Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

  • Upload
    dgg

  • View
    275

  • Download
    3

Embed Size (px)

Citation preview

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    1/212

    StruxureWareStruxureWare BuildingBuilding OperationOperation

    CreatingCreating andand ConfiguringConfiguring aa BACnetBACnet NetworkNetwork withwith b3b3BACnetBACnet DevicesDevices

    TutorialTutorial GuideGuide

    04-16030-01-enDecember 2014

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    2/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    3/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    4/212

    Copyright 2014 Schneider Electric. All rights reserved.

    The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are the sole property of SchneiderElectric SA and its subsidiaries. They may not be used for any purpose without the owner's permission, given in writing. This guide and its content are

    protected, within the meaning of the French intellectual property code (Code de la proprit intellectuelle franais, referred to hereafter as "the Code"), underthe laws of copyright covering texts, drawings and models, as well as by trademark law. You agree not to reproduce, other than for your own personal, non-commercial use as defined in the Code, all or part of this guide on any medium whatsoever without Schneider Electric's permission, given in writing. You alsoagree not to establish any hypertext links to this guide or its content. Schneider Electric does not grant any right or license for the personal and non-commercial use of the guide or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.

    Trademarks and registered trademarks are the property of their respective owners.

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    5/212

    Contents

    IntroductionIntroduction

    1 About This Guide ......................................................... 11

    1.1 Purpose of This Guide ................................................................. 13

    1.2 How This Guide is Organized ...................................................... 14

    1.3 Typographical Conventions ......................................................... 15

    2 Additional Information .................................................. 17

    2.1 Where to Find Additional Information ........................................... 19

    2.2 Regulatory Notices ...................................................................... 21

    TutorialTutorial

    3 Our Case Study ........................................................... 25

    3.1 University X ................................................................................. 27

    3.2 Requirements and Specifications ................................................ 30

    3.2.1 Devices Used for This Case Study ............................................. 30

    3.2.2 Software Used in This Tutorial ................................................... 30

    3.2.3 Specifications ........................................................................... 30

    3.3 Focus of This Tutorial .................................................................. 31

    3.3.1 Pre-existing Project Database Folders and Programs ................ 31

    3.3.2 Pre-existing Project Database Objects ...................................... 32

    3.3.3 Pre-existing WorkStation for Projects User Accounts ................. 33

    4 Creating the BACnet MS/TP Network .......................... 35

    4.1 Logging on to WorkStation for Projects ....................................... 38

    4.2 Opening a Project ....................................................................... 40

    4.3 Creating a BACnet Interface ........................................................ 41

    4.4 Creating a BACnet MS/TP Network ............................................. 43

    4.5 Configuring the MS/TP Network for b3 Communication ............... 45

    4.6 Creating a Folder ........................................................................ 46

    5 Creating and Configuring b3 BACnet Devices .............. 49

    5.1 Creating a b3 BACnet Device ...................................................... 52

    6 Creating I/O Points and Variables in the b3 BACnetDevices ........................................................................ 55

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices5

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    6/212

    6.1 Creating a b3 BACnet Device Analog Input Point ......................... 58

    6.2 Configuring the COV Increment and the Unit for a b3 BACnet DeviceAnalog Input Point ....................................................................... 61

    6.3 Creating a b3 BACnet Device Analog Output Point ...................... 65

    6.4 Configuring the COV Increment and the Unit for a b3 BACnet Device

    Analog Output Point .................................................................... 686.5 Configuring the Electrical Scale and the Engineering Scale for a b3

    BACnet Device Analog Output Point ........................................... 72

    6.6 Creating a b3 BACnet Device Analog Value ................................. 75

    6.7 Configuring the COV Increment and the Unit for a b3 BACnet DeviceAnalog Value ............................................................................... 78

    6.8 Creating a b3 BACnet Device Digital Input Point .......................... 83

    6.9 Creating a b3 BACnet Device Digital Output Point ....................... 86

    6.10 Creating a b3 BACnet Device Digital Value .................................. 89

    6.11 Creating a b3 BACnet Device Multistate Pulsed Output Point ...... 92

    7 Creating Variables in the Automation Server ................. 95

    7.1 Creating a Server Analog Value ................................................... 987.2 Configuring the Value and the Unit for a Server Analog Value ..... 100

    7.3 Creating a Server Digital Value ................................................... 103

    7.4 Creating a BACnet Value ........................................................... 104

    7.5 Configuring a BACnet Analog Value .......................................... 107

    8 Creating Programs in Automation Server and b3 BACnetDevices ...................................................................... 109

    8.1 Creating a Function Block Program ........................................... 112

    8.2 Importing Function Block Program Code ................................... 113

    8.3 Creating a Script Program ......................................................... 114

    8.4 Importing Script Program Code ................................................. 1168.5 Creating a b3 Script Program .................................................... 118

    8.6 Importing Script Program Code ................................................. 121

    9 Creating and Configuring Schedules in AutomationServer ........................................................................ 123

    9.1 Creating a Digital Schedule ....................................................... 126

    9.2 Configuring a Schedule as a Shadow ....................................... 127

    10 Creating Bindings for the b3 BACnet Devices ............. 129

    10.1 Binding Values Using a Binding Template .................................. 132

    10.2 Importing a Solution .................................................................. 139

    10.3 Binding Values Using a Binding Template .................................. 141

    11 Duplicating a b3 BACnet Device ................................. 147

    11.1 Creating a b3 BACnet Device .................................................... 150

    11.2 Merging Copied Device Content in a b3 BACnet Device ............ 152

    11.3 Copying a Folder or Object ........................................................ 154

    11.4 Renaming a Folder or Object ..................................................... 155

    11.5 Binding Values Using a Binding Template .................................. 156

    12 Creating Bindings Internal to the Automation Server ... 161

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 20146

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    7/212

    12.1 Binding Values Using a Binding Template .................................. 164

    13 Duplicating b3 BACnet Devices .................................. 169

    13.1 Creating a b3 BACnet Device .................................................... 172

    13.2 Merging Copied Device Content in a b3 BACnet Device ............ 175

    13.3 Copying a Folder or Object ........................................................ 17713.4 Renaming a Folder or Object ..................................................... 178

    13.5 Binding Values Using a Binding Template .................................. 180

    14 Deploying Servers ...................................................... 187

    14.1 Moving a Project Database ....................................................... 190

    14.2 Logging on to WorkStation for Projects ..................................... 194

    14.3 Opening a Project ..................................................................... 196

    14.4 Deploying a Server .................................................................... 197

    14.5 Logging on to WorkStation as a Building Operation User ........... 199

    14.6 Configuring a Factory-Set b3 BACnet Device after a Deploy ...... 202

    14.7 Commissioning a b3 BACnet Device ......................................... 204

    14.8 Downloading to a b3 BACnet Device ......................................... 205

    14.9 Moving a Project Database ....................................................... 206

    14.10 Summary .................................................................................. 210

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices7

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    8/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    9/212

    Introduction

    The Introduction part contains information on the purpose

    of this guide, how this guide is organized, where to findmore information, and information on regulatory notices.

