Upload
others
View
8
Download
0
Embed Size (px)
Citation preview
46
CHAPTER 3
RESULTS AND DISCUSSION
The results obtained from the experimental investigations are
presented and discussed in this chapter. The effects of untreated and treated
tannery effluents, untreated and treated textile effluents on the important
properties of the concrete such as sulphate attack, chloride attack, corrosion,
chemical attack, alkali aggregate reaction, leachability of chloride,
leachability of sulphate, permeability, compressive strength, split tensile
strength, flexural strength of PCC beam, failure load of RCC beam and bond
strength are discussed in detail and compared with the concrete specimens
prepared using potable water for M20 grade of concrete.
3.1 EFFECT ON PROPERTIES OF CONCRETE PREPARED
USING TANNERY AND TEXTILE EFFLUENTS
To analyze the properties of the concrete such as compressive
strength, tensile strength, flexural strength, bond strength, permeability,
sulphate attack, chloride attack and corrosion, respective tests were carried
out. The untreated and treated effluents from the tanneries were collected on
11-04-2005 and the characteristics of the effluents were tested on the same
day and the results are tabulated in the Table 3.1. The untreated and treated
effluents from the textile processing units were collected on 12-04-2005 and
the characteristics of the effluents were tested on the same day and the results
are tabulated in the Table 3.1. The values of the properties of the untreated
47
and treated tannery effluents, untreated and treated textile effluents are taken
as the average of the samples collected at different places.
Table 3.1 Properties of the tannery (11-04-2005) and textile effluents
(12-04-2005)
SAMPLE PARAMETERS
pH Chloride Content (mg/l)
Total Dissolved Solids (mg/l)
Sulphate (mg/l)
Untreated Tannery Effluent
12.2 750 800 980
Treated Tannery Effluent
7.2 298 595 418
Untreated Textile Effluent
8.5 657 857 447
Treated Textile
Effluent 7.1 406 330 163
The concrete samples were prepared using potable water, untreated
and treated tannery effluents, untreated and treated textile effluents. The
concrete samples were then cured in the respective water and effluents for a
period of 28 days. After 28 days of curing, the important properties of the
concrete such as compressive strength, tensile strength, flexural strength,
bond strength, sulphate attack, chloride attack, corrosion studies, permeability
etc were meticulously studied and the results are presented in the Tables 3.2
and 3.3.
48
Table 3.2 Comparison of the strength properties of the concrete
Type of water used
Compr. Str. MPa
Tensile Str. MPa
Fl. Str. MPa
Bond Str. MPa
Bond Str. due to
corrosion
Perm.(K) x 10-7
cm/sec PW 25.46 2.30 3.50 1.45 0.43 7.90
UTT 26.34 2.36 3.75 1.50 0.47 8.20
TT 25.78 2.31 3.50 1.45 0.45 8.10
UTTE 26.10 2.35 3.50 1.47 0.46 8.10
TTE 25.60 2.31 3.50 1.46 0.43 8.00
Table 3.3 Comparison of the properties of the concrete
Type of water used
Sulphate Attack Chloride Attack Corrosion studies
Loss of Wt. in %
Compr. Str. MPa
Loss of Wt. in %
Compr. Str. MPa
Loss of Wt. in %
PW 0.68 22.78 1.92 23.50 6.30
UTT 5.43 16.34 8.30 15.80 8.82
TT 4.30 19.44 5.43 17.68 7.90
UTTE 5.28 17.30 8.12 15.34 8.60
TTE 3.97 19.90 5.04 17.51 7.32
To determine the properties of the concrete such as compressive
strength, tensile strength, flexural strength, bond strength, permeability,
sulphate attack, chloride attack and corrosion, respective tests were carried
out. From the analysis (Tables 3.2 and 3.3), it is observed that there are no
significant differences in the strength properties of the concrete such as
compressive strength, tensile strength, flexural strength and bond strength
whereas significant changes are observed in the form of loss of weight and
49
reduction in compressive strength of the concrete subjected to sulphate attack
and chloride attack. There is loss of weight of the reinforcement bar
embedded in the concrete due to induced corrosion. The initial setting time is
almost same (38 minutes to 47 minutes) for all the cement paste prepared
using potable water, tannery and textile effluents.
The loss of weight of the concrete, due to sulphate attack, prepared
using untreated and treated tannery effluents, untreated and treated textile
effluents are 4.75%, 3.62%, 4.6%, 3.29% respectively more than that of the
concrete prepared using the potable water. Similarly the reduction in the
compressive strength of the concrete, due to sulphate attack, prepared using
untreated and treated tannery effluents, untreated and treated textile effluents
are 28.27%, 14.66%, 24.05%, 12.64% respectively less than that of the
concrete prepared using potable water.
The loss of weight of the concrete, due to chloride attack, prepared
using untreated and treated tannery effluents, untreated and treated textile
effluents are 6.38%, 3.51%, 6.2%, 3.12% respectively more than that of the
concrete prepared using potable water. Similarly the reduction in the
compressive strength of the concrete, due to chloride attack, prepared using
untreated and treated tannery effluents, untreated and treated textile effluents
are 32.76%, 24.76%, 34.72%, 25.49% respectively less than that of the
concrete prepared using potable water.
The loss of weight of the reinforcement bar embedded in the
concrete, due to corrosion, prepared using untreated and treated tannery
effluents, untreated and treated textile effluents are 2.52%, 1.60%, 2.30%,
1.02% respectively higher than that of the concrete prepared using potable
water.
50
3.2 SELECTION OF ADMIXTURES
From the literature it is found that the fly ash enhances most of the
properties of the concrete such as reducing the permeability, improving the
structural strength in the longer run, offering good resistance to ingress of
sulphate ions and chloride ions (Gengying Li and Xiaohua Zhao 2003, Shetty
2003, Civjan et al 2005, Gopalan 2007, Malathy and Subramanian 2008). The
fly ash is cheap and it is available in large quantities as an industrial waste.
The utilization of waste materials such as fly ash in the preparation of the
concrete provides a satisfactory solution to some of the environmental
concerns such as problems associated with waste management (Ganesan
2007) and also fly ash reduces the cost of the concrete. Hence in this present
research fly ash is considered as an admixture to be added while preparing the
concrete to minimize the adverse effects on the concrete prepared using
tannery and textile effluents (Saraswathy et al 2003, Han Young Moon and
Kook Jae Shin 2004, Scott A Civjan et al 2005, Sarat Kumar Das and Yudhbir
2006, Sideris et al 2006). The admixtures are added as per IS 9103-1978
(1978).
It is observed that beyond 5% addition of fly ash, there is no
significant improvement in the concrete properties such as sulphate attack,
chloride attack and corrosion of the reinforcement bar embedded in the
concrete. In addition if more quantity (more than 10% or 15%) of fly ash is
added, the initial setting time is prolonged (Mustafa Sahmaran 2006) and
hence the addition of fly ash is limited to 5%.
The concrete samples were prepared using the different effluents
(detailed properties of the tannery and textile effluents collected on 22-09-
2005 and 23-09-2005 respectively are given in Table 3.4) with the addition of
5% fly ash (obtained from the Mettur thermal power plant and Neyveli
51
thermal power plant). After curing, the concrete samples were tested for the
concrete properties such as loss of weight and reduction in compressive
strength subjected to sulphate attack, chloride attack, corrosion (loss of weight
of the reinforcement bar embedded in the concrete) and permeability of the
concrete. The changes in the values of the concrete properties such as sulphate
attack, chloride attack and corrosion of the reinforcement bar embedded in the
concrete due to the addition of 5% of fly ash to the concrete are tabulated in
the Table 3.5.
Table 3.4 Properties of the tannery and textile effluents collected on
22-09-2005 and 23-09-2005 respectively
SAMPLE PARAMETERS
pH Chloride Content (mg/l)
Total Dissolved Solids (mg/l)
Sulphate (mg/l)
Untreated Tannery Effluent 12.0 734 812 963
Treated Tannery Effluent 7.4 307 574 403
Untreated Textile Effluent 8.2 651 841 403
Treated Textile Effluent
7.3 389 307 144
Table 3.5 Comparison of the properties of the concrete
Type of water used
Sulphate Attack Chloride Attack Corrosion Loss of
Wt. in % Compr.
Str. Loss of
Wt. in % Compr.
Str. Loss of
Wt. in % PW 0.54 23.78 1.85 23.83 6.15 UTT 5.02 17.20 8.14 15.97 8.56 TT 4.11 21.26 5.24 17.93 7.75
UTTE 4.96 21.47 8.42 15.84 8.52 TTE 4.08 22.67 4.92 17.86 7.20
52
There is only a little reduction in loss of weight of the concrete and
reduction in compressive strength of the concrete specimens subjected to
sulphate attack, chloride attack, and corrosion of the reinforcement bar
embedded in the concrete with the addition of 5% fly ash as admixture.
In order to improve the properties of 5% fly ash blended concrete
further, silica fume (Dotto et al 2004, Bektas et al 2005, Civjan et al 2005,
Maas et al 2007), rice husk ash (Ramachandran 1998, Isaia et al 2003, Sousa
Coutinho 2003, Bui et al 2005, Agarwal 2006), calcium nitrite (Jeknavorian
and Barry 1999, Omar et al 2003, Pedro Montes et al 2004, Civjan et al 2005,
Sideris and Savva 2005, Ann et al 2006), calcium nitrate (Harald Justnes and
Nygaard 1995, Omar et al 2003, Poongodi 2005), amino-alcohols
(Wombacher et al 2004), metakaolin (Sabir et al 2001, Tsivilis et al (2003),
Batis et al 2005, Nabil and Al-Akhras 2006) and commercial products
available in the market such as webac- 2061, webac 4170, concare etc are
considered as additional admixtures for preparing the concrete to completely
nullify the adverse effects using tannery and textile effluents.
The ternary blended concrete samples were prepared using the
different effluents (detailed properties of the tannery effluent and textile
effluents collected on 10-02-2006 and 13-02-2006 respectively are given in
Table 3.6) with the addition of 5% fly ash and other admixtures such as silica
fume, rice husk ash etc.
53
Table 3.6 Properties of the tannery (10-02-2006) and textile effluents
(13-02-2006)
SAMPLE PARAMETERS
pH Chloride Content mg/l)
Total Dissolved Solids (mg/l)
Sulphate (mg/l)
Untreated Tannery Effluent 11.8 771 803 966
Treated Tannery Effluent 7.5 272 604 404
Untreated Textile Effluent 8.1 661 842 419
Treated Textile Effluent 7.5 376 298 169
The results of the addition of fly ash admixture along with the other
admixtures are tabulated in the Tables 3.7 to 3.18. Care is taken so that the
setting time of the concrete is not decreased with increase in the dosage of
corrosion inhibitor or sulphate resistant admixture or chloride resistant
admixture (Ann et al 2006).
Table 3.7 Sulphate attack on the concrete prepared using untreated
tannery effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 0.23 0.21 0.20 0.19 0.18 FA + Calcium nitrite 0.31 0.29 0.23 0.21 0.17 FA + Calcium nitrate 0.14 0.12 0.09 0.10 0.10 FA + Metakaolin 0.45 0.41 0.38 0.32 0.28 FA + Silica fume 0.26 0.23 0.20 0.21 0.19 FA + Webac 2061 0.15 0.13 0.12 0.13 0.12 FA + Webac 4170 0.16 0.14 0.11 0.13 0.11 FA + Concare 0.14 0.12 0.11 0.08 0.08
54
Table 3.8 Sulphate attack on the concrete prepared using treated
tannery effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 0.16 0.14 0.12 0.12 0.13 FA + Calcium nitrite 0.19 0.16 0.15 0.15 0.15 FA + Calcium nitrate 0.09 0.08 0.06 0.06 0.06 FA + Metakaolin 0.38 0.35 0.35 0.30 0.26 FA + Silica fume 0.17 0.16 0.16 0.15 0.16 FA + Webac 2061 0.13 0.10 0.10 0.09 0.08 FA + Webac 4170 0.13 0.11 0.11 0.09 0.08 FA + Concare 0.10 0.09 0.08 0.07 0.07
Table 3.9 Sulphate attack on the concrete prepared using untreated
textile effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 0.19 0.17 0.16 0.16 0.15
FA + Calcium nitrite 0.19 0.18 0.18 0.18 0.17
FA + Calcium nitrate 0.13 0.10 0.08 0.08 0.07
FA + Metakaolin 0.36 0.34 0.34 0.31 0.30
FA + Silica fume 0.17 0.15 0.15 0.14 0.13
FA + Webac 2061 0.14 0.11 0.11 0.10 0.10
FA + Webac 4170 0.14 0.13 0.11 0.11 0.10
FA + Concare 0.13 0.11 0.09 0.09 0.09
55
Table 3.10 Sulphate attack on the concrete prepared using treated textile
effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 0.14 0.12 0.12 0.12 0.11
FA + Calcium nitrite 0.16 0.14 0.13 0.13 0.13
FA + Calcium nitrate 0.09 0.08 0.06 0.06 0.06
FA + Metakaolin 0.35 0.33 0.32 0.32 0.31
FA + Silica fume 0.16 0.14 0.12 0.12 0.11
FA + Webac 2061 0.11 0.10 0.10 0.09 0.09
FA + Webac 4170 0.12 0.11 0.11 0.10 0.09
FA + Concare 0.09 0.07 0.06 0.06 0.06
It is observed from the experimental results (Table 3.7), by the
addition of 5% fly ash and 2.5% concare along with the concrete (prepared
using untreated tannery effluent), the loss of weight of the concrete subjected
to sulphate attack is (0.08%) less than that of the concrete added with other
admixtures such as 2.0% calcium nitrate (0.09%), 3.0% rice husk ash
(0.18%), 3.0% calcium nitrite (0.17%), 3.0% metakaolin (0.28%), 3.0% silica
fume (0.19%) etc. When the concrete is prepared using treated tannery
effluent, the loss of weight of the concrete subjected to sulphate attack is
0.06% by adding 5% fly ash and 2.0% calcium nitrate and 0.07% by adding
5% fly ash and 2.5% concare which are less than that of the concrete added
with the admixtures such as 3.0% silica fume, 3.0% webac 2061, 3.0% webac
4170 etc (Table 3.8).
56
For the concrete prepared using untreated textile effluent, the loss
of weight of the concrete subjected to sulphate attack is 0.08% by adding 5%
fly ash and 2.0% calcium nitrate and 0.09% by adding 5% fly ash and 2.0%
concare which are less than that of the concrete added with the admixtures
such as 3.0% silica fume, 3.0% webac 2061, 3.0% webac 4170 etc
(Table 3.9). The loss of weight of the concrete subjected to sulphate attack is
0.06% by adding 5% fly ash and 2.0% calcium nitrate and 0.06% by adding
5% fly ash and 2.0% concare which are less than that of the concrete added
with the admixtures such as silica fume, webac 2061, webac 4170 etc for the
concrete prepared using treated textile effluent (Table 3.10.
