Gas-Insulated-Substations
SF6 gas handling
EPAs 2012 Workshop on SF6-emission reduction strategies
Atlanta, Georgia; April 17-18, 2012
Copyright Siemens AG
Energy Sector Power Transmission High Voltage SubstationsPeter GlaubitzChristian Wallner
7/27/2019 Conf12 Wallner
2/36
Introduction
SF6 in a lifecycle process CO2-footprint reduction of GIS
Handling of SF6
Regulations on SF6
Conclusion
Page 2Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
7/27/2019 Conf12 Wallner
3/36
Power Transmission
Page 3Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
High Voltage Substations are the backbone of the Transmission System
7/27/2019 Conf12 Wallner
4/36
Requirements for
-
High system reliability
,
Compact space saving solutions Innovative solutions (devices, switchgears)
Low li e cycle costs
Reliable and competent partners (operator, manufacturer)
Smart and Power grid adaptation Environmental-sustainability
Page 4Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
7/27/2019 Conf12 Wallner
5/36
SF6 is colorlessly, odorless and a
6
SF6 is 5x heavier than air, is not toxic and
SF6
is no hazardous material
SF6 has no eco-toxic potential
SF6 has no impact for the ozonosphere
SF6 is a potent greenhouse gas (GWP* 22,800** x CO2)
Page 5Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
6 as exce en eec rca c arac ers cs
* Global Warming Potential; ** according to EU-F-Gas regulation
7/27/2019 Conf12 Wallner
6/36
SF6-emissions
l g
Herstellungroducing SF6 EntwicklungPr fungManufacturingProduktion
DevelopmentTests Commissioning
indust
ri
rocessi
SF6 is used in a closed cycle
UseecommissioningRecycling of SF6for reusedividual
cessing
in
pr
Page 6Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
=
7/27/2019 Conf12 Wallner
7/36
SF6
6
Emission
SF6-handling losses SF6-leakage
+
Technical recommendation in e.g. Definition in IEC-standards,
Cigr SF6-Handling Guide No. 276 like IEEE C37.122, IEC 62271-203,Cigr SF6-Tightness Guide No. 430
Page 7Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
7/27/2019 Conf12 Wallner
8/36
-
[%]
8D2
80
90
100
Size of building
Space requirement
Packing volume
example: the development of the
Siemens GIS 145 kV
40
50
60
8D8 8DN9
8DN8
0
10
20
68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98
source: Siemens
2010
The developments within the last decades have led to smaller gas
compartments of the switchgear and thus to considerably less used
year
Page 8Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
amount of SF6 at the same performance data.
7/27/2019 Conf12 Wallner
9/36
6
-- 68%68%
-- 77%77%
-- 75%75%
8D.5 8DQ1
420 kV
8D.5 8DQ1
420 kV
8D.6 8DN8
145 kV
8D.6 8DN8
145 kV
8D.4 8DN9
245 kV
8D.4 8DN9
245 kV
type of GIS
A significant reduction of SF6 was reached by using modern development
Siemens GIS, Cable bay with double busbar system including 2 BBSiemens GIS, Cable bay with double busbar system including 2 BB DS, 1 line DS, 1 CB, 3 ESDS, 1 line DS, 1 CB, 3 ES
Page 9Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
introduction of the GIS-technology in 1968
7/27/2019 Conf12 Wallner
10/36
Reduction of SF6-emissions in the factory
Test object is inside
Test box is equippedwith inspection
All connections are
gastight Operation of rupture
disc will allow SF6 toemitt in the test box
SF6 will be collectedin a closed cycle aftertestin
Page 10Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Internal arc testing without SF6-emission
7/27/2019 Conf12 Wallner
11/36
-
The componentes ng mus assure
very low SF6emission by usingstate-of-the-art-handling equipmentin the factories
Page 11Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Internal tightness of components
7/27/2019 Conf12 Wallner
12/36
-6
- - - -
equipment
regularly checks and trainedstaffs
Page 12Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Achieving low SF6 emission during production
7/27/2019 Conf12 Wallner
13/36
-6
Environmentally respondsiblebehavior and state-of-the-artequpmen s ea s o ow 6-emission in the factory
Page 13Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Source: GIS Factory Berlin
7/27/2019 Conf12 Wallner
14/36
Optimized gas work needs
1 mbar SF6- SF6- measurement SF - collectin devicemaintenance
unit
device
%- SF6,dew-point temperature,
for measurement of gas
6-
Source: DILO
Page 14Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
7/27/2019 Conf12 Wallner
15/36
SF6 Recollection
Gas flows through theinstrument into recovery bag(SF6-recollecting pipe)
No emission!
