Upload
fedilino-p-fornolles
View
241
Download
0
Embed Size (px)
Citation preview
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
1/92
Medium voltage products
UniGear ZS1Medium voltage, arc-proo, air insulatedswitchgear up to 24 kV insulated voltage
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
2/92
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
3/923
Index
1. UniGear ZS1
4 Description
8 IEC Classiication
10 Design eatures
12 Full tpe tested
14 Saet
18 Vacuum circuit-breaker
22 Gas circuit-breaker
24 Vacuum contactor
26 Switch-disconnector
28 Service trucks
30 UFES - Ultra ast earthing switch32 Is-limiter ault-current limitation
34 Instrument transormers
36 Measurement sensors
40 Cable terminations
42 Distribution automation
56 Automatic transer sstem
58 Tpical units
60 Technical data
2. UniGear ZS1 - Double Busbar System
64 Description
66 Characteristics68 Tpical units
70 Technical data
3. Marine Applications
74 Description
76 Characteristics
78 Tpical units
80 Technical data
UniGear ZS1 - Double Level
82 Description
84 Characteristics86 Tpical units
88 Technical data
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
4/924
UniGear ZS1 is the ABB mainline global switchgear up to 24 kV, 4000 A,
50 kA and is produced close to ou in all the six continents
More than 150,000 panels produced and installed in more than 100
countries
Each UniGear ZS1 panel consists o a single unit which can be equipped
with a circuit-breaker, contactor or switch-disconnector, as well as with all
the accessories available or conventional switchgear units
1. UniGear ZS1Description
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
5/925
Range
Up to 12-17.5 kV, 4000 A, 50 kA
Up to 24 kV, 3150 A, 31.5 kA
Standard IEC
Highl customized versions
Safety
Fitted with saet interlocks
Internal arc classiication IAC AFLR
Classiied LSC-2B, PM
CB racking with closed door
Flexibility
Wide applications
Vacuum and SF6 circuit-breaker
Vacuum contactor
Switch-disconnector
Traditional CT/VT and sensors
Wall and ree-standing solution
Quality
ABB qual it
Large installed base
Installed in high number o countries
Design includes
Protection and control
Earthing switch
Ultra ast earthing switch
IS Limiter
Integrated capacitor banks
Ba computer
Utilities and Power Plants
Powergenerationstations
Substations
Mainandauxiliaryswitchgear
Industry
Pulp and Paper
Cement
Textiles
Food
Automotive Quarring
Petrochemical
Oil and gas
Metallurg
Rolling mills
Mines
Marine
Drilling platorms
O-shore oil rigs
Cruise ships
Container shipsTankers
Cable ships
Ferries
Transport
Airports
Ports
Railwas
Underground transport
Infrastructure
Shopping malls Hospitals
Large inrastructure and civil works
Characteristics o
UniGear ZS1
Applications
Approved to be used or special applications such marine, seismic,
nuclear and tpe tested or IEC, GB/DL, GOST and CSA standards
Units can be coupled together directl with the other products o the
UniGear amil
The switchgear does not require rear access or installation or
maintenance, all the operations are carried out rom the ront
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
6/926
1. UniGear ZS1Description
UniGear ZS1 is medium voltage switchgear with a metal
enclosure, suitable for indoor installations.
Metal partitions segregate the compartments from each
other and the live parts are air-insulated.
Since the switchgear is highly modular type, this
make simple selection of components required by any
application.
The functional units of the switchgear are guaranteed arc
proof in accordance with the IEC 62271-200 Standards,
appendix AA, class A accessibility, criteria 1 to 5.
All the installation, operation and maintenance operations
can be carried out from the front of the unit.The switchgear and the earthing switches are operated
from the front with the door closed.
The switchgear can be back to wall installed.
ApparatusThe range o apparatus avai lable or Un iGear ZS1 switchgear
is the most complete on the market, including:
withdrawable vacuum circuit-breakers with mechanical or
magnetic actuator,
withdrawable gas circuit-breakers,
withdrawable vacuum contactors with uses,
ixed version o switch-disconnectors.
This makes i t possible to oer a single switchgear-user
interace, with the same operational and maintenance
procedures.
The switchgear can be i tted with instrument transormers or
sensors or current and voltage measurement and protection
and an tpe o protection and control unit.
Switchgear, busbar conigurationIn the completion o the traditional unctional units in single
level-single busbar arrangement, the UniGear ZS1 switchgear
platorm is itted with:
Double-level,
Compact units equipped with contactors with uses,
Double Busbar Sstems.
The use o these un its allows extremel e icient use o
space. In addition UniGear ZS1 single busbar is possible to
combine to other members o UniGear amil like:
UniGear 550,
UniGear 500R, UniGear MCC.
Normal operation conditionsThe rated characteristics o the switchgear are guaranteed
under the ollowing ambient conditions:
minimumambienttemperature:5C
maximumambienttemperature:+40C
For dierent temperature ranges, please contact our ABB
sales representative.
Ambienthumidity:
- maximum 24 h average o relative humidit 95% RH
- maximum 24 h average o water vapour pressure 2.2 kPa
- maximum monthl average o relative humidit 90% RH
- maximum monthl average o water vapour pressure 1.8 kPa
The normal operational altitude is up to 1,000 m above sea
level. For higher altitude applications, please contact our
ABB sales representat ive.
Presence o normal, non-corrosive and uncontaminated
atmosphere.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
7/927
IEC electrical characteristics o UniGear ZS1 - Single Busbar Sstem
Rated voltage kV 7.2 12 17.5 24
Rated insulation voltage kV 7.2 12 17.5 24Rated power requenc withstand voltage kV 1min 20 28 38 50
Rated lightning impulse withstand voltage kV 60 75 95 125
Rated requenc Hz 50/60 50/60 50/60 50/60
Rated short time withstand current kA 3 s 50 50 50 31.5
Peak current kA 125 125 125 80
Internal arc withstand current kA 1 s 50 50 50 31.5
Main busbar rated current A ...4,000 ...4,000 ...4,000 ...3,150
Circuit-breaker rated current A
630 630 630 630
1,250 1,250 1,250 1,250
1,600 1,600 1,600 1,600
2,000 2,000 2,000 2,000
2,500 2,500 2,500 2,3003,150 3,150 3,150 2,500
Circuit-breaker rated current with orced ventilation A3,600 3,600 3,600 2,500
4,000 4,000 4,000 3,150
1) For other versions, please reer to the chapters no. 2 (Double Busbar Sstem) and chapter no. 3 (Marine Applications).
2) GB/DL version is available with higher request in dielectric characteristics (42 kV) and short time withstand current (4 s).
3) The values indicated are valid or both vacuum and SF6 circuit-breaker.
4) For panel with contactor the rated current value is 400 A.
5) CSA version is available or 27,6 kV.
StandardsThe switchgear and main apparatus contained in it compl
with the ollowing Standards:
IEC62271-1forgeneralpurposes.
IEC62271-200fortheswitchgear.
IEC62271-102fortheearthingswitch.
IEC62271-100forthecircuit-breakers.
IEC60071-2fortheinsulationcoordination.
IEC60470forthecontactors.
IEC60265-1fortheswitch-disconnectors.
IEC60529fordegreeofprotections.
Colour o the external suracesRAL7035 - ligh gre (ront doors and side sheets).
Other colours available on request.
Degrees o protectionThe degrees o protection o the switchgear conorm wi th IEC
60529 Standards.
UniGear ZS1 switchgear is normall supplied with the
ollowing standard degrees o protection:
IP4Xfortheenclosure.
IP2Xforthepartitionbetweencompartments.
On request, the external housing can be supplied with a
higher degree o protection; in this case please contact our
ABB sales representative.
The electrical characterist ics o the switchboard can var or
ambient conditions other than those described in the previous
section and also i a higher degree o protection is used.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
8/928
With the release of the IEC 62271-200 standard, new
definitions and classifications of Medium Voltage
switchgear have been introduced.
One of the most significant changes is that classification
of switchgear into metal-enclosed, compartmented and
cubicle types has been abandoned.
The revision of switchgear classification rules has been
based on the users point of view, in particular on aspects
like service and maintenance of the switchgear, according
to the requirements and expectations for proper
management, from installation to dismantling.
In this context, Loss of Service Continuity (LSC) has beenselected as a fundamental parameter for the user.
According to the IEC 62271-200, UniGear ZS1 switchgear
can be defined as follows.
Loss o service continuit - LSC-2BThe various LSC categor ies describe the possibili t o
keeping other compartments and/or panels energized while
a compartment in the main circuit is opened. The deined
categories are:
LSC-1: The whole switchgear shall be put out o service or
opening a main circuit compartment or normal operation
and/ornormal maintenance or or gaining access to an
switchgear components.
LSC-2A: The same as LSC-1 with the exception that the
main busbars and the unctional units adjacent to the one
under maintenance can remain energized.
LSC-2B:The same as LSC-2A with the exception that the
cable compartment can remain energized.