Table 3.11 Chloride attack on the concrete prepared using untreated
tannery effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 0.51 0.48 0.47 0.47 0.46
FA + Calcium nitrite 0.52 0.51 0.51 0.48 0.47
FA + Calcium nitrate 0.37 0.34 0.32 0.32 0.32
FA + Metakaolin 0.49 0.47 0.45 0.45 0.44
FA + Silica fume 0.52 0.50 0.50 0.48 0.47
FA + Webac 2061 0.23 0.20 0.20 0.17 0.17
FA + Webac 4170 0.22 0.20 0.19 0.19 0.18
FA + Concare 0.32 0.30 0.27 0.26 0.26
57
Table 3.12 Chloride attack on the concrete prepared using treated
tannery effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 0.48 0.46 0.45 0.45 0.44
FA + Calcium nitrite 0.48 0.47 0.47 0.45 0.42
FA + Calcium nitrate 0.34 0.32 0.31 0.31 0.31
FA + Metakaolin 0.52 0.50 0.47 0.47 0.45
FA + Silica fume 0.50 0.49 0.48 0.46 0.43
FA + Webac 2061 0.29 0.28 0.27 0.27 0.25
FA + Webac 4170 0.31 0.29 0.26 0.25 0.21
FA + Concare 0.28 0.26 0.24 0.22 0.22
Table 3.13 Chloride attack on the concrete prepared using untreated
textile effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 0.47 0.45 0.43 0.43 0.42
FA + Calcium nitrite 0.47 0.46 0.44 0.42 0.42
FA + Calcium nitrate 0.30 0.29 0.27 0.27 0.27
FA + Metakaolin 0.49 0.48 0.44 0.42 0.41
FA + Silica fume 0.47 0.45 0.42 0.42 0.41
FA + Webac 2061 0.29 0.28 0.22 0.21 0.20
FA + Webac 4170 0.30 0.28 0.25 0.24 0.22
FA + Concare 0.24 0.22 0.19 0.18 0.18
58
Table 3.14 Chloride attack on the concrete prepared using treated
textile effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 0.44 0.42 0.40 0.39 0.36
FA + Calcium nitrite 0.45 0.43 0.41 0.41 0.38
FA + Calcium nitrate 0.31 0.30 0.27 0.27 0.27
FA + Metakaolin 0.46 0.44 0.42 0.42 0.41
FA + Silica fume 0.43 0.41 0.41 0.39 0.37
FA + Webac 2061 0.28 0.26 0.24 0.24 0.23
FA + Webac 4170 0.31 0.29 0.26 0.26 0.26
FA + Concare 0.22 0.20 0.17 0.17 0.17
From the experimental results (Table 3.11), it is observed that the
loss of weight of the concrete (prepared using untreated tannery effluent)
subjected to chloride attack is 0.17% by adding 5% fly ash and 2.5% webac
2061. The loss of weight of the concrete added with 5% fly ash and 2.5%
webac 2061 is less than that of the concrete added with 5% fly ash and other
admixtures such as 3.0% webac 4170 (0.18%), 2.5% concare (0.26%), 2.0%
calcium nitrate (0.32%) etc. The same trend is observed in the concrete
prepared using treated tannery effluent also (Table 3.12). For the concrete
added with 5% fly ash and 2.5% webac 2061 (prepared using untreated and
treated textile effluent), the loss of weight of the concrete subjected to
chloride attack is less than that of the concrete added with 5% fly ash and
other admixtures such as calcium nitrate, concare, rice husk ash, metakaolin,
silica fume etc (Tables 3.13 and 3.14).
59
Table 3.15 Corrosion studies on the concrete prepared using untreated
tannery effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 1.88 1.80 1.72 1.70 1.64
FA + Calcium nitrite 1.97 1.91 1.90 1.85 1.81
FA + Calcium nitrate 1.56 1.52 1.46 1.46 1.43
FA + Metakaolin 1.82 1.76 1.73 1.69 1.63
FA + Silica fume 1.83 1.80 1.74 1.72 1.70
FA + Webac 2061 1.59 1.56 1.54 1.51 1.51
FA + Webac 4170 1.69 1.61 1.57 1.53 1.50
FA + Concare 1.38 1.33 1.29 1.26 1.26
Table 3.16 Corrosion studies on the concrete prepared using treated
tannery effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 1.76 1.73 1.70 1.63 1.63
FA + Calcium nitrite 1.85 1.82 1.82 1.80 1.76
FA + Calcium nitrate 1.34 1.32 1.28 1.28 1.27
FA + Metakaolin 1.83 1.79 1.77 1.72 1.72
FA + Silica fume 1.82 1.80 1.80 1.78 1.74
FA + Webac 2061 1.55 1.54 1.50 1.49 1.49
FA + Webac 4170 1.68 1.66 1.64 1.61 1.58
FA + Concare 1.29 1.24 1.20 1.15 1.15
60
Table 3.17 Corrosion studies on the concrete prepared using untreated
textile effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 1.55 1.52 1.50 1.46 1.42
FA + Calcium nitrite 1.67 1.61 1.57 1.53 1.53
FA + Calcium nitrate 1.31 1.28 1.24 1.24 1.24
FA + Metakaolin 1.63 1.59 1.57 1.56 1.56
FA + Silica fume 1.65 1.61 1.60 1.58 1.58
FA + Webac 2061 1.49 1.47 1.47 1.44 1.42
FA + Webac 4170 1.60 1.58 1.56 1.55 1.51
FA + Concare 1.29 1.26 1.18 1.18 1.18
Table 3.18 Corrosion studies on the concrete prepared using treated
textile effluent
Name of the admixtures added
Loss of weight (%) 28 days (1.0 %)
28 days (1.5 %)
28 days (2.0 %)
28 days (2.5 %)
28 days (3.0 %)
FA + Rice husk ash 1.49 1.47 1.46 1.46 1.41
FA + Calcium nitrite 1.50 1.47 1.45 1.45 1.43
FA + Calcium nitrate 1.25 1.22 1.19 1.19 1.18
FA + Metakaolin 1.53 1.49 1.46 1.46 1.44
FA + Silica fume 1.54 1.50 1.47 1.46 1.44
FA + Webac 2061 1.35 1.32 1.31 1.29 1.29
FA + Webac 4170 1.44 1.43 1.42 1.40 1.40
FA + Concare 1.23 1.19 1.14 1.14 1.14
61
The loss of weight of the reinforcement bar embedded in the
concrete (prepared using untreated tannery effluent) added with 5% fly ash
and 2.5% concare (1.26%) is less than that of the concrete added with 5% fly
ash and other admixtures such as 3.0% calcium nitrate (1.43%), 3.0% rice
husk ash (1.64%), 3.0% calcium nitrite (1.81%), 3.0% metakaolin (1.63%) etc
(Table 3.15). It is evident from the Table 3.16, the loss of weight of the
reinforcement bar embedded in the concrete (prepared using treated tannery
effluent) added with 5% fly ash and 2.5% concare (1.15%) is less than that of
the concrete added with 5% fly ash and other admixtures such as 2.0%
calcium nitrate (1.28%), 2.5% rice husk ash (1.63%), 3.0% calcium nitrite
(1.76%), 2.5% metakaolin (1.72%), 2.5% webac 2061 (1.49%) etc
(Table 3.16).
It is observed from the experimental results (Table 3.17), the loss of
weight of the reinforcement bar embedded in the concrete (prepared using
untreated textile effluent) added with 5% fly ash and 2.0% concare (1.18%) is
less than that of the concrete added with 5% fly ash and other admixtures such
as 2.0% calcium nitrate (1.24%), 3.0% rice husk ash (1.42%), 2.5% calcium
nitrite (1.53%), 2.5% metakaolin (1.56%), 3.0% webac 2061 (1.42%), 3.0%
webac 4170 (1.51%) etc. The loss of weight of the reinforcement bar
embedded in the concrete (prepared using treated textile effluent) added with
5% fly ash and 2.5% concare (1.14%) is less than that of the concrete added
with 5% fly ash and other admixtures such as 3.0% calcium nitrate (1.18%),
3.0% rice husk ash (1.41%), 3.0% calcium nitrite (1.43%), 3.0% metakaolin
(1.44%), 2.5% webac 2061 (1.29%), 2.5% webac 4170 (1.40%) etc
(Table 3.18).
From the results, though the webac 2061 and webac 4170 reduced
the loss of weight of the concrete subjected to chloride attack, it has not
reduced the loss of weight of the concrete subjected to sulphate attack and the
62
loss of weight of the reinforcement bar embedded in the concrete subjected to
corrosion (Tables 3.11, 3.12, 3.13 and 3.14). Hence from the detailed
analysis, 5% fly ash and 2.5% concare or 5% fly ash and 2.0% calcium nitrate
are the better combination of admixture to reduce the adverse effects on the
concrete subjected to sulphate attack, chloride attack and corrosion of the
reinforcement bar embedded in the concrete prepared using tannery effluents.
Also 5% fly ash and 2.0 % concare or 5% fly ash and 2.0% calcium nitrate are
the better combination of admixture to reduce the adverse the effects due to
sulphate attack, chloride attack and corrosion of the reinforcement bar
embedded in the concrete prepared using textile effluents.
Based on the experimental results, the concrete blended with 5% fly
ash and 2.5% concare or 2.0% calcium nitrate are selected as the optimum
dosage for minimizing the adverse effects due to chemical attacks on the
concrete prepared using tannery effluents. The concrete blended with 5% fly
ash and 2.0% concare or 2.0% calcium nitrate is selected as the optimum
dosage for minimizing the adverse effects due to chemical attacks on the
concrete specimen cast using textile effluents. To prevent the corrosion of
reinforcement bar embedded in the concrete from the root level, a commercial
inhibitor named cempatch-R is coated on the steel reinforcement bar. The
properties of the concrete samples blended with 5% fly ash and 2.5% concare
prepared using effluents are almost equal to that of the concrete samples
blended with 5% fly ash and 2.0% concare using potable water.
The untreated and treated effluents from the tanneries were
collected on 17-03-2006 and the untreated and treated effluents from the
textile processing units were collected on 22-03-2006 and the characteristics
of the effluents were tested on the same day and the results are tabulated in
the Table 3.19.
63
Table 3.19 Properties of the tannery (17-03-2006) and textile effluents
(22-03-2006)
SAMPLE PARAMETERS
pH Chloride Content (mg/l)
Total Dissolved Solids (mg/l)
Sulphate (mg/l)
Untreated Tannery Effluent
11.8 719 832 932
Treated Tannery Effluent
7.6 290 587 441
Untreated Textile Effluent
8.0 644 838 432
Treated Textile
Effluent 7.6 410 314 149
The concrete samples were prepared and cured in the respective
effluent and water for a period of 28 days.
3.3 STUDIES ON THE PROPERTIES OF THE CONCRETE
(BLENDED WITH ADMIXTURES) PREPARED USING
EFFLUENTS FOR LONGER DURATION
The studies were extended for 2.5 years and the concrete samples
were tested after curing for 28 days, 180 days, 1 year, 2 years and 2.5 years.
The effects on the various properties of admixtures blended concrete such as
sulphate attack, chloride attack, corrosion studies, chemical attack, alkali
aggregate reaction, leachability of chloride, leachability of sulphate,
permeability, compressive strength, tensile strength, flexural strength (PCC
beams), failure load (RCC beams) and bond strength are discussed in detail.
64
3.3.1 Studies on the Sulphate Attack of the Concrete
The sulphate attack on the concrete is mainly due to chemical
reaction between calcium aluminate hydrate and sulphate ions. The result of
the chemical reaction is calcium sulphoaluminate hydrate, commonly referred
to as ettringite (3CaO.A12O3.3CaSO4.32H2O) which results in the reduction
of bond strength and internal disintegration of the concrete (Hime and Bryant
Mather 1999, Bing Tian and Cohen 2000, Vijayarangan 2006, Frank et al
2006). These solids (ettringite) have a very much higher volume up to 225%
of the concrete specimen. As a consequence, stresses are produced in the
concrete which may result in the breakdown of the cement paste and it ultimately
results in the breakdown of the concrete (Lee et al 2005a).
3.3.1.1 Loss of weight of the concrete
The loss of weight of the concrete, due to sulphate attack, prepared
using the potable water, the untreated and treated tannery effluents, the
untreated and treated textile effluents for various durations are tabulated in the
Table 3.20.
Table 3.20 Loss of weight of the concrete due to sulphate attack
prepared using the potable water, untreated and treated tannery effluents, untreated and treated textile effluents
Water used
Loss of weight of the concrete (%) 28 Days 180 days 1 Year 2 Years 2.5 years
PW 0.48 0.61 0.72 0.84 0.93 UTT 4.81 4.86 4.92 4.94 5.14 TT 3.52 3.69 3.79 3.86 3.99
UTTE 4.75 4.81 4.88 4.91 5.12 TTE 3.46 3.64 3.75 3.83 3.97
65
The loss of weight of the concrete prepared using the untreated and
treated tannery effluents, untreated and treated textile effluents after 28 days
are 4.33 %, 3.04%, 4.27% and 2.98% respectively. It is observed that the loss
of weight of the concrete prepared using the untreated and treated tannery
effluents, untreated and treated textile effluents is higher than that of the
concrete prepared using the potable water and this is due to the presence of
more amount of sulphate content in the untreated and treated tannery
effluents, untreated and treated textile effluents. There is 0.45%, 0.33%,
0.47%, 0.37%, 0.51% loss of weight of the concrete prepared using the
potable water, the untreated and treated tannery effluents, untreated and
treated textile effluents respectively after 2.5years and these are graphically
shown in the Figures 3.1 and 3.2.
There is more loss of weight of the concrete prepared using
untreated and treated tannery effluents than that of the concrete prepared
using untreated and treated textile effluents because there is more amount of
sulphate content in the tannery effluents. The loss of weight of the concrete is
because of the reaction between the concrete and sulphate ions and as a result
the volume of the concrete increases, stresses are produced and it results in
the breakdown of the cement paste and ultimately it results in the breakdown
of the concrete and so the weight of the concrete is reduced (Bing Tian and
Cohen 2000). The complete break down of the concrete is because of the
formation of the thaumasite which gradually deteriorates the internal structure
of concrete (Irassar 2009).
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) are added along with the concrete,
the loss of weight of the concrete prepared using potable water is 0.06% after
28 days and 0.12% after 2.5 years, the loss of weight of the concrete prepared
66
using untreated tannery effluent is 0.10% after 28 days and 0.14% after 2.5
years and the loss of weight of the concrete prepared using treated tannery
effluent is 0.07% after 28 days and 0.12% after 2.5 years. The loss of weight
of the concrete prepared using the untreated textile effluent is 0.09% after 28
days and 0.14% after 2.5 years and the loss of weight of the concrete prepared
using the treated textile effluent is 0.06% after 28 days and 0.12% after 2.5
years. The loss of weight of the concrete reduces from 0.48% to 0.06% for the
concrete prepared using the potable water, 4.81% to 0.10%, for untreated
tannery effluent, 3.52% to 0.07% for treated tannery effluent, 4.75% to 0.09%
for untreated textile effluent, 3.42% to 0.06% for treated textile effluent after
28 days. There is considerable reduction in the loss of weight of the concrete
subjected to sulphate attack by the addition of 5% fly ash and concare
admixture (2.5% for the concrete prepared using tannery effluent and 2.0%
for the concrete prepared using textile effluent) (Kilinckale 1997). By the
addition of 5% fly ash and concare (2.5% for the concrete prepared using
tannery effluent and 2.0% for the concrete prepared using textile effluent), the
loss of weight of the concrete is decreased (Nehdi and Hayek 2005). The
effect due to sulphate attack is almost minimized with the addition of the
admixtures, as the loss of weight of the concrete is concerned.
When 5% fly ash and 2.0% calcium nitrate are added with the
concrete, the loss of weight of the concrete prepared using potable water
decreases by 0.05% after 28 days and 0.10% after 2.5 years, the loss of weight
of the concrete prepared using the untreated tannery effluent is 0.09% after 28
days and 0.13% after 2.5 years and the loss of weight of the concrete prepared
using the treated tannery effluent is 0.06% after 28 days and 0.11% after 2.5
years. The loss of weight of the concrete prepared using the untreated textile
effluent is 0.08% after 28 days and 0.12% after 2.5 years and the loss of
weight of the concrete prepared using the treated textile effluent is 0.05%
after 28 days and 0.11% after 2.5 years.
67
The loss of weight of the concrete reduces from 0.48% to 0.05% for
the concrete prepared using potable water, 4.81% to 0.09%, for untreated
tannery effluent, 3.52% to 0.06% for treated tannery effluent, 4.75% to 0.08%
for untreated textile effluent, 3.46% to 0.06% for treated textile effluent after
28 days. There is considerable reduction in the loss of weight of the concrete
due to sulphate attack by the addition of 5% fly ash and 2.0% calcium nitrate
(Nader Ghafoori et al 2008). By the addition of 5% fly ash and 2.0% calcium
nitrate, the loss of weight of the concrete decreases or almost it becomes
negligible (Figures 3.1 and 3.2).
