CRHEATER101A00 -- CRHEATER119A00, CRHEATER264A00 -- CRHEATER269A00, CRHEATER288A00 -- CRHEATER299A00 CRHEATER301A00 CRSINGLE037A00 -- CRSINGLE054A00 Installation Instructions SMALL ROOFTOP UNITS ACCESSORY ELECTRIC HEATER AND SINGLE POINT BOX ELECTRIC COOLING AND HEAT PUMP 3 to 15 TONS TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 ......................... PACKAGE USAGE 2 .................................. PACKAGE CONTENTS 2 .............................. GENERAL 5 ......................................... GENERAL INSTALLATION SEQUENCE 8 ................ All Units Except HP--1 Size 14 and 150 8 ................. Installing Single Point Box (CRSINGLE037A00-- 054A00) 8 ........................................ Installing Electric Heater (CRHEATER101A00--119A00, CRHEATER264A00--269A00, 299A00) 10 .............. Installing Electric Heater (CRHEATER297A00, 298A00, 301A00) 10 ....................................... Heat Pump Size 14 and 150 Only 15 ..................... Installing Single Point Box (CRSINGLE047A00, 050A00--054A00 15 ................................ Installing Electric Heater (CRHEATER288A00-- 296A00) 17 ....................................... APPENDIX A 26 ..................................... APPENDIX B 33 ..................................... APPENDIX C 46 ..................................... IMPORTANT: Read these instructions completely before attempting to install this accessory. SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Turn off all power to unit and install lockout tag. Power can come to unit from from multiple sources. Verify power is off with a meter or probe. ! WARNING CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing units. CAUTION ! Copyright 2012 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 01/12 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Catalog No:IIK---CRHTRSIN01---05 Replaces: IIK---CRHTRSIN01---04

CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

Embed Size (px)

Citation preview

Page 1: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

CRHEATER101A00 --CRHEATER119A00,CRHEATER264A00 --CRHEATER269A00,CRHEATER288A00 --CRHEATER299A00CRHEATER301A00CRSINGLE037A00 --CRSINGLE054A00

Installation Instructions

SMALL ROOFTOP UNITSACCESSORY ELECTRIC HEATER

AND SINGLE POINT BOXELECTRIC COOLINGAND HEAT PUMP

3 to 15 TONS

TABLE OF CONTENTSSAFETY CONSIDERATIONS 1. . . . . . . . . . . . . . . . . . . . . . . . .

PACKAGE USAGE 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PACKAGE CONTENTS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL INSTALLATION SEQUENCE 8. . . . . . . . . . . . . . . .

All Units Except HP--1 Size 14 and 150 8. . . . . . . . . . . . . . . . .

Installing Single Point Box (CRSINGLE037A00--054A00) 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installing Electric Heater (CRHEATER101A00--119A00,CRHEATER264A00--269A00, 299A00) 10. . . . . . . . . . . . . .

Installing Electric Heater (CRHEATER297A00, 298A00,301A00) 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Heat Pump Size 14 and 150 Only 15. . . . . . . . . . . . . . . . . . . . .

Installing Single Point Box (CRSINGLE047A00,050A00--054A00 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installing Electric Heater (CRHEATER288A00--296A00) 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPENDIX A 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPENDIX B 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPENDIX C 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

IMPORTANT: Read these instructions completely beforeattempting to install this accessory.

SAFETY CONSIDERATIONSInstallation and servicing of air--conditioning equipmentcan be hazardous due to system pressure and electricalcomponents. Only trained and qualified service personnelshould install, repair, or service air-conditioningequipment.Untrained personnel can perform the basic maintenancefunctions. All other operations should be performed bytrained service personnel.

When working on air-conditioning equipment, observeprecautions in the literature, tags and labels attached tothe unit, and other safety precautions that may apply.Follow all safety codes. Wear safety glasses and workgloves.Recognize safety information. This is the safety--alert

symbol . When you see this symbol on the unit and ininstructions or manuals, be alert to the potential forpersonal injury.Understand the signal words DANGER, WARNING, andCAUTION. These words are used with the safety--alertsymbol. DANGER identifies the most serious hazardswhich will result in severe personal injury or death.WARNING signifies a hazard which could result inpersonal injury or death. CAUTION is used to identifyunsafe practices which may result in minor personalinjury or product and property damage. NOTE is used tohighlight suggestions which will result in enhancedinstallation, reliability, or operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury or death.

Turn off all power to unit and install lockout tag.Power can come to unit from from multiple sources.Verify power is off with a meter or probe.

! WARNING

CUT HAZARD

Failure to follow this caution may result in personalinjury. Sheet metal parts may have sharp edges orburrs. Use care and wear appropriate protectiveclothing, safety glasses and gloves when handlingparts and servicing units.

CAUTION!

Copyright 2012 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 01/12

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No:IIK---CRHTRSIN01---05

Replaces: IIK---CRHTRSIN01---04

Page 2: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

2

PACKAGE USAGECARRIER MODELS

MODEL NUMBER CHASSISGROUP UNIT SIZES

50HC AC---2 04---1450HCQ HP---2 04---1250TC AC---1 04---1650TCQ HP---1 04---14

BRYANT MODELSMODEL NUMBER CHASSIS

GROUP UNIT SIZES

548J HP---1 04---14549J HP---2 04---12551J AC---2 04---14558J AC---1 04---16

ICP MODELSMODEL NUMBER CHASSIS

GROUP UNIT SIZES

RAS AC---1 036---180RHS HP---1 036---150

AC: Cooling Only (air conditioner)HP: Heat Pump

PACKAGE CONTENTS--ELECTRIC HEATERS

CRHEATER101A00--119A00,CRHEATER264A00--269A00

CRHEATER297A00, 298A00, 301A00QTY CONTENTS1 Heater module1 Heater slider track*4 Screws*1 Wiring label1 Red wire (10 gauge){1 Splice connector{1 Wire tie{1 Label, Max Temp/Static

*Not included with CRHEATER101A00---109A00, 297A00, 298A00, 301A00{Supplied with electric heater packages CRHEATER101A00,CRHEATER102A00, CRHEATER103B00, and CRHEATER104B00 only.

PACKAGE CONTENTS--ELECTRIC HEATERS

CRHEATER288A00--296A00, 299A00QTY CONTENTS1 Heater module1 Heater slide track4 Screws1 Wiring label1 Label, Max Temp/Static

PACKAGE CONTENTS--CRSINGLE037A00

ITEM DESCRIPTION QUANTITYSingle Point Box Housing Assembly(Height 18--- in/449 mm) 1

Terminal block 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1

CRSINGLE038A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 18--- in/449 mm) 1

Terminal block/Fuse holder 1Fuse block 1Fuses, 60---A class RK5 6Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1

CRSINGLE039A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 18--- in/449 mm) 1

Terminal block/Fuse holder 1Fuse block 2Fuses, 60---A class RK5 9Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1

CRSINGLE040A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 18--- in/449 mm) 1

Terminal block/Fuse holder 1Fuse block 1Fuses, 60---A class RK5 4Power distribution harness 1Conductors, Tap, #10 2Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1

CRHTR,CRSIN

Page 3: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

3

CRSINGLE041A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 18--- in/449 mm) 1

Terminal block/Fuse holder 1Fuse block 1Fuses, 60---A class RK5 6Power distribution harness 1Conductors, Tap, #10 2Rain shield with conduit seal 1Screws, #10 x ½--- in 12Wire ties 7Tube clamp 1Seal strip 1

CRSINGLE042A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 25--- in/639 mm) 1

Terminal block 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE043A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 25--- in/639 mm) 1

Terminal block/Fuse holder 1Fuse block 1Terminal block (TB---10) 2Fuses, 60---A class RK5 6Power distribution harness 1Conductors, Tap, #10 6Screws, #8 x ½--- in 2Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE044A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 25--- in/639 mm) 1

Terminal block 1Fuse block 2Fuses, 60---A class T (600v) 6Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE045A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 25--- in/639 mm) 1

Terminal block/fuse holder 1Fuse block 2Fuses, 60---A class RK5 9Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE046A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 25--- in/639 mm) 1

Terminal block/fuse holder 1Fuse block 3Fuses, 60---A class RK5 12Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE047A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 33--- in/845 mm) 1

Terminal block 1Conductors, Tap, #10 3Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE048A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 25--- in/639 mm) 1

Terminal block 1Fuse block 3Fuses, 60---A class RK5 9Power distribution harness 1Conductors, Tap, #10 3Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRHTR,CRSIN

Page 4: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

4

CRSINGLE049A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 33--- in/845 mm) 1

Terminal block/Fuse holder 1Fuse block 1Fuses, 60---A class RK5 6Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE050A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 33--- in/845 mm) 1

Terminal block 1Fuse block 2Fuses, 60---A class T (600v) 6Power distribution harness 1Conductors, Tap, #10 3Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE051A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 33--- in/845 mm) 1

Terminal block/fuse holder 1Fuse block 2Fuses, 60---A class RK5 9Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE052A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 33--- in/845 mm) 1

Terminal block 1Fuse block 3Fuses, 60---A class T (600v) 9Power distribution harness 1Conductors, Tap, #10 3Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE053A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 33--- in/845 mm) 1

