Cover Architectural Collaborative Inc. This Addendum shall form part of the Contract Documents and is to be read, interpreted and coordinated with all other parts. The following revisions supersede the information contained in the original specifications and drawings issued for the above-named project. Architectural: Drawings: A201 – Door Schedule Nurses Station: Added Card Access Reader, programmed for Automatic Opening. A201 – Construction Notes: Deleted NEW POWER DOOR OPERATORS TO BE INSTALLED Added Card Reader Programmed for Automatic Opening. A203 – Door Schedule Treatment Room: Added comment on Door D-007 to swing on both sides. A203 – Detail 5: Added double swing on Door D-007. Added Note N41 SUPPLY AND INSTALL MIRROR AS SPECIFIED Electrical: Drawings: E-300 – Detail 2: Deleted Card Reader on left side of the door. Deleted Door Opener Push Button. Added Card Reader on right side of the door, on millwork. Provide all required hardware and programming to automatically open door when valid card is swiped on card reader. ADDENDUM 02 Project Name: BDH Secure Room & BDH Security Upgrade Cover Project Number: 19021 Client Project Number: 6319003 & 6320003 Client Contact: Date: Total Pages: [email protected] February 3, 2020 4 END OF ADDENDUM 02 Source: BidCentral By: Brenda Roy of Vector Projects Group Ltd Date: Feb. 03/2020

cover architectural collaborative inc

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: cover architectural collaborative inc

Cover Architectural Collaborative Inc.

This Addendum shall form part of the Contract Documents and is to be read, interpreted and coordinated with all other parts. The following revisions supersede the information contained in the original specifications and drawings issued for the above-named project.

Architectural:

Drawings:

A201 – Door Schedule Nurses Station: Added Card Access Reader, programmed for Automatic Opening.

A201 – Construction Notes: Deleted NEW POWER DOOR OPERATORS TO BE INSTALLED Added Card Reader Programmed for Automatic Opening.

A203 – Door Schedule Treatment Room: Added comment on Door D-007 to swing on both sides. A203 – Detail 5: Added double swing on Door D-007.

Added Note N41 SUPPLY AND INSTALL MIRROR AS SPECIFIED

Electrical:

Drawings:

E-300 – Detail 2: Deleted Card Reader on left side of the door. Deleted Door Opener Push Button. Added Card Reader on right side of the door, on millwork. Provide all required hardware and programming to automatically open door when valid card is swiped on card reader.

ADDENDUM 02 Project Name: BDH Secure Room & BDH Security

Upgrade Cover Project Number: 19021 Client Project Number: 6319003 & 6320003 Client Contact:

Date: Total Pages:

[email protected]

February 3, 2020 4

END OF ADDENDUM 02

So

urc

e: B

idC

entr

al

B

y: B

ren

da

Ro

y o

f V

ecto

r P

roje

cts

Gro

up

Ltd

D

ate:

Feb

. 03/

2020

Page 2: cover architectural collaborative inc

x;DN

x;DNx;?

x;?

77th Avenue

22nd Street

PRIVT7

OFFICE/CONFERENCE

OFFICE COPY

RECEIPTION

ADMINISTRATION

STOR

STOR

OFFICE

OFFICE

OFFICE

PHYSIO

TREATMENT

MEDICALRECORDS

OFFICE

OFFICE

STAFFLUNCHROOM

MEETINGROOM

WR

HSKP

STOR

HOSPICESOCIAL WORKER

20

STOR

WR

ELEV

MEDICATION

4 BED15

SEMI PRIV14

STOR

WR

PRIVATE18

DIALYSIS

STOR

HSKP

LAUNGE OFFICE

EMERGE

EMERGEHSKP

DOCTOR'SCHANGEROOM

WR

UTILITY

NURSE'SCHANGEROOM

STOR

OR

STAFFLUNCHROOM

MEDICATION

WR

NURSESSTATION

SOILEDUTILITY

CLEANUTILITY

ELECT

OFFICEEXAMROOM

OFFICE

TREATMENT

LAB FILESTOR

TREATMENT

PACSSTATION

SUPPLIES

CHANGEROOM

PLASTERROOM

X-RAY1

DATA

OFFICE

LAB

CHANGE CHANGE

OFFICE

TREATMENT

TREATMENT

WR

WR WR

PHONE

IMAGING

CHANGE

WR

WR

X-RAY

WRWRWR

WAITING

4"Conduitfor TableSupply

100 ampDisconnect, 2"Conduit In & Out(Location of conduitto be verified)