0.01
0.06
0.11
0.16
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
) PW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.1 Comparison of loss of weight of the concrete due to sulphate
attack prepared using the potable water, untreated and
treated tannery effluents (with admixtures only)
68
0.01
0.06
0.11
0.16
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
) PW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.2 Comparison of loss of weight of the concrete due to sulphate
attack prepared using the potable water, untreated and
treated textile effluents (with admixtures only)
3.3.1.2 Compressive strength of the concrete
It is evident from the Figures 3.3 and 3.4, the compressive strength
of the concrete prepared using the potable water is 23.74MPa after 28 days
and 26.36MPa after 2.5 years, the compressive strength of the concrete
prepared using the untreated tannery effluent is 18.59MPa after 28 days and
21.21MPa after 2.5 years and the compressive strength of the concrete
prepared using the treated tannery effluent is 20.32MPa after 28 days and
22.94MPa after 2.5 years. The compressive strength of the concrete prepared
using the untreated textile effluent is 18.36MPa after 28 days and 20.98MPa
after 2.5 years and the compressive strength of the concrete prepared using
the treated textile effluent is 20.09MPa after 28 days and 22.71MPa after
2.5 years.
69
The reduction in the compressive strength of the concrete prepared
using untreated and treated tannery effluents, untreated and treated textile
effluents is 27.70%, 16.83%, 29.30% and 18.17% respectively higher than
that of the concrete prepared using the potable water after 28 days. There is
11.04%, 14.09%, 12.89%, 14.27% and 13.04% increase in the compressive of
the concrete prepared using potable water, untreated and treated tannery
effluent, untreated and treated textile effluent respectively after 2.5 years.
From the experimental results, between one year and 2.5 years there are only
1.89%, 2.36%, 2.18%, 2.39% and 2.21% increase in the compressive strength
of the concrete prepared using potable water, untreated and treated tannery
effluents, untreated and treated textile effluents respectively.
The compressive strength of the concrete prepared using untreated
and treated tannery effluents, untreated and treated textile effluents is less
than that of the concrete prepared using the potable water because of the
sulphate attack which weakens the bond strength of the concrete (Yilmaz et al
1997, Young et al 1999). The concrete gets disintegrated due to the sulphate
attack which is observed from the loss of weight of the concrete. Even though
there is only a marginal loss of weight of the concrete, there is considerable
reduction in the compressive strength of the concrete because the internal
structure of the concrete gets modified and disintegrated (Marchand et al
2002).
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) are added along with the concrete,
the compressive strength of the concrete prepared using the potable water is
25.02MPa after 28 days and 27.64MPa after 2.5 years, the compressive
strength of the concrete prepared using the untreated tannery effluent is
70
25.74MPa after 28 days and 28.37MPa after 2.5 years and the compressive
strength of the concrete prepared using the treated tannery effluent is
25.40MPa after 28 days and 28.02MPa after 2.5 years. The compressive
strength of the concrete prepared using the untreated textile effluent is
25.51MPa after 28 days and 28.14MPa after 2.5 years and the compressive
strength of the concrete prepared using the treated textile effluent is
25.17MPa after 28 days and 27.79MPa after 2.5 years.
By the addition of 5% fly ash and concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent), the compressive strength of
the concrete increases by 5.39%, 38.46%, 25%, 38.94% and 25.29% using
potable water, untreated and treated tannery effluent, untreated and treated
textile effluent respectively after 28 days (Hanifi Binici and Orhan Aksogan
2006). The same trend is observed even after 2.5 years also. It is observed
from the experimental results, with the addition of the admixtures, the
compressive strength of the concrete prepared using tannery effluents and
textile effluents is almost equal to that of the compressive strength of the
concrete prepared using potable water. The decrease in the compressive
strength of the concrete subjected to sulphate attack is almost reduced with
the addition of the admixtures.
When 5% fly ash and 2.0% calcium nitrate are added along with the
concrete, the compressive strength of the concrete prepared using the potable
water is 25.47MPa after 28 days and 28.09MPa after 2.5 years, the
compressive strength of the concrete prepared using the untreated tannery
effluent is 26.19MPa after 28 days and 28.81MPa after 2.5 years and the
compressive strength of the concrete prepared using the treated tannery
71
effluent is 25.85MPa after 28 days and 28.47MPa after 2.5 years. The
compressive strength of the concrete prepared using the untreated textile
effluent is 25.96MPa after 28 days and 28.58MPa after 2.5 years and the
compressive strength of the concrete prepared using the treated textile effluent
is 25.62MPa after 28 days and 28.24MPa after 2.5 years. With the addition of
5% fly ash and 2.0% calcium nitrate, the compressive strength of the concrete
increases by 7.29%, 40.88%, 27.21%, 41.39% and 27.53% using the potable
water, the untreated and treated tannery effluents, untreated and treated textile
effluents respectively after 28 days. The same trend is observed after 2.5 years
also.
When fine aggregate, coarse aggregate, cement and admixture react
with water (hydration), silica gel and calcium hydroxide are formed. The
calcium hydroxide reacts with admixture and forms secondary gel which
hardens the concrete. The ingress of sulphate ions into the inner core of the
concrete is reduced and hence the effect of sulphate attack on the concrete is
minimized (Ezziane et al 2007). The formation of the ettringite is delayed
because of the addition of the admixture (Collepardi 2003). The increase in
the compressive strength of the concrete is because of the addition of
admixture which decreases the pore size of the concrete (Sanchez et al 2008).
The admixing fly ash (pozzolanic material) converts the leachable calcium
hydroxide into insoluble non-leachable cementitious product. In addition this
conversion is responsible for impermeability of the concrete. It is observed
from the experimental results, the compressive strength of the concrete
prepared using untreated and treated tannery effluents, untreated and treated
textile effluents is almost equal to that of the compressive strength of the
concrete prepared using the potable water with the addition of the admixtures.
The specimen subjected to sulphate attack is shown in Figure 3.5.
72
18
20
22
24
26
28
30
0 200 400 600 800 1000
Age of concrete (days)
Com
pres
sive
stre
ngth
(MPa
) PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.3 Comparison of the compressive strength of the concrete due
to sulphate attack using the potable water, untreated and
treated tannery effluents
18
20
22
24
26
28
30
0 200 400 600 800 1000
Age of concrete (days)
Com
pres
sive
stre
ngth
(MPa
) PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.4 Comparison of the compressive strength of the concrete due
to sulphate attack using the potable water, untreated and
treated textile effluents
73
SPECIMEN SUBJECTED TO SULPHATE ATTACK
Figure 3.5 Specimen subjected to sulphate attack
By the addition of 5% fly ash and 2.0% calcium nitrate or 5% fly
ash and concare (2.5% concare is added with the concrete prepared using
tannery effluent and 2.0% concare is added with the concrete prepared using
textile effluent), the adverse effect due to sulphate attack on the concrete is
minimized. The sulphate attack is minimized by adding admixtures such as
fly ash with either concare or calcium nitrate in required proportions (Khatri
et al 1997, Vu et al 2001, Bryant Mather 2004). From the results, it can be
concluded that by using ternary blended concrete, the sulphate resistance of
the concrete can be improved (Ghrici et al 2007).
3.3.2 Studies on the Chloride Attack of the Concrete
The chloride attack on the concrete is particularly important
because it primarily induces the corrosion of reinforcement bar embedded in
the concrete (Glass and Buenfeld 1998, Luping Tang 1999). It is observed
that more number of failure and collapse of structures are due to corrosion of
reinforcement bar embedded in the concrete. The concrete subjected to
74
chloride attack is characterized by efflorescence and persistent dampness in
the concrete structure.
3.3.2.1 Loss of weight of the concrete
The loss of weight of the concrete subjected to chloride attack
prepared using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents are tabulated in the Table 3.21.
Table 3.21 Loss of weight of the concrete due to chloride attack prepared
using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents
Water used Loss of weight of the concrete (%)
28 Days 180 days 1 Year 2 Years 2.5 years
PW 1.70 0.92 0.87 0.78 0.74
UTT 7.91 7.10 6.96 6.88 6.80
TT 4.61 3.79 3.70 3.62 3.57
UTTE 7.29 6.79 6.72 6.66 6.61
TTE 4.06 3.58 3.49 3.43 3.38
The loss of weight of the concrete prepared using untreated and
treated tannery effluents, untreated and treated textile effluents are 6.21%,
2.91%, 5.59% and 2.36% respectively higher than that of the concrete
specimen prepared using potable water after 28 days (Poornima 2006). There
is decrease of 0.96%, 1.11%, 1.04%, 0.68%, 0.68% loss of weight of the
concrete prepared using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents respectively after 2.5 years. It is
observed that there is more loss of weight of the concrete prepared using
75
tannery effluents than that of the concrete prepared using textile effluents
because there is more amount of chloride content in the tannery effluents. The
loss of weight of the concrete prepared using potable water is almost similar
to that of the concrete prepared using tannery and textile effluents after 2.5
years, because initially there is more loss of weight of the concrete due to the
chloride attack.
The loss of weight of the concrete is because of the deterioration of
the concrete which is often characterized by the expansion of the concrete
exposed to chloride particles (Poornima 2006). The deterioration of the
concrete is due to the penetration of chloride ions or compounds through the
cover of concrete by the process of diffusion. In addition the concrete
subjected to chloride attack has shown efflorescence and persistent dampness
on the surface of the concrete. The loss of weight of the concrete decreases
with passage of time i.e after 28 days, the loss of weight of the concrete is
1.70% but after 2.5 years it is only 0.74% for potable water and the same
phenomena is observed for all the concrete specimens cast using different
waters. This may be due to the reduction in the permeability factor of the
concrete. It is observed that the loss of weight of the concrete prepared using
untreated and treated tannery effluents, untreated and treated textile effluents
is higher than that of the concrete prepared using potable water and this is due
to presence of chloride in the untreated and treated tannery effluents,
untreated and treated textile effluents. The Figure 3.10 shows the specimens
subjected to chloride attack.
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) are added while preparing the
concrete, it is evident from the Figures 3.6 and 3.7, the loss of weight of the
concrete prepared using potable water is 0.21% after 28 days and 0.12% after
76
2.5 years, the loss of weight of the concrete prepared using untreated tannery
effluent is 0.26% after 28 days and 0.16% after 2.5 years and the loss of
weight of the concrete prepared using treated tannery effluent is 0.22% after
28 days and 0.13% after 2.5 years. The loss of weight of the concrete
prepared using untreated textile effluent is 0.18% after 28 days and 0.11%
after 2.5 years and the loss of weight of the concrete prepared using treated
textile effluent is 0.17% after 28 days and 0.10% after 2.5 years.
The loss of weight of the concrete reduces from 1.70% to 0.21% for
the concrete prepared using potable water, 7.91% to 0.26% for untreated
tannery effluent, 4.61% to 0.22% for treated tannery effluent, 7.29% to 0.18%
for untreated textile effluent, 4.06% to 0.17% for treated textile effluent after
28 days of curing. There is considerable reduction in the loss of weight of the
concrete due to chloride attack by the addition of 5% fly ash and concare
(2.5% concare is added with the concrete prepared using tannery effluent and
2.0% concare is added with the concrete prepared using textile effluent)
admixture. By the addition of 5% fly ash and concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent), the loss of weight of the
concrete decreases considerably or almost it becomes negligible (Jin Zuquan
et al 2007).
When 5% fly ash and 2% calcium nitrate are added with the
concrete, the loss of weight of the concrete prepared using potable water is
0.29% after 28 days and 0.12% after 2.5 years, the loss of weight of the
concrete prepared using untreated tannery effluent is 0.32% after 28 days and
0.15% after 2.5 years and the loss of weight of the concrete prepared using
treated tannery effluent is 0.31% after 28 days and 0.13% after 2.5 years. The
loss of weight of the concrete prepared using untreated textile effluent is
0.27% after 28 days test and 0.18% after 2.5 years and the loss of weight of
77
the concrete prepared using treated textile effluent is 0.27% after 28 days and
0.16% after 2.5 years.
The loss of weight of the concrete reduces from 1.70% to 0.29% for
the concrete prepared using potable water, 7.91% to 0.32%, for untreated
tannery effluent, 4.61% to 0.31% for treated tannery effluent, 7.29% to 0.27%
for untreated textile effluent, 4.06% to 0.27% for treated textile effluent after
28 days. There is considerable reduction in the loss of weight of the concrete
due to chloride attack by the addition of 5% fly ash and 2% calcium nitrate.
By the addition of 5% fly ash and 2% calcium nitrate, the loss of weight of
the concrete decreases or almost it becomes negligible. The effect due to
chloride attack on the concrete is almost minimized, as the loss of weight of
the concrete is concerned with the addition of admixtures.
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
) PW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.6 Comparison of loss of weight of the concrete due to chloride
attack prepared using potable water, untreated and treated
tannery effluents (admixtures only)
78
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
) PW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.7 Comparison of loss of weight of the concrete due to chloride
attack prepared using potable water, untreated and treated
textile effluents (admixtures only)
3.3.2.2 Compressive strength of the concrete
The compressive strength of the concrete prepared using potable
water is 23.24MPa after 28 days and 26.13MPa after 2.5 years. The
compressive strength of the concrete prepared using untreated tannery effluent
is 16.09MPa after 28 days and 18.98MPa after 2.5 years and the compressive
strength of the concrete prepared using treated tannery effluent is 18.75MPa
after 28 days and 21.64MPa after 2.5 years. The compressive strength of the
concrete prepared using untreated textile effluent is 15.86MPa after 28 days
and 18.75MPa after 2.5 years and the compressive strength of the concrete
prepared using treated textile effluent is 18.52MPa after 28 days and
21.41MPa after 2.5 years. The Figures 3.8 and 3.9 show the variation of the
compressive strength of the concrete due to chloride attack with and without
the addition of admixtures.
79
The decrease in the compressive strength of the concrete prepared
using untreated and treated tannery effluents, untreated and treated textile
effluents are 44.44%, 23.95%, 46.53% and 25.49% respectively more than
that of the concrete prepared using potable water after 28 days. There is
12.44%, 17.96%, 15.41%, 18.22% and 15.60% increase in the compressive
strength of the concrete prepared using potable water, untreated and treated
tannery effluents, untreated and treated textile effluents respectively after 2.5
years. It is observed that between one year and 2.5 years there are only 2.43%,
3.38%, 2.95%, 3.42% and 2.98% increase in the compressive of the concrete
prepared using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents respectively.
The compressive strength of the concrete goes on increasing with
the increase in age of the concrete. The compressive strength of the concrete
prepared using untreated and treated tannery effluents, untreated and treated
textile effluents is less than that of the concrete prepared using potable water
due to chloride attack which weakens the bond strength of concrete. The
concrete gets disintegrated due to the chloride attack and it is evident from the
loss of weight of the concrete. Hence it can be concluded that the compressive
strength of the concrete increases with reduction in loss of weight of the
concrete.
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) are added along with the concrete,
the compressive strength of the concrete prepared using potable water is
24.52MPa after 28 days and 27.41MPa after 2.5 years, the compressive
strength of the concrete prepared using untreated tannery effluent is
25.24MPa after 28 days and 28.14MPa after 2.5 years and the compressive
strength of the concrete prepared using treated tannery effluent is 24.90MPa
80
after 28 days and 27.79MPa after 2.5 years. The compressive strength of the
concrete prepared using untreated textile effluent is 25.01MPa after 28 days
and 27.91MPa after 2.5 years and the compressive strength of the concrete
prepared using treated textile effluent is 24.67MPa after 28 days and
27.56MPa after 2.5 years.
