CLIPPER POWER SYSTEM FAMILYINTEGRATED SURGE SUPPRESSION FOR LOW

VOLTAGE DISTRIBUTION ASSEMBLIES

CLIPPER POWER SYSTEM FAMILYINTEGRATED SURGE SUPPRESSION FOR LOW

VOLTAGE DISTRIBUTION ASSEMBLIES

Clipper-v.1.qrk4.o 8/24/99 9:23 AM Page 1

Page 2: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

Clipper Power System Family2

The Problem

Cutler-Hammer was the first to introduce the “direct bus bar” connected SPD that providescustomers with the lowest system let through voltage at the bus bar when compared totraditional cable connected surge protectors.

By utilizing a direct bus bar connection the CPS achieves the industry’s lowest system letthrough voltage – effectively suppressing both high and low energy transient eventsproviding protection for all connected electronic loads. This design provides superiorsuppression ratings and eliminates poor performance that results from cable connectionsand/or long lead lengths.

Other ProductsOther surge suppressor manufactures measurements are made at the SPD module or thesuppressors terminals, not at the electrical distribution equipment’s bus bar. The distancebetween module or suppressor terminals and the distribution equipment bus bar is often14 inches or more. The impedance associated with cabling required to connect the surgesuppressor to the electrical distribution equipment (also referred to lead length) significantlyeffects the overall performance of the surge suppressor and results in an increase in letthrough voltage.

Clipper Power System Product Family

Let-T

hrou

gh V

olta

ge a

t Bus

Bar

00 10 20 30

200

400

600

800

Time (Microseconds)

* Based on IEEE C62.41 (1991) Combination Wave Form Category B3/C1 (6000V, 3000A, 8 x 20 us) Using #10 AWG Wire.

Cable ConnectedSPD (14" Cable

Lead Length to Bus Bar)

IntegratedClipperPowerSystem(directbusbar)

Due to the evolution of electronics and microprocessors in today’s society engineers,integrators, and contractors are challenged to provide quality (clean) power forelectronic loads. Surges (also known as transients) due to lightning, utility grid switching,switching of external/internal inductive or capacitive loads and other sources travel onpower line conductors throughout the electrical distribution system. Research by theANSI/IEEE and others shows that solid state devices do not tolerate momentaryvoltage surges exceeding twice their normal operating voltage. In addition, surgesless than two times operating voltage can cause system operating problems andequipment downtime.

The Solution Cutler-Hammer has developed the Clipper Power System (CPS) family of products toensure that the quality power required to maximize productivity in today’scompetitive environment is supplied to commercial, industrial, institutional, medical and telecommunications facilities.

The CPS family of products used for Surge Protection Devices (SPDs), also known asTransient Voltage Surge Suppression (TVSS), incorporates clamping and filtercomponents that are integrated into low voltage distribution equipment or assemblies—switchboards, switchgear, panelboards, MCCs, automatic transfer switches, andbusway. Cutler-Hammer also offers CPS units that can be externally mounted to anymanufactures distribution equipment on new or existing installations (Retrofit CPS).

Due to the integrated “Direct Bus Bar” design, Cutler-Hammer has been able to eliminatemany problems and performance issues commonly faced in the field. The CPS offerssuperior performance by minimizing the overall let-through voltage, a significantadvantage when compared to cable-connected solutions.

The CPS also eliminates:■ Expensive horizontal “outboard” wall space;■ Field installation costs;■ Potential electrical code violations due to improper installation; and■ Invalidation of third party certifications when connecting to existing products.

Industry Breakthrough

208Y/120V PANELBOARD

Clipper-v.1.qrk4.o 8/24/99 8:48 AM Page 6

Page 3: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

Clipper Power System Family

Wide Range of Surge RatingsSurge current ratings from 100 kA to 500kA per phase provide a range of costeffective protection that is based uponlife expectancy and offers an effectivefacility-wide solution. Products are thirdparty tested to verify published surgecurrent ratings.