45" OffFloor

2.698m Ceiling Tile Height

24 x 32"Cabinet(locationto beverified)

UnistrutUnistrut

673.1

457.2

2133.6

570.6

2287.4

1524.0

2" Conduitfor WallBucky(Location tobe Verified)

4" Conduit Location to beVerified

2"Conduit(Locationto beVerified)

2"Conduit(Locationto beVerified)

NURSES STATION

100

STAFF LUNCHROOM

MEDICATION

D1D2

WAITING AREA

D27

D26

PN

STAFF LUNCHROOM

MEDICATION

NURSES STATION

100

N1

N2

N6

N5

N20

WAITING AREAN21

A201 4

D-002N3

N3

W2

D-003

N33

N4

N4

N29 N30

N29

N28 N30N28

N35

N31

N31

N31

N4N4

D-002

N6

N2

N28

N33

668 658

169

110

50

519

75

DOOR ABREVIATIONSSTL STEEL DETENTION DOORHM HOLLOW METALSF STEEL FRAMEE EXISTING

PSDF PRESSED STEEL DETENTION FRAMESG SECURITY GLAZING PANEL AS SPEC'DLG LAMINATED SAFETY GLASS

WALL ASSEMBLIES

W2NEW STUD WALL

• 16mm GWB• 152 STEEL STUDS @ 400 O/C• W/ MINERAL FIBRE INSULATION• 16 MM IMPACT RESISTANT DRYWALL• 16mm GWB

A

AS SCHEDULED

AS

SC

HE

DU

LE

D

FINISH ABREVIATIONSEXIST EXISTINGP PATCH AND MAKE GOODPLY 3/4" PLYWOOD SHEATHINGPD SOFT WALL PADDING AS SPECIFIED

PT PAINTRSF RESILIENT SHEET FLOORINGGWB GYPSUM BOARD W/ EPOXY PAINT AND PICK

RESISTANT CAULKING

Copyright reserved. This design and drawing is the exclusive property of COVER Architectural Collaborative Inc. and cannot be used for any purpose without the written consent of the Architect. This drawing is not to be used for construction until issued for that purpose by the Architect. Prior to commencement of the Work the Contractor shall verify all dimensions, datums and levels to identify any errors and omissions; ascertain any discrepancies between this drawing and the full Contract Documents; and, bring these items to the attention of the Architect for clarification. These drawings must not be scaled. These drawings supercede previous issues.

ARCHITECTURE

PROJECT #

SHEET

No. Date Description

01 2019-04-16 SD REVIEW02 2019-06-21 50% REVIEW03 2019-07-12 95% REVIEW04 2019-08-06 95% REVIEW05 2019-12-05 TENDER06 2020-01-29 BP

CONSULTANTS

CLIENT

DATE

ADDRESS

250 354 4445coverac.ca

5 - 320 Vernon StreetNelson BCV1L 4E4

REVISIONS

2/3/

2020

1:3

7:13

PM

\\CO

VER

LOC

AL\S

tora

ge\D

ata\

Proj

ects

\190

21_

BDH

Sec

ure

Roo

m\A

-CAD

\Rev

it\20

19-0

7-25

_CO

VER

_BD

H S

ecur

e R

oom

_LT.