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    10/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    11/212

    AboutAbout ThisThis GuideGuide1

    TopicsTopics

    Purpose of This Guide

    How This Guide is Organized

    Typographical Conventions

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    12/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    13/212

    1 About This Guide

    1.1 Purpose of This Guide

    1.1 Purpose of This Guide

    This tutorial provides step-by-step instructions for creating a BACnet networkconfigured with an Automation Server and b3 BACnet devices.

    This tutorial focuses on the following Building Operation Engineering Certificationobjectives:

    Create a new Building Operation system using an Automation Server and b3BACnet devices

    Integrate b3 BACnet devices in a new Building Operation system

    Organize folders and objects in the System Tree pane

    Identify engineering process and communication flow between devices andservers

    Import applications

    Use standards and templates for efficient engineering

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices13

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    14/212

    1 About This Guide

    1.2 How This Guide is Organized

    1.2 How This Guide is Organized

    This Building Operation Guide is divided into the following parts:

    Introduction

    The Introduction part contains information on the purpose of this guide, how thisguide is organized, where to find more information, and information on regulatorynotices.

    Tutorial

    The Tutorial part contains a step-by-step description of how to carry out differenttasks. If you want more information, see WebHelp or the corresponding BuildingOperation Guide.

    The Tutorial part includes a case study for a fictional customer cal led University X.You can decide if you want to follow the example or use the described proceduresas reference information. The case study in this tutorial is an example of a typicalway of configuring Building Operation for a customer. When reading through this

    tutorial, you might not have access to the devices, programs, and other files thatare needed for the fictional customer University X. However, the purpose of havinga case study is to see the procedures put in context, so you see how theprocedures could be used when configuring Building Operation, devices, orprograms for your customer.

    Note

    The programs and files that are used for the fictional customer University X areintended for training purposes only.

    14Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 2014

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    15/212

    1 About This Guide

    1.3 Typographical Conventions

    1.3 Typographical Conventions

    Building Operation Guides use the following specially marked texts:

    Tip

    Helps you understand the benefits and capabilities of the product.

    15

    Note

    Provides you with supplementary information.

    Important

    Alerts you to supplementary information that is essential to the completion of atask.

    Caution

    Alerts you to a condition that can cause loss of data.

    Warning

    Alerts you to a condition that can cause product damage or physical harm.

    Bold texts:

    User interface items, such as property names and buttons, are written in bold, forexample "On the File menu, select New."

    Example texts:

    All the example related information is indicated by blue lines and bullets.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    16/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    17/212

    AdditionalAdditional InformationInformation2

    TopicsTopics

    Where to Find Additional Information

    Regulatory Notices

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    18/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    19/212

    2 Additional Information

    2.1 Where to Find Additional Information

    2.1 Where to Find Additional Information

    All the technical Building Operation information is available online, on WebHelp.

    WebHelp is a web-based help system for StruxureWare Building Operation andAutomation Server Family products, the software and hardware that powersSmartStruxure solution.

    By pressing F1 or clicking a Help button in the StruxureWare Building Operationsoftware your web browser opens WebHelp with the latest, up-to-date, technicaldocumentation.

    Figure: Help in StruxureWare Building Operation

    Some StruxureWare Building Operation software products give you context-

    sensitive help by opening a WebHelp page that explains the view or dialog box youhave in focus. Some programs open up an overview page. From these pages, youcan follow the links to get more detailed information.

    WebHelp contains all the technical information that is in the guides, specificationsheets, and installation instructions.

    The WebHelp site

    One of the advantages with WebHelp is that you can reach Help without having theStruxureWare Building Operation software installed on your computer. By enteringthe URL address help.sbo.schneider-electric.com you can access WebHelp fromany computer, smartphone, or tablet connected to the internet.

    Finding informationThe easiest way to find information on WebHelp is to search for it.

    Figure: Home page search

    All technical information is gathered in one place, so you do not need to knowwhich guide, specification sheet, or installation instruction the information is in.

    Filtering the information

    To narrow down the search results, you can use these filters:

    Product

    Functionality

    Information type

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices19

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    20/212

    2 Additional Information

    2.1 Where to Find Additional Information

    Figure: Search filters

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201420

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    21/212

    2 Additional Information

    2.2 Regulatory Notices

    2.2 Regulatory Notices

    UL 916 Listed products for the Unites States and Canada, OpenClass Energy Management Equipment.

    WEEE - Directive of the European Union (EU)

    This equipment and its packaging carry the waste of electrical and electronicequipment (WEEE) label, in compliance with European Union (EU) Directive2002/96/EC, governing the disposal and recycling of electrical and electronicequipment in the European community.

    CE - Compliance to European Union (EU)

    2004/108/EC Electromagnetic Compatibility Directive

    This equipment complies with the rules, of the Official Journal of the EuropeanUnion, for governing the Self Declaration of the CE Marking for the European Unionas specified in the above directive(s) per the provisions of the following standards:IEC/EN 61326-1 Product Standard, IEC/EN 61010-1 Safety Standard.

    Industry Canada

    ICES-003

    This is a Class B digital device that meets all requirements of the CanadianInterference Causing Equipment Regulations.

    C-Tick (Australian Communications Authority (ACA))

    AS/NZS 3548

    This equipment carries the C-Tick label and complies with EMC and radiocommunications regulations of the Australian Communications Authority (ACA),governing the Australian and New Zealand (AS/NZS) communities.

    Federal Communications Commission

    FCC Rules and Regulations CFR 47, Part 15, Class B

    This device complies with part 15 of the FCC Rules. Operation is subject to thefollowing two conditions: (1) This device may not cause harmful interference. (2) Thisdevice must accept any interference received, including interference that may causeundesired operation.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices21

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    22/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    23/212

    Tutorial

    The Tutorial part contains a step-by-step description of

    how to carry out different tasks. If you want moreinformation, see WebHelp or the corresponding BuildingOperation Guide.

    The Tutorial part includes a case study for a fictionalcustomer called University X. You can decide if you want tofollow the example or use the described procedures asreference information. The case study in this tutorial is anexample of a typical way of configuring Building Operationfor a customer. When reading through this tutorial, youmight not have access to the devices, programs, and otherfiles that are needed for the fictional customer University X.However, the purpose of having a case study is to see the

    procedures put in context, so you see how the procedurescould be used when configuring Building Operation, devices,or programs for your customer.

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    24/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    25/212

    OurOur CaseCase StudyStudy3

    TopicsTopics

    University X

    Requirements and Specifications

    Focus of This Tutorial

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    26/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    27/212

    3 Our Case Study

    3.1 University X

    3.1 University X

    We are going to install Building Operation as the building management system forUniversity X. The university is a campus of buildings for which heating and coolingare supplied from a Central Plant with an underground distribution system. The

    case study focuses on the renovation of the Central Plant and the expansion of theSchool of Business.