Best-In-Class Extended Range Filter(55dB attenuation @ 100 kHz)The UL 1283 listed filter offers noiseattenuation over the entire frequencyspectrum that consist of 50 kHz to 100MHz. Based upon recommendedANSI/IEEE Category B3 Ringwave (6 kV,500 Amp @ 100 kHz) the filter reducesthis ringing transient to under 150 volts.Note: most suppression manufacturesclaim “sine-wave tracking” or “EMI/RFInoise filtering,” however, few publish filterperformance at 100 kHz as most offerinadequate filtering protection.

Industry Performance and SafetyStandardsThe CPS has been tested by all industrystandards (UL 1449 2nd Edition, UL1283, ANSI/IEEE C62.41 & C62.45,NEMA LS 1-1992, MIL-STD-220A, andCSA C22.2). All CPS products havebeen independent tested to verify pub-lished surge current ratings.

Ten (10) Year Extended WarrantyAn extended ten (10) year warranty isprovided on all CPS units.

Low Impedance Surge Plane™ConstructionThe Surge Plane™ diverts surge currentsequally to all MOVs, resulting in lower letthrough Voltage and longer life (seepage 4).

Conductor Level Fusing EnsuresEqual Current Diversion to all MOVsHigh surge rated conductor level fusingensures all surge components areequally stressed and provides effectiveshort circuit protection. Other designsusing individually fused MOVs have upto 20% variation in fuse performance,resulting in unequal MOV current sharing.

Internal Component DiagnosticsMonitoring and diagnostics of all internalcomponents is provided by our patentedTRI-Monitor™ system (see page 4).

Pow-R-Line 3a Panelboard withintegrated CPS-S and direct busbar connection. CPS can also beintegrated into Pow-R-Line 1a and2a panelboards.

Disconnect option also available.

Pow-R-Line C Distribution Switch-board with integrated CPS-H anddirect bus bar connection, and stan-dard model case switch for discon-nect means.

1. CPS Hybrid Surge Filter2. Direct Bus Bar Connection3. TRI-Monitor™ Diagnostic System4. Integral Circuit Breaker Disconnect

Freedom 2100 orAdvantage MCCbuckets with inte-grated CPS-S forretrofit and newinstallations.

Clipper Power System Features

1

23

4

3

Clipper-v.1.qrk4.o 8/24/99 8:46 AM Page 3

Page 4: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

Clipper Power System Family

Cutler-Hammer is the first manufacturerto develop a low impedance suppressionplatform that results in low let throughvoltages for all ANSI/IEEE definedsurges. This is achieved by lowering theoverall system inductance and ensuresrated surge current is equally diverted toall suppression components when com-pared to other designs that incorporatetraces or internal wiring with differentlengths. The addition of EMI/RFI filteringfurther enhances performance by pro-viding an additional path for transients.SPD devices that employ modular com-ponents or printed circuit boards do notincorporate surge plane technology,thereby limiting their performance andsystem integrity.

Surge Plane™ Features Standard onAll Clipper Models:■ lowest possible self-inductance due

to the 2 layer copper plane con-struction that maximizes surfacearea for shunting high frequencysurges. For example: the surfacearea of the Surge Plane™ is 15times that of #10 AWG wire, acommonly used conductor in sup-pression devices

■ mutual inductance is reduced asthe Surge Plane™ design minimizesthe loop area of all modes, resultingin lower let-through voltages

■ diverts surge current equally to allmatched MOVs within each phaseto ensure MOVs are stressed equallyand life expectancy is maximized

■ 500 kA/phase tested suppressionpaths eliminate weak links associat-ed with printed circuit board ormodular designs.

GROUND

NEUTRAL

PHASE

Surge CurrentEqually Diverted

Two Layer CopperSurge Planes

Until now, surge suppressors reliedsolely on fuses for monitoring and alarmactivation. However, fuses and circuitbreakers cannot determine if an MOVhas failed open. Even individually fusedMOVs do not provide 100% comprehen-sive monitoring reliability as the fusesare not individually monitored.