rvt

BDH SECURE ROOM# 6319003 &BDH SECURITYUPGRADE# 6320003

7649 22ND StreetGrand Forks, BCV0H 1H2

19021

A201

2020-02-03

SECURITY UPGRADE -NURSES STATION

1 : 50

Floor Plan (Demolition) - Nurse Station2

1 : 250

Key Plan - ED SECURITY UPGRADE - NURSES STATION1

1 : 50

Floor Plan (Construction) - Nurse Station3

DEMOLITION KEYNOTESKey Value Keynote Text

D1 END OF COUNTER TO BE DEMOLISHEDD2 REMOVE HANDRAILD26 REMOVE CORNER GUARDD27 REMOVE ALL EXISTING TEMPERED GLASS FROM NURSING

STATION, RETAIN EXISTING MILLWORK

CONSTRUCTION KEYNOTESKey Value Keynote Text

N1 NEW DOOR TO BE INSTALLEDN2 NEW WALL TO BE CONSTRUCTEDN3 CARD READER PROGRAMMED FOR AUTOMATIC OPENINGN4 INSTALL NEW LAMINATED SAFETY GLASS FIXED PANNEL WITH

CUTOUTS FOR PASS-THRU AND SPEAKING PORTS. GLASS TO BEINSTALLED INTO EXISTING MILLWORK COUNTER.

N5 INSTALL HANDRAIL AND WALL PROTECTIONN6 NEW COUNTER END TO BE CONSTRUCTEDN20 NEW REMOTE MONITORING STATION FOR SECURE ROOMN21 NEW SECURITY CAMERAN28 PATCH AND MAKE GOOD FINISHES AFFECTED BY DEMOLITION

AND CONSTRUCTION ACTIVITIES (WALLS, FLOORS, AND CEILINGS)N29 PROVIDE NEW PAINT FINISH TO WALLSN30 PATCH AND MAKE GOOD EXISTING FLOORING AFFECTED BY

CONSTRUCTION ACTIVITIESN31 REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR EXTENT

OF WORK IN THIS AREA, AND LAYOUTS OF DEVICES ANDFIXTURES

N33 INSTALL NEW LAMINATED SAFETY GLASS FIXED PANNELSN35 PROVIDE MAG-LOCK AND ROAM ALARM UPGRADE TO EXISTING

DOUBLE DOORS

D2

D1

1 : 50

Nurses Station Pass-Thru Elevation4

Door Schedule Nurses Station

Mark Width Height Thickness Type Mark Door Material GlazingFrame

MaterialHardware

Set Comments

D-002 914 2134 44 A HM LG SF 1 W/ CARD ACCESS PROGRAMMED FORAUTOMATIC OPENING. CLOSER

D27

D27

ROOM FINISH SCHEDULE - NURSES STATION

Name NumberFloor Base

Finish Floor Finish Wall Finish Ceiling Finish

NURSES STATION 100 EXIST/P EXIST/P PLY/GWB EXIST/P

* CONFIRM ALL DIMENSIONS ON SITE

Page 3: cover architectural collaborative inc

x;DN

x;DNx;?

x;?

PRIVT7

OFFICE

STAFFLUNCHROOM

MEETINGROOM

PCU ROOM16

FAMILY ROOMLOUNGE

WR

WR

WR

WR

PRIVATE19

HSKP

STOR

HOSPICESOCIAL WORKER

20

STOR

WR

ELEV

MEDICATION

4 BED15

SEMI PRIV14

STOR

WR

PRIVATE18

DIALYSIS

STOR

HSKP

LAUNGE OFFICE

EMERGE

EMERGEHSKP

DOCTOR'SCHANGEROOM

WR

UTILITY

NURSE'SCHANGEROOM

STOR

OR

STAFFLUNCHROOM

MEDICATION

WR

NURSESSTATION

SOILEDUTILITY

CLEANUTILITY

ELECT

OFFICEEXAMROOM

OFFICE

TREATMENT

LAB FILESTOR

TREATMENT

PACSSTATION

SUPPLIES

CHANGEROOM

PLASTERROOM

X-RAY1

DATA

OFFICE

CHANGE CHANGE

WR

WR

4"