By the addition of 5% fly ash and concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent), the compressive strength of
the concrete increases by 5.51%, 56.87%, 32.80%, 57.69% and 33.21% using
potable water, untreated and treated tannery effluents, untreated and treated
textile effluents respectively after 28 days. Almost the same trend is observed
after 2.5 years also. It is observed from the experimental results that the
compressive strength of the concrete specimens prepared using untreated and
treated tannery effluents, untreated and treated textile effluents are almost
equal to that of the compressive strength of the concrete prepared using
potable water. The decrease in the compressive strength of the concrete due to
chloride attack is almost reduced.
When 5% fly ash and 2.0% calcium nitrate are added with the
concrete, the compressive strength of the concrete prepared using potable
water is 24.97MPa after 28 days and 27.86MPa after 2.5 years, the
compressive strength of the concrete prepared using untreated tannery effluent
is 25.69MPa after 28 days and 28.58MPa after 2.5 years and the compressive
strength of the concrete prepared using treated tannery effluent is 25.35MPa
after 28 days and 28.24MPa after 2.5 years. The compressive strength of the
concrete prepared using untreated textile effluent is 25.46MPa after 28 days
and 28.35MPa after 2.5 years and the compressive strength of the concrete
prepared using treated textile effluent is 25.12MPa after 28 days and
28.014MPa after 2.5 years.
81
With the addition of 5% fly ash and 2% calcium nitrate, the compressive strength of the concrete increases by 7.44%, 59.66%, 35.20%, 60.53% and 35.64% using potable water, untreated and treated tannery effluent, untreated and treated textile effluent respectively after 28 days (Sarat Kumar Das and Yudhbir 2006). Almost the same trend is observed after 2.5 years also (Figures 3.8 and 3.9). The hardening and strength development of the blended concrete is faster than that of the conventional concrete because the blended admixture modifies the pore structure of the concrete (Yong Xin Li et al 2006). The formation of the secondary gel improves the denseness of the concrete formation and as a result the ingress of the chloride ions is prevented. It is observed from the experimental results that the compressive strength of the concrete specimen cast using tannery and textile effluents is almost equal to that of the compressive strength of the concrete specimen cast using potable water with the addition of 5% fly ash and concare (2.5% concare is added with the concrete prepared using tannery effluent and 2.0% concare is added with the concrete prepared using textile effluent) or 5% fly ash and 2% calcium nitrate.
16
18
20
22
24
26
28
30
0 200 400 600 800 1000
Age of concrete (days)
Com
pres
sive
stre
ngth
(MPa
) PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.8 Comparison of compressive strength of the concrete due to chloride attack prepared using potable water, untreated and treated tannery effluents
82
15
17
19
21
23
25
27
29
0 200 400 600 800 1000
Age of concrete (days)
Com
pres
sive
stre
ngth
(MPa
) PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.9 Comparison of compressive strength of the concrete due to
chloride attack prepared using potable water, untreated and
treated textile effluents
SPECIMEN SUBJECTED TO CHLORIDE ATTACK
Figure 3.10 Specimen subjected to chloride attack
The pozzolanic action is responsible for the impermeability of the
concrete and in turn it reduces the adverse effects on the concrete due to
chloride attack, in terms of loss of weight of the concrete and reduction in the
compressive strength of the concrete (Gruber et al 2001). Hence by the
83
addition of 5% fly ash and 2.0% calcium nitrate or 5% fly ash and concare
(2.5% concare is added with the concrete prepared using tannery effluent and
2.0% concare is added with the concrete prepared using textile effluent), the
adverse effect due to chloride attack on the concrete is reduced.
3.3.3 Studies on the Corrosion of the Concrete The corrosion is defined as a process of gradual wearing away of a
metal (reinforced bar embedded in the concrete) due to chemical and
electrochemical reaction by its surroundings. Due to high alkality of the
concrete a protective oxide film is present on the surface of the steel
reinforcement bar. This protective layer can be lost because of the presence of
chloride in the presence of water and oxygen (chemical reaction). In practice,
the action of chloride ions, on the reinforcement bar embedded in the
concrete, in inducing the corrosion is the more serious problem than any other
problems (Ormellese et al 2006, Mohd Firdows et al 2007).
In an electrochemical process, when there is a difference in
electrical potential in the steel, one part becomes anode and the other part
becomes cathode and connected by an electrolyte in the form of pore water in
the hardened cement paste. The positively charged ferrous ions (Fe++) at the
anode pass into solution while negatively charged free electrons (e-) pass
through the steel into cathode where they are absorbed by the constituents of
the electrolyte and combine with water and oxygen to form hydroxyl ions
((OH)-) (Olivier Poupard et al 2004). These travel through the electrolyte and
combine with the ferrous ions to form ferric hydroxide which is converted by
further oxidation in to rust (Tamizheselvi and Samuel Knight 2007). The
other important causes of corrosion of reinforcement bar embedded in the
concrete are due to excessive water cement ratio, permeability of the concrete,
pH of water, presence of salts, quality of water used and atmospheric
conditions (Woo-Yong Jung et al 2003, Erdogdua et al 2004). The corrosion
84
of reinforced bar embedded in the concrete is observed in the form of
deterioration and loss of weight of the material (reinforced bar) (Li 2003).
The loss of weight of the reinforcement bar embedded in the
concrete prepared using potable water is 5.36% after 28 days and 6.87% after
2.5 years, the loss of weight of the reinforcement bar embedded in the
concrete prepared using untreated tannery effluent is about 7.82% after 28
days and 9.74% after 2.5 years and the loss of weight of the reinforcement bar
embedded in the concrete prepared using treated tannery effluent is about
7.54% after 28 days and 9.49% after 2.5 years. The loss of weight of the
reinforcement bar embedded in the concrete prepared using untreated textile
effluent is about 7.92% after 28 days and 8.83% after 2.5 years and the loss of
weight of the reinforcement bar embedded in the concrete prepared using
treated textile effluent is about 7.54% after 28 days and 8.61% after 2.5 years.
The loss of weight of the reinforcement bar embedded in the concrete is
because of the reduction in cross sectional area (As a result of chemical or
electrochemical reaction, the reinforced bar is converted into oxide) of the
reinforced bar embedded in the concrete (Kapilesh Bhargava et al 2005,
Jieying Zhang and Zoubir Lounis 2006).
The loss of weight of the reinforcement bar embedded in the
concrete prepared using untreated and treated tannery effluents, untreated and
treated textile effluents is 2.46%, 2.18%, 2.56% and 2.18% respectively and is
more than that of the loss of weight of reinforcement bar embedded in the
concrete prepared using potable water after 28 days. It is observed from the
experimental results that the corrosion phenomena is more noticed in the
concrete prepared using untreated and treated tannery effluents, untreated and
treated textile effluents than that of the concrete prepared using potable water.
The same trend is observed for the entire 2.5 years as shown in the Figure
3.11 and 3.12. There is an increase of 1.51%, 1.92%, 1.95% 0.91% and 1.07%
85
loss of weight of the reinforcement bar embedded in the concrete prepared
using potable water, untreated and treated tannery effluents, untreated and
treated textile effluents between 28 days and 2.5 years. The loss of weight of
the reinforcement bar embedded in the concrete prepared using untreated
tannery effluent and untreated textile effluent is 0.28 % and 0.38% more than
that of the reinforcement bar embedded in the concrete prepared using treated
tannery effluent and treated textile effluent.
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) is added with the concrete, the loss of
weight of the reinforcement bar embedded in the concrete prepared using
potable water is 1.12% after 28 days and 2.14% after 2.5 years, the loss of
weight of the reinforcement bar embedded in the concrete prepared using
untreated tannery effluent is about 1.26% after 28 days and 2.21% after 2.5
years and the loss of weight of the reinforcement bar embedded in the
concrete treated tannery effluent is about 1.15% after 28 days and 2.16% after
2.5 years. The loss of weight of the reinforcement bar embedded in the
concrete prepared using untreated textile effluent is 1.18% after 28 days and
2.17% after 2.5 years and the loss of weight of the reinforcement bar
embedded in the concrete prepared using treated textile effluent is about
1.14% after 28 days and 2.15% after 2.5 years.
The loss of weight of the reinforcement bar embedded in the
concrete prepared using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents decreases by 4.24%, 6.56%, 6.39%,
6.74% and 6.40% respectively after 28 days. This is because of the
modification of the pore structure of the concrete and reduction in
permeability of the concrete due to the addition of the admixture (Gruber et al
2001). The movements of water and chloride ions are reduced inside the
86
concrete and as a result the corrosion of reinforced bar embedded in the
concrete is also reduced. When 5% fly ash and concare (2.5% concare is
added with the concrete prepared using tannery effluent and 2.0% concare is
added with the concrete prepared using textile effluent) are added with the
concrete, the loss of weight of the reinforcement bar embedded in the concrete
specimen is considerably decreased.
When 5% fly ash and 2% calcium nitrate are added with the
concrete, the loss of weight of the reinforcement bar embedded in the concrete
prepared using potable water is 1.16% after 28 days and 2.21% after 2.5
years, the loss of weight of the reinforcement bar embedded in the concrete
prepared using untreated tannery effluent is 1.46% after 28 days and 2.58%
after 2.5 years and the loss of weight of the reinforcement bar embedded in
the concrete prepared using treated tannery effluent is 1.28% after 28 days
and 2.35% after 2.5 years. The loss of weight of the reinforcement bar
embedded in the concrete prepared using untreated textile effluent is 1.24%
after 28 days and 2.28% after 2.5 years and the loss of weight of the
reinforcement bar embedded in the concrete prepared using treated textile
effluent is 1.19% after 28 days and 2.24% after 2.5 years.
The loss of weight of the reinforcement bar embedded in the
concrete prepared using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents decreases by 4.20%, 6.36%, 6.26%,
6.68% and 6.35% respectively after 28 days. The effects of the corrosion of
the reinforcement bar embedded in the concrete are graphically shown in
Figures 3.11 and 3.12. It is observed that the initiation of the corrosion of the
reinforcement bar embedded in the concrete is delayed due to the addition of
the admixtures and also the rate of the corrosion is reduced (Gaidis 2004,
Wombacher et al 2004). There is considerable reduction in the loss of weight
87
of the reinforcement bar embedded in the concrete due to the addition of 5%
fly ash and 2% calcium nitrate which enhances the properties of the concrete.
1
2
3
4
5
6
7
8
9
10
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.11 Comparison of loss of weight of the reinforcement bar
embedded in the concrete prepared using potable water,
untreated and treated tannery effluents
1
2
3
4
5
6
7
8
9
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
)
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.12 Comparison of loss of weight of the reinforcement bar
embedded in the concrete prepared using potable water,
untreated and treated textile effluents
88
When the reinforcement bar embedded in the concrete is coated
with chempatch-R, the loss of weight of the reinforcement bar embedded in
the concrete prepared using potable water is 0.24% after 28 days and 0.25%
after 2.5 years, the loss of weight of the reinforcement bar embedded in the
concrete prepared using untreated tannery effluent is about 0.26% after 28
days and 0.28% after 2.5 years and the loss of weight of the reinforcement bar
embedded in the concrete prepared using treated tannery effluent is about
0.26% after 28 days and 0.27% after 2.5 years. The loss of weight of the
reinforcement bar embedded in the concrete prepared using untreated textile
effluent is 0.24% after 28 days and 0.25% after 2.5 years and the loss of
weight of the reinforcement bar embedded in the concrete prepared using
treated textile effluent is 0.24% after 28 days and 0.25% after 2.5 years
(Bryant Mather 2004).
The loss of weight of the reinforcement bar embedded in the
concrete prepared using potable water, untreated and treated tannery effluent,
untreated and treated textile effluent decreases by 5.12%, 7.56%, 7.28%,
7.68% and 7.30% respectively after 28 days. After 2.5 years also the same
trend is observed. When the reinforcement is coated with chempatch-R, the
decrease in weight of reinforcement bar reduces almost to 0.27% of the total
corrosion without adding any admixture. This is due to the fact that when the
steel bar is coated with chempatch-R, a thin layer is formed around the steel
and the steel is protected from invasion of water or chloride ion present in the
concrete.
This experiment is carried out by coating the reinforcement with
chempatch-R and adding the admixtures such as 5% fly ash and concare
(2.5% concare is added with the concrete prepared using tannery effluent and
2.0% concare is added with the concrete prepared using textile effluent) and
5% fly ash and 2% calcium nitrate to the concrete.
89
When 5% fly ash and concare (2.5% concare is added with the concrete prepared using tannery effluent and 2.0% concare is added with the concrete prepared using textile effluent) are added with the concrete and the embedded reinforcement bar is coated with chempatch-R, the loss of weight of the reinforcement bar embedded in the concrete prepared using potable water is 0.01% after 28 days and 0.02% after 2.5 years, the loss of weight of the reinforcement bar embedded in the concrete prepared using untreated tannery effluent is about 0.01% after 28 days and 0.03% after 2.5 years and the loss of weight of the reinforcement bar embedded in the concrete prepared using treated tannery effluent is about 0.01% after 28 days and 0.03% after 2.5 years. The loss of weight of the reinforcement bar embedded in the concrete prepared using untreated textile effluent is 0.01% after 28 days and 0.03% after 2.5 years and the loss of weight of the reinforcement bar embedded in the concrete prepared using treated textile effluent is 0.01% after 28 days and 0.02% after 2.5 years. When 5% fly ash and 2% calcium nitrate are added with the concrete and the reinforcement bar is coated with chempatch-R, the loss of weight of the reinforcement bar embedded in the concrete prepared using potable water is 0.01% after 28 days and 0.02% after 2.5 years, the loss of weight of the reinforcement bar embedded in the concrete prepared using untreated tannery effluent is 0.01% after 28 days and 0.04% after 2.5 years and the loss of weight of the reinforcement bar embedded in the concrete prepared using treated tannery effluent is 0.01% after 28 days and 0.03% after 2.5 years. The loss of weight of the reinforcement bar embedded in the concrete prepared using untreated textile effluent is 0.01% after 28 days and 0.03% after 2.5 years and the loss of weight of the reinforcement bar embedded in the concrete prepared using treated textile effluent is 0.01% after 28 days and 0.02% after 2.5 years. From the experimental results graphically shown in Figures 3.13 and 3.14, it is observed that the corrosion of the reinforcement bar embedded in the concrete is reduced to less than 0.05% by coating the embedded reinforcement bar with chempatch-R.
90
0
0.05
0.1
0.15
0.2
0.25
0.3
0 200 400 600 800 1000
Age of concrete in (days)
Loss
of w
eigh
t (%
)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.13 Comparison of loss of weight of chempatch-R coated
reinforcement bar embedded in the concrete prepared using
potable water, untreated and treated tannery effluents
0
0.05
0.1
0.15
0.2
0.25
0.3
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
)
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.14 Comparison of loss of weight of chempatch-R coated
reinforcement bar embedded in the concrete prepared using
potable water, untreated and treated textile effluents
91
The Figures 3.15 and 3.16 shows the corrosion test in progress and
Figure 3.17 shows the concrete specimen subjected to corrosion.
CORROSION TEST SETUPCORROSION TEST SETUP
Figure 3.15 Corrosion test in progress
Figure 3.16 Observing measurements in corrosion studies
92
Figure 3.17 Specimen subjected to corrosion
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent), 5% fly ash and 2% calcium nitrate
are added to the concrete, embedded with the reinforcement bar coated with
chempatch-R, the decrease in weight of the reinforcement bar almost
decreases by less than 0.05% which is almost equal to zero. It is observed that
the loss of weight of the reinforcement bar embedded in the concrete, due to
corrosion, is totally minimized. It is concluded that the corrosion of steel
reinforcement bar embedded in the concrete prepared using tannery and
textile effluents are almost minimized with the addition of admixtures and
reinforcement bar coated with chempatch-R. The additional precautionary
steps such as providing proper cover depth, controlled water cement ratio and
avoiding congested reinforcement etc can also be adopted and practiced to
prevent and control the corrosion of the reinforcement bar embedded in the
concrete while prepared using industrial effluents (Byung Hwan Oh and
Seung Yup Jang 2007, Khatri and Sirivivatnanon 2004).