Cutler-Hammer offers the mostadvanced safety system in the industry–the TRI-Monitor™ system. This patenteddesign is the first system to incorporatethree monitoring levels:

1. Primary Protection: Monitoring ofCoordinated Overcurrent Protection is con-tinuously displayed on the front panelusing red/green indicator lights.

2. Secondary Protection: InternalInfrared Detection is used to monitor anychange in the status of the suppressioncomponents. Using an optical detectioncircuit, the unit can identify a fault condi-tion not detected by the primary protec-tion circuit (i.e., Open circuit MOV failurein any mode including N-G).

3. Tertiary Protection: Thermal Detectionprovides a back-up monitor for slowthermal overheating.

If a secondary or tertiary fault is identi-fied, the SPD unit will signal a fault condi-tion. This provides the maximum level ofsafety to operating personnel and theelectrical system.

Each level of monitoring activates aflashing trouble light and alarm annunci-ators. Unlike conventional systems, ourinfrared sensor system is a fool-proofmethod for detecting damaged sup-

pression components in any mode,including N-G. The TRI-monitor™ pro-vides continuous online monitoring 24hours a day.

Note: The TRI-Monitor™ is standard onCPS-S, CPS-S2, CPS-S3, CPS-H, CPS-H2,CPS-M, and CPS-M3 versions. TRI-Monitor™ is optional for CPS-B.

Cutler-Hammer’s Surge Plane™ - Innovation Based on Proven Ground Plane Technology

Cutler-Hammer’s SPD TRI-Monitor™ – Internal Real Time Monitoring

4

Clipper-v.1.qrk4.o 8/25/99 3:22 PM Page 4

Page 5: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

Clipper Power System Family

A Facility-Wide Protection ApproachShould Be Employed to AddressPower Quality Issues.

Why Cascaded (Coordinated)Facility-Wide Protection?As recommended in the IEEE EmeraldBook, a cascaded or staged protectionapproach should be employed toreduce an external/internal impulsewaveforms to a harmless level. A SPDfilter should be installed at the mainservice entrance and key distribution orbranch panelboards to eliminate ringingand impulse disturbances as well ashigh frequency EMI/RFI noise.

All CPS units are coordinated to work ona “system basis”. CPS units installed ateach level in the system work together toisolate and remove external/internalgenerated disturbances, creating supe-rior facility-wide performance and relia-bility. Integrated CPS units are availablein switchboards, switchgear, panel-boards, MCCs, automatic transferswitches and retrofit.

Benefits of CPS Facility-WideProtection■ high amplitude lightning impulses

reduced to negligible levels■ the industry’s lowest system let

through voltage (under 200 voltusing ANSI/IEEE Category C3Combination Waveform (20 kV, 3 kA)

■ the electrical distribution’s noiseattenuation is significantly enhanced

■ the coordinated design ensureseffective current sharing betweenmain and branch SPD devices

Typical Cascaded Electrical Distribution System

The Clipper Power System Ensures Complete Facility Protection

Cascade Performance

LV Busway

SPD Bus Plug CPS-S

Incoming LVSubstation

Switchboard CPS-S

Clipper Power System

Motor Control Centre CPS-S

Service EntranceSwitchgear orSwitchboard CPS-H

5

025µS 50µS

400V

800V

10,000V

20,000V

Let T

hrou

gh V

olta

ge (V

)

Time (microseconds)

High Energy Transient Disturbance Input at Main Panel - IEEE Category C3 Impulse (Combination) Waveform, 20,000V, 10,000A

Best Achievable Performance with single TVSS at 480 Volt main panel (Stage 1)

Two stage use of CPS’s (cascade approach ) achieves best possible surge protection (Stage 2)

Insertion Loss (ratio) 56-1 562-1 631-1 501-1 282-1

Insertion Loss (dB) 35 55 56 54 49

Attenuation Frequency 50 kHz 100 hKz 1 MHz 10 MHz 100 Mhz

Insertion Loss (ratio) 1584-1 10,000-1 100,000-1 1,778,279-1 1,000,000-1

Insertion Loss (dB) 64 80 100 125 120

Attenuation Frequency 50 kHz 100 hKz 1 MHz 10 MHz 100 Mhz

*High Frequency Extended Range EMI/RFI Filter Performance

*(Note: Single Device) **(Note: 100 ft. cable between device)