45" OffFloor

2.698m Ceiling Tile Height

673.1

457.2

2287.4

2" Conduitfor WallBucky(Location tobe Verified)

PN

D13

SUPPLIES

PLASTER ROOM

D14

D3

D4

D3 D9

D7D8

CHANGE ROOM

PACS STATION

D21D10

D11

D28

N10

N12

N11 N1

N8

N9

N7N7

CHANGE ROOM

N15

N18

WC

CHANGECHANGE

DA

TA

D-007

N25

N37

N28 N29

N30

N28N29

N30

WC

101A

N27

CASTING AREA

109

TREATMENT ROOM

101N31

N31

N12

N39

A2037

N40A2036

1220

N40

N41

TREATMENT ROOM

101D6

D5

PLASTER ROOM

DOOR ABREVIATIONSSTL STEEL DETENTION DOORHM HOLLOW METALSF STEEL FRAMEE EXISTING

PSDF PRESSED STEEL DETENTION FRAMESG SECURITY GLAZING PANEL AS SPEC'DLG LAMINATED SAFETY GLASS

C

AS

SC

HE

DU

LE

D

AS SCHEDULED

FINISH ABREVIATIONSEXIST EXISTINGP PATCH AND MAKE GOODPLY 3/4" PLYWOOD SHEATHINGPD SOFT WALL PADDING AS SPECIFIED

PT PAINTRSF RESILIENT SHEET FLOORINGGWB GYPSUM BOARD W/ EPOXY PAINT AND PICK

RESISTANT CAULKING

PAPER TOWEL DISPENSER

OSCI250

375513

SOAP DISPENSER OSCI

250

150

116

0

WP1

RIM

OF

SIN

K

86

5

PAPER TOWEL

DISPENSER OSCI SOAP

DISPENSER OSCI

WP1

610610

250250

150

RIM

OF

SIN

K

86

5

116

0

Copyright reserved. This design and drawing is the exclusive property of COVER Architectural Collaborative Inc. and cannot be used for any purpose without the written consent of the Architect. This drawing is not to be used for construction until issued for that purpose by the Architect. Prior to commencement of the Work the Contractor shall verify all dimensions, datums and levels to identify any errors and omissions; ascertain any discrepancies between this drawing and the full Contract Documents; and, bring these items to the attention of the Architect for clarification. These drawings must not be scaled. These drawings supercede previous issues.

ARCHITECTURE

PROJECT #

SHEET

No. Date Description

01 2019-04-16 SD REVIEW02 2019-06-21 50% REVIEW03 2019-07-12 95% REVIEW04 2019-08-06 95% REVIEW05 2019-12-05 TENDER06 2020-01-29 BP

CONSULTANTS

CLIENT

DATE

ADDRESS

250 354 4445coverac.ca

5 - 320 Vernon StreetNelson BCV1L 4E4

REVISIONS

2/3/

2020

2:0

2:07

PM

\\CO

VER

LOC

AL\S

tora

ge\D

ata\

Proj

ects

\190

21_

BDH

Sec

ure

Roo

m\A

-CAD

\Rev

it\20

19-0

7-25

_CO

VER

_BD

H S

ecur

e R

oom

_LT.

rvt

BDH SECURE ROOM# 6319003 &BDH SECURITYUPGRADE# 6320003

7649 22ND StreetGrand Forks, BCV0H 1H2

19021

A203

2020-02-03

TREATMENT ROOM

1 : 250

Key Plan - ED Treatment Room1

1 : 50

Floor Plan (Demolition) - Treatment Room4 1 : 50

Floor Plan (Construction) - Treatment Room5

D10

D8

D21

D3D5

D6

D5

D7

D21

D3

D3

D4

D5

D9

DEMOLITION KEYNOTESKey Value Keynote Text

D3 REMOVE WALL CABINETD4 REMOVE BASE CABINET AND COUNTERD5 PATIENT LIFT TO REMAIND6 REMOVE CURTAIN TRACKD7 REMOVE BASE CABINET AND SHELVESD8 BEDHEAD TO REMAIND9 REMOVE CRUTCHES HOOKSD10 REMOVE ALL SHELVING AND COUNTERD11 SINK TO REMAIND13 REMOVE EXISTING DOOR AND FRAMED14 ENLARGE DOOR OPENINGD21 REMOVE EXISTING SINKD28 END OF COUNTER TO BE DEMOLISHED (PART OF