    Figure: The School of Business and the Central Plant

    The Cooling Plant consists of a single chiller with a primary-secondary pumpingsystem. The secondary water loop serves four VAV air handling units with chilledwater coils located in the School of Business. The secondary loop has two waterpumps. Only one pump is required for 100 % of the load. The second pumpprovides 100 % backup. The secondary pumps are variable speed. The primarychilled water loop has a single constant volume chilled water pump. The condenserloop rejects heat by means of a cooling tower. The condenser loop has a single

    constant volume condenser water pump. The tower has two constant speed, draw-through fans to increase the capacity of the tower above the natural draft capacity.A diverting valve can be used to protect the chiller from condenser water thermalshock. The water leaving the condenser can be diverted back to the inlet of thecondenser without any cooling effect.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices27

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    28/212

    3 Our Case Study

    3.1 University X

    Figure: Cooling Plant diagram

    The heating plant consists of two boilers in parallel, each with their own inlinepumps. Much of the time only one boiler is required to meet the load but undergreater load, both boilers will operate at the same time. The flow from the twoboilers comes together in a common supply header. There is a line from the supplyheader to the mechanical systems that require a source of hot water. This line hastwo constant volume distribution pumps in parallel. Only one is required to meetthe load. The second is back-up and lead-lag is used to alternate which pumpruns. The water returning from the mechanical systems flows into the return headerwhere it can be pumped by the inline pumps through the boilers. There is acommon line between the supply header and the return header. When the inlinepumps are flowing at a rate that exceeds the distribution pump flow rate, the waterflow in the common line is from the supply header to the return header. When thedistribution pump is flowing at a rate that exceeds the combined inline pump flowrates, flow in the common line is from the return header to the supply header. Eachboiler has its own self contained control system that interfaces with BuildingOperation through a combination of binary electrical control and network variables.The inline pumps are locally controlled by the self contained control system.

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201428

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    29/212

    3 Our Case Study

    3.1 University X

    Figure: Heating Plant diagram

    Note

    The programs and files that are used for the fictional customer University X areintended for training purposes only.

    2904-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    30/212

    3 Our Case Study

    3.2 Requirements and Specifications

    3.2 Requirements and Specifications

    To be able to configure Building Operation for University X, the following devicesand software are used in this tutorial.

    3.2.1 Devices Used for This Case Study

    The following devices are used for this case study:

    Power Supply, PS-24V

    Automation Server

    BACnet Terminal Controller:

    2 x b3867 (factory-set)

    BACnet VAV Controller:

    4 x b3866-V (factory-set)

    This tutorial describes an example with b3 BACnet devices that still have theirfactory settings.

    3.2.2 Software Used in This Tutorial

    The following software is used in this tutorial:

    License Administrator, and a valid license file

    Enterprise Server

    WorkStation

    Project Configuration Server

    3.2.3 Specifications

    You find specifications in the Building Operation specification sheets for EnterpriseServer, WorkStation, Project Configuration Server, PS-24V Power Supply,Automation Server, BACnet b3867 Terminal Controllers, and BACnetb3865/866/885-V VAV Controllers with Built-in Actuator.

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201430

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    31/212

    3 Our Case Study

    3.3 Focus of This Tutorial

    3.3 Focus of This Tutorial

    The university requires the new East Wing of the School of Business to becontrolled using b3 BACnet devices. The equipment consists of two VAV-AirHandling Unit controllers and four VAV controllers.

    In this tutorial, you create and configure the BACnet network and the b3 BACnetdevices required. This includes organizing the BACnet network folder structure andestablishing communication between the network devices.

    You create and configure the BACnet network and the b3 BACnet devices off site(at the Schneider Electric office) using WorkStation for Projects.

    3.3.1 Pre-existing Project Database Folders andPrograms

    For University X, a project called University X Project has been created in the Project

    Configuration Server on the off-site computer. The University X Project includes anEnterprise Server and an Automation Server.

    The Enterprise Server called University X ES1 has the following folder structure:

    Figure: University X ES1 and its folder structure

    The Automation Server called CPlant AS controls the Cooling Plant and HeatingPlant.

    CPlant AS has the following folder structure:

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices31

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    32/212

    3 Our Case Study

    3.3 Focus of This Tutorial

    Figure: CPlant AS and its folder structure

    In this tutorial, no programs need to be present in the project database on the off-site computer.

    3.3.2 Pre-existing Project Database Objects

    For University X, the following objects are available in the project database on theoff-site computer prior to the creation and configuration of BACnet network with b3

    BACnet devices:

    ...University X ES1/Servers/CPlant AS/Cooling Application/Schedules/CoolingPlant Enable Schedule

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201432

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    33/212

    3 Our Case Study

    3.3 Focus of This Tutorial

    3.3.3 Pre-existing WorkStation for Projects UserAccounts

    For University X, the following WorkStation for Projects user account is available onthe off-site computer as well as the on-site computer:

    Pete

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices33

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    34/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    35/212

    CreatingCreating thethe BACnetBACnet MS/TPMS/TP4NetworkNetwork

    TopicsTopics

    Logging on to WorkStation for Projects

    Opening a Project

    Creating a BACnet Interface

    Creating a BACnet MS/TP Network

    Configuring the MS/TP Network for b3 Communication

    Creating a Folder

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    36/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    37/212

    4 Creating the BACnet MS/TP Network

    Our Example

    In this chapter, you prepare the Automation Server to function as the BACnetinterface and create the MS/TP network so that b3 BACnet devices can be addedfor controlling the East Wing of the School of Business.

    You first log on to WorkStation for Projects on the off-site computer and open theUniversity X Project. You then create the BACnet interface and the MS/TP network.

    Additionally, you create a folder structure in the System Tree pane to ensure thatthe network is organized to maximize operating and engineering efficiency, such ascloning multiple Air Handling Unit controllers and Variable Air Volume controllers.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices37

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    38/212

    4 Creating the BACnet MS/TP Network

    4.1 Logging on to WorkStation for Projects

    4.1 Logging on to WorkStation for Projects

    You use WorkStation for Projects to access the Project Configuration Server.

    For more information, see theLog on to WorkStation for Projects topic onWebHelp.

    In this example, you log on to the Project Configuration Server on the off-sitecomputer, using the project user account Pete.

    To log on to WorkStation for Projects

    1.1. In the Building Operation WorkStation for Projects window, in the Username box, type the user name. In this example, type Pete.

    Note

    The first time you log on to WorkStation for Projects you need to usethe administrator user account to create a project user account. For

    more information, see theCreating a Project Configuration ServerUser Accounttopic on WebHelp.

    38

    2.2. In the Password box, type the password. In this example, type Pete.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 2014

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    39/212

    4 Creating the BACnet MS/TP Network

    4.1 Logging on to WorkStation for Projects

    3.3. In the Server box, select the hypertext transfer protocol you want to use andthen enter a server name or an IP address. In this example, clickHTTPSand then enter localhost.