93
3.3.3.1 Corrosion studies of the concrete (without acceleration of
corrosion)
This experiment is carried out to study the corrosion properties of
the reinforcement bar embedded in the concrete without inducing corrosion
by any artificial means. The loss of weight of the reinforcement bar embedded
in the concrete is 0% after 28 days and 0% after 2.5 years using potable water,
untreated and treated tannery effluents, untreated and treated textile effluents.
From the experimental results, it is observed that in normal day to day
conditions there is no loss of weight of the reinforcement bar embedded in the
concrete due to corrosion even when the concrete is prepared using tannery
and textile effluents. It is concluded that there is loss of weight of the
reinforcement bar embedded in the concrete due to corrosion over a period of
2.5 years.
3.3.4 Studies on the Chemical Attack of the Concrete
Chemical attack generally occurs when calcium hydroxide present
in the concrete is vigorously attacked. The acidic solutions both mineral (such
as sulphuric, hydrochloric, nitric, and phosphoric chemicals) and organic
(such as lactic, acetic, formic, tannic chemicals) are the most aggressive
agents inducing chemical attack on the concrete. The chemical attack on the
concrete will not cause deterioration in the interior of the concrete structure
without the cement paste on the outer portion being completely destroyed.
The rate of penetration is inversely proportional to the quantity of chemical
neutralizing material, such as the calcium hydroxide, cement gel (C-S-H gel)
and limestone aggregates. In practice, the degree of chemical attack on the
concrete goes on increasing with an increase in acidity of the concrete. The
chemical attack on the concrete occurs at values of pH below 6.5, a pH of less
than 4.5 leading to severe chemical attack. Indirectly due to chemical attack,
94
when pH of the concrete reduces below 6.5, it gives rise to the corrosion of
the reinforcement bar embedded in the concrete (Tamer El Maaddawy and
Khaled Soudki 2007). The rate of chemical attack also depends on the ability
of hydrogen ions to be diffused through the cement gel (C-S-H) after calcium
hydroxide (Ca (OH)2) has been dissolved and leached out of the concrete.
3.3.4.1 Loss of weight of the concrete
From the Figures 3.18 and 3.19, the loss of weight of the concrete
prepared using potable water is 2.27% after 28 days and 1.75% after 2.5
years, the loss of weight of the concrete prepared using untreated tannery
effluent is 3.30% after 28 days and 2.80% after 2.5 years and the loss of
weight of the concrete prepared using treated tannery effluent is 3.28% after
28 days and 2.77% after 2.5 years. The loss of weight of the concrete
prepared using untreated textile effluent is 3.18% after 28 days and 2.68%
after 2.5 years and the loss of weight of the concrete prepared using treated
textile effluent is 3.14% after 28 days and 2.65% after 2.5 years.
The loss of weight of the concrete specimens cast using untreated
and treated tannery effluents, untreated and treated textile effluents are 1.03
%, 1.01%, 0.91% and 0.87% respectively more than that of the concrete
specimens cast using potable water after 28 days. After 2.5 years, the loss of
weight of the concrete samples prepared using untreated and treated tannery
effluents, untreated and treated textile effluents is 1.05 %, 1.02%, 0.93% and
0.90% respectively more than that of the concrete specimens prepared using
potable water. Almost the same trend is observed after 28 days and 2.5 years.
The loss of weight of the concrete decreases with the passage of
time i.e after 28 days, the decrease in loss of weight of the concrete is 2.27%
but after 2.5 years it is only 1.75% for potable water and this condition is
95
same for all the concrete specimens prepared using tannery and textile
effluents (Bassuoni and Nehdi 2007). This may be due to the reduction in
permeability factor of the concrete.
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) are added with the concrete, the loss
of weight of the concrete prepared using potable water is 2.23% after 28 days
and 1.73% after 2.5 years, the loss of weight of the concrete prepared using
untreated tannery effluent is 2.94% after 28 days and 2.62% after 2.5 years
and the loss of weight of the concrete prepared using treated tannery effluent
is 2.89% after 28 days and 2.58% after 2.5 years. The loss of weight of the
concrete prepared using untreated textile effluent is 2.85% after 28 days and
2.51% after 2.5 years and the loss of weight of the concrete prepared using
treated textile effluent is 2.84% after 28 days and 2.49% after 2.5 years.
The loss of weight of the concrete specimen reduces from 2.27% to
2.23% for the concrete prepared using potable water, 3.30% to 2.94%, for
untreated tannery effluent, 3.28% to 2.89% for treated tannery effluent, 3.18%
to 2.85% for untreated textile effluent, 3.14% to 2.84% for treated textile
effluent after 28 days. There is considerable reduction in the loss of weight of
the concrete due to chemical attack by the addition of fly ash and concare. By
the addition of 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) admixture, the loss of weight of the
concrete decreases or almost it becomes negligible (Gopalan 2007).
When 5% fly ash and 2% calcium nitrate are added with the
concrete, the loss of weight of the concrete prepared using potable water is
2.24% after 28 days and 1.75% after 2.5 years, the loss of weight of the
96
concrete prepared using untreated tannery effluent is 2.95% after 28 days and
2.66% after 2.5 years and the loss of weight of the concrete prepared using
treated tannery effluent is 2.90% after 28 days and 2.60% after 2.5 years. The
loss of weight of the concrete prepared using untreated textile effluent is
2.86% after 28 days and 2.52% after 2.5 years and the loss of weight of the
concrete prepared using treated textile effluent is 2.85% after 28 days and
2.51% after 2.5 years.
The loss of weight of the concrete reduces from 2.27% to 2.24% for
the concrete prepared using potable water, 3.30% to 2.95%, for untreated
tannery effluent, 3.28% to 2.90% for treated tannery effluent, 3.18% to 2.86%
for untreated textile effluent and 3.14% to 2.85% for treated textile effluent
after 28 days. There is only a little reduction in the loss of weight of the
concrete due to chemical attack by the addition of 5% fly ash and 2% calcium
nitrate.
1
1.5
2
2.5
3
3.5
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.18 Comparison of loss of weight of the concrete due to chemical
attack on the concrete prepared using potable water,
untreated and treated tannery effluents
97
1
1.5
2
2.5
3
3.5
0 200 400 600 800 1000
Age of concrete (days)
Loss
of w
eigh
t (%
)
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.19 Comparison of loss of weight of the concrete due to chemical
attack on the concrete prepared using potable water,
untreated and treated textile effluents
3.3.4.2 Compressive strength of the concrete
The compressive strength of the concrete prepared using potable
water is 17.21MPa after 28 days and 20.10MPa after 2.5 years, the
compressive strength of the concrete prepared using untreated tannery effluent
is 17.93MPa after 28 days and 20.82MPa after 2.5 years and the compressive
strength of the concrete prepared using treated tannery effluent is 17.59MPa
after 28 days and 20.48MPa after 2.5 years. The compressive strength of the
concrete prepared using untreated textile effluent is 17.70MPa after 28 days
and 20.59MPa after 2.5 years and the compressive strength of the concrete
prepared using treated textile effluent is 17.36MPa after 28 days and
20.25MPa after 2.5 years. The compressive strength of the concrete subjected
to chemical attack is graphically shown in the Figures 3.20 and 3.21.
98
It is observed from the experimental results that there is significant
decrease in the compressive strength of the concrete prepared using potable
water, untreated and treated tannery effluents, untreated and treated textile
effluents. The reduction in the compressive strength of the concrete is almost
same for all the concrete samples prepared irrespective of the water used. This
holds good for both 28 days and 2.5 years duration. But the required
compressive strength of the concrete i.e 20MPa is not obtained due to the
chemical attack. The chemical attack weakens the bond strength of the
concrete. As a result, the concrete gets disintegrated and it is observed from
the loss of weight.
The compressive strength of the concrete prepared using potable
water is 17.74MPa after 28 days and 20.63MPa after 2.5 years, the
compressive strength of the concrete prepared using untreated tannery effluent
is 18.46MPa after 28 days and 21.35MPa after 2.5 years and the compressive
strength of the concrete prepared using treated tannery effluent is 18.12MPa
after 28 days and 21.01MPa after 2.5 years. The compressive strength of the
concrete specimen prepared using untreated textile effluent is 18.23MPa after
28 days and 21.12MPa after 2.5 years and the compressive strength of the
concrete prepared using treated textile effluent is 17.89MPa after 28 days and
20.78MPa after 2.5 years.
By the addition of 5% fly ash and concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent), the compressive strength of
the concrete specimen increases by 3.08%, 2.96%, 3.01%, 2.99% and 3.05%
prepared using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents respectively after 28 days. Almost the
99
same trend is observed after 2.5 years also. It is observed from the
experimental results that the compressive strength of the concrete specimens
cast using untreated and treated tannery effluents, untreated and treated textile
effluents is almost equal to the compressive strength of the concrete specimen
cast using potable water.
The compressive strength of the concrete prepared using potable
water is 17.83MPa after 28 days and 20.72MPa after 2.5 years, the
compressive strength of the concrete prepared using untreated tannery effluent
is 18.55MPa after 28 days and 21.44MPa after 2.5 years and the compressive
strength of the concrete prepared using treated tannery effluent is 18.21MPa
after 28 days and 21.10MPa after 2.5 years. The compressive strength of the
concrete prepared using untreated textile effluent is 18.32MPa after 28 days
and 21.21MPa after 2.5 years and the compressive strength of the concrete
prepared using treated textile effluent is 17.98MPa after 28 days and
20.87MPa after 2.5 years.
By the addition of 5% fly ash and 2% calcium nitrate, the
compressive strength of the concrete increases by 3.60%, 3.46%, 3.52%,
3.50% and 3.57% using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents respectively after 28 days. Almost the
same trend is observed after 2.5 years also. It is observed from the
experimental results that the compressive strength of the concrete specimen
prepared using tannery and textile effluents is almost equal to the compressive
strength of the concrete specimen cast using potable water.
100
17
18
19
20
21
22
0 200 400 600 800 1000
Age of concrete (days)
Com
pres
sive
stre
ngth
(MPa
) PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.20 Comparison of compressive strength of the concrete due to
chemical attack on the concrete prepared using potable
water, untreated and treated tannery effluents
17
18
19
20
21
22
0 200 400 600 800 1000
Age of concrete (days)
Com
pres
sive
stre
ngth
(MPa
) PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.21 Comparison of compressive strength of the concrete due to
chemical attack on the concrete prepared using potable
water, untreated and treated textile effluents
101
By the addition of 5% fly ash and concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent) or 5% fly ash and 2%
calcium nitrate with the concrete, the reduction in loss of weight of the
concrete and increase in the compressive strength of the concrete is due to the
fact that the pH values of the concrete were improved and the alkalinity of the
concrete also got improved. It is concluded that there is no effect in terms of
loss of weight of the concrete and reduction in the compressive strength of the
concrete due to chemical attack on the concrete prepared using tannery and
textile effluents.
3.3.5 Studies on the Alkali Aggregate Reaction on the Concrete
Alkali aggregate reaction of the concrete is the reaction between
certain silicious constituents in the aggregate and the alkali sodium and
potassium hydroxide which are released during the hydration of cement. A
gelatinous product is formed which imbibes pore fluid and in doing so, the
concrete gets expanded, inducing an internal stress within the concrete. It is
observed that many failures of concrete structures such as pavement,
abutments, sea structures etc., are due to the alkali aggregate reaction (Rui
Miguel Ferreira 2004). The reaction may be due to availability of moisture,
salts present in water and alkali content in cement or aggregate etc.
The expansion of the mortar bars cast using potable water is 0.00%
after 28 days, 0.38% after 180 days, 0.46% after 1 year, 0.52% after 2 years
and 0.52% after 2.5 years, the expansion of the mortar bars cast using
untreated tannery water is about 0.00% after 28 days, 0.41% after 180 days,
0.50% after 1 year, 0.54% after 2 years and 0.54% after 2.5 years and the
102
expansion of the mortar bars cast using treated tannery water is about 0.00%
after 28 days, 0.40% after 180 days, 0.46% after 1 year, 0.53% after 2 years
and 0.54% after 2.5 years. The expansion of the mortar bars cast using
untreated textile water is about 0.00% after 28 days, 0.40% after 180 days,
0.49% after 1 years, 0.53% after 2 years and 0.53% after 2.5 years and the
expansion of the mortar bars cast using treated textile water is about 0.00%
after 28 days, 0.39% after 180 days, 0.47% after 1 year, 0.52% after 2 years
and 0.52% after 2.5 years. The effects are graphically represented in
Figures 3.22 and 3.23.
There is no expansion of the concrete due to alkali aggregate reaction after 28 days for all types of the water. There is 36.84 %, 31.71 %, 35.00 %, 32.50 % and 33.33 % increase in expansion of the mortar bar due to alkali aggregate reaction between 180 days and 2.5 years using potable water, untreated and treated tannery effluents, untreated and treated textile effluents respectively. There is 7.89 % and 5.26 % higher expansion in the concrete prepared using untreated and treated tannery effluents than that of the potable water. There is 5.26 % and 2.63 % higher expansion in the concrete prepared using untreated and treated textile effluents than that of the potable water. As far as the alkali aggregate reaction of the concrete is considered, there is no significant difference among the concrete specimens cast using potable water, untreated and treated tannery effluents, untreated and treated textile effluents. Even when the admixtures such as 5% fly ash and concare (2.5% concare is added with the concrete prepared using tannery effluent and 2.0% concare is added with the concrete prepared using textile effluent) or 5% fly ash and 2% calcium nitrate are added with the concrete, there is no significant reduction in expansion of the concrete specimens prepared using potable water or tannery and textile effluents (Figures 3.22 and 3.23) and hence it is not discussed in detail.
103
0
0.1
0.2
0.3
0.4
0.5
0.6
0 200 400 600 800 1000
Age of concrete (days)
Expa
nsio
n (%
)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.22 Comparison of expansion of mortar bar due to alkali
aggregate reaction of the concrete prepared using potable
water, untreated and treated tannery effluents
0
0.1
0.2
0.3
0.4
0.5
0.6
0 200 400 600 800 1000
Age of concrete (days)
Expa
nsio
n (%
)
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.23 Comparison of expansion of mortar bar due to alkali
aggregate reaction of the concrete prepared using potable
water, untreated and treated textile effluents
104
3.3.6 Studies on the Leachability of Sulphate from the Concrete
The leachability of the sulphate from the concrete is an important property for safeguarding the environment. When there is any rain after the construction or any water flow on the concrete, there may be a possibility of leaching out of the sulphate ions from the concrete. The sulphate present in the water immersed with the concrete samples made using potable, untreated and treated tannery effluents, untreated and treated textile effluents are 187mg/l after 28 days and 150.26mg/l after 2.5 years, 199.45mg/l after 28 days and 179.15mg/l after 2.5 years, 190.16mg/l after 28 days and 168.30mg/l after 2.5 years, 196.05mg/l after 28 days and 175.33mg/l after 2.5 years and 189.76mg/l after 28 days and 164.48mg/l after 2.5 years respectively (Figures 3.24 and 3.25). The sulphate present in the water immersed with the concrete samples made using untreated and treated tannery effluents, untreated and treated textile effluents are 6.66%, 1.69%, 4.84% and 1.48% respectively which are higher than that of the concrete made using potable water. This is due to the excess sulphate content present in the various effluents. When 5% fly ash and concare (2.5% concare is added with the concrete prepared using tannery effluent and 2.0% concare is added with the concrete prepared using textile effluent) are added with the concrete, the sulphate present in the water immersed with concrete samples made using potable, untreated and treated tannery effluents, untreated and treated textile effluents are 171.58mg/l after 28 days and 142.40mg/l after 2.5 years, 179.81mg/l after 28 days and 158.25mg/l after 2.5 years, 174.26mg/l after 28 days and 154.58mg/l after 2.5 years, 176.41mg/l after 28 days and 154.43mg/l after 2.5 years and 172.86mg/l after 28 days and 153.76mg/l after 2.5 years respectively.