UniGear ZS1 is classiied as LSC-2B because the busbar,
circuit-breaker and cable compartments are phsicall and
electricall segregated.This is the categor that deines the
possibilit o accessing the circuit-breaker compartment
with the busbars and cables energized. In case o using the
ixed version o the switch-disconnector, the panel is deined
LSC-2A because the cable and apparatus compartments are
not phisicall segregated.
Partition Metallic - PMWith regard to the tpe o partitions or shutters between
live parts and an open compartment, a distinction is made
between two partition classes:
Class PM (Partition made o Metal);
Class PI (Partition made o Insulating material).
UniGear ZS1 is deined with PM partition class having the
segregation between compartments made o metallic sheets/
shutters.
Interlock-controlled accessiblecompartmentThe ront s ide o UniGear ZS1 is classiied inter lock-controlled
because the access o the compartments containing high-
voltage parts, intended to be opened or normal operation
and/or normal maintenance, is controlled b the integral
design o the switchgear.
Tool-based accessible compartmentThe rear part o the UniGear ZS1 is classi ied tool-based
because it is possible to open the compartment containing
high-voltage parts, that ma be opened, but not or normaloperation and maintenance, onl using a tool. Special
procedures are required.
InternalarcclassificationIACAFLRUniGear ZS1 switchgear is classiied IAC AFLR.
When the switchgear is speciied and installed, some
undamental points must be taken into consideration:
Levelofthefaultcurrent(16...50kA).
Durationofthefault(0.1...1s).
Escaperoutesforthehotandtoxicgasesproducedby
combustion o materials.
Dimensionsoftheroom,withspecialattentiontotheheight.
Please consult our ABB representatives or detailed
inormation.
1. UniGear ZS1IEC Classiication
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
9/929
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
10/9210
CompartmentsEach switchgear unit consists o three power compartments:
circuit-breaker [A], busbars [B] and cables [C]; please reer to
igure 1.
Each unit is itted with a low voltage compartment [D], where
all the auxiliar instruments are housed.
Arc-proo switchgear is normall provided with a duct [E] or
evacuation o the gases produced b an arc; dierent tpes o
gas ducts are available.
All the compartments are accessible rom the ront and
maintenance operations can correctl carried out with the
switchgear installed up against a wall.
The compartments are segregated rom each other b
metallic partitions.
Main busbarsThe busbar compartment contains the main busbar sstem
connected to the upper isolating contacts o the circuit-
breaker b means o branch connections.
The main busbars are made o electroltic copper.
For ratings up to 2500 A, the busbars are lat bars; while or
currents between 3150 A and 4000 A, a special D-shape
busbar is used.The busbars are covered with insu lating material .
There is a sing le busbar compartment along the whole length
o the switchgear up to 31,5 kA, which optionall can be
divided into compartments. For 40/50 kA these bushings are
a standard eature.
Cable connectionsThe cable compartment contains the branch sstem or
connection o the power cables to the lower contacts o the
circuit-breaker.
The eeder connections are made o e lectrolt ic copper and
the are lat busbars or the whole range o currents.
For 17.5 and 24 kV the are covered with insulating material.
Earthing switchCable compartment can be itted with an earthing switch or
cable earthing.
The same device can a lso be used to earth the busbar sstem
(measurements and bus-tie units).
It can also be installed directl on the main busbar sstem in a
dedicated compartment (busbar applications).
The earthing switch has short-circuit making capacit.
Control o the earthing switch is rom the ront o the
switchgear with manual operation, and optionall, can also be
motor operated.
The position o the earth ing switch can be seen rom the
ront o the switchgear b means o a mechanical coupled
indicator.
Earthing busbarThe earthing busbar is made o electroltic copper and it runs
longitudinall throughout the switchgear, thereb guaranteeing
maximum personnel and installation saet.
Insulating bushings and shuttersThe insu lating bush ings in the c ircui t-breaker compartment
contain the contacts or connection o the circuit-breaker with
the busbar compartment and cable compartment respectivel.
The insu lating bush ings are o s ingle-pole tpe and are made
o epox resin. The shutters are metallic and are activated
automaticall during movement o the circuit-breaker rom the
racked-out position to the operation position and vice versa.
CablesSingle and three-core cables up to a maximum o twelve per
phase can be used depending on the rated voltage, the unit
dimensions and the cable cross section (please reer to page
40).The switchgear can be back to wall installed as the cables are
easil accessible rom the ront.
1. UniGear ZS1Design eatures
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
11/9211
Gas exhaust ductThe gas exhaust duct is positioned above the switchgear and
runs along its whole length.
Each power compartment is itted with a lap on its top
surace. The pressure generated b the ault makes it open,
allowing the gas to pass into the duct.
Evacuation rom the room o the hot gases and incandescent
particles produced b the internal arc must normall be
carried out. The UniGear ZS1 switchgear can be itted with a
complete range o solutions to satis all requirements, either
in the case where evacuation is possible directl at the end
o the switchgear, or when solutions rom the ront or rear are
requested.
Some installations, such as marine applications, do not
allow evacuation o the gases to the outside o the room and
thereore a dedicated solution has been developed to
guarantee personnel saet and conormit with the
Standards, such as longitudinal evacuation chimnes.
Please contact our ABB sales representative or more
inormation.
Busbar applications
Each switchgear unit can optionall be itted with anaccessor busbar application:
currentorvoltagetransformersforbusbarmeasurements.
busbarsystemearthingswitch.
topentryductorcablestomakeinterconnectionsbetween
dierent sections o switchgear.
Unit compartmentsA Circuit-breaker compartment
B Busbar compartment
C Cable compartment
D Low voltage compartment
E Compact gas duct channel
Figure 1: UniGear ZS1 single level section view
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
12/9212
The UniGear ZS1 switchgear has undergone all the tests
required by the international (IEC) Standards and local
Standards organizations (for example, the Chinese GB/DL
and Russian GOST standards).
In addition, the tests required by the main shipping
registers (LR, DNV, RINA, BV and GL) have been carried
out for use of the switchgear in marine installations.
As indicated in these standards, the tests were carried
out on the switchgear units considered most sensitive
to the effects of the tests and therefore the results were
extended across the whole range.
Each switchgear unit is subjected to routine tests in thefactory before delivery.
These tests are intended to provide a functional check of
the switchgear based on the specific characteristics of
each installation.
IEC tpe tests Short-time and peak withstand current
Temperature r ise
Internal arc capabilit
Dielectric test
Making and breaking capacit o circuit-breaker and
contactors
Earthing switch making capacit
Mechanical operations o circuit-breaker and earthing
switch
IP protectiondegree
IEC routine actor testsVisual inspect ion and check
Mechanical sequence operations
Cabling check
Electrical sequence operations Power requenc withstand voltage
Measurement o the resistance o the main circuits
Secondar insulation test
Special tpe tests required b shipping
registers or marine application Highambienttemperatures(+45C)
Inclination
Vibration
Figure 2: UniGear ZS1 during internal arc test
Description o IEC tpe tests
Short-time and peak withstand current
The test shows that the main power and the earthing circu its
resist the stresses caused b the passage o the short-circuit
current without an damage.
It should also be noted that both the earthing sstem o the
withdrawable circuit-breaker and the earthing busbar o the
switchgear are subjected to the test.
The mechanical and electrical properties o the main busbar
sstem and o the top and bottom branch connections remain
unchanged even in the case o a short-circuit.
Temperature rise
The temperature rise test is carried out at the rated current
value o the switchgear unit and shows that the temperature
does not become excessive in an part o the switchgear unit.
During the test, both the switchgear and the circuit-breaker or
contactor it ma be itted with are checked.
Internal arc capability
Please reer to page 14.
Dielectric test
These tests veri that the switchgear has suicient capabilit
to withstand the lightning impulse and the power requenc
voltage.
The power requenc withstand voltage test is carr ied out as a
tpe test, but it is also a routine test on ever switchgear unit
manuactured.
1. UniGear ZS1Full tpe-tested
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
13/9213
Figure 3: inclination test Figure 4: vibration/seismic test
Tpe tests required b the shipping
registers
High ambient temperature
The serv ice cond itions or the electrical apparatus in marine
installations are generall more severe than those in normal
land applications.
Temperature is a main actor and or this reason the shipping
register regulations require the switchgear to be able to
operateathigherambienttemperatures(45Corhigher)than
thosestatedintheIECStandards(40C).
Inclination
The test is carried out b inclining the switchgear or a deined
timeupto25alternatelyonallfoursidesandoperatingthe
apparatus.
The test proves that the switchgear is able to res ist these
extreme service conditions and that all the apparatus it
contains can be operated without an problems and without
being damaged.
Vibration
The reliabili t and sturdiness o the UniGear ZS1 switchgearhas been deinitivel proved b the result o the withstand test
to mechanical stresses due to vibration. The service
conditions on shipping installations and marine platorms
require the switchgear to work in environments strongl
aected b vibrations, such as those caused b the motors
on large cruise ships or the drilling plants o oil rigs.
1mmamplitudeinthefrequencyrangebetween2and
13.2 Hz.
0.7gaccelerationamplitudeinthefrequencyrange
between 13.2 and 100 Hz (see picture on the previous
page).