ALTERNATE PRICE 01)

CONSTRUCTION KEYNOTESKey Value Keynote Text

N1 NEW DOOR TO BE INSTALLEDN7 INSTALL CEILING EQUIPMENT THAT WAS REMOVED FROM

PREVIOUS TREATMENT RMN8 INSTALL MONITOR AND KEYBOARD RACK, WALL MOUNTEDN9 FILE ORGANIZERS TO BE MOUNTED ON WALLN10 INSTALL NEW TOILET AS SPECIFIEDN11 INSTALL NEW VANITYN12 INSTALL NEW HAND HYGIENE STATION. REPAIR GABLE END

AND MATCH FINISH WITH EXISTING PLASTIC LAMINATE.REPAIR DAMAGED WALL AND FLOORING AS A RESULT OFTHE DEMOLITION (PART OF ALTERNATE PRICE 01)

N15 INSTALL NEW HAND HYGIENE STATIONN18 INSTALL BOOM LIGHT SO AS NOT TO INTERFERE WITH

PATIENT LIFTN25 ADD A PLASTER TRAP TO THE EXISTING SINKN27 INSTALL NEW WASHROOM ACCESSORIES AS SPECIFIEDN28 PATCH AND MAKE GOOD FINISHES AFFECTED BY

DEMOLITION AND CONSTRUCTION ACTIVITIES (WALLS,FLOORS, AND CEILINGS)

N29 PROVIDE NEW PAINT FINISH TO WALLSN30 PATCH AND MAKE GOOD EXISTING FLOORING AFFECTED

BY CONSTRUCTION ACTIVITIESN31 REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR

EXTENT OF WORK IN THIS AREA, AND LAYOUTS OFDEVICES AND FIXTURES

N37 INSTALL HAND SANITIZERN39 INSTALL WALL PROTECTION (PART OF ALTERNATE PRICE

01)N40 INSTALL WALL PROTECTIONN41 SUPPLY AND INSTALL MIRROR AS SPECIFIED

1 : 50

RCP (Const.) - Treatment Room31 : 50

RCP (Demo.) - Treatment Room2

Door Schedule Treatment Room

Mark Width HeightThickne

ssTypeMark

DoorMaterial Glazing

FrameMaterial Hardware Set Comments

D-007 915 2032 51 C STL - SF 5 To swing on both sides

ROOM FINISH SCHEDULE - TREATMENT RM

Name Number Base Finish Floor FinishWall

Finish Ceiling Finish

TREATMENT ROOM 101 EXIST/P EXIST/P PLY/GWB EXIST/PWC 101A EXIST/P EXIST/P PLY/GWB EXIST/P

1 : 50

HHS TREATMENT ROOM6 1 : 50

HHS - CASTING AREA7

ALTERNATE PRICE O1

Page 4: cover architectural collaborative inc

Vending

Waiting

LOBBYE6

OFFICE/CONFERENCE

OFFICE COPY

RECEIPTION

ADMINISTRATION

PANEL UE120/208V225

********

15

13

19

17

5

7

9

1

LOADCCT.No.

VOLTAGEBUS AMPACITY

NAMEPLATE

BRKRBRKR

AMPS

TYPELOCATION

16

20

18

14

6

10

8

2

No.CCT.

LOAD

CONTRACTOR TO VERIFY CIRCUITS SHOWN ARE CORRECT.IF AS FOUND CONDITIONS DIFFER FROM THOSE SHOWNON THE DRAWING THE CONTRACTOR SHALL MAKEADJUSTMENTS TO SUIT THE INTENT OF THE WORK.