    4.4. Select Remember me to have WorkStation for Projects remember yoursettings.

    5.5. ClickLog on.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices39

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    40/212

    4 Creating the BACnet MS/TP Network

    4.2 Opening a Project

    4.2 Opening a Project

    You open a project to configure a project or to deploy a project to a server.

    For more information, see theProjectstopic on WebHelp.

    In this example, you open the University X Project on the off-site computer.

    To open a project

    1.1. In WorkStation for Projects, in the WorkStation for Projects - Projectsview, select the project that you want to open. In this example, selectUniversity X Project.

    2.2. On the toolbar, click the Open Project button .

    The project opens in WorkStation for Projects.

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201440

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    41/212

    4 Creating the BACnet MS/TP Network

    4.3 Creating a BACnet Interface

    4.3 Creating a BACnet Interface

    You create the BACnet Interface to enable the BACnet communications port on anEnterprise Server or Automation Server.

    For more information, see theBACnet Interfacetopic on WebHelp.

    In this example, you create the BACnet Interface in the CPlant AS.

    To create a BACnet Interface

    1.1. In WorkStation, in the System Tree, select the location where you want tocreate the BACnet Interface. In this example, select ...University XES1/Servers/CPlant AS.

    2.2. On the File menu, point to New and then clickInterface.

    3.3. In the object type list, select BACnet Interface.

    4.4. In the Name box, type a name for the BACnet Interface. In this example,keep the default name of BACnet Interface.

    5.5. ClickNext.

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices41

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    42/212

    4 Creating the BACnet MS/TP Network

    4.3 Creating a BACnet Interface

    6.6. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you (Recommended).

    ClickManually entered to manually enter a BACnet Instance ID, andthen type an appropriate Instance ID for the BACnet interface.

    In this example, clickAutomatically generated.

    Note

    If you enter an Instance ID manually, you must ensure that it isglobally unique among all the BACnet devices on theinternetwork (that is, among all the devices that it cancommunicate with).

    42

    7.7. In the Network ID box, enter 1, which is the universal standard for all BACnetIP communications.

    8.8. ClickCreate.

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 2014

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    43/212

    4 Creating the BACnet MS/TP Network

    4.4 Creating a BACnet MS/TP Network

    4.4 Creating a BACnet MS/TP Network

    You create an MS/TP network in order to connect a b3 BACnet device or otherBACnet device to an Automation Server.

    For more information, see theBACnet Networkstopic on WebHelp.

    In this example, you create the MS/TP Network (RS-485), which is used to controlthe new East Wing of the School of Business building. This building will becontrolled by a field bus comprised of b3 BACnet devices.

    To create a BACnet MS/TP network

    1.1. In WorkStation, in the System Tree, select the BACnet Interface. In thisexample, select ...University X ES1/Servers/CPlant AS/BACnetInterface.

    2.2. On the File menu, point to New and then clickMSTP Network.

    3.3. In the Name box, type a name for the MS/TP network. In this example,

    keep the default name MSTP Network.

    4.4. ClickNext.

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices43

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    44/212

    4 Creating the BACnet MS/TP Network

    4.4 Creating a BACnet MS/TP Network

    5.5. In the Network ID box, enter a unique number between 1 and 65534. Inthis example, enter 5555 for the Network ID.

    6.6. In the MAC address box, enter the number that represents the AutomationServer's address on the MS/TP network. In this example, enter 0.

    7.7. In the RS-485 port box, enter the location of the serial port RS485-COMAor RS485-COMB. In this example, enter ...University XES1/Servers/CPlant AS/System/Ports/Serial/RS485-COMA.

    8.8. ClickCreate.

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201444

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    45/212

    4 Creating the BACnet MS/TP Network

    4.5 Configuring the MS/TP Network for b3 Communication

    4.5 Configuring the MS/TP Network for b3Communication

    You configure the MS/TP network to optimize its performance.

    For more information, see theCommunication Between the AS and b3 BACnetDevicetopic on WebHelp.

    In this example, you configure the MS/TP network to optimize b3 communications.

    To configure the MS/TP Network for b3 communication

    1.1. In WorkStation, in the System Tree pane, select the MSTP Network. Inthis example, select ...University X ES1/Servers/CPlant AS/BACnetInterface/MSTP Network.

    2.2. On the File menu, clickProperties.

    3.3. On the Basic tab, in the MSTP baud rate box, select the baud rate. In

    this example, select 76800.

    4.4. In the Maximum master box, enter the highest node ID that will be used onthe MS/TP network and allow for adding future devices. In this example,enter 10.

    5.5. ClickOK.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices45

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    46/212

    4 Creating the BACnet MS/TP Network

    4.6 Creating a Folder

    4.6 Creating a Folder

    You create folders to organize your Building Operation database.

    In this example, you create a folder named AHU_01 in the Automation Server. Thisfolder will contain the programs, schedules, and values for the b3 BACnet device

    that will serve as AHU controller.

    To create a folder

    1.1. In WorkStation, in the System Tree pane, select the folder, server, ornetwork where you want to create the folder. In this example,select ...University X ES1/Servers/CPlant AS.

    2.2. On the File menu, point to New and then clickFolder.

    3.3. In the Name box, type a name for the folder. In this example, typeAHU_01.

    4.4. ClickCreate.

    For this example, repeat the procedure to create the following folder structure inthe Automation Server:

    Table: CPlant AS Folders

    Name Location

    Programs ...University X ES1/Servers/CPlantAS/AHU_01

    Schedules ...University X ES1/Servers/CPlantAS/AHU_01

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201446

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    47/212

    4 Creating the BACnet MS/TP Network

    4.6 Creating a Folder

    Continued

    Name Location

    Values ...University X ES1/Servers/CPlantAS/AHU_01

    VAV_01 ...University X ES1/Servers/CPlantAS/AHU_01

    Programs ...University X ES1/Servers/CPlantAS/AHU_01/VAV_01

    Values ...University X ES1/Servers/CPlantAS/AHU_01/VAV_01

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices47

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    48/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    49/212

    CreatingCreating andand ConfiguringConfiguring b3b35BACnetBACnet DevicesDevices

    TopicsTopics

    Creating a b3 BACnet Device

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    50/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    51/212

    5 Creating and Configuring b3 BACnet Devices

    Our Example

    In this chapter, you create the b3 BACnet devices on the MS/TP Network foroperation of the Air Handling Unit AHU_01 and control of the Variable Air Volumeunit VAV_01_01. The physical devices are connected to the network at the timeyou deploy the Automation Server.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices51

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    52/212

    5 Creating and Configuring b3 BACnet Devices

    5.1 Creating a b3 BACnet Device

    5.1 Creating a b3 BACnet Device

    You can create an offline b3 BACnet device, enter identifying information, and thencommission the device to make it available for network communications.