**Cascaded Facility Wide Filter Performance

Panelboard CPS-S

Let Through Voltage Based on Singleand Cascaded SPD Design

Clipper-v.1.qrk4.o 9/27/99 1:27 PM Page 5

Page 6: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

Clipper Power System Family

UL 67 (Panelboards) UL 857 (Busway) UL 1283 EMI/RFI Filter)UL 1449 2nd Edition (Surge Suppressor) UL 1449 2nd Edition (Surge Suppressor) UL 1449 2nd Edition (Surge Suppressor)UL 1283 (EMI/RFI Filter) UL 1283 (EMI/RFI Filter) CSA C22.2 Certified (suppressor)CSA C22.2 Certified (suppressor) CSA C22.2 Certified (suppressor)

Low Voltage Distribution Equipment—Complete Guide to Featuresand Applicable Safety Standards

Switchboard Switchgear Motor Control Centers

Panelboards

Pow-R-Line 1a, 2a, 3a Pow-R-Line 4

Busway Retrofit

UL 891 (Switchboard) UL 1558 (Switchgear) UL845 (MCC)UL 1449 2nd Edition (Surge Suppressor) UL 1449 2nd Edition (Surge Suppressor) UL 1449 2nd Edition (Surge Suppressor)UL 1283 (EMI/RFI Filter) UL 1283 (EMI/RFI Filter) UL 1283 (EMI/RFI Filter)CSA C22.2 Certified (suppressor) CSA C22.2 Certified (suppressor) CSA C22.2 Certified (suppressor)

■ CPS can be integrated into any switchboard■ Specifiers have the flexibility to install the

CPS in any location within the switchboard■ Disconnect switch is a standard feature■ Unique design minimizes installation

impedance

■ Available on all switchgear designs■ Disconnect switch is a standard feature■ Unique design minimizes installation

impedance■ CPS-H ideal for critical industrial

switchgear applications

■ Ideal protection for PLCs, sensors, drives,electronic starters, or other digital equipment

■ CPS designed to fit in a standard (2x) sizecompartment (12") for Freedom 2100 andAdvantage MCCs

■ May be used in new/aftermarket applications■ Ideal for water treatment, petrochemical and

other industrial applications

Features:

Safety Standards:

■ CPS used extensively on branch panel-boards for computer rooms, laboratories,schools, hospitals, industrial applications

■ 200% rated neutral is provided for non-linear loads

■ Cost effective branch protection (assumesmain panel protection employed)

■ Ideal for busway fed distribution systems ■ Easy to install CPS units, fit in standard

bus plug assembly ■ Full diagnostic and monitoring capabilities■ Isolates critical busway sections from

nearby disturbance producing loads■ Designed for new & existing facilities■ Integral disconnect

■ TVSS Filters can be externally mounted toexisting distribution equipment

■ Standard NEMA 12 enclosures■ Requires field installation■ Clipper Retrofit 100 to 400 kA/phase units■ Clipper VL 50 and 75 kA/phase units

Safety Standards:

6

The CPS surge components can be integrated into Safety Switches, Automatic Transfer Switches (ATS) and other assemblies.

Features:

Clipper-v.1.qrk4.o 8/24/99 8:46 AM Page 2

Page 7: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

Clipper Power System Family 7

Engineers and specifiers now have the flexibility to select the required CPS model for any construction project, facility expansion, or retrofit application.