31

35

33

39

37

23

29

27

21

38

42

40

34

36

32

30

22

24

3

11

25

41

4

12

26

28

53

51

57

55

47

45

56

60

58

52

54

50

48

43

59

44

46

49

UTILITY & BATHROOM LIGHTING 1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

TRAUMA ROOM LIGHTING

PLASTER ROOM LIGHTING

PLASTER SURGICAL LIGHTING

TRAUMA SURGICAL LIGHTING

TREATMENT ROOM LIGHTING

63

61

67

65 66

70

68

62

64

69

81

79

83

75

73

84

80

82

78

76

71 72

74

77

1P15ASTORAGE & X-RAY LIGHTING

1P15ASCRUB SINK

1P15A TREATMENT ROOM SURGICAL LIGHTING

1P15A HALL RECEPTACLES

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P20A

1P20A

1P15A

1P20A

1P15A

1P20A

1P15A

1P15A

1P15A

1P15A

1P20A

1P15A 1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

2P

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P20A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P20A

1P15A

1P15A

1P15A 1P20A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P20A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

1P15A

3P

30A

15A

HALL CORRIDOR RECEPTACLES

EMERGENCY STORAGE RECEPTACLES

EMERGENCY STORAGE RECEPTACLES

DIRTY UTILITY RECEPTACLES

RECEPTACLES HALL

RECEPTACLES HALL

RECEPTACLES HALL

HANDICAP RECEPTACLES RECEPTACLES HALL

CLEAN UTILITY RECEPTACLES X-RAY STORAGE RECEPTACLES

X-RAY STORAGE RECEPTACLES

RECEPTACLES HALL

RECEPTACLES HALL

WARM CAB.

TRAUMA ROOM COMPUTER RECEPTACLE

RECEPTACLES

PLASTER ROOM RECEPTACLES

PLASTER ROOM RECEPTACLES

TRAUMA ROOM RECEPTACLES

TRAUMA ROOM RECEPTACLES

TREATMENT ROOM MODULE RECEPTACLES

MEDICAL GAS AL

RECEPTACLES

TREATMENT ROOM RECEPTACLES

CORRIDOR RECEPTACLES

X-RAY ROOM P.A.C.S

TREATMENT ROOM WASH. RECEPTACLES

TREATMENT ROOM RECEPTACLES

STERIS OUTLET BELOW PANEL

X-RAY PORTABLE X-RAY RECEPTACLES

EMPTY

MEDICALGAS ALAMR LIGHTING

EMPTY

EMPTY

EMPTY

AUTO DOORS

EMPTY

EMPTY

EMPTY

SPARE CCT

RECEPTACLES

P.A.C.S CONTROL

SERVER ROOM BY X-RAY RECEPTACLES

NURSE CALL RECEPTACLES

P.A.C.S OFFICE & ENERGY

X-RAY ROOM

EMERGENCY LIGHTS TREAMENT & TRAUMA

AMB CANOPY LIGHTS + PE+ EMERG SIGN

VITROS 250 IN LAB

EMERG RAULAND MARQUEE #5

LASER PRINTER X-RAY

LASER PROCESSOR X-RAY

TRAUMA ROOM LIFT

EMERGENCY DECO SANITIZER

MEDICAL GAS BOOM

EMERGENCY STORAGE RECEPTACLES

EMERGENCY STORAGE RECEPTACLES

CLEAN UTILITY RECEPTACLES

CLEAN UTILITY RECEPTACLES

DIRTY UTILITY RECEPTACLES

DIRTY UTILITY RECEPTACLES

RECEPTACLES

RECEPTACLES

RECEPTACLES

DOOR OPENER

CRESDP

4

2

314

I RE

ML

ML

DP

CR 4

DP

3

E-300

5

POWER DOOR OPENER

PWD

POWER DOOR OPENER

RE6

I 1

3

CONSTRUCTION KEY NOTES

1 INTERCOM TO BE 2-WAY. VOLUME MAY BE LOWERED BUT NOT TURNED OFF. VOLUME IN SECLUSION ROOM TO BE ADJUSTED TO OWNERS LIKING NOT MODIFIABLE BY THE PATIENT. LOCATE IN EMERGENCY ROOM AS PER OWNERS REQUEST.

