1
PART NUMBER:CPLOWAMB001A00CPLOWAMB002A00
Installation Instructions
SMALL PACKAGED PRODUCTS
1---1/2 to 5 TONS (50/60 Hz)
MOTORMASTER II HEAD PRESSURE CONTROLLER
NOTE: Read the entire instruction manual before starting theinstallation.
SAFETY CONSIDERATIONSInstallation and servicing of this equipment can be hazardous due tomechanical and electrical components. Only trained and qualifiedpersonnel should install, repair, or service this equipment.
Untrained personnel can perform basicmaintenance functions suchas cleaning and replacing air filters. All other operations must beperformed by trained service personnel. When working on thisequipment, observe precautions in the literature, on tags, and on la-bels attached to or shippedwith theunit and other safety precautionsthat may apply.
Follow all safety codes. Installation must be in compliance with lo-cal and national building codes. Wear safety glasses, protectiveclothing, and work gloves. Have fire extinguisher available. Readthese instructions thoroughly and follow all warnings or cautionsincluded in literature and attached to the unit.
Recognize safety information. This is the safety--alert symbol .Whenyou see this symbolon theunit and in instructions ormanuals,be alert to the potential for personal injury. Understand these signalwords; DANGER, WARNING, and CAUTION. These words areusedwith the safety--alert symbol.DANGER identifies themost se-rious hazards which will result in severe personal injury or death.WARNING signifies hazards which could result in personal injuryor death. CAUTION is used to identify unsafe practices whichmayresult in minor personal injury or product and property damage.NOTE is used to highlight suggestions which will result in en-hanced installation, reliability, or operation.
Follow all safety codes.Wear safety glasses and work gloves. Havea fire extinguisher available.
ELECTRICAL SHOCK HAZARDFailure to follow this warning could cause personal injuryor death.Before performing service or maintenance operations onunit, turn off main power switch to unit and install lockouttag. Ensure electrical service to rooftop unit agrees withvoltage and amperage listed on the unit rating plate.
! WARNING
INTRODUCTIONThese instructions cover the installation of the Motormaster IIController head pressure control device. Refer to the Installationsection for directions. Louvered panels are required for thisinstallation; see Item 9 in the Installation section of this documentand Tables 1 and 2 for more information.
Table 1 – Add Louvered Panels to These Units48ES 574D
48GS 582A PY1P---B
48GX 583A PY2P---B
48SD 574A
48SZ 674A
50ES 704D
50GS 701A PA1P---B
50GX 702A PA2P---B
50JS 601A PH1P---B
50JX 602A PH2P---B
50SD 704A
50SZ 604A
Table 2 – Do NOT Add Louvered Panels to These Units48VL 577C
50SX 557A
50HX 657A
50VL 707C
50ZP 564A PA1Z
50ZH 664A PH1Z
50ZHA 664B PH3Z
50ZPA 564B PA3Z
50JZ* 602B*
48GP* 583B*
48CE* 574C
48DT* 677B
48DU* 577B
48JZ* 583B*
48XP* 574B*
48XZ* 674B
50CE* 704C*
50CR* 604C*
50DT* 607B*
50DU* 707B*
50GL* 702B*
50XP* 704B*
50XZ* 604B*
*Louvered panels are standard on these units.
2
Motormaster® II Controller InteriorC00102
Fig. 1 -- Controller Interior
SENSOR INTEGRALWIRE TIE
CONDUCTIVE GREASE3/8"HEADER TUBE
NOTE: INSTALLED SENSOR MUST BE LEFT UNINSULATED.
Sensor Connection DetailsC00103
Fig. 2 -- Sensor Connection Details
DESCRIPTION AND USAGEThe Motormaster II head pressure controller is a cycle controldevice activated by a temperature sensor mounted on a headertube of the outdoor coil (see Fig. 1). It is designed to cycle theoutdoor--fan motors to maintain the saturated condensingtemperature within normal operating limits of approximately 130to 110_F high (54_C to 43_C), 70 to 50_F low (21 to 10_C).The controller maintains working head pressure at low ambienttemperatures down to --20_F (--29_C) when properly installed.
INSTALLATION1. Disconnect power to unit. Install lockout tag.