    For more information, see theb3 BACnet Device Controllers topic on WebHelp.

    In this example, you create an AHU controller named AHU_01. You select a modelname (b3867) that corresponds to the physical device. You enter valid numbers forthe Instance ID and Infinet ID. You also enter a BACnet name for the device. Youleave the serial number unspecified. You will enter the serial number later, after youdeploy the servers.

    To create a b3 BACnet device

    1.1. In WorkStation, in the System Tree pane, select the MSTP Network whereyou want to create the b3 BACnet device. In this example,select ...University X ES1/Servers/CPlant AS/BACnetInterface/MSTP Network.

    2.2. On the File menu, point to New and then clickb3 Device.

    3.3. In the Name box, type a name for the BACnet device. In this example, typeAHU_01.

    Note

    The b3 object display Name is limited to 16 charactersconsisting solely of letters, digits, and underscores.

    52

    4.4. ClickNext.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 2014

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    53/212

    5 Creating and Configuring b3 BACnet Devices

    5.1 Creating a b3 BACnet Device

    5.5. Under Download to BACnet device, in the Instance ID box, type aunique instance ID for BACnet configuration and communication. In thisexample, type 4010.

    6.6. In the BACnet name box, type a BACnet name. Do not type a name if youwant it assigned for you. In this example, type AHU_01.

    Note

    The BACnet name is limited to 16 characters consisting solely

    of letters, digits, and underscores.

    53

    7.7. In the Model name box, select the model name. In this example, selectb3867.

    8.8. In the Infinet ID box, enter the Infinet ID for the b3 BACnet device. In thisexample, enter 1.

    Note

    The Infinet ID is required for communication between differentdevices. Each device is identified by its unique ID number.

    9.9. ClickCreate.

    Now that the device is created, you need to commission the device.For moreinformation, see section 14.7 Commissioning a b3 BACnet Device on page 204.

    For this example, repeat the procedure to create a VAV controller namedVAV_01_01. Use the following settings:

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    54/212

    5 Creating and Configuring b3 BACnet Devices

    5.1 Creating a b3 BACnet Device

    Table: b3 BACnet Device VAV_01_01

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTP Network

    Name VAV_01_01

    Instance ID 4011

    BACnet name VAV_01_01

    Model name b3866

    Infinet ID 2

    Serial number Null

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201454

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    55/212

    CreatingCreating I/OI/O PointsPoints andand6VariablesVariables inin thethe b3b3 BACnetBACnetDevicesDevices

    TopicsTopics

    Creating a b3 BACnet Device Analog Input Point

    Configuring the COV Increment and the Unit for a b3BACnet Device Analog Input Point

    Creating a b3 BACnet Device Analog Output Point

    Configuring the COV Increment and the Unit for a b3BACnet Device Analog Output Point

    Configuring the Electrical Scale and the Engineering Scalefor a b3 BACnet Device Analog Output Point

    Creating a b3 BACnet Device Analog Value

    Configuring the COV Increment and the Unit for a b3BACnet Device Analog Value

    Creating a b3 BACnet Device Digital Input Point

    Creating a b3 BACnet Device Digital Output Point

    Creating a b3 BACnet Device Digital Value

    Creating a b3 BACnet Device Multistate Pulsed Output Point

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    56/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    57/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    Our Example

    In this chapter, you create all the b3 BACnet input points, output points, and valuesthat will reside within the Air Handling Unit controller and also the Variable AirVolume controller. The data from these points and values will be mirrored up tovalues that reside within the Automation Server. The Automation Server will analyzethis data and perform logical decisions before passing the data back to the b3BACnet devices that are controlling the system.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices57

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    58/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.1 Creating a b3 BACnet Device Analog Input Point

    6.1 Creating a b3 BACnet Device AnalogInput Point

    You create analog input points in the Application folder of the b3 BACnet device.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you create an analog input point named Dat in the AHU_01 b3BACnet device.

    To create a b3 BACnet device analog input point

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet devicewhere you want to create the analog input point. In this example,expand ...University X ES1/Servers/CPlant AS/BACnetInterface/MSTP Network/AHU_01.

    2.2. SelectApplication.

    3.3. On the File menu, point to New and then clickPoint.

    4.4. In the object type list, select BACnet Analog Input (Continuum).

    5.5. In the Name box, type a name for the analog input point. In this example,type Dat.

    You can type more than 16 characters for b3 object display names and arenot restricted to using only letters, digits, and underscores.

    6.6. ClickNext.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201458

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    59/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.1 Creating a b3 BACnet Device Analog Input Point

    7.7. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you (Recommended).

    ClickManually entered to manually enter a BACnet instance ID, andthen type an appropriate Instance ID for the BACnet object.

    In this example, clickAutomatically generated.

    If you enter an Instance ID manually, you must ensure it is unique within theapplication for this type.

    8.8. ClickNext.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices59

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    60/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.1 Creating a b3 BACnet Device Analog Input Point

    9.9. In the Channel box, enter the input channel you want the point to read from.In this example, enter channel 1.

    10.10. In the Electrical type box, select the electrical type on the input point. Inthis example, select Temp(DEGC) or Temp(DEGF).

    11.11. ClickCreate.

    For this example, repeat the procedure to create an analog input point namedVAVTemp in the VAV_01_01 b3 BACnet device. Use the following settings:

    Table: VAV_01_01 b3 BACnet Device Analog Input Point VAVTemp

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/VAV_01_01/Application

    Name VAVTemp

    Channel 1

    Electrical type Temp(DEGC) or Temp(DEGF)

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201460

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    61/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.2 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Input Point

    6.2 Configuring the COV Increment and theUnit for a b3 BACnet Device AnalogInput Point

    You configure the COV increment and the unit for a b3 BACnet device analog inputpoint to ensure that the analog input point holds the COV increment and the unit asrequired by the project.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you configure the COV increment and the unit for the analog inputpoint named Dat in the AHU_01 b3 BACnet device.

    To configure the COV increment and the unit for a b3 BACnetdevice analog input point

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet deviceand then select Application. In this example, expand ...University XES1/Servers/CPlant AS/BACnet Interface/MSTP Network/AHU_01and then select Application.

    2.2. In the List View, select the b3 BACnet device analog input point. In thisexample, select Dat.

    3.3. On the File menu, clickProperties.

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices61

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    62/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.2 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Input Point

    4.4. Click the Basic tab.

    5.5. For Value, click the Configure Settings icon .

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201462

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    63/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.2 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Input Point

    6.6. Select the Configured box that is in front of the Unit box.

    7.7. In the Unit box, enter the unit. In this example, enter C (F).

    8.8. ClickOK.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices63

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    64/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.2 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Input Point

    9.9. In the COV increment box, enter the minimum change in the Value propertythat causes a COV notification to be sent. In this example, enter 1.

