconnect Com-pressor 2 ORN and OFM BLU leads; re-connect at TB10.
S Remove these leads:At C1--11, remove BLK jumper toC2--11. Discard.At C1--13, remove YEL jumper toC2--13. Discard.
S Route the first set of tap conductors (at-tached at second fuse block, with bush-ing per Step 5) into the main controlbox; connect at:BLK: C1 terminal 11YEL: C1 terminal 13BLU: IFC terminal 13
S Route the upper set of tap conductors(attached at second fuse block) into themain control box; connect at:BLK: C2 terminal 11YEL: C2 terminal 13BLU: TB10
Installing Electric Heater(CRHEATER101A00--109A00,CRHEATER110A--119A00CRHEATER264A00--269A00, 299A00CRHEATER297A00, 298A00, 301A00)
1. Remove heater cover(s) from heater mounting.bracket. Save screws.
CRHTR,CRSIN
11
NOTE: For CRHEATER101A00--109A00, 297A00,298A00, and 301A00 skip Steps 2 and 3.
2. Install heater slide bracket(s) from the heater kitthrough the bottom of the heater mounting hole(s)and fasten each with the two screws provided. (SeeFig. 13.)
NOTE: Modules CRHEATER105A00,CRHEATER109A00, CRHEATER297A00,CRHEATER298A00, CRHEATER301A00,CRHEATER112A00, CRHEATER114A00,CRHEATER115A00, and CRHEATER119A00 are keyedand must be installed in location 1 even when used as partof a 2--module option. (See Fig. 12 for AC--1 size 04 to 07and 036 to 072, AC--2 size 04 to 06, HP--1 size 04 to 07and 036 to 072, HP--2 size 04 to 06 units or Fig. 13 for
AC--1 size 08 to 14 and 090 to 150, AC--2 size 07 to 12,HP--1 size 08 to 12 and 090 to 121, HP--2 Size 07 to 09units.)
NOTE: Modules CRHEATER265A00 throughCRHEATER269A00 (480--v, used on AC--2 and HP--2 size07 only), CRHEATER299A00 (600--v, used on AC--2, size07 only), are keyed and must be installed in location 2. Inaddition, these modules are always used as a singlemodule option. (See Fig. 14)
3. To install module, engage flange on heater withtrack in unit and slide heater through mountingbracket opening. Fasten heater module to heatermounting bracket with the 4 screws saved from Step1. (See Fig. 13.)
HEATER012A
CIR#1
CIR#2
HEATER017A
C101084
Fig. 10 -- TB10 Locations and ConnectionsCRHTR,CRSIN
12
CONDUIT CONDUITDRIP BOOT
WIRE TIE
C—
CO
MM
30V—
OR
200V—
RD
OV
—Y
LD
24V 75VA
BD
236BN
—T
RA
N 3O
—B
V2075
E 60 H
Z 30-8703
C08417
Fig. 11 -- Typical Conduit Installation
4. Single--phase heater conversion208/230--v heaters CRHEATER101A00 through104B00 are factory--wired for 3--phase applicationsbut can be converted to single--phase by changingone wire as described below.Three--phase applications: Skip to Step 5. Forsingle--phase applications, rewire the heater as fol-lows (Fig. 15 and Fig. 16):a. Connect 10--gauge red wire to splice connector.b. Remove yellow wire from heater contactor ter-
minal 11 and connect to splice connector.c. Using the wire tie provided, fasten red wire to
heater power wire harness near existing wire tieon heater module. This provides strain relief forthe red wire.
KEY FOR MODULE LOCATON 1
C09010
Fig. 12 -- Typical Electric Heat Installation(AC--1 Sizes 04 to 07 and 036 to 072, AC--2 Sizes 04--06,
HP--1 Sizes 04--07 and 036 to 072, HP--2 Sizes 04--06)
TRACK
FLANGE
HEATERSLIDE
TRACK SCREWS
KEY FOR MODULE LOCATION 1
C10557
Fig. 13 -- Typical Module Installation(AC--1 Sizes 08 to 14 and 090 to 150, AC--2 Sizes 07--12,
HP--1 Sizes 08--12 and 090 to 121, HP--2 Sizes 07--09)
C11513
Fig. 14 -- Heater Bracket Keyway(AC--2, HP--2 Size 07 and 14 Units Only)
LEGENDHR -- Heater RelayHTR -- HeaterLS -- Limit Switch
C08419
Fig. 15 -- Single--Phase Heater Wiring
CRHTR,CRSIN
13
MODEL NO.
ERIAL NO.
1113
2123
OD
22.2
3123
ISTED AIRNDITIONINGUIP ACCESS 346N.
P / N 2- 5610-4 REV
RED WIRE
SPLICECONNECTOR
HEATERPOWERWIREHARNESS
C08420
Fig. 16 -- Typical Single--Phase Wiring Installed
5. Route power wires from heater module(s) throughthe foam bushing in the center partition and into thesingle point box. (See Fig. 6.) Connect to terminalblock or fuse blocks per schematics in Appendix Aor B. See Tables at beginning of each Appendix toidentify the appropriate figure.
All heaters are single bank heaters exceptCRHEATER111A00, 112A00, 268A00, 269A00,and 301A00 which are dual bank heaters. Theseheaters will be wired as two heaters (i.e., 6 leads).Fusing is shown pictorially on the unit wiringschematic label.