2. Remove unit access panel.
3. Disconnect outdoor--fan motor (OFM). (See WiringSchematic, Fig. 8 or 9.)
4. Remove OFM wires from unit control box.
5. Mount Motormaster II Controller on unit. Refer to Fig.3--6. The controller must be mounted vertically with theleads at the bottom. Using the Mounting Template (Fig.10) as a guide, drill mounting holes. To ensure electricalground, insert star washers (supplied with the controller)under the heads of mounting screws.
NOTE: Field--supplied conduit must be used between controllerand access panel (or wire into unit entrance).
6. Determine sensor location by referring to Fig. 11--38.Route sensor wire through bottom of Motormaster IIController (Fig. 1) to sensor location specified. Prior toinstallation, apply conductive grease supplied withaccessory to contact surface of sensor.
COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in componentdamage.
Sensor assembly is delicate. Handle with care.
CAUTION!
7. Attach sensor to top half of header tube as shown in Fig.2. Installed sensor must be left uninsulated.
8. Power wiring must comply with all local and NationalElectrical Code (NEC) and International Electric Code(IEC) requirements. Refer to Fig. 8 and 9 for power wiringconnections. Coil up all excess wire and secure. (Yellowand blue wires, from controller, must run to unit contactorand connect on the load side.)
UNIT OPERATION AND COMPONENT DAMAGEHAZARD
Failure to follow this caution may result in improper unitoperation or component damage.All wires must be secured so that they are not in contactwith unit tubing.
CAUTION!
9. To prevent wind cross--currents form causing abnormallylow condensing temperatures, louvered panels are requiredon some models. See Table 1 and 2 for modelsrequiring/not requiring louvered panels.
10. Reconnect power to the unit.
The Motormaster II head pressure controller is equipped with analternate operating mode. When this mode is selected, thecontroller shifts the fan cycle sequence to effectively raise theaverage condensing temperature approximately 20_F higher thanthe standard operating mode. In this alternate mode, the outdoorfan begins cycling at higher outdoor ambient temperatures. Thismode should only be used if the evaporator coil shows signs offrosting at low outdoor ambient temperatures.
To select the alternate operating mode, move the jumper wire onthe Motormaster II control board from reset T1 to T2.
Refer to Fig. 7 for thermistor resistance vs. temperature.
CPLOWAMB
3
MOTORMASTER IIWIRE LEADS
BULKHEAD
MOTORMASTER II
COMPRESSOR
CONDENSER COIL SLICE PLASTICSERVICE CAP DNUNIT AND FEEDLEADS
50ZP, ZH, 564A/664A, PA1Z/PH1Z UNITS
C00108
Fig. 3 -- Mounting Locations
CONDUIT
HOLE LOCATIONFOR CONDUITCONNECTION
6”FROM BOTTOM
OF UNIT
MOTORMASTER IICONTROLLER
EVAP COILACCESS PANEL1 3/8”
MOTORMASTER IICONTROLLER
CONDUIT
50SX/ 557A50HX/ 657A
C00141
Fig. 4 -- Mounting Locations
MOTORMASTER IIWIRE LEADS
BULKHEAD
MOTORMASTER II
SLICE PLASTICSERVICE CAP ONUNIT AND FEED LEADS
COMPRESSOR
48/50GS, GX, JS, JX, GP, GL, JZ UNITS582A/701A, 583A/702A, 601A, 602A, 583B, 702B, 602B,683B