CCTV MONITOR TO BE VISIBLE TO STAFF ONLY. MONITORS LOCATED IN EMERGENCY ROOM AS PER OWNERS REQUEST. CCTV SYSTEM TO BE OPERATED AS A STAND ALONE SYSTEM BY THE NURSES AND CONNECTED TO THE HOSPITAL CCTV SYSTEM. HOSPITAL CCTV SYSTEM TO BE SET TO DO NOT RECORD. PROVIDE PRIVACY SCREEN FOR CCTV MONITOR.

PUSH BUTTON IN OWNER DESIGNATED LOCATION. PUSH BUTTON TO REMOTELY UNLOCK SECLUSION ROOM DOOR. PROVIDE LENEL EXIT PUSH BUTTON. ADD LAMICOLD LABEL 'SECLUSION'.

HANDICAP DOOR OPENER PUSH BUTTON. PROVIDE A CIRCUIT FROM PANEL UE TO POWER DOOR OPENER. UE-65

NEW ROAMALERT DOOR CONTROLLER ABOVE T-BAR CEILING. PROVIDE EXCITER MOUNTED BESIDE DOOR. PROVIDE RS-485 TO EXISTING ROAMALERT NETWORK. PROVIDE POWER SUPPLY CONNECTED TO EMERGENCY CIRCUIT. PROVIDE KEYPAD ON EITHER SIDE OF THE DOOR TO TEMPORARILY DISABLEROAMALERT SYSTEM. SYSTEM TO ALARM WHEN PATIENT WALKS THROUGH.

PROVIDE ALL REQUIRED HARDWEAR AND PROGRAMMING TO AUTOMATICALLY OPEN DOOR WHEN VALID CARD IS SWIPED ON CARD READER.

2

3

4

5

6

CR

DPES

CR DPES

ML

ML

DP

DP

5

CR

PWD

RE

N

Copyright reserved. This design and drawing is the exclusive property of COVER Architectural Collaborative Inc. and cannot be used for any purpose without the written consent of the Architect. This drawing is not to be used for construction until issued for that purpose by the Architect. Prior to commencement of the Work the Contractor shall verify all dimensions, datums and levels to identify any errors and omissions; ascertain any discrepancies between this drawing and the full Contract Documents; and, bring these items to the attention of the Architect for clarification. These drawings must not be scaled. These drawings supercede previous issues.

ARCHITECTURE

PROJECT #

SHEET

CONSULTANTS

CLIENT

DATE

ADDRESS

250 354 4445coverac.ca

5 - 320 Vernon StreetNelson BCV1L 4E4

REVISIONS

2020

-02-

03 2

:03:

32 P

MC

:\Use

rs\n

olan

.ber

gen\

Doc

umen

ts\K

0003

36A

BDH

Sec

ure

Rm

Ele

c v2

019_

nola

n.be

rgen

GD

PVG

.rvt

BDH SECURE ROOM# 6319003 & BDHSECURITY UPGRADE# 6320003

7649 22ND StreetGrand Forks, BCV0H 1H2

K000336A

E-300

2019-08-07

NURSE CALL STATION, MAINENTRANCE & SCHEDULES

NTSE-300

4 PANEL UE - EXISTING

1 : 100E-300

2 CONSTRUCTION PLAN - NURSE STATION1 : 25E-300

3 NURSE CALL STATION FILING WALL1 : 100E-300

1 CONSTRUCTION PLAN - MAIN ENTRANCE

No. Date Description

2 2019-07-12 95% REVIEW3 2019-08-07 95% REVIEW R14 2019-12-05 TENDER REVIEW5 2020-01-27 ISSUED FOR

TENDER6 2020-02-03 ADDENDUM 02

6