If no single point box is required for the unit andheater combination, run the heater power supplywiring through the grommet holes to the main unitcontrol box’s field power connection points or tooptional factory--supplied disconnect.The optional factory--supplied disconnect has amaximum rating per Table 2. Above these a field--supplied disconnect is required.
6. Factory control wiring for heaters runs from unitcontrol box to terminal block TB--4, mounted in theheater compartment above module 1 location. (SeeFig. 5 and 19.) Connect the heater control wiring atTB--4. For AC--1 and AC--2 units, see Fig. 19. ForHP--1 and HP--2 units, see Fig. 20 except for AC--2,Size 06, 575V only See Fig. 17 and HP--2, Size 06,575V only, See Fig. 18.
Table 2 – Optional Factory Installed Disconnect Amp Ratings
ChassisGroup Unit Size Volts Amp
Rating
AC-1HP-1
04-07230 80460/575 60
AC-2HP-2 04-06
230 80460/575 60
AC-1 08-14230
80460/575
AC-2 07-12230
80460/575
HP-1 08-12230
80460/575
HP-2 07-09230
80460/575
AC-1 16230 200460/575 100
AC-2HP-1 14
230 200460/575 100
HP-2 12230 200460/575 100
C11555
Fig. 17 -- Accessory Electric Heater Control Connections(AC--2, Size 06, 575V only)
CRHTR,CRSIN
14
C11554
Fig. 18 -- Accessory Electric Heater Control Connections(HP--2, Size 06, 575V only)
LCTB
CONTLBOARD
ORN
BRN
FieldConnections
HR1: On Heater 1 in Position #1HR2: On Heater 2 in Position #2 (if installed)
2
3
12
1 3
VIO
ORN VIO BRN
VIO BRN BRNVIO
2TB4
VIO HR2
HR1
BRN
VIO BRN
Elec Htr
C08331
Fig. 19 -- Accessory Electric Heater ControlConnections (AC--1 Except Size 16 and 180,
AC--2 Except Size 14)
DEFROSTBOARD
ORN
BRN
FieldConnections
E-HEAT
P3-3
1 3
ORN BRN
VIO BRN BRNVIO
TB4
VIO HR2
HR1
BRN
VIO BRN
Elec Htr
HR1: On Heater 1 in Position #1HR2: On Heater 2 in Position #2 (if installed)
C09013
Fig. 20 -- Accessory Electric Heater ControlConnections (HP--1 Except Size 12 and 121,
HP--2 Except Size 12)
MODEL NO.
ERIAL NO.
1113
2123
OD
3123
ISTED AIRNDITIONINGUIP ACCESS 346N.
P / N 2- 5610-4 REV
C08137
Fig. 21 -- Typical 3--Phase Wiring Installed
7. Replace the center post and secure the single pointbox to the center post with one screw. (See Fig. 6.)
8. Remove knockouts for appropriate size conduitfrom unit block--off panel and single point box. In-stall conduit (rigid or electrometallic tubing)through conduit drip boot as shown. (See Fig. 11.)Drip boot will accept conduit sizes 3/4--in. to 1--1/2inches. The drip boot eliminates the need for water-tight conduit fittings at the single point box.
NOTE: Supply wiring must comply with NEC (NationalElectric Code) and all local requirements.
CRHTR,CRSIN
15
9. Mark the appropriate block on the unit nameplatefor the accessory heater kW installed. Note the re-quired Minimum Circuit Ampacity (MCA) value forthis unit--heater combination. Ensure the fieldpower conductors are sized to handle this ampacity.
10. Place adhesive--backed wiring label on flanged sideof heater cover.
11. Fasten heater cover to heater module with 2 screwsprovided with heater. Flanges of cover should faceout.
12. Set manual reset limit switch (on supply fan hous-ing) by depressing button located between the ter-minals on the switch. (See Fig. 5.)
13. Close single point box cover and secure with onescrew.
14. Replace control box cover, using remainder ofscrews saved from Step 3 of Installing Single PointBox section on page 9.
15. Replace indoor and outdoor panels with screwssaved from Step 2 of Installing Single Point Boxsection on page 8. Place adhesive--backed Max. Air/Max. Static label on external panel that coversheaters. (See Fig. 3, 4, and 42.)
16. Turn on unit power.
HP--1 Size 14 and 150, HP--2 Size 12, AC--1Size 16 and 180 and AC--2 Size 14 ONLYThe following text covers installation of single pointboxes and electric heaters shown above. For instructionson all the smaller sizes, return to page 8.Check sales packages – Following the project drawingschedule tables or submittal documents, select thescheduled heaters and single point boxes (if used) andplace at each unit.
Compare the sales package number(s) for scheduledheater modules against the approved usage table on heunit’s infoplate. See Fig. 1 and 2 for typical plate data. Ifthe scheduled heater usage does not appear on the unitinfoplate label, STOP. Contact the project engineer or thelocal distributor sales office for clarification.Open the cartons and inspect for damage.
Install Single Point Box (CRSINGLE047A00,050A00--054A00)
1. Remove kits from boxes and verify that all of thecorrect parts have arrived undamaged.
2. If power is already connected to unit, disconnect allpower to the unit per correct lock--out/tag--out pro-cedures. Disconnect field power wiring or optionalfactory--installed disconnect or HACR power leadsat TB1 and withdraw the wiring from the unit con-trol box. On units with factory--installed disconnect,the factory supplied lead wires maybe of insuffi-cient size for accessory electric heat applications. Ifso, remove the lead side factory wiring. Re--sizewires per unit nameplate data with electric heat.