PY1P-B/PA1P-B, PY2P-B/PA2P-B, PH1P-B, PH2P-B
SMALL CABINET
C00109
Fig. 5 -- Mounting Locations--Small Cabinet
MOTORMASTER IIWIRE LEADS
BULKHEAD
MOTORMASTER II
SLICE PLASTICSERVICE CAP ONUNIT AND FEED LEADS
COMPRESSOR
48/50GS, GX, JS, JX, GP, GL, JZ UNITS582A/701A, 583A/702A, 601A, 602A, 583B, 702B, 602B, 683B
PY1P-B/PA1P-B, PY2P-B/PA2P-B, PH1P-B, PH2P-B
LARGE CABINET
C00110
Fig. 6 -- Mounting Locations--Large Cabinet
CPLOWAMB
4
Table 3 – Sensor Location IndexMODEL NUMBER FIGURE NUMBER
50JX/602A/PH2P---B 024---048 Fig. 11
50JX/602/PH2P---B 060 AND 50JS/601A/PH1P---B 018---030 Fig. 12
50JS/601A/PH1P---B 036---060 Fig. 13
48GS/582A/PY1P---B/50GS/701A/PA1P---B 018---036 AND 48GX/583A/PY2P---B/50GX/702A/PA2P---B 024---030 Fig. 14
48GS/582A/PY1P---B/50GS/701A/PA1P---B 042---060 AND 48GX/583A/PY2P---B/50GX/702A/PA2P---B 036---060 Fig. 15
48GP/50GL/583B/702B 024---048 AND 50GL 024---048 Fig. 16
48GP/50GL/583B/702B 060 Fig. 17
48/50JZ/683B/602B 024---060 Fig. 18
50ZP/564A/PA1Z 024---042 Fig. 19
50ZP/564A/PA1Z 048---060 Fig. 20
50ZH/664A/PH1Z 024---042 Fig. 21
50ZH/664A/PH1Z 048---060 Fig. 22
50SZ/557A 024---060 Fig. 23
50HX/657A 048---060 Fig. 24
50HX/657A 024---042 Fig. 25
48ES/50ES/574D/704D 018---060 Fig. 26
48XP/50XP/48CE/50CE/577B/574C/704B/704C 024---060 Fig. 27
48DT/50DT/607B/677B 024---042 Fig. 28
48DU/50DU/48BL/50VL/577B/707B/577C/707C 042---060 Fig. 29
48SD/50SD/574A/704A/PY3P/PA3P 024---060 Series 301 AND A Fig. 30
48SD/50SD/574A/704A/PA3P/PY3P 024---042 Series 311 AND B Fig. 31
48DT/50DT/677B/607B 048---060 Fig. 32
48DU/50DU/577B/707B 024---036 AND 48VL/50VL/577C/707C 036---042 Fig. 33
48SZ/50SZ/674A/604A 024---060 Fig. 34
48VL/50VL/577C/707C 018---030 AND 060 Fig. 35
48XZ/50XZ/50CR/674B/604B 024---060 AND 604C 030---060 Fig. 36
50ZHA/50ZPA/564B/664B/PA3Z/PH3Z 024---042 Fig. 37
50ZHA/50ZPA/564B/664B/PA3Z 048---060 AND PH3Z048 AND PH3P 060 Fig. 38
20
40,000
30,000
20,000
10,000
040 60 80 100 120 140
50,000
TEMPERATURE (F)
RE
SIS
TAN
CE
(O
HM
S)
Thermistor Resistance vs TemperatureC00104
Fig. 7 -- Thermistor Resistance vs. Temperature Chart
CPLOWAMB
5
SINGLE-PHASE UNITS
UNIT CONTROL BOX
3-PHASE UNITS
UNIT CONTROL BOX
LOW VOLTAGECONTROL BOX*
048.060UNITS
BLK
YEL
BLK
YELYEL
YEL
YEL
YEL
YEL
BLK
BRN
OUTDOOR-FAN MOTOR
THIS WIRERELOCATEDFROM BASEUNIT CONTACTOR
VIEW A
OFC
OFCYEL
MOTORMASTER II CONTROL BOX
BLK
BLK
BLU
BLU
BLK
BLK
BLU
VIEW A208/230-V
UNITS ONLY
OF1 OF2
DR
OFR RED BRN
TRAN(SEENOTE #1)
LOGIC BOARD
GRN-YEL
BRNORG
YEL
YEL
CONTROL THERMISTOR
RELOCATE JUMPER TOTERMINAL T2 FORALTERNATE OPERATION.
O
C
CL1 T1
L2 T2
21
23
C
C
21
23
L1 T1
L2 T2
A C
CR
C1 C2
W1
T1
T2 S2
S1
OFC
C460 230 208
1 3
24
LEGEND
C ContactorDR Defrost RelayOFC Outdoor-Fan ContactorOFR Outdoor-Fan RelayTRAN Transformer
Field Wiring
*In low voltage control box, “O” is orange and “C” is Brown (common).NOTES:1. Motomaster® II transformer is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap.2. Relay, part no. HN61KB324, is field supplied and normally closed.3. CPLOWAMB002A00 transformer only contains a 400-v. supply.