105
By the addition of 5% fly ash and concare (2.5% concare is added with the concrete prepared using tannery effluent and 2.0% concare is added with the concrete prepared using textile effluent), the sulphate present in the water immersed with concrete samples made using potable water, untreated and treated tannery effluents, untreated and treated textile effluents are reduced by 8.99%, 10.92%, 9.12%, 11.13% and 9.78% respectively after 28 days. The sulphate present in the water immersed with concrete samples made using potable water, untreated tannery effluent, treated tannery effluent, untreated textile effluent and treated textile effluent are reduced by 5.52%, 13.21%, 8.88%, 13.53% and 6.97% respectively after 2.5 years. There is more amount of sulphate ion reduction in 2.5 years duration than that of 28 days. When 5% fly ash and 2% calcium nitrate are added with the concrete, the sulphate present in the water immersed with concrete samples made using potable, untreated and treated tannery effluents, untreated and treated textile effluents are 170.25mg/l after 28 days and 141.92mg/l after 2.5 years, 179.14mg/l after 28 days and 157.12mg/l after 2.5 years, 173.16mg/l after 28 days and 153.88mg/l after 2.5 years, 175.74mg/l after 28 days and 153.30mg/l after 2.5 years and 172.76mg/l after 28 days and 152.06mg/l after 2.5 years respectively. By the addition of 5% fly ash and 2.0% calcium nitrate, the sulphate present in the water immersed with concrete samples made using potable water, untreated and treated tannery effluents, untreated and treated textile effluents are reduced by 9.84%, 11.34%, 9.82%, 11.56% and 9.84% respectively after 28 days. The sulphate present in the water immersed with concrete samples made using potable water, untreated tannery effluent, treated tannery effluent, untreated textile effluent and treated textile effluent are reduced by 5.88%, 14.02%, 9.37%, 14.37% and 8.17% respectively after 2.5 years. There is more sulphate reduction after 2.5 years than after 28 days of testing which are graphically shown in Figures 3.24 and 3.25.
106
140
150
160
170
180
190
200
0 200 400 600 800 1000
Age of concrete (days)
Leac
habi
lity
(mg/
l) PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.24 Comparison of leachability of the sulphate from the
concrete prepared using potable water, untreated and
treated tannery effluents
140
150
160
170
180
190
200
0 200 400 600 800 1000
Age of concrete (days)
Leac
habi
lity
(mg/
l) PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.25 Comparison of leachability of the sulphate from the
concrete prepared using potable water, untreated and
treated textile effluents
107
The reduction in sulphate content is due to the modification of pore
structure of the concrete. The sulphate content decreases after 2.5 years due to
the hardening property of the concrete. The concrete becomes impermeable
with duration of time. It is observed from the experimental results that there is
considerable reduction in sulphate content by the addition of 5% fly ash and
concare (2.5% concare is added with the concrete prepared using tannery
effluent and 2.0% concare is added with the concrete prepared using textile
effluent) with the concrete or 5% fly ash and 2% calcium nitrate with the
concrete.
3.3.7 Studies on the Leachability of Chloride from the Concrete
The leachability of chloride from the concrete is an important
property for safe guarding the surrounding environment. When there is rain
after construction or any water flow over the concrete, there may be a
possibility of leaching of chloride particles from the concrete.
The chloride present in the water immersed with the concrete
samples made using potable, untreated and treated tannery effluents, untreated
and treated textile effluents are 82.34mg/l after 28 days and 75.24mg/l after
2.5 years, 101.14mg/l after 28 days and 97.10mg/l after 2.5 years, 91.28mg/l
after 28 days and 87.54mg/l after 2.5 years, 97.74mg/l after 28 days and
93.28mg/l after 2.5 years and 87.88mg/l after 28 days and 83.72mg/l after 2.5
years respectively.
The chloride content present in the water immersed with the
concrete samples made using untreated and treated tannery effluents,
untreated and treated textile effluents are 22.83%, 10.86%, 18.70% and 6.73%
respectively higher than that of the concrete made using potable water which
108
are graphically represented in Figures 3.26 and 3.27. This is due to the excess
chloride content present in the various effluents.
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) are added with the concrete, the
chloride present in the water immersed with concrete samples made using
potable, untreated and treated tannery effluents, untreated and treated textile
effluents are 78.84mg/l after 28 days and 70.22mg/l after 2.5 years,
101.14mg/l after 28 days and 97.10mg/l after 2.5 years, 87.42mg/l after 28
days and 83.68mg/l after 2.5 years, 93.00mg/l after 28 days and 88.28mg/l
after 2.5 years and 84.02mg/l after 28 days and 79.86mg/l after 2.5 years
respectively.
By the addition of 5% fly ash and concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent), the chloride present in the
water immersed with concrete samples made using potable water, untreated
and treated tannery effluents, untreated and treated textile effluents are
reduced by 4.44%, 4.92%, 4.42%, 5.10% and 4.59% respectively after 28
days. The chloride present in the water immersed with the concrete samples
made using potable water, untreated and treated tannery effluent, untreated
and treated textile effluent are reduced by 7.15%, 5.43%, 4.61%, 5.66% and
4.83%respectively after 2.5 years. There is more chloride reduction in 2.5
years than that of 28 days.
When 5% fly ash and 2% calcium nitrate are added with the
concrete, the chloride present in the water immersed with concrete samples
made using potable, untreated and treated tannery effluents, untreated and
109
treated textile effluents are 76.20mg/l after 28 days and 68.64mg/l after 2.5
years, 95.36mg/l after 28 days and 92.22mg/l after 2.5 years, 86.32mg/l after
28 days and 81.90mg/l after 2.5 years, 91.96mg/l after 28 days and 88.40mg/l
after 2.5 years and 82.92mg/l after 28 days and 78.08mg/l after 2.5 years
respectively.
By the addition of 5% fly ash and 2% calcium nitrate, the chloride
present in the water immersed with concrete samples made using potable
water, untreated and treated tannery effluents, untreated and treated textile
effluents are reduced by 8.06%, 6.06%, 5.75%, 6.29% and 5.98% respectively
after 28 days. The chloride present in the water immersed with concrete
samples made using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents are reduced by 9.62%, 5.29%, 6.89%,
5.52% and 7.22% respectively after 2.5 years. There is more chloride
reduction after 2.5 years than 28 days.
50
60
70
80
90
100
110
0 200 400 600 800 1000
Age of concrete (days)
Leac
habi
lity
(mg/
l) PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.26 Comparison of leachability of the chloride from the concrete
prepared using potable water, untreated and treated
tannery effluents
110
50
60
70
80
90
100
110
0 200 400 600 800 1000
Age of concrete (days)
Leac
habi
lity
(mg/
l) PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.27 Comparison of leachability of the chloride from the concrete
prepared using potable water, untreated and treated textile
effluents
The reduction in chloride content is due to the modification of pore
structure of the concrete. The chloride content decreases after 2.5 years due to
the hardening property of the concrete. The concrete becomes impermeable
with increase in the age of the concrete. It is observed from the experimental
results that there is considerable reduction in chloride content by the addition
of 5% fly ash and concare (2.5% concare is added with the concrete prepared
using tannery effluent and 2.0% concare is added with the concrete prepared
using textile effluent) with the concrete or 5% fly ash and 2% calcium nitrate
with the concrete.
3.3.8 Studies on the Permeability of the Concrete
Permeability of concrete is the property by which water can
penetrate into the pores of the concrete. The penetration of weathering agents
111
along with the water into the concrete may lead to corrosion of reinforcement
bar embedded in the concrete which in turn weakens the structures. The
penetration of materials along with the solution adversely affects the
durability aspects of the concrete. The factors affecting the permeability of the
concrete are formation of micro cracks in the transition zones, cracks
generated through higher structural stresses, cracks formed due to corrosion
of the reinforcement bar embedded in the concrete, atmospheric moisture,
quality and purity of water used for making concrete etc. The permeability of
the concrete usually determines the rate of deterioration of the concrete
(Ganesh et al 2007).
The permeability of the concrete prepared using potable water is
7.70 x 10-7 cm/sec after 28 days and 5.40 x 10-7 cm/sec after 2.5 years, the
permeability of the concrete prepared using untreated tannery effluent is 7.80
x 10-7 cm/sec after 28 days and 6.00 x 10-7 cm/sec after 2.5 years and the
permeability of the concrete prepared using treated tannery effluent is 7.70 x
10-7 cm/sec after 28 days and 5.90 x 10-7 cm/sec after 2.5 years. The
permeability of the concrete prepared using untreated textile effluent is 7.70 x
10-7 cm/sec after 28 days and 5.90 x 10-7 cm/sec after 2.5 years and the
permeability of concrete prepared using treated textile effluent is 7.60 x 10-7
cm/sec after 28 days and 5.80 x 10-7 cm/sec after 2.5 years. The effects of the
permeability of the concrete prepared using different waters with the addition
of various admixtures are graphically shown in Figures 3.28 and 3.29.
The permeability of the concrete prepared using untreated and
treated tannery effluents, untreated and treated textile effluents is 1.30 %, 0.00
%, 0.00 % and 0.00 % higher than that of the concrete prepared using potable
water after 28 days of testing. The permeability of the concrete prepared using
untreated tannery effluent and untreated textile effluent is 1.30 % and 1.32 %
112
higher than that of the concrete prepared using treated tannery and treated
textile effluent after 28 days of curing. The permeability of the concrete
significantly decreases with the increase in age of the concrete. The
permeability of the concrete prepared using potable water, untreated and
treated tannery effluents, untreated and treated textile effluents decreases by
42.59 %, 30.00 %, 30.51 %, 30.51 % and 31.03 % after 2.5 years. This is
because of the hardening of the concrete due to increase in the age of the
concrete.
From the discussion, it is clear that the permeability of the concrete
goes on decreasing with increase in age of the concrete (El-Dieb 2006). This
phenomenon is common for all the concrete specimens cast using any type of
water such as potable water, untreated and treated tannery effluents, untreated
and treated textile effluents.
By the addition of 5% fly ash and concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent) admixture, the permeability
of the concrete prepared using potable water is 7.50 x 10-7 cm/sec after 28
days and 5.00 x 10-7 cm/sec after 2.5 years, the permeability of the concrete
prepared using untreated tannery effluent is 7.60 x 10-7 cm/sec after 28 days
and 5.60 x 10-7 cm/sec after 2.5 years and the permeability of the concrete
prepared using treated tannery effluent is 7.50 x 10-7 cm/sec after 28 days and
5.50 x 10-7 cm/sec after 2.5 years. The permeability of the concrete prepared
using untreated textile effluent is 7.50 x 10-7 cm/sec after 28 days and 5.50 x
10-7 cm/sec after 2.5 years and the permeability of the concrete prepared using
treated textile effluent is 7.40 x 10-7 cm/sec after 28 days and 5.40 x 10-7
cm/sec after 2.5 years.
113
Due to the addition of 5% fly ash and concare (2.5% concare is
added with the concrete prepared using tannery effluent and 2.0% concare is
added with the concrete prepared using textile effluent), there is 2.67 %
decrease in permeability of the concrete specimen cast using potable water,
2.63 % decrease in permeability of the concrete prepared using untreated
tannery effluent and 2.67 % decrease in permeability of the concrete prepared
using treated tannery effluent after 28 days of testing. The decrease in the
permeability of the concrete is 8.00 %, 7.14 % and 7.27 % for potable water,
untreated tannery effluent and treated tannery effluent after 2.5 years. For the
remaining test duration of 180 days, 1 year and 2 years, the permeability of
the concrete goes on decreasing gradually. There is 2.63 % to 8.00 % decrease
in the permeability of the concrete due to the addition of fly ash and concare
admixture (Dinakar et al 2008). There is 2.70 % decrease in the permeability
of the concrete specimen prepared using potable water, 2.67 % decrease in the
permeability of the concrete prepared using untreated textile effluent and 2.70
% decrease in the permeability of the concrete prepared using treated textile
effluent after 28 days of curing. The decrease in the permeability of the
concrete is 8.16 %, 7.27 % and 7.41 % for potable water, untreated textile
effluent and treated textile effluent after 2.5 years. There is 2.63 % to 8.16 %
decrease in the permeability of the concrete due to addition of fly ash and
concare admixture for the concrete prepared using untreated and treated
tannery effluents, untreated and treated textile effluents. This is because of the
addition of the admixtures (fly ash and concare) which modify the pore
structure of the concrete (Khatri et al 1997).
When 5% fly ash and 2% calcium nitrate are added, the
permeability of the concrete prepared using potable water is 7.40 x 10-7
cm/sec after 28 days and 4.90 x 10-7 cm/sec after 2.5 years, the permeability
of the concrete prepared using untreated tannery effluent is 7.50 x 10-7 cm/sec
114
after 28 days and 5.50 x 10-7 cm/sec after 2.5 years and the permeability of the
concrete prepared using treated tannery effluent is 7.40 x 10-7 cm/sec after 28
days and 5.40 x 10-7 cm/sec after 2.5 years. The permeability of the concrete
prepared using untreated textile effluent is 7.40 x 10-7 cm/sec after 28 days
and 5.40 x 10-7 cm/sec after 2.5 years and the permeability of the concrete
prepared using treated textile effluent is 7.30 x 10-7 cm/sec after 28 days and
5.30 x 10-7 cm/sec after 2.5 years.
By the addition of 5% fly ash and 2% calcium nitrate admixture,
there is 4.05 % decrease in the permeability of the concrete specimen cast
using potable water, 4.00 % decrease in the permeability of the concrete
specimen cast using untreated tannery effluent and 4.05 % decrease in the
permeability of the concrete specimen cast using treated tannery effluent after
28 days of testing. The decrease in the permeability of the concrete is 10.20
%, 9.09 % and 9.26 % for potable water, untreated tannery effluent and
treated tannery effluent after 2.5 years. There is 4.00 % to 10.20 % decrease
in the permeability of the concrete due to addition of 5% fly ash and 2%
calcium nitrate. There is 4.11 % decrease in the permeability of the concrete
specimen cast using potable water, 4.05 % decrease in the permeability of the
concrete cast using untreated textile effluent and 4.11 % decrease in the
permeability of the concrete prepared using treated textile effluent after 28
days of testing. The decrease in the permeability of the concrete is 10.42 %,
9.26 % and 9.43 % for potable water, untreated textile effluent and treated
textile effluent after 2.5 years. There is 4.05 % to 10.42 % decrease in the
permeability of the concrete due to addition of 5% fly ash and 2% calcium
nitrate admixture at the early days of testing.
115
4.5
5
5.5
6
6.5
7
7.5
8
0 200 400 600 800 1000
Age of concrete (days)
Co-e
ff o
f per
m. (
10-7
cm
/sec
) PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.28 Comparison of the permeability of the concrete prepared
using potable water, untreated and treated tannery effluents
4.5
5
5.5
6
6.5
7
7.5
8
0 200 400 600 800 1000
Age of concrete (days)
Co-e
ff o
f per
m. (
10-7
cm
/sec
) PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.29 Comparison of the permeability of the concrete prepared
using potable water, untreated and treated textile effluents
116
The Figure 3.30 show the permeability test in progress
Figure 3.30 Permeability test in progress
It is observed that the permeability of the concrete is reduced by the
addition of the admixture (Ghosh et al 2002 a). This is because the admixture
reduces the permeability of concrete due to its fineness and formation of
C-S-H gel and considerable reduction in the volume of the large pores of
concrete. Another fact is that with the addition of admixture, the water cement
ratio also gets reduced considerably. The reduction in the permeability of the
concrete is because of the better interlocking of bond among the coarse
aggregate, fine aggregate and cement paste (Malathy 2004). It is because of
the better interlocking of the bond among the coarse aggregate, fine aggregate
and cement paste, the other properties of the concrete such as compressive
strength, tensile strength, bond strength of the concrete etc are improved. In
addition, the pozzolanic reaction and pore size refinement mechanisms due to
117
the addition of the admixture are responsible for decrease in the permeability
of the concrete (Ha Won Song and Seung Jun Kwon 2007). It can be
concluded that the permeability is not a constraining factor for preparing the
concrete, blended with fly ash either with concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent) or 2% calcium nitrate
admixture, prepared using the tannery and textile effluents.