3. Remove outdoor access, control box, and left indooraccess panels from the unit. Fig. 22 shows the unitwith the panels already removed.
4. Optional – The center post may be removed to facil-itate wiring.
5. Remove the bushings and plug from the controlpanel per Fig. 23. Save the bushings and discard theplug.
6. Add seal strip to the rear bottom corner of the con-trol panel as shown in Fig. 24.
7. Foil tape open screw holes on the back of the singlepoint box as shown in Fig. 24. Different single pointboxes will have different screw holes open.
Control BoxAccessPanel
OutdoorAccessPanel
Heater Covers
LeftIndoorAccessPanel
C10170
Fig. 22 -- Typical Unit with Access Panels Removed
CRHTR,CRSIN
16
Single Point Box Mounting Screws
Plug Location
Bushings(Re-installed)
C10169
Fig. 23 -- Single Point Box Installation Details
Seal Bottom Corner
Seal Back Corner
Foil Tape LocationsC101085
Fig. 24 -- Seal Strip and Foil Tape Locations
8. Remove the cover from the single point box.9. Install the single point box under the control panel
with two screws down through the control panel(Fig. 23) and one screw (not shown) into the centerpost. (See Fig. 23.) Holes have been provided.Foam wire guides in the center post may have to beremoved. If center post was removed per step 4, thesingle point box will have to be screwed into itlater.
10. The single point box kit will contain two rain shieldbrackets, a larger bracket with boot seal and a smal-ler (shorter) bracket without a seal. Remove theseal from the larger bracket and push the conduitdrip boot seal into the short rain shield bracket. (SeeFig. 25.) Discard the larger bracket.
Conduit Drip Boot
Rain Shield BracketC10167
Fig. 25 -- Rain Shield Installation
11. Install the rain shield bracket to the left and behindthe single point box using the two screws and holesprovided.
12. Re--install the bushings removed in Step 5.13. Connect the tap conductors.
a. CRSINGLE047A00, 050A00 and 052A00Connect the blue, yellow, and black power tapconductors (pigtails) from the single point box tothe unit’s power terminal block TB--1 per unitlabel wiring schematic and per Appendix A or Band connection figures. A representative installa-tion of two 480V heaters and correspondingsingle point box is shown in Fig. 26, 27, and 28.
CRHTR,CRSIN
17
b. CRSINGLE051A00, 053A00 and 054A00These kits include two sets of tap conductors(blue, yellow and black pigtails) connected atfuse blocks 1 and 2. Connect these leads in par-allel to the unit’s power terminal block TB--1 perthe unit label wiring schematic and per Ap-pendix A or B and connection figures.(These kits also include two small terminalblocks (TB10). The TB10 blocks are not usedwith the HP--1 size 14 and 150 and HP--2 size12; discard.)
Install CRHEATER288A00--296A001. Remove and save the heater covers.2. Install heater slide track(s) from the heater kit
through the bottom of the heater mounting hole(s)and fasten each with the two screws provided. (SeeFig. 29.)
3. Install the heater(s) (Fig. 30, 230V shown) into theirmounting location(s) using the screws provided.Tables 3 and 4 give the correct heater location as afunction of heater size, voltage, and supply air flowdirection.
C10174
Fig. 26 -- Heater Wiring
CRHTR,CRSIN
18
C10172
Fig. 27 -- Typical Single Point Box Wiring
CRHTR,CRSIN
19
Single Point BoxPower Wires
C10175
Fig. 28 -- Typical Control Panel Wiring
Mounting ScrewsHeater Slide Track
C10198
Fig. 29 -- Heater Slide Track Installation
CRHTR,CRSIN
20
Dual ElementHeater Module
Heater Mount Locations
Single ElementHeater Module
C10168
Fig. 30 -- Typical Heaters
Table 3 – Heater Location for HorizontalReturn and Discharge*
HeaterkW Volts
Heater Slot Location
CRHEATERXXXX00 Left Right
288A 10.0 240 -- 288A
291A 16.5 240 291A --
288A + 291A 26.5 240 291A 288A
294A 33.5 240 -- 294A
288A + 294A 43.5 240 288A{ 294A
291A + 294A 50.0 240 291A 294A
294A + 294A 67.0 240 294A{ 294A
289A 10.0 480 -- 289A
292A 16.5 480 292A --
289A + 292A 26.5 480 292A 289A
295A 33.5 480 -- 295A
289A + 295A 43.5 480 289A{ 295A
292A + 295A 50.0 480 292A 295A
295A + 295A 67.0 480 295A{ 295A
290A 10.0 600 -- 290A
293A 16.5 600 293A --
290A + 293A 26.5 600 293A 290A
296A 33.5 600 -- 296A
290A + 296A 43.5 600 290A{ 296A
293A + 296A 50.0 600 293A 296A
296A + 296A 67.0 600 296A{ 296A* XXXX --- 4 digit heater in table. For example, a CRHEATER291A000 islisted as a 291A.{Remove Restrictor Plate to install in Left Slot Location. Use foil tape tocover holes.