460-VUNITS ONLY
ORANGERED
Field supplied relay for allHeat pumps should belocated in the control box ofthe unit.
(SEENOTE #2)
COIL
4 5
13
C00106
Fig. 8 -- Wiring Schematic Heat Pumps
CPLOWAMB
6
C
21
23
T1L1
UNIT CONTROL BOX UNIT CONTROL BOX
BLU
YEL
SINGLE-PHASE UNITS 3-PHASE UNITS
C
C
C
BLU
YEL
MOTOMASTER CONTROL BOX
BLK
OUTDOOR-FAN MOTOR
THIS WIRE RELOCATEDFROM BASE UNITCONTACTOR
L2 T2
L2
L1
T2
T1
OFC
OFCBLK
BLK SEENOTE YEL
ORANGERED
460 230 208 C
CA
RED BRN24
GRN-YEL
ORG BRN
C1 C2OFC
R
W1
T2
T1
S2
S1
LOGIC BOARD
YEL
YEL
RELOCATE JUMPER TOTERMINAL T2 FORALTERNATE OPERATION CONTROL THERMISTOR
C - ContractorOFC - Outdoor- Fan ContactorTRAN - Transformer
NOTE:1. Motormaster® II is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap.2. CPLOWAMB002A00 Transformer only contains a 400V supply.
LEGEND
C00140
Fig. 9 -- Wiring Schematic, AC and Gas PACs
CPLOWAMB
7
MOUNTING TEMPLATE
CUT ALONGSOLID BORDERLINES TOREMOVETEMPLATE
5-3/8-in. REF [136.5]
TOP
DRILL 9/64-in. [3.6]DIAMETER HOLE
TEMPLATE FORMOTORMASTER® IICPLOWAMB001A00
NOTE: Dimensions in [ ] are in millimeters
DRILL 9/64-in. [3.6]DIAMETER HOLE
2-3/8-in. REF[60.3]
9-in. REF[228.6]
5-in.[127]
1-1/8-in. REF[28.6]
C00105V2
Fig. 10 -- Controller Mounting Template
CPLOWAMB
8
SENSORLOCATION
SENSORLOCATION
SENSORLOCATION
50 JX, 602A, PH2P-B 024Left Back
SENSORLOCATION
50 JX, 602A, PH2P-B 042Left Back
50 JX, 602A, PH2P-B 048Left Back
50 JX, 602A, PH2P-B 030/036Left Back
A07440
Fig. 11 -- Sensor Mounting Location
SENSORLOCATION
SENSORLOCATION
50JX, 602A,PH2P-B 060LEFT BACK
50JS, 601A,PH1P-B 024LEFT BACK
SENSORLOCATION
SENSORLOCATION
50JS, 601A,PH1P-B 018LEFT BACK
50JS, 601A,PH1P-B 030LEFT BACK
A07441
Fig. 12 -- Sensor Mounting Location
SENSORLOCATION
SENSORLOCATION SENSOR
LOCATION
SENSORLOCATION
50JS.601A.PHIP-B 036
LEFT BACK
50JS.601A.PHIP-B 042
LEFT BACK
50JS.601A.PHIP-B 048
LEFT BACK
50JS.601A.PHIP-B 060
LEFT BACK
A07442
Fig. 13 -- Sensor Mounting Location
RETURN BEND END
RETURN BEND END
SENSORLOCATION
SENSORLOCATION
48GS, 582A, PY1P-B, 50GS, 701A, PA1P-B, 018, 024, 030 & 03648GX, 583A, PY2P-B, 024, 50GX, 702A, PA2P-B, 024
LEFT BACK
50/48GX030, 702A/583A030, PA2P/PY2P 030 (B SERIES)LEFT BACK
A07443
Fig. 14 -- Sensor Mounting Location
CPLOWAMB
9
SENSORLOCATION
48/50GX060702A/582A/583A060PA2P/PY1P/PY2P060 (B SERIES)
LEFT BACK
RETURN BEND END
SENSORLOCATION
50/48GS048701A/582A048PA1P/PY1P048 (B SERIES)
LEFT BACK
RETURN BEND END
SENSORLOCATION
48GS.582A,PY1PB04250GS,701A,PY2PB04248GX,583A,PY2P-B 03650GX,702A,PA2P-B 036
LEFT BACK
RETURN BEND END
SENSORLOCATION