Page 15Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Source: DILO, GAS-WIKA-Siemens
7/27/2019 Conf12 Wallner
16/36
6
Use of strong and big maintenance units - should be able to recoveru u
Minimum Residual pressure to be achieved < 20mbar - according to IEC62271-303-
compartments it's not always possible.
Page 16Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
7/27/2019 Conf12 Wallner
17/36
6
10kg]
SFSF66--residual quantity (emission) dependence on the SFresidual quantit y (emission) dependence on the SF66 rated filling pressure /rated filling pressure /
compartment size / SFcompartment size / SF66 residual pressureresidual pressure
7
8
9
residualqua
ntity
[
420 kV-circuit breaker, 3-pole- volume: approx. 7000 l
- working pressure: 6,6 bar abs.
420 kV-disconnector, 3-pole
- volume: approx. 870 l
- working pressure: 4,8bar abs.
4
5
6SF6
- SF6-amount: approx. 300 kg
- SF6-density: 43 g/l
- SF6-amount: approx. 27 kg
- SF6-density: 26,7 g/l
1
2
3
With State-of-the-art-handling equipment SF6 recovery of each gas compartment
0 20 40 60 80 100 120 140 160 180 200
SF6 residual press ure [m bar]Source: Cigr-Guide no. 276; Application of table 25
Page 17Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
very ow pressure - m ar s poss e, us securng osses o a easless than 2% during maintenance and end of life.
7/27/2019 Conf12 Wallner
18/36
Gas-tightness
Gas-tightness essential for the functionality static and dynamic solutions
IEC 62271-203 High-voltage switchgear and controlgear Part 203: Gas-insulatedmetal-enclosed switchgear for rated voltages above 52 kV (09/2011)
required leakage rate
7/27/2019 Conf12 Wallner
19/36
Type testing on SF6-tightness according to
Nowadays SF6-tightness can be confirmed (integral measuringprocess with state-of-the-art measurement devices) in the range of
7/27/2019 Conf12 Wallner
20/36
State-of-the-art
n
145 kV145 kV
1968
Number ofinstalled bays
evoluti
Theimagecannotbedisplayed.Your computer may nothaveenough memory to open theimage,or theimagemay havebeen corrupted.Restartyour computer,and then open thefi leagain.Ifthered x stillappears,you may haveto del etetheimageand then insertitagain.
Todays
experience
GI
2012.- No generic life limitation- Issues of aging and deteriorationGas leakages
Theimagecannotbedisplayed.Your computer may nothaveenough memory to open theimage,or theimagemay havebeen corrupted.Restartyour computer,and then open thefil eagain.Ifthered x stillappears,you may haveto deletetheimageand then insertitagain.
Originallyexpectedlife-time
Secondary systems Corrosion
FirstInstallation
0 5040302010
Page 20Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Continuous development assures the sustainable performance
7/27/2019 Conf12 Wallner
21/36
In the Past State-of-the-art-technology
6
Short maintenance intervals (frequentopening of gas compartments) 2 openings during life time: once after 25years of service, once during end-of-lifeprocedure after 40-50 years.