Terminal block 1Fuse block 4Fuses, 60---A class RK5 12Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRSINGLE054A00ITEM DESCRIPTION QUANTITY

Single Point Box Housing Assembly(Height 33--- in/845 mm) 1

Terminal block 1Fuse block 5Fuses, 60---A class RK5 15Power distribution harness 1Conductors, Tap, #10 6Terminal block (TB10) 2Screws, #8 x ½--- in 2Rain shield, small 1Rain shield with conduit seal 1Screws, #10 x ½--- in 8Wire ties 7Seal strip 1

CRHTR,CRSIN

Page 5: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

5

GENERALPuronR UnitsThis installation instruction manual describes theinstallation of electric heaters and associated fuseblock/field power termination kits (single point box orSPB) on small rooftop units in nominal cooling capacitiesfrom 3 to 15 tons. These rooftop units use Puronrefrigerant (R-410A). See Package Usage tables on page2 for applicable unit models. Unit types include coolingunits (AC) and heat pumps (HP) distributed over severalchassis sizes. Unit AC--1, AC--2, HP--1, HP--2 areidentified.This information does not include selection data. Refer toproject plans, job submittals and selection programs forheater and field power termination/SPB kit usage.Some electric heaters used on these Puron (R-410A) unitsmay also be installed in earlier R-22 rooftop units. Referto Form 50-8SI or IIK-548-36-49 for installationinstructions on heater packages CRHEATER101A00through 119A00 with earlier models. Contact your localdistributor office for a copy of this form.

Electric HeatersHeaters are shipped with one heater per carton. Thecarton is marked with a Sales Package Number. On allheaters except CRHEATER101A00 through 119A00, theheater Model Number (as marked on the heater infoplate)is the same as the Sales Package number. OnCRHEATER101A00 through 119A00 heaters, the value inposition 9 of the part number differs between the salespackage part number (value is 1) and bare heater modelnumber (value is 0). (See Table 1.)The heaters are modular in design, with heater framesholding open coil resistance wires strung through ceramicinsulators, limit switches and one or two controlcontactors. Power conductors are attached. One or twoheater modules may be used in a unit.Heater modules are installed in the compartment belowthe indoor (supply) fan outlet. Access is through theindoor access panel. Heater modules slide into thecompartment on tracks along the bottom of the heateropening. (See Fig. 13.)NOTE: The following heaters do not use the slide track --CRHEATER101A00--109A00, 297A00, 298A00, and301A00.

Not all available heater modules may be used in everyunit. Use only those heater modules that are UL listed foruse in a specific size unit. Refer to the label on the unitcabinet for the list of approved heaters. (See Fig. 1 and2.) See Appendix C for electric heater module data.

Single Point Boxes and FusesThe Single Point Box kits provide a field powertermination location plus an enclosure for heater fuseswhen required by code. The SPBs are installed under theunit’s main control box and include a hinged cover plusall internal wiring. Minimum components of the SPB area field power terminal block with tap conductors (toconnect to the unit’s main control box field terminals).Maximum component population includes up to five fuseblocks.Fuses for electric heater circuits are required and providedwhen the unit’s MOCP exceeds 60-A or when the totalheater Full Load Amp value exceeds 48-A. When fusesare required and provided, the cooling circuit is alsoprovided with fuse protection; some units require minorwiring changes in the main control box (see section onTB10 terminal blocks).

No FusesIf the unit’s MOCP device rating is 60-A or less, then theMOCP device is recognized as providing the requiredovercurrent protection to the heater and no internal fusingis required. If two heater modules are installed, a singlepoint box that contains only a field power terminal blockis required. If only one heater module is installed, no fuseor single point box is required. Connect field power leadsand heater power leads to the unit’s field connectionterminals in the main control box. See tables at thebeginning of Appendix A and B for where-usedinformation on the single point boxes and for connectionsFigure number.

Units with Factory Installed HACRThe amp rating of the HACR factory installed option isbased on the size, voltage, indoor motor and otherelectrical options of the unit as shipped from the factory.When field installed accessory electric heaters are addedor changed in the unit, the HACR may no longer be of theproper amp rating and therefore will need to be removedfrom the unit. See unit nameplate and label on factoryinstalled HACR for the amp rating of the HACR that wasshipped with the unit from the factory. See unitnameplates for the proper fuse, HACR or maximumover--current protection device required on the unit withfield installed electric heat.

CRHTR,CRSIN

Page 6: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

6

Table 1 – Heater Model Number

Bare Heater ModelNumber C R H E A T E R 0 0 1 A 0 0

Heater Sales PackagePNOIncludes:Bare HeaterCarton and packingmaterialsInstallation sheet

C R H E A T E R 1 0 1 A 0 0

7310 West Morris StreetIndianapolis, IN 46231 U.S.A.

BREAKER PER NEC

MAX OVERCURRENT

MINIMUM UNIT DISCONNECT

FLA LRA

PROTECTION DEVICE

VOLT

OTHER

LBS kg

CAPACITY Btu/Hr CAPACITY kW EER COP

COOLING

HP HEATING

THIS EQUIPMENT COMPLIES WITH THE

2004 REQUIREMENTS OF ASHRAE 90.1

CarrierCorporation

MODEL

QTY VOLTS AC PH HZ RLA LRA REF. SYSTEM R410A TEST PRESSURE GAGE

COMPR A

COMPR B

LBS

LBS

kg

kg

HI

LO

PSI kPa

PSI kPa

FAN MTR QTY VOLTS AC PH HZ FLA

OUTDOOR

COMPR C

INDOOR

PWR.EXH.

ELC.HEATCHARGE SYSTEM PER INSTALLATION INSTRUCTIONS

SUITABLE FOR OUTDOOR INSTALLATION

POWER

SUPPLY PH HZ

PERMISSIBLEVOLTAGE AT UNIT MINMAX

DOWN SUPPLYMIN CLEARANCE TO COMBUSTIBLE MATERIALS _____INCHES ______mm.

FOR FIRST _____INCHES______mm. OF DUCT WHEN ELECTRIC HEATER IS INSTALLEDSIDE SUPPLY

MIN CLEARANCE TO COMBUSTIBLE MATERIALS _____INCHES ______mm.

FOR FIRST _____INCHES______mm. OF DUCT WHEN ELECTRIC HEATER IS INSTALLED

*FOR INSTALLATION ON COMBUSTIBLE FLOORING OR

CLASS A,B, OR C ROOFING MATERIAL

ACCESSORYHEATER MODEL

NUMBER

CHECK

HEREVOLTS PH HZ

HEATER FLA

MIN CKT AMPS

FUSE OR HACRBREAKERPER NEC

MAXIMUM OVERCURRENT PROTECTION DEVICE

SINGLE PT. BOX MODEL NUMBER

MINIMUM UNIT DISCONNECT

FLA LRA

INSTALLER NOTE: 1.INSTALL ACCESS HEATER PER INSTALL INSTR ENCLOSED WITH HEATER. MARKSPACE "CHECK HERE" FOR MODEL USED USE MIN CKT AMPS & MAX OVER-CURRENT DEVICE AMPS LISTED FOR HEATER. IF NO HEATER IS USEDMARK SPACE "CHECK HERE" FOR NONE.

2.HEATERS ARE MANUFACTURED BY EMERSON HEATING PRODUCTS OR TUTCO ELECTRIC.

MIN. CKT.AMPS

MAX FUSE OR HACR

50TC-A06A2A5A0A0A0

10.7 4.9 650 4482450 3103

1 208/230 3 60 15.6 110

1 208/230 1 60 1.51 208/230 3 60 5.2

208/230 3 60

253 187 26.2

40

26 144-

1 2512 305

1 2512 305

17.25900013

102A 208/240

3 60 13.6/15.6

26.2/26.2

40/40 -/- - 26/26 144/144

104B 208/240

3 60 21.9/25.3

33.9/38.1

40/40 -/- - 31/35 144/144

105A 208/240

3 60 33.4/38.5

48.3/54.6

50/60 -/- 037 44/50 144/144

104B+104B 208/240

3 60 43.8/50.5

61.3/69.6

70/70 -/- 038 56/64 144/144

104B+105A 208/240

3 60 55.2/63.8

75.5/86.3

80/90 -/- 038 69/79 144/144

C10531

Fig. 1 -- Unit Informative Data Label

CRHTR,CRSIN

Page 7: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

7

BOX MODELNUMBER

SINGLE PTBOX MODELNUMBER

SINGLE PTBOX MODELNUMBER

1.INSTALL ACCESS. HEATER AND/OR POWER EXHAUST PER INSTALL INSTR ENCLOSED

USE MIN CKT AMPS AND MAX OVER CURRENT DEVICE AMPS LISTED FOR HEATER

HERE

CHECK

MODEL

REFRIGERANT CHARGE R410A

ELECTRICAL DATA FOR ACCESSORY POWER EXHAUST INSTALLED

IN COMBINATAION WITH ELECTRIC HEATER

ACCESSORYHEATER MODEL

NUMBER

HEATER

FLA

FLA

LRA

INSTALLER NOTE:

WITH HEATER AND POWER EXHAUST. MARKSPACE "CHECK HERE" FOR MODEL USED.