50/48GS/060701A/582A060PA1P/PY1P06048/50GX042&048583A/702A042&048PY2P/PA2P042&048 (B SERIES)
LEFT BACK
RETURN BEND END
A07444
Fig. 15 -- Sensor Mounting Location
48GP024/50GL024583B024/702B024
LEFT BACK48GP030/50GL030583B030/702B030
LEFT BACK
48GP036/50GL036583B036/702B036
LEFT BACK 48GP042, 048/50GL042, 048583B042, 048/702B042, 048
LEFT BACK
SENSORLOCATION SENSOR
LOCATION
SENSORLOCATION SENSOR
LOCATION
A07445
Fig. 16 -- Sensor Mounting Location
CPLOWAMB
10
SENSOR LOCATION
48GP060/50GL060583B060/702B060
LEFT BACKA07446
Fig. 17 -- Sensor Mounting Location
48/50JZ024683B/602B024
LEFT BACK
SENSORLOCATION
48/50JZ030, 036683B/602B030, 036
LEFT BACK
SENSORLOCATION
48/50JZ060683B/602B060
LEFT BACK
SENSORLOCATION
48/50JZ042, 048683B/602B042, 048
LEFT BACK
SENSORLOCATION
A07447
Fig. 18 -- Sensor Mounting Location
CPLOWAMB
11
SENSORLOCATION
50ZP, 564A, PA1Z024 50ZP, 564A, PA1Z030
SENSORLOCATION
50ZP, 564A, PA1Z042
SENSORLOCATION
50ZP, 564A, PA1Z036
SENSORLOCATION
A07448
Fig. 19 -- Sensor Mounting Location
SENSORLOCATION
50ZP/564A/PA1Z060
SENSORLOCATION
50ZP/564A/PA1Z048
A07449
Fig. 20 -- Sensor Mounting Location
CPLOWAMB
12
SENSORLOCATION
50ZH/664A/PH1Z024
SENSORLOCATION
50ZH/664A/PH1Z030
SENSORLOCATION
50ZH/664A/PH1Z042
SENSORLOCATION
50ZH/664A/PH1Z036
A07450
Fig. 21 -- Sensor Mounting Location
SENSORLOCATION
50ZH/664A/PH1Z048
SENSORLOCATION
50ZH/664A/PH1Z060
A07451
Fig. 22 -- Sensor Mounting Location
CPLOWAMB
13
SENSORLOCATION
SENSORLOCATION
SENSORLOCATION
SENSORLOCATION
50SX/557A 024 50SX/557A 030/036
50SX/557A 042/048 50SX/557A 060A07452
Fig. 23 -- Sensor Mounting Location
SensorLocation
SensorLocation
50HX/657A/048 50HX/657A/060A07453
Fig. 24 -- Sensor Mounting Location
CPLOWAMB
14
SensorLocation
50HX/657A024
SensorLocation
50HX/657A030
SensorLocation
50HX/657A036
SensorLocation
50HX/657A042A07454
Fig. 25 -- Sensor Mounting Location
CPLOWAMB
15
SENSORLOCATION
48ES-024 574DNW02450ES-024 704DNX024
SENSORLOCATION
48ES-030 574DNW03050ES-030 574DPW030 704DNX030 704DPX030
SENSORLOCATION
48ES-036 574DNW03650ES-036 574DPW036 574DEW036 704DNX036 704DPX036 704DEX036
SENSORLOCATION
48ES-060 574DNW06050ES-060 574DPW060 574DEW060 704DNX060 704DPX060 704DEX060
SENSORLOCATION
48ES-048 574DNW04850ES-048 574DPW048 574DEW048 704DNX048 704DPX048 704DEX048
SENSORLOCATION
48ES-018 574DNW01850ES-018 704DNX018
LEFT BACK
LEFT BACK
LEFT BACK
LEFT BACK
LEFT BACK
LEFT BACKA07403
Fig. 26 -- Sensor Mounting Location
CPLOWAMB
16
SENSORLOCATION
48XP-024 574BNW02448XP-030 574BNW03050XP-024 704BNX02450XP-030 704BNX03048CE-024 574CNW02448CE-030 574CNW03050CE-024 704CNX02450CE-030 704CNX030
LEFT
SENSORLOCATION
