Upload
rohitkb09
View
214
Download
0
Embed Size (px)
Citation preview
8/7/2019 Charging Heat Pumps and Airs
1/15
8/7/2019 Charging Heat Pumps and Airs
2/15
EXPANSION VALVE SYSTEM1. Purge gauge lines. Connect service gauge manifold to base-valve service ports. Run systemat least 10 minutes to allow pressure to stabilize.
2. Temporarily install thermometer on liquid (small) line near liquid line service valve withadequate contact and insulate for best possible reading.
3. Check subcooling and superheat. Systems with TXV application should have a subcooling andsuperheat of 9 3 F.
a. If subcooling and superheat are low, adjust TXV to 9 3F then check subcooling.
b. If subcooling is low and superheat is high, add charge to raise subcooling to 9 3F thencheck superheat.
c. If subcooling and superheat are high, adjust TXV valve to 9 3F then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV valve to 9 3F superheat andremove chargeto lower the subcooling to 9 3F.
NOTE: Do NOT adjust the charge based on suction pressure unless there is a grossundercharge.
4. Disconnect manifold set, installation is complete.
Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp.
8/7/2019 Charging Heat Pumps and Airs
3/15
SUPERHEAT METHOD
THE SUPERHEAT METHOD IS USED FOR SYSTEMSUSING A FIXED ORIFICE TYPE METERING DEVICE
OrificeMetering
Device
8/7/2019 Charging Heat Pumps and Airs
4/15
USING SUPERHEAT
CALCULATORGET THE RETURN WET BULB TEMPERATURE AT THE RETURN
AIR GRILL USING A SLING PSYCHROMETER OR METER CAPABLEOF READING WET BULB TEMPERTURE
GET THE OUTSIDE AMBIENT TEMPERATURE IN THE SHADE OFTHE CONDENSING UNIT
SET ARROW TO INDOOR ENTERING AIR WET BULBTEMPERATURE
LOCATE CONDENSER ENTERING AIR DRY BULB TEMPERATURE
READ REQUIRED SUPERHEAT TEMPERATURE AT CONDENSERENTERING AIR DRY BULB TEMPERATURE
ADD CHARGE TO LOWER SUPER HEAT
REMOVE CHARGE TO RAISE SUPERHEAT
8/7/2019 Charging Heat Pumps and Airs
5/15
USING SUPERHEAT TABLEGET THE OUTSIDE AMBIENTTEMPERATURE IN THE SHADE OF THECONDENSING UNIT
GET THE RETURN DRY BULBTEMPERATURE AT THE RETURN AIR GRILL
INTERSECT THE 2 NUMBERS
THAT WILL GIVE YOU THE AMOUNT OFSUPERHEAT YOU NEED
8/7/2019 Charging Heat Pumps and Airs
6/15
Super-heat and Sub-coolingcharts
The super-heat andsub-cooling charts
will be posted on theback side of thecontrol door.
8/7/2019 Charging Heat Pumps and Airs
7/15
EXAMPLE AMBIENT OUTSIDE TEMPERATURE(IN THE SHADE OF THECONDENSOR) IS 95 DEGRESSRETURN AIR (DRY BULB) IS 75DEGREES
INTERSECT THE 2 NUMBERS ANDYOUR SUPER HEAT WILL BE 5DEGREE
8/7/2019 Charging Heat Pumps and Airs
8/15
INSTALL THERMOMETERINSTALL ON THE SUCTION LINE( LARGER LINE )
INSULATE THE PROBE FOR ANMORE ACCURATE READING
8/7/2019 Charging Heat Pumps and Airs
9/15
READING THE SATURATEDEVAPORATER TEMPERTUREON THE LOW SIDE OF YOURCOMPOUND GAUGES ( BLUE )
THE OUTSIDE READING IS YOURPRESSURE
THE INSIDE (R 22) IS YOURSATURATED EVAPORIZINGTEMPERTURE
8/7/2019 Charging Heat Pumps and Airs
10/15
EXAMPLEYOUR LOW SIDE PRESSURE IS 75PSI
DIRECTLY BELOW THAT NUMBER ISTHE SATURATED EVAPORIZINGTEMPERATURE, WHICH IS 44DEGREES
TAKE YOU SUCTION LINETEMPERTURE, WHICH IS 65DEGREE
8/7/2019 Charging Heat Pumps and Airs
11/15
EXAMPLESUBTRACT THE 2 NUMBERS AND THATHOW MUCH SUPEREHEAT YOU HAVE
65 - 44 =21 SUPERHEAT
WE ONLY NEEDED 5 DEGREES
ADD CHARGE TO LOWER SUPER HEAT
REMOVE CHARGE TO RAISE SUPERHEAT
8/7/2019 Charging Heat Pumps and Airs
12/15
Set unit to operate at low stage cooling.
Operate for 10 minutes.
Check and record low stage liquid pressure at the
service valve.Set thermostat to operate at high stage.
Operate for 10 minutes.
Check and record high stage liquid pressure atservice valve.
Charging Two Stage Units
8/7/2019 Charging Heat Pumps and Airs
13/15
8/7/2019 Charging Heat Pumps and Airs
14/15
8/7/2019 Charging Heat Pumps and Airs
15/15