Circuit-breaker making and breaking capacity
The circu it-breaker or contactor is subjected to the rated
current and short-circuit current breaking tests.
Furthermore, it is also subjected to the opening and closing o
capacitive and inductive loads, capacitor banks and/or cable
lines.
Earthing switch making capacity
The earthing switch o the UniGear ZS1 switchgear can be
closed under short-circuit. Although, the earthing switch is
normall interlocked to avoid being operated on circuits which
are still live.However, should this happen or an one o several reasons,
personnel saet would be ull saeguarded.
Mechanical operations
The mechanical endurance tests on all the operating parts
ensures the reliabilit o the apparatus. General experience in
the electro-technical sector shows that mechanical aults are
one o the most common causes o a ault in an installation.
The circu it-breaker is tested b carring out a high number o
operations - higher than those which are normall carried out
b installations in the iled.
Furthermore, the switchgear components are part o a qualitcontrol program and samples are regularl taken rom the
production lines and subjected to mechanical lie tests to veri
that the qualit is identical to that o the components subjected
to the tpe tests.
IP protectiondegree
The IP protection degree is the resistance oered b the
UniGear ZS1 against penetration o solid objects and liquids.
This degree o res istance is indicated b the preix IP ollowed
bytwocharachters(i.e.IP4X).
The irs t number identiies the degree o protection against the
entrance o solid objects, the second one is related to liquids.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
14/9214
When developing modern medium voltage switchgear,
personnel safety must necessarily take priority. This is
why the UniGear ZS1 switchgear has been designed and
tested to withstand an internal arc due to a short-circuit
current of the same current level as the maximum short-
time withstand level.
The tests show that the metal housing of UniGear
ZS1 switchgear is able to protect personnel near the
switchgear in the case of a fault which evolves as far as
striking an internal arc.
An internal arc is a highl unlikel ault, although it cantheoreticall be caused b various actors, such as:
Insulation deects due to qualit deterioration o the
components. The reasons can be adverse environmental
conditions and a highl polluted atmosphere.
Overvoltages o atmospheric origin or generated b the
operation o a component.
Inadequate training o the personnel in charge o the
installation.
Breakage or tampering o the saet interlocks.
Overheating o the contact area, due to the presence
o corrosive agents or when the connections are not
suicientl tightened. Entr o small animals into the switchgear (i.e. through
cable entrance).
Material let behind inside the switchgear during
maintenance activities.
The characterist ics o the UniGear ZS1 switchgear notabl
reduce the incidence o these causes or aults, but some o
them ma not be eliminated completel.
The energ produced b the internal arc causes the ollowing
phenomena:
Increase in the internal pressure.
Increase in temperature.Visual and acoustic eects.
Mechanical stresses on the switchgear structure.
Melting, decomposition and evaporation o materials.
Unless suitabl protected, these phenomena have ver
serious consequences or the personnel, such as wounds
(due to the shock wave, ling parts and the doors opening)
and burns (due to emission o hot gases).
The interna l arc test veri ies that the compartment doors
remain closed and that no components are ejected rom the
switchgear even when subjected to ver high pressures, and
that no lames or incandescent gases penetrate, therebensuring saet o the personnel near the switchgear.
The test also ensure that no holes are produced in external
accessible parts o the housing, and inall, that all the
connections to the earthing circuit remain intact, hence
guaranteeing the saet o personnel who ma access the
switchgear ater the ault.
The IEC 62271-200 Standard describes the methods to
be used or carring out the test and the criteria which the
switchgear must conorm to.
The UniGear ZS1 switchgear ull conorms to al l the ive
criteria indicated b the IEC standards.
The IAC classiication is proved b the test according to theollowing designations:
General: classiication IAC (Internal Arc Classiied)
Accessib ilit : A, B or C (switchgear accessible to authorized
personnel onl (A), to all (B), not accessible due to
installation (C)
F,L,R:accessfromthefront(FFront),fromthesides(L
Lateral)andfromtherear(Rrear).
Test values: test current in k iloamperes (kA), and duration in
seconds (s).
The parameters o each speci ic plant mean that evacuation
o the hot gases and incandescent particles must be checkedver careull in order to ensure and maintain personnel saet.
Fault limiting sstemsThe structure o the UniGear ZS1 switchgear oers complete
passive tpe protection against the eects o a ault due to an
internal arc or a time o 1 second up to 50 kA.
ABB has also deve loped excel lent active protection sstems
which allow ver important objectives to be achieved:
Detection and extinction o the ault, normall in less than
100 ms, which improves network stabilit.
Limitation o damage on the apparatus.
Limitation o outage time or the switchgear unit.
For active protection against an internal arc, devices
consisting o various tpes o sensors can be installed in the
various compartments, which detect the immediate outburst
o the ault and carr out selective tripping o the circuit-
breakers.
The aul t l imit ing sstems are based on sensors which use the
pressure or light generated b the arc ault as trigger or ault
disconnection.
1. UniGear ZS1Saet
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
15/9215
Melting
of Steel
Melting of
Copper
Melting
of Cables
0 100 200 500 ms
kA2 s
ITHThe ITH sensors consist o micro-switches positioned on the
top o the switchgear near the gas exhaust laps o the three
power compartments (busbars, circuit-breaker and cables).
The shock wave makes the laps open and operate the
micro-switches connected to the shunt opening release o the
circuit-breaker.
Totaltripp ing timeis 75 ms(15 ms ITH+60mscircu it-
breaker).
FRD (Fast Recover Device)This sstem cons ists o pressure sensors located in the lowvoltage compartment and connected to the three power
compartments b means o small tubes.
The sensors detect the rising ront o the pressure wave which
develops on the outburst o the arc and react b making the
circuit-breakers open.
The sensors are protected against the external environment
and the can be checked even with the switchgear in
operation.
Totaltripp ing timeis 75 ms(15 ms FRD +60msci rcuit -
breaker).
TVOCThis sstem consists o an e lectronic monitoring device located
in the low voltage compartment which is connected to optic
sensors. These are distributed in the power compartments and
are connected to the device b means o optic bres.
When a certain pre-set light level is exceeded, the device
opens the circuit-breakers.
To prevent the sstem rom intervening due to light occasionall
generated b external phenomena (fash o a camera,
refections o external lights, etc.), current transormers can also
be connected to the monitoring device.
The protection module onl sends the opening command to the
circuit-breaker i it receives the light and short-circuit current
signal simultaneousl.
Totaltripp ing timeis 62 ms(2 msT VOC +60msci rcuit -
breaker).
Figure 5: Arc duration and damage caused
REAThis sstem oers the same unctionalit as TVOC. The REA
sstem consists o the main unit (REA 101) and optional
extension units (REA 103, 105, 107) which make it possible to
create customized solutions with selective tripping. For more
inormation, please see the dedicated chapter at page 50.
Totaltripping timei s62,5ms (2, 5msRE A+60mscirc uit-
breaker).
Arc protection in IED
The REF615, RET615, REM615 and REF610 IEDs (IntelligentElectronic Device) can optionall be itted with a ast and
selective arc lash protection. It oers a two-to three-channel
arc-ault protection sstem or arc lash supervision o the
circuit breaker, cable and busbar compartment o switchgear
panels.
Totaltripping timei s72ms(12msI ED+ 60ms circu it-
breaker).
UFES (ultra ast earthing switch)The UFES is an innovative design o an extremel ast-acting
earthing switch, grounding all 3 phases within < 4 ms ater
detection o an internal arc ault.
For more inormation please see the dedicated chapter at
page 30.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
16/9216
Figure 6: Double key lock on earthing switch
The UniGear ZS1 switchgear is fitted with all the
interlocks and accessories needed to guarantee the
highest level of safety and reliability for both installation
and personnel.
InterlocksThe saet mechanical inter locks are standard ones [15],
please see the dedicated table at page 17.
The are set out b the IEC standards and are thereore
necessar to guarantee the correct operation sequence.
ABB saet interlocks guarantees the highest level o rel iabi lit,
even in the case o an accidental error, and enables highest
operator saet sstem o interlocks.
KesThe use o ke interlocks is ver important in realis ing the
interlocking logics between panels o the same switchgear, or
o other medium, low and high voltage switchgear. The logics
are realised b means o distributors or b ringing the kes.
The apparatus truck [6] can be locked in the racked-
outposition and the relevant lock ke can onl be removed
with the apparatus in this position.The earthing switch closing [7] and opening [8] operations can
be locked b means o kes, ke logic is explained in the table
at page 15.
These locks can also be appl ied to the earthing switch o
busbar applications.
The circu it-breaker racking-in/out operations [9] and earthing
switch opening/closing [10] can be prevented b means o
ke locks, which prevent insertion o the relevant operating
levers.
The ke lock can also be appl ied to the earthing switch o
busbar applications. The kes can alwas be removed.
PadlocksThe circu it-breaker [11] and cables [12] compartment doors
can be locked in the closed position b means o padlocks.