Surge Current Per Phase 100 kA 120 kA 160 kA 200 kA 250 kA 300 kA 400 kA 500kASurge Current Mode

L-N (Line-to-Neutral) 50 kA 60 kA 80 kA 100 kA 125 kA 150 kA 200 kA 250kAL-G (Line-to-Ground) 50 kA 60 kA 80 kA 100 kA 125 kA 150 kA 200 kA 250kAN-G (Neutral-to-Ground) 50 kA 60 kA 80 kA 100 kA 125 kA 150 kA 200 kA 250kAL-L (Line-to-Line, Delta, andUngrounded Applications Only) 50 kA 60 kA 80 kA 100 kA 125 kA 150 kA 200 kA 250kA

Single Pulse Surge Current TestBased on ANSI/IEEE C62.41 8x20microsecond waveform Yes Yes Yes Yes Yes Yes Yes Yes

Modes of Protection All All All All All All All All3-Phase Wye System 7 7 7 7 7 7 7 73-Phase Delta System 6 6 6 6 6 6 6 6

Filter Attenuation(Based on MIL-STD-220A) @ 100 kHz 55 dB 55 dB 55 dB 55 dB 55 dB 55 dB 55 dB 55dB

Surge Withstand CapabilitiesANSI/IEEE C3 Wave (10 kA) 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000

SPD TRI-Monitor™ System:Overcurrent Protection Yes Yes Yes Yes Yes Yes Yes YesInfrared Detection Optional Yes Yes Yes Yes Yes Yes YesThermal Detection Optional Yes Yes Yes Yes Yes Yes Yes

Diagnostic Package BD SD SD SD SD SD SD SDDirect Bus Bar Connection Yes Yes Yes Yes Yes Yes Yes YesWarranty

Clipper Power System 10 Years 10 Years 10 Years 10 Years 10 Years 10 Years 10 Years 10 Years

Cutler-Hammer Clipper Power System Specifications(Guide for applying the appropriate surge suppressor based upon life expectancy and performance.)

CPS Models CPS-B CPS-S CPS-S2 CPS-S3* CPS-H CPS-H2* CPS-M* CPS-M3*

*Optional sizes to meet competitive specifications. All CPS have been independent tested to verify all suppressor components can survive published surge current ratings. Test documents are available upon request.

Clipper Model CPS-H - The standard offering for serviceentrance or high exposure locations.

Clipper Model CPS-S2 - For protecting large distribution panelboards or distribution switchboards, heavy equipment, or variable speed drives.

Clipper Model CPS-S - For protecting branch panelboardsfeeding sensitive electronic equipment.

Clipper Model CPS-B - An economical solution for protectingnon-critical branch panels or panels with upstream TVSSprotection and located deep within the facility.

CPS integrated assemblies can be ordered from your nearest Cutler-Hammer sales engineer or distributor.

CPS Retrofit Ordering Guidelines

Catalog #: CPS CH

Surge RatingsBX 100 kA/phaseSX 120 kA/phaseS2 160 kA/phaseS3 200 kA/phaseHX 250 kA/phaseH2 300 kA/phaseMX 400 kA/phaseM3 500 kA/phase

120/208 230/400 277/480 347/600Voltage Code 240V 400V 400V 600V

120/240 Single Split Phase (3W+G) 240S – – –Three Phase Delta High Leg (4W+G) 240H – – –Three Phase Wye (4W+G) 208Y 400Y 480Y 600YThree Phase Delta (3W+G) 240D 400D 480D 600DThree Phase Resistive / 208U 400U 480U 600UUngrounded Wye (4W+G)

Diagnostics Package

BD (Basic Diagnostics): Status Indicator Lights on each phaseSD (Standard Diagnostics): B plus TRI-MONITOR™,

Flashing Trouble Alarm & 200 kA1C Internal FusingED (Enhanced Diagnostics): S plus Form “C” Contact & Push-to-test FeaturePD (Premium Diagnostics): E plus Audible Alarm & Transient Counter

Enclosure Options

RSX Standard (NEMA 12 surface mount)RFM FlushmountR4X Non-metallic corrosion and weather proofRSD NEMA 12 with disconnectRC2 Caseless version