Limited SF6-handling instruction Detailed explained SF6-handling instructionand regulations
SF6-maintenance units with a minimum High power SF6-maintenance units with6- - 6-
Insensitive SF6-leakage detectors Sensitive SF6-leakage detectors to findsmallest leaks
- -
collecting the used gas
gas are now offeredFundamental tests and implementation ofnew production processes
Using Helium for leakage detection wherepossible (e.g. housing leakage test)
Page 21Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Since the implementation is a continuous improvement
7/27/2019 Conf12 Wallner
22/36
SF6 History 2005 Implementation
Based on the previous voluntary commitment(1996)
Agreed with and recognized by the GermanGovernment in 2005
Sco e: Switch ear and Com onents >1 kV
Quantified and dedicated targets for 2020 bylifecycles and responsibilities
Annual monitorin of activit data andemissions according to IPCC 2006Guidelines for verification
Mission:SF6-emissions should be avoided wherever possib le.
The specific quantity of SF6 used to fulfill functions is
Page 22Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
.
7/27/2019 Conf12 Wallner
23/36
6
1.200.000 1,1Bestand (kg) Emissionsrate (%)
1.050.000
1.100.000
1.150.000
0,8
0,9
1
850.000
900.000
950.000
. .
inkg
0,5
0,6
0,7
in%
700.000
750.000
800.000
0,2
0,3
0,4
600.000
650.000
2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010
0
,
Page 23Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Emission on electric power equipment 2000 - 2010
- . .
7/27/2019 Conf12 Wallner
24/36
SF6-emissions
l g
Herstellungroducing SF6 EntwicklungPr fungManufacturingProduktionDevelopment
Tests Commissioning
indus
tri
roces
si
SF6 is used in a closed cycle
UseecommissioningRecycling of SF6for reusedividual
cessing
in
p
r
The EU-F-Gas regulation concentrates
Page 24Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
=
on the individual processing
7/27/2019 Conf12 Wallner
25/36
EU-F-Gas regulation 842/2006
*
Regulation (EC) No 842/2006 of the European Parliamentand of the Council on fluorinated greenhouse gases
SF6 is considered in limited products only
The use of SF6 in electric power
equipment is permitted
Certain measures to be carried out bymanufacturers and users have been
Amendments have been released to
Page 25Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
*California Air Resources Board
7/27/2019 Conf12 Wallner
26/36
European F-Gas-regulation 842/2006 -
6
(EC) 305/2008 definitions, minimum
Article 5 Trainin andRegulation (EC)
(EC) 1493/2007 defini tions, format
requirement on certification of staffcertification.on certainfluorinated
greenhouse* of reporting
(EC) 1494/2007 defini tions, formArticle 7 Labelling
o a e s
Page 26Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
*) certain fl uorinated greenhouse gases means hydrofluorocarbons (HFCs), perfluorocarbons (PFCs) and sulphur hexafluoride (SF6)
7/27/2019 Conf12 Wallner
27/36
European F-Gas-regulation 842/2006, article 2
Definitions for SF6-handling
Recovery
Collection and storage of SF6 from electric power equipment or containers
in practice: taking out SF6 from equipment and putting it into a container Recycling
Reuse o recovered F6 ollowing a basic cleaning process in practice: recycling of SF6 on site Reclamation
* 6performance in practice: used SF6 is reprocessed (e.g. SF6-production plant)
Destruction
Transformation or destruction into one or more stable substances which are notfluorinated GHG in practice: burning of SF6
* - IEC 60376 S ecification of technical rade sulfur hexafluoride SF for use in electrical e ui ment
Page 27Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
- IEC 60480 Guidelines for the checking and treatment of sulfu r hexafluoride (SF6) taken from electrical equipment and specification for its re-use
7/27/2019 Conf12 Wallner
28/36
European F-Gas-regulation 842/2006, article 5
*
Commission regulation No. 305/2008 establishing minimum requirements and
the conditions for mutual recognition for the certification of personnel recovering
certain fluorinated GHG from HV switchgear