AND POWER EXHAUST.

2.HEATERS ARE MANUFACTURED BY EMERSON HEATING PRODUCTS OR TUTCO ELECTRIC.

ELECTRICAL DATA FOR ACCESSORY POWER EXHAUST ONLY

ACCESSORYPOWER EXHAUST

MODEL NUMBER

CHECK

HERE

VOLTS PH HZ MIN CKTAMPS

FUSE ORHACR

BREAKERPER NEC

MAXIMUMOVERCURRENTPOROTECTION

DEVICE

MINIMUMUNIT

DISCONNECT

FLA

LRA

FLA

EXHAUSTPOWER

FUSE ORHACR

BREAKERPER NEC

MAXIMUMOVERCURRENTPOROTECTION

DEVICE

MINIMUMUNIT

DISCONNECT

SINGLE PTBOX MODELNUMBER

FLA

LRA

FLA

LRA

FLA

LRA

FLA

LRA

FLA

LRA

VOLTS PH HZ MIN CKTAMPS

SINGLE PTBOX MODELNUMBER

SINGLE PTBOX MODELNUMBER

SINGLE PT

50TC-A06A2A5A0A0A0

28.128

146

-/-

-/-

-/-

-/-

-/-

40 -/-

40/40

40/45

60/60

70/80

80/90

146/146

CRPWREXH_

146/146

146/146

28/28

33/37

146/146

47/52

59/66

146/146

72/82

28.1/28.4

36.3/40.5

50.6/57.0

63.6/72.0

77.9/88.6

102A208/240

3 60 13.6/15.6

-

104B208/240

3 60 21.9/25.3

-

105A208/240

3 60 33.4/38.5

037

104B+104B208/240

3 60 43.8/50.5

038

104B+105A208/240

3 60 55.2/63.8

038

*50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0**50TC-A06A2A5A0A0A0*

C10532

Fig. 2 -- Unit Informative Data Label, Power Exhaust Installed

CRHTR,CRSIN

Page 8: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

8

TB10NOTE: TB10’s are not used on AC--1 size 16 and 180,HP--1 size 14 and 150, AC--2 size 14, and HP--2 size 12.

On larger 208/230-3-60 units, the MOCP rating for thebase cooling circuit exceeds 60-A. On these applications,the single point box kit contains two small single-poleterminal blocks that are installed in the main control box.Minor relocation of wiring results in separating the indoorfan motor load from the main power circuit, allowing thisload to be protected with a second fuse set. See singlepoint box kits CRSINGLE043A00, 045A00, 049A00,051A00, 053A00 and 054A00. (Units AC--1 size 14 and150 and HP--1 size 12 and 121, AC--2 size 12, HP--2 size09 use only one TB10 block to separate Compressor 2 andoutdoor fan motor loads from main unit circuit).

Single Point Box ContentsSee Package Content tables for a list of componentsincluded in each single point box kit. Note the heightdifferences and their use in specific size units.

Control WiringHeater modules contain one or two heater controlcontactors. If two heater modules are installed, or atwo-circuit heater module is installed, the cooling unit(AC type) can be connected for one-stage or two-stageheating control. On all heat pump units (HP type), allheater contactors will be connected to providesecond-stage heating control.

GENERAL INSTALLATIONSEQUENCE

1. Pre-stage heater packages and single point boxes byplacing the required component cartons at each unit.

2. Check the heater sales package number and singlepoint box part number (if used) against the partnumbers on the unit’s infoplate. See Fig. 1 and 2for typical data.

3. Install the SPB and connect power wiring tap con-ductors to field power terminals in main controlbox.

4. Install the electric heater module(s) and connectheater power conductors to single point box or mainunit control box per appropriate connections figure.(See Appendix A and B.) On AC--1 15 ton, AC--212--1/2 ton, HP--1 12--1/2 ton and HP--2 10 tonmodels with factory installed non--fused disconnectremove lead side factory wiring. Re--size wires perunit nameplate data with accessory electric heat.

5. Connect the heater control contactors to unit termin-al block TB4.

6. Mark the unit infoplate to indicate which heatermodule(s) have been installed.

7. Note the required wire size ampacity (WSA) for thefield power supply conductors. Select and installsuitable field power conductors from external safetydisconnect to unit power connection points, or con-firm wiring already provided is suitable for requiredWSA.

All Units Except HP--1 Size 14 and 150, HP--2Size 12,AC--1 Size 16 and 180, AC--2 Size 14The following text covers installation of single pointboxes and electric heaters in all units EXCEPT the HP-1size 14 and 150, HP--2 Size 12, AC--1 Size 16 and 180,AC--2 Size 14. For instructions on these units, skip topage 14.Check sales packages – Following the project drawingschedule tables or submittal documents, select thescheduled heaters and single point boxes (if used) andplace at each unit.Compare the sales package number(s) for scheduledheater modules against the approved usage table on theunit’s infoplate. See Fig. 1 and 2 for typical plate data. Ifthe scheduled heater usage does not appear on the unitinfoplate label, STOP. Contact the project engineer or thelocal distributor sales office for clarification.Open the cartons and inspect for damage.

Installing Single Point Box(CRSINGLE037A00--054A00)

1. If power is already connected to unit, disconnect allpower to the unit per correct lock--out/tag--out pro-cedures.

2. Remove indoor and outdoor access panel. (See Fig.3 and 4.) Save panel and screws.

DISCONNECT MOUNTINGLOCATION

UNIT BLOCK-OFFPANEL

OUTDOORACCESS PANEL

INDOORACCESSPANEL

MAX. TEMP/STATIC LABEL

C11510

Fig. 3 -- Typical Access Panel Location(AC--1/HP--1 3 to 6 Ton, AC--2/HP--2 3 to 5 Ton)

DISCONNECT MOUNTINGLOCATION

UNITBLOCK-OFFPANEL

OUTDOORACCESS PANEL

INDOORACCESSPANELMAX. TEMP/

STATIC LABEL

C11511

Fig. 4 -- Typical Access Panel Location(AC--1 71/2 to 121/2 Ton, AC--2 6 to 10 Ton,HP--1 71/2 to 10 Ton, HP--2 6 to 8.5 Ton )

CRHTR,CRSIN

Page 9: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

9

HEATERMOUNTINGBRACKET

HEATERMODULE(LOCATION 2)

HEATERMODULE(LOCATION 1)

SINGLE POINT BOX(NOT SHIPPED WITHUNIT)

HEATERCOVERS

MAINCONTROLBOX

CENTERPOST

C11514

(Size 04--06 and 036--060)

HEATERCOVERS

HEATERMOUNTINGBRACKETHEATER

MODULE(LOCATION 2)

HEATERMODULE(LOCATION 1)

MAINCONTROLBOX

SINGLE POINT BOX(NOT SHIPPED WITHUNIT)

CENTERPOST

C11515

(Size 07--15 and 072--180)

Fig. 5 -- Typical Component Location

ALLIED PA

MODEL NO.

ERIAL NO.

CORP.

1113

2123

OD

22.2

3123

ISTED AIRNDITIONINGUIP ACCESS 346N.

P / N 2- 5610-4 REV

1113

2123

CONTROLBOX

BUSHING

SINGLEPOINT BOXMOUNTINGSCREWS

FOAMBUSHING

DRIP BOOTBRACKETMOUNTINGSCREWS

HEATERRELAYS

POWERWIRES

HEATERMOUNTINGSCREWS

C08136

Fig. 6 -- Typical Single Point Kit Installation

3. Remove control box cover and center post. Savescrews. (See Fig. 5.)

4. If unit does not have the factory--installed discon-nect or HACR option or has not had field powerwiring connected, skip to Step 5.When unit is equipped with factory--installed dis-connect or HACR or has field power wiring connec-ted, disconnect the power leads at the control boxterminals and withdraw the conductors from thecontrol box.

5. Add seal strip to the rear bottom corner of the con-trol panel as shown in Fig. 7. Foil tape open screwholes on the back of the single point box as shownin Fig. 7. Different single point boxes will have dif-ferent screw holes open.

6. All bushings in the area of the control box wherethe single point box (SPB) mounts, must be re-moved prior to securing the SPB to the control box.(See Fig. 8.) Also, for units installed in the snowbelt, all unplugged holes in the bottom of the con-trol box which are not used must be plugged beforeinstalling the SPB. Use foil tape or reinstall thebushings from the outside of the control box prior tosecuring the SPB. (See Fig. 9.)

7. Remove the single point box cover. Secure singlepoint box to the underside of the control box withthe 2 screws provided. (See Fig. 6.) Re--install bush-ing on the SPB tap conductors. (See Fig. 9.)

8. Secure the rainshield (conduit drip boot bracket) as-sembly to the back of the single point box with 2 ofthe screws provided. (See Fig. 6.) The channel por-tion of the bracket assembly extends to the top pan-el behind the control box. Secure all wires to brack-et with field--supplied wire tie as shown. (See Fig.11.)