Table 4 – Heater Location for VerticalReturn and Discharge*
HeaterkW Volts
Heater Slot Location
CRHEATERXXXX00 Left Right
288A 10.0 240 -- 288A
291A 16.5 240 291A --
288A + 291A 26.5 240 291A 288A
294A 33.5 240 -- 294A
288A + 294A 43.5 240 288A{ 294A
291A + 294A 50.0 240 291A 294A
294A + 294A 67.0 240 294A{ 294A
289A 10.0 480 -- 289A
292A 16.5 480 292A --
289A + 292A 26.5 480 292A 289A
295A 33.5 480
295A {(Supply ductopening =~31” x 16”)
295A(Supply ductopening =~36” x 30”)
289A + 295A 43.5 480 289A{ 295A
292A + 295A 50.0 480 292A 295A
295A + 295A 67.0 480 295A{ 295A
290A 10.0 600 -- 290A
293A 16.5 600 293A --
290A + 293A 26.5 600 293A 290A
296A 33.5 600 -- 296A
290A + 296A 43.5 600 290A{ 296A
293A + 296A 50.0 600 293A 296A
296A + 296A 67.0 600 296A{ 296A* XXXX --- 4 digit heater in table. For example, a CRHEATER291A000 islisted as a 291A.{ Remove Restrictor Plate to install in Left Slot Location. Use foil tape tocover holes.
CRHTR,CRSIN
21
4. Connect the heater control wiring to terminal blockTB4 (located to left of the heaters, see Fig. 40 and41.)TB4 has five terminals. (See Fig. 31 and 33.) Bot-tom row left terminal is “R Use”; it has a factoryRED connection. Bottom row right terminal is “CUse”; it has a factory BRN connection. For ACunits, top row left is designated as “W1 Use” ad hasfactory ORN connections. The top row center isdesignated as “W2 Use” and has factory VIO con-nections. For HP units, top row left and center ter-minals are designated “W2 Use” and have factoryORN connections. The fifth terminal is for field--option connection of a staging control.
CRHEATER288A00--293A00 HeatersThese heaters have two control wires: ORN forheater contactor and BRN for control common.Connect BRN wire(s) to TB4’s “C Use” terminal.(Second BRN wire will require use of the piggybackterminal on the factory BRN wire.) For AC units,connect heater ORN control wiring to ORN on TB4for 1st stage heating and for units with heater pack-ages, connect to VIO on TB4 for 2nd stage heating.(See Fig. 36.) For HP units, connect heater ORNcontrol wires(s) to an availabel terminal on TB4’s“W2 Use” group. (See Fig. 35.)
CRHEATER294A00--296A00 HeatersThese heaters have four control wires: ORN andVIO for heater contactors, RED for safety circuitpower and BRN for control common. Connect REDwire to TB4’s “R Use”. Connect BRN wire toTB4’s “C Use” terminal. For AC units with oneheater package that has these 4 control wires, con-nect heater ORN control wiring to ORN on TB4 for1st stage heating and to VIO on TB4 for 2nd stageheating.For AC units with 2 of these heater packages thathas 4 control wires, connect both the ORN and VIOcontrol wires from the heater to ORN on TB4 for 1st
stage heating and connect the ORN and VIO controlwires from the other heater to VIO on TB4 for 2nd
stage heating. (See Fig. 38.)For AC units with one of these heater packages thathas these 4 control wires plus a heater package thathas 3 control wires, connect both the ORN and VIOcontrol wires from the 4 control wire heater to ORNon TB4 for 1st stage heating and connect the ORNcontrol wire from the other heater with 3 controlwires to VIO on TB4 for 2nd stage heating.For HP units, connect ORN and VIO wires to TB4’s“W2 Use” terminals.(See Fig. 39.)
NOTE 4AND 6
RED
EHR
EHRORN
TRAN2 FROM POWER SCHEMATIC
24V BRN24V
CB
3.2 AMPS
BRN
GRN/YEL
24V
RED
BRN
1 0
1 0
8 6
FPT
BLK BLK
BRNBRN
BRN
RED
ELECTRICHEAT(ACCESSORY)SEE HEATER LABEL DIAGRAM
BRN
BRN
24V
5
TRAN1 FROM POWER SCHEMATIC
24V BRN24VGRN/YEL
CB
3.2 AMPS
BRNOFRVIO
TB4
3
ORN ORN
RED
C10561
Fig. 31 -- TB4 Wiring (HP Only)
C11127
Fig. 32 -- TB4 Wiring (AC Only)
NOTE:Optional Outdoor Temperature Controlat One Heater Stage – Move heater wire to this terminal and connect outdoor temperature switch between 2nd and 3rd terminals.
W2 Use
R Use C Use
C10604
Fig. 33 -- TB4 Terminal Use (HP Only)
NOTE:Optional Outdoor Temperature Controlat One Heater Stage – Move heater wire to this terminal and connect outdoor temperature switch between 2nd and 3rd terminals.
W1 Use
R Use C Use12 CONTROL
BOARD
8 CONTROLBOARD
VIOVIO
W2 Use
C11129
Fig. 34 -- TB4 Terminal Use (AC Only)
5. Cover the heater wiring with the heater covers perFig. 41.
6. If the center post was removed in Step 4 on page 14,reinstall the center post, screw the single point boxto the center post and replace any foam wire guidesper step 9.
7. Set manual reset limit switch (on supply fan hous-ing) by depressing button located between the ter-minals on the switch. (See Fig. 5 and 6.)