Thes eca nbeap pliedt ob oth doo rclosi ngv ersi onswith
central handle (standard) or screws (optional).
The operations or apparatus racking-in/out [13] and earthing
switch opening/closing [14] can be prevented b appling the
padlocks to the insertion slots o the relevant operating levers.
The padlock can also be appl ied to the earthing switch o
busbar applications.The metallic segregation shutters [15] between circui t-breaker,
busbars and cables compartments can be locked b means
o two independent padlocks in both the open and closed
positions.
Padlocks rom 4 to 8 mm diameter can be accommodated.
Locking magnetsThe locking magnets enable automatic interlocking logics
without human intervention.
The circu it-breaker racking-in/out [16] and the earthing switch
closing/opening [17] operations can be interlocked.
This magnet can also be applied to the earthing switch o
busbar applications.
The magnets operate with active logics and there ore the lack
o auxiliar voltage leaves the interlocking sstem active in
saet condition.
1. UniGear ZS1Saet
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
17/9217
Standard safety interlocks (mandatory)
Type Description Condition to be met
1A Apparatus rack ing-in/out Apparatus in open position
B Apparatus closing Deined truck position
2A Apparatus rack ing-in Apparatus multi -contact plug plugged
B Apparatus multi-contact plug unplugging Truck in test position
3A Earthing switch closing Truck in test posit ion
B Apparatus racking-in Earthing switch in open position
4A Apparatus compartment door opening Truck in test posit ion
B Apparatus racking-in Apparatus compartment door closed
5A Feeder compartment door opening Earthing switch in ON position
B Earthing switch opening Cable compartment door closed
Note: Apparatus are circuit-breakers and contactors.
Keys (on request)
6 Apparatus racking-in lock Can onl be removed with the t ruck in the racked-out pos it ion
7 Earthing switch closing lock Can onl be removed with the earthing switch open
8 Earthing switch opening lock Can onl be removed with the earthing closed
9 Insert ion o the apparatus raking- in/out c rank lever Can alwas be removed
10 Insertion o the earthing switch operating lever Can alwas be removed
Padlocks
11 Apparatus compartment door opening
12 Cable compartment door opening
13 Insertion o the apparatus raking-in/out crank lever
14 Insertion o the earthing switch operating lever
15 Shutters opening or closing
Locking magnets (on request)
16 Apparatus racking-in/out Magnet energized
17 Earthing switch ON/OFF Magnet energized
Accessory devices
20 Shutters ail-sae
The device locks the shutters i n the closed pos ition when theapparatus is removed rom the compartment. The operator cannotopen the shutters manuall. The shutters can onl be operated bthe apparatus truck or the service trucks (please see the dedicatedchapter at page 28).
21 Apparatus-switchgear unit compatibilit matrixThe apparatus multi -contact plug and relati ve swi tchgear unit socketare equipped with a mechanical matrix, that disables apparatusracking-in into a switchgear unit with an inappropriate rated current.
22 Circuit-breaker mechanical operating mechanism
The apparatus compartment is equipped with a mechanical device,that enables circuit-breaker closing and/or opening directl b meanso the ront operating mechanism pushbuttons, keeping the door
closed. The controls can be operated with the circuit-breakers in theoperation and racked-out position.
Tpes o interlocks
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
18/9218
1. UniGear ZS1
Vacuum circuit-breaker
UniGear ZS1 switchgear can be fitted with the widest
range of apparatus available on the market today, and of
these the vacuum circuit-breaker now occupies a position
of prime importance in all sectors of primary distribution.
Vacuum circuit-breakers cover the whole range of
switchgear parameters and therefore the whole range of
applications.
Many years of experience gained in developing and using
vacuum interrupters is today reflected in the range of
ABB circuit-breakers, which stand out for their
exceptional electrical and mechanical characteristics,
extremely long life, low maintenance, compactness and
the use of highly innovative construction techniques.
ABB develops and produces a complete range of
interrupters for use in circuit-breakers and contactors and
for all medium voltage applications.
Figure 7: UniGear ZS1
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
19/9219
VD4 circuit-breakerThe VD4 medium voltage circu it-breaker inter rupters use
vacuum to extinguish the electric arc and as the insulating
medium.
Thanks to the unequalled proper ties o vacuum and the
breaking technique used, current interruption takes place
without arc chopping and without overvoltages. Restoration
o the dielectric properties ollowing interruption is extremel
rapid.
The VD4 circu it-breakers are used or protection o cables,
overhead lines, motors, transormers, generators and
capacitor banks.
PolesThe VD4 medium voltage circu it-breakers use vacuum
interrupters embedded in poles (1).
Embedding the interrupter in the pole makes the circuit-
breaker particularl sturd and protects the interrupter itsel
against shocks, deposits o dust and humidit.
The vacuum inter rupter houses the contacts and provides the
interruption chamber.
ABB circu it-breakers use the most advanced vacuum-
breaking techniques: with radial magnetic low or circuit-
breakers with medium-low ratings and with axialmagnetic low
or those with high breaking capacit.
Both techniques guarantee even distribution o the arc roots
over the whole surace o the contacts, allowing optimum
perormance at all current values.
The structure o a vacuum inter rupter is re lativel simp le. The
housing is made up o a ceramic insulator closed at the ends
b stainless steel covers. The contacts are made o purecopper and sintered chrome and are welded to the copper
terminals. A metallic bellows allows movement o the moving
contact-terminal group, at the same time guaranteeing that
the vacuum is maintained in the interrupter. The interrupter
components are welded in an environment under a ver
strong vacuum to guarantee a vacuum o less than 10 -5 Pa in
the interrupter.
This means that the interrupter does not an ionisable
material. In an case, on detachment o the contacts, an
electric arc is generated which onl consists o the melted
and vaporised material o the contact.
A metal lic shie ld is integrated inside the inter rupter to capturethe metallic vapours given o during interruption, as well as
or controlling the electric ield. The particular shape o the
contacts generates a magnetic ield which orces the arc to
rotate and to involve a much wider surace than that o a ixed
contact arc.
Apart rom limiting the thermal stress on the contacts, this
makes contact erosion negligible and, above all, allows
theinterruption process to be controlled even with ver high
short-circuit currents.
The electric arc remains supported b the external energ unt il
the current passes through its natural zero.
The ABB vacuum interrupters are zero current interrupters andare ree o an re-striking phenomena.
The rapid reduction o the current densit and ast
condensation o the metallic vapours, that happens at the at
the instant that the current passes through zero, allow the
maximum dielectric strength between the interrupter contacts
to be re-established within a ew milliseconds. Supervision o
the vacuum level is not necessar as the circuit-breaker poles
are sealed-or-lie and do not require an maintenance.
(1) Circui t-breakers up to 17.5 kV - 1250 A - 31.5 kA are made opolamide poles.
Figure 8: VD4 circuit-breaker with mechanical actuator
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
20/9220
Operating mechanismThe VD4 circuit-breaker is tted with a mechanical stored
energ tpe operating mechanism.
The trip ree mechanism allows opening and closing operations
independent o the operator.
The operating mechanism spring sstem can be recharged
either manuall or b means o a geared motor. The apparatus
can be opened and closed b means o the pushbuttons on
the ront o the operating mechanism or b means o electric
releases (shunt closing, shunt opening and undervoltage).
The circuit-breakers are alwas tted with an anti-pumping
device to eliminate the possibilit o simultaneous opening and
closing commands, closing commands with springs discharged
or with the main contacts not et in their run-end position.
TruckThe poles and operating mechanism are xed onto a metal
support and handling truck.
The truck is provided with a wheel sstem which makes
the operations or racking the apparatus into and out o the
switchgear unit possible with the door closed. The truck allows
ecient earthing o the circuit-breaker b means o the metallic
structure o the switchgear unit.The vacuum circuit-breaker truck can be motor-operated.
The racking-out and racking-in operations can be carried out
b means o electrical controls, either locall b the operator or
b a remote sstem.
Apparatus-operator interaceThe ront part o the circuit-breaker provides the user interace.
It eatures the ollowing equipment:
ONpushbutton.
OFFpushbutton.
Operationcounter.
Indicatorofthecircuit-breakeropenandclosedstate.
Indicatorofthechargedordischargedstateoftheoperating
mechanism springs.
Manualchargingdevicefortheoperatingmechanism
springs.
Overrideselectoroftheundervoltagerelease(optional).
eVD4 circuit-breakerThe eVD4 circuit-breaker is a complete plug and pla medium
voltage electrical eeder protection sstem. It is an evolution
o the traditional concept o a circuit-breaker that with a single
device, can carr out the breaking, measurement, protection,
control and communication unctions.
The eVD4 circuit-breaker is derived rom the VD4 series with its
renowned reliabilit and robust characteristics.
eVD4 integrates the ABB RelionfamilyRBX615series
protection device with combined current and voltage
sensors.
Withthisintegratedsolution,theMTTRMeanTimeto
RepairofthesystemmanagedbyeVD4ismuchlowerthan
traditional solutions. This makes the eVD4 the ideal solution
or all installations where a high degree o continuit o service
is required.