Seal Bottom Corner

Seal Back Corner

Foil Tape LocationsC101085

Fig. 7 -- Seal Strip and Foil Tape Locations

CRHTR,CRSIN

Page 10: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

10

C09005

Fig. 8 -- Control Box -- Bushings to Remove

C09006

Fig. 9 -- Bushings Replaced from Outside Control Box

9. Connect power tap conductors to unit main controlbox.a. Single point boxes with two or three tap con-

ductors--Route the tap conductors (with bushingadded per Step 5) into the unit main control box.Connect the power tap conductors to the desig-nated terminals in the unit’s control box for fieldpower connections. Refer to the wiring diagramin the unit, to unit installation instructions forField Power Wiring Connections or to AppendixA or B.

b. Single point boxes with six tap conductors(CRSINGLE043A00, 045A00, 049A00, 051A00,053A00 and 054A00)(1.) All units EXCEPT AC--1 size 14 and 150

and HP--1 size 12 and 121These single point boxes include two sets ofthree--lead power tap conductors connectedto two separate fuse blocks. These kits alsoinclude two terminal blocks (TB10A andTB10B) and attachment screws. Mount

these terminal blocks in the unit’s controlbox next to compressor contactor C1. (SeeAppendix A or B.)S Relocate these wires:

At IFC terminal 13, disconnectCompressor 1 BLU and Compressor 2ORN leads; reconnect at TB10A.At C1 terminal 13, disconnect ID FanYEL lead; reconnect at TB10B.At C1 terminal 11, disconnect BLKjumper; reconnect to IFC terminal 11.

S Route the first set of tap conductors(attached at upper fuse block, withbushing per Step 5) into the main controlbox; connect at:BLK: C1 terminal 11YEL: C1 terminal 13BLU (long lead with terminal): TB10A

S Route the second set of tap conductors(attached at second fuse block) into themain control box; connect at:BLK: IFC terminal 11YEL (long lead with terminal): TB10BBLU: IFC terminal 13

(2.) Units AC--1 size 14 and 150 and HP--1 Size12 and 121, AC--2 size 12, HP--2 size 09OnlyMount one TB10 terminal block in theunit’s control box between compressor con-tactors C1 and C2. (See Fig. 10.)S Relocate these wires:

At IFC terminal 13, disconnect Com-pressor 2 ORN and OFM BLU leads; re-connect at TB10.

S Remove these leads:At C1--11, remove BLK jumper toC2--11. Discard.At C1--13, remove YEL jumper toC2--13. Discard.

S Route the first set of tap conductors (at-tached at second fuse block, with bush-ing per Step 5) into the main controlbox; connect at:BLK: C1 terminal 11YEL: C1 terminal 13BLU: IFC terminal 13

S Route the upper set of tap conductors(attached at second fuse block) into themain control box; connect at:BLK: C2 terminal 11YEL: C2 terminal 13BLU: TB10

Installing Electric Heater(CRHEATER101A00--109A00,CRHEATER110A--119A00CRHEATER264A00--269A00, 299A00CRHEATER297A00, 298A00, 301A00)

1. Remove heater cover(s) from heater mounting.bracket. Save screws.

CRHTR,CRSIN

Page 11: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

11

NOTE: For CRHEATER101A00--109A00, 297A00,298A00, and 301A00 skip Steps 2 and 3.

2. Install heater slide bracket(s) from the heater kitthrough the bottom of the heater mounting hole(s)and fasten each with the two screws provided. (SeeFig. 13.)

NOTE: Modules CRHEATER105A00,CRHEATER109A00, CRHEATER297A00,CRHEATER298A00, CRHEATER301A00,CRHEATER112A00, CRHEATER114A00,CRHEATER115A00, and CRHEATER119A00 are keyedand must be installed in location 1 even when used as partof a 2--module option. (See Fig. 12 for AC--1 size 04 to 07and 036 to 072, AC--2 size 04 to 06, HP--1 size 04 to 07and 036 to 072, HP--2 size 04 to 06 units or Fig. 13 for

AC--1 size 08 to 14 and 090 to 150, AC--2 size 07 to 12,HP--1 size 08 to 12 and 090 to 121, HP--2 Size 07 to 09units.)

NOTE: Modules CRHEATER265A00 throughCRHEATER269A00 (480--v, used on AC--2 and HP--2 size07 only), CRHEATER299A00 (600--v, used on AC--2, size07 only), are keyed and must be installed in location 2. Inaddition, these modules are always used as a singlemodule option. (See Fig. 14)

3. To install module, engage flange on heater withtrack in unit and slide heater through mountingbracket opening. Fasten heater module to heatermounting bracket with the 4 screws saved from Step1. (See Fig. 13.)

HEATER012A

CIR#1

CIR#2

HEATER017A

C101084

Fig. 10 -- TB10 Locations and ConnectionsCRHTR,CRSIN

Page 12: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

12

CONDUIT CONDUITDRIP BOOT

WIRE TIE

C—

CO

MM

30V—

OR

200V—

RD

OV

—Y

LD

24V 75VA

BD

236BN

—T

RA

N 3O

—B

V2075

E 60 H

Z 30-8703

C08417

Fig. 11 -- Typical Conduit Installation

4. Single--phase heater conversion208/230--v heaters CRHEATER101A00 through104B00 are factory--wired for 3--phase applicationsbut can be converted to single--phase by changingone wire as described below.Three--phase applications: Skip to Step 5. Forsingle--phase applications, rewire the heater as fol-lows (Fig. 15 and Fig. 16):a. Connect 10--gauge red wire to splice connector.b. Remove yellow wire from heater contactor ter-

minal 11 and connect to splice connector.c. Using the wire tie provided, fasten red wire to

heater power wire harness near existing wire tieon heater module. This provides strain relief forthe red wire.

KEY FOR MODULE LOCATON 1

C09010

Fig. 12 -- Typical Electric Heat Installation(AC--1 Sizes 04 to 07 and 036 to 072, AC--2 Sizes 04--06,

HP--1 Sizes 04--07 and 036 to 072, HP--2 Sizes 04--06)

TRACK

FLANGE

HEATERSLIDE

TRACK SCREWS

KEY FOR MODULE LOCATION 1

C10557

Fig. 13 -- Typical Module Installation(AC--1 Sizes 08 to 14 and 090 to 150, AC--2 Sizes 07--12,

HP--1 Sizes 08--12 and 090 to 121, HP--2 Sizes 07--09)

C11513

Fig. 14 -- Heater Bracket Keyway(AC--2, HP--2 Size 07 and 14 Units Only)

LEGENDHR -- Heater RelayHTR -- HeaterLS -- Limit Switch

C08419

Fig. 15 -- Single--Phase Heater Wiring

CRHTR,CRSIN

Page 13: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

13

MODEL NO.

ERIAL NO.

1113

2123

OD

22.2

3123

ISTED AIRNDITIONINGUIP ACCESS 346N.

P / N 2- 5610-4 REV

RED WIRE

SPLICECONNECTOR

HEATERPOWERWIREHARNESS

C08420

Fig. 16 -- Typical Single--Phase Wiring Installed

5. Route power wires from heater module(s) throughthe foam bushing in the center partition and into thesingle point box. (See Fig. 6.) Connect to terminalblock or fuse blocks per schematics in Appendix Aor B. See Tables at beginning of each Appendix toidentify the appropriate figure.

All heaters are single bank heaters exceptCRHEATER111A00, 112A00, 268A00, 269A00,and 301A00 which are dual bank heaters. Theseheaters will be wired as two heaters (i.e., 6 leads).Fusing is shown pictorially on the unit wiringschematic label.

If no single point box is required for the unit andheater combination, run the heater power supplywiring through the grommet holes to the main unitcontrol box’s field power connection points or tooptional factory--supplied disconnect.The optional factory--supplied disconnect has amaximum rating per Table 2. Above these a field--supplied disconnect is required.

6. Factory control wiring for heaters runs from unitcontrol box to terminal block TB--4, mounted in theheater compartment above module 1 location. (SeeFig. 5 and 19.) Connect the heater control wiring atTB--4. For AC--1 and AC--2 units, see Fig. 19. ForHP--1 and HP--2 units, see Fig. 20 except for AC--2,Size 06, 575V only See Fig. 17 and HP--2, Size 06,575V only, See Fig. 18.

Table 2 – Optional Factory Installed Disconnect Amp Ratings

ChassisGroup Unit Size Volts Amp

Rating

AC-1HP-1

04-07230 80460/575 60

AC-2HP-2 04-06

230 80460/575 60

AC-1 08-14230

80460/575

AC-2 07-12230

80460/575

HP-1 08-12230

80460/575

HP-2 07-09230

80460/575

AC-1 16230 200460/575 100

AC-2HP-1 14

230 200460/575 100

HP-2 12230 200460/575 100

C11555

Fig. 17 -- Accessory Electric Heater Control Connections(AC--2, Size 06, 575V only)

CRHTR,CRSIN

Page 14: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

14

C11554

Fig. 18 -- Accessory Electric Heater Control Connections(HP--2, Size 06, 575V only)

LCTB

CONTLBOARD

ORN

BRN

FieldConnections

HR1: On Heater 1 in Position #1HR2: On Heater 2 in Position #2 (if installed)

2

3

12

1 3

VIO

ORN VIO BRN

VIO BRN BRNVIO

2TB4

VIO HR2

HR1

BRN

VIO BRN

Elec Htr

C08331

Fig. 19 -- Accessory Electric Heater ControlConnections (AC--1 Except Size 16 and 180,

AC--2 Except Size 14)

DEFROSTBOARD

ORN

BRN

FieldConnections

E-HEAT

P3-3

1 3

ORN BRN

VIO BRN BRNVIO

TB4

VIO HR2

HR1

BRN

VIO BRN

Elec Htr

HR1: On Heater 1 in Position #1HR2: On Heater 2 in Position #2 (if installed)

C09013

Fig. 20 -- Accessory Electric Heater ControlConnections (HP--1 Except Size 12 and 121,

HP--2 Except Size 12)

MODEL NO.