48XP-036 574BNW03650XP-036 574BPW03648CE-036 704BNX03650CE-036 704BPX036
LEFT
SENSORLOCATION
48XP-042 574BNW04250XP-042 574BPW04248CE-042 704BNX04250CE-042 704BPX04248ES-042 574CNW04250ES-042 574CPW042 704CNX042 704CPX042 574DNW042 574DPW042 574DEW042 704DNX042 704DPX042 704DEX042 LEFT
SENSORLOCATION
48XP-048 574BNW04850XP-048 574BPW04848CE-048 704BNX04850CE-048 704BPX048 574CNW048 574CPW048 704CNX048 704CPX048
LEFTLEFT
SENSORLOCATION
48XP-060 574BNW06050XP-060 574BPW06048CE-060 704BNX06050CE-060 704BPX060 574CNW060 574CPW060 704CNX060 704CPX060
A07404
Fig. 27 -- Sensor Mounting Location
CPLOWAMB
17
SENSORLOCATION
48DT-024 677BNW02450DT-024 607BNX024
LEFT
LEFT
LEFT
LEFT
SENSORLOCATION
48DT-030 677BNW03050DT-030 607BNX030
SENSORLOCATION
48DT-036 677BNW03650DT-036 607BNX036
SENSORLOCATION
48DT-042 677BNW04250DT-042 607BNX042
A07405
Fig. 28 -- Sensor Mounting Location
CPLOWAMB
18
SENSORLOCATION
48DU-042 577BNW04848DU-048 577BNW04250DU-042 707BNX04250DU-048 707BNX04848VL-048 577CNW04850VL-048 707CNX048
SENSORLOCATION
48DU-060 577BNW06050DU-060 707BNX060
LEFT
LEFT
A07406
Fig. 29 -- Sensor Mounting Location
CPLOWAMB
19
SENSORLOCATION
48SD-024 574ANW02450SD-024 704ANX024PY3P024 PA3P024
301 and A Series
LEFT
SENSORLOCATION
48SD-030 574ANW03050SD-030 574APW030 704ANX030 704APX030 PY3P024 PA3P024
301 and A SeriesLEFT
SENSOR LOCATION
48SD-036 574ANW03650SD-036 574APW036 574AEW036 704ANX036 704APX036 704AEX036 PY3P036 PA3P036
301 and A Series
LEFT
SENSORLOCATION
48SD-042 574ANW04250SD-042 574APW042 574AEW042 704ANX042 704APX042 704AEX042 PY3P042 PA3P042
301 and A Series
LEFT
SENSORLOCATION
48SD-048 574ANW04850SD-048 574APW048 574AEW048 704ANX048 704APX048 704AEX048 PY3P048 PA3P048
48SD-060 574ANW06050SD-060 574APW060 574AEW060 704ANX060 704APX060 704AEX060 PY3P060 PA3P060
301, 311, A and B Series
SENSORLOCATION
LEFT LEFT
301, 311, A and B Series
A07408
Fig. 30 -- Sensor Mounting Location
CPLOWAMB
20
SENSORLOCATION
48SD-024 574ANW02450SD-024 704ANX024 PA3P024 PY3P024
311 and B Series
48SD-030 574ANW03050SD-030 574APW030 704ANX030 704APX030 PY3P030 PA3P030
SENSORLOCATION
311 and B Series
SENSORLOCATION
48SD-036 574ANW03650SD-036 574APW036 574AEW036 704ANX036 704APX036 704AEX036 PY3P036 PA3P036
311 and B Series
48SD-042 574ANW04250SD-042 574APW042 574AEW042 704ANX042 704APX042 704AEX042 PY3P042 PA3P-042
SENSORLOCATION
311 and B Series
LEFT
LEFT
LEFTLEFT
A07415
Fig. 31 -- Sensor Mounting Location
CPLOWAMB
21
SENSORLOCATION
48DT-048 677BNW04850DT-048 607BNX048
SENSORSENSORLOCATIONLOCATION
48DT-060 677BNW06050DT-060 607BNX060
LEFT LEFTA07409