The eVD4 is available in ixed and withdrawable versions or
UniGear ZS1 switchgear and it is mechanicall
interchangeable with the VD4 circuit-breaker.
1. UniGear ZS1Vacuum circuit-breaker
Figure 9: eVD4 circuit-breaker with on bord sensors, protection and control unit RBX 615.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
21/9221
VM1 circuit-breakerThe conventional mechanical stored energ tpe o operating
mechanism used on the VD4 circuit-breakers can be replaced
with an operating mechanism with magnetic actuator, creating
the VM1 series o circuit-breakers.
All the characteristics o the circuit-breakers described in
this chapter remain unchanged except or the operating
mechanism.
The operating mechanism is based on a greatl reduced
number o components:
Actuatorwithpermanentmagnets.Theheartoftheo perating
mechanism consists o the magnetic actuator which carries
out the closing and opening operations, and keeps the main
contacts in their positions taken up ater the operation.
The magnet transmits the operating mechanism to the
interrupters b means o a single transmission lever.
Electroniccontroldevice.Allthefunctions(trip,operation,
energ charging and watchdog) are carried out b the
integrated electronic controller. The circuit-breaker is tted
with a multivoltage direct and alternating current eeder.
Capacitors. The energ required to switch the operating
mechanism is provided b an incorporated capacitor
bank. The stored energ guarantees the complete O-C-O
reclosing sequence.
Positionsensors.Thepositionoft hecircuit-breakercontacts
is detected b means o electronic proximit sensors.
StandardsIEC 62271-100 or the circuit-breaker.
Figure 10: VM1 circuit-breaker with magnetic actuator
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
22/9222
Fig. 11: HD4 circuit-breaker
UniGear ZS1 switchgear can also be fitted with SF6 gas
circuit-breakers.
The ABB vacuum and gas series of circuit-breakers are
mechanically interchangeable and the same switchgear
unit can therefore take either type of apparatus. Only ABB
can offer apparatus representing both techniques for the
whole range of applications, voltage levels (12-17.5-24
kV), rated current (630...4000 A) and breaking capacity
(16...50 kA).
This makes it possible to specify the optimum solution
for the installation characteristics and the feeders to be
switched and protected.ABBs long practical experience shows that the two types
of circuit-breakers are equally valid and complementary.
HD4 circuit-breakerThe HD4 medium voltage circuit-breakers use
sulphurhexaluoride gas (SF6) to extinguish the electric arc
and as the insulating medium.
Thanks to the excellent properties o SF6 gas, interruption
o the currents takes place without arc chopping and
overvoltages. There is no restriking phenomenon ater
interruption and the dielectric properties ollowing interruption
are recovered extremel rapidl.
Gas circuit-breakers are available or all electric power
distribution applications. The are particularl recommended
or use on capacitor banks, motors, transormers insulated
in oil and in installations where components which are
particularl sensitive to dielectric and dnamic stresses are
installed (or example, old cables or transormers).
PolesThe HD4 circuit-breaker poles use the autopuer breaking
sstem, combining the compression and sel-blast techniquesin a single solution.
The autopuer sstem is the most innovative technique in the
ield o gas circuit-breakers and originates rom high voltage
apparatus.
The combinat ion o the compression and sel-blast techniques
allows the best perormance to be obtained at all current
values. Both techniques are alwas present, but whereas the
ormer operates optimall in switching low currents, the latter
acts eectivel during operation at higher current values.
The autopuer technique allows the use o a smaller quantit
o gas than that required b circuit-breakers based on other
techniques. For the same reason, the gas pressure is also
considerabl reduced. The autopuer technique guarantees
the insulating withstand voltage and the breaking capacit up
to 30% o the rated value, even with zero relative pressure.
The whole range o HD4 circuit-breakers uses the same gaspressure or all rated voltage levels (12-17.5-24 kV). SF6 gas
pressure level monitoring is not necessar, since the circuit-
breaker poles are sealed-or-lie pressure sstems and are
maintenance-ree.
The are itted with a pressure contro l device or checking
that the characteristics are not altered due to transport or
incorrect operations.
1. UniGear ZS1Gas circuit-breaker
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
23/9223
Figure 12: HD4-HXA circuit-breaker
Operating mechanismThe HD4 circuit-breaker is i tted with a mechanical
storedenerg operating mechanism. This is trip ree and
thereore allows opening and closing operations independent
o the operator.
The operating mechanism spr ing sstem can be recharged
either manuall or b means o a geared motor. The operating
mechanism is o the same tpe or the whole series and has a
standardised range o accessories and spare parts.
All the accessor components can easil be replaced b
means o plug-socket connectors.
Opening and the closing o the apparatus can be carried
out b pushbuttons on the ront o the operating mechanism
or b electric releases (shunt closing, shunt opening and
undervoltage).
The circu it-breakers are a lwas itted with an anti -pumping
device to eliminate the possibilit o simultaneous opening
and closing commands, closing commands with springs
discharged or with the main contacts not et in their run-end
position.
TruckThe poles and operating mechanism are ixed onto a metal
support and handling truck.
The truck is provided with a wheel sstem which makes
the operations or racking the apparatus out o and into the
switchgear unit possible with the door closed.
The truck a llows eective earthing o the c ircui t-breaker b
means o the metallic structure o the switchgear unit.
Apparatus-operator interace
The ront panel o the c ircui t-breaker provides theuserinterace. It eatures the ollowing equipment:
ONpushbutton.
OFFpushbutton.
operationcounter
indicatorofthecircuit-breakeropenandclosedstate
indicatorofthechargedanddischargedstateofthe
operating mechanism springs
manualchargingdevicefortheoperatingmechanism
springs
overrideselectoroftheundervoltagerelease(optional)
LEDgaspressureindicator(optional)
HD4-HXAcircuit-breakerforhigh
unidirectional componentsThe range o HD4 circuit-breakers is extended b the HD4-
HXAversion.
This series o circuit-breakers maintains a ll the eatures
described in this chapter, but is notable or its abilit to switch
loads with strong unidirectional components.
Forbreakingcapacitiesof40kAorlower,HD4-HXA
circuit-breakers are able to switch loads with unidirectional
components IDC = 100%, up to service voltage 13.8 kV;
at 50 kA the unidirectional component percentage IDC isreduced to 50%.The can be used in all installations aected
b strong unidirectional components, but their natural ield o
application is ound in switching and protecting transormers
o the auxiliar circuits in power generating stations.
StandardsIEC 62271-100 or the circuit-breaker.
IEC 60376 or the SF6 gas.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
24/9224
V-Contact VSC medium voltage contactors are apparatus
suitable for operating in alternating current and are
usually used to control feeders which require a high
number of operations per hour.
They are suitable for operating and protecting motors,
transformers and power factor correction banks.
Fitted with appropriate fuses, they can be used in circuits
with fault levels up to 1000 MVA.
The electrical life of V-Contact VSC contactors is defined
as being in category AC3 with 100,000 operations
(closing/opening), 400 A interrupted current.
V-Contact VSC contactorThe contactors cons ist o a monobloc o resin containing the
ollowing components:
vacuuminterrupters
movingequipment
magneticactuator
multivoltagefeeder
accessoriesandauxiliarycontacts.
The V-Contact contactors are provided in the ollowing
versions:
VSC7/Pforvoltagesupto7.2kV.
VSC7/PGforvoltagesupto7kVwith32kVpower
requenc withstand voltage.
VSC12/Pforvoltagesupto12kV.
VSC12/PGforvoltagesupto12kVwith42kVpower
requenc withstand voltage.
Both versions are available with an operating mechanism with
electrical or mechanical latching.
The V-Contact VSC contactors are mechanical l
interchangeable with the ormer V-Contact V/P contactor and
with the whole series o ABB circuit-breakers, the same
switchgear unit can thereore take both tpes o apparatus
without modiication.
A version o V-Contact VSC contactors is a lso used in the
UniGear MCC compact switchgear up to 400 A.
Operating mechanismDue to the magnetic actuator, V-Contact VSC contactors
need negligible auxiliar power in all conigurations (15W
inrush - 5W continuous).
The V-Contact VSC is available in three dierent
conigurations.
SCO (single command operation).
The contactor closes the suppl o auxiliar voltage to
the multivoltage eeder input, when the auxiliar is cut the
contactor opens.
DCO (double command operation).
The contactor closes the suppl o auxiliar voltage to the
multivoltage eeder closing input and opens when opening
input is supplied; anti pumping unction is supplied as a
standard.
DCO coniguration is also available, on request, with a
delaed undervoltage unction. This unction enables
automatic opening o the contactor when the auxiliar
voltage level drops below IEC deined levels.
Opening can be delaed rom 0 to 5 seconds (customer
setting b dip switches).
All conigurations are suitable or 1,000,000 mechanical
operations.
FusesThe contactor is itted with medium voltage uses or
protection o the operated eeders.
Coordination between the contactor, uses and protection unit
is guaranteed in accordance with the IEC 60470 Standards
or apparatus in class C.