ERIAL NO.

1113

2123

OD

3123

ISTED AIRNDITIONINGUIP ACCESS 346N.

P / N 2- 5610-4 REV

C08137

Fig. 21 -- Typical 3--Phase Wiring Installed

7. Replace the center post and secure the single pointbox to the center post with one screw. (See Fig. 6.)

8. Remove knockouts for appropriate size conduitfrom unit block--off panel and single point box. In-stall conduit (rigid or electrometallic tubing)through conduit drip boot as shown. (See Fig. 11.)Drip boot will accept conduit sizes 3/4--in. to 1--1/2inches. The drip boot eliminates the need for water-tight conduit fittings at the single point box.

NOTE: Supply wiring must comply with NEC (NationalElectric Code) and all local requirements.

CRHTR,CRSIN

Page 15: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

15

9. Mark the appropriate block on the unit nameplatefor the accessory heater kW installed. Note the re-quired Minimum Circuit Ampacity (MCA) value forthis unit--heater combination. Ensure the fieldpower conductors are sized to handle this ampacity.

10. Place adhesive--backed wiring label on flanged sideof heater cover.

11. Fasten heater cover to heater module with 2 screwsprovided with heater. Flanges of cover should faceout.

12. Set manual reset limit switch (on supply fan hous-ing) by depressing button located between the ter-minals on the switch. (See Fig. 5.)

13. Close single point box cover and secure with onescrew.

14. Replace control box cover, using remainder ofscrews saved from Step 3 of Installing Single PointBox section on page 9.

15. Replace indoor and outdoor panels with screwssaved from Step 2 of Installing Single Point Boxsection on page 8. Place adhesive--backed Max. Air/Max. Static label on external panel that coversheaters. (See Fig. 3, 4, and 42.)

16. Turn on unit power.

HP--1 Size 14 and 150, HP--2 Size 12, AC--1Size 16 and 180 and AC--2 Size 14 ONLYThe following text covers installation of single pointboxes and electric heaters shown above. For instructionson all the smaller sizes, return to page 8.Check sales packages – Following the project drawingschedule tables or submittal documents, select thescheduled heaters and single point boxes (if used) andplace at each unit.

Compare the sales package number(s) for scheduledheater modules against the approved usage table on heunit’s infoplate. See Fig. 1 and 2 for typical plate data. Ifthe scheduled heater usage does not appear on the unitinfoplate label, STOP. Contact the project engineer or thelocal distributor sales office for clarification.Open the cartons and inspect for damage.

Install Single Point Box (CRSINGLE047A00,050A00--054A00)

1. Remove kits from boxes and verify that all of thecorrect parts have arrived undamaged.

2. If power is already connected to unit, disconnect allpower to the unit per correct lock--out/tag--out pro-cedures. Disconnect field power wiring or optionalfactory--installed disconnect or HACR power leadsat TB1 and withdraw the wiring from the unit con-trol box. On units with factory--installed disconnect,the factory supplied lead wires maybe of insuffi-cient size for accessory electric heat applications. Ifso, remove the lead side factory wiring. Re--sizewires per unit nameplate data with electric heat.

3. Remove outdoor access, control box, and left indooraccess panels from the unit. Fig. 22 shows the unitwith the panels already removed.

4. Optional – The center post may be removed to facil-itate wiring.

5. Remove the bushings and plug from the controlpanel per Fig. 23. Save the bushings and discard theplug.

6. Add seal strip to the rear bottom corner of the con-trol panel as shown in Fig. 24.

7. Foil tape open screw holes on the back of the singlepoint box as shown in Fig. 24. Different single pointboxes will have different screw holes open.

Control BoxAccessPanel

OutdoorAccessPanel

Heater Covers

LeftIndoorAccessPanel

C10170

Fig. 22 -- Typical Unit with Access Panels Removed

CRHTR,CRSIN

Page 16: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

16

Single Point Box Mounting Screws

Plug Location

Bushings(Re-installed)

C10169

Fig. 23 -- Single Point Box Installation Details

Seal Bottom Corner

Seal Back Corner

Foil Tape LocationsC101085

Fig. 24 -- Seal Strip and Foil Tape Locations

8. Remove the cover from the single point box.9. Install the single point box under the control panel

with two screws down through the control panel(Fig. 23) and one screw (not shown) into the centerpost. (See Fig. 23.) Holes have been provided.Foam wire guides in the center post may have to beremoved. If center post was removed per step 4, thesingle point box will have to be screwed into itlater.

10. The single point box kit will contain two rain shieldbrackets, a larger bracket with boot seal and a smal-ler (shorter) bracket without a seal. Remove theseal from the larger bracket and push the conduitdrip boot seal into the short rain shield bracket. (SeeFig. 25.) Discard the larger bracket.

Conduit Drip Boot

Rain Shield BracketC10167

Fig. 25 -- Rain Shield Installation

11. Install the rain shield bracket to the left and behindthe single point box using the two screws and holesprovided.

12. Re--install the bushings removed in Step 5.13. Connect the tap conductors.

a. CRSINGLE047A00, 050A00 and 052A00Connect the blue, yellow, and black power tapconductors (pigtails) from the single point box tothe unit’s power terminal block TB--1 per unitlabel wiring schematic and per Appendix A or Band connection figures. A representative installa-tion of two 480V heaters and correspondingsingle point box is shown in Fig. 26, 27, and 28.

CRHTR,CRSIN

Page 17: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

17

b. CRSINGLE051A00, 053A00 and 054A00These kits include two sets of tap conductors(blue, yellow and black pigtails) connected atfuse blocks 1 and 2. Connect these leads in par-allel to the unit’s power terminal block TB--1 perthe unit label wiring schematic and per Ap-pendix A or B and connection figures.(These kits also include two small terminalblocks (TB10). The TB10 blocks are not usedwith the HP--1 size 14 and 150 and HP--2 size12; discard.)

Install CRHEATER288A00--296A001. Remove and save the heater covers.2. Install heater slide track(s) from the heater kit

through the bottom of the heater mounting hole(s)and fasten each with the two screws provided. (SeeFig. 29.)

3. Install the heater(s) (Fig. 30, 230V shown) into theirmounting location(s) using the screws provided.Tables 3 and 4 give the correct heater location as afunction of heater size, voltage, and supply air flowdirection.

C10174

Fig. 26 -- Heater Wiring

CRHTR,CRSIN

Page 18: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

18

C10172

Fig. 27 -- Typical Single Point Box Wiring

CRHTR,CRSIN

Page 19: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

19

Single Point BoxPower Wires

C10175

Fig. 28 -- Typical Control Panel Wiring

Mounting ScrewsHeater Slide Track

C10198

Fig. 29 -- Heater Slide Track Installation

CRHTR,CRSIN

Page 20: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

20

Dual ElementHeater Module

Heater Mount Locations

Single ElementHeater Module

C10168

Fig. 30 -- Typical Heaters

Table 3 – Heater Location for HorizontalReturn and Discharge*

HeaterkW Volts

Heater Slot Location

CRHEATERXXXX00 Left Right

288A 10.0 240 -- 288A

291A 16.5 240 291A --

288A + 291A 26.5 240 291A 288A

294A 33.5 240 -- 294A

288A + 294A 43.5 240 288A{ 294A

291A + 294A 50.0 240 291A 294A

294A + 294A 67.0 240 294A{ 294A

289A 10.0 480 -- 289A

292A 16.5 480 292A --

289A + 292A 26.5 480 292A 289A

295A 33.5 480 -- 295A

289A + 295A 43.5 480 289A{ 295A

292A + 295A 50.0 480 292A 295A

295A + 295A 67.0 480 295A{ 295A

290A 10.0 600 -- 290A

293A 16.5 600 293A --

290A + 293A 26.5 600 293A 290A

296A 33.5 600 -- 296A

290A + 296A 43.5 600 290A{ 296A

293A + 296A 50.0 600 293A 296A

296A + 296A 67.0 600 296A{ 296A* XXXX --- 4 digit heater in table. For example, a CRHEATER291A000 islisted as a 291A.{Remove Restrictor Plate to install in Left Slot Location. Use foil tape tocover holes.