    10.10. ClickOK.

    For this example, repeat the procedure to configure the COV increment and theunit for the analog input point named VAVTemp in the VAV_01_01 b3 BACnetdevice. Use the following settings:

    Table: VAV_01_01 b3 BACnet Device Analog Input Point VAVTemp

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/VAV_01_01/Application

    Name VAVTemp

    Unit C (F)

    COV increment 1

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201464

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    65/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.3 Creating a b3 BACnet Device Analog Output Point

    6.3 Creating a b3 BACnet Device AnalogOutput Point

    You create analog output points in the Application folder of the b3 BACnet device.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you create an analog output point named VlvPosn in the AHU_01b3 BACnet device.

    To create a b3 BACnet device analog output point

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet devicewhere you want to create the analog output point. In this example,expand ...University X ES1/Servers/CPlant AS/BACnetInterface/MSTP Network/AHU_01.

    2.2. SelectApplication.

    3.3. On the File menu, point to New and then clickPoint.

    4.4. In the object type list, select BACnet Analog Output (Continuum).

    5.5. In the Name box, type a name for the analog output point. In this example,type VlvPosn.

    You can type more than 16 characters for b3 object display names and arenot restricted to using only letters, digits, and underscores.

    6.6. ClickNext.

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices65

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    66/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.3 Creating a b3 BACnet Device Analog Output Point

    7.7. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you (Recommended).

    ClickManually entered to manually enter a BACnet Instance ID, andthen type an appropriate Instance ID for the BACnet object.

    In this example, clickAutomatically generated.

    If you enter an Instance ID manually, you must ensure it is unique within theapplication for this type.

    8.8. ClickNext.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201466

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    67/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.3 Creating a b3 BACnet Device Analog Output Point

    9.9. In the Channel box, enter the output channel you want the point to write to.In this example, enter channel 6.

    10.10. In the Electrical type box, select the electrical type on the output point. Inthis example, select Voltage.

    11.11. ClickCreate.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices67

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    68/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.4 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Output Point

    6.4 Configuring the COV Increment and theUnit for a b3 BACnet Device AnalogOutput Point

    You configure the COV increment and the unit for a b3 BACnet device analogoutput point to ensure that the analog output point holds the COV increment andthe unit as required by the project.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you configure the COV increment and the unit for the analog outputpoint named VlvPosn in the AHU_01 b3 BACnet device.

    To configure the COV increment and the unit for a b3 BACnetdevice analog output point

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet device andthen select Application. In this example, expand ...University XES1/Servers/CPlant AS/BACnet Interface/MSTP Network/AHU_01and then select Application.

    2.2. In the List View, select the b3 BACnet device analog output point. In thisexample, select VlvPosn.

    3.3. On the File menu, clickProperties.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201468

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    69/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.4 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Output Point

    4.4. Click the Basic tab.

    5.5. For Value, click the Configure Settings icon .

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices69

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    70/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.4 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Output Point

    6.6. Select the Configured box that is in front of the Unit box.

    7.7. In the Unit box, enter the unit. In this example, enter %.

    8.8. ClickOK.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201470

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    71/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.4 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Output Point

    9.9. In the COV increment box, enter the minimum change in the Value propertythat causes a COV notification to be sent. In this example, enter 2.

    10.10. ClickOK.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices71

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    72/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.5 Configuring the Electrical Scale and the Engineering Scale for a b3 BACnet Device Analog Output Point

    6.5 Configuring the Electrical Scale and theEngineering Scale for a b3 BACnetDevice Analog Output Point

    You configure the electrical scale and the engineering scale for a b3 BACnet deviceanalog output point to ensure that the analog output point holds the conversionsettings as required by the project.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you configure the electrical scale and the engineering scale for theanalog output point named VlvPosn in the AHU_01 b3 BACnet device.

    To configure the electrical scale and the engineering scale fora b3 BACnet device analog output point

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet device andthen select Application. In this example, expand ...University XES1/Servers/CPlant AS/BACnet Interface/MSTP Network/AHU_01and then select Application.

    2.2. In the List View, select the b3 BACnet device analog output point. In thisexample, select VlvPosn.

    3.3. On the File menu, clickProperties.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201472

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    73/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.5 Configuring the Electrical Scale and the Engineering Scale for a b3 BACnet Device Analog Output Point

    4.4. Click the Advanced tab.

    5.5. Under Conversion Settings, in the Electrical scale top box, enter thehighest electrical value for the analog output point. In this example, enter 10(Volt).

    6.6. In the Electrical scale bottom box, enter the lowest electrical value for theanalog output point. In this example, enter 0 (Volt).

    7.7. In the Engineering scale top box, enter the highest engineering value forthe analog output point. In this example, enter 100.

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices73

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    74/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.5 Configuring the Electrical Scale and the Engineering Scale for a b3 BACnet Device Analog Output Point

    8.8. In the Engineering scale bottom box, enter the lowest engineering valuefor the analog output point. In this example, enter 0.

    9.9. ClickOK.

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201474

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    75/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.6 Creating a b3 BACnet Device Analog Value

    6.6 Creating a b3 BACnet Device AnalogValue

    You create analog values in the Application folder of the b3 BACnet device.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you create an analog value named DatSP in the AHU_01 b3BACnet device.

    To create a b3 BACnet device analog value

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet devicewhere you want to create the analog value. In this example,expand ...University X ES1/Servers/CPlant AS/BACnetInterface/MSTP Network/AHU_01.

    2.2. SelectApplication.

    3.3. On the File menu, point to New and then clickValue.

    4.4. In the object type list, select BACnet Analog Value (Continuum).

    5.5. In the Name box, type a name for the analog value. In this example, typeDatSP.

    You can type more than 16 characters for b3 object display names and arenot restricted to using only letters, digits, and underscores.

    6.6. ClickNext.

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices75

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    76/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.6 Creating a b3 BACnet Device Analog Value

    7.7. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you (Recommended).

    ClickManually entered to manually enter a BACnet Instance ID, andthen type an appropriate Instance ID for the BACnet object.

    In this example, clickAutomatically generated.

    If you enter an Instance ID manually, you must ensure it is unique within theapplication for this type.

    8.8. ClickCreate.

    For this example, repeat the procedure to create the other analog values for theAHU_01 and VAV_01_01 b3 BACnet devices. Use the following settings:

    Table: AHU_01 b3 BACnet Device Analog Value

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/AHU_01/Application

    Name StPrSP

    Table: VAV_01_01 b3 BACnet Device Analog Values

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/VAV_01_01/Application

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201476

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    77/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.6 Creating a b3 BACnet Device Analog Value

    Continued

    Component Setting

    Name DmprPosn

    TermLoad

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices77

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    78/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.7 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Value

    6.7 Configuring the COV Increment and theUnit for a b3 BACnet Device AnalogValue

    You configure the COV increment and the unit for a b3 BACnet device analog valueto ensure that the analog value holds the COV increment and the unit as required bythe project.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you configure the COV increment and the unit for the analog valuenamed DatSP in the AHU_01 b3 BACnet device.