The use-holder rame is usua ll preset or installation o a set
o three uses per phase with average dimensions and tpe o
striker, according to the ollowing Standards:
DIN43625.
BS2692.
Figure 13: V-Contact VSC contactor
1. UniGear ZS1Vacuum contactor
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
25/9225
Maximum load currents of the fuses
Feeder Transformers Motors Capacitors
Rated voltage Fuse Maximum load Fuse Maximum load Fuse Maximum load
3.6 kV 200A 160A 315A 250A 450A 360A
7.2 kV 200A 160A 315A 250A 355A 285A
12 kV 200A 160A 200A 160A 200A 160A
Figure 14: Fuse according to DIN Standards
Electrical characteristics
VSC7/P VSC12/P
Rated voltage kV 7.2 12
Rated insulation voltage kV 7.2 12
Rated power requenc withstand voltagekV 1min
20 (3) 28 (3)
Rated lightning impulse withstand voltage kV 60 75
Rated requenc Hz 50/60 50/60
Rated short-time withstand current kA (1) 50 50
Peak current kA 125 125
Internal arc withstand current (2) kA 1s 50 50
Maximum rated current o the contactor A 400 400
(1) Limited b the uses.
(2) The internal arc withstand values are guaranteed in the compartments on the suppl side o the uses (busbars and apparatus) b the structure o the switchgear and on the load side (eeder)
b the limiting properties o the uses.
(3) VSC7/PG or 32 kV power requenc withstand voltage and VSC12/PG or 42 kV power requenc withstand voltage are available on request in a dedicated panel.
Maximum performances of the contactor with fuses
3.6 kV 7.2 kV 12 kV
Motors kW 1,000 1,800 3,000
Transormers kVA 2,000 2,500 2,500
Capacitors kVAR 1,000 1,800 3,000
The ol lowing uses can be applied:
DINtypewithalengthof192,292and442mm
BStypewithalengthof235,305,410,454and553mm.
The use-holder rames are i tted with a device or automatic
opening when even just one use blows.
This same device does not allow contactor clos ing when even
a single use is missing.
The ABB range o uses or transormer protection is ca lled
CEF, whereas CMF is or motors and capacitors.
StandardsIEC60470forthecontactor
IEC60282-1forthefuses
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
26/9226
The UniGear panels can be fitted with ABB NAL type
switch-disconnectors.
These units are used to switch and protect feeders and
transformers or the auxiliary services transformers in sub
and power station.
The NAL switch-disconnectors are medium voltage
air-insulated apparatus consisting of a fixed support to
which the post insulators are applied (top and bottom),
the system of contacts (fixed and moving) and latching
pliers (of the fuses or of the insulating bars).
NAL-NALF switch-disconnectorThe switch-d isconnector is itted with two sstems o moving
blade contacts, the main one (through which the load current
passes with the switch in the closed position) and the arc-
breaking one (through which the current passes during the
opening and closing operations).
This solution means the main contacts are not stressed and
thereore keeps the electrical characteristics o the apparatus
unchanged.
During switch-disconnector opening air is compressed b
the pistons contained in the top insulator clinders. At the
moment o opening and separation o the contacts, a blast o
compressed air is emitted through special nozzles, so the arc
is cooled and deionised.
This leads to a gradual increase in the arc res istance which
causes its extinction. The movement o the p istons is
snchronised with the arc-breaking contacts o the switch-
disconnector -this guarantees the highest inlow o air at the
moment o separation o the contacts and there b ensures
reliable arc extinction.
The unit can be itted with insu lating bars (NAL switch-
disconnector unit) or with medium voltage uses (NALFswitch-
disconnector unit with uses).
The NALF switch-disconnector is i tted with an automatic
release mechanism or use tripping and uses uses in
accordance with DIN 43625 Standards. The ABB range ouses or transormer protection is CEF. Each unit is itted
with an earthing switch with making capacit or earthing the
cables.
Switch-disconnector control, like that o the earthing switch,
is carried out manuall rom the switchgear ront panel.
The position o both items o apparatus can be seen directl
rom the ront o the switchgear through an inspection
window.
The switchgear panel can be itted with a set o three current
transormers or with measurement sensors.
The Disconnector Feeder unit (DF) consists o two power
compartments: busbars and switch-disconnector/cables.The latter contains both the switch-disconnector and the
connection terminals o the power cables.
Figure 15: NALF switch-disconnector
1. UniGear ZS1Switch-disconnector
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
27/9227
Segregation between the power compartments takes place
automaticall with earthing switch closure. An insulating
shutter creates complete separation between the ixed
contacts o the switch-disconnector, making the top ones
inaccessible to the operators. This makes maintenance
operations on the cables and uses possible, keeping the
remainder o the switchgear in operation.
UniGear ZS1 panel with ixed switch-disconnector is classiied
LSC-2A because the cable and apparatus compartments are
not phisicall segregated.
The switch-disconnector, earthing switch and access door
to the cables compartment are interlocked with each other
to guarantee maximum saet or the personnel and correct
operation.
Each switchgear panel is itted with an auxiliar compartment,
where the instruments and auxiliar cabling are housed.
All the switchgear panels are access ible rom the ront and
maintenance and service operations can thereore be carried
out even when the switchgear is wall-mounted.
Standards
IEC60265-1fortheswitch-disconnector
IEC60282-1forthefuses
Electrical characteristics
Rated voltage kV 12 17.5 24
Rated insulation voltage kV 12 17.5 24
Rated power requenc withstand voltage (1) kV 1 min 28 38 50
Rated lightning impulse withstand voltage kV 75 95 125
Rated requenc Hz 50/60 50/60 50/60
(1) Limited b the uses.
(2) The internal arc withstand values are guaranteed in the compartment on the suppl si de o the uses (busbars) b the structure o the switchgear and on the load side (cabl es)
b the limiting properties o the uses.
NALF switch-disconnector unit with fuses
Rated short-time withstand current kA (1) ...25 ...25 ...20
Peak current kA ...100 ...100 ...63
Maximum rated current o the uses A 100 63 63
Internal arc withstand current (2) kA 1 s ...40 ...40 ...25
Selection table of the fuses for protection transformers
Transformerrated voltage
[kV]
Transormer rated output (kVA)Fuse rated
voltage[kV]25 50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000
CEF Fuse-link In [A]
3 16 25 25 40 40 50 63 80 100 125
3.6/7.25 10 16 25 25 25 40 40 50 63 80 100 125
6 6 16 16 25 25 25 40 40 50 63 80 100 125
10 6 10 16 16 16 20 20 25 31.5 40 50 63 80 100 12512
12 6 6 10 16 16 16 20 20 25 40 40 50 63 80 100 125
15 6 6 10 10 16 16 16 20 20 25 40 40 50 63 80 100 125 17.5
20 6 6 6 10 10 16 16 16 20 20 25 31.5 40 50 63 8024
24 6 6 6 6 10 10 16 16 16 20 20 25 40 40 50 63 80
The tab le was calculated acco rding to standards IEC 6 0787 and IEC 6 2271-105 (or opera ting voltages up t o 24 kV ). The ollowing t ransormer work condit ions were as sumed:
Maximumlong-lastingoverload150% Magnetizinginrushcurrent12Induring100ms
Transformershort-circuitvoltageaccordingtoIEC60076-5
Standardambientworkingconditionsoffuses
The tab le above de tail s the r ated current o a parti cular use l ink o r a gi ven l ine voltage and transor mer rating. For d ierent cri teria , the use selecti on mus t be recalculated .
The gi ven l imits o the rated curren t o use are not mandator or use in the NALF di sconnector / NAL wi thout use tr ipping ss tem. Rated current values o t he cor responding uses or these
applications are given in the ABB catalogue FUSES.
(1) GB/DL version is available with higher request in dielectric characteristics.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
28/9228
The UniGear ZS1 range is equipped with all the service
trucks needed for service maintenance activities.
The trucks are divided into four different types:
Earthing without making capacity
Earthing with making capacity
Cable test
Isolation
Earthing truck without making capacitThese trucks carr out the same unction as the earthing
switches without making capacit.
The there ore have no capacit to earth live circu its in ault
conditions.
The are used to ensure an addi tional ixed earth, as is
required b certain installation service and maintenance
procedures, as a urther saet guarantee or personnel.
The use o these trucks require the removal o the apparatus
(circuit-breaker or contactor) rom the switchgear and its
replacement with the truck.
The switchgear panels preset or use o the earthing trucks
must be provided with a ke lock which, when activated,
prevents their racking-in.
This truck is available in two versions:
Earthingofthemainbusbarsystem.
Earthingofthepowercables.
The earthing truck o the main busbars, during the racking-
in phase, onl lits the top shutter and earths the contacts
connected to the top branch connections (and thereore to the
main busbar sstem) b means o the switchgear structure.
The earthing truck o the power cables, dur ing the racking-
in phase, onl activates the bottom shutter and earths the
contacts connected to the bottom branch connections (and
thereore to the power cables) b means o the switchgear
structure.
These trucks can also be used in the bus-tie unit . In this case,
the earth one o the two sides o the main busbar sstem.