Table 4 – Heater Location for VerticalReturn and Discharge*

HeaterkW Volts

Heater Slot Location

CRHEATERXXXX00 Left Right

288A 10.0 240 -- 288A

291A 16.5 240 291A --

288A + 291A 26.5 240 291A 288A

294A 33.5 240 -- 294A

288A + 294A 43.5 240 288A{ 294A

291A + 294A 50.0 240 291A 294A

294A + 294A 67.0 240 294A{ 294A

289A 10.0 480 -- 289A

292A 16.5 480 292A --

289A + 292A 26.5 480 292A 289A

295A 33.5 480

295A {(Supply ductopening =~31” x 16”)

295A(Supply ductopening =~36” x 30”)

289A + 295A 43.5 480 289A{ 295A

292A + 295A 50.0 480 292A 295A

295A + 295A 67.0 480 295A{ 295A

290A 10.0 600 -- 290A

293A 16.5 600 293A --

290A + 293A 26.5 600 293A 290A

296A 33.5 600 -- 296A

290A + 296A 43.5 600 290A{ 296A

293A + 296A 50.0 600 293A 296A

296A + 296A 67.0 600 296A{ 296A* XXXX --- 4 digit heater in table. For example, a CRHEATER291A000 islisted as a 291A.{ Remove Restrictor Plate to install in Left Slot Location. Use foil tape tocover holes.

CRHTR,CRSIN

Page 21: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

21

4. Connect the heater control wiring to terminal blockTB4 (located to left of the heaters, see Fig. 40 and41.)TB4 has five terminals. (See Fig. 31 and 33.) Bot-tom row left terminal is “R Use”; it has a factoryRED connection. Bottom row right terminal is “CUse”; it has a factory BRN connection. For ACunits, top row left is designated as “W1 Use” ad hasfactory ORN connections. The top row center isdesignated as “W2 Use” and has factory VIO con-nections. For HP units, top row left and center ter-minals are designated “W2 Use” and have factoryORN connections. The fifth terminal is for field--option connection of a staging control.

CRHEATER288A00--293A00 HeatersThese heaters have two control wires: ORN forheater contactor and BRN for control common.Connect BRN wire(s) to TB4’s “C Use” terminal.(Second BRN wire will require use of the piggybackterminal on the factory BRN wire.) For AC units,connect heater ORN control wiring to ORN on TB4for 1st stage heating and for units with heater pack-ages, connect to VIO on TB4 for 2nd stage heating.(See Fig. 36.) For HP units, connect heater ORNcontrol wires(s) to an availabel terminal on TB4’s“W2 Use” group. (See Fig. 35.)

CRHEATER294A00--296A00 HeatersThese heaters have four control wires: ORN andVIO for heater contactors, RED for safety circuitpower and BRN for control common. Connect REDwire to TB4’s “R Use”. Connect BRN wire toTB4’s “C Use” terminal. For AC units with oneheater package that has these 4 control wires, con-nect heater ORN control wiring to ORN on TB4 for1st stage heating and to VIO on TB4 for 2nd stageheating.For AC units with 2 of these heater packages thathas 4 control wires, connect both the ORN and VIOcontrol wires from the heater to ORN on TB4 for 1st

stage heating and connect the ORN and VIO controlwires from the other heater to VIO on TB4 for 2nd

stage heating. (See Fig. 38.)For AC units with one of these heater packages thathas these 4 control wires plus a heater package thathas 3 control wires, connect both the ORN and VIOcontrol wires from the 4 control wire heater to ORNon TB4 for 1st stage heating and connect the ORNcontrol wire from the other heater with 3 controlwires to VIO on TB4 for 2nd stage heating.For HP units, connect ORN and VIO wires to TB4’s“W2 Use” terminals.(See Fig. 39.)

NOTE 4AND 6

RED

EHR

EHRORN

TRAN2 FROM POWER SCHEMATIC

24V BRN24V

CB

3.2 AMPS

BRN

GRN/YEL

24V

RED

BRN

1 0

1 0

8 6

FPT

BLK BLK

BRNBRN

BRN

RED

ELECTRICHEAT(ACCESSORY)SEE HEATER LABEL DIAGRAM

BRN

BRN

24V

5

TRAN1 FROM POWER SCHEMATIC

24V BRN24VGRN/YEL

CB

3.2 AMPS

BRNOFRVIO

TB4

3

ORN ORN

RED

C10561

Fig. 31 -- TB4 Wiring (HP Only)

C11127

Fig. 32 -- TB4 Wiring (AC Only)

NOTE:Optional Outdoor Temperature Controlat One Heater Stage – Move heater wire to this terminal and connect outdoor temperature switch between 2nd and 3rd terminals.

W2 Use

R Use C Use

C10604

Fig. 33 -- TB4 Terminal Use (HP Only)

NOTE:Optional Outdoor Temperature Controlat One Heater Stage – Move heater wire to this terminal and connect outdoor temperature switch between 2nd and 3rd terminals.

W1 Use

R Use C Use12 CONTROL

BOARD

8 CONTROLBOARD

VIOVIO

W2 Use

C11129

Fig. 34 -- TB4 Terminal Use (AC Only)

5. Cover the heater wiring with the heater covers perFig. 41.

6. If the center post was removed in Step 4 on page 14,reinstall the center post, screw the single point boxto the center post and replace any foam wire guidesper step 9.

7. Set manual reset limit switch (on supply fan hous-ing) by depressing button located between the ter-minals on the switch. (See Fig. 5 and 6.)

CRHTR,CRSIN

Page 22: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

22

8. Replace all access panels, posts and covers removedin Steps 3 and 8 on page 14 and 15. Place adhesive--backed Max. Air/Max. Static label on external panelthat covers heaters. (See Fig. 4, 4, and 42.)

NOTE: Supply wiring must comply with NEC (NationalElectric Code) and all local requirements.

9. Mark the appropriate block on the unit nameplatefor the accessory heater kW installed. Note the re-quired Minimum Circuit Ampacity (MCA) value forthis unit--heater combination. Ensure the fieldpower conductors are sized to handle this ampacity.Check also that the unit disconnect size and theovercurrent protection device for the branch circuitconductors are suitable for this unit--heater combin-ation.

10. Run conduit through (rigid or EMT) the conduitdrip boot in the rain shield bracket to the singlepoint box. Provide an appropriate fitting to connectthe conduit to the single point box wall and groundappropriately. (See Fig. 26.) Drip boot will acceptsizes ¾--in to 1--1/2 in. The drip boot eliminates theneed for watertight conduit fittings at the singlepoint box.

11. Run wire through conduit connecting outside powerto the designated terminals at the top of the singlepoint box. Ground appropriately. (See Fig. 28.)

12. If all other work on the unit is done, reapply powerper lock--out/tag out procedures.

TRAN2

HC1

HC1

HEATER 1

HEATER 2 (IF INSTALLED)

BRN

BRN

BRN

TBTS

TS

TB4

ORN

ORN

RED ORN

ORNEHR

TB4

RED

C10562

Fig. 35 -- Electric Heater Control Connections--Heat Pump with 1 or 2 CRHEATER288A00--293A00

HC1

HC1

HEATER 1

*HEATER 2 (IF INSTALLED)

BRN

BRN

BRN

TB4

TB4

ORN

ORN

RED

8 12CONTROLBOARD

U

VIO

CONTROLBOARD

CONTROLBOARD

3

CONTROLBOARD

2

* 2 stage heat shown. Connect orange wire fromHeater 2 HC1 to orange on TB4 for 1 stage heat.

LS1ORN

LS1 LS2ORNORN ORN

LS1ORN

LS1 LS2ORNORN ORN

C11134

Fig. 36 -- Electric Heater Control Connections -- Air Conditioner with 1 or 2 CRHEATER288A00--293A00

CRHTR,CRSIN

Page 23: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

23

TRAN2

HC2

HC1

HCR2

HCR1 BRN

BRN

BRN

BRN

BRN BRN

BRN

HCR1

HCR2

LS

RED

RED

TB4

RED ORN

ORNEHR

VIO

ORN

TB4

RED

TB

C10563

Fig. 37 -- Electric Heater Control Connections--Heat Pump with 1 CRHEATER294A00--296A00

HC2

HC1

HCR2

HCR1 BRN

BRN

BRN

BRN

BRN BRN

HCR1

HCR2

RED

ORN

VIO

ORN

TB4

TB4

12 CONTROLBOARD

U

8

CONTROLBOARD

CONTROLBOARD

3

CONTROLBOARD

12 VIO

RED

REDLS1LS1 LS2

RED

C11135

Fig. 38 -- Electric Heater Control Connections -- Air Conditioner with 1 CRHEATER294A00--296A00

CRHTR,CRSIN

Page 24: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

24

TRAN2

HC2

HC1

HC1

HCR2

HCR1

BRN

BRN

BRN

BRN

BRN

BRN BRN

TB

HCR2

HCR1LS

RED

RED

TB4

RED ORN

EHRORN

ORN

VIO ORN

TB4

LS

1-STG HEATER

2-STG HEATER

BRNRED

C10564

Fig. 39 -- Electric Heater Control Connections--Heat Pump with 1 CRHEATER288A00--293A00Plus 1 CRHEATER294A00--296A00 (2--Stage Heater)

Terminal Block 4(TB4)

Heater Cover

C10173

Fig. 40 -- Heater Wiring

CRHTR,CRSIN

Page 25: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

25

Terminal Block 4(TB4)