CRHTR,CRSIN
22
8. Replace all access panels, posts and covers removedin Steps 3 and 8 on page 14 and 15. Place adhesive--backed Max. Air/Max. Static label on external panelthat covers heaters. (See Fig. 4, 4, and 42.)
NOTE: Supply wiring must comply with NEC (NationalElectric Code) and all local requirements.
9. Mark the appropriate block on the unit nameplatefor the accessory heater kW installed. Note the re-quired Minimum Circuit Ampacity (MCA) value forthis unit--heater combination. Ensure the fieldpower conductors are sized to handle this ampacity.Check also that the unit disconnect size and theovercurrent protection device for the branch circuitconductors are suitable for this unit--heater combin-ation.
10. Run conduit through (rigid or EMT) the conduitdrip boot in the rain shield bracket to the singlepoint box. Provide an appropriate fitting to connectthe conduit to the single point box wall and groundappropriately. (See Fig. 26.) Drip boot will acceptsizes ¾--in to 1--1/2 in. The drip boot eliminates theneed for watertight conduit fittings at the singlepoint box.
11. Run wire through conduit connecting outside powerto the designated terminals at the top of the singlepoint box. Ground appropriately. (See Fig. 28.)
12. If all other work on the unit is done, reapply powerper lock--out/tag out procedures.
TRAN2
HC1
HC1
HEATER 1
HEATER 2 (IF INSTALLED)
BRN
BRN
BRN
TBTS
TS
TB4
ORN
ORN
RED ORN
ORNEHR
TB4
RED
C10562
Fig. 35 -- Electric Heater Control Connections--Heat Pump with 1 or 2 CRHEATER288A00--293A00
HC1
HC1
HEATER 1
*HEATER 2 (IF INSTALLED)
BRN
BRN
BRN
TB4
TB4
ORN
ORN
RED
8 12CONTROLBOARD
U
VIO
CONTROLBOARD
CONTROLBOARD
3
CONTROLBOARD
2
* 2 stage heat shown. Connect orange wire fromHeater 2 HC1 to orange on TB4 for 1 stage heat.
LS1ORN
LS1 LS2ORNORN ORN
LS1ORN
LS1 LS2ORNORN ORN
C11134
Fig. 36 -- Electric Heater Control Connections -- Air Conditioner with 1 or 2 CRHEATER288A00--293A00
CRHTR,CRSIN
23
TRAN2
HC2
HC1
HCR2
HCR1 BRN
BRN
BRN
BRN
BRN BRN
BRN
HCR1
HCR2
LS
RED
RED
TB4
RED ORN
ORNEHR
VIO
ORN
TB4
RED
TB
C10563
Fig. 37 -- Electric Heater Control Connections--Heat Pump with 1 CRHEATER294A00--296A00
HC2
HC1
HCR2
HCR1 BRN
BRN
BRN
BRN
BRN BRN
HCR1
HCR2
RED
ORN
VIO
ORN
TB4
TB4
12 CONTROLBOARD
U
8
CONTROLBOARD
CONTROLBOARD
3
CONTROLBOARD
12 VIO
RED
REDLS1LS1 LS2
RED
C11135
Fig. 38 -- Electric Heater Control Connections -- Air Conditioner with 1 CRHEATER294A00--296A00
CRHTR,CRSIN
24
TRAN2
HC2
HC1
HC1
HCR2
HCR1
BRN
BRN
BRN
BRN
BRN
BRN BRN
TB
HCR2
HCR1LS
RED
RED
TB4
RED ORN
EHRORN
ORN
VIO ORN
TB4
LS
1-STG HEATER
2-STG HEATER
BRNRED
C10564
Fig. 39 -- Electric Heater Control Connections--Heat Pump with 1 CRHEATER288A00--293A00Plus 1 CRHEATER294A00--296A00 (2--Stage Heater)
Terminal Block 4(TB4)
Heater Cover
C10173
Fig. 40 -- Heater Wiring
CRHTR,CRSIN
25
Terminal Block 4(TB4)
Heater Covers
C10171
Fig. 41 -- Heater Wiring and Covers
C11512
Fig. 42 -- Max. Air Temp/Max. Ext. Static
CRHTR,CRSIN
26
APPENDIX ACOOLING APPLICATIONS
SPBCRSINGLEnnnA00
AC---1 Units AC---2 Units04---07036---072
08090
09---12102---121
14150 04---06 07 08---09
NONE Fig. 43 Fig. 43037 Fig. 44 Fig. 44038 Fig. 45 Fig. 45040 Fig. 46 Fig. 46042 Fig. 44 Fig. 44043 Fig. 47 Fig. 47044 Fig. 48045 Fig. 49046047 Fig. 44 Fig. 44 Fig. 44049 Fig. 50 Fig. 51 Fig. 50050 Fig. 52 Fig. 52 Fig. 52051 Fig. 53 Fig. 54 Fig. 53
Unit Control BoxC IFC
13 13 11
HEATER
HeaterWires
Unit DisconnectMOCP 60-A Max
FieldPowerConductors
C10484
Fig. 43 -- AC and Heat Pump No Single Point Box
CRHTR,CRSIN
27
Unit Control BoxHP-1 SIZE 14 AND 150 ONLY
ALL UNITSUnit Control BoxEXCEPT HP-1
SIZE 14 AND 150C IFC
TB
HEATER
HEATER #2IF USED
TBI
11 12 13
11 1313
BLK YEL BLU
BLK YEL BLU
BLK
YEL
BLU
HEATERWIRESSPB
037A042A047A
TAPCONDUCTORS
FIELDPOWERCONDUCTORS
UNIT DISCONNECTMOCP 60-A MAX
C10485
Fig. 44 -- AC and Heat Pump Single Point BoxCRSINGLE037A00, 042A00, 047A00
Unit Control BoxC IFC
FU2HEATER
FU3HEATER
!!"5"5
HeaterWires
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
FieldPower Conductors
Tap Conductors
13 13 11
Field TapPower Conductors
Heater 104 #2if used
Heater 104 #1or Heater 105
C10486
Fig. 45 -- AC Single Point Box CRSINGLE038A00
CRHTR,CRSIN
28
Unit Control BoxC IFC
FU2HEATER
FU3HEATER
HeaterWires
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
FieldPower Conductors
Tap Conductors
13 13 11
C10487
Fig. 46 -- AC Single Point Box CRSINGLE040A00 Single Phase
Unit Control BoxC
11 13 11 13
IFCTB-10BTB-10A
FU2HEATER111A or 112A
CIR 1
CIR 2
BLU BLUBLK BLKYEL YEL
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
ALT.TWO HEATER
MODULESFactory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
FU3
C10489
Fig. 47 -- AC Single Point Box CRSINGLE043A00
CRHTR,CRSIN
29
Unit Control BoxC IFC
TB
FU2HEATER
FU3HEATER
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
11
TapConductors
FieldPowerConductors
HeaterWires
13 13
C10490
Fig. 48 -- AC Single Point Box CRSINGLE044A00
Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.