Process and responsibilities
IndividualIndividualTrainingnotsubectto
Evaluation
bod / Proof of Certification
certificatecertificate
conditions of
regulation)
Examination
(content defined)
competenceo y ssues
certifications
Evaluation body andCertification body have
to be independent
Page 28Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
*) regulation refers to HV switchgear only
7/27/2019 Conf12 Wallner
29/36
European F-Gas-regulation 842/2006, article 6
The reporting is a must to do in case of
SF6 > 1 t SF6 > 1 tcountry A country BImport Export
EuropeanUnion
or bottles or bottles
The reporting is not necessary for
import /import /import /import /
exportexport
exporexporinside EUinside EU
countriescountries
equipmentequipment < 1 t per< 1 t peryear andyear and
companycompany
Page 29Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
In some countries additional voluntary commitments regarding reporting exist
7/27/2019 Conf12 Wallner
30/36
European F-Gas-regulation 842/2006, article 7
Standards required SF6-weight already in the past: declaration ofweight of gas according toIEEE C37.122 or IEC 62271-203
additional label*NEW
*
The label shall be placed clearly, indelibly andadjacent to the service point of the equipment
Weight of SF6 filling 99 kg
Page 30Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
between the different manufactures
7/27/2019 Conf12 Wallner
31/36
Review required 5 years after implementation (7/067/11)
epor o e comm ss on pu s e on ep em er ,
includes 26 substances, one is SF6
positive results regarding our electrical power applications
strong reduction of F-gas-emission demanded in general
No modification for electrical power equipment, very small adjustments
-,
Other branches/ substances strongly affected
Draft of modified EU-F-Gas-regulation
will be available autumn 2012 (planned by EU-commission)
Final decision by the EU Parliament
Scheduled until beginning of 2014
Page 31Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Link: http://ec.europa.eu/clima/policies/f-gas/index_en.htm
7/27/2019 Conf12 Wallner
32/36
SF RECYCLING6GUIDE
No. 234
Avoid SF6handlinglosses due to state-of-the-art handling
2003SF6 HANDLING
GUIDE
Guarantee of SF6 tightness due to state-of--
.
2005 SF6 TIGHTNESSGUIDE
2012
Cigr SC B3 delivers and bundles
all technical and environmentally
No. 430
Page 32Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
aspects on SF62010
7/27/2019 Conf12 Wallner
33/36
6
WG B3.17 Residual life concepts applied to HV GIS
(Finished, will be published in 6/2012) WG B3.25 SF anal sis for AIS1/GIS and MTS2 Condition Assessment
WG B3.30 Guide to minimize the use of SF6 during routine testing
1 Air Insulated Switchgear2 Mixed Technology Switchgear
Page 33Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Brochures can be downloaded on http://www.e-cigre.org/
7/27/2019 Conf12 Wallner
34/36
- ommon spec ca ons or 6- nsua e an air-insulated high-voltage switchgear and controlgear
IEC 62271-200 Standard of medium-voltage SF6-GIS
- - Revision published in 9/2011
IEC 62271-3031 Use and handling of SF6
IEC 603762 Specification for new SF6-gas IEC 604802 Checking and treatment of sulfur hexafluoride (SF6) taken from electric equipment IEEE C37.122 Gas Insulated Substations IEEE C37.122 IEEE Guide for Sul hur Hexaflouride
ASTM D2472-00 SF6-gas1 Revision in progress: IEC 62271-42 Maintenance of the standardscheduled until 2014.
Page 34Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
Target: 1 standard only, SF6-Gas mixtures to be included, recommendation on monitoring
7/27/2019 Conf12 Wallner
35/36
Implementation of adequate maintenance
strategy for aged equipment
Evaluation of each SF6-leakage for
systematical or individual failure
Gas tight equipment and low SF6
-emission
reduce life-cycle costs
Residual Life of equipment goes in line with
ow6-emss on
For end-of-life procedures, SF6 has to be
Page 35Copyright Siemens AG
Energy Sector - Power Transmission - High Voltage SubstationsChristian Wallner
7/27/2019 Conf12 Wallner
36/36
Thank you for your attention!