Heater Covers

C10171

Fig. 41 -- Heater Wiring and Covers

C11512

Fig. 42 -- Max. Air Temp/Max. Ext. Static

CRHTR,CRSIN

Page 26: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

26

APPENDIX ACOOLING APPLICATIONS

SPBCRSINGLEnnnA00

AC---1 Units AC---2 Units04---07036---072

08090

09---12102---121

14150 04---06 07 08---09

NONE Fig. 43 Fig. 43037 Fig. 44 Fig. 44038 Fig. 45 Fig. 45040 Fig. 46 Fig. 46042 Fig. 44 Fig. 44043 Fig. 47 Fig. 47044 Fig. 48045 Fig. 49046047 Fig. 44 Fig. 44 Fig. 44049 Fig. 50 Fig. 51 Fig. 50050 Fig. 52 Fig. 52 Fig. 52051 Fig. 53 Fig. 54 Fig. 53

Unit Control BoxC IFC

13 13 11

HEATER

HeaterWires

Unit DisconnectMOCP 60-A Max

FieldPowerConductors

C10484

Fig. 43 -- AC and Heat Pump No Single Point Box

CRHTR,CRSIN

Page 27: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

27

Unit Control BoxHP-1 SIZE 14 AND 150 ONLY

ALL UNITSUnit Control BoxEXCEPT HP-1

SIZE 14 AND 150C IFC

TB

HEATER

HEATER #2IF USED

TBI

11 12 13

11 1313

BLK YEL BLU

BLK YEL BLU

BLK

YEL

BLU

HEATERWIRESSPB

037A042A047A

TAPCONDUCTORS

FIELDPOWERCONDUCTORS

UNIT DISCONNECTMOCP 60-A MAX

C10485

Fig. 44 -- AC and Heat Pump Single Point BoxCRSINGLE037A00, 042A00, 047A00

Unit Control BoxC IFC

FU2HEATER

FU3HEATER

!!"5"5

HeaterWires

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

FieldPower Conductors

Tap Conductors

13 13 11

Field TapPower Conductors

Heater 104 #2if used

Heater 104 #1or Heater 105

C10486

Fig. 45 -- AC Single Point Box CRSINGLE038A00

CRHTR,CRSIN

Page 28: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

28

Unit Control BoxC IFC

FU2HEATER

FU3HEATER

HeaterWires

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

FieldPower Conductors

Tap Conductors

13 13 11

C10487

Fig. 46 -- AC Single Point Box CRSINGLE040A00 Single Phase

Unit Control BoxC

11 13 11 13

IFCTB-10BTB-10A

FU2HEATER111A or 112A

CIR 1

CIR 2

BLU BLUBLK BLKYEL YEL

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

ALT.TWO HEATER

MODULESFactory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

FU3

C10489

Fig. 47 -- AC Single Point Box CRSINGLE043A00

CRHTR,CRSIN

Page 29: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

29

Unit Control BoxC IFC

TB

FU2HEATER

FU3HEATER

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

11

TapConductors

FieldPowerConductors

HeaterWires

13 13

C10490

Fig. 48 -- AC Single Point Box CRSINGLE044A00

Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.

Unit Control Box C IFC

FU2HEATER111A or 112A

CIR 1

CIR 2

HEATER

11 13 11 13

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

BLU BLUBLK BLKYEL YEL

TB-10BTB-10A

FU3

FU4

C10491

Fig. 49 -- AC Single Point Box CRSINGLE045A00

CRHTR,CRSIN

Page 30: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

30

Unit Control BoxC

11 13 11 13

IFCTB-10BTB-10A

FU2HEATER111A or 112A

CIR 1

CIR 2

BLU BLUBLK BLKYEL YEL

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

ALT.TWO HEATER

MODULESFactory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

FU3

C10489

Fig. 50 -- AC Single Point Box CRSINGLE049A00(Except Size 14 and 150)

Unit Control BoxC2 TB-10 C1 IFC

FU2HEATER112A

CIR 1

HEATER117A or 110A

CIR 2

$$&:&:

11 13 11 13 13

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

BLU BLUBLK BLKYEL YEL

FU3

C10566

Fig. 51 -- AC Single Point Box CRSINGLE049A00(Size 14 and 150 Only)

CRHTR,CRSIN

Page 31: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

31

Unit Control BoxC IFC

TB

FU2HEATER

FU3HEATER

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

11

TapConductors

FieldPowerConductors

HeaterWires

13 13

C10490

Fig. 52 -- AC Single Point Box CRSINGLE050A00

Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.

Unit Control Box C IFC

FU2HEATER111A or 112A

CIR 1

CIR 2

HEATER

11 13 11 13

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

BLU BLUBLK BLKYEL YEL

TB-10BTB-10A

FU3

FU4

C10491

Fig. 53 -- AC Single Point Box CRSINGLE051A00(Except Size 14 and 150)

CRHTR,CRSIN

Page 32: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

32

Unit Control Box C2 C1 TB-10 IFC

FU2HEATER112A

CIR 1

CIR 2

HEATER117A or 110A

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.

11 13 11 13 13

FU3

FU4

C10567

Fig. 54 -- AC Single Point Box CRSINGLE051A00(Size 14 Only and 150)

CRHTR,CRSIN

Page 33: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

33

APPENDIX BHEAT PUMP APPLICATIONS

SPBCRSINGLEnnnA00 HP---1 Units HP---2 Units

04---07036---072

08---09090---102

12121

14150 04---06

NONE Fig. 43* Fig. 43*037 Fig. 44* Fig. 44038 Fig. 55 Fig. 55039 Fig. 56040 Fig. 57 Fig. 57041 Fig. 58 Fig. 58047 Fig. 44* Fig. 44* Fig. 44*049 Fig. 59 Fig. 60050 Fig. 61 Fig. 61 Fig. 62051 Fig. 63 Fig. 64 Fig. 65052 Fig. 66 Fig. 66 Fig. 67053 Fig. 68 Fig. 69 Fig. 70054 Fig. 71 Fig. 72 Fig. 73

* Figure is in Appendix A

Unit Control Box C IFC

!! !!

FU2

HTR

7

TapConductors

FieldPowerConductors

HeaterWires

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

BLUBLK YEL

11 13 11 13

FU3

C10497

Fig. 55 -- Heat Pump Single Point Box CRSINGLE038A00

CRHTR,CRSIN

Page 34: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

34

Unit Control BoxC IFC

!! !!

FU2

HTR 1

HTR 2

HeaterWires

Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.

TapConductors

FieldPowerConductors

BLUBLK YEL

11 13 11 13

FU3

FU4

C10498

Fig. 56 -- Heat Pump Single Point Box CRSINGLE039A00

Unit Control Box C

FU2

HTR 1

HeaterWires

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

FieldPowerConductors

TapConductors

BLK YEL

11 23

FU3

C10499

Fig. 57 -- Heat Pump Single Point Box CRSINGLE040A00 1--Phase

CRHTR,CRSIN

Page 35: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

35

Unit Control BoxC

!! !!

FU2

HTR 1

HTR 2

11

TapConductors

FieldPowerConductors

HeaterWires

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.

23

FU3

C10500

Fig. 58 -- Heat Pump Single Point Box CRHEATER041A00 1--Phase

Unit Control BoxC IFC

FU2

HEATER 117A OR 110A

08 09 12

:

TB-10A

HeaterWires

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

TapConductors

FieldPowerConductors

11 13 11 13

BLU BLUBLK BLKYEL YEL

TB-10B

FU3

C10501

Fig. 59 -- Heat Pump Single Point Box CRHEATER049A00(Except Size 12 and 121)

CRHTR,CRSIN

Page 36: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

36

Unit Control BoxC2 C1 IFC

FU2

FU3

HEATER 117A OR 110A

11 13 11 13 13

TB-10

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

BLUBLK YEL BLUBLK YEL

Factory wiring connects line-sideof FU2 to line-side terminals on FU3.This wiring not illustrated for simplicity in this figure.

HEATERWIRES

C10568

Fig. 60 -- Heat Pump Single Point Box CRHEATER049A00(Size 12 Only and 121)

Unit Control Box C IFC

TB

FU2

HEATER 116A

HEATER 1 HEATER 114A

08 08 09 09 12 12

NOTE: ALL HEATERS CONNECT TO FU3

!!"7"711 13 13

TapConductors

FieldPowerConductors

BLU BLUBLK BLKYEL YEL

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU3.This wiring not illustrated for simplicity in this figure.

HeaterWires

6 Wires

FU3

C10502

Fig. 61 -- Heat Pump Single Point Box CRHEATER050A(Except Size 14 and 150)

CRHTR,CRSIN

Page 37: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

37

Unit Control Box

TB

FU2

HEATER CIR 1 289A

CIR 2 HEATER 292A

14 14

NOTE: ALL HEATERS CONNECT TO FU3

11 12 13

TB1

BLUBLK YEL

HEATERWIRES

6 WIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU3.This wiring not illustrated for simplicity in this figure.

FU3

C10569

Fig. 62 -- Heat Pump Single Point Box CRHEATER050A00(Size 14 Only and 150)

!"

Unit Control BoxC IFC

FU2

FU3

CIR 1

FU4HEATER 112A

CIR 2

11 13 11 13

HeaterWires

Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.