Monitor Options

Blank No OptionsCX Form “C” ContactsCA Form “C” Contact /

Audible AlarmTX Transient CounterAX Audible Alarm

– – – – – –– – – –– – –

Clipper-v.1.qrk4.o 9/27/99 1:40 PM Page 7

Page 8: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

Clipper Power System Family

Let through Voltage is the key perfor-mance measure for a suppressiondevice. NEMA LS 1-1992 and ANSI/IEEE C62.41 & 45 recommend testingSPD using high energy combination

waveforms (i.e. Cat. C3 & C1) andinternally generated ringwave tran-sients (i.e. Cat. B3). The CPS designoffers superior performance on allANSI/IEEE recommended waveforms

because of our unique low impedanceSurge Plane™, matched MOVs oneach mode and phase, tuned sup-pression filter, and high quality con-struction/ manufacturing process.

Exceptional Let Through Performance

When installing a surge suppressor ina retrofit environment, it is important tomount the suppressor as close to theelectrical equipment as possible, keepthe wiring (lead length) between theelectrical equipment and the suppressoras short as possible (less than 14 inchesis recommended), and twist/wire tie theconductors to reduce inductive effects.

Retrofit Installation Recommendations

8

*ANSI/IEEE Category C3 Combination Wave (20 kV, 10 kA) 8 x 20 µs 120/240V; 208Y/120V; 240V Delta 470 470 470 850 850 850480Y/277V; 480V Delta 900 900 900 1500 1500 1500600Y/347V; 600V Delta 1600 1600 1600 2200 2200 2200

*ANSI/IEEE Category C1 Combination Wave (6 kV, 3 kA) 8 x 20 µs 120/240V; 208Y/120V; 240V Delta 400 400 400 800 800 800480Y/277V; 480V Delta 800 800 800 1500 1500 1500600Y/347V; 600V Delta 1200 1200 1200 2000 2000 2000

*UL 1449 2nd Edition (6 kV, 500 Amp)120/240V; 208Y/120V; 240V Delta 330 330 330 700 700 700480Y/277V; 480V Delta 800 800 800 1500 1500 1500600Y/347V; 600V Delta 900 1000 900 1800 1800 1800

CPS Let Through Ratings

Operating System Voltage Wye System Delta SystemL-G L-N N-G L-L L-G L-L

120/240V; 208Y/120 150V

480Y/277 200V

600Y/347 300V

Operating **Cat B3 RingwaveSystem Voltage (6 kV, 500A, 100 kHz)

L-N Mode

Cut at 7.75”

CPS-S with hybrid suppressor protectingcritical computer loads.

* Indicates dynamic test method. ** Indicates static test method.

3020100

10,000

8,000

6,000

4,000

2,000

0

Surg

e Cu

rren

t (A)

Time (Microseconds)

12,000

Cat. C1 (6 kV, 3 kA) Impulse

Cat. C3 (20 kV, 10 kA) Impulse

2010-10 0

6,000

Surg

e Vo

ltage

(V)

4,000

2,000

0

-2,000

-4,000

Time (Microseconds)

8,000

Cat. B3 (6 kV, 100 kHz) Ringwave

Test Surge Waveforms

Clipper-v.1.qrk4.o 8/25/99 3:23 PM Page 8

Page 9: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

Reflected Wave Trap (RWT):Protection for drives/motorsagainst reflected wave spikes.

The AEGIS Family of Surge Filters:Provides protection for PLCs andcritical loads.

Datacom Family of SurgeSuppressors: For all telephoneand data communication lines.

Residential Package: CompleteHome Surge Protector (CHSP) andSurge Trap surge strips.

MainDistribution

Panel

PBX(Telephone Switch)

Datacom Protector atBuilding Entrance

NOTE: all incoming data, telephone,4-20 mA and signal lines require protection

Datacom Protectors

MCC

12.47kV

Utility Service

480V

CPS

CPS

Electronic Load

Work Station

Small h.p. Motor

AEGIS

Motor

Motor

AFD

PLC

WelderProduction Floor

Office Panel

AEGIS

AEGISCPS RWT Datacom

PC Capter

Printers

Server Lamp Fax

Motor

ReflectedWave Trap

(RWT)

CPS

In addition to the Clipper Power System family of products, Cutler-Hammeroffers a complete line of surge protection devices designed for the industrial,commercial, automation, residential and telecommunication markets.