Unit Control Box C IFC
FU2HEATER111A or 112A
CIR 1
CIR 2
HEATER
11 13 11 13
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
BLU BLUBLK BLKYEL YEL
TB-10BTB-10A
FU3
FU4
C10491
Fig. 49 -- AC Single Point Box CRSINGLE045A00
CRHTR,CRSIN
30
Unit Control BoxC
11 13 11 13
IFCTB-10BTB-10A
FU2HEATER111A or 112A
CIR 1
CIR 2
BLU BLUBLK BLKYEL YEL
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
ALT.TWO HEATER
MODULESFactory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
FU3
C10489
Fig. 50 -- AC Single Point Box CRSINGLE049A00(Except Size 14 and 150)
Unit Control BoxC2 TB-10 C1 IFC
FU2HEATER112A
CIR 1
HEATER117A or 110A
CIR 2
$$&:&:
11 13 11 13 13
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
BLU BLUBLK BLKYEL YEL
FU3
C10566
Fig. 51 -- AC Single Point Box CRSINGLE049A00(Size 14 and 150 Only)
CRHTR,CRSIN
31
Unit Control BoxC IFC
TB
FU2HEATER
FU3HEATER
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
11
TapConductors
FieldPowerConductors
HeaterWires
13 13
C10490
Fig. 52 -- AC Single Point Box CRSINGLE050A00
Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.
Unit Control Box C IFC
FU2HEATER111A or 112A
CIR 1
CIR 2
HEATER
11 13 11 13
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
BLU BLUBLK BLKYEL YEL
TB-10BTB-10A
FU3
FU4
C10491
Fig. 53 -- AC Single Point Box CRSINGLE051A00(Except Size 14 and 150)
CRHTR,CRSIN
32
Unit Control Box C2 C1 TB-10 IFC
FU2HEATER112A
CIR 1
CIR 2
HEATER117A or 110A
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.
11 13 11 13 13
FU3
FU4
C10567
Fig. 54 -- AC Single Point Box CRSINGLE051A00(Size 14 Only and 150)
CRHTR,CRSIN
33
APPENDIX BHEAT PUMP APPLICATIONS
SPBCRSINGLEnnnA00 HP---1 Units HP---2 Units
04---07036---072
08---09090---102
12121
14150 04---06
NONE Fig. 43* Fig. 43*037 Fig. 44* Fig. 44038 Fig. 55 Fig. 55039 Fig. 56040 Fig. 57 Fig. 57041 Fig. 58 Fig. 58047 Fig. 44* Fig. 44* Fig. 44*049 Fig. 59 Fig. 60050 Fig. 61 Fig. 61 Fig. 62051 Fig. 63 Fig. 64 Fig. 65052 Fig. 66 Fig. 66 Fig. 67053 Fig. 68 Fig. 69 Fig. 70054 Fig. 71 Fig. 72 Fig. 73
* Figure is in Appendix A
Unit Control Box C IFC
!! !!
FU2
HTR
7
TapConductors
FieldPowerConductors
HeaterWires
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
BLUBLK YEL
11 13 11 13
FU3
C10497
Fig. 55 -- Heat Pump Single Point Box CRSINGLE038A00
CRHTR,CRSIN
34
Unit Control BoxC IFC
!! !!
FU2
HTR 1
HTR 2
HeaterWires
Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.
TapConductors
FieldPowerConductors
BLUBLK YEL
11 13 11 13
FU3
FU4
C10498
Fig. 56 -- Heat Pump Single Point Box CRSINGLE039A00
Unit Control Box C
FU2
HTR 1
HeaterWires
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
FieldPowerConductors
TapConductors
BLK YEL
11 23
FU3
C10499
Fig. 57 -- Heat Pump Single Point Box CRSINGLE040A00 1--Phase
CRHTR,CRSIN
35
Unit Control BoxC
!! !!