BLU BLUBLK BLKYEL YEL

TapConductors

FieldPowerConductors

TB-10A TB-10B

C10503

Fig. 63 -- Heat Pump Single Point Box CRHEATER051A00(Except Size 12--14 and 121--150)

CRHTR,CRSIN

Page 38: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

38

Unit Control Box C2 TB-10 C1 IFC

FU2

HEATER 112A

CIR 1

HEATER 117A or

CIR 2 110A

11 13 11 13 13

BLUBLK YEL BLUBLK YEL

Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

FU3

FU4

C10570

Fig. 64 -- Heat Pump Single Point Box CRHEATER051A00(Size 12 Only and 121)

Unit Control Box

FU2

FU3

FU4 HEATER 291A

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

Factory wiring connects line-sideof FU2 to line-side terminals on FU3-FU4.This wiring not illustrated for simplicity in this figure.

11 12 13

BLUBLK YEL

TB1

C10571

Fig. 65 -- Heat Pump Single Point Box CRHEATER051A00(Size 14 Only and 150)

CRHTR,CRSIN

Page 39: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

39

!"

Unit Control Box C IFC

TB

FU3

HEATER 1

HEATER 2

08 09 12

HeaterWiresFactory wiring connects line-side

of TB to line-side terminals on FU2-FU4.This wiring not illustrated for simplicity in this figure.

TapConductors

FieldPowerConductors

11 13 13

BLU BLUBLK BLKYEL YEL

FU4

FU2

C10504

Fig. 66 -- Heat Pump Single Point Box CRHEATER052A00(Except Size 14 and 150)

Unit Control Box

TB

FU2

FU3

CIR 1

FU4 HEATER 294A

CIR 2

11 12 13

TB1

BLUBLK YEL

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU4.This wiring not illustrated for simplicity in this figure.

C10572

Fig. 67 -- Heat Pump Single Point Box CRHEATER052A00(Size 14 and 150 Only)

CRHTR,CRSIN

Page 40: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

40

Unit Control BoxC IFC

TB

FU2

FU3

CIR 1

FU4HEATER 112A

CIR 2

FU5

HEATER 117A

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU5.This wiring not illustrated for simplicity in this figure.

TB-10BTB-10A

11 13 11 13

TapConductors

FieldPowerConductors

HeaterWires

BLU BLUBLK BLKYEL YEL

C10505

Fig. 68 -- Heat Pump Single Point Box CRHEATER053A00(Except Size 12--14 and 121--150)

CRHTR,CRSIN

Page 41: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

41

Unit Control Box C2 C1 IFC

TB

FU2

FU3 HEATER 117A or 110A (when used)

FU4HEATER 112A

CIR 1

FU5

CIR 2

TB-10

11 1113 13 13

TAPCONDUCTORSFIELD

POWERCONDUCTOR

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU5.This wiring not illustrated for simplicity in this figure.

BLUBLK YEL BLUBLK YEL

HEATERWIRES

C10573

Fig. 69 -- Heat Pump Single Point Box CRHEATER053A00(Size 12 and 121 Only)

CRHTR,CRSIN

Page 42: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

42

Unit Control Box

TB

FU2

FU3

FU4

HEATER 288A

CIR 1

HEATER 294A

FU5

HEATER 291A

CIR 2

HEATERWIRES

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU5.This wiring not illustrated for simplicity in this figure.

BLUBLK YEL

11 12 13

TB1

1414

C10574

Fig. 70 -- Heat Pump Single Point Box CRHEATER053A00(Size 14 and 150 Only)

CRHTR,CRSIN

Page 43: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

43

Unit Control BoxC TB-1OB IFC

!!!! !!!!

TapConductors

TB

FU2

FU3

FU4

CIR 1

FU5HEATER

112A

CIR 2

FU6

HEATER 117A

HeaterWires

BLU BLUBLK BLKYEL YEL

TB-1OA

11 13 11 13

FieldPowerConductors

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU6.This wiring not illustrated for simplicity in this figure.

C10506

Fig. 71 -- Heat Pump Single Point Box CRHEATER054A00(Except Size 12--14 and 121--150)

CRHTR,CRSIN

Page 44: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

44

Unit Control Box C2 TB-10 C1 IFC$& $&

TB

FU2

FU3

FU4

CIR 1

FU5 HEATER 112A

CIR 2

FU6

HEATER 117A

or 110A

HeaterConductors

911 13 11 13 13

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU6.This wiring not illustrated for simplicity in this figure.

BLUBLK YEL BLUBLK YEL

C10575

Fig. 72 -- Heat Pump Single Point Box CRHEATER054A00(Size 12 and 121 Only)

CRHTR,CRSIN

Page 45: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

45

Unit Control Box

TB

FU2

FU3

FU4

HEATER 288A or 291A

FU5

CIR 1

HEATER 294A

FU6

CIR 2

11 12

TB1

13

BLUBLK YEL

TAPCONDUCTORS

FIELDPOWER

CONDUCTOR

HEATERWIRES

Factory wiring connects line-sideof TB to line-side terminals on FU2-FU6.This wiring not illustrated for simplicity in this figure.

14

C10576

Fig. 73 -- Heat Pump Single Point Box CRHEATER054A00(Size 14 and 150 Only)

CRHTR,CRSIN

Page 46: CRHEATER101A00 -- CRHEATER119A00, …dms.hvacpartners.com/docs/1009/Public/00/IIK-CRHTRSIN01-05.pdf · CRHEATER264A00 --CRHEATER269A00, CRHEATER288A00 --CRHEATER299A00 CRHEATER301A00

46

APPENDIX CELECTRIC HEATER DATA

CRHEATERXXXX00

SALESPKG

NUMBER

HEATERMODELNUMBER

VOLTS KW FLA1---PH

FLA3---PH

QTYCIRS

50TC558JRAS

50TCQ548JRHS

50HC551J

50HCQ549J

Used onAC---1 HP---1 AC---2 HP---2

101A 001A 208 / 240 3.3 / 4.4 15.9 / 18.6 9.4 / 10.6 1

04---07036---072

04---07036---072

04---06 04---06

102A 002A 208 / 240 4.9 / 6.5 23.6 / 27.3 13.8 / 15.7 1

103B 003B 208 / 240 6.5 / 8.7 31.2 / 36.2 18.1 / 20.7 1

104B 004B 208 / 240 7.9 / 10.5 38.0 / 43.8 22.2 / 25.3 1

105A 005A 208 / 240 12.1 / 16.0 --- --- --- 33.6 / 38.4 1

106A 006A 480 6.0 --- --- --- 7.0 1

107A 007A 480 8.8 --- --- --- 10.5 1

108A 008A 480 11.5 --- --- --- 13.8 1

109A 009A 480 14.0 --- --- --- 16.8 1

297A 297A 600 10.0 --- --- --- 9.2 1

298A 298A 600 15.0 --- --- --- 13.8 1

301A 301A 600 25.0 --- --- --- 23.1 2 06 06

110A 010A 208 / 240 12.0 / 16.0 --- --- --- 33.3 / 38.5 1

08---14090---150

08---12090---121 07---12 07---09

111A 011A 208 / 240 18.6 / 24.8 --- --- --- 51.7 / 59.7 2

112A 012A 208 / 240 24.0 / 32.0 --- --- --- 66.7 / 77.1 2

113A 013A 480 16.5 --- --- --- 19.8 1

114A 014A 480 27.8 --- --- --- 33.4 1

115A 015A 480 33.0 --- --- --- 39.7 1

116A 016A 480 13.9 --- --- --- 16.7 1

117A 017A 208 / 240 7.8 / 10.4 --- --- --- 21.7 / 25.0 1

118A 018A 600 18.0 --- --- --- 17.0 1

119A 019A 600 36.0 --- --- --- 34.0 1

264A 264A 208 / 240 4.9 / 6.5 --- --- --- 13.5 / 15.6 1

07 07

265A 265A 480 6.0 --- --- --- 7.2 1

266A 266A 480 11.5 --- --- --- 13.8 1

267A 267A 480 14.0 --- --- --- 16.8 1

268A 268A 480 23.0 --- --- --- 27.7 2

269A 269A 480 25.5 --- --- --- 30.7 2

288A 288A 208 / 240 7.5 / 10 --- --- --- 21.3 / 24.5 1

16180

14150 14 12

289A 289A 480 10.0 --- --- --- 12.1 1

290A 290A 600 10.0 --- --- --- 9.6 1

291A 291A 208 / 240 12.4 / 16.5 --- --- --- 34.5 / 39.7 1

292A 292A 480 16.5 --- --- --- 19.9 1

293A 293A 600 16.5 --- --- --- 15.9 1

294A 294A 208 / 240 25.2 / 33.5 --- --- --- 70.0 / 80.6 2

295A 295A 480 33.5 --- --- --- 40.3 2

296A 296A 600 33.5 --- --- --- 32.2 2

299A 299A 600 28.0 --- --- --- 25.7 2 07 07

Copyright 2012 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 01/12

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No:IIK---CRHTRSIN01---05

Replaces: IIK---CRHTRSIN01---04

CRHTR,CRSIN