3.3.9 Studies on the Compressive Strength of the Concrete
The compressive strength of the hardened cement is the most
important of all the properties of the concrete. It is used as a qualitative
measure for other properties of the hardened concrete. Almost in all structural
applications the concrete is employed primarily to resist the compressive
stresses.
The compressive strength of the concrete prepared using potable
water is 23.91MPa after 28 days and 26.84MPa after 2.5 years, the
compressive strength of the concrete prepared using untreated tannery effluent
is 24.71MPa after 28 days and 27.56MPa after 2.5 years and the compressive
strength of the concrete prepared using treated tannery effluent is 24.36MPa
after 28 days and 27.29MPa after 2.5 years. The compressive strength of the
concrete prepared using untreated textile effluent is 24.48MPa after 28 days
and 27.33MPa after 2.5 years and the compressive strength of the concrete
prepared using treated textile effluent is 24.13MPa after 28 days and
27.06MPa after 2.5 years.
The compressive strength of the concrete prepared using untreated
and treated tannery effluents, untreated and treated textile effluents is 3.34 %,
118
1.88%, 2.38 % and 0.92 % respectively higher than that of the concrete
prepared using potable water after 28 days of testing because of the chemicals
and salts present in the untreated and treated tannery effluents, untreated and
treated textile effluents (Saricimen et al 2004). The compressive strength of
the concrete samples prepared using untreated tannery and untreated textile
effluent is 1.44 % and 1.45 % higher than that of the concrete samples
prepared using treated tannery effluent and treated treated textile effluent after
28 days of testing which are shown graphically in the Figures 3.31 and 3.32.
The increase in the compressive strength of the concrete between 28 days and
1 year prepared using potable water, untreated and treated tannery effluents,
untreated and treated textile effluents is 9.66 %, 11.17 %, 11.29 %, 9.07 %
and 9.57 % respectively. The increase in the compressive strength of the
concrete between 1 year and 2.5 years prepared using potable water, untreated
and treated tannery effluents, untreated and treated textile effluents is 2.36 %,
2.34 %, 2.32 %, 2.36 % and 2.34 % respectively. The compressive strength of
the concrete increases in the range of 9.07 % to 11.29 % up to one year and
there after the increment in the compressive strength of the concrete becomes
negligible (approximately 2.36 %).
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) are added with the concrete, the
compressive strength of the concrete prepared using potable water is
25.24MPa after 28 days and 28.18MPa after 2.5 years, the compressive
strength of the concrete prepared using untreated tannery effluent is
25.96MPa after 28 days and 28.89MPa after 2.5 years, the compressive
strength of the concrete prepared using treated tannery effluent is 25.69MPa
after 28 days and it is 28.53MPa after 2.5 years. The compressive strength of
the concrete prepared using untreated textile effluent is 25.73MPa after 28
days and 28.66MPa after 2.5 years, the compressive strength of the concrete
119
prepared using treated textile effluent is 25.46MPa after 28 days and it is
28.30MPa after 2.5 years.
With the addition of 5% fly ash and concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent) there is 5.56 % increase in
the compressive strength of the concrete prepared using potable water, 5.05 %
increase in the compressive strength of the concrete prepared using untreated
tannery effluent and 5.46 % increase in the compressive strength of the
concrete prepared using treated tannery effluent after 28 days of testing
(Krishnaswami et al 2007). The increase in the compressive strength of the
concrete is 4.99 %, 4.82 % and 4.54 % for potable water, untreated and
treated tannery effluent after 2.5 years respectively. For the remaining test
duration of 180 days, 1 year and 2 years, the compressive strength of the
concrete is increasing gradually (Figures 3.31 and 3.32). There is 4.54 % to
5.56 % increase in the compressive strength of the concrete due to the
addition of 5% fly ash and concare admixture (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent).
There is 4.97 % increase in the compressive strength of the
concrete prepared using potable water, 5.10 % increase in the compressive
strength of the concrete prepared using untreated textile effluent and 5.51 %
increase in the compressive strength of the concrete prepared using treated
textile effluent after 28 days of testing. The increase in the compressive
strength of the concrete is 4.13 %, 4.86 % and 4.58 % for potable water,
untreated and treated textile effluents after 2.5 years respectively. For the
remaining test duration of 180 days, 1 year and 2 years, the compressive
strength of the concrete is increasing gradually. The reason for the increase in
the compressive strength of the concrete due to the addition admixture is that
the cement particles inside the concrete are packed closer and denser than
120
earlier. Due to the reaction between fly ash and concare with the calcium
hydroxide present in the concrete more gel is formed which ultimately
produces C-S-H gel (Malathy 2004). The added admixture (fly ash and
concare) sometimes also acts as the filler material inside the concrete and
increases the compressive strength of the concrete (Oner and Akyuz 2007).
There is 4.97% to 5.51% increase in the compressive strength of the concrete
due to the addition of 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) admixture for untreated and treated
tannery effluents, untreated and treated textile effluents (Eshmaiel Ganjian
and Homayoon Sadeghi Pouya 2005).
When 5% fly ash and 2% calcium nitrate are added with the
concrete, the compressive strength of the concrete prepared using potable
water is 25.69MPa after 28 days and 28.53MPa after 2.5 years, the
compressive strength of the concrete prepared using untreated tannery effluent
is 26.40MPa after 28 days and 29.33MPa after 2.5 years, the compressive
strength of the concrete prepared using treated tannery effluent is 26.04MPa
after 28 days and 28.98MPa after 2.5 years. The compressive strength of the
concrete prepared using untreated textile effluent is 26.17MPa after 28 days
and 29.10MPa after 2.5 years, the compressive strength of the concrete
prepared using treated textile effluent is 25.81MPa after 28 days and
28.75MPa after 2.5 years.
By the addition of 5% fly ash and 2% calcium nitrate with the
concrete, there is 7.44 % increase in the compressive strength of the concrete
prepared using potable water, 6.83 % increase in the compressive strength of
the concrete prepared using untreated tannery effluent and 6.89 % increase in
the compressive strength of the concrete prepared using treated tannery
121
effluent after 28 days of testing (Aggoun et al 2008). The increase in the
compressive strength of the concrete is 6.29 %, 6.42 % and 6.19 % for potable
water, untreated and treated tannery effluent after 2.5 years respectively. For
the remaining test duration of 180 days, 1 year and 2 years, the compressive
strength of the concrete is increasing gradually as shown graphically in the
Figures 3.31 and 3.32. There is 6.19 % to 7.44 % increase in the compressive
strength of the concrete due to the addition of 5% fly ash and 2% calcium
nitrate.
There is 6.48 % increase in the compressive strength of the
concrete prepared using potable water, 6.90 % increase in the compressive
strength of the concrete prepared using untreated textile effluent and 6.96 %
increase in the compressive strength of the concrete prepared using treated
textile effluent after 28 days of testing. The increase in the compressive
strength of the concrete is 5.43 %, 6.47 % and 6.24 % for potable water,
untreated and treated textile effluent after 2.5 years respectively. For the
remaining test duration of 180 days, 1 year and 2 years, the compressive
strength of the concrete is increasing gradually. It is observed that the
compressive strength of the concrete rapidly increases up to a period of 1 year
and later on the increase in the compressive strength of the concrete is
reduced. There is 6.45 % to 6.96 % increase in the compressive strength of
the concrete due to the addition of 5% fly ash and 2% calcium nitrate
admixture at the early days of testing (Krishnaswami et al 2007). The increase
in the compressive strength of the concrete due to the addition of admixture is
because of the hardening of the internal structure of the concrete and
reduction in permeability of the concrete (Ismail Yurtdas et al 2006).
122
22
24
26
28
30
0 200 400 600 800 1000
Age of concrete (days)
Com
pres
sive
stre
ngth
(MPa
)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.31 Comparison of compressive strength of the concrete
prepared using potable water, untreated and treated
tannery effluents
23
24
25
26
27
28
29
30
0 200 400 600 800 1000
Age of concrete (days)
Com
pres
sive
stre
ngth
(MPa
) PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.32 Comparison of compressive strength of the concrete
prepared using potable water, untreated and treated textile
effluents
123
The Figure 3.33 shows the compressive strength test in progress.
Figure 3.33 Compressive strength test in progress
It is observed that the compressive strength of the concrete blended
with 5% fly ash and 2% calcium nitrate admixture is more than that of the
concrete blended with 5% fly ash and concare admixture (2.5% concare is
added with the concrete prepared using tannery effluent and 2.0% concare is
added with the concrete prepared using textile effluent). Hence it is concluded
that there is no major adverse effect on the compressive strength of the
concrete prepared using tannery and textile effluents.
3.3.10 Studies on the Tensile Strength of the Concrete
Tensile strength of the concrete is one of the basic and important
properties of the concrete. The knowledge of the tensile strength of the
concrete is required for the design of the concrete structural elements subject
to transverse shear, torsion, shrinkage and temperature. This is an indirect test
124
to determine the tensile strength of the concrete cylindrical specimens. In
reinforced concrete members, considerable importance is placed on the tensile
strength of the concrete since steel reinforcement bars embedded in the
concrete are provided to resist all the tensile forces. The tensile stresses may
develop in the concrete due to drying shrinkage, rusting of steel reinforcement
bar embedded in the concrete, temperature changes etc., and hence the
knowledge of tensile strength of the concrete is very essential to ensure the
safety of the structure.
The tensile strength of the concrete prepared using potable water is
2.23MPa after 28 days and 2.40MPa after 2.5 years, the tensile strength of the
concrete prepared using untreated tannery effluent is 2.26MPa after 28 days
and 2.45MPa after 2.5 years and the tensile strength of the concrete prepared
using treated tannery effluent is 2.23MPa after 28 days and 2.43MPa after 2.5
years. The tensile strength of the concrete prepared using untreated textile
effluent is 2.26MPa after 28 days and 2.42MPa after 2.5 years and the tensile
strength of the concrete prepared using treated textile effluent is 2.25MPa
after 28 days and 2.41MPa after 2.5 years.
From the Figures 3.34 and 3.35, the tensile strength of the concrete
prepared using untreated and treated tannery effluents, untreated and treated
textile effluents is 1.35 %, 0.45 %, 1.35 % and 0.90 % respectively higher
than that of the concrete prepared using potable water after 28 days of curing.
The tensile strength of the concrete samples prepared using untreated tannery
effluent and untreated textile effluent is 0.89 % and 0.44 % higher than that of
the concrete samples prepared using treated tannery effluent and treated
textile effluent after 28 days of testing. For the remaining test duration of 180
days, 1 year and 2 years, the tensile strength of the concrete is increasing
gradually. As like as that of the compressive strength of the concrete, the
tensile strength of the concrete prepared using untreated tannery effluent and
125
untreated textile effluent is also slightly higher than that of the concrete made
of potable water. The tensile strength of the concrete (ft) varies between
0.68√fck to 0.71√fck, where fck is the compressive strength of the concrete.
The admixtures such as concare and calcium nitrate are added with
the fly ash for enhancing the durability properties of the concrete and the
effect of these admixtures on the tensile strength of the concrete are also
studied and graphically represented in the Figures 3.34 and 3.35.
When 5% fly ash and concare (2.5% concare is added with the
concrete prepared using tannery effluent and 2.0% concare is added with the
concrete prepared using textile effluent) are added with the concrete, the
tensile strength of the concrete prepared using potable water after 28 days is
2.39MPa and 2.64MPa after 2.5 years, the tensile strength of the concrete
prepared using untreated tannery effluent after 28 days is 2.47MPa and
2.71MPa after 2.5 years and the tensile strength of the concrete prepared using
treated tannery effluent after 28 days is 2.42MPa and 2.68MPa after 2.5 years.
The tensile strength of the concrete prepared using untreated textile effluent is
2.43MPa after 28 days and 2.68MPa after 2.5 years and the tensile strength of
the concrete prepared using treated textile effluent is 2.41MPa after 28 days
and 2.66MPa after 2.5 years.
There is 7.17 % increase in the tensile strength of the concrete
specimen cast using potable water, 9.29 % increase in the tensile strength of
the concrete prepared using untreated tannery effluent and 8.04 % increase in
the tensile strength of the concrete prepared using treated tannery effluent
after 28 days of testing. The increase in the tensile strength of the concrete is
10.0 %, 10.61 % and 10.29 % for potable water, untreated tannery effluent
and treated tannery effluent after 2.5 years. For the remaining test duration of
126
180 days, 1 year and 2 years, the tensile strength of the concrete is increasing
gradually. There is 7.17 % to 10.29 % increase in the tensile strength of the
concrete due to the addition of 5% fly ash and concare admixture (2.5%
concare is added with the concrete prepared using tannery effluent and 2.0%
concare is added with the concrete prepared using textile effluent). There is
7.17 % increase in the tensile strength of the concrete prepared using potable
water, 8.0 % increase in the tensile strength of the concrete prepared using
untreated textile effluent and 7.11 % increase in the tensile strength of the
concrete prepared using treated textile effluent after 28 days of testing. The
increase in the tensile strength of the concrete is 10.00 %, 10.74 % and 10.37
% for potable water, untreated textile and treated textile effluent after 2.5
years. For the remaining test duration of 180 days, 1 year and 2 years, the
tensile strength of the concrete is increasing gradually. There is 7.11 % to
10.74 % increase in the tensile strength of the concrete due to the addition of
5% fly ash and concare admixture (2.5% concare is added with the concrete
prepared using tannery effluent and 2.0% concare is added with the concrete
prepared using textile effluent) for untreated and treated tannery effluents,
untreated and treated textile effluents.
When 5% fly ash and 2% calcium nitrate are added, the tensile
strength of the concrete prepared using potable water is 2.39MPa after 28 days
and 2.64MPa after 2.5 years, the tensile strength of the concrete prepared
using untreated tannery effluent is 2.48MPa after 28 days and 2.72MPa after
2.5 years and the tensile strength of the concrete prepared using treated
tannery effluent is 2.43MPa after 28 days and 2.69MPa after 2.5 years. The
tensile strength of the concrete prepared using untreated textile effluent is
2.44MPa after 28 days and 2.69MPa after 2.5 years and the tensile strength of
127
the concrete prepared using treated textile effluent is 2.41MPa after 28 days
and 2.67MPa after 2.5 years.
2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3
0 200 400 600 800 1000
Age of concrete (days)
Tens
ile st
reng
th (M
Pa)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.34 Comparison of tensile strength of the concrete prepared
using potable water, untreated and treated tannery effluents
2
2.2
2.4
2.6
2.8
3
0 200 400 600 800 1000
Age of concrete (days)
Tens
ile st
reng
th (M
Pa)
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.35 Comparison of tensile strength of the concrete prepared
using potable water, untreated and treated textile effluents
128
By the addition of 5% fly ash and 2% calcium nitrate admixture,
there is 7.17 % increase in the tensile strength of the concrete prepared using
potable water, 9.73 % increase in the tensile strength of the concrete prepared
using untreated tannery effluent and 8.48 % increase in the tensile strength of
the concrete prepared using treated tannery effluent after 28 days of testing.
The increase in the tensile strength of the concrete is 10.00 %, 11.02 % and
10.70 % for potable water, untreated tannery effluent and treated tannery
effluent after 2.5 years. For the remaining test duration of 180 days, 1 year
and 2 years, the tensile strength of the concrete is increasing gradually. There
is 7.17 % to 11.02 % increase in the tensile strength of the concrete due to
addition of 5% fly ash and 2% calcium nitrate. There is 4.48 % increase in the
tensile strength of the concrete prepared using potable water, 7.96 % increase
in the tensile strength of the concrete prepared using untreated textile effluent
and 7.11 % increase in the tensile strength of the concrete prepared using
treated textile effluent after 28 days of testing. The increase in the tensile
strength of the concrete is 8.75 %, 11.16 % and 10.79 % for potable water,
untreated textile effluent and treated textile effluent after 2.5 years. For the
remaining test duration of 180 days, 1 year and 2 years, the tensile strength of
the concrete is increasing gradually. There is 4.48 % to 11.16 % increase in
tensile strength of the concrete due to the addition of 5% fly ash and 2%
calcium nitrate admixture at the early days of testing.