Clipper Power System Family

Cut

at

.75”

Cutler-Hammer products are designed to provide facility-wide surge protection.

9

Clipper-v.1.qrk4.o 8/24/99 8:59 AM Page b

Page 10: CLIPPER POWER SYSTEM FAMILY INTEGRATED SURGE SUPPRESSION ...pub/@electrical/documents/conte… · clipper power system family integrated surge suppression for low voltage distribution

ArgentinaChileBrazilMexicoAustralia

PhillipinesVenezuelaUnited KingdomThailandGermany

KoreaChinaMalaysiaSingapore

Internationally, we have sales and marketing representatives in the following countries:

ArgentinaChileBrazilMexicoAustralia

PhillipinesVenezuelaUnited KingdomThailandGermany

KoreaChinaMalaysiaSingapore

Internationally, we have sales and marketing representatives in the following countries:

Cutler-HammerB.37.01.B.S.E08/99Printed In Canada

Cutler-Hammer, a part of Eaton Corporation, is a leader in the development and manufacturingof power distribution equipment, electrical control products, and advanced industrial automa-tion solutions.

For more information on Cutler-Hammer products and services, call 1-800-525-2000 or 1-616-982-1059. Or contact our web site at www.cutlerhammer.eaton.com

Cutler-Hammer, a part of Eaton Corporation, is a leader in the development and manufacturingof power distribution equipment, electrical control products, and advanced industrial automa-tion solutions.

For more information on Cutler-Hammer products and services, call 1-800-525-2000 or 1-616-982-1059. Or contact our web site at www.cutlerhammer.eaton.com

Cutler-Hammer is committed to the highest level of customer service. Our globalstrategy – with sales and manufacturing operations in strategic worldwide locations – is positioned to fulfill our customer’s needs, wherever they are located.

In North America we ensure quality service through:• Main manufacturing facilities for distribution assemblies• “Quick ship” local satellite locations specializing in panelboards/switchboards

or Motor Control Centers

Satellite Manufacturing Plant Locations:

Atlanta, GA (2)Baltimore, MDCalgary, ABChicago, IL (2)Cleveland, OHDallas, TXDenver, CO (2)

Halifax, NSHouston, TX (2)Los Angeles, CA (2)Montreal, PQPortland, OROrlando, FLPhoenix, AZ

Raleigh, NCSan Francisco, CASeattle, WASt. Louis, MOToronto, ONVancouver, BCWindsor, CT (2)

Cutler-Hammer is committed to the highest level of customer service. Our globalstrategy – with sales and manufacturing operations in strategic worldwide locations – is positioned to fulfill our customer’s needs, wherever they are located.

In North America we ensure quality service through:• Main manufacturing facilities for distribution assemblies• “Quick ship” local satellite locations specializing in panelboards/switchboards

or Motor Control Centers

Sumter, SCGrand Prairie, TXFayetteville, NC

Greenwood, SCAsheville, NCAirdrie, AlbertaCalgary, Alberta

Oakville, OntarioSan Juan, Costa RicaRio de Janeiro, Brazil

Main Manufacturing Plant Locations:

Sumter, SCGrand Prairie, TXFayetteville, NC

Greenwood, SCAsheville, NCAirdrie, AlbertaCalgary, Alberta

Oakville, OntarioSan Juan, Costa RicaRio de Janeiro, Brazil

Main Manufacturing Plant Locations:

Satellite Manufacturing Plant Locations:

Atlanta, GA (2)Baltimore, MDCalgary, ABChicago, IL (2)Cleveland, OHDallas, TXDenver, CO (2)

Halifax, NSHouston, TX (2)Los Angeles, CA (2)Montreal, PQPortland, OROrlando, FLPhoenix, AZ

Raleigh, NCSan Francisco, CASeattle, WASt. Louis, MOToronto, ONVancouver, BCWindsor, CT (2)