Earthing truck with making capacitThese trucks carr out the same unction as the earthing
switches with making capacit.
The cons ist o circu it-breakers provided with top (ear thing o
the main busbars) or bottom (earthing o the power cables)
terminals onl. The contacts without terminals are short-
circuited b means o a copper bar and connected to earth b
means o the apparatus truck.
The keep all the characterist ics o the circuit-breakers, such
as ull making and breaking capacit on live circuits under
ault conditions.
The are used to ensure extremel eective earthing on
circuits stressed b a ault. The allow opening and closing
operations to be carried out rapidl with electric remote
control.
The use o these trucks require the removal o the apparatus
(circuit-breaker or contactor) rom the switchgear and its
replacement with the truck.
The switchgear panels preset or use o the earth ing trucks
must be provided with a ke lock which, when activated,
prevents their being racked-in.
Figure 16: HD4 service truck
1. UniGear ZS1Service trucks
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
29/9229
This truck is available in two vers ions:
Earthing o the main busbar sstem.
Earthing o the power cables.
The earthing truck o the main busbars, during the racking-
in phase, onl lits the top shutter and presets the contacts
connected to the top branch connections (and thereore to
the main busbar sstem) or closing to earth b means o
operating mechanism.
The earthing truck o the power cables, dur ing the racking-
in phase, onl activates the bottom shutter and presets the
contacts connected to the bottom branch connections (andthereore to the power cables) or closing to earth b means
o operating mechanism.
These trucks can also be used in the bus-tie unit . In this case,
the earth one o the two sides o the main busbar sstem.
Power cable test truckThese trucks allow the insu lation tests on the power cables to
be carried out without accessing the eeder compartment or
disconnecting the cables rom the switchgear.
The use o these trucks require the removal o the apparatus
(circuit-breaker or contactor) rom the switchgear and its
replacement with the truck.
The truck, dur ing the racking- in phase, onl activates the
bottom shutter and, b means o the connectors it is itted
with, allows connection o the test apparatus cables.
This truck can onl be used in the incoming/outgoing eeders
with the door open.
Isolating truckThe isolating t ruck allows the top switchgear contacts to
be connected directl to the bottom ones. Connection
is made extremel sae b using the poles o the circuit-
breakers to insulate the connection busbars rom the
external environment. In the incoming/outgoing eeder units
it connects the main busbar sstem to the power cables,
whereas in the bus-tie, to the two sides o the busbar sstem.
This truck has its application in UniGear switchgear or
making incoming/outgoing eeders without a circuit-breaker
in radial networks, or making cable connections between
two items o switchgear placed in ront o each other, in
making interconnection units and in creating the bus-tie riser
coniguration with double insulation (in this case, both the
units are made up o bus-ties, the ormer itted with a circuit-
breaker and the latter with an isolating truck).
The switchgear panels preset or use o the isolating trucks
must be itted with a ke lock which, when activated, prevents
their being racked-in.
Main busbar sstem earthing
truck, without making capacit.
Power cable earthing truck,
without making capacit.
Cable test truck.
Main busbar sstem earthing
truck, with making capacit.
Power cable earthing truck,
with making capacit.
Isolating truck.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
30/9230
The UFES (Ultra Fast Earthing Switch) is an innovative
design of an extremely fast-acting earthing switch,
grounding all 3 phases within less than 4 ms after
detection of an internal arc fault.
The extremel short operating time o the primar switching
element, in conjunction with rapid and reliable detection o
ault current and light, ensures that an internal arc ault is
extinguished nearl immediatel ater its ormation. Thermal
and mechanical damage inside o the protected switchgear
sstem are thus eectivel prevented.
Figure 17: Electronic device for measurement,
logic and tripping, type QRU1
Figure 18: Primary switching element type U1
Electrical maximum characteristics in UniGear ZS1 IEC
Rated insulation voltage (rms) (1) kV 12 17.5 24
Rated power requenc withstand voltage (rms) kV 28 38 50
Rated lightning impulse withstand voltage (peak) kV 75 95 125
Rated requenc Hz 50/60 50/60 50/60
Rated short-time withstand current (rms) (1) kA 50 50 31.5
Rated short-circuit making current kA 125 125 80
Rated duration o short-circuit s 3 3 3
(1) GB/D L version i s avai lable wit h higher request i n die lectr ic characte risti cs (42 kV) and sho rt-time wi thstand curren t (4 s ).
The UFES is avai lable to ul il a variet o applications in the
UniGear ZS1 switchgear:
Busbar installation with top-housing box
Cable compartment installation (12/17.5 kV 50 kA version)
Unbeatable advantages in case o an arc ault event
Drastic reduction o repair costs: no damages on the
switchgear equipment to be expected. No exchange o the
ault panel.
Greatl increased sstem availabilit: ater inspection and
elimination o the ault reason the switchgear can be takeninto service again within shortest possible time.
Greatl increased operator saet or human mal-operation
under maintenance conditions.
1. UniGear ZS1Ultra Fast Earthing Switch
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
31/9231
0.0 20.0 40.0 60.0 80.0 100.0 120.0
I(t)
Time in ms
Short-circuit current In
DC component
Arcing time wi th UFES
Finalclearingoffaultcurrentbyupstreamcircuit-breaker-80ms+timex
Reaching time or tripping criteria
0 10 20 30 40 50 60 70 80 90 100
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0
Time in ms
Overpressure in bar
Pressure curve with UFES (4 ms) Pressure curve without UFES
Reaching time or tripping criteria
0.0 5.0 10.0 15.0 20.0 25.0
I(t)
Time in ms
0.0 5.0 10.0 15.0 20.0 25.0
I(t)
Time in ms
0.0 5.0 10.0 15.0 20.0 25.0
I(t)
Time in ms
0.0 5.0 10.0 15.0 20.0 25.0
I(t)
Time in ms
0.0 20.0 40.0 60.0 80.0 100.0 120.0
I(t)
Time in ms
UFES
CT
CB
1.
QRU
Ik
UFES
CT
CB
2.
QRU
Ik
UFES
CT
CB
3.
QRU
Ik
UFES
CT
CB
4.
QRU
Ik
UFES
CT
CB
5.
QRU
Ik
(Optional)
tTC
+ < 4 ms
tTCtTC
Figure 19: In rare cases, failure inside a switchgear cubicle due either to a
defect, an exceptional service condition or mainly by human mal-operation
may initiate an internal arc. The faster the arc will be interrupted, the less
destruction on the switchgear equipment will occur.
Figure 20: Avoidance of the severe effects of an internal arc fault, such as
- Rapid temperature rise (up to 20,000 C)
- Rapid pressure rise (see figure)
- Burning of materials
by fastest possible extinction.
Figure 21: Event sequence description
1. Internal arc formation.2. Arc detection by the electronic device (light and current).
3. ~ 1-2 ms after detection: Tripping signal to the UFES primary switching elements
4. ~ 3-4 ms after detection: Bolted 3-phase earthing by operation of the UFES primary switching elements.
Interruption of the arc voltage: Immediate extinction of the arc.
Controlled fault current flow via UFES primary switching elements to earth potential.
5. Final clearing of the fault current by the upstream circuit-breaker.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
32/9232
i
t
160 kA
80 kA
(31.5 kA x Hx2)
lnk perm.
= 31.5 kA
lnk
= 31.5 kA lnk
= 31.5 kAT1 T2
l = l1+l
2
l1
l2
l1
l2
Short-circuit currents too high?
The IS-limiter, a switching device with extremely short
operating time, solves the problem.
The rising g lobal demand or energ requires more power ul
or additional transormers and generators, and an increasing
interconnection o the individual suppl networks.
This can lead to the permissible short-circuit currents or the
equipment being exceeded causing severe dnamic or
thermal damage or even complete destruction.
The replacement o ex ist ing switchgear and cable connections
b new equipment with a higher short-circuit strength is otentechnicall impossible or uneconomical or the user.
The use o IS-limiters reduces the short-circuit current in both
new sstems and expansions o existing sstems, thus saving
cost.
A short-circuit downstream rom an outgoing eeder breaker is
assumed. The oscillogram shown below indicates the course
o the short-circuit currents in the irst hal wave.
A short-circuit current o 31.5 kA can low to the ault location
through each transormer. This would result in a total short-
circuit current o 63 kA, which is twice as much as the
switchgear capabilit.
The course o the current through the IS
limiter in such an
event is shown below as current i2.