    To configure the COV increment and the unit for a b3 BACnetdevice analog value

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet device andthen select Application. In this example, expand ...University XES1/Servers/CPlant AS/BACnet Interface/MSTP Network/AHU_01and then select Application.

    2.2. In the List View, select the b3 BACnet device analog value. In thisexample, select DatSP.

    3.3. On the File menu, clickProperties.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201478

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    79/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    80/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.7 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Value

    6.6. Select the Configured box that is in front of the Unit box.

    7.7. In the Unit box, enter the unit. In this example, enter C (F).

    8.8. ClickOK.

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201480

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    81/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.7 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Value

    9.9. In the COV increment box, enter the minimum change in the Value propertythat causes a COV notification to be sent. In this example, enter 1.

    10.10. ClickOK.

    For this example, repeat the procedure to configure the COV increment and theunit for the other analog values in the AHU_01 and VAV_01_01 b3 BACnet devices.Use the following settings:

    Table: AHU_01 b3 BACnet Device Analog Value StPrSP

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/AHU_01/Application

    Name StPrSP

    Unit Pa (inH2O)

    COV increment 0.05

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices81

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    82/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.7 Configuring the COV Increment and the Unit for a b3 BACnet Device Analog Value

    Component Setting

    Table: VAV_01_01 b3 BACnet Device Analog Value DmprPosn

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/VAV_01_01/Application

    Name DmprPosn

    Unit %

    COV increment 2

    Table: VAV_01_01 b3 BACnet Device Analog Value TermLoad

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/VAV_01_01/Application

    Name TermLoad

    Unit %

    COV increment 1

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201482

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    83/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    84/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.8 Creating a b3 BACnet Device Digital Input Point

    7.7. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you (Recommended).

    ClickManually entered to manually enter a BACnet Instance ID, andthen type an appropriate Instance ID for the BACnet object.

    In this example, clickAutomatically generated.

    If you enter an Instance ID manually, you must ensure it is unique within theapplication for this type.

    8.8. ClickNext.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201484

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    85/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.8 Creating a b3 BACnet Device Digital Input Point

    9.9. In the Channel box, enter the input channel you want the point to read from.In this example, enter channel 2.

    10.10. ClickCreate.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices85

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    86/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.9 Creating a b3 BACnet Device Digital Output Point

    6.9 Creating a b3 BACnet Device DigitalOutput Point

    You create digital output points in the Application folder of the b3 BACnet device.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you create a digital output point named FanCmd in the AHU_01 b3BACnet device.

    To create a b3 BACnet device digital output point

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet devicewhere you want to create the digital output point. In this example,expand ...University X ES1/Servers/CPlant AS/BACnetInterface/MSTP Network/AHU_01.

    2.2. SelectApplication.

    3.3. On the File menu, point to New and then clickPoint.

    4.4. In the object name list, select BACnet Digital Output (Continuum).

    5.5. In the Name box, type a name for the digital output point. In this example,type FanCmd.

    You can type more than 16 characters for b3 object display names and arenot restricted to using only letters, digits, and underscores.

    6.6. ClickNext.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201486

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    87/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.9 Creating a b3 BACnet Device Digital Output Point

    7.7. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you (Recommended).

    ClickManually entered to manually enter a BACnet Instance ID, andthen type an appropriate Instance ID for the BACnet object.

    In this example, clickAutomatically generated.

    If you enter an Instance ID manually, you must ensure it is unique within theapplication for this type.

    8.8. ClickNext.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices87

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    88/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.9 Creating a b3 BACnet Device Digital Output Point

    9.9. In the Channel box, enter the output channel you want the point to write to.In this example, enter channel 1.

    10.10. ClickCreate.

    For this example, repeat the procedure to create a digital output point named Lightin the VAV_01_01 b3 BACnet device. Use the following settings:

    Table: VAV_01_01 b3 BACnet Device Digital Output Point Light

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/VAV_01_01/Application

    Name Light

    Channel 3

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201488

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    89/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.10 Creating a b3 BACnet Device Digital Value

    6.10 Creating a b3 BACnet Device DigitalValue

    You create digital values in the Application folder of the b3 BACnet device.

    For more information, see theb3 BACnet Device Point and Value Configurationtopic on WebHelp.

    In this example, you create a digital value named VentReq in the AHU_01 b3BACnet device.

    To create a b3 BACnet device digital value

    1.1. In WorkStation, in the System Tree pane, expand the b3 BACnet devicewhere you want to create the digital value. In this example,expand ...University X ES1/Servers/CPlant AS/BACnetInterface/MSTP Network/AHU_01.

    2.2. SelectApplication.

    3.3. On the File menu, point to New and then clickValue.

    4.4. In the object type list, select BACnet Digital Value (Continuum).

    5.5. In the Name box, type a name for the digital value. In this example, typeVentReq.

    You can type more than 16 characters for b3 object display names and arenot restricted to using only letters, digits, and underscores.

    6.6. ClickNext.

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices89

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    90/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.10 Creating a b3 BACnet Device Digital Value

    7.7. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you (Recommended).

    ClickManually entered to manually enter a BACnet Instance ID, andthen type an appropriate Instance ID for the BACnet object.

    In this example, clickAutomatically generated.

    If you enter an Instance ID manually, you must ensure it is unique within theapplication for this type.

    8.8. ClickCreate.

    For this example, repeat the procedure to create the other digital values in theAHU_01 and VAV_01_01 b3 BACnet devices. Use the following settings:

    Table: AHU_01 b3 BACnet Device Digital Values

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/AHU_01/Application

    Name OccCmd

    FanAlarm

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201490

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    91/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.10 Creating a b3 BACnet Device Digital Value

    Component Setting

    Table: VAV_01_01 b3 BACnet Device Digital Values

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/MSTPNetwork/VAV_01_01/Application

    Name OccStatus

    OccCmd

    Ovrd

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices91

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    92/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    93/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.11 Creating a b3 BACnet Device Multistate Pulsed Output Point

    6.6. ClickNext.

    7.7. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you (Recommended).

    ClickManually entered to manually enter a BACnet Instance ID, andthen type an appropriate Instance ID for the BACnet object.

    In this example, clickAutomatically generated.

    If you enter an Instance ID manually, you must ensure it is unique within theapplication for this type.

    8.8. ClickNext.

    Continued on next page

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices93

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    94/212

    6 Creating I/O Points and Variables in the b3 BACnet Devices

    6.11 Creating a b3 BACnet Device Multistate Pulsed Output Point

    9.9. In the Channel box, enter the channel where you want to put the multistatepulsed output. In this example, enter channel 1.