The Figure 3.36 shows the tensile strength test in progress.
129
Figure 3.36 Tensile strength test in progress
By the addition of 5% fly ash with either concare (2.5% concare is
added with the concrete prepared using tannery effluent and 2.0% concare is
added with the concrete prepared using textile effluent) or 2% calcium nitrate,
there is slight increment in the tensile strength of the concrete. It is concluded
that there is no significant effect in replacing potable water with tannery and
textile effluents on the tensile strength of the concrete.
3.3.11 Studies on the Flexural Strength of the Concrete for Plain
Cement Concrete Beams
It is a well known fact that concrete is relatively strong in
compression and weak in tension.
The flexural strength of the concrete prepared using potable water
is 3.25MPa after 28 days and 3.75MPa after 2.5 years, the flexural strength of
130
the concrete prepared using untreated tannery effluent is 3.50MPa after 28
days and 3.75MPa after 2.5 years and the flexural strength of concrete
prepared using treated tannery effluent is 3.25MPa after 28 days and 3.75MPa
after 2.5 years as depicted in Figure 3.37. The flexural strength of the concrete
prepared using untreated textile effluent is 3.50MPa after 28 days and
3.75MPa after 2.5 years and the flexural strength of the concrete prepared
using treated textile effluent is 3.25MPa after 28 days and 3.75MPa after 2.5
years as shown in Figure 3.38.
It is evident from the Figures 3.37 and 3.38, the flexural strength of
the concrete beams prepared using untreated and treated tannery effluents,
untreated and treated textile effluents is 7.69 %, 0 %, 7.69 % and 0 %
respectively higher than that of the concrete prepared using potable water. At
the end of 2.5 years the flexural strength of the concrete is almost same for the
concrete made of potable water, untreated and treated tannery effluents,
untreated and treated textile effluents. For the remaining test duration of 180
days, 1 year and 2 years, the flexural strength of the concrete is increasing
gradually and almost equal for all the concrete specimens prepared using
potable water, untreated and treated tannery effluents, untreated and treated
textile effluents. As like as the compressive strength of the concrete, the
flexural strength of the concrete cast using untreated tannery effluent and
untreated textile effluent is also slightly higher than that of the concrete made
of potable water. The flexural strength of the concrete (fs) varies between
0.40√fck to 0.42√fck, where fck is the compressive strength of the concrete.
Since there is no effect and marginal increase in flexural strength of the
concrete by adding 5% fly ash with either concare (2.5% concare is added
with the concrete prepared using tannery effluent and 2.0% concare is added
with the concrete prepared using textile effluent) or 2% calcium nitrate, it is
not discussed in detail (Figures 3.37 and 3.38). It is concluded that the
flexural strength of the concrete is almost same for all the concrete samples
131
prepared using potable water, tannery and textile effluents with and without
the addition of the admixtures.
3
3.25
3.5
3.75
4
4.25
0 200 400 600 800 1000
Age of concrete (days)
Flex
ural
stre
ngth
(MPa
)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.37 Comparison of flexural strength of plain cement concrete
beams prepared using potable water, untreated and treated
tannery effluents
3
3.25
3.5
3.75
4
0 200 400 600 800 1000
Age of concrete (days)
Flex
ural
stre
ngth
(MPa
)
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.38 Comparison of flexural strength of plain cement concrete
beams prepared using potable water, untreated and treated
textile effluents
132
The Figure 3.39 shows the flexural strength test in progress.
Figure 3.39 Flexural strength test in progress
3.3.12 Studies on the Failure Load of the (RCC) Beam
This is the practical and typical field condition and the knowledge
of the failure of the reinforced cement concrete (RCC) beam is essential,
while the potable water is replaced with the tannery and textile effluents.
Since there is considerable effect on reinforcement bar embedded in the
concrete due to induced corrosion, the effect on the reinforced concrete beam
has to be necessarily studied.
The failure load of the RCC beam prepared using potable water is
31.00 KN after 28 days and 33.90 KN after 2.5 years, the failure load of the
RCC beam prepared using untreated tannery effluent is 31.20 KN after 28
days and 34.00 KN after 2.5 years and the failure load of the RCC beam
133
prepared using treated tannery effluent is 31.00 KN after 28 days and 34.00
KN after 2.5 years. The failure load of the RCC beam prepared using
untreated textile effluent is 31.10 KN after 28 days and 34.10 KN after 2.5
years and the failure load of the RCC beam prepared using treated textile
effluent is 31.00 KN after 28 days and 34.00 KN after 2.5 years. The failure
load is almost same for all the RCC beam specimens prepared irrespective of
using various waters as graphically depicted in Figures 3.40 and 3.41.
The failure load of the RCC beam using untreated and treated
tannery effluents, untreated and treated textile effluents is 0.65 %, 0 %, 0.32
% and 0% respectively more than that of the concrete prepared using potable
water. After 2.5 years, the failure load of the RCC beam prepared using
untreated and treated tannery effluents, untreated and treated textile effluents
is 0.29 %, 0.29 %, 0.59 % and 0.29 % respectively more than that of the
concrete prepared using potable water. Approximately there is 7.74 % to 7.05
% increase in the failure load of the RCC beam prepared using potable water
and untreated tannery and textile effluents up to one year, but there-after the
increase in failure load of the RCC beam is only 1.50 % to 1.80 % until 2.5
years.
There is no significant effect on the failure load of the RCC beam
even after adding 5% fly ash along with either concare (2.5% concare is
added with the concrete prepared using tannery effluent and 2.0% concare is
added with the concrete prepared using textile effluent) or 2% calcium nitrate
(Figures 3.40 and 3.41). It is concluded that there is no disastrous effect on
the failure load of the RCC beam prepared by using the tannery and textile
effluents.
134
30
31
32
33
34
35
0 200 400 600 800 1000
Age of concrete (days)
Load
in K
NPWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.40 Comparison of failure load of reinforced cement concrete
beam prepared using potable water, untreated and treated
tannery effluents
30
31
32
33
34
35
0 200 400 600 800 1000
Age of concrete (days)
Load
in K
N
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.41 Comparison of failure load of reinforced cement concrete
beam prepared using potable water, untreated and treated
textile effluents
135
The Figures 3.42 and 3.43 shows the loading and testing of RCC
beams and specimens subjected to failure load test.
Figure 3.42 Loading and testing of RCC beams
Figure 3.43 Specimens subjected to failure load test of RCC beams
136
3.3.13 Studies on the Bond Strength of the Concrete
The bond strength of the concrete that exists between the cement
paste and the embedded steel reinforcement bar in the concrete is of
considerable importance. A perfect bond existing between the concrete and
the steel rebar is one of the important causes for the durability of the
reinforced concrete structures. The bond strength of the concrete depends
upon the friction and adhesion between the concrete and the embedded
reinforcement bars. The roughness of the steel surface is also one of the
important factors affecting the bond strength of the concrete. The pull out test
is carried out to determine the bond strength of the concrete developed
between the concrete and the embedded reinforcement bar. Due to the
presence of chlorides in the tannery and textile effluents, used for preparing
the concrete, the threat of corrosion of the reinforcement bar embedded in the
concrete is a major concern. Hence the studies related to corrosion of the
reinforcement bar embedded in the concrete and bond behavior of the
concrete have to be carried out (Lan Chung et al 2008).
The bond strength of the concrete prepared using potable water,
untreated and treated tannery effluents after 28 days is 1.43MPa, 1.49MPa
and 1.46MPa respectively. The bond strength of the concrete prepared using
potable water is 4% less than that of the concrete specimen cast using
untreated tannery effluent and 2.09 % less than the concrete specimen cast
using treated tannery effluent. Almost the same trend is observed for the
remaining test duration of 180 days, 1 year, 2 years and 2.5 years. When 5%
fly ash and 2.5% concare are added while preparing the concrete, the bond
strength of the concrete prepared using potable water, untreated and treated
tannery effluents after 28 days are 1.51MPa, 1.56MPa and 1.54MPa
respectively. There is an increase of 5.59%, 4.69%, and 5.48% in bond
strength of the concrete by the addition of 5% fly ash and 2.5% concare with
137
the concrete prepared using potable water, untreated and treated tannery
effluents respectively. The bond strength of the concrete goes on increasing in
the range of 4.40% to 5.70% for the other duration of testing. By the addition
of 5% fly ash and 2.0% calcium nitrate, there is an increase of 6.29%, 5.37%
and 6.16% of bond strength of the concrete prepared using potable water,
untreated and treated tannery effluents respectively. It is observed that there is
a considerable increase in the bond strength of the concrete with the addition
of the admixtures which are represented graphically in Figure 3.44.
When the corrosion is induced, the bond strength of the concrete
prepared using potable water, untreated and treated tannery effluents after 28
days and 2.5 years is 0.44MPa, 0.46MPa, 0.45MPa and 0.56MPa, 0.57MPa,
0.57MPa respectively. The bond strength of the concrete prepared using
potable water is 4.55% less than that of the concrete specimen cast using
untreated tannery effluent and 2.27 % less than the concrete specimen cast
using treated tannery effluent. There is 27.27%, 29.55% and 26.67% increase
in the bond strength of the concrete after 2.5 years. Due to corrosion of the
rebar, the bond strength of the concrete is largely reduced (Figure 3.44).
When 5% fly ash and 2.5% concare are added, the bond strength of
the concrete prepared using potable water, untreated and treated tannery
effluents after 28 days and 2.5 years is 0.91MPa, 0.93MPa, 0.91MPa and
1.01MPa, 1.04MPa, 1.02MPa respectively as shown in the figure 3.34. Due to
the addition of fly ash and concare admixture, there is 106.82%, 102.17%,
102.22% increase in bond strength of the concrete prepared using potable
water, untreated and treated tannery effluents after 28 days of testing. By the
addition of 5% fly ash and 2.0% calcium nitrate, there is 113.64%, 106.52%,
108.89% increase in the bond strength of the concrete prepared using potable
water, untreated and treated tannery effluent after 28 days of testing. There is
138
more than 102.22% increase in the bond strength due to the addition of the
admixtures. The effects are represented graphically in Figure 3.45.
1.4
1.5
1.6
1.7
1.8
0 200 400 600 800 1000
Age of concrete (days)
Bond
stre
ngth
(MPa
)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.44 Comparison of bond strength of the concrete prepared using
potable water, untreated and treated tannery effluents
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
0 200 400 600 800 1000
Age of concrete (days)
Bond
stre
ngth
(MPa
)
PWUTTTTPW with CUTT with CTT with CPW with CNUTT with CNTT with CN
Figure 3.45 Comparison of bond strength of the concrete prepared using
potable water, untreated and treated tannery effluents (after
induced corrosion)
139
The bond strength of the concrete prepared using potable water,
untreated and treated textile effluents after 28 days is 1.43MPa, 1.46MPa and
1.45MPa respectively. The bond strength of the concrete prepared using
potable water is 2.09% less than that of the concrete specimen cast using
untreated textile effluent and 1.39% less than that of the concrete specimen
cast using treated textile effluent. Almost the same trend is observed for the
remaining test duration of 180 days, 1 year, 2 years and 2.5 years. When 5%
fly ash and 2.0%concare admixture are added, the bond strength of the
concrete prepared by using potable water, untreated and treated textile
effluents after 28 days are 1.51MPa, 1.54MPa and 1.52MPa respectively.
There is an increase of 5.59%, 5.47%, and 4.82% in the bond
strength of the concrete by adding 5% fly ash and 2.0% concare while
preparing the concrete prepared by using potable water, untreated and treated
textile effluents respectively. The bond strength of the concrete increases in
the range of 4.40% to 5.90% up to 2.5 years of testing. By the addition of 5%
fly ash and 2% calcium nitrate admixture, there is an increase of 6.29%,
6.84% and 6.21% of the bond strength of the concrete prepared using potable
water, untreated and treated textile effluents respectively. It is observed that
there is increase in the bond strength of the concrete by the addition of the
admixtures. The effects are shown graphically in Figure 3.46.
By induced corrosion, the bond strength of the concrete prepared
using potable water, untreated and treated textile effluents after 28 days and
2.5 years is 0.40MPa, 0.42MPa, 0.42MPa and 0.53MPa, 0.55MPa, 0.55MPa
respectively. The bond strength of the concrete prepared using potable water
is 5.00% less than that of the concrete specimen cast using untreated textile
effluent and 5.00 % less than the specimen using treated textile effluent.
There is 32.50%, 30.95% and 30.95% increase in the bond strength of the
concrete after 2.5 years prepared by using potable water, untreated and treated
140
textile effluents. Due to corrosion of the rebar embedded in the concrete, the
bond strength of the concrete is largely reduced.
The bond strength of the blended concrete (5% fly ash and 2.0%
concare) prepared using potable water, untreated and treated textile effluents
after 28 days and 2.5 years is 0.87MPa, 0.89MPa, 0.88MPa and 0.98MPa,
1.00MPa, 0.99MPa respectively. Due to the addition of 5% fly ash and 2.0%
concare, there is 117.50%, 111.90%, 109.52% increase in the bond strength of
the concrete prepared by using potable water, untreated and treated textile
effluents after 28 days of testing. By the addition of 5% fly ash and 2%
calcium nitrate, there is 125.00%, 121.43%, 119.05% increase in the bond
strength of the concrete prepared by using potable water, untreated and treated
textile effluents after 28 days of testing. There is more than 109.52% increase
in the bond strength of the concrete due to the addition of the admixtures as
graphically illustrated in the Figure 3.47.
1.4
1.5
1.6
1.7
1.8
0 200 400 600 800 1000
Age of concrete (days)
Bond
stre
ngth
(MPa
)
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.46 Comparison of bond strength of the concrete prepared using
potable water, untreated and treated textile effluents
141
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
0 200 400 600 800 1000
Age of concrete (days)
Bond
stre
ngth
(MPa
)
PWUTTETTEPW with CUTTE with CTTE with CPW with CNUTTE with CNTTE with CN
Figure 3.47 Comparison of bond strength of the concrete prepared using
potable water, untreated and treated textile effluents (after
induced corrosion)
It is observed from the experimental results that there is good
improvement in the bond strength of the concrete by the addition of 5% fly
ash and concare (2.5% concare is added with the concrete prepared using
tannery effluent and 2.0% concare is added with the concrete prepared using
textile effluent) with the concrete or 5% fly ash and 2% calcium nitrate with
the concrete.
3.4 COST BENEFIT ANALYSIS
The treatment of effluents (processed water/waste water) in the
tanneries and textile processing units incur approximately about 45 to 80
paise per litre of processed water. The transport cost from the tanneries and
the textile processing units to the site (where the construction activity takes
place) is approximately around 35 to 45 paise per litre of water, if the
construction site is within 30-40 kilometres from the tanneries and the textile
142
processing units, which accounts 2.0% of the total cost of the building. The
admixtures to be added with the concrete costs approximately about 3% of the
total cost of the building. The coating of the reinforcement bar to be
embedded in the concrete costs approximately 1% of the total cost of the
building. Altogether approximately 6.0% cost of the building is increased.
The cost of buying potable water in scarcity season costs approximately 1%
of the total cost of the building. So there is 5.0% increase in the total cost of
the building. Even though there is an increase in the cost (5.0%) of the
building constructed using tannery and textile effluents, it reduces the water
demand considerably during the water scarcity period and also the tannery
and textile effluents are safely disposed. It also reduces the pollution, protects
the environment and conserves the non renewable resources (water).