FU2
HTR 1
HTR 2
11
TapConductors
FieldPowerConductors
HeaterWires
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.
23
FU3
C10500
Fig. 58 -- Heat Pump Single Point Box CRHEATER041A00 1--Phase
Unit Control BoxC IFC
FU2
HEATER 117A OR 110A
08 09 12
:
TB-10A
HeaterWires
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
TapConductors
FieldPowerConductors
11 13 11 13
BLU BLUBLK BLKYEL YEL
TB-10B
FU3
C10501
Fig. 59 -- Heat Pump Single Point Box CRHEATER049A00(Except Size 12 and 121)
CRHTR,CRSIN
36
Unit Control BoxC2 C1 IFC
FU2
FU3
HEATER 117A OR 110A
11 13 11 13 13
TB-10
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
BLUBLK YEL BLUBLK YEL
Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.
HEATERWIRES
C10568
Fig. 60 -- Heat Pump Single Point Box CRHEATER049A00(Size 12 Only and 121)
Unit Control Box C IFC
TB
FU2
HEATER 116A
HEATER 1 HEATER 114A
08 08 09 09 12 12
NOTE: ALL HEATERS CONNECT TO FU3
!!"7"711 13 13
TapConductors
FieldPowerConductors
BLU BLUBLK BLKYEL YEL
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU3.This wiring not illustrated for simplicity in this figure.
HeaterWires
6 Wires
FU3
C10502
Fig. 61 -- Heat Pump Single Point Box CRHEATER050A(Except Size 14 and 150)
CRHTR,CRSIN
37
Unit Control Box
TB
FU2
HEATER CIR 1 289A
CIR 2 HEATER 292A
14 14
NOTE: ALL HEATERS CONNECT TO FU3
11 12 13
TB1
BLUBLK YEL
HEATERWIRES
6 WIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU3.This wiring not illustrated for simplicity in this figure.
FU3
C10569
Fig. 62 -- Heat Pump Single Point Box CRHEATER050A00(Size 14 Only and 150)
!"
Unit Control BoxC IFC
FU2
FU3
CIR 1
FU4HEATER 112A
CIR 2
11 13 11 13
HeaterWires
Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.
BLU BLUBLK BLKYEL YEL
TapConductors
FieldPowerConductors
TB-10A TB-10B
C10503
Fig. 63 -- Heat Pump Single Point Box CRHEATER051A00(Except Size 12--14 and 121--150)
CRHTR,CRSIN
38
Unit Control Box C2 TB-10 C1 IFC
FU2
HEATER 112A
CIR 1
HEATER 117A or
CIR 2 110A
11 13 11 13 13
BLUBLK YEL BLUBLK YEL
Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
FU3
FU4
C10570
Fig. 64 -- Heat Pump Single Point Box CRHEATER051A00(Size 12 Only and 121)
Unit Control Box
FU2
FU3
FU4 HEATER 291A
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.
11 12 13
BLUBLK YEL
TB1
C10571
Fig. 65 -- Heat Pump Single Point Box CRHEATER051A00(Size 14 Only and 150)
CRHTR,CRSIN
39
!"
Unit Control Box C IFC
TB
FU3
HEATER 1
HEATER 2
08 09 12
HeaterWiresFactory wiring connects line-side
of TB to line-side terminals on FU2-FU4.This wiring not illustrated for simplicity in this figure.
TapConductors
FieldPowerConductors
11 13 13
BLU BLUBLK BLKYEL YEL
FU4
FU2
C10504
Fig. 66 -- Heat Pump Single Point Box CRHEATER052A00(Except Size 14 and 150)
Unit Control Box
TB
FU2
FU3
CIR 1
FU4 HEATER 294A
CIR 2
11 12 13
TB1
BLUBLK YEL
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU4.This wiring not illustrated for simplicity in this figure.
C10572
Fig. 67 -- Heat Pump Single Point Box CRHEATER052A00(Size 14 and 150 Only)
CRHTR,CRSIN
40
Unit Control BoxC IFC
TB
FU2
FU3
CIR 1
FU4HEATER 112A
CIR 2
FU5
HEATER 117A
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU5.This wiring not illustrated for simplicity in this figure.
TB-10BTB-10A
11 13 11 13
TapConductors
FieldPowerConductors
HeaterWires
BLU BLUBLK BLKYEL YEL
C10505
Fig. 68 -- Heat Pump Single Point Box CRHEATER053A00(Except Size 12--14 and 121--150)
CRHTR,CRSIN
41
Unit Control Box C2 C1 IFC
TB
FU2
FU3 HEATER 117A or 110A (when used)
FU4HEATER 112A
CIR 1
FU5
CIR 2
TB-10
11 1113 13 13
TAPCONDUCTORSFIELD
POWERCONDUCTOR
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU5.This wiring not illustrated for simplicity in this figure.
BLUBLK YEL BLUBLK YEL
HEATERWIRES
C10573
Fig. 69 -- Heat Pump Single Point Box CRHEATER053A00(Size 12 and 121 Only)
CRHTR,CRSIN
42
Unit Control Box
TB
FU2
FU3
FU4
HEATER 288A
CIR 1
HEATER 294A
FU5
HEATER 291A
CIR 2
HEATERWIRES
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU5.This wiring not illustrated for simplicity in this figure.