    10.10. ClickCreate.

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201494

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    95/212

    CreatingCreating VariablesVariables inin thethe7AutomationAutomation ServerServer

    TopicsTopics

    Creating a Server Analog Value

    Configuring the Value and the Unit for a Server AnalogValue

    Creating a Server Digital Value

    Creating a BACnet Value

    Configuring a BACnet Analog Value

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    96/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    97/212

    7 Creating Variables in the Automation Server

    Our Example

    In this chapter, you create all the server values and BACnet values that reside in theAutomation Server within the BACnet Interface. The server values are mirrored fromthe values in the b3 BACnet devices. Programs in the Automation Server performlogical decisions to these values and then pass that data down to the BACnetvalues that reside in the Automation Server within the BACnet Interface. Thosevalues are then passed down to the b3 BACnet devices.

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices97

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    98/212

    7 Creating Variables in the Automation Server

    7.1 Creating a Server Analog Value

    7.1 Creating a Server Analog Value

    You create analog values in the Automation Server or Enterprise Server for thefollowing reasons:

    A variable needs to be bound to multiple programs.

    A calibrated analog input variable needs to be forced.

    For more information, see theBindings Overviewtopic on WebHelp.

    In this example, you create an analog value named VlvPosn_AS in the AutomationServer AHU_01 folder.

    To create a server analog value

    1.1. In WorkStation, in the System Tree pane, select the server or folder whereyou want to add an analog value. In this example, select ...University XES1/Servers/CPlant AS/AHU_01/Values.

    2.2. On the File menu, point to New and then clickValue.

    3.3. In the object type list, selectAnalog Value.

    4.4. In the Name box, type a name for the analog value. In this example, type

    VlvPosn_AS.

    5.5. ClickCreate.

    For this example, repeat the procedure to create the required analog values in theAutomation Server AHU_01/VAV_01 folder. Use the following settings:

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 201498

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    99/212

    7 Creating Variables in the Automation Server

    7.1 Creating a Server Analog Value

    Table: Analog Values in the Automation Server AHU_01/VAV_01 folder

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/AHU_01/VAV_01/Values

    Name DmprPosn_AS

    TermLoad_AS

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices99

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    100/212

    7 Creating Variables in the Automation Server

    7.2 Configuring the Value and the Unit for a Server Analog Value

    7.2 Configuring the Value and the Unit for aServer Analog Value

    You configure the value and the unit for a server analog value to ensure that the

    server analog value holds the value and the unit as required by the project.For more information, see theBindings Overviewtopic on WebHelp.

    In this example, you configure the analog value named VlvPosn_AS in theAutomation Server AHU_01 folder. You set the unit to percent (%), but leave thevalue as is.

    To configure the value and the unit for a server analog value

    1.1. In WorkStation, in the System Tree pane, select the server analog value youwant to configure. In this example, select ...University XES1/Servers/CPlant AS/AHU_01/Values/VlvPosn_AS.

    2.2. On the File menu, clickProperties.

    3.3. Under Status Information, click the Configure button .

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 2014100

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    101/212

    7 Creating Variables in the Automation Server

    7.2 Configuring the Value and the Unit for a Server Analog Value

    4.4. Select the Configured box that is in front of the Unit box.

    5.5. In the Unit box, enter the unit. In this example, enter %.

    6.6. ClickOK.

    7.7. ClickOK.

    For this example, repeat the procedure to configure the analog values in theAutomation Server AHU_01/VAV_01 folder. Use the following settings:

    Table: Analog Value in the Automation Server AHU_01/VAV_01 Folder DmprPosn_AS

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/AHU_01/VAV_01/Values

    Name DmprPosn_AS

    Unit %

    Table: Analog Value in the Automation Server AHU_01/VAV_01 Folder TermLoad_AS

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/AHU_01/VAV_01/Values

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices101

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    102/212

    7 Creating Variables in the Automation Server

    7.2 Configuring the Value and the Unit for a Server Analog Value

    Continued

    Component Setting

    Name TermLoad_AS

    Unit %

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 2014102

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    103/212

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    104/212

    7 Creating Variables in the Automation Server

    7.4 Creating a BACnet Value

    7.4 Creating a BACnet Value

    You create a BACnet analog, digital, or multistate value in a local server so you canthen configure a control system parameter for the server. The server can be anAutomation Server or an Enterprise Server. The BACnet values that you create are

    visible to other workstations and devices in the BACnet internetwork. You createBACnet values for a server in the Application folder of the server's BACnet Interface.

    For more information, see theBACnet Objects and Propertiestopic on WebHelp.

    In this example, you create a BACnet analog value named AHU_01_DatSP in theApplication folder of the Automation Server's BACnet Interface.

    To create a BACnet value

    1.1. In WorkStation, in the System Tree, expand the BACnet Interface and thenselect Application. In this example, expand ...University XES1/Servers/CPlant AS/BACnet Interface and then select

    Application.

    2.2. On the File menu, point to New and then clickValue.

    3.3. In the object type list, select the type of BACnet value that you want to create.Do not select String Value or Time Stamp Value, which are not BACnetobject types. In this example, select BACnet Analog Value.

    4.4. In the Name box, type a name for the value. In this example, typeAHU_01_DatSP.

    5.5. ClickNext.

    Continued on next page

    Crea ting and Configuring a BACnet Network with b3 BACnet Devices 04-16030-01-en, December 2014104

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    105/212

    7 Creating Variables in the Automation Server

    7.4 Creating a BACnet Value

    6.6. Under Instance ID, generate or enter a BACnet Instance ID:

    ClickAutomatically generated to have the server generate a BACnetInstance ID for you.

    ClickManually entered to manually enter a BACnet Instance ID, andthen type an appropriate Instance ID for the BACnet object.

    In this example, clickAutomatically generated.

    7.7. In the Command priority retain level box, select one of the followingoptions to configure the warm start and cold start settings for a commandpriority array:

    Warm start: The variable retains the last value set by a user orapplication. However, the variable reverts to the default value for a coldstart.

    Cold start: The variable retains the last value set by a user or applicationfor a warm start or cold start.

    No: The variable reverts to the default value upon a restart.

    In this example, select Cold start.

    8.8. ClickCreate.

    For this example, repeat the procedure to create the remaining BACnet analog anddigital values in the same folder. Use the following settings:

    Table: BACnet Analog Values

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/Application

    Type BACnet Analog Value

    04-16030-01-en, December 2014 Crea ting and Configuring a BACnet Network with b3 BACnet Devices105

  • 7/26/2019 Creating and Configuring a BACnet Network With b3 BACnet Devices Tutorial Guide

    106/212

    7 Creating Variables in the Automation Server

    7.4 Creating a BACnet Value

    Continued

    Component Setting

    Name AHU_01_StPrSP

    Command priority retain level Cold start

    Table: BACnet Digital Values

    Component Setting

    Location ...University X ES1/Servers/CPlantAS/BACnet Interface/Application

    Type BACnet Digital Value

    Name AHU_01_VAVOccCmd

    AHU_01_VentReq

    AHU_01_OccCmd

    Command priority retain level Cold start

    Crea ting and Configuring a BACnet Network with b