It can be seen that the IS-limiter operates so rapidl, that
there is no contribution via the transormer T2 to the total
peak short-circuit current (i1+i2). Thereore, a switchgearwith a rating o 31.5 kA is suitable or this application.
i = i1+i
2
whithout Is-limiter
Current i = i1+i
2
at the ault location
i = i1+i
2
with Is-limiter
Single line diagram
o a bus tie or a
sstem with
lnk
= 31.5 kA
and with anlS
- limiter
Technical Data
Rated voltage kV 12.0 17.5 24.0 36.0/40.5
Rated current A1250/2000/2500/
3000/40001)1250/2000/2500/
3000/40001)1250/1600/2000/
25001)/3000 1)1250/2000/25001)
Interrupting current kARMS
Up to 210 Up to 210 Up to 140 Up to 140
1) with cooling an
1. UniGear ZS1IS-limiter: ault-current limitation
Figure 22: IS-limiter application diagram Figure 23: I
S-limiter
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
33/9233
110 kV
40 MVA8%
10 kV/31.5 kA 10 kV/40 kA
OptionA
OptionC
OptionB
10 kV/16 kA
10 kV/25 kA
I kT
= 15 kA
IkG
= 3 kA
T1
A B CIS-1
IT1
T2
IS-2
IT2
T3
IT3
OptionD
31.5 MVA
12%
Potential applicationsSuch a ast switching device caters or a variet o applications
which cannot be ullled b conventional switches. The most
important o these are presented below.
Advantages o all IS-limiter applications:
Reductionofshort-circuitcurrentsatthefaultlocation
Noupgradingoftheexistingswitchgear.
Option A, igure 24Coupling-parallel operation o two sstems.
Advantages:Improvingpowerquality
Increasingthereliabilityofthesystem
Reductionofthenetwork-impedance
Optimalloadflow
Option B, igure 24IS-limiter in the generator eeder to protect the high voltage sstem.
Advantages:
Generatorcanbeconnectedindependentoftheshort-
circuit capabilit o the sstem
Existingbusbarsystemdoesnotneedtobechanged
Noneed forexp ensiveg enerator breaker
Option C, igure 24IS-limiter and reactor connected in parallel.
Advantages:
Avoidcopperlossesofthereactor
Avoidvoltagedropoverthereactor
Noelectro-magneticfieldofthereactor
Option D, igure 25
Station service suppl and public network.Advantages:
Private/industrialgeneratorfeedercanbeconnectedtothe
(ull loaded) grid
SelectivetrippingoftheIS-limiter (I
S-limiter will operate onl
or short-circuit aults in the grid)
Option E, igure 26I in the case o two I
S-limiters being installed in a switch-
board selective tripping is required, a measurement o the
total current becomes necessar.
Advantage: The IS-limiter trips as ollows:
Short-circuit in section A: Onl IS-limiter no. 1 trips.
Short-circuit in section B: IS-limiter no. 1 and no. 2 trip.
Short-circuit in section C: Onl IS-limiter no. 2 trips.
Figure 24: Three possible applications of IS-limiters in one figure
(Option A, B, C)
Figure 26: Use of more than one Is-limiter with selectivity (Option E)
Figure 25: Is-limiter in connecting point with a public supply network
(Option D)
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
34/9234
Block tpe current transormersThe block tpe current transormers are epox resin insu lated
and used to suppl the measurement devices and protection
instruments. These transormers can have a wound core or a
bushing bar with one or more cores, with perormance and
accurac classes suitable or the installation requirements.
The conorm to the IEC 60044-1 Standards.
Thei r dimensions are in accordance with the DIN 42600
Narrow Tpe Standard, in the Medium and Long Size versions
up to 2500 A, where the are o the toroidal tpe in the
range o currents rom 3150 A to 4000 A (KOKS tpe).
The current transormers can also be provided with a
capacitive socket or connection to voltage signalling devices.
The current transormers are normal l itted on the load
side o the apparatus compartment or measurement o the
phase currents o the switchgear unit. Fitting on the suppl
side o the apparatus compartment is also possible (busbar
applications) or measuring the busbar currents or or realising
particular protection schemes. The ABB range o current
transormers is designated TPU.
Ring core current transormersThe toroidal transormers are o the epox res in insulated tpeand are used to suppl measurement and protection devices.
These transormers can eature either a closed or openable
core.
The can be used both or measuring phase currents or or
detecting the earth ault current.
The conorm with the IEC 60044-1 Standards.
Figure 28: TPU 1250 A
Figure 29: TPU 2500 A
Figure 27: Toroidal current transformer Figure 30: KOKS 3150 A
1. UniGear ZS1Instrument transormers
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
35/9235
Voltage transormersThe voltage transormers are o the epox resin insu lated tpe
and are used to suppl measurement and protection devices.
The are available or ixed assembl or or installa tion on
removable and withdrawable trucks.
The conorm with the IEC 60044-2 Standards.
Thei r dimensions are in accordance wi th the DIN 42600
Narrow tpe Standard.
These transormers can have one or two poles, with
perormance and precision classes suited to the unctional
requirements o the instruments connected to them.
When the are installed on removable or withdrawable trucks
the are itted with medium voltage protection uses.
The withdrawable t rucks also allow replacement o the uses
with the switchgear in service. Truck racking-out with the
door closed automaticall operates closure o a metallic
segregation shutter between the live parts o the switchgear
and the instrument compartment.
Fixed voltage transormers can be installed directl on the
main busbar sstem in a dedicated compartment (busbar
applications).
The ABB range o voltage transormers is designated TJC,
TDC,TJP.
Figure 31: VT truck with fuses
Figure 32: Single pole VTs - type TJC
Figure 33: Double-pole VTs - type TDC
Figure 34: Single-pole VTs with fuse - type TJP
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
36/9236
1. UniGear ZS1Measurement sensors
Figure 35: Linearity of advanced ABB sensors and example of output signal waveforms compared to conventional saturated CT
Electronic instrument transormersFuture or measuring currents and voltages in intelligent
UniGear is a low-power instrument transormer (according to
present IEC standards the belong to the group o Electronic
instrument transormers) called a sensor or short. These
products replace conventional instrument transormers o
both block and ring core tpes.
The characterist ic eature o advanced ABB sensors is
the level o output signal, which is ull adapted to it new
microprocessor-based equipment without the need o having
unnecessar power.
The analogue output s igna l level depends on the principle
used and can be:
IntherangeofmVforcurrentsensor(typicalvalueis150
mV at rated primar current).
Intherangeofvoltsforvoltagesensorswherethedivision
ratio is 1:10000 (e.g. output 1/3 V or 10 000/3 kV
nominal sstem voltage at primar/input side).
The UniGear ZS1 can be itted with KEVCD block tpe sensor
KEVCDisblocktypesensorwithshapethatconforms
to DIN size standard. Two versions could be selected:
one providing current measurement together with voltage
indication capabilit or second one, providing, in addition
to these, also voltage measurement possibilit. All
measurements/sensings or each phase is realized within a
single bod, so there is no need or additional devices.
Characteristics o the sensorsConstruction o current and voltage sensors is done without
the use o erromagnetic core. This act results in several
important beneits or the user and the application:
sensorbehaviorisnotinfluencedbynon-linearityand
width o hsteresis curve; that results in accurate and
linear response over a wide dnamic range o measured
quantitites
singledevice/sensorcouldbeusedforbothprotectionand
or measurement purposes (no need or a separate design/
product)
therearenohysteresislosses,sosensorsarehaving
excellent requenc response also at requencies dierent
rom the rated one, thus providing ver precise input to
protection unctions, allowing more precise ault analsis
and eicient ault location.
sensorsdonothavedangerousstatesinoperation(no
problem to keep output short-circuited or let open),
resulting in high saet or surrounding devices and
personell. The output signal remains ver low even in ault
situations o the network.
theuseofsensorsdisablethepossibilityofrelated
erroresonance phenomena, thus even more increasing the
saet and reliabilit o the power network; urthermore,
there is no need or additional protection equipment, special
burden or wiring.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
37/9237
Figure 36: KEVCD block type current and voltage sensor
ABB sensors are connected to the measurement and
protection evaluation devices b means o shielded cables
and connectors, providing a high degree o immunit to
electromagnetic disturbances.
Accurac o these sensors is veri ied and tested including the
cabling, so precise inormation is assured up to the evaluation
device.
Beneits o the sensorsDue to the linear response and wide dnamic range, sensors
are much more standardized devices (compared to a number
o dierent designs o CTs and VTs). Thereore, it is mucheasier to select the appropriate design (it simpli engineering
tasks) and there could be also reduction in spare parts on
user side.
Signiicantl decreased power consumption during operation
o sensors due to negligible losses introduced b sensors
(no iron = no hsteresis losses; less winding and negligible
output current = small losses in sensor winding) results in
huge savings or lost energ and minimized temperature rise
(thus improving temperature conditions and ageing within
application). It also results in signiicantl lighter devices,
having weight onl a raction o that provided b conventional
CTs or VTs. Thereore, no special machines/tools are neededto car them and transport costs can be smaller.
Fast connection o sensors to IEDs without an tools and
material needed simpli and reduce assembl eort.
7/29/2019 Catalogue UG ZS1 RevF 2012 09 En
38/9238
1. UniGear ZS1Measurement sensors
Current sensorThe current sensor is based on Rogowski Coil principle.
Rogowski Coil work in the same manner as conventional iron-
core current transormers (CTs). The main dierence between
Rogowski Coils and CTs is that Rogowski Coil windings are
wound over a non-magnetic core, instead o over an iron
core. As a result, Rogowski Coils are linear since the non-
magnetic core cannot saturate. Rogowski Coils produce
output voltage (U