Fig. 32 -- Sensor Mounting Location
SENSORLOCATION
48DU-024 577BNW02450DU-024 707BNX024
LEFT
SENSOR LOCATION
48DU-030 577BNW03050DU-030 707BNX03048VL-036 577CNW03648VL-042 577CNW04250VL-036 707CNX03650VL-042 707CNX042
LEFT
SENSORLOCATION
48DU-036 577BNW03650DU-036 707BNX036
LEFT
A07410
Fig. 33 -- Sensor Mounting Location
CPLOWAMB
22
SENSORLOCATION
48SZ-024 674ANW02450SZ024 604ANX024
LEFT
SENSORSENSORLOCATIONLOCATION
48SZ-030 674ANW03050SZ-030 674APW030 604ANX030 604APX030
LEFT
48SZ-036 674ANW03650SZ-036 674APW036 604ANX036 604APX036
SENSORSENSORLOCATIONLOCATION
LEFT
SENSORLOCATION
48SZ-042 674ANW04250SZ-042 674APW042 604ANX042 604APX042
LEFT
SENSORLOCATION
48SZ-048 674ANW04850SZ-048 674APW048 604ANX048 604APX048
LEFT
SENSORLOCATION
48SZ-060 674ANW06050SZ-060 674APW060 604ANX060 604APX060
LEFT
A07411
Fig. 34 -- Sensor Mounting Location
CPLOWAMB
23
SENSORLOCATION
48VL-024 577CNW02448VL-030 577CNW03050VL-024 577CPW03050VL-030 707CNX024 707CNX030 707CPX030
LEFT
48VL-060 577CNW06050VL-060 577CPW060 577CEW060 707CNX060 707CPX060 707CEX060
LEFT
SENSORLOCATION
48VL-018 577CNW01850VL-018 707CNX018
LEFT
SENSORLOCATION
A07412
Fig. 35 -- Sensor Mounting Location
CPLOWAMB
24
SENSORLOCATION
48XZ-036 674BNW03650XZ-036 674BPW03650CR-036 604BNX036 604BPX036 604CNX036 604CPX036
SENSORSENSORLOCATIONLOCATION
48XZ-048 674BNW04850XZ-048 674BPW04850CR-048 604BNX048 604BPX048 604CNX048 604CPX048
LEFT
LEFT
48XZ-060 674BNW06050XZ-060 674BPW06050CR-060 604BNX060 604BPX060 604CNX060 604CPX060
LEFT
SENSORLOCATION
48XZ-042 674BNW04250XZ-042 674BPW04250CR-042 604BNX042 604BPX042 604CNX042 604CPX042
LEFT
SENSORLOCATION
48XZ-024 674BNW02448XZ-030 674BNW03050XZ-024 674BPW03050XZ-030 604BNX02450CR-024 604BNX03050CR-030 604BPX030 604CNX030 604CPX030
A07413
Fig. 36 -- Sensor Mounting Location
CPLOWAMB
25
SENSORSENSORLOCATIONLOCATION
50ZHA024 564BNW02450ZPA024 664BNX024 PA3Z024 PH3Z024
SENSORSENSORLOCATIONLOCATION
50ZHA030 564BNW03050ZPA030 564BPW030 664BNX030 664BPX030 PA3Z030 PH3Z030
SENSORLOCATION
50ZHA036 564BNW03650ZPA036 564BPW036 664BNX036 664BPX036 PA3Z036 PH3Z036
A07414
Fig. 37 -- Sensor Mounting Location
CPLOWAMB
26
SENSORLOCATION
50ZHA042 564BNW04250ZPA042 564BPW042 664BNX042 664BPX042 PA3Z042 PH3Z042
SENSORSENSORLOCATIONLOCATION
50ZPA048 564BNW04850ZHA048 564BPW048 664BNX048 664BPX048 PA3Z048 PH3Z048
SENSORLOCATION
50ZHA060 564BNW06050ZPA060 564BPW060 664BNX060 664BPX060 PA3Z060 PH3P060
A07416
Fig. 38 -- Sensor Mounting Location
Copyright 2007 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: IIKCPLOWAMB---01Replaces: IIK 555A--18--37
Printed in U.S.A. Edition Date: 06/07