BLUBLK YEL
11 12 13
TB1
1414
C10574
Fig. 70 -- Heat Pump Single Point Box CRHEATER053A00(Size 14 and 150 Only)
CRHTR,CRSIN
43
Unit Control BoxC TB-1OB IFC
!!!! !!!!
TapConductors
TB
FU2
FU3
FU4
CIR 1
FU5HEATER
112A
CIR 2
FU6
HEATER 117A
HeaterWires
BLU BLUBLK BLKYEL YEL
TB-1OA
11 13 11 13
FieldPowerConductors
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU6.This wiring not illustrated for simplicity in this figure.
C10506
Fig. 71 -- Heat Pump Single Point Box CRHEATER054A00(Except Size 12--14 and 121--150)
CRHTR,CRSIN
44
Unit Control Box C2 TB-10 C1 IFC$& $&
TB
FU2
FU3
FU4
CIR 1
FU5 HEATER 112A
CIR 2
FU6
HEATER 117A
or 110A
HeaterConductors
911 13 11 13 13
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU6.This wiring not illustrated for simplicity in this figure.
BLUBLK YEL BLUBLK YEL
C10575
Fig. 72 -- Heat Pump Single Point Box CRHEATER054A00(Size 12 and 121 Only)
CRHTR,CRSIN
45
Unit Control Box
TB
FU2
FU3
FU4
HEATER 288A or 291A
FU5
CIR 1
HEATER 294A
FU6
CIR 2
11 12
TB1
13
BLUBLK YEL
TAPCONDUCTORS
FIELDPOWER
CONDUCTOR
HEATERWIRES
Factory wiring connects line-sideof TB to line-side terminals on FU2-FU6.This wiring not illustrated for simplicity in this figure.
14
C10576
Fig. 73 -- Heat Pump Single Point Box CRHEATER054A00(Size 14 and 150 Only)
CRHTR,CRSIN
46
APPENDIX CELECTRIC HEATER DATA
CRHEATERXXXX00
SALESPKG
NUMBER
HEATERMODELNUMBER
VOLTS KW FLA1---PH
FLA3---PH
QTYCIRS
50TC558JRAS
50TCQ548JRHS
50HC551J
50HCQ549J
Used onAC---1 HP---1 AC---2 HP---2
101A 001A 208 / 240 3.3 / 4.4 15.9 / 18.6 9.4 / 10.6 1
04---07036---072
04---07036---072
04---06 04---06
102A 002A 208 / 240 4.9 / 6.5 23.6 / 27.3 13.8 / 15.7 1
103B 003B 208 / 240 6.5 / 8.7 31.2 / 36.2 18.1 / 20.7 1
104B 004B 208 / 240 7.9 / 10.5 38.0 / 43.8 22.2 / 25.3 1
105A 005A 208 / 240 12.1 / 16.0 --- --- --- 33.6 / 38.4 1
106A 006A 480 6.0 --- --- --- 7.0 1
107A 007A 480 8.8 --- --- --- 10.5 1
108A 008A 480 11.5 --- --- --- 13.8 1
109A 009A 480 14.0 --- --- --- 16.8 1
297A 297A 600 10.0 --- --- --- 9.2 1
298A 298A 600 15.0 --- --- --- 13.8 1
301A 301A 600 25.0 --- --- --- 23.1 2 06 06
110A 010A 208 / 240 12.0 / 16.0 --- --- --- 33.3 / 38.5 1
08---14090---150
08---12090---121 07---12 07---09
111A 011A 208 / 240 18.6 / 24.8 --- --- --- 51.7 / 59.7 2
112A 012A 208 / 240 24.0 / 32.0 --- --- --- 66.7 / 77.1 2
113A 013A 480 16.5 --- --- --- 19.8 1
114A 014A 480 27.8 --- --- --- 33.4 1
115A 015A 480 33.0 --- --- --- 39.7 1
116A 016A 480 13.9 --- --- --- 16.7 1
117A 017A 208 / 240 7.8 / 10.4 --- --- --- 21.7 / 25.0 1
118A 018A 600 18.0 --- --- --- 17.0 1
119A 019A 600 36.0 --- --- --- 34.0 1
264A 264A 208 / 240 4.9 / 6.5 --- --- --- 13.5 / 15.6 1
07 07
265A 265A 480 6.0 --- --- --- 7.2 1
266A 266A 480 11.5 --- --- --- 13.8 1
267A 267A 480 14.0 --- --- --- 16.8 1
268A 268A 480 23.0 --- --- --- 27.7 2
269A 269A 480 25.5 --- --- --- 30.7 2
288A 288A 208 / 240 7.5 / 10 --- --- --- 21.3 / 24.5 1
16180
14150 14 12
289A 289A 480 10.0 --- --- --- 12.1 1
290A 290A 600 10.0 --- --- --- 9.6 1
291A 291A 208 / 240 12.4 / 16.5 --- --- --- 34.5 / 39.7 1
292A 292A 480 16.5 --- --- --- 19.9 1
293A 293A 600 16.5 --- --- --- 15.9 1
294A 294A 208 / 240 25.2 / 33.5 --- --- --- 70.0 / 80.6 2
295A 295A 480 33.5 --- --- --- 40.3 2
296A 296A 600 33.5 --- --- --- 32.2 2
299A 299A 600 28.0 --- --- --- 25.7 2 07 07
Copyright 2012 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 01/12
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No:IIK---CRHTRSIN01---05
Replaces: IIK---CRHTRSIN01---04
CRHTR,CRSIN